Trane Gas Heating Products Reference Guide

Gas Heating Products
Indoor and Outdoor Units
Indirect Fired, Direct Fired, and Gas Unit Heaters
March 2006 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Propeller fan gas unit heaters, centrifugal gas unit heaters, duct furnaces, horizontal blower assemblies, indoor make-up air handlers and rooftop gas heating units are available in a wide range of sizes with a variety of factory-
Propeller Fan Gas Unit Heaters Model GPND/GPPD
The Trane propeller gas unit heater is a complete heat generating and distribution plant equipped with automatic safety controls. Available for natural or propane gas operation, this unit heater carries a ten-year non prorated warranty on the heat exchanger, draft hood assembly and burners.
installed options to meet your application needs. All units are CSA certified, conforming to the toughest standards for safe and efficient operation. Contact the local Trane sales office for more information.
Propeller Fan Gas Unit Heaters
GPND/GPPD 003 004 006 007 010 012 015 017 020 022 025 030 035 040 Input MBh 30.0 45.0 60.0 75.0 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 24.3 36.5 48.6 60.8 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet 4"R 4"R 5"R 5"R 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10"OV 10"OV 12"OV CFM 700 800 1050 1100 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F3042425050565051566160505256 Outlet Velocity 700 750 640 672 950 900 1045 1070 1000 950 980 1100 1150 1050 Nominal Horsepower 1/30 1/30 1/30 1/30 1/20 1/10 1/4 1/3 1/3 1/3 1/3 (2) 1/4 (2) 1/3 (2) 1/3 Motor Full Load Amps 1.3 1.3 1.3 1.3 2.6 2.8 4.0 4.5 4.5 4.5 4.5 8.0 9.0 9.0
Centrifugal Fan Gas Unit Heaters Model GCND/GCPD
Centrifugal fan gas unit heaters are designed for applications where ductwork or discharge nozzles are used. They are ideal for commercial and institutional applications where a low noise level is desired. A duct discharge flange may be ordered in lieu of horizontal louvers. These gas unit heaters carry a ten-year non­prorated warranty on the heat exchanger, draft hood assembly and burners.
Centrifugal Fan Gas Unit Heaters
GCND/GCPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10" OV 10" OV 12" OV Free Air Delivery 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Temperature Rise F 62595656626465565662 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Full Load Amps 5.0 5.9 7.2 7.2 11.0 11.0 11.0 11.0 14.0 14.0
UH-TS-1 2
Indirect Fired
A Complete Line of Gas Heating Products
High Efficiency Propeller Fan Gas Unit Heaters Model GHND/GHPD
Trane high efficiency propeller fan gas unit heaters can achieve annual fuel savings of 20 to 25 percent or more over conventional gravity-
power venting allows for side wall venting, smaller openings and single­walled vent pipe. These high efficiency gas fan unit heaters carry a ten-year non-prorated warranty on the heat exchanger, flue collector and burners.
vented heaters. Features include a factory installed flue vent fan and sealed flue collector that control combustion and excess air during the on-cycle. Heated air no longer escapes through the draft diverted opening during the off cycle. Energy­saving intermittent pilot ignition reduces gas losses. The pilot only operates when required. Horizontal
High Efficiency Propeller Fan Gas Unit Heater
GHND/GHPD 003 004 006 007 010 012 015 017 020 022 025 030 035 040 Input MBh 30.0 45.0 60.0 75.0 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 24.0 36.0 48.0 60.0 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Rec. Flue Size 4’R 4"R 4"R 4’R 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R CFM 750 800 1050 1100 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F3042425050565051566160505256 Outlet Velocity 680 720 610 640 775 910 1045 1070 1010 950 980 1100 1150 1050 Nominal Horsepower 1/30 1/30 1/30 1/30 1/20 1/10 1/4 1/3 1/3 1/3 1/3 (2) 1/4 (2) 1/3 (2) 1/3 Motor Amps 1.3 1.3 1.3 1.3 2.6 2.8 4.0 4.5 4.5 4.5 4.5 8.0 9.0 9.0
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
.
High Efficiency Centrifugal Fan Gas Unit Heaters Model GBND/GBPD
carries a ten-year non-prorated warranty on the heat exchanger, flue collector and burners.
The Trane high efficiency centrifugal fan gas unit heater incorporates the same features as the high efficiency propeller unit heater. An exceptionally balanced centrifugal blower assembly results in quieter operation. The high efficiency centrifugal fan is also well-suited for high static applications where ductwork is required. Duct discharge flanges may be ordered in lieu of horizontal louvers to accommodate ductwork. Trane’s high efficiency centrifugal fan gas unit heater
High Efficiency Centrifugal Fan Gas Unit Heater
GBND/GBPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Flue Outlet 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R Free Air Delivery 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Amps 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
3 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Separated Combustion Propeller Fan Gas Unit Heaters Model GAND/GAPD
The Trane separated combustion propeller fan gas unit heaters can yield higher seasonal efficiencies. A power venting system draws in a controlled amount of outdoor air for combustion and exhausts flue products from the building. The burners, pilot and flue system are totally enclosed within the unit, effectively isolating the entire combustion process from the dust, humidity and chemicals in the heater’s surrounding environment.
Separated Combustion Propeller Fan Gas Unit Heater
GAND/GAPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"R 6"R 6"R Combustion Air Inlet 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"OV 6"OV 6"OV CFM 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F 50565051566160505256 Outlet Velocity 775 910 1045 1070 1000 950 980 1100 1150 1050 Nominal Horsepower 1/20 1/10 1/4 1/3 1/3 1/3 1/2 (2) 1/4 (2) 1/3 (2) 1/3 Motor Amps 2.6 2.8 4.0 4.5 4.5 4.5 5.5 8.0 9.0 9.0
Separated Combustion Centrifugal Fan Gas Unit Heaters Model GKND/GKPD
The separated combustion centrifugal fan gas unit heater incorporates all the same features as the separated combustion propeller unit heater.
In addition, this unit features quiet operation due to an exceptionally balanced centrifugal blower assembly and high static applications where duct work is required. Duct discharge flanges may be ordered in lieu of horizontal louvers to accommodate duct work.
Separated Combustion Centrifugal Fan Gas Unit Heater
GKND/GKPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"R 6"R 6"R Combustion Air Inlet 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"OV 6"OV 6"OV CFM 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Temperature Rise F 62595656626465565662 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Amps 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4
Indoor Gas Duct Furnaces Model GDND/GDPD
Also available with bottom or side access to the burner drawer.
Trane duct furnaces are CSA certified for installation downstream of cooling coils in air conditioning systems. Both LP (propane) and natural gas units are available with left or right-hand controls for ganging of units in the field. Approved in blow-thru applications only.
Indoor Gas Duct Furnaces
GDND/GDPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Max CFM 2469 3086 3704 4321 4938 5556 6173 7407 8642 9877 Pressure Drop .90 .80 .75 .75 .75 .75 .80 .90 .90 .90 Min Temperature Rise F 30303030303030303030 Min CFM 929 1157 1389 1620 1852 2083 2315 2778 3241 3704 Pressure Drop .12 .13 .15 .14 .14 .14 .14 .13 .13 .14 Max Temperature Rise F 80808080808080808080 Flue Outlet 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10"OV 10"OV 12"OV
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
UH-TS-1 4
Loading...