Trane GSWD, WPWD, EXWA User Manual

Installation Owner Diagnostics
Water-to-Water
Water-Source Heat Pump Models WPWD, GSWD and EXWA
Models
WPWD
024-072 – 60 HZ
GSWD
024-072 – 60 HZ
“A” and later Design Sequence
EXWA
240 – 60 HZ
WSHP-SVX02A-EN
Notice
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
NOTICE:
WARNING -Indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury.
CAUTION -Indicates a potentially hazardous situation which, if
not
avoided, may result in minor or moderate injury. It
may also be used to alert against unsafe practices.
CAUTION -Indicates a situation that may result in equipment or
property-damage-only accidents.
Important!
Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
NOTICE:
Unit contains HCFC (R-22) Refrigerant Instructions! Section 608, Paragraph C of the 1990 Clean Air Act states:
Effective July 1, 1992, it shall be unlawful for any person, in course of maintaining, servicing, repairing, or disposing of an air conditioning system, to knowingly vent or release any CFC or HCFC refrigerant. Minimal releases (air purges or refrigerant hoses) associated with good faith attempts to recapture or recycle are exempt from the ban on venting.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
© 2002 American Standard Inc. WSHP-SVX02A-EN
Contents
Installation/Startup/Commissioning
Pre-installation Checklist General Information Dimensions/Weights Installation Instructions Electrical Requirements Pre-Startup Checklist
Startup/Commissioning
Sequence of Operation Operating Pressures Startup Checklist & Log
Maintenance
4 4
5 6 10 19 20
21 21 22 30
24 25
Warranty Information Troubleshooting Checklist Unit Wiring
WSHP-SVX02A-EN 3
26 28 29
Pre-installation Checklist
WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifica­tions.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com­pleted. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
4. Verify that the refrigerant charge has been retained during shipment by use of gauges. Schrader taps are located external to the cabinet on the 2-ton through 6-ton equipment.
5. After assuring that charge has been retained, reinstall the schrader caps to
assure that refrigerant leakage does not occur.
WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth (mold) on the interior insulation, the insulation should be removed and replaced prior to operating the system.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
1. Place the unit(s) on a dry surface or raise above the ground to assure ade­quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
4. Store units in the normal UP orientation to maintain oil in the compressor.
5. Do not stack more than three units in total height for the WPWD/GSWD 2-ton through 6-ton configurations, and no more than two units high for the EXWA 20-ton configuration.
4 WSHP-SVX02A-EN
General Information
Unit Nameplate
The unit nameplate is located at the front of the unit. It includes the unit model number, serial number, electri­cal characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the compressor shell.
Unit Description
Before shipment, each unit is leak test­ed, dehydrated, charged with refriger­ant and run tested for proper control operation.
Water-to-Refrigerant Coils
The brazed-plate water-to-refrigerant heat exchangers for the 2-ton through 6-ton equipment are constructed of stainless steel.
The water-to-refrigerant heat ex­changers for the 20-ton equipment are an inner copper tube or cupro-nickel
(option available on the source-side only) and steel tube (tube-within-a­tube) design.
Both heat exchanger types are leak tested to assure there is no cross leak­age between the water and refrigerant gas.
Water Connections
One inch brass swivel connections are provided for the 2-ton through 6-ton equipment. Each brass fitting has a one inch gasket for the connector. The gaskets are shipped in the electrical compartment to prevent loss at the job site.
Water connections for the 20-ton are located inside the unit at the units front (source-side) and back (load­side). The fitting consist of a 2-inch fe­male pipe threaded connection.
Controls
The control system offered to control the unit is a Basic 24 volt control for the 2-ton through 6-ton unit sizes, and a deluxe 24 volt micro processing board for the 20-ton unit.
All power wiring to the equipment is made at the unit contactor for the 2-
ton through 6-ton equipment, and at the power block for the 20-ton equip­ment.
All low voltage wiring is made at the unit’s low voltage terminal board.
Wiring Connections
Troubleshooting and connection dia­grams for the equipment may be locat­ed in the back of this manual.
Basic 24V Controls
(for 2-ton through 6-ton units)
Safety devices for equipment contain­ing the basic 24V control option in­clude a low pressure switch and a freezestat to prevent compressor op­eration during low temperature activi­ty. The switch is set to activate at refrigerant pressures of 35 psig or 7 psig to fit most applications.
A high pressure switch prevents com­pressor operation during high or ex­cessive discharge pressures exceeding 395 psig.
The lockout relay communicates the low or high pressure situation to the compressor to prevent operation. The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm may be accomplished through the lockout relay to drive light emitting diodes (LEDs) on a field sup­plied status indicating thermostat. Ter­minal 6 on the lockout relay is open for field use in malfunction indications. This feature will drive dry contacts only, and cannot be used to drive field installed control inputs.
Deluxe 24V Controls
(for 20-ton unit)
Units containing the Deluxe 24V con­trol design will incorporate a micro­processor-based control board. The Trane microprocessor board is factory wired to a terminal strip to provide all necessary terminals for field connec­tion. The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, unit safety con­trol, diagnostics and a generic relay
(which may be available for field use). See page 17 for diagnostic informa­tion. Desuperheater
(Option for 2-ton through 6-ton units)
For units containing the desuperheat­er option, the unit is shipped from the factory with a desuperheater water coil and pump mounted internal to the unit cabinetry. For domestic hot water hook-up instructions, see manual WSHPC-IN-4 or 72-9006-02.
The desuperheater pump fuse is locat­ed in the control box within a contain­er. The fuse is not factory installed to avoid possible pump damage at initial start-up. If the fuse in installed and the unit is started without water in the sys­tem, the pump will be damaged. See page 17 for fuse installation.
Schrader Connections
Connections for the low and high side of the refrigeration system are located conveniently on the unit’s right side for the 2-ton through 6-ton units, and behind the front, refrigeration access panel for the 20-ton unit.
WSHP-SVX02A-EN 5
Table 1: Unit weights
Size
024 163 153 036 183 173 042 203 193 048 214 204 060 244 234 072 277 267 240 1222 1156
Shipping
Weight
with pallet (lb)
w/o pallet (lb)
Shipping
Weight
Dimensions/Weights/ Clearance
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Unit Location and Clearances
Locate the unit in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and technician safety. The unit access panels may be easily re­moved. There must be enough space for service personnel to perform main­tenance or repair. Provide sufficient room to make water, and electrical connection(s). Local and national codes should be followed in providing electrical power connections. See Fig-
ure 1 for mechanical clearances.
Figure 1: Mechanical clearances
6 WSHP-SVX02A-EN
Dimensions
WPWD/GSWD 024-036
WSHP-SVX02A-EN 7
Dimensions
WPWD/GSWD 042-072
8 WSHP-SVX02A-EN
Dimensions
EXWA 240
WSHP-SVX02A-EN 9
Installation
General Installation Checks
The checklist below is a summary of the steps required to successfully in­stall a unit. This checklist is intended to acquaint the installing personnel with procedures required in the installation process. It does not replace the de­tailed instructions called out in the ap­plicable sections of this manual.
1 Remove packaging and inspect the
unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropri­ate sales representation.
Note: The units have been tied to the skid by (4) angle brackets. Re­move these brackets from the unit to slide unit from skid.
2 Verify the correct model, options
and voltage from the unit name­plate.
3 Verify the installation location of
the unit will provide the required clearance for proper operation.
4 Remove refrigeration access panel
and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Main Electrical
5 Verify the power supply complies
with the unit nameplate specifica­tions.
6 Inspect all control panel compo-
nents; tighten any loose connec­tions.
7 Connect properly sized and pro-
tected power supply wiring to a field-supplied/installed disconnect switch and to the main power ter­minal block (1TB1) in the unit con­trol box for the 20-ton equipment, or (1K1) for the 2-ton through 6­ton equipment.
8 Install proper grounding wires to
an earth ground.
Note: All field-installed wiring must comply with NEC and applicable local codes.
Low Voltage Wiring (AC & DC) Requirements
9 Connect properly sized control wir-
ing to the proper termination points between the field supplied thermostat and the terminal strip located in the equipment control box.
10 WSHP-SVX02A-EN
Installation
Figure 2: Racking installation
WARNING Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Unit Placement
Units may be placed into a field sup­plied mechanical rack (See Figure 2), or placed on a finished floor. Loosen compressor bolts to release tension of the rubber grommets to help reduce vibration during operation. Sound proofing material (field supplied) is recommended to help attenuate noise generated by compressor vibration.
It is important to leave appropriate clearances around the unit to achieve
maintenance and serviceability to the equipment. See page 6 for service clearance dimensions.
Water Connection
Connect the source-side and load-side water-in/water-out from the water-to­water heat pump to the source system and the load system.
Note: The source for a water-to-water
heat pump is typically a boiler/cooling tower or geothermal loop.
The load for a water-to-water heat pump is typically fresh-air unit(s), fan coil(s), hydronic coil(s), radiant heat, wall fin, or potable water.
The source and load connections for the 2-ton through 6-ton equipment is on the right hand side of the unit.
The 20-ton equipment incorporates the source-side connection at the unit’s front, and the load-side connec­tion at the unit’s back.
For vibration isolation, it is recom­mended that flexible steel braided hoses be installed instead of hard pip­ing the equipment to the main loop system or mechanical device.
Trane offers 4-types of hose kit varia­tions:
• Stainless steel braided flexible hose with manual shut-off (ball) valves
• Stainless steel braided flexible hose with manual deluxe shut-off (ball) valves
• Stainless steel braided flexible hose with manual circuit-setter valve
• Stainless steel braided flexible hose with automatic balancing valve
Additional accessories, such as a strainer are recommended for use to eliminate contaminants from entering the brazed-plate or co-axial water-to­refrigerant heat exchangers.
Figure 3: Water connection
WSHP-SVX02A-EN 11
Installation
Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). Fig- ure 4. An extra pipe may be necessary to connect the hose kits. See Page 14 for antifreeze/water mixture by vol­ume.
(1) Water circulation system should be filled with clean water using the water make up connections. Note: Air vents should be opened during filling.
(2) With the air vents closed, start the circulating pump and then crack the air vents to bleed off the trapped air, as­suring circulation through all compo­nents of the system.
Note: Make up water must be available to the system to replace the volume formerly occupied by the air that is
Connecting a Loop Pump Kit Closed Loop System
All piping external to the unit is the re­sponsibility of the installer. The water pipe installation must be done in ac­cordance with local codes. If no local code applies, national codes should be followed. It is the contractor’s respon­sibility to know and adhere to all appli­cable codes.
Water inlet and outlet to the unit’s wa­ter-to-refrigerant heat exchanger are clearly marked on the submittal draw­ings found on pages 7 through 9. The supply and return piping must be in­stalled correctly to the unit to ensure the safety devices will work properly. Units that are not piped accordingly will not obtain the manufacturers war­ranty.
A pump module (Figure 5) and hose kit (Figure 6) are typically used to connect the unit to closed loop piping in do­mestic applications.
bled off.
(3) With the air vented and the water circulating, the entire system should be checked for leaks with re­pairs made as required. (4) Operate the supplementary heat system making checks per manufacturer’s instructions. Dur­ing this operation, visual checks should be made for leaks that may have occurred due to increased heat. Repair as required.
(5) Open the system at the lowest point for the initial blow down (making sure the make up water is equal to the water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 hours.
(6) Shut down pumps and supplemen­tary heat system. Reconnect the hoses placing the water-to-refrigerant heat exchanger in the water circulating sys­tem.
FROM UNIT’S
W.O.
TO UNIT’S
W.I.
BRONZE OR CAST IRON PUMP
PURGING CAP (2)
SHUT-OFF 3-WAY VALVE (2)
Figure 5 Pump module
1" MPT x BARB FITTINGS, 1" MPT x BARB ELBOWS with PRESSURE TEMPERATURE PORTS, AND 10’ OF RUBBER HOSE with 4 HOSE CLAMPS.
Note: Vents should be open when the pumps and supplementary heat sys-
tem are shut down.
Figure 4: Flushing water loop
Figure 6: Hose kit
12 WSHP-SVX02A-EN
Installation
Figure 7: Loop pump kit installation
Supply/Return Pipe Connections to the Loop Pump Kit (1) Connect the supply and return hos-
es to the water-inlet (from supply) and water-outlet (to return) of the unit. The
rubber gaskets for the water-in and water-out connections are located in the control box. These gaskets require field installation prior to connecting the water piping to the unit.
(2) Hand tighten the 1" FPT brass swiv­el quick connections to the 1" MPT adapter with P/T ports. Using a wrench, tighten the adapter approxi­mately 1/2 additional turn. Care must
be taken to avoid overtightening as to not dislodge the snap ring.
(3) The water lines should be routed not to interfere with access to the unit. The use of a short length of high pres­sure hose with the swivel fitting may simplify the connections and prevent vibration. Pressure/Temperature (P/T) ports are required for troubleshooting the hydronic side of the unit. Extreme
care should be taken by the installing contractor to prevent dirt or other for­eign matter from entering the pipes or piping components during construc­tion. Pipes should be capped until they are in place and ready to be connected to the system.
(4) Install the Trane loop pump mod­ule. See installation manual WSHPC­IN-5 or 72-9006-03 for instructions. If the unit does not contain a Trane loop pump module, two ball valves must be installed between the unit and the loop’s water pump to isolate the unit from the system’s water loop during maintenance and emergency situa­tions. See Figure 7.
If the unit s contain a Trane loop pump module, shut-off valves are supplied by the manufacturer within the pump module assembly.
(5) Connect the unit’s water-in and wa­ter-out hose to the loop pump module.
(6) The pumps connect to the load side 230 volt compressor contactor, and re­quire a field installed 6 amp in-line fuse and holder.
(7) Insulate all indoor piping. Equip­ment is designed to operate with fluid temperature of 25ºF to 120ºF
WSHP-SVX02A-EN 13
Water Heater Hook-up (option)
Instructions for connection from the desuperheater (option) water-in/out to the domestic hot water heater may be found in WSHPC-IN-4 or 72-9006-02. This water heater kit (Figure 8) ships in all units with the desuperheater op­tion. The kit is zip tied to the compres­sor base; and consists of piping connections and shut-off valve.
For units containing the desuperheat­er option, the desuperheater pump fuse is located within a container in­side of the control box. The fuse is not factory installed.
Note: If the fuse is installed, and the unit is started without water in the sys­tem, pump damage may occur.
Using Antifreeze
In areas of the country where entering water temperatures drop below 45°F or where piping is being run through areas subject to freezing, the loop must be freeze protected by using an approved antifreeze solution to pre­vent the earth loop water from freez­ing inside the heat exchanger. Methanol and glycols are the most commonly used antifreeze solutions. Consult your geothermal unit supplier for locally approved solutions in your area.
Propylene glycol is not recommended in installations where the water tem­perature are expected to fall below 30°F. At extreme temperatures, the viscosity increases to the point where normal loop circulating pumps may not maintain proper flow.
If propylene glycol is the only locally approved solution for anti-freeze, good engineering practices should be used to achieve the desired flow.
Calculate the approximate volume of water in the system by using the re­quirements detailed in Table 2. Add three gallons to this total to allow for the water contained in the hose kit and geothermal unit.
Installation
Figure 8: Water heater kit
Table 2: Antifreeze requirements based on volume
Type of Antifreeze
Methanol 25% 21% 16% 10% 3%
Propylene Glycol - - - - 6%
Minimum Temperature for Freeze Protection
10°F 15°F 20°F 25°F 30°F
14 WSHP-SVX02A-EN
Filling the Loop Pump Kit System
Once the loop, pump module and unit are fully connected, the system will need to be filled with water or water/ antifreeze solution. See Page 14 for an­tifreeze/water mixture by volume.
Fill both sides of the outside portion of the loop first via the pump module. The hose kit and unit should be filled last after purging of the ground loop is complete.
To fill the outside loop; (1) attach a water hose to the 1-inch FPT brass valve ports located on the front of the pump module (the caps at the front of the module should be removed). (2) Rotate both valve 1 and valve 2 to the "Position B" to prevent water from go­ing to the unit. (3) Turn on the water and allow the earth loop to slowly fill with water. (4) Run the water until a steady flow of water without air bub­bles is observed coming out of the dis­charge hose.
To fill the hose kit and unit; (1) Re- position valve 1 to the "Position A" to fill the unit and hose kit. (2) Turn the water on and allow the hose kit and unit to be filled slowly with water. (3) Run the water until a steady flow of water without air bubbles is observed coming out of the discharge hose.
System Pressurization (1) Rotate both valves 1 and 2 to the
"Position D" to pressurize the system. (2) Examine all internal unit fittings or connections for leaks. (3) After check­ing for leaks, the system is ready to be flushed.
Note: There may be a certain amount of entrained air left in the loop system.
Cleaning and Flushing the Water Loop
All installations must be thoroughly flushed to remove air and dirt from the earth loop before running the system. The pumps used in the pump module are not adequate to use for the flush­ing out of the unit. A secondary pump capable of delivering 50 gpm at 60 feet of head (a 1 1/2 hp or larger pump) is
Installation
Filling the Hose Kit and Unit and/or
Hose Kit and Unit Flush
Run System Full System Flush
normally suitable for jobs up to six tons. The loop must be flushed with a high volume of water at a minimum velocity of (2 feet per second) in both directions. See Table 3 for flow rates required to flush earth loops. Table 3: System flushing flow rates
Pipe
3/4" PE 3.02 3.8
1" PE 4.73 6.0 1 1/4" PE 7.55 9.5 1 1/2" PE 9.93 13.0
2" PE 15.36 21.0
Gallons per
100 Ft.
Minimum
Flush GPM
Filling the Outside Loop and/or
Outside Loop Flush
Note: The plastic 1-inch MPT valve plugs must be replaced after filling and/or flushing is completed.
See "Position C" for valve rotation to place the valves in RUN position.
WSHP-SVX02A-EN 15
Installation Power Wiring
Field Installed Power Wiring
Power wiring to the equipment must conform to National and Local Electric Codes (NEC) by a professional electri­cian.
WARNING
Live Electrical Components!
During installation, testing, ser­vicing and troubleshooting of this product, it may be necessary to work with live electrical compo­nents. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical compo­nents perform these tasks. Failure to follow all electrical safety pre­cautions when exposed to live electrical components could re­sult in death or serious injury.
Verify that the power supply available is compatible with the unit’s name­plate. Use only copper conductors to connect the power supply to the unit.
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conduc­tors. Failure to use copper con­ductors may result in equipment damage.
The high voltage connection is made at the 1TB1 terminal block for the 20­ton equipment, and at 1K1 for the 2­ton through 6-ton equipment. The ter­minal block or contactor is located in­side the unit control box. Refer to the customer connection diagram that is shipped with the unit for specific ter­mination points.
Provide proper grounding for the unit in accordance with the local and na­tional codes.
Control Power Transformer
The 24-volt control power transform­ers are to be used only with the acces­sories called out in this manual. Transformers rated greater than 50 VA are equipped with internal circuit breakers. If a circuit breaker trips, turn OFF all power to the unit before at­tempting to reset it.
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects be­fore servicing. Follow proper lockout/tagout procedures to en­sure the power can not be inad­vertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
The transformer is located in the control box.
Main Unit Power Wiring
A field supplied disconnect switch must be installed at or near the unit in accordance with the National Electric Code (NEC latest edition).
Location of the applicable electric ser­vice entrance for HIGH (line voltage) may be found on the unit submittal at the front of this manual (pages 7 through 9).
16 WSHP-SVX02A-EN
Controls Using 24 VAC
Before installing any wire, refer to the electrical access locations on the unit submittals located on pages 7 through
9. Ensure that the AC control wiring be-
tween the controls and the unit’s ter­mination point does not exceed three (3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3-ohms per conductor may cause component failure due to insufficient AC voltage supply.
Check all loads and conductors for grounds, shorts, and mis-wiring.
Use copper conductors unless other­wise specified.
Do not run the AC low voltage wiring in the same conduit with the high volt­age power wiring.
Table 4: 24V AC conductors
Distance
from unit to Control
000-460 feet 18 gauge 461-732 feet 16 gauge
733-1000 feet 14 gauge
Recommended
Wire Size
Installation Low Voltage Wiring
Figure 9: Low voltage connection
Low voltage connection diagrams are shown in Figure 9. Optional desuper­heater fuse installation shown in Fig-
ure 10.
Figure 10: Desuperheater fuse installation
Table 5: Deluxe controller diagnostic LEDs
Color: Green Color: Red
LED1 LED2 LED3
OFF OFF OFF Control OFF
ON OFF OFF Normal/Compressor OFF ON OFF FLASH Anti-short Cycle ON OFF ON Normal/Compressor ON
FLASH ON OFF Brownout Condition
ON FLASH ON Soft Lockout (low pressure) ON FLASH FLASH Soft Lockout (high pressure) ON ON ON Manual Lockout (low pressure) ON ON FLASH Manual Lockout (high pressure) ON FLASH OFF Manual Lockout (condensate overflow) ON ON OFF Compressor Disable
WSHP-SVX02A-EN 17
Controller Mode
Installation
Changing Freezestat or Low Pres­sure Cutout Switches
(WPWD/GSWD models ONLY)
Each unit has two factory installed low pressure cutout switches and one freezestat. Only one of the low pres­sure cutout switches is connected to the 24 volt control circuit, dependent on which freezestat is being used (i.e. 35°F or 20°F). Both the freezestat and the low pressure cutout are in the lock­out relay circuit. The freezestat moni­tors the temperature of the water leaving the source and load side wa­ter-to-refrigerant heat exchangers, protecting the heat exchanger from fluid freeze up. The low pressure cut­out monitors the suction pressure of the compressor to protect the com­pressor from liquid floodback or oper­ating under loss of charge conditions.
Units can be ordered from the factory with either the 35°F or 20°F freezestat option. The 20°F freezestat is ONLY used on closed loop systems with an­tifreeze solution. The 35°F freezestat is used on all other systems. The type of freezestat on a unit can be determined from the appropriate digit in the model number. Digit 11 and/or 12 with a se­lection of 1 is a 35°F freezestat, where­as selection 2 is a 20°F freezestat.
What Freezestat Should Be Applied?
As previously mentioned, every unit is shipped from the factory with two low pressure cutouts installed in the refrig­erant circuit. One of the low pressure cutouts disables the compressor at 35 psig, while the other disables the com­pressor at 7 psig. The 35 psig cutout is used with the 35°F freezestat, while the 7 psig cutout is used with the 20°F freezestat. Occasionally it will be necessary to change the freezestat in the field. Ex­amples of when this change-out is necessary include:
(1) A unit with a 35°F freezestat is go­ing to be put on a closed loop system with antifreeze. By definition, the unit requires a 20°F freezestat.
(2) A unit with a 20°F freezestat is go­ing to be put on an open well system or a closed loop system with NO anti­freeze solution. By definition, the unit must have a 35°F freezestat installed prior to operation.
The best time to install the freezestat/ low pressure cutout is prior to install­ing the unit. The freezestat is easily ac­cessible from the top service door.
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects be­fore servicing. Follow proper lockout/tagout procedures to en­sure the power can not be inad­vertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
Changing a Freezestat and Low Pressure Cutout
The freezestat is located in the top of the source-side water-to-refrigerant heat exchanger leaving water line. The freezestat is located in the twelve o’clock position. The capillary tube is inserted into the well approximately 8­inches. Remove the existing freezestat and replace it with the new freezestat.
Note: The wires must be moved from one low pressure cutout to the other.
The low pres­sure cutouts are located in the insu-
lated re­frigerant lines. The high
pressure cutout is locat­ed in the un-insulated compressor dis­charge line and is the only pressure cutout located in this line. Change the wires from
the old low pressure cutout to the new low pressure cutout.
Identifying the Low Pressure Cutouts The 7 psig low pressure cutout is used with a 20°F freezestat. It is installed in the insulated line and is in the piping tee going to the external schrader port. The 35 psig low pressure cutout is used with a 35°F freezestat. It is in­stalled in the insulated line and is not connected to any fittings.
The 395 psig high press cutout is in­stalled in the un-insulated compressor discharge line. It is the only cutout lo­cated in this line. Further, it is connect­ed to an external schrader port.
If the low pressure cutout is not changed when the freezestat is changed, problems will occur. If the 35 psig low pressure cutout is connected to a 20°F freezestat, the unit will go out repeatedly on the low pressure cutout. If the 7 psig low pressure cutout is used with the 35°F freezestat, no prob­lems will occur as long as the freez­estat is operating normally. However, if the freezestat does fail, the loop wa­ter could freeze before the suction pressure dropped low enough for the 7 psig cutout to take the unit off the line. Also, in a loss of charge situation, the heat exchanger would freeze be­fore the freezestat could take the unit off-line.
Figure 11: Pressure switch location
18 WSHP-SVX02A-EN
Electrical Requirements
Table E-1: Electrical performance WPWD/EXWA
Model/MBH VOLTS-AC/HZ/PH Min.
Util. Volt
WPWD024 208-230/60/1 197 253 11.4 56.0 1 14.3 25 0.4 14.7 25
220-240/50/1 198 264 9.6 47.0 1 12.0 20 0.4 12.4 20
265/60/1 239 292 9.6 47.0 1 12.0 20 0.4 12.4 20
WPWD036 208-230/60/1 197 253 15.0 73.0 1 18.8 30 0.4 19.2 30
208-230/60/3 197 253 10.7 63.0 1 13.4 20 0.4 13.8 20 220-240/50/1 198 264 14.3 71.0 1 17.9 30 0.4 18.3 30
265/60/1 239 292 14.3 71.0 1 17.9 30 0.4 18.3 30
380-415/50/3 342 456 5.0 31.0 1 6.3 15.0 0.4 6.7 15.0
460/60/3 414 506 5.0 31.0 1 6.3 15 0.4 6.7 15
WPWD042 208-230/60/1 197 253 18.4 95.0 1 23.0 40 0.4 23.4 40
208-230/60/3 197 253 11.4 77.0 1 14.3 25 0.4 14.7 25 220-240/50/1 198 264 16.4 83.0 1 20.5 35 0.4 20.9 35
265/60/1 239 292 16.4 83.0 1 20.5 35 0.4 20.9 35
380-415/50/3 342 456 5.7 39.0 1 7.1 15.0 0.4 7.5 15.0
460/60/3 414 506 5.7 39.0 1 7.1 15 0.4 7.5 15
WPWD048 208-230/60/1 197 253 20.4 109.0 1 25.5 45 0.4 25.9 45
208-230/60/3 197 253 13.9 88.0 1 17.4 30 0.4 17.8 30 380-415/50/3 342 456 7.1 44.0 1 8.9 15.0 0.4 9.3 15.0
460/60/3 414 506 7.1 44.0 1 8.9 15 0.4 9.3 15
WPWD060 208-230/60/1 197 253 28.0 169.0 1 35.0 60 0.4 35.4 60
208-230/60/3 197 253 20.0 123.0 1 25.0 45 0.4 25.4 45 380-415/50/3 342 456 7.5 49.5 1 9.4 15.0 0.4 9.8 15.0
460/60/3 414 506 7.5 49.5 1 9.4 15 0.4 9.8 15 575/60/3 517 633 6.4 40.0 1 8.0 15 0.4 8.4 15
WPWD072 208-230/60/1 197 253 32.1 169.0 1 40.1 70 0.4 40.5 70
208-230/60/3 197 253 19.3 137.0 1 24.1 40 0.4 24.5 40 380-415/50/3 342 456 10.0 62.0 1 12.5 20.0 0.4 12.9 20.0
460/60/3 414 506 10.0 62.0 1 12.5 20 0.4 12.9 20
575/60/3 517 633 7.8 50.0 1 9.8 15 0.4 10.2 15 EXWA180 380-415/50/3 342 456 16.7 133.0 2 37.58 50 -- -- -­EXWA240 208/60/3 197 229 31.7 232.0 2 71.39 100 -- -- --
230/60/3 207 253 31.7 261.0 2 71.39 100 -- -- --
460/60/3 414 506 14.1 112.0 2 31.73 45 -- -- --
575/60/3 518 633 11.2 92.0 2 25.24 35 -- -- --
Table E-2: Electrical performance GSWD
Model/MBH VOLTS-AC/HZ/PH Min.
GSWD024 208-230/60/1 197 253 11.4 56.0 1 2.5 0.4 17.2 25 GSWD036 208-230/60/1 197 253 15.0 73.0 1 2.5 0.4 21.7 35 GSWD042 208-230/60/1 197 253 18.4 95.0 1 2.5 0.4 25.9 40 GSWD048 208-230/60/1 197 253 20.4 109.0 1 2.5 0.4 28.4 45 GSWD060 208-230/60/1 197 253 28.0 169.0 1 2.5 0.4 37.9 60 GSWD072 208-230/60/1 197 253 32.1 169.0 1 2.5 0.4 43.0 70
Util. Volt
Max
Util.
Volt
Max Util. Volt
Compressor
Each
RLA
Compressor
Data
LRA No.
of
Comp
No.
of
Comp
Without Desup With Desup
MCA Max
Aux Pump Amps
Pump
RLA
Fuse
Desup
MCA Max
Desup
RLA
MCA Max
FuseRLA LRA
Fuse
WSHP-SVX02A-EN 19
Pre-Start Checklist
Pre-Start-up Checklist
Before energizing the unit, the following system devices must be checked:
____ Is the high voltage power supply correct and in accordance with the nameplate ratings? ____ Is the field wiring and circuit protection the correct size? ____ Is the low voltage control circuit wiring correct per the unit wiring diagram? ____ Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from the water-
to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accor­dance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
____ Is vibration isolation provided? (i.e. unit isolation pad, hosekits) ____ Is unit serviceable? (See clearance specifications on page 6). ____ Are the low/high-side pressure temperature caps secure and in place? ____ Are all the unit access panels secure and in place? ____ Is the thermostat in the OFF position? ____ Is the water flow established and circulating through all the units? ____ Is the zone sensor correctly wired and in a good location? ____ Has all work been done in accordance with applicable local and national codes? ____ Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?
20 WSHP-SVX02A-EN
Sequence of Operation
Initial Unit Start-up
Start-up with the system controls is included below: Note: Air Handlers should not be operated in the construction phase of dry walling. The air-to-refrigerant coil will foul, and the warranty will be void.
1.Set the system control to the desired mode of operation.
2.Set the control switch to fans and circulation pumps. The compressor should NOT run.
3.Reduce the temperature control setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/temperature plugs and comparing to tables contained in specification
sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9°F-12°F); compressor amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
4.Check the cooling refrigerant pressures against values in Table OP1. (Page 22).
5.Turn the system control switch to the OFF position. Unit should stop running and the reversing valve should de-ener-
gize.
6.Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7.Turn the thermostat to the lowest setting.
8.Set the thermostat system switch to the opposite mode of operation.
9.Adjust the temperature setting upward until the unit is energized. A water temperature decrease of approximately 5°F-
9°F leaving the heat exchanger should be noted. The compressor operation should be smooth with no frost observed in the refrigeration circuit.
10.Check the heating refrigerant pressures against values in Table OP1. (Page 22)
11.Set the system control to maintain the desired space temperature.
12.Instruct the owner on system operation.
WSHP-SVX02A-EN 21
Operating Pressures
Operating Pressures
Table OP-1: Cooling mode operating pressures
Unit Size Entering
Load
(Degree F)
EXWA 240 53.6 46-56 103-143 49-59 188-228 49-59 238-278 EXWA 240 86 61-71 111-151 84-94 205-245 87-97 259-299
Table OP-2: Heating mode operating pressures
Unit Size Entering
Load
(Degree F)
EXWA 240 75 46-56 160-200 65-75 170-210 86-96 183-223 EXWA 240 104 49-59 245-285 68-78 254-294 94-107 268-308 EXWA 240 122 49-59 310-350 68-78 320-360 95-105 333-373
Suction
Pressure
Suction
Pressure
Entering Source Temperature (Degree F)
50 86 104
Discharge
Pressure
Entering Source Temperature (Degree F)
50 68 104
Discharge
Pressure
Suction
Pressure
Suction
Pressure
Discharge
Pressure
Discharge
Pressure
Suction
Pressure
Suction
Pressure
Discharge
Pressure
Discharge
Pressure
22 WSHP-SVX02A-EN
Operating Pressures
Water Pressure Drop
Tables 6 and 7 should be used to define feet of head/pressure drop. Note: To calculate feet of head, when using gauges that read in PSIG, multiply PSI by 2.31.
Table 6: Cooling water pressure drops (WPD) in feet of head
Unit Size
024
036
042
048
060
072
240
GPM
3.8
7.0 4.5 5.4
8.9 7.2 8.7
4.6
8.5 6.6 7.9
10.8 10.6 12.7
5.2
9.5 8.6 10.3
12.1 14.1 17.1
6.0
11.0 11.6 14.0
14.0 19.1 23.1
7.6
14.0 19.1 23.1
17.8 31.5 38.1
8.7
16.0 25.3 30.5
20.4 41.8 50.5
30.0
55.0 8.1 9.7
70.0 12.2 14.7
Source Load
EWTFFt. Head
Pressure
1.3
80
1.9
80
2.4
80
3.3
80
5.4
80
7.1
80
2.9
80
EWTFFt. Head
Pressure
1.6
53.6
2.3
53.6
3.0
53.6
4.0
53.6
6.5
53.6
8.6
53.6
3.6
53.6
Table 7: Heating water pressure drops (WPD) in feet of head
Unit Size
024
036
042
048
060
072
240
GPM
3.8
7.0 5.1 4.5
8.9 8.3 7.2
4.6
8.5 7.6 6.6
10.8 12.2 10.6
5.2
9.5 9.8 8.6
12.1 16.2 14.1
6.0
11.0 13.3 11.6
14.0 21.9 19.1
7.6
14.0 21.9 19.1
17.8 36.1 31.5
8.7
16.0 28.9 25.3
20.4 47.9 41.8
30.0
55.0 9.2 8.1
70.0 13.9 12.2
Source Load
EWTFFt. Head
Pressure
1.5
60
2.2
60
2.8
60
3.8
60
6.2
60
8.2
60
3.4
60
EWTFFt. Head
Pressure
1.3
80
1.9
80
2.4
80
3.3
80
5.4
80
7.1
80
2.9
80
Water Volume
Table 8 is provided for use in calculating glycol requirements for the unit.
Table 8: Water volume
Unit Size
024 55 0.032 0.238 036 105 0.061 0.455 042 105 0.061 0.455 048 259 0.150 1.121 060 259 0.150 1.121 072 259 0.150 1.121 240 1057 0.615 4.576
Water Side
Volume
Cubic In.
Water Side
Volume
Cubic Ft.
Water Side
Volume Gallons
Note: The EXWA 240 has two circuits.
Flow Checks
For the operating temperature drop (heating) and rise (cooling), refer to Table OP1 and OP2 for the proper water tempera­ture change. Depending on the unit size, entering water temperature and water flow rate, the cooling temperature rise is from 8°F-16°F. Based on the same criteria for heating, the temperature drop is from 2°F-13°F.
Pressure
Using the P/T ports and one 0-60 psi pressure gauge with the P/T port adapter, measure the pressure difference between the water-in and water-out connections. Compare the pressure differential to Table 6 to determine flow.
Start-up Checklist and Log
Use the form on page 24 to log system and unit temperatures during start-up.
WSHP-SVX02A-EN 23
Start-up Checklist and Log
Installing Contractor: Use this form to thoroughly check-out the system and units before and during
start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name: Model Number: Date: Serial Number:
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
MODE
Entering fluid temperature Leaving fluid temperature Temperature differential Water coil heat exchanger
(Water Pressure IN) Water coil heat exchanger
(Water Pressure OUT) Pressure Differential
COMPRESSOR
HEAT
Source Source
F F F
F F
PSIG PSIG
PSIG PSIG
PSIG PSIG
Load Load
F F F F
F F
PSIG PSIG
PSIG PSIG
PSIG PSIG
COOL
F
Amps Volts Discharge line temperature
F F
F F
(after 10 minutes)
24 WSHP-SVX02A-EN
Maintenance
Preventive Maintenance
Maintenance on the unit is simplified with the following preventive sugges­tions:
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects be­fore servicing. Follow proper lockout/tagout procedures to en­sure the power can not be inad­vertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
Check the contactors and relays within the control panel at least once a year. It is good practice to check the tight­ness of the various wiring connections within the control panel.
A strainer (60 mesh or greater) must be used on an open loop system to keep debris from entering the unit heat exchanger and to ensure a clean sys­tem.
For units on well water, it is important to check the cleanliness of the water­to-refrigerant heat exchanger. Should it become contaminated with dirt and scaling as a result of bad water, the heat exchanger will have to be back flushed and cleaned with a chemical that will remove the scale. This service should be performed by an experi­enced service person.
WARNING
Hazardous Chemicals!
Coil cleaning agents can be either acidic or highly alkaline. Handle chemical carefully. Proper han­dling should include goggles or face shield, chemical resistant gloves, boots, apron or suit as re­quired. For personal safety, refer to the cleaning agent manufactur­ers Materials Safety Data Sheet and follow all recommended safe handling practices. Failure to fol­low all safety instructions could result in death or serious injury.
It should be noted that the water qual­ity should be checked periodically. See
Table 9.
Table 9: Water Quality Table
Scaling
Calcium and magnesium (total hardness)
Corrosion
pH 7-9.5 Hydrogen Sulfide Less than 1 ppm Sulfates Less than 25 ppm Chlorides Less than 125 ppm Carbon Dioxide Less than 75 ppm Total dissolved solids
(TDS)
Biological Growth
Iron Bacteria Low
Erosion
Suspended Solids
Less than 350 ppm
Less than 1000 ppm
Low
WSHP-SVX02A-EN 25
Warranty Information
Warranty Information
Standard Warranty
The standard water-source heat pump warranty is Trane’s parts-only warranty, running 12-months from star­tup, not to exceed 18-months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard 1-year coverage through the fifth year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start-up.
26 WSHP-SVX02A-EN
Troubleshooting
WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures recommend­ed in this section of the manual could result in exposure to electri­cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern­ing these procedures. When possi­ble, disconnect all electrical power including remote discon­nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in­advertently energized. When nec­essary to work with live electrical components, have a qualified li­censed electrician or other indi­vidual who has been trained in handling live electrical compo­nents per these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
Preliminary Trouble Inspection
If operational difficulties are encoun­tered, be sure to perform the prelimi­nary checks before referring to the troubleshooting chart on page 28.
• Verify that the unit is receiving elec­tric supply power.
• Ensure that the fuses in the fused
disconnect are intact.
After completing the preliminary checks, inspect the unit for other obvi­ous problems such as leaking connec­tion, broken or disconnected wires, etc. If everything appears to be in or­der, but the unit still fails to operate properly, refer to the troubleshooting chart on page 28.
General Operation
The standard model is designed for in­door installation. When the unit is in­stalled in an unconditioned space, the unit may not start in cool weather (ap­proximately 45°F). It may then be nec­essary to start the unit in the cooling mode for three to five minutes. The unit may then be shut-off (there will be a two minute time-out of the unit), and restarted in the heating mode. The freeze protection thermostat should also be checked as it may be adversely affected by ambient temperature. Like any other type of mechanical equipment, the unit performs best when it is well maintained.
Operation with a Conventional Thermostat
The unit is equipped with safety con­trols, including high pressure control, low pressure control and a freeze pro­tection thermostat, set to shut off the compressor under abnormal tempera­ture or pressure conditions. If the safe­ties shut off the compressor, a lockout relay prevents short cycling from the abnormal condition. When conditions are corrected, the lockout control can be reset by setting the thermostat sys­tem switch to OFF wait a few minutes for the system pressure to equalize, and then return to HEAT or COOL. If the condition continues, an authorized service person should check out the unit.
WSHP-SVX02A-EN 27
Troubleshooting Checklist
Problem Heating Cooling Cause Correction
X X Main power off Check fuses
No response to any thermostat setting
Unit short cycles X X Thermostat or sensor improperly located Relocate
Insufficient capacity
High pressure switch open
High head pressure
Low suction pressure
Low Pressure switch open
Freezestat open
X X Defective control transformer Replace X X Broken or loose connection Repair X X Defective thermostat Replace X X Transformer Reset Transformer
X X Low on refrigerant charge X X Restricted thermal expansion valve Replace
X X Defective reversing valve See WSHP-IOM-# for touch test chart X X Thermostat improperly located Relocate X X Unit undersized Recalculate heat gains/losses X X Inadequate water flow Increase GPM X X Scaling in heat exchanger Clean or replace
X Water too hot Decrease temperature
X Water too cold Increase temperature
X Inadequate GPM Increase water flow to unit
X Water too hot Decrease temperature X X Overcharged with refrigerant Decrease charge X X Defective pressure switch Check or replace
X Trash in heat exchanger Backflush
X Low water flow Increase GPM X X Overcharge of refrigerant Decrease charge X X Non-condensable in system Evacuate and recharge by weight X X Water too hot Decrease temperature X X Undercharged Locate leak, repair and recharge X X Restricted thermal expansion valve Repair / replace X Inadequate GPM Increase GPM X Inadequate GPM Increase GPM X Water too cold Increase temperature X X Undercharged with refrigerant Increase charge X X Defective pressure switch Replace
X X Heat transfer fluid too cold
X Inadequate GPM Increase GPM X Water too cold Increase GPM X X Defective freezestat Replace freezestat
X Heat transfer fluid too cold
Locate leak, repair and recharge by weight (not by superheat)
Raise water temperature. For smaller tonnage units, switch pressure switch wires from 35 psig to 7 psig
Replace freezestat. For smaller tonnage units, switch pressure wires from 35 psig to 7 psig.
28 WSHP-SVX02A-EN
Unit Wiring 2-ton through 6-Ton Equipment
WSHP-SVX02A-EN 29
Unit Wiring 20-Ton Equipment
30 WSHP-SVX02A-EN
Trane An American Standard Company www.trane.com
Literature Order Number WSHP-SVX02A-EN File Number SV-UN-WSHP-SVX02A-8-02 Supersedes WSHPC-IOM-4 and 72-9036-02 Stocking Location Inland
For more information, contact your local district office or e-mail us at comfort@trane.com
Since Trane has a policy of continuous product and data improvement and reserves the right to change design and specifications without notice.
Loading...