Trane GEHE 072-180, EXHF 006-070, GEHE 006-060, GEVE 072-300, EXVF 006-070 Installation, Operation And Maintenance Manual

...
Page 1
Installation, Operation, and Maintenance
Water Source Heat Pump
Axiom™ Horizontal/Vertical
Model Numbers
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
December 2016
GEHE 006-060 - 50/60 Hz GEVE 006-060 - 50/60 Hz GEHE 072-180 - 50/60 Hz GEVE 072-300 - 50/60 Hz EXHF 006-070 - 60 Hz EXVF 006-070 - 60 Hz
SAFETY WARNING
WSHP-SVX01Q-EN
Page 2
Introduction
Read this manual thoroughlybefore operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
© 2016 Ingersoll Rand All rights reserved WSHP-SVX01Q-EN
Page 3
Copyright
This document andthe information in it arethe property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated GEH* models in Table 53, p. 88.
Minor running changes.
Introduction
WSHP-SVX01Q-EN 3
Page 4
Table of Contents
Copyright ............................. 3
Model Number Description - .5 to 25 Tons .5
Model Number Description - .5 to 6 Tons .. 6
Overview of Manual ..................... 7
Unit Nameplate ..................... 7
Compressor Nameplate ............... 7
Model Number Description ............ 7
General Information ..................... 8
Pre-Installation ......................... 12
Unit Inspection Checklist ............. 12
Jobsite Inspection Checklist .......... 12
Jobsite Storage .................... 12
Unit Dimensions ........................ 13
Service Clearances .................... 13
Weights ................................ 53
Weight Distribution for Hanging the GEH and
EXH Model ........................ 53
Installation ............................. 54
General Installation Checks ........... 54
Main Electrical ..................... 54
Supply-Air Ductwork ................ 55
Return-Air Ductwork ................. 55
Ducted Panel ....................... 55
Ducted Filter Rack (GEH .5 to 5 ton and EXH .5
to 6 ton only) ....................... 56
Dual Filtration (GEH .5 to 5 ton and EXH .5 to
6 ton) ............................. 56
Sound Attenuation Pad .............. 57
Hanging the Horizontal Unit .......... 57
Condensate Drain Connection ......... 57
Supply/Return Pipe Connections ...... 58
Cleaning and Flushing the Water Loop . 58
Field Installed Power Wiring .......... 58
Main Unit Power Wiring ............. 58
Control Power Transformer ........... 59
Thermostat Location ................ 59
Controls Using 24 VAC .............. 59
Blower Motor Speed-Tap Retrofit ...... 60
Hole Plug Installation ................ 61
Air Flow Adjustment .................61
Waterside Economizer Installation ......62
Waterside Economizer Installation for GEH
and GEV 6 to 25 Ton Models ...........65
Waterside Economizer Start-Up Sequence .67
Electrical Data ...........................69
Pre-Start Checklist .......................86
Start-Up ................................87
Initial Unit Start-up ....................87
Start-Up Checklist and Log ............87
Operating Pressures .................87
Water Pressure Drop ................108
Water Volume ......................110
Maintenance ...........................111
Preventive Maintenance .............111
Condensate Trap ...................112
Troubleshooting ........................113
Wiring Diagrams .......................115
Warranty Information ...................127
Standard Warranty ..................127
Extended Warranty .................127
4 WSHP-SVX01Q-EN
Page 5
Model Number Description - .5 to 25Tons
Digits 1-3 - Unit Configuration
GEH = Standard Efficiency Horizontal
GEV = Standard Efficiency Vertical
.5 to 15Tons
.5 to 25Tons
Digit4-Development Sequence
E = R-410A
Digits 5-7 - Nominal Capacity
006 = .5 Tons 009 = .75 Tons 012 = 1Tons 015 = 1.25 Tons 018 = 1.5 Tons 024 = 2Tons 030 = 2.5Tons 035 = 3Tons (Horizontal only) 036 = 3Tons (Vertical only) 042 = 3.5Tons 048 = 4Tons 060 = 5Tons 072 = 6Tons 090 = 7.5 Tons 120 = 10Tons 150 = 12.5Tons 180 = 15Tons 240 = 20Tons 300 = 25 Tons
Digit 8 - Voltage (Volts/Hz/Phase)
0 = 115/60/1 1 = 208/60/1 2 = 230/60/1 3 = 208/60/3 4 = 460/60/3 5 = 575/60/3 7 = 265/60/1 8 = 230/60/3
1
Digit 9 - Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil 8 = Insulated Cupro-Nickel Water Coil
Digit 10 - Current Design Sequence
Digit 11 - Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
4 = Heating and Cooling Circuit with HGR
and WSE
2
Digit 12 - Blower Configuration
1 = Standard Blower Motor 2 = High Static Blower Motor A = Drive Package A B = Drive Package B C = Drive Package C D = Drive Package D E = Drive Package E F = Drive Package F G = Drive Package G H = Drive Package H J = Drive Package J 1*= 2 Speed Drive Package A 2*= 2 Speed Drive Package B 3 = 2 Speed Drive Package C 4= 2 Speed Drive Package D 5= 2 Speed Drive Package E 6= 2 Speed Drive Package F 7= 2 Speed Drive Package G 8= 2 Speed Drive Package H 9= 2 Speed Drive Package J
3
3
Digit 13 - Freeze Protection
A= 20°F Freezestat B= 35°F Freezestat
4
Digit 14 - Open Digit = 0
Digit 15 - Supply-Air
Arrangement
B = Back Supply-Air Arrangement F = Front Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T = Top Supply-Air Arrangement
Digit 16 - Return-Air
Arrangement
B = Back Return-Air Arrangement F = Front Return-Air Arrangement L = Left Return-Air Arrangement R = Right Return-Air Arrangement
2
2
Digit 17 - Control Types
0 = Basic 24V Controls D = Deluxe 24V Controls B =Tracer® ZN524 Controls F = UC400 G = UC400 w/Wireless Comm
5
Digit 18 - Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 - Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 - Temperature Sensor
0 = NoTemperature Sensor 1 = Entering Water Sensor
Digit 21 - Open
Digit 22 - Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat 5 = External Supplemental Electric Heat
3
Digit 23 - Open
Digit 24 - Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4=2”MERV8 5=2”MERV13
Digit 25 - Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
6
Digits 26-36 - Does Not Apply to GEH or GEV
000 00000000 = Digits 26-36 are not applicable to the GEH or GEV products
2
1
.5 to 1Ton only
2
6 to 25 Tons only
WSHP-SVX01Q-EN 5
3
.5 to 5 Tons only
4
Extended Range Geothermal
5
.5 to 5 Tons only
6
.5 to 5 Tons (horizontal only)
Page 6
Model Number Description - .5 to 6Tons
Digits 1-3 — Unit Configuration
EXH =High Efficiency Horizontal EXV =High Efficiency Vertical
Digit 4 Development Sequence
F
Digits 5-7 — Nominal Capacity
006 =.5 Tons 009 =.75 Tons 012 =1Tons 015 =1.25 Tons 018 =1.5 Tons 024 =2Tons 030 =2.5Tons 036 =3Tons 042 =3.5Tons 048 =4Tons 060 =5Tons 070 =6Tons
Digit 8 — Voltage (Volts/Hz/ Phase)
1 = 208/60/1 2 = 230/60/1 3 = 208/60/3 4 = 460/60/3 7 = 265/60/1 8 = 230/60/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper Water
Coil/Suction Line
8 = Insulated Cupro-Nickel Water
Coil/Suction Line
Digit 10 — Current Design Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
Digit 12 — Blower Configuration
3 = ECM Motor
Digit 13 - Freeze Protection
A = 20°F Freezestat B = 35°F Freezestat
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement
Digit 16 — Return-Air
Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 — Control Types
D = Deluxe 24V Controls B = Tracer® ZN524 Controls F = UC400 G = UC400 w/ Wireless Comm
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = No AdditionalTemperature Sensor 1 = Entering Water Sensor
Digit 21 — Open Digit
Digit 22 — Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat
Digit 23 — Open Digit
Digit 24 — Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4= MERV8 5 = MERV13
Digit 25 — Acoustic
Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digits 26-36 — Does not Apply to EXH or EXV
00000000000 Digits 26-36 are not applicable to the EXH or EXV products
6 WSHP-SVX01Q-EN
Page 7
Overview of Manual
Note: One copy of this document ships with each unit and
is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for HVAC systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
Service and maintenance work should be performed by a qualified technician and all electrical service and maintenance work should be performed by a qualified licensed electrician.
Unit Nameplate
The unit nameplate is located on the outside of the control
box access panel at thefront of the unit. Itincludes the unit model number, serial number, electrical characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Model Number Description
All products are identified by a multiple-character model number that preciselyidentifies a particular type ofunit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial number printed on the unit nameplate.
WSHP-SVX01Q-EN 7
Page 8
General Information
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak tested to assure there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).
Table 1. High/Low pressure switch
Trip Recover Unit
LP 40 +/-4 56 +/-4 psig
HP 650 +/-10 550 +/-10 psig
Controls
Basic 24V control is available for the GEH/V .5 -5 ton models and the Deluxe 24V control option is available for all unit sizes.Tracer® ZN524, LonTalk® certified control option is available for all unitsizes. UC400 and UC400 with wireless comm BACnet® is available in all unit sizes.
All power wiring to the equipment is made at the unit
contactor for .5to 5 ton, 1-phase units. For 3-phaseunits all power wiring to the equipmentis made tothe contactor or power block. For EXH/V070 units all power wiring to the equipment is made to the power block. For the GEH/V 6 to 25 tons units all power wiring is made to the high voltage terminal block. All low-voltage wiring is made at the unit’s low voltage terminal board. EXH and EXV 460V units require a neutral wire.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system
is required to operate the water-source heat pump.The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V
control systems may be locatedin the back of this manual.
All digital control troubleshooting tips and connection
diagrams are located in CNT-SVX11*-EN (ZN524). All digital control troubleshooting tips and connection diagrams are located in BAS-SVX065*-EN (UC400).
Basic 24V Controls
Safety devices for equipment containing the basic 24V control option include a low-pressure switch to prevent compressor operation during low temperature or low suction activity.The switch is set to activate at refrigerant pressure of 40 psig to fit most applications.
A high pressure switch prevents compressor operation
during high or excessive discharge pressures exceeding 650 psig.
The lockout relay will disable the compressor on a high or
low pressure condition. For units that contain a condensate overflow switch option, a condensate overflow condition will also disable the compressor through the lockout relay.The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay.
This feature will drive dry contacts only, and cannot be
used to drive field installed control inputs.Trane provides a 3.5-minute time delay for compressor control.
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board.The
Trane® microprocessor board is factory wired to a
terminal strip to provide all necessary terminals for field connection.The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, condensate overflow, unit safety control, diagnostics, and a generic relay (which may be available for field use). See Table 64, p. 113 for diagnostic information and Figure 59, p. 62 and Figure 60, p. 63 for thermostat connections.
Tracer® UC400 (option)
TheTracer® UC400 is a BTL Listed BACnet® controller that
can operate stand- alone or within aBuilding Automations system such asTracer® SC. For installation, operation and Programming, see BAS-SVX065*-EN (UC400).
Tracer® ZN524 Controls (option)
The digital ZN524 controller is designed to support the .5
to 25 ton water-source heat pumps in either a standalone, or as a full building automation (open protocol) system.
For installation, operation and diagnostics see CNT­SVX11A-EN (ZN524).
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual 1/
6 HP bronze pump and a brass three-way shut-off valve. Cast iron pumps are also available.The pump module kits shall contain the necessary components for the installation, operation and maintenance of the water circuit of a closed-loop distributed pumping application.
8 WSHP-SVX01Q-EN
Page 9
General Information
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin
economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 60°F (for the Deluxe control option), or below the programmed set-point (for the ZN524 or UC400 control option).
When the temperature is less than the setpoint, fluid will
flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control. Entering water temperature sensor is factory provided for field installation on the entering water side of the coil.
Boilerless Control/Electric Heat (Option)
Systems that do not contain a boiler may contain a boilerless control with electric heat.Trane® offers both a factory mounted electric heat option (.5 to 5 ton only), and a field mounted duct heater option.
If the .5 to5 ton GEH, GEV andEXH/V070 unitincorporates the factory mounted option, the unit will ship from the factory with an internally mounted nichrome open wire heating element, designed to start-up electric heat as the systems primary heat in the event entering water temperature falls below 55°F. Once the entering water temperature rises above 60°F, the boilerless controller returns the unit to normal compressor heating operation, and locks out the electric heater.
For units comprised of the field installed duct heater option, the unit will ship from the factory with controls available to interface with the field provided electric heat selection.
Note: For geothermal applications, the boilerless
controller has an adjustable setting of 25, 35, 45, 55, and 60 degrees.
Supplemental or Boilerless Electric Heat (option)
The GEH/V 6 to 25 ton models which contain boilerless
control electric heat or supplemental electric heat will contain the controls interface ONLY for field provided electric heat selection.The heater for this model shall be external to the equipment by the contractor for ease of installation. All power connections for the electric heater will be completely separate from theunit for field supplied electric heat.
Note: When the unit has boilerless control, the electric
heat is not used as supplemental electric heat, but as a primary heat.
the reheat coil to control not only the space temperature, but to also reduce therelative humidity of the space.When operating in the reheat mode (meaning the sensible temperature has been met in the space), the humidistat signals the reheat relay coil to energize, allowing the high pressure refrigerant gas to flow from the compressor through the reheat valve, into the reversing valve and reheat coil.
A switching relay has been provided for the reheat
application to adjust the blower motor from normal operation to low speed when the hot gas reheat is energized (for .5 to 5 ton and EXH/V070 equipment only).
Note: A high static blower motor is required to support
the hot gas reheat option for the GEH/V .5 -5 ton.
Note: Units containing the hot gas reheat option should
not be used as a make-up air unit.
2 Speed Blower Motor (option)
The 6 to25 ton GEH/Vmodels have indoorblowers that are
available with 2 speed motors, selectable in the model number (Digit 12, drive packages one to nine). High speed airflow matches the single speed motor airflow, referenced in the Fan Performance tables. Low fan speed airflow is approximately 50% of high fan speed airflow.
The 6 to 25 ton GEH/V two-speed blower motors are
available with the following options: Deluxe24V or UC400 controls, Heat Pump (HP) or HP w/Hot Gas Reheat or HP w/
Waterside Economizer. Not available with Boilerless or
Supplemental Electric Heat.
Table 2. 6 to 25 ton GEH/V fan speed for two-speed
drive packages one to nine
RV State Fan Compressor 1 Compressor 2 Fan Speed
Heat OFF OFF OFF OFF Heat ON OFF OFF LOW Heat ON ON OFF HIGH Heat ON ON ON HIGH Cool OFF OFF OFF OFF Cool ON OFF OFF LOW Cool ON ON OFF LOW Cool ON ON ON HIGH
Hot Gas Reheat (option)
With the reheat option, the return-air from the space is
conditioned by the air-to-refrigerant coil, then reheated by
WSHP-SVX01Q-EN 9
Page 10
General Information
Table 3. Refrigerant charge
Model
(60 Hz)
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
Circuit 1 Circuit 2 Circuit 1 Circuit 2
GEHE006 25.3 / .717 ----- 26.8 / .760 ----­GEHE009 26.0 /.737 ----- 27.5 / .780 ----­GEHE012 28.5 / .808 ----- 30.5 / .865 ----­GEHE015 29.0 / .822 ----- 30.5 / .865 ----­GEHE018 36.5 / 1.035 ----- 39.5 / 1.120 ----­GEHE024 39.0 / 1.106 ----- 42.0 / 1.191 ----­GEHE030 44.0 / 1.247 ----- 46.5 / 1.318 ----­GEHE035 53.0 / 1.503 ----- 56.0 / 1.588 ----­GEHE042 57.0 / 1.616 ----- 60.5 / 1.715 ----­GEHE048 61.0 / 1.729 ----- 65.5 / 1.857 ----­GEHE060 73.0 / 2.070 ----- 77.5 / 2.197 ----­GEVE006 25.7 / .789 ----- 27.2 / .771 ----­GEVE009 26.5 / .751 ----- 28.0 / .794 ----­GEVE012 29.5 / .836 ----- 31.5 / .893 ----­GEVE015 27.5 / .780 ----- 29.5 / .836 ----­GEVE018 37.0 / 1.049 ----- 40.0 / 1/134 ----­GEVE024 39.0 / 1.106 ----- 41.5 / 1.177 ----­GEVE030 44.5 / 1.262 ----- 47.0 / 1.332 ----­GEVE036 51.0 / 1.446 ----- 54.5 / 1.545 ----­GEVE042 54.0 / 1.531 ----- 57.5 / 1.630 ----­GEVE048 61.0 / 1.729 ----- 66.0 / 1.871 ----­GEVE060 74.0 / 2.098 ----- 79.5 / 2.254 ----­GEHE072 55 / 1.559 55 / 1.559 59 / 1.673 55 / 1.559 GEHE090 64 / 1.814 54 / 1.531 68 / 1.928 54 / 1.531 GEHE120 86 / 2.438 86 / 2.438 90 / 2.551 86 / 2.438 GEHE150 136 / 3.856 136 / 3.856 144 / 4.082 136 / 3.856 GEHE180 126 / 3.572 126 / 3.572 134 / 3.799 126 / 3.572 GEVE072 58 / 1.644 58 / 1.644 62 / 1.758 58 / 1.644 GEVE090 83 / 2.353 75 / 2.126 87 / 2.466 75 / 2.126 GEVE120 88 / 2.495 88 / 2.495 92 / 2.608 88 / 2.495 GEVE150 122 / 3.459 122 / 3.459 130 / 3.685 122 / 3.459 GEVE180 128 / 3.629 128 / 3.629 136 / 3.856 128 / 3.629 GEVE240 284 / 8.051 284 / 8.051 292 / 8.278 284 / 8.051 GEVE300 260 / 7.371 260 / 7.371 267 / 7.569 260 / 7.371 EXHF006 25.3 / 0.717 ----- 26.8 / 0.760 ----­EXHF009 26.0 / 0.737 ----- 27.5 / 0.780 ----­EXHF012 28.5 / 0.808 ----- 30.5 / 0.865 ----­EXHF015 29.0 / 0.822 ----- 30.5 / 0.865 ----­EXHF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXHF024 50.5 / 1.432 ----- 53.0 / 1.503 ----­EXHF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXHF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXHF042 81.0 / 2.296 ----- 85.5 / 2.424 ----­EXHF048 83.0 / 2.353 ----- 87.5 / 2.481 ----­EXHF060 114.0 / 3.232 ----- 118.5 / 3.359 ----­EXHF070 122.0 / 3.459 ----- 127.0 / 3.600 -----
10 WSHP-SVX01Q-EN
Page 11
Table 3. Refrigerant charge (continued)
General Information
Model
(60 Hz)
EXVF006 25.7 / 0.729 ----- 27.2 / 0.771 ----­EXVF009 26.5 / 0.751 ----- 28.0 / 0.794 ----­EXVF012 29.5 / 0.836 ----- 31.5 / 0.893 ----­EXVF015 30.0 / 0.850 ----- 32.0 / 0.907 ----­EXVF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXVF024 52.0 / 1.474 ----- 54.5 / 1.545 ----­EXVF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXVF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXVF042 81.0 / 2.296 ----- 86.0 / 2.438 ----­EXVF048 83.0 / 2.353 ----- 88.5 / 2.509 ----­EXVF060 114.0 / 3.232 ----- 119.5 / 3.388 ----­EXVF070 122.0 / 3.459 ----- 128.0 / 3.629 -----
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
WSHP-SVX01Q-EN 11
Page 12
Pre-Installation
WARNING
Fiberglass Wool!
Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation.You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, a NIOSH approved dust/mist respirator, long sleeves and pants when working with products containing fiberglass wool.
Unit Inspection Checklist
Unpack all components of the kit.
Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
Important: Equipment is shipped FOB (Free on Board)
at the manufacturer.Therefore, freight claims for damages against the carrier must be initiated by the receiver.
Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the shipment.
Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Do not attempt to repair any damaged parts until the parts are inspected by the carrier’s representative.
Jobsite Inspection Checklist
Always perform the following checks before
accepting a unit:
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the
unit(s) are unloaded. Once the billof lading is signed at the jobsite, the unit(s) are now the property of the SOLDTO party and future freight claims MAY NOT be accepted by the freight company.
Jobsite Storage
NOTICE:
Microbial Growth!
Wet interior unit insulation can become an
amplification site for microbial growth (mold), which could result in odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, it should be removed and replaced prior to operating the system.
NOTICE:
Microbial Growth!
Failure to follow instructions below could result in odors and damage to the equipment and building materials.The floor or foundation must be level and the condensate drain at the proper height for proper coil drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold).
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unitshould be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
Cover the unit(s) with a water proof tarp to protect them from the elements.
Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
Store units in the normal UP orientationto maintain oil in the compressor.
Horizontal units may be stacked no more than three units high. Do not stack the vertical unit configurations.
12 WSHP-SVX01Q-EN
Page 13
Unit Dimensions
Service Clearances
Per NEC requirements, 36 inches of access and working space shall be provided and maintained around allcontrol boxes and electrical equipment to permit ready and safe operation and maintenance of such equipment. Local codes may require more clearance to electrical equipment. Check all code requirements prior to unit installation.
Figure 1. Clearances - GEH .5 to 5 tons & EXH .5 to 6Tons
14"
14"
LEFT RETURN
BACK SUPPLY
UNIT FRONT
36"
14"
14" 14”
LEFT RETURN
RIGHT SUPPLY
14"
UNIT FRONT UNIT FRONT
36"
14"14"
14"
14"
LEFT RETURN LEFT SUPPLY
36"
14"
A minimum 14 inch clearancefor servicing the unit is required for all .5 to 5 tons and EXH070 configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/ maintenance ability.The optimum clearance required is 20 inches.
3"
Equipment containing a same-side supply/ return combination requires a 3 inches limitation on one side. Access to theTXV may not be possible with this 3 inches clearance.
This configuration is typically applied in a
corridor installation, where space limitations force the left or right side of the unit against a wall.
RIGHT RETURN
BACK SUPPLY
14"
UNIT FRONT
14"
36"
RIGHT RETURN
LEFT SUPPLY
14"
UNIT FRONT
36"
Figure 2. Clearance - GEH 6 to 15 Tons
24"
36"
CONTROL BOX
TOP VIE W
24"
14"
3"
BLOWER ACCESS PANEL
RIGHT RETURN RIGHT SUPPLY
UNIT FRONT
36"
14"
Service clearance dimensions for the GEH 6 to15 tons horizontal includes a two side access appropriate for control and blower motor/wheel access.
WSHP-SVX01Q-EN 13
Page 14
Unit Dimensions
Figure 3. Clearance - GEV .5 to 5 tons & EXV .5 to 6Tons
1"
24"
1"
1"
UNIT FRONT
UNIT FRONT
36"
36"
24"
LEFT
RETURN
TOP/BACK
SUPPLY
TOP/BACK
1"
RIGHT
RETURN
SUPPLY
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.This will enable panel removal from the unit for service/maintenance.
A 1 inch minimum clearance between the filterrackand any obstacle is required for units in a free return application to provide proper air flow to the air-to-refrigerant coil. A 12 inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork.
The 1 inch dimension shown in the back of the unit
represents the supply duct collar for the back supply option.This clearance is needed to clear these flanges.
Figure 4. Clearance - GEV 6 to 10Tons
24"
FRONT RETURN
TOP SUPPLY
ACCESS PANEL FOR SHEAVES AND BELTS
36"
24"
Figure 5. Clearance - GEV 12.5 to 25 Tons
18"
24"
CONTROL BOX
36"
FRONT RETURN-AIR
BACK SUPPLY-AIR
UNIT FRONT
18"
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.The unit may be serviced through the front access panel or remaining open sides.
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.The unit may be serviced through the front access panel.
24"
14 WSHP-SVX01Q-EN
Page 15
Figure 6. Left return/left supply (GEH/EXH)
TOP
F X G
OPENING
C
BLOWER
ACCESS
PANEL
1"
DRAIN
3/4" NPTI
BACK LEFT SIDE FRONT
H
Q
K
1/2"
H
J
RS
N
A
HI VOLT
WCI mounting location
LO VOLT
ED
6 3/4"
1"
Unit Dimensions
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
1 3/8"
14"
RIGHT SIDE
Table 4. Dimensional data left return/left supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
2. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
Hi-042,
048, 060
EXH Unit
(50 Hz) A B C D
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
access on either side of the filter. 3 in. clearance.
WSHP-SVX01Q-EN 15
Page 16
Unit Dimensions
Figure 7. Left return/back supply (GEH/EXH)
TOP
F X G
OPENING
C
1"
BLOWER
H
ACCESS
PANEL
N
A
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
BP
REFRIG
AND
CONTROL
Q
ACCESS
L (W.O.)
M (W.I.)
7"
DRAIN 3/4" NPTI
H
J
K
BACK LEFT SIDE FRONT
ED
14"
1"
1/2"
1 3/8"
RIGHT SIDE
Table 5. Dimensional data left return/back supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/213-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
060 58 33 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
070 N/A 58 39 21 29-1/2 23-1/213-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
S
S
16 WSHP-SVX01Q-EN
Page 17
Figure 8. Left return/right supply (GEH/EXH)
TOP
N
A
ED
BLOWER ACCESS
1"
PANEL
Q
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
Unit Dimensions
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
DRAIN 3/4" NPTI
BACK LEFT SIDE FRONT
RIGHT SIDE
1/2"
F X G
OPENING
C
H
K
H
1"
1 3/8"
14"
J
Table 6. Dimensional data left return/right supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
S
S
WSHP-SVX01Q-EN 17
Page 18
Unit Dimensions
Figure 9. Right return/left supply (GEH/EXH)
R
TOP
N
A
ED
1"
BLOWER ACCESS
PANEL
DRAIN 3/4" NPTI
RIGHT SIDE
H
K
H
BACK LEFT SIDE FRONT
J
7"
C
F X G
OPENING
WCI mounting location
HI VOLT
LO VOLT
14"
1”
S
6 3/4"
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
Q
1/2"
1 3/8”
Table 7. Dimensional data right return/left supply (GEH/EXH)
GEH
Unit (60
Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
060
EXH
Unit (60
Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this 3 in. clearance.
(a)Return air opening dimension. (b)Filter rack dimension.
GEH
Unit (50
Hz) A B C D
Hi-042,
048, 060
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
EXH
Unit (50
Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
(b)
S
S
18 WSHP-SVX01Q-EN
Page 19
Figure 10. Right return/back supply (GEH/EXH)
R
TOP
N
F X G
OPENING
ED
A
Unit Dimensions
S
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
1”
Q
1/2"
6 3/4”
7"
1 3/8”
BLOWER ACCESS
PANEL
HI VOLT
WCI mounting location
LO VOLT
14"
H
K
C
1"
H
DRAIN 3/4" NPTI
RIGHT SIDE
J
BACK LEF T SIDE FRONT
Table 8. Dimensional data right return/back supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
WSHP-SVX01Q-EN 19
Page 20
Unit Dimensions
Figure 11. Right return/right supply (GEH/EXH)
HI VOLT
LO VOLT
1"
S
6 3/4"
FRONT
BP
REFRIG
AND
CONTROL
ACCESS
R
TOP
N
A
ED
BLOWER
ACCESS
PANEL
1"
DRAIN 3/4" NPTI
BACK
C
WCI mounting location
LEFT SIDE
F X G
OPENING
L (W.O.)
M (W.I.)
Q
1/2"
14"
RIGHT SIDE
7"
1 3/8"
H
H
J
K
Table 9. Dimensional data right return/right supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
2. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
access on either side of the filter. 3 in. clearance.
20 WSHP-SVX01Q-EN
Page 21
Figure 12. Left return/top supply (GEV/EXV)
D L
F
Unit Dimensions
K
B
WCI mounting location
JM
TOP
LEFT SIDE
D
E
8 3/4”
H
8 5/8”
BLOWER ACCESS
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
12”
9 1/2”
G
3 5/8”
W.O .
DRAIN
W.I .
C
RIGHT SIDE
Table 10. Dimensional data left return/top supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 015 006-012 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 030 015-024 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 5-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
060
GEV Unit
(50 Hz) A B C D E F G H J K L M
Hi-042,
048, 060
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
EXV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.I.
NPTI
W.O. NPTI
W.O. NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
WSHP-SVX01Q-EN 21
Page 22
Unit Dimensions
Figure 13. Left return/back supply (GEV/EXV)
D
E
M
F
D
B
J
TOP
WCI mounting location
LEFT SIDE
8 3/4”
H
3 5/8”
BLOWER
ACCESS
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
W.O .
DRAIN
9 1/2”
12”
G
3 5/8”
W.I .
C
RIGHT SIDE
Table 11. Dimensional data left return/back supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 009 006 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012 - 015 009-012 19-1/2 31-1/4 21-1/2 11-1/2 4-3/4 3-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 030 015-024 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 5-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
060
GEV Unit
(50 Hz) A B C D E F G H J K L M
Hi-042,
048, 060
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
EXV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.I.
NPTI
W.O. NPTI
W.O. NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
22 WSHP-SVX01Q-EN
Page 23
Figure 14. Right return/top supply (GEV/EXV)
A
H
Unit Dimensions
F
D
L
K
M
B
WCI mounting location
HI VOLT
LOW VOLT
c
LEFT SIDE
3 5/8”
8 3/4”
BLOWER ACCESS
COMP/CONTROL
ACCESS
W.O .
DRAIN
FRONT
W.I .
3 5/8”
9 1/2”
G
12”
D
E
J
TOP
RIGHT SIDE
Table 12. Right return/top supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 015 006 - 012 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 024 015-018 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 2-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
GEV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.O. NPTI
030 024 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4
060
Hi-042,
048, 060
EXV Unit
(50 Hz) A B C D E F G H J K L M
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
W.I.
W.O.
NPTI
NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
WSHP-SVX01Q-EN 23
Page 24
Unit Dimensions
Figure 15. Right return/back supply (GEV/EXV)
F
D
B
COMP/CONTROL
WCI mounting location
HIGH VOLT
LOW VOLT
8 3/4”
3 5/8”
BLOWER
ACCESS
ACCESS
W.O .
DRAIN
W.I .
3 5/8”
D
E
J
TOP
H
9 1/2”
12”
G
M
C
LEFT SIDE
A
FRONT
RIGHT SIDE
Table 13. Dimensional data right return/back supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 009 006 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012 - 015 009 - 012 19-1/2 31-1/4 21-1/2 11-1/2 6 1-1/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 024 015-018 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 2 1-1/4 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
GEV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.O. NPTI
030 024 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4
060
Hi-042,
048, 060
EXV Unit
(50 Hz) A B C D E F G H J K L M
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
W.I.
W.O.
NPTI
NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
24 WSHP-SVX01Q-EN
Page 25
Figure 16. Right return/left supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
5/8”
BLOWER ACCESS
PANEL
4 7/8”
1 3/4”
23 7/8”
7 5/8”
(54)
2 1/8"
18 3/8”
1”
1 1/4”
A
74 1/2”
81”
85”
TOP VIE W
W.O. “D” NPTI
1 1/8” DIA.
24 VOLT
36”
1 1/2”
Unit Dimensions
4 5/8”
40 5/8”
18 3/4”
BACK SIDE
MOUNTING HOLE
3 1/8”
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
RETURN AIR
OPENING
1” DIA.
4X’s
14 1/2”
B
C
W.I. “D” NPTI
SUPPLY OPENING
1” DUCT FLANGE
LEFT SIDE
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
2 1/4”
23 1/4
16 1/2”
6 1/2”
Table 14. Dimensional data right return/left supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/4 in. 15-5/8 in. 6-5/8 in. 1-1/4 in. 090 072 36-1/8 in. 12-3/4 in. 6-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
WSHP-SVX01Q-EN 25
Page 26
Unit Dimensions
Figure 17. Right return/back supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
74 1/2”
81”
85”
23 7/8”
2 1/8"
1 3/4”
18 3/8”
6 1/8”
36”
4 5/8”
40 5/8”
5/8”
18 3/4”
3 1/8"
BLOWER ACCESS
4 7/8”
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
PANEL
14 1/2”
1 1/4”
TOP VIE W
W.O. “D” NPTI
A 1 1/2”
B
C
W.I. “D” NPTI
LEFT SIDE
RETURN AIR
OPENING
24 VOLT
1 1/8” DIA.
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
2 1/4”
23 1/4
16 1/2”
6 1/2”
Table 15. Dimensional data right return/back supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/4 in. 15-5/8 in. 6-5/8 in. 1-1/4 in. 090 072 36-1/8 in. 12-3/4 in. 6-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
26 WSHP-SVX01Q-EN
1” DIA.
MOUNTING HOLE
4X’s
SUPPLY OPENING
1” DUCT FLANGE
Page 27
Figure 18. Left return/right supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
40 5/8”
4 5/8”
36”
74 1/2”
1 3/4”
24 3/4”
Unit Dimensions
23 1/4"
16 1/2”
1 1/2”
2 1/4”
6 1/2”
LEFT SIDE
RETURN AIR
OPENING
TOP VIE W
W.O. “D” NPTI
24 VOLT
1 1/8” DIA.
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
81”
85”
18 3/8”
A
W.I. “D” NPTI
7 5/8”
1 1/4”
C
1 1/4”
14 1/2”
B
DRAIN CONNECTION
1/2” SCHEDULE 40 PVC
BLOWER ACCESS PANEL
1”
4 7/8”
5/8”
18 3/4”
3 1/8”
BACK SIDE
1” DIA.
MOUNTING HOLE
4X’S
Table 16. Dimensional data left return/right supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/8 in. 17 in. 8 in. 1-1/4 in. 090 072 36-1/8 in. 13-3/4 in. 7-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
WSHP-SVX01Q-EN 27
SUPPLY OPENING
1” DUCT FLANGE
Page 28
Unit Dimensions
Figure 19. Left return/back supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
23 1/4"
(591)
40 5/8”
16 1/2"
(419)
36”
1 1/2”
4 5/8”
W.O. “D” NPTI
24 VOLT 1 1/8” DIA.
WCI mounting location
74 1/2”
81”
85”
TOP VIE W
A
6 1/2”
1 3/4”
18 3/8”
B
C
24 3/4”
6 1/8”
14 1/2”
1 1/4”
BLOWER ACCESS PANEL
1 1/4”
4 7/8”
5/8”
18 3/4
6 1/2”
1” DIA.
MOUNTING HOLE
4X’S
2 1/4”
LEFT SIDE
HIGH VOLTAGE
7/8” DIA.
SUPPLY OPENING
1” DUCT FLANGE
W.I. “D” NPTI
RETURN AIR OPENING
DRAIN CONNECTION
1/2" SCHEDULE 40 PVC
3 1/8”
Table 17. Dimensional data left return/back supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/8 in. 17 in. 8 in. 1-1/4 in. 090 072 36-1/8 in. 13-3/4 in. 7-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
28 WSHP-SVX01Q-EN
Page 29
Unit Dimensions
Figure 20. Right return/left supply GEH 12.5 to 15 tons (150-180) 60 Hz; GEH 10 to 12.5 tons (120-150) 50 Hz
85"
4 5/8"
42"
29 3/4"
2"
74 1/2"
46 5/8"
1 3/8"
23 3/4"
BACK SIDE
BLOWER ACCESS
4 7/8"
3 1/8"
RETURN AIR
OPENING
PANEL
1"
DRAIN CONNECTION 1/2" SCHEDULE 40 PVC
16 3/4"
24 7/8"
2 1/4"
2"
5 5/8"
7 1/8"
21 3/8"
61 1/4"
W.I. 1 1/2"
NPTI
87"
91"
LEFT SIDE
TOP VIEW
W.O. 1 1/2" NPTI
24 VOLT
1 1/8" DIA.
WCI mounting location
HIGH VOLTAGE
7/8" DIA.
2 1/4"
2 1/4"
30 1/4"
22 3/4"
9 1/8"
MOUNTING HOLE
1" DIA.
4X'S
WSHP-SVX01Q-EN 29
SUPPLY OPENING 1" DUCT FLANGE
Page 30
Unit Dimensions
Figure 21. Right return/back supply GEH 12.5 to 15 tons (60 Hz); GEH 10 to 12.5 tons (50 Hz)
85"
1 3/8"
23 3/4"
BLOWER ACCESS
4 7/8"
PANEL
29 3/4"
2"
16 3/4"
2 1/4"
24 7/8”
2"
21 3/8"
7 1/8"
5 5/8”
TOP VIEW
61 1/4"
74 1/2"
87"
91"
W.O. 1 1/2” NPTI
WCI mounting location
24 VOLT
1 1/8” DIA.
4 5/8"
46 5/8"
42"
1 1/2"
30 1/4"
22 3/4"
3 1/8"
DRAIN CONNECTION
1/2” SCHEDULE 40 PVC
W.I. 1 1/2" (38)
NPTI
MOUNTING HOLE
1” DIA.
4X’S
LEFT SIDE
RETURN AIR
OPENING
HIGH VOLTAGE
7/8” DIA.
2 1/4"
9 1/8"
SUPPLY OPENING 1” DUCT FLANGE
30 WSHP-SVX01Q-EN
Page 31
Figure 22. Left return/right supply GEH 12.5 to 15 tons (60 Hz); GEH 10 to 12.5 tons (50 Hz)
85”
46 5/8”
42”
4 5/8”
74 1/2”
2"
29 3/4”
Unit Dimensions
30 1/4"
22 3/4"
2 1/8”
9 1/8”
LEFT SIDE
2 1/4”
TOP VIEW
W.O. 1 1/2”
NPTI
24 VOLT 1 1/8” DIA.
WCI mounting location
HIGH VOLTAGE 7/8” DIA.
RETURN AIR
87”
91”
OPENING
21 3/8”
39 1/2”
W.I. 1 1/2” NPTI
7 1/8”
2 1/4”
2”
16 3/4"
24 7/8"
5 5/8"
DRAIN CONNECTION
1/2" SCHEDULE 40 PVC
BLOWER ACCESS PANEL
1”
4 7/8”
1 3/8"
23 3/4"
3 1/8”
BACK SIDE
MOUNTING HOLE
1” DIA.
WSHP-SVX01Q-EN 31
SUPPLY OPENING 1” DUCT FLANGE
4X’S
Page 32
Unit Dimensions
Figure 23. Left return/back supply GEH 12.5 to 15 tons (60 Hz); GEH 10 to 12.5 tons (50 Hz)
85"
30 1/4"
46 5/8"
22 3/4"
4 5/8"
42"
2 1/8"
W.O. 1 1/2" NPTI
24 VOLT 1 1/8" DIA.
WCI mounting location
74 1/2"
87"
91"
TOP VIEW
39 1/2"
2"
21 3/8"
5 5/8"
7 1/8"
24 7/8"
29 3/4"
2 1/4"
BLOWER ACCESS PANEL
2"
16 3/4"
4 7/8"
1 3/8"
23 3/4"
9 1/8"
2 1/4"
HIGH VOLTAGE 7/8" DIA.
LEFT SIDE
MOUNTING HOLE
1" DIA.
4X'S
32 WSHP-SVX01Q-EN
W.I. 1 1/2" NPTI
SUPPLY OPENING 1" DUCT FLANGE
DRAIN CONNECTION
1/2" SCHEDULE 40 PVC
RETURN AIR
OPENING
3 1/8"
Page 33
Unit Dimensions
Figure 24. Front return/back supply
ACCESS PANEL FOR
SHEAVES AND BELTS
1”
13 1/2"
24 VOLT
46 1/2"
HIGH VOLTAGE
7/8" DIA.
1 5/8"
1 1/8"
WCI mounting location
15"
5"
(a)
GEV 6 to 10 tons (60 Hz); 6 and 7.5 tons (50 Hz)
15 3/4”
13 18"
39 5/8"
42"
38 7/8"
22 3/8"
W.I. "C" NPTI
3/4"
SUPPLY OPENING 1" DUCT FLANGE
W.O. "C" NPTI
DRAIN 3/4" NPTI
11 1/2"
A
1 7/8"
31 3/8"
36 1/4"
4 7/8"
62 5/8"
B
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 18. Dimensional data front return/back supply GEV 6 to 10 tons (60 Hz); 6 and 7.5 tons (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C
6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in.
7.5 ton 6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in. 10 ton 7.5 ton 6-1/2 in. 18-1/2 in. 1-1/2 in.
WSHP-SVX01Q-EN 33
Page 34
Unit Dimensions
Figure 25. Front return/top supply
ACCESS PANEL FOR
SHEAVES AND BELTS
1"
38 7/8"
63"
24 VOLT 1 1/8"
22 3/8"
HIGH VOLTAGE
7/8" DIA.
WCI mounting location
15"
5"
1 5/8"
(a)
GEV 6 to 10 tons (60 Hz); 6 and 7.5 tons (50 Hz)
15 5/8
1 1/8"
13 3/8"
W.O. "C" NPTI
DRAIN 3/4" NPTI
11 1/2"
A
1 7/8"
31 3/8"
36 1/4"
4 7/8"
62 5/8"
B
3/4"
13 1/4"
W.I. "C" NPTI
SUPPLY OPENING 1" DUCT FLANGE
39 5/8"
42"
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 19. Dimensional data front return/top supply GEV 6 to 10 tons (60 Hz); 6 and 7.5 tons (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C
6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in.
7.5 ton 6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in. 10 ton 7.5 ton 6-1/2 in. 18-1/2 in. 1-1/2 in.
34 WSHP-SVX01Q-EN
Page 35
Unit Dimensions
Figure 26. Back return/front supply
ACCESS PANEL FOR
SHEAVES AND BELTS
1"
38 7/8"
24 VOLT 1 1/8"
22 3/8"
3/4"
HIGH VOLTAGE
7/8" DIA.
1 5/8"
WCI mounting location
15"
5"
(a)
GEV 6 to 10 tons (60 Hz); 6 and 7.5 ton (50 Hz)
39 5/8"
13 1/8"
15 3/4”
42"
62 5/8"
W.I. "C" NPTI
4 7/8"
36 1/4"
31 3/8"
1 1/8"
13 1/2"
W.O. "C" NPTI
DRAIN 3/4" NPTI
11 1/2"
A
1 7/8"
46 1/2"
B
RETURN AIR
OPENING
SUPPLY OPENING 1" DUCT FLANGE
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 20. Dimensional data back return/front supply GEV 6 to 10 tons (60 Hz); 6 and 7.5 ton (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C
6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in.
7.5 ton 6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in.
10 ton 7.5 ton 6-1/2 in. 18-1/2 in. 1-1/2 in.
WSHP-SVX01Q-EN 35
Page 36
Unit Dimensions
Figure 27. Back return/top supply
ACCESS PANEL FOR
SHEAVES AND BELTS
1"
38 7/8"
24 VOLT 1 1/8"
22 3/8"
3/4"
HIGH VOLTAGE
7/8" DIA.
1 5/8"
WCI mounting location
5"
RETURN AIR
OPENING
15"
(a)
GEV 6 to 10 tons (60 Hz); 6 and 7.5 ton (50 Hz)
63"
13 1/4"
W.I. "C" NPTI
39 5/8"
15 5/8”
42"
13 1/2"
1 1/8"
W.O. "C" NPTI
DRAIN 3/4" NPTI
A
1 7/8"
11 1/2"
31 3/8"
4 7/8"
36 1/4"
62 5/8"
B
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 21. Dimensional data back return/top supply GEV 6 to 10 tons (60 Hz); 6 and 7.5 ton (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C
6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in
7.5 ton 6 ton 6-5/8 in. 18-3/8 in. 1-1/4 in. 10 ton 7.5 ton 6-1/2 in. 18-1/2 in. 1-1/2 in.
36 WSHP-SVX01Q-EN
SUPPLY OPENING 1" DUCT FLANGE
Page 37
Unit Dimensions
/2
Figure 28. Front return/back supply
15 7/8"
49 1/8"
WCI mounting
location
24 VOLT 1 1/8"O.D.
6 7/8"
20 1/2"20 1
(a)
GEV 12.5 to 15 tons (60 Hz); GEV 10 and 12.5 ton (50 H)z
4 3/4"
31 1/2"
74 1/2"
81 5/8"
36 1/4"
TOP VIEW
18 5/8"
31 1/2"
38 7/8"
67 5/8"
27 1/8"
CONTROL
BOX ACCESS
10"
W.O. 1 1/2" NPTI
DRAIN 3/4" NPTI
12 1/2"
23 1/2
HIGH VOLTAGE
7/8" O.D.
2 3/8"
1"
FRONT VIEW
W.I. 1 1/2"
NPTI
2 5/8"
4 1/4"
SIDE VIEW
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
WSHP-SVX01Q-EN 37
Page 38
Unit Dimensions
1 /2
"
"
"
Figure 29. Back return/front supply GEV 12.5 to 15 tons (60 Hz); GEV 10 and 12.5 ton (50 Hz)
81 5/8"
38 7/8"
27 1/8"
1/8
24 VOLT
1 1/8"
O.D.
WCI mounting
location
36 1/4"
6 7/8"
4 3/4"
15 7/8"
49 1/8"
20 1/2"
31 1/2"
67 5/8"
31 1/2"
CONTROL
BOX ACCESS
74 1/2"
TOP VIEW
18 5/8"
10"
W.O. 1 1/2" NPTI
DRAIN 3/4" NPTI
12 1/2"
23 1/2
1"
HIGH VOLTAGE
7/8" (22) O.D.
SIDE VIEW
FRONT VIEW
2 3/8"
W.I. 1 1/2"
RETURN AIR OPENING
NPTI
2 5/8"
4 1/4"
38 WSHP-SVX01Q-EN
Page 39
Unit Dimensions
Figure 30. Front return/top supply
36 1/4"
4 3/4"
24 VOLT
1 1/8" O.D.
WCI mounting
location
6 7/8"
20 1/2"
(a)
GEV 12.5 to 15 tons (60 Hz); GEV 10 and 12.5 ton (50 Hz)
31 1/2"
74 1/2"
81 5/8"
TOP VIEW
18 5/8"
31 1/2"
38 7/8"
68"
27 1/8"
27
CONTROL
BOX ACCESS
15 7/8"
10"
14 3/8"
W.O. 1 1/2" NPTI
DRAIN 3/4" NPTI
12 1/2"
23 1/2
HIGH VOLTAGE 7/8" O.D.
2 3/8"
SIDE VIEW
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
1"
FRONT VIEW
SUPPLY OPENING WITH 1" DUCT FLANGE
W.I. 1 1/2"
NPTI
2 5/8"
4 1/4"
RETURN AIR OPENING
WSHP-SVX01Q-EN 39
Page 40
Unit Dimensions
1 /2
"
7
Figure 31. Back return/top supply
36 1/4"
38 7/8"
(a)
GEV 12.5 to 15 ton (60 Hz); GEV 10 and 12.5 ton (50 Hz)
81 5/8"
4 3/4"
31 1/2"
74 1/2"
TOP VIEW
18 5/8"
31 1/2"
68"
14 3/8"
10"
15
15 7/8"
W.O. 1 1/2" NPTI
DRAIN 3/4" NPTI
1"
27 1/8"
1/8
24 VOLT
1 1/8"
WCI mounting
O.D.
HIGH VOLTAGE
7/8" O.D.
SIDE VIEW
location
6 7/8"
20 1/2"
2 3/8"
FRONT VIEW
RETURN AIR OPENING
CONTROL
BOX ACCESS
W.I. 1 1/2"
NPTI
2 5/8"
4 1/4"
12 1/2"
SUPPLY OPENING WITH 1" DUCT FLANGE
23 1/2
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
40 WSHP-SVX01Q-EN
Page 41
Unit Dimensions
/2
Figure 32. Front return/back supply
36 1/4"
4 3/4"
24 VOLT
B
D
WCI mounting
location
1 1/8" O.D.
67 5/8"
6 7/8"
20 1/2"20 1
(a)
GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
31 1/2"
6 1/4"
74 1/2"
81 5/8"
TOP VIEW
C
AA
38 7/8"
27 1/8"
19 1/8”
CONTROL
BOX ACCESS
W.O . 2" NPTI
DRAIN 3/4" NPTI
12 1/2"
E
HIGH VOLTAGE
7/8" O.D.
SIDE VIEW
2 3/8"
1"
FRONT VIEW
W.I . 2"
NPTI
2 5/8"
4 1/4"
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 22. Dimensional data front return/back supply GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C D E
20 ton 15 ton 15-5/8 in. 13-1/2 in. 12 in. 51-5/8 in. 20-7/8 in.
25 ton Std Static 20 ton Std Static 14-3/4 in. 15-7/8 in. 13-7/8 in. 49-1/8 in. 23-1/2 in.
25 ton High Static 20 ton High Static 15-5/8 in. 13-1/2 in. 12 in. 51-5/8 in. 23-1/2 in.
WSHP-SVX01Q-EN 41
Page 42
Unit Dimensions
6
2
"
Figure 33. Back return/front supply
4 3/4"
38 7/8"
27 1/8"
8
24 VOLT
1 1/8"
O.D.
WCI mounting
location
36 1/4"
6 7/8"
20 1/2"
0 1/2"
31 1/2"
B
67 5/8"
D
(a)
GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
81 5/8"
74 1/2"
6 1/4"
TOP VIE W
C
19 1/8"
CONTROL
BOX ACCESS
AA
W.O . 2" NPTI
DRAIN 3/4" NPTI
12 1/2"
E
1"
HIGH VOLTAGE
7/8" O.D.
2 3/8"
FRONT VIEW
W.I . 2"
NPTI
2 5/8"
4 1/4"
SIDE VIEW
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 23. Dimensional data back return/front supply GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C D E
20 ton 15 ton 15-5/8 in. 13-1/2 in. 12 in. 51-5/8 in. 20-7/8 in.
25 ton Std Static 20 ton Std Static 14-3/4 in. 15-7/8 in. 13-7/8 in. 49-1/8 in. 23-1/2 in.
25 ton High Static 20 ton High Static 15-5/8 in. 13-1/2 in. 12 in. 51-5/8 in. 23-1/2 in.
42 WSHP-SVX01Q-EN
Page 43
Unit Dimensions
"
Figure 34. Front return/top supply
6 7/8"
0 1/2 20 1/2"
4 3/4"
38 7/8"
27 1/8"
27
31 1/2"
68"
24 VOLT
1 1/8"
O.D.
WCI mounting
location
36 1/4"
(a)
GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
B
1 1/4"
6 1/4"
74 1/2"
81 5/8"
TOP VIE W
C
19 1/8"
CONTROL
BOX ACCESS
A
A
W.O . 2" NPTI
DRAIN 3/4" NPTI
12 1/2"
D
HIGH VOLTAGE 7/8" O.D.
2 3/8"
1"
(25.4)
FRONT VIEW
W.I . 2"
NPTI
2 5/8"
4 1/4"
SIDE VIEW
SUPPLY OPENINGS WITH 1" DUCT FLANGE
RETURN AIR OPENING
(a)NEC requires that the GEV072-300 front return must be a non-ducted return.
Table 24. Dimensional data front return/top supply GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
Unit (60 Hz) Unit (50 Hz) A B C D
20 ton 15 ton 15-5/8 in. 13-1/2 in. 12 in. 20-7/8 in.
25 ton Std Static 20 ton Std Static 14-3/4 in. 15-7/8 in. 13-7/8 in. 23-1/2 in.
25 ton High Static 20 ton High Static 15-5/8 in. 13-1/2 in. 12 in. 23-1/2 in.
WSHP-SVX01Q-EN 43
Page 44
Unit Dimensions
8
/
"
B
/
Figure 35. Back return/top supply
4
3/4"
38 7/8"
27 1/8"
24 VOLT
1 1/8"
O.D.
WCI mounting
location
36 1/4"
31 1/2"
6 7/8"
2
0 1 20 1/2"
(a)
GEV 20 and 25 ton (60 Hz); GEV 15 and 20 ton (50 Hz)
81 5/8"
74 1/2"
B
6 1/4"
TOP VIE W
C
A
W.O . 2" NPTI
DRAIN 3/4" NPTI
12 1/2"
6
68"
19 1/8"
CONTROL
BOX ACCESS
A
1 1/4"
1 1
D
1"
HIGH VOLTAGE 7/8" O.D.
2 3/8"
FRONT VIEW
W.I . 2"
NPTI
2 5/8"
4 1/4"
SIDE VIEW
RETURN AIR OPENING
SUPPLY OPENING WITH 1" DUCT FLANGE
(a)NEC requires GEV072-300 front return must be non-ducted return.
Table 25. Dimensional data back return/top supply GEV 20 and 25 ton (240 and 300) 60 Hz; GEV 15 and 20 ton (180 and
240) 50 Hz
Unit (60 Hz) Unit (50 Hz) A B C D
20 ton 15 ton 15-5/8 in. 13-1/2 in. 12 in. 20-7/8 in.
25 ton Std Static 20 ton Std Static 14-3/4 in. 15-7/8 in. 13-7/8 in. 23-1/2 in.
25 ton High Static 20 ton High Static 15-5/8 in. 13-1/2 in. 12 in. 23-1/2 in.
44 WSHP-SVX01Q-EN
Page 45
Unit Dimensions
Figure 36. Waterside economizer
TOP VIEW
A = TO FIELD
SUPPLY PIPING
B = TO FIELD
RETURN PIPING
(a)
(GEH/EXH)
20"
5/8"
G 1 1/2"
N
H
M
5/8”
FRONT VIEW
5"
K
L
J
(a)Waterside economizer installation requires field piping.
F
2 1/2"
C
D
E
Table 26. Dimensional data waterside economizer (GEH/EXH)
GEH
(60 Hz)
006-015 006-012 1/2 1/2 16-1/8 13-5/8 1-1/2 10-3/4 23 2-1/4 7-1/2 1/2 1 4 18-1/2 018-030 015-024 3/4 3/4 18-1/2 15-5/8 1-1/2 13-3/4 26 3-1/4 6-7/8 1/2 1 4 18-1/2 035-042 030-036 3/4 3/4 21 17-5/8 2-1/4 16-1/2 30 3-3/4 6-1/4 1-1/4 2 4-1/2 23-1/2 048-060 042-060 1 1 23-1/8 19-5/8 2-1/2 19-1/2 34 5-1/4 5-7/8 1-1/4 2 4-1/2 23-1/2
EXH
(60 Hz)
006-015 1/2 1/2 16-1/8 13-5/8 1-1/2 10-3/4 23 2-1/4 7-1/2 1/2 1 4 18-1/2 018-024 3/4 3/4 18-1/2 15-5/8 1-1/2 13-3/4 26 3-1/4 6-7/8 1/2 1 4 18-1/2 030-036 3/4 3/4 21 17-5/8 2-1/4 16-1/2 30 3-3/4 6-1/4 1-1/4 2 4-1/2 23-1/2 042-070 1 1 23-1/8 19-5/8 2-1/2 19-1/2 34 5-1/4 5-7/8 1-1/4 2 4-1/2 23-1/2
GEH
(50 Hz) A NPTI B NPTI C D E F G H J K L M N
EXH
(50 Hz) A NPTI B NPTI C D E F G H J K L M N
WSHP-SVX01Q-EN 45
Page 46
Unit Dimensions
Figure 37. Hanging unit waterside economizer (GEH/EXH)
Table 27. Dimensional data hanging unit waterside economizer (GEH/EXH)
GEH Unit
(60 Hz)
006-015 006-012 38-3/4 18-3/4 21-3/4 17 0 54 lbs 84 lbs 018-030 015-024 44-3/4 21-3/4 24-3/4 21 1 65 lbs 95 lbs 035-042 030-036 48-3/4 23-3/4 28-3/4 21 2 76 lbs 106 lbs 048-060 042-048 56-3/4 31-3/4 32-3/4 25 1 97 lbs 127 lbs
EXH Unit
(60 Hz)
006-015 38-3/4 18-3/4 21-3/4 17 0 54 lbs 84 lbs 018-024 44-3/4 21-3/4 24-3/4 21 1 65 lbs 95 lbs 030-036 48-3/4 23-3/4 28-3/4 21 2 76 lbs 106 lbs 042-070 56-3/4 31-3/4 32-3/4 25 1 97 lbs 127 lbs
GEH Unit
(50 Hz) A B C D E
EXH Unit
(50 Hz) A B C D E
Hanging
Weight
Hanging
Weight
Shipping
Weight
Shipping
Weight
46 WSHP-SVX01Q-EN
Page 47
Unit Dimensions
Figure 38. GEH 6 to 10 tons (60 Hz), GEH 6 to 7.5 tons (50 Hz) - right return with waterside economizer
9 7/8"
18 1/2"
50 5/8"
36"
C
D
E
"B" OD COPPER TO FIELD SUPPLY PIPING
"A" NPTI FOR FIELD RETURN PIPING
23 7/8"
2 1/8"
(a)Field piping required on waterside economizer.
Figure 39. GEH 6 to 10 tons (60 Hz), GEH 6 to 7.5 tons (50 Hz) - left return with waterside economizer
(a)
(a)
9 7/8"
18 1/2"
50 5/8"
24 3/4"
1 1/4"
"B" OD COPPER TO
FIELD SUPPLY PIPING
"A" NPTI FOR
FIELD RETURN PIPING
C
36"
D
E
(a)Field piping required on waterside economizer.
Table 28. Dimensional data GEH 6 to 10 tons (60 Hz), GEH 6 to 7.5 tons (50 Hz), waterside economizer
Hanging
GEH (60 Hz) GEH (50 Hz) A B C D E
072 1-1/4 1-3/8 31 9-7/8 3-7/8 138 lbs 168 lbs 090 072 1-1/4 1-3/8 31 9-7/8 3-7/8 144 lbs 174 lbs 120 090 1-1/2 1-5/8 30-3/4 12-1/2 4-1/2 166 lbs 196 lbs
Weight
Shipping
Weight
WSHP-SVX01Q-EN 47
Page 48
Unit Dimensions
Figure 40. GEH 12.5 to 15 tons (60 Hz), GEH 10 to 12.5 tons (50 Hz), right return with waterside economizer
9 7/8"
56 1/2"
42"
48 3/4"
12"
1 5/8" OD COPPER TO FIELD SUPPLY PIPING
1 1/2" NPTI FOR FIELD RETURN PIPING
(a)
18 1/2"
29 3/4"
2 1/4"
5 3/8"
(a)Field piping required on waterside economizer.
Table 29. Dimensional data GEH 12.5 to 15 tons (60 Hz), GEH 10 to 12.5 tons (50 Hz), right return with waterside
economizer
GEH (60 Hz) GEH (50 Hz) Hanging Weight Shipping Weight
150 120 138 lbs 168 lbs 180 150 144 lbs 174 lbs
48 WSHP-SVX01Q-EN
Page 49
Unit Dimensions
Figure 41. GEH 12.5 to 15 tons (60 Hz), GEH 10 to 12.5 tons (50 Hz), left return with waterside economizer
9 7/8"
18 1/2"
56 1/2"
42"
29 3/4"
2 1/4"
1 5/8" OD COPPER TO
FIELD SUPPLY PIPING
1 1/2" NPTI FOR
FIELD RETURN PIPING
27 1/8"
12"
(a)
5 3/8"
(a)Field piping required on waterside economizer.
Table 30. Dimensional dataGEH 12.5 to15 tons (60Hz), GEH 10 to 12.5tons (50 Hz)- left returnwith waterside economizer
GEH (60 Hz) GEH (50 Hz) Hanging Weight Shipping Weight
150 - 180 120-150 213 lbs 243 lbs
WSHP-SVX01Q-EN 49
Page 50
Unit Dimensions
Figure 42. GEV 6 to 10 tons (60 Hz), 6 and 7.5 tons (50 Hz) - waterside economizer
C
13"
A = TO FIELD RETURN PIPING
B = TO FIELD SUPPLY PIPING
13 1/4"
2 1/4"
Table 31. Dimensional data GEV 6 to 10 tons (60 Hz), 6 and 7.5 tons (50 Hz) - waterside economizer
Hanging
Unit (60 Hz) Unit (50 Hz) A B C
072 1-1/4 1-3/8 4 148 lbs 090 072 1-1/4 1-1/4 4 168 lbs 120 090 1-1/2 1-5/8 4-3/8 207 lbs
Weight
Shipping
Weight
178 lbs 198 lbs 237 lbs
50 WSHP-SVX01Q-EN
Page 51
Figure 43. GEV 12.5 to 25 tons - waterside economizer
Unit Dimensions
13"
D
TOP VIEW
A = TO FIELD RETURN PIPING
B = TO FIELD SUPPLY PIPING
Table 32. Dimensional data GEV 12.5 to 25 tons - waterside economizer
GEV (60 Hz) GEV (50 Hz)
150-180 120-150 1-1/2 1-5/8 15-7/8 4-3/8 275 lbs 305 lbs
240 180 2 2-1/8 16-1/4 4-7/8 310 lbs 340 lbs 300 240 2 2-1/8 16-1/4 4-7/8 395 lbs 425 lbs
WSHP-SVX01Q-EN 51
A
NPTI
C
2 3/4"
FRONT VIEWSIDE VIEW
B
I.D. C D Hanging Weight Shipping Weight
Page 52
Unit Dimensions
Figure 44. Waterside economizer coil piping diagram
Note: (applicable only to 6 to 25 ton models)
Unit Water Outlet
Unit Heat
Exchanger
Unit
Water
Inlet
Port A
WSE Coil
Outlet
TEE
3 Way Valve
WSE Coil
Inlet
WSE
Coil
Port AB
Please match the
entering water
port marking with
the marking label
on the valve prior
to using this
diagram.
Port B
Entering Water
52 WSHP-SVX01Q-EN
Page 53
Weights
Table 33. Unit weights GEH .5 to 5 tons
GEH (60 Hz)
006 195 165 009 195 165 012 203 173 015 203 173 018 268 248 024 285 253 030 285 253 035 318 288 042 318 288 048 428 398 060 428 398
Shipping Weight with
pallet (lbs)
Unit Weight without
Table 34. Unit weights GEV .5 to 5 tons
GEV (60 Hz)
006 195 165 009 195 165 012 203 173 015 203 173 018 268 248 024 285 253 030 285 253 036 308 288 042 308 288 048 396 348 060 396 349
Shipping Weight with
pallet (lbs)
Unit Weight without
pallet (lbs)
pallet (lbs)
Table 36. Unit weights EXH .5 to 6 tons (continued)
EXH (60 Hz)
030 329 299 036 343 313 042 461 431 048 454 424 060 474 444 070 514 484
Shipping Weight with
pallet (lbs)
Unit Weight without
pallet (lbs)
Weight Distribution for Hanging the GEH
and EXH Model
WARNING
Improper Unit Lift!
Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury, and equipment or property-only damage. Test lift unit approximately 24 inches to verify proper center of gravity lift point.To avoid dropping of unit, reposition lifting point if unit is not level.
Approximate weight distribution for proper hangingof the
GEH and EXH unit is indicated by weight distribution in
Figure 45, p. 53.
Tolerance on the weights determined are ±15%.
Figure 45. Weight distribution GEH .5 to 5 tons; EXH .5
to6tons
Table 35. Unit weights EXV .5 to 6 tons
EXV (60 Hz)
006 195 165 009 195 165 012 203 173 015 203 173 018 284 264 024 301 269 030 319 299 036 333 313 042 402 381 048 422 374 060 442 394 070 482 434
Shipping Weight with
pallet (lbs)
Unit Weight without
Table 36. Unit weights EXH .5 to 6 tons
EXH (60 Hz)
006 195 165 009 195 165 012 203 173 015 203 173 018 284 264 024 301 269
Shipping Weight with
pallet (lbs)
Unit Weight without
pallet (lbs)
Figure 46. Weight distribution GEH 6 to 15 tons
pallet (lbs)
WSHP-SVX01Q-EN 53
Page 54
Installation
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
General Installation Checks
The checklist below is a summary of the steps required to
successfully install a commercial unit.This checklist is intended to acquaint the installing personnel with what is required in the installation process. It does not replace the detailed instructions that are in the applicable sections of this manual.
1. Remove packaging and inspect the unit. Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representation.
The GEH/V .5 to 5ton and EXH/V .5 to 6 tonunits have been
anchored to the skid by (2) shipping bolts. The removal of these bolts willrequire a 3/8 (9.7 mm) ratchet with a .5 (12.7 mm) socket.
The GEV 6 to 25 ton units have been anchored to the skid
with (4) angle brackets. Remove these brackets before lifting unit into place.
The GEH 6 to 15 ton units are anchored to the cross brace
of the skid with (4) wood screws. Remove these screws prior to lifting the unit into place.
2. Verify the correct model, options and voltage from the unit nameplate.
3. Pull out all field attached parts (i.e. filter rack, duct collar, filter and mounting screws) from the unit packaging for field mounting.
4. Verify the installation location of the unit will provide the required clearance for proper operation.
5. Remove refrigeration access panel and inspect the unit. Be certain the refrigerant tubing has clearance from adjacent parts.
6. Fabricate and install duct work
7. Install and connect a condensate drain line and trap to the drain connection.
Main Electrical
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
1. Verify the power supply complies with the unit nameplate specifications.
2. Inspect all control panel components; tighten any loose connections.
3. Connect properly sized and protected power supply wiring to a field-supplied/installed disconnect switch and to the main compressor contactor/power block 1K1 (compressor contactor on the .5 to 5 ton) for GEH/ V .5 to 5 tonand EXH/V .5 to 6 ton unitsor 1TB1 for GEH/ V 6 to 25 ton equipment in the unit control panel.
4. Install proper grounding wires to anearth ground. EXH and EXV 460 V units require a neutral (a four wire system).
Note: All field-installed wiring must comply with NEC
and applicable local codes.
Electric Heat Requirements
5. Verify that the power supply complies with the electric heater specifications on the unit and heater nameplate.
6. Inspect the heater junction box and control panel; tighten any loose connections.
7. Check electric heat circuits for continuity.
Low Voltage Wiring Requirements
8. Install the zone sensor or thermostat.
9. Connect properly sized control wiring to the proper termination points between the zone sensor or thermostat and the unit control panel.
Filter Installation
Each unit ships with 1" or 2" throwaway filters. 2" MERV 8 or 2" MERV 13 filters are also available options.The quantity of filters is determined by unit size.The GEH .5 to 5 ton and EXH units require field installation of the 1" or 2" ducted filters rack. All sheet metal bracket, filter and hardware are in a box located onthe side ofthe unit within the unit packaging. All .5 to 25 ton verticals and GEH 6 to 15 ton horizontal units ship with the filter rack and filters factory installed.
Note: Do not operate the unit without filters.
54 WSHP-SVX01Q-EN
Page 55
Installation
Supply-Air Ductwork
Horizontal .5 to 5 ton and EXHF units require duct flanges to be field installed.The duct flange ships in a box on the side of the unit. Install the flange with (8) 3/8 in. factory supplied screws.
Install the 1 in. supply-air duct flange to the vertical and horizontal equipment with the (8) 5/16 in. factory-supplied screws.The duct collar assembly for each unit is shipped with the unit in the same box where the IOM manual is located.
When attaching the field ductwork to the unit, provide a
watertight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork. See Figure 47, p. 55.
Elbows with turning vanes or splitters are recommended to minimize air noise dueto turbulence and to reducestatic pressure.
Figure 47. Flexible supply-air connector (field provided)
GEH supply duct
Supply-Air Boot (Field Supplied)
1-inch Duct Collar (Factory Provided)
Figure 48. Flexible return-air connector (field provided)
GEV return duct
SUPPLY-AIR
RETURN
AIR
Return-Air Boot (Field Provided)
Filter Flange (Factory Provided)
Ducted Panel
The return-air arrangement may be easily converted from
a free return-air system, to a ducted return-air systemwith the addition of a return-air side panel. By replacing the filter racks with the return-air panel, a complete seal from the duct to the unit is possible.The 1.5 duct flange facilitates ease of field connection to the duct system.This accessory is typically used when the return-air filter is placed in a built-in ceiling grille, or placed within a field provided filter rack assembly.
Figure 49. Return-air duct panel
Return-Air Ductwork
Install the 1”-2” adjustable filter rack to the horizontal equipment with the use of (4) 5/16 in. factory supplied screws.The vertical equipment factoryships with the filter rack and filter(s) installed.
When attaching the field ductwork to the unit, provide a
water-tight flexible connector at the unit to prevent operating sounds from transmitting through the ductwork.
Elbows with turning vanes or splitters are recommended to minimize air noise dueto turbulence and to reducestatic pressure.
WSHP-SVX01Q-EN 55
Table 37. Opening size and part number GEH
Unit Size
(60 Hz)
006-015 006-012 17.5 in. 13 in. 4474 1133 0100 018-030 015-024 20.5 in. 16 in. 4474 5628 0100 035-042 030-036 22.5 in. 17 in. 4474 1135 0100 048-060 042-060 26.5 in. 19 in. 4474 1136 0100
Unit Size
(50 Hz) A B
Duct Collar
Part Number
Page 56
Installation
Figure 50. Install return-air duct panel
Unit Top
Install the return­air duct panel to the return-air opening with the six screws provided for the
Unit Top
filter rack assembly.
3 3/4
"
Unit Side
Unit Side
A
DUCT PANEL with 1 1/2"-FLANGE
1"
B
Table 38. Opening size and part number EXH
EXH (60 hz) A (in.) B (in.)
006-015 17-1/2 13 447411330100 018-024 20-1/2 16 447456280100 030-036 22-1/2 17 447411350100 042-070 26-1/2 19 447411360100
Duct Collar Part
Number
Ducted Filter Rack (GEH .5 to 5 ton and EXH .5 to 6 ton only)
Table 39. Ducted filter opening size
Unit Size A (in.) B (in.) C (in.)
GEV 048-060 30.7 26.6 5.5 EXH 006-015 21.1 15.4 5.4 EXH 018-030 24.5 18.4 5.6 EXH 036-042 26.4 19.4 5.5 EXH 048-070 30.7 21.4 5.5
EXV 006-015 20.7 17.1 5.5 EXV 018-030 20.7 23.1 5.5 EXV 036-042 25.7 22.4 4.3 EXV 048-070 30.7 26.6 5.5
Dual Filtration (GEH .5 to 5 ton and EXH .5 to6ton)
Note: The dual-filtration design is typically used in a free-
return application.
The horizontal, GEH and EXH model, allows the installer
flexibility in design applications such as a dual filtration option.With the dual filtration design, the unit will contain a lower static which translates into a decrease in filter maintenance. For installation of a dual filtration accessory for the GEH and EXH model, verify that an extra set of return-air filter racks and filter have been ordered from the factory.This accessory will be shipped separate from the unit, and should be located in a separate box than the unit.
1. Remove the return-air side panel from the GEH and EXH unit.This panel is held in place by screws.
When it is necessary
to have filter access at the unit in a ducted return, a ducted filter rack is available.This option allows access to the filter at the unit.
Vertical unit filter
racks are available in right or left access configurations. Horizontal units are available in top, bottom or side access configurations.
Table 39. Ducted filter opening size
Unit Size A (in.) B (in.) C (in.)
GEH 006-015 21.1 15.4 5.4 GEH 018-030 24.5 18.4 5.6 GEH 035-042 26.4 19.4 5.5 GEH 048-060 30.7 21.4 5.5 GEV 006-015 20.7 17.1 5.5 GEV 018-030 20.7 23.1 5.5 GEV 036-042 25.7 22.4 4.3
Figure 51. Side panel
2. Install the top/bottom filter rack at the new opening.
The adjustable filter rack is held in place with four
screws that once held the panel.
56 WSHP-SVX01Q-EN
Page 57
Installation
Figure 52. Install top/bottom filter rack
3. Install the 1”or 2” filter.
Figure 53. Install filter
unit. All plumbing to the unit should conform per national and local codes and isthe responsibility of the contractor.
Figure 54. Hanging the unit
3/8" ALL-THREAD
(BY OTHERS) 3/8" WASHER / NUT (BY OTHERS)
RETURN-AIR
SUPPLY-AIR
Condensate Drain Connection
Figure 55. Negative pressure system
Sound Attenuation Pad
For sound-sensitive installations, a vibration pad (field provided) should be placed beneath the horizontal or vertical equipment. For the horizontal unit, the pad should be approximately twice the size of the unit foot print. For the vertical unit, the pad shouldbe .5 in. thick, and equal to the overall unit foot print.
Hanging the Horizontal Unit
WARNING
Risk of Unit Dropping!
Failure to follow instruction below could result in death or serious injury.To prevent modules/subassemblies from dropping, ALWAYS place, assemble, and suspend them one at a time.
To hang the horizontal configuration (see Figure 54, p. 57):
1. Install the hanging isolators (located in the return-air section of the unit) into the four hanging brackets.
2. Secure the equipment to a joist, concrete, etc. with the use of 3/8 in. field provided (all-thread) rod. Each corner should contain field provided nuts and washers to complete the hanging installation.
3. Slope horizontal units in two directions.The unit should contain a dual .25-12 pitch toward the drain connection.This will insure proper drainage of the
Install proper trapping to the equipment.The unit drain connection is .75 in. NPT for all GEV .5 to 25 ton and GEH .5 to 5 ton and EXH/V .5to 6 ton models. For 6 to15ton GEH models, the drain connection is .5 in. PVC schedule 40 pipe.
When designing the condensate trap for the water-source
system, it is important to consider the unit draw-thru design requiring negative pressure trapping.
In a properly trapped system, when condensate forms during normal operation, the water level in the trap rises until there is a constant flow. It is imperative to maintain water in the trap and not allow the trap to dry out during heating season. Keeping trap primed at all times will enable the water to flow properly. See Figure 55, p. 57 for appropriate dimensions required in a negative pressure system.
WSHP-SVX01Q-EN 57
Page 58
Installation
Supply/Return Pipe Connections
Figure 56. Supply/return pipe connections
Field Installed Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified
WATER-OUT
WATER-IN
AUTOMATIC BALANCING
HOSE KIT
RETURN TO LOOP
SUPPLY FROM CENTRAL PUMP
Connect the supply and return hoses to the water-inlet (from supply) and water-outlet (to return) of the unit. For vibration isolation, it is recommended that flexible steel braided hoses be installed instead of hard piping the equipment to the main loop system.
Cleaning and Flushing the Water Loop
After the piping system is complete, the flexible hose
connectors should be doubled back to complete the water circuit external to the unit (avoiding trash settle-out in the condenser). An extra pipe may be necessary to connect the hose kits.
1. Water circulation system should be filled with clean water using the water make up connections.
Note: Air vents should be open during filling.
2. With the air vents closed, start the circulating pump and then crack the air vents to bleed off the trapped air, assuring circulation through all components of the system.
Note: Make up water must be available to the system to
replace the volume formerly occupied by the air that is bled off.
3. With the air vented and the watercirculating, the entire system should be checked for leaks with repairs made as required.
4. Operate the supplementary heat system (boiler) making checksper manufacturer’sinstructions. During this operation, visual checks should be made for leaks that may have occurred due to increased heat. Repair as required.
5. Open the system at the lowest point for the initial blow down (making sure the make up water is equal to the water being dumped). Continue blow down until the water leaving the drain runs clear, but not less than 2 hours.
6. Shut down pumps and supplementary heat system. Reconnect the hoses placing the water-to-refrigerant heat exchanger in the water circulating system.
Note: Vents should be open when the pumps and
supplementary heat system are shut down.
58 WSHP-SVX01Q-EN
personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
Verify that the power supply available is compatible with
the unit’s nameplate. Use only copper conductors to connect the power supply to the unit.
Main Unit Power Wiring
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
A field supplied disconnect switch must be installed at or
near the unit in accordance withthe National Electric Code (NEC latest edition).
Location of the applicable electric service entrance for HIGH (line voltage) may be found in the Dimensions section of this manual.
The high-voltage connection is made at the 1K1 contactor
or 1TB1 power block inside the unit control box. See
Figure 57, p. 58. Refer to thecustomer connection diagram
that is shipped with the unit for specific termination points.
Provide proper grounding for the unit in accordance with the local and national codes.
Figure 57. Power wiring example
Page 59
Control PowerTransformer
The 24 V control power transformers are to be used only
with the accessories called out in this manual. A 50 VA transformer is externally fused.Transformers rated greater than 50 VA are equipped with circuit breakers. If a circuit breaker trips, turn OFF all power to the unit before attempting to reset it.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
The transformer is located in the control panel.
Thermostat Location
Figure 58. Thermostat/sensor location
NO
YES
NO
5 Feet
NO
Installation
NOTICE
Component Failure!
Resistance in excess of 3 Ohms per conductor could result in component failure due to insufficient AC voltage supply.
Check all loads and conductors for grounds, shorts, and mis-wiring. Use copper conductors unless otherwise specified. Do not run the AC low-voltage wiring in the same conduit with the high voltage power wiring.
Table 40. 24V AC conductors
Distance from unit to
control Recommended wire size
000-460 ft 18 gauge 461-732 ft 16 gauge
733-1000 ft 14 gauge
Figure 59. Low-voltage connection (GEH/V .5 to 5 ton
and EXH/V
Basic Controls Wall Mounted Thermostat
1TB1
1
24 VAC
2
FAN
3
REVERSING VALVE (COOL)
4
COMPRESSOR & VAR SPD PUMP SOLENOID
5
24 VAC GENERAL ALARM OUTPUT
6
24 VAC COMMON & VAR SPD PUMP SOLENOID
7 8 9 10 11 12 13 14 15 16 17 18
(a)
.5 to 6 ton equipment)
Deluxe Controls Wall Mounted Thermostat
1TB1
1
24 VAC
2
FAN
3
REVERSING VALVE (COOL)
4
COMPRESSOR & VAR SPD PUMP SOLENOID
5 6
24 VAC COMMON & VAR SPD PUMP SOLENOID
7
ELECTRIC HEAT
8 9
24 VAC COMPRESSOR DISABLE INPUT 24 VAC COMPRESSOR DISABLE INPUT
10 11 12 13 14 15
ALARM CONTACT OUTPUT
16
ALARM CONTACT OUTPUT
17 18
Location of the thermostat or zone sensor is an important element of effective room control.
Areas where the thermostat or zone sensor should not be
located include:
Behind doors or corners
Near hot or cold air ducts
Near radiant heat (heat emitted from appliances or the sun)
Near concealed pipes or chimneys
On outside walls or other non conditioned surfaces
In air-flows from adjacent zones or other units.
Controls Using 24 VAC
Before installing any wire, refer to the electrical access locations in the “Unit Dimensions,” p. 13 of this manual.
Ensure that the AC control wiring between the controls and the unit termination point does not exceed 3 Ohms/ conductor for the length of the run.
Deluxe Controls with Reheat
1TB1
1
24 VAC
2
FAN
3
REVERSING VALVE (COOL)
4
COMPRESSOR
5
24 VAC COMMON & VAR SPD PUMP SOLENOID
6 7 8
24 VAC COMPRESSOR DISABLE INPUT
9
24 VAC COMPRESSOR DISABLE INPUT
10
HUMIDISTAT
11
VAR SPD PUMP SOLENOID
12 13 14 15
ALARM CONTACT OUTPUT
16
ALARM CONTACT OUTPUT
17 18
(a)Basic controls not available on EXH/V units
Low-voltage connection diagrams for basic and deluxe 24
V control packages mounted on .5-6 ton equipment sizes
are shown in Figure 59, p. 59.
WSHP-SVX01Q-EN 59
Page 60
Installation
Figure 60. Low-voltage connection (GEH/V 6 to 25 ton)
Deluxe Controls with
-all Heat Pump Units w/ Reheat using X13511090010 (T8511)
1TB2
24 VAC (R)
1
FAN (G)
2
COMPRESSOR 1 (Y1)
3
COMPRESSOR 2 (Y2)
4
REVERSING VALVE (0) & HUMIDISTAT
5
24 VAC COMMON (C) & WATER ISOLATION VA
6
COMPRESSOR DISABLE
7
COMPRESSOR DISABLE
8
ALARM
9
ALARM
10
ELECTRIC HEAT
11
ELECTRIC HEAT
12
HUMIDISTAT
13
WATER ISOLATION VALVE
14
3RD STAGE HEAT (W3)
15
NOT USED
16
Deluxe Controls with
-all Heat Pump Units without Reheat using X13511090010 (T8511)
1TB2
24 VAC (R)
1
FAN (G)
2
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
3
COMPRESSOR 2 (Y2)
4
REVERSING VALVE (0) & HUMIDISTAT
5
24 VAC COMMON (C) & WATER ISOLATION VA
6
COMPRESSOR DISABLE
7
COMPRESSOR DISABLE
8
ALARM
9
ALARM
10
ELECTRIC HEAT
11
ELECTRIC HEAT
12
HUMIDISTAT
13
NOT USED
14
3RD STAGE HEAT (W3)
15
NOT USED
16
Deluxe Controls with
-all Heat Pump Units w/ Reheat
using X13511091010/X13511092010 (T7300)
1TB2
24 VAC (R)
1
FAN (G)
2
COMPRESSOR 1 (Y1)
3
COMPRESSOR 2 (Y2)
4
REVERSING VALVE (0) & HUMIDISTAT
5
24 VAC COMMON (X) & WATER ISOLATION VA
6
COMPRESSOR DISABLE
7
COMPRESSOR DISABLE
8
ALARM
9
ALARM
10
ELECTRIC HEAT
11
ELECTRIC HEAT
12
HUMIDISTAT
13
WATER ISOLATION VALVE
14
3RD STAGE HEAT (W1)
15
NOT USED
16
Deluxe Controls with
-all Heat Pump Units without Reheat
using X13511091010/X13511092010 (T7300)
1TB2
24 VAC (R)
1
FAN (G)
2
COMPRESSOR 1 (Y1) & WATER ISOLATION VA
3
COMPRESSOR 2 (Y2)
4
REVERSING VALVE (0) & HUMIDISTAT
5
24 VAC COMMON (X) & WATER ISOLATION VA
6
COMPRESSOR DISABLE
7
COMPRESSOR DISABLE
8
ALARM
9
ALARM
10
ELECTRIC HEAT
11
ELECTRIC HEAT
12
HUMIDISTAT
13
NOT USED
14
3RD STAGE HEAT (W1)
15
NOT USED
16
Low-voltage connection diagrams for deluxe 24V control packages for these thermostats mounted on 6-25 ton equipment sizes are shown in Figure 60, p. 60.
For controls using DC analog input/outputs, see appropriate installation, operation and diagnostic manuals for connection, CNT-SVX11*-EN (ZN524). For installation, operation and Programming see BAS­SVX065*-EN (UC400).
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
1. Remove service access panel at the unit front.
Figure 61. Service access panel
2. Find the blower motor relay.The relay is located in
Figure 62, p. 60.The relay location is consistent in all
control configurations.
Figure 62. Relay location
Blower Motor Speed-Tap Retrofit
Note: For GEH/V .5 to 5 ton units only.
Motors installed in the unit include 4-speed or 3-speed configurations. All voltages include a 4-speed configuration, with the exception of 380V, 415V, 460V which contain a 3-speed arrangement and 575V which contains a 2-speed arrangement.To modify the rpm of the motor, the following steps must be followed.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
60 WSHP-SVX01Q-EN
Removing Speed-tap Wire
3. For units w/o Hot Gas Reheat: Remove undesired speed-tap wire from 1K4 relay at spade 3. Wire tie the lead, to eliminate a short.
4. For units with Hot Gas Reheat: Remove undesired speed-tap wire from 1K8 relay at spade 6. Wire tie the lead, to eliminatea short. Hot Gas Reheat requires both speed taps to be adjusted toenable reheat as the lower speed tap.
Page 61
Installation
Figure 63. Wiring change
Connecting Desired Speed-tap Wire
5. For units without hot gas reheat, select desired speed­tap wire. Connect desired speed tap wire to 1K4 relay at spade 3.
6. For units with hot gas reheat, select desired speed-tap wire. Connect desired speed tap wire to 1K8 relay at spade 6.
Figure 64. Connecting speed-tap wire
Hole Plug Installation
Figure 65. Hole plug installation
1. Locate two Hayco plastic plugs enclosed with the Installation, Operation, and Maintenance manual.
2. Use these plugs to plug the two shipping bolt holes in the bottom of the GEV*/EXV* units after shipping bolt removal.
Air Flow Adjustment
Note: GEH/V 6 to 25 ton units only.
To increase cfm, loosen the turns open set screw on the
sheave, and turn the sheave clockwise.To decrease cfm, Loosen the turns open set screw on the sheave, and turn the sheave counterclockwise.
To increase belt tension, loosen the adjustment bolt and
pull motor mounting plate back until the belt is tight.
Tighten the adjustment bolt after the belt has reached the
desired tension.
See Figure 66, p. 62 for fan motor and sheave adjustment
7. Install service front panel. Reconnectpower to the unit.
Rotating Components!
WARNING
Table 41. 4-speed motor (115, 208, 230, 265)
Lead Colors
Lead Black Blue Orange Red
Speed High Medium High Medium Low Low
Table 42. 3-speed motor (380, 415, 460)
Lead Colors
Lead Black Blue Orange
Speed High Medium Low
Note: When using the medium or low speed tap, the purple wire must be
jumpered to the high speed tap (blk).
Table 43. 2-speed motor (575)
Lead Colors
Lead Black Blue
Speed High Low
WSHP-SVX01Q-EN 61
Failure to disconnect power before servicing could result in rotating components cutting and slashing technician which could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized.
Page 62
Installation
Figure 66. Fan motor and sheave adjustment
1.Belt
2.Adjustment Bolt and Plate
3.Sheave
1
2
3
Figure 67. ECM control board and dip switch setting
Dip switch to select profile
disconnected when the DIP switch is set,the motor will not be programmed to the new setting.
Profile A = 110% of rated airflow
ProfileB=100%ofrated airflow
Profile C = 90% of rated airflow
Profile D = 80% of rated airflow
Waterside Economizer Installation
Note: GEH .5 to 5 and EXH .5 to 6 ton units.
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
Note: EXH/V .5 to 6 ton high efficiency units only: Units
are shipped from the factory on profile setting B.
To adjust the cfm, disconnect the powerto the unit. Set the
DIP switch located in the control box to the desired profile setting. Connect the power to the unit. If the power is not
The following steps were sequenced to aid in the
installation and mating of a water side economizer to a water-source heat pump (GEH .5 to 5 ton) and (EXH 1.5 to 6 ton).
1. Remove the control side service panel of the water­source heat pump unit.
2. Removerubber isolation grommets from the return-air section. Place them in a convenient location.
3. Attach ducted panel to the water-source heat pump unit with six factory provided screws.This panel is shipped loose with the water-source heat pump but must be field installed to the unit.
Figure 68. Step 3
62 WSHP-SVX01Q-EN
Page 63
Installation
4. Attach the water side economizing unit to the ducted panel of the water-source heat pump with 10-factory provided screws.The economizing package fits to the outside of the of the water-source heat pump.Trane recommends the mating of the systems be made via 3­screws spaced evenly across the top, 3-screws spaced evenly across the bottom (installed immediately after hanging the unit), and 2-screws on each side.
Note: Waterside economizer option is configured for
right return. Left return requires additional field piping.
Figure 69. Step 4
5. Install the 18-inch steel braided hose between the upper most piping connection of the economizer, and the water-in of the heat pump.The hose is shipped loose with the water-side economizer.
Figure 71. Step 6
7. Verify the control board for the water side economizer is located at the back of the control box.The temperature rating of this board is factory set to 55ºF.
For units with boilerless (electric heat) control and water side economizer, the boilerless control board is factory set to 45ºF.
Figure 72. Step 7
Figure 70. Step 5
6. Install the SUPPLY and RETURN hoses to the:
a. 2-position valve’s threaded connection
b. water-out threaded connection of the water-source
heat pump
8. Thread the bulb and wire through the low voltage hole of the water-source heat pump. See Figure 73, p. 63.
Figure 73. Step 8
WSHP-SVX01Q-EN 63
Page 64
Installation
9. Wire-tie the sensor to the water SUPPLY side of the piping (ON, or BEFORE) the 2-position valve. See
Figure 74, p. 64.
Figure 74. Step 9
10. Bundle excess sensor wire, and wire tie the bundle neatly. See Figure 75, p. 64.
Figure 75. Step 10
WHT = 1TB1-15
See Figure 77, p. 64.
Figure 77. Step 12
13. Bundle excess valve wire, and wire tie the bundle neatly. See Figure 78, p. 64.
Figure 78. Step 13
11. Thread the valve’s wire lead through the low voltage hole of the heat pump. See Figure 76, p. 64.
Figure 76. Step 11
12. Wire the valve to the terminal strip according to the unit wire diagram located on the service control panel.
RED = 1TB1-14
BLK = 1TB1-18
64 WSHP-SVX01Q-EN
14. Install control side service panel.
15. Install the hanging isolation grommets (see Figure 79,
p. 64) into the hanging bracketsThe unit isolators were
located in the return-air section of the unit. See Step 2. Isolators for the economizing package are located with the economizer.
Note: GEH .5-5 ton and EXH .5-6 ton.
Figure 79. Step 15
Page 65
Installation
16. Insulate the economizing piping package and the supply/return/by-pass hoses (3-hoses) via field provided pipe insulation. Insulatingthe piping will stop condensation from forming on the pipe and dripping onto the ceiling tiles.
Note: Trane does not provide insulation on the
economizing piping package.This insulation must be field provided and field installed.
Note: Trane does not provide condensate overflow
protection of the waterside economizer.This must be field provided and installed.
17. Install filter rack (top and bottom) to the economizing package.The filter rack is located in the unit’s packaging along with the filter.
18. Hang unit. See Figure 54, p. 57 for hanging of the packaged unit. Bottom screws referenced in Step 4 must be installed at this time.
19. Field pipe the drain lines of the waterside economizer and water-source heat pump together prior to installing a condensate trap (see Figure 80, p. 65.See
Figure 55, p. 57 for proper trapping of condensation.
Figure 80. Step 19
Table 44. Economizer part numbers
GEH Unit 60 HzGEH Unit 50 HzWaterside Economizer Part
Number
006-015 006-012 4474 1690 0100 018-030 015-024 4474 7072 0100 035-042 030-036 4474 1692 0100 048-060 042-048 4474 1693 0100
EXH Unit 60 hzEXH Unit 50 HzWaterside Economizer Part
Number
006-015 4474 1690 0100 018-024 4474 7072 0100 030-036 4474 1692 0100 042-070 4474 1639 0100
Waterside Economizer Installation for GEH
and GEV 6 to 25Ton Models
WARNING
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
1. Remove the filter frame from the unit.
2. Remove the waterside service panel from the unit.
3. Remove the control box service panel from the unit.
4. Remove the economizer and miscellaneous mounting parts from it’s packaging.
5. GEV ONLY: Mount the economizer support angle (4475 1637 0100) found in the economizer packaging in the same holes of the return air filter frame removed in
Step 1.The support angle screws into the unit roof.
6. GEV ONLY: Hang the economizer assembly from the economizer support angle mounted in Step 5.
7. Secure the economizer to theunit using thefour plates (4475 1630 0100) found in the economizer packaging.
Two plates should be applied to each economizer side.
GEV ONLY: Secure the bracket on the bottom of the economizer cabinet to the unit compressor compartment center post.
8. Install the field portion of the water piping and the 3­way valve together.
9. Verify the control board for the waterside economizer is located at the back of the control box.The temperature rating of this board is factory set to 55ºF.
10.Thread the economizer’s entering water temperature sensor (4RT1) through the water-in line of the water­source heat pump upstream from the valve.This sensor is used by the economizer’s 3-way valve to determine if water flow should be directedthrough the waterside economizing coil.
11. Tie wrap the thermistor to the water line (supply side) upstream of the water pipe to the economizer.The thermistor must be situated so that the thermistor is
WSHP-SVX01Q-EN 65
Page 66
Installation
capable of reading the actual entering water temperature regardless of the economizer’s on or off situation.
12. Insulate the thermistor with tubing insulation.
13.Tie wrap each end of the tubing insulation to prevent air filtration.The tie wraps and insulation arelocated in a bag and shipped inside of the unit.
14.Thread the factory wire harness through the low voltage hole of the heatpump to the 3-way valve’s wire harness.
15. Connect the factory installed wire harness to the to the wire harness supplied with the 3-way valve (see
Table 45, p. 66).
Table 45. Actuator/factory harness wire table
Actuator Wire # Color Factory Harness Wire # Color
1 BLK = 25L-Black 2 WHT = 23T-White 3 WHT = 73A-White
16. Bundle excess valve wire, and wire tie the bundle neatly.
17. Install control side service panel to the heat pump.
18. Install the unit filter frame to the economizing inlet.
19. Insulate the economizing piping package with field supplied pipe insulation.Insulating the pipingwill help stop condensation from forming on the pipe.
Notes:
Trane does not provide insulation on the economizing
piping package.This insulation must be field provided and field installed.
Trane does not provide condensate overflow protection of the waterside economizer.This must be field provided and field installed.
20. Install waterside service panel to the heat pump.
21. The economizer condensate linemust be trapped prior to the unit’s drain line.This helps prevent air from being sucked through the drain line causing condensate to spit or build-upin the economizer or unit drain pans. Field pipe the drain lines of the waterside economizer and water-source heat pump together prior to installing a condensate trap. See page
“Condensate Drain Connection,” p. 57 for proper
trapping of condensation.
66 WSHP-SVX01Q-EN
Page 67
Waterside Economizer Start-Up Sequence
1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO.The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data. Water leaving the heat exchanger should be warmer than the entering water temperature (approximately 9-12ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be coolwith no frost observedin the refrigerant circuit.
4. Check the cooling refrigerant pressures against values in Table 53, p. 88.
Note: If cooling mode is activated, and the entering water
temperature of the heat pump falls below 55ºF, the 2-position, water side economizing valve will become energized (open) and compressor operation will halt allowing for free cooling in the space.
5. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.
6. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5-9°F leaving the heat exchanger should be noted.The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values in Table 53, p. 88.
Note: For units with boilerless electric heat option: In
heating mode, if the entering watertemperature of the heat pump falls below 45ºF, the electric heater will be energized, and compressor operation will halt. Once the entering water temperature rises above 50ºF, the boilerless controls returns the unit to normal operation.
11. Set the thermostat to maintain the desired space temperature.
12. Instruct the owner on system operation.
WSHP-SVX01Q-EN 67
Page 68
Waterside Economizer Start-Up Sequence
Table 46. Waterside economizing three-way valve specifications
Unit Size (60 Hz) Unit Size (50 Hz)
GEH006-015 GEH006-012 1/2 FPT 600 psi 200 psi
GEH018-042 GEH015-036 3/4 FPT 600 psi 200 psi
GEH048-060 GEH042-060 1 FPT 600 psi 200 psi
GEV/GEH
6-7.5 Ton
GEV/GEH
10-15 Ton
GEV
20 & 25 Ton
EXH006-015 1/2 FPT 600 psi 200 psi
EXH 018-036 3/4 FPT 600 psi 200 psi
EXH 042-070 1 FPT 600 psi 200 psi
Note: The valve body is constructed from forged brass with nickel plating, with the ball and stem constructed of stainless steel. For other information
pertaining to the economizing water valve, see the valve’s data plate.
GEV
6 Ton
GEV/GEH
7.5-12.5 Ton
GEV
15 & 20 Ton
Size
1-1/4 FPT 600 psi 200 psi
1.5 FPT 600 psi 200 psi
2 FPT 600 psi 200 psi
Valve Conn.
Valve Pres.
Rating
"Valve Close-
off pressure
Valve Temp.
Range Actuator
Non-spring return type
"0ºF to 212ºF
-18ºC to 121ºC
"0ºF to 212ºF
-18ºC to 121ºC
"0ºF to 212ºF
-18ºC to 121ºC
0ºF to 212ºF
-18ºC to 121ºC
0ºF to 212ºF
-18ºC to 121ºC
0ºF to 212ºF
-18ºC to 121ºC
0ºF to 212ºF
-18ºC to 121ºC
0°F to 212°F
-18°C to 121°C
0°F to 212°F
-18°C to 121°C
24 VAC +/- 20%
135 second stroke time
10 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
30 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
23 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
33 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
37 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
57 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
10 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
30 Cv at full port
Non-spring return type
24 VAC +/- 20%
135 second stroke time
23 Cv at full port
68 WSHP-SVX01Q-EN
Page 69
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEH/V006 115/60/1 6.8 5.6 30.0 1 7.5 1.20 1/12 1 8.20 15 0.0 0.0 GEH/V006 208/60/1 3.9 3.3 14.0 1 4.2 0.60 1/12 1 4.73 15 0.0 0.0 GEH/V006 208/60/1 4.5 3.3 14.0 1 4.2 0.60 1/12 1 5.68 15 0.8 3.9 GEH/V006 230/60/1 3.8 3.2 15.0 1 4.2 0.60 1/12 1 4.60 15 0.0 0.0 GEH/V006 230/60/1 4.9 3.2 15.0 1 4.2 0.60 1/12 1 6.18 15 1.0 4.3 GEH/V006 265/60/1 3.0 2.5 11.0 1 3.5 0.52 1/12 1 3.65 15 0.0 0.0 GEH/V006 265/60/1 5.5 2.5 11.0 1 3.5 0.52 1/12 1 6.92 15 1.3 5.0 GEH/V009 115/60/1 7.6 6.4 36.0 1 8.6 1.20 1/12 1 9.20 15 0.0 0.0 GEH/V009 208/60/1 4.3 3.7 16.0 1 4.8 0.60 1/12 1 5.23 15 0.0 0.0 GEH/V009 208/60/1 6.5 3.7 16.0 1 4.8 0.60 1/12 1 8.14 15 1.2 5.9 GEH/V009 230/60/1 4.1 3.5 17.0 1 4.8 0.60 1/12 1 4.98 15 0.0 0.0 GEH/V009 230/60/1 7.1 3.5 17.0 1 4.8 0.60 1/12 1 8.90 15 1.5 6.5 GEH/V009 265/60/1 3.3 2.8 13.0 1 3.7 0.52 1/12 1 4.02 15 0.0 0.0 GEH/V009 265/60/1 8.1 2.8 13.0 1 3.7 0.52 1/12 1 10.08 15 2.0 7.5 GEH/V012 115/60/1 13.7 12.1 58.0 1 16.9 1.57 1/8 1 16.70 25 0.0 0.0 GEH/V012 208/60/1 7.0 6.3 30.0 1 8.8 0.70 1/8 1 8.58 15 0.0 0.0 GEH/V012 208/60/1 8.5 6.3 27.0 1 8.8 0.70 1/8 1 10.67 15 1.6 7.8 GEH/V012 230/60/1 7.0 6.3 30.0 1 8.8 0.70 1/8 1 8.58 15 0.0 0.0 GEH/V012 230/60/1 9.4 6.3 30.0 1 8.8 0.70 1/8 1 11.74 15 2.0 8.7 GEH/V012 265/60/1 5.7 5.0 23.0 1 7.0 0.72 1/8 1 6.97 15 0.0 0.0 GEH/V012 265/60/1 10.7 5.0 23.0 1 7.0 0.72 1/8 1 13.40 15 2.7 10.0 GEH/V015 208/60/1 8.6 7.9 36.0 1 11.1 0.70 1/8 1 10.58 15 0.0 0.0 GEH/V015 208/60/1 10.3 7.9 36.0 1 11.1 0.70 1/8 1 12.89 15 2.0 9.6 GEH/V015 230/60/1 8.6 7.9 36.0 1 11.1 0.70 1/8 1 10.58 15 0.0 0.0 GEH/V015 230/60/1 11.6 7.9 36.0 1 11.1 0.70 1/8 1 14.46 15 2.5 10.9 GEH/V015 265/60/1 7.1 6.4 30.0 1 9.0 0.72 1/8 1 8.72 15 0.0 0.0 GEH/V015 265/60/1 13.2 6.4 30.0 1 9.0 0.72 1/8 1 16.47 20 3.3 12.5 GEH/V018 208/60/1 10.5 9.6 42.0 1 13.4 0.90 1/8 1 12.90 20 0.0 0.0 GEH/V018 208/60/1 12.7 9.6 42.0 1 13.4 0.90 1/8 1 15.91 20 2.5 11.8 GEH/V018 230/60/1 10.5 9.6 42.0 1 13.4 0.90 1/8 1 12.90 20 0.0 0.0 GEH/V018 230/60/1 13.9 9.6 42.0 1 13.4 0.90 1/8 1 17.43 20 3.0 13.0 GEH/V018 265/60/1 8.5 7.7 35.0 1 10.8 0.80 1/8 1 10.43 15 0.0 0.0 GEH/V018 265/60/1 15.9 7.7 35.0 1 10.8 0.80 1/8 1 19.87 20 4.0 15.1 GEH/V024 208/60/1 14.9 12.8 58.3 1 20.0 2.10 1/3 1 18.10 30 0.0 0.0 GEH/V024 208/60/1 17.8 12.8 58.3 1 20.0 2.10 1/3 1 22.22 30 3.3 15.7 GEH/V024 230/60/1 14.9 12.8 58.3 1 20.0 2.10 1/3 1 18.10 30 0.0 0.0 GEH/V024 230/60/1 19.5 12.8 58.3 1 20.0 2.10 1/3 1 24.36 30 4.0 17.4 GEH/V024 265/60/1 11.1 9.6 54.0 1 15.0 1.53 1/3 1 13.53 20 0.0 0.0 GEH/V024 265/60/1 21.5 9.6 54.0 1 15.0 1.53 1/3 1 26.91 30 5.3 20.0 GEH/V024 208/60/3 9.2 7.7 53.7 1 12.0 1.53 1/3 1 11.16 15 0.0 0.0 GEH/V024 208/60/3 10.6 7.7 53.7 1 12.0 1.53 1/3 1 13.22 15 3.3 9.0 GEH/V024 230/60/3 9.8 7.7 53.7 1 12.0 2.10 1/3 1 11.73 15 0.0 0.0 GEH/V024 230/60/3 12.1 7.7 53.7 1 12.0 2.10 1/3 1 15.18 20 4.0 10.0
FLA
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor hpFan
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
WSHP-SVX01Q-EN 69
Page 70
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEH/V024 460/60/3 4.6 3.6 28.0 1 5.6 0.95 1/3 1 5.45 15 0.0 0.0 GEH/V024 460/60/3 7.6 3.6 28.0 1 5.6 0.95 1/3 1 9.50 15 5.3 6.7 GEH/V030 208/60/1 16.2 14.1 73.0 1 22.0 2.10 1/3 1 19.73 30 0.0 0.0 GEH/V030 208/60/1 21.8 14.1 73.0 1 22.0 2.10 1/3 1 27.26 30 4.1 19.7 GEH/V030 230/60/1 16.2 14.1 73.0 1 22.0 2.10 1/3 1 19.73 30 0.0 0.0 GEH/V030 230/60/1 23.8 14.1 73.0 1 22.0 2.10 1/3 1 29.80 30 5.0 21.7 GEH/V030 265/60/1 12.7 11.2 60.0 1 17.5 1.53 1/3 1 15.53 25 0.0 0.0 GEH/V030 265/60/1 26.4 11.2 60.0 1 17.5 1.53 1/3 1 33.04 35 6.6 24.9 GEH/V030 208/60/3 11.0 8.9 58.0 1 13.9 2.10 1/3 1 13.23 20 0.0 0.0 GEH/V030 208/60/3 13.5 8.9 58.0 1 13.9 2.10 1/3 1 16.85 20 4.1 11.4 GEH/V030 230/60/3 11.0 8.9 58.0 1 13.9 2.10 1/3 1 13.23 20 0.0 0.0 GEH/V030 230/60/3 14.7 8.9 58.0 1 13.9 2.10 1/3 1 18.31 20 5.0 12.6 GEH/V030 460/60/3 5.2 4.2 28.0 1 6.5 0.95 1/3 1 6.20 15 0.0 0.0 GEH/V030 460/60/3 9.2 4.2 28.0 1 6.5 0.95 1/3 1 11.54 15 6.6 8.3
GEH035 208/60/1 17.7 14.1 77.0 1 22.0 3.60 1/2 1 21.23 35 0.0 0.0 GEH035 208/60/1 27.2 14.1 77.0 1 22.0 3.60 1/2 1 33.95 35 4.9 23.6 GEH035 230/60/1 17.7 14.1 77.0 1 22.0 3.60 1/2 1 21.23 35 0.0 0.0 GEH035 230/60/1 29.7 14.1 77.0 1 22.0 3.60 1/2 1 37.11 40 6.0 26.1 GEH035 265/60/1 15.0 12.2 72.0 1 19.0 2.77 1/2 1 18.02 30 0.0 0.0 GEH035 265/60/1 32.8 12.2 72.0 1 19.0 2.77 1/2 1 40.96 45 8.0 30.0 GEH035 208/60/3 12.6 9.0 71.0 1 14.0 3.60 1/2 1 14.85 20 0.0 0.0 GEH035 208/60/3 17.2 9.0 71.0 1 14.0 3.60 1/2 1 21.50 25 4.9 13.6 GEH035 230/60/3 12.6 9.0 71.0 1 14.0 3.60 1/2 1 14.85 20 0.0 0.0 GEH035 230/60/3 18.7 9.0 71.0 1 14.0 3.60 1/2 1 23.33 25 6.0 15.1 GEH035 460/60/3 7.3 5.6 38.0 1 8.8 1.70 1/2 1 8.70 15 0.0 0.0 GEH035 460/60/3 11.7 5.6 38.0 1 8.8 1.70 1/2 1 14.60 15 8.0 10.0 GEV036 208/60/1 20.3 16.7 79.0 1 26.0 3.60 1/2 1 24.48 40 0.0 0.0 GEV036 208/60/1 27.2 16.7 79.0 1 26.0 3.60 1/2 1 33.95 40 4.9 23.6 GEV036 230/60/1 20.3 16.7 79.0 1 26.0 3.60 1/2 1 24.48 40 0.0 0.0 GEV036 230/60/1 29.7 16.7 79.0 1 26.0 3.60 1/2 1 37.11 40 6.0 26.1 GEV036 265/60/1 16.3 13.5 72.0 1 21.0 2.77 1/2 1 19.65 30 0.0 0.0 GEV036 265/60/1 32.8 13.5 72.0 1 21.0 2.77 1/2 1 40.96 45 8.0 30.0 GEV036 208/60/3 14.0 10.4 73.0 1 16.3 3.60 1/2 1 16.60 25 0.0 0.0 GEV036 208/60/3 17.2 10.4 73.0 1 16.3 3.60 1/2 1 21.50 25 4.9 13.6 GEV036 230/60/3 14.0 10.4 73.0 1 16.3 3.60 1/2 1 16.60 25 0.0 0.0
GEV036 230/60/3 18.7 10.4 73.0 1 16.3 3.60 1/2 1 23.33 25 6.0 15.1 GEH/V036 380-415/50/3 7.7 6.0 44.0 1 9.3 1.70 1/2 1 9.20 15 0.0 0.0 GEH/V036 380-415/50/3 11.6 6.0 44.0 1 9.3 1.70 1/2 1 14.56 15 7.2 9.9
GEV036 460/60/3 7.5 5.8 38.0 1 9.0 1.70 1/2 1 8.95 15 0.0 0.0
GEV036 460/60/3 11.7 5.8 38.0 1 9.0 1.70 1/2 1 14.60 15 8.0 10.0 GEH/V042 208/60/1 21.5 17.9 112.0 1 28.0 3.60 1/2 1 25.98 40 0.0 0.0 GEH/V042 208/60/1 31.0 17.9 112.0 1 28.0 3.60 1/2 1 38.75 40 5.7 27.4 GEH/V042 230/60/1 21.5 17.9 112.0 1 28.0 3.60 1/2 1 25.98 40 0.0 0.0 GEH/V042 230/60/1 34.0 17.9 112.0 1 28.0 3.60 1/2 1 42.54 45 7.0 30.4 GEH/V042 208/60/3 17.1 13.5 88.0 1 21.1 3.60 1/2 1 20.48 30 0.0 0.0 GEH/V042 208/60/3 19.4 13.5 88.0 1 21.1 3.60 1/2 1 24.28 30 5.7 15.8
FLA
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor hpFan
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
70 WSHP-SVX01Q-EN
Page 71
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEH/V042 230/60/3 17.1 13.5 88.0 1 21.1 3.60 1/2 1 20.48 30 0.0 0.0 GEH/V042 230/60/3 21.2 13.5 88.0 1 21.1 3.60 1/2 1 26.46 30 7.0 17.6 GEH/V042 460/60/3 7.7 6.0 44.0 1 9.3 1.70 1/2 1 9.20 15 0.0 0.0 GEH/V042 460/60/3 13.4 6.0 44.0 1 9.3 1.70 1/2 1 16.72 20 9.3 11.7 GEH/V042 575/60/3 6.2 4.9 34.0 1 7.7 1.31 1/2 1 7.44 15 0.0 0.0 GEH/V048 208/60/1 24.2 21.4 135.0 1 33.4 2.80 1/2 1 29.55 50 0.0 0.0 GEH/V048 208/60/1 34.1 21.4 135.0 1 33.4 2.80 1/2 1 42.56 50 6.5 31.3 GEH/V048 230/60/1 24.2 21.4 135.0 1 33.4 2.80 1/2 1 29.55 50 0.0 0.0 GEH/V048 230/60/1 37.6 21.4 135.0 1 33.4 2.80 1/2 1 46.98 50 8.0 34.8 GEH/V048 208/60/3 17.3 14.5 98.0 1 22.6 2.80 1/2 1 20.93 35 0.0 0.0 GEH/V048 208/60/3 20.8 14.5 98.0 1 22.6 2.80 1/2 1 26.05 35 6.5 18.0 GEH/V048 230/60/3 17.3 14.5 98.0 1 22.6 2.80 1/2 1 20.93 35 0.0 0.0 GEH/V048 230/60/3 22.9 14.5 98.0 1 22.6 2.80 1/2 1 28.60 35 8.0 20.1 GEH/V048 460/60/3 7.7 6.3 55.0 1 9.9 1.40 1/2 1 9.28 15 0.0 0.0 GEH/V048 460/60/3 14.7 6.3 55.0 1 9.9 1.40 1/2 1 18.38 20 10.6 13.3 GEH/V048 575/60/3 7.4 6.0 41.0 1 9.4 1.40 1/2 1 8.90 15 0.0 0.0 GEH/V060 208/60/1 31.7 26.3 134.0 1 41.0 5.40 1 1 38.28 60 0.0 0.0 GEH/V060 208/60/1 36.7 26.3 134.0 1 41.0 5.40 1 1 45.81 60 6.5 31.3 GEH/V060 230/60/1 31.7 26.3 134.0 1 41.0 5.40 1 1 38.28 60 0.0 0.0 GEH/V060 230/60/1 40.2 26.3 134.0 1 41.0 5.40 1 1 50.23 60 8.0 34.8 GEH/V060 208/60/3 21.0 15.6 110.0 1 24.4 5.40 1 1 24.90 40 0.0 0.0 GEH/V060 208/60/3 23.4 15.6 110.0 1 24.4 5.40 1 1 29.30 40 6.5 18.0 GEH/V060 230/60/3 21.0 15.6 110.0 1 24.4 5.40 1 1 24.90 40 0.0 0.0 GEH/V060 230/60/3 25.5 15.6 110.0 1 24.4 5.40 1 1 31.85 40 8.0 20.1 GEH/V060 460/60/3 10.5 7.8 52.0 1 12.1 2.70 1 1 12.45 20 0.0 0.0 GEH/V060 460/60/3 16.0 7.8 52.0 1 12.1 2.70 1 1 20.01 25 10.6 13.3 GEH/V060 575/60/3 8.0 5.8 38.9 1 9.1 2.20 1 1 9.45 15 0.0 0.0
GEH072 208/60/1 39.9 16.7 79 2 26 6.5 1.0 1 44.08 60
GEH072 230/60/1 39.9 16.7 79 2 26 6.5 1.0 1 44.08 60
GEH072 208/60/1 42.7 16.7 79 2 26 9.3 1.5 1 46.88 60
GEH072 230/60/1 42.3 16.7 79 2 26 8.9 1.5 1 46.48 60
GEH072 208/60/1 44.6 16.7 79 2 26 11.2 2.0 1 48.78 60
GEH072 230/60/1 43.6 16.7 79 2 26 10.2 2.0 1 47.78 60
GEH072 208/60/3 24.3 10.4 73 2 16.3 3.5 1.0 1 26.90 35
GEH072 230/60/3 24.6 10.4 73 2 16.3 3.8 1.0 1 27.20 35
GEH072 460/60/3 13.4 5.8 38 2 9 1.8 1.0 1 14.85 20
GEH072 208/60/3 26.4 10.4 73 2 16.3 5.6 1.5 1 29.00 35
GEH072 230/60/3 25.6 10.4 73 2 16.3 4.8 1.5 1 28.20 35
GEH072 460/60/3 14.0 5.8 38 2 9 2.4 1.5 1 15.45 20
GEH072 208/60/3 27.9 10.4 73 2 16.3 7.1 2.0 1 30.50 40
GEH072 230/60/3 27.0 10.4 73 2 16.3 6.2 2.0 1 29.60 40
GEH072 460/60/3 14.7 5.8 38 2 9 3.1 2.0 1 16.15 20
GEH090 208/60/3 28.4
GEH090 230/60/3 28.7
FLA
RLA
(ea)
14.5/
10.4
14.5/
10.4
Comp
LRA
No. of
(ea)
Comp
98/73 2
98/73 2
Cmp MCC
22.6/
16.3
22.6/
16.3
Blower
Motor
Blower
Motor hpFan
FLA
3.5 1.0 1 32.03 45
3.8 1.0 1 32.33 45
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
WSHP-SVX01Q-EN 71
Page 72
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEH090 460/60/3 13.9 6.3/5.8 55/38 2 9.9/9 1.8 1.0 1 15.48 20
GEH090 208/60/3 30.5
GEH090 230/60/3 29.7
GEH090 460/60/3 14.5 6.3/5.8 55/38 2 9.9/9 2.4 1.5 1 16.08 20
GEH090 208/60/3 32.0
GEH090 230/60/3 31.1
GEH090 460/60/3 15.2 6.3/5.8 55/38 2 9.9/9 3.1 2.0 1 16.78 20
GEH090 575/60/3 12.1 6/3.8
GEH090 208/60/3 34.3
GEH090 230/60/3 33.1
GEH090 460/60/3 16.7 6.3 55 2 9.9 4.1 3.0 1 18.28 20
GEH090 575/60/3 13.1 6/3.8
GEH120 208/60/3 37.6 16 110 2 24.9 5.6 1.5 1 41.60 50
GEH120 230/60/3 36.8 16 110 2 24.9 4.8 1.5 1 40.80 50
GEH120 460/60/3 18.0 7.8 52 2 12.1 2.4 1.5 1 19.95 25
GEH120 208/60/3 39.1 16 110 2 24.9 7.1 2.0 1 43.10 50
GEH120 230/60/3 38.2 16 110 2 24.9 6.2 2.0 1 42.20 50
GEH120 460/60/3 18.7 7.8 52 2 12.1 3.1 2.0 1 20.65 25
GEH120 575/60/3 13.7 5.7 38.9 2 8.9 2.3 2.0 1 15.13 20
GEH120 208/60/3 41.4 16 110 2 24.9 9.4 3.0 1 45.40 60
GEH120 230/60/3 40.2 16 110 2 24.9 8.2 3.0 1 44.20 60
GEH120 460/60/3 19.7 7.8 52 2 12.1 4.1 3.0 1 21.65 25
GEH120 575/60/3 14.7 5.7 38.9 2 8.9 3.3 3.0 1 16.13 20
GEH120 208/60/3 46.0 16 110 2 24.9 14.0 5.0 1 50.00 60
GEH120 230/60/3 45.0 16 110 2 24.9 13.0 5.0 1 49.00 60
GEH120 460/60/3 22.1 7.8 52 2 12.1 6.5 5.0 1 24.05 30
GEH120 575/60/3 16.7 5.7 38.9 2 8.9 5.3 5.0 1 18.13 20
GEH150 208/60/3 50.4 22.4 149 2 35 5.6 1.5 1 56.00 70
GEH150 230/60/3 49.6 22.4 149 2 35 4.8 1.5 1 55.20 70
GEH150 460/60/3 23.6 10.6 75 2 16.5 2.4 1.5 1 26.25 35
GEH150 575/60/3 17.3 7.7 54 2 12 1.9 1.5 1 19.23 25
GEH150 208/60/3 51.9 22.4 149 2 35 7.1 2.0 1 57.50 70
GEH150 230/60/3 51.0 22.4 149 2 35 6.2 2.0 1 56.60 70
GEH150 460/60/3 24.3 10.6 75 2 16.5 3.1 2.0 1 26.96 35
GEH150 575/60/3 17.7 7.7 54 2 12 2.3 2.0 1 19.63 25
GEH150 208/60/3 54.2 22.4 149 2 35 9.4 3.0 1 59.80 80
GEH150 230/60/3 53.0 22.4 149 2 35 8.2 3.0 1 58.60 80
GEH150 460/60/3 25.3 10.6 75 2 16.5 4.1 3.0 1 27.95 35
GEH150 575/60/3 18.7 7.7 54 2 12 3.3 3.0 1 20.63 25
GEH150 208/60/3 58.8 22.4 149 2 35 14.0 5.0 1 64.40 80
FLA
RLA
(ea)
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
Comp
LRA
No. of
(ea)
Comp
98/73 2
98/73 2
98/73 2
98/73 2
41/
36.5
98/73 2
98/73 2
41/
36.5
Blower
Cmp
Motor
MCC
22.6/
16.3
22.6/
16.3
22.6/
16.3
22.6/
16.3
9.4/
2
5.9
22.6/
16.3
22.6/
16.3
9.4/
2
5.9
Blower
Motor hpFan
FLA
5.6 1.5 1 34.13 45
4.8 1.5 1 33.33 45
7.1 2.0 1 35.63 50
6.2 2.0 1 34.73 45
2.3 2.0 1 13.60 15
9.4 3.0 1 37.93 50
8.2 3.0 1 36.73 50
3.3 3.0 1 14.60 20
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
72 WSHP-SVX01Q-EN
Page 73
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEH150 230/60/3 57.8 22.4 149 2 35 13.0 5.0 1 63.40 80
GEH150 460/60/3 27.7 10.6 75 2 16.5 6.5 5.0 1 30.35 40
GEH150 575/60/3 20.7 7.7 54 2 12 5.3 5.0 1 22.63 30
GEH180 208/60/3 57.1 25 164 2 39 7.1 2.0 1 63.35 80
GEH180 230/60/3 56.2 25 164 2 39 6.2 2.0 1 62.45 80
GEH180 460/60/3 27.5 12.2 100 2 19 3.1 2.0 1 30.56 40
GEH180 575/60/3 20.3 9 78 2 14 2.3 2.0 1 22.55 30
GEH180 208/60/3 59.4 25 164 2 39 9.4 3.0 1 65.65 90
GEH180 230/60/3 58.2 25 164 2 39 8.2 3.0 1 64.45 80
GEH180 460/60/3 28.5 12.2 100 2 19 4.1 3.0 1 31.55 40
GEH180 575/60/3 21.3 9 78 2 14 3.3 3.0 1 23.55 30
GEH180 208/60/3 64.0 25 164 2 39 14.0 5.0 1 70.25 90
GEH180 230/60/3 63.0 25 164 2 39 13.0 5.0 1 69.25 90
GEH180 460/60/3 30.9 12.2 100 2 19 6.5 5.0 1 33.95 45
GEH180 575/60/3 23.3 9 78 2 14 5.3 5.0 1 25.55 30
GEH180 208/60/3 70.0 25 164 2 39 20.0 7.5 1 76.25 100
GEH180 230/60/3 69.4 25 164 2 39 19.4 7.5 1 75.65 100
GEH180 460/60/3 34.1 12.2 100 2 19 9.7 7.5 1 37.15 45
GEH180 575/60/3 26.0 9 78 2 14 8.0 7.5 1 28.25 35
GEV072 208/60/1 40.0 16.7 79 2 26 6.6 1.0 1 44.13 60
GEV072 230/60/1 39.9 16.7 79 2 26 6.5 1.0 1 44.08 60
GEV072 208/60/1 42.7 16.7 79 2 26 9.3 1.5 1 46.88 60
GEV072 230/60/1 42.3 16.7 79 2 26 8.9 1.5 1 46.48 60
GEV072 208/60/1 44.6 16.7 79 2 26 11.2 2.0 1 48.78 60
GEV072 230/60/1 43.6 16.7 79 2 26 10.2 2.0 1 47.81 60
GEV072 208/60/3 24.3 10.4 73 2 16.3 3.5 1.0 1 26.90 35
GEV072 230/60/3 24.6 10.4 73 2 16.3 3.8 1.0 1 27.20 35
GEV072 460/60/3 13.4 5.8 38 2 9 1.8 1.0 1 14.85 20
GEV072 208/60/3 26.4 10.4 73 2 16.3 5.6 1.5 1 29.00 35
GEV072 230/60/3 25.6 10.4 73 2 16.3 4.8 1.5 1 28.20 35
GEV072 460/60/3 14.0 5.8 38 2 9 2.4 1.5 1 15.45 20
GEV072 208/60/3 27.9 10.4 73 2 16.3 7.1 2.0 1 30.50 40
GEV072 230/60/3 27.0 10.4 73 2 16.3 6.2 2.0 1 29.60 40
GEV072 460/60/3 14.7 5.8 38 2 9 3.1 2.0 1 16.16 20
GEV090 208/60/3 28.4
GEV090 230/60/3 28.7
GEV090 460/60/3 13.9 6.3/5.8 55/38 2 9.9/9 1.8 1.0 1 15.48 20
GEV090 208/60/3 30.5
GEV090 230/60/3 29.7
GEV090 460/60/3 14.5 6.3/5.8 55/38 2 9.9/9 2.4 1.5 1 16.08 20
GEV090 208/60/3 32.0
GEV090 230/60/3 31.1
FLA
RLA
(ea)
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
14.5/
10.4
Comp
LRA
No. of
(ea)
Comp
98/73 2
98/73 2
98/73 2
98/73 2
98/73 2
98/73 2
Cmp MCC
22.6/
16.3
22.6/
16.3
22.6/
16.3
22.6/
16.3
22.6/
16.3
22.6/
16.3
Blower
Motor
Blower
Motor hpFan
FLA
3.5 1.0 1 32.03 45
3.8 1.0 1 32.33 45
5.6 1.5 1 34.13 45
4.8 1.5 1 33.33 45
7.1 2.0 1 35.63 50
6.2 2.0 1 34.73 45
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
WSHP-SVX01Q-EN 73
Page 74
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Heat
Amps
Total
Comp
Unit
Model Volts
GEV090 460/60/3 15.2 6.3/5.8 55/38 2 9.9/9 3.1 2.0 1 16.79 20
GEV090 575/60/3 12.1 6/3.8
GEV090 208/60/3 34.3
GEV090 230/60/3 33.1
GEV090 460/60/3 16.2 6.3/5.8 55/38 2 9.9/9 4.1 3.0 1 17.78 20
GEV090 575/60/3 13.1 6/3.8
GEV120 208/60/3 37.6 16 110 2 24.9 5.6 1.5 1 41.60 50
GEV120 230/60/3 36.8 16 110 2 24.9 4.8 1.5 1 40.80 50
GEV120 460/60/3 18.0 7.8 52 2 12.1 2.4 1.5 1 19.95 25
GEV120 208/60/3 39.1 16 110 2 24.9 7.1 2.0 1 43.10 50
GEV120 230/60/3 38.2 16 110 2 24.9 6.2 2.0 1 42.20 50
GEV120 460/60/3 18.7 7.8 52 2 12.1 3.1 2.0 1 20.66 25
GEV120 575/60/3 13.7 5.7 38.9 2 8.9 2.3 2.0 1 15.13 20
GEV120 208/60/3 41.4 16 110 2 24.9 9.4 3.0 1 45.40 60
GEV120 230/60/3 40.2 16 110 2 24.9 8.2 3.0 1 44.20 60
GEV120 460/60/3 19.7 7.8 52 2 12.1 4.1 3.0 1 21.65 25
GEV120 575/60/3 14.7 5.7 38.9 2 8.9 3.3 3.0 1 16.13 20
GEV120 208/60/3 46.0 16 110 2 24.9 14.0 5.0 1 50.00 60
GEV120 230/60/3 45.0 16 110 2 24.9 13.0 5.0 1 49.00 60
GEV120 460/60/3 22.1 7.8 52 2 12.1 6.5 5.0 1 24.05 30
GEV120 575/60/3 16.7 5.7 38.9 2 8.9 5.3 5.0 1 18.13 20
GEV150 208/60/3 51.9 22.4 149 2 35 7.1 2.0 1 57.50 70
GEV150 230/60/3 51.0 22.4 149 2 35 6.2 2.0 1 56.60 70
GEV150 460/60/3 24.3 10.6 75 2 16.5 3.1 2.0 1 26.96 35
GEV150 575/60/3 17.7 7.7 54 2 12 2.3 2.0 1 19.63 25
GEV150 208/60/3 54.2 22.4 149 2 35 9.4 3.0 1 59.80 80
GEV150 230/60/3 53.0 22.4 149 2 35 8.2 3.0 1 58.60 80
GEV150 460/60/3 25.3 10.6 75 2 16.5 4.1 3.0 1 27.95 35
GEV150 575/60/3 18.7 7.7 54 2 12 3.3 3.0 1 20.63 25
GEV150 208/60/3 58.8 22.4 149 2 35 14.0 5.0 1 64.40 80
GEV150 230/60/3 57.8 22.4 149 2 35 13.0 5.0 1 63.40 80
GEV150 460/60/3 27.7 10.6 75 2 16.5 6.5 5.0 1 30.35 40
GEV150 575/60/3 20.7 7.7 54 2 12 5.3 5.0 1 22.63 30
GEV180 208/60/3 59.4 25 164 2 39 9.4 3.0 1 65.65 90
GEV180 230/60/3 58.2 25 164 2 39 8.2 3.0 1 64.45 80
GEV180 460/60/3 28.5 12.2 100 2 19 4.1 3.0 1 31.55 40
GEV180 575/60/3 21.3 9 78 2 14 3.3 3.0 1 23.55 30
GEV180 208/60/3 64.0 25 164 2 39 14.0 5.0 1 70.25 90
GEV180 230/60/3 63.0 25 164 2 39 13.0 5.0 1 69.25 90
GEV180 460/60/3 30.9 12.2 100 2 19 6.5 5.0 1 33.95 45
GEV180 575/60/3 23.3 9 78 2 14 5.3 5.0 1 25.55 30
GEV180 208/60/3 70.0 25 164 2 39 20.0 7.5 1 76.25 100
GEV180 230/60/3 69.4 25 164 2 39 19.4 7.5 1 75.65 100
FLA
RLA
(ea)
14.5/
10.4
14.5/
10.4
Comp
LRA
No. of
(ea)
Comp
41/
36.5
98/73 2
98/73 2
41/
36.5
Blower
Cmp
Motor
MCC
9.4/
2
5.9
22.6/
16.3
22.6/
16.3
9.4/
2
5.9
Blower
Motor hpFan
FLA
2.3 2.0 1 13.60 15
9.4 3.0 1 37.93 50
8.2 3.0 1 36.73 50
3.3 3.0 1 14.60 20
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
(a)
74 WSHP-SVX01Q-EN
Page 75
Electrical Data
Table 47. Electrical data standard static motors (.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Maximum
(a)
Electric
Amps
Total
Comp
Unit
Model Volts
GEV180 460/60/3 34.1 12.2 100 2 19 9.7 7.5 1 37.15 45
GEV180 575/60/3 26.0 9 78 2 14 8.0 7.5 1 28.25 35
GEV240 208/60/3 74.2 30.1 225 2 47 14.0 5.0 1 81.73 110
GEV240 230/60/3 73.2 30.1 225 2 47 13.0 5.0 1 80.73 110
GEV240 460/60/3 39.9 16.7 114 2 26 6.5 5.0 1 44.08 60
GEV240 575/60/3 29.7 12.2 80 2 19 5.3 5.0 1 32.75 40
GEV240 208/60/3 80.2 30.1 225 2 47 20.0 7.5 1 87.73 110
GEV240 230/60/3 79.6 30.1 225 2 47 19.4 7.5 1 87.13 110
GEV240 460/60/3 43.1 16.7 114 2 26 9.7 7.5 1 47.28 60
GEV240 575/60/3 32.4 12.2 80 2 19 8.0 7.5 1 35.45 45
GEV240 208/60/3 86.2 30.1 225 2 47 26.0 10.0 1 93.73 110
GEV240 230/60/3 85.2 30.1 225 2 47 25.0 10.0 1 92.73 110
GEV240 460/60/3 45.9 16.7 114 2 26 12.5 10.0 1 50.08 60
GEV240 575/60/3 34.4 12.2 80 2 19 10.0 10.0 1 37.45 45
GEV240 208/60/3 97.2 30.1 225 2 47 37.0 15.0 1 106.45 125
GEV240 230/60/3 96.2 30.1 225 2 47 36.0 15.0 1 105.20 125
GEV240 460/60/3 51.4 16.7 114 2 26 18.0 15.0 1 55.90 70
GEV240 575/60/3 38.5 12.2 80 2 19 14.1 15.0 1 42.03 50
GEV300 208/60/3 110.2 48.1 245 2 75 14.0 5.0 1 122.23 150
GEV300 230/60/3 109.2 48.1 245 2 75 13.0 5.0 1 121.23 150
GEV300 460/60/3 43.7 18.6 125 2 29 6.5 5.0 1 48.35 60
GEV300 575/60/3 34.7 14.7 100 2 23 5.3 5.0 1 38.38 50
GEV300 208/60/3 116.2 48.1 245 2 75 20.0 7.5 1 128.23 175
GEV300 230/60/3 115.6 48.1 245 2 75 19.4 7.5 1 127.63 175
GEV300 460/60/3 46.9 18.6 125 2 29 9.7 7.5 1 51.55 70
GEV300 575/60/3 37.4 14.7 100 2 23 8.0 7.5 1 41.08 50
GEV300 208/60/3 122.2 48.1 245 2 75 26.0 10.0 1 134.23 175
GEV300 230/60/3 121.2 48.1 245 2 75 25.0 10.0 1 133.23 175
GEV300 460/60/3 49.7 18.6 125 2 29 12.5 10.0 1 54.35 70
GEV300 575/60/3 39.4 14.7 100 2 23 10.0 10.0 1 43.08 50
GEV300 208/60/3 133.2 48.1 245 2 75 37.0 15.0 1 145.23 175
GEV300 230/60/3 132.2 48.1 245 2 75 36.0 15.0 1 144.23 175
GEV300 460/60/3 55.2 18.6 125 2 29 18.0 15.0 1 59.85 70
GEV300 575/60/3 43.5 14.7 100 2 23 14.1 15.0 1 47.18 60
(a)Applies to .5 to 5 tons units only
FLA
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor hpFan
Motors
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
Heat
(a)
Table 48. Electrical data high static motors .5 to 5 tons
Total
Model
No. Volts
GEH/V006 115/60/1 6.8 5.6 30.0 1 7.5 1.20 1/12 1 8.20 15 0.0 0.0 GEH/V006 208/60/1 3.9 3.3 14.0 1 4.2 0.60 1/12 1 4.73 15 0.0 0.0 GEH/V006 208/60/1 4.5 3.3 14.0 1 4.2 0.60 1/12 1 5.68 15 0.8 3.9 GEH/V006 230/60/1 3.8 3.2 15.0 1 4.2 0.60 1/12 1 4.60 15 0.0 0.0 GEH/V006 230/60/1 4.9 3.2 15.0 1 4.2 0.60 1/12 1 6.18 15 1.0 4.3
WSHP-SVX01Q-EN 75
Unit
FLA
Comp
RLA
(ea)
Comp
LRA (ea)
No. of
Comp.
Cmp MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motor
Num
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
Page 76
Electrical Data
Table 48. Electrical data high static motors .5 to 5 tons (continued)
Model
No. Volts
GEH/V006 265/60/1 3.0 2.5 11.0 1 3.5 0.52 1/12 1 3.65 15 0.0 0.0 GEH/V006 265/60/1 5.5 2.5 11.0 1 3.5 0.52 1/12 1 6.92 15 1.3 5.0 GEH/V009 115/60/1 7.6 6.4 36.0 1 8.6 1.20 1/12 1 9.20 15 0.0 0.0 GEH/V009 208/60/1 4.3 3.7 16.0 1 4.8 0.60 1/12 1 5.23 15 0.0 0.0 GEH/V009 208/60/1 6.5 3.7 16.0 1 4.8 0.60 1/12 1 8.14 15 1.2 5.9 GEH/V009 230/60/1 4.1 3.5 17.0 1 4.8 0.60 1/12 1 4.98 15 0.0 0.0 GEH/V009 230/60/1 7.1 3.5 17.0 1 4.8 0.60 1/12 1 8.90 15 1.5 6.5 GEH/V009 265/60/1 3.3 2.8 13.0 1 3.7 0.52 1/12 1 4.02 15 0.0 0.0 GEH/V009 265/60/1 8.1 2.8 13.0 1 3.7 0.52 1/12 1 10.08 15 2.0 7.5 GEH/V012 115/60/1 13.7 12.1 58.0 1 16.9 1.57 1/8 1 16.70 25 0.0 0.0 GEH/V012 208/60/1 7.0 6.3 30.0 1 8.8 0.70 1/8 1 8.58 15 0.0 0.0 GEH/V012 208/60/1 8.5 6.3 27.0 1 8.8 0.70 1/8 1 10.67 15 1.6 7.8 GEH/V012 230/60/1 7.0 6.3 30.0 1 8.8 0.70 1/8 1 8.58 15 0.0 0.0 GEH/V012 230/60/1 9.4 6.3 30.0 1 8.8 0.70 1/8 1 11.74 15 2.0 8.7 GEH/V012 265/60/1 5.7 5.0 23.0 1 7.0 0.72 1/8 1 6.97 15 0.0 0.0 GEH/V012 265/60/1 10.7 5.0 23.0 1 7.0 0.72 1/8 1 13.40 15 2.7 10.0 GEH/V015 208/60/1 8.6 7.9 36.0 1 11.1 0.70 1/8 1 10.58 15 0.0 0.0 GEH/V015 208/60/1 10.3 7.9 36.0 1 11.1 0.70 1/8 1 12.89 15 2.0 9.6 GEH/V015 230/60/1 8.6 7.9 36.0 1 11.1 0.70 1/8 1 10.58 15 0.0 0.0 GEH/V015 230/60/1 11.6 7.9 36.0 1 11.1 0.70 1/8 1 14.46 15 2.5 10.9 GEH/V015 265/60/1 7.1 6.4 30.0 1 9.0 0.72 1/8 1 8.72 15 0.0 0.0 GEH/V015 265/60/1 13.2 6.4 30.0 1 9.0 0.72 1/8 1 16.47 20 3.3 12.5 GEH/V018 208/60/1 11.7 9.6 42.0 1 13.4 2.10 1/3 1 14.10 20 0.0 0.0 GEH/V018 208/60/1 13.9 9.6 42.0 1 13.4 2.10 1/3 1 17.41 20 2.5 11.8 GEH/V018 230/60/1 11.7 9.6 42.0 1 13.4 2.10 1/3 1 14.10 20 0.0 0.0 GEH/V018 230/60/1 15.1 9.6 42.0 1 13.4 2.10 1/3 1 18.93 20 3.0 13.0 GEH/V018 265/60/1 9.2 7.7 35.0 1 10.8 1.53 1/3 1 11.16 15 0.0 0.0 GEH/V018 265/60/1 16.6 7.7 35.0 1 10.8 1.53 1/3 1 20.78 25 4.0 15.1 GEH/V024 208/60/1 14.9 12.8 58.3 1 20.0 2.10 1/3 1 18.10 30 0.0 0.0 GEH/V024 208/60/1 17.8 12.8 58.3 1 20.0 2.10 1/3 1 22.22 30 3.3 15.7 GEH/V024 230/60/1 14.9 12.8 58.3 1 20.0 2.10 1/3 1 18.10 30 0.0 0.0 GEH/V024 230/60/1 19.5 12.8 58.3 1 20.0 2.10 1/3 1 24.36 30 4.0 17.4 GEH/V024 265/60/1 11.1 9.6 54.0 1 15.0 1.53 1/3 1 13.53 20 0.0 0.0 GEH/V024 265/60/1 21.5 9.6 54.0 1 15.0 1.53 1/3 1 26.91 30 5.3 20.0 GEH/V024 208/60/3 9.2 7.7 53.7 1 12.0 1.53 1/3 1 11.16 15 0.0 0.0 GEH/V024 208/60/3 10.6 7.7 53.7 1 12.0 1.53 1/3 1 13.22 15 3.3 9.0 GEH/V024 230/60/3 9.8 7.7 53.7 1 12.0 2.10 1/3 1 11.73 15 0.0 0.0 GEH/V024 230/60/3 12.1 7.7 53.7 1 12.0 2.10 1/3 1 15.18 20 4.0 10.0 GEH/V024 460/60/3 4.6 3.6 28.0 1 5.6 0.95 1/3 1 5.45 15 0.0 0.0 GEH/V024 460/60/3 7.6 3.6 28.0 1 5.6 0.95 1/3 1 9.50 15 5.3 6.7 GEH/V030 208/60/1 16.2 14.1 73.0 1 22.0 2.10 1/3 1 19.73 30 0.0 0.0 GEH/V030 208/60/1 21.8 14.1 73.0 1 22.0 2.10 1/3 1 27.26 30 4.1 19.7 GEH/V030 230/60/1 16.2 14.1 73.0 1 22.0 2.10 1/3 1 19.73 30 0.0 0.0 GEH/V030 230/60/1 23.8 14.1 73.0 1 22.0 2.10 1/3 1 29.80 30 5.0 21.7 GEH/V030 265/60/1 12.7 11.2 60.0 1 17.5 1.53 1/3 1 15.53 25 0.0 0.0 GEH/V030 265/60/1 26.4 11.2 60.0 1 17.5 1.53 1/3 1 33.04 35 6.6 24.9
Unit
FLA
RLA
(ea)
LRA (ea)
No. of
Comp.
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motor
Num
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
Total
Maximum
Comp
76 WSHP-SVX01Q-EN
Page 77
Table 48. Electrical data high static motors .5 to 5 tons (continued)
Electrical Data
Model
No. Volts
GEH/V030 208/60/3 11.0 8.9 58.0 1 13.9 2.10 1/3 1 13.23 20 0.0 0.0 GEH/V030 208/60/3 13.5 8.9 58.0 1 13.9 2.10 1/3 1 16.85 20 4.1 11.4 GEH/V030 230/60/3 11.0 8.9 58.0 1 13.9 2.10 1/3 1 13.23 20 0.0 0.0 GEH/V030 230/60/3 14.7 8.9 58.0 1 13.9 2.10 1/3 1 18.31 20 5.0 12.6 GEH/V030 460/60/3 5.2 4.2 28.0 1 6.5 0.95 1/3 1 6.20 15 0.0 0.0 GEH/V030 460/60/3 9.2 4.2 28.0 1 6.5 0.95 1/3 1 11.54 15 6.6 8.3
GEH035 208/60/1 17.7 14.1 77.0 1 22.0 3.60 1/2 1 21.23 35 0.0 0.0
GEH035 208/60/1 27.2 14.1 77.0 1 22.0 3.60 1/2 1 33.95 35 4.9 23.6
GEH035 230/60/1 17.7 14.1 77.0 1 22.0 3.60 1/2 1 21.23 35 0.0 0.0
GEH035 230/60/1 29.7 14.1 77.0 1 22.0 3.60 1/2 1 37.11 40 6.0 26.1
GEH035 265/60/1 15.0 12.2 72.0 1 19.0 2.77 1/2 1 18.02 30 0.0 0.0
GEH035 265/60/1 32.8 12.2 72.0 1 19.0 2.77 1/2 1 40.96 45 8.0 30.0
GEH035 208/60/3 12.6 9.0 71.0 1 14.0 3.60 1/2 1 14.85 20 0.0 0.0
GEH035 208/60/3 17.2 9.0 71.0 1 14.0 3.60 1/2 1 21.50 25 4.9 13.6
GEH035 230/60/3 12.6 9.0 71.0 1 14.0 3.60 1/2 1 14.85 20 0.0 0.0
GEH035 230/60/3 18.7 9.0 71.0 1 14.0 3.60 1/2 1 23.33 25 6.0 15.1
GEH035 460/60/3 7.3 5.6 38.0 1 8.8 1.70 1/2 1 8.70 15 0.0 0.0
GEH035 460/60/3 11.7 5.6 38.0 1 8.8 1.70 1/2 1 14.60 15 8.0 10.0
GEV036 208/60/1 20.3 16.7 79.0 1 26.0 3.60 1/2 1 24.48 40 0.0 0.0
GEV036 208/60/1 27.2 16.7 79.0 1 26.0 3.60 1/2 1 33.95 40 4.9 23.6
GEV036 230/60/1 20.3 16.7 79.0 1 26.0 3.60 1/2 1 24.48 40 0.0 0.0
GEV036 230/60/1 29.7 16.7 79.0 1 26.0 3.60 1/2 1 37.11 40 6.0 26.1
GEV036 265/60/1 16.3 13.5 72.0 1 21.0 2.77 1/2 1 19.65 30 0.0 0.0
GEV036 265/60/1 32.8 13.5 72.0 1 21.0 2.77 1/2 1 40.96 45 8.0 30.0
GEV036 208/60/3 14.0 10.4 73.0 1 16.3 3.60 1/2 1 16.60 25 0.0 0.0
GEV036 208/60/3 17.2 10.4 73.0 1 16.3 3.60 1/2 1 21.50 25 4.9 13.6
GEV036 230/60/3 14.0 10.4 73.0 1 16.3 3.60 1/2 1 16.60 25 0.0 0.0
GEV036 230/60/3 18.7 10.4 73.0 1 16.3 3.60 1/2 1 23.33 25 6.0 15.1
GEH/V036 380-415/50/3 7.7 6.0 44.0 1 9.3 1.70 1/2 1 9.20 15 0.0 0.0 GEH/V036 380-415/50/3 11.6 6.0 44.0 1 9.3 1.70 1/2 1 14.56 15 7.2 9.9
GEV036 460/60/3 7.5 5.8 38.0 1 9.0 1.70 1/2 1 8.95 15 0.0 0.0
GEV036 460/60/3 11.7 5.8 38.0 1 9.0 1.70 1/2 1 14.60 15 8.0 10.0
GEH/V042 208/60/1 21.5 17.9 112.0 1 28.0 3.60 1/2 1 25.98 40 0.0 0.0 GEH/V042 208/60/1 31.0 17.9 112.0 1 28.0 3.60 1/2 1 38.75 40 5.7 27.4 GEH/V042 230/60/1 21.5 17.9 112.0 1 28.0 3.60 1/2 1 25.98 40 0.0 0.0 GEH/V042 230/60/1 34.0 17.9 112.0 1 28.0 3.60 1/2 1 42.54 45 7.0 30.4 GEH/V042 208/60/3 17.1 13.5 88.0 1 21.1 3.60 1/2 1 20.48 30 0.0 0.0 GEH/V042 208/60/3 19.4 13.5 88.0 1 21.1 3.60 1/2 1 24.28 30 5.7 15.8 GEH/V042 230/60/3 17.1 13.5 88.0 1 21.1 3.60 1/2 1 20.48 30 0.0 0.0 GEH/V042 230/60/3 21.2 13.5 88.0 1 21.1 3.60 1/2 1 26.46 30 7.0 17.6 GEH/V042 460/60/3 7.7 6.0 44.0 1 9.3 1.70 1/2 1 9.20 15 0.0 0.0 GEH/V042 460/60/3 13.4 6.0 44.0 1 9.3 1.70 1/2 1 16.72 20 9.3 11.7 GEH/V042 575/60/3 6.2 4.9 34.0 1 7.7 1.31 1/2 1 7.44 15 0.0 0.0 GEH/V048 208/60/1 26.8 21.4 135.0 1 33.4 5.40 1 1 32.15 50 0.0 0.0 GEH/V048 208/60/1 36.7 21.4 135.0 1 33.4 5.40 1 1 45.81 50 6.5 31.3 GEH/V048 230/60/1 26.8 21.4 135.0 1 33.4 5.40 1 1 32.15 50 0.0 0.0
Unit
FLA
RLA
(ea)
LRA (ea)
No. of
Comp.
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motor
Num
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
Total
Maximum
Comp
WSHP-SVX01Q-EN 77
Page 78
Electrical Data
Table 48. Electrical data high static motors .5 to 5 tons (continued)
Model
No. Volts
GEH/V048 230/60/1 40.2 21.4 135.0 1 33.4 5.40 1 1 50.23 60 8.0 34.8 GEH/V048 208/60/3 19.9 14.5 98.0 1 22.6 5.40 1 1 23.53 35 0.0 0.0 GEH/V048 208/60/3 23.4 14.5 98.0 1 22.6 5.40 1 1 29.30 35 6.5 18.0 GEH/V048 230/60/3 19.9 14.5 98.0 1 22.6 5.40 1 1 23.53 35 0.0 0.0 GEH/V048 230/60/3 25.5 14.5 98.0 1 22.6 5.40 1 1 31.85 35 8.0 20.1 GEH/V048 460/60/3 9.0 6.3 55.0 1 9.9 2.70 1 1 10.58 15 0.0 0.0 GEH/V048 460/60/3 16.0 6.3 55.0 1 9.9 2.70 1 1 20.01 25 10.6 13.3 GEH/V048 575/60/3 8.2 6.0 41.0 1 9.4 2.20 1 1 9.70 15 0.0 0.0 GEH/V060 208/60/1 31.7 26.3 134.0 1 41.0 5.40 1 1 38.28 60 0.0 0.0 GEH/V060 208/60/1 36.7 26.3 134.0 1 41.0 5.40 1 1 45.81 60 6.5 31.3 GEH/V060 230/60/1 31.7 26.3 134.0 1 41.0 5.40 1 1 38.28 60 0.0 0.0 GEH/V060 230/60/1 40.2 26.3 134.0 1 41.0 5.40 1 1 50.23 60 8.0 34.8 GEH/V060 208/60/3 21.0 15.6 110.0 1 24.4 5.40 1 1 24.90 40 0.0 0.0 GEH/V060 208/60/3 23.4 15.6 110.0 1 24.4 5.40 1 1 29.30 40 6.5 18.0 GEH/V060 230/60/3 21.0 15.6 110.0 1 24.4 5.40 1 1 24.90 40 0.0 0.0 GEH/V060 230/60/3 25.5 15.6 110.0 1 24.4 5.40 1 1 31.85 40 8.0 20.1 GEH/V060 460/60/3 10.5 7.8 52.0 1 12.1 2.70 1 1 12.45 20 0.0 0.0 GEH/V060 460/60/3 16.0 7.8 52.0 1 12.1 2.70 1 1 20.01 25 10.6 13.3 GEH/V060 575/60/3 8.0 5.8 38.9 1 9.1 2.20 1 1 9.45 15 0.0 0.0
Unit
FLA
RLA
(ea)
LRA (ea)
No. of
Comp.
Comp
Cmp MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motor
Num
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
Total
Maximum
Comp
Table 49. Electrical data - ECM motors - .5 to 6 tons EXH*/EXV*
Model
Unit
No. Volts
EXH006 208/60/1 3.70 3.3 14.0 0.40 1/3 4.53 15 0.0 0.0 EXH006 208/60/1 4.34 3.3 14.0 0.40 1/3 5.43 15 0.8 3.9 EXH006 230/60/1 3.60 3.2 15.0 0.40 1/3 4.40 15 0.0 0.0 EXH006 230/60/1 4.75 3.2 15.0 0.40 1/3 5.93 15 1.0 4.3 EXH006 265/60/1 2.90 2.5 11.0 0.40 1/3 3.53 15 0.0 0.0 EXH006 265/60/1 5.42 2.5 11.0 0.40 1/3 6.77 15 1.3 5.0 EXH009 208/60/1 4.30 3.7 16.0 0.60 1/3 5.23 15 0.0 0.0 EXH009 208/60/1 6.51 3.7 16.0 0.60 1/3 8.14 15 1.2 5.9 EXH009 230/60/1 4.10 3.5 17.0 0.60 1/3 4.98 15 0.0 0.0 EXH009 230/60/1 7.12 3.5 17.0 0.60 1/3 8.90 15 1.5 6.5 EXH009 265/60/1 3.40 2.8 13.0 0.60 1/3 4.10 15 0.0 0.0 EXH009 265/60/1 8.15 2.8 13.0 0.60 1/3 10.18 15 2.0 7.5 EXH012 208/60/1 7.02 6.3 30.0 0.72 1/3 8.60 15 0.0 0.0 EXH012 208/60/1 8.56 6.3 27.0 0.72 1/3 10.70 15 1.6 7.8 EXH012 230/60/1 7.02 6.3 30.0 0.72 1/3 8.60 15 0.0 0.0 EXH012 230/60/1 9.42 6.3 30.0 0.72 1/3 11.77 15 2.0 8.7 EXH012 265/60/1 5.72 5.0 23.0 0.72 1/3 6.97 15 0.0 0.0 EXH012 265/60/1 10.72 5.0 23.0 0.72 1/3 13.40 15 2.7 10.0 EXH015 208/60/1 8.79 7.9 36.0 0.89 1/3 10.77 15 0.0 0.0 EXH015 208/60/1 10.51 7.9 36.0 0.89 1/3 13.13 15 2.0 9.6 EXH015 230/60/1 8.79 7.9 36.0 0.89 1/3 10.77 15 0.0 0.0
Total
FLA
Comp
RLA (ea)
Comp
LRA (ea)
Blower
Motor
FLA
Blower
Motor
hp
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat Amps
78 WSHP-SVX01Q-EN
Page 79
Table 49. Electrical data - ECM motors - .5 to 6 tons EXH*/EXV* (continued)
Electrical Data
Model
Unit
No. Volts
EXH015 230/60/1 11.76 7.9 36.0 0.89 1/3 14.70 15 2.5 10.9 EXH015 265/60/1 7.29 6.4 30.0 0.89 1/3 8.89 15 0.0 0.0 EXH015 265/60/1 13.34 6.4 30.0 0.89 1/3 16.68 20 3.3 12.5 EXH018 208/60/1 11.10 9.6 42.0 1.50 1/2 13.50 20 0.0 0.0 EXH018 208/60/1 13.33 9.6 42.0 1.50 1/2 16.66 20 2.5 11.8 EXH018 230/60/1 11.10 9.6 42.0 1.50 1/2 13.50 20 0.0 0.0 EXH018 230/60/1 14.54 9.6 42.0 1.50 1/2 18.18 20 3.0 13.0 EXH018 265/60/1 9.00 7.7 35.0 1.30 1/2 10.93 15 0.0 0.0 EXH018 265/60/1 16.39 7.7 35.0 1.30 1/2 20.49 25 4.0 15.1 EXH024 208/60/1 15.70 13.5 58.3 2.20 1/2 19.08 30 0.0 0.0 EXH024 208/60/1 17.87 13.5 58.3 2.20 1/2 22.34 30 3.3 15.7 EXH024 230/60/1 15.70 13.5 58.3 2.20 1/2 19.08 30 0.0 0.0 EXH024 230/60/1 19.59 13.5 58.3 2.20 1/2 24.49 30 4.0 17.4 EXH024 265/60/1 10.10 9.0 54.0 1.10 1/2 12.35 20 0.0 0.0 EXH024 265/60/1 21.10 9.0 54.0 1.10 1/2 26.38 30 5.3 20.0 EXH030 208/60/1 17.30 14.1 77.0 3.20 1/2 20.83 30 0.0 0.0 EXH030 208/60/1 26.76 14.1 77.0 3.20 1/2 33.45 35 4.9 23.6 EXH030 230/60/1 17.30 14.1 77.0 3.20 1/2 20.83 30 0.0 0.0 EXH030 230/60/1 29.29 14.1 77.0 3.20 1/2 36.61 40 6.0 26.1 EXH030 265/60/1 13.70 10.9 60.0 2.80 1/2 16.43 25 0.0 0.0 EXH030 265/60/1 32.80 10.9 60.0 2.80 1/2 41.00 45 8.0 30.0 EXH036 208/60/1 18.10 14.1 77.0 4.00 3/4 21.63 35 0.0 0.0 EXH036 208/60/1 27.56 14.1 77.0 4.00 3/4 34.45 35 4.9 23.6 EXH036 230/60/1 18.10 14.1 77.0 4.00 3/4 21.63 35 0.0 0.0 EXH036 230/60/1 30.09 14.1 77.0 4.00 3/4 37.61 40 6.0 26.1 EXH036 265/60/1 15.70 12.2 72.0 3.50 3/4 18.75 30 0.0 0.0 EXH036 265/60/1 33.50 12.2 72.0 3.50 3/4 41.88 45 8.0 30.0 EXH036 208/60/3 13.00 9.0 71.0 4.00 3/4 15.25 20 0.0 0.0 EXH036 208/60/3 17.60 9.0 71.0 4.00 3/4 22.00 25 4.9 13.6 EXH036 230/60/3 13.00 9.0 71.0 4.00 3/4 15.25 20 0.0 0.0 EXH036 230/60/3 19.06 9.0 71.0 4.00 3/4 23.83 25 6.0 15.1 EXH036 460/60/3 9.10 5.6 38.0 3.50 3/4 10.50 15 0.0 0.0 EXH036 460/60/3 13.48 5.6 38.0 3.50 3/4 16.85 20 8.0 10.0 EXH042 208/60/1 22.30 17.9 112.0 4.40 3/4 26.78 40 0.0 0.0 EXH042 208/60/1 35.65 17.9 112.0 4.40 3/4 44.56 45 6.5 31.3 EXH042 230/60/1 22.30 17.9 112.0 4.40 3/4 26.78 40 0.0 0.0 EXH042 230/60/1 39.18 17.9 112.0 4.40 3/4 48.98 50 8.0 34.8 EXH042 208/60/3 17.60 13.2 88.0 4.40 3/4 20.90 30 0.0 0.0 EXH042 208/60/3 22.44 13.2 88.0 4.40 3/4 28.05 30 6.5 18.0 EXH042 230/60/3 17.60 13.2 88.0 4.40 3/4 20.90 30 0.0 0.0 EXH042 230/60/3 24.48 13.2 88.0 4.40 3/4 30.60 35 8.0 20.1 EXH042 460/60/3 9.80 6.0 44.0 3.80 3/4 11.30 15 0.0 0.0 EXH042 460/60/3 17.10 6.0 44.0 3.80 3/4 21.38 25 10.6 13.3 EXH048 208/60/1 25.00 19.9 109.0 5.10 3/4 29.98 45 0.0 0.0 EXH048 208/60/1 36.35 19.9 109.0 5.10 3/4 45.44 50 6.5 31.3 EXH048 230/60/1 25.00 19.9 109.0 5.10 3/4 29.98 45 0.0 0.0
Total
FLA
Comp
RLA (ea)
Comp
LRA (ea)
Blower
Motor
FLA
Blower
Motor
hp
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat Amps
Maximum
WSHP-SVX01Q-EN 79
Page 80
Electrical Data
Table 49. Electrical data - ECM motors - .5 to 6 tons EXH*/EXV* (continued)
Model
Unit
No. Volts
EXH048 230/60/1 39.88 19.9 109.0 5.10 3/4 49.85 50 8.0 34.8 EXH048 208/60/3 18.20 13.1 83.1 5.10 3/4 21.48 30 0.0 0.0 EXH048 208/60/3 23.14 13.1 83.1 5.10 3/4 28.93 30 6.5 18.0 EXH048 230/60/3 18.20 13.1 83.1 5.10 3/4 21.48 30 0.0 0.0 EXH048 230/60/3 25.18 13.1 83.1 5.10 3/4 31.48 35 8.0 20.1 EXH048 460/60/3 10.50 6.1 41.0 4.40 3/4 12.03 15 0.0 0.0 EXH048 460/60/3 17.70 6.1 41.0 4.40 3/4 22.13 25 10.6 13.3 EXH060 208/60/1 34.40 26.4 134.0 8.00 1 41.00 60 0.0 0.0 EXH060 208/60/1 39.25 26.4 134.0 8.00 1 49.06 60 6.5 31.3 EXH060 230/60/1 34.40 26.4 134.0 8.00 1 41.00 60 0.0 0.0 EXH060 230/60/1 42.78 26.4 134.0 8.00 1 53.48 60 8.0 34.8 EXH060 208/60/3 24.00 16.0 110.0 8.00 1 28.00 40 0.0 0.0 EXH060 208/60/3 26.04 16.0 110.0 8.00 1 32.55 40 6.5 18.0 EXH060 230/60/3 24.00 16.0 110.0 8.00 1 28.00 40 0.0 0.0 EXH060 230/60/3 28.08 16.0 110.0 8.00 1 35.10 40 8.0 20.1 EXH060 460/60/3 14.70 7.8 52.0 6.90 1 16.65 20 0.0 0.0 EXH060 460/60/3 20.20 7.8 52.0 6.90 1 25.26 30 10.6 13.3 EXH070 208/60/1 37.10 30.1 158.0 7.00 1 44.63 70 0.0 0.0 EXH070 208/60/1 38.25 30.1 158.0 7.00 1 47.81 70 6.5 31.3 EXH070 230/60/1 37.10 30.1 158.0 7.00 1 44.63 70 0.0 0.0 EXH070 230/60/1 41.78 30.1 158.0 7.00 1 52.23 70 8.0 34.8 EXH070 208/60/3 27.50 20.5 155.0 7.00 1 32.63 50 0.0 0.0 EXH070 208/60/3 27.50 20.5 155.0 7.00 1 32.63 50 6.5 18.0 EXH070 230/60/3 27.50 20.5 155.0 7.00 1 32.63 50 0.0 0.0 EXH070 230/60/3 27.50 20.5 155.0 7.00 1 33.85 50 8.0 20.1 EXH070 460/60/3 15.70 9.6 75.0 6.10 1 18.10 25 0.0 0.0 EXH070 460/60/3 19.40 9.6 75.0 6.10 1 24.26 25 10.6 13.3
EXV006 208/60/1 3.76 3.3 14.0 0.46 1/3 4.59 15 0.0 0.0 EXV006 208/60/1 4.40 3.3 14.0 0.46 1/3 5.50 15 0.8 3.9 EXV006 230/60/1 3.66 3.2 15.0 0.46 1/3 4.46 15 0.0 0.0 EXV006 230/60/1 4.81 3.2 15.0 0.46 1/3 6.01 15 1.0 4.3 EXV006 265/60/1 2.96 2.5 11.0 0.46 1/3 3.59 15 0.0 0.0 EXV006 265/60/1 5.48 2.5 11.0 0.46 1/3 6.85 15 1.3 5.0 EXV009 208/60/1 4.31 3.7 16.0 0.61 1/3 5.24 15 0.0 0.0 EXV009 208/60/1 6.52 3.7 16.0 0.61 1/3 8.15 15 1.2 5.9 EXV009 230/60/1 4.11 3.5 17.0 0.61 1/3 4.99 15 0.0 0.0 EXV009 230/60/1 7.13 3.5 17.0 0.61 1/3 8.91 15 1.5 6.5 EXV009 265/60/1 3.41 2.8 13.0 0.61 1/3 4.11 15 0.0 0.0 EXV009 265/60/1 8.16 2.8 13.0 0.61 1/3 10.20 15 2.0 7.5 EXV012 208/60/1 6.91 6.3 30.0 0.61 1/3 8.49 15 0.0 0.0 EXV012 208/60/1 8.45 6.3 27.0 0.61 1/3 10.56 15 1.6 7.8 EXV012 230/60/1 6.91 6.3 30.0 0.61 1/3 8.49 15 0.0 0.0 EXV012 230/60/1 9.31 6.3 30.0 0.61 1/3 11.63 15 2.0 8.7 EXV012 265/60/1 5.61 5.0 23.0 0.61 1/3 6.86 15 0.0 0.0 EXV012 265/60/1 10.61 5.0 23.0 0.61 1/3 13.26 15 2.7 10.0 EXV015 208/60/1 8.73 7.9 36.0 0.83 1/3 10.71 15 0.0 0.0
Total
FLA
Comp
RLA (ea)
Comp
LRA (ea)
Blower
Motor
FLA
Blower
Motor
hp
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat Amps
Maximum
80 WSHP-SVX01Q-EN
Page 81
Table 49. Electrical data - ECM motors - .5 to 6 tons EXH*/EXV* (continued)
Electrical Data
Model
Unit
No. Volts
EXV015 208/60/1 10.45 7.9 36.0 0.83 1/3 13.06 15 2.0 9.6 EXV015 230/60/1 8.73 7.9 36.0 0.83 1/3 10.71 15 0.0 0.0 EXV015 230/60/1 11.70 7.9 36.0 0.83 1/3 14.62 15 2.5 10.9 EXV015 265/60/1 7.23 6.4 30.0 0.83 1/3 8.83 15 0.0 0.0 EXV015 265/60/1 13.28 6.4 30.0 0.83 1/3 16.60 20 3.3 12.5 EXV018 208/60/1 11.10 9.6 42.0 1.50 1/2 13.50 20 0.0 0.0 EXV018 208/60/1 13.33 9.6 42.0 1.50 1/2 16.66 20 2.5 11.8 EXV018 230/60/1 11.10 9.6 42.0 1.50 1/2 13.50 20 0.0 0.0 EXV018 230/60/1 14.54 9.6 42.0 1.50 1/2 18.18 20 3.0 13.0 EXV018 265/60/1 9.00 7.7 35.0 1.30 1/2 10.93 15 0.0 0.0 EXV018 265/60/1 16.39 7.7 35.0 1.30 1/2 20.49 25 4.0 15.1 EXV024 208/60/1 15.70 13.5 58.3 2.20 1/2 19.08 30 0.0 0.0 EXV024 208/60/1 17.87 13.5 58.3 2.20 1/2 22.34 30 3.3 15.7 EXV024 230/60/1 15.70 13.5 58.3 2.20 1/2 19.08 30 0.0 0.0 EXV024 230/60/1 19.59 13.5 58.3 2.20 1/2 24.49 30 4.0 17.4 EXV024 265/60/1 10.10 9.0 54.0 1.10 1/2 12.35 20 0.0 0.0 EXV024 265/60/1 21.10 9.0 54.0 1.10 1/2 26.38 30 5.3 20.0 EXV030 208/60/1 17.30 14.1 77.0 3.20 1/2 20.83 30 0.0 0.0 EXV030 208/60/1 26.76 14.1 77.0 3.20 1/2 33.45 35 4.9 23.6 EXV030 230/60/1 17.30 14.1 77.0 3.20 1/2 20.83 30 0.0 0.0 EXV030 230/60/1 29.29 14.1 77.0 3.20 1/2 36.61 40 6.0 26.1 EXV030 265/60/1 13.70 10.9 60.0 2.80 1/2 16.43 25 0.0 0.0 EXV030 265/60/1 32.80 10.9 60.0 2.80 1/2 41.00 45 8.0 30.0 EXV036 208/60/1 18.10 14.1 77.0 4.00 3/4 21.63 35 0.0 0.0 EXV036 208/60/1 27.56 14.1 77.0 4.00 3/4 34.45 35 4.9 23.6 EXV036 230/60/1 18.10 14.1 77.0 4.00 3/4 21.63 35 0.0 0.0 EXV036 230/60/1 30.09 14.1 77.0 4.00 3/4 37.61 40 6.0 26.1 EXV036 265/60/1 15.70 12.2 72.0 3.50 3/4 18.75 30 0.0 0.0 EXV036 265/60/1 33.50 12.2 72.0 3.50 3/4 41.88 45 8.0 30.0 EXV036 208/60/3 13.00 9.0 71.0 4.00 3/4 15.25 20 0.0 0.0 EXV036 208/60/3 17.60 9.0 71.0 4.00 3/4 22.00 25 4.9 13.6 EXV036 230/60/3 13.00 9.0 71.0 4.00 3/4 15.25 20 0.0 0.0 EXV036 230/60/3 19.06 9.0 71.0 4.00 3/4 23.83 25 6.0 15.1 EXV036 460/60/3 9.10 5.6 38.0 3.50 3/4 10.50 15 0.0 0.0 EXV036 460/60/3 13.48 5.6 38.0 3.50 3/4 16.85 20 8.0 10.0 EXV042 208/60/1 22.30 17.9 112.0 4.40 3/4 26.78 40 0.0 0.0 EXV042 208/60/1 35.65 17.9 112.0 4.40 3/4 44.56 45 6.5 31.3 EXV042 230/60/1 22.30 17.9 112.0 4.40 3/4 26.78 40 0.0 0.0 EXV042 230/60/1 39.18 17.9 112.0 4.40 3/4 48.98 50 8.0 34.8 EXV042 208/60/3 17.60 13.2 88.0 4.40 3/4 20.90 30 0.0 0.0 EXV042 208/60/3 22.44 13.2 88.0 4.40 3/4 28.05 30 6.5 18.0 EXV042 230/60/3 17.60 13.2 88.0 4.40 3/4 20.90 30 0.0 0.0 EXV042 230/60/3 24.48 13.2 88.0 4.40 3/4 30.60 35 8.0 20.1 EXV042 460/60/3 9.80 6.0 44.0 3.80 3/4 11.30 15 0.0 0.0 EXV042 460/60/3 17.10 6.0 44.0 3.80 3/4 21.38 25 10.6 13.3 EXV048 208/60/1 25.00 19.9 109.0 5.10 3/4 29.98 45 0.0 0.0
Total
FLA
Comp
RLA (ea)
Comp
LRA (ea)
Blower
Motor
FLA
Blower
Motor
hp
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat Amps
Maximum
WSHP-SVX01Q-EN 81
Page 82
Electrical Data
Table 49. Electrical data - ECM motors - .5 to 6 tons EXH*/EXV* (continued)
Model
Unit
No. Volts
EXV048 208/60/1 36.35 19.9 109.0 5.10 3/4 45.44 50 6.5 31.3 EXV048 230/60/1 25.00 19.9 109.0 5.10 3/4 29.98 45 0.0 0.0 EXV048 230/60/1 39.88 19.9 109.0 5.10 3/4 49.85 50 8.0 34.8 EXV048 208/60/3 18.20 13.1 83.1 5.10 3/4 21.48 30 0.0 0.0 EXV048 208/60/3 23.14 13.1 83.1 5.10 3/4 28.93 30 6.5 18.0 EXV048 230/60/3 18.20 13.1 83.1 5.10 3/4 21.48 30 0.0 0.0 EXV048 230/60/3 25.18 13.1 83.1 5.10 3/4 31.48 35 8.0 20.1 EXV048 460/60/3 10.50 6.1 41.0 4.40 3/4 12.03 15 0.0 0.0 EXV048 460/60/3 17.70 6.1 41.0 4.40 3/4 22.13 25 10.6 13.3 EXV060 208/60/1 34.40 26.4 134.0 8.00 1 41.00 60 0.0 0.0 EXV060 208/60/1 39.25 26.4 134.0 8.00 1 49.06 60 6.5 31.3 EXV060 230/60/1 34.40 26.4 134.0 8.00 1 41.00 60 0.0 0.0 EXV060 230/60/1 42.78 26.4 134.0 8.00 1 53.48 60 8.0 34.8 EXV060 208/60/3 24.00 16.0 110.0 8.00 1 28.00 40 0.0 0.0 EXV060 208/60/3 26.04 16.0 110.0 8.00 1 32.55 40 6.5 18.0 EXV060 230/60/3 24.00 16.0 110.0 8.00 1 28.00 40 0.0 0.0 EXV060 230/60/3 28.08 16.0 110.0 8.00 1 35.10 40 8.0 20.1 EXV060 460/60/3 14.70 7.8 52.0 6.90 1 16.65 20 0.0 0.0 EXV060 460/60/3 20.20 7.8 52.0 6.90 1 25.26 30 10.6 13.3 EXV070 208/60/1 37.10 30.1 158.0 7.00 1 44.63 70 0.0 0.0 EXV070 208/60/1 38.25 30.1 158.0 7.00 1 47.81 70 6.5 31.3 EXV070 230/60/1 37.10 30.1 158.0 7.00 1 44.63 70 0.0 0.0 EXV070 230/60/1 41.78 30.1 158.0 7.00 1 52.23 70 8.0 34.8 EXV070 208/60/3 27.50 20.5 155.0 7.00 1 32.63 50 0.0 0.0 EXV070 208/60/3 27.50 20.5 155.0 7.00 1 32.63 50 6.5 18.0 EXV070 230/60/3 27.50 20.5 155.0 7.00 1 32.63 50 0.0 0.0 EXV070 230/60/3 27.50 20.5 155.0 7.00 1 33.85 50 8.0 20.1 EXV070 460/60/3 15.70 9.6 75.0 6.10 1 18.10 25 0.0 0.0 EXV070 460/60/3 19.40 9.6 75.0 6.10 1 24.26 25 10.6 13.3
Total
FLA
Comp
RLA (ea)
Comp
LRA (ea)
Blower
Motor
FLA
Blower
Motor
hp
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Electric
Heat kW
Electric
Heat Amps
Maximum
Table 50. Electrical data two speed blower motor 6 to 25 tons
Model
No. Volts
GEH072 208/60/3 24.1 10.4 73 2 16.3 3.3 1.0 1 26.70 35 GEH072 230/60/3 23.8 10.4 73 2 16.3 3.0 1.0 1 26.40 35 GEH072 460/60/3 13.1 5.8 38 2 9 1.5 1.0 1 14.55 20 GEH072 208/60/3 25.7 10.4 73 2 16.3 4.9 1.5 1 28.30 35 GEH072 230/60/3 25.2 10.4 73 2 16.3 4.4 1.5 1 27.80 35 GEH072 460/60/3 13.8 5.8 38 2 9 2.2 1.5 1 15.25 20 GEH072 208/60/3 27.5 10.4 73 2 16.3 6.7 2.0 1 30.10 40 GEH072 230/60/3 26.9 10.4 73 2 16.3 6.1 2.0 1 29.50 35 GEH072 460/60/3 14.7 5.8 38 2 9 3.1 2.0 1 16.15 20 GEH090 208/60/3 28.2 14.5/10.4 98/73 2 22.6/16.3 3.3 1.0 1 31.83 45 GEH090 230/60/3 27.9 14.5/10.4 98/73 2 22.6/16.3 3.0 1.0 1 31.53 45
82 WSHP-SVX01Q-EN
Total
FLA
Comp RLA
(ea)
Comp
LRA
(ea)
No. of
Comp. Cmp MCC
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
No.
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Page 83
Table 50. Electrical data two speed blower motor 6 to 25 tons (continued)
Electrical Data
Model
No. Volts
GEH090 460/60/3 13.6 6.3/5.8 55/38 2 9.9/9 1.5 1.0 1 15.18 20 GEH090 208/60/3 29.8 14.5/10.4 98/73 2 22.6/16.3 4.9 1.5 1 33.43 45 GEH090 230/60/3 29.3 14.5/10.4 98/73 2 22.6/16.3 4.4 1.5 1 32.93 45 GEH090 460/60/3 14.3 6.3/5.8 55/38 2 9.9/9 2.2 1.5 1 15.88 20 GEH090 208/60/3 31.6 14.5/10.4 98/73 2 22.6/16.3 6.7 2.0 1 35.23 45 GEH090 230/60/3 31.0 14.5/10.4 98/73 2 22.6/16.3 6.1 2.0 1 34.63 45 GEH090 460/60/3 15.2 6.3/5.8 55/38 2 9.9/9 3.1 2.0 1 16.78 20 GEH090 208/60/3 33.7 14.5/10.4 98/73 2 22.6/16.3 8.8 3.0 1 37.33 50 GEH090 230/60/3 32.9 14.5/10.4 98/73 2 22.6/16.3 8.0 3.0 1 36.53 50 GEH090 460/60/3 16.6 6.3 55 2 9.9 4.0 3.0 1 18.18 20 GEH120 208/60/3 36.9 16 110 2 24.9 4.9 1.5 1 40.90 50 GEH120 230/60/3 36.4 16 110 2 24.9 4.4 1.5 1 40.40 50 GEH120 460/60/3 17.8 7.8 52 2 12.1 2.2 1.5 1 19.75 25 GEH120 208/60/3 38.7 16 110 2 24.9 6.7 2.0 1 42.70 50 GEH120 230/60/3 38.1 16 110 2 24.9 6.1 2.0 1 42.10 50 GEH120 460/60/3 18.7 7.8 52 2 12.1 3.1 2.0 1 20.65 25 GEH120 208/60/3 40.8 16 110 2 24.9 8.8 3.0 1 44.80 60 GEH120 230/60/3 40.0 16 110 2 24.9 8.0 3.0 1 44.00 60 GEH120 460/60/3 19.6 7.8 52 2 12.1 4.0 3.0 1 21.55 25 GEH120 208/60/3 46.6 16 110 2 24.9 14.6 5.0 1 50.60 60 GEH120 230/60/3 45.2 16 110 2 24.9 13.2 5.0 1 49.20 60 GEH120 460/60/3 22.2 7.8 52 2 12.1 6.6 5.0 1 24.15 30 GEH150 208/60/3 49.7 22.4 149 2 35 4.9 1.5 1 55.30 70 GEH150 230/60/3 49.2 22.4 149 2 35 4.4 1.5 1 54.80 70 GEH150 460/60/3 23.4 10.6 75 2 16.5 2.2 1.5 1 26.05 35 GEH150 208/60/3 51.5 22.4 149 2 35 6.7 2.0 1 57.10 70 GEH150 230/60/3 50.9 22.4 149 2 35 6.1 2.0 1 56.50 70 GEH150 460/60/3 24.3 10.6 75 2 16.5 3.1 2.0 1 26.95 35 GEH150 208/60/3 53.6 22.4 149 2 35 8.8 3.0 1 59.20 80 GEH150 230/60/3 52.8 22.4 149 2 35 8.0 3.0 1 58.40 80 GEH150 460/60/3 25.2 10.6 75 2 16.5 4.0 3.0 1 27.85 35 GEH150 208/60/3 59.4 22.4 149 2 35 14.6 5.0 1 65.00 80 GEH150 230/60/3 58.0 22.4 149 2 35 13.2 5.0 1 63.60 80 GEH150 460/60/3 27.8 10.6 75 2 16.5 6.6 5.0 1 30.45 40 GEH180 208/60/3 56.7 25 164 2 39 6.7 2.0 1 62.95 80 GEH180 230/60/3 56.1 25 164 2 39 6.1 2.0 1 62.35 80 GEH180 460/60/3 27.5 12.2 100 2 19 3.1 2.0 1 30.55 40 GEH180 208/60/3 58.8 25 164 2 39 8.8 3.0 1 65.05 90 GEH180 230/60/3 58.0 25 164 2 39 8.0 3.0 1 64.25 80 GEH180 460/60/3 28.4 12.2 100 2 19 4.0 3.0 1 31.45 40 GEH180 208/60/3 64.6 25 164 2 39 14.6 5.0 1 70.85 90 GEH180 230/60/3 63.2 25 164 2 39 13.2 5.0 1 69.45 90 GEH180 460/60/3 31.0 12.2 100 2 19 6.6 5.0 1 34.05 45 GEH180 208/60/3 72.1 25 164 2 39 22.1 7.5 1 78.35 100 GEH180 230/60/3 70.0 25 164 2 39 20.0 7.5 1 76.25 100 GEH180 460/60/3 34.4 12.2 100 2 19 10.0 7.5 1 37.45 45
Total
FLA
Comp RLA
(ea)
LRA
(ea)
No. of
Comp. Cmp MCC
Comp
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
No.
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Maximum
WSHP-SVX01Q-EN 83
Page 84
Electrical Data
Table 50. Electrical data two speed blower motor 6 to 25 tons (continued)
Model
No. Volts
GEV072 208/60/3 24.1 10.4 73 2 16.3 3.3 1.0 1 26.70 35 GEV072 230/60/3 23.8 10.4 73 2 16.3 3.0 1.0 1 26.40 35 GEV072 460/60/3 13.1 5.8 38 2 9 1.5 1.0 1 14.55 20 GEV072 208/60/3 25.7 10.4 73 2 16.3 4.9 1.5 1 28.30 35 GEV072 230/60/3 25.2 10.4 73 2 16.3 4.4 1.5 1 27.80 35 GEV072 460/60/3 13.8 5.8 38 2 9 2.2 1.5 1 15.25 20 GEV072 208/60/3 27.5 10.4 73 2 16.3 6.7 2.0 1 30.10 40 GEV072 230/60/3 26.9 10.4 73 2 16.3 6.1 2.0 1 29.50 35 GEV072 460/60/3 14.7 5.8 38 2 9 3.1 2.0 1 16.15 20 GEV090 208/60/3 28.2 14.5/10.4 98/73 2 22.6/16.3 3.3 1.0 1 31.83 45 GEV090 230/60/3 27.9 14.5/10.4 98/73 2 22.6/16.3 3.0 1.0 1 31.53 45 GEV090 460/60/3 13.6 6.3/5.8 55/38 2 9.9/9 1.5 1.0 1 15.18 20 GEV090 208/60/3 29.8 14.5/10.4 98/73 2 22.6/16.3 4.9 1.5 1 33.43 45 GEV090 230/60/3 29.3 14.5/10.4 98/73 2 22.6/16.3 4.4 1.5 1 32.93 45 GEV090 460/60/3 14.3 6.3/5.8 55/38 2 9.9/9 2.2 1.5 1 15.88 20 GEV090 208/60/3 31.6 14.5/10.4 98/73 2 22.6/16.3 6.7 2.0 1 35.23 45 GEV090 230/60/3 31.0 14.5/10.4 98/73 2 22.6/16.3 6.1 2.0 1 34.63 45 GEV090 460/60/3 15.2 6.3/5.8 55/38 2 9.9/9 3.1 2.0 1 16.78 20 GEV090 208/60/3 33.7 14.5/10.4 98/73 2 22.6/16.3 8.8 3.0 1 37.33 50 GEV090 230/60/3 32.9 14.5/10.4 98/73 2 22.6/16.3 8.0 3.0 1 36.53 50 GEV090 460/60/3 16.1 6.3/5.8 55/38 2 9.9/9 4.0 3.0 1 17.68 20 GEV120 208/60/3 36.9 16 110 2 24.9 4.9 1.5 1 40.90 50 GEV120 230/60/3 36.4 16 110 2 24.9 4.4 1.5 1 40.40 50 GEV120 460/60/3 17.8 7.8 52 2 12.1 2.2 1.5 1 19.75 25 GEV120 208/60/3 38.7 16 110 2 24.9 6.7 2.0 1 42.70 50 GEV120 230/60/3 38.1 16 110 2 24.9 6.1 2.0 1 42.10 50 GEV120 460/60/3 18.7 7.8 52 2 12.1 3.1 2.0 1 20.65 25 GEV120 208/60/3 40.8 16 110 2 24.9 8.8 3.0 1 44.80 60 GEV120 230/60/3 40.0 16 110 2 24.9 8.0 3.0 1 44.00 60 GEV120 460/60/3 19.6 7.8 52 2 12.1 4.0 3.0 1 21.55 25 GEV120 208/60/3 46.6 16 110 2 24.9 14.6 5.0 1 50.60 60 GEV120 230/60/3 45.2 16 110 2 24.9 13.2 5.0 1 49.20 60 GEV120 460/60/3 22.2 7.8 52 2 12.1 6.6 5.0 1 24.15 30 GEV150 208/60/3 51.5 22.4 149 2 35 6.7 2.0 1 57.10 70 GEV150 230/60/3 50.9 22.4 149 2 35 6.1 2.0 1 56.50 70 GEV150 460/60/3 24.3 10.6 75 2 16.5 3.1 2.0 1 26.95 35 GEV150 208/60/3 53.6 22.4 149 2 35 8.8 3.0 1 59.20 80 GEV150 230/60/3 52.8 22.4 149 2 35 8.0 3.0 1 58.40 80 GEV150 460/60/3 25.2 10.6 75 2 16.5 4.0 3.0 1 27.85 35 GEV150 208/60/3 59.4 22.4 149 2 35 14.6 5.0 1 65.00 80 GEV150 230/60/3 58.0 22.4 149 2 35 13.2 5.0 1 63.60 80 GEV150 460/60/3 27.8 10.6 75 2 16.5 6.6 5.0 1 30.45 40 GEV180 208/60/3 58.8 25 164 2 39 8.8 3.0 1 65.05 90 GEV180 230/60/3 58.0 25 164 2 39 8.0 3.0 1 64.25 80 GEV180 460/60/3 28.4 12.2 100 2 19 4.0 3.0 1 31.45 40 GEV180 208/60/3 64.6 25 164 2 39 14.6 5.0 1 70.85 90
Total
FLA
Comp RLA
(ea)
LRA
(ea)
No. of
Comp. Cmp MCC
Comp
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
No.
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Maximum
84 WSHP-SVX01Q-EN
Page 85
Table 50. Electrical data two speed blower motor 6 to 25 tons (continued)
Electrical Data
Model
No. Volts
GEV180 230/60/3 63.2 25 164 2 39 13.2 5.0 1 69.45 90 GEV180 460/60/3 31.0 12.2 100 2 19 6.6 5.0 1 34.05 45 GEV180 208/60/3 72.1 25 164 2 39 22.1 7.5 1 78.35 100 GEV180 230/60/3 70.0 25 164 2 39 20.0 7.5 1 76.25 100 GEV180 460/60/3 34.4 12.2 100 2 19 10.0 7.5 1 37.45 45 GEV240 208/60/3 74.8 30.1 225 2 47 14.6 5.0 1 82.33 110 GEV240 230/60/3 73.4 30.1 225 2 47 13.2 5.0 1 80.93 110 GEV240 460/60/3 40.0 16.7 114 2 26 6.6 5.0 1 44.18 60 GEV240 208/60/3 82.3 30.1 225 2 47 22.1 7.5 1 89.83 110 GEV240 230/60/3 80.2 30.1 225 2 47 20.0 7.5 1 87.73 110 GEV240 460/60/3 43.4 16.7 114 2 26 10.0 7.5 1 47.58 60 GEV240 208/60/3 87.8 30.1 225 2 47 27.6 10.0 1 95.33 125 GEV240 230/60/3 85.2 30.1 225 2 47 25.0 10.0 1 92.73 110 GEV240 460/60/3 46.4 16.7 114 2 26 13.0 10.0 1 50.58 60 GEV240 460/60/3 53.4 16.7 114 2 26 20.0 15.0 1 58.40 70 GEV300 208/60/3 110.8 48.1 245 2 75 14.6 5.0 1 122.83 150 GEV300 230/60/3 109.4 48.1 245 2 75 13.2 5.0 1 121.43 150 GEV300 460/60/3 43.8 18.6 125 2 29 6.6 5.0 1 48.45 60 GEV300 208/60/3 118.3 48.1 245 2 75 22.1 7.5 1 130.33 175 GEV300 230/60/3 116.2 48.1 245 2 75 20.0 7.5 1 128.23 175 GEV300 460/60/3 47.2 18.6 125 2 29 10.0 7.5 1 51.85 70 GEV300 208/60/3 123.8 48.1 245 2 75 27.6 10.0 1 135.83 175 GEV300 230/60/3 121.2 48.1 245 2 75 25.0 10.0 1 133.23 175 GEV300 460/60/3 50.2 18.6 125 2 29 13.0 10.0 1 54.85 70 GEV300 460/60/3 57.2 18.6 125 2 29 20.0 15.0 1 62.20 80
Total
FLA
Comp RLA
(ea)
LRA
(ea)
No. of
Comp. Cmp MCC
Comp
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motor
No.
Minimum
Circuit
Ampacity
Overcurrent
Protective
Device
Maximum
Table 51. Electrical minimum and maximum .5 to 25 tons
Digit 8 Rated Voltage Hz Ph Min Utiliz. Volts Max Utiliz. Volts
0 115 60 1 104 126 1 208 60 1 197 229 2 230 60 1 207 253 3 208 60 3 187 229 4 460 60 3 414 506 5 575 60 3 518 633 7 265 60 1 239 292 8 230 60 3 207 253
WSHP-SVX01Q-EN 85
Page 86
Pre-Start Checklist
Before energizing the unit, the following system devices must be checked:
Is the high voltage power supply correct and in accordance with the nameplate ratings?
Is phasing of the unit correct per compressor rotation (scroll compressor only)?
Is the field wiring and circuit protection the correct size?
Is the low voltage control circuit wiring correct per the unit wiring diagram?
Is the piping system clean/complete and correct? (A recommendation of all system flushing of debris from the water-to-refrigerant heat exchanger, along with air purging from the water-to-refrigerant heat exchanger be done in accordance with the Closed-Loop/Ground Source Heat Pump Systems Installation Guide).
Is vibration isolation provided? (i.e. unit isolation pad, hose kits)
Is unit serviceable? (See clearance specifications in
“Unit Dimensions,” p. 13).
Are the low/high-side pressure temperature caps secure and in place?
Are all the unit access panels secure and in place?
Is the thermostat in the OFF position?
Is the water flow established and circulating through all the units?
Is the duct work correctly sized, run, taped, insulated and weather proofed with proper unit arrangement?
Is the condensate line properly sized, run, trapped, pitched and primed?
Is the zone sensor correctly wired and in a good location?
Does the indoor blower turn freely without rubbing?
Has all work been done in accordance with applicable local and national codes?
Has heat transfer fluid been added in the proper mix to prevent freezing in closed system application?
86 WSHP-SVX01Q-EN
Page 87
Start-Up
Initial Unit Start-up
Note: Start-up with the heat pump thermostat is included
below:
1. Set the thermostat to the highest position.
2. Set the thermostat system switch to COOL with the fan control to AUTO.The compressor should NOT run.
3. Reduce the thermostat setting until the compressor, reversing valve, solenoid valve, and loop pump are energized. Adjust water flow utilizing pressure/ temperature plugs and comparing to tables contained in specification sheet data.
Water leaving the heat exchanger should be warmer
than the entering water temperature (approximately 9­12ºF); blower operation should be smooth; compressor and blower amps should be within data plate ratings; the suction line should be cool with no frost observed in the refrigerant circuit.
4. Check the cooling refrigerant pressures against values in Table 53, p. 88.
5. Turn the thermostat system switch to the OFF position. Unit should stop running and the reversing valve should de-energize.
6. Leave unit off for approximately FIVE minutes to allow for pressure equalization.
7. Turn the thermostat to the lowest setting.
8. Set the thermostat system switch to the HEAT position.
9. Adjust the temperature setting upward until the unit is energized. Warm air should blow from the register. A water temperature decrease of approximately 5-9ºF leaving the heat exchanger should be noted.The blower and compressor operation should be smooth with no frost observed in the refrigeration circuit.
10. Check the heating refrigerant pressures against values in Table 53, p. 88.
11. Set the thermostat to maintain the desired space temperature.
12. Instruct the owner on system operation.
Table 52. Checklist
MODE Heat Cool
Pressure Differential
COMPRESSOR
Amps
Volts
Discharge line temperature (after 10
minutes)
_________PSIG_________PSI
G
_______F _______F
Start-Up Checklist and Log
Installing Contractor: Use this checklist to thoroughly check-out the system and units before and during start-up. (This form need not be returned to the factory unless requested during technical service support).
Job Name:________________________
Model Number:____________________
Date:______________________________
Serial Number:_____________________
In order to minimize troubleshooting and costly system failures, complete the following checks and data entries before the system is put into full operation.
Operating Pressures
There are many variables (airflow, air temperatures) in an
air conditioning system that will affect operating refrigerant pressures and temperatures.The charts below shows approximate conditions and is based on air flow at the rated SCFM, entering air at 80.6°F(DB), 66.2°F(WB) in cooling, 68°F(DB) in heating. (+)Heating data with 35°F EWT is based on the use of an anti-freeze solution having a freezing point 20°F lower than the minimum expected entering temperature.
Table 52. Checklist
MODE Heat Cool
Entering fluid temperature _______F _______F
Leaving fluid temperature _______F _______F
Temperature differential _______F _______F Return-air temperature DB/WB _______F _______F Supply-air temperature DB/WB _______F _______F
Temperature differential _______F _______F
Water coil heat exchanger (Water
Pressure IN)
Water coil heat exchanger (Water
Pressure OUT)
WSHP-SVX01Q-EN 87
________PSIG ________PSIG
________PSIG ________PSIG
Page 88
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units
Operating Data
Cooling Heating
Entering
Water
Temp
Model No.
GEH*/GEV*006 (60 Hz) 35 1.4 94-108 279-355 6-8 23-29 GEH*/GEV*006 (60 Hz) 35 1.7 96-110 281-357 5-6 23-29 GEH*/GEV*006 (60 Hz) 45 1.4 143-165 190-243 13-16 24-30 110-127 297-377 7-9 26-34 GEH*/GEV*006 (60 Hz) 45 1.7 143-164 184-235 11-13 24-31 113-130 300-382 6-8 27-34 GEH*/GEV*006 (60 Hz) 55 1.4 145-167 217-277 13-16 23-30 128-147 317-404 8-10 30-39 GEH*/GEV*006 (60 Hz) 55 1.7 144-166 210-268 11-13 24-30 131-151 320-407 7-9 31-39 GEH*/GEV*006 (60 Hz) 68 1.4 148-171 254-324 12-15 23-29 154-177 345-439 10-12 35-45 GEH*/GEV*006 (60 Hz) 68 1.7 147-170 244-312 10-13 23-29 158-182 349-444 8-10 36-45 GEH*/GEV*006 (60 Hz) 75 1.4 148-171 281-358 12-15 23-29 169-195 361-459 10-13 38-48 GEH*/GEV*006 (60 Hz) 75 1.7 148-170 273-348 10-13 23-29 175-201 366-466 9-11 38-48 GEH*/GEV*006 (60 Hz) 86 1.4 149-172 328-418 12-15 22-28 197-226 388-494 11-15 41-52 GEH*/GEV*006 (60 Hz) 86 1.7 149-172 320-407 10-13 23-29 203-234 395-502 10-12 41-52 GEH*/GEV*006 (60 Hz) 95 1.4 151-173 373-474 12-15 22-28 — GEH*/GEV*006 (60 Hz) 95 1.7 150-173 363-462 10-13 22-28
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*009 (60Hz)
GEH*/GEV*006 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
(°F)
35 1.7 93-107 272-346 6-7 20-26
35 2.1 95-110 274-348 5-6 21-27
45 1.7 142-164 187-238 13-16 22-28 109-126 288-366 7-9 24-30
45 2.1 142-164 181-230 11-14 22-27 112-129 291-370 6-7 24-31
55 1.7 144-166 214-272 12-15 21-27 127-146 305-388 8-10 27-34
55 2.1 144-166 207-263 10-13 21-27 130-150 309-393 7-8 27-35
68 1.7 146-168 258-328 12-15 20-26 153-176 330-420 9-12 31-39
68 2.1 146-168 250-318 10-12 21-26 157-181 335-427 8-10 32-40
75 1.7 147-169 286-363 12-15 20-25 168-193 345-439 10-13 33-42
75 2.1 147-169 277-352 9-12 20-26 174-200 350-446 8-11 34-43
86 1.7 149-171 336-427 12-15 19-25 195-224 370-471 11-14 36-46
86 2.1 148-171 326-415 9-12 20-25 202-232 375-477 9-12 37-47
95 1.7 149-172 386-491 12-15 19-24
95 2.1 149-172 375-477 9-12 19-24
35 2.2 92-106 288-367 10-13 21-27
35 2.8 — 95-109 290-370 8-11 21-27
45 2.2 142-163 183-233 12-15 22-28 108-125 304-387 12-15 24-30
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Temp
Rise
(°F DB)
Air
88 WSHP-SVX01Q-EN
Page 89
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*012 (60Hz)
GEH*/GEV*009 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
GEH*/GEV*015 (60Hz)
GEH*/GEV*012 (50 Hz)
Entering
Water
Temp
(°F)
45 2.8 142-163 175-223 9-12 23-29 111-128 307-391 9-12 24-31
55 2.2 143-164 212-270 12-15 21-27 126-145 322-410 13-16 26-33
55 2.8 143-164 204-260 9-12 22-27 130-149 325-413 10-13 27-34
68 2.2 144-166 257-327 12-15 21-26 152-174 346-441 14-18 29-37
68 2.8 144-166 248-316 9-12 21-26 157-180 352-448 11-15 29-37
75 2.2 145-167 284-361 12-15 20-26 167-192 361-460 15-19 30-38
75 2.8 145-167 274-349 9-12 20-26 173-199 366-466 12-15 30-39
86 2.2 146-168 332-422 12-15 19-25 194-223 384-489 16-21 32-40
86 2.8 146-168 321-409 9-12 20-25 201-231 390-497 13-17 32-41
95 2.2 147-170 376-478 12-15 19-24
95 2.8 147-170 365-465 9-12 19-24
35 2.8 91-105 296-377 6-7 20-25
35 3.5 — 93-107 299-380 5-6 20-26
45 2.8 138-159 180-230 11-14 22-28 107-123 313-398 7-8 23-29
45 3.5 138-158 174-221 9-11 22-27 109-126 316-402 5-7 23-30
55 2.8 139-159 210-267 11-14 21-27 124-143 332-423 8-10 26-33
55 3.5 138-159 203-258 9-11 21-27 128-147 336-427 6-8 27-34
68 2.8 140-161 254-324 11-14 20-26 150-172 358-456 9-11 30-38
68 3.5 140-161 246-313 9-11 21-26 154-178 364-463 7-9 30-39
75 2.8 141-162 281-358 11-14 20-25 165-190 373-475 10-12 32-40
75 3.5 140-162 272-347 9-11 20-26 171-196 379-483 8-10 32-41
86 2.8 142-163 328-417 11-14 19-25 191-220 399-508 11-14 34-43
86 3.5 142-163 318-405 9-11 20-25 198-228 405-515 9-11 34-44
95 2.8 143-165 371-472 11-14 19-24
95 3.5 143-165 361-459 9-11 19-24
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Start-Up
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 89
Page 90
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*/GEV*018 (60Hz)
GEH*/GEV*015 (50 Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
Entering
Water
Temp
(°F)
35 3.3 89-102 276-351 6-7 21-26
35 4.2 — 91-105 279-354 5-6 21-27
45 3.3 142-163 186-237 12-15 23-29 104-120 292-372 7-9 24-30
45 4.2 142-163 179-227 9-12 23-29 107-123 295-376 5-7 24-31
55 3.3 142-163 216-275 12-15 23-29 121-139 310-395 8-10 27-34
55 4.2 142-163 207-264 9-12 23-29 125-143 313-399 6-8 27-35
68 3.3 142-163 262-333 12-15 22-28 146-168 334-425 9-12 31-39
68 4.2 142-163 252-321 9-12 22-28 151-174 338-430 7-9 32-40
75 3.3 142-164 289-368 12-15 21-27 161-185 347-441 10-13 33-42
75 4.2 142-164 280-356 9-12 21-27 167-192 351-447 8-10 34-43
86 3.3 143-165 338-430 12-15 20-26 188-216 365-464 11-14 36-46
86 4.2 143-165 327-416 9-12 20-26 195-225 370-471 9-11 37-47
95 3.3 144-166 383-488 12-15 19-24
95 4.2 144-166 372-473 9-12 19-25
35 76-88 279-355 6-7 21-30
35 78-89 280-357 5-6 21-31
45 4.5 114-131 172-219 12-16 20-26 89-103 290-369 7-9 24-34
45 5.6 114-131 165-211 10-13 20-26 91-105 292-371 6-7 24-34
55 4.5 115-132 200-255 12-15 20-26 106-122 307-390 8-10 27-37
55 5.6 115-132 193-246 10-12 20-26 108-125 309-394 6-8 28-38
68 4.5 120-139 239-304 12-15 19-25 124-143 326-415 9-12 31-42
68 5.6 120-138 231-294 10-12 20-25 129-148 330-420 7-9 32-43
75 4.5 121-140 264-336 12-15 19-25 139-159 340-432 10-13 34-44
75 5.6 121-139 256-325 9-12 19-25 143-165 343-437 8-10 34-45
86 4.5 124-143 305-389 12-15 18-24 163-188 363-462 11-14 38-49
86 5.6 124-143 297-378 9-12 19-24 169-195 368-468 9-12 39-50
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
90 WSHP-SVX01Q-EN
Page 91
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*024 (60Hz) GEH*018 (50Hz)
GEH*024 (60Hz) GEH*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEV*024 (60Hz) GEV*018 (50Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
Entering
Water
Temp
(°F)
95 4.5 126-145 344-437 12-15 18-24
95 5.6 126-145 335-426 9-12 18-24
35 76-87 270-344 6-7 21-30
35 78-89 272-346 5-6 21-31
45 4.5 114-132 173-221 12-16 20-26 88-102 283-360 7-9 24-34
45 5.6 114-131 167-212 10-12 20-26 90-104 285-362 6-7 24-34
55 4.5 116-133 202-258 12-15 20-25 105-121 299-381 8-10 27-37
55 5.6 116-133 195-249 10-12 20-26 107-124 301-384 6-8 28-38
68 4.5 122-140 242-308 12-15 20-26 123-141 315-401 9-12 31-41
68 5.6 122-140 234-298 10-12 20-26 127-146 318-405 7-9 32-42
75 4.5 123-141 268-341 12-15 19-25 137-158 327-417 10-13 34-44
75 5.6 123-141 259-330 10-12 20-25 142-163 331-421 8-10 34-45
86 4.5 126-145 310-394 12-15 19-25 161-186 349-444 11-14 38-49
86 5.6 125-144 301-383 9-12 19-25 167-193 353-449 9-12 39-50
95 4.5 127-146 349-445 12-15 19-25
95 5.6 127-146 340-433 9-12 19-25
35 77-89 276-351 6-7 21-30
35 79-90 277-352 4-6 21-30
45 5.6 120-138 171-218 12-15 22-27 91-104 290-369 7-8 24-34
45 7.0 120-138 165-210 10-12 22-28 93-107 292-371 5-7 24-34
55 5.6 121-140 200-254 12-15 21-27 108-124 307-390 8-10 27-37
55 7.0 121-139 193-245 9-12 22-27 111-127 309-393 6-8 28-38
68 5.6 122-140 249-317 12-15 20-26 128-148 329-419 9-11 32-42
68 7.0 122-140 241-306 9-12 20-26 133-152 333-423 7-9 32-43
75 5.6 123-141 275-350 12-15 20-26 143-164 342-436 10-12 34-45
75 7.0 123-141 267-340 9-12 20-26 148-170 346-440 8-10 35-46
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Start-Up
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 91
Page 92
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Entering
Water
Temp
Model No.
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEH*030 (60 Hz) GEH*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEV*030 (60 Hz) GEV*024 (50 Hz)
GEHE035 (60 Hz) 32 8.4 87-100 267-340 4-5 18-27 GEHE035 (60 Hz) 45 6.6 134-155 180-229 12-15 20-26 103-118 282-359 6-8 22-31 GEHE035 (60 Hz) 45 8.4 134-154 174-222 9-12 20-26 106-121 285-362 5-6 22-32 GEHE035 (60 Hz) 55 6.6 136-156 208-265 12-15 20-25 119-136 297-377 7-9 25-35 GEHE035 (60 Hz) 55 8.4 136-156 201-256 9-12 20-26 122-140 300-382 6-8 25-35 GEHE035 (60 Hz) 68 6.6 138-159 250-318 12-15 19-25 142-163 318-405 9-11 29-39 GEHE035 (60 Hz) 68 8.4 138-158 242-308 9-12 19-25 146-168 323-411 7-9 30-40 GEHE035 (60 Hz) 75 6.6 139-160 275-350 12-15 18-24 155-179 331-422 10-12 32-42 GEHE035 (60 Hz) 75 8.4 139-160 266-339 9-11 18-24 161-185 336-428 8-10 33-43 GEHE035 (60 Hz) 86 6.6 142-163 317-404 11-14 18-24 179-206 354-450 11-14 36-47 GEHE035 (60 Hz) 86 8.4 142-163 309-393 9-11 18-24 185-213 359-457 9-11 37-49 GEHE035 (60 Hz) 95 6.6 144-166 355-452 11-14 17-23
(°F)
86 5.6 126-146 310-395 11-14 20-26 168-193 365-465 11-14 38-49
86 7.0 126-145 302-384 9-11 20-26 174-200 370-470 9-11 39-50
95 5.6 128-148 350-446 11-14 19-25
95 7.0 128-147 341-434 9-11 19-25
35 76-88 266-338 6-7 21-30
35 78-90 268-341 5-6 22-31
45 5.6 115-132 172-218 12-15 21-27 87-100 275-351 6-8 24-33
45 7.0 115-132 165-210 9-12 21-27 90-103 278-354 5-7 24-34
55 5.6 116-134 201-256 12-15 20-26 104-119 292-371 8-10 27-37
55 7.0 116-134 194-247 9-12 21-26 107-123 295-375 6-8 28-38
68 5.6 121-139 242-308 11-15 20-26 122-141 311-396 9-11 31-41
68 7.0 120-138 234-298 9-12 20-26 126-145 314-400 7-9 32-42
75 5.6 122-140 268-341 11-14 20-26 136-157 324-412 9-12 34-44
75 7.0 122-140 260-331 9-12 20-26 141-162 328-418 8-10 34-45
86 5.6 124-142 311-396 11-14 19-25 161-185 345-439 11-14 38-49
86 7.0 123-142 303-385 9-11 19-25 167-192 350-445 9-11 39-50
95 5.6 125-144 351-447 11-14 19-25
95 7.0 125-144 342-436 9-11 19-25
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
92 WSHP-SVX01Q-EN
Page 93
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Entering
Water
Temp
Model No.
GEHE035 (60 Hz) 95 8.4 144-165 347-441 9-11 17-23 — GEH*030 (50 Hz) 35 76-88 294-375 6-8 21-30 GEH*030 (50 Hz) 45 6.7 115-132 174-222 12-15 20-26 89-102 306-390 7-9 24-34 GEH*030 (50 Hz) 45 8.4 115-132 168-214 9-12 20-26 91-105 309-394 6-7 24-34 GEH*030 (50 Hz) 55 6.7 117-134 203-259 11-15 19-25 106-122 327-416 8-11 27-37 GEH*030 (50 Hz) 55 8.4 116-134 196-250 9-12 20-25 108-125 329-419 7-9 28-38 GEH*030 (50 Hz) 68 6.7 120-138 244-311 11-14 19-25 126-145 351-446 10-12 32-42 GEH*030 (50 Hz) 68 8.4 119-137 237-301 9-11 19-25 130-150 354-450 8-10 32-43 GEH*030 (50 Hz) 75 6.7 121-139 270-343 11-14 19-25 141-162 367-468 10-13 34-45 GEH*030 (50 Hz) 75 8.4 121-139 262-333 9-11 19-25 145-167 372-473 9-11 35-46 GEH*030 (50 Hz) 86 6.7 124-142 312-397 11-14 18-24 165-190 395-503 12-15 39-50 GEH*030 (50 Hz) 86 8.4 124-142 303-386 9-11 19-24 172-197 399-508 10-12 40-51 GEH*030 (50 Hz) 95 6.7 126-145 351-447 11-14 18-24 — GEH*030 (50 Hz) 95 8.4 126-144 342-435 9-11 18-24 — GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEV*036 (60 Hz)
GEV*030 (50 Hz) GEH*042 (60 Hz)
GEH*036 (50 Hz) GEH*042 (60 Hz)
GEH*036 (50 Hz) GEH*042 (60 Hz)
GEH*036 (50 Hz)
(°F)
35 77-88 286-364 6-8 22-31
35 78-90 288-366 5-6 22-31
45 6.7 116-134 169-215 12-15 20-26 89-103 296-377 7-9 25-34
45 8.4 116-134 163-208 10-12 21-26 91-105 298-380 6-7 25-35
55 6.7 118-136 198-251 12-15 20-26 106-122 315-401 8-10 28-38
55 8.4 118-135 191-243 10-12 20-26 109-125 318-404 7-8 29-39
68 6.7 121-139 238-303 12-15 20-25 128-147 341-434 10-12 33-43
68 8.4 121-139 231-294 10-12 20-26 132-151 344-437 8-10 33-44
75 6.7 122-141 263-335 12-15 19-25 143-164 357-454 10-13 36-46
75 8.4 122-140 255-325 9-12 19-25 147-169 360-458 9-11 36-47
86 6.7 125-144 304-387 12-15 19-25 168-193 383-488 12-15 40-51
86 8.4 125-143 296-377 9-12 19-25 174-200 387-492 10-12 41-52
95 6.7 127-146 342-436 11-15 19-24
95 8.4 127-146 334-425 9-12 19-25
35 74-86 269-342 6-7 20-30
35 76-87 270-344 5-6 21-30
45 7.8 116-134 173-220 12-16 21-27 86-99 281-358 7-8 23-33
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Start-Up
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 93
Page 94
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEH*042 (60 Hz) GEH*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
GEV*042 (60 Hz) GEV*036 (50 Hz)
Entering
Water
Temp
(°F)
45 9.8 116-134 167-212 10-13 21-27 88-101 283-360 5-7 24-33
55 7.8 118-135 201-256 12-15 21-26 102-118 298-379 8-10 27-36
55 9.8 118-135 194-247 10-12 21-26 105-121 300-382 6-8 27-37
68 7.8 122-140 242-308 12-15 20-26 121-140 317-403 9-11 31-41
68 9.8 121-140 235-299 10-12 21-26 125-144 321-408 7-9 31-42
75 7.8 123-141 267-340 12-15 20-26 135-156 331-422 10-12 33-44
75 9.8 123-141 259-330 9-12 20-26 140-161 336-427 8-10 34-45
86 7.8 125-144 308-392 12-15 20-25 159-183 355-451 11-14 38-49
86 9.8 125-144 300-382 9-12 20-26 165-190 359-457 9-12 39-50
95 7.8 127-146 346-441 11-15 19-25
95 9.8 127-146 338-430 9-12 19-25
35 75-86 268-341 6-7 20-30
35 76-87 268-341 5-6 21-30
45 7.8 116-133 173-220 12-16 21-26 86-99 283-360 7-9 23-33
45 9.8 116-133 167-212 10-12 21-27 88-102 283-360 6-7 24-33
55 7.8 117-135 201-256 12-15 20-26 103-118 298-380 8-10 27-37
55 9.8 117-135 194-247 10-12 20-26 105-121 301-383 6-8 27-37
68 7.8 122-140 242-308 12-15 20-26 122-140 318-404 9-12 31-41
68 9.8 121-140 234-298 9-12 20-26 126-144 321-409 7-9 31-42
75 7.8 123-141 267-340 12-15 20-25 136-156 331-422 10-13 33-44
75 9.8 122-141 259-330 9-12 20-26 140-161 336-427 8-10 34-45
86 7.8 126-144 307-390 11-15 19-25 160-184 355-452 11-14 38-49
86 9.8 125-144 299-380 9-12 19-25 166-190 359-457 9-12 39-50
95 7.8 127-147 345-439 11-14 18-24
95 9.8 127-146 337-428 9-11 18-24
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
94 WSHP-SVX01Q-EN
Page 95
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEH*048 (60 Hz) GEH*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
Entering
Water
Temp
(°F)
35 74-85 263-334 6-8 20-29
35 76-87 265-337 5-6 20-29
45 9.0 120-138 184-234 13-16 23-29 85-98 273-348 7-9 23-32
45 11.2 120-138 176-225 10-13 23-29 87-100 275-350 6-7 23-33
55 9.0 121-140 214-273 13-16 23-28 101-117 289-368 8-10 26-36
55 11.2 121-139 206-262 10-13 23-28 104-120 292-372 6-8 26-36
68 9.0 125-144 256-326 13-16 22-28 117-135 305-388 9-12 30-40
68 11.2 125-144 247-315 10-13 23-28 122-140 310-394 7-10 30-41
75 9.0 126-146 282-359 12-16 22-28 131-151 318-405 10-13 32-43
75 11.2 126-145 273-348 10-13 22-28 136-156 322-410 8-10 33-44
86 9.0 129-148 324-412 12-15 21-27 154-177 339-431 11-14 36-47
86 11.2 128-147 314-400 10-12 22-27 160-184 344-437 9-12 37-48
95 9.0 130-150 364-463 12-15 21-27
95 11.2 130-149 354-451 10-12 21-27
35 63-73 248-315 5-7 19-28
35 64-74 249-316 4-5 19-28
45 9.0 120-138 184-234 13-16 22-28 72-82 257-327 6-8 21-30
45 11.2 119-137 177-225 10-13 22-28 73-84 259-329 5-6 21-30
55 9.0 121-139 214-272 13-16 22-27 86-99 270-344 7-9 24-33
55 11.2 121-139 206-262 10-13 22-27 88-101 272-347 6-7 24-34
68 9.0 125-144 255-325 12-16 21-27 102-118 287-366 8-10 27-37
68 11.2 125-144 246-314 10-13 21-27 105-120 290-369 7-8 28-38
75 9.0 126-145 281-358 12-16 21-27 114-131 299-381 9-11 30-40
75 11.2 126-145 272-346 10-13 21-27 117-135 302-384 7-9 30-41
86 9.0 129-149 323-412 12-16 20-26 136-156 318-405 10-13 34-44
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Start-Up
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 95
Page 96
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEV*048 (60 Hz) GEV*042 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEH*060(60 Hz)
GEH*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*042 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
Entering
Water
Temp
(°F)
86 11.2 129-148 314-399 10-12 21-26 140-161 321-409 8-10 34-45
95 9.0 131-151 363-462 12-15 20-26
95 11.2 131-150 353-449 10-12 20-26
35 69-79 265-337 6-7 20-30
35 70-81 267-339 5-6 21-30
45 11.2 111-128 176-225 13-16 21-26 79-91 274-348 6-8 23-32
45 14.0 108-124 170-217 10-13 21-27 81-93 275-350 5-7 23-32
55 11.2 113-129 205-261 12-16 20-26 95-109 290-369 7-9 26-36
55 14.0 112-129 198-252 10-13 20-26 97-111 291-371 6-8 26-36
68 11.2 117-135 243-309 12-16 20-26 115-132 311-396 9-11 30-40
68 14.0 117-134 235-300 10-12 20-26 118-136 314-399 7-9 31-41
75 11.2 118-136 268-342 12-15 20-25 128-147 324-412 10-12 33-43
75 14.0 118-136 260-331 10-12 20-26 132-152 327-416 8-10 33-44
86 11.2 121-139 309-393 12-15 19-25 151-174 347-442 11-14 37-48
86 14.0 121-139 301-383 10-12 19-25 157-180 351-447 9-11 38-49
95 11.2 123-141 348-442 12-15 19-25
95 14.0 122-141 339-431 9-12 19-25
35 70-81 261-332 6-7 20-30
35 72-82 262-333 5-6 20-30
45 11.2 115-133 178-227 13-16 21-27 80-92 269-342 6-8 23-32
45 14.0 115-132 172-219 10-13 21-27 82-94 270-344 5-7 23-32
55 11.2 117-134 207-264 12-16 20-26 95-110 284-362 7-10 26-36
55 14.0 117-134 200-255 10-13 21-26 97-112 286-364 6-8 26-36
68 11.2 122-140 248-315 12-16 20-26 116-134 304-387 9-11 31-41
68 14.0 121-140 240-305 10-13 21-26 120-138 308-392 7-9 31-42
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
96 WSHP-SVX01Q-EN
Page 97
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Entering
Water
Temp
Model No.
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz)
GEV*060(60 Hz)
GEV*048 (50 Hz) GEH*/GEV*072 (60 Hz) 32 12 67 - 77 250 - 319 6 - 8 20 - 24 GEH*/GEV*072 (60 Hz) 32 18 70 - 80 253 - 322 4 - 5 20 - 25 GEH*/GEV*072 (60 Hz) 45 12 129 - 148 176 - 224 15 - 18 25 - 30 85 - 97 266 - 338 8 - 10 24 - 29 GEH*/GEV*072 (60 Hz) 45 18 128 - 148 163 - 208 10 - 12 25 - 31 89 - 103 269 - 342 5 - 7 25 - 30 GEH*/GEV*072 (60 Hz) 55 12 130 - 150 205 - 260 14 - 18 24 - 30 102 - 117 281 - 357 8 - 11 28 - 35 GEH*/GEV*072 (60 Hz) 55 18 130 - 149 191 - 243 10 - 12 24 - 30 107 - 123 285 - 362 6 - 7 29 - 35 GEH*/GEV*072 (60 Hz) 68 12 133 - 153 247 - 314 14 - 18 23 - 29 125 - 144 300 - 382 10 - 13 34 - 42 GEH*/GEV*072 (60 Hz) 68 18 132 - 152 232 - 296 9 - 12 24 - 29 133 - 153 305 - 388 7 - 9 35 - 43 GEH*/GEV*072 (60 Hz) 77 12 134 - 155 286 - 363 15 - 18 23 - 28 139 - 160 311 - 396 11 - 14 37 - 45 GEH*/GEV*072 (60 Hz) 77 18 134 - 154 268 - 341 10 - 12 23 - 29 148 - 170 317 - 403 8 - 10 38 - 47 GEH*/GEV*072 (60 Hz) 86 12 136 - 156 317 - 403 14 - 17 22 - 28 163 - 188 329 - 419 13 - 16 41 - 50 GEH*/GEV*072 (60 Hz) 86 18 135 - 155 300 - 382 9 - 12 23 - 28 175 - 201 335 - 427 9 - 11 43 - 53 GEH*/GEV*072 (60 Hz) 95 12 137 - 158 356 - 453 13 - 17 22 - 27 — GEH*/GEV*072 (60 Hz) 95 18 137 - 157 340 - 432 9 - 11 22 - 27 — GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz) GEH*/GEV*090 (60 Hz)
GEH*/GEV*072 (50 Hz)
(°F)
75 11.2 123-141 273-347 12-16 20-26 129-149 318-404 10-12 33-44
75 14.0 123-141 265-337 10-12 20-26 134-154 321-408 8-10 34-45
86 11.2 125-144 313-399 12-15 20-25 153-176 341-434 11-14 38-49
86 14.0 125-144 305-388 10-12 20-25 158-182 344-438 9-12 38-50
95 11.2 127-146 352-447 12-15 19-25
95 14.0 127-146 343-436 9-12 19-25
32 15 65 - 75 245 - 312 6 - 8 22 - 27
32 22.5 68 - 78 248 - 316 4 - 5 23 - 28
45 15 125 - 144 183 - 233 15 - 19 24 - 30 83 - 95 260 - 331 8 - 10 26 - 31
45 22.5 124 - 143 170 - 216 10 - 12 24 - 30 87 - 101 263 - 335 5 - 7 26 - 32
55 15 126 - 145 213 - 271 14 - 18 24 - 29 100 - 115 274 - 348 8 - 11 29 - 36
55 22.5 126 - 145 198 - 252 10 - 12 24 - 29 105 - 121 277 - 353 6 - 7 30 - 37
68 15 128 - 148 257 - 327 14 - 18 23 - 28 123 - 142 291 - 370 10 - 13 34 - 42
68 22.5 128 - 147 241 - 307 9 - 12 23 - 29 131 - 150 296 - 376 7 - 9 35 - 43
77 15 130 - 150 298 - 379 15 - 19 23 - 28 137 - 158 301 - 383 11 - 14 37 - 45
77 22.5 130 - 149 279 - 355 10 - 12 23 - 28 146 - 168 306 - 390 8 - 10 38 - 47
86 15 131 - 151 328 - 418 14 - 17 22 - 27 161 - 185 317 - 403 13 - 16 40 - 50
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 97
Page 98
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*/GEV*090 (60 Hz) GEH*/GEV*072 (50 Hz)
GEH*/GEV*090 (60 Hz) GEH*/GEV*072 (50 Hz)
GEH*/GEV*090 (60 Hz) GEH*/GEV*072 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*120 (60 Hz) GEH*/GEV*090 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
Entering
Water
Temp
(°F)
86 22.5 131 - 151 311 - 396 9 - 12 22 - 28 173 - 199 324 - 412 9 - 11 42 - 52
95 15 133 - 153 370 - 471 13 - 17 22 - 27
95 22.5 133 - 153 352 - 448 9 - 11 22 - 27
32 20 65 - 75 246 - 313 6 - 7 25 - 30
32 30 68 - 79 248 - 316 4 - 5 25 - 31
45 20 124 - 143 174 - 221 14 - 18 23 - 29 84 - 96 259 - 330 7 - 9 28 - 34
45 30 123 - 142 162 - 206 9 - 12 23 - 29 88 - 101 263 - 335 5 - 6 28 - 34
55 20 125 - 144 202 - 258 14 - 18 23 - 29 101 - 116 274 - 349 8 - 10 30 - 37
55 30 125 - 144 189 - 241 9 - 12 23 - 29 106 - 122 279 - 355 6 - 7 31 - 38
68 20 127 - 146 244 - 311 13 - 17 23 - 28 124 - 143 292 - 372 10 - 12 34 - 42
68 30 127 - 146 230 - 293 9 - 11 23 - 28 132 - 152 297 - 378 7 - 8 35 - 43
77 20 129 - 148 281 - 358 14 - 18 23 - 28 139 - 159 303 - 385 10 - 13 37 - 45
77 30 128 - 148 265 - 337 9 - 12 23 - 28 147 - 170 308 - 392 7 - 9 37 - 46
86 20 130 - 150 311 - 396 13 - 16 22 - 27 163 - 187 320 - 407 12 - 15 40 - 50
86 30 130 - 150 296 - 376 9 - 11 22 - 27 174 - 200 326 - 415 8 - 11 41 - 51
95 20 132 - 152 348 - 443 13 - 16 22 - 27
95 30 132 - 152 333 - 423 8 - 11 22 - 27
32 25 66 - 75 256 - 326 7 - 8 23 - 29
32 37.5 69 - 79 258 - 329 5 - 6 24 - 30
45 25 120 - 138 187 - 238 15 - 19 22 - 29 84 - 96 272 - 346 8 - 10 26 - 32
45 37.5 120 - 138 172 - 219 10 - 12 22 - 29 88 - 102 275 - 350 6 - 7 26 - 32
55 25 122 - 140 216 - 275 14 - 18 22 - 28 101 - 116 290 - 369 9 - 11 28 - 35
55 37.5 121 - 140 200 - 255 10 - 12 22 - 28 107 - 123 293 - 372 6 - 8 29 - 37
68 25 124 - 143 259 - 329 14 - 18 22 - 28 124 - 143 310 - 395 11 - 14 32 - 40
68 37.5 124 - 142 242 - 308 9 - 12 22 - 28 132 - 152 315 - 401 7 - 9 33 - 42
77 25 126 - 145 300 - 382 14 - 18 22 - 28 138 - 159 323 - 411 12 - 15 34 - 43
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
98 WSHP-SVX01Q-EN
Page 99
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*150 (60 Hz) GEH*/GEV*120 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*180 (60 Hz) GEH*/GEV*150 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
Entering
Water
Temp
(°F)
77 37.5 125 - 144 280 - 356 10 - 12 22 - 28 148 - 170 328 - 418 8 - 10 36 - 45
86 25 128 - 147 328 - 417 13 - 17 21 - 27 162 - 187 344 - 438 13 - 17 37 - 47
86 37.5 127 - 146 309 - 393 9 - 11 22 - 27 174 - 201 351 - 446 9 - 12 39 - 49
95 25 129 - 149 366 - 466 13 - 17 21 - 27
95 37.5 129 - 148 348 - 442 9 - 11 21 - 27
32 30 62 - 71 260 - 331 7 - 9 23 - 29
32 45 65 - 75 263 - 334 5 - 6 24 - 30
45 30 119 - 136 189 - 240 15 - 19 22 - 29 79 - 91 277 - 352 8 - 10 26 - 32
45 45 118 - 136 172 - 219 10 - 13 22 - 29 84 - 97 280 - 356 6 - 7 27 - 33
55 30 120 - 138 220 - 280 15 - 19 22 - 28 96 - 111 294 - 375 9 - 11 29 - 36
55 45 120 - 138 205 - 261 10 - 12 22 - 28 102 - 117 297 - 378 6 - 8 30 - 37
68 30 122 - 140 266 - 338 14 - 18 22 - 28 119 - 137 316 - 402 11 - 14 32 - 41
68 45 121 - 140 249 - 317 10 - 12 22 - 28 127 - 146 320 - 407 7 - 9 34 - 43
77 30 123 - 142 308 - 392 15 - 19 22 - 28 133 - 153 329 - 419 12 - 15 35 - 43
77 45 123 - 141 288 - 367 10 - 13 22 - 28 142 - 163 334 - 425 8 - 10 36 - 46
86 30 124 - 143 340 - 432 14 - 18 21 - 27 156 - 179 351 - 447 13 - 17 38 - 48
86 45 124 - 143 321 - 409 9 - 12 21 - 27 167 - 192 357 - 455 9 - 12 40 - 50
95 30 126 - 145 381 - 485 14 - 17 21 - 27
95 45 126 - 145 363 - 461 9 - 12 21 - 27
32 40 64 - 73 256 - 326 6 - 8 25 - 31
32 60 67 - 77 259 - 329 4 - 5 26 - 32
45 40 126 - 145 178 - 226 15 - 19 23 - 29 82 - 94 270 - 344 7 - 9 27 - 34
45 60 125 - 144 165 - 210 10 - 12 23 - 29 86 - 99 274 - 349 5 - 7 28 - 35
55 40 127 - 146 208 - 265 14 - 18 23 - 29 99 - 113 285 - 362 8 - 10 29 - 37
55 60 127 - 146 194 - 247 10 - 12 23 - 29 104 - 120 289 - 368 6 - 7 30 - 38
68 40 129 - 148 253 - 321 14 - 18 22 - 29 122 - 140 303 - 386 10 - 13 33 - 41
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Start-Up
Air
Temp
Rise
(°F DB)
WSHP-SVX01Q-EN 99
Page 100
Start-Up
Table 53. Operating pressures in cooling/heating for GE* units (continued)
Operating Data
Cooling Heating
Model No.
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*240 (60 Hz) GEH*/GEV*180 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
GEH*/GEV*300 (60 Hz) GEH*/GEV*240 (50 Hz)
Entering
Water
Temp
(°F)
68 60 129 - 148 237 - 301 9 - 12 23 - 29 129 - 149 309 - 394 7 - 9 34 - 42
77 40 131 - 150 294 - 374 15 - 19 22 - 28 135 - 156 315 - 400 11 - 14 34 - 43
77 60 130 - 150 275 - 350 10 - 12 22 - 28 144 - 166 322 - 409 8 - 10 36 - 45
86 40 132 - 152 325 - 414 14 - 17 22 - 28 159 - 183 334 - 425 12 - 16 37 - 47
86 60 132 - 152 308 - 392 9 - 12 22 - 28 170 - 196 342 - 436 9 - 11 39 - 49
95 40 134 - 154 367 - 467 13 - 17 22 - 27
95 60 134 - 154 349 - 444 9 - 11 22 - 28
32 50 62 - 71 275 - 350 6 - 8 24 - 30
32 75 65 - 75 279 - 355 4 - 6 25 - 31
45 50 120 - 138 181 - 231 15 - 19 22 - 28 80 - 92 291 - 370 8 - 10 26 - 33
45 75 119 - 137 169 - 215 10 - 13 22 - 28 84 - 97 295 - 376 5 - 7 27 - 34
55 50 121 - 140 209 - 267 14 - 18 22 - 28 96 - 111 309 - 394 8 - 11 29 - 36
55 75 121 - 139 196 - 249 10 - 12 22 - 28 102 - 117 314 - 399 6 - 8 30 - 37
68 50 124 - 142 251 - 320 14 - 18 22 - 27 119 - 137 330 - 420 10 - 13 32 - 40
68 75 123 - 142 236 - 301 9 - 12 22 - 27 127 - 146 335 - 427 7 - 9 33 - 42
77 50 126 - 145 289 - 368 15 - 18 21 - 27 133 - 153 342 - 435 11 - 14 34 - 43
77 75 125 - 144 272 - 346 10 - 12 21 - 27 142 - 163 348 - 443 8 - 10 35 - 45
86 50 127 - 147 319 - 406 13 - 17 21 - 27 156 - 180 362 - 461 13 - 16 37 - 46
86 75 127 - 146 302 - 385 9 - 11 21 - 27 168 - 193 371 - 472 9 - 11 39 - 49
95 50 130 - 149 357 - 454 13 - 17 21 - 26
95 75 129 - 148 340 - 433 9 - 11 21 - 26
Water
Flow
(GPM)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Rise
(°F)
Air Temp
Drop
(°F DB)
Suction
Pressure
(psig)
Discharge
Pressure
(psig)
Water
Temp
Drop
(°F)
Air
Temp
Rise
(°F DB)
Table 54. Operating pressures in cooling/heating for EX* units (60 Hz)
Cooling Heating
Entering
water
Model
EXH*006 35 1.4 94-108 279-355 6-8 23-29 EXH*006 35 1.7 96-110 281-357 5-6 23-29
temp (ºF)
100 WSHP-SVX01Q-EN
Water
flow
(GPM)
Suction
pressure
(psig)
Operating Data
Discharge
pressure
(psig)
Water
temp rise
(ºF)
Air temp
drop
(ºF DB)
Suction
pressure
(psig)
Discharge
pressure
(psig)
Water
Temp drop
(ºF)
Air temp
rise
(ºF DB)
Loading...