Trane GEHE 072-180, EXHF 006-070, GEHE 006-060, GEVE 072-300, EXVF 006-070 Installation, Operation And Maintenance Manual

...
Installation, Operation, and Maintenance
Water Source Heat Pump
Axiom™ Horizontal/Vertical
Model Numbers
Only qualified personnel should install and service the equipment.The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
December 2016
GEHE 006-060 - 50/60 Hz GEVE 006-060 - 50/60 Hz GEHE 072-180 - 50/60 Hz GEVE 072-300 - 50/60 Hz EXHF 006-070 - 60 Hz EXVF 006-070 - 60 Hz
SAFETY WARNING
WSHP-SVX01Q-EN
Introduction
Read this manual thoroughlybefore operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required.Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards.To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situationthat could resultin equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious injury. Technicians, in order to protect themselves from potential electrical, mechanical, and chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and labels, as well as the instructions below:
Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.
If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
© 2016 Ingersoll Rand All rights reserved WSHP-SVX01Q-EN
Copyright
This document andthe information in it arethe property of Trane, and may not be used or reproduced in whole or in
part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Updated GEH* models in Table 53, p. 88.
Minor running changes.
Introduction
WSHP-SVX01Q-EN 3
Table of Contents
Copyright ............................. 3
Model Number Description - .5 to 25 Tons .5
Model Number Description - .5 to 6 Tons .. 6
Overview of Manual ..................... 7
Unit Nameplate ..................... 7
Compressor Nameplate ............... 7
Model Number Description ............ 7
General Information ..................... 8
Pre-Installation ......................... 12
Unit Inspection Checklist ............. 12
Jobsite Inspection Checklist .......... 12
Jobsite Storage .................... 12
Unit Dimensions ........................ 13
Service Clearances .................... 13
Weights ................................ 53
Weight Distribution for Hanging the GEH and
EXH Model ........................ 53
Installation ............................. 54
General Installation Checks ........... 54
Main Electrical ..................... 54
Supply-Air Ductwork ................ 55
Return-Air Ductwork ................. 55
Ducted Panel ....................... 55
Ducted Filter Rack (GEH .5 to 5 ton and EXH .5
to 6 ton only) ....................... 56
Dual Filtration (GEH .5 to 5 ton and EXH .5 to
6 ton) ............................. 56
Sound Attenuation Pad .............. 57
Hanging the Horizontal Unit .......... 57
Condensate Drain Connection ......... 57
Supply/Return Pipe Connections ...... 58
Cleaning and Flushing the Water Loop . 58
Field Installed Power Wiring .......... 58
Main Unit Power Wiring ............. 58
Control Power Transformer ........... 59
Thermostat Location ................ 59
Controls Using 24 VAC .............. 59
Blower Motor Speed-Tap Retrofit ...... 60
Hole Plug Installation ................ 61
Air Flow Adjustment .................61
Waterside Economizer Installation ......62
Waterside Economizer Installation for GEH
and GEV 6 to 25 Ton Models ...........65
Waterside Economizer Start-Up Sequence .67
Electrical Data ...........................69
Pre-Start Checklist .......................86
Start-Up ................................87
Initial Unit Start-up ....................87
Start-Up Checklist and Log ............87
Operating Pressures .................87
Water Pressure Drop ................108
Water Volume ......................110
Maintenance ...........................111
Preventive Maintenance .............111
Condensate Trap ...................112
Troubleshooting ........................113
Wiring Diagrams .......................115
Warranty Information ...................127
Standard Warranty ..................127
Extended Warranty .................127
4 WSHP-SVX01Q-EN
Model Number Description - .5 to 25Tons
Digits 1-3 - Unit Configuration
GEH = Standard Efficiency Horizontal
GEV = Standard Efficiency Vertical
.5 to 15Tons
.5 to 25Tons
Digit4-Development Sequence
E = R-410A
Digits 5-7 - Nominal Capacity
006 = .5 Tons 009 = .75 Tons 012 = 1Tons 015 = 1.25 Tons 018 = 1.5 Tons 024 = 2Tons 030 = 2.5Tons 035 = 3Tons (Horizontal only) 036 = 3Tons (Vertical only) 042 = 3.5Tons 048 = 4Tons 060 = 5Tons 072 = 6Tons 090 = 7.5 Tons 120 = 10Tons 150 = 12.5Tons 180 = 15Tons 240 = 20Tons 300 = 25 Tons
Digit 8 - Voltage (Volts/Hz/Phase)
0 = 115/60/1 1 = 208/60/1 2 = 230/60/1 3 = 208/60/3 4 = 460/60/3 5 = 575/60/3 7 = 265/60/1 8 = 230/60/3
1
Digit 9 - Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper-Water Coil 8 = Insulated Cupro-Nickel Water Coil
Digit 10 - Current Design Sequence
Digit 11 - Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
4 = Heating and Cooling Circuit with HGR
and WSE
2
Digit 12 - Blower Configuration
1 = Standard Blower Motor 2 = High Static Blower Motor A = Drive Package A B = Drive Package B C = Drive Package C D = Drive Package D E = Drive Package E F = Drive Package F G = Drive Package G H = Drive Package H J = Drive Package J 1*= 2 Speed Drive Package A 2*= 2 Speed Drive Package B 3 = 2 Speed Drive Package C 4= 2 Speed Drive Package D 5= 2 Speed Drive Package E 6= 2 Speed Drive Package F 7= 2 Speed Drive Package G 8= 2 Speed Drive Package H 9= 2 Speed Drive Package J
3
3
Digit 13 - Freeze Protection
A= 20°F Freezestat B= 35°F Freezestat
4
Digit 14 - Open Digit = 0
Digit 15 - Supply-Air
Arrangement
B = Back Supply-Air Arrangement F = Front Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T = Top Supply-Air Arrangement
Digit 16 - Return-Air
Arrangement
B = Back Return-Air Arrangement F = Front Return-Air Arrangement L = Left Return-Air Arrangement R = Right Return-Air Arrangement
2
2
Digit 17 - Control Types
0 = Basic 24V Controls D = Deluxe 24V Controls B =Tracer® ZN524 Controls F = UC400 G = UC400 w/Wireless Comm
5
Digit 18 - Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 - Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 - Temperature Sensor
0 = NoTemperature Sensor 1 = Entering Water Sensor
Digit 21 - Open
Digit 22 - Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat 5 = External Supplemental Electric Heat
3
Digit 23 - Open
Digit 24 - Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4=2”MERV8 5=2”MERV13
Digit 25 - Acoustic Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
6
Digits 26-36 - Does Not Apply to GEH or GEV
000 00000000 = Digits 26-36 are not applicable to the GEH or GEV products
2
1
.5 to 1Ton only
2
6 to 25 Tons only
WSHP-SVX01Q-EN 5
3
.5 to 5 Tons only
4
Extended Range Geothermal
5
.5 to 5 Tons only
6
.5 to 5 Tons (horizontal only)
Model Number Description - .5 to 6Tons
Digits 1-3 — Unit Configuration
EXH =High Efficiency Horizontal EXV =High Efficiency Vertical
Digit 4 Development Sequence
F
Digits 5-7 — Nominal Capacity
006 =.5 Tons 009 =.75 Tons 012 =1Tons 015 =1.25 Tons 018 =1.5 Tons 024 =2Tons 030 =2.5Tons 036 =3Tons 042 =3.5Tons 048 =4Tons 060 =5Tons 070 =6Tons
Digit 8 — Voltage (Volts/Hz/ Phase)
1 = 208/60/1 2 = 230/60/1 3 = 208/60/3 4 = 460/60/3 7 = 265/60/1 8 = 230/60/3
Digit 9 — Heat Exchanger
1 = Copper-Water Coil 2 = Cupro-Nickel Water Coil 7 = Insulated Copper Water
Coil/Suction Line
8 = Insulated Cupro-Nickel Water
Coil/Suction Line
Digit 10 — Current Design Sequence
Digit 11 — Refrigeration Circuit
0 = Heating and Cooling Circuit 2 = Heating and Cooling Circuit with
Hot Gas Reheat
3 = Heating and Cooling Circuit with
Waterside Economizer
Digit 12 — Blower Configuration
3 = ECM Motor
Digit 13 - Freeze Protection
A = 20°F Freezestat B = 35°F Freezestat
Digit 14 — Open Digit = 0
Digit 15 — Supply-Air
Arrangement
B = Back Supply-Air Arrangement L = Left Supply-Air Arrangement R = Right Supply-Air Arrangement
T =Top Supply-Air Arrangement
Digit 16 — Return-Air
Arrangement
L = Left Return-Air Arrangement R = Right Return-Air Arrangement
Digit 17 — Control Types
D = Deluxe 24V Controls B = Tracer® ZN524 Controls F = UC400 G = UC400 w/ Wireless Comm
Digit 18 — Tstat/Sensor Location
0 = Wall Mounted Location
Digit 19 — Fault Sensors
1 = Condensate Overflow Sensor 3 = Condensate Overflow and Filter
MaintenanceTimer 6 = Condensate Overflow and Fan Status J = Fan Status, Filter MaintenanceTimer
and Condensate Overflow Sensor
Digit 20 — Temperature Sensor
0 = No AdditionalTemperature Sensor 1 = Entering Water Sensor
Digit 21 — Open Digit
Digit 22 — Electric Heat
0 = No Electric Heat 1 = Internal Boilerless Electric Heat 4 = External Boilerless Electric Heat
Digit 23 — Open Digit
Digit 24 — Filter Type
1 = 1"Throwaway Filter 2 = 2"Throwaway Filter 4= MERV8 5 = MERV13
Digit 25 — Acoustic
Arrangement
0 = Enhanced Sound Attenuation 1 = Deluxe Sound Attenuation
Digits 26-36 — Does not Apply to EXH or EXV
00000000000 Digits 26-36 are not applicable to the EXH or EXV products
6 WSHP-SVX01Q-EN
Overview of Manual
Note: One copy of this document ships with each unit and
is customer property. It must be retained by the unit’s maintenance personnel.
This booklet describes proper installation, operation, and
maintenance procedures for HVAC systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
Service and maintenance work should be performed by a qualified technician and all electrical service and maintenance work should be performed by a qualified licensed electrician.
Unit Nameplate
The unit nameplate is located on the outside of the control
box access panel at thefront of the unit. Itincludes the unit model number, serial number, electrical characteristics, refrigerant charge, and other pertinent unit data.
Compressor Nameplate
The nameplate for the compressors are located on the
compressor shell.
Model Number Description
All products are identified by a multiple-character model number that preciselyidentifies a particular type ofunit. Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.
When ordering replacement parts or requesting service,
be sure to refer to the specific model number and serial number printed on the unit nameplate.
WSHP-SVX01Q-EN 7
General Information
Unit Description
Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and run tested for proper control operation.
Air-to-Refrigerant Coil
The air-to-refrigerant coil is aluminum fin, mechanically
bonded to the copper tubing.
Water-to-Refrigerant Coil
The water-to-refrigerant coil is a copper or cupro-nickel
(option) and steel tube (tube-within-a-tube) design, leak tested to assure there is no cross leakage between the water tube (copper/cupro-nickel) and refrigerant gas (steel tube).
Table 1. High/Low pressure switch
Trip Recover Unit
LP 40 +/-4 56 +/-4 psig
HP 650 +/-10 550 +/-10 psig
Controls
Basic 24V control is available for the GEH/V .5 -5 ton models and the Deluxe 24V control option is available for all unit sizes.Tracer® ZN524, LonTalk® certified control option is available for all unitsizes. UC400 and UC400 with wireless comm BACnet® is available in all unit sizes.
All power wiring to the equipment is made at the unit
contactor for .5to 5 ton, 1-phase units. For 3-phaseunits all power wiring to the equipmentis made tothe contactor or power block. For EXH/V070 units all power wiring to the equipment is made to the power block. For the GEH/V 6 to 25 tons units all power wiring is made to the high voltage terminal block. All low-voltage wiring is made at the unit’s low voltage terminal board. EXH and EXV 460V units require a neutral wire.
System Input Devices and Functions
A thermostat, zone sensor, or building automation system
is required to operate the water-source heat pump.The flexibility of having several mode capabilities depends upon the type of sensor and/or remote panel selected.
Troubleshooting and connection diagrams for the 24V
control systems may be locatedin the back of this manual.
All digital control troubleshooting tips and connection
diagrams are located in CNT-SVX11*-EN (ZN524). All digital control troubleshooting tips and connection diagrams are located in BAS-SVX065*-EN (UC400).
Basic 24V Controls
Safety devices for equipment containing the basic 24V control option include a low-pressure switch to prevent compressor operation during low temperature or low suction activity.The switch is set to activate at refrigerant pressure of 40 psig to fit most applications.
A high pressure switch prevents compressor operation
during high or excessive discharge pressures exceeding 650 psig.
The lockout relay will disable the compressor on a high or
low pressure condition. For units that contain a condensate overflow switch option, a condensate overflow condition will also disable the compressor through the lockout relay.The relay may be reset at the thermostat, or by cycling power to the unit.
General alarm is accomplished through the lockout relay.
This feature will drive dry contacts only, and cannot be
used to drive field installed control inputs.Trane provides a 3.5-minute time delay for compressor control.
Deluxe 24V Controls (option)
Units containing the Deluxe 24V control design will incorporate a microprocessor-based control board.The
Trane® microprocessor board is factory wired to a
terminal strip to provide all necessary terminals for field connection.The deluxe board is equipped with a random start relay, anti-short cycle timer, brown out protection, compressor disable, condensate overflow, unit safety control, diagnostics, and a generic relay (which may be available for field use). See Table 64, p. 113 for diagnostic information and Figure 59, p. 62 and Figure 60, p. 63 for thermostat connections.
Tracer® UC400 (option)
TheTracer® UC400 is a BTL Listed BACnet® controller that
can operate stand- alone or within aBuilding Automations system such asTracer® SC. For installation, operation and Programming, see BAS-SVX065*-EN (UC400).
Tracer® ZN524 Controls (option)
The digital ZN524 controller is designed to support the .5
to 25 ton water-source heat pumps in either a standalone, or as a full building automation (open protocol) system.
For installation, operation and diagnostics see CNT­SVX11A-EN (ZN524).
Pump Module (field installed accessory)
The pump module shall consist of either a single or dual 1/
6 HP bronze pump and a brass three-way shut-off valve. Cast iron pumps are also available.The pump module kits shall contain the necessary components for the installation, operation and maintenance of the water circuit of a closed-loop distributed pumping application.
8 WSHP-SVX01Q-EN
General Information
Waterside Economizer (Option)
Instructions for mechanical connection of the waterside economizer to the water-source heat pump may be found in the dimensional section of this manual.
The waterside economizer is designed to begin
economizing mode when water temperatures fall below the field adjustable temperature of 25, 35, 45, 55 or 60°F (for the Deluxe control option), or below the programmed set-point (for the ZN524 or UC400 control option).
When the temperature is less than the setpoint, fluid will
flow into the economizing coil, while simultaneously halting mechanical operation of the compressor. Mechanical cooling will continue on a call for a second stage from the thermostat or system control. Entering water temperature sensor is factory provided for field installation on the entering water side of the coil.
Boilerless Control/Electric Heat (Option)
Systems that do not contain a boiler may contain a boilerless control with electric heat.Trane® offers both a factory mounted electric heat option (.5 to 5 ton only), and a field mounted duct heater option.
If the .5 to5 ton GEH, GEV andEXH/V070 unitincorporates the factory mounted option, the unit will ship from the factory with an internally mounted nichrome open wire heating element, designed to start-up electric heat as the systems primary heat in the event entering water temperature falls below 55°F. Once the entering water temperature rises above 60°F, the boilerless controller returns the unit to normal compressor heating operation, and locks out the electric heater.
For units comprised of the field installed duct heater option, the unit will ship from the factory with controls available to interface with the field provided electric heat selection.
Note: For geothermal applications, the boilerless
controller has an adjustable setting of 25, 35, 45, 55, and 60 degrees.
Supplemental or Boilerless Electric Heat (option)
The GEH/V 6 to 25 ton models which contain boilerless
control electric heat or supplemental electric heat will contain the controls interface ONLY for field provided electric heat selection.The heater for this model shall be external to the equipment by the contractor for ease of installation. All power connections for the electric heater will be completely separate from theunit for field supplied electric heat.
Note: When the unit has boilerless control, the electric
heat is not used as supplemental electric heat, but as a primary heat.
the reheat coil to control not only the space temperature, but to also reduce therelative humidity of the space.When operating in the reheat mode (meaning the sensible temperature has been met in the space), the humidistat signals the reheat relay coil to energize, allowing the high pressure refrigerant gas to flow from the compressor through the reheat valve, into the reversing valve and reheat coil.
A switching relay has been provided for the reheat
application to adjust the blower motor from normal operation to low speed when the hot gas reheat is energized (for .5 to 5 ton and EXH/V070 equipment only).
Note: A high static blower motor is required to support
the hot gas reheat option for the GEH/V .5 -5 ton.
Note: Units containing the hot gas reheat option should
not be used as a make-up air unit.
2 Speed Blower Motor (option)
The 6 to25 ton GEH/Vmodels have indoorblowers that are
available with 2 speed motors, selectable in the model number (Digit 12, drive packages one to nine). High speed airflow matches the single speed motor airflow, referenced in the Fan Performance tables. Low fan speed airflow is approximately 50% of high fan speed airflow.
The 6 to 25 ton GEH/V two-speed blower motors are
available with the following options: Deluxe24V or UC400 controls, Heat Pump (HP) or HP w/Hot Gas Reheat or HP w/
Waterside Economizer. Not available with Boilerless or
Supplemental Electric Heat.
Table 2. 6 to 25 ton GEH/V fan speed for two-speed
drive packages one to nine
RV State Fan Compressor 1 Compressor 2 Fan Speed
Heat OFF OFF OFF OFF Heat ON OFF OFF LOW Heat ON ON OFF HIGH Heat ON ON ON HIGH Cool OFF OFF OFF OFF Cool ON OFF OFF LOW Cool ON ON OFF LOW Cool ON ON ON HIGH
Hot Gas Reheat (option)
With the reheat option, the return-air from the space is
conditioned by the air-to-refrigerant coil, then reheated by
WSHP-SVX01Q-EN 9
General Information
Table 3. Refrigerant charge
Model
(60 Hz)
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
Circuit 1 Circuit 2 Circuit 1 Circuit 2
GEHE006 25.3 / .717 ----- 26.8 / .760 ----­GEHE009 26.0 /.737 ----- 27.5 / .780 ----­GEHE012 28.5 / .808 ----- 30.5 / .865 ----­GEHE015 29.0 / .822 ----- 30.5 / .865 ----­GEHE018 36.5 / 1.035 ----- 39.5 / 1.120 ----­GEHE024 39.0 / 1.106 ----- 42.0 / 1.191 ----­GEHE030 44.0 / 1.247 ----- 46.5 / 1.318 ----­GEHE035 53.0 / 1.503 ----- 56.0 / 1.588 ----­GEHE042 57.0 / 1.616 ----- 60.5 / 1.715 ----­GEHE048 61.0 / 1.729 ----- 65.5 / 1.857 ----­GEHE060 73.0 / 2.070 ----- 77.5 / 2.197 ----­GEVE006 25.7 / .789 ----- 27.2 / .771 ----­GEVE009 26.5 / .751 ----- 28.0 / .794 ----­GEVE012 29.5 / .836 ----- 31.5 / .893 ----­GEVE015 27.5 / .780 ----- 29.5 / .836 ----­GEVE018 37.0 / 1.049 ----- 40.0 / 1/134 ----­GEVE024 39.0 / 1.106 ----- 41.5 / 1.177 ----­GEVE030 44.5 / 1.262 ----- 47.0 / 1.332 ----­GEVE036 51.0 / 1.446 ----- 54.5 / 1.545 ----­GEVE042 54.0 / 1.531 ----- 57.5 / 1.630 ----­GEVE048 61.0 / 1.729 ----- 66.0 / 1.871 ----­GEVE060 74.0 / 2.098 ----- 79.5 / 2.254 ----­GEHE072 55 / 1.559 55 / 1.559 59 / 1.673 55 / 1.559 GEHE090 64 / 1.814 54 / 1.531 68 / 1.928 54 / 1.531 GEHE120 86 / 2.438 86 / 2.438 90 / 2.551 86 / 2.438 GEHE150 136 / 3.856 136 / 3.856 144 / 4.082 136 / 3.856 GEHE180 126 / 3.572 126 / 3.572 134 / 3.799 126 / 3.572 GEVE072 58 / 1.644 58 / 1.644 62 / 1.758 58 / 1.644 GEVE090 83 / 2.353 75 / 2.126 87 / 2.466 75 / 2.126 GEVE120 88 / 2.495 88 / 2.495 92 / 2.608 88 / 2.495 GEVE150 122 / 3.459 122 / 3.459 130 / 3.685 122 / 3.459 GEVE180 128 / 3.629 128 / 3.629 136 / 3.856 128 / 3.629 GEVE240 284 / 8.051 284 / 8.051 292 / 8.278 284 / 8.051 GEVE300 260 / 7.371 260 / 7.371 267 / 7.569 260 / 7.371 EXHF006 25.3 / 0.717 ----- 26.8 / 0.760 ----­EXHF009 26.0 / 0.737 ----- 27.5 / 0.780 ----­EXHF012 28.5 / 0.808 ----- 30.5 / 0.865 ----­EXHF015 29.0 / 0.822 ----- 30.5 / 0.865 ----­EXHF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXHF024 50.5 / 1.432 ----- 53.0 / 1.503 ----­EXHF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXHF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXHF042 81.0 / 2.296 ----- 85.5 / 2.424 ----­EXHF048 83.0 / 2.353 ----- 87.5 / 2.481 ----­EXHF060 114.0 / 3.232 ----- 118.5 / 3.359 ----­EXHF070 122.0 / 3.459 ----- 127.0 / 3.600 -----
10 WSHP-SVX01Q-EN
Table 3. Refrigerant charge (continued)
General Information
Model
(60 Hz)
EXVF006 25.7 / 0.729 ----- 27.2 / 0.771 ----­EXVF009 26.5 / 0.751 ----- 28.0 / 0.794 ----­EXVF012 29.5 / 0.836 ----- 31.5 / 0.893 ----­EXVF015 30.0 / 0.850 ----- 32.0 / 0.907 ----­EXVF018 45.0 / 1.276 ----- 48.0 / 1.361 ----­EXVF024 52.0 / 1.474 ----- 54.5 / 1.545 ----­EXVF030 53.0 / 1.503 ----- 56.0 / 1.588 ----­EXVF036 70.0 / 1.984 ----- 73.0 / 2.070 ----­EXVF042 81.0 / 2.296 ----- 86.0 / 2.438 ----­EXVF048 83.0 / 2.353 ----- 88.5 / 2.509 ----­EXVF060 114.0 / 3.232 ----- 119.5 / 3.388 ----­EXVF070 122.0 / 3.459 ----- 128.0 / 3.629 -----
Heat Pump
(oz)/(Kg)
Heat Pump w/HGR
(oz)/(Kg)
WSHP-SVX01Q-EN 11
Pre-Installation
WARNING
Fiberglass Wool!
Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation.You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, a NIOSH approved dust/mist respirator, long sleeves and pants when working with products containing fiberglass wool.
Unit Inspection Checklist
Unpack all components of the kit.
Check carefully for any shipping damage. If any damage is found it must be reported immediately and a claim made against the transportation company.
Important: Equipment is shipped FOB (Free on Board)
at the manufacturer.Therefore, freight claims for damages against the carrier must be initiated by the receiver.
Visually inspect the components for shipping damage as soon as possible after delivery, before it is stored. Concealed damage must be reported within 15 days.
If concealed damage is discovered, stop unpacking the shipment.
Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the carrier’s terminal of damage immediately by phone and by mail. Request an immediate joint inspection of the damage by the carrier and the consignee.
Do not attempt to repair any damaged parts until the parts are inspected by the carrier’s representative.
Jobsite Inspection Checklist
Always perform the following checks before
accepting a unit:
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, for signs of shipping damage. Do not sign the bill of lading accepting the unit(s) until inspection has been completed. Check for damage promptly after the
unit(s) are unloaded. Once the billof lading is signed at the jobsite, the unit(s) are now the property of the SOLDTO party and future freight claims MAY NOT be accepted by the freight company.
Jobsite Storage
NOTICE:
Microbial Growth!
Wet interior unit insulation can become an
amplification site for microbial growth (mold), which could result in odors and damage to the equipment and building materials. If there is evidence of microbial growth on the interior insulation, it should be removed and replaced prior to operating the system.
NOTICE:
Microbial Growth!
Failure to follow instructions below could result in odors and damage to the equipment and building materials.The floor or foundation must be level and the condensate drain at the proper height for proper coil drainage and condensate flow. Standing water and wet surfaces inside the equipment can become an amplification site for microbial growth (mold).
This unit is intended for indoor use only.To protect the unit
from damage due to the elements, and to prevent possible IAQ contaminant sources from growing, the unitshould be stored indoors. If indoor storage is not possible, the following provisions for outdoor storage must be met:
Place the unit(s) on a dry surface or raise above the ground to assure adequate air circulation beneath the unit.
Cover the unit(s) with a water proof tarp to protect them from the elements.
Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which has been determined to be a cause of odors and serious health related indoor air quality problems.
Store units in the normal UP orientationto maintain oil in the compressor.
Horizontal units may be stacked no more than three units high. Do not stack the vertical unit configurations.
12 WSHP-SVX01Q-EN
Unit Dimensions
Service Clearances
Per NEC requirements, 36 inches of access and working space shall be provided and maintained around allcontrol boxes and electrical equipment to permit ready and safe operation and maintenance of such equipment. Local codes may require more clearance to electrical equipment. Check all code requirements prior to unit installation.
Figure 1. Clearances - GEH .5 to 5 tons & EXH .5 to 6Tons
14"
14"
LEFT RETURN
BACK SUPPLY
UNIT FRONT
36"
14"
14" 14”
LEFT RETURN
RIGHT SUPPLY
14"
UNIT FRONT UNIT FRONT
36"
14"14"
14"
14"
LEFT RETURN LEFT SUPPLY
36"
14"
A minimum 14 inch clearancefor servicing the unit is required for all .5 to 5 tons and EXH070 configurations from other mechanical and electrical equipment (where shown) to enable panel removal from the unit for service/ maintenance ability.The optimum clearance required is 20 inches.
3"
Equipment containing a same-side supply/ return combination requires a 3 inches limitation on one side. Access to theTXV may not be possible with this 3 inches clearance.
This configuration is typically applied in a
corridor installation, where space limitations force the left or right side of the unit against a wall.
RIGHT RETURN
BACK SUPPLY
14"
UNIT FRONT
14"
36"
RIGHT RETURN
LEFT SUPPLY
14"
UNIT FRONT
36"
Figure 2. Clearance - GEH 6 to 15 Tons
24"
36"
CONTROL BOX
TOP VIE W
24"
14"
3"
BLOWER ACCESS PANEL
RIGHT RETURN RIGHT SUPPLY
UNIT FRONT
36"
14"
Service clearance dimensions for the GEH 6 to15 tons horizontal includes a two side access appropriate for control and blower motor/wheel access.
WSHP-SVX01Q-EN 13
Unit Dimensions
Figure 3. Clearance - GEV .5 to 5 tons & EXV .5 to 6Tons
1"
24"
1"
1"
UNIT FRONT
UNIT FRONT
36"
36"
24"
LEFT
RETURN
TOP/BACK
SUPPLY
TOP/BACK
1"
RIGHT
RETURN
SUPPLY
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.This will enable panel removal from the unit for service/maintenance.
A 1 inch minimum clearance between the filterrackand any obstacle is required for units in a free return application to provide proper air flow to the air-to-refrigerant coil. A 12 inch minimum clearance between the filter rack and any obstacle should be provided to properly attached ductwork.
The 1 inch dimension shown in the back of the unit
represents the supply duct collar for the back supply option.This clearance is needed to clear these flanges.
Figure 4. Clearance - GEV 6 to 10Tons
24"
FRONT RETURN
TOP SUPPLY
ACCESS PANEL FOR SHEAVES AND BELTS
36"
24"
Figure 5. Clearance - GEV 12.5 to 25 Tons
18"
24"
CONTROL BOX
36"
FRONT RETURN-AIR
BACK SUPPLY-AIR
UNIT FRONT
18"
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.The unit may be serviced through the front access panel or remaining open sides.
A 24 inch clearance from other mechanical and electrical equipment (where shown) is recommended for all configurations.The unit may be serviced through the front access panel.
24"
14 WSHP-SVX01Q-EN
Figure 6. Left return/left supply (GEH/EXH)
TOP
F X G
OPENING
C
BLOWER
ACCESS
PANEL
1"
DRAIN
3/4" NPTI
BACK LEFT SIDE FRONT
H
Q
K
1/2"
H
J
RS
N
A
HI VOLT
WCI mounting location
LO VOLT
ED
6 3/4"
1"
Unit Dimensions
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
1 3/8"
14"
RIGHT SIDE
Table 4. Dimensional data left return/left supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
2. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
Hi-042,
048, 060
EXH Unit
(50 Hz) A B C D
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
access on either side of the filter. 3 in. clearance.
WSHP-SVX01Q-EN 15
Unit Dimensions
Figure 7. Left return/back supply (GEH/EXH)
TOP
F X G
OPENING
C
1"
BLOWER
H
ACCESS
PANEL
N
A
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
BP
REFRIG
AND
CONTROL
Q
ACCESS
L (W.O.)
M (W.I.)
7"
DRAIN 3/4" NPTI
H
J
K
BACK LEFT SIDE FRONT
ED
14"
1"
1/2"
1 3/8"
RIGHT SIDE
Table 5. Dimensional data left return/back supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/213-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
060 58 33 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
070 N/A 58 39 21 29-1/2 23-1/213-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
S
S
16 WSHP-SVX01Q-EN
Figure 8. Left return/right supply (GEH/EXH)
TOP
N
A
ED
BLOWER ACCESS
1"
PANEL
Q
R
HI VOLT
WCI mounting location
LO VOLT
S
6 3/4"
Unit Dimensions
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
7"
DRAIN 3/4" NPTI
BACK LEFT SIDE FRONT
RIGHT SIDE
1/2"
F X G
OPENING
C
H
K
H
1"
1 3/8"
14"
J
Table 6. Dimensional data left return/right supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
S
S
WSHP-SVX01Q-EN 17
Unit Dimensions
Figure 9. Right return/left supply (GEH/EXH)
R
TOP
N
A
ED
1"
BLOWER ACCESS
PANEL
DRAIN 3/4" NPTI
RIGHT SIDE
H
K
H
BACK LEFT SIDE FRONT
J
7"
C
F X G
OPENING
WCI mounting location
HI VOLT
LO VOLT
14"
1”
S
6 3/4"
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
Q
1/2"
1 3/8”
Table 7. Dimensional data right return/left supply (GEH/EXH)
GEH
Unit (60
Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
060
EXH
Unit (60
Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this 3 in. clearance.
(a)Return air opening dimension. (b)Filter rack dimension.
GEH
Unit (50
Hz) A B C D
Hi-042,
048, 060
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
EXH
Unit (50
Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
(b)
S
S
18 WSHP-SVX01Q-EN
Figure 10. Right return/back supply (GEH/EXH)
R
TOP
N
F X G
OPENING
ED
A
Unit Dimensions
S
BP
REFRIG
AND
CONTROL
ACCESS
L (W.O.)
M (W.I.)
1”
Q
1/2"
6 3/4”
7"
1 3/8”
BLOWER ACCESS
PANEL
HI VOLT
WCI mounting location
LO VOLT
14"
H
K
C
1"
H
DRAIN 3/4" NPTI
RIGHT SIDE
J
BACK LEF T SIDE FRONT
Table 8. Dimensional data right return/back supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
3 in. clearance.
WSHP-SVX01Q-EN 19
Unit Dimensions
Figure 11. Right return/right supply (GEH/EXH)
HI VOLT
LO VOLT
1"
S
6 3/4"
FRONT
BP
REFRIG
AND
CONTROL
ACCESS
R
TOP
N
A
ED
BLOWER
ACCESS
PANEL
1"
DRAIN 3/4" NPTI
BACK
C
WCI mounting location
LEFT SIDE
F X G
OPENING
L (W.O.)
M (W.I.)
Q
1/2"
14"
RIGHT SIDE
7"
1 3/8"
H
H
J
K
Table 9. Dimensional data right return/right supply (GEH/EXH)
GEH Unit
(60 Hz)
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
EXH Unit
(60 Hz)
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4 018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4 030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4 042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
2. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
(a)Return air opening dimension. (b)Filter rack dimension.
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
060
048, 060
EXH Unit
(50 Hz) A B C D
Hi-042,
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
(a)
E F x G H J KL NPTIM NPTI N P Q R
(b)
S
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
access on either side of the filter. 3 in. clearance.
20 WSHP-SVX01Q-EN
Figure 12. Left return/top supply (GEV/EXV)
D L
F
Unit Dimensions
K
B
WCI mounting location
JM
TOP
LEFT SIDE
D
E
8 3/4”
H
8 5/8”
BLOWER ACCESS
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
12”
9 1/2”
G
3 5/8”
W.O .
DRAIN
W.I .
C
RIGHT SIDE
Table 10. Dimensional data left return/top supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 015 006-012 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 030 015-024 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 5-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
060
GEV Unit
(50 Hz) A B C D E F G H J K L M
Hi-042,
048, 060
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
EXV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.I.
NPTI
W.O. NPTI
W.O. NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
WSHP-SVX01Q-EN 21
Unit Dimensions
Figure 13. Left return/back supply (GEV/EXV)
D
E
M
F
D
B
J
TOP
WCI mounting location
LEFT SIDE
8 3/4”
H
3 5/8”
BLOWER
ACCESS
COMP/CONTROL
ACCESS
HI VOLT
LO VOLT
A
FRONT
W.O .
DRAIN
9 1/2”
12”
G
3 5/8”
W.I .
C
RIGHT SIDE
Table 11. Dimensional data left return/back supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 009 006 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012 - 015 009-012 19-1/2 31-1/4 21-1/2 11-1/2 4-3/4 3-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 030 015-024 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 5-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 1/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
060
GEV Unit
(50 Hz) A B C D E F G H J K L M
Hi-042,
048, 060
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
EXV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.I.
NPTI
W.O. NPTI
W.O. NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
22 WSHP-SVX01Q-EN
Figure 14. Right return/top supply (GEV/EXV)
A
H
Unit Dimensions
F
D
L
K
M
B
WCI mounting location
HI VOLT
LOW VOLT
c
LEFT SIDE
3 5/8”
8 3/4”
BLOWER ACCESS
COMP/CONTROL
ACCESS
W.O .
DRAIN
FRONT
W.I .
3 5/8”
9 1/2”
G
12”
D
E
J
TOP
RIGHT SIDE
Table 12. Right return/top supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 015 006 - 012 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 024 015-018 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 5-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 2-1/2 5-5/8 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 5-3/4 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
GEV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.O. NPTI
030 024 21-1/2 39-1/4 21-1/2 13-1/2 4 4 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4
060
Hi-042,
048, 060
EXV Unit
(50 Hz) A B C D E F G H J K L M
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
W.I.
W.O.
NPTI
NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
WSHP-SVX01Q-EN 23
Unit Dimensions
Figure 15. Right return/back supply (GEV/EXV)
F
D
B
COMP/CONTROL
WCI mounting location
HIGH VOLT
LOW VOLT
8 3/4”
3 5/8”
BLOWER
ACCESS
ACCESS
W.O .
DRAIN
W.I .
3 5/8”
D
E
J
TOP
H
9 1/2”
12”
G
M
C
LEFT SIDE
A
FRONT
RIGHT SIDE
Table 13. Dimensional data right return/back supply (GEV/EXV)
GEV Unit
(60 Hz)
006 - 009 006 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012 - 015 009 - 012 19-1/2 31-1/4 21-1/2 11-1/2 6 1-1/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 018 - 024 015-018 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 9-3/4 3/4 3/4 3/4 3/4
036, 042 030, 036 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
Std-48 Std-42 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-1/8 11-3/8 1/2 1 1 3/4
Hi-048,
EXV Unit
(60 Hz)
006-019 N/A 19-1/2 31-1/4 21-1/2 11-1/2 4 1-3/4 9-1/2 15 17 6-7/8 8 3/4 1/2 1/2 3/4 012-015 N/A 19-1/2 31-1/4 21-1/2 11-1/2 2 1-1/4 9-1/2 15 17 8-1/4 9-3/4 3/4 1/2 1/2 3/4 018-024 N/A 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4 030-036 N/A 24-1/2 41-7/8 26-1/2 18 3-1/4 1-7/8 9-1/2 19 23 10-1/2 13-1/2 3/4 3/4 3/4 3/4
042-60 N/A 26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Notes:
1. Units in a free return application will require more than a 1 in. clearance to provide proper air flow to the unit’s air-to-refrigerant coil.
GEV Unit
(50 Hz) A B C D E F G H J K L M
W.I.
NPTI
W.O. NPTI
030 024 21-1/2 39-1/4 21-1/2 13-1/2 4 3-7/8 9-1/2 20-1/2 20 8-1/4 11-3/8 3/4 3/4 3/4 3/4
060
Hi-042,
048, 060
EXV Unit
(50 Hz) A B C D E F G H J K L M
26-1/2 46-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
W.I.
W.O.
NPTI
NPTI
070 N/A 26-1/2 50-7/8 30-1/2 18 4-1/4 2 9-1/2 29 27-7/8 13-7/8 13-7/8 1/2 1 1 3/4
Drain
FPT
Drain
FPT
24 WSHP-SVX01Q-EN
Figure 16. Right return/left supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
5/8”
BLOWER ACCESS
PANEL
4 7/8”
1 3/4”
23 7/8”
7 5/8”
(54)
2 1/8"
18 3/8”
1”
1 1/4”
A
74 1/2”
81”
85”
TOP VIE W
W.O. “D” NPTI
1 1/8” DIA.
24 VOLT
36”
1 1/2”
Unit Dimensions
4 5/8”
40 5/8”
18 3/4”
BACK SIDE
MOUNTING HOLE
3 1/8”
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
RETURN AIR
OPENING
1” DIA.
4X’s
14 1/2”
B
C
W.I. “D” NPTI
SUPPLY OPENING
1” DUCT FLANGE
LEFT SIDE
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
2 1/4”
23 1/4
16 1/2”
6 1/2”
Table 14. Dimensional data right return/left supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/4 in. 15-5/8 in. 6-5/8 in. 1-1/4 in. 090 072 36-1/8 in. 12-3/4 in. 6-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
WSHP-SVX01Q-EN 25
Unit Dimensions
Figure 17. Right return/back supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
74 1/2”
81”
85”
23 7/8”
2 1/8"
1 3/4”
18 3/8”
6 1/8”
36”
4 5/8”
40 5/8”
5/8”
18 3/4”
3 1/8"
BLOWER ACCESS
4 7/8”
DRAIN CONNECTION 1/2" (22) SCHEDULE 40 PVC
PANEL
14 1/2”
1 1/4”
TOP VIE W
W.O. “D” NPTI
A 1 1/2”
B
C
W.I. “D” NPTI
LEFT SIDE
RETURN AIR
OPENING
24 VOLT
1 1/8” DIA.
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
2 1/4”
23 1/4
16 1/2”
6 1/2”
Table 15. Dimensional data right return/back supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/4 in. 15-5/8 in. 6-5/8 in. 1-1/4 in. 090 072 36-1/8 in. 12-3/4 in. 6-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
26 WSHP-SVX01Q-EN
1” DIA.
MOUNTING HOLE
4X’s
SUPPLY OPENING
1” DUCT FLANGE
Figure 18. Left return/right supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
40 5/8”
4 5/8”
36”
74 1/2”
1 3/4”
24 3/4”
Unit Dimensions
23 1/4"
16 1/2”
1 1/2”
2 1/4”
6 1/2”
LEFT SIDE
RETURN AIR
OPENING
TOP VIE W
W.O. “D” NPTI
24 VOLT
1 1/8” DIA.
WCI mounting location
HIGH VOLTAGE
7/8” DIA.
81”
85”
18 3/8”
A
W.I. “D” NPTI
7 5/8”
1 1/4”
C
1 1/4”
14 1/2”
B
DRAIN CONNECTION
1/2” SCHEDULE 40 PVC
BLOWER ACCESS PANEL
1”
4 7/8”
5/8”
18 3/4”
3 1/8”
BACK SIDE
1” DIA.
MOUNTING HOLE
4X’S
Table 16. Dimensional data left return/right supply - GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/8 in. 17 in. 8 in. 1-1/4 in. 090 072 36-1/8 in. 13-3/4 in. 7-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
WSHP-SVX01Q-EN 27
SUPPLY OPENING
1” DUCT FLANGE
Unit Dimensions
Figure 19. Left return/back supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
79”
23 1/4"
(591)
40 5/8”
16 1/2"
(419)
36”
1 1/2”
4 5/8”
W.O. “D” NPTI
24 VOLT 1 1/8” DIA.
WCI mounting location
74 1/2”
81”
85”
TOP VIE W
A
6 1/2”
1 3/4”
18 3/8”
B
C
24 3/4”
6 1/8”
14 1/2”
1 1/4”
BLOWER ACCESS PANEL
1 1/4”
4 7/8”
5/8”
18 3/4
6 1/2”
1” DIA.
MOUNTING HOLE
4X’S
2 1/4”
LEFT SIDE
HIGH VOLTAGE
7/8” DIA.
SUPPLY OPENING
1” DUCT FLANGE
W.I. “D” NPTI
RETURN AIR OPENING
DRAIN CONNECTION
1/2" SCHEDULE 40 PVC
3 1/8”
Table 17. Dimensional data left return/back supply GEH 6 to 10 tons (60 Hz); GEH 6 to 7.5 tons (50 Hz)
GEH (60 Hz) GEH (50 Hz) A B C D
072 36-1/8 in. 17 in. 8 in. 1-1/4 in. 090 072 36-1/8 in. 13-3/4 in. 7-3/4 in. 1-1/4 in. 120 090 36-1/8 in. 13 in. 7-1/4 in. 1-1/2 in.
28 WSHP-SVX01Q-EN
Unit Dimensions
Figure 20. Right return/left supply GEH 12.5 to 15 tons (150-180) 60 Hz; GEH 10 to 12.5 tons (120-150) 50 Hz
85"
4 5/8"
42"
29 3/4"
2"
74 1/2"
46 5/8"
1 3/8"
23 3/4"
BACK SIDE
BLOWER ACCESS
4 7/8"
3 1/8"
RETURN AIR
OPENING
PANEL
1"
DRAIN CONNECTION 1/2" SCHEDULE 40 PVC
16 3/4"
24 7/8"
2 1/4"
2"
5 5/8"
7 1/8"
21 3/8"
61 1/4"
W.I. 1 1/2"
NPTI
87"
91"
LEFT SIDE
TOP VIEW
W.O. 1 1/2" NPTI
24 VOLT
1 1/8" DIA.
WCI mounting location
HIGH VOLTAGE
7/8" DIA.
2 1/4"
2 1/4"
30 1/4"
22 3/4"
9 1/8"
MOUNTING HOLE
1" DIA.
4X'S
WSHP-SVX01Q-EN 29
SUPPLY OPENING 1" DUCT FLANGE
Unit Dimensions
Figure 21. Right return/back supply GEH 12.5 to 15 tons (60 Hz); GEH 10 to 12.5 tons (50 Hz)
85"
1 3/8"
23 3/4"
BLOWER ACCESS
4 7/8"
PANEL
29 3/4"
2"
16 3/4"
2 1/4"
24 7/8”
2"
21 3/8"
7 1/8"
5 5/8”
TOP VIEW
61 1/4"
74 1/2"
87"
91"
W.O. 1 1/2” NPTI
WCI mounting location
24 VOLT
1 1/8” DIA.
4 5/8"
46 5/8"
42"
1 1/2"
30 1/4"
22 3/4"
3 1/8"
DRAIN CONNECTION
1/2” SCHEDULE 40 PVC
W.I. 1 1/2" (38)
NPTI
MOUNTING HOLE
1” DIA.
4X’S
LEFT SIDE
RETURN AIR
OPENING
HIGH VOLTAGE
7/8” DIA.
2 1/4"
9 1/8"
SUPPLY OPENING 1” DUCT FLANGE
30 WSHP-SVX01Q-EN
Loading...
+ 98 hidden pages