Trane Gas Heating Products Reference Guide

Gas Heating Products
Indoor and Outdoor Units
Indirect Fired, Direct Fired, and Gas Unit Heaters
March 2006 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Propeller fan gas unit heaters, centrifugal gas unit heaters, duct furnaces, horizontal blower assemblies, indoor make-up air handlers and rooftop gas heating units are available in a wide range of sizes with a variety of factory-
Propeller Fan Gas Unit Heaters Model GPND/GPPD
The Trane propeller gas unit heater is a complete heat generating and distribution plant equipped with automatic safety controls. Available for natural or propane gas operation, this unit heater carries a ten-year non prorated warranty on the heat exchanger, draft hood assembly and burners.
installed options to meet your application needs. All units are CSA certified, conforming to the toughest standards for safe and efficient operation. Contact the local Trane sales office for more information.
Propeller Fan Gas Unit Heaters
GPND/GPPD 003 004 006 007 010 012 015 017 020 022 025 030 035 040 Input MBh 30.0 45.0 60.0 75.0 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 24.3 36.5 48.6 60.8 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet 4"R 4"R 5"R 5"R 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10"OV 10"OV 12"OV CFM 700 800 1050 1100 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F3042425050565051566160505256 Outlet Velocity 700 750 640 672 950 900 1045 1070 1000 950 980 1100 1150 1050 Nominal Horsepower 1/30 1/30 1/30 1/30 1/20 1/10 1/4 1/3 1/3 1/3 1/3 (2) 1/4 (2) 1/3 (2) 1/3 Motor Full Load Amps 1.3 1.3 1.3 1.3 2.6 2.8 4.0 4.5 4.5 4.5 4.5 8.0 9.0 9.0
Centrifugal Fan Gas Unit Heaters Model GCND/GCPD
Centrifugal fan gas unit heaters are designed for applications where ductwork or discharge nozzles are used. They are ideal for commercial and institutional applications where a low noise level is desired. A duct discharge flange may be ordered in lieu of horizontal louvers. These gas unit heaters carry a ten-year non­prorated warranty on the heat exchanger, draft hood assembly and burners.
Centrifugal Fan Gas Unit Heaters
GCND/GCPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10" OV 10" OV 12" OV Free Air Delivery 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Temperature Rise F 62595656626465565662 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Full Load Amps 5.0 5.9 7.2 7.2 11.0 11.0 11.0 11.0 14.0 14.0
UH-TS-1 2
Indirect Fired
A Complete Line of Gas Heating Products
High Efficiency Propeller Fan Gas Unit Heaters Model GHND/GHPD
Trane high efficiency propeller fan gas unit heaters can achieve annual fuel savings of 20 to 25 percent or more over conventional gravity-
power venting allows for side wall venting, smaller openings and single­walled vent pipe. These high efficiency gas fan unit heaters carry a ten-year non-prorated warranty on the heat exchanger, flue collector and burners.
vented heaters. Features include a factory installed flue vent fan and sealed flue collector that control combustion and excess air during the on-cycle. Heated air no longer escapes through the draft diverted opening during the off cycle. Energy­saving intermittent pilot ignition reduces gas losses. The pilot only operates when required. Horizontal
High Efficiency Propeller Fan Gas Unit Heater
GHND/GHPD 003 004 006 007 010 012 015 017 020 022 025 030 035 040 Input MBh 30.0 45.0 60.0 75.0 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 24.0 36.0 48.0 60.0 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Rec. Flue Size 4’R 4"R 4"R 4’R 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R CFM 750 800 1050 1100 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F3042425050565051566160505256 Outlet Velocity 680 720 610 640 775 910 1045 1070 1010 950 980 1100 1150 1050 Nominal Horsepower 1/30 1/30 1/30 1/30 1/20 1/10 1/4 1/3 1/3 1/3 1/3 (2) 1/4 (2) 1/3 (2) 1/3 Motor Amps 1.3 1.3 1.3 1.3 2.6 2.8 4.0 4.5 4.5 4.5 4.5 8.0 9.0 9.0
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
.
High Efficiency Centrifugal Fan Gas Unit Heaters Model GBND/GBPD
carries a ten-year non-prorated warranty on the heat exchanger, flue collector and burners.
The Trane high efficiency centrifugal fan gas unit heater incorporates the same features as the high efficiency propeller unit heater. An exceptionally balanced centrifugal blower assembly results in quieter operation. The high efficiency centrifugal fan is also well-suited for high static applications where ductwork is required. Duct discharge flanges may be ordered in lieu of horizontal louvers to accommodate ductwork. Trane’s high efficiency centrifugal fan gas unit heater
High Efficiency Centrifugal Fan Gas Unit Heater
GBND/GBPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Flue Outlet 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R Free Air Delivery 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Amps 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
3 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Separated Combustion Propeller Fan Gas Unit Heaters Model GAND/GAPD
The Trane separated combustion propeller fan gas unit heaters can yield higher seasonal efficiencies. A power venting system draws in a controlled amount of outdoor air for combustion and exhausts flue products from the building. The burners, pilot and flue system are totally enclosed within the unit, effectively isolating the entire combustion process from the dust, humidity and chemicals in the heater’s surrounding environment.
Separated Combustion Propeller Fan Gas Unit Heater
GAND/GAPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"R 6"R 6"R Combustion Air Inlet 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"OV 6"OV 6"OV CFM 1480 1650 2200 2530 2640 2700 3100 4400 5000 5300 Temperature Rise F 50565051566160505256 Outlet Velocity 775 910 1045 1070 1000 950 980 1100 1150 1050 Nominal Horsepower 1/20 1/10 1/4 1/3 1/3 1/3 1/2 (2) 1/4 (2) 1/3 (2) 1/3 Motor Amps 2.6 2.8 4.0 4.5 4.5 4.5 5.5 8.0 9.0 9.0
Separated Combustion Centrifugal Fan Gas Unit Heaters Model GKND/GKPD
The separated combustion centrifugal fan gas unit heater incorporates all the same features as the separated combustion propeller unit heater.
In addition, this unit features quiet operation due to an exceptionally balanced centrifugal blower assembly and high static applications where duct work is required. Duct discharge flanges may be ordered in lieu of horizontal louvers to accommodate duct work.
Separated Combustion Centrifugal Fan Gas Unit Heater
GKND/GKPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Flue Outlet (1) 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"R 6"R 6"R Combustion Air Inlet 4’R 4"R 4"R 4’R 5"R 5"R 5"R 6"OV 6"OV 6"OV CFM 1200 1575 1975 2300 2400 2600 2850 3950 4600 4800 Temperature Rise F 62595656626465565662 Outlet Velocity 880 950 1030 1045 965 935 930 1080 1090 1000 Nominal Horsepower 1/4 1/3 1/2 1/2 3/4 3/4 3/4 3/4 1 1 Motor Amps 5.1 6.6 7.4 7.4 12.0 12.0 12.0 12.0 15.4 15.4
Indoor Gas Duct Furnaces Model GDND/GDPD
Also available with bottom or side access to the burner drawer.
Trane duct furnaces are CSA certified for installation downstream of cooling coils in air conditioning systems. Both LP (propane) and natural gas units are available with left or right-hand controls for ganging of units in the field. Approved in blow-thru applications only.
Indoor Gas Duct Furnaces
GDND/GDPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Max CFM 2469 3086 3704 4321 4938 5556 6173 7407 8642 9877 Pressure Drop .90 .80 .75 .75 .75 .75 .80 .90 .90 .90 Min Temperature Rise F 30303030303030303030 Min CFM 929 1157 1389 1620 1852 2083 2315 2778 3241 3704 Pressure Drop .12 .13 .15 .14 .14 .14 .14 .13 .13 .14 Max Temperature Rise F 80808080808080808080 Flue Outlet 6"R 6"R 7"R 7"R 8"R 8"R 8"R 10"OV 10"OV 12"OV
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
UH-TS-1 4
Indirect Fired
A Complete Line of Gas Heating Products
High Efficiency Indoor Gas Duct Furnace Model GLND/GLPD
The Trane high efficiency indoor gas duct furnaces can achieve annual fuel savings of 20 to 25 percent or more
Energy saving intermittent pilot ignition reduces gas losses. The pilot operates only when required. Horizontal power venting allows side wall venting, smaller openings and single wall vent pipe.
over conventional gravity vented units. Features include a factory installed flue vent fan and sealed flue collector that control combustion and excess air during the on-cycle. Heated air no longer escapes through the draft diverted opening during the off cycle.
High Efficiency Indoor Gas Duct Furnace
GLND/GLPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Max CFM 2469 3086 3704 4321 4938 5556 6173 7407 8642 9877 Pressure Drop 0.90 0.80 0.75 0.75 0.75 0.75 0.80 0.90 0.90 0.90 Min. Temperature Rise F 30303030303030303030 Min. CFM 929 1157 1389 1620 1852 2083 2315 2778 3241 3704 Pressure Drop 0.12 0.13 0.15 0.14 0.14 0.14 0.14 0.13 0.13 0.14 Max Temperature Rise F 80808080808080808080 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Rec. Flue Size 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
Separated Combustion Indoor Gas Duct Furnaces Model GMND/GMPD
The Trane separated combustion indoor gas duct furnace achieves higher seasonal efficiencies by using outside air for combustion. It overcomes slight negative pressures near exhaust fans or paint booths. The burners, pilot and flue system are totally enclosed within the unit, isolated from dust, humidity and chemicals in the atmosphere.
High Efficiency Centrifugal Fan Gas Unit Heater
GMND/GMPD 010 012 015 017 020 022 025 030 035 040 Input MBh 100.0 125.0 150.0 175.0 200.0 225.0 250.0 300.0 350.0 400.0 Output MBh 80.0 100.0 120.0 140.0 160.0 180.0 200.0 240.0 280.0 320.0 Max CFM 3700 4625 5550 6475 7401 8326 9251 11101 12951 14801 Pressure Drop 2.03 1.92 1.81 1.86 1.90 1.93 1.96 2.00 2.02 2.05 Min. Temperature Rise F 20202020202020202020 Min. CFM 822 1028 1233 1439 1645 1850 2056 2467 2878 3289 Pressure Drop 0.10 0.09 0.09 0.09 0.09 0.09 0.09 0.10 0.10 0.10 Max Temperature Rise F 90909090909090909090 Flue Outlet (1) 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" 5 1/8" Rec. Flue Size 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R Comb Air Inlet 4R4R4R4R5R5R5R60V60V60V Rec. Flue Size 4"R 4"R 4"R 4"R 5"R 5"R 5"R 6"R 6"R 6"R
1. All flue outlets are 5 1/8" O.D. ±1/32" (reducer by installer where required). Increaser supplied by manufacturer for 030,035,040 sizes.
5 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Tubular Heat Exchanger Propeller Fan Unit Heater Model GTND/GTPD
The Trane tubular heat exchanger is a durable unit heater that provides an alternative to the traditional clam shell style. These propeller style units combine the latest tubular heat exchanger technology with in-shot burner design to create an efficient operating unit.
Tubular Heat Exchanger Propeller Gas Unit Heater
GTND/GTPD 003 004 006 007 009 010 012 015 017 020 025 030 035 040 Input MBh 30 45 60 75 90 100 125 150 175 200 250 300 350 400 Output MBh 24.3 36.5 48.6 60.8 72.9 81.0 101.3 121.5 141.8 162.0 202.5 243.0 283.5 324.0 CFM 500 750 1000 1250 1400 1600 2200 2400 2850 3200 3450 5000 5600 5800 Air Temperature Rise F4545454545474247464754454751 Motor Amps 1.9 1.9 2.6 2.6 2.6 4.2 4.7 4.7 5.8 5.8 5.8 9.4 11.6 11.6
UH-TS-1 6
Indirect Fired
A Complete Line of Gas Heating Products
Single Rooftop Gas Duct Furnace Arrangement A Model GFAA/GFBA/GFCA/GFDA
Trane rooftop duct furnaces combine all the features of indoor units with rail mounting and watertight construction. Side access burner drawer and intermittent pilot ignition are standard. Gravity venting is standard; optional power venting is available. Available in double or triple furnace sizes. For outdoor use only. Approved in blow-thru applications only.
Single Rooftop Gas Duct Furnace - Arrangement A
GFAA/GFBA/GFCA/GFDA 10152025303540 Input MBh 100.0 150.0 200.0 250.0 300.0 350.0 400.0 Output MBh 80.0 120.0 160.0 200.0 240.0 280.0 320.0 Max CFM 3704 5556 7407 9259 11111 12963 14815 Pressure Drop 1.10 1.00 1.05 1.08 1.10 1.11 1.12 Min. Temperature Rise 20 20 20 20 20 20 20 Min. CFM 1235 1852 2469 3086 3704 4321 4938 Pressure Drop 0.15 0.15 0.15 0.15 0.15 0.15 0.15 Max. Temperature Rise F 60606060606060
1. Also available in double (500-800 MBh) and triple (1200 MBh) furnace sizes.
2. Above single furnace models also available in a 60-90° temperature rise.
7 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Single, Double and Triple Furnace Indoor Make-Up Air Handlers ­Arrangements B,D,G,K Model GSAA/GSBA
cooling with horizontal discharge. All units are completely packaged, rail mounted, wired, piped, and test fired to assure a smooth installation and
easy start-up. Trane gas fired indoor make-up air handling units are designed for applications requiring heating, cooling, ventilating and make-up air. Unit sizes range from 900-9,800 CFM with gas inputs of 100-1200 MBh. Units are available in four different arrangements: heating only, heating with DX, chilled water or evaporative
Single Furnace Indoor Make-Up Air Handler
GSAA/GSBA 10152025303540 Input MBh 100.0 150.0 200.0 250.0 300.0 350.0 400.0 Output MBh 80.0 120.0 160.0 200.0 240.0 280.0 320.0 Max CFM 900-2400 1400-3600 1800-4900 2300-5500 2700-7400 3200-8600 3700-9800 Max Temperature Rise F80808080808080 Min. Temperature Rise F30303030303030
Double Furnace Indoor Make-Up Air Handler
GSAA/GSBA 50 60 70 80 Input MBh 500.0 600.0 700.0 800.0 Output MBh 400.0 480.0 560.0 640.0 Max CFM 2300-6000 2700-7400 3200-8600 3700-9800 Max Temperature Rise F 160 160 160 160 Min. Temperature Rise F 60 60 60 60
Triple Furnace Indoor Make-Up Air Handler
GSAA/GSBA 12 Input MBh 1200.0 Output MBh 960.0 Max CFM 4500-9800 Max Temperature Rise F 180 Min. Temperature Rise F 90
UH-TS-1 8
Indirect Fired
A Complete Line of Gas Heating Products
Single, Double and Triple Furnace Indoor Make-Up Air Handlers ­Arrangements B,D,G,K Model GXAA/GXBA
cooling with horizontal discharge. All
units are completely packaged, rail
mounted, wired, piped, and test fired
to assure a smooth installation and
easy start-up. Trane gas fired indoor make-up air handling units are designed for applications requiring heating, cooling, ventilating and make-up air. Unit sizes range from 900-9,800 CFM with gas inputs of 100-1200 MBh. Units are available in four different arrangements: heating only, heating with DX, chilled water or evaporative
Single Furnace Indoor Make-Up Air Handler
GXAA/GXBA 10 15 20 25 30 35 40 Input MBh 100.0 150.0 200.0 250.0 300.0 350.0 400.0 Output MBh 80.0 120.0 160.0 200.0 240.0 280.0 320.0 Max CFM 900-2400 1400-3600 1800-4900 2300-5500 2700-7400 3200-8600 3700-9800 Max Temperature Rise F80808080808080 Min. Temperature Rise F30303030303030
Double Furnace Indoor Make-Up Air Handler
GXAA/GXBA 50 60 70 80 Input MBh 500.0 600.0 700.0 800.0 Output MBh 400.0 480.0 560.0 640.0 Max CFM 2300-6000 2700-7400 3200-8600 3700-9800 Max Temperature Rise F 160 160 160 160 Min. Temperature Rise F 60 60 60 60
Triple Furnace Indoor Make-Up Air Handler
GXAA/GXBA 12 Input MBh 1200.0 Output MBh 960.0 Max CFM 4500-9800 Max Temperature Rise F 180 Min. Temperature Rise F 90
9 UH-TS-1
Indirect Fired
A Complete Line of Gas Heating Products
Single, Double and Triple Furnace Rooftops - Arrangements B-L Model GRAA/GRBA/GRCA/GRDA
Trane rooftop heating units are designed for applications requiring heating, cooling, ventilating and make-up air. Unit sizes range from 800-14,000 CFM with gas inputs of
Units are available in eight different
arrangements: heating only, heating
with DX, chilled water or evaporative
cooling with horizontal discharge or
downflow supply. All units are
completely packaged, rail mounted,
wired, piped, waterproofed and test
fired to assure a smooth installation
and easy start-up. 100-1200 Mbh. Units are ETL and CSA
certified for electrical safety in compliance with UL-1995 Standard for HVAC equipment.
Single Furnace - Arrangement B-L
GRAA/GRBA/GRCA/GRDA 10 15 20 25 30 35 40 Input MBh 100.0 150.0 200.0 250.0 300.0 350.0 400.0 Output MBh 80.0 120.0 160.0 200.0 240.0 280.0 320.0 Max CFM 800-3800 1200-4500 1600-7400 2000-7500 3700-11000 2800-13000 3200-14000 Max Temperature Rise F90909090909090 Min. Temperature Rise F20202020202020
Double Furnace - Arrangement B-L
GRAA/GRBA 50 60 70 80 Input MBh 500.0 600.0 700.0 800.0 Output MBh 400.0 480.0 560.0 640.0 Max CFM 3000-7500 3700-11000 4500-13000 5000-13500 Max Temperature Rise F 120 120 120 120 Min. Temperature Rise F 40 40 40 40
Triple Furnace - Arrangement G,J
GRAA/GRBA 12 Input MBh 1200.0 Output MBh 960.0 Max CFM 5500-13000 Max Temperature Rise F 180 Min. Temperature Rise F 60
UH-TS-1 10
Direct Fired
A Complete Line of Gas Heating Products
Direct Fired Outdoor Rooftop Gas Heating Unit Model DFOA
different unit sizes. Special units with
CFM ranges up to 100,000 and
cooling coil capability are also
available. All units are completely Trane’s direct fired outdoor heating
units are designed for relieving negative pressure conditions inside industrial and commercial facilities.
piped, wired, waterproofed and
tested at the factory. All units are built
with UL approved components,
where applicable.
Unit sizes range from 1600-64,000 CFM with gas inputs of 275-7975 MBh. Units are available in horizontal and vertical configurations and in ten
Direct Fired Outdoor Rooftop Gas Heating Unit
DFOA 109 112 115 118 215 218 220 Burner Range MBh 275-550 275-825 550-990 550-1375 825-1925 1100-2475 1650-3850 CFM Range 1600-3000 3250-4250 4500-6000 6500-8500 9000-12000 12500-17000 18000-26000
Continued
DFOA 222 225 230 Burner Range MBh 2200-4400 2475-6600 3850-7975 CFM Range 25000-31000 30000-46000 44000-64000
Direct Fired Indoor Gas Make-Up Air Heater Model DFIA
Direct fired indoor heating units are designed specifically for indoor installations in an industrial or commercial setting. Their modular design provides “mix and match” flexibility that can be used to customize these heaters for any
indoor application. Unit sizes range
from 1600-64,000 CFM with gas
inputs of 275-9075 Mbh. Units are
available in 14 standard models, both
horizontal and vertical configuration.
These units are suitable for floor or
ceiling suspension, with horizontal,
top and downflow discharge
arrangements available. All units are
completely piped, wired and test fired
at the factory.
Direct Fired Indoor Gas Make-Up Air Heater
DFIA 109 112 115 118 120 122 125 130 Burner Range MBh 275-550 275-825 550-990 550-1375 825-1650 990-2200 1375-3025 1925-4400 CFM Range 1600-3000 3250-4250 4500-6000 6500-8500 9000-11000 11000-15000 14000-20000 22000-30000
Continued
DFIA 215 218 220 222 225 230 Burner Range MBh 825-1925 1100-2750 1650-3850 2200-4400 2475-6600 3850-9075 CFM Range 9000-12000 12500-17000 18000-26000 25000-31000 30000-46000 44000-64000
11 UH-TS-1
Tr a n e A business of American Standard Companies www.trane.com
For more information, contact your local Trane office or e-mail us at comfort@trane.com
Literature Order Number UH-TS-1
Date March 2006
Supersedes UH-TS-1-0106
Stocking Location Inland
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.
Loading...