Trane UCCA Catalogue

Catalog
Performance Climate Changer Air Handler Model UCCA
Sizes 3-30
December 20 13
CLCH-PRC024A-EN
Trane Performance Climate Changer™ Air Handlers
Mixing box with angled filter rack
Coil
Direct-drive fan
2-inch double-wall foam injected casing
VFD
Low voltage control enclosure
2-inch R13 foam insulated panels and doors
Less than 0.005 inches at +/-4 inches w.g. panel and door deflection
All airfoil bladed dampers meet ASHRAE 90.1 lowest specified leakage
Quick-connect wiring minimizes installation costs and provides wiring integrity between sections
Factory engineered and mounted control packages
Hinged and handled access doors
UL/CUL listed
AHRI Standard 430-certified air-handling unit
AHRI Standard 410-certified coils
2-inch/4-inch combination filter, or 2-inch/4-inch combination filter in a mixing box
Fan options including forward curved (FC) and direct-drive plenum (DDP) fans
Electric heat including full modulating control
Units ship on skid for forklift transportation at job site
Building Information Modeling (BIM) drawing to minimiz e jobsite ductwork, electrical, p iping, and structural interference
2 CLCH-PRC024A-EN
Table of Contents
Trane Performance Climate Changer™ Air Handlers . . . . . . . . . . . . . . . . . . . . . 2
Model Number Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Construction and Integrity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Engineered for Good IAQ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Control Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Proven Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Standard AHU Arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Operating Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
DX Cooling Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Sloped Drain Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Serviceability/Cleanability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Filtration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Dehumidification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Single Source Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
AHRI Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
UL Listing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
ISO Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Horizontal Draw-Thru . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Vertical Draw-Thru . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Components and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mixing Box/Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electric Heat Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Unit Configurations and Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Coil Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Coil Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Fan Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Fan Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Direct-Drive Plenum Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
FC Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Filter Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
CLCH-PRC024A-EN 3
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Controls Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Fuse Sizes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Motor Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Equations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Dimensions and Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Service Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Horizontal Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Vertical Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
VFD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Hydronic Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Steam Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
DX Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Mixing Box/Filter Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Filter Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
UL and C-UL Listed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Unit Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Casing Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Unit Flooring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Access Doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
FC Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Direct-Drive Plenum Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Fan Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Fan Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Hydronic Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
4 CLCH-PRC024A-EN
Refrigerant Cooling Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Steam Heating Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Electric Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Control Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Mixing Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Control Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
CLCH-PRC024A-EN 5
Model Number Descriptions
Digit 1, 2, 3, 4— Unit Model
UCCA = Performance Climate Changer
Air Handler
Digit 5 - Configuration
A = Horizontal/front top with housed fan B = Horizontal/top front with housed fan C = Vertical/front top with housed fan D = Vertical/top front with housed fan E = Vertical/back top with housed fan F = Vert ical/top back with housed fan G = Horizontal/front top with DDP fan H = Horizontal/top front with DDP fan S = Special
Digit 6, 7 - Unit size
3 = Unit size 3 6 = Unit size 6 8 = Unit size 8 10 = Unit size 10 12 = Unit size 12 14 = Unit size 14 17 = Unit size 17 21 = Unit size 21 25 = Unit size 25 30 = Unit size 30
Digit 8 - Unit voltage
0 = No motor, controls, or electric heat A = 208 volt/60 hertz/3 phase odp B = 230 volt/60 hertz/3 phase odp C = 460 volt/60 hertz/3 phase odp D = 575 volt/60 hertz/3 phase odp S = Special
Digit 9 - Open
0 = Open for future use
Digit 10, 11 - Design sequence
A0 = A0
Digit 12 - Connections
R = Polymer drain pan, RH coil/RH motor L = Polymer drain pan, LH coil/LH motor C = Polymer drain pan, RH coil/LH motor D = Polymer drain pan, LH coil/RH motor E = Stainless steel drain pan, RH coil/
RH motor
F = Stainless steel drain pan, LH coil/
LH motor
G = Stainless steel drain pan, RH coil/
LH motor
H = Stainless steel drain pan, LH coil/
RH motor
S = Special
Digit 13 - Coil #1 first in airstream
0 = No unit coil #1 A = 1 row preheat hydronic/9 fins per in. B = 1 row preheat hydronic/12 fins per in. C = 1 row preheat hydronic/14 fins per in. D = 2 row preheat hydronic/9 fins per in. E = 2 row preheat hydronic/12 fins per in. F = 2 row preheat hydronic/14 fins per in. G = 1 row preheat steam/6 fins per in. H = 4 row hydronic/9 fins per in. J = 4 row hydronic/12 fins per in. K = 4 row hydronic/14 fins per in. L = 6 row hydronic/9 fins per in. M = 6 row hydronic/12 fins per in. N = 6 row hydronic/14 fins per in. P = 8 row hydronic/9 fins per in. R = 8 row hydronic/12 fins per in. T = 8 row hydronic/14 fins per in. U = 4 row DX/9 fins per in. V = 4 row DX/12 fins per in. W = 4 row DX/14 fins per in. Y = 6 row DX/9 fins per in. Z = 6 row DX/12 fins per in. 1 = 6 row DX/14 fins per in. S = Special
Digit 14 - Coil #2 second in airstream
0 = No unit coil #2 A = 1 row reheat hydronic/9 fins per in. B = 1 row reheat hydronic/12 fins per in. C = 1 row reheat hydronic/14 fins per in. D = 2 row reheat hydronic/9 fins per in. E = 2 row reheat hydronic/12 fins per in. F = 2 row reheat hydronic/14 fins per in. G = 1 row reheat steam/6 fins per in. H = 4 row hydronic/9 fins per in. J = 4 row hydronic/12 fins per in. K = 4 row hydronic/14 fins per in. L = 6 row hydronic/9 fins per in. M = 6 row hydronic/12 fins per in. N = 6 row hydronic/14 fins per in. P = 8 row hydronic/9 fins per in. R = 8 row hydronic/12 fins per in. T = 8 row hydronic/14 fins per in. U = 4 row DX/9 fins per in. V = 4 row DX/12 fins per in. W = 4 row DX/14 fins per in. Y = 6 row DX/9 fins per in. Z = 6 row DX/12 fins per in. 1 = 6 row DX/14 fins per in. S = Special
Digit 15 - Coil options
0 = None 1 = Aluminum fin, galvanized coil casing 2 = Aluminum fin, stainless steel coil
casing
S = Special
Digit 16 - Controller options
0 = None 1 = Unwired end devices 2 = Control interface S = Special
Digit 17 - Electric heat/factory mounted
0 = No electric heat 1 = Electric heat with 1 stage 2 = Electric heat with 2 stages 4 = Electric heat with 4 stages 5 = SSR control S = Special
Digit 18, 19, 20 - Electric heater kW
000 = None 006 = 6.0 kW 007 = 7.0 kW 008 = 8.0 kW 009 = 9.0 kW 010 = 10.0 kW 011 = 11.0 kW 012 = 12.0 kW 013 = 13.0 kW 014 = 14.0 kW 015 = 15.0 kW 016 = 16.0 kW 017 = 17.0 kW 018 = 18.0 kW 020 = 20.0 kW 022 = 22.0 kW 024 = 24.0 kW 026 = 26.0 kW 027 = 28.0 kW 030 = 30.0 kW 032 = 32.0 kW 034 = 34.0 kW 036 = 36.0 kW 038 = 38.0 kW 041 = 41.0 kW 044 = 44.0 kW 047 = 47.0 kW 050 = 50.0 kW 053 = 53.0 kW 056 = 56.0 kW 059 = 59.0 kW 063 = 63.0 kW 067 = 67.0 kW 071 = 71.0 kW 075 = 75.0 kW 079 = 79.0 kW 083 = 83.0 kW 087 = 87.0 kW 091 = 91.0 kW 095 = 95.0 kW 100 = 100 kW 105 = 105 kW 110 = 110 kW 115 = 115 kW 120 = 120 kW SSS = Special
Digit 21 - Electric heat options
0 = None A = Line fuse, door interlocking
disconnect switch and airflow switch
S = Special
6 CLCH-PRC024A-EN
Model Number Descriptions
Digit 22 - Refrigerant circuit options
0 = None 1 = Single refrigerant circuit arr with
1 stage DX 1/4-in. distributor
2 = Face split refrigerant circuit arr with
2 stage DX 1/4-in. distributor
3 = Intertwined refrigerant circuit arr with
2 stage DX 1/4-in. distributor
4 = Single refrigerant circuit arr with
2 stage DX 1/4-in. distributor
5 = Face split refrigerant circuit arr with
4 stage DX 1/4-in. distributor
6 = Intertwined refrigerant circuit arr with
4 stage DX 1/4-in. distributor
A = Single refrigerant circuit arr with
1 stage DX 3/16-in. distributor
B = Face split refrigerant circuit arr with
2 stage DX 3/16-in. distributor
C = Intertwined refrigerant circuit arr with
2 stage DX 3/16-in. distributor
D = Single refrigerant circuit arr with
2 stage DX 3/16-in. distributor
E = Face split refrigerant circuit arr with
4 stage DX 3/16-in. distributor
F = Intertwined refrigerant circuit arr with
4 stage DX 3/16-in. distributor
S = Special
Digit 23 - Motor horsepower
0 = No motor A = 1 hp (0.746 kW) B = 1 1/2 hp (1.119 kW) C = 2 hp (1.492 kW) D = 3 hp (2.238 kW) E = 5 hp (3.730 kW) F = 7 1/2 hp (5.595 kW) G = 10 hp (7.460 kW) H = 15 hp (11.190 kW) S = Special
Digit 24 - Volume control
0 = None A = FC fan constant volume with variable
pitch sheaves
B = FC fan constant volume with fixed
pitch sheaves or DDP fan
C = FC fan with fixed pitch sheaves or
DDP fan and variable frequency drive
D = FC fan with fixed pitch sheaves or
DDP fan and variable frequency drive and shaft grounding
E = FC fan constant volume with fixed
pitch sheaves or DDP and shaft grounding
S = Special
Digit 25 - Drives
0 = None A = 650 rpm fixed/600-700 rpm variable B = 700 rpm fixed/650-750 rpm variable C = 750 rpm fixed/700-800 rpm variable D = 800 rpm fixed/750-850 rpm variable E = 850 rpm fixed/800-900 rpm variable F = 900 rpm fixed/850-950 rpm variable G = 950 rpm fixed/900-1000 rpm variable H = 1000 rpm fixed/950-1050 rpm variable J = 1050 rpm fixed/1000-1100 rpm variable K = 1100 rpm fixed/1050-1150 rpm variable L = 1150 rpm fixed/1100-1200 rpm variable M = 1200 rpm fixed/1150-1250 rpm
variable
N = 1250 rpm fixed/1200-1300 rpm
variable
P = 1300 rpm fixed/1250-1350 rpm
variable
R = 1350 rpm fixed/1300-1400 rpm
variable
T = 1400 rpm fixed/1350-1450 rpm
variable
U = 1450 rpm fixed/1400-1500 rpm
variable
V = 1500 rpm fixed/1450-1550 rpm
variable
W = 1550 rpm fixed/1500-1600 rpm
variable
Y = 1600 rpm fixed/1550-1650 rpm
variable
Z = 1650 rpm fixed/1600-1700 rpm
variable
1 = 1700 rpm fixed/1650-1750 rpm
variable
2 = 1750 rpm fixed/1700-1800 rpm
variable
3 = 1800 rpm fixed/1750-1850 rpm
variable
4 = 1850 rpm fixed/1800-1900 rpm
variable
5 = 1900 rpm fixed/1850-1950 rpm
variable
6 = 1950 rpm fixed/1900-2000 rpm
variable
7 = 2000 rpm fixed/1950-2050 rpm
variable 8 = Direct-drive plenum fan S = Special
Digit 26, 27 - VFD setting/DDP fan speed
00 = Housed fan 54 = 54 hertz/1604 rpm 55 = 55 hertz/1634 rpm 56 = 56 hertz/1663 rpm 57 = 57 hertz/1693 rpm 58 = 58 hertz/1723 rpm 59 = 59 hertz/1752 rpm 60 = 60 hertz/1782 rpm 61 = 61 hertz/1872 rpm 62 = 62 hertz/1841 rpm 62 = 63 hertz/1871 rpm 64 = 64 hertz/1901 rpm 65 = 65 hertz/1931 rpm 66 = 66 hertz/1960 rpm 67 = 67 hertz/1990 rpm 68 = 68 hertz/2020 rpm
69 = 69 hertz/2049 rpm 70 = 70 hertz/2079 rpm 71 = 71 hertz/2109 rpm 72 = 72 hertz/2138 rpm 73 = 73 hertz/2168 rpm 74 = 74 hertz/2198 rpm 75 = 75 hertz/2228 rpm 76 = 76 hertz/2257 rpm 77 = 77 hertz/2287 rpm 78 = 78 hertz/2317 rpm 79 = 79 hertz/2346 rpm 80 = 80 hertz/2376 rpm 81 = 81 hertz/2406 rpm 82 = 82 hertz/2435 rpm 83 = 83 hertz/2465 rpm 84 = 84 hertz/2495 rpm 85 = 85 hertz/2525 rpm 86 = 86 hertz/2554 rpm 87 = 87 hertz/2584 rpm 88 = 88 hertz/2614 rpm 89 = 89 hertz/2643 rpm 90 = 90 hertz/2673 rpm 91 = 91 hertz/2703 rpm 92 = 92 hertz/2732 rpm 93 = 93 hertz/2762 rpm 94 = 94 hertz/2792 rpm 95 = 95 hertz/2822 rpm 96 = 96 hertz/2851 rpm 97 = 97 hertz/2881 rpm 98 = 98 hertz/2911 rpm 99= 99 hertz/2941 rpm A0 = 100 hertz/2970 rpm A1 = 101 hertz/3000 rpm A2 = 102 hertz/3030 rpm A3 = 103 hertz/3060 rpm A4 = 104 hertz/3089 rpm A5 = 105 hertz/3119 rpm A6 = 106 hertz/3149 rpm A7 = 107 hertz/3178 rpm A8 = 108 hertz/3208 rpm A9 = 109 hertz/3238 rpm B0 = 110 hertz/3267 rpm B1 = 111 hertz/3297 rpm B2 = 112 hertz/3327 rpm B3 = 113 hertz/3357 rpm B4 = 114 hertz/3386 rpm B5 = 115 hertz/3416 rpm B6 = 116 hertz/3446 rpm B7 = 117 hertz/3475 rpm B8 = 118 hertz/3505 rpm B9 = 119 hertz/3535 rpm C0 = 120 hertz/3564 rpm SS - Special
Digit 28 - Mixing Box/Filter section
0 = None A = 2-in. flat filter rack B = 2-in. flat filter/mixing box C = 2-in. angle filter section D = 2-in. angle filter/mixing box E = 2-in./4-in. combination filter rack F = 2-in./4-in. combination filter/ mixing box S = Special
CLCH-PRC024A-EN 7
Model Number Descriptions
Digit 29 - Filter type
0 = Customer supplied/no filters A = 2-in. MERV 8 B = 2-in. MERV 13 C = 2-in. MERV 8/4-in. MERV 11 D = 2-in. MERV 8/4-in. MERV 13 E = 2-in. MERV 13/4-in. MERV 13 S = Special
Digit 30 - Controls options 1
0 = None 1 = Low limit switch, condensate overflow
switch, dirty filter switch and fan status switch
S = Special
Digit 31 - Controls options 2
0 = None A = Discharge air sensor B = Discharge air sensor and mixed air
sensor
C = Discharge air sensor, mixed air
sensor, factory-mounted n.o. mixing box actuator
D = Discharge air sensor, mixed air
sensor, factory-mounted n.c. mixing box actuator
S = Special
Digit 32 - Controls options 3
0 = None A = Outdoor air temperature sensor
hard wired
B = Duct static pressure sensor hard
wired
C = Outdoor air temperature sensor and
duct static pressure sensor hard wired
S = Special
Digit 33 - Special
0 = Standard order S = Special order
8 CLCH-PRC024A-EN
Features and Benefits
The Performance Climate Changer air handler, model UCCA, provides a cost-effective solution to meet cataloged air handling needs. As a customizable, cataloged air handler, components are available to meet a wide range of commercial and institutional applications for the indoor air handler market. Pre-engineered options expand that flexibility while ensuring proven, tested performance and dependability. These features add flexibility and are engineered to provide good indoor air quality, including:
Single point power
Factory mounted, wired and tested controls
Two-inch double-wall injected foam casing
Direct-drive plenum fans
Filter options including MERV 11 and MERV 13 filters, which help ac hi eve points toward LEED certification
Variety of coil options that include hydronic, DX, steam and electric heat
Construction and Integrity
Panels and doors are designed to provide extraordinary insulating capabilities for efficient and cost-effective performance. Standard double-wall panels and doors include two-inch closed cell foam insulation providing a minimum R-value of 13, in addition to premium panel strength and
0.005 inch deflection at +/- 4 inches w.g.
Heavy-duty door handles and hinges are surface-mounted and a removable hinge pin allows for easy door removal.
Engineered fo r Good IAQ
The building industry is continuously evolving and the rate of change is accelerating. The Performance air handler is engineered to address today’s multifaceted design issues required to provide good indoor air quality (IAQ). Building owners must give particular attention to maintaining and documenting IAQ to ensure occupa nt comfort and to meet industry and government regulatory standards.
ASHRAE Standard 62.1 provides guidance regarding suitable outside air volume to be brought into the building, recommended air filtration, and procedures to control microbial growth. The Performance air handler enables you to configure an IAQ-ready air-handling system that addresses these concerns.
Sloped Drain Pan
The drain pan is positively sloped in every plane to assure proper drainage and help maximize protection from microbial growth.
Drain pans are made from a noncorrosive polymer material, double-wall construction, and foamed in place to help eliminate condensation beneath the drain pan. An optional stainless steel drain pan is also available.
CLCH-PRC024A-EN 9
Features and Benefits
Serviceability/Cleanability
Full-size access doors are provided for cleaning of internal components
Removable coil panels
Smooth, cleanable interior double-wall surfaces help improve indoor air quality
Coils are raised up out of the drain pan to ma ke all coils removab le from the side and pr ovide easier access to the drain pan for cleaning
Filtration
Performance air handlers are available with a wide variety of filtra tio n op tions, including:
Two-inch MERV 8 or MERV 13 flat or angled filters
Combination filter racks including two-inch MERV 8 or MERV 13 and four-inch MERV 11 or MERV 13
A factory-mounted dirty filter switch can be used to indicate when the filter needs replacement.
Ventilation
An optional mixing box with ultra low-leak dampers is available for use when ventilation air is delivered directly to the unit. This mixing box can also function as a zero to 100 percent economizer to improve energy efficiency.
Dehumidification
Performance air handler model UCCA can be configured for either a constant-volume or VAV application. VAV systems generally provide effective, coincidental dehumidification over a wide range of indoor load conditions. As long as any space needs cooling, the VAV air handler supplies dry (low dew point) air to all of the VAV terminal units.
For direct control of space humidity in a constant-volume application, the Performance air handler can be configured with a hydronic or steam heating coil in the reheat position. This would allow the cooling and heating coils to modulate inde pendently to directly control both temperature and humidity in the space. A unit-mounted electric heater, with a single-point connection, is also available in the reheat position.
10 CLCH-PRC024A-EN
Control Solutions
Performance air handlers are available with an optional control interface. This package can be used as part of a stand-alone operation, or it can be fully integrated into a comprehensive control system. The T rane Earthwi se™ system incor porates the bene fits of factory-installed cont rols and links the air handler to the Tracer™ SC system controls building management system. This option is designed to lower installation costs and risk while dramatically improving the quality of the application and the performance of the air handler. The entire air handler control system is engineered, mounted, wired, and tested before leaving the factory. As a result of strict quality manufacturing methods, these control options bring consistency and reliability to the control­system package and provide single-source responsibility.
The following control devices are available as stand ard mounted on fan sections:
Variable-frequency drives (VFDs)
Control interface package – Fan motor disconnect switch – Fused transformer(s) – Fan contactor – Customer terminal strip for field-provided controls
Various end device options, including: – Low limit protection – Condensate overflow switch – Fan status switch – Filter status switch – Discharge air sensor – Mixed air sensor – Damper actuator
Features and Benefits
Single Source Responsibility
Equipment and interoperable controls, engineered and provided by a single manufacturer, provide faster construction cycles and simplify job-site coordination efforts. This simplification reduces installation time, expense, and risk.Trane equipment and controls package provides the optimal performance when integrated in a Trane Earthwise™ system. This is a powerful system architectur e that unifi es Trane HVA C equipme nt, direct d igital contr ol, and bui lding manage ment into a cohesive whole with an assured source of support. This system is managed with the Tracer™ building management system.
CLCH-PRC024A-EN 11
Features and Benefits
Pro ven Performance
AHRI Standards
Figure 1. AHRI Standard 430
Figure 2. AHRI Standard 410
UL Listing
Trane combines comprehensive performance certification by AHRI with thorough laboratory testing and advanced manufacturing methods. Together , these elements help assure that each Trane air handler operates predictably and reliably throughout the life of the unit.
Unlike other rating methods that check fan performance alone, Trane units are performance-tested in accordance with AHRI Standard 430. This certification process evaluates the air handler on the basis of airflow, static pressure, fan speed, and brake horsepower.
Heating and cooling coils are rigorously tested and certified with AHRI Standard 410 to assure that they, too, deliver published performance.
AHRI Standard 260 is the first ducted-air-handler sound rating procedure. It i s intended to provide engineers with better, more accurate, ducted sound power levels so that they can design quieter and more cost-effective comfort systems. Sound ratings for Trane air handlers have been developed from extensive AHRI Standard 260 testing and laboratory data.
Trane air han dlers are UL-listed to U.S. and Canadian safety standards.
ISO Certification
Certification by the International Standardization Organization (ISO) ensures that an organization can consistently deliver a product or service that meets the customer’s contractual requirements by following documented processes. The ISO 9001 quality assurance model establishes the requirements for an organization whose business processes range from design and development to production. Having the quality management system of our manufacturing pl ants ISO 9001-certified directly benefits Trane customers because our continuous process improvements can reduce business costs, improve product quality, and en able faster ship cycles
12 CLCH-PRC024A-EN
Application Considerations
FC fan with top front discharge FC fan with front top discharge Direct-drive fan with front discharge
The Performance Climate Changer air handler, model UCCA, offers a wide range of application flexibility while maintaining a simple, easy to install unit design. These units are a great choice when a compact, reliable air handler is needed when budget is a critical factor.
Typical applications include many different types of buildings such as: schools, office buildings, hospitals and retail. Applications can be either constant volume or variable air volume. Some applications include:
Two-pipe hydronic system for cooling and/or heating
Two-pipe hydronic cooling system with electric heat
Four-pipe system with dedicated heating and cooling coils
Direct expansion (DX) split systems with hydronic heat
Standard AHU Arrangements
T o complete the air -handling system, the unit must be arranged in a way that fits the available space and meets the application requirement. The Performance air handler provides a draw-thru AHU arrangement that places the coils and filters upstream of a ducted supply fan.
Horizontal Draw-Thru
Figure 3. Hori zontal draw-thru units
T rane air handlers in a horizontal draw-thru arrangement provide the system components that are required in a single-level unit. An optional blow-thru electric heater is also available. Accepted system design practices are generally the only restrictions in a horizontal draw-thru application.
CLCH-PRC024A-EN 13
Application Considerations
FC fan with
back top discharge
FC fan with
top back discharge
FC fan with
front top discharge
FC fan with
top front discharge
Vertical Draw-Thru
Figure 4. Vertical draw-thru units
Installation
T rane air handlers in a vertical draw-thru arrangement result in a shorter footprint than horizontal draw-thru units. This arrangement stacks a fan on top of the coil section. When designing an air handler in this configuration, a vertical draw-thru fan performance curve should be used to account for the airflow impingement by a coil as the air flows through the coil and turns up into the fan.
Horizontal units can be floor-mounted on a house-keeping pad or suspended from the ceiling. V ertical units are floor-mounted on a house-keeping pad. Refer to CLCH-S VX009A-EN Installation, Operation, Maintenance (IOM) manual for installation instructions.
All units are shipped with isolation system tied down for shipment purposes. To utilize standard internal isolation, remove shipping tie-downs per the IOM. If external isolation is being utilized, install units with external vibration isolation on all connection points, including the ductwork connections and piping connections.
It is important to consider pr oper condensate management before installation. You must mount the unit high enough so that the condensate drain pan can be properly trapped. Refer to CLCH-SVX009A-EN IOM for specific trapping instructions.
Install units in accordance to all applicable ASHRAE standards, SMACNA, and local code requirements.
14 CLCH-PRC024A-EN
Operating Limitations
Do not operate unit above maximum fan speed or unit airflow as shown in the unit fan curves. Unit operation at greater than maximum fan speed can drastically reduce bearing life and result in a catastrophic failure. Operating at greater than the maximum allowable airflow in the cooling mode may result in unsatisfactory operation due to moisture carryover from the coil. In addition, it is often not economical to operate a unit at its maximum fan speed due to the greater motor power requirements.
Do not operate units with electric heat below the minimum airflow listed in CLCH-SVX009A-EN IOM. This is to prevent excessive leaving air temperatures and electric heat limit trips.
Do not operate a hydronic (or steam) coil and electric heat simultaneously. This is to prevent excessive leaving air temperatures and limit trips . Electric heat units are equipped with a lockout switch to disable the electric heater if the temperature of the hydronic (or steam) coil is greater than 95°F (35C).
Do no operate coils above the fluid flow limits listed in the installation manual. This is to prevent noise and erosion within the coil. A minimum or “self venting” fluid flow rate is also listed in the installation manual. If coils operate below this flow rate, you should periodically vent them by flushing at a higher flow rate. These low fluid flow rates may also be too low to be included in the AHRI certification.
DX Cooling Units
Application Considerations
Performance air hand lers with a DX cooling coil will often be connected to an air -cooled condensing unit. Some condensing un its have two, independent re frigeration circuits, while the DX coil in size 3 through 10 units can be configured with a single circuit. Do not manifold two, independent refrigeration circuits into a single-circuited DX (evaporator) coil. If the condensing un it does have two, independent refrigeration circuits, configure the DX coil to have either two or four distributors.
DX coils, equipped with either two or four distributors, can be configured with either intertwined or horizontal split circuiting. Intertwined circuited is preferred in VAV applications. At low loads, refrigerant is fed to alternating tubes, and the coil performs as though its fin surface area is substantially greater. Therefore, the coil surface can be warmer at part load, whic h reduces the risk of frost and still provides a constant leaving-air temperature.
CLCH-PRC024A-EN 15
Components and Options
Performance Climate Changer air handler model UCCA provides a standard configuration with coil(s) and fan, and then allows customization with various optional accessory sections.
Figure 5. A variety of coils are available on
Performance air handlers
Coils
The variety of T rane coil types, sizes, arrangements, and materials allows you to select a coil that is optimized for pressure drop and capacity requirements. Published coil performance is certified in accordance with AHRI Standard 410 and meets CRN standards.
Trane is at the leading edge of coil technology. Through extensive laboratory testing and numerous job-site installations, Trane has developed an enhanced fin surface that has superior heat transfer characteristics and allows greater velocities of air to move through the cooling coil without causing moisture carryover.
The industry is familiar with the 500 fpm limit through a cooling coil as a “rule of thumb” to safeguard ag ainst moisture carryo ver. However , some applications have tight dimensiona l constraints that require high coil face velocities. Trane’s fin design extends this limit in excess of 625 fpm, depending upon air conditions, coil siz e, and spacing. Tested data for moisture carryover is incorporated in the T rane Official Product Se lection System (TOPSS™). In cases where moisture carryover is possible, the TOPSS program alerts you to this fact with a moisture carryover warning.
Coil options include the following:
Four- to eight-row, ½-inch OD (outside diameter) chilled water coils
Four-to six-row, ½-inch OD refrigerant coils
One- or two-row ½-inch OD hot water coils
One-row, 1-inch OD distributing-type steam coils
Figure 6. Direct-drive plenum fans and FC
fans are available
16 CLCH-PRC024A-EN
Fans
T rane offers flexible fan types and options, including variable-frequency drives (VFDs) for modulation in variable-air-volume systems. Fan types include:
Single-width/single-inlet (SWSI) direct-drive plenum fans with front or top discharge
Double-width/double-inlet (DWDI) centrifugal forward-curved (FC) fans with front or top discharge
Each fan is rated in accordance with Standard 430 of the Air Conditioning Heating and Refrigeration Institute (AHRI) and all DWDI fans are AHRI Standard 430-certified to assure published performance.
To verify that fan performance will satisfy design requirements, use the TOPSS selection program. The AHRI Standard 430-certified fan curves include the fan section casing effect. TOPSS also takes into account air density, fan and motor heat, drive losses, and use of high-performance filters that affect fan performance.
Components and Options
Figure 7. Mixing box with angled filter rack
Figure 8. Electric heat
Mixing Box/Filter Section
A mixing box is available for those applications where both return air and fresh air are delivered directly to the unit or as part of an economizer control strategy. The mixing box also has the flexibility to provide a wide variety of filtration options, including 2-inch flat or angled filters and 2­inch/4-inch combination flat filters.
Effectively controlling particulates by removing them from the air stream is key to good IAQ. That necessitates proper filter selection. In addition to mixing box/filter sections, filter sections are also available with angled or flat filters.
Electric Heat Section
In addition to hydronic and steam coil options, the unit is also available with a unit mounted electric heater in the reheat position. The unit will have single point power connection to the elect ric heater. The heater is available with step control or SSR-full modulating control.
CLCH-PRC024A-EN 17
General Data
Mixing box /flat filter section
Mixing box /angle filter section
Angle filter
FC fan with top front discharge
FC fan with front top discharge
Direct-drive fan with front discharge
Flat filter
Electric heat
Electric heat
Electric heat
Unit Configurations and Components
Figure 9. Horizontal configurations and components
18 CLCH-PRC024A-EN
Figure 10. Vertical configurations and components
Mixing/angle fileter section
Mixing/flat filter section Angle filter
Flat filter
FC fan with top back discharge
Electric heat
Mixing/angle fileter section
Mixing/flat filter section Angle filter
Flat filter
FC fan with front top discharge
Electric heat
General Data
CLCH-PRC024A-EN 19
General Data
Mixing/angle fileter section
Mixing/flat filter section Angle filter
Flat filter FC fan with back top discharge
Electric heat
Mixing/angle fileter section
Mixing/flat filter section Angle filter
Flat filter
FC fan with top front discharge
Electric heat
Figure 11. Vertical configurations and components
20 CLCH-PRC024A-EN
-
Table 1. Performance air handler model UCCA data
General Data
Nom airflow (CFM)
1500 3000 4000 5000 6000 7000 3500 10500 12500 15000
Unit size 3 6 8 10 12 14 7 21 25 30
Horz unit height (in.) 27.50 32.50 38.00 38.00 41.80 45.60 48.10 54.30 60.60 60.60
Horz unit width (in.) 34.00 47.00 51.00 63.00 71.00 71.00 79.00 79.00 81.00 94.00
Horz unit length (in.) 51.90 54.90 52.30 54.70 54.70 56.20 60.20 60.20 62.90 69.60
Vert unit height (in.) 51.40 61.30 65.10 69.90 80.10 83.80 92.90 99.20 n/a n/a
Vert unit width (in.) 34.00 47.00 51.00 63.00 71.00 71.00 79.00 79.00 n/a n/a
Vert unit length (in.) 34.10 37.10 29.40 32.10 36.10 36.10 42.10 42.10 n/a n/a
Coils Hydronic/DX coils
Area (ft2) 2.80 5.60 7.60 9.90 12.30 14.30 16.30 20.4.00 24.00 28.50
Width (in.) 17.50 22.50 27.50 27.50 30.00 35.00 35.00 43.75 50.00 50.00
Length (in.) 23.00 36.00 40.00 52.00 59.00 59.00 67.00 67.00 69.00 82.00
Velocity (fpm) 536.60 533.30 523.60 503.50 488.10 488.1 522.00 515.80 521.70 526.80
Dry Weight (lb.)
- 1-row 26 39 47 58 72 80 87 112 126 145
- 2-row 35 55 69 86 107 120 132 168 192 223
- 4-row 53 89 114 144 177 201 223 281 325 380
- 6-row 72 122 158 201 247 282 314 394 457 536
- 8-row 90 156 203 258 316 363 405 507 589 693
Wet Weight (lb. )
- 1-row 29 43 53 66 82 91 99 128 145 167
- 2-row 40 64 81 102 127 143 158 200 230 268
- 4-row 63 107 138 175 216 247 274 345 400 470
- 6-row 85 149 195 248 305 350 391 491 570 671
- 8-row 108 192 251 321 394 454 508 636 740 873
Steam coils
Area (ft2) 1.8 4.4 6.5 8.5 9.8 13.315.116.821.325.3
Width (in.) 12 18 24 24 24 33 33 36 45 45
Length (in.) 22353951595866676881
Velo ci ty (FPM) 818 686 615 588 610 527 562 627 588 593
Weight (lb.) 44 67 85 102 112 139 154 191 241 276
CLCH-PRC024A-EN 21
General Data
Table 1. Performance air ha nd ler model UCCA data
Nom airflow (CFM)
1500 3000 4000 5000 6000 7000 3500 10500 12500 15000
Unit size 3 6 8 10 12 14 7 21 25 30 Fan/Motor data
FC fans
Wheel size (in.) 9x7 12x9 12x12 15x15 18x15 18x18 20x15 20x20 20x18 22x20
Maximum RPM 2000 1500 1700 1400 1200 1200 1100 1000 1300 1150
Motor HP 1-2 1-3 1-5 1 - 5 1 - 7 1/2 1 - 7 1/2 1 - 10 2 - 15 3 - 15 1 1/2 - 15
Minimum design CFM 1050 2100 2800 3500 4200 4900 5950 7350 8750 10500
DDP fans
Wheel size (in.) 11 14 16 18 18 20 20 2 x 18 2 x 20 2 x 20
Maximum RPM 3600 3600 3400 3025 3025 2720 2720 3025 2720 2720
Motor HP 1-2 1 1/2 - 5 2- 7 1/2 3 - 7 1/2 3 - 10 3 - 15 3 - 15 3- 10 3- 10 5 - 15
Filters (height x width) with quantity per size
2 in. and 2/4 in. combination flat filter
- 16 x 20 4 2 2 4 2
- 16 x 25 4 1 1 2 2 6
- 20 x 20 2 2 4 2
- 20 x 25 1 2 1 1 2 6 4
Area (ft2) 3.5 6.9 8.9 11.1 16.3 16.3 20.0 22.5 26.4 30.6
Nominal Velocity (fpm) 432.0 432.0 450.0 450.0 369.2 430.8 425.0 466.7 473.7 490.9
2-in. Angle Filter
- 16 x 20 2 6 6 6 4 12
- 16 x 25 2 3 3 8
- 20 x 20 4 2 4 6 8
- 20 x 25 2 12
Area (ft2) 5.6 11.1 12.5 15.6 21.7 21.7 30.0 31.1 41.7 48.9
Nominal Velocity (fpm) 270.0 270.0 320.0 321.4 276.9 323.1 283.3 337.5 300.0 306.8
Mix Box
Damper Area (ft2) 1.3 2.4 3.1 4.1 5.1 5.6 7.0 8.2 10.3 12.0
Nominal Velocity (fpm) 1166.9 1224.7 1288.5 1205.6 1178.0 1239.2 1217.0 1277.9 1208.1 1247.1
Notes: Coil weight based on 12 fins per inch, galvanized casing
Coil width = length in direction of coil header, typically vertical. Coil length = length of coil in direction of the coil tubes, typically horizontal and perpendicular to airflow. Unit sizes 21-30 have two stacked steam coils Fan wheel size is diameter x length of blade (width). Minimum airflow limit is for units with hot water, steam, or electric heat. There is no minimum airflow for cooling-only units.
22 CLCH-PRC024A-EN
General Data
Coil Data
Table 2. Number of circuits and distributors
Single Horizontal Face Split Intertwined
Coil Fin
Unit Size
10 1 10 27.50 52.00 2 10 27.50 52.00 2 10 27.50 52.00
12 - - - - 2 11 30.00 59.00 2 11 30.00 59.00
14 - - - - 2 13 35.00 59.00 2 13 35.00 59.00
17 - - - - 2 13 35.00 67.00 2 13 35.00 67.00
21 - - - - 2 17 43.75 67.00 4 17 43.75 67.00
25 - - - - 2 19 50.00 69.00 4 19 50.00 69.00
30 - - - - 4 39 50.00 82.00 4 39 50.00 82.00
Dist Circuits
3 1 3 17.50 23.00 - - - - - - - -
6 1 5 22.50 36.00 - - - - - - - -
8 1 7 27.50 40.00 2 7 27.50 40.00 2 7 27.50 40.00
Width Length Width Length Width Length
Dist Circuits
Coil Fin
Coil Fin
Dist Circuits
CLCH-PRC024A-EN 23
Performance Data
Coil Data
Table 3. Hydronic/DX coil performance data
Size Width (in) Length (in) Coil Area (ft2)
3 17.50 23.00 2.80
6 22.50 36.00 5.60
8 27.50 40.00 7.60
10 27.50 52.0 9.90
12 30.00 59.00 12.30
14 35.00 59.00 14.30
17 35.00 67.00 16.30
21 43.75 67.00 20.40
25 50.00 69.00 24.00
30 50.00 82.00 28.50
Table 4. Steam coil performance data
Size Width (in) Length (in) Coil Area (ft2)
3 12.00 22.00 1.80
6 18.00 35.00 4.40
8 24.00 39.00 6.50
10 24.00 51.00 8.50
12 24.00 59.00 9.80
14 33.00 58.00 13.30
17 33.00 66.00 15.10
21
25
30
18.00 67.00
18.00 67.00
12.00 68.00
33.00 68.00
12.00 81.00
33.00 81.00
16.80
21.30
25.30
24 CLCH-PRC024A-EN
Performance Data
1.00 bhp
1.50 bhp
2.00 bhp
1000 RPM
1500 RPM
2000 RPM
2500 RPM
3000 RPM
3500 RPM
3600 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
26
0
1
2
3
4
5
6
7
8
0 500 1000 1500 2000 2500
Total Static Pressure (in H2O)
Airow (cfm)
Fan Motor Data
Table 5. Fan motor data
Unit Size 3 6 8 10 12 14 17 21 25 30
Nominal Airflow
(cfm) 1500 3000 4000 5000 6000 7000 8500 10,500 12,500 15,000
FC Fan Wheel size (in) 9x7 12x9 12x12 15x15 18x15 18x18 20x15 20x20 20x18 22x20
DDP Fan Wheel Size (in) 11 14 16 18 18 20 20 2 x 18 2 x 20 2 x 20
Maximum RPM (FC) 2000 1500 1700 1400 1200 1200 1100 1000 1300 1150
Maximum RPM (DDP) 3600 3600 3400 3025 3025 2720 2720 3025 2720 2720
Motor HP (FC) 1-2 1-3 1-5 1 - 5 1 - 7 1/2 1 - 7 1/2 1 - 10 2 - 15 3 - 15 1 1/2 - 15
Motor HP (DDP) 1-2 1 1/2 - 5 2- 7 1/2 3 - 7 1/2 3 - 10 3 - 15 3 - 15 3- 10 3- 10 5 - 15
Minimum Design CFM 1050 2100 2800 3500 4200 4900 5950 7350 8750 10500
Maximum Design CFM 1800 3600 4800 6000 7200 8400 10200 12600 15000 18000
Fan Curves
Direct-Drive Plenum Fans
Figure 12. Size 3 horizontal 11-inch DDP single fan
CLCH-PRC024A-EN 25
Performance Data
1.50 bhp
2.00 bhp
3.00 bhp
5.00 bhp
1000 RPM
1500 RPM
2000 RPM
2500 RPM
3000 RPM
3500 RPM
3600 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
26
0
1
2
3
4
5
6
7
8
9
10
11
12
0 500 1000 1500 2000
2500 3000
3500 4000
4500
5000
Total Static Pressure (in H2O)
Airow (cfm)
2.00 bhp
3.00 bhp
5.00 bhp
7.50 bhp
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2600 RPM
2800 RPM
3000 RPM
3200 RPM
3400 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
32
0.0
2.5
5.0
7.5
10.0
12.5
0
1000
2000 3000 4000 5000
6000 7000
Total Static Pressure (in H2O)
Airow (cfm)
Figure 13. Size 6 horizontal 14-inch DDP single fan
26 CLCH-PRC024A-EN
Figure 14. Size 8 horizontal 16-inch DDP single fan
Figure 15. Size 10 horizontal 18-inch DDP single fan
3.00 bhp
5.00 bhp
7.50 bhp
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2600 RPM
2800 RPM
3000 RPM
3025 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
31
0.0
2.5
5.0
7.5
10.0
12.5
0 1000 2000 3000 4000 5000 6000 7000 8000 9000
Total Static Pressure (in H2O)
Airow (cfm)
3.00 bhp
5.00 bhp
7.50 bhp
10.00 bhp
1000 RPM
1200 RPM
1400 RPM
1600 RPM
1800 RPM
2000 RPM
2200 RPM
2400 RPM
2600 RPM
2800 RPM
3000 RPM
3025 RPM
45 %WO
50 %WO
60 %WO
70 %WO
80 %WO
90 %WO
31
0.0
2.5
5.0
7.5
10.0
12.5
0 1000
2000
3000 4000 5000 6000 7000
8000
9000
Total Static Pressure (in H2O)
Performance Data
Figure 16. Size 12 horizontal 18-inch DDP single fan
CLCH-PRC024A-EN 27
Airow (cfm)
Loading...
+ 61 hidden pages