Page 1
Insight
™
Ducted Air Handler
Product Data
Heat Pump Split System Air Conditioning
30 to 50 MBh - 50 Hz
Air Handler Models
TWE030CA
TWE040CA
TWE050CA
Condensing Models
TWJ020-036CA
TWA030-060CD
TWE-PRC001-EN-10-15-99
Page 2
TWE
Features and
Benefits
Air Handling Units
Features
• Ships horizontal
• Six way convertibility-horizontal (left and
right), upflow, downflow (front and rear
access)
• Electrical, refrigerant, condensate and
blower access convertible to either side
• Corrosion resistant galvanized steel
with attractive finish
• Internally enhanced finned coil tubes
• Direct drive motor
• Standard filters
• Multi-speed blower
• 220 volt primary and 24 volt secondary
transformer
• Insulated cabinet
• External access to heater circuit
breakers
• Start kits are not required
• Built-in indoor fan delay function for
increased efficiency. No kit required.
New Features
• Improved filter access and latch Eliminate current T-bar and shipping
bracket.
• Provision for 1-1/8 inches thick field
supplied electrostatic filter
• Reversible Duct Flanges - Fits up to
1-1/2 inches duct board
• Improve controls access with control
box mounted next to blower.
• 40 VA transformer with 5 amp automotive style fuse on 3 tons and less
• 5 Amp automotive style fuse replaces
Bussman “red cap” fuse on 3.5 to 5 ton
models
• Blower mounting brackets improved Front access to screw with power driver
• Improved bottom carton cushioning
• 1 inch thick foil faced insulation for all
models
TWJ
©American Standard Inc. 1999 TWE5-PRC001-EN-10-15-99
TWA
Condensing Units
Features:
• Vertical Air Discharge
• High Efficiency TRANE Climatuff
Compressor
• Powder Paint finish
• Brazed connections
• Spine Fin™ Outdoor Coil
• Switchover Valves
Benefits:
• Flexibility in application
®
• Quality and reliability
• Uniform covering for a smooth, attractive
and corrosion-resistant finish
Page 3
Contents
Features and Benefits 2
Air Handling Units 2
Condensing Units 2
System Performance 4
Selection Procedure 4
Model Number Nomenclature 4
General Data 5
TWE030CA40B 5
TWE040CA40C 5
TWE050CA50D 5
TWJ020CA00A0 6
TWJ024CA00A0 6
TWJ030CA00A0 6
TWJ036CA00A0 6
TWA030CD00A0 7
TWA040CD00A0 7
TWA050CD00A0 7
TWA060CD00A0 7
TWE5-PRC001-EN-10-15-99 3
Performance Data 8
TWJ/TWE Cooling 8
TWA/TWE Cooling 12
TWJ/TWE Heating 16
TWA/TWE Heating 20
Evaporator Fan Performance 24
Air Pressure Drop 26
Supplementary Heaters 27
Electrical Data 28
Dimensions 29
Convertibility 31
Mechanical Specification Options 32
Page 4
System
Performance
Cooling Capacity
95° F (35° C)
Outdoor Unit Indoor Unit CFM CMH MBh Kw
Ducted Air Handlers
TWJ020CA00A TWE030CA00A 700 1185 20 6
TWJ024CA00A TWE030CA00A 900 1520 27 8
TWJ030CA00A TWE030CA00A 1000 1690 31 9
TWJ030CA00A TWE040CA00A 1100 1860 33 9.5
TWJ036CA00A TWE030CA00A 1100 1860 38 11
TWJ036CA00A TWE040CA00A 1325 2240 40.5 11.5
TWJ036CA00A TWE050CA00A 1400 2360 41.6 12
TWA030CD00A TWE030CA00A 1000 1690 32 9
TWA030CD00A TWE040CA00A 1100 1860 34 9.6
TWA040CD00A TWE040CA00A 1300 2200 42 12
TWA040CD00A TWE050CA00A 1500 2535 43 12.5
TWA050CD00A TWE050CA00A 1800 3040 51 14.5
TWA060CD00A TWE050CA00A 1800 3040 63 18
123456 7891 01 11 2
TWE030CA40A0
PRODUCT TYPE
TW= Split System Component
Heat Pump Compatible
AIRFLOW CONFIGURATION
E = Convertible
REFRIGERANT CONNECTIONS
0= Brazed
Selection
Procedure
Model Number Nomenclature
NOMINAL NET COOLING
CAPACITY
30 = 30 MBh
40 = 40 MBh
50 = 50 MBh
PRODUCT
SERVICE CHANGE
MINOR DESIGN
MODIFICATION
NOT USED
REFRIGERANT FLOW CONTR OL
4 = Accutron™ Flow Control/Check Valve
5 = Bleed TXV
ELECTRICAL CHARACTERISTICS
A = 220V/1/50
MAJOR DESIGN MODIFICATION
4 TWE5-PRC001-EN-10-15-99
Page 5
General
Data TWE
TWE Product Specifications
Model TWE030CA40B TWE040CA40C TWE050CA50D
Power Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50
Indoor Coil - Type Plate Fin Plate Fin Plate Fin
Rows 3 3 3
Fins per inch (Fins per 25.4 mm) 14 14 14
Face Area sq ft (sq m) 3.21 (.30) 5.04 (.47) 6.19 (.58)
Tube Size in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Refrigerant Control FCCV FCCV FCCV
Drain Conn. Size in. (mm) 3/4 NPT 3/4 NPT 3/4 NPT
Duct Connections See Outline Drawing See Outline Drawing See Outline Drawing
Indoor Fan - Type Centrifugal Centrifugal Centrifugal
No. Used 1 1 1
Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4)
Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0)
Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3
Airflow (High)
CFM @ 0.0 in. w.g. See Fan Performance Table See Fan Performance Table See Fan Performance Table
CMH @ 0.0 Pa See Fan Performance Table See Fan Performance Table See Fan Performance Table
No. Motors - HP 1 - 1/3 1 - 1/3 1 - 3/4
Motor RPM 1000 900 900
Volts/Ph/Hz 220/1/50 220/1/50 220/1/50
F.L. Amps 2.6 2.1 4.5
L.R. Amps 3.3 4.2 10.1
Filters
Vertical Applications
Filter Furnished Yes Yes Yes
Type Furnished Throwaway Throwa w ay High Velocity
No.-Size-Thic kness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1
Horizontal Applications
Filter Furnished No No No
Type Recommended See Note Below See Note Below See Note Below
No.-Size-Thic kness See Note Below See Note Below See Note Below
Refrigerant Line Size
Line Size ID Gas in. (mm) 7/8 (22.23) 1-1/8 (28.56) 1-1/8 (28.56)
Line Size ID Liquid in. (mm) 3/8 (9.52) 3/8 (9.52) 3/8 (9.52)
Dimensions (H x W x D)
Crated- in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5
- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597)
Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0
Weight Ibs. (kg)
Shipping 125 (56.7) 165 (74.8) 198 (898)
Net 115 (52.2) 150 (68.0) 183 (83.0)
Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter : Face Area (sq ft) = CFM/300
High Velocity Filter: Face Area (sq ft) = CFM/500
- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)
TWE5-PRC001-EN-10-15-99 5
Page 6
General
Data TWJ
12
TWJ030CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
®
1 - 1
200/230/1/50
19 - 94
PROPELLER
1
18 (457)
DIRECT - 1
1975
932
1 - 1/5
900
200/230/1/60/50
1.60
SPINE FIN™
1
24 (.945)
16.84 (1.56)
3/8 (9.52)
6 LBS., 12 OZ. (3.06)
YES
7/8 (22.2)
3/8 (9.52)
Model
Po wer Conn. - Volts/Ph/Hz
Fuse Size - max. amps
Compressor - Type
No. Used - No. Speeds
V olts/Ph/Hz
F.L. Amps - L.R. Amps
Outdoor Fan - Type
No. Used
Diameter in. (mm)
Type Drive - No. Speeds
CFM @ 0.0 in. w.g.
3
(M) 3/HR. @ 0.0 mm w.g.
No. Motors - HP
Motor Speed (RPM)
V olts/Ph/Hz
F.L. Amps
Outdoor Coil - Type
No. Rows
Fins/in. (mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant
R-22 (O.D. Unit)
4
- lbs. (kg)
Factory Supplied
5
Line Size - OD Gas
Line Size - OD Liq.
in. (mm)
5
in. (mm)
TWJ020CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
1 - 1
200/230/1/50
10 - 60
PROPELLER
1
18 (457)
DIRECT - 1
1503
3
709
1 - 1/8
690
200/230/1/60/50
0.90
SPINE FIN™
1
24 (.945)
12.22 (1.14)
3/8 (9.52)
5 LBS., 4 OZ (2.38)
YES
3/4 (19.1)
5/16 (7.94)
TWJ Product Specifications
TWJ024CA00A0
200/230/1/60
®
PER LOCAL CODES
CLIMATUFF
®
1 - 1
200/230/1/50
17.9 - 69
PROPELLER
1
18 (457)
DIRECT - 1
1987
938
1 - 1/5
1075
200/230/1/50
1.60
SPINE FIN™
1
24 (.945)
16.84 (1.56)
3/8 (9.52)
4 LBS, 13 OZ. (2.18)
YES
3/4 (19.1)
5/16 (7.94)
FCCV
Restrictor Orifice Size in. (mm)
0.051 (1.30)
0.061 (1.55)
0.065 (1.65)
Dimensions (H x W x D)
Crated- in.
- (mm)
Uncrated
25 X 26-1/2 X 30
(635 X 673 X 762)
SEE OUTLINE DRAWINGS
33-1/4 X 30 X 26-1/2
(845 X 762 X 673)
SEE OUTLINE DRAWINGS
33-1/4 X 26-1/2 X 30
(845 X 673 X 762)
SEE OUTLINE DRAWINGS
Weight lbs. (kg)
Shipping
Net
NOTES:
1
RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
2
RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
3
STANDARD AIR - DRY COIL - OUTDOOR
4
THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5
MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
170 (77.1)
162 (73.5)
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
187 (84.8)
178 (80.7)
214 (97.1)
205 (93.0)
TWJ036CA00A0
200/230/1/60
PER LOCAL CODES
CLIMATUFF
®
1 - 1
200/230/1/60/50
21.9 - 95
PROPELLER
1
22 (559)
DIRECT - 1
2748
1297
1 - 1/4
900
200/230/1/50
1.40
SPINE FIN™
1
24 (.945)
23.11 (2.15)
3/8 (9.52)
8 LBS., 2 OZ. (3.69)
YES
7/8 (22.2)
3/8 (9.52)
0.073 (1.85)
37-1/2 X 34-3/4 X 30-1/2
(953 X 883 X 775)
SEE OUTLINE DRAWINGS
252 (114)
238 (108)
6 TWE5-PRC001-EN-10-15-99
Page 7
General
Data TWA
12
TW A050CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
®
1 - 1
380/415/3/50
9 - 71
PROPELLER
1
26 (660)
DIRECT - 1
3141
1482
1 - 1/3
825/690
460/1/60/50
1.0
SPINE FIN™
1
24 (.945)
28.91 (2.69)
3/8 (9.52)
10 LBS.,9 OZ. (4.79)
YES
1-1/8 (3.18)
3/8 (9.52)
Model
Po wer Conn. - Volts/Ph/Hz
Fuse Size - max. amps
Compressor - Type
No. Used - No. Speeds
Volts/Ph/Hz
F.L. Amps - L.R. Amps
Outdoor Fan - Type
No. Used
Diameter in. (mm)
Type Drive - No. Speeds
CFM @ 0.0 in. w.g.
3
(M) 3/HR. @ 0.0 mm w.g.
No. Motors - HP
Motor Speed (RPM)
Volts/Ph/Hz
F.L. Amps
Outdoor Coil - Type
No. Rows
Fins/in. (mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant
R-22 (O.D. Unit)
4
- lbs. (kg)
Factory Supplied
5
Line Size - OD Gas
Line Size - OD Liq.
5
in. (mm)
in. (mm)
TWA030CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
1 - 1
380/415/3/50
5 - 51
PROPELLER
1
18 (457)
DIRECT - 1
1976
3
933
1 - 1/4
1075/900
460/1/60/50
0.80
SPINE FIN™
1
24 (.945)
16.84 (1.56)
3/8 (9.52)
6 LBS.,12 OZ. (3.06)
YES
7/8 (22.2)
3/8 (9.52)
TW A Pr oduct Specifications
TW A040CD00A0
380/415/3/60
®
PER LOCAL CODES
CLIMATUFF
®
1 - 1
380/415/3/50
7 - 51
PROPELLER
1
22 (559)
DIRECT - 1
2738
1292
1 - 1/3
825/690
460/1/60/50
1.0
SPINE FIN™
1
24 (.945)
20.32 (1.89)
3/8 (9.52)
8 LBS.,13 OZ. (4.00)
YES
1-1/8 (3.18)
3/8 (9.52)
FCCV
Restrictor Orifice Size in. (mm)
0.065 (1.65)
0.075 (1.91)
0.086 (2.18)
Dimensions (H x W x D)
Crated- in.
- (mm)
Uncrated
33-1/4 X 30 X 26-1/2
(845 X 762 X 673)
SEE OUTLINE DRA WINGS
33-1/4 X 34-3/4 X 30-1/2
(845 X 883 X 775)
SEE OUTLINE DRA WINGS
37-1/2 X 40-3/4 X 36-1/2
(953 X 1035 X 927)
SEE OUTLINE DRA WINGS
Weight lbs. (kg)
Shipping
Net
NOTES:
1
RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
2
RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
3
STANDARD AIR - DRY COIL - OUTDOOR
4
THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5
MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
219 (99.3)
210 (95.3)
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
251 (114)
239 (108)
308 (140)
293 (133)
TW A060CD00A0
380/415/3/60
PER LOCAL CODES
CLIMATUFF
®
1 - 1
380/415/3/50
10.6 - 64
PROPELLER
1
26 (660)
DIRECT - 1
3931
1855
1 - 1/3
825
460/1/60/50
1.7
SPINE FIN™
2
24 (.945)
35.39 (3.29)
3/8 (9.52)
16 LBS.,12 OZ. (7.60)
YES
1-1/8 (3.18)
3/8 (9.52)
0.086 (2.18)
45-1/2 X 41 X 37
(1156 X 1041 X 940)
SEE OUTLINE DRA WINGS
395 (179)
376 (171)
TWE5-PRC001-EN-10-15-99 7
Page 8
Performance
Data Cooling English Units
TWJ020CA WITH TWE030CA4 A T 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 18.2 15.5 16.7 18.0 18.6* 19.1* 1.34
85 63 19.7 13.0 14.3 15.5 16.8 18.1 1.39
67 21.2 10.3 11.6 12.8 14.1 15.4 1.44
71 22.7 7.5 8.8 10.1 11.3 12.6 1.49
59 17.9 15.3 16.6 17.8 18.4* 18.8* 1.40
90 63 19.3 12.8 14.1 15.4 16.7 17.9 1.45
67 20.8 10.1 11.4 12.7 13.9 15.2 1.50
71 22.3 7.4 8.6 9.9 11.2 12.4 1.55
59 17.5 15.2 16.4 17.6* 18.1* 18.5* 1.46
95 63 18.9 12.7 14.0 15.2 16.5 17.8 1.51
67 20.4 10.0 11.3 12.5 13.8 15.1 1.56
71 21.9 7.2 8.5 9.8 11.0 12.3 1.62
59 17.0 15.0 16.2 17.2* 17.7* 18.1* 1.53
100 63 18.4 12.5 13.8 15.0 16.3 17.6 1.58
67 19.8 9.8 11.0 12.3 13.6 14.9 1.63
71 21.3 7.0 8.3 9.5 10.8 12.1 1.68
59 16.5 14.7 16.0 16.8* 17.3* 17.7* 1.59
105 63 17.9 12.3 13.6 14.8 16.1 17.4 1.64
67 19.2 9.6 10.8 12.1 13.4 14.6 1.70
71 20.7 6.8 8.1 9.3 10.6 11.9 1.75
59 15.6 14.3 15.6* 16.0* 16.4* 16.9* 1.72
115 63 16.8 11.9 13.1 14.4 15.7 16.9* 1.78
67 18.1 9.2 10.4 11.7 13.0 14.2 1.83
71 19.4 6.4 7.7 8.9 10.2 11.5 1.89
TWJ024CA WITH TWE030CA4 A T 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 24.2 19.7 21.3 22.9 24.3* 24.9* 1.92
85 63 26.0 16.7 18.3 19.8 21.4 23.0 1.98
67 28.0 13.3 14.9 16.5 18.0 19.6 2.05
71 30.0 9.9 11.5 13.0 14.6 16.2 2.12
59 23.8 19.6 21.1 22.7 24.0* 24.6* 2.01
90 63 25.6 16.5 18.1 19.7 21.2 22.8 2.08
67 27.5 13.2 14.7 16.3 17.9 19.4 2.14
71 29.5 9.7 11.3 12.8 14.4 16.0 2.21
59 23.4 19.4 21.0 22.5 23.7* 24.3* 2.10
95 63 25.2 16.4 17.9 19.5 21.0 22.6 2.17
67 27.1 13.0 14.5 16.1 17.7 19.2 2.24
71 29.0 9.5 11.1 12.7 14.2 15.8 2.31
59 22.8 19.2 20.7 22.3 23.2* 23.8* 2.21
100 63 24.6 16.1 17.7 19.2 20.8 22.4 2.27
67 26.4 12.7 14.3 15.9 17.4 19.0 2.34
71 28.3 9.3 10.9 12.4 14.0 15.6 2.41
59 22.2 18.9 20.5 22.0 22.8* 23.3* 2.31
105 63 24.0 15.9 17.4 19.0 20.6 22.1 2.37
67 25.7 12.5 14.1 15.6 17.2 18.8 2.44
71 27.6 9.0 10.6 12.2 13.7 15.3 2.51
59 21.1 18.4 20.0 21.3* 21.8* 22.4* 2.52
115 63 22.7 15.4 16.9 18.5 20.1 21.6 2.58
67 24.4 12.0 13.6 15.1 16.7 18.3 2.65
71 26.2 8.6 10.1 11.7 13.3 14.8 2.71
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 625 800
TOTAL CAP . X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 20400 BTUH
AIRFLOW = 700 CFM
COMPRESSOR POWER = 1562 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
S.E.E.R. = 10.30 BTUH/W ATT
E.E.R. = 9.50 BTUH/WA T T
NOTE:RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 800 1025
TOTAL CAP . X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 27100 BTUH
AIRFLOW = 900 CFM
COMPRESSOR POWER = 2239 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 180 WATTS
E.E.R. = 8.90 BTUH/WA T T
NOTE:RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWJ030CA WITH TWE030CA4 A T 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 29.0 22.8 24.5 26.2 28.0 29.3* 2.57
85 63 31.2 19.4 21.2 22.9 24.6 26.3 2.66
67 33.5 15.7 17.4 19.2 20.9 22.6 2.75
71 35.8 11.9 13.6 15.3 17.1 18.8 2.85
59 28.5 22.6 24.3 26.0 27.7 28.9* 2.69
90 63 30.6 19.2 20.9 22.7 24.4 26.1 2.78
67 32.9 15.5 17.2 18.9 20.7 22.4 2.88
71 35.2 11.7 13.4 15.1 16.9 18.6 2.97
59 28.0 22.3 24.1 25.8 27.5 28.5* 2.82
95 63 30.1 19.0 20.7 22.4 24.2 25.9 2.91
67 32.3 15.3 17.0 18.7 20.4 22.2 3.00
71 34.6 11.5 13.2 14.9 16.6 18.4 3.10
59 27.3 22.1 23.8 25.5 27.2 28.0* 2.95
100 63 29.4 18.7 20.4 22.1 23.9 25.6 3.04
67 31.5 15.0 16.7 18.4 20.1 21.9 3.13
71 33.8 11.2 12.9 14.6 16.3 18.1 3.23
59 26.6 21.8 23.5 25.2 26.8* 27.4* 3.08
105 63 28.7 18.4 20.1 21.9 23.6 25.3 3.17
67 30.8 14.7 16.4 18.1 19.9 21.6 3.26
71 32.9 10.9 12.6 14.3 16.1 17.8 3.36
59 25.3 21.2 22.9 24.6 25.7* 26.3* 3.35
115 63 27.2 17.8 19.6 21.3 23.0 24.7 3.43
67 29.2 14.1 15.8 17.6 19.3 21.0 3.52
71 31.3 10.3 12.0 13.8 15.5 17.2 3.62
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 875 1125
TOTAL CAP . X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32400 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 3002 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 8.30 BTUH/WA T T
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
8 TWE5-PRC001-EN-10-15-99
Page 9
Performance
Data Cooling Metric Units
TWJ020CA WITH TWE030CA4 A T 1189 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR F AN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 5.8 3.8 4.2 4.5 4.9 5.3 1.4
32.2 17.2 5.7 3.8 4.1 4.5 4.9 5.2 1.5
35.0 17.2 5.5 3.7 4.1 4.5 4.8 5.2 1.5
37.8 17.2 5.4 3.7 4.0 4.4 4.8 5.2 1.6
40.6 17.2 5.2 3.6 4.0 4.3 4.7 5.1 1.6
46.1 17.2 4.9 3.5 3.8 4.2 4.6 5.0* 1.8
15.0 5.3 4.5 4.9 5.3 5.4* 5.6* 1.3
19.4 6.2 3.0 3.4 3.8 4.1 4.5 1.4
21.7 6.7 2.2 2.6 3.0 3.3 3.7 1.5
15.0 5.2 4.5 4.9 5.2 5.4* 5.5* 1.4
19.4 6.1 3.0 3.3 3.7 4.1 4.5 1.5
21.7 6.5 2.2 2.5 2.9 3.3 3.6 1.5
15.0 5.1 4.5 4.8 5.2* 5.3* 5.4* 1.5
19.4 6.0 2.9 3.3 3.7 4.0 4.4 1.6
21.7 6.4 2.1 2.5 2.9 3.2 3.6 1.6
15.0 5.0 4.4 4.7 5.0* 5.2* 5.3* 1.5
19.4 5.8 2.9 3.2 3.6 4.0 4.4 1.6
21.7 6.2 2.1 2.4 2.8 3.2 3.5 1.7
15.0 4.8 4.3 4.7 4.9* 5.1* 5.2* 1.6
19.4 5.6 2.8 3.2 3.5 3.9 4.3 1.7
21.7 6.1 2.0 2.4 2.7 3.1 3.5 1.8
15.0 4.6 4.2 4.6* 4.7* 4.8* 5.0* 1.7
19.4 5.3 2.7 3.0 3.4 3.8 4.2 1.8
21.7 5.7 1.9 2.3 2.6 3.0 3.4 1.9
TWJ024CA WITH TWE030CA4 A T 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D .B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 7.6 4.9 5.4 5.8 6.3 6.7 2.0
32.2 17.2 7.5 4.8 5.3 5.8 6.2 6.7 2.1
35.0 17.2 7.4 4.8 5.2 5.7 6.2 6.6 2.2
37.8 17.2 7.2 4.7 5.2 5.6 6.1 6.6 2.3
40.6 17.2 7.0 4.7 5.1 5.6 6.0 6.5 2.4
46.1 17.2 6.7 4.5 5.0 5.4 5.9 6.3 2.6
15.0 7.1 5.8 6.2 6.7 7.1* 7.3* 1.9
19.4 8.2 3.9 4.4 4.8 5.3 5.7 2.0
21.7 8.8 2.9 3.4 3.8 4.3 4.7 2.1
15.0 7.0 5.7 6.2 6.7 7.0* 7.2* 2.0
19.4 8.1 3.9 4.3 4.8 5.2 5.7 2.1
21.7 8.6 2.8 3.3 3.8 4.2 4.7 2.2
15.0 6.9 5.7 6.2 6.6 6.9* 7.1* 2.1
19.4 7.9 3.8 4.2 4.7 5.2 5.6 2.2
21.7 8.5 2.8 3.3 3.7 4.2 4.6 2.3
15.0 6.7 5.6 6.1 6.5 6.8* 7.0* 2.2
19.4 7.7 3.7 4.2 4.7 5.1 5.6 2.3
21.7 8.3 2.7 3.2 3.6 4.1 4.6 2.4
15.0 6.5 5.5 6.0 6.4 6.7* 6.8* 2.3
19.4 7.5 3.7 4.1 4.6 5.0 5.5 2.4
21.7 8.1 2.6 3.1 3.6 4.0 4.5 2.5
15.0 6.2 5.4 5.9 6.2* 6.4* 6.6* 2.5
19.4 7.1 3.5 4.0 4.4 4.9 5.4 2.7
21.7 7.7 2.5 3.0 3.4 3.9 4.3 2.7
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1061 1358
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 5.98 KW
AIRFLOW = 1189 CMH
COMPRESSOR POWER = 1562 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
S.E.E.R. = 10.30 BTUH/WATT
E.E.R. = 9.50 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1358 1741
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 7.94 KW
AIRFLOW = 1528 CMH
COMPRESSOR POWER = 2239 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 180 WATTS
E.E.R. = 8.90 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 19 MM SUCT.
AND 8 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWJ030CA WITH TWE030CA4 A T 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D .B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.7
32.2 17.2 9.0 5.6 6.1 6.7 7.1 7.6 2.8
35.0 17.2 8.8 5.6 6.1 6.6 7.1 7.6 2.9
37.8 17.2 8.6 5.5 6.0 6.5 7.0 7.5 3.0
40.6 17.2 8.4 5.4 5.9 6.4 6.9 7.4 3.2
46.1 17.2 8.0 5.2 5.7 6.2 6.7 7.2 3.4
TWE5-PRC001-EN-10-15-99 9
15.0 8.5 6.7 7.2 7.7 8.2 8.6* 2.6
19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.8
21.7 10.5 3.5 4.0 4.5 5.0 5.5 2.8
15.0 8.4 6.6 7.1 7.6 8.1 8.5* 2.7
19.4 9.6 4.5 5.0 5.5 6.1 6.6 2.9
21.7 10.3 3.4 3.9 4.4 5.0 5.4 3.0
15.0 8.2 6.5 7.1 7.6 8.1 8.4* 2.8
19.4 9.5 4.5 5.0 5.5 6.0 6.5 3.0
21.7 10.1 3.4 3.9 4.4 4.9 5.4 3.1
15.0 8.0 6.5 7.0 7.5 8.0 8.2* 3.0
19.4 9.2 4.4 4.9 5.4 5.9 6.4 3.1
21.7 9.9 3.3 3.8 4.3 4.8 5.3 3.2
15.0 7.8 6.4 6.9 7.4 7.9* 8.0* 3.1
19.4 9.0 4.3 4.8 5.3 5.8 6.3 3.3
21.7 9.6 3.2 3.7 4.2 4.7 5.2 3.4
15.0 7.4 6.2 6.7 7.2 7.5* 7.7* 3.3
19.4 8.6 4.1 4.6 5.2 5.7 6.2 3.5
21.7 9.2 3.0 3.5 4.0 4.5 5.0 3.6
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1486 1910
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.49 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 3002 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 8.30 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
Page 10
Performance
Data Cooling English Units
TWJ030CA WITH TWE040CA4-B A T 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 30.7 25.1 27.1 29.1 31.0* 31.6* 2.65
85 63 33.0 21.2 23.2 25.2 27.2 29.2 2.75
67 35.3 16.9 18.9 20.9 22.9 24.9 2.84
71 37.7 12.5 14.5 16.5 18.5 20.4 2.94
59 30.1 24.9 26.9 28.9 30.5* 31.2* 2.78
90 63 32.3 21.0 22.9 24.9 26.9 28.9 2.87
67 34.6 16.6 18.6 20.6 22.6 24.6 2.97
71 37.0 12.2 14.2 16.2 18.2 20.2 3.07
59 29.5 24.6 26.6 28.6 30.0* 30.7* 2.91
95 63 31.7 20.7 22.7 24.7 26.7 28.7 3.00
67 33.9 16.4 18.4 20.4 22.3 24.3 3.10
71 36.2 12.0 14.0 15.9 17.9 19.9 3.20
59 28.8 24.3 26.3 28.3 29.3* 30.0* 3.04
100 63 30.9 20.4 22.4 24.3 26.3 28.3 3.13
67 33.0 16.0 18.0 20.0 22.0 24.0 3.23
71 35.3 11.6 13.6 15.6 17.6 19.6 3.33
59 28.0 24.0 26.0 27.9 28.7* 29.4* 3.17
105 63 30.0 20.0 22.0 24.0 26.0 28.0 3.27
67 32.1 15.7 17.7 19.7 21.7 23.7 3.36
71 34.3 11.3 13.3 15.3 17.3 19.3 3.46
59 26.5 23.3 25.3 26.8* 27.4* 28.1* 3.45
115 63 28.4 19.4 21.4 23.4 25.4 27.3 3.54
67 30.4 15.1 17.1 19.0 21.0 23.0 3.63
71 32.4 10.7 12.7 14.6 16.6 18.6 3.73
TWJ036CA WITH TWE030CA4 A T 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 33.9 25.9 27.8 29.7 31.6 33.4 2.52
85 63 36.7 22.4 24.3 26.1 28.0 29.9 2.60
67 39.5 18.4 20.3 22.1 24.0 25.9 2.68
71 42.5 14.3 16.2 18.0 19.9 21.8 2.77
59 33.4 25.7 27.6 29.4 31.3 33.2 2.65
90 63 36.1 22.1 24.0 25.9 27.8 29.6 2.73
67 38.9 18.1 20.0 21.9 23.8 25.6 2.82
71 41.8 14.0 15.9 17.8 19.7 21.5 2.91
59 32.8 25.4 27.3 29.2 31.1 32.9* 2.78
95 63 35.5 21.9 23.8 25.6 27.5 29.4 2.87
67 38.3 17.9 19.8 21.6 23.5 25.4 2.95
71 41.2 13.8 15.7 17.5 19.4 21.3 3.04
59 32.1 25.1 27.0 28.9 30.7 32.4* 2.92
100 63 34.7 21.5 23.4 25.3 27.2 29.0 3.00
67 37.4 17.6 19.4 21.3 23.2 25.1 3.09
71 40.2 13.5 15.3 17.2 19.1 21.0 3.18
59 31.3 24.8 26.7 28.5 30.4 31.8* 3.06
105 63 33.9 21.2 23.1 25.0 26.8 28.7 3.14
67 36.5 17.2 19.1 21.0 22.8 24.7 3.23
71 39.3 13.1 15.0 16.9 18.7 20.6 3.31
59 29.8 24.1 26.0 27.9 29.7 30.6* 3.35
115 63 32.2 20.5 22.4 24.3 26.2 28.0 3.42
67 34.8 16.5 18.4 20.3 22.2 24.0 3.50
71 37.4 12.5 14.3 16.2 18.1 19.9 3.58
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.02
SENS. CAP. X0.95 X1.07
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 34100 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 3104 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 9.05 BTUH/WATT
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAP ACITY)
TOTAL CAPA CITY, COMP. KW AND APP. DEW PT. ARE
VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
CORRECTION FACTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.02
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 38500 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2957 WATTS
I.D. FAN POWER = 540 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWJ036CA WITH TWE040CA4-B A T 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 37.2 30.6 33.0 35.5 37.6* 38.5* 2.63
85 63 40.1 25.8 28.3 30.7 33.1 35.6 2.71
67 43.1 20.6 23.0 25.4 27.9 30.3 2.80
71 46.2 15.2 17.6 20.1 22.5 25.0 2.89
59 36.5 30.3 32.7 35.2 37.0* 37.9* 2.76
90 63 39.3 25.5 28.0 30.4 32.8 35.3 2.85
67 42.3 20.3 22.7 25.1 27.6 30.0 2.94
71 45.3 14.9 17.3 19.8 22.2 24.7 3.03
59 35.8 30.0 32.4 34.9 36.5* 37.3* 2.90
95 63 38.6 25.2 27.7 30.1 32.5 35.0 2.99
67 41.5 20.0 22.4 24.8 27.3 29.7 3.07
71 44.4 14.6 17.0 19.5 21.9 24.4 3.17
59 34.9 29.6 32.0 34.5 35.7* 36.5* 3.04
100 63 37.6 24.8 27.3 29.7 32.1 34.6 3.13
67 40.4 19.6 22.0 24.4 26.9 29.3 3.22
71 43.3 14.2 16.6 19.1 21.5 24.0 3.31
59 34.0 29.2 31.6 34.1* 34.9* 35.8* 3.19
105 63 36.6 24.4 26.9 29.3 31.7 34.2 3.27
67 39.3 19.2 21.6 24.0 26.5 28.9 3.36
71 42.1 13.8 16.2 18.7 21.1 23.6 3.45
59 32.1 28.4 30.8 32.6* 33.4* 34.2* 3.48
115 63 34.6 23.6 26.1 28.5 30.9 33.4 3.56
67 37.1 18.4 20.8 23.2 25.7 28.1 3.64
71 39.8 13.0 15.4 17.9 20.3 22.8 3.73
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1175 1525
TOTAL CAP . X0.97 X1.01
SENS. CAP. X0.92 X1.04
COMPR. KW X0.98 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 41300 BTUH
AIRFLOW = 1350 CFM
COMPRESSOR POWER = 3066 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 10.80 BTUH/W ATT
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
10 TWE5-PRC001-EN-10-15-99
Page 11
Performance
Data Cooling Metric Units
TWJ030CA WITH TWE040CA4-B A T 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR F AN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.8
32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.9
35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 3.0
37.8 17.2 9.1 6.0 6.6 7.1 7.7 8.3 3.1
40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 3.3
46.1 17.2 8.3 5.7 6.3 6.9 7.4 8.0 3.5
15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.7
19.4 10.3 5.0 5.5 6.1 6.7 7.3 2.8
21.7 11.0 3.7 4.2 4.8 5.4 6.0 2.9
15.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.8
19.4 10.1 4.9 5.4 6.0 6.6 7.2 3.0
21.7 10.8 3.6 4.2 4.7 5.3 5.9 3.1
15.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.9
19.4 9.9 4.8 5.4 6.0 6.5 7.1 3.1
21.7 10.6 3.5 4.1 4.7 5.2 5.8 3.2
15.0 8.4 7.1 7.7 8.3 8.6* 8.8* 3.0
19.4 9.7 4.7 5.3 5.9 6.4 7.0 3.2
21.7 10.3 3.4 4.0 4.6 5.2 5.7 3.3
15.0 8.2 7.0 7.6 8.2 8.4* 8.6* 3.2
19.4 9.4 4.6 5.2 5.8 6.4 6.9 3.4
21.7 10.0 3.3 3.9 4.5 5.1 5.7 3.5
15.0 7.8 6.8 7.4 7.9* 8.0* 8.2* 3.5
19.4 8.9 4.4 5.0 5.6 6.2 6.7 3.6
21.7 9.5 3.1 3.7 4.3 4.9 5.4 3.7
TWJ036CA WITH TWE030CA4 A T 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D .B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 10.8 6.6 7.1 7.6 8.2 8.8 2.6
32.2 17.2 10.6 6.5 7.0 7.6 8.1 8.7 2.7
35.0 17.2 10.4 6.4 7.0 7.5 8.1 8.6 2.9
37.8 17.2 10.2 6.3 6.9 7.4 8.0 8.5 3.0
40.6 17.2 9.9 6.2 6.8 7.3 7.9 8.4 3.1
46.1 17.2 9.4 6.0 6.6 7.1 7.7 8.2 3.4
15.0 9.9 7.6 8.1 8.7 9.3 9.8 2.5
19.4 11.6 5.4 5.9 6.5 7.0 7.6 2.7
21.7 12.5 4.2 4.7 5.3 5.8 6.4 2.8
15.0 9.8 7.5 8.1 8.6 9.2 9.7 2.7
19.4 11.4 5.3 5.9 6.4 7.0 7.5 2.8
21.7 12.2 4.1 4.7 5.2 5.8 6.3 2.9
15.0 9.6 7.4 8.0 8.6 9.1 9.6* 2.8
19.4 11.2 5.2 5.8 6.3 6.9 7.4 3.0
21.7 12.1 4.0 4.6 5.1 5.7 6.2 3.0
15.0 9.4 7.4 7.9 8.5 9.0 9.5* 2.9
19.4 11.0 5.2 5.7 6.2 6.8 7.4 3.1
21.7 11.8 4.0 4.5 5.0 5.6 6.2 3.2
15.0 9.2 7.3 7.8 8.4 8.9 9.3* 3.1
19.4 10.7 5.0 5.6 6.2 6.7 7.2 3.2
21.7 11.5 3.8 4.4 5.0 5.5 6.0 3.3
15.0 8.7 7.1 7.6 8.2 8.7 9.0* 3.3
19.4 10.2 4.8 5.4 5.9 6.5 7.0 3.5
21.7 11.0 3.7 4.2 4.7 5.3 5.8 3.6
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1656 2165
TOTAL CAP . X0.98 X1.02
SENS. CAP. X0.95 X1.07
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.99 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 3104 WATTS
I.D. FAN PO WER = 300 WATTS
O.D. FAN POWER = 195 WATTS
E.E.R. = 9.05 BTUH/WA T T
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1656 2165
TOTAL CAP . X0.98 X1.02
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 11.28 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2957 WATTS
I.D. FAN PO WER = 540 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 9.65 BTUH/WA T T
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWJ036CA WITH TWE040CA4-B A T 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR F AN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 11.7 7.6 8.3 9.0 9.7 10.4 2.7
32.2 17.2 11.5 7.5 8.2 8.9 9.6 10.3 2.8
35.0 17.2 11.3 7.4 8.1 8.8 9.5 10.3 3.0
37.8 17.2 11.0 7.3 8.0 8.7 9.4 10.1 3.1
40.6 17.2 10.7 7.1 7.9 8.6 9.3 10.0 3.3
46.1 17.2 10.1 6.9 7.6 8.4 9.1 9.8 3.6
TWE5-PRC001-EN-10-15-99 11
15.0 10.9 9.0 9.7 10.4 11.0* 11.3* 2.6
19.4 12.6 6.0 6.7 7.4 8.2 8.9 2.8
21.7 13.5 4.5 5.2 5.9 6.6 7.3 2.9
15.0 10.7 8.9 9.6 10.3 10.8* 11.1* 2.8
19.4 12.4 5.9 6.7 7.4 8.1 8.8 2.9
21.7 13.3 4.4 5.1 5.8 6.5 7.2 3.0
15.0 10.5 8.8 9.5 10.2 10.7* 10.9* 2.9
19.4 12.2 5.9 6.6 7.3 8.0 8.7 3.1
21.7 13.0 4.3 5.0 5.7 6.4 7.1 3.2
15.0 10.2 8.7 9.4 10.1 10.5* 10.7* 3.0
19.4 11.8 5.7 6.4 7.1 7.9 8.6 3.2
21.7 12.7 4.2 4.9 5.6 6.3 7.0 3.3
15.0 10.0 8.6 9.3 10.0* 10.2* 10.5* 3.2
19.4 11.5 5.6 6.3 7.0 7.8 8.5 3.4
21.7 12.3 4.0 4.7 5.5 6.2 6.9 3.5
15.0 9.4 8.3 9.0 9.6* 9.8* 10.0* 3.5
19.4 10.9 5.4 6.1 6.8 7.5 8.2 3.6
21.7 11.7 3.8 4.5 5.2 5.9 6.7 3.7
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1995 2590
TOTAL CAP . X0.97 X1.01
SENS. CAP. X0.92 X1.04
COMPR. KW X0.98 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 12.10 KW
AIRFLOW = 2293 CMH
COMPRESSOR POWER = 3066 WATTS
I.D. FAN PO WER = 360 WATTS
O.D. FAN POWER = 235 WATTS
E.E.R. = 10.80 BTUH/W ATT
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
Page 12
Performance
Data Cooling English Units
TWA030CD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 28.8 22.6 24.4 26.1 27.8 29.2* 2.13
85 63 31.0 19.3 21.0 22.8 24.5 26.2 2.21
67 33.3 15.6 17.3 19.1 20.8 22.5 2.29
71 35.7 11.8 13.6 15.3 17.0 18.7 2.37
59 28.3 22.4 24.1 25.8 27.6 28.7* 2.24
90 63 30.4 19.1 20.8 22.5 24.2 26.0 2.32
67 32.7 15.4 17.1 18.8 20.5 22.3 2.40
71 35.1 11.6 13.3 15.0 16.8 18.5 2.48
59 27.7 22.2 23.9 25.6 27.3 28.3* 2.35
95 63 29.9 18.9 20.6 22.3 24.0 25.7 2.42
67 32.1 15.2 16.9 18.6 20.3 22.0 2.51
71 34.4 11.4 13.1 14.8 16.5 18.2 2.59
59 27.0 21.9 23.6 25.3 27.1* 27.7* 2.46
100 63 29.1 18.5 20.3 22.0 23.7 25.4 2.54
67 31.3 14.8 16.6 18.3 20.0 21.7 2.62
71 33.5 11.1 12.8 14.5 16.2 17.9 2.70
59 26.3 21.6 23.3 25.0 26.5* 27.2* 2.57
105 63 28.3 18.2 20.0 21.7 23.4 25.1 2.65
67 30.4 14.5 16.2 18.0 19.7 21.4 2.73
71 32.6 10.7 12.5 14.2 15.9 17.6 2.81
59 24.9 21.0 22.7 24.4 25.4* 26.0* 2.80
115 63 26.8 17.6 19.3 21.1 22.8 24.5 2.87
67 28.8 13.9 15.6 17.3 19.1 20.8 2.95
71 30.8 10.1 11.8 13.6 15.3 17.0 3.02
TWA030CD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 30.8 25.2 27.1 29.1 31.0* 31.7* 2.21
85 63 33.0 21.2 23.2 25.2 27.2 29.2 2.29
67 35.4 16.9 18.9 20.9 22.9 24.9 2.37
71 37.9 12.5 14.5 16.5 18.5 20.5 2.45
59 30.1 24.9 26.9 28.9 30.5* 31.2* 2.32
90 63 32.3 21.0 23.0 24.9 26.9 28.9 2.40
67 34.7 16.7 18.6 20.6 22.6 24.6 2.48
71 37.0 12.3 14.2 16.2 18.2 20.2 2.56
59 29.5 24.6 26.6 28.6 29.9* 30.6* 2.43
95 63 31.6 20.7 22.7 24.7 26.7 28.6 2.51
67 33.9 16.4 18.4 20.4 22.3 24.3 2.59
71 36.2 12.0 14.0 16.0 17.9 19.9 2.67
59 28.6 24.2 26.2 28.2 29.3* 29.9* 2.54
100 63 30.8 20.3 22.3 24.3 26.3 28.3 2.62
67 32.9 16.0 18.0 20.0 22.0 24.0 2.70
71 35.2 11.6 13.6 15.6 17.6 19.6 2.78
59 27.8 23.9 25.9 27.9* 28.6* 29.2* 2.66
105 63 29.9 20.0 22.0 23.9 25.9 27.9 2.73
67 32.0 15.7 17.6 19.6 21.6 23.6 2.81
71 34.2 11.3 13.2 15.2 17.2 19.2 2.90
59 26.2 23.2 25.2 26.5* 27.2* 27.8* 2.89
115 63 28.1 19.3 21.2 23.2 25.2 27.2 2.96
67 30.1 14.9 16.9 18.9 20.9 22.9 3.04
71 32.1 10.6 12.5 14.5 16.5 18.5 3.11
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 875 1125
TOTAL CAP . X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32200 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 2505 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 9.55 BTUH/WA T T
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 975 1275
TOTAL CAP . X0.98 X1.02
SENS. CAP. X0.95 X1.07
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 34100 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2594 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 10.45 BTUH/W ATT
NOTE:RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWA040CD WITH TWE040CA4-B AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 39.3 32.2 34.8 37.4 39.6* 40.5* 2.79
85 63 42.2 27.1 29.7 32.3 34.9 37.4 2.90
67 45.2 21.5 24.1 26.7 29.3 31.8 3.01
71 48.4 15.8 18.4 21.0 23.6 26.1 3.13
59 38.5 31.9 34.4 37.0 39.0* 39.9* 2.93
90 63 41.4 26.8 29.4 32.0 34.5 37.1 3.04
67 44.3 21.2 23.8 26.4 28.9 31.5 3.16
71 47.4 15.5 18.1 20.7 23.2 25.8 3.29
59 37.7 31.5 34.1 36.7 38.4* 39.2* 3.07
95 63 40.5 26.5 29.1 31.6 34.2 36.8 3.18
67 43.4 20.9 23.5 26.0 28.6 31.2 3.31
71 46.4 15.2 17.7 20.3 22.9 25.5 3.44
59 36.7 31.1 33.7 36.3 37.5* 38.4* 3.21
100 63 39.4 26.0 28.6 31.2 33.8 36.4 3.33
67 42.3 20.5 23.0 25.6 28.2 30.8 3.46
71 45.2 14.7 17.3 19.9 22.5 25.1 3.59
59 35.7 30.7 33.3 35.9* 36.7* 37.6* 3.36
105 63 38.4 25.6 28.2 30.8 33.4 35.9 3.48
67 41.1 20.0 22.6 25.2 27.8 30.3 3.61
71 44.0 14.3 16.9 19.5 22.1 24.6 3.75
59 33.7 29.9 32.4 34.2* 35.0* 35.9* 3.65
115 63 36.2 24.8 27.4 29.9 32.5 35.1 3.78
67 38.8 19.2 21.8 24.3 26.9 29.5 3.92
71 41.5 13.5 16.1 18.6 21.2 23.8 4.06
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1325 1700
TOTAL CAP . X0.98 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 43500 BTUH
AIRFLOW = 1500 CFM
COMPRESSOR POWER = 3309 WATTS
I.D. FAN POWER = 420 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.45 BTUH/W ATT
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP . DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
12 TWE5-PRC001-EN-10-15-99
Page 13
Performance
Data Cooling Metric Units
TWA030CD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GR OSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 9.1 5.7 6.2 6.7 7.2 7.7 2.2
32.2 17.2 8.9 5.6 6.1 6.6 7.1 7.6 2.3
35.0 17.2 8.8 5.5 6.0 6.5 7.0 7.5 2.4
37.8 17.2 8.5 5.4 5.9 6.4 6.9 7.4 2.5
40.6 17.2 8.3 5.3 5.9 6.4 6.9 7.4 2.7
46.1 17.2 7.9 5.2 5.7 6.2 6.7 7.2 2.9
15.0 8.4 6.6 7.1 7.6 8.1 8.6* 2.1
19.4 9.8 4.6 5.1 5.6 6.1 6.6 2.3
21.7 10.5 3.5 4.0 4.5 5.0 5.5 2.4
15.0 8.3 6.6 7.1 7.6 8.1 8.4* 2.2
19.4 9.6 4.5 5.0 5.5 6.0 6.5 2.4
21.7 10.3 3.4 3.9 4.4 4.9 5.4 2.5
15.0 8.1 6.5 7.0 7.5 8.0 8.3* 2.3
19.4 9.4 4.5 5.0 5.4 5.9 6.4 2.5
21.7 10.1 3.3 3.8 4.3 4.8 5.3 2.6
15.0 7.9 6.4 6.9 7.4 7.9* 8.1* 2.5
19.4 9.2 4.3 4.9 5.4 5.9 6.4 2.6
21.7 9.8 3.3 3.8 4.2 4.7 5.2 2.7
15.0 7.7 6.3 6.8 7.3 7.8* 8.0* 2.6
19.4 8.9 4.2 4.7 5.3 5.8 6.3 2.7
21.7 9.6 3.1 3.7 4.2 4.7 5.2 2.8
15.0 7.3 6.2 6.7 7.1 7.4* 7.6* 2.8
19.4 8.4 4.1 4.6 5.1 5.6 6.1 3.0
21.7 9.0 3.0 3.5 4.0 4.5 5.0 3.0
TWA030CD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR F AN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D .B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 9.7 6.2 6.8 7.4 8.0 8.6 2.3
32.2 17.2 9.5 6.2 6.7 7.3 7.9 8.5 2.4
35.0 17.2 9.3 6.1 6.7 7.2 7.8 8.4 2.5
37.8 17.2 9.0 5.9 6.5 7.1 7.7 8.3 2.6
40.6 17.2 8.8 5.9 6.4 7.0 7.6 8.2 2.7
46.1 17.2 8.2 5.7 6.2 6.8 7.4 8.0 3.0
15.0 9.0 7.4 7.9 8.5 9.1* 9.3* 2.2
19.4 10.4 5.0 5.5 6.1 6.7 7.3 2.4
21.7 11.1 3.7 4.2 4.8 5.4 6.0 2.5
15.0 8.8 7.3 7.9 8.5 8.9* 9.1* 2.3
19.4 10.2 4.9 5.4 6.0 6.6 7.2 2.5
21.7 10.8 3.6 4.2 4.7 5.3 5.9 2.6
15.0 8.6 7.2 7.8 8.4 8.8* 9.0* 2.4
19.4 9.9 4.8 5.4 6.0 6.5 7.1 2.6
21.7 10.6 3.5 4.1 4.7 5.2 5.8 2.7
15.0 8.4 7.1 7.7 8.3 8.6* 8.8* 2.5
19.4 9.6 4.7 5.3 5.9 6.4 7.0 2.7
21.7 10.3 3.4 4.0 4.6 5.2 5.7 2.8
15.0 8.1 7.0 7.6 8.2* 8.4* 8.6* 2.7
19.4 9.4 4.6 5.2 5.7 6.3 6.9 2.8
21.7 10.0 3.3 3.9 4.5 5.0 5.6 2.9
15.0 7.7 6.8 7.4 7.8* 8.0* 8.1* 2.9
19.4 8.8 4.4 5.0 5.5 6.1 6.7 3.0
21.7 9.4 3.1 3.7 4.2 4.8 5.4 3.1
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1486 1910
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.43 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2505 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 9.55 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1656 2165
TOTAL CAP. X0.98 X1.02
SENS. CAP. X0.95 X1.07
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.99 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2594 WATTS
I.D. FAN POWER = 300 WATTS
O.D. FAN POWER = 214 WATTS
E.E.R. = 10.45 BTUH/W ATT
NOTE:RATED WITH 7.62 METERS OF 22 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWA040CD WITH TWE040CA4-B AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR F AN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D .B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 12.4 7.9 8.7 9.5 10.2 11.0 2.9
32.2 17.2 12.1 7.9 8.6 9.4 10.1 10.9 3.0
35.0 17.2 11.9 7.8 8.5 9.3 10.0 10.8 3.2
37.8 17.2 11.5 7.6 8.4 9.1 9.9 10.7 3.3
40.6 17.2 11.3 7.5 8.3 9.0 9.8 10.5 3.5
46.1 17.2 10.6 7.3 8.0 8.8 9.5 10.3 3.8
TWE5-PRC001-EN-10-15-99 13
15.0 11.5 9.4 10.2 11.0 11.6* 11.9* 2.8
19.4 13.2 6.3 7.1 7.8 8.6 9.3 3.0
21.7 14.2 4.6 5.4 6.2 6.9 7.6 3.1
15.0 11.3 9.3 10.1 10.8 11.4* 11.7* 2.9
19.4 13.0 6.2 7.0 7.7 8.5 9.2 3.2
21.7 13.9 4.5 5.3 6.1 6.8 7.6 3.3
15.0 11.0 9.2 10.0 10.8 11.3* 11.5* 3.1
19.4 12.7 6.1 6.9 7.6 8.4 9.1 3.3
21.7 13.6 4.5 5.2 5.9 6.7 7.5 3.4
15.0 10.8 9.1 9.9 10.6 11.0* 11.3* 3.2
19.4 12.4 6.0 6.7 7.5 8.3 9.0 3.5
21.7 13.2 4.3 5.1 5.8 6.6 7.4 3.6
15.0 10.5 9.0 9.8 10.5* 10.8* 11.0* 3.4
19.4 12.0 5.9 6.6 7.4 8.1 8.9 3.6
21.7 12.9 4.2 5.0 5.7 6.5 7.2 3.8
15.0 9.9 8.8 9.5 10.0* 10.3* 10.5* 3.7
19.4 11.4 5.6 6.4 7.1 7.9 8.6 3.9
21.7 12.2 4.0 4.7 5.4 6.2 7.0 4.1
CORRECTION FACTORS - OTHER AIRFLOWS
(MULTIPLY OR ADD AS INDICATED)
AIRFLOW 2250 2887
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 12.75 KW
AIRFLOW = 2547 CMH
COMPRESSOR POWER = 3309 WATTS
I.D. FAN POWER = 420 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.45 BTUH/W ATT
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
Page 14
Performance
Data Cooling English Units
TWA040CD WITH TWE050CA5-C AT 1500 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
59 40.1 33.2 35.9 38.6 40.6* 41.5* 2.78
85 63 43.1 28.0 30.7 33.3 36.0 38.7 2.89
67 46.1 22.2 24.9 27.5 30.2 32.9 3.01
71 49.3 16.3 18.9 21.6 24.3 27.0 3.13
59 39.1 32.8 35.5 38.2 39.8* 40.7* 2.91
90 63 42.0 27.5 30.2 32.9 35.6 38.2 3.02
67 44.9 21.7 24.4 27.1 29.8 32.4 3.14
71 48.0 15.8 18.5 21.2 23.8 26.5 3.27
59 38.1 32.4 35.0 37.7 38.9* 39.8* 3.04
95 63 40.9 27.1 29.8 32.4 35.1 37.8 3.15
67 43.7 21.3 24.0 26.6 29.3 32.0 3.28
71 46.7 15.4 18.0 20.7 23.4 26.1 3.41
59 37.0 31.9 34.6 37.2* 38.0* 38.9* 3.16
100 63 39.7 26.6 29.3 32.0 34.6 37.3 3.29
67 42.5 20.8 23.5 26.2 28.8 31.5 3.41
71 45.3 14.9 17.6 20.2 22.9 25.6 3.55
59 35.9 31.4 34.1 36.3* 37.1* 37.9* 3.30
105 63 38.5 26.1 28.8 31.5 34.2 36.8 3.42
67 41.2 20.3 23.0 25.7 28.4 31.0 3.55
71 44.0 14.4 17.1 19.8 22.4 25.1 3.69
59 33.6 30.5 33.2 34.4* 35.2* 36.0* 3.56
115 63 36.1 25.2 27.9 30.6 33.2 35.9 3.69
67 38.6 19.4 22.1 24.7 27.4 30.1 3.82
71 41.2 13.5 16.2 18.8 21.5 24.2 3.96
TWA050CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
100 63 48.2 31.8 34.9 38.0 41.1 44.2 4.21
105 63 46.8 31.2 34.3 37.4 40.5 43.7 4.38
115 63 43.9 30.1 33.2 36.3 39.4 42.5 4.71
59 48.8 39.6 42.7 45.8 49.0* 50.1* 3.60
85 63 52.3 33.4 36.5 39.6 42.7 45.9 3.72
67 55.9 26.6 29.7 32.8 35.9 39.0 3.84
71 59.6 19.6 22.7 25.8 29.0 32.1 3.96
59 47.6 39.1 42.2 45.3 48.0* 49.1* 3.77
90 63 51.0 32.9 36.0 39.1 42.2 45.3 3.88
67 54.5 26.0 29.2 32.3 35.4 38.5 4.00
71 58.1 19.1 22.2 25.3 28.4 31.5 4.13
59 46.4 38.5 41.6 44.8 47.0* 48.1* 3.93
95 63 49.7 32.3 35.5 38.6 41.7 44.8 4.05
67 53.1 25.5 28.6 31.7 34.9 38.0 4.17
71 56.6 18.6 21.7 24.8 27.9 31.0 4.30
59 45.1 38.0 41.1 44.2 45.9* 46.9* 4.10
67 51.5 24.9 28.1 31.2 34.3 37.4 4.33
71 54.9 18.0 21.1 24.2 27.3 30.4 4.46
59 43.7 37.4 40.5 43.6 44.8* 45.8* 4.27
67 50.0 24.4 27.5 30.6 33.7 36.8 4.50
71 53.2 17.4 20.5 23.6 26.8 29.9 4.62
59 41.1 36.3 39.4 41.6* 42.5* 43.5* 4.61
67 46.9 23.2 26.3 29.5 32.6 35.7 4.83
71 49.9 16.3 19.4 22.5 25.6 28.7 4.94
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1325 1700
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 43800 BTUH
AIRFLOW = 1500 CFM
COMPRESSOR POWER = 3279 W ATTS
I.D. FAN POWER = 510 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.30 BTUH/WATT
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1575 2025
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 53100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 4171 W ATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 255 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
TWA060CD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D . B .W . B .C A P . 7 27 47 67 88 0 K W
100 63 57.2 35.8 38.9 42.1 45.2 48.4 5.38
105 63 55.7 35.2 38.3 41.5 44.6 47.8 5.61
115 63 52.6 33.9 37.1 40.2 43.4 46.5 6.06
59 57.2 43.7 46.8 50.0 53.1 56.3 4.61
85 63 61.6 37.6 40.7 43.9 47.0 50.2 4.77
67 66.1 30.8 34.0 37.1 40.2 43.4 4.93
71 70.8 23.8 27.0 30.1 33.3 36.4 5.10
59 55.9 43.1 46.3 49.4 52.6 55.7 4.80
90 63 60.1 37.0 40.2 43.3 46.5 49.6 4.96
67 64.6 30.2 33.4 36.5 39.7 42.8 5.13
71 69.1 23.2 26.4 29.5 32.7 35.8 5.30
59 54.6 42.5 45.7 48.8 52.0 55.0* 5.00
95 63 58.7 36.4 39.6 42.7 45.9 49.0 5.16
67 63.1 29.6 32.8 35.9 39.1 42.2 5.33
71 67.5 22.7 25.8 29.0 32.1 35.3 5.50
59 53.2 41.9 45.1 48.2 51.4 53.8* 5.23
67 61.4 29.0 32.1 35.3 38.4 41.6 5.55
71 65.8 22.0 25.2 28.3 31.5 34.6 5.71
59 51.8 41.3 44.4 47.6 50.7 52.7* 5.45
67 59.8 28.4 31.5 34.7 37.8 40.9 5.77
71 64.0 21.4 24.5 27.7 30.8 34.0 5.93
59 48.9 40.1 43.2 46.3 49.3* 50.4* 5.91
67 56.5 27.1 30.2 33.4 36.5 39.7 6.20
71 60.5 20.1 23.3 26.4 29.6 32.7 6.36
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 1575 2025
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 63100 BTUH
AIRFLOW = 1800 CFM
COMPRESSOR POWER = 5326 W ATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 395 WATTS
E.E.R. = 9.20 BTUH/WATT
NOTE:RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES F.
14 TWE5-PRC001-EN-10-15-99
Page 15
Performance
Data Cooling Metric Units
TWA040CD WITH TWE050CA5-C AT 2547 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 12.6 8.2 9.0 9.8 10.5 11.3 2.9
32.2 17.2 12.3 8.1 8.8 9.6 10.4 11.2 3.0
35.0 17.2 12.0 7.9 8.7 9.5 10.3 11.1 3.2
37.8 17.2 11.6 7.8 8.6 9.4 10.1 10.9 3.3
40.6 17.2 11.3 7.6 8.4 9.2 10.0 10.8 3.4
46.1 17.2 10.6 7.4 8.2 9.0 9.7 10.5 3.7
15.0 11.7 9.7 10.5 11.3 11.9* 12.2* 2.8
19.4 13.5 6.5 7.3 8.1 8.8 9.6 3.0
21.7 14.4 4.8 5.5 6.3 7.1 7.9 3.1
15.0 11.5 9.6 10.4 11.2 11.7* 11.9* 2.9
19.4 13.2 6.4 7.1 7.9 8.7 9.5 3.1
21.7 14.1 4.6 5.4 6.2 7.0 7.8 3.3
15.0 11.2 9.5 10.3 11.0 11.4* 11.7* 3.0
19.4 12.8 6.2 7.0 7.8 8.6 9.4 3.3
21.7 13.7 4.5 5.3 6.1 6.9 7.6 3.4
15.0 10.8 9.3 10.1 10.9* 11.1* 11.4* 3.2
19.4 12.5 6.1 6.9 7.7 8.4 9.2 3.4
21.7 13.3 4.4 5.2 5.9 6.7 7.5 3.5
15.0 10.5 9.2 10.0 10.6* 10.9* 11.1* 3.3
19.4 12.1 5.9 6.7 7.5 8.3 9.1 3.5
21.7 12.9 4.2 5.0 5.8 6.6 7.4 3.7
15.0 9.8 8.9 9.7 10.1* 10.3* 10.5* 3.6
19.4 11.3 5.7 6.5 7.2 8.0 8.8 3.8
21.7 12.1 4.0 4.7 5.5 6.3 7.1 4.0
TWA050CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 15.3 9.8 10.7 11.6 12.5 13.4 3.7
32.2 17.2 14.9 9.6 10.5 11.5 12.4 13.3 3.9
35.0 17.2 14.6 9.5 10.4 11.3 12.2 13.1 4.1
37.8 17.2 14.1 9.3 10.2 11.1 12.0 13.0 4.2
40.6 17.2 13.7 9.1 10.0 11.0 11.9 12.8 4.4
46.1 17.2 12.9 8.8 9.7 10.6 11.5 12.5 4.7
15.0 14.3 11.6 12.5 13.4 14.4* 14.7* 3.6
19.4 16.4 7.8 8.7 9.6 10.5 11.4 3.8
21.7 17.5 5.7 6.7 7.6 8.5 9.4 4.0
15.0 13.9 11.5 12.4 13.3 14.1* 14.4* 3.8
19.4 16.0 7.6 8.6 9.5 10.4 11.3 4.0
21.7 17.0 5.6 6.5 7.4 8.3 9.2 4.1
15.0 13.6 11.3 12.2 13.1 13.8* 14.1* 3.9
19.4 15.6 7.5 8.4 9.3 10.2 11.1 4.2
21.7 16.6 5.4 6.4 7.3 8.2 9.1 4.3
15.0 13.2 11.1 12.0 13.0 13.4* 13.7* 4.1
19.4 15.1 7.3 8.2 9.1 10.0 11.0 4.3
21.7 16.1 5.3 6.2 7.1 8.0 8.9 4.5
15.0 12.8 11.0 11.9 12.8 13.1* 13.4* 4.3
19.4 14.6 7.1 8.1 9.0 9.9 10.8 4.5
21.7 15.6 5.1 6.0 6.9 7.9 8.8 4.6
15.0 12.0 10.6 11.5 12.2* 12.5* 12.7* 4.6
19.4 13.7 6.8 7.7 8.6 9.6 10.5 4.8
21.7 14.6 4.8 5.7 6.6 7.5 8.4 4.9
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 2250 2887
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.06
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 12.83 KW
AIRFLOW = 2547 CMH
COMPRESSOR POWER = 3279 W ATTS
I.D. FAN POWER = 510 WATTS
O.D. FAN POWER = 244 WATTS
E.E.R. = 10.30 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
CORRECTION FA CTORS - OTHER AIRFLOWS
(MUL TIPLY OR ADD AS INDICATED)
AIRFLOW 2675 3439
TOTAL CAP. X0.99 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 15.56 KW
AIRFLOW = 3057 CMH
COMPRESSOR POWER = 4171 W ATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 255 WATTS
E.E.R. = 9.65 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.
AND 9.5 MM LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONL Y FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
TWA060CD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D. I.D. TO TAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
29.4 17.2 18.0 11.0 11.9 12.9 13.8 14.7 4.8
32.2 17.2 17.6 10.8 11.8 12.7 13.6 14.5 5.0
35.0 17.2 17.2 10.7 11.6 12.5 13.4 14.4 5.2
37.8 17.2 16.8 10.5 11.4 12.3 13.2 14.2 5.4
40.6 17.2 16.3 10.3 11.2 12.2 13.1 14.0 5.6
46.1 17.2 15.4 9.9 10.9 11.8 12.7 13.6 6.1
TWE5-PRC001-EN-10-15-99 15
15.0 16.8 12.8 13.7 14.6 15.6 16.5 4.6
19.4 19.4 9.0 10.0 10.9 11.8 12.7 4.9
21.7 20.7 7.0 7.9 8.8 9.8 10.7 5.1
15.0 16.4 12.6 13.6 14.5 15.4 16.3 4.8
19.4 18.9 8.8 9.8 10.7 11.6 12.5 5.1
21.7 20.2 6.8 7.7 8.6 9.6 10.5 5.3
15.0 16.0 12.5 13.4 14.3 15.2 16.1* 5.0
19.4 18.5 8.7 9.6 10.5 11.5 12.4 5.3
21.7 19.8 6.7 7.6 8.5 9.4 10.3 5.5
15.0 15.6 12.3 13.2 14.1 15.1 15.8* 5.2
19.4 18.0 8.5 9.4 10.3 11.3 12.2 5.6
21.7 19.3 6.4 7.4 8.3 9.2 10.1 5.7
15.0 15.2 12.1 13.0 13.9 14.9 15.4* 5.4
19.4 17.5 8.3 9.2 10.2 11.1 12.0 5.8
21.7 18.8 6.3 7.2 8.1 9.0 10.0 5.9
15.0 14.3 11.7 12.7 13.6 14.4* 14.8* 5.9
19.4 16.6 7.9 8.8 9.8 10.7 11.6 6.2
21.7 17.7 5.9 6.8 7.7 8.7 9.6 6.4
CORRECTION FA CTORS - OTHER AIRFLOWS
AIRFLOW 2675 3439
TOTAL CAP. X0.98 X1.01
SENS. CAP. X0.95 X1.05
COMPR. KW X0.99 X1.01
GROSS CAPACITY = 18.49 KW
AIRFLOW = 3057 CMH
COMPRESSOR POWER = 5326 W ATTS
I.D. FAN POWER = 750 WATTS
O.D. FAN POWER = 395 WATTS
E.E.R. = 9.20 BTUH/WATT
NOTE:RATED WITH 7.62 METERS OF 28.6 MM SUCT.
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPA CITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT. ARE
VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.
(MUL TIPLY OR ADD AS INDICATED)
VALUES AT ARI RATING CONDITIONS
AND 9.5 MM LIQUID LINES
Page 16
Performance
Data Heating English Units
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-3 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
2 6.79 6.60 6.50 6.41 1.47 1.54 1.58 1.61
7 8.13 7.90 7.78 7.67 1.50 1.57 1.61 1.64
12 9.48 9.20 9.06 8.92 1.52 1.60 1.63 1.67
17 10.8 10.5 10.3 10.2 1.55 1.63 1.66 1.70
22 11.2 10.9 10.7 10.5 1.56 1.64 1.68 1.71
27 11.6 11.2 11.0 10.9 1.57 1.65 1.69 1.73
32 11.9 11.6 11.4 11.2 1.58 1.66 1.70 1.74
37 12.3 11.9 11.8 11.6 1.60 1.68 1.71 1.75
42 12.7 12.3 12.1 11.9 1.61 1.69 1.73 1.77
47 18.9 18.3 18.0 17.7 1.71 1.79 1.84 1.88
52 20.2 19.6 19.3 19.0 1.73 1.82 1.87 1.91
57 21.6 20.9 20.6 20.2 1.76 1.85 1.90 1.94
62 22.9 22.2 21.8 21.5 1.79 1.88 1.92 1.97
67 24.3 23.5 23.1 22.7 1.81 1.91 1.95 2.00
72 25.6 24.8 24.4 24.0 1.84 1.93 1.98 2.03
TWJ024CA WITH TWE030CA4 A T 900 CFM
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-3 8.10 7.93 7.85 7.77 1.86 1.94 1.98 2.03
2 9.91 9.70 9.60 9.49 1.92 2.01 2.06 2.10
7 11.7 11.5 11.3 11.2 1.99 2.08 2.13 2.17
12 13.5 13.2 13.1 12.9 2.06 2.15 2.20 2.25
17 15.3 15.0 14.8 14.7 2.12 2.22 2.27 2.32
22 16.2 15.9 15.7 15.5 2.18 2.28 2.33 2.38
27 17.1 16.7 16.5 16.3 2.23 2.34 2.39 2.44
32 18.0 17.6 17.4 17.2 2.29 2.40 2.45 2.51
37 18.9 18.4 18.2 18.0 2.34 2.45 2.51 2.57
42 19.8 19.3 19.1 18.9 2.39 2.51 2.57 2.63
47 26.2 25.6 25.3 25.0 2.52 2.65 2.71 2.77
52 28.0 27.4 27.0 26.7 2.59 2.72 2.78 2.85
57 29.8 29.1 28.8 28.4 2.66 2.79 2.86 2.92
62 31.6 30.9 30.5 30.2 2.72 2.86 2.93 3.00
67 33.5 32.7 32.3 31.9 2.79 2.93 3.00 3.07
72 35.3 34.4 34.0 33.6 2.86 3.00 3.07 3.14
TWJ020CA WITH TWE030CA4 A T 700 CFM
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 700 CFM TIMES CORR. FACT OR
AIRFLOW 625 800
HEATING CAP. X0.99 X1.02
COMPR. KW X1.01 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 700 CFM
HEATING CAP. (HIGH TEMP.) = 18300 BTUH
HEATING CAP. (LOW TEMP.) = 10500 BTUH
COMPR. POWER (HIGH TEMP.) = 1354 WATTS
COMPR. POWER (LOW TEMP.) = 1185 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.00
COEFF. OF PERF. (LOW TEMP.) = 1.88
OUTDOOR FAN POWER = 130 WATTS
INDOOR FAN PO WER = 310 WATTS
NOTE: RATED WITH 25 FEET OF 3/4
AIRFLOW 800 1025
HEATING CAP. X0.99 X1.02
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 900 CFM
HEATING CAP. (HIGH TEMP.) = 25600 BTUH
HEATING CAP. (LOW TEMP.) = 15000 BTUH
COMPR. POWER (HIGH TEMP.) = 2038 WATTS
COMPR. POWER (LOW TEMP.) = 1614 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.84
COEFF. OF PERF. (LOW TEMP.) = 1.96
OUTDOOR FAN POWER = 180 WATTS
INDOOR FAN PO WER = 430 WATTS
NOTE: RATED WITH 25 FEET OF 3/4
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
SUCTION AND 5/16 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 900 CFM TIMES CORR. FACT OR
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
SUCTION AND 5/16 LIQUID LINE
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TWJ030CA WITH TWE030CA4 A T 1000 CFM
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-3 9.79 9.60 9.51 9.41 2.27 2.38 2.44 2.49
2 11.8 11.6 11.5 11.4 2.36 2.47 2.53 2.59
7 13.9 13.6 13.5 13.3 2.44 2.56 2.62 2.69
12 15.9 15.6 15.4 15.3 2.53 2.65 2.72 2.78
17 18.0 17.6 17.4 17.2 2.61 2.74 2.81 2.88
22 18.9 18.5 18.3 18.2 2.69 2.83 2.89 2.96
27 19.9 19.5 19.3 19.1 2.77 2.91 2.98 3.05
32 20.9 20.4 20.2 20.0 2.85 2.99 3.06 3.14
37 21.8 21.4 21.2 20.9 2.92 3.07 3.15 3.22
42 22.8 22.3 22.1 21.8 3.00 3.16 3.23 3.31
47 30.2 29.6 29.3 29.0 3.12 3.28 3.37 3.45
52 32.3 31.6 31.3 30.9 3.21 3.37 3.46 3.54
57 34.3 33.6 33.2 32.9 3.29 3.46 3.55 3.64
62 36.4 35.6 35.2 34.8 3.38 3.55 3.64 3.73
67 38.4 37.6 37.2 36.8 3.46 3.64 3.74 3.83
72 40.5 39.6 39.2 38.7 3.55 3.73 3.83 3.92
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1000 CFM TIMES CORR. FACTOR
AIRFLOW 875 1125
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 29600 BTUH
HEATING CAP. (LOW TEMP.) = 17600 BTUH
COMPR. POWER (HIGH TEMP.) = 2649 WATTS
COMPR. POWER (LOW TEMP.) = 2109 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.64
COEFF. OF PERF. (LOW TEMP.) = 1.86
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN PO WER = 440 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
16 TWE5-PRC001-EN-10-15-99
= VALUE AT NEW AIRFLOW)
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
SUCTION AND 3/8 LIQUID LINE
Page 17
Performance
Data Heating Metric Units
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-19.4 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-16.7 2.0 1.9 1.9 1.9 1.5 1.5 1.6 1.6
-13.9 2.4 2.3 2.3 2.2 1.5 1.6 1.6 1.6
-11.1 2.8 2.7 2.7 2.6 1.5 1.6 1.6 1.7
-8.3 3.2 3.1 3.0 3.0 1.5 1.6 1.7 1.7
-5.6 3.3 3.2 3.1 3.1 1.6 1.6 1.7 1.7
-2.8 3.4 3.3 3.2 3.2 1.6 1.6 1.7 1.7
0.0 3.5 3.4 3.3 3.3 1.6 1.7 1.7 1.7
2.8 3.6 3.5 3.5 3.4 1.6 1.7 1.7 1.8
5.6 3.7 3.6 3.5 3.5 1.6 1.7 1.7 1.8
8.3 5.5 5.4 5.3 5.2 1.7 1.8 1.8 1.9
11.1 5.9 5.7 5.7 5.6 1.7 1.8 1.9 1.9
13.9 6.3 6.1 6.0 5.9 1.8 1.9 1.9 1.9
16.7 6.7 6.5 6.4 6.3 1.8 1.9 1.9 2.0
19.4 7.1 6.9 6.8 6.7 1.8 1.9 2.0 2.0
22.2 7.5 7.3 7.1 7.0 1.8 1.9 2.0 2.0
TWJ024CA WITH TWE030CA4 A T 1528 CMH
O.D . HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-19.4 2.4 2.3 2.3 2.3 1.9 1.9 2.0 2.0
-16.7 2.9 2.8 2.8 2.8 1.9 2.0 2.1 2.1
-13.9 3.4 3.4 3.3 3.3 2.0 2.1 2.1 2.2
-11.1 4.0 3.9 3.8 3.8 2.1 2.2 2.2 2.3
-8.3 4.5 4.4 4.3 4.3 2.1 2.2 2.3 2.3
-5.6 4.7 4.7 4.6 4.5 2.2 2.3 2.3 2.4
-2.8 5.0 4.9 4.8 4.8 2.2 2.3 2.4 2.4
0.0 5.3 5.2 5.1 5.0 2.3 2.4 2.5 2.5
2.8 5.5 5.4 5.3 5.3 2.3 2.5 2.5 2.6
5.6 5.8 5.7 5.6 5.5 2.4 2.5 2.6 2.6
8.3 7.7 7.5 7.4 7.3 2.5 2.7 2.7 2.8
11.1 8.2 8.0 7.9 7.8 2.6 2.7 2.8 2.8
13.9 8.7 8.5 8.4 8.3 2.7 2.8 2.9 2.9
16.7 9.3 9.1 8.9 8.8 2.7 2.9 2.9 3.0
19.4 9.8 9.6 9.5 9.3 2.8 2.9 3.0 3.1
22.2 10.3 10.1 10.0 9.8 2.9 3.0 3.1 3.1
TWJ020CA WITH TWE030CA4 A T 1189 CMH
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1189 CMH TIMES CORR. FACTOR
AIRFLOW 1061 1358
HEATING CAP. X0.99 X1.02
COMPR. KW X1.01 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
AIRFLOW = 1189 CMH
HEATING CAP. (HIGH TEMP.) = 5.36 KW
HEATING CAP. (LOW TEMP.) = 3.08 KW
COMPR. POWER (HIGH TEMP.) = 1354 WATTS
COMPR. POWER (LO W TEMP.) = 1185 WATTS
COEFF. OF PERF . (HIGH TEMP.) = 3.00
COEFF. OF PERF . (LOW TEMP.) = 1.88
OUTDOOR FAN PO WER = 130 WATTS
INDOOR FAN POWER = 310 W ATTS
NOTE: RATED WITH 7.62 METERS OF 19 MM
AIRFLOW 1358 1741
HEATING CAP. X0.99 X1.02
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
AIRFLOW = 1528 CMH
HEATING CAP. (HIGH TEMP.) = 7.50 KW
HEATING CAP. (LOW TEMP.) = 4.39 KW
COMPR. POWER (HIGH TEMP.) = 2038 WATTS
COMPR. POWER (LO W TEMP.) = 1614 WATTS
COEFF. OF PERF . (HIGH TEMP.) = 2.84
COEFF. OF PERF . (LOW TEMP.) = 1.96
OUTDOOR FAN PO WER = 180 WATTS
INDOOR FAN POWER = 430 W ATTS
NOTE: RATED WITH 7.62 METERS OF 19 MM
= VALUE AT NEW AIRFLOW)
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
SUCTION AND 8 MM LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1528 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
SUCTION AND 8 MM LIQUID LINE
O.D . HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOWATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-19.4 2.9 2.8 2.8 2.8 2.3 2.4 2.4 2.5
-16.7 3.5 3.4 3.4 3.3 2.4 2.5 2.5 2.6
-13.9 4.1 4.0 4.0 3.9 2.4 2.6 2.6 2.7
-11.1 4.7 4.6 4.5 4.5 2.5 2.7 2.7 2.8
-8.3 5.3 5.2 5.1 5.0 2.6 2.7 2.8 2.9
-5.6 5.5 5.4 5.4 5.3 2.7 2.8 2.9 3.0
-2.8 5.8 5.7 5.7 5.6 2.8 2.9 3.0 3.0
0.0 6.1 6.0 5.9 5.9 2.8 3.0 3.1 3.1
2.8 6.4 6.3 6.2 6.1 2.9 3.1 3.2 3.2
5.6 6.7 6.5 6.5 6.4 3.0 3.2 3.2 3.3
8.3 8.8 8.7 8.6 8.5 3.1 3.3 3.4 3.5
11.1 9.5 9.3 9.2 9.1 3.2 3.4 3.5 3.5
13.9 10.0 9.8 9.7 9.6 3.3 3.5 3.5 3.6
16.7 10.7 10.4 10.3 10.2 3.4 3.5 3.6 3.7
19.4 11.3 11.0 10.9 10.8 3.5 3.6 3.7 3.8
22.2 11.9 11.6 11.5 11.3 3.5 3.7 3.8 3.9
TWE5-PRC001-EN-10-15-99 17
TWJ030CA WITH TWE030CA4 A T 1698 CMH
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1698 CMH TIMES CORR. FACTOR
AIRFLOW 1486 1910
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEATING CAP. (HIGH TEMP.) = 8.67 KW
HEATING CAP. (LOW TEMP.) = 5.16 KW
COMPR. POWER (HIGH TEMP.) = 2649 WATTS
COMPR. POWER (LO W TEMP.) = 2109 WATTS
COEFF. OF PERF . (HIGH TEMP.) = 2.64
COEFF. OF PERF . (LOW TEMP.) = 1.86
OUTDOOR FAN PO WER = 195 WATTS
INDOOR FAN POWER = 440 W ATTS
NOTE: RATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
= VALUE AT NEW AIRFLOW)
Page 18
Performance
Data Heating English Units
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DR Y BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-3 9.46 9.27 9.17 9.08 2.12 2.24 2.30 2.36
2 11.6 11.3 11.2 11.1 2.19 2.31 2.37 2.44
7 13.6 13.4 13.2 13.1 2.26 2.39 2.45 2.52
12 15.7 15.4 15.2 15.1 2.33 2.47 2.53 2.60
17 17.8 17.5 17.3 17.1 2.40 2.54 2.61 2.68
22 18.9 18.5 18.3 18.1 2.47 2.61 2.68 2.76
27 19.9 19.5 19.3 19.1 2.54 2.69 2.76 2.83
32 21.0 20.5 20.3 20.1 2.61 2.76 2.83 2.91
37 22.0 21.6 21.3 21.1 2.67 2.83 2.91 2.99
42 23.1 22.6 22.3 22.1 2.74 2.90 2.98 3.06
47 30.4 29.7 29.4 29.1 2.83 3.00 3.08 3.17
52 32.5 31.8 31.4 31.1 2.91 3.08 3.16 3.25
57 34.6 33.8 33.5 33.1 2.98 3.15 3.24 3.33
62 36.7 35.9 35.5 35.1 3.05 3.23 3.32 3.41
67 38.8 37.9 37.5 37.1 3.12 3.31 3.40 3.49
72 40.9 40.0 39.5 39.1 3.19 3.38 3.48 3.57
TWJ036CA WITH TWE030CA4 A T 1100 CFM
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 8.32 8.18 8.11 8.04 2.00 2.09 2.13 2.18
-3 10.8 10.6 10.5 10.4 2.13 2.22 2.27 2.32
2 13.3 13.0 12.9 12.8 2.25 2.36 2.41 2.46
7 15.8 15.5 15.3 15.2 2.38 2.49 2.54 2.60
12 18.3 17.9 17.7 17.5 2.50 2.62 2.68 2.74
17 20.7 20.3 20.1 19.9 2.63 2.75 2.82 2.88
22 21.9 21.5 21.3 21.1 2.71 2.85 2.91 2.98
27 23.1 22.7 22.4 22.2 2.80 2.94 3.01 3.08
32 24.3 23.8 23.6 23.3 2.89 3.03 3.10 3.18
37 25.5 25.0 24.7 24.5 2.98 3.13 3.20 3.27
42 26.7 26.2 25.9 25.6 3.06 3.22 3.30 3.37
47 35.6 34.9 34.5 34.2 3.38 3.55 3.64 3.72
52 38.1 37.3 36.9 36.6 3.50 3.68 3.77 3.87
57 40.6 39.8 39.3 38.9 3.63 3.82 3.91 4.01
62 43.1 42.2 41.8 41.3 3.75 3.95 4.05 4.15
67 45.6 44.6 44.2 43.7 3.88 4.08 4.19 4.29
72 48.0 47.1 46.6 46.1 4.00 4.22 4.32 4.43
TWJ030CA WITH TWE040CA4-B AT 1100 CFM
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 975 1275
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 29800 BTUH
HEATING CAP. (LOW TEMP.) = 17500 BTUH
COMPR. POWER (HIGH TEMP.) = 2504 WATTS
COMPR. POWER (LOW TEMP.) = 2047 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.92
COEFF. OF PERF. (LOW TEMP.) = 2.00
OUTDOOR FAN POWER = 195 WATTS
INDOOR FAN PO WER = 300 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1100 CFM TIMES CORR. FACTOR
AIRFLOW 975 1275
HEATING CAP. X0.99 X1.02
COMPR. KW X1.02 X0.97
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 35000 BTUH
HEATING CAP. (LOW TEMP.) = 20400 BTUH
COMPR. POWER (HIGH TEMP.) = 2776 WATTS
COMPR. POWER (LOW TEMP.) = 1982 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.88
COEFF. OF PERF. (LOW TEMP.) = 2.16
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN PO WER = 540 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
= VALUE AT NEW AIRFLOW)
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TWJ036CA WITH TWE040CA4-B A T 1400 CFM
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-13 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
-8 7.73 7.59 7.52 7.45 1.84 1.93 1.98 2.03
-3 10.3 10.1 10.0 9.94 1.94 2.05 2.10 2.15
2 12.9 12.7 12.5 12.4 2.05 2.16 2.22 2.27
7 15.5 15.2 15.1 14.9 2.16 2.27 2.33 2.39
12 18.1 17.7 17.6 17.4 2.26 2.39 2.45 2.52
17 20.7 20.3 20.1 19.9 2.37 2.50 2.57 2.64
22 22.0 21.6 21.3 21.1 2.44 2.58 2.65 2.72
27 23.3 22.8 22.6 22.4 2.52 2.66 2.73 2.81
32 24.6 24.1 23.9 23.6 2.59 2.74 2.82 2.89
37 25.9 25.4 25.1 24.9 2.67 2.82 2.90 2.97
42 27.2 26.7 26.4 26.1 2.74 2.90 2.98 3.06
47 36.3 35.5 35.1 34.8 3.00 3.18 3.27 3.36
52 38.9 38.1 37.7 37.2 3.11 3.29 3.39 3.48
57 41.5 40.6 40.2 39.7 3.22 3.41 3.50 3.60
62 44.1 43.1 42.7 42.2 3.32 3.52 3.62 3.72
67 46.6 45.7 45.2 44.7 3.43 3.63 3.74 3.84
72 49.2 48.2 47.7 47.2 3.54 3.75 3.85 3.96
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1400 CFM TIMES CORR. FACTOR
AIRFLOW 1175 1525
HEATING CAP. X0.98 X1.01
COMPR. KW X1.03 X0.99
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1350 CFM
HEATING CAP. (HIGH TEMP.) = 35400 BTUH
HEATING CAP. (LOW TEMP.) = 20200 BTUH
COMPR. POWER (HIGH TEMP.) = 2590 WATTS
COMPR. POWER (LOW TEMP.) = 1906 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 235 WATTS
INDOOR FAN PO WER = 360 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
18 TWE5-PRC001-EN-10-15-99
= VALUE AT NEW AIRFLOW)
Page 19
Performance
Data Heating Metric Units
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-19.4 2.8 2.7 2.7 2.7 2.1 2.2 2.3 2.4
-16.7 3.4 3.3 3.3 3.3 2.2 2.3 2.4 2.4
-13.9 4.0 3.9 3.9 3.8 2.3 2.4 2.5 2.5
-11.1 4.6 4.5 4.5 4.4 2.3 2.5 2.5 2.6
-8.3 5.2 5.1 5.1 5.0 2.4 2.5 2.6 2.7
-5.6 5.5 5.4 5.4 5.3 2.5 2.6 2.7 2.8
-2.8 5.8 5.7 5.7 5.6 2.5 2.7 2.8 2.8
0.0 6.2 6.0 5.9 5.9 2.6 2.8 2.8 2.9
2.8 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.0
5.6 6.8 6.6 6.5 6.5 2.7 2.9 3.0 3.1
8.3 8.9 8.7 8.6 8.5 2.8 3.0 3.1 3.2
11.1 9.5 9.3 9.2 9.1 2.9 3.1 3.2 3.3
13.9 10.1 9.9 9.8 9.7 3.0 3.2 3.2 3.3
16.7 10.8 10.5 10.4 10.3 3.0 3.2 3.3 3.4
19.4 11.4 11.1 11.0 10.9 3.1 3.3 3.4 3.5
22.2 12.0 11.7 11.6 11.5 3.2 3.4 3.5 3.6
TWJ036CA WITH TWE030CA4 A T 1868 CMH
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 2.4 2.4 2.4 2.4 2.0 2.1 2.1 2.2
-19.4 3.2 3.1 3.1 3.0 2.1 2.2 2.3 2.3
-16.7 3.9 3.8 3.8 3.8 2.3 2.4 2.4 2.5
-13.9 4.6 4.5 4.5 4.5 2.4 2.5 2.5 2.6
-11.1 5.4 5.2 5.2 5.1 2.5 2.6 2.7 2.7
-8.3 6.1 5.9 5.9 5.8 2.6 2.8 2.8 2.9
-5.6 6.4 6.3 6.2 6.2 2.7 2.8 2.9 3.0
-2.8 6.8 6.7 6.6 6.5 2.8 2.9 3.0 3.1
0.0 7.1 7.0 6.9 6.8 2.9 3.0 3.1 3.2
2.8 7.5 7.3 7.2 7.2 3.0 3.1 3.2 3.3
5.6 7.8 7.7 7.6 7.5 3.1 3.2 3.3 3.4
8.3 10.4 10.2 10.1 10.0 3.4 3.5 3.6 3.7
11.1 11.2 10.9 10.8 10.7 3.5 3.7 3.8 3.9
13.9 11.9 11.7 11.5 11.4 3.6 3.8 3.9 4.0
16.7 12.6 12.4 12.2 12.1 3.8 4.0 4.1 4.2
19.4 13.4 13.1 13.0 12.8 3.9 4.1 4.2 4.3
22.2 14.1 13.8 13.7 13.5 4.0 4.2 4.3 4.4
TWJ030CA WITH TWE040CA4-B A T 1868 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 1868 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 1656 2165
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEA TING CAP. (HIGH TEMP.) = 8.73 KW
HEA TING CAP. (LOW TEMP.) = 5.13 KW
COMPR. POWER (HIGH TEMP.) = 2504 WATTS
COMPR. POWER (LO W TEMP.) = 2047 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.92
COEFF. OF PERF . (LOW TEMP.) = 2.00
OUTDOOR FAN PO WER = 195 WATTS
INDOOR F AN PO WER = 300 WATTS
NOTE: R ATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 1868 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 1656 2165
HEATING CAP. X0.99 X1.02
COMPR. KW X1.02 X0.97
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEA TING CAP. (HIGH TEMP.) = 10.25 KW
HEA TING CAP. (LOW TEMP.) = 5.98 KW
COMPR. POWER (HIGH TEMP.) = 2776 WATTS
COMPR. POWER (LO W TEMP.) = 1982 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.88
COEFF. OF PERF . (LOW TEMP.) = 2.16
OUTDOOR FAN PO WER = 235 WATTS
INDOOR F AN PO WER = 540 WATTS
NOTE: R ATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-25.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
-22.2 2.3 2.2 2.2 2.2 1.8 1.9 2.0 2.0
-19.4 3.0 3.0 2.9 2.9 1.9 2.0 2.1 2.2
-16.7 3.8 3.7 3.7 3.6 2.0 2.2 2.2 2.3
-13.9 4.5 4.5 4.4 4.4 2.2 2.3 2.3 2.4
-11.1 5.3 5.2 5.2 5.1 2.3 2.4 2.5 2.5
-8.3 6.1 5.9 5.9 5.8 2.4 2.5 2.6 2.6
-5.6 6.4 6.3 6.2 6.2 2.4 2.6 2.7 2.7
-2.8 6.8 6.7 6.6 6.6 2.5 2.7 2.7 2.8
0.0 7.2 7.1 7.0 6.9 2.6 2.7 2.8 2.9
2.8 7.6 7.4 7.4 7.3 2.7 2.8 2.9 3.0
5.6 8.0 7.8 7.7 7.6 2.7 2.9 3.0 3.1
8.3 10.6 10.4 10.3 10.2 3.0 3.2 3.3 3.4
11.1 11.4 11.2 11.0 10.9 3.1 3.3 3.4 3.5
13.9 12.2 11.9 11.8 11.6 3.2 3.4 3.5 3.6
16.7 12.9 12.6 12.5 12.4 3.3 3.5 3.6 3.7
19.4 13.7 13.4 13.2 13.1 3.4 3.6 3.7 3.8
22.2 14.4 14.1 14.0 13.8 3.5 3.8 3.8 4.0
TWE5-PRC001-EN-10-15-99 19
TWJ036CA WITH TWE040CA4-B A T 2378 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 2378 CMH TIMES CORR. FACTO R
AIRFLOW 1995 2590
HEATING CAP. X0.98 X1.01
COMPR. KW X1.03 X0.99
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2293 CMH
HEA TING CAP. (HIGH TEMP.) = 10.37 KW
HEA TING CAP. (LOW TEMP.) = 5.92 KW
COMPR. POWER (HIGH TEMP.) = 2590 WATTS
COMPR. POWER (LO W TEMP.) = 1906 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF . (LOW TEMP.) = 2.36
OUTDOOR FAN PO WER = 235 WATTS
INDOOR F AN PO WER = 360 WATTS
NOTE: R ATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
= VALUE AT NEW AIRFLOW)
Page 20
Performance
Data Heating English Units
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 7.48 7.28 7.18 7.08 1.69 1.76 1.79 1.83
-13 8.81 8.57 8.45 8.33 1.78 1.85 1.89 1.92
-8 10.1 9.86 9.72 9.59 1.86 1.94 1.98 2.02
-3 11.4 11.1 11.0 10.8 1.95 2.03 2.08 2.12
2 12.8 12.4 12.3 12.1 2.03 2.13 2.17 2.22
7 14.1 13.7 13.5 13.4 2.12 2.22 2.27 2.31
12 15.4 15.0 14.8 14.6 2.20 2.31 2.36 2.41
17 16.7 16.3 16.1 15.9 2.29 2.40 2.45 2.51
22 17.7 17.3 17.0 16.8 2.36 2.47 2.53 2.58
27 18.7 18.2 18.0 17.7 2.42 2.54 2.60 2.66
32 19.7 19.2 19.0 18.7 2.49 2.61 2.67 2.73
37 20.7 20.2 19.9 19.6 2.55 2.68 2.74 2.80
42 21.7 21.2 20.9 20.6 2.62 2.75 2.81 2.88
47 28.8 28.0 27.6 27.2 2.73 2.87 2.93 3.00
52 30.8 30.0 29.5 29.1 2.80 2.94 3.01 3.08
57 32.8 31.9 31.5 31.0 2.88 3.02 3.09 3.17
62 34.8 33.9 33.4 32.9 2.95 3.10 3.17 3.25
67 36.8 35.8 35.3 34.8 3.02 3.18 3.25 3.33
72 38.8 37.8 37.2 36.7 3.10 3.26 3.33 3.41
TWA030CD WITH TWE040CA4-B AT 1100 CFM
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP. INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DR Y BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 7.58 7.37 7.26 7.16 1.49 1.56 1.59 1.63
-13 8.87 8.62 8.50 8.38 1.58 1.65 1.69 1.73
-8 10.2 9.88 9.74 9.60 1.66 1.75 1.79 1.83
-3 11.4 11.1 11.0 10.8 1.75 1.84 1.88 1.93
2 12.7 12.4 12.2 12.0 1.84 1.93 1.98 2.03
7 14.0 13.6 13.5 13.3 1.92 2.02 2.08 2.13
12 15.3 14.9 14.7 14.5 2.01 2.12 2.17 2.23
17 16.6 16.2 15.9 15.7 2.10 2.21 2.27 2.33
22 17.7 17.2 16.9 16.7 2.15 2.27 2.33 2.39
27 18.7 18.2 18.0 17.7 2.21 2.33 2.39 2.45
32 19.8 19.2 19.0 18.7 2.27 2.39 2.46 2.52
37 20.8 20.3 20.0 19.7 2.32 2.45 2.52 2.58
42 21.9 21.3 21.0 20.7 2.38 2.51 2.58 2.65
47 29.1 28.3 27.9 27.5 2.47 2.61 2.68 2.75
52 31.2 30.4 29.9 29.5 2.53 2.68 2.75 2.82
57 33.3 32.4 31.9 31.5 2.60 2.74 2.82 2.89
62 35.4 34.4 33.9 33.4 2.66 2.81 2.89 2.96
67 37.5 36.5 35.9 35.4 2.72 2.88 2.96 3.03
72 39.6 38.5 37.9 37.4 2.78 2.94 3.02 3.10
TWA030CD WITH TWE030CA4 AT 1000 CFM
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1000 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 875 1125
HEATING CAP. X0.98 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 28000 BTUH
HEATING CAP. (LOW TEMP.) = 16300 BTUH
COMPR. POWER (HIGH TEMP.) = 2212 WATTS
COMPR. POWER (LOW TEMP.) = 1745 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.86
COEFF. OF PERF. (LOW TEMP.) = 1.98
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN PO WER = 440 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 975 1275
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 28400 BTUH
HEATING CAP. (LOW TEMP.) = 16200 BTUH
COMPR. POWER (HIGH TEMP.) = 2097 WATTS
COMPR. POWER (LOW TEMP.) = 1698 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.16
COEFF. OF PERF. (LOW TEMP.) = 2.14
OUTDOOR FAN POWER = 214 WATTS
INDOOR FAN PO WER = 300 WATTS
NOTE: RATED WITH 25 FEET OF 7/8
SUCTION AND 3/8 LIQUID LINE
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TWA040CD WITH TWE040CA4-B AT 1500 CFM
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 9.52 9.31 9.20 9.10 1.88 1.97 2.02 2.06
-13 11.1 10.9 10.8 10.6 1.96 2.06 2.11 2.16
-8 12.8 12.5 12.3 12.2 2.04 2.14 2.20 2.25
-3 14.4 14.1 13.9 13.7 2.12 2.23 2.29 2.35
2 16.0 15.6 15.5 15.3 2.20 2.32 2.38 2.44
7 17.6 17.2 17.0 16.9 2.28 2.41 2.47 2.54
12 19.2 18.8 18.6 18.4 2.36 2.49 2.56 2.63
17 20.8 20.4 20.2 20.0 2.44 2.58 2.65 2.72
22 22.2 21.7 21.5 21.3 2.52 2.67 2.75 2.82
27 23.6 23.1 22.8 22.6 2.61 2.76 2.84 2.92
32 24.9 24.4 24.1 23.9 2.69 2.86 2.94 3.02
37 26.3 25.7 25.4 25.2 2.78 2.95 3.03 3.11
42 27.7 27.1 26.8 26.5 2.87 3.04 3.12 3.21
47 36.6 35.8 35.4 35.0 3.09 3.28 3.37 3.46
52 39.2 38.4 37.9 37.5 3.20 3.39 3.49 3.59
57 41.9 40.9 40.5 40.0 3.30 3.51 3.61 3.71
62 44.5 43.5 43.0 42.5 3.41 3.62 3.73 3.83
67 47.1 46.1 45.5 45.0 3.52 3.74 3.85 3.96
72 49.7 48.6 48.1 47.5 3.63 3.85 3.97 4.08
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1500 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1325 1700
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1500 CFM
HEATING CAP. (HIGH TEMP.) = 35800 BTUH
HEATING CAP. (LOW TEMP.) = 20400 BTUH
COMPR. POWER (HIGH TEMP.) = 2612 WATTS
COMPR. POWER (LOW TEMP.) = 1918 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.32
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN PO WER = 420 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
20 TWE5-PRC001-EN-10-15-99
Page 21
Performance
Data Heating Metric Units
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 2.2 2.1 2.1 2.1 1.7 1.8 1.8 1.8
-25.0 2.6 2.5 2.5 2.4 1.8 1.9 1.9 1.9
-22.2 3.0 2.9 2.8 2.8 1.9 1.9 2.0 2.0
-19.4 3.3 3.3 3.2 3.2 2.0 2.0 2.1 2.1
-16.7 3.8 3.6 3.6 3.5 2.0 2.1 2.2 2.2
-13.9 4.1 4.0 4.0 3.9 2.1 2.2 2.3 2.3
-11.1 4.5 4.4 4.3 4.3 2.2 2.3 2.4 2.4
-8.3 4.9 4.8 4.7 4.7 2.3 2.4 2.5 2.5
-5.6 5.2 5.1 5.0 4.9 2.4 2.5 2.5 2.6
-2.8 5.5 5.3 5.3 5.2 2.4 2.5 2.6 2.7
0.0 5.8 5.6 5.6 5.5 2.5 2.6 2.7 2.7
2.8 6.1 5.9 5.8 5.7 2.5 2.7 2.7 2.8
5.6 6.4 6.2 6.1 6.0 2.6 2.8 2.8 2.9
8.3 8.4 8.2 8.1 8.0 2.7 2.9 2.9 3.0
11.1 9.0 8.8 8.6 8.5 2.8 2.9 3.0 3.1
13.9 9.6 9.3 9.2 9.1 2.9 3.0 3.1 3.2
16.7 10.2 9.9 9.8 9.6 3.0 3.1 3.2 3.3
19.4 10.8 10.5 10.3 10.2 3.0 3.2 3.3 3.3
22.2 11.4 11.1 10.9 10.8 3.1 3.3 3.3 3.4
TWA030CD WITH TWE040CA4-B AT 1868 CMH
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 2.2 2.2 2.1 2.1 1.5 1.6 1.6 1.6
-25.0 2.6 2.5 2.5 2.5 1.6 1.6 1.7 1.7
-22.2 3.0 2.9 2.9 2.8 1.7 1.8 1.8 1.8
-19.4 3.3 3.3 3.2 3.2 1.8 1.8 1.9 1.9
-16.7 3.7 3.6 3.6 3.5 1.8 1.9 2.0 2.0
-13.9 4.1 4.0 4.0 3.9 1.9 2.0 2.1 2.1
-11.1 4.5 4.4 4.3 4.2 2.0 2.1 2.2 2.2
-8.3 4.9 4.7 4.7 4.6 2.1 2.2 2.3 2.3
-5.6 5.2 5.0 5.0 4.9 2.2 2.3 2.3 2.4
-2.8 5.5 5.3 5.3 5.2 2.2 2.3 2.4 2.5
0.0 5.8 5.6 5.6 5.5 2.3 2.4 2.5 2.5
2.8 6.1 5.9 5.9 5.8 2.3 2.5 2.5 2.6
5.6 6.4 6.2 6.2 6.1 2.4 2.5 2.6 2.7
8.3 8.5 8.3 8.2 8.1 2.5 2.6 2.7 2.8
11.1 9.1 8.9 8.8 8.6 2.5 2.7 2.8 2.8
13.9 9.8 9.5 9.3 9.2 2.6 2.7 2.8 2.9
16.7 10.4 10.1 9.9 9.8 2.7 2.8 2.9 3.0
19.4 11.0 10.7 10.5 10.4 2.7 2.9 3.0 3.0
22.2 11.6 11.3 11.1 11.0 2.8 2.9 3.0 3.1
TWA030CD WITH TWE030CA4 AT 1698 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 1698 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 1486 1910
HEATING CAP. X0.98 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEA TING CAP. (HIGH TEMP.) = 8.20 KW
HEA TING CAP. (LOW TEMP.) = 4.78 KW
COMPR. POWER (HIGH TEMP.) = 2212 WATTS
COMPR. POWER (LO W TEMP.) = 1745 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.86
COEFF. OF PERF . (LOW TEMP.) = 1.98
OUTDOOR FAN PO WER = 214 WATTS
INDOOR F AN PO WER = 440 WATTS
NOTE: R ATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 1868 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 1656 2165
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEA TING CAP. (HIGH TEMP.) = 8.32 KW
HEA TING CAP. (LOW TEMP.) = 4.75 KW
COMPR. POWER (HIGH TEMP.) = 2097 WATTS
COMPR. POWER (LO W TEMP.) = 1698 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.16
COEFF. OF PERF . (LOW TEMP.) = 2.14
OUTDOOR FAN PO WER = 214 WATTS
INDOOR F AN PO WER = 300 WATTS
NOTE: R ATED WITH 7.62 METERS OF 22 MM
SUCTION AND 9.5 MM LIQUID LINE
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 2.8 2.7 2.7 2.7 1.9 2.0 2.0 2.1
-25.0 3.3 3.2 3.2 3.1 2.0 2.1 2.1 2.2
-22.2 3.8 3.7 3.6 3.6 2.0 2.1 2.2 2.3
-19.4 4.2 4.1 4.1 4.0 2.1 2.2 2.3 2.3
-16.7 4.7 4.6 4.5 4.5 2.2 2.3 2.4 2.4
-13.9 5.2 5.0 5.0 5.0 2.3 2.4 2.5 2.5
-11.1 5.6 5.5 5.4 5.4 2.4 2.5 2.6 2.6
-8.3 6.1 6.0 5.9 5.9 2.4 2.6 2.7 2.7
-5.6 6.5 6.4 6.3 6.2 2.5 2.7 2.8 2.8
-2.8 6.9 6.8 6.7 6.6 2.6 2.8 2.8 2.9
0.0 7.3 7.1 7.1 7.0 2.7 2.9 2.9 3.0
2.8 7.7 7.5 7.4 7.4 2.8 3.0 3.0 3.1
5.6 8.1 7.9 7.9 7.8 2.9 3.0 3.1 3.2
8.3 10.7 10.5 10.4 10.3 3.1 3.3 3.4 3.5
11.1 11.5 11.3 11.1 11.0 3.2 3.4 3.5 3.6
13.9 12.3 12.0 11.9 11.7 3.3 3.5 3.6 3.7
16.7 13.0 12.7 12.6 12.5 3.4 3.6 3.7 3.8
19.4 13.8 13.5 13.3 13.2 3.5 3.7 3.8 4.0
22.2 14.6 14.2 14.1 13.9 3.6 3.8 4.0 4.1
TWE5-PRC001-EN-10-15-99 21
TWA040CD WITH TWE040CA4-B AT 2547 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 2547 CMH TIMES CORR. FACTO R
AIRFLOW 2250 2887
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2547 CMH
HEA TING CAP. (HIGH TEMP.) = 10.49 KW
HEA TING CAP. (LOW TEMP.) = 5.98 KW
COMPR. POWER (HIGH TEMP.) = 2612 WATTS
COMPR. POWER (LO W TEMP.) = 1918 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF . (LOW TEMP.) = 2.32
OUTDOOR FAN PO WER = 244 WATTS
INDOOR F AN PO WER = 420 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE
= VALUE AT NEW AIRFLOW)
Page 22
Performance
Data Heating English Units
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 9.68 9.46 9.36 9.25 1.94 2.04 2.08 2.13
-13 11.3 11.1 11.0 10.8 2.02 2.13 2.18 2.23
-8 13.0 12.7 12.6 12.4 2.10 2.21 2.27 2.32
-3 14.6 14.3 14.2 14.0 2.19 2.30 2.36 2.42
2 16.3 15.9 15.8 15.6 2.27 2.39 2.45 2.51
7 17.9 17.6 17.4 17.2 2.35 2.48 2.54 2.61
12 19.6 19.2 19.0 18.8 2.43 2.57 2.63 2.70
17 21.2 20.8 20.6 20.4 2.51 2.65 2.73 2.80
22 22.6 22.1 21.8 21.6 2.59 2.74 2.82 2.89
27 23.9 23.4 23.1 22.8 2.67 2.83 2.91 2.99
32 25.2 24.6 24.4 24.1 2.76 2.92 3.00 3.08
37 26.5 25.9 25.6 25.3 2.84 3.01 3.09 3.17
42 27.8 27.2 26.9 26.6 2.92 3.09 3.18 3.27
47 37.2 36.4 36.0 35.6 3.13 3.32 3.41 3.51
52 39.9 39.0 38.6 38.1 3.23 3.43 3.53 3.63
57 42.5 41.6 41.1 40.7 3.34 3.54 3.64 3.75
62 45.2 44.2 43.7 43.2 3.44 3.65 3.76 3.86
67 47.9 46.8 46.3 45.7 3.54 3.76 3.87 3.98
72 50.5 49.4 48.8 48.3 3.65 3.88 3.99 4.10
TWA050CD WITH TWE050CA5-C AT 1800 CFM
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 12.5 12.2 12.1 12.0 2.50 2.62 2.67 2.73
-13 14.9 14.6 14.4 14.2 2.60 2.72 2.78 2.84
-8 17.3 16.9 16.7 16.5 2.69 2.82 2.88 2.94
-3 19.7 19.2 19.0 18.8 2.78 2.92 2.98 3.05
2 22.0 21.6 21.3 21.1 2.87 3.02 3.09 3.16
7 24.4 23.9 23.7 23.4 2.97 3.12 3.19 3.27
12 26.8 26.3 26.0 25.7 3.06 3.22 3.30 3.38
17 29.2 28.6 28.3 28.0 3.15 3.32 3.40 3.48
22 30.2 29.5 29.2 28.9 3.25 3.42 3.51 3.59
27 31.1 30.5 30.2 29.8 3.34 3.52 3.61 3.70
32 32.1 31.4 31.1 30.8 3.44 3.63 3.72 3.81
37 33.1 32.4 32.0 31.7 3.54 3.73 3.83 3.92
42 34.0 33.3 33.0 32.6 3.63 3.83 3.93 4.03
47 48.0 47.0 46.5 46.0 4.00 4.23 4.34 4.45
52 51.2 50.1 49.5 49.0 4.14 4.38 4.50 4.61
57 54.3 53.1 52.5 52.0 4.28 4.53 4.65 4.78
62 57.5 56.2 55.6 54.9 4.43 4.68 4.81 4.94
67 60.6 59.3 58.6 57.9 4.57 4.83 4.97 5.10
72 63.7 62.3 61.6 60.9 4.71 4.98 5.12 5.26
TWA040CD WITH TWE050CA5-C AT 1500 CFM
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1500 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1325 1700
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1500 CFM
HEATING CAP. (HIGH TEMP.) = 36400 BTUH
HEATING CAP. (LOW TEMP.) = 20800 BTUH
COMPR. POWER (HIGH TEMP.) = 2566 WATTS
COMPR. POWER (LOW TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 244 WATTS
INDOOR FAN PO WER = 510 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1575 2025
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 47000 BTUH
HEATING CAP. (LOW TEMP.) = 28600 BTUH
COMPR. POWER (HIGH TEMP.) = 3222 WATTS
COMPR. POWER (LOW TEMP.) = 2313 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF. (LOW TEMP.) = 2.50
OUTDOOR FAN POWER = 255 WATTS
INDOOR FAN PO WER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
O.D . HEA TING CAPACITY (BTUH/1000) AT TOT AL PO WER IN KILO W ATTS AT
TWA060CD WITH TWE050CA5-C AT 1800 CFM
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICATED INDOOR DRY BULB TEMP.
F . 60 70 75 80 60 70 75 80
-18 14.0 13.8 13.7 13.5 3.24 3.37 3.43 3.50
-13 16.9 16.6 16.4 16.3 3.36 3.50 3.57 3.64
-8 19.7 19.4 19.2 19.1 3.49 3.64 3.71 3.79
-3 22.6 22.2 22.0 21.8 3.62 3.77 3.85 3.93
2 25.4 25.0 24.8 24.6 3.74 3.91 3.99 4.07
7 28.3 27.8 27.6 27.3 3.87 4.04 4.13 4.22
12 31.1 30.6 30.3 30.1 3.99 4.18 4.27 4.36
17 34.0 33.4 33.1 32.8 4.12 4.31 4.41 4.50
22 35.7 35.1 34.8 34.5 4.52 4.74 4.85 4.95
27 37.4 36.8 36.5 36.2 4.93 5.17 5.28 5.40
32 39.1 38.5 38.2 37.8 5.33 5.59 5.72 5.85
37 40.9 40.2 39.8 39.5 5.74 6.02 6.16 6.30
42 42.6 41.9 41.5 41.2 6.14 6.45 6.60 6.76
47 53.9 53.0 52.5 52.1 5.33 5.59 5.72 5.85
52 57.2 56.3 55.8 55.3 5.53 5.80 5.94 6.08
57 60.6 59.5 59.0 58.5 5.73 6.02 6.16 6.30
62 63.9 62.8 62.3 61.7 5.94 6.23 6.38 6.53
67 67.2 66.1 65.5 64.9 6.14 6.44 6.60 6.75
72 70.5 69.3 68.7 68.1 6.34 6.66 6.82 6.98
CORRECTION FA CTORS - OTHER AIRFLO WS
(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW 1575 2025
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1800 CFM
HEATING CAP. (HIGH TEMP.) = 53000 BTUH
HEATING CAP. (LOW TEMP.) = 33400 BTUH
COMPR. POWER (HIGH TEMP.) = 4446 WATTS
COMPR. POWER (LOW TEMP.) = 3166 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.76
COEFF. OF PERF. (LOW TEMP.) = 2.26
OUTDOOR FAN POWER = 395 WATTS
INDOOR FAN PO WER = 750 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8
SUCTION AND 3/8 LIQUID LINE
22 TWE5-PRC001-EN-10-15-99
Page 23
Performance
Data Heating Metric Units
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 2.8 2.8 2.7 2.7 1.9 2.0 2.1 2.1
-25.0 3.3 3.3 3.2 3.2 2.0 2.1 2.2 2.2
-22.2 3.8 3.7 3.7 3.6 2.1 2.2 2.3 2.3
-19.4 4.3 4.2 4.2 4.1 2.2 2.3 2.4 2.4
-16.7 4.8 4.7 4.6 4.6 2.3 2.4 2.5 2.5
-13.9 5.2 5.2 5.1 5.0 2.3 2.5 2.5 2.6
-11.1 5.7 5.6 5.6 5.5 2.4 2.6 2.6 2.7
-8.3 6.2 6.1 6.0 6.0 2.5 2.7 2.7 2.8
-5.6 6.6 6.5 6.4 6.3 2.6 2.7 2.8 2.9
-2.8 7.0 6.9 6.8 6.7 2.7 2.8 2.9 3.0
0.0 7.4 7.2 7.1 7.1 2.8 2.9 3.0 3.1
2.8 7.8 7.6 7.5 7.4 2.8 3.0 3.1 3.2
5.6 8.1 8.0 7.9 7.8 2.9 3.1 3.2 3.3
8.3 10.9 10.7 10.5 10.4 3.1 3.3 3.4 3.5
11.1 11.7 11.4 11.3 11.2 3.2 3.4 3.5 3.6
13.9 12.5 12.2 12.0 11.9 3.3 3.5 3.6 3.8
16.7 13.2 13.0 12.8 12.7 3.4 3.7 3.8 3.9
19.4 14.0 13.7 13.6 13.4 3.5 3.8 3.9 4.0
22.2 14.8 14.5 14.3 14.2 3.7 3.9 4.0 4.1
TWA050CD WITH TWE050CA5-C AT 3057 CMH
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 3.7 3.6 3.5 3.5 2.5 2.6 2.7 2.7
-25.0 4.4 4.3 4.2 4.2 2.6 2.7 2.8 2.8
-22.2 5.1 5.0 4.9 4.8 2.7 2.8 2.9 2.9
-19.4 5.8 5.6 5.6 5.5 2.8 2.9 3.0 3.0
-16.7 6.4 6.3 6.2 6.2 2.9 3.0 3.1 3.2
-13.9 7.1 7.0 6.9 6.9 3.0 3.1 3.2 3.3
-11.1 7.9 7.7 7.6 7.5 3.1 3.2 3.3 3.4
-8.3 8.6 8.4 8.3 8.2 3.2 3.3 3.4 3.5
-5.6 8.8 8.6 8.6 8.5 3.3 3.4 3.5 3.6
-2.8 9.1 8.9 8.8 8.7 3.3 3.5 3.6 3.7
0.0 9.4 9.2 9.1 9.0 3.4 3.6 3.7 3.8
2.8 9.7 9.5 9.4 9.3 3.5 3.7 3.8 3.9
5.6 10.0 9.8 9.7 9.6 3.6 3.8 3.9 4.0
8.3 14.1 13.8 13.6 13.5 4.0 4.2 4.3 4.4
11.1 15.0 14.7 14.5 14.4 4.1 4.4 4.5 4.6
13.9 15.9 15.6 15.4 15.2 4.3 4.5 4.7 4.8
16.7 16.8 16.5 16.3 16.1 4.4 4.7 4.8 4.9
19.4 17.8 17.4 17.2 17.0 4.6 4.8 5.0 5.1
22.2 18.7 18.3 18.0 17.8 4.7 5.0 5.1 5.3
TWA040CD WITH TWE050CA5-C AT 2547 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 2547 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 2250 2887
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2547 CMH
HEA TING CAP. (HIGH TEMP.) = 10.67 KW
HEA TING CAP. (LOW TEMP.) = 6.09 KW
COMPR. POWER (HIGH TEMP.) = 2566 WATTS
COMPR. POWER (LO W TEMP.) = 1900 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.18
COEFF. OF PERF . (LOW TEMP.) = 2.30
OUTDOOR FAN PO WER = 244 WATTS
INDOOR F AN PO WER = 510 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 3057 CMH TIMES CORR. FACTO R
= VALUE AT NEW AIRFLOW)
AIRFLOW 2675 3439
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 3057 CMH
HEA TING CAP. (HIGH TEMP.) = 13.77 KW
HEA TING CAP. (LOW TEMP.) = 8.38 KW
COMPR. POWER (HIGH TEMP.) = 3222 WATTS
COMPR. POWER (LO W TEMP.) = 2313 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 3.24
COEFF. OF PERF . (LOW TEMP.) = 2.50
OUTDOOR FAN PO WER = 255 WATTS
INDOOR F AN PO WER = 750 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE
O.D. HEATING CAPACITY IN KILOWATTS AT TOTAL POWER IN KILOW ATTS AT
TEMP . INDICATED INDOOR DRY BULB TEMP. INDICA TED INDOOR DRY BULB TEMP.
C. 15.6 21.1 23.9 26.7 15.6 21.1 23.9 26.7
-27.8 4.1 4.0 4.0 4.0 3.2 3.4 3.4 3.5
-25.0 5.0 4.9 4.8 4.8 3.4 3.5 3.6 3.6
-22.2 5.8 5.7 5.6 5.6 3.5 3.6 3.7 3.8
-19.4 6.6 6.5 6.4 6.4 3.6 3.8 3.8 3.9
-16.7 7.4 7.3 7.3 7.2 3.7 3.9 4.0 4.1
-13.9 8.3 8.1 8.1 8.0 3.9 4.0 4.1 4.2
-11.1 9.1 9.0 8.9 8.8 4.0 4.2 4.3 4.4
-8.3 10.0 9.8 9.7 9.6 4.1 4.3 4.4 4.5
-5.6 10.5 10.3 10.2 10.1 4.5 4.7 4.8 4.9
-2.8 11.0 10.8 10.7 10.6 4.9 5.2 5.3 5.4
0.0 11.5 11.3 11.2 11.1 5.3 5.6 5.7 5.8
2.8 12.0 11.8 11.7 11.6 5.7 6.0 6.2 6.3
5.6 12.5 12.3 12.2 12.1 6.1 6.4 6.6 6.8
8.3 15.8 15.5 15.4 15.3 5.3 5.6 5.7 5.8
11.1 16.8 16.5 16.3 16.2 5.5 5.8 5.9 6.1
13.9 17.8 17.4 17.3 17.1 5.7 6.0 6.2 6.3
16.7 18.7 18.4 18.3 18.1 5.9 6.2 6.4 6.5
19.4 19.7 19.4 19.2 19.0 6.1 6.4 6.6 6.8
22.2 20.7 20.3 20.1 20.0 6.3 6.7 6.8 7.0
TWE5-PRC001-EN-10-15-99 23
TWA060CD WITH TWE050CA5-C AT 3057 CMH
CORRECTION FA CT ORS - OTHER AIRFLOWS
(VALUE AT 3057 CMH TIMES CORR. FACTO R
AIRFLOW 2675 3439
HEATING CAP. X0.99 X1.01
COMPR. KW X1.02 X0.98
VALUES AT ARI RA TING CONDITIONS OF:
21.1& 8.3/6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 3057 CMH
HEA TING CAP. (HIGH TEMP.) = 15.53 KW
HEA TING CAP. (LOW TEMP.) = 9.79 KW
COMPR. POWER (HIGH TEMP.) = 4446 WATTS
COMPR. POWER (LO W TEMP.) = 3166 WATTS
COEFF. OF PERF. (HIGH TEMP.) = 2.76
COEFF. OF PERF . (LOW TEMP.) = 2.26
OUTDOOR FAN PO WER = 395 WATTS
INDOOR F AN PO WER = 750 WATTS
NOTE: RATED WITH 7.62 METERS OF 28.6 MM
SUCTION AND 9.5 MM LIQUID LINE
= VALUE AT NEW AIRFLOW)
Page 24
Performance
Data
Evaporator Fan Performance
Blower Performance — TWE030CA40B — Wet Coil
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
600 1018.8 0.72 (179.4) 0.71 (176.9)
650 1103.7 0.62 (154.4) 0.61 (152.0)
700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6)
750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1)
800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7)
850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3)
900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)
950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7)
1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3)
1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0)
1100 1867.8 0.31 (77.2) 0.31 (77.2)
1150 1952.7 0.20 (49.8) 0.22 (54.8)
1200 2037.6 0.08 (19.9) 0.10 (24.9)
NOTES:
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOL TS 220 VOL TS
Blower Performance — TWE040CA40C — Wet Coil
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
700 1188.6 0.58 (144.5)
750 1273.5 0.61 (152.0) 0.55 (137.0)
800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5)
850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5)
900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)
950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1)
1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6)
1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2)
1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7)
1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8)
1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3)
1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9)
1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5)
1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8)
1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9)
1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9)
1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)
NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOLTS 220 VOLTS
24 TWE5-PRC001-EN-10-15-99
Page 25
Performance
Data
Evaporator Fan Performance
Blower Performance — TWE050CA50D — Wet Coil
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
900 1528.2
950 1613.1 0.63 (156.9)
1000 1698.0 0.61 (152.0) 0.62 (154.4)
1050 1782.9 0.58 (144.5) 0.60 (149.5)
1100 1867.8 0.54 (134.5) 0.57 (142.0)
1150 1952.7 0.50 (124.6) 0.53 (132.0)
1200 2037.6 0.45 (112.1) 0.49 (122.1)
1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6)
1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7)
1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7)
1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3)
1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8)
1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4)
1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0)
1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6)
1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2)
1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7)
1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8)
1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4)
1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4)
1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5)
1950 3311.1 0.02 (5.0)
NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtr act 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOL TS 220 VOL TS
TWE5-PRC001-EN-10-15-99 25
Page 26
Performance
Data
Air Pressure Drop (Inches) - Electric Heaters
Pressure Drop For Electric Heaters In Air Handler Models
NUMBER OF RACKS
12 34 5
AIRFLOW AIRFLOW AIR PRESSURE DROP
CFM CMH IN. W.G. (P ASCALS)
600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)
700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0)
800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)
900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5)
1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9)
1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9)
1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4)
1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4)
1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4)
1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4)
1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3)
1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3)
1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3)
1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3)
2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)
NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.
HEATER RACKS
HEATER NO. OF
MODEL NO. RACKS
BAY96X1405 1
BAY96X1406 2
BAY96X1408 2
BAY96X1410 2
BAY96X1411 3
BAY96X1415 3
BAY96X1419 4
BAY96X1421 4
BAY96X1426 5
BAY96X3411 3
BAY96X3415 3
26 TWE5-PRC001-EN-10-15-99
Page 27
Supplementary
Heaters
THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.
TWE030C-Heater Model Number BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW
Vertical A/C or Elec. Furnace LLLLLLLLLLLL
Upflow Heat Pump LLLLLLLLMMLL
Vertical A/C or Elec. Furnace LLLLLLLLLLLL
Downflow Heat Pump LLLLLLLLHHLH
Horizontal A/C or Elec. Furnace LLLLLLLLLLLL
Left Heat Pump LLLLLLLLMMLL
Horizontal A/C or Elec. Furnace LLLLLLLLLLLL
Right Heat Pump LLLLLLLLHHLL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.
TWE040C-Heater Model Number BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW
Vertical A/C or Elec. Furnace LLLLLLLLLLLL
Upflow Heat Pump LLLLLMMHHHMM
Vertical A/C or Elec. Furnace LLLLLLLLLLLL
Downflow Heat Pump LLLLLLLHHHLL
Horizontal A/C or Elec. Furnace LLLLLLLLLLLL
Left Heat Pump LLLLLLLHHHLL
Horizontal A/C or Elec. Furnace LLLLLLLLLLLL
Right Heat Pump LLLLLLLHHHLL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.
TWE050C-Heater Model Number BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1415 1419 1421 1426 3415
Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 21.6 KW 12.8 KW
Vertical A/C or Elec. Furnace — — LLLL L LLL
Upflow Heat Pump L L LLLL M MHL
Vertical A/C or Elec. Furnace — — LLLL L LLL
Downflow Heat Pump L L LLLL H HHL
Horizontal A/C or Elec. Furnace — — LLLL L LLL
Left Heat Pump L L LLLL H HHL
Horizontal A/C or Elec. Furnace — — LLLL L LLL
Right Heat Pump L L LLLL MMHL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A and 1414 not approved for this model.
TWE5-PRC001-EN-10-15-99 27
Page 28
Electrical
Data
System Wiring Diagram
Legend
Symbols
NOTES:
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED
CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.
28 TWE5-PRC001-EN-10-15-99
Page 29
Dimensions
TWE030-050C Outline Drawing
ALL DIMENSIONS ARE IN INCHES (MM)
MINIMUM UNIT CLEARANCE SALE
TO COMBUSTIBLE SERVICE CLEARANCE
SIDES 0 (0) 2 (50.8)
FRONT 0 (0) 21 (533.4)
BACK 0 (0) 0 (0)
INLET DUCT 0 (0) 1 (25.4)
OUTLET DUCT 1 (25.4)
TWE5-PRC001-EN-10-15-99 29
MA TERIAL (REQUIRED) (RECOMMENDED)
MODEL NO. A B C D E F
TWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV
TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV
TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV
(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)
(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)
(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)
FLOW
CONTROL
Page 30
Dimensions
TWJ020-036CA and TWA030-060CA Outline Drawing
All dimensions are in inches (mm)
1
/8 (28.6) DIA. K.O. WITH
1
7
/8 (22.2) DIA. HOLE
ELECTRICAL POWER
9
(229)
5
(127)
5
/8 (41)
1
SERVICE PANEL
ELECTRICAL AND
REFRIGERANT COMPONENTS
CLEARANCES PER PREVAILING
7
/
8
6
(175)
3
/
4
9
(248)
7
/8 (22.2) DIA. HOLE
LOW VOLTAGE
1
8
/
4
(210)
(121)
2
GAS LINE BALL SERVICE VALVE, BALL
1/4 TURN "D" O.D. FEMALE BRAZED
CONNECTION WITH 1/4" SAE FLARE
PRESSURE T AP FITTING.
LIQUID LINE SERVICE VALVE, "E" O.D.
FEMALE BRAZED CONNECTION WITH
3
2
/8 (60)
1/4" SAE FLARE PRESSURE TAP
FITTING.
FIG. 2
4
(51)
1
1
(32)
3
/
C
B
TOP DISCHARGE AREA SHOULD BE
UNRESTRICTED FOR AT LEAST FIVE (5)
FEET ABOVE UNIT. UNIT SHOULD BE
PLACED SO ROOF RUN-OFF WATER
/
4
DOES NOT POUR DIRECTLY ON UNIT,
AND SHOULD BE AT LEAST 12" (305)
FROM WALL AND ALL SURROUNDING
SHRUBBERY ON TWO SIDES. OTHER
TWO SIDES UNRESTRICTED.
A
4
GAS LINE SERVICE VALVE, "D" O.D.
FEMALE BRAZED CONNECTION WITH
1/4" SAE FLARE PRESSURE TAP
FITTING.
LIQUID LINE SERVICE VALVE, "E" O.D.
FEMALE BRAZED CONNECTION WITH
1/4" SAE FLARE PRESSURE TAP
FITTING.
FIG. 1
MODEL Figure A B C D E
TWJ020CA00A 1 243/8 281/4 245/8
(619) (718) (625) (19) (8)
TWJ024CA00A 1 323/4 281/4 245/8
(832) (718) (625) (19) (8)
TWJ030CA00A 1 323/4 281/4 245/8
(832) (718) (625) (22.2) (9.53)
TWJ036CA00A 2 37 327/8 283/4
(940) (835) (730) (22.2) (9.53)
TWA030CD00A 1 323/4 281/4 245/8
(832) (718) (625) (22.2) (9.53)
TWA040CD00A 2 323/4 327/8 283/4 11/8
(832) (835) (730) (28.6) (9.53)
TWA050CD00A 2 37 387/8 343/4 11/8
(940) (987) (883) (28.6) (9.53)
TWA060CD00A 2 443/4 387/8 343/4 11/8
(1137) (987) (883) (28.6) (9.53)
From Dwg. 21D147562 Rev. 6
3
3
7
7
7
5
/4
/4
/8
/8
/8
/16
5
/16
3
/8
3
/8
3
/8
3
/8
3
/8
3
/8
30 TWE5-PRC001-EN-10-15-99
Page 31
Convertibility
TWE030 Through 050 Convertibility
Six (6) Way Convertibility
One Unit - 4 Applications
Easy Conver sion to Opposite Side Access
TWE5-PRC001-EN-10-15-99 31
Page 32
Mechanical
Specification Options
General
Blower coil units shall be completely
factory assembled including coil, condensate drain pan, fan, motor, filters and
controls in an insulated casing that can
be applied in horizontal or vertical
configuration.
This new line of TWE-C air handlers
provides exclusive compact size combined with simple four-way convertibility
in three sizes. The unit ships in the right
hand horizontal configuration and
converts to vertical upflow just by
standing the unit on end. No tools
required. Simple coil rotation provides
downflow and horizontal left applications.
The four-way convertibility provides you
inventory benefits and service/installation
flexibility. The simple conversion provides
opposite side access for installation and
service.
Casing
Units shall have rugged sheet metal and
steel frame construction and shall be
painted with an enamel finish. Casing
shall be insulated and knockouts shall be
provided for electrical power and control
wiring.
Refrigerant Circuits
The TWE units shall have a single
refrigerant circuit. TWE03-040C refr igerant circuit shall be controlled by a flow
control check valve (FCCV). The
TWE050C refrigerant circuit shall be
controlled by a factory-installed thermal
expansion valve.
Coil
Aluminum fin surface shall be mechanically bonded to 3/8-inch OD copper
tubing. Coils shall be factory pressure
and leak tested.
Fan
Forward curved, dynamically and
statically balanced with three-speed
direct drive shall be standard, fan motor
bearing shall be permanently lubr icated.
Controls
Fan contactor, and plug-in module for
accessory electric heat control shall be
included. TWE models shall also include
check valves.
Filters
Filters shall be included as standard.
Accessories
Electric Heaters — Shall be available in
a wide range of capacities and voltages
with various staging options and plug in
control wiring. Heaters shall fit inside
internal compartment.
The Trane Company
Trane International Unitary Systems
1789 Chaussée de W avre
1160 Brussels
Belgium