Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Product Data
TWE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
TTB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
TTA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Performance Data
TTB/TWE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TTA/TWE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Supplementary Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
System Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
©American Standard Inc. 1999
2 TWE5-PRC000-EN
Page 3
TWE

Features and Benefits

AIR HANDLING UNITS
Features
Ships horizontal
Six way convertibility- horizontal (left
and right), upflow, downflow (front and rear access)
Electrical, refrigerant, condensate and
blower access convertible to either side
Corrosion resistant galvanized steel with
attractive finish
Internally enhanced finned coil tubes
Direct drive motor
Standard filters
Multi-speed blower
220 volt primary and 24 volt secondary
transformer
Insulated cabinet
External access to heater circuit breakers
Start kits are not required
Built-in indoor fan delay function for
increased efficiency. No kit required.
New Features
Improved filter access and latch -
Eliminate current T-bar and shipping bracket.
Provision for 1 1/8” thick field supplied
electrostatic filter
Reversible Duct Flanges - Fits up to
1 1/2” duct board
Improve controls access with control
box mounted next to blower.
40 VA transformer with 5 amp
automotive style fuse on 3 tons and less
5 Amp automotive style fuse replaces
Bussman “red cap” fuse on 3.5 to 5 ton models
Blower mounting brackets improved -
Front access to screw with power driver
Improved bottom carton cushioning
1” thick foil faced insulation for all
models
TTB
TTA
CONDENSING UNITS
Features:
Vertical Air Discharge
High Efficiency TRANE Climatuff
Compressor
Powder Paint finish
Brazed or flare connections
3TWE5-PRC000-EN
Benefits:
Flexibility in application
®
Quality and reliability
Uniform covering for a smooth,
attractive and corrosion-resistant finish
Page 4

System Performance

Outdoor Unit Indoor Unit *MBh kW CFM CMH
Ducted Air Handlers TTB524CA00A TWE030CA40B 25.8 6.9 900 1520 TTB530CA00A TWE030CA40C 30.8 8.4 1000 1689 TTB530CA00A TWE040CA40C 32.4 9.5 1200 2038 TTB536CA00A TWE040CA40C 39.0 10.1 1200 2038 TTA030CD00A† TWE030CA40B 30.5 8.9 1000 1689 TTA030CD00A† TWE040CA40C 32.5 9.4 1125 1900 TTA040CD00A† TWE040CA40C 41.0 12.0 1325 2238 TTA040CD00A† TWE050CA50D 43.9 12.8 1600 2703 TTA050CD00A† TWE050CA50D 52.7 15.4 1800 3040 TTA060CD00A† TWE050CA50D 62.8 18.4 1800 3040
†Outdoor: 380-415/50/3, Indoor: 220-240/50/1
*Cooling capacity is based on 94ºF outside ambient, 80ºF DB/67ºF WB air on coil.
95º F Indoor
4 TWE5-PRC000-EN
Page 5

Model Nomenclature

TW E 0 30 C A 4 0 A 0
1,2 3 4 5,6 7 8 9 10 11 12
Digit 1,2 - Product Type TW = Split System Component
Heat Pump Compatible
Digit 3 - Airflow Configuration E = Convertible
Digit 4 - Refrigerant Connections 0 = Brazed
5 = Flare
Digits 5,6 - Nominal Capacity 30 = 30 MBh
40 = 40 MBh 50 = 50 MBh
Digit 7 C = Development Sequence
Digit 8 - Voltage A = 220/1/50
Digit 9 - Refrigerant Flow Control 4 = Accutron Flow Control/ Check Valve
5 = Bleed TXV
Digit 10 - Not Used
Digit 11 - Minor Design Change
Digit 12 - Service Digit
5TWE5-PRC000-EN
Page 6
Product Data
Table 1 — TWE Product Specifications
Model TWE030CA40B TWE040CA40C TWE050CA50D Power Conn.— Volts/Ph/Hz 220/1/50 220/1/50 220/1/50 Indoor Coil - Type Plate Fin Plate Fin Plate Fin
Rows 3 3 3 Fins per inch (Fins per 25.4mm) 14 14 14 Face Area ft Tube Size in. (mm) Refrigerant Control FCCV FCCV FCCV Drain Conn. Size in. (mm) Duct Connections —————————— SEE OUTLINE DRAWING ———————————
Indoor Fan - Type Centrifugal Centrifugal Centrifugal
No. Used 1 1 1 Diameter in. (mm) 10.0 (254.0) 10.0 (254.0) 11.0 (279.4) Width in. (mm) 8.0 (203.2) 10.0 (254.0) 10.0 (254.0) Type Drive - No. Speeds Direct - 3 Direct - 3 Direct - 3 Airflow (High)
CFM @ 0.0 in. w.g. —————————— SEE FAN PERFORMANCE TABLE ——————————
CMH @ 0.0 mm w.g. —————————— SEE FAN PERFORMANCE TABLE —————————— No. Motors - HP 1 ­Motor RPM 1000 900 900 Volts/Ph/Hz 220/1/50 220/1/50 220/1/50 F.L. Amps 2.6 2.1 4.5 L.R. Amps 3.3 4.2 10.1
Filters
Vertical Applications
Filter Furnished Yes Yes Yes
Type Furnished Throwaway Throwaway High Velocity
No.-Size-Thickness 1 - 20 x 20 - 1 1 - 20 x 20 - 1 1 - 2 2 x 20 - 1 Horizontal Applications
Filter Furnished No No No
Type Recommended —————————— SEE NOTE BELOW ——————————
No.-Size-Thickness —————————— SEE NOTE BELOW ——————————
Refrigerant Line Size
Line Size ID Gas in. (mm) Line Size ID Liquid in. (mm)
Dimensions (H x W x D)
Crated - in. 44.5 x 24.0 x 23.5 53.25 x 26.0 x 23.5 59.5 x 26.0 x 23.5
- (mm) (1130 x 610 x 597) (1353 x 660 x 597) (1511 x 660 x 597) Uncrated - in. 43.0 x 21.5 x 21.0 52.0 x 23.5 x 21.0 58.0 x 23.5 x 21.0
- (mm) (1092 x 546 x 533) (1321 x 597x 533) (1473 x 597 x 533)
Weight Ibs. (kg)
Shipping 125 (56.7) 165 (74.8) 198 (898) Net 115 (52.2) 150 (68.0) 183 (83.0)
Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter: Face Area (ft2) = CFM/300 High Velocity Filter: Face Area (ft2) = CFM/500
2
-(m2) 3.21 (.30) 5.04 (.47) 6.19 (.58)
3
/8 (9.52)
3
/4 NPT
1
/3 1 - 1/3 1 - 3/4
7
/8 (22.23) 11/8 (28.56) 11/8 (28.56)
3
/8 (9.52)
3
/8 (9.52)
3
/4 NPT
3
/8 (9.52)
3
/8 (9.52)
3
/4 NPT
3
/8 (9.52)
6 TWE5-PRC000-EN
Page 7
Product Data
Table 2 — TTB5 Product Specifications
1,2
Model TTB524CA00A TTB530CA00A Power Conn. — Volts/Ph/Hz 200-230/1/50 200-230/1/50
Min. Brch. Cir. Ampacity
3
19 20 Br. Cir. Max. (Amps) 30 30 Prot. Rtg. Recmd. (Amps) 30 30 Compressor Type Climatuff® Reciprocating Climatuff® Reciprocating No. Used - No. Speeds 1 — 1 1 — 1 Volts/Ph/Hz 200-230/1/50 200-230/1/50 R.L. Amps - L.R. Amps 13.9 — 60 13.9 — 79 Voltage Utilization Range 180-253 180-253 Brch. Cir. Selec. Cur. Amps 13.9 14.9 Outdoor Fan - Type Propeller Propeller Dia. - in. (mm) - No. Used 18 (457) — 1 18 (457) — 1 Type Drive - No. Speeds Direct — 1 Direct — 1 CFM @ 0.0 in. w.g.
4
1925 2225 CMH @ 0.0 mm w.g. 908 1050 No. Motors 1 1 Motor HP (W)
1
/6 (124)
1
/6 (124) Motor Speed RPM 1100 1100 Volts/Ph/Hz 200-230/1/50 200-230/1/50 F.L. Amps 1.30 1.30 Outdoor Coil - Type Spine Fin
Spine Fin
Rows - Fins/in. (Fins/mm) 1 — 24 (1) 1 — 24 (1) Face Area - ft2 (m2) 10.96 (1.02) 14.93 (1.39) Tube Size - in. (mm)
3
/8 (10)
3
/8 (10)
Refrigerant
R-225 - lbs. (kg) 4 lbs, 15 oz. (2.24) 6 lbs, 11 oz. (3.03) Factory Supplied Yes Yes Line Size - O.D. Gas Line Size - O.D. Liq.6 - in. (mm)
6
- in. (mm)
3
/4 (20)
5
/16 (8)
3
/4 (20)
5
/16 (8)
Dimensions (H x W x D)
Crated - in. 263/8 x 267/8 x 267/8 333/8 x 267/8 x 267/8
- (mm) (670 x 683 x 683) (848 x 683 x 683)
Uncrated See Outline Dwg. See Outline Dwg.
Weight lbs. (kg)
Shipping 176 (79.8) 184 (83.5) Net 166 (75.3) 174 (78.9)
Notes:
1
Rated in accordance with ARI Standard 210/240.
2
Rated in accordance with ARI Standard 270.
3
Calculated in accordance with National Electric Code. Suitable for use with HACR circuit breakers or fuses.
4
Standard air — dry coil — outdoor.
5
This value approximate. For more precise value see unit nameplate and service instructions.
6
Max. linear length 80 ft.; max. lift — suction 60 ft.; max. lift — liquid 60 ft. Max. length of precharged tubing 50 ft. For greater length refer to
Refrigerant Piping Manual Pub. No. 32-3009.
7TWE5-PRC000-EN
Page 8
Product Data
Table 3 — TTB5 Product Specifications
1,2
Model TTB536CA00A Power Conn. - Volts/Ph/Hz 200-230/1/50
Min. Brch. Cir. Ampacity
3
24 Br. Cir. Max. (Amps) 40 Prot. Rtg. Recmd. (Amps) 40 Compressor Type Climatuff® Reciprocating No. Used - No. Speeds 1 — 1 Volts/Ph/Hz 200-230/1/50 R.L. Amps - L.R. Amps 17.6 — 95 Voltage Utilization Range 180-253 Brch. Cir. Selec. Cur. Amps 17.6 Outdoor Fan - Type Propeller Dia. in. (mm) - No. Used 18 (457) — 1 Type Drive - No. Speeds Direct — 1 CFM @ 0.0 in. w.g.
4
2225 CMH @ 0.0 mm w.g. 1050 No. Motors 1 Motors HP (W)
1
/6 (124) Motor Speed RPM 1100 Volts/Ph/Hz 200-230/1/50 F.L. Amps 1.30 Outdoor Coil - Type Spine Fin
Rows - Fins/in. (Fins/mm) 1 — 24 (1) Face Area - ft2 (m2) 14.93 (1.39) Tube Size - in. (mm)
3
/8 (10)
Refrigerant
R-225 - lbs. (kg) 6 lbs, 11 oz. (3.03) Factory Supplied Yes Line Size - O.D. Gas Line Size - O.D. Liq.6 - in. (mm)
6
- in. (mm)
3
/4 (20)
5
/16 (8)
Dimensions (H x W x D)
Crated - in. 333/8 x 267/8 x 267/8
- (mm) (848 x 683 x 683)
Uncrated See Outline Dwg.
Weight lbs. (kg)
Shipping 203 (92.1) Net 193 (87.5)
Notes:
1
Rated in accordance with ARI Standard 210/240.
2
Rated in accordance with ARI Standard 270.
3
Calculated in accordance with National Electric Code. Suitable for use with HACR circuit breakers or fuses.
4
Standard air — dry coil — outdoor.
5
This value approximate. For more precise value see unit nameplate and service instructions.
6
Max. linear length 80 ft.; max. lift — suction 60 ft.; max. lift — liquid 60 ft. Max. length of precharged tubing 50 ft. For greater
length refer to Refrigerant Piping Manual Pub. No. 32-3009.
8 TWE5-PRC000-EN
Page 9
Product Data
Table 4 — TTA Product Specifications
Model TTA030CD00A TTA040CD00A TTA050CD00A TTA060CD00A Power Conn. - Volts/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50
Fuse Size - max. amps Per Local Codes Per Local Codes Per Local Codes Per Local Codes
Compressor - Type —————————— Climatuff® Reciprocating ——————————
No. Used - No. Speeds 1 - 1 1 - 1 1 - 1 1 - 1 Volts/Ph/Hz 380-415/3/50 380-415/3/50 380-415/3/50 380-415/3/50 F.L. Amps L.R. Amps 51.0 51.0 71.0 64.0
Outdoor Fan - Type Propeller Propeller Propeller Propeller
No. Used 1111 Diameter in. (mm) 18 (457) 18 (457) 22 (559) 26 (660) Type Drive - No. Speeds Direct-1 Direct-1 Direct-1 Direct-1
No. Motors - HP 1 ­Motor Speed (RPM) 1 (900) 1 (900) 1 (690) 1 (690) Volts/Ph/Hz 400/1/50 400/1/50 400/1/50 400/1/50 F.L. Amps 0.80 0.80 1.00 1.70
Outdoor Coil - Type Spine Fin
No. Rows - Fins/in. 1 - 24 1 - 24 1 - 24 1 - 24 Face Area ft2 (m2) 12.22 (1.14) 16.84 (1.57) 25.50 (2.37) 35.39 (3.29) Tube Size in. (mm)
Refrigerant
R-22 Line Size - OD Gas in. (mm) Line Size - OD Liq. in. (mm)
Dimensions (H x W x D)
Crated - in. 25.0 x 30.0 x 26.5 33.3 x 30.0 x 26.5 41.3 x 34.8 x 31.3 45.5 x 41.0 x 37.0
- (mm) (635 x 762 x 673) (846 x 762 x 673) (1049 x 884 x 795) (1156 x 1041 x 940) Uncrated - in. 24.3 x 28.3 x 24.6 32.8 x 28.3 x 24.6 40.6 x 32.9 x 28.8 44.8 x 38.9 x 34.8
- (mm) (617 x 719 x 625) (833 x 719 x 625) (1031 x 836 x 732) (1138 x 988 x 884)
Weight- lbs. (kg)
Shipping 190.0 (86.2) 211.0 (95.7) 254.0 (115.2) 333.0 (151.0) Net 181.0 (82.1) 200.0 (90.7) 239.0 (108.4) 314.0 (142.0)
1
At ARI system rating conditions of 80° F-DB/67° F-WB indoor & 95° F-DB outdoor.
2
Rated for 25 feet (7.5 meters) of evacuated refrigerant piping.
1
5.0 7.0 9.0 10.6
CFM @ 0.0 in. w.g. 1815 1845 2225 4250 CMH @ 0.0 mm w.g. 3083 3134 3780 7220
2
- lbs. (kg) 5 Ibs, 12 oz. (2.61) 7 Ibs, 2 oz. (3.23) 9 Ibs, 2 oz. (4.14) 13 Ibs, 0 oz. (5.90)
1
/4 1 - 1/4 1 - 1/3 1 - 1/3
3
/8 (9.52)
7
/8 (22.3) 11/8 (28.6) 11/8 (28.6) 11/8 (28.6)
3
/8 (9.52)
Spine Fin
3
3
/8 (9.52)
/8 (9.52)
Spine Fin
3
3
/8 (9.52)
/8 (9.52)
Spine Fin
3
/8 (9.52)
3
/8 (9.52)
9TWE5-PRC000-EN
Page 10
Performance Data Cooling English Units
TTB524CA00A WITH TWE030CA40B
AT 900 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 22.9 20.9 22.6 23.4* 24.0* 24.6* 1.90
85 63 24.7 17.6 19.3 21.0 22.7 24.4 1.97
67 26.6 13.9 15.6 17.3 19.0 20.7 2.04 71 28.6 10.2 11.9 13.6 15.3 17.0 2.11 59 22.6 20.7 22.4 23.1* 23.8* 24.3* 2.01
90 63 24.4 17.4 19.1 20.8 22.5 24.2 2.07
67 26.2 13.8 15.5 17.2 18.9 20.6 2.14 71 28.1 10.0 11.7 13.4 15.1 16.8 2.21 59 22.3 20.6 22.3* 22.9* 23.5* 24.0* 2.11
95 63 24.0 17.3 19.0 20.7 22.4 24.0* 2.18
67 25.8 13.6 15.3 17.0 18.7 20.4 2.25 71 27.7 9.9 11.6 13.3 15.0 16.7 2.32 59 21.5 20.2 21.7* 22.3* 22.8* 23.4* 2.20
100 63 23.2 16.9 18.6 20.3 22.0 23.4* 2.26
67 24.9 13.2 14.9 16.6 18.4 20.1 2.33 71 26.7 9.5 11.2 12.9 14.6 16.3 2.40 59 20.8 19.9 21.1* 21.6* 22.2* 22.7* 2.29
105 63 22.4 16.6 18.3 20.0 21.7 22.7* 2.35
67 24.0 12.9 14.6 16.3 18.0 19.7 2.41 71 25.7 9.1 10.8 12.5 14.2 15.9 2.48 59 19.3 19.2 19.8* 20.3* 20.8* 21.3* 2.47
115 63 20.7 15.9 17.6 19.3 20.8* 21.3* 2.53
67 22.2 12.2 13.9 15.6 17.3 19.0 2.58 71 23.8 8.4 10.1 11.8 13.5 15.2 2.64
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 775 1025 AIRFLOW 775 1025
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS GROSS CAPACITY = 25800 BTUH AIRFLOW = 900 CFM COMPRESSOR POWER = 2245 WATTS I.D. FAN POWER = 425 WATTS O.D. FAN POWER = 165 WATTS S.E.E.R. = 8.71 BTUH/WATT E.E.R. = 9.10 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
TTB530CA00A WITH TWE030CA40B
AT 1000 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 27.4 24.2 26.1 27.6* 28.3* 29.0* 2.05
85 63 29.5 20.5 22.4 24.3 26.2 28.1 2.12
67 31.6 16.5 18.4 20.2 22.1 24.0 2.20 71 33.9 12.3 14.2 16.1 18.0 19.8 2.28 59 27.1 24.1 25.9 27.3* 28.0* 28.7* 2.15
90 63 29.1 20.4 22.3 24.1 26.0 27.9 2.23
67 31.2 16.3 18.2 20.1 21.9 23.8 2.31 71 33.4 12.1 14.0 15.9 17.8 19.7 2.39 59 26.7 23.9 25.8 27.0* 27.7* 28.4* 2.25
95 63 28.7 20.2 22.1 24.0 25.9 27.7 2.33
67 30.8 16.1 18.0 19.9 21.8 23.7 2.41 71 33.0 11.9 13.8 15.7 17.6 19.5 2.49 59 25.8 23.5 25.4 26.3* 27.0* 27.6* 2.34
100 63 27.8 19.8 21.7 23.6 25.4 27.3 2.42
67 29.8 15.7 17.6 19.5 21.4 23.2 2.50 71 31.9 11.5 13.4 15.3 17.2 19.1 2.58 59 25.0 23.1 25.0 25.6* 26.3* 26.6* 2.43
105 63 26.8 19.4 21.3 23.1 25.0 26.9* 2.51
67 28.8 15.3 17.2 19.1 20.9 22.8 2.59 71 30.8 11.1 13.0 14.9 16.8 18.6 2.67 59 23.2 22.3 23.5* 24.2* 24.7* 25.3* 2.62
115 63 25.0 18.6 20.4 22.3 24.2 25.3* 2.69
67 26.7 14.5 16.3 18.2 20.1 22.0 2.77 71 28.6 10.3 12.2 14.0 15.9 17.8 2.84
C
ORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW 1000 1000 AIRFLOW 1000 1000 TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 30800 BTUH AIRFLOW = 1000 CFM COMPRESSOR POWER = 2410 WATTS I.D. FAN POWER = 440 WATTS O.D. FAN POWER = 170 WATTS S.E.E.R. = 9.80 BTUH/WATT E.E.R. = 10.20 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
10 TWE5-PRC000-EN
Page 11
Performance Data Cooling Metric Units
TTB524CA00A WITH TWE030CA40B
AT 1528 CMH
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 6.7 6.1 6.6 6.9* 7.0* 7.2* 1.90
29.4 17.2 7.2 5.2 5.7 6.2 6.7 7.1 1.97
19.4 7.8 4.1 4.6 5.1 5.6 6.1 2.04
21.7 8.4 3.0 3.5 4.0 4.5 5.0 2.11
15.0 6.6 6.1 6.6 6.8* 7.0* 7.1* 2.01
32.2 17.2 7.1 5.1 5.6 6.1 6.6 7.1 2.07
19.4 7.7 4.0 4.5 5.0 5.5 6.0 2.14
21.7 8.2 2.9 3.4 3.9 4.4 4.9 2.21
15.0 6.5 6.0 6.5* 6.7* 6.9* 7.0* 2.11
35.0 17.2 7.0 5.1 5.6 6.1 6.6 7.0 2.18
19.4 7.6 4.0 4.5 5.0 5.5 6.0 2.25
21.7 8.1 2.9 3.4 3.9 4.4 4.9 2.32
15.0 6.3 5.9 6.4* 6.5* 6.7* 6.9* 2.20
37.8 17.2 6.8 5.0 5.4 5.9 6.4 6.9 2.26
19.4 7.3 3.9 4.4 4.9 5.4 5.9 2.33
21.7 7.8 2.8 3.3 3.8 4.3 4.8 2.40
15.0 6.1 5.8 6.2* 6.3* 6.5* 6.7* 2.29
40.6 17.2 6.6 4.9 5.4 5.9 6.4 6.7 2.35
19.4 7.0 3.8 4.3 4.8 5.3 5.8 2.41
21.7 7.5 2.7 3.2 3.7 4.2 4.7 2.48
15.0 5.7 5.6 5.8* 5.9* 6.1* 6.2* 2.47
46.1 17.2 6.1 4.7 5.2 5.7 6.1 6.2 2.53
19.4 6.5 3.6 4.1 4.6 5.1 5.6 2.58
21.7 7.0 2.5 3.0 3.5 4.0 4.5 2.64
C
ORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW 0.368 0.486 AIRFLOW 0.368 0.486 TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT ARI RATING CONDITIONS GROSS CAPACITY = 7.54 KW AIRFLOW = 0.42 CMS AIRFLOW = 900. CFM COMPRESSOR POWER = 2245 WATTS I.D. FAN POWER = 425 WATTS O.D. FAN POWER = 165 WATTS COP = 2.67 EER = 9.10 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
TTB530CA00A WITH TWE030CA40B
AT 1700 CMH
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.0 7.1 7.6 8.1* 8.3* 8.5* 2.05
29.4 17.2 8.6 6.0 6.6 7.1 7.7 8.2 2.12
19.4 9.3 4.8 5.4 5.9 6.5 7.0 2.20
21.7 9.9 3.6 4.2 4.7 5.3 5.8 2.28
15.0 7.9 7.1 7.6 8.0* 8.2* 8.4* 2.15
32.2 17.2 8.5 6.0 6.5 7.1 7.6 8.2 2.23
19.4 9.1 4.8 5.3 5.9 6.4 7.0 2.31
21.7 9.8 3.5 4.1 4.7 5.2 5.8 2.39
15.0 7.8 7.0 7.6 7.9* 8.1* 8.3* 2.25
35.0 17.2 8.4 5.9 6.5 7.0 7.6 8.1 2.33
19.4 9.0 4.7 5.3 5.8 6.4 6.9 2.41
21.7 9.7 3.5 4.0 4.6 5.2 5.7 2.49
15.0 7.6 6.9 7.4 7.7* 7.9* 8.1* 2.34
37.8 17.2 8.1 5.8 6.4 6.9 7.4 8.0 2.42
19.4 8.7 4.6 5.2 5.7 6.3 6.8 2.50
21.7 9.3 3.4 3.9 4.5 5.0 5.6 2.58
15.0 7.3 6.8 7.3* 7.5* 7.7* 2.0* 2.43
40.6 17.2 7.9 5.7 6.2 6.8 7.3 7.9 2.51
19.4 8.4 4.5 5.0 5.6 6.1 6.7 2.59
21.7 9.0 3.3 3.8 4.4 4.9 5.4 2.67
15.0 6.8 6.5 6.9* 7.1* 7.2* 7.4* 2.62
46.1 17.2 7.3 5.4 6.0 6.5 7.1 7.4 2.69
19.4 7.8 4.2 4.8 5.3 5.9 6.4 2.77
21.7 8.4 3.0 3.6 4.1 4.7 5.2 2.84
C
ORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW 0.472 0.472 AIRFLOW 0.472 0.472 TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT ARI RATING CONDITIONS GROSS CAPACITY = 9.02 KW AIRFLOW = 0.47 CMS AIRFLOW = 1000. CFM COMPRESSOR POWER = 2410 WATTS I.D. FAN POWER = 440 WATTS O.D. FAN POWER = 170 WATTS COP = 2.99 EER = 10.20 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
11TWE5-PRC000-EN
Page 12
Performance Data Cooling English Units
TTB530CA00A WITH TWE040CA40C
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 29.1 27.5 29.3* 30.1* 30.8* 31.5* 2.18
85 63 31.2 22.9 25.2 27.5 29.9 31.5* 2.26
67 33.4 17.8 20.2 22.5 24.8 27.1 2.34 71 35.7 12.7 15.0 17.4 19.7 22.0 2.42 59 28.7 27.3 29.0* 29.7* 30.4* 31.1* 2.29
90 63 30.8 22.7 25.0 27.3 29.7 31.1* 2.37
67 32.9 17.6 20.0 22.3 24.6 26.9 2.45 71 35.1 12.5 14.8 17.2 19.5 21.8 2.54 59 28.3 27.1 28.6* 29.4* 30.1* 30.7* 2.40
95 63 30.3 22.5 24.8 27.1 29.5 30.7* 2.48
67 32.4 17.4 19.8 22.1 24.4 26.7 2.56 71 34.6 12.3 14.6 16.9 19.3 21.6 2.65 59 27.4 26.7 27.9* 28.6* 29.2* 29.9* 2.49
100 63 29.3 22.1 24.4 26.7 29.0 29.9* 2.57
67 31.3 17.0 19.3 21.7 24.0 26.3 2.65 71 33.4 11.9 14.2 16.5 18.8 21.2 2.74 59 26.5 26.3 27.1* 27.8* 28.4* 29.0* 2.58
105 63 28.3 21.7 24.0 26.3 28.4* 29.0* 2.66
67 30.2 16.6 18.9 21.2 23.6 25.9 2.74 71 32.2 11.4 13.8 16.1 18.4 20.7 2.83 59 24.6 24.8* 25.5* 26.1* 26.7* 27.3* 2.76
115 63 26.3 20.8 23.1 25.5 26.7* 27.3* 2.84
67 28.1 15.7 18.1 20.4 22.7 25.0 2.92 71 29.9 10.6 12.9 15.2 17.6 19.9 3.01
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1200 1200 AIRFLOW 1200 1200
TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32400 BTUH AIRFLOW = 1200 CFM COMPRESSOR POWER = 2562 WATTS I.D. FAN POWER = 325 WATTS O.D. FAN POWER = 170 WATTS S.E.E.R. = 10.82 BTUH/WATT E.E.R. = 10.60 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
TTB536CA00A WITH TWE040CA40C
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 35.2 30.5 32.8 35.2 36.0* 36.9* 2.61
85 63 37.8 25.9 28.3 30.6 32.9 35.3 2.72
67 40.5 20.9 23.2 25.5 27.9 30.2 2.83 71 43.3 15.7 18.0 20.4 22.7 25.0 2.94 59 34.6 30.2 32.5 34.7* 35.5* 36.4* 2.75
90 63 37.1 25.6 27.9 30.3 32.6 35.0 2.85
67 39.8 20.5 22.9 25.2 27.6 29.9 2.96 71 42.5 15.4 17.7 20.0 22.4 24.7 3.08 59 33.9 29.9 32.2 34.1* 35.0* 35.8* 2.88
95 63 36.4 25.3 27.6 30.0 32.3 34.6 2.99
67 39.0 20.2 22.6 24.9 27.2 29.6 3.10 71 41.7 15.0 17.4 19.7 22.1 24.4 3.21 59 32.7 29.3 31.7 33.2* 34.0* 34.8* 2.98
100 63 35.1 24.7 27.1 29.4 31.7 34.1 3.09
67 37.6 19.7 22.0 24.3 26.7 29.0 3.20 71 40.2 14.5 16.8 19.2 21.5 23.8 3.31 59 31.5 28.8 31.1 32.2* 33.0* 33.7* 3.08
105 63 33.8 24.2 26.5 28.8 31.2 33.5 3.18
67 36.2 19.1 21.4 23.8 26.1 28.4 3.29 71 38.7 13.9 16.2 18.6 20.9 23.3 3.40 59 29.1 27.6 29.4* 30.2* 30.9* 31.6* 3.29
115 63 31.2 23.0 25.4 27.7 30.0 31.6* 3.38
67 33.4 18.0 20.3 22.6 25.0 27.3 3.48 71 35.7 12.8 15.1 17.5 19.8 22.1 3.59
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1200 1200 AIRFLOW 1200 1200
TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 39000 BTUH AIRFLOW = 1200 CFM COMPRESSOR POWER = 3099 WATTS I.D. FAN POWER = 325 WATTS O.D. FAN POWER = 170 WATTS S.E.E.R. = 10.95 BTUH/WATT E.E.R. = 10.85 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
12 TWE5-PRC000-EN
Page 13
Performance Data Cooling
TTB530CA00A WITH TWE040CA40C
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.5 8.1 8.6* 8.8* 9.0* 9.2* 2.18
29.4 17.2 9.1 6.7 7.4 8.1 8.8 9.2* 2.26
19.4 9.8 5.2 5.9 6.6 7.3 7.9 2.34
21.7 10.5 3.7 4.4 5.1 5.8 6.4 2.42
15.0 8.4 8.0 8.5* 8.7* 8.9* 9.1* 2.29
32.2 17.2 9.0 6.7 7.3 8.0 8.7 9.1* 2.37
19.4 9.6 5.2 5.9 6.5 7.2 7.9 2.45
21.7 10.3 3.7 4.3 5.0 5.7 6.4 2.54
15.0 8.3 7.9 8.4* 8.6* 8.8* 9.0* 2.40
35.0 17.2 8.9 6.6 7.3 7.9 8.6 9.0* 2.48
19.4 9.5 5.1 5.8 6.5 7.1 7.8 2.56
21.7 10.1 3.6 4.3 5.0 5.7 6.3 2.65
15.0 8.0 7.8 8.2* 8.4* 8.6* 8.8* 2.49
37.8 17.2 8.6 6.5 7.1 7.8 8.5 8.8* 2.57
19.4 9.2 5.0 5.7 6.4 7.0 7.7 2.65
21.7 9.8 3.5 4.2 4.8 5.5 6.2 2.74
15.0 7.8 7.7 7.9* 8.1* 8.3* 8.5* 2.58
40.6 17.2 8.3 6.4 7.0 7.7 8.3* 8.5* 2.66
19.4 8.8 4.9 5.5 6.2 6.9 7.6 2.74
21.7 9.4 3.3 4.0 4.7 5.4 6.1 2.83
15.0 7.2 7.3* 7.5* 7.6* 7.8* 8.0* 2.76
46.1 17.2 7.7 6.1 6.8 7.5 7.8 8.0 2.84
19.4 8.2 4.6 5.3 6.0 6.7 7.3 2.92
21.7 8.8 3.1 3.8 4.5 5.2 5.8 3.01
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 566 566 AIRFLOW 566 566
TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.48 KW AIRFLOW = 0.57 CMS COMPRESSOR POWER = 2562WATTS I.D. FAN POWER = 325 WATTS O.D. FAN POWER = 170 WATTS COP = 3.11 EER = 10.60 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
AT 2039 CMH
Metric Units
TTB536CA00A WITH TWE040CA40C
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 10.3 8.9 9.6 10.3 10.5* 10.8* 2.61
29.4 17.2 11.1 7.6 8.3 9.0 9.6 10.3 2.72
19.4 11.9 6.1 6.8 7.5 8.2 8.8 2.83
21.7 12.7 4.6 5.3 6.0 6.7 7.3 2.94
15.0 10.1 8.8 9.5 10.2* 10.4* 10.7* 2.75
32.2 17.2 10.9 7.5 8.2 8.9 9.6 10.3 2.85
19.4 11.7 6.0 6.7 7.4 8.1 8.8 2.96
21.7 12.5 4.5 5.2 5.9 6.6 7.2 3.08
15.0 9.9 8.8 9.4 10.0* 10.3* 10.5* 2.88
35.0 17.2 10.7 7.4 8.1 8.8 9.5 10.1 2.99
19.4 11.4 5.9 6.6 7.3 8.0 8.7 3.10
21.7 12.2 4.4 5.1 5.8 6.5 7.1 3.21
15.0 9.6 8.6 9.3 9.7* 10.0* 10.2* 2.98
37.8 17.2 10.3 7.2 7.9 8.6 9.3 10.0 3.09
19.4 11.0 5.8 6.4 7.1 7.8 8.5 3.20
21.7 11.8 4.2 4.9 5.6 6.3 7.0 3.31
15.0 9.2 8.4 9.1 9.4* 9.7* 9.9* 3.08
40.6 17.2 9.9 7.1 7.8 8.4 9.1 9.8 3.18
19.4 10.6 5.6 6.3 7.0 7.6 8.3 3.29
21.7 11.3 4.1 4.7 5.4 6.1 6.8 3.40
15.0 8.5 8.1 8.6* 8.8* 9.1* 9.3* 3.29
46.1 17.2 9.1 6.7 7.4 8.1 8.8 9.3* 3.38
19.4 9.8 5.3 5.9 6.6 7.3 8.0 3.48
21.7 10.5 3.8 4.4 5.1 5.8 6.5 3.59
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 566 566 AIRFLOW 566 566
TOTAL CAP. X1.00 X1.00 SENS. CAP. X1.00 X1.00 COMPR. KW X1.00 X1.00
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 11.41 KW AIRFLOW = 0.57 CMS COMPRESSOR POWER = 3099 WATTS I.D. FAN POWER = 325 WATTS O.D. FAN POWER = 170 WATTS COP = 3.18 EER = 10.85 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
AT 2039 CMH
13TWE5-PRC000-EN
Page 14
Performance Data Cooling English Units
TTA030CD WITH TWE030CA4
AT 1000 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 27.3 21.8 23.5 25.2 26.9 27.9* 2.27
85 63 29.5 18.5 20.2 21.9 23.6 25.3 2.35
67 31.7 14.9 16.6 18.3 20.0 21.7 2.43 71 34.1 11.2 12.9 14.6 16.3 18.0 2.51 59 26.8 21.6 23.3 25.0 26.7 27.5* 2.38
90 63 28.9 18.3 20.0 21.7 23.4 25.1 2.46
67 31.1 14.7 16.4 18.1 19.8 21.5 2.54 71 33.4 10.9 12.6 14.3 16.0 17.7 2.63 59 26.3 21.4 23.1 24.8 26.4* 27.1* 2.49
95 63 28.3 18.1 19.8 21.5 23.2 24.9 2.57
67 30.5 14.4 16.1 17.8 19.5 21.2 2.65 71 32.7 10.7 12.4 14.1 15.8 17.5 2.74 59 25.6 21.1 22.8 24.5 25.9* 26.5* 2.61
100 63 27.6 17.8 19.5 21.2 22.9 24.6 2.69
67 29.7 14.1 15.8 17.5 19.2 20.9 2.77 71 31.8 10.4 12.1 13.8 15.5 17.2 2.85 59 24.9 20.8 22.5 24.2 25.3* 26.0* 2.73
105 63 26.9 17.5 19.2 20.9 22.6 24.3 2.80
67 28.9 13.8 15.5 17.2 18.9 20.6 2.88 71 31.0 10.1 11.8 13.5 15.2 16.9 2.96 59 23.6 20.2 21.9 23.7* 24.2* 24.8* 2.97
115 63 25.4 16.9 18.6 20.3 22.0 23.7 3.04
67 27.3 13.2 14.9 16.6 18.3 20.0 3.11 71 29.2 9.5 11.2 12.9 14.6 16.3 3.19
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 975 1275 AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32500 BTUH AIRFLOW = 1125 CFM COMPRESSOR POWER = 2733 WATTS I.D. FAN POWER = 290 WATTS O.D. FAN POWER = 227 WATTS E.E.R. = 9.60 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
TTA030CD WITH TWE040CA4-B
AT 1125 CFM
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 72 74 76 78 80 KW
59 29.4 24.8 26.8 28.9 30.0* 30.7* 2.34
85 63 31.7 20.9 22.9 24.9 27.0 29.0 2.42
67 34.0 16.5 18.5 20.6 22.6 24.6 2.50 71 36.5 12.1 14.1 16.1 18.1 20.2 2.59 59 28.8 24.6 26.6 28.6 29.5* 30.2* 2.45
90 63 31.0 20.6 22.6 24.6 26.7 28.7 2.53
67 33.3 16.2 18.2 20.3 22.3 24.3 2.62 71 35.6 11.8 13.8 15.8 17.8 19.9 2.71 59 28.2 24.3 26.3 28.3* 29.0* 29.7* 2.57
95 63 30.3 20.3 22.3 24.4 26.4 28.4 2.65
67 32.5 15.9 18.0 20.0 22.0 24.0 2.73 71 34.8 11.5 13.5 15.5 17.6 19.6 2.82 59 27.4 23.9 26.0 27.7* 28.3* 29.0* 2.69
100 63 29.4 20.0 22.0 24.0 26.0 28.1 2.77
67 31.5 15.6 17.6 19.6 21.7 23.7 2.85 71 33.8 11.1 13.1 15.2 17.2 19.2 2.94 59 26.6 23.6 25.6 27.0* 27.6* 28.3* 2.81
105 63 28.5 19.6 21.6 23.7 25.7 27.7 2.89
67 30.6 15.2 17.3 19.3 21.3 23.3 2.97 71 32.7 10.8 12.8 14.8 16.8 18.9 3.05 59 25.0 22.9 25.0 25.7* 26.3* 26.9* 3.06
115 63 26.8 18.9 21.0 23.0 25.0 26.9* 3.13
67 28.7 14.5 16.6 18.6 20.6 22.6 3.20 71 30.6 10.0 12.1 14.1 16.1 18.2 3.28
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 975 1275 AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32500 BTUH AIRFLOW = 1125 CFM COMPRESSOR POWER = 2733 WATTS I.D. FAN POWER = 290 WATTS O.D. FAN POWER = 227 WATTS E.E.R. = 9.60 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
14 TWE5-PRC000-EN
Page 15
Performance Data Cooling Metric Units
TTA030CD00A WITH TWE030CA40B
AT 1700 CMH
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.0 6.4 6.9 7.4 7.9 8.2* 2.27
29.4 17.2 8.6 5.4 5.9 6.4 6.9 7.4 2.35
19.4 9.3 4.4 4.9 5.4 5.9 6.4 2.43
21.7 10.0 3.3 3.8 4.3 4.8 5.3 2.51
15.0 7.9 6.3 6.8 7.3 7.8 8.1* 2.38
32.2 17.2 8.5 5.4 5.9 6.4 6.9 7.4 2.46
19.4 9.1 4.3 4.8 5.3 5.8 6.3 2.54
21.7 9.8 3.2 3.7 4.2 4.7 5.2 2.63
15.0 7.7 6.3 6.8 7.3 7.7* 7.9* 2.49
35.0 17.2 8.3 5.3 5.8 6.3 6.8 7.3 2.57
19.4 8.9 4.2 4.7 5.2 5.7 6.2 2.65
21.7 9.6 3.1 3.6 4.1 4.6 5.1 2.74
15.0 7.5 6.2 6.7 7.2 7.6* 7.8* 2.61
37.8 17.2 8.1 5.2 5.7 6.2 6.7 7.2 2.69
19.4 8.7 4.1 4.6 5.1 5.6 6.1 2.77
21.7 9.3 3.0 3.5 4.0 4.5 5.0 2.85
15.0 7.3 6.1 6.6 7.1 7.4* 7.6* 2.73
40.6 17.2 7.9 5.1 5.6 6.1 6.6 7.1 2.80
19.4 8.5 4.0 4.5 5.0 5.5 6.0 2.88
21.7 9.1 3.0 3.5 4.0 4.5 5.0 2.96
15.0 6.9 5.9 6.4 6.9* 7.1* 7.3* 2.97
46.1 17.2 7.4 5.0 5.4 5.9 6.4 6.9 3.04
19.4 8.0 3.9 4.4 4.9 5.4 5.9 3.11
21.7 8.6 2.8 3.3 3.8 4.3 4.8 3.19
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 975 1275 AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 8.94 KW AIRFLOW = 0.57 CMS COMPRESSOR POWER = 2653 WATTS I.D. FAN POWER = 430 WATTS O.D. FAN POWER = 227 WATTS EER = 8.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCTION AND 7/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
TTA030CD00A WITH TWE040CA40C
AT 1911 CMH
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 8.6 7.3 7.9 8.5 8.8* 9.0* 2.34
29.4 17.2 9.3 6.1 6.7 7.3 7.9 8.5 2.42
19.4 10.0 4.8 5.4 6.0 6.6 7.2 2.50
21.7 10.7 3.5 4.1 4.7 5.3 5.9 2.59
15.0 8.4 7.2 7.8 8.4 8.6* 8.8* 2.45
32.2 17.2 9.1 6.0 6.6 7.2 7.8 8.4 2.53
19.4 9.8 4.7 5.3 5.9 6.5 7.1 2.62
21.7 10.4 3.5 4.0 4.6 5.2 5.8 2.71
15.0 8.3 7.1 7.7 8.3* 8.5* 8.7* 2.57
35.0 17.2 8.9 5.9 6.5 7.1 7.7 8.3 2.65
19.4 9.5 4.7 5.3 5.9 6.4 7.0 2.73
21.7 10.2 3.4 4.0 4.5 5.2 5.7 2.82
15.0 8.0 7.0 7.6 8.1* 8.3* 8.5* 2.69
37.8 17.2 8.6 5.9 6.4 7.0 7.6 8.2 2.77
19.4 9.2 4.6 5.2 5.7 6.4 6.9 2.85
21.7 9.9 3.3 3.8 4.5 5.0 5.6 2.94
15.0 7.8 6.9 7.5 7.9* 8.1* 8.3* 2.81
40.6 17.2 8.4 5.7 6.3 6.9 7.5 8.1 2.89
19.4 9.0 4.5 5.1 5.7 6.2 6.8 2.97
21.7 9.6 3.2 3.8 4.3 4.9 5.5 3.05
15.0 7.3 6.7 7.3 7.5* 7.7* 7.9* 3.06
46.1 17.2 7.9 5.5 6.2 6.7 7.3 7.9* 3.13
19.4 8.4 4.2 4.9 5.4 6.0 6.6 3.20
21.7 9.0 2.9 3.5 4.1 4.7 5.3 3.28
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 975 1275 AIRFLOW 975 1275
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 9.5 KW AIRFLOW = 1913 CMH COMPRESSOR POWER = 2653 WATTS I.D. FAN POWER = 430 WATTS O.D. FAN POWER = 227 WATTS EER = 8.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCTION AND 7/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
15TWE5-PRC000-EN
Page 16
Performance Data Cooling
TTA040CD WITH TWE040CA4B
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. GROSS SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 36.9 29.5 31.8 34.1 36.4 37.7* 3.24
85 63 39.7 25.0 27.3 29.6 31.9 34.2 3.37
67 42.6 20.0 22.3 24.6 26.9 29.3 3.51 71 45.6 14.9 17.2 19.6 21.9 24.2 3.64 59 36.2 29.2 31.5 33.8 36.1 37.1* 3.39
90 63 38.9 24.7 27.0 29.3 31.6 33.9 3.53
67 41.7 19.7 22.0 24.3 26.6 28.9 3.66 71 44.6 14.6 16.9 19.2 21.5 23.8 3.81 59 35.4 28.9 31.2 33.5 35.6* 36.5* 3.54
95 63 38.0 24.3 26.6 29.0 31.3 33.6 3.68
67 40.8 19.3 21.7 24.0 26.3 28.6 3.82 71 43.6 14.2 16.6 18.9 21.2 23.5 3.97 59 34.5 28.5 30.8 33.1 34.9* 35.7* 3.70
100 63 37.0 23.9 26.2 28.5 30.9 33.2 3.84
67 39.7 18.9 21.2 23.5 25.9 28.2 3.99 71 42.4 13.8 16.1 18.4 20.7 23.1 4.14 59 33.5 28.1 30.4 32.7 34.1* 34.9* 3.85
105 63 36.0 23.5 25.8 28.1 30.4 32.8 4.00
67 38.6 18.5 20.8 23.1 25.4 27.7 4.15 71 41.2 13.4 15.7 18.0 20.3 22.6 4.31 59 31.6 27.3 29.6 31.8* 32.5* 33.3* 4.17
115 63 33.9 22.7 25.0 27.3 29.6 31.9 4.32
67 36.3 17.7 20.0 22.3 24.6 26.9 4.48 71 38.8 12.6 14.9 17.2 19.5 21.8 4.65
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1150 1500 AIRFLOW 1150 1500
TOTAL CAP. X0.98 X1.02 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 40800 BTUH AIRFLOW = 1325 CFM COMPRESSOR POWER = 3820 WATTS I.D. FAN POWER = 380 WATTS O.D. FAN POWER = 197 WATTS E.E.R. = 9.00 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 1325 CFM
English Units
TTA040CD WITH TWE050CA5C
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. GROSS SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1375 1775 AIRFLOW 1375 1775
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.93 X1.05 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 43900 BTUH AIRFLOW = 1570 CFM COMPRESSOR POWER = 3720 WATTS I.D. FAN POWER = 530 WATTS O.D. FAN POWER = 197 WATTS E.E.R. = 9.45 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
59 40.5 34.2 37.0 39.9 41.3* 42.2* 3.16
85 63 43.4 28.6 31.5 34.3 37.1 39.9 3.29
67 46.4 22.5 25.3 28.1 31.0 33.8 3.43 71 49.5 16.2 19.1 21.9 24.7 27.5 3.57 59 39.4 33.8 36.6 39.4 40.4* 41.3* 3.29
90 63 42.2 28.2 31.0 33.8 36.7 39.5 3.42
67 45.1 22.0 24.9 27.7 30.5 33.3 3.57 71 48.2 15.8 18.6 21.4 24.2 27.1 3.71 59 38.4 33.3 36.2 38.7* 39.6* 40.4* 3.42
95 63 41.1 27.7 30.6 33.4 36.2 39.0 3.56
67 43.9 21.6 24.4 27.2 30.0 32.9 3.70 71 46.8 15.3 18.1 21.0 23.8 26.6 3.85 59 37.3 32.9 35.7 37.7* 38.6* 39.5* 3.55
100 63 39.9 27.3 30.1 32.9 35.7 38.5 3.69
67 42.6 21.1 23.9 26.7 29.6 32.4 3.84 71 45.4 14.8 17.7 20.5 23.3 26.1 4.00 59 36.1 32.4 35.2 36.8* 37.7* 38.5* 3.69
105 63 38.7 26.8 29.6 32.4 35.2 38.1 3.83
67 41.3 20.6 23.5 26.3 29.1 31.9 3.98 71 44.0 14.4 17.2 20.0 22.8 25.6 4.14 59 33.9 31.5 34.1* 34.9* 35.7* 36.5* 3.96
115 63 36.2 25.8 28.7 31.5 34.3 36.5* 4.11
67 38.7 19.7 22.5 25.3 28.1 31.0 4.26 71 41.2 13.4 16.2 19.1 21.9 24.7 4.42
AT 1600 CFM
16 TWE5-PRC000-EN
Page 17
Performance Data Cooling
TTA040CD00A WITH TWE040CA40C
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 10.8 8.6 9.3 10.0 10.7 11.0* 3.24
29.4 17.2 11.6 7.3 8.0 8.7 9.3 10.0 3.37
19.4 12.5 5.9 6.5 7.2 7.9 8.6 3.51
21.7 13.4 4.4 5.0 5.7 6.4 7.1 3.64
15.0 10.6 8.6 9.2 9.9 10.6 10.9* 3.39
32.2 17.2 11.4 7.2 7.9 8.6 9.3 9.9 3.53
19.4 12.2 5.8 6.4 7.1 7.8 8.5 3.66
21.7 13.1 4.3 5.0 5.6 6.3 7.0 3.81
15.0 10.4 8.5 9.1 9.8 10.4* 10.7* 3.54
35.0 17.2 11.1 7.1 7.8 8.5 9.2 9.8 3.68
19.4 12.0 5.7 6.4 7.0 7.7 8.4 3.82
21.7 12.8 4.2 4.9 5.5 6.2 6.9 3.97
15.0 10.1 8.4 9.0 9.7 10.2* 10.5* 3.70
37.8 17.2 10.8 7.0 7.7 8.4 9.1 9.7 3.84
19.4 11.6 5.5 6.2 6.9 7.6 8.3 3.99
21.7 12.4 4.0 4.7 5.4 6.1 6.8 4.14
15.0 9.8 8.2 8.9 9.6* 10.0* 10.2* 3.85
40.6 17.2 10.5 6.9 7.6 8.2 8.9 9.6 4.00
19.4 11.3 5.4 6.1 6.8 7.4 8.1 4.15
21.7 12.1 3.9 4.6 5.3 5.9 6.6 4.31
15.0 9.3 8.0 8.7 9.3* 9.5* 9.8* 4.17
46.1 17.2 9.9 6.7 7.3 8.0 8.7 9.3 4.32
19.4 10.6 5.2 5.9 6.5 7.2 7.9 4.48
21.7 11.4 3.7 4.4 5.0 5.7 6.4 4.65
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1150 1500 AIRFLOW 1150 1500
TOTAL CAP. X0.98 X1.02 SENS. CAP. X0.94 X1.06 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 12.0 KW AIRFLOW = 2253 CMS COMPRESSOR POWER = 3820 WATTS I.D. FAN POWER = 380 WATTS O.D. FAN POWER = 197 WATTS EER = 9.00 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 2250 CMH
Metric Units
TTA040CD00A WITH TWE050CA50D
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 11.9 10.0 10.8 11.7 12.1* 12.4* 3.16
29.4 17.2 12.7 8.4 9.2 10.0 10.9 11.7 3.29
19.4 13.6 6.6 7.4 8.2 9.1 9.9 3.43
21.7 14.5 4.7 5.6 6.4 7.2 8.1 3.57
15.0 11.5 9.9 10.7 11.5 11.8* 12.1* 3.29
32.2 17.2 12.4 8.3 9.1 9.9 10.8 11.6 3.42
19.4 13.2 6.4 7.3 8.1 8.9 9.8 3.57
21.7 14.1 4.6 5.4 6.3 7.1 7.9 3.71
15.0 11.3 9.8 10.6 11.3* 11.6* 11.8* 3.42
35.0 17.2 12.0 8.1 9.0 9.8 10.6 11.4 3.56
19.4 12.9 6.3 7.1 8.0 8.8 9.6 3.70
21.7 13.7 4.5 5.3 6.2 7.0 7.8 3.85
15.0 10.9 9.6 10.5 11.0* 11.3* 11.6* 3.55
37.8 17.2 11.7 8.0 8.8 9.6 10.5 11.3 3.69
19.4 12.5 6.2 7.0 7.8 8.7 9.5 3.84
21.7 13.3 4.3 5.2 6.0 6.8 7.6 4.00
15.0 10.6 9.5 10.3 10.8* 11.0* 11.3* 3.69
40.6 17.2 11.3 7.9 8.7 9.5 10.3 11.2 3.83
19.4 12.1 6.0 6.9 7.7 8.5 9.3 3.98
21.7 12.9 4.2 5.0 5.9 6.7 7.5 4.14
15.0 9.9 9.2 10.0* 10.2* 10.5* 10.7* 3.96
46.1 17.2 10.6 7.6 8.4 9.2 10.0 10.7 4.11
19.4 11.3 5.8 6.6 7.4 8.2 9.1 4.26
21.7 12.1 3.9 4.7 5.6 6.4 7.2 4.42
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1375 1775 AIRFLOW 1375 1775
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.93 X1.05 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 12.0 KW AIRFLOW = 2253 CMS COMPRESSOR POWER = 3720 WATTS I.D. FAN POWER = 380 WATTS O.D. FAN POWER = 197 WATTS EER = 9.00 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 2717 CMH
17TWE5-PRC000-EN
Page 18
Performance Data Cooling
TTA050CD WITH TWE050CA5C
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. GROSS SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 48.8 39.4 42.5 45.6 48.7 49.9* 3.62
85 63 52.1 33.2 36.3 39.4 42.5 45.6 3.75
67 55.5 26.3 29.4 32.5 35.6 38.7 3.89 71 59.0 19.3 22.4 25.5 28.6 31.7 4.03 59 47.6 38.9 42.0 45.1 47.9* 48.9* 3.77
90 63 50.8 32.7 35.8 38.9 42.0 45.1 3.91
67 54.1 25.8 28.9 32.0 35.1 38.2 4.05 71 57.5 18.8 21.9 25.0 28.1 31.2 4.19 59 46.4 38.4 41.5 44.6 47.0* 47.9* 3.93
95 63 49.5 32.1 35.3 38.4 41.5 44.6 4.07
67 52.7 25.3 28.4 31.5 34.6 37.7 4.21 71 56.0 18.3 21.4 24.5 27.6 30.7 4.35 59 45.1 37.8 40.9 44.0 45.9* 46.8* 4.09
100 63 48.1 31.6 34.7 37.8 40.9 44.0 4.23
67 51.2 24.7 27.8 30.9 34.0 37.1 4.37 71 54.4 17.7 20.8 23.9 27.0 30.1 4.51 59 43.8 37.3 40.4 43.5 44.8* 45.7* 4.25
105 63 46.7 31.0 34.1 37.2 40.3 43.4 4.38
67 49.6 24.2 27.3 30.4 33.5 36.6 4.52 71 52.7 17.2 20.3 23.4 26.5 29.6 4.67 59 41.2 36.2 39.3 41.6* 42.5* 43.4* 4.57
115 63 43.8 29.9 33.0 36.1 39.2 42.3 4.71
67 46.6 23.0 26.1 29.2 32.3 35.4 4.84 71 49.4 16.1 19.2 22.3 25.4 28.5 4.98
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1525 1975 AIRFLOW 1525 1975
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.93 X1.04 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 52500 BTUH AIRFLOW = 1750 CFM COMPRESSOR POWER = 4202 WATTS I.D. FAN POWER = 730 WATTS O.D. FAN POWER = 202 WATTS E.E.R. = 9.75 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 1800 CFM
English Units
TTA060CD WITH TWE050CA5C
GROSS CAPACITY IN BTU/H x 1000
O.D. I.D. GROSS SENS. CAP. AT ENTERING D.B. TEMP. COMPR. D.B. W.B. CAP. 72 74 76 78 80 KW
59 57.5 43.6 46.8 49.9 53.0 56.2 4.71
85 63 61.6 37.4 40.6 43.7 46.8 50.0 4.87
67 65.8 30.6 33.7 36.8 40.0 43.1 5.04 71 70.2 23.5 26.7 29.8 32.9 36.1 5.22 59 56.2 43.0 46.2 49.3 52.5 55.6 4.90
90 63 60.2 36.9 40.0 43.1 46.3 49.4 5.06
67 64.3 30.0 33.1 36.2 39.4 42.5 5.23 71 68.6 22.9 26.1 29.2 32.3 35.5 5.40 59 54.9 42.5 45.6 48.7 51.9 55.0* 5.09
95 63 58.8 36.3 39.4 42.5 45.7 48.8 5.25
67 62.8 29.4 32.5 35.7 38.8 41.9 5.42 71 66.9 22.3 25.5 28.6 31.7 34.9 5.59 59 53.5 41.9 45.0 48.1 51.3 54.0* 5.31
100 63 57.3 35.7 38.8 41.9 45.1 48.2 5.47
67 61.2 28.8 31.9 35.0 38.2 41.3 5.63 71 65.2 21.7 24.9 28.0 31.1 34.3 5.79 59 52.2 41.3 44.4 47.5 50.7 52.9* 5.53
105 63 55.8 35.0 38.2 41.3 44.5 47.6 5.68
67 59.6 28.2 31.3 34.4 37.6 40.7 5.84 71 63.5 21.1 24.2 27.4 30.5 33.7 6.00 59 49.4 40.1 43.2 46.3 49.4* 50.6* 5.98
115 63 52.8 33.8 37.0 40.1 43.2 46.4 6.12
67 56.4 26.9 30.1 33.2 36.3 39.5 6.26 71 60.0 19.9 23.0 26.2 29.3 32.4 6.41
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1525 1975 AIRFLOW 1525 1975
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.04 COMPR. KW X0.98 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 62500 BTUH AIRFLOW = 1750 CFM COMPRESSOR POWER = 5402 WATTS I.D. FAN POWER = 730 WATTS O.D. FAN POWER = 386 WATTS E.E.R. = 9.15 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 1800 CFM
18 TWE5-PRC000-EN
Page 19
Performance Data Cooling
TTA050CD WITH TWE050CA5C
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 14.3 11.5 12.5 13.4 14.3 14.6* 3.62
29.4 17.2 15.3 9.7 10.6 11.5 12.5 13.4 3.75
19.4 16.3 7.7 8.6 9.5 10.4 11.3 3.89
21.7 17.3 5.7 6.6 7.5 8.4 9.3 4.03
15.0 13.9 11.4 12.3 13.2 14.0* 14.3* 3.77
32.2 17.2 14.9 9.6 10.5 11.4 12.3 13.2 3.91
19.4 15.9 7.6 8.5 9.4 10.3 11.2 4.05
21.7 16.8 5.5 6.4 7.3 8.2 9.1 4.19
15.0 13.6 11.3 12.2 13.1 13.8* 14.0* 3.93
35.0 17.2 14.5 9.4 10.3 11.3 12.2 13.1 4.07
19.4 15.4 7.4 8.3 9.2 10.1 11.0 4.21
21.7 16.4 5.4 6.3 7.2 8.1 9.0 4.35
15.0 13.2 11.1 12.0 12.9 13.4* 13.7* 4.09
37.8 17.2 14.1 9.3 10.2 11.1 12.0 12.9 4.23
19.4 15.0 7.2 8.1 9.1 10.0 10.9 4.37
21.7 15.9 5.2 6.1 7.0 7.9 8.8 4.51
15.0 12.8 10.9 11.8 12.7 13.1* 13.4* 4.25
40.6 17.2 13.7 9.1 10.0 10.9 11.8 12.7 4.38
19.4 14.5 7.1 8.0 8.9 9.8 10.7 4.52
21.7 15.4 5.0 5.9 6.9 7.8 8.7 4.67
15.0 12.1 10.6 11.5 12.2* 12.5* 12.7* 4.57
46.1 17.2 12.8 8.8 9.7 10.6 11.5 12.4 4.71
19.4 13.7 6.7 7.6 8.6 9.5 10.4 4.84
21.7 14.5 4.7 5.6 6.5 7.4 8.4 4.98
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1525 1975 AIRFLOW 1525 1975
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.93 X1.04 COMPR. KW X0.99 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 14.6 KW AIRFLOW = 3056 CMH COMPRESSOR POWER = 4202 WATTS I.D. FAN POWER = 730 WATTS O.D. FAN POWER = 202 WATTS EER = 9.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 3056 CMH
Metric Units
TTA060CD WITH TWE050CA5C
GROSS CAPACITY IN KILOWATTS
O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. COMPR.
D.B. W.B. CAP. 22.2 23.3 24.4 25.6 26.7 KW
15.0 16.8 12.8 13.7 14.6 15.5 16.5 4.71
29.4 17.2 18.0 11.0 11.9 12.8 13.7 14.7 4.87
19.4 19.3 9.0 9.9 10.8 11.7 12.6 5.04
21.7 20.6 6.9 7.8 8.7 9.6 10.6 5.22
15.0 16.5 12.6 13.5 14.4 15.4 16.3 4.90
32.2 17.2 17.6 10.8 11.7 12.6 13.6 14.5 5.06
19.4 18.8 8.8 9.7 10.6 11.5 12.5 5.23
21.7 20.1 6.7 7.6 8.6 9.5 10.4 5.40
15.0 16.1 12.5 13.4 14.3 15.2 16.1* 5.09
35.0 17.2 17.2 10.6 11.5 12.5 13.4 14.3 5.25
19.4 18.4 8.6 9.5 10.5 11.4 12.3 5.42
21.7 19.6 6.5 7.5 8.4 9.3 10.2 5.59
15.0 15.7 12.3 13.2 14.1 15.0 15.8* 5.31
37.8 17.2 16.8 10.5 11.4 12.3 13.2 14.1 5.47
19.4 17.9 8.4 9.3 10.3 11.2 12.1 5.63
21.7 19.1 6.4 7.3 8.2 9.1 10.0 5.79
15.0 15.3 12.1 13.0 13.9 14.9 15.5* 5.53
40.6 17.2 16.3 10.3 11.2 12.1 13.0 13.9 5.68
19.4 17.5 8.3 9.2 10.1 11.0 11.9 5.84
21.7 18.6 6.2 7.1 8.0 8.9 9.9 6.00
15.0 14.5 11.7 12.7 13.6 14.5* 14.8* 5.98
46.1 17.2 15.5 9.9 10.8 11.7 12.7 13.6 6.12
19.4 16.5 7.9 8.8 9.7 10.6 11.6 6.26
21.7 17.6 5.8 6.7 7.7 8.6 9.5 6.41
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED) AIRFLOW 1525 1975 AIRFLOW 1525 1975
TOTAL CAP. X0.98 X1.01 SENS. CAP. X0.94 X1.04 COMPR. KW X0.98 X1.01
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 14.6 KW AIRFLOW = 3056 CMH COMPRESSOR POWER = 4202 WATTS I.D. FAN POWER = 730 WATTS O.D. FAN POWER = 202 WATTS EER = 9.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY) TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL ALL TEMPERATURES IN DEGREES F
AT 3056 CMH
19TWE5-PRC000-EN
Page 20
Performance Data
Evaporator Fan Performance
BLOWER PERFORMANCE — TWE030CA40B — WET COIL
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
600 1018.8 0.72 (179.4) 0.71 (176.9) 650 1103.7 0.62 (154.4) 0.61 (152.0) 700 1188.6 0.86 (214.2) 0.51 (127.0) 0.84 (209.2) 0.50 (124.6) 750 1273.5 0.75 (186.8) 0.40 (99.6) 0.72 (179.4) 0.39 (97.1) 800 1358.4 0.89 (221.7) 0.65 (161.9) 0.29 (72.2) 0.87 (216.7) 0.62 (154.4) 0.28 (69.7) 850 1443.3 0.81 (201.8) 0.54 (134.5) 0.18 (44.8) 0.79 (196.8) 0.51 (127.0) 0.17 (42.3) 900 1528.2 0.72 (179.4) 0.43 (107.1) 0.06 (14.9) 0.69 (171.9) 0.40 (99.6) 0.08 (19.9)
950 1613.1 0.63 (156.9) 0.32 (79.7) 0.61 (152.0) 0.30 (74.7) 1000 1698.0 0.53 (132.0) 0.21 (52.3) 0.51 (127.0) 0.17 (42.3) 1050 1782.9 0.42 (104.6) 0.10 (24.9) 0.40 (99.6) 0.02 (5.0) 1100 1867.8 0.31 (77.2) 0.31 (77.2) 1150 1952.7 0.20 (49.8) 0.22 (54.8) 1200 2037.6 0.08 (19.9) 0.10 (24.9)
NOTES: Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. for downflow. Horizontal: As shipped, but without filter. Subtract 0.05" W.G. for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOLTS 220 VOLTS
BLOWER PERFORMANCE — TWE040CA40C — WET COIL
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
700 1188.6 0.58 (144.5) 750 1273.5 0.61 (152.0) 0.55 (137.0) 800 1358.4 0.61 (152.0) 0.58 (144.5) 0.52 (129.5) 0.58 (144.5) 850 1443.3 0.57 (142.0) 0.54 (134.5) 0.48 (119.6) 0.52 (129.5) 900 1528.2 0.53 (132.0) 0.51 (127.0) 0.44 (109.6) 0.49 (122.1)
950 1613.1 0.49 (122.1) 0.47 (117.1) 0.40 (99.6) 0.57 (142.0) 0.45 (112.1) 1000 1698.0 0.45 (112.1) 0.43 (107.1) 0.34 (84.7) 0.53 (132.0) 0.50 (124.6) 0.40 (99.6) 1050 1782.9 0.40 (99.6) 0.38 (94.7) 0.28 (69.7) 0.48 (119.6) 0.45 (112.1) 0.35 (87.2) 1100 1867.8 0.36 (89.7) 0.34 (84.7) 0.22 (54.8) 0.43 (107.1) 0.40 (99.6) 0.30 (74.7) 1150 1952.7 0.31 (77.2) 0.29 (72.2) 0.15 (37.4) 0.39 (97.1) 0.37 (92.2) 0.22 (54.8) 1200 2037.6 0.26 (64.8) 0.24 (59.8) 0.08 (19.9) 0.35 (87.2) 0.32 (79.7) 0.17 (42.3) 1250 2122.5 0.21 (52.3) 0.18 (44.8) 0.00 (0.0) 0.31 (77.2) 0.28 (69.7) 0.10 (24.9) 1300 2207.4 0.17 (42.3) 0.13 (32.4) 0.26 (64.8) 0.22 (54.8) 0.01 (2.5) 1350 2292.3 0.11 (27.4) 0.07 (17.4) 0.21 (52.3) 0.18 (44.8) 1400 2377.2 0.06 (14.9) 0.01 (2.5) 0.15 (37.4) 0.12 (29.9) 1450 2462.1 0.01 (2.5) 0.11 (27.4) 0.08 (19.9) 1500 2547.0 0.00 0.05 (12.5) 0.02 (5.0)
NOTES: Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. for downflow. Horizontal: As shipped, but without filter. Subtract 0.05" W.G. for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOLTS 220 VOLTS
20 TWE5-PRC000-EN
Page 21
Performance Data
BLOWER PERFORMANCE — TWE050CA50D — WET COIL
UPFLOW & DOWNFLOW (See Notes) HORIZONTAL; NO FILTER (See Notes)
CFM CMH Hl MED LO Hl MED LO
900 1528.2
950 1613.1 0.63 (156.9) 1000 1698.0 0.61 (152.0) 0.62 (154.4) 1050 1782.9 0.58 (144.5) 0.60 (149.5) 1100 1867.8 0.54 (134.5) 0.57 (142.0) 1150 1952.7 0.50 (124.6) 0.53 (132.0) 1200 2037.6 0.45 (112.1) 0.49 (122.1) 1250 2122.5 0.61 (152.0) 0.39 (97.1) 0.64 (159.4) 0.44 (109.6) 1300 2207.4 0.59 (147.0) 0.57 (142.0) 0.33 (82.2) 0.62 (154.4) 0.61 (152.0) 0.38 (94.7) 1350 2292.3 0.56 (139.5) 0.53 (132.0) 0.26 (64.8) 0.59 (147.0) 0.58 (144.5) 0.32 (79.7) 1400 2377.2 0.52 (129.5) 0.49 (122.1) 0.18 (44.8) 0.56 (139.5) 0.55 (137.0) 0.25 (62.3) 1450 2462.1 0.48 (119.6) 0.45 (112.1) 0.10 (24.9) 0.52 (129.5) 0.52 (129.5) 0.18 (44.8) 1500 2547.0 0.44 (109.6) 0.40 (99.6) 0.01 (2.5) 0.49 (122.1) 0.48 (119.6) 0.11 (27.4) 1550 2631.9 0.40 (99.6) 0.35 (87.2) 0.47 (117.1) 0.44 (109.6) 0.00 (0.0) 1600 2716.8 0.35 (87.2) 0.30 (74.7) 0.45 (112.1) 0.40 (99.6) 1650 2801.7 0.31 (77.2) 0.25 (62.3) 0.41 (102.1) 0.35 (87.2) 1700 2886.6 0.26 (64.8) 0.20 (49.8) 0.36 (89.7) 0.28 (69.7) 1750 2971.5 0.21 (52.3) 0.14 (34.9) 0.30 (74.7) 0.20 (49.8) 1800 3056.4 0.16 (39.9) 0.08 (19.9) 0.24 (59.8) 0.13 (32.4) 1850 3141.3 0.11 (27.4) 0.02 (5.0) 0.17 (42.3) 0.07 (17.4) 1900 3226.2 0.05 (12.5) 0.10 (24.9) 0.01 (2.5) 1950 3311.1 0.02 (5.0)
NOTES: Vertical: With filter, no horizontal drip tray. Small apex baffle
Subtract 0.06" W.G. for downflow. Horizontal: As shipped, but without filter. Subtract 0.05" W.G for horizontal left.
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
220 VOLTS 220 VOLTS
21TWE5-PRC000-EN
Page 22
Performance Data
Air Pressure Drop (Inches) - Electric Heaters
PRESSURE DROP FOR ELECTRIC HEATERS
IN AIR HANDLER MODELS
NUMBER OF RACKS
12 34 5
AIRFLOW AIRFLOW AIR PRESSURE DROP
CFM CMH IN. W.G. (PASCALS)
600 1018.8 0.01 (2.5) 0.02 (5.0) 0.02 (5.0) 700 1188.6 0.01 (2.5) 0.02 (5.0) 0.02 (5.0) 800 1358.4 0.02 (5.0) 0.03 (7.5) 0.03 (7.5) 0.04 (10.0)
900 1528.2 0.03 (7.5) 0.03 (7.5) 0.04 (10.0) 0.05 (12.5) 1000 1698.0 0.04 (10.0) 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 1100 1867.8 0.04 (10.0) 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 1200 2037.6 0.05 (12.5) 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 1300 2207.4 0.06 (14.9) 0.07 (17.4) 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 1400 2377.2 0.07 (17.4) 0.08 (19.9) 0.10 (24.9) 0.11 (27.4) 0.13 (32.4) 1500 2547.0 0.08 (19.9) 0.09 (22.4) 0.11 (27.4) 0.13 (32.4) 0.15 (37.4) 1600 2716.8 0.09 (22.4) 0.10 (24.9) 0.12 (29.9) 0.15 (37.4) 0.17 (42.3) 1700 2886.6 0.10 (24.9) 0.11 (27.4) 0.14 (34.9) 0.17 (42.3) 0.19 (47.3) 1800 3056.4 0.11 (27.4) 0.13 (32.4) 0.16 (39.9) 0.19 (47.3) 0.21 (52.3) 1900 3226.2 0.13 (32.4) 0.15 (37.4) 0.18 (44.8) 0.21 (52.3) 0.23 (57.3) 2000 3396.0 0.14 (34.9) 0.17 (42.3) 0.20 (49.8) 0.23 (57.3) 0.26 (64.8)
NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.
HEATER RACKS
HEATER NO. OF
MODEL NO. RACKS BAY96X1405 1 BAY96X1406 2 BAY96X1408 2 BAY96X1410 2 BAY96X1411 3 BAY96X1415 3 BAY96X1419 4 BAY96X1421 4 BAY96X1426 5 BAY96X3411 3 BAY96X3415 3
22 TWE5-PRC000-EN
Page 23

Supplementary Heaters

THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.
TWE030C-HEATER MODEL NUMBER BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415 Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW Vertical A/C or Elec. Furnace LLLLLLLLLLLL Upflow Heat Pump LLLLLLLLMMLL Vertical A/C or Elec. Furnace LLLLLLLLLLLL Downflow Heat Pump LLLLLLLLHHLH Horizontal A/C or Elec. Furnace LLLLLLLLLLLL Left Heat Pump LLLLLLLLMMLL Horizontal A/C or Elec. Furnace LLLLLLLLLLLL Right Heat Pump LLLLLLLLHHLL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.
TWE040C-HEATER MODEL NUMBER BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1411 1411A 1415 1419 1421 3411 3415 Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 8.8 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW Vertical A/C or Elec. Furnace LLLLLLLLLLLL Upflow Heat Pump LLLLLMMHHHMM Vertical A/C or Elec. Furnace LLLLLLLLLLLL Downflow Heat Pump LLLLLLLHHHLL Horizontal A/C or Elec. Furnace LLLLLLLLLLLL Left Heat Pump LLLLLLLHHHLL Horizontal A/C or Elec. Furnace LLLLLLLLLLLL Right Heat Pump LLLLLLLHHHLL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.
TWE050C-HEATER MODEL NUMBER BAY96X
Unit 1405 1406 1408,F 1410,F 1410A 1415 1419 1421 1426 3415 Position Application 4.0 KW 4.8 KW 6.4 KW 8.0 KW 8.8 KW 12.8 KW 16.0 KW 17.6 KW 21.6 KW 12.8 KW Vertical A/C or Elec. Furnace LLLL L LLL Upflow Heat Pump L L LLLL MMHL Vertical A/C or Elec. Furnace LLLL L LLL Downflow Heat Pump L L LLLL H HHL Horizontal A/C or Elec. Furnace LLLL L LLL Left Heat Pump L L LLLL H HHL Horizontal A/C or Elec. Furnace LLLL L LLL Right Heat Pump L L LLLL MMHL
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A & 1414 not approved for this model.
23TWE5-PRC000-EN
Page 24

System Wiring Diagram

NOTES:
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC
SPEED CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.
3. A 220V HIGH VOLTAGE CONTROL IN TTB5-C NEEDS TO BE
CHANGED WITH 24V LOW VOLTAGE CONTROL KIT (ACYLVCR006A)
WHEN MATCHED WITH TWE-C AIR HANDLING UNITS.
24 TWE5-PRC000-EN
Page 25
TWE030-050C Outline Drawing
All dimensions are in inches (mm)

Dimensional Data

MINIMUM UNIT CLEARANCE SALE
TO COMBUSTIBLE SERVICE CLEARANCE
SIDES 0 (0) 2 (50.8)
FRONT 0 (0) 21 (533.4)
BACK 0 (0) 0 (0)
INLET DUCT 0 (0) 1 (25.4)
OUTLET DUCT 1 (25.4)
MATERIAL (REQUIRED) (RECOMMENDED)
MODEL NO. A B C D E F TWE030CA4 43.00 15.57 21.50 19.50 20.28 21.63 FCCV
TWE040CA4 51.75 24.32 23.50 21.50 22.28 23.63 FCCV
TWE050CA5 57.90 30.47 23.50 21.50 22.28 23.63 TXV
(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)
(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)
(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)
CONTROL
25TWE5-PRC000-EN
FLOW
Page 26
Dimensional Data
TTB524-536CA Outline Drawing
All dimensions are in inches (mm)
SERVICE PANEL ELECTRICAL AND REFRIGERANT COMPONENTS CLEARANCES PER PREVAILING CODES
PT. NO. SIZE A B C D E
CABINET
TTB524CA 25A 251/2 11/16
TTB530CA/ 25C 321/2 11/16 TTB536CA (826) 14 UNS-2A 20UNF-2A (19) (8)
TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST 1524 (5 FEET) ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT AND SHOULD BE AT LEAST 305 (12”) FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.
1 INCH = (25.40 MILLIMETERS)
1
(648) 14 UNS-2A 20UNF-2A (19 (8)
/2
1
/2
3
3
5
/4
/4
/16
5
/16
FLARE NUT TORQUE
TORQUE FT-LBS (NEWTON METERS)
APPLIED TUBE SIZE MINIMUM MAXIMUM
1
/4 (6.35) 8 (11.0) 10 (14.0)
5
/16 (7.94) 10 (14.0) 15 (20.0)
3
/8 (9.52) 15 (20.0) 25 (34.0)
1
/2 (12.70) 25 (34.0) 35 (47.0)
5
/8 (15.88) 40 (54.0) 55 (75.0)
3
/4 (19.05) 50 (68.0) 60 (81.0)
BACK-UP HEX SIZE
1 1/16-14 = 1 1/16
(27)
1
/2-20 = 1/2
(13)
“C” SAE MALE FLARE FOR “E” O.D. TUBE SIZE
CONNECTION WITH 1/4” SAE FLARE PRESSURE TAP FITTING.
“B” SAE MALE FLARE FOR “D” O.D. TUBE SIZE
CONNECTION WITH 1/4” SAE FLARE PRESSURE TAP FITTING.
26 TWE5-PRC000-EN
Page 27
TTA030-060C Outline Drawing
All dimensions are in inches (mm)
Dimensional Data
FIG. 2
FIG. 1
TOP DISCHARGE AREA SHOULD BE UNRESTRICTED FOR AT LEAST FIVE (5) FEET ABOVE UNIT. UNIT SHOULD BE PLACED SO ROOF RUN-OFF WATER DOES NOT POUR DIRECTLY ON UNIT, AND SHOULD BE AT LEAST 12” (305) FROM WALL AND ALL SURROUNDING SHRUBBERY ON TWO SIDES. OTHER TWO SIDES UNRESTRICTED.
MODEL Figure A B C D E TTA030C 1 24 3/8 28 1/4 24 5/87/8
TTA040C 1 32 3/4 28 1/4 24 5/8 1 1/83/8
TTA050C 2 40 5/8 32 7/8 28 3/4 1 1/83/8
TTA060C 2 44 3/4 38 7/8 34 3/4 1 1/83/8
(619.1) (714.4) (625.5) (22.2) (9.53)
(831.9) (714.4) (625.5) (28.6) (9.53)
(1031.9) (835.0) (730.3) (28.6) (9.53)
(1136.7) (987.4) (882.7) (28.6) (9.53)
3
/8
27TWE5-PRC000-EN
Page 28
Dimensional Data
TWE030 Through 050 Convertibility
Six (6) Way Convertibility
One Unit - 4 Applications
Easy Conversion to Opposite Side Access
28 TWE5-PRC000-EN
Page 29

Mechanical Specifications

General
Blower coil units shall be completely factory assembled including coil, condensate drain pan, fan, motor, filters and controls in an insulated casing that can be applied in horizontal or vertical configuration.
This new line of TWE-C air handlers provides exclusive compact size combined with simple four-way convertibility in three sizes. The unit ships in the right hand horizontal configuration and converts to vertical upflow just by standing the unit on end. No tools required. Simple coil rotation provides downflow and horizontal left applications.
The four-way convertibility provides you inventory benefits and service/ installation flexibility. The simple conversion provides opposite side access for installation and service.
Casing
Units shall have rugged sheet metal and steel frame construction and shall be painted with an enamel finish. Casing shall be insulated and knockouts shall be provided for electrical power and control wiring.
Refrigerant Circuits
The TWE units shall have a single refrigerant circuit. TWE03-040C refrigerant circuit shall be controlled by a flow control check valve (FCCV). The TWE050C refrigerant circuit shall be controlled by a factory-installed thermal expansion valve.
Coil
Aluminum fin surface shall be mechanically bonded to copper tubing. Coils shall be factory pressure and leak tested.
Fan
Forward curved, dynamically and statically balanced with three-speed direct drive shall be standard, fan motor bearing shall be permanently lubricated.
Controls
Fan contactor, and plug-in module for accessory electric heat control shall be included. TWE models shall also include check valves.
Filters
Filters shall be included as standard.
Accessories Electric Heaters — Shall be available in a
wide range of capacities and voltages with various staging options and plug in control wiring. Heaters shall fit inside internal compartment.
3
/8-inch OD
29TWE5-PRC000-EN
Page 30
The Trane Company
International Unitary Products Group
3600 Pammel Creek Road
La Crosse, WI 54601-7599
www.trane.com
An American Standard Company
File No. TWE5-PRC000-EN 4/99 Supersedes TWE5-PRC000-EN 2/98 Stocking Location La Crosse
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change design and specification without notice.
Loading...