These instructions are given as a guide to good practice
in the installation, start-up, operation, and maintenance
by the user, of Trane CGAX chillers or CXAX heat pumps.
They do not contain full service procedures necessary
for the continued successful operation of this equipment.
The services of a qualified technician should be
employed through the medium of a maintenance
contract with a reputable service company. Read this
manual thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated,
charged and tested in accordance with factory standard
before shipment.
Warnings and cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualified
personnel.
WARNING!: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious
injury.
CAUTION!: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe
practices or for equipment or property-damage only
accidents.
CAUTION!: Time before to work on the electrical panel
of the unit with Low Ambient option: once the unit is
off (confirmed by the extinction of the display), it is
mandatory to wait five minutes before working on the
electrical panel.
Reception
On arrival, inspect the unit before signing the delivery
note. Specify any visible damage on the delivery note,
and send a registered letter of protest to the last carrier
of the goods within 7 days of delivery.
Notify the local TRANE sales office at the same
time. The delivery note must be clearly signed and
countersigned by the driver.
Any concealed damage shall be notified by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales office
at the same time.
Important notice: No shipping claims will be accepted
by TRANE if the above mentioned procedure is not
respected.
For more information, refer to the general sales
conditions of your local TRANE sales office.
Note: Unit inspection in France.
Delay to send registered letter in case of visible and
concealed damage is only 72 hours.
Warranty
Warranty is based on the general terms and conditions
of the manufacturer. The warranty is void if the
equipment is repaired or modified without the written
approval of the manufacturer, if the operating limits are
exceeded or if the control system or the electrical wiring
is modified. Damage due to misuse, lack of maintenance
or failure to comply with the manufacturer’s instructions
or recommendations is not covered by the warranty
obligation. If the user does not conform to the rules of
this manual, it may entail cancellation of warranty and
liabilities by the manufacturer.
Safety recommendations
To avoid death, injury, equipment or property damage,
the following recommendations should be observed
during maintenance and service visits:
1. The maximum allowable pressures for system leak
testing on low and high pressure side are given in the
chapter “Installation”. Do not exceed test pressure by
using an appropriate device.
2. Disconnect the main power supply before any
servicing on the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by
qualified and experienced personnel.
CG-SVX027D-GB
3
General Information
Maintenance contract
It is strongly recommended that you sign a maintenance
contract with your local Service Agency. This contract
provides regular maintenance of your installation by a
specialist in our equipment.
Regular maintenance ensures that any malfunction is
detected and corrected in good time and minimizes
the possibility that serious damage will occur. Finally,
regular maintenance ensures the maximum operating
life of your equipment.
We would remind you that failure to respect these
installation and maintenance instructions may result in
immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and
maintaining it in perfect operating condition over a long
period of time, the manufacturer has at your disposal a
refrigeration and air conditioning service school.
The principal aim of this is to give operators and
technicians a better knowledge of the equipment they
are using, or that is under their charge. Emphasis is
particularly given to the importance of periodic checks on
the unit operating parameters as well as on preventive
maintenance, which reduces the cost of owning the unit
by avoiding serious and costly breakdown.
2 = Contactors for single pump external to the unit
4 = Contactor for twin pump external to the unit
5 = Single pump package low pressure
6 = Single pump package high pressure
7 = Twin pump package low pressure
8 = Twin pump package high pressure
Digit 36 — Pump Flow Control
X = Constant Flow (no pump flow control)
B = Manual Flow Setpoint on VFD
C = Variable primary Flow (constant delta T)
Digit 37 — Buffer Tank
X = No Tank
1 = With Tank
Digit 44 — Literature language
B = Spanish
C = German
D = English
E = French
H = Dutch
J = Italian
M = Swedish
N = Turkish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
Y = Romanian
3 = Hungarian
Digit 45 — Under/Over Voltage Protection
X = None
1 = With
Digit 46 — Open for future options
Digit 38 — Open digit for future options
Digit 39 — Installation Accessories
1 = None
4 = Neoprene pads
Digit 40 — Open digit for future options
Digit 41 — Acoustical options
2 = High external static pressure
3 = Standard
4 = Low Noise
Digit 42 — Condenser Protection
X = Without
A = Condenser Guard Grill
Digit 43 — Open digit for future options
Digit 47 — Customer witness performance test
X = None
Digit 48 — Open for future options
Digit 49 — Supplementary Heat Control
X = None
1 = With
Digit 50 — Special design
X = Standard
S = Special design
6
CG-SVX027D-GB
Unit Description
Conquest chillers, CGAX, air cooled scroll compressor
type liquid chillers and CXAX heat pumps, are
designed for outdoor installation. Units can have one
or two independent refrigerant circuits, two or more
compressors per circuit. Unit are packaged with an
evaporator made with a braze plate heat exchanger, and
one or more condenser coils.
Each unit is completely assembled, hermetic package,
refrigerant circuit factory piped, electrical components
wired, leak tested, dehydrated, charged and tested
for proper control operations prior to shipment. The
chilled water inlet and outlet openings are covered for
shipment.
A new generation of chiller control systems, providing
improved control capabilities. Integrated safety protocols
to protect both compressor and motor from electrical
faults like thermal overload and phase reversal.
Each refrigerant circuit is provided with filter, electronic
expansion valve, and charging valves.
In cooling mode on the CXAX or on the CGAX, the
evaporator is a brazed plate and frame heat exchanger
equipped with water drain and vent connections on the
water piping.
Condenser coil is available in four different
configurations: fin and tube with aluminium fins, or
black epoxy pre-coating aluminum fins for the heat
pump versions, and MicroChannel type or E-coating
Microchannel type for the cooling only versions.
Accessory/options information
Check all the accessories and loose parts which are
shipped with the unit against the original order. Included
in these items will be rigging diagrams, wiring diagrams,
and service literature, which are placed inside the control
panel and/or starter panel for shipment. Also check for
optional components, such as couplings and pipe stubs
or neoprene pads.
The following pictograms can be found on the unit. Take
necessary precautions to avoid damage and injury.
Figure 1 - Warning pictograms
1 = Risk that unit is powered up
2 = Risk hazard due to fan rotation
3 = Risk hazard of burns on compressors or refrigeration
piping
4 = Unit contains refrigerant gas. See specific warnings.
5 = Risk of residual voltage when speed drive or
softstarter or Low Ambient options are present
6 = Unit under pressure
7 = Risk to cut, particularly on heat exchanger fins
8 = Read instructions before installation
9 = Disconnect all electric power before servicing
10 = Read technical instructions
CG-SVX027D-GB
7
Pre-Installation
Mandatory Start-up Checklist
This checklist is not intended to be a substitution for
the contractors installation instruction. This checklist is
intended to be a guide for the Trane technician just prior
to unit ‘start-up’. Many of the recommended checks and
actions could expose the technician to electrical and
mechanical hazards. Refer to the appropriate sections in
the unit manual for appropriate procedures, component
specifications and safety instructions.
Except where noted; it is implied that the technician is to
use this checklist for inspection / verification of prior task
completed by the general contractor at installation.
1. Unit clearances adequate for service and to avoid air
recirculation, etc.
2. Unit exterior inspected. CXAX condensor coil will not
be obstructed at any time by snow or ice during winter
conditions.
3. Unit properly grounded
4. Crankcase heaters working for 24 hours prior to arrival
of Trane technician performing start up
5. Correct voltage supplied to unit and electric heaters
(imbalance not to exceed 2%)
6. Unit power phasing (A-B-C sequence) proper for
compressor rotation
7. Copper power wiring meets sizing requirement in job
submittal
8. All automation and remote controls installed/wired
9. All wiring connections tight
10. Prove chilled water side Interlock and Interconnecting
Wiring Interlock and externals (chilled water pump)
11. Field installed control wiring landed on correct
terminals (external start/stop, emergency stop, chilled
water reset…)
12. Verify all refrigerant and oil valves are open/back
seated
13. Compressor oil levels (1/2 -3/4 high in glass) proper
14. Verify chilled water strainer is clean and free of debris
and evaporator chilled water circuits are filled
15. A pressure switch device to detect lack of water is
not included in the pump package. Installation of
this type of device is highly recommended to avoid
sealing damage due to operation of pump without
enough water.
16. Close the fused-disconnect switches that supplies
power to the chilled water pump starter
17. Start the chilled water pump to begin circulation
of the water. Inspect piping for leaks and repair as
necessary. Check the physical presence of the water
pressure switch.
18. With water circulating through the system, adjust
water flow and check water pressure drop through
evaporator
19. Return chilled water pump to auto
20. Verify all the chiller controller Menu Items.
21. All panels/doors secured prior to start-up
22. All coil fins inspected and straightened
23. Rotate fans before starting unit to inspect for
potential audible and visual signs of rubbing.
Start unit
24. Press AUTO key. The unit will start if the chiller
control calls for cooling and the safety interlocks are
closed
25. Check the evaporator and the condenser refrigerant
pressure on the chiller controller.
26. Confirm Superheat and subcooling values are normal
27. Compressor operation normal and within amperage
rating
28. Operating log completed
29. Press stop key
30. Inspect fans again after being under load to ensure
no signs or rubbing exist
31. Verify the chilled water pump runs for at least
1 minute (possibility to configure maxi 10 mn) after
the chiller is commanded to stop (for normal chilled
water systems)
Unit storage
If the chiller is to be stored for more than one month
prior to installation, observe the following precautions:
• Store the chiller in a dry, vibration-free, secure area.
• Units charged with refrigerant should not be stored
where temperatures exceed 68°C.
• At least every three months, attach a gauge and
manually check the pressure in the refrigerant circuit.
If the refrigerant pressure is below 13 bar at 20°C
(or 10 bar at 10°C), call a qualified service organization
and the appropriate Trane sales office.
Note: if the unit is stored before servicing near a
construction site it is highly recommended to protect
micro channel coils from any concrete and iron element.
Failure to do so may considerably reduce reliablity of
the unit.
8
CG-SVX027D-GB
Pre-Installation
Installation requirements and
contractor responsibilities
A list of the contractor responsibilities typically
associated with the unit installation process is provided.
• Wiring sizes per submittals and local codes
and regulations
• Terminal lugs
• Disconnect Switch
• Unit mounted starter
• Grooved pipes coupling
and stub pipe (Optional)
• Control voltage wiring
• Ground connection(s)
• BAS Wiring (optional)
• Chilled water pump contactor and wiring
including interlock
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Waterowpressuregauges
• Isolation and balancing valves in water
piping
• Vents and rains
• Pressure relief valves
• Pressure switch device to detect lack of
water
CG-SVX027D-GB
9
General Data
Table 1 - CGAX 015-036 General Data
CGAX
015
Net Cooling Capacity (1)(kW)43495965748299
Total Power input in cooling (1)(kW)15171922262933
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)12121212121215
Power Cable Cross Section (max)mm²353535353535150
Disconnect switch size(A)8080100100100100250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)20.423.227.931.635.439.145.1
Unit rated amps(A)34.539.246.952.057.165.575.4
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.7184.7189.8191.0199.5
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.9121.5126.6129.0140.7
Power factor0.8680.8660.8700.8880.9020.8700.873
Digit 12=1 and Digit 15=A
Maximum Power input(kW)19.422.125.829.533.337.043.0
Unit rated amps(A)33.838.545.450.555.664.073.8
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)116.3160.3167.2183.2188.3189.5197.9
Unit start up amps (with soft starter - Digit 26=B) (4)77.1103.5110.4120.0125.1127.5139.1
Power factor0.8450.8460.8360.8610.8800.8470.854
Digit 12=1 and Digit 15=C
Maximum Power input(kW)20.423.226.830.634.338.144.1
Unit rated amps(A)34.539.246.251.356.464.874.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.0184.0189.1190.3198.7
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.2120.8125.9128.3139.9
Power factor0.8680.8660.8540.8750.8920.8590.864
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27,5+7,57,5+1010+1010+1313+1315+1512+12+12
Max Compr Power input Circuit 1/Circuit 2kW9,2 + 9,29,2+ 1212 + 1212 + 15,715,7 + 15,7 17,61 + 17,6
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP80x66P80x92P80x92P80x92P120Tx76P120Tx76 P120Tx104
Evaporator Water Content volume(l)3.85.35.35.39.29.212.5
Nominal water connection size
(Grooved coupling) - Without HYM
Nominal water connection size
(Grooved coupling) - With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.501.501.501.50
Rated Amps(A)2.442.442.443.503.503.503.50
Single pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.20
Rated Amps(A)2.442.442.443.503.503.503.50
Twin pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)324324324324324324444
Antifreeze Heater without pump package(W)120120120120120120180
Antifreeze Heater with pump package(W)280280280280280280340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.232.232.962.962.962.964.46
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h13753137181224812231122111219313727
Max Power InputKw1,951,951,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95
Max AmpsA333 + 33 + 33 + 33 + 33 + 3
Motor RPM(rpm)915915915915915915915
Digit 12=1 and Digit 15=A
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw0,890,890,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89
Max AmpsA2,222,222,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22
Motor RPM(rpm)686686686686686686686
Digit 12=1 and Digit 15=C
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw1,951,951,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89
Max AmpsA333 + 2,223 + 2,223 + 2,223 + 2,223 + 2,22
Motor RPM(rpm)686686686686686686686
Water content volume(l)0.140.140.140.140.350.350.35
Dimensions (7)
Unit Length(mm)2346234623462346234623462327
Unit Width(mm)1285128512851285128512852250
Std Unit Height(mm)1524152415241524152415241524
LN or External SP unit -
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Pump VFD option(kg)0
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)11112797116129147164
Total Power input in cooling (1)(kW)38413539475158
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)15151515151515
Power Cable Cross Section (max)mm²150150150150150150150
Disconnect switch size(A)250250250250250250250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)51.158.746.455.863.370.778.2
Unit rated amps(A)82.698.278.193.5103.7113.9130.7
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)215.3223.7199.9215.3236.4246.6256.2
Unit start up amps (with soft starter - Digit 26=B) (4)152.1161.7143.1158.5173.2183.4194.2
Power factor0.9010.8700.8660.8700.8880.9020.870
Digit 12=1 and Digit 15=A
Maximum Power input(kW)49.055.544.251.659.066.574.0
Unit rated amps(A)81.095.876.590.4100.6110.8127.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)213.7221.3198.3212.2233.3243.5253.1
Unit start up amps (with soft starter - Digit 26=B) (4)150.5159.3141.5155.4170.1180.3191.1
Power factor0.8860.8470.8460.8360.8610.8800.847
Digit 12=1 and Digit 15=C
Maximum Power input(kW)50.056.646.453.761.268.676.1
Unit rated amps(A)81.896.678.191.9102.1112.3129.1
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)214.5222.1199.9213.7234.8245.0254.6
Unit start up amps (with soft starter - Digit 26=B) (4)151.3160.1143.1156.9171.6181.8192.6
Power factor0.8940.8550.8660.8540.8750.8920.859
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Quantity#1111111
TypeStainless steel Copper Brazed plate Heat exchanger
Evaporator modelP120Tx104P120Tx104DP300x82DP300x82DP300x82 DP300x114 DP300x114
Evaporator Water Content volume(l)12.512.58.58.58.511.811.8
Nominal water connection size
(Grooved coupling) - Without HYM
Nominal water connection size
(Grooved coupling) - With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Single pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Twin pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)444444444444444444444
Antifreeze Heater without pump package(W)180180120120120180180
Antifreeze Heater with pump package(W)340340280280280340340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.232.962.962.962.96
(in) -
(mm)
(in) -
(mm)
SE-SN
15,7 +
15,7 + 15,7
25,3 +
25,3 + 25,3
158 +
158 + 158
2" - 60,32" - 60,33" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
(l)2000200020002000200020002000
CGAX
045
SE-SN
17,6 +
17,6 + 17,6
29,5 +
29,5 + 29,5
155 +
155 + 155
CGAX
035
SE-SN
7,5+10 /
7,5+10
9,2 + 12 /
9,2 + 12
15,5 + 20,2 /
15,5 + 20,2
98 + 142 /
98 + 142
CGAX
040
SE-SN
10+10 /
10+10
12 + 12 /
12 + 12
20,2 + 20,2 /
20,2 + 20,2
142 + 142 /
142 + 142
CGAX
046
SE-SN
10+13
/10+13
12 + 15,7 /
12 + 15,7
20,2 + 25,3 /
20,2 + 25,3
142 + 158 /
142 + 158
CGAX
052
SE-SN
13+13 /
13+13
15,7 + 15,7 /
15,7 + 15,7
25,3 + 25,3 /
25,3 + 25,3
158 + 158 /
158 + 158
CGAX
060
SE-SN
15+15 /
15+15
17,6 + 17,6 /
17,6 + 17,6
29,5 + 29,5 /
29,5 + 29,5
155 + 155 /
155 + 155
12
CG-SVX027D-GB
General Data
Table 1 - CGAX 039-060 General Data (continued)
CGAX
039
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h14660135951468612249122331244712205
Water content volume(l)0.50.52x 0.142x 0.142x 0.142x 0.352x 0.35
Dimensions (7)
Unit Length(mm)2327232723272327232723272327
Unit Width(mm)2250225022502250225022502250
Std Unit Height(mm)1524152415241524152415241524
LN or External SP unit -
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Pump VFD option(kg)0
Partial heat recovery option(kg)4.64.62x 1.482x 1.482x 1.482x 3.822x 3.82
Water Buffer tank option(kg)425425425425
System data
Nb of refrigerant circuit#1122222
Minimum cooling load % (6)%33332225222525
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)43495965748299
Total Power input in cooling (1)(kW)15171922262933
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)12121212121215
Power Cable Cross Section (max)mm²353535353535150
Disconnect switch size(A)8080100100100100250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)20.423.227.931.635.439.145.1
Unit rated amps(A)34.539.246.952.057.165.575.4
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.7184.7189.8191.0199.5
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.9121.5126.6129.0140.7
Power factor0.8680.8660.8700.8880.9020.8700.873
Digit 12=1 and Digit 15=A
Maximum Power input(kW)19.422.125.829.533.337.043.0
Unit rated amps(A)33.838.545.450.555.664.073.8
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)116.3160.3167.2183.2188.3189.5197.9
Unit start up amps (with soft starter - Digit 26=B) (4)77.1103.5110.4120.0125.1127.5139.1
Power factor0.8450.8460.8360.8610.8800.8470.854
Digit 12=1 and Digit 15=C
Maximum Power input(kW)20.423.226.830.634.338.144.1
Unit rated amps(A)34.539.246.251.356.464.874.6
Unit start up amps (w/o soft starter - Digit 26=A) (4) (A)117.0161.0168.0184.0189.1190.3198.7
Unit start up amps (with soft starter - Digit 26=B) (4)77.8104.2111.2120.8125.9128.3139.9
Power factor0.8680.8660.8540.8750.8920.8590.864
Compressor
Compressor Number per Circuit#2222223
TypeScrollScrollScrollScrollScrollScrollScroll
Model Circuit1 / Circuit 27,5+7,57,5+1010+1010+1313+1315+1512+12+12
Max Compr Power input Circuit 1/Circuit 2kW9,2 + 9,29,2+ 1212 + 1212 + 15,7 15,7 + 15,7 17,61 + 17,6
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.501.501.501.50
Rated Amps(A)2.442.442.443.503.503.503.50
Single pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)9610086113120110103
Motor Power(kW)1.201.201.201.50
Rated Amps(A)2.442.442.443.503.503.503.50
Twin pump - High head pressure option
Max available Head Pressure(kPa)170174162152161152190
Motor Power(kW)2.302.302.302.302.302.303.00
Rated Amps(A)5.035.035.035.035.035.036.23
Expansion Tank Volume(l)25252525252535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)324324324324324324444
Antifreeze Heater without pump package(W)120120120120120120180
Antifreeze Heater with pump package(W)280280280280280280340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#1111112
Face area per circuit(m²)2.232.232.962.962.962.964.46
Quantity#1122222
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h13753137181224812231122111219313727
Max Power InputKw1,951,951,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95 1,95 + 1,95
Max AmpsA333 + 33 + 33 + 33 + 33 + 3
Motor RPM(rpm)915915915915915915915
Digit 12=1 and Digit 15=A
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw0,890,890,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89 0,89 + 0,89
Max AmpsA2,222,222,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22 2,22 + 2,22
Motor RPM(rpm)686686686686686686686
Digit 12=1 and Digit 15=C
Fan / motor TypeFixed speed AC motor / Variable speed - EC motor
Airowperfanm3/h13788138281236212362123701237513827
Max Power InputKw1,951,951,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89 1,95 + 0,89
Max AmpsA333 + 2,223 + 2,223 + 2,223 + 2,223 + 2,22
Motor RPM(rpm)686686686686686686686
Water content volume(l)0.140.140.140.140.350.350.35
Dimensions (7)
Unit Length(mm)2346234623462346234623462327
Unit Width(mm)1285128512851285128512852250
Std Unit Height(mm)1524152415241524152417241524
LN or External SP unit -
Single pump - Standard head pressure(kg)46464649494945
Single pump - High head pressure(kg)51515151515149
Twin pump - Standard head pressure(kg)70707075757571
Twin pump - High head pressure(kg)82828282828286
Pump VFD option(kg)0
Partial heat recovery option(kg)1.481.481.481.483.823.823.82
Water Buffer tank option(kg)319319319319319319425
System data
Nb of refrigerant circuit#1111111
Minimum cooling load % (6)%50435043505033
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on
Net Cooling Capacity (1)(kW)11112797116129147164
Total Power input in cooling (1)(kW)38413539475158
Unit electrical data (2) (3) (4)
Short Circuit Unit Capacity (9)(kA)15151515151515
Power Cable Cross Section (max)mm²150150150150150150150
Disconnect switch size(A)250250250250250250250
Digit 12=2 or Digit 12=1 and Digit 41=2
Maximum Power input(kW)51.158.746.455.863.370.778.2
Unit rated amps(A)82.698.278.193.5103.7113.9130.7
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)215.3223.7199.9215.3236.4246.6256.2
Unit start up amps (with soft starter - Digit 26=B) (4)152.1161.7143.1158.5173.2183.4194.2
Power factor0.9010.8700.8660.8700.8880.9020.870
Digit 12=1 and Digit 15=A
Maximum Power input(kW)49.055.544.251.659.066.574.0
Unit rated amps(A)81.095.876.590.4100.6110.8127.6
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)213.7221.3198.3212.2233.3243.5253.1
Unit start up amps (with soft starter - Digit 26=B) (4)150.5159.3141.5155.4170.1180.3191.1
Power factor0.8860.8470.8460.8360.8610.8800.847
Digit 12=1 and Digit 15=C
Maximum Power input(kW)50.056.646.453.761.268.676.1
Unit rated amps(A)81.896.678.191.9102.1112.3129.1
Unit start up amps (w/o soft starter - Digit 26=A) (4)(A)214.5222.1199.9213.7234.8245.0254.6
Unit start up amps (with soft starter - Digit 26=B) (4)151.3160.1143.1156.9171.6181.8192.6
Power factor0.8940.8550.8660.8540.8750.8920.859
Compressor
Compressor Number per Circuit#3322222
TypeScrollScrollScrollScrollScrollScrollScroll
Without HYM
Nominal water connection size (Grooved coupling) -
With HYM
Hydraulic Module Components
Single pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Single pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Twin pump - Standard head pressure option
Max available Head Pressure(kPa)131104111133114113178
Motor Power(kW)2.302.301.502.302.302.302.30
Rated Amps(A)5.035.033.505.035.035.035.03
Twin pump - High head pressure option
Max available Head Pressure(kPa)176151198179162162138
Motor Power(kW)3.003.003.003.003.003.003.00
Rated Amps(A)6.236.236.236.236.236.236.23
Expansion Tank Volume(l)35353535353535
Max User water loop Volume for factory mounted
expansion tank (1)
Optionnal water Buffer tank volume(l)444444444444444444444
Antifreeze Heater without pump package(W)180180120120120180180
Antifreeze Heater with pump package(W)340340280280280340340
Condenser
TypeFull aluminum Micro channel heat exchanger
Quantity of coil#2222222
Face area per circuit(m²)5.935.932.232.962.962.962.96
(in) -
(mm)
(in) -
(mm)
SE-SN
15,7 +
15,7 + 15,7
25,3 +
25,3 + 25,3
158 +
158 + 158
2" - 60,32" - 60,3 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1 3" OD - 76,1
(l)2000200020002000200020002000
CXAX
045
SE-SN
17,6 +
17,6 + 17,6
29,5 +
29,5 + 29,5
155 +
155 + 155
CXAX
035
SE-SN
7,5+10 /
7,5+10
9,2 + 12 /
9,2 + 12
15,5 + 20,2 /
15,5 + 20,2
98 + 142 /
98 + 142
CXAX
040
SE-SN
10+10 /
10+10
12 + 12 /
12 + 12
20,2 + 20,2 /
20,2 + 20,2
142 + 142 /
142 + 142
CXAX
046
SE-SN
10+13
/10+13
12 + 15,7 /
12 + 15,7
20,2 + 25,3 /
20,2 + 25,3
142 + 158 /
142 + 158
CXAX
052
SE-SN
13+13 /
13+13
15,7 + 15,7 /
15,7 + 15,7
25,3 + 25,3 /
25,3 + 25,3
158 + 158 /
158 + 158
3.003.00
CXAX
060
SE-SN
15+15 /
15+15
17,6 + 17,6 /
17,6 + 17,6
29,5 + 29,5 /
29,5 + 29,5
155 + 155 /
155 + 155
16
CG-SVX027D-GB
General Data
Table 2 - CXAX 039-060 General Data (continued)
CXAX
039
Condenser Fan
Quantity#2324444
Diameter(mm)800
Fan / motor TypePropeller fan : Fixed speed AC motor / Variable speed - EC motor / HESP MAX SPEED
Digit 12=2 or Digit 12=1 and Digit 41=2
Fan / motor TypeEC motor / HESP MAX SPEED
Airowperfanm3/h14660135951468612249122331244712205
Water content volume(l)0.50.52x 0.142x 0.142x 0.142x 0.352x 0.35
Dimensions (7)
Unit Length(mm)2327232723272327232723272327
Unit Width(mm)2250225022502250225022502250
Std Unit Height(mm)1524152415241524152415241724
LN or External SP unit -
Single pump - Standard head pressure(kg)47474547474747
Single pump - High head pressure(kg)49494949494949
Twin pump - Standard head pressure(kg)75757575757575
Twin pump - High head pressure(kg)86868484848484
Pump VFD option(kg)0
Partial heat recovery option(kg)4.64.62x 1.482x 1.482x 1.482x 3.822x 3.82
Water Buffer tank option(kg)425425425425425425425
System data
Nb of refrigerant circuit#
Minimum cooling load % (6)%33332225222525
(1) Indicative performance at Evaporator water temperature : 12°C / 7°C - Condenser air temperature 35°C - for detailled performances, on a given unit,
consult Order Write Up.
(2) under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) If the power line of the unit is protected by fuses gG of the same size as the disconnect switch.
(6) OIL058E or 0IL057E are European reference for POE oil and can be mixed in any proportion with OIL00078 or OIL 00080 (same oil with US reference on