Trane GEHE 006-060 - 50-60 Hz, GEVE 006-060 - 50-60 Hz, GEHE 072-120 - 50-60 Hz, GEVE 072-300 - 50-60 Hz, EXHF 006-070 - 60 Hz Installation and Maintenance Manual

...
Installation, Operation, and Maintenance
Water Source Heat Pump
Axiom™ Horizontal/Vertical
Model Numbers
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
September 2014
GEHE 006-060 - 50/60 Hz GEVE 006-060 - 50/60 Hz GEHE 072-120 - 50/60 Hz GEVE 072-300 - 50/60 Hz EXHF 006-070 - 60 Hz EXVF 006-070 - 60 Hz
SAFETY WARNING
WSHP-SVX01N-EN

Introduction

Read this manual thoroughlybeforeoperating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or serious injury.
© 2014 Trane All rights reserved WSHP-SVX01N-EN

Copyright

This document andthe information in it arethe property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Axiom, ReliaTel,TOPSS,Tracer,Trane, and theTrane logo are trademarks or registered trademarks ofTrane in the United States and other countries.Trane is a business of Ingersoll Rand. All trademarks referenced in this document are the trademarks of their respective owners.
LonTalk is a registered trademark of Echelon Corporation.
BACnet is a registered trademark of ASHRAE.
Revision History
Introduction
WSHP-SVX01N-EN (12 Sep 2014)
Edited Model Number, Electrical Data, Fan Performance - 2 speed motor change
WSHP-SVX01N-EN 3
Table of Contents
Introduction ............................. 2
Warnings, Cautions, and Notices ........ 2
Important Environmental Concerns ..... 2
Important Responsible Refrigerant Practices 2
Copyright ............................. 3
Model Number Description ............... 5
½to5Ton ............................ 5
Model Number Description ............... 6
6to25Ton ........................... 6
Model Number Description ............... 7
½to6Ton ............................ 7
Overview of Manual ..................... 8
Unit Nameplate ..................... 8
Compressor Nameplate ............... 8
Model Number Description ............ 8
General Information ..................... 9
Pre-Installation ......................... 13
Unit Inspection Checklist ............. 13
Jobsite Inspection Checklist .......... 13
Jobsite Storage .................... 13
Unit Dimensions and Weights ........... 14
GEH and EXH Clearance Dimensions . . . 14
GEV ½ to 5 tons and EXV ½ to 6 tons clear-
ance dimensions ................... 15
Weight Distribution for Hanging the GEH and
EXH Model ........................ 55
Installation ............................. 56
General Installation Checks ........... 56
Main Electrical ..................... 56
Supply-Air Ductwork ................ 57
Return-Air Ductwork ................. 57
Ducted Panel ....................... 57
Ducted Filter Rack ................... 58
Dual Filtration (GEH ½-5 ton and EXH ½-6
ton) .............................. 58
Sound Attenuation Pad .............. 59
Hanging the Horizontal Unit .......... 59
Condensate Drain Connection ......... 59
Supply/Return Pipe Connections .......60
Types of Hose Connections ............60
Cleaning and Flushing the Water Loop . .61
Field Installed Power Wiring ...........61
Main Unit Power Wiring ..............61
Control Power Transformer ...........62
Thermostat Location .................62
Controls Using 24 VAC ...............62
Blower Motor Speed-Tap Retrofit .......63
Hole Plug Installation .................64
Air Flow Adjustment .................64
Waterside Economizer Installation ......65
Waterside Economizer Installation for GEH
and GEV 6 to 25 Ton Models ...........68
Waterside Economizer Start-Up Sequence .70
Electrical Data ...........................72
Pre-Start Checklist .......................92
Start-Up ................................93
Initial Unit Start-up ....................93
Start-Up Checklist and Log ............93
Operating Pressures .................93
Water Pressure Drop ................115
Water Volume ......................117
Maintenance ...........................118
Preventive Maintenance .............118
Condensate Trap ...................118
Troubleshooting ........................119
Wiring Diagrams .......................121
Warranty Information ...................131
Standard Warranty ..................131
Extended Warranty .................131
4 WSHP-SVX01N-EN

Model Number Description

½to5Ton

GEH E 006 11*01B0BRD01000010 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26-36
Digits 1-3 — Unit Configuration
GEH = Standard Efficiency Horizontal GEV = Standard Efficiency Vertical
Digit 4 Development Sequence
E = R-410A
Digits 5-7 — Nominal Capacity
006=½Ton 030=2½Ton 009=¾Ton 036=3Ton 012=1Ton 042=3½Ton 015=1¼Ton 048=4Ton 018 = 1½Ton 060= 5Ton 024=2Ton
Digit 8 — Voltage (Volts/Hz/ Phase)
0 = 115/60/1 5 = 575/60/3 1 = 208/60/1 6 = 220-240/50/1 2 = 230/60/1 7 = 265/60/1 3 = 208/60/3 8 = 230/60/3 4 = 460/60/3 9 = 380-415/50/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil 8 = Insulated Cupro-Nickel Water Coil
Digit 10 — Current Design Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
Digit 12 — Blower Configuration
1 = Standard Blower Motor 2 = High Static Blower Motor
Digit 13 — Freeze Protection
A= 20°F Freezestat (extended range
geothermal)
B= 35°F Freezestat
Digit 14 —Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement F = Front Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement
Digit 16 — Return-Air
Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 — Control Types
0 = Basic 24V Controls D = Deluxe 24V Controls B =Tracer ZN524 Controls F = UC400 G = UC400 w/ Wireless Comm
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = None 1 = Entering Water Sensor
Digit 21 — Open
Digit 22 — Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat
Digit 23 — Open
Digit 24 — Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4=MERV8 5=MERV13
Digit 25 — Acoustic
Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digits 26-36 — Does Not Apply to GEH or GEV
000 00000000 = Digits 26-36 are not applicable to the GEH or GEV products
WSHP-SVX01N-EN 5

Model Number Description

6to25Ton

GEH E 072 11*0A00ABD0000001 0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25-36
Digits 1-3 - Unit Configuration
GEH = High Efficiency Horizontal GEV = High Efficiency Vertical
Digit4-Development Sequence
E = R-410A
Digits 5-7 - Nominal Capacity
072=6Ton 180=15Ton 090 = 7½Ton 240 = 20Ton 120=10Ton 300=25Ton 150 = 12½Ton
Digit 8 - Voltage (Volts/Hz/ Phase)
1 = 208/60/1 2 = 230/60/1 3 = 208/60/3 4 = 460/60/3 5 = 575/60/3 6 = 220-240/50/1 7 = 265/60/1 8 = 230/60/3 9 = 380-415/50/3
Digit 9 - Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil 8 = Insulated Cupro-Nickel Water Coil
Digit 10 - Current Design Sequence
Digit 11 - Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
4 = Heating and Cooling Circuit with
HGR and WSE
Digit 12 - Blower Configuration
A = Drive Package A (GEH/GEV)
B = Drive Package B (GEH/GEV) C = Drive Package C (GEH/GEV) D = Drive Package D (GEH/GEV) E = Drive Package E (GEH/GEV) F = Drive Package F (GEH/GEV) G = Drive Package G (GEH/GEV) H = Drive Package H (GEH/GEV) J = Drive Package J (GEH/GEV) 1 = 2 Speed Drive Package A (GEH/GEV) 2 = 2 Speed Drive Package B (GEH/GEV) 3 = 2 Speed Drive Package C (GEH/GEV) 4 = 2 Speed Drive Package D (GEH/GEV) 5 = 2 Speed Drive Package E (GEH/GEV) 6 = 2 Speed Drive Package F (GEH/GEV) 7 = 2 Speed Drive Package G (GEH/GEV) 8 = 2 Speed Drive Package H (GEH/GEV) 9= 2 Speed Drive Package J (GEH/GEV)
Digit 13 - Freeze Protection
A = 20°F Freezestat
B = 35°F Freezestat
Digit 14 - Open Digit = 0
Digit 15 - Supply-Air
Arrangement
B = Back Supply-Air Arrangement F = Front Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement
Digit 16 - Return-Air
Arrangement
B = Back Return-Air Arrangement F = Front Return-Air Arrangement L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 - Control Types
D = Deluxe 24V Controls B = Tracer ZN524 Controls F = UC400 G = UC400 w/ Wireless Comm
Digit 18 - Open
0 = Wall Mounted Location
Digit 19 - Fault Sensors
0 = No Fault Sensor 1 = Condensate Overflow Sensor 2 = Filter MaintenanceTimer 3 = Condensate Overflow and Filter
MaintenanceTimer 4 = Fan Status Sensor 6 = Condensate Overflow and Fan
Status H = Fan Status and Filter
MaintenanceTimer J = Fan Status, Filter Maintenance
Timer and Condensate Overflow
Sensor
Digit 20 - Open
0 = No AdditionalTemperature Sensor
Digit 21 - Open
Digit 22 - Electric Heat
0 = No Electric Heat 4 = External Boilerless Electric Heat 5 = External Supplemental Electric
Heat
Digit 23 - Open
Digit 24 - Filter Type
1 = 1 in.Throwaway Filter 2 = 2 in.Throwaway Filter
Digit 25-36 - Does Not Apply to GEH or GEV
00000000000 = Digits 25-36 are not applicable to the GEH or GEV products
6 WSHP-SVX01N-EN

Model Number Description

½to6Ton

EXH F 006 11*03B0BRD01000010 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26-36
Digits 1-3 — Unit Configuration
EXH = High Efficiency Horizontal EXV = High Efficiency Vertical
Digit 4 Development Sequence
F
Digits 5-7 — Nominal Capacity
006 - 1/2 ton 030 = 2½Ton 009 - 3/4 ton 036 = 3Ton 012 - 1 ton 042 = 3½Ton 015-1¼ton 048=4Ton 018 = 1½Ton 060= 5Ton 024 = 2Ton 070= 6Ton
Digit 8 — Voltage (Volts/Hz/ Phase)
1 = 208/60/1 4 = 460/60/3 2 = 230/60/1 7 = 265/60/1 3 = 208/60/3 8 = 230/60/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper Water
Coil/Suction Line
8 = Insulated Cupro-Nickel Water
Coil/Suction Line
Digit 10 — Current Design Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
Digit 12 — Blower Configuration
3 = ECM Motor
Digit 13 - Freeze Protection
A = 20°F freezestat
B = 35°F freezestat
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement
Digit 16 — Return-Air
Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 — Control Types
D = Deluxe 24V Controls B = Tracer™ ZN524 Controls F = UC400 G = UC400 w/ Wireless Comm
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = No AdditionalTemperature Sensor 1 = Entering Water Sensor
Digit 21 — Open Digit
Digit 22 — Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat
Digit 23 — Open Digit
Digit 24 — Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4= MERV8 5 = MERV13
Digit 25 — Acoustic
Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digits 26-36 — Does not Apply to EXH or EXV
000 00000000 Digits 26-36 are not applicable to the EXH or EXV products
WSHP-SVX01N-EN 7

Overview of Manual

Note: One copy of this document ships with each unit and
is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for HVAC systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
Service and maintenance work should be performed by a qualified technician and all electrical service and maintenance work should be performed by a qualified licensed electrician.

Unit Nameplate

The unit nameplate is located on the outside of the control
box access panel at thefront of the unit. Itincludes the unit model number, serial number, electrical characteristics, refrigerant charge, and other pertinent unit data.

Compressor Nameplate

The nameplate for the compressors are located on the
compressor shell.

Model Number Description

All products are identified by a multiple-character model number that preciselyidentifies a particular type of unit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial number printed on the unit nameplate.
8 WSHP-SVX01N-EN

General Information

Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak tested to assure there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).
Table 1. High/Low pressure switch
Trip Recover Unit
LP 40 +/-4 56 +/-4 psig
HP 650 +/-10 550 +/-10 psig
Controls
Basic 24V control is available for the GEH/V ½ -5 ton models and the Deluxe 24V control option is available for all unit sizes.Tracer™ ZN524, LonTalk® certified control option is available for allunit sizes. UC400 and UC400 with wireless comm BACnet is available in all unit sizes.
All power wiring to the equipment is made at the unit
contactor for ½- 5 ton, 1-phase units. For 3-phase units all power wiring to the equipmentis made tothe contactor or power block. For EXH/V070 units all power wiring to the equipment is made to the power block. For the GEH/V 6-25 tons units all power wiring is made to the high voltage terminal block. All low-voltage wiring is made at the unit’s low voltage terminal board. EXH and EXV 460V units require a neutral wire.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system
is required to operate the water-source heat pump.The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V
control systems may be locatedin the back of this manual.
All digital control troubleshooting tips and connection
diagrams are located in WSHP-PRB002-EN (ZN524).
Basic 24V Controls
Safety devices for equipment containing the basic 24V control option include a low-pressure switch to prevent compressor operation during low temperature or low suction activity.The switch is set to activate at refrigerant pressure of 40 psig to fit most applications.
A high pressure switch prevents compressor operation
during high or excessive discharge pressures exceeding 650 psig.
The lockout relay will disable the compressor on a high or
low pressure condition. For units that contain a condensate overflow switch option, a condensate overflow condition will also disable the compressor through the lockout relay.The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay.
This feature will drive dry contacts only, and cannot be
used to drive field installed control inputs.Trane provides a 3½-minute time delay for compressor control.
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board.The
Trane® microprocessor board is factory wired to a
terminal strip to provide all necessary terminals for field connection.The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, condensate overflow, unit safety control, diagnostics, and a generic relay (which may be available for field use). See Table 65, p. 119 for diagnostic information and Figure 59, p. 62 and Figure 60, p. 63 for thermostat connections.
Tracer™ UC400
TheTracer™ UC400 is a BTL Listed BACnet® controller
that can operate stand- alone or within a Building
Automations system such asTracer™ SC.
Tracer ZN524 Controls (option)
The digital ZN524 controller is designed to support the ½
to 25 ton water-source heat pumps in either a standalone, peer-to-peer with aTracer Loop Controller, or as a full building automation (open protocol) system.
For installation, operation and diagnostics see WSHP­PRB002-EN (ZN524).
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual 1/
6 HP bronze pump and a brass three-way shut-off valve. Cast iron pumps are also acceptable.The pump module kits shall contain the necessary components for the installation, operation and maintenance of the water circuit of a closed-loop distributed pumping application.
WSHP-SVX01N-EN 9
General Information
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin
economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 60°F (for the Deluxe control option), or below the programmed set-point (for the ZN524 control option).
When the temperature is less than the setpoint, fluid will
flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control. Entering water temperature sensor is factory provided for field installation on the entering water side of the coil.
Boilerless Control/Electric Heat (Option)
Systems that do not contain a boiler may contain a boilerless control with electric heat.Trane® offers both a factory mounted electric heat option, and a field mounted duct heater option.
If the ½-5 ton GEH, GEV and EXH/V070 unit incorporates the factory mounted option, the unit will ship from the factory with an internally mounted nichrome open wire heating element, designed to start-up electric heat as the systems primary heat in the event entering water temperature falls below 55°F. Once the entering water temperature rises above 60°F, the boilerless controller returns the unit to normal compressor heating operation, and locks out the electric heater.
For units comprised of the field installed duct heater option, the unit will ship from the factory with controls available to interface with the field provided electric heat selection.
Note: For geothermal applications, the boilerless
controller has an adjustable setting of 25, 35, 45, 55, and 60 degrees.
Supplemental or Boilerless Electric Heat (option)
The GEH/V 6-25 ton models which contain boilerless
control electric heat or supplemental electric heat will contain the controls interface ONLY for field provided electric heat selection.The heater for this model shall be external to the equipment by the contractor for ease of installation. All power connections for the electric heater will be completely separate from theunit for field supplied electric heat.
Note: When the unit has boilerless control, the electric
heat is not used as supplemental electric heat, but as a primary heat.
Hot Gas Reheat (option)
With the reheat option, the return-air from the space is
conditioned by the air-to-refrigerant coil, then reheated by the reheat coil to control not only the space temperature, but to also reduce the relative humidityof the space. When operating in the reheat mode (meaning the sensible temperature has been met in the space), the humidistat signals the reheat relay coil to energize, allowing the high pressure refrigerant gas to flow from the compressor through the reheat valve, into the reversing valve, or reheat coil.
A switching relay has been provided for the reheat
application to adjust the blower motor from normal operation to low speed when the hot gas reheat is energized (for ½ -5 ton and EXH/V070 equipment only).
Note: A high static blower motor is required to support
the hot gas reheat option for the GEH/V ½ -5 ton.
Note: Units containing the hot gas reheat option should
not be used as a make-up air unit.
2 Speed Blower Motor (option)
The 6-25 ton GEH/V models have indoor blowers that are
available with 2 speed motors, selectable in the model number (Digit 12, drive packages one to nine). High speed airflow matches the single speed motor airflow, referenced in the Fan Performance tables. Low fan speed airflow is approximately 50% of high fan speed airflow.
The 6-25 ton GEH/V two-speed blower motors are
available with the following options: Deluxe24V or UC400 controls, Heat Pump (HP) or HP w/Hot Gas Reheat or HP w/
Waterside Economizer. Not available with Boilerless or
Supplemental Electric Heat.
Table 2. 6 to 25 ton GEH/V fan speed for two-speed
RV State Fan
drive packages one to nine
Compresso
r 1
Heat OFF OFF OFF OFF Heat ON OFF OFF HIGH Heat ON ON OFF HIGH Heat ON ON ON HIGH Cool OFF OFF OFF OFF Cool ON OFF OFF LOW Cool ON ON OFF LOW Cool ON ON ON HIGH
Compresso
r 2 Fan Speed
10 WSHP-SVX01N-EN
Table 3. Refrigerant charge
General Information
Model
(60 Hz)
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
Circuit 1 Circuit 2 Circuit 1 Circuit 2
GEHE006 25.3 / .717 ----- 26.8 / .760 ----­GEHE009 26.0 / .737 ----- 27.5 / .780 ----­GEHE012 28.5 / .808 ----- 30.5 / .865 ----­GEHE015 29.0 / .822 ----- 30.5 / .865 ----­GEHE018 36.5 / 1.035 ----- 39.5 / 1.120 ----­GEHE024 39.0 / 1.106 ----- 42.0 / 1.191 ----­GEHE030 44.0 / 1.247 ----- 46.5 / 1.318 ----­GEHE036 50.0 / 1.417 ----- 53.5 / 1.517 ----­GEHE042 57.0 / 1.616 ----- 60.5 / 1.715 ----­GEHE048 61.0 / 1.729 ----- 65.5 / 1.857 ----­GEHE060 73.0 / 2.070 ----- 77.5 / 2.197 ----­GEVE006 25.7 / .789 ----- 27.2 / .771 ----­GEVE009 26.5 / .751 ----- 28.0 / .794 ----­GEVE012 29.5 / .836 ----- 31.5 / .893 ----­GEVE015 27.5 / .780 ----- 29.5 / .836 ----­GEVE018 37.0 / 1.049 ----- 40.0 / 1/134 ----­GEVE024 39.0 / 1.106 ----- 41.5 / 1.177 ----­GEVE030 44.5 / 1.262 ----- 47.0 / 1.332 ----­GEVE036 51.0 / 1.446 ----- 54.5 / 1.545 ----­GEVE042 54.0 / 1.531 ----- 57.5 / 1.630 ----­GEVE048 61.0 / 1.729 ----- 66.0 / 1.871 ----­GEVE060 74.0 / 2.098 ----- 79.5 / 2.254 ----­GEHE072 55 / 1.559 55 / 1.559 59 / 1.673 55 / 1.559 GEHE090 64 / 1.814 54 / 1.531 68 / 1.928 54 / 1.531 GEHE120 86 / 2.438 86 / 2.438 90 / 2.551 86 / 2.438 GEHE150 136 / 3.856 136 / 3.856 144 / 4.082 136 / 3.856 GEHE180 126 / 3.572 126 / 3.572 134 / 3.799 126 / 3.572 GEVE072 58 / 1.644 58 / 1.644 62 / 1.758 58 / 1.644 GEVE090 83 / 2.353 75 / 2.126 87 / 2.466 75 / 2.126 GEVE120 88 / 2.495 88 / 2.495 92 / 2.608 88 / 2.495 GEVE150 122 / 3.459 122 / 3.459 130 / 3.685 122 / 3.459 GEVE180 128 / 3.629 128 / 3.629 136 / 3.856 128 / 3.629 GEVE240 284 / 8.051 284 / 8.051 292 / 8.278 284 / 8.051 GEVE300 260 / 7.371 260 / 7.371 267 / 7.569 260 / 7.371 EXHF006 25.3 / 0.717 ----- 26.8 / 0.760 ----­EXHF009 26.0 / 0.737 ----- 27.5 / 0.780 ----­EXHF012 28.5 / 0.808 ----- 30.5 / 0.865 ----­EXHF015 29.0 / 0.822 ----- 30.5 / 0.865 ----­EXHF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXHF024 50.5 / 1.432 ----- 53.0 / 1.503 ----­EXHF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXHF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXHF042 81.0 / 2.296 ----- 85.5 / 2.424 ----­EXHF048 83.0 / 2.353 ----- 87.5 / 2.481 -----
continued on next page
WSHP-SVX01N-EN 11
General Information
Table 3. Refrigerant charge (continued)
Model
(60 Hz)
EXHF060 114.0 / 3.232 ----- 118.5 / 3.359 ----­EXHF070 122.0 / 3.459 ----- 127.0 / 3.600 ----­EXVF006 25.7 / 0.729 ----- 27.2 / 0.771 ----­EXVF009 26.5 / 0.751 ----- 28.0 / 0.794 ----­EXVF012 29.5 / 0.836 ----- 31.5 / 0.893 ----­EXVF015 30.0 / 0.850 ----- 32.0 / 0.907 ----­EXVF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXVF024 52.0 / 1.474 ----- 54.5 / 1.545 ----­EXVF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXVF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXVF042 81.0 / 2.296 ----- 86.0 / 2.438 ----­EXVF048 83.0 / 2.353 ----- 88.5 / 2.509 ----­EXVF060 114.0 / 3.232 ----- 119.5 / 3.388 ----­EXVF070 122.0 / 3.459 ----- 128.0 / 3.629 -----
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
12 WSHP-SVX01N-EN

Pre-Installation

WARNING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

Unit Inspection Checklist

Unpack all components of the kit.
Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
Important: Equipment is shipped FOB (Free on Board)
at the manufacturer.Therefore, freight claims for damages against the carrier must be initiated by the receiver.
Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the shipment.
Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Do not attempt to repair any damaged parts until the parts are inspected by the carrier’s representative.

Jobsite Storage

WARNING
Microbial Growth!
Wet interior unit insulation can become an amplification
site for microbialgrowth (mold), which may cause odors and serious health related indoor air quality problems. If there is evidence of microbial growth (mold) on the interiorinsulation, removeor replace the insulation prior to operating the system. Failure to remove microbial growth could result in serious health problems.
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible IAQ contaminant sources fromgrowing, the unit should be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
Cover the unit(s) with a water proof tarp to protect them from the elements.
Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
Store units in the normal UP orientationto maintain oil in the compressor.
Horizontal units may be stacked no more than three units high. Do not stack the vertical unit configurations.

Jobsite Inspection Checklist

Always perform the following checks before
accepting a unit:
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the unit(s) are unloaded. Once thebill of lading is signed at the jobsite, the unit(s) are now the property of the SOLDTO party and future freight claims MAY NOT be accepted by the freight company.
WSHP-SVX01N-EN 13

Unit Dimensions and Weights

GEH and EXH Clearance Dimensions

Access to the unit for service purposes should be provided
at installation. All ½-5 tons and EXH070 configurations (see Figure 1, p. 14) require an 18 in. (457 mm) surround clearance from other mechanical and electricalequipment (where shown) to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes
Figure 1. GEH ½ to 5 tons and EXH ½ to 6 tons clearance
18" (457) (3-SIDES)
LEFT RETURN
BACK SUPPLY
UNIT FRONT
36"
(914)
18" (457)
(3-SIDES)
LEFT RETURN
RIGHT SUPPLY
UNIT FRONT
36"
(914)
require a greater service clearance than listed below. Check all code requirements prior to unit installations.
Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) limitation on one side. Access to theTXV may not be possible with this 3 in. (229 mm) clearance.This configuration is typically applied in a corridor installation, where space limitations force the left or right side of the unit against a wall.
18" (457) (3-SIDES)
LEFT RETURN LEFT SUPPLY
3"
(76)
UNIT FRONT
36"
(914)
18" (457)
(3-SIDES)
RIGHT RETURN
BACK SUPPLY
UNIT FRONT
36"
(914)
Figure 2. GEH 6-15 tons clearance
36"
(914)
SERVICE
CLEARANCE
TOP VIEW
CONTROL BOX
18" (457) (3-SIDES)
RIGHT RETURN
LEFT SUPPLY
UNIT FRONT
36"
(914)
18" (457) (3-SIDES)
RIGHT RETURN RIGHT SUPPLY
3"
(76)
UNIT FRONT
36"
(914)
Service clearance dimensions for the GEH 6-15 tons horizontal (see Figure 2, p. 14) includes a two side access appropriate for control and blower motor/wheel access. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
20"
(508)
SERVICE
CLEARANCE
BLOWER ACCESS PAN EL
14 WSHP-SVX01N-EN
Unit Dimensions and Weights
E

GEV ½ to 5 tons and EXV ½ to 6 tons clearance dimensions

Access to the unit for service purposes should be provided
at installation. A 24 in. surround clearance (see Figure 3,
p. 15) from other mechanical and electrical equipment
(where shown) is recommended for all configurations.
This will enable panel removal from the unit for service/
maintenance. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations. Units in a free return application will require more than a 12 in. minimum clearance to provide proper air flow to the units air-to-refrigerant coil. Pictured in Figure 3,p. 15 minimum 1” clearance on return side with properly attached duct work.
Figure 3. GEV ½-5 tons and EXV ½-6 tons clearance
dimensions
1"
(25.4)
24"
(610)
RIGHT RETURN
TOP/BACK SUPPLY
1"
(25.4)
UNIT FRONT
36"
(914)
1"
(25.4)
GEV 6–10 Tons Clearance Dimensions
A 36 in. service clearance is required for all configurations
at the unit front. It is recommended that 20 in of service clearance for the sides (see Figure 4, p. 15) from other mechanical and electrical equipment (where shown).The unit may be serviced through the front access panel or remaining open sides. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
Figure 4. GEV 6–10 tons clearance
FRONT RETURN
TOP SUPPLY
ACCESS PANEL FOR SHEAVES AND BELTS
20"
(508)
SERVICE
CLEARANCE
(914)
SERVICE
CLEARANC
GEV 12½–25 Tons Clearance Dimensions
Figure 5, p. 15 outlines service clearances. A 36 in. service
clearance is requiredfor all configurationsat the unitfront.
A 24 in. service clearance (see Figure 3, p. 15) from other
mechanical and electrical equipment (where shown) is recommended for all configurations.The unit may be serviced through the front accesspanel. Some local codes require a greater service clearance than listed below. Check all code requirements prior to unit installations.
Figure 5. GEV 12½–25 tons clearance
18" (457)
CONTROL BOX
NEC REQ.
MIN. 36" (914)
C.B. TO WALL
CLEARANCE
FRONT RETURN-AIR
BACK SUPPLY-AIR
UNIT FRONT
16" (406) TO
FILTER FRAME
FOR RETURN-AIR
MIN. SERVICE CLEARANCE FOR EITHER LEFT OR RIGHT SIDE IS 22" (559). FOR FAN SHAFT REMOVAL, A 22" (559) CLEARANCE MUST BE PROVIDED ON EITHER THE LEFT OR RIGHT SIDE.
36"
UNIT FRONT
24"
(610)
1"
(25.4)
36"
(914)
LEFT RETURN
TOP/BACK SUPPLY
WSHP-SVX01N-EN 15
Unit Dimensions and Weights
Figure 6. Left return/left supply (GEH/EXH)
BP
TOP
F X G
OPENING
C
BLOWER
ACCESS
PANEL
1" (25.4)
DRAIN
3/4" (19) NPTI
BACK LEFT SIDE FRONT
RIGHT SIDE
H
Q
K
(13)
1/2"
14"
(356")
H
J
RS
N
A
HI VOLT
WCI mounting location
LO VOLT
ED
6 3/4"
1" (25.4)
REFRIG
AND
CONTROL
(171)
ACCESS
L (W.O.)
M (W.I.)
7"
(178)
1 3/8" (35)
Table 4. Left return/left supply (GEH/EXH)
GEH Unit A B C D
006, 009 012, 015
018 024, 030 036, 042
Std-048
Hi-048,
06058(1473)33(838)21(533)
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
EXH Unit A B C D
006-009 012-015 018-024 030-036 042-070
070
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
(a) Return air opening dimension (b) Filter rack dimension
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
es:
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
with this 3 in. (229 mm) clearance.
access on either side of the filter.
(a)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 6-7/8 x 9-7/8
(175) x (251) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
4-1/2
1-3/4
(114) 4-1/4
(108) 4-3/4
1-3/8
(121) 4-3/4
1-3/8
(121)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
(45)
3/4
(19) (35) (35)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/4
1-3/4
(108)
(45)
4-1/4 (108)
(19)
4-3/4
1-3/8
(121)
(35)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
3/4
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
(b)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
16 WSHP-SVX01N-EN
Figure 7. Left return/back supply (GEH/EXH)
Unit Dimensions and Weights
BP
TOP
F X G
OPENING
C
1"(25.4)
H
DRAIN 3/4" (19) NPTI
BLOWER
H
J
BACK LEFT SIDE FRONT
14"
RIGHT SIDE
(356)
ACCESS
PANEL
K
N
A
Table 5. Left return/back supply (GEH/EXH)
GEH Unit A B C D
006, 009 012, 015
018 024, 030 036, 042
Std-048
Hi-048, 060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
(175) x (203) 6-7/8 x 9-7/8
(175) x (251) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
23-1/2
(749)
23-1/2
(749)
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
R
HI VOLT
WCI mounting location
LO VOLT
ED
6-7/8 x 8
1" (25.4)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
S
6 3/4"
(171)
Q
1/2"
(13)
4-1/2
1-3/4
(114)
(45)
4-1/4 (108)
(19)
4-3/4
1-3/8
(121)
(35)
4-3/4
1-3/8
(121)
(35)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
5-1/4
1-1/2
(133)
(38)1 (25)1 (25)
3/4
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
7"
(178)
1 3/8" (35)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
EXH Unit A B C D
006-009 012-015 018-024 030-036 042-070
070
es:
Not
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
29-1/2 29-1/2
(a)
(597) (597)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749) 231/2
(749)
6 -7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
9-3/4 (248)
9-3/4 (248)
1-3/4 2-3/4 3-1/4
1-1/2 1-1/2
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(45) (70) (83)
(38)1(25)1(25) (38)1(25)1(25)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the
control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is
responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible with this 3 in. (229 mm) clearance.
ance from other
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension (b) Filter rack dimension
WSHP-SVX01N-EN 17
Unit Dimensions and Weights
Figure 8. Left return/right supply (GEH/EXH)
TOP
N
A
ED
BLOWER
1" (25.4)
ACCESS
PANEL
Q
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
BP
REFRIG
AND
(171)
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
(178)
DRAIN 3/4" (19) NPTI
BACK LEFT SIDE FRONT
RIGHT SIDE
1/2"
(13)
C
F X G
OPENING
H
K
H
1" (25.4)
14"
J
1 3/8" (35)
Table 6. Left return/right supply (GEH/EXH)
GEH Unit A B C D
40 40 46 46 50 58 58
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)
(381) (381) (457) (457) (483) (533) (533)
006, 009 012, 015
018 024, 030 036, 042
Std-048
Hi-048, 060
(1016) (1016) (1168) (1168) (1270) (1473) (1473)
EXH Unit A B C D
006-009 012-015 018-024 030-036 042-070
070
es:
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension (b) Filter rack dimension
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
15 15 18 18 19 21 21
(a)
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
15
6-7/8 x 8 (175) x
(381)
15
(381)
18
(457)
18
(457)
20
(508)
23-1/2
(749)
23-1/2
(749)
(203)
6-7/8 x 9-7/8 (175) x (251)
8-1/4 x 9-3/4 (210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)
13-1/8 x 11-3/8
(333) x (289)
13-7/8 x 13-7/8
(352) x (352)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
17
(432)
18
(457)
18
(457)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
4-3/4 (121)
4 (102)
5-1/4 (133)
5-1/4 (133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
(13) (13) (19) (19) (19)
2-3/4
(70)
3-1/4
(83)
3-1/4
(83)
1
(25)
1-1/2
(38)1 (25)1 (25)
1-1/2
(38)1 (25)1 (25)
1/2 1/2 3/4 3/4 3/4
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
E F x G H J KL NPTIM NPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
5-1/4 (133)
5-1/4 (133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(13) (13) (19) (19)
2-3/4
(70)
3-1/4
(83)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
1/2 1/2 3/4 3/4
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
18 WSHP-SVX01N-EN
Figure 9. Right return/left supply (GEH/EXH)
R
TOP
N
A
ED
1" (25.4)
BLOWER
ACCESS
PANEL
DRAIN 3/4" (19) NPTI
RIGHT SIDE
H
K
H
BACK LEFT SIDE FRONT
J
7" (178)
C
F X G
OPENING
WCI mounting location
HI VOLT
LO VOLT
1"(25.4)
14"
(356)
S
6 3/4"
Unit Dimensions and Weights
BP
REFRIG
AND
CONTROL
(171)
ACCESS
L (W.O.)
M (W.I.)
Q
(13)
1/2"
1 3/8"(35)
Table 7. Right return/left supply (GEH/EXH)
GEH Unit A B C D
006, 009 012, 015
018 024, 030 036, 042
Std-048
Hi-048, 060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
EXH Unit A B C D
006-009 012-015 018-024 030-036 042-070
es:
Not
070
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
(a)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 6-7/8 x 9-7/8
(175) x (251)
8-1/4 x 9-3/4 (210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1 (25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
4-3/4 (121)
5-1/4 (133)
5-1/4 (133)
1-3/4
1/2
(45)
(13)
3/4 (19)
1-3/8 1-3/8
1-1/2 1-1/2
1/2
(13)
3/4
(35)
(19)
3/4
(35)
(19)
3/4
(19) (38)1 (25)1 (25) (38)1 (25)1 (25)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
5-1/4 (133)
5-1/4 (133)
1-3/4
1/2
(45)
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(13) (13) (19) (19)
3/4
(19)
1-3/8
(35)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
1/2 1/2 3/4 3/4
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension (b) Filter rack dimension
(b)
(b)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
WSHP-SVX01N-EN 19
Unit Dimensions and Weights
Figure 10. Right return/back supply (GEH/EXH)
R
TOP
N
F X G
OPENING
A
ED
S
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
H
Q
1" (25.4)
6 3/4" (171)
1/2" (13)
7"
(178)
1 3/8" (35)
BLOWER
ACCESS
PANEL
HI VOLT
WCI mounting location
LO VOLT
(356)
14"
K
C
1" (25.4)
H DRAIN 3/4" (19) NPTI
J
BACK LEFT SIDE FRONT
RIGHT SIDE
Table 8. Right return/back supply (GEH/EXH)
GEH Unit A B C D
006,009
012,015
018
024,030
036,042
Std-048
Hi-048,
060
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
46
(1168)23(584)18(457)23(584)18(457)
25
50
(1270)
(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)33(838)21(533)
EXH Unit A B C D
006-009
012-015
018-024
030-036
042-070
070
Not
es:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
(a) Return air opening dimension (b) Filter rack dimension
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
(a)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
23-1/2
(749)
23-1/2
(749)
8 x 6-3/4 (203) x (171) 9-1/2 x 6-3/4
(241) x (171) 9-1/2 x 8-1/8 (241) x (206)
11-1/4 x 8-1/4
(286) x (210)
13-1/2 x 10-1/2
(343) x (267)17(432)4(102)1(25)
13-1/8 x 11-1/4
(333) x (286)18(457)
13-1/2 x 13-3/4
(343) x (349)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
4-1/2 (114) 4-1/2 (114) 4-3/4 (121) 4-3/4 (121)
5-1/8 (130) 5-1/8 (130)
1-5/8
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
(41)
1-5/8
(41)
3-1/4
(83)
3-1/4
(83)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
38-3/4
(984)
38-3/4
(984) 44-3/4 (1137) 44-3/4 (1137) 48-3/4 (1238) 56-3/4
(1441) 56-3/4
(1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
E F x G H J KL NPTIM NPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
9-3/4 (248)
9-3/4 (248)
1-3/4
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(45)
2-3/4
(70)
3-1/4
(83)
1-1/2
(38)1(25)1(25)
1-1/2
(38)1(25)1(25)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
(b)
(b)
S
3-1/4
(83)
3-1/4
(83) 4-1/4 (108) 4-1/4 (108) 3-1/4
(83) 5-1/2 (140) 5-1/2 (140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from other
20 WSHP-SVX01N-EN
Figure 11. Right return/right supply (GEH/EXH)
S
6 3/4" (171)
FRONT
1"
(25.4)
1" (25.4)
BLOWER ACCESS
PANEL
DRAIN 3/4" (19) NPTI
TOP
BACK
R
N
A
ED
C
LEFT SIDE
HI VOLT
WCI mounting location
LO VOLT
F X G
OPENING
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
Unit Dimensions and Weights
Q
(13)
1/2"
(356)
14"
H
7" (178)
1 3/8" (35)
RIGHT SIDE
H
J
K
Table 9. Right return/right supply (GEH/EXH)
GEH Unit A B C D
40
40 46 46 50 58 58
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
33
(838)
33
(838)
(381) (381) (457) (457) (483) (533) (533)
006, 009 012, 015
018 024, 030 036, 042
Std-048
Hi-048, 060
(1016) (1016) (1168) (1168) (1270) (1473) (1473)
EXH Unit A B C D
006-009 012-015 018-024 030-036 042-070
es:
Not
070
40
(1016)20(508)15(381)20(508)15(381)
40
(1016)20(508)15(381)20(508)15(381)
46
(1168)23(584)18(457)23(584)18(457)
50
(1270)25(635)19(483)25(635)20(508)
58
(1473)33(838)21(533)
58
(1473)39(991)21(533)
15 15 18 18 19 21 21
(a)
20
(508)
20
(508)
23
(584)
23
(584)
25
(635)
29-1/2
(597)
29-1/2
(597)
(a)
29-1/2
(597)
29-1/2
(597)
E F x G H J KLNPTIMNPTI N P Q R
15
(381)
15
(381)
18
(457)
18
(457)
20
(508)
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 6-7/8 x 9-7/8
(175) x (251) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)
13-1/8 x 11-3/8
(333) x (289)
13-7/8 x 13-7/8
(352) x (352)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
13-1/2
(343)
(457) (457)
18 18
4-1/2 (114)
4-1/4 (108)
4-3/4 (121)
4-3/4 (121)
4 (102)
5-1/4 (133)
5-1/4 (133)
1-3/4
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
3/4
(19)
(45)
2-3/4
(70)
3-1/4
(83)
3-1/4
(83)
1
(25)
1-1/2
(38)1 (25)1 (25)
1-1/2
(38)1 (25)1 (25)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
31-3/4
(806)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
E F x G H J KL NPTIM NPTI N P Q R
23-1/2
(749)
23-1/2
(749)
6-7/8 x 8
(175) x (203) 8-1/4 x 9-3/4
(210) x (248)
8-1/4 x 11-3/8
(210) x (289)
10-1/2 x 13-1/2
(267) x (343)17(432)4(102)1(25)
13-1/8 x 11-3/8
(333) x (289)18(457)
13-7/8 x 13-7/8
(352) x (352)18(457)
11-1/2
(292)
11-1/2
(292)
13-1/2
(343)
4-1/2
1-3/4
(114)
(45)
4-1/4
2-3/4
(108)
(70)
4-3/4
3-1/4
(121)
(83)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
5-1/4
1-1/2
(133)
(38)1(25)1(25)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
38-3/4
(984)
38-3/4
(984)
44-3/4 (1137)
48-3/4 (1238)
56-3/4 (1441)
56-3/4 (1441)
18-3/4
(476)
18-3/4
(476)
21-3/4
(552)
23-3/4
(603)
31-3/4
(806)
37-3/4
(959)
13-5/8
(346)
13-5/8
(346)
16-5/8
(422)
17-5/8
(448)
19-5/8
(498)
19-5/8
(498)
1. All dimensions are in inches followed by millimeters in parenthesis.
2. 2. Access to the unit for service purposes should be provided at installation. Horizontal units require an 18 in. (457 mm) surround clear
other mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Equipment containing a same-side supply/return combination requires a 3 in. (229 mm) clearance on one side. Access to the TXV may not be possible with this 3 in. (229 mm) clearance.
4. If hot gas reheat is specified for a size 018, 024, the actual cabinet size increases to an 036 cabinet.
5. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
access on either side of the filter.
(a) Return air opening dimension (b) Filter rack dimension
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
18-1/2
(597)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
(b)
18-1/2
(470)
18-1/2
(470)
18-1/2
(470)
23-1/2
(597)
23-1/2
(597)
23-1/2
(597)
ance from
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
S
3-1/4
(83)
3-1/4
(83)
4-1/4 (108)
3-1/4
(83)
5-1/2 (140)
5-1/2 (140)
Note: It is recommended to order a bottom access filter rack with right return/right supply combination due to potential
problem with return air filter removal.
WSHP-SVX01N-EN 21
Unit Dimensions and Weights
D
L
K
D
E
JM
F
B
H
3 5/8"
(92)
8 3/4"
(222)
A
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
W.O.
DRAIN
W.I.
C
3 5/8"
(92)
BLOWER ACCESS
COMP/CONTROL
ACCESS
TOP
LEFT SIDE
FRONT
RIGHT SIDE
G
Figure 12. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER
ACCESS
COMP/CONTROL
WCI mounting location
8 3/4"
(222)
3 5/8"
(92)
ACCESS
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
3 5/8"
(92)
W.O.
DRAIN
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 10. Left return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
W.O.
Drain
GEV Unit A B C D E F G H J K L M
19-1/2
31-1/4
21-1/2
006-015
018, 024, 030
036, 042
Std-048
Hi-048, 060
EXV Unit A B C D E F G H J K L M
006-009
012-015
018-024
030-036
042-060
070
Not
es:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
22 WSHP-SVX01N-EN
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
19-1/2
(495)
19-1/2
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
46-7/8 (1191)
31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
50-7/8 (1292)
11-1/2
(546)
(292)4(102)
21-1/2
13-1/2
(546)
(343)4(102)4(1021)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
21-1/2
11-1/2
(546)
(292)4(102)
21-1/2
11-1/2
(546)
(292)
21-1/2
13-1/2
(546)
(343)4(102)4(1021)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
5-3/4 (146)
3-1/4
5-3/4
(83)
(146)
4-1/4 (108)2 (51)
4-1/4 (108)2 (51)
5-3/4 (146)
5-1/2
5-5/8
(140)
(142)
3-1/4
5-3/4
(83)
(146)
4-1/4 (108)2(51)
4-1/4 (108)2(51)
9-1/2 (241)15(381)17(432)
9-1/2 (241)
9-1/2 (241)19(483)23(584)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
9-1/2 (241)15(381)17(432)
9-1/2 (241)15(381)17(432)
9-1/2 (241)
9-1/2 (241)19(483)23(584)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
23-3/4
(603)17(432)
27-7/8
(708)
27-7/8
(708)
23-3/4
(603)17(432)
27-7/8
(708)
27-7/8
(708)
6-7/8 (175)8 (203)
9-3/4
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8 (175)8(203)
8-1/4 (210)
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4 (248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
NPTI
NPTI
3/4
1/2
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
1/2
(12.7)
3/4
(19)
3/4
(19)
W.O. NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
(19)
(12.7)
3/4
(19)
1/4 (6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
W.I.
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
1/4 (6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
D
E
jM
D
F
H
8 3/4"
(222)
3 5/8"
(92)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
A
12"
(305)
3 5/8"
(92)
C
BLOWER
ACCESS
COMP/CONTROL
ACCESS
9 1/2"
(241)
G
LEFT SIDE
FRONT
RIGHT SIDE
TOP
Figure 13. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER
ACCESS
B
COMP/CONTROL
WCI mounting location
8 3/4"
(222)
3 5/8"
(92)
ACCESS
HI VOLT
LO VOLT
12"
(305)
9 1/2"
(241)
3 5/8"
(92)
W.O.
DRAIN
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 11. Left return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
GEV Unit A B C D E F G H J K L M
4
(83)
(83)
006-009
012-015
1-3/4
(44)
3-3/4
(95)
3-7/8
(98)
1-7/8
(48)
1-3/4
(44)
3-3/4
(95)
3-7/8
(98)
1-7/8
(48)
9-1/2
15 (381)
(241)
9-1/2
23-3/4
(241)
9-1/2 (241)
9-1/2 (241)
9-1/2 (241)
9-1/2 (241)15(381)17(432)
9-1/2 (241)15(381)17(432)
9-1/2 (241)
9-1/2 (241)19(483)23(584)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
(603)
19 (483) 23 (584)
29 (737)
29 (737)
23-3/4
(603)17(432)
17
(432)
17 (432)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
6-7/8 (175)8 (203)
9-3/4 8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8 (175)8(203)
8-1/4 (210)
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4
(248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
(102)
006-015
018, 024,
030
036, 042
Std-048
Hi-048, 060
EXV Unit A B C D E F G H J K L M
006-009
012-015
018-024
030-036
042-060
070
e:
Not
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
19-1/2
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
WSHP-SVX01N-EN 23
(495)
(546)
(622)
(673)
(673)
(495)
(495)
(546)
(622)
(673)
(673)
31-1/4
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
46-7/8 (1191)
31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
50-7/8 (1292)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)
30-1/2
(775)
30-1/2
(775)
21-1/2
(546)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
18 (457)
18 (457)
18 (457)
006-009
11-1/2
(292)
13-1/2
(343)4 (102)
4-3/4 (121)
012-015
3-1/4
4-1/4 (108)2 (51)
4-1/4 (108)2 (51)
11-1/2
(292)4(102)
11-1/2
(292)
13-1/2
(343)4(102)
5-1/4 (133)
3-1/4
4-1/4 (108)2(51)
4-1/4 (108)2(51)
NPTI
3/4
1/2 (13) 1/2 (13)
(19)
3/4
(19)
1/4 (6)
1/2
1 (25.4)
(13)
1/2
1 (25.4) 1 (25.4)
(13)
W.I.
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
1/4 (6)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
W.O. NPTI
3/4
(19)
3/4
(19)
1 (25.4)
W.O. NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
C
A
3 5/8"
(92)
8 3/4"
(222)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
3 5/8"
(92)
12"
(305)
H
B
D
L
F
J M
E
D
K
9 1/2"
(241)
G
FRONT
RIGHT SIDE
TOP
LEFT SIDE
BLOWER
ACCESS
COMP/CONTROL
ACCESS
Figure 14. Right return/top supply: GEVE—“A” and later design sequence; EXV—”A” and later design sequence)
TOP
BLOWER
ACCESS
COMP/CONTROL
ACCESS
WCI mounting location
HI VOLT
LO VOLT
3 5/8"
(92)
8 3/4"
(222)
W.O.
DRAIN
12"
9 1/2"
(305)
3 5/8"
(92)
(241)
W.I.
LEFT SIDE
FRONT
RIGHT SIDE
Table 12. Right return/top supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
W.O.
Drain
GEV Unit A B C D E F G H J K L M
006-015
018, 024, 030
036, 042
Std-048
Hi-048, 060
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
EXV Unit A B C D E F G H J K L M
006-009
012-015
018-024
030-036
042-060
070
Not
e:
1. All dimensions are in inches followed by millimeters in parenthesis.
2. Access to the unit for service purposes should be provided at installation. Vertical units require an 24 in. (610 mm) surround clearance from other
mechanical and electrical equipment to enable panel removal from the unit for service/maintenance ability. NEC requires 36 in. clearance on the control panel side of the unit. Some local codes require a greater service clearance. Check all code requirements prior to unit installations. Installer is responsible for following all local and NEC code requirements.
3. Units in a free return application will require more than a 1 in. (25.4 mm) clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
24 WSHP-SVX01N-EN
19-1/2
19-1/2
21-1/2
24-1/2
26-1/2
26-1/2
(495)
(546)
(622)
(673)
(673)
(495)
(495)
(546)
(622)
(673)
(673)
31-1/4
39-1/4
41-7/8 (1064)
46-7/8 (1191)
46-7/8 (1191)
31-1/4
31-1/4
39-1/4
41-7/8 (1064)
46-7/8 (1191)
50-7/8 (1292)
(794)
(997)
(794)
(794)
(997)
21-1/2
21-1/2
26-1/2
30-1/2
30-1/2
21-1/2
21-1/2
21-1/2
26-1/2
30-1/2
30-1/2
11-1/2
(546)
(546)
(673)
(775)
(775)
(546)
(546)
(546)
(292)4 (102)
13-1/2
(343)4 (102)4(1021)
18 (457)
18 (457)
18 (457)
11-1/2
(292)4(102)
11-1/2
(292)
13-1/2
(343)4(102)4(102)
(673)18(457)
(775)18(457)
(775)18(457)
5-3/4 (146)
3-1/4
4-1/4 (108)2 (51)
4-1/4 (108)2 (51)
2-1/2
3-1/4
4-1/4 (108)2(51)
4-1/4 (108)2(51)
(83)
(64)
(83)
5-3/4 (146)
5-3/4 (146)
5-3/4 (146)
5-5/8 (143)
9-1/2 (241)15(381)17(432)
9-1/2
23-3/4
(241)
9-1/2 (241)19(483)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
9-1/2 (241)15(381)17(432)
9-1/2 (241)15(381)17(432)
9-1/2 (241)
9-1/2 (241)19(483)23(584)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
(603)
23-3/4
(603)17(432)
17 (432)
23 (584)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
27-7/8
(708)
6-7/8 (175)8 (203)
9-3/4
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
6-7/8 (175)8(203)
8-1/4 (210)
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
9-3/4 (248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
NPTI
3/4
(19)
3/4
(19)
1-3/4
(19)
1/2
(13)1 (25)1 (25)
1/2
(13)1 (25)1 (25)
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
1/2
(13)
3/4
(19)
3/4
(19)
W.I.
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
NPTI
1/2
(13)
3/4
(19)
3/4
(19)
W.O. NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
C
A
3 5/8"
(92)
8 3/4"
(222)
LO VOLT
HI VOLT
W.I.
DRAIN
W.O.
3 5/8"
(92)
12"
(305)
H
B
D
L
F
J M
E
D
K
9 1/2"
(241)
G
FRONT
RIGHT SIDE
TOP
LEFT SIDE
BLOWER
ACCESS
COMP/CONTROL
ACCESS
Figure 15. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
TOP
BLOWER ACCESS
COMP/CONTROL
ACCESS
WCI mounting location
HI VOLT
LO VOLT
3 5/8"
(92)
8 3/4"
(222)
W.O.
DRAIN
W.I.
3 5/8"
(92)
9 1/2"
(241)
12"
(305)
LEFT SIDE
FRONT
RIGHT SIDE
Table 13. Right return/back supply: GEVE—“A” and later design sequence; EXV—“A” and later design sequence
W.I.
GEV Unit A B C D E F G H J K L M
4
006-015
018, 024,
030
036, 042
Std-048
Hi-048, 060
19-1/2
(495)
21-1/2
(546)
24-1/2
(622)
26-1/2
(673)
26-1/2
(673)
31-1/4
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
46-7/8 (1191)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)
30-1/2
(775)
30-1/2
(775)
006-009
11-1/2
(292)
012-015
13-1/2
(343)4 (102)
18 (457) 18 (457) 18 (457)
(102)
(152)
3-1/4 4-1/4
(108)2 (51) 4-1/4
(108)2 (51)
6
(83)
1-3/4
(44)
006-009
1-1/4
(32)
012-015
3-7/8
(98)
1-7/8
(48)
9-1/2
15 (381) 17 (432)
(241)
9-1/2
23-3/4
(241)
9-1/2 (241)19(483)
9-1/2 (241)29(737)
9-1/2 (241)29(737)
(603)
17 (432)
23 (584)
27-7/8
(708)
27-7/8
(708)
6-7/8 (175)8 (203)
9-3/4
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
(248)
11-3/8
(289)
13-1/2
(343)
13-7/8
(352)
11-3/8
(289)
NPTI
3/4
1/2 (13) 1/2 (13)
(19)
3/4
(19)
1-3/4
(19)
1/2
(13)1 (25)1 (25)
1/2
(13)1 (25)1 (25)
W.I.
EXV Unit A B C D E F G H J K L M
006-009 012-015 018-024 030-036 042-060
070
e: All dimensions are in inches followed by millimeters in parenthesis.
Not
19-1/2 19-1/2 21-1/2 24-1/2 26-1/2 26-1/2
WSHP-SVX01N-EN 25
(495) (495) (546) (622) (673) (673)
31-1/4
(794)
31-1/4
(794)
39-1/4
(997)
41-7/8 (1064)
46-7/8 (1191)
50-7/8 (1292)
21-1/2
(546)
21-1/2
(546)
21-1/2
(546)
26-1/2
(673)18(457)
30-1/2
(775)18(457)
30-1/2
(775)18(457)
11-1/2
(292)4(102)
11-1/2
(292)2(51)
13-1/2
(343)4(102)
3-1/4
(83)
4-1/4 (108)2(51)
4-1/4 (108)2(51)
1-3/4 1-1/4 3-7/8 1-7/8
9-1/2
(44)
(241)15(381)17(432) 9-1/2
(32)
(241)15(381)17(432) 9-1/2
(98) (48)
(241) 9-1/2
(241)19(483)23(584) 9-1/2
(241)29(737) 9-1/2
(241)29(737)
23-3/4
(603)17(432)
27-7/8
(708)
27-7/8
(708)
6-7/8 (175)8(203)
8-1/4 (210)
8-1/4 (368)
10-1/2
(267)
13-7/8
(352)
13-1/8
(333)
9-3/4 (248)
11-3/8
(289)
13-1/2
(343)
11-3/8
(289)
11-3/8
(289)
NPTI
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
1/2
(13)1(25.4)1(25.4)
1/2
(13)1(25.4)1(25.4)
3/4
(19)
3/4
(19)
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
W.O. NPTI
3/4
(19)
3/4
(19)
W.O. NPTI
1/2
(13)
1/2
(13)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Drain
FPT
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
3/4
(19)
Unit Dimensions and Weights
Figure 16. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—right return/left supply
(16)
5/8"
18 3/4"
(476)
BLOWER ACCESS
PANEL
4 7/8"
(124)
1"
(25.4)
14 1/2"
(368)
20"
(508)
SERVICE
CLEARANCE
1 3/4"
(44)
23 7/8"
(606)
(54)
2 1/8"
1 1/4"
B
C
(32)
7 5/8"
(194)
18 3/8"
(467)
A
79"
(2007)
74 1/2"
(1892)
81"
(2057)
(2159)
TOP VIEW
85"
W.O. "D" NPTI
24 VOLT
1 1/8" (28.6) DIA.
WCI mounting location
36"
(914)
SERVICE
CLEARANCE
(117)
4 5/8"
40 5/8"
36"
(1032)
(914)
1 1/2"
(38)
16 1/2"
(419)
23 1/4"
(591)
(79)
3 1/8"
BACK SIDE
RETURN AIR
1" (25.4) DIA.
MOUNTING HOLE
4X'S
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
OPENING
(79 )
W.I. "D" NPTI
SUPPLY OPENING 1" (25.4) DUCT FLANGE
LEFT SIDE
HIGH VOLTAGE
7/8" (22.2) DIA.
2 1/4"
(57)
6 1/2"
(165)
Table 14. GEH 6–10 tons (072-120) 60 Hz; GEH 6–7½ tons (072-090) 50 Hz—right return/left supply
GEH (60 Hz) GEH (50 Hz) A B C D
072
090 072
120 090
36-1/4 in. (921 mm)
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
15-5/8 in. (397 mm)
12-3/4 in. (324 mm)
13 in.
(330 mm)
6-5/8 in.
(168 mm)
6-3/4 in.
(171 mm)
7-1/4 in.
(184 mm)
1-1/4 in. (32 mm)
1-1/4 in. (32 mm)
1-1/2 in. (38 mm)
26 WSHP-SVX01N-EN
Unit Dimensions and Weights
Figure 17. GEH 6–10 tons (072–120) 60 Hz; GEH 6–7½ tons (072–090) 50 Hz—right return/back supply
36"
(914)
SERVICE
CLEARANCE
(117)
4 5/8"
40 5/8"
36"
(1032)
(914)
23 7/8"
(606)
1 3/4"
(44)
18 3/8"
(467)
79"
(2007)
74 1/2"
(1892)
(16)
5/8"
18 3/4"
(476)
4 7/8"
(124)
(79)
3 1/8"
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
BLOWER ACCESS
PANEL
14 1/2"
(368)
1 1/4"
2 1/8"
(32)
(54)
B
6 1/8"
81"
(2057)
(156)
85"
(2159)
20"
(508)
SERVICE
CLEARANCE
TOP VIEW
W.O. "D" NPTI
A
C
W.I. "D" NPTI
LEFT SIDE
RETURN AIR
OPENING
24 VOLT
1 1/8" (28.6) DIA.
WCI mounting location
HIGH VOLTAGE
7/8" (22.2) DIA.
1 1/2"
(38)
2 1/4"
(57)
16 1/2"
(419)
(165)
6 1/2"
23 1/4"
(591)
1" (25.4) DIA.
MOUNTING HOLE
4X'S
SUPPLY OPENING
1" (25.4) DUCT FLANGE
Table 15. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—right return/back supply
GEH (60 Hz) GEH (50 Hz) A B C D
072
090 072
120 090
36-1/4 in. (921 mm)
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
WSHP-SVX01N-EN 27
15-5/8 in. (397 mm)
12-3/4 in. (324 mm)
13 in.
(330 mm)
6-5/8 in.
(168 mm)
6-3/4 in.
(171 mm)
7-1/4 in.
(184 mm)
1-1/4 in. (32 mm)
1-1/4 in. (32 mm)
1-1/2 in. (38 mm)
Unit Dimensions and Weights
Figure 18. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz - left return/right supply
23 1/4"
(591)
CLEARANCE
40 5/8" (1032)
16 1/2"
(419)
36"
(914)
SERVICE
36"
(914)
1 1/2"
(38)
4 5/8"
20"
(508)
7 5/8" (194)
SERVICE
CLEARANCE
1 3/4"
(44)
24 3/4"
(629)
1 1/4"
(32)
1 1/4"
B
C
(32)
14 1/2"
(368)
BLOWER ACCESS PANEL
1"
(25.4)
4 7/8"
(124)
18 3/4"
(476)
5/8"
(16)
79"
(2007)
(117)
TOP VIEW
W.O. "D" NPTI
24 VOLT 1 1/8" (28.6) DIA.
WCI mounting location
74 1/2"
(1892)
81"
(2057)
85"
(2159)
18 3/8"
(467)
A
6 1/2"
1" (25.4) DIA.
MOUNTING HOLE
4X'S
(57)
2 1/4"
(165)
LEFT SIDE
RETURN AIR
OPENING
HIGH VOLTAGE 7/8" (22.2) DIA.
W.I. "D" NPTI
SUPPLY OPENING 1" (25.4) DUCT FLANGE
DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC
(79)
3 1/8"
BACK SIDE
Table 16. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/right supply
GEH (60 Hz) GEH (50 Hz) A B C D
072
090 072
120 090
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
17 in.
(432 mm) 13-3/4 in.
(349 mm)
13 in.
(330 mm)
8 in.
(203 mm)
7-3/4 in.
(197 mm)
7-1/4 in.
(184 mm)
1-1/4 in. (32 mm)
1-1/4 in. (32 mm)
1-1/2 in. (38 mm)
28 WSHP-SVX01N-EN
Unit Dimensions and Weights
Figure 19. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/back supply
36"
(914)
SERVICE
CLEARANCE
40 5/8"
(1032)
36"
(914)
4 5/8"
(117)
79"
(2007)
74 1/2"
(1892)
1 3/4"
(44)
18 3/8"
(467)
24 3/4"
(629)
23 1/4"
(591)
20"
(508)
SERVICE
CLEARANCE
16 1/2"
(419)
6 1/2"
1 1/2"
(38)
(159)
2 1/4"
LEFT SIDE
(57)
W.O. "D" NPTI
24 VOLT 1 1/8" (28.6) DIA.
WCI mounting location
HIGH VOLTAGE 7/8" (22.2) DIA.
81"
(2057)
85"
(2159)
TOP VIEW
A
W.I. "D" NPTI
1 1/4"
(156)
6 1/8"
BLOWER ACCESS PANEL
14 1/2"
(368)
B
C
DRAIN CONNECTION
1/2" (22) SCHEDULE 40 PVC
(32)
1 1/4"
(32)
4 7/8"
(124)
3 1/8"
(79)
18 3/4"
(476)
5/8"
(16)
RETURN AIR
OPENING
1" (25.4) DIA.
MOUNTING HOLE
4X'S
SUPPLY OPENING 1" (25.4) DUCT FLANGE
Table 17. GEH 6-10 tons (072-120) 60 Hz; GEH 6-7½ tons (072-090) 50 Hz—left return/back supply
GEH (60 Hz) GEH (50 Hz) A B C D
072
090 072
120 090
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
36-1/8 in. (917 mm)
WSHP-SVX01N-EN 29
17 in.
(432 mm) 13-3/4 in.
(349 mm)
13 in.
(330 mm)
8 in.
(203 mm)
7-3/4 in.
(197 mm)
7-1/4 in.
(184 mm)
1-1/4 in. (32 mm)
1-1/4 in. (32 mm)
1-1/2 in. (38 mm)
Unit Dimensions and Weights
Figure 20. GEH 12½-15 tons (150-180) 60 Hz; GEH 10-12½ tons (120-150) 50 Hz—right return/left supply
5/8"
20"
(508)
SERVICE
CLEARANCE
1 3/4"
(44)
23 7/8"
(606)
7 5/8"
(194)
BLOWER ACCESS
(16)
4 7/8"
(124)
PANEL
(25.4)
1"
(54)
2 1/8"
1 1/4"
(32)
18 3/8"
(467)
A
79"
(2007)
74 1/2" (1892)
81"
(2057)
85"
(2159)
TOP VIEW
W.O. "D" NPTI
24 VOLT
1 1/8" (28.6) DIA.
36"
(914)
SERVICE
CLEARANCE
(117)
4 5/8"
40 5/8"
36"
(1032)
(914)
1 1/2"
(38)
18 3/4"
(476)
BACK SIDE
1" (25.4) DIA.
MOUNTING HOLE
14 1/2"
(368)
(79)
3 1/8"
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
RETURN AIR
OPENING
(79 )
4X'S
B
C
SUPPLY OPENING 1" (25.4) DUCT FLANGE
W.I. "D" NPTI
LEFT SIDE
WCI mounting location
HIGH VOLTAGE
7/8" (22.2) DIA.
(57)
2 1/4"
16 1/2"
(419)
(165)
6 1/2"
23 1/4"
(591)
30 WSHP-SVX01N-EN
Loading...
+ 102 hidden pages