Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
March 2015
SSA-SVX06E-EN
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs such as HCFCs and
HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the
air conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
•With the change to Microchannel, the Odyssey split
system now offers a 50Hz, 6.25 standard air handler
(TWE076E) and a 60Hz, 7.5 ton standard/SZVAV/2Speed VFD air handler (TWE090E). See
performance data for additional details on this new
split system.
•Odyssey air handlers now have the ability to
convert from Single Zone VAV to 2–Speed Fan
control in order to comply with certain sections of
California Title 24 and ASHRAE 90.1. See
“Installation, 2-Speed VFD Units,” p. 25 for
configuration details.
SSA-SVX06E-EN
3
Table of Contents
Model Number Description. . . . . . . . . . . . . . . . . 5
This manual describes proper installation, operation,
and maintenance procedures for air cooled systems. By
carefully reviewing the information within this manual
and following the instructions, the risk of improper
operation and/or component damage will be
minimized. It is important that periodic maintenance be
performed to help assure trouble free operation.
Should equipment failure occur, contact a qualified
service organization with qualified, experienced HVAC
technicians to properly diagnose and repair this
equipment.
IImmppoorrttaanntt:: All phases of this installation must comply
with the NATIONAL, STATE & LOCAL
CODES. In addition to local codes, the
installation must conform with National
Electric Code -ANSI/NFPA NO. 70 LATEST
REVISION.
Any individual installing, maintaining, or servicing this
equipment must be properly trained, licensed and
qualified.
IImmppoorrttaanntt:: Do not remove the VFD without first
contacting technical support! For
performance-related questions and
diagnostic support in North America call 1877-872-6363. Any return requires a claim
number FIRST. Removal of the VFD prior to
this step will void the unit’s warranties.
Installation procedures should be performed in the
sequence that they appear in this manual. Do not
destroy or remove the manual from the unit. The
manual should remain weather-protected with the unit
until all installation procedures are complete.
NNoottee:: It is not the intention of this manual to cover all
possible variations in systems that may occur or
to provide comprehensive information
concerning every possible contingency that may
be encountered during an installation. If
additional information is required or if specific
problems arise that are not fully discussed in this
manual, contact your local sales office.
Use the installation checklist provided In this manual to
verify that all necessary installation procedures have
been completed. Do not use the checklist as a
substitute for reading the information contained in the
manual. Read the entire manual before beginning
installation procedures.
Unit Description
These air handler models incorporate a single slab coil
assembly, improved application flexibility, servicing,
maintenance accessibility and an improved accessory
line. They are fully convertible, (vertical to horizontal
discharge) without field removal of the coil assembly.
They are shipped ready for horizontal installation.
All units have one drain pan that can be installed in any
one of four positions. This allows for vertical or
horizontal applications and right or left exit.
IImmppoorrttaanntt:: All dual circuit (digit 7 = E) have an
intertwined coil, except for the 25 ton,
TWE251 and TWE300 units.
6
SSA-SVX06E-EN
Pre-Installation
The final position for the air handler must be dictated
by required service access to it, weight distribution
over structural supports, and by the locations of
electrical, refrigerant and condensate drainage
connections. After this is determined, the following
preparations should be made.
Unit Inspection
Inspect material carefully for any shipping damage. If
damaged, it must be reported to, and claims made
against the transportation company. Compare the
information that appears on the unit nameplate with
ordering and submittal data to ensure the proper unit
was shipped. Available power supply must be
compatible with electrical characteristics specified on
component nameplates. Replace damaged parts with
authorized parts only.
Inspection Checklist
To protect against loss due to damage incurred in
transit, complete the following checklist upon receipt of
the unit.
Inspect individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
Inspect the unit for concealed damage before it is
stored and as soon as possible after delivery.
Concealed damage must be reported within 15
days. If concealed damage is discovered, stop
unpacking the shipment. Do not remove damaged
material from the receiving location. Take photos of
the damage if possible. The owner must provide
reasonable evidence that the damage did not occur
after delivery.
Notify the carrier’s terminal of damage immediately
by phone and by mail. Request an immediate joint
inspection of the damage by the carrier and the
consignee.
Notify the sales representative and arrange for
repair. Do not repair the unit until the damage is
inspected by the carrier’s representative.
Testing for Leaks
All TWE units are shipped with a holding charge of
nitrogen in each circuit and should be leak tested
before installation.
1. Remove the access panel.
2. Locate the liquid line or suction line access valve for
each circuit.
3. Install gauges to determine if the circuits are still
pressurized. If not, the charge has escaped and
should be repaired as required to obtain a leak-free
circuit.
Before preparing the unit for lifting, estimate the
approximate center of gravity for lifting safety. Because
of placement of internal components, the unit weight
may be unevenly distributed. See “Weights,” p. 20 for
approximate unit weights.
The crated unit can be moved using a forklift of suitable
capacity. For lifting the unit into an elevated mounting
position, run lifting straps or slings under the unit and
attach securely to the lifting device.
Repositioning Drain Pan
Air handlers come with one drain pan that can be
installed in any one of four positions; this allows for
vertical or horizontal application and right or left
condensate line connection.
NNoottee:: Important! All air handlers are shipped with the
drain pan installed in the horizontal position and
the connection on the left side (as shown in
Figure 1, p. 8. If an alternate position is required,
the drain pan should be repositioned before
setting the air handler.
1. Remove the access plate at the opposite end of the
drain connection. This plate secures and lifts the
back end of the drain pan for sloping. It must be
removed before the drain pan can be removed. This
is done as follows:
a. Remove the screw
b. Lift the access plate up
c. Pull the plate out. If the drain pan is to be moved
to the vertical position also remove the other
two access plates.
2. Remove the screw securing the drain pan.
a. Lift the pan up
b. Slide the pan out
3. Install the drain pan into the new position.
SSA-SVX06E-EN
7
PPrree--IInnssttaallllaattiioonn
a. Slide the drain pan into the opening
b. Lift the drain pan up
c. Push it in all the way
d. Drop it down over the lip of the opening, secure
with screw
4. Install the access plate on the opposite end of the
drain pain.
a. Slide the edge of the access plate under the
drain pan
b. Lift the access plate and drain pan up
c. Push the access plate in
d. Drop the access plate down over the lip of the
opening, secure with screw
NNoottee:: If the drain pan is being moved to the vertical
position, install the other access plates over
the horizontal position opening
•Available power supply must agree with electrical
data on component nameplate.
•Some standard air handlers are shipped wired for
208-230 volt applications and can be converted for
460 volt by rewiring the blower motor. (This
includes models TWE090D3, TWE090E3,
TWE120D3, TWE120E3, TWE150E3 and TWE180E3).
Converting Motor to 460 Volt
1. Ensure power is disconnected to unit by following
the warning above.
2. Remove unit access panels closest to motor.
3. Open terminal cover on lead end of motor.
4. Pull voltage selector plug from low voltage
selection (see Figure 3, p. 9).
5. Shift the plug (or rotate 180°) to align plug for high
voltage selection and re-insert plug.
IImmppoorrttaanntt:: When re-inserting voltage selection
plug, ensure it is fully seated.
6. Replace terminal cover on lead end of motor.
7. Replace unit access panels.
Figure 3. Voltage change plug
Refrigerant Piping
Reorienting Evaporator Coil (TWE126/
150 and 156/180)
IImmppoorrttaanntt:: Applies to TWE126/150 and 156/180 when
positioned for vertical upflow. Unit is
shipped in the horizontal position. If
installing in the vveerrttiiccaall ppoossiittiioonn, the coil
mmuusstt bbee reoriented by rotating the coil 4
degrees (control box side) from the
shipped position.
1. Remove screws from top evaporator coil bracket
(bracket that attaches coil to cabinet and runs the
length of the unit).
2. Rotate evaporator coil approximately 4 degrees
clockwise - looking from the control box end. When
the evaporator coil is rotated, the lower set of
evaporator coil bracket holes will align with the
support bracket (from which it was originally
fastened).
3. Reinsert screws in evaporator coil bracket.
SSA-SVX06E-EN
9
Topbracketscrews
Rotate4°clockwise
PPrree--IInnssttaallllaattiioonn
Figure 4. Evaporator coil reorientation for TWE126,
150, 156, 180
The air handler is designed so that refrigerant piping
can enter from either the right or left hand side. It is
shipped with the intent that the refrigerant lines will
enter from the left hand side. To convert to right hand
entry, unbraze the elbow on the suction line and rotate
180° and rebraze.
IImmppoorrttaanntt:: Access to refrigerant lines is limited in all
horizontal and some vertical applications.
Therefore, refrigerant lines should be
stubbed out and temporarily capped prior
to setting the air handler. Protect adjacent
surfaces from heat damage when brazing
in and around the air handler.
The general location of the air handler is normally
selected by the architect, contractor and/or buyer. For
proper installation, the following items must be
considered:
•Available power supply must agree with electrical
data on component nameplate.
•If external accessories are installed on the unit,
additional clearances must be provided.
•All duct work should be properly insulated to
prevent condensation and heat loss.
•Refrigerant gas piping must be insulated.
It is recommended that the outline drawings in the
Dimensional Data section be studied and dimensions
properly noted and checked against the selected
installation site. By noting in advance which features
are to be used, proper clearance allowances can be
made for installation and possible future service.
IImmppoorrttaanntt:: When installing these units “free standing”
with discharge grills and isolators, a top
support with isolator should be added to
prevent tipping. Support and isolator can
be attached to a wall or other appropriate
structure.
If adding external accessories to the unit,
additional clearances must be considered
for the overall space needed.
For installation of accessories available for this air
handler, follow the installation instructions that are
shipped with each accessory.
If the air handler will be suspended, use a suspension
mounting kit to isolate the unit from the structure. This
is usually accomplished with spring or rubber isolators,
which are offered as an accessory.
Mounting rods must be field supplied. Isolator
selection is dependent upon total unit weight including
accessories — see “Weights,” p. 20 for approximate
unit weights.
Align holes in the cabinet with structural supports and
secure suspension rods to the structure, then to the air
handler cabinet. If hole locations do not permit proper
alignment with existing structure, it may be necessary
to field fabricate cross members on existing structural
beams.
NNoottee:: When other than bottom return is to be used,
side panel removal for return duct installation
must be secured over the bottom opening.
Leveling
This air handler has a double sloped drain pan. In order
to assure proper drainage along the length of the drain
pan, it is important to have the unit properly leveled. Be
sure the air handler is level.
Auxiliary Drain Pan
A field fabricated, auxiliary drain pan should be
installed under the unit for all horizontal applications
and when air handlers are installed above ceilings or in
other locations where condensate overflow may cause
damage.
This drain pan will eliminate any excess condensation
that may be due to extreme humidity or an obstructed
drain in the primary drain pan. Drain lines from this
pan must be installed, but should not be connected to
the primary drain line from the unit. Isolate the
auxiliary drain pan from both the air handler and the
structure.
1. Locate cloth bag(s) attached to the refrigerant tube
of the coil that contains a stainless steel clamp and
insulation material (approximately 9” long by 4”
wide) for each refrigerant circuit. This is for
attaching and insulating the expansion valve bulb(s)
to the suction line(s).
knockout in the end of the air handler. Uncoil the
cap tube with the bulb attached at the expansion
valve and place the grommet on the cap tube.
b. With the grommet around the tube, push the
bulb through the hole and position the grommet
back into its original position (one bulb and cap
tube on single circuit units, and two bulbs and
cap tubes on dual circuit units).
a. Attach the bulb(s) to the suction tube(s) inside
the cabinet, approximately 10” from the right
end of the unit.
3. Attach the bulb(s) on a horizontal section of tube
where the entire length of the bulb is in contact with
the tube (see Figure 18, p. 23), approximately 45
degrees off vertical (a 10 or 2 o’clock position).
4. After attaching to the suction line(s), either inside or
outside of the cabinet, wrap the insulation around
the bulb(s) and suction tube(s).
NNoottee:: Suction piping should be insulated.
Refrigerant Piping
Installation, brazing, leak testing and evacuation of
refrigerant lines are covered in the installation
instructions that shipped with the outdoor unit. Read
the instructions before beginning installation of
refrigerant lines.
NNoottee:: When air handler is installed in the vertical
position and close proximity trapping of
condensate is required, use of a subbase
accessory to raise the air handler for clearance of
the drain trap is recommended. See Figure 19, p.
The drain pan condensate connection is a female slip
joint type for 1” Schedule 40 PVC pipe. Use PVC cement
and tubing as required (field supplied) to construct a
trap. A union or flexible tubing and clamps may be
installed if the drain pan is to be removed periodically
for cleaning.
Air handlers are shipped with throwaway filters
installed. For replacement filters consult the air handler
service facts for correct size and number.
23
FilterFrame
IInnssttaallllaattiioonn
To replace filters from the end of the unit, remove lower
access panel (either end) and slide old filters out and
replace with new ones.
To replace from the front of the unit, remove one “L”
shaped angle. Remove and replace filters and reinstall
“L” shaped angle. See Figure 20, p. 24.
To convert from 1” filter to a 2” filter on units so
equipped, remove lower access panels from both ends
of the air handler. Remove screws and rotate the “L”
shaped angles from both the top and bottom of the
filter track 180° to increase the width of the filter
opening.
Figure 20. Filter location
SZVAV Units
For SZVAV units, air flow is set by using potentiometer
R-136 on the ReliaTel options module found in the air
handler control box, see Figure 21, p. 24. The
potentiometer will adjust the maximum air flow
between the range of 60 Hz to 44.50 Hz. If the desired
maximum operating point from the catalog fan table is
lower than 44.50 Hz, parameter 6-15 on the VFD must
be reprogrammed to 50 Hz. The VFD is preset from the
factory to a default of 25 Hz for the lower limit and does
not need to be reprogrammed.
Figure 21. ReliaTel options module
Duct Connections
The supply and return ducts should be connected to
the unit with flame retardant duct connectors to reduce
vibration transmission. The return duct should be sized
to the same dimensions as the return inlet of the unit.
IImmppoorrttaanntt:: Duct flanges are provided for attachment of
the duct work and are packaged on the
outside of the cabinet for TWE150, 180, 240,
300 and TWE126, 156, 201, 251. The duct
flanges are fastened to the pallet below the
coil (bottom return) on the TWE051, 061,
076, 090, 101 and 120 models.
Air Flow Settings
Standard Units
Unit is shipped for nominal airflow with nominal static
pressure. Please refer to the fan performance table in
either the product catalog or unit service facts and
select the proper drive package for each application.
Failure to do so could result in improper airflow
causing coil frosting or condensate management
problems. Condensate management problems such as
water blow off could be the result of too great of air
face velocity across the coil. To ensure proper
operation refer to “Fan Belt Adjustment,” p. 44.
Measure the voltage between TP1 on the RTOM and
ground. Use Table 4, p. 24 to set the desired maximum
operating supply fan speed.
Table 4. SZVAV air handler speed to voltage
Parameter 6-15 Set to 60 Hz
TP1
High Speed
(Hz)
38.00<0.1044.001.65
38.400.2044.401.70
38.800.3044.801.75
39.200.4545.201.83
39.600.5545.601.90
40.000.7046.001.95
40.400.8046.402.00
40.800.9546.802.05
41.201.0547.202.10
41.601.1547.602.13
42.001.2548.002.17
42.401.3048.402.21
(RTOM)
Voltage
(Vdc)
High Speed
(Hz)
TP1
(RTOM)
Voltage
(Vdc)
24
SSA-SVX06E-EN
IInnssttaallllaattiioonn
Table 4. SZVAV air handler speed to voltage
(continued)
Parameter 6-15 Set to 60 Hz
TP1
High Speed
(Hz)
42.801.3548.802.27
43.201.4549.202.30
43.601.5549.602.35
——50.00>2.40
44.50<0.1052.251.65
45.020.2052.771.70
45.530.3053.281.75
46.050.4553.801.83
46.570.5554.321.90
47.080.7054.831.95
47.600.8055.352.00
48.120.9555.872.05
48.631.0556.382.10
49.151.1556.902.13
49.671.2557.422.17
50.181.3057.932.21
50.701.3558.452.27
51.221.4558.972.30
51.731.5559.482.35
——60.00>2.40
(RTOM)
Voltage
(Vdc)
High Speed
(Hz)
TP1
(RTOM)
Voltage
(Vdc)
2-Speed VFD Units
To configure units with an RTOM for 2-speed operation
move plug PPM 10 from PPF 10 to TP. Refer to “Heating
and Cooling Setpoint Arbitration,” p. 27 for setpoint
connection. Complete the configuration by
reprogramming VFD parameter 6-10 to 5.00 V and
parameter 6-11 to 7.60 V. For 2-Speed VFD controlled
units the desired maximum air flow (High Speed) is set
by reprogramming parameter 6-15 on the VFD to the
frequency value that best meets the RPM requirement
as shown in the catalog fan tables.
The minimum air flow (Low Speed) is set by
reprogramming parameter 6-14 on the VFD. Refer to
Table 5, p. 25 to see the allowed Low Speed range for a
given High Speed. Use the Menu button and up and
down arrows on the keypad to access the parameters.
Table 5. 2-Speed VFD programming speeds
High
Speed
(Hz)
60.0025.00 - 39.6048.0025 - 31.68
59.0025.00 - 38.9447.0025 - 31.02
58.0025.00 - 38.2846.0025 - 30.36
57.0025.00 - 37.6245.0025 - 29.70
56.0025.00 - 36.9644.0025 - 29.04
55.0025.00 - 36.3043.0025 - 28.38
54.0025.00 - 35.6442.0025 - 27.72
53.0025.00 - 34.9841.0025 - 27.06
52.0025.00 - 34.3240.0025 - 26.40
51.0025.00 - 33.6639.0025 - 25.74
50.0025.00 - 33.0038.0025 - 25.08
49.0025.00 - 32.34——
Low Speed
(Hz)
Ranges
High Speed
(Hz)
Low Speed
(Hz)
Ranges
Minimum Supply Fan Output
Refer to Table 6, p. 25 for details on minimum supply
fan output signals associated with each unit function.
Note that each value represents the actual Fan Output
% based on 100% being the customers selected
maximum operating speed.
Table 6. Minimum supply fan speeds for SZVAV units
VFD Parameter 6-15 Set to 60 Hz
Minimum
Function
Ventilation Only
Cool 1 (C1 or C2)
Cool 2 (C1 + C2 Energized)
CV Staged Heat
VFD Parameter 6-15 Set to 50 Hz
Function
Ventilation Only
Cool 1 (C1 or C2)
Cool 2 (C1 + C2 Energized)
CV Staged Heat
Table 7. Minimum supply fan speeds for 2-Speed units
Fan Output %
58%
58%
80%
100%
Minimum
Fan Output %
64%
64%
83%
100%
SSA-SVX06E-EN
Function
Ventilation Only
Cool 1 (C1)
Fan Output %
42 - 66%
42 - 66%
(a)
(a)
25
HeaterControlSinglePointPower
LineVoltageEntrance
ControlWiring
IInnssttaallllaattiioonn
Table 7. Minimum supply fan speeds for 2-Speed units
(continued)
Function
Cool 2 (C1 + C2 Energized)
CV Staged Heat
(a)
Fan Output percentage is based on the customer chosen upper and
lower speed settings.
Fan Output %
100%
100%
IImmppoorrttaanntt:: Do not remove the VFD without first
contacting technical support! For
performance-related questions and
diagnostic support in North America call 1877-872-6363. Any return requires a claim
number FIRST. Removal of the VFD prior to
this step will void the unit warranty.
3. Ensure all connections are tight and no wires
exposed.
4. All accessories must be installed and wired
according to the instructions packaged with that
accessory.
For air handler power entry only, or for dual power
entry (power entry for air handler and power entry
for electric heats), the electrical connections are
made in the fan control box located in the right side
of the air handler and electric heater respectively.
Wiring entrance is through holes provided in the
end of the air handler cabinet, Figure 22, p. 26.
Breaker or fuse size can be selected using the
nameplates attached to the unit and electric heater.
may cause a noise problem within the building
structure.
Table 8. Recommended thermostat wire size
Wire Size
(Gauge)Physical distance between Unit & T’stat
2230 Feet
2050 Feet
1875 Feet
16125 Feet
14200 Feet
Maximum Wire Length
Setpoints
SSA-SVX06E-EN
IInnssttaallllaattiioonn
EDC Switch Wiring
EElleeccttrroommeecchhaanniiccaall UUnniittss: To enable the Evaporator
Defrost Control Switch remove the "W3" jumper
between LTB1-B1 and LTB1-B2 at the Outdoor
Condenser Section.
RReelliiaaTTeell UUnniittss: To enable the Evaporator Defrost
Control Switch move wire "W11" from LTB2-B2 to LTB2R, and move wire "W12" from LTB2-B1 to LTB2-CD at
the Indoor Air Handler Section.
NNoottee:: Refer to wiring schematics for more detail.
Heating and Cooling Setpoint Arbitration
Figure 23. Discharge air cooling setpoint
Single Zone VAV units will require traditional Zone
Heating (if Heat installed) and Cooling Setpoints that
are used on constant volume units in addition to two
new setpoints: Discharge Air Cool (Externally Mounted
Potentiometer in Control Box) and Discharge Air Heat
(DA Heat R-42) Setpoint limits. The Zone Heating and
Cooling Setpoints will be selectable via the existing
RTRM customer connections for a Zone Sensor panel
and the DA Heat and Cool Setpoints will be customer
selectable via an onboard potentiometer on the RTOM,
and an off board potentiometer mounted inside the
control box with ranges 50-150°F and 40-90°F
respectively.
The setpoint tables should be used as a reference when
setting the DA Heat (R–42) and Discharge Air Cool
(Control Box Mounted Potentiometer) setpoints. Note
that the recommended settings for these setpoints are
100°F for the DA Heat Setpoint, and 50°F for the DA
Cool Setpoint.
Table 9. DA heat setpoint
Voltage
(Vdc)
0.00500.98751.611002.06125
0.09511.00761.631012.08126
0.13521.03771.661022.09127
0.16531.06781.691032.11128
0.20541.08791.711042.12129
0.24551.11801.721052.13130
0.28561.13811.741062.13131
0.31571.16821.761072.14132
0.35581.18831.781082.16133
0.39591.21841.791092.17134
0.42601.23851.811102.19135
0.46611.26861.831112.20136
0.50621.28871.841122.21137
0.53631.31881.861132.23138
0.57641.33891.881142.24139
0.61651.36901.891152.25140
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
SSA-SVX06E-EN
27
IInnssttaallllaattiioonn
Table 9. DA heat setpoint (continued)
Voltage
(Vdc)
0.65661.38911.911162.26141
0.68671.41921.931172.28142
0.72681.43931.951182.29143
0.76691.46941.961192.30144
0.79701.48951.981202.32145
0.83711.51962.001212.33146
0.87721.53972.011222.34147
0.90731.56982.031232.36148
0.94741.58992.051242.37149
——————2.40150
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Voltage
(Vdc)
Setpoint
(ºF)
Table 10. DA cool setpoint (mounted above keyboard)
Note: The potentiometer voltage readings can be verified via the provided test points located next to each potentiometer. Use a DC voltmeter to the Vdc
reading between those points and common.
Checkout Procedure
Complete the “Installation Checklist,” p. 28 once
installation of field wiring connections is complete. All
operational checks (unit running) must be made after
the outdoor unit is installed and system
interconnection is complete.
Complete this checklist once the unit is installed to
28
verify that all recommended procedures have been
accomplished before the system is started. Operational
checks cannot be performed until the outdoor unit is
installed and system interconnection is complete.
Verify that the unit electrical power is disconnected.
Inspect all field wiring connections. All connections
should be clean and tight.
Inspect unit ground connection(s). Ground must
comply with all applicable codes.
Inspect unit suspension arrangement (if used). Unit
position must be secure. Remove any tools or
debris found in or near the unit.
Inspect duct outlets. Outlets must be open and
unrestricted.
Inspect unit drain lines. Pipe connections must be
tight and drain line unrestricted.
SSA-SVX06E-EN
RTRMJ-4
RTOMJ-1
FieldInstalledWires
T’stat
Air Handler
Disconnect Switch
(By Others)
Disconnect Switch
(By Others) Note 2
Electric
Heat Accessory
Disconnect Switch
(By Others)
B
A
B
D
C
IInnssttaallllaattiioonn
Inspect fan assembly to insure all moving parts
move freely.
If unit is horizontally mounted, make sure
secondary drain pan has been installed.
Inspect unit for proper filters, securely installed and
not touching the coil surface. All cabinet panels
must be secure.
Instruct owner/operator on proper system
operating and maintenance procedure.
Thermostat and Control
Connections
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer-supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
1. Observe all notes on the wiring diagrams.
2. Mount the thermostat or zone sensor in the desired
location.
3. Install color coded low voltage cables between
outdoor unit, indoor unit and thermostat. For
SZVAV units, install low voltage and
communication wires between the RTRM in the
condenser and the RTOM in the air handler. See
schematic and connection print for more detail.
4. Connect low voltage control wiring to the low
voltage terminal board located at the control box
per the typical interconnecting wiring diagrams. For
SZVAV units, connect the ReliaTel harness (supplied
with the air handler), between the RTRM and RTOM.
See Figure 24, p. 29.
Figure 24. RTOM to RTRM harness
Figure 25. Electromechanical jobsite connections
A.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
C.
Cooling only thermostat: 3 to 7 wires depending on stages of
electric heat
D.
3 to 7 wires depending on type of outdoor unit(s)
ReliaTel Controls
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
NNootteess::
1. When electric heater accessory is used,
single point power entry or dual point power
entry is field optional. Single point power
entry option is through electric heater only.
2. ***Choose only one of the following;
Thermostat, Zone Sensor, or NSB Panel.
Electromechanical Controls
Wiring shown with dashed lines is to be furnished and
installed by the customer. All customer supplied wiring
must be copper only and must conform to NEC and
local electrical codes. Codes may require line of sight
between disconnect switch and unit.
NNoottee:: When electric heater accessory is used, single
point power entry or dual point power entry is
field optional. Single point power entry option is
through electric heater only.
SSA-SVX06E-EN
29
NSB Panel
Zone
Sensor
T’stat
Air Handler
Disconnect Switch
(By Others)
Disconnect Switch
(By Others) Note 2
Electric
Heat Accessory
Disconnect Switch
(By Others)
Note 2
B
A
B
D
F
EC
IInnssttaallllaattiioonn
Figure 26. ReliaTel jobsite connections
A.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
B.
3 power wires, line voltage for 3 phase, (2 power wires for
single phase)
C.
Cooling only thermostat: 3 to 7 wires depending on stages of
electric heat
C.
Heat Pump thermostat: 5 to 8 wires depending on stages of
electric heat
D.
3 to 7 wires depending on type of outdoor unit(s)
E. Zone Sensor: 4 to 10 wires depending on zone sensor model
F.
Night Setback Panel: 7 wires
(a)
For SZVAV air handlers: 4 additional wires are required (2 of which
require twisted pair or shielded wire) in order to make connections
between ReliaTel boards in the condenser and air handler.
(a)
30
SSA-SVX06E-EN
Electrical Data
60 Hz Models
Includes Standard, SZVAV and 2–Speed VFD air
handlers.
Table 11. Voltage operating range (all air handlers)
Model Number:
Digit 8
1
3
4
K
W
Electrical
Characteristics
208-230/60/1
208-230/60/3
460/60/3
380/60/3
575/60/3
Table 12. Electrical characteristics — standard and low static motors — 60 Hz standard air handler
Standard Evaporator Fan MotorLow Static Evaporator Fan Motor
No. Volts Phase
120810.756.0 41.0 7.515
123010.755.9 45.0 7.415
120830.752.5 16.4 3.115
123030.752.4 16.4 3.015
146030.751.28.21.515
120811.56.8 31.5 8.520
123011.56.2 31.5 7.815
120831.55.3 34.3 6.615
123031.55.0 34.3 6.315
138031.53.0 20.2 3.815
146031.52.5 17.0 3.115
157531.51.8 13.6 2.315
1208128.557.4 10.620
1230127.757.4 9.620
1208327.033.9 7.815
1230326.633.9 7.315
1380323.328.0 4.115
1460323.319.0 3.615
1575322.315.6 4.015
1460322.823.0 3.415
1460334.639.3 5.815
Hp
FLA LRAFLA LRA
Tons
Model Number
5
7.5
TWE090DW, EW
10
TWE120D3, E3
TWE120DW, EW
12.5
15
Unit
TWE061D1, E1
TWE061D1, E1
TWE061D3, E3
TWE061D3, E3
TWE061D4, E4
TWE061DW157530.751.36.11.615
TWE090D1, E1
TWE090D1, E1
TWE090D3, E3
TWE090D3, E3
TWE090DK, EK
TWE090D3, E3
TWE120D1, E1
TWE120D1, E1
TWE120D3, E3
TWE120D3, E3
TWE120DK, EK
(a)
TWE150E31208326.023.0 7.415
TWE150E31230325.523.0 6.915
TWE150EK1380323.3 28.04.115
TWE150E3
TWE150EW1575322.2 18.02.815
TWE180E31208339.474.9 11.820
TWE180E31230339.274.9 11.520
TWE180EK1380358.1 63.5 10.115
TWE180E3
TWE180EW1575333.4 24.64.315
(a)
(a)
Unit Operating
Voltage Range
Amps
187-253
187-253
414-506
342-418
518-632
MCA MFS No. Volts Phase
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
N/AN/AN/AN/AN/A N/AN/AN/A
Hp
Amps
MCA MFS
SSA-SVX06E-EN
31
EElleeccttrriiccaall DDaattaa
Table 12. Electrical characteristics — standard and low static motors — 60 Hz standard air handler (continued)
Tons
20
25
Note: For additional information contact product support.
High Static Evaporator Fan MotorUltra-High Static Evaporator Fan Motor
No. Volts Phase
Hp
Amps
FLA LRAFLA LRA
MCA MFS No. Volts Phase
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
Hp
Amps
MCA MFS
Standard Evaporator Fan MotorHigh Static Evaporator Fan Motor
No. Volts Phase
1208326.243.48151208339.4711220
1230325.8488151230339.2641220
1460322.9244151460334.6 35.5615
1575322.220.63151575333.7 28.4515
Hp
Amps
FLA LRAFLA LRA
MCA MFS No. Volts Phase
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
N/AN/AN/AN/AN/AN/AN/A N/A
Hp
Amps
MCA MFS
SSA-SVX06E-EN
33
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz
Tons
Used With
TWE061D1,
5
TWE061E1
TWE061D3,
5
TWE061E3
TWE061D4,
5
TWE061E4
5TWE061DW
TWE090D1,
7.5
TWE090E1
TWE090D3,
7.5
TWE090E3
TWE090D3,
7.5
TWE090E3
TWE090DW,
7.5
TWE090EW
TWE120D1,
10
TWE120E1
TWE120D3,
10
TWE120E3
Heater Model
Number
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
Heater kW
Rating
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
BAYHTRL405*5.00
BAYHTRL410*9.96117.020.0
BAYHTRL415*14.96125.025.0
Unit Power
Supply
208-230/1/60
208-230/3/60
460/3/60
Control
Stages
Minimum Circuit
Ampacity
1
1
1
2
1
1
1
2
33.5/37.435.0/40.0
59.5/67.460.0/70.0
85.5/97.490.0/100.0
111.5/127.4
16.1/18.020.0/20.0
29.0/33.030.0/35.0
42.2/48.045.0/50.0
68.0/77.9
110.015.0
BAYHTRL425*24.92240.040.0
BAYHTRLW05*5.00
BAYHTRLW10*9.96115.015.0
BAYHTRLW15*14.96121.020.0
575/3/60
18.015.0
BAYHTRLW25*24.92233.035.0
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL129*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
21.63/28.80
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
BAYHTRL405*5.00
208-230/1/60
208-230/3/60
1
1
1
2
2
1
1
1
2
2
111.015.0
34.5/37.840.0/40.0
60.5/67.8
86.5/97.890.0/100.0
112.5/127.8
138.6/157.8
19.6/21.325.0/25.0
32.5/36.235.0/40.0
45.7/51.250.0/60.0
71.5/82.0
98.7/112
BAYHTRL410*9.96119.020.0
BAYHTRL415*14.96126.030.0
(c)
460/3/60
BAYHTRL425*24.92241.045.0
BAYHTRL435*34.88256.060.0
BAYHTRLW05*5.00
111.015.0
BAYHTRLW10*9.96117.015.0
BAYHTRLW15*14.96123.025.0
575/3/60
BAYHTRLW25*24.92236.035.0
BAYHTRLW35*34.88248.045.0
BAYHTRL106*
BAYHTRL112*
BAYHTRL117*
BAYHTRL123*
BAYHTRL129*
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
4.33/5.76
8.65/11.52
12.98/17.28
17.31/23.04
21.63/28.80
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
208-230/1/60
208-230/3/60
1
1
1
2
2
1
1
1
2
2
36.6/39.640.0/45.0
62.6/69.6
88.6/99.690.0/100.0
114.6/129.6
140.7/159.6
21.0/23.025.0/30.0
34.0/38.035.0/40.0
47.0/53.050.0/60.0
73.0/83.0
98.7/113.0
Maximum Fuse
or HACR Circuit
(a)
(a)
(a)
(a)
(a)
(a)
(b)
(a)
(a)
(a)
(a)
(b)
Breaker Size
125.0/150.0
70.0/80.0
70.0/70.0
125.0/150.0
150.0/175.0
80.0/90.0
100.0/125.0
70.0/70.0
125.0/150.0
150.0/175.0
80.0/90.0
100.0/125.0
34
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz
(continued)
Tons Used With
TWE120D3
10
TWE120E3
TWE120DW,
10
TWE120EW
12.5TWE150E3
TWE150E3
12.5
12.5 TWE150EW
15TWE180E3
TWE180E3
15
15TWE180EW
20TWE240E3
20TWE240E4
20TWE240EW
Heater Model
Number
BAYHTRL405*5.00
BAYHTRL410*9.96120.020.0
(c)
,
BAYHTRL415*14.96127.030.0
(c)
BAYHTRL425*24.92242.045.0
BAYHTRL435*34.88257.060.0
BAYHTRLW05*5.00
BAYHTRLW10*9.96116.015.0
BAYHTRLW15*14.96122.025.0
BAYHTRLW25*24.92235.035.0
BAYHTRLW35*34.88247.045.0
BAYHTRM310A
BAYHTRM320A
BAYHTRM330A
BAYHTRM350A
BAYHTRM410*10.00
BAYHTRM420*19.92134.035.0
(c)
BAYHTRM430*29.92249.050.0
BAYHTRM450*49.84279.080.0
BAYHTRMW10*10.00
BAYHTRMW20*19.92127.030.0
BAYHTRMW30*29.92239.040.0
BAYHTRMW50*49.84263.070.0
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM42*19.92136.040.0
(c)
BAYHTRM430*29.92251.060.0
BAYHTRM450*49.84281.090.0
BAYHTRMW10*10.00
BAYHTRMW20*19.92130.030.0
BAYHTRMW30*29.92242.045.0
BAYHTRMW50*49.84267.070.0
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.92139.040.0
BAYHTRM430*29.92254.060.0
BAYHTRM450*49.84284.090.0
BAYHTRMW10*10.00
BAYHTRMW20*19.92132.035.0
BAYHTRMW30*29.92245.045.0
BAYHTRMW50*49.84270.070.0
Heater kW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
Control
Stages
Minimum Circuit
Ampacity
112.015.0
110.015.0
1
1
2
2
119.020.0
115.015.0
1
1
2
2
121.025.0
117.020.0
1
1
2
2
124.030.0
120.025.0
33.5/36.935/40
59.3/66.860/70
85.5/96.890/100
137.3/156.7150/175
37.8/41.645.0/45.0
63.7/71.470.0/80.0
89.8/101.590.0/110.0
141.6/161.4
44.1/49.060.0/60.0
71.0/79.080.0/90.0
97.0/109.0100.0/110.0
149.0/169.0
Maximum Fuse
or HACR Circuit
Breaker Size
(b)
(b)
150.0/175.0
150.0/175.0
SSA-SVX06E-EN
35
EElleeccttrriiccaall DDaattaa
Table 15. Unit wiring with electric heat (single point connection) — 5-25 ton standard air handlers — 60 Hz
(continued)
Tons Used With
25TWE300E3
25TWE300E4
25TWE300EW
Notes:
1. kW ratings are at: 208/240V for 208-230V air handlers; 480V for 460V air handlers; 600V for 575V air handlers. For other than
rated voltage, capacity = (voltage/rated voltage)
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Electric heat not available with 380/60 Hz models.
4. The HACR circuit breaker is for U.S.A. installations only.
(a)
Field wire must be rated at least 75°C.
(b)
Field wire must be rated at least 90°C.
(c)
With motor field wired for 460V.
Heater Model
Number
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.92142.045.0
BAYHTRM430*29.92257.060.0
BAYHTRM450*49.84287.090.0
BAYHTRMW10*10.00
BAYHTRMW20*19.92134.035.0
BAYHTRMW30*29.92247.050.0
BAYHTRMW50*49.84272.080.0
Heater kW
Rating
7.51/10
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
208-230/3/60
460/3/60
575/3/60
2
x rated capacity.
Control
Stages
Minimum Circuit
Ampacity
1
1
2
2
127.030.0
122.025.0
51.0/53.060.0/90.0
77.0/83.085.0/90.0
103.0/113.0110.0/125.0
155.0/173.0175.0/175.0
Maximum Fuse
or HACR Circuit
Breaker Size
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —
60 Hz
TonsUsed With
7.5TWE090E3*3
7.5TWE090E4*4
7.5TWE090EW*3
TWE120D3*3, E3*3
10
Heater Model
Number
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
BAYHTRL305*5.00
BAYHTRL310*9.9611920
BAYHTRL315*14.9612730
BAYHTRL325*24.9224245
BAYHTRL335*34.8825760
BAYHTRLW05*5.00
BAYHTRLW10*9.9611620
BAYHTRLW15*14.9612225
BAYHTRLW25*24.9223435
BAYHTRLW35*34.8824750
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
Heater KW
Rating
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
Unit Power
Supply
208-230/3/60
460/3/60
575/3/60
208-230/3/60
Control
Stages
1
1
1
2
2
11215
1915
1
1
1
2
2
Minimum
Circuit
Ampacity
21/2325/25
34/3835/40
47/5350/60
73/8380/90
99/113100/125
21/2325/25
34/3835/40
47/5350/60
73/8380/90
99/113100/125
Maximum Fuse or
HACR Circuit
Breaker Size
36
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —
60 Hz (continued)
TonsUsed With
TWE120D3*4, E3*4
10
TWE120D4*3, E4*3
10
TWE120D4*4, E4*4
10
TWE120DW*3, EW*3
10
TWE120DW*4, EW*4
10
12.5TWE150E3*3
12.5TWE150E3*4
12.5TWE150E4*3
12.5TWE150E4*4
12.5TWE150EW*3
Heater Model
Number
BAYHTRL305*
BAYHTRL310*
BAYHTRL315*
BAYHTRL325*
BAYHTRL335*
BAYHTRL405*5.00
BAYHTRL410*9.9611920
BAYHTRL415*14.9612730
BAYHTRL425*24.9224245
BAYHTRL435*34.8825760
BAYHTRL405*5.00
BAYHTRL410*9.9612125
BAYHTRL415*14.9612930
BAYHTRL425*24.9224445
BAYHTRL435*34.8825960
BAYHTRLW05*5.00
BAYHTRLW10*9.9611620
BAYHTRLW15*14.9612225
BAYHTRLW25*24.9223435
BAYHTRLW35*34.8824750
BAYHTRLW05*5.00
BAYHTRLW10*9.9611820
BAYHTRLW15*14.9612425
BAYHTRLW25*24.9223640
BAYHTRLW35*34.8824950
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.9213435
BAYHTRM430*29.9224950
BAYHTRM450*49.8427980
BAYHTRM410*10.00
BAYHTRM420*19.9213840
BAYHTRM430*29.9225360
BAYHTRM450*49.8428390
BAYHTRMW10*10.00
BAYHTRMW20*19.9212830
BAYHTRMW30*29.9224145
BAYHTRMW50*49.8426670
Heater KW
Rating
3.76/5.00
7.48/9.96
11.24/14.96
18.72/24.92
26.20/34.88
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
Control
Stages
1
1
1
2
2
11215
11415
1915
11115
1
1
2
2
1
1
2
2
11920
12325
11620
Minimum
Circuit
Ampacity
25/2730/30
38/4240/45
38/5740/60
77/8780/90
103/117110/125
34/3835/40
60/6860/70
86/9890/100
138/158150/175
43/4745/50
69/7770/80
95/107100/110
147/167150/175
Maximum Fuse or
HACR Circuit
Breaker Size
SSA-SVX06E-EN
37
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —
60 Hz (continued)
TonsUsed With
12.5TWE150EW*4
15TWE180E3*3
15TWE180E3*4
15TWE180E4*3
15TWE180E4*4
15TWE180EW*3
15TWE180EW*4
20TWE240E3*3
20TWE240E3*4
20TWE240E4*3
20TWE240E4*4
Heater Model
Number
BAYHTRMW10*10.00
BAYHTRMW20*19.9213235
BAYHTRMW30*29.9224445
BAYHTRMW50*49.8426970
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.9213640
BAYHTRM430*29.9225160
BAYHTRM450*49.8428190
BAYHTRM410*10.00
BAYHTRM420*19.9213840
BAYHTRM430*29.9225360
BAYHTRM450*49.8428390
BAYHTRMW10*10.00
BAYHTRMW20*19.9213030
BAYHTRMW30*29.9224345
BAYHTRMW50*49.8426870
BAYHTRMW10*10.00
BAYHTRMW20*19.9213235
BAYHTRMW30*29.9224445
BAYHTRMW50*49.8426970
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.9213840
BAYHTRM430*29.9225360
BAYHTRM450*49.8428390
BAYHTRM410*10.00
BAYHTRM420*19.9214145
BAYHTRM430*29.9225660
BAYHTRM450*49.8428690
Heater KW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
Unit Power
Supply
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
575/3/60
575/3/60
208-230/3/60
208-230/3/60
460/3/60
460/3/60
Control
Stages
11920
1
1
2
2
1
1
2
2
12125
12325
11820
11920
1
1
2
2
1
1
2
2
12325
12630
Minimum
Circuit
Ampacity
38/4240/45
64/7270/80
90/10290/110
142/162150/175
43/4745/50
69/7770/80
95/107100/110
147/167150/175
43/4745/50
69/7770/80
95/107100/110
147/167150/175
51/5560/60
77/8580/90
103/115110/125
155/175175/175
Maximum Fuse or
HACR Circuit
Breaker Size
38
SSA-SVX06E-EN
EElleeccttrriiccaall DDaattaa
Table 16. Unit wiring with electric heat (single point connection) — 7.5-25 ton SZVAV and 2-Speed VFD air handlers —
60 Hz (continued)
TonsUsed With
20TWE240EW*3
20TWE240EW*4
25TWE300E3*3
25TWE300E4*3
25TWE300EW*3
Notes:
1. kW ratings are at: 208/240V for 208-230V air handlers; 480V for 460V air handlers; 600V for 575V air handlers. For other than rated
voltage, capacity = (voltage/rated voltage)
2. Any power supply and circuits must be wired and protected in accordance with local codes.
3. Electric heat not available with 380/60 Hz models.
4. The HACR circuit breaker is for U.S.A. installations only.
Heater Model
Number
BAYHTRMW10*10.00
BAYHTRMW20*19.9213235
BAYHTRMW30*29.9224445
BAYHTRMW50*49.8426970
BAYHTRMW10*10.00
BAYHTRMW20*19.9213435
BAYHTRMW30*29.9224750
BAYHTRMW50*49.8427280
BAYHTRM310*
BAYHTRM320*
BAYHTRM330*
BAYHTRM350*
BAYHTRM410*10.00
BAYHTRM420*19.9214145
BAYHTRM430*29.9225660
BAYHTRM450*49.8428690
BAYHTRMW10*10.00
BAYHTRMW20*19.9213435
BAYHTRMW30*29.9224750
BAYHTRMW50*49.8427280
Heater KW
Rating
7.51/10.00
14.96/19.92
22.47/29.92
37.44/49.84
2
x rated capacity.
Unit Power
Supply
575/3/60
575/3/60
208-230/3/60
460/3/60
575/3/60
Control
Stages
11920
12225
1
1
2
2
12630
12225
Minimum
Circuit
Ampacity
51/5560/60
77/8580/90
103/115110/125
155/175175/175
Maximum Fuse or
HACR Circuit
Breaker Size
SSA-SVX06E-EN
39
EElleeccttrriiccaall DDaattaa
50 Hz Models
Includes standard air handlers
Table 17. Electrical characteristics — standard motor — 50 Hz air handler
Standard Evaporator Fan Motor
TonsUnit Model Number
4.6TWE051DD
6.25
8.33
10.4TWE126ED
13TWE156ED
16.7TWE201ED
20.9TWE251ED
TWE076DD, ED
TWE101DD, ED
No.VoltsPhase
138031.48.0
141531.08.4
138033.117.0
141533.216.8
138033.417.3
141533.219.0
138033.235.0
141533.135.0
138034.033.1
141534.036.1
138038.043.2
141538.048.6
138037.571.0
141537.277.0
Amps
FLALRA
Table 18. Unit wiring — air handler — 50 Hz
Tons
4.6TWE051DD
6.25
8.33
10.4TWE126ED
13TWE156ED
16.7TWE201ED
20.9TWE251ED
Unit Model
Number
TWE076DD, ED
TWE101DD, ED
Minimum Unit Operating
Voltage Range
380/415
380/415
380/415
380/415
380/415
380/415
380/415
Maximum Fuse
Circuit Ampacity
Ampacity
415
515
515
515
615
1015
1015
Size or Maximum
Circuit Breaker
Table 19. Unit wiring with electric heat (single point connection) — air handlers
Heater
Model No.
BAYHTRL405*5
BAYHTRL410*9.9612225
BAYHTRL415*14.9613135
BAYHTRL425*24.9224950
BAYHTRL405*5
BAYHTRL410*9.9612325
BAYHTRL415*14.9613235
BAYHTRL425*24.9225050
BAYHTRL435*34.8826870
Heater
kW Rating
To Use
with Unit
TWE051DD
TWE076DD, ED
Control
Stages
11315
11415
Minimum
Circuit
Ampacity
Maximum
Fuse Breaker
Size
40
SSA-SVX06E-EN
Table 19. Unit wiring with electric heat (single point connection) — air handlers (continued)
EElleeccttrriiccaall DDaattaa
BAYHTRL405*5
BAYHTRL410*9.9612325
BAYHTRL415*14.9613235
BAYHTRL425*24.9225050
BAYHTRL435*34.8826870
BAYHTRM410*10
BAYHTRM420*19.9214145
BAYHTRM430*29.9225960
BAYHTRM450*49.84294100
BAYHTRM410*10
BAYHTRM420*19.9214145
BAYHTRM430*29.9225960
BAYHTRM450*49.84295100
BAYHTRM410*10
BAYHTRM420*19.9214650
BAYHTRM430*29.9226570
BAYHTRM450*49.842100100
BAYHTRM410*10
BAYHTRM420*19.9214650
BAYHTRM430*29.9226570
BAYHTRM450*49.842100100
Notes:
1. Field wire must be rated at least 167°F (75°C).
2. Field wire must be rated at least 194°F (90°C).
3. Heater kW ratings are at 400v for 3 phase, 400v air handlers.
4. For other than rated voltage, capacity = (voltage/rated voltage)2 x rated capacity and kW = (voltage/rated voltage)
2 rated kW.
5. Any power supply and circuits must be wired and protected in accordance with local codes.
Units configured for SZVAV control will utilize Supply
Fan Mode selection as is currently implemented into
ReliaTel controls for normal Zone Control and will be
selectable between AAUUTTOO and OONN via a connected
Zone Sensor module or through BAS/Network
controllers.
Supply Fan Mode Auto Operation
For active Cooling, and Heating operation the Supply
Fan will be commanded OONN and will ramp up to the
appropriate minimum speed once the unit determines
that there is a request for capacity control. Once the
active request is cleared and all capacity is deenergized normal supply fan off delays as implemented
on constant volume units will be in effect. During the
Supply Fan Off-Delay, the supply fan will remain
energized for the predetermined time at the previous
unit function's minimum speed. All other cases which
would bring the Supply Fan OONN will function as on
non-SZVAV units.
Supply Fan Mode ON Operation
For active unit control with the Supply Fan Mode set to
OONN, the unit will energize the Supply Fan and hold the
Fan Speed output at minimum speed until there is a
request for the fan speed to increase. This will hold true
for all cases except during Unoccupied periods in
which the Supply Fan Mode is forced to AAUUTTOO and will
operate the Supply Fan as described above for all
Cooling, and Heating requests.
Supply Air Temperature Control - Cooling
For Cooling operation the unit will control the active
capacity outputs to meet a varying, calculated
Discharge Air Setpoint that is calculated based on zone
conditions in order to maintain the Zone Temperature
to the active Zone Setpoint. Note that this setpoint will
be clamped between the user selected DA Heat and DA
Cool setpoints for compressor control. In general, as
the zone temperature rises above the ZCSP, the Active
Discharge Air Setpoint will be calculated down. This
calculated setpoint is a direct indication of space
demand and is also used to determine the proper
supply fan speed to meet the space requirements.
During active capacity control, the unit will utilize a +/-
3.5°F deadband around the active Discharge Air
Setpoint to determine when to request additional
cooling capacity. If the unit is maintaining the discharge
air temperature within the +/- 3.5°F deadband around
the calculated discharge air setpoint requirements, no
additional capacity will be requested.
Occupied Cooling Operation
For normal Cooling operation, available Cooling
capacity will be staged or modulated in order to meet
the calculated discharge air setpoint between the user
selected upper and lower limits. If the current active
cooling capacity is controlling the discharge air within
the deadband no additional Cooling capacity change
will be requested. As the Discharge Air Temperature
rises above the deadband the control will request
additional capacity as required (additional compressor
operation). As the Discharge Air Temperature falls
below the deadband the algorithm will request a
reduction in active capacity.
Compressor Cooling
Compressor output control and protection schemes
will function similar to non-SZVAV units. Normal
compressor HPC and LPC control will remain in effect
as well as normal 3-minute minimum on, off, and interstage timers. Also, the condenser fans will be
controlled similar to non-SZVAV units.
Cooling Sequence
If the control determines that there is a need for
compressor stages in order to meet the discharge air
requirements, once supply fan proving has been made,
the unit will begin to stage compressors accordingly.
Note that a 5 second delay will be enforced between
the command for supply fan output operation and the
command for compressor output operation. This delay
is enforced to ensure that the supply fan is energized
and ramping up to operating speed prior to energizing
compressors.
As the zone cooling demand continues to increase, if
additional capacity is required, the supply fan output
will be modulated above minimum speed in order to
meet the zone requirements. Note that the supply fan
speed will remain at the compressor stage's associated
minimum value until the control requires additional
capacity to meet the zone demand.
As the cooling load in the zone decreases the control
will reduce the speed of the fan down to minimum per
compressor stage and control the compressor outputs
accordingly. As the compressors begin to de-energize,
the Supply Fan speed will fall back to the Cooling
Stage's associated minimum fan speed but not below.
As the load in the zone continues to drop, cooling
42
SSA-SVX06E-EN
SSttaarrtt--UUpp
capacity will be reduced in order to maintain the
calculated discharge air setpoint.
Cooling Stages Minimum Fan Speed
As the unit begins to stage compressors to meet the
cooling demand, the following minimum Supply Fan
Speeds will be utilized for each corresponding Cooling
Stage. Note that the Supply Fan Speed will be allowed
to ramp up beyond the minimum speed in order to
meet the zone cooling demand. The minimum fan
speed for units with 2 stages of DX Cooling will be 58%
of the unit's full airflow capacity. At Stage 1 of DX
Cooling the Fan Speed will be at a minimum of 58%
and at Stage 2 of DX Cooling the Fan Speed will be at a
minimum of 80%.
Occupied Heating Operation
Occupied Heating operation on units configured with
SZVAV control will utilize two separate control
methodologies based on heating configurations. For all
"Staged" Heating types (Electric and Gas), the unit will
utilize 100% full airflow during all active heating
periods like traditional Constant Volume units. For
Modulating Gas heat units, the unit will have the ability
to control the discharge air temperature to the
calculated discharge air heating setpoint in order to
maintain the Zone Temperature to the Zone Heating
setpoint.
Staged Heating Operation
For units configured with Mechanical or Auxiliary Heat
once the control determines that there is an active
heating capacity request, the unit will energize the
Supply Fan and ramp up to full speed. The control
methodology during Active Heating will be identical to
traditional Constant Volume units; heating stages will
be energized/de-energized to meet the Zone Heating
demand. Note that all Electric staging sequences will
be identical to Constant Volume units.
Unoccupied Cooling and Heating Operation
For SZVAV units, the unit will control Heating and
Cooling, as during Occupied periods using the normal
heating and cooling SZVAValgorithms. In Unoccupied
periods the unit will utilize setback setpoints, and Auto
fan mode operation as on normal Constant Volume
units.
Failure and Overriding Conditions
Certain failure and overriding conditions require
special handling of the Supply Fan Speed on units
configured with SZVAV. See below for a list of these
conditions:
1. SSuuppppllyy FFaann PPrroovviinngg FFaaiilluurree - If a Supply Fan
Proving failure is detected the Supply Fan will be
de-energized after 40s of run time and the Fan
Speed output will go to the corresponding
minimum speed voltage.
2. ZZoonnee TTeemmppeerraattuurree SSeennssoorr FFaaiilluurree - If the Active
Zone Temperature input goes out of range, the unit
will discontinue all Heating, Cooling, and
Dehumidification operation.
3. SSuuppppllyy AAiirr TTeemmppeerraattuurree SSeennssoorr FFaaiilluurree - If the
Supply Air Temperature input goes out of range,
the unit will revert back to Full Airflow, Traditional
CV control. The unit will call out a Supply Air
Temperature Sensor Failure Alarm, the RTRM
System LED will flash the 2-blink error code, and
Cool LEDs will flash.
2–Speed VFD Applications
General Description of Functionality
Cooling Operation (DX Cooling)
Units with a 2-Speed VFD control scheme will utilize a
thermostat's heating and cooling outputs to
differentiate between high and low speed. When the
unit receives a G or Y1 call from the thermostat the
supply fan will run at the user selected low speed. Once
the zone load demands the second stage of cooling,
and the unit receives the Y2 call from the thermostat
the supply fan will be signaled to run at the user
selected high speed. All other compressor staging will
be handled the same as all standard thermostat
controlled units.
Heating Operation
Units with 2-Speed VFD controls will utilize traditional
CV Heating control schemes with full airflow provided
based on the customer selected VFD controlled
maximum speed. When the unit receives the W1 call
from the thermostat a relay will signal the supply fan to
run at high speed. All the electric heaters that can be
outfitted in the field are wired up to interlock W1 and
W2 so the supply fan will always run at the user
selected high speed during heat modes.
SSA-SVX06E-EN
43
Maintenance
Perform all of the indicated maintenance procedures at
the intervals scheduled. This will prolong the life of the
unit and reduce the possibility of costly equipment
failure.
The fan belts must be inspected periodically to assure
proper unit operation. Replacement is necessary if the
belts appear frayed or worn.
When removing or installing the new belts, do not
stretch them over the sheaves. Loosen the belts using
the belt tension adjustment bolts on the motor
mounting base.
Once the new belts are installed, using a Browning or
Gates tension gauge (or equivalent), adjust the belt
tension as follows:
1. To determine the appropriate belt deflection:
a. Measure the center-to-center shaft distance (in
inches) between the fan and motor sheaves.
b. Divide the distance measured in Step 1a by 64;
the resulting value represents the amount of
belt deflection that corresponds to the proper
belt tension.
2. Set the large O-ring on the belt tension gauge at the
deflection value determined in Step 1b.
3. Set the small O-ring at zero on the force scale of the
gauge plunger.
4. Place the large end of the gauge at the center of the
belt span; then depress the gauge plunger until the
large O-ring is even with the top of the next belt or
even with a straightedge placed across the fan and
motor sheaves.
5. Remove the belt tension gauge. The small
O-ring now indicates a number other than zero on
the plunger’s force scale. This number represents
the force (in pounds) required to give the needed
deflection.
6. Compare the “force” scale reading (Step 5) with the
appropriate “force” value listed in the Belt tension
table. If the “force” reading is outside the range,
readjust the belt tension.
NNoottee:: Actual belt deflection “force” must not
exceed the maximum “force” value shown in
Figure 27, p. 44.
Recheck the belt tension at least twice during the
first 2 to 3 days of operation. Belt tension may
decrease until the new belts are “run in”.
Figure 27. Belt tension gauge
Table 20. Belt tension measurement and deflection
Belts Cross
Section
A
B
Small Pitch
Diameter Range
3.0 - 3.63
3.8 - 4.8
5.0 - 7.04
3.4 - 4.24
4.4 - 5.6
5.8 - 8.8
Standard V-BeltV-Belt with Molded Notches
Min.Max.Min.Max.
3-1/2
5-1/87-1/86-1/29-1/8
6-3/88-3/47-3/810-1/8
Monthly
The following warning complies with State of
California law, Proposition 65.
Conduct the following maintenance inspections once
per month:
Inspect air filters and clean (or replace) if necessary.
Check unit wiring to ensure all connections are tight
and that the wiring insulation is intact.
Check drain pans and condensate piping to insure
they are free of obstacles.
Manually rotate the indoor fan to ensure proper
operation.
Inspect the evaporator coils for dirt and debris. If
the coils appear dirty, clean them.
Observe indoor fan operation and correct any
unusual or excessive vibration. Clean blower
wheels as needed.
Annually (Cooling Season)
The following maintenance procedures must be
performed at the beginning of each cooling season to
ensure efficient unit operation:
Perform all of the monthly maintenance
inspections.
With the unit operating, check unit superheat and
record the reading in the “Maintenance Log,” p. 46
Remove any accumulation of dust and/or dirt from
the unit casing.
Remove corrosion from any surface and repaint.
Check the gasket around the control panel door to
ensure it fits correctly and is in good condition to
prevent water leakage.
Inspect the evaporator fan belt. If it is worn or
frayed, replace it.
Inspect the control panel wiring to ensure that all
connections are tight and that the insulation is
intact.
Check refrigerant piping and fittings for leaks.
Inspect the evaporator coils for dirt and debris. If
the coils appear dirty, clean them.
Coil Cleaning
Regular coil maintenance, including annual cleaningenhances the unit's operating efficiency by minimizing:
•compressor head pressure and amperage draw
•water carryover
•fan brake horsepower
•static pressure losses
At least once each year — or more often if the unit is
located in a “dirty” environment — clean the coil using
the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging
the coils.
SSA-SVX06E-EN
45
MMaaiinntteennaannccee
Maintenance Log
Subcooling (°F)
(at service valve)
Superheat (°F)
(at compressor)
Circuit #1Circuit #2Circuit #1Circuit #2
Discharge Pressure
(C1)(C2)(C1)(C2)
Suction Pressure
Wet
Bulb
Dry
Bulb
Evaporator Entering AirCompressor
(°F)
Temp.
Ambient
Date
Note: Perform each inspection once per month (during cooling season) while unit is operating
Note: Wiring diagrams are available through e-Library or by contacting your local sales office.
CircuitVolts Hz
Ph
Schematic/
Connection
Electromechanical
(2 speed)
Reliatel
SchematicConnectionSchematicConnection
N/AN/AN/AN/A
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice.