CO2 Duct Sensor
and CO2 Wall Sensor
Figure 2: CO2 Wall SensorFigure 1: CO2 Duct Sensor
The wall and duct-mounted carbon
dioxide (CO
especially for demand-controlled
ventilation zone applications. The sensor
is compatible with Trane VAV and
VariTrac
and reliable sensing performance come
from advanced silicon based NonDispersive Infrared (NDIR) technology.
When connected to a building
automation system and the appropriate
ventilation equipment, the Trane CO
sensors measure and record carbon
dioxide in parts-per-million (ppm) in
occupied building spaces. These carbon
dioxide measurements are typically
used to identify under-ventilated
building zones and to override outdoor
airflow beyond design ventilation rates
if the CO
Please visit
Trane representative for more
information.
) sensors are designed
2
®
controllers. Long-term stability
exceeds acceptable levels.
2
trane.com
or contact a local
Features
Wall- or Duct-mounted
Measures CO2 in ppm.
NDIR Sensing Technology
Demand-Controlled Ventilation
Table 1: Sensor Specifications
Duct Wall
Measuring Range 0–2000 parts per million (ppm)
Accuracy at 77°F (25°C) < ± (30 ppm CO
Recommended calibration interval 5 years
Response time 1 minute (0-63%)
2
Operating Temperature 23 to 113°F 59 to 95°F
Storage Temperature -4 to 158°F (-20 to 70°C)
Humidity Range 0–85% relative humidity (RH)
Output Signal (jumper selectable) 4-20 mA, 0–20 mA, 0–10 VDC
Resolution of analog outputs 10 ppm CO
Power Supply Nominal 24 VAC
Power Consumption < 5 VA
Housing Material ABS plastic
Dimensions 3 1/8" x 3 1/8" x 7 3/4" 4 1/4" x 3 1/8" x 1 7/16"
+ 3% of reading) + 3% of reading)
(-5 to 45°C) (15 to 35°C)
(80 mm x 80 mm x (108 mm x 80 mm x
200 mm) 36 mm)
2
< ± (40 ppm CO
2
2
©2002 American Standard, Inc. All rights reserved
VAV-SLB008-EN
Figure 3: Dimensional Data
108 mm
(4.25")
80 mm
(3.125")
36 mm
(1.4375")
Specifications:
Measuring range: 0–2000 parts per million (ppm) CO
Accuracy at 25˚C: <± (40 ppm CO
Non-linearity: < 1% full scale (FS)
Temperature dependence of output: 0.3% FS/degrees C
Long-term stability: <5.0" FS/5 years
Recommended calibration interval: 5 years
Response time: 1 minute (0–63%)
Operating temperature: From 59 to 95˚F (15 to 35˚C)
Storage temperature: From -4 to 158˚F (-20 to 70˚C)
Humidity range: 0–85% relative humidity (FH)
Output signals (jumper selectable): 4–20 mS, 0–20 mA, 0–10 Vdc
Resolution of analog outputs: 10 ppm CO
Recommended external load: Current output: max. 500 ohms
Voltage output: min. 1000 ohms
Power supply: Nominal 24 Vac
Power consumption: <5 VA
Warm-up time: < 15 minutes
Housing material: ABS plastic
Mounting holes: For standard Asian, European, and North American junction boxes
Trane
An American Standard Company
www.trane.com
For more information contact
your local district office or
e-mail us at comfort @trane.com
©2002 American Standard, Inc. All rights reserved
+ 3% of reading)
2
(includes repeatability and calibration uncertainty)
2
Literature Order Number VAV-SLB008-EN
File Number SB-TD-VAV-000-SLB008-EN-0602
Supersedes New
Stocking Location La Crosse
Trane has a policy of continuous product and product data improvement and reserves the right to change design
and specifications without notice.
2