Trane Gas Heat Sections Installation and Maintenance Manual

Page 1
Installation, Operation and Maintenance
Gas Heat Sections
for Performance Climate Changer™ Air Handlers
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improper ly installed, adjusted or alt ered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
November 2012
CLCH-SVX08A-EN
Page 2

Warnings, Cautions and Notices

Warnings, Cautions and Notices.
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situ ations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION:
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTION
NOTICE:
Warnings, Cautions and Notices appear at
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous
s
situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
Note that warnings,
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the oz one layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. T rane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow r equirements f or field wiring installat ion and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit coul d result in exposure to electrical, mechanical and chemical hazards.
Before installing/servi cing this unit, technicians MUST put on all P ersonal Protectiv e Equipment (PPE) recommended for the work being undertaken. AL WAYS r efer to appropr iate MSDS sheets and OSHA guidelines for proper PPE.
When work ing with or ar ound hazar dous c hemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, tec hnicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failur e to f ollow r ecommendation s could resul t in death or serious injury.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
© 2012 Trane All rights reserved CLCH-SVX08A-EN
Page 3
Table of Contents
Warnings, Cautions and Notices Model Number Description
Overview of Manual Nameplate
General Information
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . . 5
Product Information
Burner Specifications . . . . . . . . . . . . . . . . . 5
Description
Pre-Installation
Arrival at Jobsite
Flue Stack for Indoor Air Handler . . . . . . . 8
Protective Covering . . . . . . . . . . . . . . . . . . 8
Hardware Kits . . . . . . . . . . . . . . . . . . . . . . . 8
Rain Hood . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Instruction Manuals . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . . . . . . 6
. . . . . . . . . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . . . . . . . . . . . 8
Receiving Inspection Storage
Installation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Outdoor Units . . . . . . . . . . . . . . . . . . . . . . . 8
Indoor Units . . . . . . . . . . . . . . . . . . . . . . . . 9
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Contractors’ Responsibilities
Installing Contractor . . . . . . . . . . . . . . . . . . 9
Electrical and/or Controls Contractor . . . 10
. . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . 4
. . . . . . . . . . . . . . . . . . . . 5
. . . . . . . . . . . . . . . . . . . 8
. . . . . . . . . . . . 9
Service Clearance Recommendations Installations at High Altitude Rigging/Lifting
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . 11
Duct Connections
Combustion Air Duct . . . . . . . . . . . . . . . . 11
Duct Transitions . . . . . . . . . . . . . . . . . . . . 11
Airflow Direction . . . . . . . . . . . . . . . . . . . 11
Rain Hood - Combustion Air Inlet . . . . . . 12
Flue Stack Installation
Outdoor Gas Heat Section . . . . . . . . . . . . 13
Indoor Gas Heat Section . . . . . . . . . . . . . 13
. . . . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . . . . . 11
. . . . . . . . . . . . . . . . . 13
. . . . . . . . . . . 11
. . . . . . . . . . 2
. . . 10
Heat Exchanger Condensate Piping . . . . .14
Wiring
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
High-Voltage Wiring
Wiring Entrance Locations . . . . . . . . . . . .15
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Low-Voltage Wiring
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Initial Startup
Pre-Startup . . . . . . . . . . . . . . . . . . . . . . . . .20
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Pre-Purge and Pilot Ignition . . . . . . . . . . .21
Main Burner Ignition . . . . . . . . . . . . . . . . .21
Pre-Purge and Main Flame Ignition . . . . .22
. . . . . . . . . . . . . . . . . . . . . . . . .20
Final Check Out Normal Shutdown
. . . . . . . . . . . . . . . . . . .15
. . . . . . . . . . . . . . . . . . . .16
. . . . . . . . . . . . . . . . . . . . . . .22
. . . . . . . . . . . . . . . . . . . . .23
Seasonal Startup/Shutdown
Seasonal Shutdown . . . . . . . . . . . . . . . . . .23
Seasonal Startup . . . . . . . . . . . . . . . . . . . .23
Routine Maintenance
. . . . . . . . . . . . . . . . . . . .24
Heating Mode Maintenance Service Personnel Maintenance
Troubleshooting
. . . . . . . . . . . . . . . . . . . . . . . . .25
. . . . . . . . . . . .23
. . . . . . . . . . . . .24
. . . . . . . . .24
Piping
CLCH-SVX07C-EN 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Gas Piping
Proper Gas Pressure . . . . . . . . . . . . . . . . 14
. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Page 4

Model Number Description

Overview of Manual

Use this manual to install, startup, operate, and maintain the Performance Climate Changer™ air handler gas heat

Nameplate

Each air handler section includes a nameplate/label (see
Figure 1), which identifies the type of section, customer
tagging information, the unit serial number, the unit order number, t he build-section position for installation, and the unit model number.
Figure 1. Performance air handler section nameplate
section. Carefully review the procedures discussed in this manual to minimize installation and startup difficulties.
Note: The unit serial number and order number is
required when ordering parts or requesting service for a Trane air handler.
4 CLCH-SVX08A-EN
Page 5

General Information

Product Info rmation

Model and serial numbers for the gas heat section are designated on the nameplate located on the piping-side access door inside the section. Record the information below for a permanent record of the equipment installed on your job site. The nameplate also contains the range of
retain these settings in case the unit should ever need adjustment after service repairs.
Note: This information is required when ordering repair
parts.
settings for whic h the g as heat unit is capable. R ecord and
Model Number____________________________________________________________________________
Serial Number_____________________________________________________________________________
Air Handler Sales Order Number____________________________________________________________
Air Handler Serial Number_________________________________________________________________
Startup Date_______________________________________________________________________________
Altitude Above Sea Level___________________________________________________________________
Calorific Value_____________________________________________________________________________

Burner Specifications

Maximum Firing MBh______________________________________________________________________
Minimum Firing MBh______________________________________________________________________
Type of Gas________________________________________________________________________________
Maximum Inlet Gas Pressure_______________________________________________________________
Minimum Inlet Gas Pressure___________________________________________________________ _____
Temperature Rise (ºF)_______________________________________________________________________
Manifold Pressure at Maximum MBh________________________________________________________
Table 1. Motor and Electrical Specifications
Specifications Gas Heater Input Power Burner Motor
Volts 115 115
Hertz 60 60 60 60
Phase 1 1
HP n/a n/a
FLA/Amps n/a 6
MCA n/a n/a n/a MOP n/a n/a n/a
Note:1Powered by a "line to 115 volt" transformer for all gas heaters except 115/60/1 rated units.
1
Control Power
1
Exhaust Motor
CLCH-SVX08A-EN 5
Page 6
General Information

Description

The gas heat section consists of a drum-and-tube heat exchanger, burner, gas train components, and a control panel for electrical connections. It is an integral part of the entire air-handling system.
An access door is provided for serv ice and maintenance of the burner and gas train components.
The gas heat section must be in a blow-thru position downstream from the supply fan. Downstream sections must be separated by a blank access section and discharge temperatures must be controlled so as not to exceed the
Figure 2. Gas heat section with external vestibule Figure 3. Gas heat section with internal vestibule
temperature limits of components in the downstream sections.
Depending on the heater size, an external vestibule that extends the width of the gas heat section may be used to house the burner and gas train components (see Figure 2). The external vestibule, if required, ships attached to the gas heat section. Some heaters have gas train components in an internal vestibule (see Figure 3). Refer to Table 2 for vestibule locations.
6 CLCH-SVX08A-EN
Page 7
Table 2. Vestibule locations
General Information
Unit Size
6 200 Ext 35 360 Int 66 700 Int 6 300 Ext 35 560 Int 66 860 Int 8 200 Ext 35 700 Int 66 1000 Int
8 300 Ext 35 860 Int 66 1250 Int 10 200 Ext 35 1000 Ext 66 1500 Int 10 360 Ext 35 1 250 Ext 66 1750 Int 12 200 Int 35 1500 Ext 66 2000 Ext 12 360 Ext 35 1 750 Ext 66 2400 Ext 14 200 Int 40 560 Int 80 860 Int 14 360 Ext 40 700 Int 80 1000 Int 17 200 Int 40 860 Int 80 1250 Int 17 360 Ext 40 1 000 Ext 80 1500 Int 17 560 Ext 40 1250 Ext 80 1750 Int 17 700 Ext 40 1 500 Ext 80 2000 Ext 21 200 Int 40 1750 Ext 80 2400 Ext 21 360 Ext 50 560 Int 100 1000 Int 21 560 Ext 50 700 Int 100 1250 Int 21 700 Ext 50 860 Int 100 1500 Int 21 860 Ext 50 1000 Int 100 1750 Int 21 1000 Ext 50 1250 Ext 100 2000 Int 25 360 Ext 50 1500 Ext 100 2400 Ext 25 560 Ext 50 1750 Ext 120 1000 Int 25 700 Ext 50 2000 Ext 120 1250 Int 25 860 Ext 57 560 Int 120 1500 Int 25 1000 Ext 57 700 Int 120 1750 Int 30 360 Int 57 860 Int 120 2000 Int 30 560 Int 57 1000 Int 120 2400 Int 30 700 Int 57 1250 Ext 30 860 Int 57 1500 Ext 30 1000 Ext 57 1750 Ext
(MBH)
Gas Output
Vestibule
Type Unit Size
Gas Output
(MBH)
57 2000 Ext
Vestibule
Type Unit Size
Gas Output
(MBH)
Vestibule
Type
CLCH-SVX08A-EN 7
Page 8

Pre-Installation

Arrival at Jobsite

Gas heat sections arrive at the jobsite with an integral base frame for the purpose of mounting units to a housekeeping pad or roof curb. The base frame variables in height from the standard 2.5- inches to 8 inches.
The gas heat section is designed with the necessary number of lift points for safe installation. The lift points are designed to accept standard rigging devices and are removable after installation. Indo or sections size 3-30 will also be shipped with a shipping skid designed for forklift transport.
Outdoor gas heat sections ship with wooden blocks fastened under the base channel. The blocks elevate the section for shipping protection and ease of handling. Leave the wooden blocks attached until the section is placed in its final position to avoid bending the base channel during rigging and handling.
Flue Stack for Outdoor Air Handler A stainless-steel flue stack is provided with outdoor air
handlers. It ships inside the gas heat section and must be mounted on the flue opening on th e side of the unit. The flue stack mus t be installed on the gas heat section before assembling the gas heat section to the air handler.
It is very difficult to remove the flue from inside the unit once the unit is assembled.

Flue Stack for Indoor Air Handler

Indoor air handlers require a field-engineered and field­installed flue stack. Local codes and practices vary throughout the country . The engineer shoul d size the flue based on MBh output, horizontal and vertical run lengths, type of flue material, NFPA 54 Fuel Gas Code, and local codes. The flue should be designed for 800 degrees F (430 degrees C). If horizontal runs over 20 feet or other static­increasing transitions are necessary , a flue booster fan will be required.

Hardware Kits

Hardware kids ship inside the air handler fan section in a plastic bag or cardboard box. This kit contains gasketing and screws. For outdoor units, roof joint connection strips and wall panel seam caps are included. These are used when fastening the gas heat section to the air handler. Keep the hardware with the gas heat section until it is ready to install.

Rain Hood

A rain hood is provided for outdoor units with internal vestibules. The rain hood is shipped on a sepa r ate woo d skid. A kit containing mounting hardware ships inside the
gas heat section and must be removed before assembly to the air handler.

Instruction Manuals

Individual instruction manuals for all of the gas train components (such as flame-control relay valves, pressure switches, and actuators) ship inside the piping vestibule. Retain these manual for future repair or troubleshooting.

Receiving Inspection

Upon receipt of the gas he at section, inspect it for damage that may have occurred during shipment. Report damage immediately to the freight company. Trane is not
responsible for shipping damage.
Inspect the access door latches and hinges for damage.
Open the access door and check for internal, hidden damage. Concealed damage must be reported within 15 days of receipt.
Locate the hardware kit.
Locate the flue stack if it is an outdoor unit.
If shipped on a skid, do not remove the gas heat section from the skid at this time.
NOTICE:
Equipment Damage!
Do not use type B flue stacks with this product as they are not suitable for the flue gas temperatur es. Failur e to follow this recommendation could result in equipment damage.

Protective Covering

The large openings of the gas heat section are protected by an Oriented Strand Board (OSB) panel covering. The OSB panel is held in place by sheet metal screws. Leave the covering attached to the section until it is ready to install to prevent debris from entering the section.
8 CLCH-SVX08A-EN

Storage

Outdoor Units

A gas heat section designed for outdoor use requires no special protection during storage. Select a solid, well­drained area. Concrete or black top surfaces are recommended. If concrete or black top is not available, set the section on wood timbers to prevent dirt, mud, snow, etc. from getting into the un it. Keep access doors closed to prevent damage to gas train components.
If needed, cover with a canvas tarp. Covering the unit with clear or black plastic sheets is not recommended because this material traps condensed moisture, which can cause equipment damage resulting from rust and corrosion.
Page 9

Installation

T rane war ranty does not cover equipment damage due to negligence during storage.

Indoor Units

For a gas heat section designed for indoor use, Trane recommends indoor storage. If outdoor storage is necessary, select a solid, well-drained area. Concrete or black top surfaces are recommended. If concrete or black top is not available, set the unit on wood timbers to prevent dirt, mud, snow, etc. from getting into the module.
Installation
:
WARNING
Improper Unit Lift!
Do not lift unit from top! Lift unit from lifting lugs only located at bottom of unit. Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to proper ly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or pr operty-only damage.
Keep access doors closed to prevent damage to gas train components.
Cover the unit with a canvas tarp. Covering the unit with clear or black plastic sheets is not recommended because this material traps condensed moisture, which can cause equipment damage resulting from rust and corrosion.
T rane war ranty does not cover equipment damage due to negligence during storage.
WARNING
Combustible Materials!
Maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials. Refer to unit nameplate and installation instr uctions for proper clearances. Improper clearances could result in combustible materials catching on fire. Failure to maintain proper clearances could result in death or serious injury or property damage.

Contractors’ Responsibilities

WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrang ements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possib ly crushing operator/ technician which could r esul t in death or serious injury .
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of t his product and all warnings as provided in this manual. Failur e t o f ollo w all instr u ctions could result in death or serious injury.

Installing Contractor

Unpack the gas heat section and remove the skid.
Remove protective coverings.
Rig and/or move the section to the air handler location. The contractor must provide slings, spreader bars, clevis hooks, pins, etc. for rigging.
For outdoor gas heat sections, a level roof curb or structural steel support system is required. If the gas heat section is provided with an external piping vestibule, no support is required for the vestibule.
For outdoor sections, install the flue stack. The flue must be removed from the airstream before assembly. Install the flue stack on the gas heat section before assembling the gas heat section to the air handler.
Clear debris from combustion air inlet s located on the side or bottom of the gas heat section. Remove any debris obstructing combustion air inlets.
In areas where snow drifts are higher than the bottom of the vestibule, a hood or louver may have to be installed for combustion air.
Assemble the gas heat section to the air-handling system. Refer to the Performance Climate Changer air handler Installation, Operation, and Maintenance manual, CLCH-SVX07B-EN for specific assembly instructions. This manual ships inside the supply fan section of the air handler.
CLCH-SVX08A-EN 9
Page 10
Installation
Filter mixing box
Coil
Fan
Gas heat
Access door
UV lights
VFD
F
E
D
C
B
A
Penetrate the unit casing and connect the supply gas line to the gas train. Gas supply line connection sizes are shown in
Table 3.
Table 3. Gas supply line connection sizes
Gas Output
(MBh) 200-560 700-1000
Connection Size
(NPT)
1 in. 1 1/4 in. 1 1/2 in. 2 in.
1250-
1750
2000-
2400
For indoor gas heat sections, install a field-engineered flue stack according to local codes. S ee Table 4 for flue connection sizes.
Table 4. Flue connection sizes for g a s heat secti ons
Gas Output (MBh) Flue Size (inches)
200, 360, 560 8 × 8
300, 360 9 × 9
700, 860, 1000 12 × 12
1750 10 × 10
2000, 2400 14 x 14

Electrical and/or Controls Contractor

Provide power to the gas heat section. See “Wiring” on
page 15 for power requirements.
Provide a binary start–stop signal.
Provide an analog 0 to 10 Vdc modulating signal. A 0 to 10 Vdc interface module is installed as standard equipment. A 4 to 20 mA interface module is available and may have been installed on the unit for the control signal in lieu of the 0 to 10 Vdc signal.
Provide an interloc k in the start-stop signal circuit with the air handler supply fan. This interlock must insure the start-stop signal is interrupted to the gas heat system if the supply fan is shut off . The gas heat system must not operate without the supply fan providing airflow.
All wiring must comply with applicable local and National Electric Code (NEC) specifications.
Table 5. Service clearances (inches)
For VAV units, provide temperature sensors for entering and leaving air in gas heat section.
All power and control wiring for the gas heat section must be field provided. All power and control wiring for any section downstream of the gas heat must be field provided.

Service Clearance Recommendations

A minimum clearance of the section width plus 12 inches on the access door side of the gas heat section is recommended for routine maintenance. This clearance provides enough room to replace the heat exchanger in the event of failure. The section side panels must be removed to access the heat exchanger. Refer to Figure 4 for service clearance recommendations for the air handler.
Figure 4. Service Clearance
Component 3 4 6 8 10 12 14 17 21 25 30 35 40 50 57 66 80 100 120 A (filter) B (coil) C (UV Lights)
D (external starter or VFD) D (internal starter or VFD)
E (fan) F (gas heat ­Ext Vestibule) F (gas heat ­Int Vestibule)
Note: At a minimum, the above clearance dimensions are recommended on one side of the unit for regular service and maintenance. Refer to as-built
submittal for locations of items such as filter access doors, coil, piping connections, motor locations, etc. Sufficient clearance must be provided on all sides of unit for removal of access panels, plug panels, or section-to-section attachment brackets. Clearance for starters, VFDs, or other high-voltage devices must be provided per NEC requirements.
10 CLCH-SVX08A-EN
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 52 56 58 58 48 59 59 66 77 82 87 87 95 95 109 115 128 141 141 156 156 170 197 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 52 56 58 58
61 61 61 61 61 61 61 61 64 64 64 64 64 64 64 64 64 64 64
48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 51 54 58 61 60 66 66 66 70 77 77 93 93 101 101
N/A N/A 89 90 108 100 100 105 115 115 118 136 140 156 156 170 179 180 N/A
N/A N/A 56 63 74 79 84 84 92 92 106 112 125 138 138 153 153 167 194
Page 11
Installation

Installations at High Altitude

WARNING
Hazard of Explosion!
Installations at altitudes of 3,000 feet above sea lev el or higher may require adjustment of the air-fuel linkage for proper combustion. Linkage and air-fuel adjustment should only be done by an experienced, qualified gas heat technician. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.
Adjustment of gas train li nkages is not normally required. However, for high altitude installations, adjustment to the air -fuel linkages may be necessary for proper combustion. Heater outputs must be derated four percent for every 1000 feet over 2000 feet above sea level. When specifying gas heaters, the engineer should provide the MBh and airflow required at altitude. All Trane literature is based on nominal outputs at sea level.
It is recommended that the services of an experienced, qualified gas heat technician be employed to adjust air -fuel linkages for proper combustion.

Rigging/Lifting

Outdoor units with external vestibules do not have a rain hood. Combustion air enters through openings in the bottom of the vestibule.
All indoor units ship with a screened opening on the combustion air inlet.
If combustion air is to be ducted to the gas heat vestibule, the unit’s capacity must be derated to account for the resistance in the air duct. For every 0.14 inches wg of duct resistance, unit capacity (MBh output) will reduce by five percent.
If combustion air is ducted to the vestibule, it is strongly recommended that an experienced gas heat technician chec k the system and emission levels in the exhaust flue at start up. Carbon dioxide should be between 8.2 and 9.4 percent. This corresponds to the allowable range of excess air needed for combustion. The add itional static pres sure of the inlet air duct may change the fuel-air ratio slightly necessitating system adjustment.
Separated combustion can be a desirable opti on, but will require more field-installation time and material. The burner fans are not sized to handle any static in the combustion air stream. A booster fan will likely be required to overcome combustion air duct static.
Combustion air cannot be ducted directly to the combustion air fan. The airflow through the vestibule is needed to keep the temperatures in the vestibule down.
Refer to the Performance Climate Changer™ air handler Installation, Operation, and Maintenance manual, CLCH­SVX07B-EN, for instructions on equipment rigging and lifting. This manual ships inside the unit fan section.

Assembly

Refer to the design engineer’s plans and submit tals for the location of the gas heat section in the air handler. The g as heat section will arrive at the job site as an individual section. It is not shipped with the air handler. Hardware for fastening the gas heat section to the air handler can be found in the fan section. Final assembly of the air handler should be done at the unit installation site. Refer to the Performance Climate Changer™ air handler Installation, Operation, and Maintenance manual, CLCH-SVX07B-EN, for further instructions on equipment assembly.

Duct Connections

All duct connections to the gas heat section should be installed in accordance with the standards of the National Fire Protection Association (NFPA) and the Sheet Metal and Air Conditioning Contractors Na tional Association, Inc. (SMACNA).

Combustion Air Duct

Outdoor units with internal vestibules have a rain hood that requires field mounting.

Duct Transitions

When the gas heat section is the last section of the air handler, and duct transitions should be smooth and uniform from all sides. Follow recommendations for duct transitions from SMACNA.
Fasten the ductwork directly to the ductwork opening. When using lined ductwork, the insulation should not obstruct the discharge opening.

Airflow Direction

The airflow direction through the gas heater is important because it prevents localized “hot spots” on the heat exchanger. Airflow direction labels denoting correct airflow direction through the gas heat section are provided on the burner side of the heating section. See Figure 5.
Figure 5. Airflow direction label
CLCH-SVX08A-EN 11
Page 12
Installation
Hood
Butyl tape
Hinge
side
2 3/8 in.
Center hood left-to-right over opening
Combustion air opening
Rain hood
Access door
Airflow
Airflow from the supply fan should enter on the drum (or primary) side of the heat exchanger (Figure 6) and exit on the tube (or secondary) side (Figure 7).
Figure 6. Entering airside (drum or primary) of gas heat
section
Figure 7. Leaving air side (tube or secondary) of gas heat
section

Rain Hood - Combustion Air Inlet

Rain hoods are only required on an outdoor unit with an internal vestibule. Depending on unit siz e, the combustion air opening will be in the access doo r or in the side pane l. A unit with an external vestibule has the combustion air opening in the floor of the vestibule and does not require a rain hood, unless excessive snowdrifts are expected.
Rain hoods for the combustion air opening ship loose and must be installed at the job site. The assembly consists of the hood, butyl tape and number 10 screws.
Figure 8. Installation of rain hood for combustion air
opening
Install butyl tape between the hood and the side panel or door panel (see Figure 8).
Locate the bottom edge of the hood 2 3/8 inches below the bottom edge of the inlet air opening and center the hood left-to-right over the inlet air opening (see
Figure 9).
Install the hood to the unit with number 10 screws.
Figure 9. Center inlet air opening
12 CLCH-SVX08A-EN
Page 13

Flue Stack Installation

Outdoor Gas Heat Section

The flue stack for outdoor gas heat sections ships inside the gas heat section (see Figure 10). Attach the flue stac k to the flue collar and secure it with screws as indicated in
Figure 11. See Table 6 for flue connection sizes.
Figure 10. Outdoor air handler flue stack
Installation
Figure 11. Outdoor air handler flue stack installation
A rain hood or screen is recommended on the flue to prevent possible blockage from bird nests and beehives. The rain hood or screen must be field provided.
It is very difficult to remove f lue from inside the unit once the unit is assembled.

Indoor Gas Heat Section

For indoor gas heat sections, a field-engineered flue stack is required. Install according to local codes. See connection sizes in Table 6.
Table 6. Flue connection sizes for gas heat sections
Gas Output (MBh) Flue Size (inches)
200, 360, 560 8 × 8
300, 360 9 × 9
700, 860, 1000 12 × 12
1750 10 × 10
2000, 2400 1 4 x 14
CLCH-SVX08A-EN 13
Page 14

Piping

Piping
WARNING
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.

Gas Piping

Note: Installation must conform with the American
National Standard Z223.1 (NFPA 54), the National Fuel Gas Code, latest edition, in the absence of local codes.
Gas piping should always b e done in accordance with local codes.
Tighten all joints securely.
Pipe unions should be a “ground joint” type to prevent leakage.
Provide adequate support for field-installed piping to avoid placing stress on the gas train and controls.
Run takeoff lines from the side or top of the main g as line to prevent moisture from being drawn into the gas train of the unit.
Provide a drip leg in the field-installed piping, install ing it near the unit.

Proper Gas Pressure

NOTICE:
Excessive Gas Pressure!
The gas pressure at the inlet to the gas train must not exceed 14 in. wc. A properly sized gas regulator that provides a maximum of 14 in wc. of gas pressure, must be supplied in the gas inlet line to unit. Failure to maintain proper gas pr essur e could r esult in damage t o the gas train components.
To assure sufficient gas pressure at the unit, use appropriately sized gas pipe for unit capacity . R efer to the National Fuel Gas Code for pipe sizing information.
Select an appropriately sized gas pressure regulator to assure the required gas supply pressure is maintained at the unit.
Required gas pressure to the gas train is 7 to 14 inc hes wc (0.25 to 0.5 psig) for units through 2400 MBh. Note that a minimum of 9 inches wc (0.32 psig) is required for 1250-2000 MBh heaters with 10:1 turndown capability. For all size units, do not exceed 14 inc hes wc (0.5 psig) inlet gas pressure.
Gas pressure and volume must be maintain ed and stable at high fire.
If the gas pressure regulator serves more than one heating unit, it must be sized appropriately to ensure that the inlet gas pressure at each unit is 7 to 14 inc hes wc while all burners are firing. Nine inch es wc is required for 1250 to 2000 10:1 turndown heaters. Gas pressure must not exceed 14 inches wc when all units are off.
Check the gas supply press ure before making the final connection to the unit. If the gas pressure is too high, damage to the gas valve could occur.
Table 7. Gas supply line connection sizes
Gas Output (MBh) 200-560 700-1000 1250-1750 2000-2400
Connection Size (NPT)
1 in. 1 1/4 in. 1 1/2 in. 2 in.

Heat Exchanger Condensate Piping

Condensate usually does not form in the heat exchanger during normal heating operation. However, if the unit operates for extended periods of time at very low fire, or if the air handler serves as a cooling unit also, condensate can form in the heat exchanger and should be removed.
All units are equipped with a condensate drain and drain valve. The condensate drain is on the same side as the gas train located inside the piping vestibule.
Since the drain line is equipped with a shut-off valve, a condensate p-trap is not required, but may be installed for convenience to avoid periodic manual draining. If a p-trap and drain is to be connecte d to the condensate drain line, consult local plumbing codes for disposal of the condensate may be a slightly acidic solution.
Use Figure 12 as a guideline for p-trap construction. The use of a tee-fitting at the connection to the condensate
outlet is recommended. This allows for priming and cleaning the trap. If a tee-fitting is used, be sure to furnish a plug or cap for the clean out opening. Be sure to replace the plug after priming or cleaning the trap.
14 CLCH-SVX08A-EN
Page 15
Figure 12. Heat exchanger condensate piping
J
H
L
Normal operation
Tee with cap
L=H+J+diameter where: H = 5 inches J = 2.5 inches

Wiring

Wiring

WARNING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, y ou MUST follo w r equirements f or field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servici ng . Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
CLCH-SVX08A-EN 15
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.

High-Voltage Wiring

Wiring Entrance Locations

Indoor air handlers can accept conduit penetrations on any side of the piping vestibule. For outdoor air handlers, the recommended conduit entrance into the gas heat section is through the floor of the piping vestibule.
Terminate conduits on the power junction box or gas heater control panel as appropriate.
Wiring
All field wiring must be in accordance with the National Electric Code and state and local requirements.
All wiring (including low-voltage wiring) must be copper conductors only with the insulation rated for 600 volts.
Refer to the nameplate located on the gas heater section for the proper Input Voltage, Minimum Circuit
Page 16
Wiring
Ampacity (MCA) and Maximum Overcurrent Protection (MOP) requirements for proper electrical installation.
•See Table 8 for power supply requirements.
Note: Factory wiring routed through the heated part of
the cabinet has insulation rated for 600˚F.
Input voltage must be within +/- 1 0 percent of specified value.
Ground the supply power in the junction box to the ground lead provided.
Do not route any wires through the heat exchanger section unless the insulation is rated for 600˚F or higher. Radiant heat from the heat exchanger will damage wire insulation that is unsuitable for high temperatures.
Table 8. Power supply requirements
3:1 and 10:1 Burner Turndown Units
Gas Output (MBh) 200-1000 1250-2000 2000
Voltage/Ph 115-575/1 208-575/3 208/230/460/575/3
Minimum Circuit Ampacity (MCA) less than 15 less than 15
Maximum Overcurrent Protection (MOP) 15 15
Note:1All except the 2000 MBh output, 208 volt, 3 phase unit. This unit will have a marked MCA of 16.1
2
All except the 2000 MBh output, 208 and 230 volt, 3 phase units. These units have a marked MOP of 20
3
2000 MBh with optional 3 hp exhaust motor required for long horizontal flue vents
20:1 Burner Turndown Units
Gas Output (MBh) 1250-1750 2000 2400
Voltage/Ph 208-575/3 208/230/460/575/3 208/230/460/575/3
Minimum Circuit Ampacity (MCA) less than 15 17.3/16.0/8.0/6.4 20.9/19.0/9.5/7.6
Maximum Overcurrent Protection (MOP) 15 20/20/15/15 25/25/15/15
Note: The MCA and MOP for the 2000 MBh with optional 3 hp exhaust motor will be the same as 2400 MBh.
1
2
19.71/17.9/9.0/7.2
3
25/25/15/15
Gas Heaters with 200–1000 MBh Output
Single-phase 120, 208, 230, 460 or 575 volt power is required to operate the heater controls or power the transformer (TRANS1), if provided.
Single-phase power for 208, 230 460 and 575 voltage is provided for the gas heat off two legs of the three-phase supply to the air -handling unit. A transformer in the piping vestibule is provided to step down the voltage required for gas heat.
Gas Heaters with 1250–2400 MBh Output
Three-phase 208, 230, 460 or 575 volt power is required to operate the exhaust fan and power the transformer (TRANS1).

Low-Voltage Wiring

NOTICE:
Equipment Damage!
The gas heat system will not operate without a supply fan providing airflow. Operating the gas heat system without a supply fan could result in damage to equipment or property.
The gas heat control system requires a binary signal for on/off control. Provide an interloc k in the star t-stop signal circuit with the air handler supply fan. This interlock must insure the start-stop signal is interrupted to the gas heat system if the supply fan is shut off. The gas heat system must not operate without the supply fan providing airflow.
The control system also requires a 0 to 10 Vdc analog signal for modulation where 10 Vdc is a signal for full heat. A 4 to 20 mA interface module is available.
16 CLCH-SVX08A-EN
Page 17
Figure 13. 200-1000 MBh 3:1 or 10:1 turndown wiring diagram
Wiring
CLCH-SVX08A-EN 17
Page 18
Wiring
Figure 14. 1250-2000 MBh 3:1 or 10:1 turndown wiring diagram
18 CLCH-SVX08A-EN
Page 19
Figure 15. 1250-2400 MBh 20:1 turndown wiring diagram
Wiring
CLCH-SVX08A-EN 19
Page 20

Operation

Pre-Startup

WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases fr om fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of t his product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servici ng . Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
WARNING
Hazard of Explosion!
Installations at altitudes of 3,000 feet above sea lev el or higher may require adjustment of the air-fuel linkage for proper combustion. Linkage and air-fuel adjustment should only be done by an experienced, qualified gas heat technician. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.
1. Close all manual gas valves.
2. Move the manual disconnect switch in the vestibule to the OFF position.
3. Check the air shutter and modulating gas valve linkages for tightness.
4. Attach a manometer to the bleed port on the side of the first manual gas valve in the burner vestibule at the inlet end of the gas train, upstream of the automatic gas valve/regulator. This manometer c hecks incoming gas pressure and should measure 7 to 14 inches wc. (Exception: 1250 through 2000 Mbh with 10:1 turndown require 9 to 14 inches wc.)
5. Attach another manometer to the burner manifold to check the burner manifold pressure while the unit is firing.
6. Attach a third manometer to the pilot gas line to c hec k the pilot gas pressure while the unit is firing.
7. Remove any debris from combustion air inlets and/or hoods. Note that some combustion air inlets are located on the floor panel of the piping vestibule. Insure the openings are not blocked.
8. For units with burners size 1250 and larger, ensure exhaust fan rotation is correct.
Figure 16. Control panel for the JR burner on 200-1000
mbh (3:1 & 10:1 turndown) units
Gas heat sections have been run-tested in the factory to assure proper operation and ease of startup. The actuator linkages controlling the air–fuel mixture are preset for optimum efficiency and perfor ma nce.
Thoroughly review all service literature before startup and servicing. The sequence of operation and all details of the flame-safeguard control system can be found in the burner equipment literature. The technical bulletins cover the individual components of the heating system. This literature ships inside the piping vestibule of the g as heat section.

Initial Startup

Note: The procedures discussed in this section should be
done by qualified technicians who are experienced with gas heating equipment.
20 CLCH-SVX08A-EN
Page 21
Figure 17. Control panel for the FDM burner on 1250-
2400 (20:1 turndown) units

Startup

WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electr ical components could result in death or serious injury.
1. Start the air-handling unit fan. The field-installed supply fan interlock and primary airflow switch contacts (AI1) should close.
2. The high-temperature-limit switc h contacts (HL1), the modulating gas valve actuator, and its end switch contacts (AES) should be closed.
3. The building control system should call for heat, closing a contact between terminals four and five.
4. Open the manual gas valve outside the unit next to the gas pressure regulator and bleed air from the piping.
5. Measure the gas pressure at the manual gas valve. The inlet gas pressure should not exceed 14 inches wg. Adjust the gas pressure, if necessary.
6. Open the first manual gas valve in the burner vestibule.
7. Open the manual gas valve in the pilot gas line and bleed the air from the line.
Operation
8. R emo ve any debris from combustion air inlets and/or hoods. Note that some combustion air inlets are located on the floor panel of the piping vestibule. Insure the openings are not blocked.

Pre-Purge and Pilot Ignition

(3:1, 10:1 Turndown, 200-2000 MBh)
Move the manual disconnect switch in the heater vestibule to the ON position. The system should energize, and the combustion blower motor should start, indicating that all of the safety/limit contacts are closed:
HLI1: high-temperature limit
AI1: airflow interlock
HPGS1: high-pressure gas switch
LPGS1: low-pressure gas switch
The combustion airflow switch (CAFS1) should close, starting the purge timer, the green power light should illuminate on the flame-relay panel, the combustion air dampers should open and the prepurge cycle should begin. The combustion air blower should run for approximately 90 seconds to evacuate the heat exchanger of any combustible gases before the ignition sequence. This prepurge cycle is initiated before every startup.
With the prepurge cycle complete, the ignition transformer and pilot solenoid should be energized, allowing gas to flow to the pilot burner. The pilot should light immediately. The pilot flame gas pressure should be
2.5 to 3 inches wg.
If the pilot does not light within 10 seconds, the flame relay should shut down the system, and the red Flame Failure light should illuminate on the fla me relay panel. If the pilot does not light, press the Reset button to clear the fault and repeat the procedure outlined in “Startup” on page 21.
The pilot flame can be viewed through the small sight glass on the burner.
Cycle the pilot on and off several times to ensure its reliability. Turn the manual disconnect switch in the control panel to the Off position.

Main Burner Ignition

(3:1, 10:1 Turndown, 200-2000 MBh)
1 . With the manual disconnect switc h in the Off position,
open the second manual gas valve located downstream of the automatic gas valve/regulator in the piping vestibule. Note that this valve is just upstream of the modulating gas valve.
2. Turn the manual disconnect switch to the On position. After the pre-purge and pilot cycle, the main gas valve will energize and the main burner will light.
3. The amber Main Flame light should illuminate on the flame-relay panel after the ultra-violet flame sensor has detected the main flame. The flame can be observed through the larger sight glass under the burner. Normal flame color is blue; abnormal color is
CLCH-SVX08A-EN 21
Page 22
Operation
yellow, indicating a need for adjustments by a qualified technician. Note that smaller sized heaters have the sight glass on the side opposite the piping connection side.
4. Check the flame-signal strength from the ultra-violet sensor. A 0 to 15 Vdc, 1 0K ohm (mini mum) voltmeter is required.
5. Insert the positive probe of the voltmeter into the positive (+) flame-signal test point on the flame relay cover.
6. Connect the negative probe to the negative (-) test point on the flame relay cover. Table 9 shows the desired signal strengths.
7. Allow the burner to ramp up to full fire.
.
Table 9. Signal strengths
Signal Strength Ultra-Violet Sensor
Good 5.0–11.0 Vdc Marginal 1.7–5.0 Vdc Inadequate 0.0–1.7 Vdc

Pre-Purge and Main Flame Ignition

(20:1 Turndown, 1250-2400 MBh)
With the manual gas cocks closed move the manual disconnect switch in the heater vestibule to the ON position. The system should energize, and the combustion blower motor should start, indicating that all of the safety/ limit contacts are closed:
HLI1: high-temperature limit
AI1: airflow interlock
HPGS1: high-pressure gas switch
LPGS1: low-pressure gas switch
The combustion airflow switch (CAFS1) should close, starting the purge timer, the green power light should illuminate on the flame-relay panel, and the prepurge cycle should begin. The combustion air blower should run for approximately 90 seconds to evacuate the heat exchanger of any combustible gases before the ignition sequence. This prepurge cycle is initiated before every startup.
At the end of the purge cycle, the ignition transformer and automatic gas valves will energize. With the manual gas cocks closed, the burner should go into a safety lockout condition. The flame safeguard will have to be reset manually . Turn the manual disconnect switch in the control panel to the OFF position.
Note: Prior to opening the manual gas coc k make cert ain
the modulating gas linkage is set to operate in all positions without binding.
1 . T urn the manual disconnect switc h in the control panel
to the ON position. After the prepurge sequence is complete the ignition transformer will energize providing ignition spark and the main automatic gas
valves will open. With the ignition spark energized and the automatic gas valve open, slowly open the manual gas shut off cocks. Flame should be established. (Make sure the modulating gas valve is adequately open).
2. At initial start up, air may be trapped in the g as lines so more than one attempt to light of f may be required. Do not allow unburned gas to accumul ate in the combustion chamber.
3. Once flame is established run the mod motor to position the modulating gas valve wide open.
4. The amber Main Flame light should illuminate on the flame relay panel after the ultra-violet flame sensor has detected the main flame. The flame can be observed through the larger sight glass under the burner. Normal flame color is blue; abnormal color is yellow, indicating a need for adjustments by a qualified technician. Note that smaller sized heaters have the sight glass on the side opposite the piping connection side.
5. Check the flame-signal strength from the flame rod. A 0 to 15 Vdc, 1 megohm/volt (minimum) meter is required.
6. Insert the positive probe of the voltmeter into the positive (+) flame-signal test point on the flame relay cover.
7. Connect the negative probe to the negative (-) test point on the flame relay cover. Flame signal strength should be a steady dc voltage between 1.25 and 5.0 volts.
8. Allow the burner to ramp up to full fire.

Final Check Out

1. Check the gas pressure at the burner manifold. It should be the same pressure that is indicated on the Manifold Pressure at Max. Input nameplate at full fire. Refer to the Power Flame burner nameplate for this value.
2. Adjust the gas pressure at the automatic gas valve/ regulator by removing the dust cap on the main gas valve/regulator and turning the adjusting screw. Turn the adjusting screw clockwise to increase the gas pressure; turn the adjusting screw counter-clockwise to decrease the gas pressure. If the pressure cannot be maintained at full fire at the setting shown on the nameplate and the regulator is adjusted fully open, contact your local gas utility.
3. Using a gas analyzer, check the emissions in the exhaust gas. Acceptable values are:
a. Carbon monoxide (CO)—400 ppm or less corrected
to 12 percent carbon dioxide. b. Efficiency—75 percent or higher c. Oxygen—8 to12 percent d. Carbon dioxide - 8.2 to 9.4 percent
22 CLCH-SVX08A-EN
Page 23
Operation
:
NOTICE:
Over Firing Burners!
If fuel and air adjustment linkages were adjusted in the start-up process, insure that the burner is not allowed to over fire. The gas pressure on the manifold must not exceed the gas pressure stated on the Powerflame burner name plate. Over firing operation could result in equipment and property damage.
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases from fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of t his product and all warnings as provided in this manual. Failur e t o f ollo w all instructions could result in death or serious injury.
The gas heat module/secti on goes through the following routine every time it is started. The air handler fan must be running, and the Power light on the flame-relay module should be illuminated.
1 . A contact closure command (the signal to start) comes
from a thermostat or building automation system.
2. The combustion air blower starts and runs for approximately 90 seconds. This 90-second run is a pre­purge cycle to clear the heat exchanger of combustible gases before ignition.
3. 3:1 and 10:1 turndown, 200-2000 Mbh: The pilot light ignites, and the pilot light on the flame-relay module should illuminate. (The pilot flame can be viewed through the small sight glass on the burner.) The pilot flame will burn for 10 seconds, then the flame light on the flame-relay module should illuminate.
4. 3:1 and 10:1 turndo wn, 200-2000 Mbh: The main burner ignites, the modulating gas-valve actuator starts to open, and the main light on the flame-relay module should illuminate. Note that it could take as long as 30 seconds for the actuator to fully open.
5. 20:1 turndown, 1250 thru 2400 Mbh: The main burner lights and the main burner light on the flame­relay should illuminate. The modulating gas-valve actuator starts to open, and the main light on the flame­relay module should illuminate. Note that it could take as long as 30 seconds for the actuator to fully open.
6. The gas-valve actuator slowly modulates open or closed in response to the heat load required in the building.
7. Complete the start-up checklist and send a copy as directed to T rane to validate the warranty.

Normal Shutdown

When the system no longer requires heat, the temperature control system opens the heat start contacts. The pilot valve (3:1, 10:1 turndown burners), modulating gas valve (20:1 turndown burners), automatic gas valve/regulator, redundant automatic gas valve, and combustion blower motor immediately de-energize, shutting down the heating system.
The air-handling unit fan should run for a minimum of three to ten minutes after heater shutdown to cool the heat exchanger.

Seasonal Startup/Shutdown

Note: This procedure should be performed by a qualified
technician who is experienced in the servicing of gas heating equipment.
The following recommended proced ur e s for se asonal shutdown and startup are important to maintaining your equipment in proper working order.

Seasonal Shutdown

When heating system is to be shut down for extended period of time:
Disconnect the main power to the heating module/ section.
Open the manual disconnect switch in the control panel.
Close all manual valves in the gas line.

Seasonal Startup

When heating system is to be started for first time in the season:
Disconnect electrical power.
If the heat exchanger does not have a p-trap and condensate drain line, connect a hose to the drain valve and drain any accumulated condensate.
Check all electrical terminals for tight connections.
Open all manual gas valves and ensure that these valves operate freely.
Check the air shutter and modulating gas valve linkages for tightness.
Clean dust, dirt, and debris from the air shutters on the combustion fan and the air inlet louver.
Check the exhaust flue for debris and clean as necessary.
Re-connect the power and initiate the startup sequence.
CLCH-SVX08A-EN 23
Page 24

Routine Maintenance

:
WARNING
Hazardous Gases and Flammable Vapors!
Exposure to hazardous gases fr om fuel substances have been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of t his product and all warnings as provided in this manual. Failure to follow all instructions could result in death or serious injury.

Heating Mode Maintenance

Table 10. Routine maintenance in heating mode
Task Frequency Remarks
Unit startup Weekly Listen to and visually inspect the unit during normal startup. Unit shutdown Weekly Listen to and visually inspect the unit during normal shutdown. Check fuel valves, pilot and main Weekly Open limit switches and listen to and visually inspect. Check combustion safety controls:
• Flame failure
• Flame signal strength
Drain condensate from heat exchanger Weekly This task only needs to be done if the unit runs for extended hours at low fire. Clean air inlet louver Monthly Use brush and vacuum cleaner Clean combustion air blower and motor Monthly Use brush and vacuum cleaner Clean exhaust flue Monthly Use brush and vacuum cleaner Clean combustion air dampers Monthly Use brush and vacuum cleaner Check combustion air inlets for obstruction. Remove debris.
Check gas piping for leaks Yearly
Weekly
Weekly
Monthly Use brush or vacuum cleaner.
• Close manual fuel supply for the pilot and the main fuel valves ; check safety shutdown timing and record.
• Follow procedur e to c heck flame signal str ength outlined in “Main Burner Ignition” on
page 21.
Use soap bubble solution or equivalent leak tester.
WARNING: Do not use an open flame to perform a leak test as personal injury or death
could occur.

Service Personnel Maintenance

Table 11. Rou tine maintenance for trained service personnel
Task Frequency Remarks
Inspect burner components Semiannually Refer to burner and component manufacturer’s manuals
Inspect airflow sensor lines for obstructions.
Visually inspect safety switches Semiannually
Check flue emissions Annually Use a combustion analyzer Check fuel valves, main Annually Perform valve leak test per valve manufacturer’s instructions Check safety controls:
• High limit
•Airflow
• Low gas pressure
• High gas pressure
• Exhaust fan switch (where applicable)
Inspect gas pilot assembly Annually Remove and clean if applicable
24 CLCH-SVX08A-EN
Annually Refer to control manufacturer’s instructions
Inspect terminal connections for tightness. Inspect switches for fused contacts. Check that settings haven’t changed or been tampered with.
Page 25

Troubleshooting

:
WARNING
Hazardous Service Procedures!
The maintenance and troubleshooting procedures recommended in this manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concerning these procedures. Unless specified otherwise, disconnect all electrical power including remote disconnect and disc ha rge all energy storing devices such as capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licen sed electrician or other individual who has been trained in handling live electrical components perform these tasks. Fa ilure to follow all of the recommended safety warnings provided, could result in death or serious injury.
Table 12. Troubleshooting gas heat sections
Symptom Probable Cause Recommended Action
• Check the fuse/breaker panel and reset or replace the device.
• Check the fuses if provided, in gas heat control panel and replace as needed. Open the gas valve. There may be more than one manual gas valve in the piping system.
Be sure to check all valves.
• Repair or replace the thermostat, if defective.
• Set thermostat to heating mode. Verify that one of the following safety switches has tripped:
High Limit. This switch trips due to a high temperature condition in the gas heat section. Allow the air handler fan to run and cool he at exchanger. The switch must be manually reset when the heat exchanger cools.
Airflow Interlock. This switch trips when there is no or very low airflow over the heat exchanger. Repair the air handler fan, if necessary. Also, check to see if the unit is running with a variable-frequency drive. The minimum speed may be set too low.
High Pressure Gas. This switch trips if there is excessive gas pressure in the gas p iping. Adjust the gas pressure regulator or contact the local gas utility.
Low Pressure Gas. This switch trips when there is very low gas pressure in the gas piping. Adjust the gas pressure regulator or contact the local gas utility.
Press the Reset button to reset the flame relay and attempt to restart the gas heat module/section. If the unit continues to trip-out, see the troubleshooting symptom below.
• The combustion air motor may be overloaded. Press the Reset button on back side of the combustion air blower motor.
• The combustion air blower motor may be defective. Replace the motor.
• The modulating gas valve e nd switch contacts ma y be op en, indi cating that t he gas valve is not fully closed. Look for jammed linkages and repair as necessary.
• Replace the modulating gas valve and actuator.
• Check airflow switch sensor tubes for c logging or obstruction. Remov e debris to clear tubes.
• Check exhaust flue for obstructions. Clear obstructions.
• Check inlet air damper for obstructions. Clear obstructions.
• Check airflow switch sensor tubes for c logging or obstruction. Remov e debris to clear tubes.
• Check exhaust flue for obstructions. Clear obstructions.
• Check if air balancing damper is closed. Open damper.
• Check 3-phase wiring to unit for corr ect phasing. Motor ma y be running backwards.
Check combustion air inlet (into piping vestibule) for ob structions blocking ent rance of combustion air. Remove obstructions or debris.
Unit not running, no heat in building.
Unit only runs when service access door on piping vestibule is open
Loss of power, fuse blown, or circuit breaker tripped
Manual gas valve closed
Thermostat not calling for heat
Safety switch tripped
Unit locked out on flame failure; “Alarm” LED illuminated on flame­relay panel.
Combustion airflow switch contacts may be open
Induced draft exhauster fan, if so equipped, airflow switch contacts may be open.
Combustion airflow switch contacts may be open.
Hazardous Gases and Flammable Vapors!
Exposure to hazardous g ases from fuel substances ha ve been shown to cause cancer, birth defects or other reproductive harm. Improper installation, adjustment, alteration, service or use of this product could cause flammable mixtures or lead to excessive carbon monoxide. To avoid hazardous gases and flammable vapors follow proper installation and set up of this product and all warnings as provided in this manual. Failur e to follow all instr ucti ons cou ld result in death or serious injury.
WARNING
CLCH-SVX08A-EN 25
Page 26
Troubleshooting
Table 12. Troubleshooting gas heat sections
• The manual gas valve may be closed; open it.
• (3:1 and 10:1 turndown burners) UV flame sensor may be dirty; check the lens for dirt, soot, and so on, and clean the lens, if necessary.
• Check the ignition cable and wiring for loose, frayed connections or broken wiring. Repair as necessary.
Flame sensor not sensing pilot flame
Unit will not run, locks out on flame failure; “Al arm” LED illuminated on flame relay panel.
Low flame signal voltage
CO is above 400 ppm. Gas pressure not adjust properly. Adjust gas pressure. See “Proper Gas Pressure” on page 14.
• Pilot solenoid valve may not be opening.
• Check for voltage at the pilot solenoid valve.
• Check for sufficient gas pressure in the pilot line and adjust the pilot pressure regulator.
• (20:1 Turndown Burners) Check flame rod for cleanliness, adequate grounding and that it is properly located in the flame. Also ensure that temperature at flame rod insulator is no greater than 500 F (260 C).
• Perform Ignition Interference Test per component manufacturers manual.
• Check flame signal voltage per procedure in Start-Up section.
• (3:1 and 10:1 turndown burners) UV flame sensor may be dirty; chec k lens for dirt, soot, and so on and clean the lens, if necessary.
• The flame sensor may be defective; replace it.
• (20:1 turndown burners) Check flame rod for cleanliness, adequate grounding and that it is properly located in the flame. Also ensure that temperature at flame rod insulator is no greater than 500 F (260 C).
26 CLCH-SVX08A-EN
Page 27

Notes

Notes
CLCH-SVX08A-EN 27
Page 28
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.T r ane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
© 2012 Trane All rights reserved CLCH-SVX08A-EN 10 Nov 2012 Supersedes CLCH-SVX08A-EN (02 Feb 2012)
We are committed to using environmentally conscious print practices that reduce waste.
Loading...