Trane UCM 4.0 and WirelessVAV Communication, UCM 4.0 Installation/ Operator Programming

Installation/ Operator Programming
UCM 4.0 and Wireless VAV Communication
May 2001
VAV-SVX01B-EN
Contents
Chapter 1 – General Information 4
UCM Control Module 4.0 (UMC 4.0) Specifications UCM 4.0 Enhancements UCM 4.0 Features Shipping Storage
Chapter 2 – VAV Start-Up/Check-Out Procedure 6
Pre-power Up Checkout for the UCM 4.0 UCM Operational LEDs Zone Sensor Checkout
Chapter 3 – UCM 4.0 Installation and Wiring 7
UCM 4.0 Power Wiring Zone Sensor Wiring Communication Wiring DIP Switch Settings
Chapter 4 – UCM 4.0 Programming and Operation 14
Typical UCM Operating Behavior UCM Status UCM Set Points UCM Setup
Chapter 5 – Sequence of Operations 24
Single Duct Units Parallel Fan-Powered Units Series Fan-Powered Units Zone Sensor Ffunctions Flow Sensor Failure Modes
©American Standard Inc. 1999 VAV-SVX01B-EN
Contents
Chapter 6 – Air and Water Balancing 28
Air Balancing Water Balancing
Chapter 7 – Wireless VAV Systems 30 Chapter 8 – Trouble-Shooting 38
UCM 4.0 Problems Wireless Receiver Problems
Chapter 9 – Appendix 42
VAV-SVX01B-EN 3
General Information
Chapter Overview
This chapter contains information about the following
Unit Control Module 4.0 (UCM 4.0)SpecificationsUCM 4.0 EnhancementsUCM 4.0 FeaturesShippingStorage
CHAPTER 1: GENERAL INFORMATION Unit Control Module 4.0
(UCM 4.0)
The UCM 4.0 is a microprocessor­based, Direct Digital Controller (DDC) for the (Variable Air Volume) VAV terminal unit. It contains the control logic to modulate the flow of supply air through the VAV terminal in response to the load requirements within the VAV zone.
The function of the UCM is to control the VAV terminal unit to vary the volumetric airflow rate to the zone. VAV units are available with either pneumatic, analog electronic, or microprocessor controls (DDC VAV). This manual discusses only terminal units with DDC/VAV controls. Factory installed DDC/VAV controls are available with all single duct terminal units, including parallel fan-powered, and series fan-powered units. Two UCMs are required for dual duct units (one for the heating duct and one for the cooling duct).
The UCM modulates a VAV’s damper blade based on a zone temperature, measured airflow, and set points to continuously control conditioned air delivery to the space. The volume of incoming air is monitored and the damper adjusts to provide accurate control independent of the duct pressure. The damper modulates between operator set points depending on space conditions. Additionally, fan and heat outputs may be energized depending on the application. Available inputs include a twisted/shielded communication link, zone sensor, auxiliary temperature sensor (optional), CO2 Sensor (optional), and Occupy/ Unoccupy Sensor (optional), and 24 VAC power.
Specifications
Power Requirements
The UCM 4.0 requires 24 VAC, 50/60 Hz, and up to 50 VA, depending on the number of heat outputs (stages), which consume 10 VA each.
Operating Environments – UCM 4.0
0°– 140°F (0°– 60°C), 10% to 90% relative humidity, non-condensing
Storage Environments – UCM 4.0
-40°– 150°F (-40°–65.6°C), 10% to 90% relative humidity, non-condensing
Mounting
Typically, the UCM 4.0 is factory installed. However, UCM 4.0 is available with retrofit kits, in which case it must be field installed.
See Chapter 8 for wireless system mounting.
Tracer Summit and UCM 4.0 Communications Link Wiring
Communications Link wiring must be 18 AWG twisted shielded pair wire. Each conductor must be stranded tinned copper. The maximum total wire length is 5,000 feet (1,524 m). Refer to Chapters 2 and 3 for further information about wire selection.
UCM 4.0 Enhancements
The enhanced VAV UCM is backward
compatible with VariTrane boxes (VXXD and VXXE) VariTrac dampers, and VariTrac II dampers.
UCM 4.0 adds support for operation
with VariTrane Series F valves (¼-turn blade dampers) via 90-second drive time.
UCM 4.0 adds a second, CO
interfacing, mode of operation to the auxiliary analog input (TB3-5). This is a 1 to 10 volt DC input with a mapping of input voltage to CO of 200 parts per million (PPM) of CO per volt. The use of this new auxiliary analog input as an interface to a CO detector is mutually exclusive with the use of the input as auxiliary temperature input. Therefore, the use of the C0 not recommended for stand-alone applications requiring auto-changeover.
UCM 4.0 adds a binary 24 VAC, dry
contact input. It can be configured either as a generic input or as an occupancy detector input.
UCM 4.0 adds a VariTrac Bypass
Damper mode of operation. In this
®
D VAV
®
2
output data value
2
2
2
interfacing mode of operation is
2
4
VAV-SVX01B-EN
General Information
mode, supply air temperature and supply air pressure is made available on the Com 4 link. The damper position is a COM 4-control parameter. A Com 4 configurable failsafe position was added. The supply air temperature uses a new “s” input (TB3-7). The use of this new input is mutually exclusive with the Zone temp input (TB3-1).
UCM 4.0 now assumes the hot water
valve is closed after reset. This prevents a reset during hot water override from causing the valve to stop moving. This also changes the behavior after reset, when there is a reheat demand, the hot water valve now opens (from assumed closed position) to the desired reheat position.
In a wireless system, the hard-wired
sensor can now be configured as not present. The hard-wired sensor failures will not be reported as long as at least one wireless zone sensor is reporting valid temperature values.
For standalone units, series or parallel
fan operation will use the unoccupied fan control when the local unoccupied request (** function) is received. In UCM 3.3 and prior, the fan would operate as if occupied during local unoccupied request
UCM 4.0 adds a local minimum heating
flow set point. The use of and value of this set point is configurable.
UCM 4.0 Backward Compatibility
UCM 4.0 can be used to replace UCM I, UCM II, and UCM III with no compatibil­ity issues. However, if the communicat­ing device (i.e. Command Unit I or Comfort Manager™ I) is a COM 3 device (1992 or earlier), then you will need an upgrade chip. The Comfort Manager chip upgrade is Kit 1511 and the Command Unit chip upgrade is Kit
1512.
UCM 4.0 Features
Heat and Fan Outputs
All fan outputs are rated for 10 VA each. Magnetic contactors are rated for 10 VA. Mercury contactors are rated for 12 VA.
Wiring Diagram
Figure 1 shows a typical wiring diagram for the redesigned UCM hardware. The new service part number is BRD 2087.
VAV-SVX01B-EN 5
Figure 1. UCM 4.0 Board Layout
Zone Sensor, Auxiliary Sensor, and Thumbwheel Set Point Calibration
If there is a discrepancy between a measured temperature and what the UCM reports, a calibration offset value can be edited in the UCM setup screen to correct the displayed value.
Flow Sensor Calibration
If there is a discrepancy between a measured flow and what the UCM reports, the measured value can be entered, which automatically calculates a calibration multiplier to correct the displayed value.
Water Valve Override
Each UCM that has proportional or staged hot water heat outputs can be edited to override the water valve to its maximum position.
Ventilation Set Points and Ratio Calculation
Set point values needed for a space to satisfy indoor air quality requirements are provided. A resultant ventilation ratio can be used to calculate an air handler’s outside air damper minimum position or other control strategies.
Water Heat Output Configuration
UCMs that have hot water heat outputs can be configured for normally open or normally closed.
Zone Sensor Functions
Zone sensor functions now include: air valve drive to maximum, use unoccu­pied set points, timed override, and cancel timed override.
Slaving of Zone Sensors
Up to three (3) UCM 4.0s may be connected to a single zone sensor.
Generic UCM Capability
UCM 4.0 can be configured to control non-Trane VAV boxes.
Shipping
Each VAV product and its service literature are shipped in the same package. When unpacking, make sure that the literature is not lost or dis­carded with the packing material. Visually inspect the individual compo­nents for obvious defects or damage. All components are thoroughly inspected before leaving the factory. Any claims for damage incurred during shipment must be filed with the carrier.
Storage
When any component of the VAV system and/or field installed accesso­ries must be stored for a period of time prior to being installed, they must be protected from the elements. The storage location temperature should be between -40° – 150°F (-40°– 65.6°C) and the relative humidity should be 10% to 90%, non-condensing.
The warranty will not cover damage to the VAV system or controls due to negligence during storage. A controlled indoor environment must be used for storage.
VAV Start-Up/ Check-Out Procedure
Chapter Overview
This chapter contains information pertaining to the following:
Pre-power up check-out for the UCM
4.0
UCM operational LEDsZone Sensor check-out
UCM 4.0 Pre-Power Check-out
[ ]Check the supply voltage at TB1. Proper
polarity must be maintained. TB1-1 is the hot side (+) and TB1-2 is the ground side (-) of the 24 VAC input. The UCM cannot be powered from a common 24 VAC transformer that is supplying power to a device containing a full­wave rectifier bridge in its power supply. The acceptable voltage is 20 to 28 VAC (24 VAC cataloged). However, voltages at either extreme may result in increased system instability.
[ ]Verify that communications wiring has
properly been terminated atTB2-1 (+) and TB2-2 (-). Polarity is very important on the communications link.
[ ]Verify that the zone sensor connections
are correct as detailed in the UCM wiring chapter.
[ ]Verify that the proper unit DIP switch
settings have been set on each UCM.
[ ]Verify that the tubing is properly
connected to the transducer.
CHAPTER 2: VAV START-UP/CHECK-OUT PROCEDURE Light Emitting Diode (LED)
Operations
The UCM has one green LED located near TB3 and one yellow LED located near TB2 on the UCM circuit board. These LED’s are used to help diagnose commu­nication (yellow) or circuit board prob­lems (green).
The green LED (red on older boards) is a power indicator. It is steady on when the power is on and the software is functioning correctly. If it blinks with a 1 second on 1 second off cycle when power is applied, then the board is not functioning and must be replaced.
Table 1 - Green LED Power Function Indication
LED State Indication
“On” Board functioning correctly Blinking Board malfunction (Replace Board) “Off” Board does not have power
The yellow LED functions as the communication indicator. The indication from the yellow LED is as follows:
Table 2 – Yellow LED Communication Indicator Function
LED State Indication
“On” Incorrect (reversed)
Blinking slowly Communication is occurring on the approx. 1 link but not for that particular UCM. blink/sec.
Blinking quickly Communication is occurring on the (multiple blinks link, specifically with that UCM. blinks/sec.
“Off” Polarity is correct and no
communication polarity, no connection, or shorted lines.
communication is occurring on the link
Zone Sensor Check-out
If an erroneous temperature is being reported to the UCM, use the Zone Sensor Temperature-Resistance Table to verify the integrity of the adjustable set point potentiometer or sensor. The resistance should be measured across the terminals to which the device is connected.
Note: Disconnect the zone sensor from the UCM when making the checks listed in the table below.
Table 3 – Zone Sensor Temperature-Resistance Table
Temp. Resistance Resistance
(°F) (Ohms) (k Ohms)
55 792 17.0 56 772 16.5 57 753 16.1 58 733 15.7 59 714 15.4
60 694 15.0 61 675 14.6 62 656 14.3 63 636 14.0 64 617 13.6
65 597 13.3 66 578 13.0 67 558 12.6 68 539 12.3 69 519 12.1
70 500 11.8 71 481 11.5 72 461 11.2 73 442 11.0 74 422 10.7
75 403 10.4 76 383 10.2 77 364 10.0 78 344 9.7 79 325 9.5
80 306 9.3 81 286 9.0 82 267 8.8 83 247 8.6 84 228 8.4 85 208 8.2
Thermostat
Thumbwheel Sensor
6
Note: Thumbwheel resistance checks are made at terminal 2 and 3 on the zone sensor. Temperature sensor resistance is measured at terminal 1 and 2 of the zone sensor.
VAV-SVX01B-EN
UCM 4.0 Installation and Wiring
CHAPTER 3: UCM 4.0 INSTALLATION AND WIRING
Figures 2 – 5 show wiring diagrams for typical applications of UCM 4.0
Figure 2. Wiring Diagram for Single Duct Units with Field Installed Re-heat
VAV-SVX01B-EN 7
UCM 4.0 Installation and Wiring
Figure 3. Wiring Diagram for Single Duct Units with Factory Installed Electric Re-heat
8
VAV-SVX01B-EN
UCM 4.0 Installation and Wiring
Figure 4. Wiring Diagram for Fan-Powered Units with Field Installed Re-heat
VAV-SVX01B-EN 9
UCM 4.0 Installation and Wiring
Figure 5. Wiring Diagram for Fan-Powered Units with Factory Installed Electric Re-heat
10
VAV-SVX01B-EN
UCM 4.0 Installation and Wiring
Chapter Overview
This chapter contains information about the following:
UCM 4.0 Power WiringZone Sensor WiringCommunication WiringDIP switch Settingsire Selection
UCM 4.0 Power Wiring
Power Requirements Caution: Disconnect all power external to the unit to prevent injury or death from electrical shock. Use copper conductors only. The use of aluminum or other types of wire may result in overheating and equipment damage.
Use at least 16 AWG for power wiring and connect to terminal TB1-1 (+) and TB1-2 (-). 24 VAC is required to power the UCM control and has an acceptable voltage tolerance of 20 to 28 VAC. Replace the UCM control box cover after field wiring to prevent any electromagnetic interference.
NOTE: A dedicated 24 VAC, 50VA NEC class 2 transformer is recommended to power the UCM. When powering multiple UCM’s from one transformer, polarity must be maintained. Terminal TB1-1 is designated positive (+) and terminal TB1-2 is negative (-) to the unit casing ground. All wiring must comply with the National Electric Code (NEC) and local codes. Maximum wire lengths should be based on NEC specifications.
The power consumption for cooling only Series F Models (VariTrac and VariTrane) is 12 VA (4 VA for the air valve/actuator and 8 VA for the board). Units with fans and/or reheat outputs are rated at 10 VA maximum for magnetic contactors and 12 VA maximum for mercury contactors for each output. To determine the total UCM power requirement, add the power consumption per stage to the circuit board power requirement. For example, a Series F unit containing magnetic contactors with three stages of reheat would consume 42 VA.
NOTE: VariTrane and VariTrac cooling only Series D and E models consume 20 VA (12 VA for the actuator and 8 VA for the board). The heating output ratings remain the same.
Refer to Figure 1 for UCM terminal locations.
Zone Sensor Wiring
Location and Mounting
A zone sensor in each control zone should be located in the most critical area of the zone. Sensors should not be mounted in direct sunlight or in the area’s supply air stream. Subdivision of the zone may be necessary for ad­equate control and comfort.
Avoid mounting zone sensors in areas subject to the following:
Drafts or “dead spots” behind doors or
corners.
Hot or cold air ducts.Radiant heat from the sun or
appliances.
Concealed pipes or chimneys.Unheated or uncooled surfaces behind
the sensor such as outside walls.
Air flows from adjacent zones or other
units.
Wiring
Each unit must be controlled by a zone sensor that is designated specifically for use with the UCM control. Field wiring for the zone sensors must meet the following requirements:
Must be 14 to 18 AWG.Refer to the sensor instructions for
terminal connections.
If local codes require enclosed
conductors, the zone sensor wires should be installed in conduit. Do not route zone sensor wires in conduit with 24 VAC or other high power conducting wires.
Multiple UCM’s Per Zone Sensor
Up to three (3) UCM’s may be con­nected to a single zone sensor and thumbwheel set point.
Connect terminal connections TB3-1,
TB3-2, and TB3-3 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s). NOTE: Proper polarity must be maintained.
Cut jumper wires W1 and W2 on the
slaved UCM’s (never cut jumper wires W1 and W2 on the master UCM).
VAV-SVX01B-EN 11
UCM 4.0 Installation and Wiring
Multiple UCM’s per Auxiliary Duct Temperature Sensor
Up to three (3) UCMs may be con­nected to a single auxiliary duct temperature sensor.
Connect terminal connections TB3-5
and TB3-6 in parallel (i.e. daisy chain) from the master UCM to the slaved UCM(s). NOTE: Proper polarity must be maintained.
Cut jumper wire W4 on the slaved
UCMs (never cut jumper wire W4 on the master UCM).
Zone Sensor Options
Depending on the zone sensor options used, a maximum of five wires may be required to run from the UCM to the zone sensor. The zone sensor options are:
Zone sensor only (2 wires) – Part
Number X13510609-01.
Zone sensor with external adjustable
set point and communications jack (5 wires) – Part Number X13510606-01.
Zone sensor with external adjustable
night set back, timed override (TOV) on/ cancel button, and communications jack (5 wires) – Part Number X13510606-02.
Sensor with night set back, timed
override (TOV) on/cancel button, and communications jack (4 wires) – Part Number X13510606-03.
Digital zone sensor - Part Number
X13511067-01
NOTE: All wiring from the zone sensor to the Com link must be twisted shielded pair wiring.
Communication Wiring
Communication Link Wiring
The “Communication Link” is the communication wiring between Tracer Summit and all VAV box Unit Control Modules (UCM). Tracer Summit be connected to the UCM communica­tion link in a “daisy chain” configura­tion.
®
can
Note: It is not necessary for each UCM to be connected to the line in sequential order by address. Also, multiple communication links may be run and terminated at the Tracer Summit. However, a consistent, documented wiring path will help troubleshoot communication problems after installation.
Field wiring for the communication link must meet the following requirements:
1. All wiring must be in accordance with the National Electrical code and local codes.
2.Communication link wiring must be at least 18 AWG twisted shielded pair wire. Shields must be grounded at the Tracer Summit or Central Control Panel (CCP) only. More than one ground reference will cause communications failures. Shields must be daisy chained. Tape the shield at the last VAV UCM to prevent any connection between the shield and ground. Wire specifications are as follows:
Plenum Cable
Stranded, tinned copper insulated with extruded FEP. Conductors cabled and shielded with overall aluminum/ Mylar tape and stranded, tinned copper drawn wire. Extruded jacket, 300 volt, 150°C NEC 725-2 (b) class 2, type CL2P, 25 pF/ft.
Non-Plenum Cable
Stranded tinned copper insulated with polyethylene. Conductors cabled and shielded with overall aluminum/ polyester tape and stranded, tinned copper drain wire. Chrome gray PVC jacket, 300 volt, 60°C NEC type CM, 24 pF/ft.
Wire Capacitance
Wire capacitance must comply with the following table:
Max. Communication Max.
Link Wiring Length Wire Capacitance
1,000 feet (304.8m) Up to 60 pF/ft. (196.9 pF/m) 2,000 feet (609.6 m) Up to 50 pF/ft. (164.0 pF/m) 3,000 feet (914.4m) Up to 40 pF/ft. (131.2 pF/m)
4,000 feet (1,219.2 m) Up to 30 pF/ft. (98.4 pF/m)
5,000 feet (1,524 m) Up to 25 pF/ft. (82.0 pF/m)
3.The maximum wire length should not exceed 5,000 feet (1,524 m).
4.Communication link wiring cannot pass between buildings.
5.A maximum of 63 UCMs can be connected to each COM Link. Daisy chaining is a typical configuration. “STAR” chaining is also acceptable.
Note: Polarity is extremely important and must be observed on communica­tion link connections.
6.At the VAV box, communication link wires must be connected to TB2-1, 3 (+) and TB2-2, 4 (-) terminals on the UCM.
7. Verify that the UCM address is properly set (DIP switch SW1). See Table 4 for proper DIP switch settings.
12
VAV-SVX01B-EN
UCM 4.0 Installation and Wiring
DIP Switch Settings
DIP Switch SW1 contains six switches for addressing the UCM. These switches allow a user to set a unique communication address for each UCM. Each UCM on a given communication link must have a unique address in order for Tracer Summit or the CCP to communicate to it. Refer to Table 3 for UCM 4.0 DIP switch settings.
Note: When using Eware to communi­cate to the UCM, you must add 64 to the DIP switch address. For example, a UCM with the DIP switch address set to 1 would be UCM Number 65 in Eware.
Table 4 – DIP Switch Settings for UCM 4.0
UCM Eware
Unit # Address Dip 1 Dip 2 Dip 3 Dip 4 Dip 5 Dip 6
1 65 OFF ON ON ON ON ON 2 66 ON OFF ON ON ON ON 3 67 OFF OFF ON ON ON ON 4 68 ON ON OFF ON ON ON 5 69 OFF ON OFF ON ON ON 6 70 ON OFF OFF ON ON ON 7 71 OFF OFF OFF ON ON ON
872 ONONONOFFONON
9 73 OFF ON ON OFF ON ON 10 74 ON OFF ON OFF ON ON 11 75 OFF OFF ON OFF ON ON 12 76 ON ON OFF OFF ON ON 13 77 OFF ON OFF OFF ON ON 14 78 ON OFF OFF OFF ON ON
15 79 OFF OFF OFF OFF ON ON 16 80 ON ON ON ON OFF ON 17 81 OFF ON ON ON OFF ON 18 82 ON OFF ON ON OFF ON 19 8 3 OFF OFF ON ON OFF ON 20 84 ON ON OFF ON OFF ON 21 85 OFF ON OFF ON OFF ON
22 86 ON OFF OFF ON OFF ON 23 87 OFF OFF OFF ON OFF ON 24 88 ON ON ON OFF OFF ON 25 89 OFF ON ON OFF OFF ON 26 90 ON OFF ON OFF OFF ON 27 91 OFF OFF ON OFF OFF ON 28 92 ON ON OFF OFF OFF ON
29 93 OFF ON OFF OFF OFF ON 30 94 ON OFF OFF OFF OFF ON 31 95 OFF OFF OFF OFF OFF ON 32 96 ON ON ON ON ON OFF 33 97 OFF ON ON ON ON OFF 34 98 ON OFF ON ON ON OFF 35 99 OFF OFF ON ON ON OFF
36 100 ON ON OFF ON ON OFF 37 101 OFF ON OFF ON ON OFF 38 102 ON OFF OFF ON ON OFF 39 103 OFF OFF OFF ON ON OFF 40 104 ON ON ON OFF ON OFF 41 105 OFF ON ON OFF ON OFF 42 106 ON OFF ON OFF ON OFF
43 107 OFF OFF ON OFF ON OFF 44 108 ON ON OFF OFF ON OFF 45 109 OFF ON OFF OFF ON OFF 46 110 ON OFF OFF OFF ON OFF 47 111 OFF OFF OFF OFF ON OFF 48112 ONONONONOFFOFF 49 113 OFF ON ON ON OFF OFF
50 114 ON OFF ON ON OFF OFF 51 115 OFF OFF ON ON OFF OFF 52 116 ON ON OFF ON OFF OFF 53 117 OFF ON OFF ON OFF OFF 54 118 ON OFF OFF ON OFF OFF 55 119 OFF OFF OFF ON OFF OFF 56 120 ON ON ON OFF OFF OFF
57 121 OFF ON ON OFF OFF OFF 58 122 ON OFF ON OFF OFF OFF 59 123 OFF OFF ON OFF OFF OFF 60 124 ON ON OFF OFF OFF OFF 61 125 OFF ON OFF OFF OFF OFF 62 126 ON OFF OFF OFF OFF OFF 63 127 OFF OFF OFF OFF OFF OFF
VAV-SVX01B-EN 13
Loading...
+ 30 hidden pages