Trane GAM5 Series, GAM5A0C42M31SAA, GAM5A0C48M41SAA, GAM5A0C60M51SAA, GAM5A0A18M11SAA Installer's Manual

...
18-GJ04D1-2
Installer’s Guide
Convertible Air Handlers 1-1/2 – 5 Ton
GAM5A0A18M11SAA GAM5A0A24M21SAA GAM5A0B30M21SAA
GAM5A0C42M31SAA GAM5A0C48M41SAA GAM5A0C60M51SAA
GAM5A0B36M31SAA
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
Important: This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems nor provide for every possible contingency to be met in connection with the installation. Should further informa­tion be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing ONLY A.H.R.I. approved, matched indoor and outdoor systems. Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficien­cy, optimum performance, and the best overall system reliability.
Note: Condensation may occur on the surface of the air handler when installed in an unconditioned space. When units are installed in unconditioned spaces, verify that all electrical and refrigerant line penetrations on the air handler are sealed completely.
The GAM5 air handlers will only use the following internal electric heaters: BAYEAAC05BK1AA BAYEAAC05LG1AA BAYEAAC08BK1AA BAYEAAC08LG1AA BAYEAAC10BK1AA BAYEAAC10LG1AA BAYEABC15BK1AA BAYEABC20BK1AA BAYEACC25BK1AA
Table of Contents
Section 1. Safety Information. ......................................................................... 3
Section 2. Unit Design. ........................................................................................ 4
Section 3. Unit Preparation. ............................................................................. 6
Section 4. Optional Cabinet Disassembly. ............................................... 7
Section 5. Place Unit at Location. ............................................................... 12
Section 6. Unit Location Considerations. ............................................... 13
Section 7. Setting the Unit - Vertical Installation. ................................ 18
Section 8. Setting the Unit - Horizontal Installation. ......................... 20
Section 9. Connecting the Duct work. ...................................................... 21
Section 10. Refrigerant Line. ......................................................................... 22
Section 11. Refrigerant Line Brazing. ....................................................... 23
Section 12. Condensate Drain Piping. ...................................................... 26
Section 13. Electrical - Low Voltage. .......................................................... 28
Section 14. Electrical - High Voltage. ......................................................... 33
Section 15. Time Delay Switch Adjustment. .......................................... 35
Section 16. Filters. ............................................................................................... 35
Section 17. Unit Outline Drawing. ............................................................... 36
Section 18. Start Up. ........................................................................................... 37
Section 19. Sequence of Operation. .......................................................... 39
Section 20. Checkout Procedures. ............................................................. 40
Note: Representative illustrations only included in this document. Most illustrations display the upflow configu­ration.
2
Section 1. Safety Information
WARNING
!
CAUTION
!
WARNING
!
CAUTION
!
CAUTION
!
SAFETY HAZARD! This information is intended for use
by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air condition­ing product may result in personal injury and/or property damage. The manufacturer or seller cannot be responsible for the interpreta­tion of this information, nor can it assume any liability in connection with its use.
LIVE ELECTRICAL COMPONENTS! During instal-
lation, testing, servicing, and troubleshooting of this product, it may be necessary to work with live electrical components. Failure to fol­low all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
HAZARDOUS VAPORS! Do not install an air handler
with a non-ducted return in the same closet, alcove, or utility room as a fossil fuel device. Hazardous vapors can be distributed throughout the conditioned space and equipment damage can result.
CORROSION HAZARD! To prevent shortening its service
life, the air handler should not be used during the finishing phases of construction. The low return air temperatures can lead to the formation of condensate. Condensate in the presence of chlorides and fluorides from paint, varnish, stains, adhesives, cleaning com­pounds, and cement creates a corrosive condition which may cause rapid deterioration of the cabinet and internal components.
SAFETY HAZARD! Sharp Edge Hazard. Be careful of sharp
edges on equipment or any cuts made on sheet metal while install­ing or servicing. Personal injury may result.
Important: Due to the unique design of this unit, which allows the electrical wiring to be routed within the insula­tion, do not screw, cut, or otherwise puncture the unit cabinet in any location other than the ones illustrated in this Installer Guide or in an approved accessory’s In­staller Guide.
Important: Under no conditions should metal strapping be attached to the unit to be used as support mecha­nisms for carrying or suspension purposes.
3
Section 2. Unit Design
Screws can be drilled into bottom of unit. (1/2” max. screw length) (Typical all sides)
Screws, saw cuts, and other penetrations are allowed in the blower section for installation of Side Return Kit. (Typical both sides)
Screws are allowed up to 3- 3/4” from the top of the cabinet (heater compartment). (Typical both sides)
Screws for ange kit attachment are allowed along the interior of the cabinet (see arrows) (Typical all sides)
No penetrations allowed. (Typical all sides)
Screws allowed only in the rst 3/4” of front bottom of unit (in cross member)
2.1 Cabinet Penetration
Important: Due to the unique design of this unit, which allows the electrical wiring to be routed within the insulation, do not screw, cut, or otherwise punc­ture the unit cabinet in any location other than the ones illustrated.
Important: Under no conditions should metal strap­ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes.
2.2 Panel Removal
The unit contains four (4) access panels: Blower/Fil­ter, Coil, Line Set, and Heater.
The Blower/Filter panel is removed using 1/4 turn thumb screws.
1. Turn thumb screws on Blower/Filter panel.
2. Pull top of panel out, away from cabinet.
3. Lift panel up out of channel.
4. Set aside.
4
The Coil, Line Set, and Heater panels are removed using Phillips head screws.
Coil and Heater panels must be removed prior to re­moving the Line Set panel.
To remove Coil Panel:
1. Turn screws on Coil panel.
2. Pull bottom of panel out, away from cabinet.
3. Pull panel down and out of channel.
4. Set aside.
#3 Size Phillips
To remove Heater Panel:
1. Turn screws on Heater panel.
2. Pull panel straight out, away from cabinet.
3. Set aside.
Removal of the Line Set panel is required for all refrig­erant line brazing and some condensate line assembly depending on your orientation.
To remove Line Set panel:
1. Remove both Heater and Coil panels.
2. Turn screws on Line Set Panel.
2. Pull panel straight out, away from cabinet.
3. Set aside.
5
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report promptly to
the carrier any damage found to the unit.
Note: The unit is shipped “upside-down” in the downflow orientation and may be easiest to trans­port to the job site in that orientation. If the unit must be transported in a horizontal position, it must be laid on its back (marked “REAR” on carton).
Note: After the unit is removed from the carton, depress the Schrader valve to verify coil is pressur­ized.
3.2 Unit Accessories
Accessory Number Description Fits Cabinet Size
BAYEAAC05BK1A Electric Heater, 5kW, Breaker, 24V Control, 1 Ph A to C
BAYEAAC05LG1A Electric Heater, 5kW, Lugs, 24V Control, 1 Ph A to C
BAYEAAC08BK1A Electric Heater, 8kW, Breaker, 24V Control, 1 Ph A to C
BAYEAAC08LG1A Electric Heater, 8kW, Lugs, 24V Control, 1 Ph A to C
BAYEAAC10BK1A Electric Heater, 10kW, Breaker, 24V Control, 1 Ph A to C
BAYEAAC10LG1A Electric Heater, 10kW, Lugs, 24V Control, 1 Ph A to C
BAYEABC15BK1A Electric Heater, 15kW, Breaker, 24V Control, 1 Ph B to C
BAYEABC20BK1A Electric Heater, 20kW, Breaker, 24V Control, 1 Ph B to C
BAYEACC25BK1A Electric Heater, 25kW, Breaker, 24V Control, 1 Ph C
BAYSUPFLGA Supply Duct Flange A A
BAYSUPFLGBA Supply Duct Flange B B
BAYSUPFLGCA Supply Duct Flange C C
BAYRETFLGAA Return Duct Flange A A
BAYRETFLGB Return Duct Flange B B
BAYRETFLGCA Return Duct Flange C C
TASB175 Plenum Stand A A
TASB215 Plenum Stand B B
TASB235 Plenum Stand C C
BAYSRKIT100A Side Return Kit A to C
BAYICSKIT01A Internal Condensate Switch Kit A to C
BAYHHKIT001A Horizontal Hanger Kit A to C
BAYUVCLK001A UVC Lights A to C
BAYLVKIT100A Low Voltage Conduit Entry Kit A to C
Table 3.2
6
Section 4. Optional Cabinet Disassembly
4.1 Disassemble cabinet for installation in tight areas or as needed.
Note: The unit is shipped “upside-down” in the downflow orientation and may be easiest to transport to the job site in that orientation. If the unit must be transported in a horizontal position, it must be laid on its back (marked “REAR” on carton).
Note: To reassemble cabinet, follow the steps in reverse order. Ensure electrical connections are secure and the plug clips are engaged.
STEP 1 - Remove all four front panels. See Section
2.2.
Blower Electrical
Connections
7
STEP 2 - Disconnect the two wiring connections routed to the blower assembly.
STEP 3 - Slide Blower assembly out of unit using built-in blower support channels and set aside.
Wiring
Connections
Blower Support
Channel
STEP 4 - Remove airflow diverter from the bottom of
coil drain pan by gripping the plastic diverter, using your thumbs to spread the top of the diverter slightly outwards, and then pulling down and out through the blower opening as illustrated.
Diverter
8
STEP 5 - Disconnect wires to the EEV motor and sensors inside the coil assembly. Cut the wire ties on those wire harnesses.
STEP 6 - Slide Coil assembly out of unit using built­in coil support channels and set aside.
Coil Support
Channel
STEP 7 - Use a 5/16 Allen wrench on the locking
mechanism on each side of the bottom half of the cabinet to loosen the locking mechanism. The locks loosen by turning counter-clockwise approximately 3/4 of a turn.
9
1
2
STEP 8 - Lift the Coil section up and away from the Blower section. Set aside.
10
STEP 9 - For extremely tight spaces where the cabinet needs to be rotated through a small opening, remove the top panel and all cross members. Use a manual driver to avoid stripping screw holes.
Note: Cross Members are removed by rotating them toward the door opening and then lifting up and out of the unit.
2
1
STEP 10 - Continue preparation by following the proper carrying procedures shown in Section 5.
11
Section 5. Place Unit at Location
5.1 Carry Unit
STEP 1 - Carry the unit to the installation location.
STEP 2 - Reassemble by reversing the steps listed in
Section 4 if disassembly was required.
Important: Under no conditions should metal strap­ping be attached to the unit to be used as support mechanisms for carrying or suspension purposes.
Approved carrying:
1. Hold by the cross members within the cabinet or unit top plate and use as handles for lifting and carrying the coil and blower sections.
Cross Member
Unit Top Plate
12
Cross Members
Loading...
+ 28 hidden pages