Trane TWE061D-E***A, TWE090D-E**BA, TWE120D-E**BA, TWE150E**BA, TWE180E**BA Installation and Maintenance Manual

...
Installation, Operation, and Maintenance
Split System Air Conditioners Odyssey™
Air Handler — 5 to 25 Tons
MMooddeell ((6600 HHzz)) TWE061D/E***A TWE090D/E**BA TWE120D/E**BA TWE150E**BA TWE180E**BA TWE240E**BA TWE300E**BA
MMooddeell ((5500 HHzz)) TWE051D***A TWE076D/E***A TWE101D/E***A TWE126E***A TWE156E***A TWE201E***A TWE251E***A
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
March 2015
SSA-SVX06E-EN
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee eelleeccttrriiccaall ccooddeess..
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee MMaatteerriiaall SSaaffeettyy DDaattaa SShheeeettss ((MMSSDDSS))//SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee MMSSDDSS//SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
©2015 Trane All rights reserved
SSA-SVX06E-EN
IInnttrroodduuccttiioonn
WWAARRNNIINNGG
RReeffrriiggeerraanntt uunnddeerr HHiigghh PPrreessssuurree!!
SSyysstteemm ccoonnttaaiinnss ooiill aanndd rreeffrriiggeerraanntt uunnddeerr hhiigghh pprreessssuurree.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr rreeffrriiggeerraanntt aaddddiittiivveess..
WWAARRNNIINNGG
RR--441100AA RReeffrriiggeerraanntt uunnddeerr HHiigghheerr PPrreessssuurree tthhaann RR--2222!!
TThhee uunniittss ddeessccrriibbeedd iinn tthhiiss mmaannuuaall uussee RR--441100AA rreeffrriiggeerraanntt wwhhiicchh ooppeerraatteess aatt hhiigghheerr pprreessssuurreess tthhaann RR--2222.. UUssee OONNLLYY RR--441100AA rraatteedd sseerrvviiccee eeqquuiippmmeenntt oorr ccoommppoonneennttss wwiitthh tthheessee uunniittss.. FFoorr ssppeecciiffiicc hhaannddlliinngg ccoonncceerrnnss wwiitthh RR--441100AA,, pplleeaassee ccoonnttaacctt yyoouurr llooccaall TTrraannee rreepprreesseennttaattiivvee..
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
With the change to Microchannel, the Odyssey split system now offers a 50Hz, 6.25 standard air handler (TWE076E) and a 60Hz, 7.5 ton standard/SZVAV/2­Speed VFD air handler (TWE090E). See performance data for additional details on this new split system.
Odyssey air handlers now have the ability to convert from Single Zone VAV to 2–Speed Fan control in order to comply with certain sections of California Title 24 and ASHRAE 90.1. See
“Installation, 2-Speed VFD Units,” p. 25 for
configuration details.
SSA-SVX06E-EN
3
Table of Contents
Model Number Description. . . . . . . . . . . . . . . . . 5
Air Handler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Information . .. . . . . . . . . . . . . .. . . . . . . . 6
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Pre-Installation . . . . . . . . . . . . . . . . . . . . . .. . . . . . . 7
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Inspection Checklist . . . . . . . . . . . . . . . . . . . 7
Testing for Leaks. . . . . . . . . . . . . . . . . . . . . . . . . . 7
Lifting Recommendations . . . . . . . . . . . . . . . . . 7
Repositioning Drain Pan. . . . . . . . . . . . . . . . . . . 7
Field Conversion to 460 Volt . . . . . . . . . . . . . . . 9
Converting Motor to 460 Volt. . . . . . . . . . . 9
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . 9
Reorienting Evaporator Coil
(TWE126/150 and 156/180) . . . . . . . . . . . . . 9
Preparation for Refrigerant
Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Installations, Limitations and
Recommendations. . . . . . . . . . . . . . . . . . . . . . . 10
Dimensional Data . . . . . . . . . . . . . .. . . . . . . . . . . 11
Weights . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . . . . 20
Air Handler. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Air Flow Settings . . . . . . . . . . . . . . . . . . . . . . . . 24
Standard Units. . . . . . . . . . . . . . . . . . . . . . . 24
SZVAV Units . . . . . . . . . . . . . . . . . . . . . . . . . 24
2-Speed VFD Units . . . . . . . . . . . . . . . . . . . 25
Minimum Supply Fan Output . . . . . . . . . 25
Electrical Connections . . . . . . . . . . . . . . . . . . . 26
Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
EDC Switch Wiring . . . . . . . . . . . . . . . . . . . 27
Heating and Cooling Setpoint
Arbitration . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Checkout Procedure . . . . . . . . . . . . . . . . . . . . . 28
Installation Checklist . . . . . . . . . . . . . . . . . . . . . 28
Thermostat and Control
Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Electromechanical Controls . . . . . . . . . . . 29
ReliaTel Controls . . . . . . . . . . . . . . . . . . . . . 29
Electrical Data . . . . . . . . . . . . . . . . . . . . . . .. . . . . . 31
60 Hz Models. . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
50 Hz Models. . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Start-Up . . . . . . . . . . . . . . . . .. . . . . .. . . . . . . . . . . . 42
Sequence of Operation. . . . . . . . . . . . . . . . . . . 42
Variable Air Volume Applications
(SZVAV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2–Speed VFD Applications . . . . . . . . . . . . 43
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . 22
Horizontal Suspension . . . . . . . . . . . . . . . . . . . 22
Leveling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Auxiliary Drain Pan. . . . . . . . . . . . . . . . . . . 22
Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . 22
Condensate Piping. . . . . . . . . . . . . . . . . . . . . . . 23
Filter Replacement. . . . . . . . . . . . . . . . . . . . . . . 23
Duct Connections. . . . . . . . . . . . . . . . . . . . . . . . 24
Maintenance . . . . . . . . . . . . . . . . . . . .. . . . . . . . . . 44
Fan Belt Adjustment . . . . . . . . . . . . . . . . . . . . . 44
Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Annually (Cooling Season) . . . . . . . . . . . . . . . 45
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . . . 46
Wiring Diagram Matrix . . . . . . . . . . . . . . . . . . .. 47
4
SSA-SVX06E-EN

Model Number Description

Air Handler

T WE 2 40 E D 0 0 * *
1 2 3 4 5 6 7 8 9 10 11 12
T WE 201 E D 0 0 * *
1 2 3 4 5 6 7 8 9 10 11 12
NNoottee:: When ordering replacement parts or requesting
service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate.
DDIIGGIITTSS 11 -- 33:: PPrroodduucctt TTyyppee
TWE = Split System Heat Pump/Cooling Air Handler
DDIIGGIITTSS 44 -- 66:: NNoommiinnaall GGrroossss CCoooolliinngg CCaappaacciittyy ((MMBBhh))
061 = 5 Tons (60 Hz) 090 = 7.5 Tons (60 Hz) 120 = 10 Tons (60 Hz) 150 = 12.5 Tons (60 Hz) 180 = 15 Tons (60 Hz) 240 = 20 Tons (60 Hz) 300 = 25 Tons (60 Hz) 051 = 4.6 Tons (50 Hz) 076 = 6.25 Tons (50 Hz) 101 = 8.33 Tons (50 Hz) 126 = 10.4 Tons (50 Hz) 156 = 13.0 Tons (50 Hz) 201 = 16.7 Tons (50 Hz) 251 = 20.9 Tons (50 Hz)
DDIIGGIITT 77:: MMaajjoorr DDeevveellooppmmeenntt SSeeqquueennccee
D = Single Refrigeration Circuit E = Dual Refrigeration Circuit
DDIIGGIITT 88:: EElleeccttrriiccaall CChhaarraacctteerriissttiiccss
3 = 208–230/60/3 4 = 460/60/3 W = 575/60/3 D = 380-415/50/3 K = 380/60/3
DDIIGGIITTSS 99 -- 1100:: FFaaccttoorryy IInnssttaalllleedd OOppttiioonnss
00 = Packed Stock (Standard) 03 = 2-Speed Variable Frequency Drive (VFD) standard
motor (electromechanical condenser only) 04 = 2-Speed Variable Frequency Drive (VFD) oversized
motor (electromechanical condenser only) R3 = Single Zone Variable Air Volume (VFD) standard
motor - (ReliaTel condenser only) R4 = Single Zone Variable Air Volume (VFD) oversized motor - (ReliaTel condenser only)
DDIIGGIITTSS 1111:: MMiinnoorr DDeessiiggnn SSeeqquueennccee
* = Current Design Sequence
1
DDIIGGIITTSS 1122:: SSeerrvviiccee DDiiggiitt
* = Current Design Sequence
1
1.
* = sequential alpha character
SSA-SVX06E-EN
5

General Information

This manual describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
IImmppoorrttaanntt:: All phases of this installation must comply
with the NATIONAL, STATE & LOCAL CODES. In addition to local codes, the installation must conform with National Electric Code -ANSI/NFPA NO. 70 LATEST REVISION.
Any individual installing, maintaining, or servicing this equipment must be properly trained, licensed and qualified.
IImmppoorrttaanntt:: Do not remove the VFD without first
contacting technical support! For performance-related questions and diagnostic support in North America call 1­877-872-6363. Any return requires a claim number FIRST. Removal of the VFD prior to this step will void the unit’s warranties.
Installation procedures should be performed in the sequence that they appear in this manual. Do not destroy or remove the manual from the unit. The
manual should remain weather-protected with the unit until all installation procedures are complete.
NNoottee:: It is not the intention of this manual to cover all
possible variations in systems that may occur or to provide comprehensive information concerning every possible contingency that may be encountered during an installation. If additional information is required or if specific problems arise that are not fully discussed in this manual, contact your local sales office.
Use the installation checklist provided In this manual to verify that all necessary installation procedures have been completed. Do not use the checklist as a substitute for reading the information contained in the manual. Read the entire manual before beginning installation procedures.

Unit Description

These air handler models incorporate a single slab coil assembly, improved application flexibility, servicing, maintenance accessibility and an improved accessory line. They are fully convertible, (vertical to horizontal discharge) without field removal of the coil assembly. They are shipped ready for horizontal installation.
All units have one drain pan that can be installed in any one of four positions. This allows for vertical or horizontal applications and right or left exit.
IImmppoorrttaanntt:: All dual circuit (digit 7 = E) have an
intertwined coil, except for the 25 ton, TWE251 and TWE300 units.
6
SSA-SVX06E-EN

Pre-Installation

The final position for the air handler must be dictated by required service access to it, weight distribution over structural supports, and by the locations of electrical, refrigerant and condensate drainage connections. After this is determined, the following preparations should be made.

Unit Inspection

Inspect material carefully for any shipping damage. If damaged, it must be reported to, and claims made against the transportation company. Compare the information that appears on the unit nameplate with ordering and submittal data to ensure the proper unit was shipped. Available power supply must be compatible with electrical characteristics specified on component nameplates. Replace damaged parts with authorized parts only.

Inspection Checklist

To protect against loss due to damage incurred in transit, complete the following checklist upon receipt of the unit.
Inspect individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material.
Inspect the unit for concealed damage before it is stored and as soon as possible after delivery. Concealed damage must be reported within 15 days. If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location. Take photos of the damage if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Notify the sales representative and arrange for repair. Do not repair the unit until the damage is inspected by the carrier’s representative.

Testing for Leaks

All TWE units are shipped with a holding charge of nitrogen in each circuit and should be leak tested before installation.
1. Remove the access panel.
2. Locate the liquid line or suction line access valve for each circuit.
3. Install gauges to determine if the circuits are still pressurized. If not, the charge has escaped and should be repaired as required to obtain a leak-free circuit.

Lifting Recommendations

WWAARRNNIINNGG
IImmpprrooppeerr UUnniitt LLiifftt!!
TTeesstt lliifftt uunniitt aapppprrooxxiimmaatteellyy 2244 iinncchheess ttoo vveerriiffyy pprrooppeerr cceenntteerr ooff ggrraavviittyy lliifftt ppooiinntt.. TToo aavvooiidd ddrrooppppiinngg ooff uunniitt,, rreeppoossiittiioonn lliiffttiinngg ppooiinntt iiff uunniitt iiss nnoott lleevveell..
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
UUssee sspprreeaaddeerr bbaarrss ttoo pprreevveenntt ssttrraappss ffrroomm ddaammaaggiinngg tthhee uunniitt.. IInnssttaallll tthhee bbaarrss bbeettwweeeenn lliiffttiinngg ssttrraappss,, bbootthh uunnddeerrnneeaatthh tthhee uunniitt aanndd aabboovvee tthhee uunniitt ttoo pprreevveenntt tthhee ssttrraappss ffrroomm ccrruusshhiinngg tthhee uunniitt ccaabbiinneett oorr ddaammaaggiinngg tthhee ffiinniisshh..
Before preparing the unit for lifting, estimate the approximate center of gravity for lifting safety. Because of placement of internal components, the unit weight may be unevenly distributed. See “Weights,” p. 20 for approximate unit weights.
The crated unit can be moved using a forklift of suitable capacity. For lifting the unit into an elevated mounting position, run lifting straps or slings under the unit and attach securely to the lifting device.

Repositioning Drain Pan

Air handlers come with one drain pan that can be installed in any one of four positions; this allows for vertical or horizontal application and right or left condensate line connection.
NNoottee:: Important! All air handlers are shipped with the
drain pan installed in the horizontal position and the connection on the left side (as shown in
Figure 1, p. 8. If an alternate position is required,
the drain pan should be repositioned before setting the air handler.
1. Remove the access plate at the opposite end of the drain connection. This plate secures and lifts the back end of the drain pan for sloping. It must be removed before the drain pan can be removed. This is done as follows:
a. Remove the screw
b. Lift the access plate up
c. Pull the plate out. If the drain pan is to be moved
to the vertical position also remove the other two access plates.
2. Remove the screw securing the drain pan.
a. Lift the pan up
b. Slide the pan out
3. Install the drain pan into the new position.
SSA-SVX06E-EN
7
PPrree--IInnssttaallllaattiioonn
a. Slide the drain pan into the opening
b. Lift the drain pan up
c. Push it in all the way
d. Drop it down over the lip of the opening, secure
with screw
4. Install the access plate on the opposite end of the drain pain.
a. Slide the edge of the access plate under the
drain pan
b. Lift the access plate and drain pan up
c. Push the access plate in
d. Drop the access plate down over the lip of the
opening, secure with screw
NNoottee:: If the drain pan is being moved to the vertical
position, install the other access plates over the horizontal position opening
Figure 1. Drain pan location
Figure 2. Drain pan relocation
NNOOTTIICCEE
SSyysstteemm CCoommppoonneenntt DDaammaaggee!!
TThheessee aaiirr hhaannddlleerrss aarree sshhiippppeedd wwiitthh aa ddrryy nniittrrooggeenn hhoollddiinngg cchhaarrggee iinn tthhee ccooiill.. DDeepprreessss oorr rreemmoovvee tthhee aacccceessss vvaallvvee ccoonnee ttoo bblleeeedd ooffff tthhee nniittrrooggeenn pprriioorr ttoo bbrraazziinngg.. TTeemmppoorraarriillyy ccaapp ooffff ttuubbeess iiff tthhee rreeffrriiggeerraanntt lliinnee ccoonnnneeccttiioonnss aarree ttoo bbee mmaaddee llaatteerr..
8
SSA-SVX06E-EN
To cha nge voltage , pull plug, ro tate 18 0° a nd reins e rt
VIE W OF TERMI NAL EN D
GENERAL
ELECTRIC™
MARATHON™
HIGH LOW
HIGH LOW
To cha nge voltage , pull s e lect or plu g o ut, sh ift plug
to align arrow t o 460V for h igh voltage or 23 0V for low volta ge a s de sire d . Pus h p lug back in.
460V
ver
Conn e ct lines to L1, L2, L3
To revers e rota tion, intercha n ge a ny two lin e conn ect ions
PPrree--IInnssttaallllaattiioonn

Field Conversion to 460 Volt

WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss aanndd ddiisscchhaarrggee aallll mmoottoorr ssttaarrtt//rruunn ccaappaacciittoorrss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt// ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. FFoorr vvaarriiaabbllee ffrreeqquueennccyy ddrriivveess oorr ootthheerr eenneerrggyy ssttoorriinngg ccoommppoonneennttss pprroovviiddeedd bbyy TTrraannee oorr ootthheerrss,, rreeffeerr ttoo tthhee aapppprroopprriiaattee mmaannuuffaaccttuurreerr’’ss lliitteerraattuurree ffoorr aalllloowwaabbllee wwaaiittiinngg ppeerriiooddss ffoorr ddiisscchhaarrggee ooff ccaappaacciittoorrss.. VVeerriiffyy wwiitthh aann aapppprroopprriiaattee vvoollttmmeetteerr tthhaatt aallll ccaappaacciittoorrss hhaavvee ddiisscchhaarrggeedd..
FFoorr aaddddiittiioonnaall iinnffoorrmmaattiioonn rreeggaarrddiinngg tthhee ssaaffee ddiisscchhaarrggee ooff ccaappaacciittoorrss,, sseeee PPRROODD--SSVVBB0066AA--EENN..
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee eelleeccttrriiccaall ccooddeess..
Available power supply must agree with electrical data on component nameplate.
Some standard air handlers are shipped wired for 208-230 volt applications and can be converted for 460 volt by rewiring the blower motor. (This includes models TWE090D3, TWE090E3, TWE120D3, TWE120E3, TWE150E3 and TWE180E3).

Converting Motor to 460 Volt

1. Ensure power is disconnected to unit by following the warning above.
2. Remove unit access panels closest to motor.
3. Open terminal cover on lead end of motor.
4. Pull voltage selector plug from low voltage selection (see Figure 3, p. 9).
5. Shift the plug (or rotate 180°) to align plug for high voltage selection and re-insert plug.
IImmppoorrttaanntt:: When re-inserting voltage selection
plug, ensure it is fully seated.
6. Replace terminal cover on lead end of motor.
7. Replace unit access panels.
Figure 3. Voltage change plug

Refrigerant Piping

Reorienting Evaporator Coil (TWE126/ 150 and 156/180)

IImmppoorrttaanntt:: Applies to TWE126/150 and 156/180 when
positioned for vertical upflow. Unit is shipped in the horizontal position. If installing in the vveerrttiiccaall ppoossiittiioonn, the coil mmuusstt bbee reoriented by rotating the coil 4 degrees (control box side) from the shipped position.
1. Remove screws from top evaporator coil bracket (bracket that attaches coil to cabinet and runs the length of the unit).
2. Rotate evaporator coil approximately 4 degrees clockwise - looking from the control box end. When the evaporator coil is rotated, the lower set of evaporator coil bracket holes will align with the support bracket (from which it was originally fastened).
3. Reinsert screws in evaporator coil bracket.
SSA-SVX06E-EN
9
Top bracket screws
Rotate 4° clockwise
PPrree--IInnssttaallllaattiioonn
Figure 4. Evaporator coil reorientation for TWE126, 150, 156, 180

Preparation for Refrigerant Piping

NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
DDoo nnoott aappppllyy hheeaatt ttoo rreemmoovvee sseeaall ccaappss uunnttiill tthhee ggaauuggee ppoorrtt ccoorreess hhaavvee bbeeeenn rreemmoovveedd.. IIff sseeaall ccaappss aarree iinnttaacctt,, aapppplliiccaattiioonn ooff hheeaatt mmaayy ggeenneerraattee eexxcceessssiivvee pprreessssuurree iinn tthhee uunniitt aanndd rreessuulltt iinn ddaammaaggee ttoo tthhee ccooiill oorr eexxppaannssiioonn vvaallvvee..
The air handler is designed so that refrigerant piping can enter from either the right or left hand side. It is shipped with the intent that the refrigerant lines will enter from the left hand side. To convert to right hand entry, unbraze the elbow on the suction line and rotate 180° and rebraze.
IImmppoorrttaanntt:: Access to refrigerant lines is limited in all
horizontal and some vertical applications. Therefore, refrigerant lines should be stubbed out and temporarily capped prior to setting the air handler. Protect adjacent surfaces from heat damage when brazing in and around the air handler.

Installations, Limitations and Recommendations

NNOOTTIICCEE
SSyysstteemm CCoommppoonneenntt DDaammaaggee!!
PPrrooppeerrllyy iinnssuullaattee aallll rreeffrriiggeerraanntt ggaass ppiippiinngg ttoo pprreevveenntt ppoossssiibbllee wwaatteerr ddaammaaggee dduuee ttoo ccoonnddeennssaattiioonn aanndd ttoo pprreevveenntt ccaappaacciittyy lloossss aanndd ppoossssiibbllee ccoommpprreessssoorr ddaammaaggee..
The general location of the air handler is normally selected by the architect, contractor and/or buyer. For proper installation, the following items must be considered:
Available power supply must agree with electrical data on component nameplate.
If external accessories are installed on the unit, additional clearances must be provided.
All duct work should be properly insulated to prevent condensation and heat loss.
Refrigerant gas piping must be insulated.
It is recommended that the outline drawings in the Dimensional Data section be studied and dimensions properly noted and checked against the selected installation site. By noting in advance which features are to be used, proper clearance allowances can be made for installation and possible future service.
IImmppoorrttaanntt:: When installing these units “free standing”
with discharge grills and isolators, a top support with isolator should be added to prevent tipping. Support and isolator can be attached to a wall or other appropriate structure.
If adding external accessories to the unit, additional clearances must be considered for the overall space needed.
For installation of accessories available for this air handler, follow the installation instructions that are shipped with each accessory.
10
SSA-SVX06E-EN

Dimensional Data

H
D
W
Figure 5. Height, width and depth measurements
Model Number
TWE051, 061 48-1/8 (1222.4) 39-5/8 (1006.5) 23-5/8 (600.0)
TWE076, 090 54-1/8 (1374.8) 49-1/8 (1247.8) 26-1/2 (673.1)
TWE101, 120 54-1/8 (1374.8) 65-1/8 (1654.2) 26-1/2 (673.1)
TWE126, 150, 156, 180 69-1/8 (1756.0) 81-1/4 (2063.7) 30 (762.0)
TWE201, 240, 251, 300 71-7/8 (1806.6) 94-1/4 (2394.0) 32-1/8 (816.0)
Note: Full dimensional data is available on the following pages.
H - in. (mm) W - in. (mm) D - in. (mm)
SSA-SVX06E-EN
11
3" (76.2)
48 1/16" (1220. 8)
10 7/16"
(265. 1)
34 9/16"
(877. 9)
35 5/8"
(904. 9)
1 1/8"
(28.6)
12"
(304. 8)
13 9/16" (344.5)
20 1/16"
(509. 6)
1 11/16"
(42.9)
5 15/16"
(150. 8)
13 3/16" (335)
12"
(304.8)
13 9/16"
(344.5)
13 5/16" (338.14)
1 3/4"
(44.45)
2 3/4"
(69.9)
DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
32 1/2"
(825.5)
12 7/16"
(315.9)
1 3/8"
(34.9)
.99" (25.15)
.99" (25.15) 1 3/8" (34.9)
3 3/16" (81)
3 7/16" (87.3)
22 5/8"
(574.7)
22 5/8"
(574.7)
16 1/4"
(412.8)
.77"
(19.6)
.50" (12.7)
3 9/16"
(90.5)
7 9/16"
(192.1)
37 15/16"
(963.6)
24 1/16"
(611.2)
2 5/16"
(58.7)
6 7/8"
(174.6)
6 15/16" (176.2)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCES S P ANEL
NOTES :
1. P ANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCES S P LATE MUST BE RE-INSTALLED AFTER S LIDING DRAIN PAN BACK INTO UNIT.
3. IF P ERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUS PENSION
COP PER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION
LIQUID LINES
1 3/8" (34.9) O.D. SUCTION LINE
REMOTE BULB TXV
FILTER ACCES S PANEL 22" (558.8) MIN. DISTANCE BOTH SIDE
FILTER
SUP PLY OPENING
BOTTOM RETURN
SIDE RETURN
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
(4) - HOLE FOR HORIZONTAL SUS PENS ION
SIDE RETURN
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE
1" (25.4) HEIGHT
SUP PLY
OPEN
HEATER VENTILATION
HEATER CONTROL AND SINGLE POWER ENTRY WIRES
32 1/2" (825.5)
2 3/4" (69.9)
DDiimmeennssiioonnaall DDaattaa
Figure 6. 4.6, 5 ton air handler, single circuit
12
SSA-SVX06E-EN
Figure 7. 5 ton air handler, dual circuit
3" (76.2)
48 1/16"
(1220. 8)
10 7/16"
(265. 1)
34 9/16"
(877. 9)
35 5/8"
(904. 9)
1 1/8"
(28.6)
12"
(304. 8)
13 9/16"
(344. 5)
20 1/16"
(509. 6)
1 11/16"
(42.9)
5 15/16"
(150. 8)
13 3/16" (335)
16 1/8"
(409. 6)
17 5/16"
(439. 7)
17 7/8"
(454)
12"
(304.8)
13 9/16"
(344.5)
16 1/8"
(409.6)
17 5/16"
(439.7)
3 5/16"
(338.14)
1 3/4"
(44.45)
2 3/4"
(69.8)
32 1/2"
(825.5)
DRAIN CONNECTION FOR HORIZONTAL (SEE NOTE 2,3,5)
12 7/16"
(315. 9)
3 11/16" (93.7)
1 11/16" (42.9)
1 3/8" (34.9)
.99" (25.15)
.99" (25.15)
1 3/8" (34.9)
1 11/16" (42.9)
3 3/16" (81)
3 11/16" (93.7)
3 7/16" (87.3)
22 5/8"
(574. 7)
1 13/16"
(46.04)
22 5/8"
(574. 7)
16 1/4"
(412. 8)
.77" (19.6)
.50" (12.7)
3 9/16"
(90.5)
7 9/16"
(192. 1)
37 15/16"
(963. 6)
24 1/16"
(611. 2)
2 5/16"
(58.7)
6 7/8"
(174. 6)
6 15/16"
(176. 2)
BOTTOM RETURN
SIDE RETURN
DUCT FLANGE 1" (25.4) HEIGHT
SUP PLY
OPEN
CONTROL WIRING
LINE VOLTAGE
CONTROL BOX
ACCES S PANEL
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, P LASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER S LIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VE
RTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONF IGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
SUPPLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
(4) - HOLE FOR HORIZONTAL SUS PENSION
COP PER LIQUID LINE FIELD CONNECTION
COP PER SUCTION LINE FIELD CONNECTION
LIQUID LINES
(2) REMOTE BULB TXV
FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE
BOTH S IDE
SIDE RETURN
SIDE R ETURN
BOTTOM RETURN
BOTTOM RETURN
SUP PLY OPENING
FILTER
(4) HOLE FOR HORIZONTAL SUS PENSION
DRAIN CONNECTION
SUCTION LINE
COP PER LIQUID LINE FIELD CONNECTION
HEATER VENTILATION
HEATER CONTROL AND SINGLE P OWER ENTRY WIRES
32 1/2" (825.5)
2 3/4" (69.8)
DDiimmeennssiioonnaall DDaattaa
SSA-SVX06E-EN
13
16 7/8"
(428.6)
1 13/16"
(46)
2 3/4"
(69.85)
42"
(1066.8)
1 9/16"
(39.7)
16 1/16"
(408)
16"
(406. 4)
8 13/16" (223.8)
3 1/2" (88.9)
1 3/16" (30.2)
22 7/8"
(581)
45 1/8"
(1146. 2)
6 3/4"
(171. 45)
36 7/8"
(936. 6)
10 7/16"
(265. 1)
54 1/16"
(1373. 2)
1 3/16" (30.16)
16 11/16"
(423. 9)
17 7/16"
(442. 9)
20"
(508)
3 5/8" (92.1)
1 11/16" (42.9)
16 11/16"
(423.9)
17 3/8"
(441.3)
1 9/16" (39.7)
3 1/2" (88.9)
25 1/2"
(647. 7)
16 1/4"
(412. 8)
.70"
(17.8)
25 1/2"
(647. 7)
24 1/16"
(611. 2)
11 11/16"
(296. 8)
47 1/2"
(1206. 5)
8 5/16"
(211. 1)
12 5/16"
(312. 7)
2 1/4" (57.15)
6 13/16"
(173)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCESS PANEL
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCES S PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC P IPE DRAIN CONNECTION VE
RTICAL CONFIGURATION.
5. 1" (25.4) FEMALE S CHED. 40 (10.2) P VC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUSPENSION
COP PER LIQUID LINE FIELD CONNECTION
COPPER SUCTION LINE FIELD CONNECTION
LIQUID LINES
SUCTION LINE
REMOTE BULB TXV
FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
FILTER
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
(4) HOLE FOR HORIZONTAL SUS PENSION
SIDE RETURN
BOTTOM RETURN
SIDE RETURN
SUP PLY OPENING
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE 1" (25.4)
HEIGHT
SUP PLY
OPEN
HEATER VENTILATION
HEATER CONTROL AND SINGLE P OWER ENTRY WIRES
42"
(1066.8)
2 3/4"
(69.85)
DDiimmeennssiioonnaall DDaattaa
Figure 8. 6.25, 7.5 ton air handler, single circuit
14
SSA-SVX06E-EN
Figure 9. 6.25, 7.5 ton air handler, dual circuit
16 7/8"
(406.4)
1 13/16"
(46)
2 3/4"
(69.9)
42"
(1066.8)
1 9/16"
(39.7)
16 1/16"
(408)
20 1/16"
(509.6)
16 3/4"
(425.5)
16 1/4"
(412.8)
13 3/4"
(349.3)
3 5/8" (92.1)
1 5/8" (41.3)
1 5/16" (33.3)
11 1/16"
(281)
13 3/4"
(349. 2)
16 1/4"
(412. 8)
16 3/4"
(425. 5)
19 1/16"
(484. 2)
20 1/16"
(509.6)
3 5/8" (92.1)
1 5/8" (41.3)
1 5/16" (33.3)
16"
(406. 4)
8 13/16" (223.8)
3 1/2" (88.9)
1 3/16" (30.2)
22 7/8"
(581)
45 1/8"
(1146. 2)
6 3/4"
(171. 5)
36 7/8"
(936. 6)
10 7/16"
(265. 1)
54 1/16"
(1373. 2)
1 3/16" (30.2)
25 1/2"
(647. 7)
16 1/4"
(412. 8)
.70"
(17.78)
25 1/2"
(647. 7)
24 1/16"
(611. 2)
11 11/16"
(296. 9)
47 1/2"
(1206. 5)
8 5/16"
(211. 1)
12 5/16"
(312. 7)
2 1/4" (57.15)
6 13/16" (173)
BOTTOM RETURN
SIDE RETURN
CONTROL WIRING
LINE VOLTAGE
CONTROL BOX
ACCES S PANEL
NOTES :
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO SLIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUS PENSION
COP PER LIQUID LINE FIELD CONNECTION
COP PER SUCTION LINE
FIELD CONNECTION
LIQUID LINES
SUCTION LINE
(2) REMOTE BULB TXV
FILTER ACCESS PANEL 22" (559) MIN. DISTANCE BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
FILTER
SUP PLY OPENING
BOTTOM RETURN
SIDE RETURN
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
(4) HOLE FOR HORIZONTAL SUS PENSION
SIDE RETURN
DUCT FLANGE 1" (25.4)
HEIGHT
SUP PLY
OPEN
HEATER
VENTILATION
HEATER CONTROL
AND SINGLE P OWER
ENTRY WIRES
42"
(1066.8)
2 3/4"
(69.9)
DDiimmeennssiioonnaall DDaattaa
SSA-SVX06E-EN
15
3 1/2" (89)
8 7/8"
(225. 4)
16 1/16"
(408)
1 3/16"
(30.2)
22 7/8"
(581)
61 1/8"
(1552. 6)
6 3/4"
(171. 45)
36 7/8"
(936. 63)
10 7/16" (265.1)
54 1/16"
(1373. 2)
58"
(1473.2)
2 3/4"
(69.8)
1 13/16"
(46)
16 7/8"
(428.6)
15 15/16"
(404. 8)
1 11/16"
(42.9)
16 11/16"
(423. 9)
17 3/8"
(441. 4)
20"
(508)
1 11/16" (42.9)
3 5/8" (92.1)
16 11/16"
(423.9)
17 3/8"
(441.3)
1 11/16" (42.9)
3 5/8" (92.1)
63 1/2"
(1613)
1 3/16" (30.2)
16 1/4"
(412. 8)
.70" (17.8)
25 1/2"
(647. 7)
19 11/16"
(500. 1)
24 1/16"
(611. 2)
63 1/2"
(1612. 9)
20 5/16"
(515. 9)
16 5/16"
(414. 3)
2 1/4" (57.2)
6 13/16" (173)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCES S PANEL
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER S LIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) P VC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC P IPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
COP PER LIQUID LINE FIELD CONNECTION
COP PER SUCTION LINE FIELD CONNECTION
LIQUID LINES
SUCTION LINE
REMOTE BULB TXV
FILTER ACCESS PANEL 22" (559) MIN. DISTANCE BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUPPLY OP ENING
SIDE RETURN
(4) - HOLE FOR HORIZONTAL SUS PENSION
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE
1" (25.4) HEIGHT
SUP PLY
OPEN
HEATER VENTILATION
HEATER CONTROL
AND SINGLE P OWER
ENTRY WIRES
25 1/2" (647. 7)
58"
(1473.2)
2 3/4" (69.8)
BOTTOM RETURN
SIDE RETURN
(4) HOLE FOR HORIZONTAL SUS PENSION
FILTER
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
DDiimmeennssiioonnaall DDaattaa
Figure 10. 8.33, 10 ton air handler, single circuit
16
SSA-SVX06E-EN
3 1/2" (89)
8 7/8"
(225. 4)
16 1/16"
(408)
1 3/16"
(30.2)
22 7/8"
(581)
61 1/8"
(1552. 6)
6 3/4"
(171. 45)
36 7/8"
(936. 6)
10 7/16" (265.1)
54 1/16"
(1373. 2)
11" (279.4)
13 11/16"
(347. 7)
16 1/4"
(412. 8)
16 11/16"
(423. 9)
19"
(482.6)
20"
(508)
1 5/16" (33.4)
1 5/8" (41.3)
3 5/8" (92.1)
3 5/8" (92.1)
1 5/8" (41.3)
1 5/16" (33.3)
13 3/4"
(349.3)
16 1/4"
(412.8)
16 3/4"
(425.5)
20 1/16"
(509.6)
58"
(1473.2)
2 3/4"
(69.8)
1 13/16"
(46)
16 7/8"
(428.6)
15 15/16"
(404. 8)
1 11/16"
(42.9)
1 3/16"
(30.2)
25 1/2"
(647. 7)
16 1/4"
(412. 7)
.70" (17.8)
25 1/2"
(647. 7)
19 11/16"
(500. 1)
24 1/16"
(611. 2)
63 1/2"
(1613)
20 5/16"
(515. 9)
16 5/16"
(414. 3)
2 1/4" (57.15)
6 13/16" (173)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCES S PANEL
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER S LIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) P VC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUS PENSION
COP PER LIQUID LINE FIELD CONNECTION
COP PER SUCTION LINE FIELD CONNECTION
SUCTION LINE
(2) REMOTE BULB TXV
FILTER ACCESS PANEL 22" (558.8) MIN. DISTANCE
BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
LIQUID LINES
FILTER
BOTTOM RETURN
SIDE RETURN
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
SIDE RETURN
SUP PLY OPENING
(4) HOLE FOR HORIZONTAL SUS PENSION
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE 1" (25.4)
HEIGHT
SUP PLY
OPEN
HEATER
VENTILATION
HEATER CONTROL
AND SINGLE P OWER
ENTRY WIRES
58"
(1473.2)
2 3/4" (69.8)
Figure 11. 8.33, 10 ton air handler, dual circuit
DDiimmeennssiioonnaall DDaattaa
SSA-SVX06E-EN
17
19 1/2"
(495.3)
74 1/8"
(1882.8)
3 7/16" (87.3)
2 3/4"
(69.8)
17 7/8"
(454)
3 5/16" (84.1)
4 1/4" (108)
20"
(508)
12 13/16" (325.4)
22"
(558.8)
21 1/2"
(546. 1)
18 11/16"
(474. 7)
18 5/16"
(465. 1)
15 13/16"
(401. 6)
12" (304.8)
21 1/2"
(546.1)
1 5/16" (33.3)
2 1/8" (54)
2 7/16" (62)
4 1/4" (108)
25 1/8"
(638. 2)
18 11/16"
(474.6)
18 3/8"
(466.7)
15 13/16"
(401.64)
4 1/8" (104.8)
2 5/16" (58.7)
2" (50.8)
9 5/8"
(244. 5)
48"
(1219. 2)
11 7/16" (290.5)
1 3/16"
(30.2)
69 1/16"
(1754. 2)
79 5/8"
(2022. 5)
1 1/4"
(31.8)
77 3/16"
(1960. 6)
29 1/16"
(738. 2)
2 7/8" (73)
16 5/16"
(414. 3)
29 1/16"
(738. 2)
4 5/16" (109.5)
12 1/8"
(308)
79 9/16"
(2020. 9)
54 15/16"
(1395. 4)
12 3/8" (314.3)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCES S PANEL
NOTES:
1. PANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOS ITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT FOR CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER SLIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED. 40 (10.2) P VC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED. 40 (10.2) PVC P IPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUS PENSION
COPPER LIQUID LINE FIELD CONNECTION
COP PER SUCTION LINE FIELD CONNECTION
LIQUID LINES
SUCTION LINE
(2) REMOTE BULB TXV
FILTER ACCESS PANEL 22" (559) MIN.
DISTANCE
BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
SIDE RETURN
BOTTOM RETURN
FILTER
SUP PLY OPENING
BOTTOM RETURN
SIDE RETURN
BOTTOM RETURN
SUP PLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
(4) HOLE FOR HORIZONTAL SUS PENSION
SIDE RETURN
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE 1" (25.4)
HEIGHT
SUP PLY
OPEN
HEATER CONTROL
AND SINGLE P OWER
ENTRY WIRES
74 1/8"
(1882.8)
2 3/4" (69.8)
SUP PLY
OPEN
DDiimmeennssiioonnaall DDaattaa
Figure 12. 10.4, 13, 12.5, 15 ton air handler, dual circuit
18
SSA-SVX06E-EN
20 15/16"
(531.8)
2 15/16"
(74.6)
4 3/4"
(120.6)
83 1/8"
(2111.4)
3"
(76.2)
20 15/16"
(531.8)
20" (508)
12 13/16"
(325. 4)
25 1/2"
(647.7)
21 13/16"
(554)
21 3/8"
(542. 9)
19 1/8"
(485. 8)
18 3/8"
(466.7)
15 7/8"
(403. 2)
12 7/8"
(327)
25 1/2"
(647.7)
11 7/16"
(290.5)
50 13/16"
(1290.6)
9 5/8"
(244.5)
71 7/8"
(1825.6)
1 11/16"
(42.9)
89 3/16"
(2265.4)
92 9/16"
(2351.1)
4" (101.6)
3 3/8" (85.7)
1 15/16" (49.2)
1 11/16" (42.9)
3 7/8" (98.4)
3 1/4" (82.5)
1 7/8" (47.6)
1 9/16" (39.7)
28 1/2"
(724)
1 3/16"
(30.2)
31 1/8"
(790.6)
4 1/4" (108)
16 5/16"
(414.3)
31 1/8"
(790.6)
4 15/16" (125.4)
92 9/16"
(2351.1)
18 5/8"
(473.1)
6 7/16" (163.5)
18 7/8"
(479.4)
54 15/16"
(1395.4)
BOTTOM RETURN
SIDE RETURN
CONTROL BOX
ACCESS PANEL
NOTES :
1. P ANEL DEPTH 1/2" (12.7) (TYP. ALL PANELS).
2. REMOVABLE DRAIN PAN AND ATTACHED DRAIN CONNECTION MAY BE INSTALLED ON END OF UNIT IN EITHER THE VERTICAL OR HORIZONTAL CONFIGURATION, PLASTIC DRAIN PAN ACCESS PLATE ON THE END OF UNIT OPPOSITE DRAIN CONNECTION MUST BE REMOVED TO S LIDE DRAIN PAN OUT OF UNIT CLEANING. ACCESS PLATE MUST BE RE-INSTALLED AFTER S LIDING DRAIN PAN BACK INTO UNIT.
3. IF PERIODIC DRAIN PAN CLEANING IS REQUIRED, ALLOW ROOM FOR PARTIAL REMOVAL OF DRAIN PAN CONNECTION AT END OF UNIT.
4. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION VERTICAL CONFIGURATION.
5. 1" (25.4) FEMALE SCHED .40 (10.2) PVC PIPE DRAIN CONNECTION HORIZONTAL CONFIGURATION.
SEE NOTES 2,3,4
SEE NOTES 2,3,4
(4) - HOLE FOR HORIZONTAL SUS PENSION
COP PER LIQUID LINE
FIELD CONNECTION
COP PER SUCTION LINE FIELD CONNECTION
SUCTION LINE
REMOTE BULB TXV
FILTER ACCESS PANEL 22" (559) MIN. DISTANCE BOTH S IDE
DRAIN CONNECTION
FOR HORIZONTAL
(SEE NOTE 2,3,5)
SIDE RETURN
BOTTOM RETURN
LIQUID LINES
(4) HOLE FOR HORIZONTAL SUS PENSION
SUP PLY HORIZONTAL - RETURN VERTICAL / RETURN HORIZONTAL
SUPPLY VERTICAL - RETURN HORIZONTAL / RETURN VERTICAL
BOTTOM RETURN
SIDE RETURN
FILTER
SUP PLY OPENING
BOTTOM RETURN
SIDE RETURN
CONTROL WIRING
LINE VOLTAGE
DUCT FLANGE 1" (25.4)
HEIGHT
SUP PLY OPEN
HEATER CONTROL AND SINGLE P OWER ENTRY WIRES
21 13/16"
(554)
19 1/8" (485.8)
18 3/8" (466.7)
15 7/8"
(403.2)
83 1/8"
(2111.4)
4 3/4"
(120.6)
Figure 13. 16.7, 20.9, 20, 25 ton air handler, dual circuit
DDiimmeennssiioonnaall DDaattaa
SSA-SVX06E-EN
19

Weights

T
op View
Control Box Access

Air Handler

Table 1. Standard air handler (TWE) — unit and corner weights - (60 Hz)
Tons
7.5
12.5 TWE150E 730 676 168 192 181 135 196 164 145 171
Model
Number
TWE061D/E
5
TWE090D/E
TWE120D/E
10
15 TWE180E 729 675 167 192 181 135 196 163 145 171
20 TWE240E 891 818 258 168 161 231 256 181 146 235
25 TWE300E 972 899 211 229 184 275 272 176 228 223
Shipping
Max (lbs)
263 232 55 71 51 55 54 67 50 61
360 323 67 99 75 82 56 92 87 88
429 393 77 121 110 85 79 118 77 119
Net Max
(lbs)
Table 2. SZVAV and 2-Speed VFD air handler (TWE) — unit and corner weights - (60 Hz)
Tons
7.5 TWE090E 360 323 67 99 75 82 56 92 87 88
12.5 TWE150E 730 676 168 192 181 135 196 164 145 171
Model
Number
TWE120D/E
10
15 TWE180E 729 675 167 192 181 135 196 163 145 171
20 TWE240E 891 818 258 168 161 231 256 181 146 235
25 TWE300E 972 899 211 229 184 275 272 176 228 223
Shipping
Max (lbs)
429 393 77 121 110 85 79 118 77 119
Net Max
(lbs)
Corner Weights - Vertical Corner Weights - Horizontal
1 2 3 4 1 2 3 4
Corner Weights - Vertical Corner Weights - Horizontal
1 2 3 4 1 2 3 4
Table 3. Standard air handler (TWE) — unit and corner weights - (50 Hz)
Tons
4.6 TWE051D 263 232 55 71 51 55 54 67 50 61
6.25
8.33
10.4 TWE126E 730 676 168 192 181 135 196 164 145 171
16.7 TWE201E 891 818 258 168 161 231 256 181 146 235
20.9 TWE251E 972 899 211 229 184 275 272 176 228 223
Model
Number
TWE076D/E
TWE101D/E
13 TWE156E 729 675 167 192 181 135 196 163 145 171
Shipping
Max (lbs)
360 323 67 99 75 82 56 92 87 88
429 393 77 121 110 85 79 118 77 119
Net Max
(lbs)
Corner Weights - Vertical Corner Weights - Horizontal
1 2 3 4 1 2 3 4
Figure 14. Vertical — TWE051, 076, 101, 061, 090, 120
20
SSA-SVX06E-EN
Figure 15. Vertical — TWE126, 156, 201, 251, 150, 180, 240, 300
op View
Control Box Access
Top View
Control Box Access
Top View
Control Box Access
Figure 16. Horizontal — TWE051, 076, 101, 061, 090, 120
WWeeiigghhttss
Figure 17. Horizontal — TWE126, 156, 201, 251, 150, 180, 240, 300
SSA-SVX06E-EN
21

Installation

Horizontal Suspension

If the air handler will be suspended, use a suspension mounting kit to isolate the unit from the structure. This is usually accomplished with spring or rubber isolators, which are offered as an accessory.
Mounting rods must be field supplied. Isolator selection is dependent upon total unit weight including accessories — see “Weights,” p. 20 for approximate unit weights.
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
BBeeffoorree hhaannggiinngg tthhee uunniitt oonn ssuussppeennssiioonn rrooddss,, rreeiinnffoorrccee tthhee ccaabbiinneett aarroouunndd tthhee ssuussppeennssiioonn hhoolleess bbyy uussiinngg aa llaarrggee wwaasshheerr iinnssiiddee tthhee ccaabbiinneett.. WWaasshheerrss sshhoouulldd bbee bbeettwweeeenn tthhee sskkiinn ooff tthhee aaiirr hhaannddlleerr aanndd tthhee nnuutt oonn tthhee ssuussppeennssiioonn rroodd..
Align holes in the cabinet with structural supports and secure suspension rods to the structure, then to the air handler cabinet. If hole locations do not permit proper alignment with existing structure, it may be necessary to field fabricate cross members on existing structural beams.
NNoottee:: When other than bottom return is to be used,
side panel removal for return duct installation must be secured over the bottom opening.

Leveling

This air handler has a double sloped drain pan. In order to assure proper drainage along the length of the drain pan, it is important to have the unit properly leveled. Be sure the air handler is level.

Auxiliary Drain Pan

A field fabricated, auxiliary drain pan should be installed under the unit for all horizontal applications and when air handlers are installed above ceilings or in other locations where condensate overflow may cause damage.
This drain pan will eliminate any excess condensation that may be due to extreme humidity or an obstructed drain in the primary drain pan. Drain lines from this pan must be installed, but should not be connected to the primary drain line from the unit. Isolate the auxiliary drain pan from both the air handler and the structure.
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
EEnnssuurree tthhaatt tthhee rreeffrriiggeerraanntt lliinneess ppaassssiinngg tthhrroouugghh tthhee ccaabbiinneett aarree nnoott rreessttiinngg oonn sshhaarrpp sshheeeett mmeettaall eeddggeess aanndd tthhaatt tthhee bbuullbb((ss)) aarree aattttaacchheedd ttoo tthhee ssuuccttiioonn lliinnee ooff tthhee ssaammee cciirrccuuiitt..
1. Locate cloth bag(s) attached to the refrigerant tube of the coil that contains a stainless steel clamp and insulation material (approximately 9” long by 4” wide) for each refrigerant circuit. This is for attaching and insulating the expansion valve bulb(s) to the suction line(s).
2. Attach the expansion valve bulb(s)
oonn aaiirr hhaannddlleerrss tthhaatt wwiillll hhaavvee rreeffrriiggeerraanntt lliinneess eenntteerriinngg tthhee ccaabbiinneett ffrroomm tthhee lleefftt ssiiddee::
a. Remove the split rubber grommet from the
knockout in the end of the air handler. Uncoil the cap tube with the bulb attached at the expansion valve and place the grommet on the cap tube.
b. With the grommet around the tube, push the
bulb through the hole and position the grommet back into its original position (one bulb and cap tube on single circuit units, and two bulbs and cap tubes on dual circuit units).
oonn aaiirr hhaannddlleerrss tthhaatt wwiillll hhaavvee rreeffrriiggeerraanntt lliinneess eenntteerriinngg tthhee ccaabbiinneett ffrroomm tthhee rriigghhtt ssiiddee::
a. Attach the bulb(s) to the suction tube(s) inside
the cabinet, approximately 10” from the right end of the unit.
3. Attach the bulb(s) on a horizontal section of tube where the entire length of the bulb is in contact with the tube (see Figure 18, p. 23), approximately 45 degrees off vertical (a 10 or 2 o’clock position).
4. After attaching to the suction line(s), either inside or outside of the cabinet, wrap the insulation around the bulb(s) and suction tube(s).
NNoottee:: Suction piping should be insulated.

Refrigerant Piping

Installation, brazing, leak testing and evacuation of refrigerant lines are covered in the installation instructions that shipped with the outdoor unit. Read the instructions before beginning installation of refrigerant lines.
22
SSA-SVX06E-EN
Between
10 and 2 OClock
Bulb Retaining Clip
Insulating
Tape
V
ENT
DRAIN
CLEAN OUT
Materials 2 each - TEE 2 each - 90° ELL 1 each - PLUG 2 each - 6 NIPPLE 2 each - 2 NIPPLE 1 each - 1 NPT to PVC or COPPER ADAPTER
IInnssttaallllaattiioonn
WWAARRNNIINNGG
FFiibbeerrggllaassss WWooooll!!
YYoouu MMUUSSTTwweeaarr aallll nneecceessssaarryy PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) iinncclluuddiinngg gglloovveess,, eeyyee pprrootteeccttiioonn,, aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr,, lloonngg sslleeeevveess aanndd ppaannttss wwhheenn wwoorrkkiinngg wwiitthh pprroodduuccttss ccoonnttaaiinniinngg ffiibbeerrggllaassss wwooooll..
PPrreeccaauuttiioonnaarryy MMeeaassuurreess::
•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt..
•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr..
•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg--sslleeeevveedd,, lloooossee--ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyee pprrootteeccttiioonn..
•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg;; rriinnssee wwaasshheerr tthhoorroouugghhllyy..
•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr-­oouutt,, aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnss rreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUssee tthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr..
FFiirrsstt AAiidd MMeeaassuurreess::
•• EEyyee CCoonnttaacctt -- FFlluusshh eeyyeess wwiitthh wwaatteerr ttoo rreemmoovvee dduusstt.. IIff ssyymmppttoommss ppeerrssiisstt,, sseeeekk mmeeddiiccaall aatttteennttiioonn..
•• SSkkiinn CCoonnttaacctt -- WWaasshh aaffffeecctteedd aarreeaass ggeennttllyy wwiitthh ssooaapp aanndd wwaarrmm wwaatteerr aafftteerr hhaannddlliinngg..
Figure 18. Remote bulb installation
NNoottee:: When air handler is installed in the vertical
position and close proximity trapping of condensate is required, use of a subbase accessory to raise the air handler for clearance of the drain trap is recommended. See Figure 19, p.
23 for a typical drain trap assembly.
Figure 19. Typical drain trap assembly

Filter Replacement

WWAARRNNIINNGG
FFiibbeerrggllaassss WWooooll!!
YYoouu MMUUSSTT wweeaarr aallll nneecceessssaarryy PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) iinncclluuddiinngg gglloovveess,, eeyyee pprrootteeccttiioonn,, aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr,, lloonngg sslleeeevveess aanndd ppaannttss wwhheenn wwoorrkkiinngg wwiitthh pprroodduuccttss ccoonnttaaiinniinngg ffiibbeerrggllaassss wwooooll..
PPrreeccaauuttiioonnaarryy MMeeaassuurreess::
•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt..
•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr..
•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg--sslleeeevveedd,, lloooossee--ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyee pprrootteeccttiioonn..
•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg;; rriinnssee wwaasshheerr tthhoorroouugghhllyy..
•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr-­oouutt,, aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnss rreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUssee tthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr..

Condensate Piping

The drain pan condensate connection is a female slip joint type for 1” Schedule 40 PVC pipe. Use PVC cement and tubing as required (field supplied) to construct a trap. A union or flexible tubing and clamps may be installed if the drain pan is to be removed periodically for cleaning.
SSA-SVX06E-EN
FFiirrsstt AAiidd MMeeaassuurreess::
•• EEyyee CCoonnttaacctt -- FFlluusshh eeyyeess wwiitthh wwaatteerr ttoo rreemmoovvee dduusstt.. IIff ssyymmppttoommss ppeerrssiisstt,, sseeeekk mmeeddiiccaall aatttteennttiioonn..
•• SSkkiinn CCoonnttaacctt -- WWaasshh aaffffeecctteedd aarreeaass ggeennttllyy wwiitthh ssooaapp aanndd wwaarrmm wwaatteerr aafftteerr hhaannddlliinngg..
Air handlers are shipped with throwaway filters installed. For replacement filters consult the air handler service facts for correct size and number.
23
Filter Frame
IInnssttaallllaattiioonn
To replace filters from the end of the unit, remove lower access panel (either end) and slide old filters out and replace with new ones.
To replace from the front of the unit, remove one “L” shaped angle. Remove and replace filters and reinstall “L” shaped angle. See Figure 20, p. 24.
To convert from 1” filter to a 2” filter on units so equipped, remove lower access panels from both ends of the air handler. Remove screws and rotate the “L” shaped angles from both the top and bottom of the filter track 180° to increase the width of the filter opening.
Figure 20. Filter location

SZVAV Units

For SZVAV units, air flow is set by using potentiometer R-136 on the ReliaTel options module found in the air handler control box, see Figure 21, p. 24. The potentiometer will adjust the maximum air flow between the range of 60 Hz to 44.50 Hz. If the desired maximum operating point from the catalog fan table is lower than 44.50 Hz, parameter 6-15 on the VFD must be reprogrammed to 50 Hz. The VFD is preset from the factory to a default of 25 Hz for the lower limit and does not need to be reprogrammed.
Figure 21. ReliaTel options module

Duct Connections

The supply and return ducts should be connected to the unit with flame retardant duct connectors to reduce vibration transmission. The return duct should be sized to the same dimensions as the return inlet of the unit.
IImmppoorrttaanntt:: Duct flanges are provided for attachment of
the duct work and are packaged on the outside of the cabinet for TWE150, 180, 240, 300 and TWE126, 156, 201, 251. The duct flanges are fastened to the pallet below the coil (bottom return) on the TWE051, 061, 076, 090, 101 and 120 models.

Air Flow Settings

Standard Units

Unit is shipped for nominal airflow with nominal static pressure. Please refer to the fan performance table in either the product catalog or unit service facts and select the proper drive package for each application. Failure to do so could result in improper airflow causing coil frosting or condensate management problems. Condensate management problems such as water blow off could be the result of too great of air face velocity across the coil. To ensure proper operation refer to “Fan Belt Adjustment,” p. 44.
Measure the voltage between TP1 on the RTOM and ground. Use Table 4, p. 24 to set the desired maximum operating supply fan speed.
Table 4. SZVAV air handler speed to voltage
Parameter 6-15 Set to 60 Hz
TP1
High Speed
(Hz)
38.00 <0.10 44.00 1.65
38.40 0.20 44.40 1.70
38.80 0.30 44.80 1.75
39.20 0.45 45.20 1.83
39.60 0.55 45.60 1.90
40.00 0.70 46.00 1.95
40.40 0.80 46.40 2.00
40.80 0.95 46.80 2.05
41.20 1.05 47.20 2.10
41.60 1.15 47.60 2.13
42.00 1.25 48.00 2.17
42.40 1.30 48.40 2.21
(RTOM) Voltage
(Vdc)
High Speed
(Hz)
TP1 (RTOM) Voltage
(Vdc)
24
SSA-SVX06E-EN
IInnssttaallllaattiioonn
Table 4. SZVAV air handler speed to voltage (continued)
Parameter 6-15 Set to 60 Hz
TP1
High Speed
(Hz)
42.80 1.35 48.80 2.27
43.20 1.45 49.20 2.30
43.60 1.55 49.60 2.35
50.00 >2.40
44.50 <0.10 52.25 1.65
45.02 0.20 52.77 1.70
45.53 0.30 53.28 1.75
46.05 0.45 53.80 1.83
46.57 0.55 54.32 1.90
47.08 0.70 54.83 1.95
47.60 0.80 55.35 2.00
48.12 0.95 55.87 2.05
48.63 1.05 56.38 2.10
49.15 1.15 56.90 2.13
49.67 1.25 57.42 2.17
50.18 1.30 57.93 2.21
50.70 1.35 58.45 2.27
51.22 1.45 58.97 2.30
51.73 1.55 59.48 2.35
60.00 >2.40
(RTOM) Voltage
(Vdc)
High Speed
(Hz)
TP1 (RTOM) Voltage
(Vdc)

2-Speed VFD Units

To configure units with an RTOM for 2-speed operation move plug PPM 10 from PPF 10 to TP. Refer to “Heating
and Cooling Setpoint Arbitration,” p. 27 for setpoint
connection. Complete the configuration by reprogramming VFD parameter 6-10 to 5.00 V and parameter 6-11 to 7.60 V. For 2-Speed VFD controlled units the desired maximum air flow (High Speed) is set by reprogramming parameter 6-15 on the VFD to the frequency value that best meets the RPM requirement as shown in the catalog fan tables.
The minimum air flow (Low Speed) is set by reprogramming parameter 6-14 on the VFD. Refer to
Table 5, p. 25 to see the allowed Low Speed range for a
given High Speed. Use the Menu button and up and down arrows on the keypad to access the parameters.
Table 5. 2-Speed VFD programming speeds
High
Speed
(Hz)
60.00 25.00 - 39.60 48.00 25 - 31.68
59.00 25.00 - 38.94 47.00 25 - 31.02
58.00 25.00 - 38.28 46.00 25 - 30.36
57.00 25.00 - 37.62 45.00 25 - 29.70
56.00 25.00 - 36.96 44.00 25 - 29.04
55.00 25.00 - 36.30 43.00 25 - 28.38
54.00 25.00 - 35.64 42.00 25 - 27.72
53.00 25.00 - 34.98 41.00 25 - 27.06
52.00 25.00 - 34.32 40.00 25 - 26.40
51.00 25.00 - 33.66 39.00 25 - 25.74
50.00 25.00 - 33.00 38.00 25 - 25.08
49.00 25.00 - 32.34
Low Speed
(Hz)
Ranges
High Speed
(Hz)
Low Speed
(Hz)
Ranges

Minimum Supply Fan Output

Refer to Table 6, p. 25 for details on minimum supply fan output signals associated with each unit function. Note that each value represents the actual Fan Output % based on 100% being the customers selected maximum operating speed.
Table 6. Minimum supply fan speeds for SZVAV units
VFD Parameter 6-15 Set to 60 Hz
Minimum
Function
Ventilation Only
Cool 1 (C1 or C2)
Cool 2 (C1 + C2 Energized)
CV Staged Heat
VFD Parameter 6-15 Set to 50 Hz
Function
Ventilation Only
Cool 1 (C1 or C2)
Cool 2 (C1 + C2 Energized)
CV Staged Heat
Table 7. Minimum supply fan speeds for 2-Speed units
Fan Output %
58%
58%
80%
100%
Minimum
Fan Output %
64%
64%
83%
100%
SSA-SVX06E-EN
Function
Ventilation Only
Cool 1 (C1)
Fan Output %
42 - 66%
42 - 66%
(a)
(a)
25
Heater Control Single Point Power
Line Voltage Entrance
Control Wiring
IInnssttaallllaattiioonn
Table 7. Minimum supply fan speeds for 2-Speed units (continued)
Function
Cool 2 (C1 + C2 Energized)
CV Staged Heat
(a)
Fan Output percentage is based on the customer chosen upper and lower speed settings.
Fan Output %
100%
100%
IImmppoorrttaanntt:: Do not remove the VFD without first
contacting technical support! For performance-related questions and diagnostic support in North America call 1­877-872-6363. Any return requires a claim number FIRST. Removal of the VFD prior to this step will void the unit warranty.

Electrical Connections

WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss aanndd ddiisscchhaarrggee aallll mmoottoorr ssttaarrtt//rruunn ccaappaacciittoorrss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt// ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. FFoorr vvaarriiaabbllee ffrreeqquueennccyy ddrriivveess oorr ootthheerr eenneerrggyy ssttoorriinngg ccoommppoonneennttss pprroovviiddeedd bbyy TTrraannee oorr ootthheerrss,, rreeffeerr ttoo tthhee aapppprroopprriiaattee mmaannuuffaaccttuurreerr’’ss lliitteerraattuurree ffoorr aalllloowwaabbllee wwaaiittiinngg ppeerriiooddss ffoorr ddiisscchhaarrggee ooff ccaappaacciittoorrss.. VVeerriiffyy wwiitthh aann aapppprroopprriiaattee vvoollttmmeetteerr tthhaatt aallll ccaappaacciittoorrss hhaavvee ddiisscchhaarrggeedd..
FFoorr aaddddiittiioonnaall iinnffoorrmmaattiioonn rreeggaarrddiinngg tthhee ssaaffee ddiisscchhaarrggee ooff ccaappaacciittoorrss,, sseeee PPRROODD--SSVVBB0066AA--EENN..
3. Ensure all connections are tight and no wires exposed.
4. All accessories must be installed and wired according to the instructions packaged with that accessory.
For air handler power entry only, or for dual power entry (power entry for air handler and power entry for electric heats), the electrical connections are made in the fan control box located in the right side of the air handler and electric heater respectively. Wiring entrance is through holes provided in the end of the air handler cabinet, Figure 22, p. 26. Breaker or fuse size can be selected using the nameplates attached to the unit and electric heater.
Figure 22. Electrical entries
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee eelleeccttrriiccaall ccooddeess..
1. All electrical lines, sizing, protection, and grounding must be in accordance with the National Electric Code and local codes.
2. Isolate conduit whenever vibration transmission
26
may cause a noise problem within the building structure.
Table 8. Recommended thermostat wire size
Wire Size
(Gauge) Physical distance between Unit & T’stat
22 30 Feet
20 50 Feet
18 75 Feet
16 125 Feet
14 200 Feet
Maximum Wire Length

Setpoints

SSA-SVX06E-EN
IInnssttaallllaattiioonn

EDC Switch Wiring

EElleeccttrroommeecchhaanniiccaall UUnniittss: To enable the Evaporator Defrost Control Switch remove the "W3" jumper between LTB1-B1 and LTB1-B2 at the Outdoor Condenser Section.
RReelliiaaTTeell UUnniittss: To enable the Evaporator Defrost Control Switch move wire "W11" from LTB2-B2 to LTB2­R, and move wire "W12" from LTB2-B1 to LTB2-CD at the Indoor Air Handler Section.
NNoottee:: Refer to wiring schematics for more detail.

Heating and Cooling Setpoint Arbitration

Figure 23. Discharge air cooling setpoint
Single Zone VAV units will require traditional Zone Heating (if Heat installed) and Cooling Setpoints that are used on constant volume units in addition to two new setpoints: Discharge Air Cool (Externally Mounted Potentiometer in Control Box) and Discharge Air Heat (DA Heat R-42) Setpoint limits. The Zone Heating and Cooling Setpoints will be selectable via the existing RTRM customer connections for a Zone Sensor panel and the DA Heat and Cool Setpoints will be customer selectable via an onboard potentiometer on the RTOM, and an off board potentiometer mounted inside the control box with ranges 50-150°F and 40-90°F respectively.
The setpoint tables should be used as a reference when setting the DA Heat (R–42) and Discharge Air Cool (Control Box Mounted Potentiometer) setpoints. Note that the recommended settings for these setpoints are 100°F for the DA Heat Setpoint, and 50°F for the DA Cool Setpoint.
Table 9. DA heat setpoint
Voltage
(Vdc)
0.00 50 0.98 75 1.61 100 2.06 125
0.09 51 1.00 76 1.63 101 2.08 126
0.13 52 1.03 77 1.66 102 2.09 127
0.16 53 1.06 78 1.69 103 2.11 128
0.20 54 1.08 79 1.71 104 2.12 129
0.24 55 1.11 80 1.72 105 2.13 130
0.28 56 1.13 81 1.74 106 2.13 131
0.31 57 1.16 82 1.76 107 2.14 132
0.35 58 1.18 83 1.78 108 2.16 133
0.39 59 1.21 84 1.79 109 2.17 134
0.42 60 1.23 85 1.81 110 2.19 135
0.46 61 1.26 86 1.83 111 2.20 136
0.50 62 1.28 87 1.84 112 2.21 137
0.53 63 1.31 88 1.86 113 2.23 138
0.57 64 1.33 89 1.88 114 2.24 139
0.61 65 1.36 90 1.89 115 2.25 140
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
SSA-SVX06E-EN
27
IInnssttaallllaattiioonn
Table 9. DA heat setpoint (continued)
Voltage
(Vdc)
0.65 66 1.38 91 1.91 116 2.26 141
0.68 67 1.41 92 1.93 117 2.28 142
0.72 68 1.43 93 1.95 118 2.29 143
0.76 69 1.46 94 1.96 119 2.30 144
0.79 70 1.48 95 1.98 120 2.32 145
0.83 71 1.51 96 2.00 121 2.33 146
0.87 72 1.53 97 2.01 122 2.34 147
0.90 73 1.56 98 2.03 123 2.36 148
0.94 74 1.58 99 2.05 124 2.37 149
2.40 150
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Table 10. DA cool setpoint (mounted above keyboard)
Setpoint (°F) Voltage (Vdc) Setpoint (°F) Voltage (Vdc) Setpoint (°F) Voltage (Vdc)
40 <0.10 51 1.30 61 2.00
41 0.20 52 1.35 62 2.05
42 0.30 53 1.45 63 2.10
43 0.45 54 1.55 64 2.13
44 0.55 55 1.65 65 2.17
45 0.70 56 1.70 66 2.21
46 0.80 57 1.75 67 2.27
47 0.95 58 1.83 68 2.30
48 1.05 59 1.90 69 2.35
49 1.15 60 1.95 70 >2.40
50 1.25
Note: The potentiometer voltage readings can be verified via the provided test points located next to each potentiometer. Use a DC voltmeter to the Vdc reading between those points and common.

Checkout Procedure

Complete the “Installation Checklist,” p. 28 once installation of field wiring connections is complete. All operational checks (unit running) must be made after the outdoor unit is installed and system interconnection is complete.

Installation Checklist

WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd..
Complete this checklist once the unit is installed to
28
verify that all recommended procedures have been accomplished before the system is started. Operational checks cannot be performed until the outdoor unit is installed and system interconnection is complete.
Verify that the unit electrical power is disconnected.
Inspect all field wiring connections. All connections should be clean and tight.
Inspect unit ground connection(s). Ground must comply with all applicable codes.
Inspect unit suspension arrangement (if used). Unit position must be secure. Remove any tools or debris found in or near the unit.
Inspect duct outlets. Outlets must be open and unrestricted.
Inspect unit drain lines. Pipe connections must be tight and drain line unrestricted.
SSA-SVX06E-EN
RTRMJ-4
RTOMJ-1
FieldInstalled Wires
Tstat
Air Handler
Disconnect S witch
(By Others)
Disconnect S witch
(By Others) Note 2
Electric
Heat Accessory
Disconnect S witch
(By Others)
B
A
B
D
C
IInnssttaallllaattiioonn
Inspect fan assembly to insure all moving parts
move freely.
If unit is horizontally mounted, make sure
secondary drain pan has been installed.
Inspect unit for proper filters, securely installed and
not touching the coil surface. All cabinet panels must be secure.
Instruct owner/operator on proper system
operating and maintenance procedure.

Thermostat and Control Connections

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer-supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.
1. Observe all notes on the wiring diagrams.
2. Mount the thermostat or zone sensor in the desired
location.
3. Install color coded low voltage cables between
outdoor unit, indoor unit and thermostat. For SZVAV units, install low voltage and communication wires between the RTRM in the condenser and the RTOM in the air handler. See schematic and connection print for more detail.
4. Connect low voltage control wiring to the low
voltage terminal board located at the control box per the typical interconnecting wiring diagrams. For SZVAV units, connect the ReliaTel harness (supplied with the air handler), between the RTRM and RTOM. See Figure 24, p. 29.
Figure 24. RTOM to RTRM harness
Figure 25. Electromechanical jobsite connections
A.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
C.
Cooling only thermostat: 3 to 7 wires depending on stages of electric heat
D.
3 to 7 wires depending on type of outdoor unit(s)

ReliaTel Controls

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.
NNootteess::
1. When electric heater accessory is used, single point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.
2. ***Choose only one of the following; Thermostat, Zone Sensor, or NSB Panel.

Electromechanical Controls

Wiring shown with dashed lines is to be furnished and installed by the customer. All customer supplied wiring must be copper only and must conform to NEC and local electrical codes. Codes may require line of sight between disconnect switch and unit.
NNoottee:: When electric heater accessory is used, single
point power entry or dual point power entry is field optional. Single point power entry option is through electric heater only.
SSA-SVX06E-EN
29
NSB P anel
Zone
Sensor
Tstat
Air Handler
Disconnect S witch
(By Others)
Disconnect S witch
(By Others) Note 2
Electric
Heat Accessory
Disconnect S witch
(By Others)
Note 2
B
A
B
D
F
EC
IInnssttaallllaattiioonn
Figure 26. ReliaTel jobsite connections
A.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for single phase)
C.
Cooling only thermostat: 3 to 7 wires depending on stages of electric heat
C.
Heat Pump thermostat: 5 to 8 wires depending on stages of electric heat
D.
3 to 7 wires depending on type of outdoor unit(s)
E. Zone Sensor: 4 to 10 wires depending on zone sensor model
F.
Night Setback Panel: 7 wires
(a)
For SZVAV air handlers: 4 additional wires are required (2 of which require twisted pair or shielded wire) in order to make connections between ReliaTel boards in the condenser and air handler.
(a)
30
SSA-SVX06E-EN

Electrical Data

60 Hz Models

Includes Standard, SZVAV and 2–Speed VFD air handlers.
Table 11. Voltage operating range (all air handlers)
Model Number:
Digit 8
1
3
4
K
W
Electrical
Characteristics
208-230/60/1
208-230/60/3
460/60/3
380/60/3
575/60/3
Table 12. Electrical characteristics — standard and low static motors — 60 Hz standard air handler
Standard Evaporator Fan Motor Low Static Evaporator Fan Motor
No. Volts Phase
1 208 1 0.75 6.0 41.0 7.5 15
1 230 1 0.75 5.9 45.0 7.4 15
1 208 3 0.75 2.5 16.4 3.1 15
1 230 3 0.75 2.4 16.4 3.0 15
1 460 3 0.75 1.2 8.2 1.5 15
1 208 1 1.5 6.8 31.5 8.5 20
1 230 1 1.5 6.2 31.5 7.8 15
1 208 3 1.5 5.3 34.3 6.6 15
1 230 3 1.5 5.0 34.3 6.3 15
1 380 3 1.5 3.0 20.2 3.8 15
1 460 3 1.5 2.5 17.0 3.1 15
1 575 3 1.5 1.8 13.6 2.3 15
1 208 1 2 8.5 57.4 10.6 20
1 230 1 2 7.7 57.4 9.6 20
1 208 3 2 7.0 33.9 7.8 15
1 230 3 2 6.6 33.9 7.3 15
1 380 3 2 3.3 28.0 4.1 15
1 460 3 2 3.3 19.0 3.6 15
1 575 3 2 2.3 15.6 4.0 15
1 460 3 2 2.8 23.0 3.4 15
1 460 3 3 4.6 39.3 5.8 15
Hp
FLA LRA FLA LRA
Tons
Model Number
5
7.5
TWE090DW, EW
10
TWE120D3, E3
TWE120DW, EW
12.5
15
Unit
TWE061D1, E1
TWE061D1, E1
TWE061D3, E3
TWE061D3, E3
TWE061D4, E4
TWE061DW 1 575 3 0.75 1.3 6.1 1.6 15
TWE090D1, E1
TWE090D1, E1
TWE090D3, E3
TWE090D3, E3
TWE090DK, EK
TWE090D3, E3
TWE120D1, E1
TWE120D1, E1
TWE120D3, E3
TWE120D3, E3
TWE120DK, EK
(a)
TWE150E3 1 208 3 2 6.0 23.0 7.4 15
TWE150E3 1 230 3 2 5.5 23.0 6.9 15
TWE150EK 1 380 3 2 3.3 28.0 4.1 15
TWE150E3
TWE150EW 1 575 3 2 2.2 18.0 2.8 15
TWE180E3 1 208 3 3 9.4 74.9 11.8 20
TWE180E3 1 230 3 3 9.2 74.9 11.5 20
TWE180EK 1 380 3 5 8.1 63.5 10.1 15
TWE180E3
TWE180EW 1 575 3 3 3.4 24.6 4.3 15
(a)
(a)
Unit Operating Voltage Range
Amps
187-253
187-253
414-506
342-418
518-632
MCA MFS No. Volts Phase
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Hp
Amps
MCA MFS
SSA-SVX06E-EN
31
EElleeccttrriiccaall DDaattaa
Table 12. Electrical characteristics — standard and low static motors — 60 Hz standard air handler (continued)
Tons
20
25
Note: For additional information contact product support.
(a)
Field wired for 460V.
Unit
Model Number
TWE240E3 1 208 3 5 14.0 90.8 17.5 30 1 208 3 3 9.4 74.9 11.8 25
TWE240E3 1 230 3 5 13.6 103.0 17.0 30 1 230 3 3 9.2 74.9 11.5 25
TWE240EK 1 380 3 5 8.1 63.5 10.1 15
TWE240E4 1 460 3 5 6.6 44.8 9.0 15 1 460 3 3 4.6 39.3 5.8 15
TWE240EW 1 575 3 5 5.3 36.2 6.6 15 1 575 3 3 3.4 24.6 4.3 15
TWE300E3 1 208 3 7.5 19.6 150.0 25.0 40 1 208 3 7.5 19.6 150 25 40
TWE300E3 1 230 3 7.5 17.8 150.0 25.0 40 1 230 3 7.5 17.8 150 25 40
TWE300EK 1 380 3 7.5 10.9 72.9 13.6 20
TWE300E4 1 460 3 7.5 8.9 75.0 12.0 20 1 460 3 7.5 8.9 75 12 20
TWE300EW 1 575 3 7.5 7.1 60.0 9.0 15 1 575 3 7.5 7.1 60 9 15
Table 13. Electrical characteristics — high and ultra-high static motors — 60 Hz standard air handler
Tons
5
7.5
10
12.5
15
20
Unit
Model Number
TWE061D1, E1
TWE061D1, E1
TWE061D3, E3
TWE061D3, E3
TWE061D4, E4
TWE061DW 1 575 3 1.5 1.8 13.6 2.3 15
TWE090D1, E1
TWE090D1, E1
TWE090D3, E3
TWE090D3, E3
TWE090D3, E3
TWE090DW, EW
TWE120D1, E1
TWE120D1, E1
TWE120D3, E3
TWE120D3, E3
TWE120D3, E3
TWE120DW, EW
TWE150E3 1 208 3 3 9.4 74.9 11.8 25 1 208 3 5 14 98 17.5 35
TWE150E3 1 230 3 3 9.2 74.9 11.5 25 1 230 3 5 13.6 103 17 35
TWE150E3
TWE150EW 1 575 3 3 3.4 24.6 4.3 15 1 575 3 5 5.2 36.2 6.5 15
TWE180E3 1 208 3 5 14 98 17.5 30
TWE180E3 1 230 3 5 13.6 103 17 30
TWE180E3
TWE180EW 1 575 3 5 5.2 36.2 6.5 15
TWE240E3
TWE240E3
TWE240E4
TWE240EW
(a)
(a)
(a)
(a)
Standard Evaporator Fan Motor Low Static Evaporator Fan Motor
No. Volts Phase
Hp
Amps
FLA LRA FLA LRA
MCA MFS No. Volts Phase
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Hp
Amps
MCA MFS
High Static Evaporator Fan Motor Ultra-High Static Evaporator Fan Motor
No.
Volts Phase
1 208 1 1.5 6.8 31.5 8.5 20
1 230 1 1.5 6.2 31.5 7.8 15
1 208 3 1.5 5.3 34.3 6.6 15
1 230 3 1.5 5 34.3 6.3 15
1 460 3 1.5 2.5 17 3.1 15
1 208 1 2 8.5 57.4 10.6 20
1 230 1 2 7.7 57.4 9.6 20
1 208 3 2 7 33.9 7.8 15 1 208 3 3 9.4 74.9 11.8 25
1 230 3 2 6.6 33.9 7.3 15 1 230 3 3 9.2 74.9 11.5 25
1 460 3 2 3.3 19 3.6 15 1 460 3 3 4.6 39.3 5.8 15
1 575 3 2 2.3 15.6 4 15 1 575 3 3 3.4 24.6 4.3 15
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
1 208 3 3 9.4 74.9 11.8 25
1 230 3 3 9.2 74.9 11.5 25
1 460 3 3 4.6 39.3 5.8 15
1 575 3 3 3.4 24.6 4.3 15
1 460 3 3 4.6 39.3 5.8 15 1 460 3 5 6.6 44.8 8.3 20
1 460 3 5 6.6 44.8 8.3 15
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Hp
Amps
FLA LRA FLA LRA
MCA MFS No.
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
1 208 3 7.5 19.6 114 25 45
1 230 3 7.5 17.6 126 22 40
1 460 3 7.5 9 61.4 11.3 25
1 575 3 7.5 7.2 49.8 9 20
Volts Phase
Hp
Amps
MCA MFS
32
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 13. Electrical characteristics — high and ultra-high static motors — 60 Hz standard air handler (continued)
Tons
25
Note: For additional information contact product support.
(a)
Field wired for 460V.
Unit
Model Number
TWE300E3 1 208 3 7.5 19.6 150 25 40
TWE300E3 1 230 3 7.5 17.8 150 25 40
TWE300E4 1 460 3 7.5 8.9 75 12 20
TWE300EW 1 575 3 7.5 7.1 60 9 15
Table 14. Electrical characteristics — standard and oversized motors — 60 Hz SZVAV and 2-Speed VFD air handler
Tons
7.5
10
12.5
15
20
25
Notes:
1. For additional information contact product support.
2. Not available with 380/60 Hz models.
Unit
Model Number
TWE090E4 1 208 3 2 6.2 43.4 8 15 1 208 3 3 9.4 71 12 20
TWE090E3 1 230 3 2 5.8 48 8 15 1 230 3 3 9.2 64 12 20
TWE090E4 1 460 3 2 2.9 24 4 15 1 460 3 3 4.6 35.5 6 15
TWE090E4 1 575 3 2 2.2 20.6 3 15 1 575 3 3 3.7 28.4 5 15
TWE120D3, E3
TWE120D3, E3
TWE120D4, E4
TWE120DW, EW
TWE150E3 1 208 3 2 6.2 43.4 8 15 1 208 3 5 13.4 99.5 17 30
TWE150E3 1 230 3 2 5.8 48 8 15 1 230 3 5 12.6 110 17 30
TWE150E4 1 460 3 2 2.9 24 4 15 1 460 3 5 6.3 55 8 15
TWE150EW 1 575 3 2 2.2 20.6 3 15 1 575 3 5 5.1 44 7 15
TWE180E3 1 208 3 3 9.4 71 12 20 1 208 3 5 13.4 99.5 17 30
TWE180E3 1 230 3 3 9.2 64 12 20 1 230 3 5 12.6 110 17 30
TWE180E4 1 460 3 3 4.6 35.5 6 15 1 460 3 5 6.3 55 8 15
TWE180EW 1 575 3 3 3.7 28.4 5 15 1 575 3 5 5.1 44 7 15
TWE240E3 1 208 3 5 13.4 99.5 17 30 1 208 3 7.5 19.6 113.4 25 45
TWE240E3 1 230 3 5 12.6 110 17 30 1 230 3 7.5 17.6 124 25 45
TWE240E4 1 460 3 5 6.3 55 8 15 1 460 3 7.5 8.8 63 11 15
TWE240EW 1 575 3 5 5.1 44 7 15 1 575 3 7.5 7.1 50.4 9 15
TWE300E3 1 208 3 7.5 19.6 113.4 25 45
TWE300E3 1 230 3 7.5 17.6 124 25 45
TWE300E4 1 460 3 7.5 8.8 63 12 20
TWE300EW 1 575 3 7.5 7.1 50.4 9 15
High Static Evaporator Fan Motor Ultra-High Static Evaporator Fan Motor
No. Volts Phase
Hp
Amps
FLA LRA FLA LRA
MCA MFS No. Volts Phase
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Hp
Amps
MCA MFS
Standard Evaporator Fan Motor High Static Evaporator Fan Motor
No. Volts Phase
1 208 3 2 6.2 43.4 8 15 1 208 3 3 9.4 71 12 20
1 230 3 2 5.8 48 8 15 1 230 3 3 9.2 64 12 20
1 460 3 2 2.9 24 4 15 1 460 3 3 4.6 35.5 6 15
1 575 3 2 2.2 20.6 3 15 1 575 3 3 3.7 28.4 5 15
Hp
Amps
FLA LRA FLA LRA
MCA MFS No. Volts Phase
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A N/A
Hp
Amps
MCA MFS
SSA-SVX06E-EN
33
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz
Tons
Used With
TWE061D1,
5
TWE061E1
TWE061D3,
5
TWE061E3
TWE061D4,
5
TWE061E4
5 TWE061DW
TWE090D1,
7.5 TWE090E1
TWE090D3,
7.5 TWE090E3
TWE090D3,
7.5
TWE090E3
TWE090DW,
7.5
TWE090EW
TWE120D1,
10
TWE120E1
TWE120D3,
10
TWE120E3
Heater Model
Number
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
Heater kW
Rating
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
BAYHTRL405* 5.00
BAYHTRL410* 9.96 1 17.0 20.0
BAYHTRL415* 14.96 1 25.0 25.0
Unit Power
Supply
208-230/1/60
208-230/3/60
460/3/60
Control
Stages
Minimum Circuit
Ampacity
1
1
1
2
1
1
1
2
33.5/37.4 35.0/40.0
59.5/67.4 60.0/70.0
85.5/97.4 90.0/100.0
111.5/127.4
16.1/18.0 20.0/20.0
29.0/33.0 30.0/35.0
42.2/48.0 45.0/50.0
68.0/77.9
1 10.0 15.0
BAYHTRL425* 24.92 2 40.0 40.0
BAYHTRLW05* 5.00
BAYHTRLW10* 9.96 1 15.0 15.0
BAYHTRLW15* 14.96 1 21.0 20.0
575/3/60
1 8.0 15.0
BAYHTRLW25* 24.92 2 33.0 35.0
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL129*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
21.63/28.80
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
BAYHTRL405* 5.00
208-230/1/60
208-230/3/60
1
1
1
2
2
1
1
1
2
2
1 11.0 15.0
34.5/37.8 40.0/40.0
60.5/67.8
86.5/97.8 90.0/100.0
112.5/127.8
138.6/157.8
19.6/21.3 25.0/25.0
32.5/36.2 35.0/40.0
45.7/51.2 50.0/60.0
71.5/82.0
98.7/112
BAYHTRL410* 9.96 1 19.0 20.0
BAYHTRL415* 14.96 1 26.0 30.0
(c)
460/3/60
BAYHTRL425* 24.92 2 41.0 45.0
BAYHTRL435* 34.88 2 56.0 60.0
BAYHTRLW05* 5.00
1 11.0 15.0
BAYHTRLW10* 9.96 1 17.0 15.0
BAYHTRLW15* 14.96 1 23.0 25.0
575/3/60
BAYHTRLW25* 24.92 2 36.0 35.0
BAYHTRLW35* 34.88 2 48.0 45.0
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL129*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
21.63/28.80
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
208-230/1/60
208-230/3/60
1
1
1
2
2
1
1
1
2
2
36.6/39.6 40.0/45.0
62.6/69.6
88.6/99.6 90.0/100.0
114.6/129.6
140.7/159.6
21.0/23.0 25.0/30.0
34.0/38.0 35.0/40.0
47.0/53.0 50.0/60.0
73.0/83.0
98.7/113.0
Maximum Fuse
or HACR Circuit
(a)
(a)
(a)
(a)
(a)
(a)
(b)
(a)
(a)
(a)
(a)
(b)
Breaker Size
125.0/150.0
70.0/80.0
70.0/70.0
125.0/150.0
150.0/175.0
80.0/90.0
100.0/125.0
70.0/70.0
125.0/150.0
150.0/175.0
80.0/90.0
100.0/125.0
34
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz (continued)
Tons Used With
TWE120D3
10
TWE120E3
TWE120DW,
10
TWE120EW
12.5 TWE150E3
TWE150E3
12.5
12.5 TWE150EW
15 TWE180E3
TWE180E3
15
15 TWE180EW
20 TWE240E3
20 TWE240E4
20 TWE240EW
Heater Model
Number
BAYHTRL405* 5.00
BAYHTRL410* 9.96 1 20.0 20.0
(c)
,
BAYHTRL415* 14.96 1 27.0 30.0
(c)
BAYHTRL425* 24.92 2 42.0 45.0
BAYHTRL435* 34.88 2 57.0 60.0
BAYHTRLW05* 5.00
BAYHTRLW10* 9.96 1 16.0 15.0
BAYHTRLW15* 14.96 1 22.0 25.0
BAYHTRLW25* 24.92 2 35.0 35.0
BAYHTRLW35* 34.88 2 47.0 45.0
BAYHTRM310A
BAYHTRM320A
BAYHTRM330A
BAYHTRM350A
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 34.0 35.0
(c)
BAYHTRM430* 29.92 2 49.0 50.0
BAYHTRM450* 49.84 2 79.0 80.0
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 27.0 30.0
BAYHTRMW30* 29.92 2 39.0 40.0
BAYHTRMW50* 49.84 2 63.0 70.0
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM42* 19.92 1 36.0 40.0
(c)
BAYHTRM430* 29.92 2 51.0 60.0
BAYHTRM450* 49.84 2 81.0 90.0
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 30.0 30.0
BAYHTRMW30* 29.92 2 42.0 45.0
BAYHTRMW50* 49.84 2 67.0 70.0
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 39.0 40.0
BAYHTRM430* 29.92 2 54.0 60.0
BAYHTRM450* 49.84 2 84.0 90.0
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 32.0 35.0
BAYHTRMW30* 29.92 2 45.0 45.0
BAYHTRMW50* 49.84 2 70.0 70.0
Heater kW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
Control
Stages
Minimum Circuit
Ampacity
1 12.0 15.0
1 10.0 15.0
1
1
2
2
1 19.0 20.0
1 15.0 15.0
1
1
2
2
1 21.0 25.0
1 17.0 20.0
1
1
2
2
1 24.0 30.0
1 20.0 25.0
33.5/36.9 35/40
59.3/66.8 60/70
85.5/96.8 90/100
137.3/156.7 150/175
37.8/41.6 45.0/45.0
63.7/71.4 70.0/80.0
89.8/101.5 90.0/110.0
141.6/161.4
44.1/49.0 60.0/60.0
71.0/79.0 80.0/90.0
97.0/109.0 100.0/110.0
149.0/169.0
Maximum Fuse
or HACR Circuit
Breaker Size
(b)
(b)
150.0/175.0
150.0/175.0
SSA-SVX06E-EN
35
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz (continued)
Tons Used With
25 TWE300E3
25 TWE300E4
25 TWE300EW
Notes:
1. kW ratings are at: 208/240V for 208-230V air handlers; 480V for 460V air handlers; 600V for 575V air handlers. For other than rated voltage, capacity = (voltage/rated voltage)
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Electric heat not available with 380/60 Hz models.
4. The HACR circuit breaker is for U.S.A. installations only.
(a)
Field wire must be rated at least 75°C.
(b)
Field wire must be rated at least 90°C.
(c)
With motor field wired for 460V.
Heater Model
Number
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 42.0 45.0
BAYHTRM430* 29.92 2 57.0 60.0
BAYHTRM450* 49.84 2 87.0 90.0
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 34.0 35.0
BAYHTRMW30* 29.92 2 47.0 50.0
BAYHTRMW50* 49.84 2 72.0 80.0
Heater kW
Rating
7.51/10
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
208-230/3/60
460/3/60
575/3/60
2
x rated capacity.
Control
Stages
Minimum Circuit
Ampacity
1
1
2
2
1 27.0 30.0
1 22.0 25.0
51.0/53.0 60.0/90.0
77.0/83.0 85.0/90.0
103.0/113.0 110.0/125.0
155.0/173.0 175.0/175.0
Maximum Fuse
or HACR Circuit
Breaker Size
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —
60 Hz
Tons Used With
7.5 TWE090E3*3
7.5 TWE090E4*4
7.5 TWE090EW*3
TWE120D3*3, E3*3
10
Heater Model
Number
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
BAYHTRL305* 5.00
BAYHTRL310* 9.96 1 19 20
BAYHTRL315* 14.96 1 27 30
BAYHTRL325* 24.92 2 42 45
BAYHTRL335* 34.88 2 57 60
BAYHTRLW05* 5.00
BAYHTRLW10* 9.96 1 16 20
BAYHTRLW15* 14.96 1 22 25
BAYHTRLW25* 24.92 2 34 35
BAYHTRLW35* 34.88 2 47 50
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
Heater KW
Rating
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
Unit Power
Supply
208-230/3/60
460/3/60
575/3/60
208-230/3/60
Control
Stages
1
1
1
2
2
1 12 15
1 9 15
1
1
1
2
2
Minimum
Circuit
Ampacity
21/23 25/25
34/38 35/40
47/53 50/60
73/83 80/90
99/113 100/125
21/23 25/25
34/38 35/40
47/53 50/60
73/83 80/90
99/113 100/125
Maximum Fuse or
HACR Circuit Breaker Size
36
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers — 60 Hz (continued)
Tons Used With
TWE120D3*4, E3*4
10
TWE120D4*3, E4*3
10
TWE120D4*4, E4*4
10
TWE120DW*3, EW*3
10
TWE120DW*4, EW*4
10
12.5 TWE150E3*3
12.5 TWE150E3*4
12.5 TWE150E4*3
12.5 TWE150E4*4
12.5 TWE150EW*3
Heater Model
Number
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
BAYHTRL405* 5.00
BAYHTRL410* 9.96 1 19 20
BAYHTRL415* 14.96 1 27 30
BAYHTRL425* 24.92 2 42 45
BAYHTRL435* 34.88 2 57 60
BAYHTRL405* 5.00
BAYHTRL410* 9.96 1 21 25
BAYHTRL415* 14.96 1 29 30
BAYHTRL425* 24.92 2 44 45
BAYHTRL435* 34.88 2 59 60
BAYHTRLW05* 5.00
BAYHTRLW10* 9.96 1 16 20
BAYHTRLW15* 14.96 1 22 25
BAYHTRLW25* 24.92 2 34 35
BAYHTRLW35* 34.88 2 47 50
BAYHTRLW05* 5.00
BAYHTRLW10* 9.96 1 18 20
BAYHTRLW15* 14.96 1 24 25
BAYHTRLW25* 24.92 2 36 40
BAYHTRLW35* 34.88 2 49 50
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 34 35
BAYHTRM430* 29.92 2 49 50
BAYHTRM450* 49.84 2 79 80
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 38 40
BAYHTRM430* 29.92 2 53 60
BAYHTRM450* 49.84 2 83 90
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 28 30
BAYHTRMW30* 29.92 2 41 45
BAYHTRMW50* 49.84 2 66 70
Heater KW
Rating
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
Control
Stages
1
1
1
2
2
1 12 15
1 14 15
1 9 15
1 11 15
1
1
2
2
1
1
2
2
1 19 20
1 23 25
1 16 20
Minimum
Circuit
Ampacity
25/27 30/30
38/42 40/45
38/57 40/60
77/87 80/90
103/117 110/125
34/38 35/40
60/68 60/70
86/98 90/100
138/158 150/175
43/47 45/50
69/77 70/80
95/107 100/110
147/167 150/175
Maximum Fuse or
HACR Circuit Breaker Size
SSA-SVX06E-EN
37
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers — 60 Hz (continued)
Tons Used With
12.5 TWE150EW*4
15 TWE180E3*3
15 TWE180E3*4
15 TWE180E4*3
15 TWE180E4*4
15 TWE180EW*3
15 TWE180EW*4
20 TWE240E3*3
20 TWE240E3*4
20 TWE240E4*3
20 TWE240E4*4
Heater Model
Number
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 32 35
BAYHTRMW30* 29.92 2 44 45
BAYHTRMW50* 49.84 2 69 70
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 36 40
BAYHTRM430* 29.92 2 51 60
BAYHTRM450* 49.84 2 81 90
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 38 40
BAYHTRM430* 29.92 2 53 60
BAYHTRM450* 49.84 2 83 90
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 30 30
BAYHTRMW30* 29.92 2 43 45
BAYHTRMW50* 49.84 2 68 70
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 32 35
BAYHTRMW30* 29.92 2 44 45
BAYHTRMW50* 49.84 2 69 70
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 38 40
BAYHTRM430* 29.92 2 53 60
BAYHTRM450* 49.84 2 83 90
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 41 45
BAYHTRM430* 29.92 2 56 60
BAYHTRM450* 49.84 2 86 90
Heater KW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
Control
Stages
1 19 20
1
1
2
2
1
1
2
2
1 21 25
1 23 25
1 18 20
1 19 20
1
1
2
2
1
1
2
2
1 23 25
1 26 30
Minimum
Circuit
Ampacity
38/42 40/45
64/72 70/80
90/102 90/110
142/162 150/175
43/47 45/50
69/77 70/80
95/107 100/110
147/167 150/175
43/47 45/50
69/77 70/80
95/107 100/110
147/167 150/175
51/55 60/60
77/85 80/90
103/115 110/125
155/175 175/175
Maximum Fuse or
HACR Circuit Breaker Size
38
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers — 60 Hz (continued)
Tons Used With
20 TWE240EW*3
20 TWE240EW*4
25 TWE300E3*3
25 TWE300E4*3
25 TWE300EW*3
Notes:
1. kW ratings are at: 208/240V for 208-230V air handlers; 480V for 460V air handlers; 600V for 575V air handlers. For other than rated voltage, capacity = (voltage/rated voltage)
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Electric heat not available with 380/60 Hz models.
4. The HACR circuit breaker is for U.S.A. installations only.
Heater Model
Number
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 32 35
BAYHTRMW30* 29.92 2 44 45
BAYHTRMW50* 49.84 2 69 70
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 34 35
BAYHTRMW30* 29.92 2 47 50
BAYHTRMW50* 49.84 2 72 80
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410* 10.00
BAYHTRM420* 19.92 1 41 45
BAYHTRM430* 29.92 2 56 60
BAYHTRM450* 49.84 2 86 90
BAYHTRMW10* 10.00
BAYHTRMW20* 19.92 1 34 35
BAYHTRMW30* 29.92 2 47 50
BAYHTRMW50* 49.84 2 72 80
Heater KW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
2
x rated capacity.
Unit Power
Supply
575/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
Control
Stages
1 19 20
1 22 25
1
1
2
2
1 26 30
1 22 25
Minimum
Circuit
Ampacity
51/55 60/60
77/85 80/90
103/115 110/125
155/175 175/175
Maximum Fuse or
HACR Circuit Breaker Size
SSA-SVX06E-EN
39
EElleeccttrriiccaall DDaattaa

50 Hz Models

Includes standard air handlers
Table 17. Electrical characteristics — standard motor — 50 Hz air handler
Standard Evaporator Fan Motor
Tons Unit Model Number
4.6 TWE051DD
6.25
8.33
10.4 TWE126ED
13 TWE156ED
16.7 TWE201ED
20.9 TWE251ED
TWE076DD, ED
TWE101DD, ED
No. Volts Phase
1 380 3 1.4 8.0
1 415 3 1.0 8.4
1 380 3 3.1 17.0
1 415 3 3.2 16.8
1 380 3 3.4 17.3
1 415 3 3.2 19.0
1 380 3 3.2 35.0
1 415 3 3.1 35.0
1 380 3 4.0 33.1
1 415 3 4.0 36.1
1 380 3 8.0 43.2
1 415 3 8.0 48.6
1 380 3 7.5 71.0
1 415 3 7.2 77.0
Amps
FLA LRA
Table 18. Unit wiring — air handler — 50 Hz
Tons
4.6 TWE051DD
6.25
8.33
10.4 TWE126ED
13 TWE156ED
16.7 TWE201ED
20.9 TWE251ED
Unit Model
Number
TWE076DD, ED
TWE101DD, ED
Minimum Unit Operating
Voltage Range
380/415
380/415
380/415
380/415
380/415
380/415
380/415
Maximum Fuse
Circuit Ampacity
Ampacity
4 15
5 15
5 15
5 15
6 15
10 15
10 15
Size or Maximum
Circuit Breaker
Table 19. Unit wiring with electric heat (single point connection) — air handlers
Heater
Model No.
BAYHTRL405* 5
BAYHTRL410* 9.96 1 22 25
BAYHTRL415* 14.96 1 31 35
BAYHTRL425* 24.92 2 49 50
BAYHTRL405* 5
BAYHTRL410* 9.96 1 23 25
BAYHTRL415* 14.96 1 32 35
BAYHTRL425* 24.92 2 50 50
BAYHTRL435* 34.88 2 68 70
Heater
kW Rating
To Use
with Unit
TWE051DD
TWE076DD, ED
Control
Stages
1 13 15
1 14 15
Minimum
Circuit
Ampacity
Maximum
Fuse Breaker
Size
40
SSA-SVX06E-EN
Table 19. Unit wiring with electric heat (single point connection) — air handlers (continued)
EElleeccttrriiccaall DDaattaa
BAYHTRL405* 5
BAYHTRL410* 9.96 1 23 25
BAYHTRL415* 14.96 1 32 35
BAYHTRL425* 24.92 2 50 50
BAYHTRL435* 34.88 2 68 70
BAYHTRM410* 10
BAYHTRM420* 19.92 1 41 45
BAYHTRM430* 29.92 2 59 60
BAYHTRM450* 49.84 2 94 100
BAYHTRM410* 10
BAYHTRM420* 19.92 1 41 45
BAYHTRM430* 29.92 2 59 60
BAYHTRM450* 49.84 2 95 100
BAYHTRM410* 10
BAYHTRM420* 19.92 1 46 50
BAYHTRM430* 29.92 2 65 70
BAYHTRM450* 49.84 2 100 100
BAYHTRM410* 10
BAYHTRM420* 19.92 1 46 50
BAYHTRM430* 29.92 2 65 70
BAYHTRM450* 49.84 2 100 100
Notes:
1. Field wire must be rated at least 167°F (75°C).
2. Field wire must be rated at least 194°F (90°C).
3. Heater kW ratings are at 400v for 3 phase, 400v air handlers.
4. For other than rated voltage, capacity = (voltage/rated voltage)2 x rated capacity and kW = (voltage/rated voltage)
2 rated kW.
5. Any power supply and circuits must be wired and protected in accordance with local codes.
6. MCA and Maximum Fuse Size is based on 400V.
TWE101DD,
TWE101ED
TWE126ED
TWE156ED
TWE201ED
TWE251ED
1 14 15
1 19 20
1 23 25
1 29 30
1 29 30
SSA-SVX06E-EN
41

Start-Up

Sequence of Operation

NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
EEnnssuurree tthhee ddiissccoonnnneecctt ffoorr tthhee iinnddoooorr aaiirr hhaannddlleerr iiss cclloosseedd bbeeffoorree ooppeerraattiinngg tthhee ssyysstteemm.. OOppeerraattiinngg tthhee oouuttddoooorr uunniitt wwiitthhoouutt tthhee iinnddoooorr ffaann eenneerrggiizzeedd ccaann ccaauussee uunniitt ttrriipp--oouutt oonn hhiigghh pprreessssuurree ccoonnttrrooll aanndd//oorr lliiqquuiidd fflloooodd bbaacckk ttoo tthhee ccoommpprreessssoorr..

Variable Air Volume Applications (SZVAV)

Supply Fan Mode Operation
Units configured for SZVAV control will utilize Supply Fan Mode selection as is currently implemented into ReliaTel controls for normal Zone Control and will be selectable between AAUUTTOO and OONN via a connected Zone Sensor module or through BAS/Network controllers.
Supply Fan Mode Auto Operation
For active Cooling, and Heating operation the Supply Fan will be commanded OONN and will ramp up to the appropriate minimum speed once the unit determines that there is a request for capacity control. Once the active request is cleared and all capacity is de­energized normal supply fan off delays as implemented on constant volume units will be in effect. During the Supply Fan Off-Delay, the supply fan will remain energized for the predetermined time at the previous unit function's minimum speed. All other cases which would bring the Supply Fan OONN will function as on non-SZVAV units.
Supply Fan Mode ON Operation
For active unit control with the Supply Fan Mode set to OONN, the unit will energize the Supply Fan and hold the Fan Speed output at minimum speed until there is a request for the fan speed to increase. This will hold true for all cases except during Unoccupied periods in which the Supply Fan Mode is forced to AAUUTTOO and will operate the Supply Fan as described above for all Cooling, and Heating requests.
Supply Air Temperature Control - Cooling
For Cooling operation the unit will control the active capacity outputs to meet a varying, calculated Discharge Air Setpoint that is calculated based on zone conditions in order to maintain the Zone Temperature to the active Zone Setpoint. Note that this setpoint will be clamped between the user selected DA Heat and DA Cool setpoints for compressor control. In general, as the zone temperature rises above the ZCSP, the Active Discharge Air Setpoint will be calculated down. This calculated setpoint is a direct indication of space
demand and is also used to determine the proper supply fan speed to meet the space requirements. During active capacity control, the unit will utilize a +/-
3.5°F deadband around the active Discharge Air Setpoint to determine when to request additional cooling capacity. If the unit is maintaining the discharge air temperature within the +/- 3.5°F deadband around the calculated discharge air setpoint requirements, no additional capacity will be requested.
Occupied Cooling Operation
For normal Cooling operation, available Cooling capacity will be staged or modulated in order to meet the calculated discharge air setpoint between the user selected upper and lower limits. If the current active cooling capacity is controlling the discharge air within the deadband no additional Cooling capacity change will be requested. As the Discharge Air Temperature rises above the deadband the control will request additional capacity as required (additional compressor operation). As the Discharge Air Temperature falls below the deadband the algorithm will request a reduction in active capacity.
Compressor Cooling
Compressor output control and protection schemes will function similar to non-SZVAV units. Normal compressor HPC and LPC control will remain in effect as well as normal 3-minute minimum on, off, and inter­stage timers. Also, the condenser fans will be controlled similar to non-SZVAV units.
Cooling Sequence
If the control determines that there is a need for compressor stages in order to meet the discharge air requirements, once supply fan proving has been made, the unit will begin to stage compressors accordingly. Note that a 5 second delay will be enforced between the command for supply fan output operation and the command for compressor output operation. This delay is enforced to ensure that the supply fan is energized and ramping up to operating speed prior to energizing compressors.
As the zone cooling demand continues to increase, if additional capacity is required, the supply fan output will be modulated above minimum speed in order to meet the zone requirements. Note that the supply fan speed will remain at the compressor stage's associated minimum value until the control requires additional capacity to meet the zone demand.
As the cooling load in the zone decreases the control will reduce the speed of the fan down to minimum per compressor stage and control the compressor outputs accordingly. As the compressors begin to de-energize, the Supply Fan speed will fall back to the Cooling Stage's associated minimum fan speed but not below. As the load in the zone continues to drop, cooling
42
SSA-SVX06E-EN
SSttaarrtt--UUpp
capacity will be reduced in order to maintain the calculated discharge air setpoint.
Cooling Stages Minimum Fan Speed
As the unit begins to stage compressors to meet the cooling demand, the following minimum Supply Fan Speeds will be utilized for each corresponding Cooling Stage. Note that the Supply Fan Speed will be allowed to ramp up beyond the minimum speed in order to meet the zone cooling demand. The minimum fan speed for units with 2 stages of DX Cooling will be 58% of the unit's full airflow capacity. At Stage 1 of DX Cooling the Fan Speed will be at a minimum of 58% and at Stage 2 of DX Cooling the Fan Speed will be at a minimum of 80%.
Occupied Heating Operation
Occupied Heating operation on units configured with SZVAV control will utilize two separate control methodologies based on heating configurations. For all "Staged" Heating types (Electric and Gas), the unit will utilize 100% full airflow during all active heating periods like traditional Constant Volume units. For Modulating Gas heat units, the unit will have the ability to control the discharge air temperature to the calculated discharge air heating setpoint in order to maintain the Zone Temperature to the Zone Heating setpoint.
Staged Heating Operation
For units configured with Mechanical or Auxiliary Heat once the control determines that there is an active heating capacity request, the unit will energize the Supply Fan and ramp up to full speed. The control methodology during Active Heating will be identical to traditional Constant Volume units; heating stages will be energized/de-energized to meet the Zone Heating demand. Note that all Electric staging sequences will be identical to Constant Volume units.
Unoccupied Cooling and Heating Operation
For SZVAV units, the unit will control Heating and Cooling, as during Occupied periods using the normal heating and cooling SZVAValgorithms. In Unoccupied periods the unit will utilize setback setpoints, and Auto fan mode operation as on normal Constant Volume units.
Failure and Overriding Conditions
Certain failure and overriding conditions require
special handling of the Supply Fan Speed on units configured with SZVAV. See below for a list of these conditions:
1. SSuuppppllyy FFaann PPrroovviinngg FFaaiilluurree - If a Supply Fan Proving failure is detected the Supply Fan will be de-energized after 40s of run time and the Fan Speed output will go to the corresponding minimum speed voltage.
2. ZZoonnee TTeemmppeerraattuurree SSeennssoorr FFaaiilluurree - If the Active Zone Temperature input goes out of range, the unit will discontinue all Heating, Cooling, and Dehumidification operation.
3. SSuuppppllyy AAiirr TTeemmppeerraattuurree SSeennssoorr FFaaiilluurree - If the Supply Air Temperature input goes out of range, the unit will revert back to Full Airflow, Traditional CV control. The unit will call out a Supply Air Temperature Sensor Failure Alarm, the RTRM System LED will flash the 2-blink error code, and Cool LEDs will flash.

2–Speed VFD Applications

General Description of Functionality
Cooling Operation (DX Cooling)
Units with a 2-Speed VFD control scheme will utilize a thermostat's heating and cooling outputs to differentiate between high and low speed. When the unit receives a G or Y1 call from the thermostat the supply fan will run at the user selected low speed. Once the zone load demands the second stage of cooling, and the unit receives the Y2 call from the thermostat the supply fan will be signaled to run at the user selected high speed. All other compressor staging will be handled the same as all standard thermostat controlled units.
Heating Operation
Units with 2-Speed VFD controls will utilize traditional CV Heating control schemes with full airflow provided based on the customer selected VFD controlled maximum speed. When the unit receives the W1 call from the thermostat a relay will signal the supply fan to run at high speed. All the electric heaters that can be outfitted in the field are wired up to interlock W1 and W2 so the supply fan will always run at the user selected high speed during heat modes.
SSA-SVX06E-EN
43

Maintenance

Perform all of the indicated maintenance procedures at the intervals scheduled. This will prolong the life of the unit and reduce the possibility of costly equipment failure.

Fan Belt Adjustment

WWAARRNNIINNGG
RRoottaattiinngg CCoommppoonneennttss!!
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd..
The fan belts must be inspected periodically to assure proper unit operation. Replacement is necessary if the belts appear frayed or worn.
When removing or installing the new belts, do not stretch them over the sheaves. Loosen the belts using the belt tension adjustment bolts on the motor mounting base.
Once the new belts are installed, using a Browning or Gates tension gauge (or equivalent), adjust the belt tension as follows:
1. To determine the appropriate belt deflection:
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64;
the resulting value represents the amount of belt deflection that corresponds to the proper belt tension.
2. Set the large O-ring on the belt tension gauge at the deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the
gauge plunger.
4. Place the large end of the gauge at the center of the belt span; then depress the gauge plunger until the large O-ring is even with the top of the next belt or even with a straightedge placed across the fan and motor sheaves.
5. Remove the belt tension gauge. The small O-ring now indicates a number other than zero on the plunger’s force scale. This number represents the force (in pounds) required to give the needed deflection.
6. Compare the “force” scale reading (Step 5) with the appropriate “force” value listed in the Belt tension table. If the “force” reading is outside the range, readjust the belt tension.
NNoottee:: Actual belt deflection “force” must not
exceed the maximum “force” value shown in
Figure 27, p. 44.
Recheck the belt tension at least twice during the first 2 to 3 days of operation. Belt tension may decrease until the new belts are “run in”.
Figure 27. Belt tension gauge
Table 20. Belt tension measurement and deflection
Belts Cross
Section
A
B
Small Pitch
Diameter Range
3.0 - 3.6 3
3.8 - 4.8
5.0 - 7.0 4
3.4 - 4.2 4
4.4 - 5.6
5.8 - 8.8
Standard V-Belt V-Belt with Molded Notches
Min. Max. Min. Max.
3-1/2
5-1/8 7-1/8 6-1/2 9-1/8
6-3/8 8-3/4 7-3/8 10-1/8

Monthly

The following warning complies with State of California law, Proposition 65.
44
Deflection Force (Lbs.)
4-1/2 3-7/8 5-1/2
5
5-1/2
5-1/2 5-3/4
4-1/2 6-1/4
5
6-7/8
8
SSA-SVX06E-EN
MMaaiinntteennaannccee
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee ww//CCaappaacciittoorrss!!
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss aanndd ddiisscchhaarrggee aallll mmoottoorr ssttaarrtt//rruunn ccaappaacciittoorrss bbeeffoorree sseerrvviicciinngg.. FFoollllooww pprrooppeerr lloocckkoouutt// ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaannnnoott bbee iinnaaddvveerrtteennttllyy eenneerrggiizzeedd.. FFoorr vvaarriiaabbllee ffrreeqquueennccyy ddrriivveess oorr ootthheerr eenneerrggyy ssttoorriinngg ccoommppoonneennttss pprroovviiddeedd bbyy TTrraannee oorr ootthheerrss,, rreeffeerr ttoo tthhee aapppprroopprriiaattee mmaannuuffaaccttuurreerr’’ss lliitteerraattuurree ffoorr aalllloowwaabbllee wwaaiittiinngg ppeerriiooddss ffoorr ddiisscchhaarrggee ooff ccaappaacciittoorrss.. VVeerriiffyy wwiitthh aann aapppprroopprriiaattee vvoollttmmeetteerr tthhaatt aallll ccaappaacciittoorrss hhaavvee ddiisscchhaarrggeedd..
FFoorr aaddddiittiioonnaall iinnffoorrmmaattiioonn rreeggaarrddiinngg tthhee ssaaffee ddiisscchhaarrggee ooff ccaappaacciittoorrss,, sseeee PPRROODD--SSVVBB0066AA--EENN..
NNOOTTIICCEE
OOppeerraattiinngg UUnnddeerr VVaaccuuuumm!!
DDoo nnoott ooppeerraattee oorr aappppllyy ppoowweerr ttoo tthhee ccoommpprreessssoorr wwhhiillee uunnddeerr aa vvaaccuuuumm..
WWAARRNNIINNGG
FFiibbeerrggllaassss WWooooll!!
YYoouu MMUUSSTTwweeaarr aallll nneecceessssaarryy PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) iinncclluuddiinngg gglloovveess,, eeyyee pprrootteeccttiioonn,, aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr,, lloonngg sslleeeevveess aanndd ppaannttss wwhheenn wwoorrkkiinngg wwiitthh pprroodduuccttss ccoonnttaaiinniinngg ffiibbeerrggllaassss wwooooll..
PPrreeccaauuttiioonnaarryy MMeeaassuurreess::
•• AAvvooiidd bbrreeaatthhiinngg ffiibbeerrggllaassss dduusstt..
•• UUssee aa NNIIOOSSHH aapppprroovveedd dduusstt//mmiisstt rreessppiirraattoorr..
•• AAvvooiidd ccoonnttaacctt wwiitthh tthhee sskkiinn oorr eeyyeess.. WWeeaarr lloonngg--sslleeeevveedd,, lloooossee--ffiittttiinngg ccllootthhiinngg,, gglloovveess,, aanndd eeyyee pprrootteeccttiioonn..
•• WWaasshh ccllootthheess sseeppaarraatteellyy ffrroomm ootthheerr ccllootthhiinngg;; rriinnssee wwaasshheerr tthhoorroouugghhllyy..
•• OOppeerraattiioonnss ssuucchh aass ssaawwiinngg,, bblloowwiinngg,, tteeaarr-­oouutt,, aanndd sspprraayyiinngg mmaayy ggeenneerraattee ffiibbeerr ccoonncceennttrraattiioonnss rreeqquuiirriinngg aaddddiittiioonnaall rreessppiirraattoorryy pprrootteeccttiioonn.. UUssee tthhee aapppprroopprriiaattee NNIIOOSSHH aapppprroovveedd rreessppiirraattoorr..
FFiirrsstt AAiidd MMeeaassuurreess::
•• EEyyee CCoonnttaacctt -- FFlluusshh eeyyeess wwiitthh wwaatteerr ttoo rreemmoovvee dduusstt.. IIff ssyymmppttoommss ppeerrssiisstt,, sseeeekk mmeeddiiccaall aatttteennttiioonn..
•• SSkkiinn CCoonnttaacctt -- WWaasshh aaffffeecctteedd aarreeaass ggeennttllyy wwiitthh ssooaapp aanndd wwaarrmm wwaatteerr aafftteerr hhaannddlliinngg..
Conduct the following maintenance inspections once per month:
Inspect air filters and clean (or replace) if necessary.
Check unit wiring to ensure all connections are tight and that the wiring insulation is intact.
Check drain pans and condensate piping to insure they are free of obstacles.
Manually rotate the indoor fan to ensure proper operation.
Inspect the evaporator coils for dirt and debris. If the coils appear dirty, clean them.
Observe indoor fan operation and correct any unusual or excessive vibration. Clean blower wheels as needed.

Annually (Cooling Season)

The following maintenance procedures must be performed at the beginning of each cooling season to ensure efficient unit operation:
Perform all of the monthly maintenance inspections.
With the unit operating, check unit superheat and record the reading in the “Maintenance Log,” p. 46
Remove any accumulation of dust and/or dirt from the unit casing.
Remove corrosion from any surface and repaint. Check the gasket around the control panel door to ensure it fits correctly and is in good condition to prevent water leakage.
Inspect the evaporator fan belt. If it is worn or frayed, replace it.
Inspect the control panel wiring to ensure that all connections are tight and that the insulation is intact.
Check refrigerant piping and fittings for leaks.
Inspect the evaporator coils for dirt and debris. If the coils appear dirty, clean them.

Coil Cleaning

Regular coil maintenance, including annual cleaning­enhances the unit's operating efficiency by minimizing:
compressor head pressure and amperage draw
water carryover
fan brake horsepower
static pressure losses
At least once each year — or more often if the unit is located in a “dirty” environment — clean the coil using the instructions outlined below. Be sure to follow these instructions as closely as possible to avoid damaging the coils.
SSA-SVX06E-EN
45
MMaaiinntteennaannccee

Maintenance Log

Subcooling (°F)
(at service valve)
Superheat (°F)
(at compressor)
Circuit #1 Circuit #2 Circuit #1 Circuit #2
Discharge Pressure
(C1) (C2) (C1) (C2)
Suction Pressure
Wet
Bulb
Dry
Bulb
Evaporator Entering Air Compressor
(°F)
Temp.
Ambient
Date
Note: Perform each inspection once per month (during cooling season) while unit is operating
46
SSA-SVX06E-EN

Wiring Diagram Matrix

Table 21. Wiring schematics for TWE air handlers
Electromechanical
(Sd)
Model No. Ton Circuit Volts Hz Ph
TWE051DD 4.6
TWE061D3 5
TWE061D4 5
TWE061DW 5
TWE061DK 5
TTA076DD 6.25
TWE061D1 5
TWE090D1 7.5
TWE120D1 10
TWE061E3 5 Dual 208-230 60 3 2313-0431
TWE061E4 5 Dual 460 60 3 2313-0431
TWE061EW 5 Dual 575 60 3 2313-0431
TWE061EK 5 Dual 380 60 3 2313-0431
TWE061E1 5 Dual 208-230 60 1 2313-0432
TWE090E1 7.5 Dual 208-230 60 1 2313-0432
TWE120E1 10 Dual 208-230 60 1 2313-0432
TWE090D3 7.5
TWE090D4 7.5
TWE090DW 7.5
TWE090DK 7.5
TWE090E3 7.5 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE090E4 7.5 Dual 460 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE090EW 7.5 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE090EK 7.5 Dual 380 60 3 2313-0431
TWE101DD 8.33
TWE101ED 8.33 Dual 380-415 50 3 2313-0431
TWE120D3 10
TWE120DW 10
TWE120DK 10
TWE120E3 10 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE120EW 10 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE120EK 10 Dual 380 60 3 2313-0431
TWE126ED 10.4 Dual 380-415 50 3 2313-0431
TWE150E3 12.5 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE150EW 12.5 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE150EK 12.5 Dual 380 60 3 2313-0431
TWE156ED 13 Dual 380-415 50 3 2313-0431
TWE180E3 15 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE180EW 15 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE180EK 15 Dual 380 60 3 2313-0431
TWE201ED 16.7 Dual 380-415 50 3 2313-0431
TWE240E3 20 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE240E4 20 Dual 380-415 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE240EW 20 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE240EK 20 Dual 380 60 3 2313-0431
TWE251ED 20.9 Dual 380-415 50 3 2313-0431
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
Single
380-415 50 3 2313-0401
208-230 60 3 2313-0401
460 60 3 2313-0401
575 60 3 2313-0401
380 60 3 2313-0401
380-415 50 3 2313-0401
208-230 60 1 2313-0402
208-230 60 1 2313-0402
208-230 60 1 2313-0402
208-230 60 3 2313-0401 2313-0451 2313-0453 1213-1400 1213-1401
460 60 3 2313-0401 2313-0451 2313-0453 1213-1400 1213-1401
575 60 3 2313-0401 2313-0451 2313-0453 1213-1400 1213-1401
380 60 3 2313-0401
380-415 50 3 2313-0401
208-230 60 3 2313-0401 2313-0451 2313-0453 1213-1400 1213-1401
575 60 3 2313-0401 2313-0451 2313-0453 1213-1400 1213-1401
380 60 3 2313-0401
Schematic/ Connection
Electromechanical
(2 speed)
Reliatel
Schematic Connection Schematic Connection
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
SSA-SVX06E-EN
47
WWiirriinngg DDiiaaggrraamm MMaattrriixx
Table 21. Wiring schematics for TWE air handlers (continued)
Electromechanical
(Sd)
Model No. Ton
TWE300E3 25 Dual 208-230 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE300E4 25 Dual 380-415 50 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE300EW 25 Dual 575 60 3 2313-0431 2313-0451 2313-0453 1213-1400 1213-1401
TWE300EK 25 Dual 380 60 3 2313-0431
Note: Wiring diagrams are available through e-Library or by contacting your local sales office.
Circuit Volts Hz
Ph
Schematic/ Connection
Electromechanical
(2 speed)
Reliatel
Schematic Connection Schematic Connection
N/A N/A N/A N/A
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.
©2015 Trane All rights reserved
SSA-SVX06E-EN
Supersedes SSA-SVX06D-EN (January 2014)
02 Mar 2015
We are committed to using environmentally
conscious print practices that reduce waste.
Loading...