Trane City RTSF050, City RTSF060, City RTSF070, City RTSF090, City RTSF100 Installation Operation & Maintenance

...
Installation Operation Maintenance
Water-cooled Liquid Chillers with Helical Rotary Compressors
RTSF: 180-385kW (R1234ze)
RLC-SVX023A
Contents
Introduction .......................................................................................................3
Unit model number description ....................................................................... 5
General Data ......................................................................................................7
Unit Description ................................................................................................. 8
Installation - Mechanical ................................................................................. 10
Installation - Electrical ..................................................................................... 21
Operating Principles Mechanical ....................................................................27
Typical Operating map ....................................................................................33
Controls/Tracer TD7 Operator Interface ......................................................... 34
Pre-Start Checkout ..........................................................................................35
Unit Start-up .................................................................................................... 37
Periodic Maintenance ...................................................................................... 38
Maintenance Procedures ................................................................................41
Recommended service routine frequencies .................................................. 46
Additional services .......................................................................................... 47
2 © Trane 2019
RLC-SVX023A
Introduction
Foreword
These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane City chiller RTSF, manufactured in France. A separate manual is available for the use and maintenance of the unit’s control, Tracer™ UC800. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up. Units are assembled, pressure tested, dehydrated, charged and tested in accordance with factory standard before shipment.
Warnings and Cautions
Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents.
Safety Recommendations
To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter “Installation”. Insure to do not exceed test pressure by using appropriate device.
2. Disconnect all power supplies before any servicing on the unit.
3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.
4. To avoid any risk, it is recommended to place the unit on an area with restricted access.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any visible damage on the delivery note, and send a registered letter of protest to the last carrier of the goods within 7 days of delivery.
Notify the local TRANE sales office at the same time. The delivery note must be clearly signed and countersigned by the driver.
Any concealed damage shall be notified by a registered letter of protest to the last carrier of the goods within 7 days of delivery. Notify the local TRANE sales office at the same time.
Important notice: No shipping claims will be accepted by TRANE if the above mentioned procedure is not respected.
For more information, refer to the general sales conditions of your local TRANE sales office.
Note: Unit inspection in France. Delay to send registered letter in case of visible and concealed damage is only 72 hours.
Loose Parts Inventory
Check all the accessories and loose parts that are shipped with the unit against the shipping list. Included in these items will be the Water Flow Switch (optional), rigging and electrical diagrams, service literature, which are placed inside the control panel and/or starter panel for shipment. If optional elastomeric isolators are ordered with the unit they are shipped mounted on the horizontal support frame of the chiller. The isolators’ location and distribution weight diagram is placed with the service literature inside the starter/control panel.
Warranty
Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer’s instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer.
RLC-SVX023A
3
Introduction
Unit Description
The RTSF units are helical-rotary type, water-cooled, liquid chillers, designed for installation indoors. The RTSF units are packaged with an evaporator and condenser.
Note: Each RTSF unit is a completely assembled, hermetic package that is factory-piped, wired, leak tested, dehydrated, charged and tested for proper control operations prior to shipment. The chilled water inlet and outlet openings are covered for shipment.
The RTSF series features Trane’s exclusive Adaptive Control logic with UC800 controls. It monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can correct these variables, when necessary, to optimize operational efficiencies, avoid chiller shutdown, and keep producing chilled water.
Compressor loading/unloading is provided by AFD (Adaptive Frequency Drive) coordinated with slide valve operation.
Each refrigerant circuit is provided with filter, sight glass, electronic expansion valve, and charging valves on the RTSF.
The evaporator and condenser are manufactured in accordance with Pressure Equipment Directive standards. The evaporator and the condenser are insulated according the option ordered. Both evaporator and condenser water pipes are equipped with water drain and vent connections.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Trane Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
Refrigerant
Consult the addendum to Manuals for units with refrigerant, for conformity to the Pressure Equipment Directive (PED) 97/23/EC or 2014/68/EU and Machinery Directive 2006/42/EC and for specific caution for R1234ze.
4
RLC-SVX023A
Unit model number description
Digit 1, 2, 3, 4 – Unit Model
RTSF
Digit 5, 6, 7 – Unit size
50 = 50 Nominal tons 60 = 60 Nominal tons 70 = 70 Nominal tons 90 = 90 Nominal tons 100 = 100 Nominal tons 110 = 110 Nominal tons
Digit 8 – Unit Power supply
D = 400 V – 50 Hz – 3Ph
Digit 9 – Factory
E = Europe F = ICS
Digit 10 & 11 – Design sequence
(Factory assigned)
Digit 12 & 13 – Not used
Digit 14 – Agency listing
C = CE marking
Digit 15 – Pressure Vessel Code
2 = PED (Pressure Equipment Directive)
Digit 16 – Unit Application
X = Cooling Mode - Below 50°C Leaving Condenser Temp H = Cooling Mode - Above 50°C Leaving Condenser Temp L = Heat pump - Below 50°C Leaving Condenser Temp M = Heat pump - Above 50°C Leaving Condenser Temp
Digit 27 – Not Used
Digit 28 – Evaporator pump
X = Without
Digit 29 – Condenser Size
A = Condenser A B = Condenser B C = Condenser C D = Condenser D
Digit 30 & 31 – Not Used
Digit 32 – Condenser Pump
X = Without
Digit 33 – Condenser Water side pressure
X = 10 Bar Condenser Water Pressure
Digit 34 – Condenser Thermal Insulation
X = Without H = With Condenser Insulation
Digit 35 – Oil cooler
X = Without C = With
Digit 36 – Evaporator Pump Smart Flow control
X = Without E = VPF Constant Delta T Evaporator
Digit 37 – Power Protection
F = Disconnect switch with fuses B = Disconnect switch with circuit breakers
Digit 17 – Refrigerant
Z = R1234ze unit with Factory charge (with oil) Y = R1234ze with pre-charge (with oil) L = R1234ze unit with Nitrogen (no oil)
Digit 18 – Sound Attenuation Package
X = Without A = Aesthetic option L = Sound attenuation package
Digit 19 – Relief Valve Option
L = Single Relief Valve Condenser 2 = Single Relief Valve Condenser & Evaporator D = Dual relief valve with 3 way valve condenser 4 = Dual relief valve with 3 way valve condenser & Evaporator
Digit 20 – Compressor Type
L = CHHP Low VI H = CHHP or CHHW High VI
Digit 21 – Evaporator Size
A = Evaporator A B = Evaporator B C = Evaporator C D = Evaporator D
Digit 22 & 23 & 24 – Not Used
Digit 25 – Evaporator Water side Pressure
X = 10 Bar Evaporator Water Pressure
Digit 26 – Evaporator application
N = Comfort Cooling (above 5°C) P = Process Cooling below 5°C C = Ice Making (from -7°C to 20°C)
Digit 38 – Not Used
Digit 39 – Relay Card
1 = With additional relay card
Digit 40 – Smart com protocol
X = Without B = BACnet MSTP interface C = BACnet IP interface M = Modbus RTU interface L = LonTalk interface
Digit 41 – Communication customer input/output
X = Without A = External Set points & Capacity outputs – Voltage Signal B = External Set points & Capacity outputs – Current Signal
Digit 42 – Outdoor Air Temperature Sensor
X = Without A = Outdoor Air Temperature Sensor – CWR/Low Ambient
Digit 43 – Not Used
Digit 44 – Master Slave Set
X = Without M = With
RLC-SVX023A
5
Unit model number description
Digit 45 – Energy meter
X = Without M = With
Digit 46 – Condenser Pump Smart Flow Control/Other Condenser Pressure Control Outputs
X = Without 1 = Condenser Pressure in % HPC 2 = Differential Pressure 3 = Condenser Head Pressure Flow Control 4 = VPF Constant Delta T Condenser Flow Control
Digit 47 – Power socket
X = Without P = Included (230V-100W)
Digit 48 – Factory test
X = Without B = Visual Inspection E = Test E - 1 point with Report Non Witnessed S = Special test
Digit 49 – Installation Accessory
X = Without 1 = Neoprene isolators 4 = Neoprene pads
Digit 50 – Connection Accessory
X = Grooved pipe connection W = Grooved pipe with coupling and pipe stub
Digit 51 – Flow switch
X = Without A = Evaporator or Condenser B = Evaporator and Condenser
Digit 52 – Literature Language
C = Spanish D = German E = English F = French H = Dutch I = Italian M = Swedish P = Polish R = Russian T = Czech V = Portugese 6 = Hungarian 8 = Turkish
Digit 53 – Not Used
Digit 54 – EXV selection
X = Standard EXV
Digit 55 – AFD Selection
A = AFD A B = AFD B C = AFD C D = AFD D E = AFD E F = AFD F
Digit 56 – Design special
X = Without S = Special
6
RLC-SVX023A
General Data
Table 1 – General Data RTSF Standard efficiency - R1234ze
Indicative performances (1)
Cooling Capacity (1) (kW) 183 220 264 314 363 388 Total Power input in cooling (1) (kW) 37 43 53 64 80 90
Unit Electrical data (2) (5)
Low VI compressor - digit 20 =L
Maximum Power Input (kW) 66 77 91 111 130 ­Unit rated amps (2) (A) 100 117 138 168 196 ­Unit start up amps (2) (A) 100 117 138 168 196 ­Displacement power factor 0.95 0.95 0.95 0.95 0.95 -
High VI compressor - Digit 20 = H
Maximum Power Input (kW) 87 103 125 150 178 178 Unit rated amps (2) (A) 131 155 190 227 270 270 Unit start up amps (2) (A) 131 155 190 227 270 270 Displacement power factor 0.95 0.95 0.95 0.95 0.95 0.95 Short Circuit Unit Capacity (kA) 35 35 35 35 35 35 Max Power cable (cross) mm² 1x 240 1x 240 1x 240 1x 240 1x 240 1x 240 Disconnect switch size (3) (A) 400 400 400 400 400 400
Compressor
Type Screw Screw Screw Screw Screw Screw Model 60 70 85 100 120 140
Low VI compressor - digit 20 =L
Max compressors Power Input (kW) 65 76 91 110 129 ­Max Amps (3) (6) (A) 98 115 136 166 194 ­Start up Amps (A) 98 115 136 166 194 -
High VI compressor - Digit 20 = H
Max compressors Power Input (kW) 86 102 124 149 177 177 Max Amps (3) (6) (A) 129 153 188 225 268 268 Start up Amps (A) 129 153 188 225 268 268 Motor RPM (rpm) Oil sump heater (kW) 0.275 0.275 0.275 0.275 0.275 0.275
Evaporator
Type BPHE BPHE BPHE BPHE BPHE BPHE Evaporator model C B B A A A Evaporator Water Content volume (l) 52 59 69 92 92 92
Evap. Water Flow rate - Minimum (4) (l/s) 3.6 4.8 4.8 6.4 6.4 6.4 Evap. Water Flow rate - Maximum (4) (l/s) 38.6 38.6 38.6 38.6 38.6 38.6 Nominal water connection size (Grooved coupling) (in) - (mm) 4" 4" 4" 4" 4" 4"
Condenser
Type BPHE BPHE BPHE BPHE BPHE BPHE Condenser model B B A A A A Condenser Water Content volume (l) 49 49 69 69 69 69
Cond. Water Flow rate - Minimum (4) 1.9 1.9 2.7 2.7 2.7 2.7 Cond. Water Flow rate - Maximum (4) 39 39 39 39 39 39 Nominal water connection size (Grooved coupling) (l) 4” 4” 4” 4” 4” 4”
Dimensions
Unit Length (mm) 2334 2334 2334 2334 2334 2334 Unit Width (mm) 922 922 922 922 922 922 Unit Height (mm) 1941 1941 1959 1959 1959 1959
Weights
Shipping Weight (5) (kg) 1611 1675 1900 1986 1986 1986 Operating Weight (5) (kg) 1690 1771 2018 2127 2127 2127
System data (6)
Nb of refrigerant circuits # 1 1 1 1 1 1 Minimum cooling load % % 25% 25% 25% 25% 25% 25%
Standard unit
R1234ze refrigerant charge (6) (kg) 31 34 42 47 47 47 Oil charge (6) (l) 5 5 7 7 7 7 POE Oil type OIL0066E/OIL0067E
RTSF050 RTSF060 RTSF070 RTSF090 RTSF100 RTSF110
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser water temperature 30 / 35°C - for detailed performances consult
order write up. (2) Under 400V/3/50Hz. (3) Option fuse + disconnect switch. (4) Height reaches 2050 mm with the sound attenuation package option. (5) Additional weight of + 158kg in case of a sound attenuation package option. (6) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
RLC-SVX023A
7
Unit Description
Component location for typical RTSF Unit
16
13
2
5
17
18
15
14
2 = Power cable gland plate
for customer wiring 4 = Suction line 5 = Oil separator 6 = Condenser water outlet 7 = Condenser water inlet
4
5
9
8 = Evaporator water outlet 9 = Evaporator water inlet 13 = External control wiring
cable gland plate for
customer wiring 14 = Compressor 15 = Discharge line 16 = Unit nameplate (on the
side of starter/control
panel) 17 = EXV 18 = Condenser
1 = Control panel 3 = Tracer TD7 interface 4 = Suction line 10 = Auxiliary Oil Cooler (Optional) 11 = Evaporator 12 = Adaptive Frequency Drive
8
6
4
10
11 12
7
3
1
8
RLC-SVX023A
Unit Description
Installation overview and requirements
Contractor responsibilities
A list of the contractor responsibilites typically associated with the installation process is provided in Table 2.
• Locate and maintain the loose parts. Loose parts are located in the control panel.
• Install the unit on a foundation with flat support surfaces, level within 5 mm and of sufficient strength to support concentrated loading. Place the manufacturer-supplied isolation pad assemblies under the unit.
• Install the unit per the instructions outlined in the “Mechanical Installation” section.
• Complete all water piping and electrical connections.
Note: Field piping must be arranged and supported to avoid stress on the equipment. It is strongly recommended that the piping contractor provide at least 1m of clearance between the pre-installation piping and the planned location of the unit. This will allow for proper fit-up upon arrival of the unit at the installation site. All necessary piping adjustments can be made at that time
• Where specified, supply and install valves in the water
piping upstream and downstream of the evaporator and condenser, to isolate the heat exchangers for maintenance and to balance/trim the system.
• Supply and install flow switches or equivalent devices in both the chilled water and condenser water piping. Interlock each switch with the proper pump starter and Tracer UC800, to ensure that the unit can only operate when water flow is established.
• Supply and install taps for thermometers and pressure gauges in the water piping, adjacent to the inlet and outlet connections of both the evaporator and the condenser.
• Where specified, supply and install strainers ahead of all
pumps and automatic modulating valves.
• Supply and install refrigerant pressure relief piping from the pressure relief to the atmosphere.
• Start the unit under supervision of a qualified service technician.
• Where specified, supply and insulate the evaporator
and any other portion of the unit, as required, to prevent sweating under normal operating conditions.
• For unit-mounted starters, cutouts are provided at the top of the panel for line-side wiring.
• Supply and install the wire terminal lugs to the starter.
• Supply and install field wiring to the line-side lugs of the starter.
Table 2 – Installation Responsibility
Requirement
Foundation Meet foundation requirements
Rigging Safety chains
Isolation Isolation pads Other type of isolators
Electrical - Circuit breakers or fusible
Water piping Flow switches (may be eld
Insulation Insulation Insulation
Water piping connection components
Caution on exposure to refrigerant
Trane supplied Trane installed
disconnects (Optional)
- Unit mounted starter
- Wye Delta starter or AFD (Adaptive Frequency Drive)
- Grooved pipe
- Grooved pipe to agged
connection (optional)
Trane supplied Field installed
- Flow switches (may be eld
supplied)
- Harmonic lters (on request
according to customer electrical network and equipment)
supplied)
Customer supplied Customer installed
Clevis connectors Lifting beams
- Circuit breakers or fusible disconnect
- Electrical connections to unit mounted starter (optional)
- Electrical connections to remote mounted starter (optional)
- Wiring sizes per submittal and local regulations
- Terminal lugs
- Ground connections
- BAS wiring (optional)
- Control voltage wiring
- Chilled water pump contactor and wiring including interlock
- Option relays and wiring
- Taps for thermometers and gauges
- Thermometers
- Strainers (as required)
- Water ow pressure gauges
- Isolation and balancing valves in water piping
- Vents and drain on waterbox valves
- Pressure relief valves for water side
Respect recommendation of IOM addendum
RLC-SVX023A
9
Installation - Mechanical
Storage
If the chiller is to be stored more than one month prior to installation, observe the following precautions:
• Do not remove the protective coverings from the electrical panel.
• Store the chiller in a dry, vibration-free, secure area.
• At least every three months, attach a gauge and
manually check the pressure in the refrigerant circuit. If the refrigerant pressure is below 3.4 bar at 21°C (2 bar at 10 °C), call a qualified service organization and the appropriate Trane sales office.
NOTE: Pressure will be approximately 1.0 bar if shipped with the optional nitrogen charge.
Noise Considerations
• Refer to Engineering Bulletin for sound consideration
applications.
• Locate the unit away from sound-sensitive areas.
• Install the isolation pads under the unit. Refer to “Unit
Isolation.”
• Install rubber vibration isolators in all water piping.
• Use flexible electrical conduit for final connection to the
Tracer UC800.
• Seal all wall penetrations.
NOTE: Consult an acoustical engineer for critical applications.
Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the chiller operating weight (including completed piping and full operating charges of refrigerant, oil and water).
Refer to General information for unit operating weights.
Once in place, level the chiller within 5 mm over its length and width.
The manufacturer is not responsible for equipment problems resulting from an improperly designed or constructed foundation.
Clearances
Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all service points. A minimum of 1 m is recommended for compressor service and to provide sufficient clearance for the opening of control panel doors. In all cases, local codes will take precedence over these recommendations. If the room configuration requires a variance to the clearance dimensions, contact your sales representative.
NOTE: Required vertical clearance above the unit is at least 1 m. There should be no piping or conduit located over the compressor motor.
NOTE: Maximum clearances are given. Depending on the unit configuration, some units may require less clearance than others in the same category.
Ventilation
The unit produces heat even though the compressor is cooled by the refrigerant. Make provisions to remove heat generated by unit operation from the equipment room. Ventilation must be adequate to maintain an ambient temperature lower than 40°C. Vent the pressure relief valves in accordance with all local and national codes. Refer to “Pressure Relief Valves”. Make provisions in the equipment room to keep the chiller from being exposed to ambient temperatures below 10°C.
Water Drainage
Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Condenser and evaporator water pipes are provided with drain connections. Refer to “Water Piping.” All local and national codes apply.
Access Restrictions
Refer to the unit submittals for specific dimensional information (documents supplied in document package coming with unit).
Vibration Eliminators
• Provide rubber boot type isolators for all water piping
at the unit.
• Provide flexible conduit for electrical connections to the
unit.
• Isolate all pipe hangers and be sure they are not
supported by main structure beams that could introduce vibration into occupied spaces.
• Make sure that the piping does not put additional stress
on the unit.
NOTE: Do not use metal braided type eliminators on the water piping. Metal braided eliminators are not effective at the frequencies at which the unit will operate.
10
RLC-SVX023A
Handling Procedure
INSTRUCTIONS DE LEVAGE ET DE MANUTENTION IL EST RECOMMANDE D'UTILISER LES ORGANES DE LEVAGE ET DE MANUTENTION MONTRES PAR LE SCHEMA ET DE SUIVRE LES INSTRUCTIONS SUIVANTES :
1 -ATTENTION : CETTE UNITE DOIT ETRE LEVEE ET MANUTENTIONNEE AVEC PRECAUTIONS. EVITER LES A-COUPS LORS DU LEVAGE ET DE LA MANUTENTION.
ANWEISUNGEN FUER DEN TRANSPORT MIT HEBEZEUG ES WIRD EMPFOHLEN, DIE MASCHINE ENTSPRECHEND DER ZEICHNUNG MIT EINEM KRAN ANZUHEBEN UND DIE FOLGENDEN ANWEISUNGEN ZU BEACHTEN :
1 -BEIM ANHEBEN VORSICHTIG VORGEHEN, STOESSE UND ERSCHUETTERUNGEN UNBEDINGT VERMEIDEN.
SPECIAL LIFTING AND MOVING INSTRUCTIONS IT IS RECOMMENDED TO USE THE SPECIAL BUILT-IN RIGGING POINTS SHOWN IN THE DIAGRAM AND TO FOLLOW THE FOLLOWING INSTRUCTIONS :
1 -CAUTION : THIS UNIT MUST BE LIFTED AND HANDLED WITH CARE. AVOID SHOCKS WHILE HANDLING.
ISTRUZIONI PER IL SOLLEVAMENTO E LA MOVIMENTAZIONE DELL'UNITA SI RACCOMANDA DI SEGUIRE LE ISTRUZIONI QUI RIPORTATE PER IL SOLLEVAMENTO E LA MOVIMENTAZIONE DELL'UNITA :
1 -ATTENZIONE : EFFETTUARE IL SOLLEVAMENTO DELL'UNITA CON LA MASSIMA CURA EVITARE CARICHI ECCESSIVI, SOLLEVARE LENTAMENTE E UNIFORMEMENTE.
HIJS EN TRANSPORT INSTRUCTIES DE TOE TE PASSEN HIJSMETHODE IS ALS VOLGT VOORGESCHREVEN :
1 -WAARSCHUWING : DEZE MACHINE VOORZICHTIG VERPLAATSEN. VOORKOM SCHOKKEN EN STOTEN BIJ HET HIJSEN.
INSTRUCCIONES DE TRANSPORTE Y DESCARGA SE RECOMIENDA SEGUIR LAS INSTRUCCIONES SIGUIENTES PARA LA CARGA Y DESCARGA DE LA UNIDAD :
1 -ATENCION : ESTA UNIDAD DEBE SER DESCARGADA CON EL MAYOR CUIDADO PARA EVITAR CHOQUES. DESCARGAR DESPACIO Y CUIDADOSAMENTE.
B
RTSF
050-060-070-090-100-110
57384397
Sheet 1 of 2
Date: Revision: B
19-DEC-2018
INSTRUCTIONS DE LEVAGE ET DE MANUTENTION IL EST RECOMMANDE D'UTILISER LES ORGANES DE LEVAGE ET DE MANUTENTION MONTRES PAR LE SCHEMA ET DE SUIVRE LES INSTRUCTIONS SUIVANTES :
1 -ATTENTION : CETTE UNITE DOIT ETRE LEVEE ET MANUTENTIONNEE AVEC PRECAUTIONS. EVITER LES A-COUPS LORS DU LEVAGE ET DE LA MANUTENTION.
ANWEISUNGEN FUER DEN TRANSPORT MIT HEBEZEUG ES WIRD EMPFOHLEN, DIE MASCHINE ENTSPRECHEND DER ZEICHNUNG MIT EINEM KRAN ANZUHEBEN UND DIE FOLGENDEN ANWEISUNGEN ZU BEACHTEN :
1 -BEIM ANHEBEN VORSICHTIG VORGEHEN, STOESSE UND ERSCHUETTERUNGEN UNBEDINGT VERMEIDEN.
SPECIAL LIFTING AND MOVING INSTRUCTIONS IT IS RECOMMENDED TO USE THE SPECIAL BUILT-IN RIGGING POINTS SHOWN IN THE DIAGRAM AND TO FOLLOW THE FOLLOWING INSTRUCTIONS :
1 -CAUTION : THIS UNIT MUST BE LIFTED AND HANDLED WITH CARE. AVOID SHOCKS WHILE HANDLING.
ISTRUZIONI PER IL SOLLEVAMENTO E LA MOVIMENTAZIONE DELL'UNITA SI RACCOMANDA DI SEGUIRE LE ISTRUZIONI QUI RIPORTATE PER IL SOLLEVAMENTO E LA MOVIMENTAZIONE DELL'UNITA :
RELEASED 21/Dec/2018 09:34:29 GMT
Follow instructions given in the lifting and handling document supplied with documentation package shipped with the unit.
Figure 1 – Handling
YES NO
Installation - Mechanical
Isolation Pads
1. The elastomeric pads shipped (as standard) are adequate for most installations. For additional details on isolation practices, consult an acoustical engineer for sensitive installations. It is possible that some vibration frequencies can be transmitted into the foundations. This depends on the building structure. It is recommended for these situations to use neoprene isolators instead of elastomeric pads. Drawings to locate isolation pads are supplied with unit document package.
2. During final positioning of the unit, place the isolation
pads as indicated in submittal drawings. Level the unit.
Drawings to locate isolation pads are included with in document package sent with the unit.
RLC-SVX023A
930
1042
11
Installation - Mechanical
Unit Leveling
NOTE: The electrical panel side of the unit is designated
as the “front” of the unit.
1. Check unit level end-to-end by placing a level on the chiller structure (compressor frame for example).
2. Adjust to within 5 mm of level front-to-back.
Water Piping
Piping Connections
To prevent equipment damage, bypass the unit if using an acidic flushing agent.
Make water piping connections to the evaporator and condenser. Isolate and support piping to prevent stress on the unit. Construct piping according to local and national codes. Insulate and flush piping before connecting to unit.
The chilled water connections to the evaporator are to be grooved-pipe type connections. Do not attempt to weld these connections. Refer to submittal for dimension of tube stub for grooved connection. Refer to submittal for dimension of tube stub for grooved connection.
To prevent damage to chilled water components, do not allow evaporator pressure (maximum working pressure) to exceed 10 bar.
Reversing Water Connections is prohibited
It is critical to keep the factory layout for water connections. Therefore reversing water connections may lead to functional disorder.
NOTE: Dimensions of tube stub for grooved connection are included in submittal drawings.
Vents and Drains
Install pipe plugs in evaporator and condenser water connections drain and vent connections before filling the water systems. To drain water, remove vent and drain plugs, install a NPT connector in the drain connection and connect a hose to it.
Water Treatment
WARNING: Do not use untreated or improperly treated water. Use of untreated or improperly treated water may result in equipment damage.
The following disclamatory label is provided on each unit:
The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is advisable. The warranty specifically excludes liability for corrosion, erosion or deterioration of the manufacturer’s equipment. The manufacturer assumes no responsibilities for the results of the use of untreated or improperly treated water, or saline or brackish water.
12
RLC-SVX023A
Installation - Mechanical
Evaporator Piping Components
Note: Make sure all piping components are between the shutoff valves, so that isolation can be accomplished on both the condenser and the evaporator. “Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below.
Entering Chilled Water Piping
• Air vents (to bleed air from system)
• Water pressure gauges with shutoff valves
• Pipe unions
• Vibration eliminators (rubber boots)
• Shutoff (isolation) valves
• Thermometers
• Clean out tees
• Pipe strainer
Leaving Chilled Water Piping
• Air vents (to bleed air from system)
• Water pressure gauges with shutoff valves
• Pipe unions
• Vibration eliminators (rubber boots)
• Shutoff (isolation) valves
• Thermometers
• Clean out tees
• Balancing valve
• Pressure relief valve
To prevent evaporator damage, do not exceed 10 bar evaporator water pressure for standard units.
To prevent heat exchangers damage, install a strainer in the evaporator water inlet piping.
Condenser Piping Components
“Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below.
Entering Condenser Water Piping
• Air vents (to bleed air from system)
• Water pressure gauges with shutoff valves
• Pipe unions
• Vibration eliminators (rubber boots)
• Shutoff (isolation) valves
• Thermometers
• Clean out tees
• Pipe strainer
• Flow switch
Leaving Condenser Water Piping
• Air vents (to bleed air from system)
• Water pressure gauges with shutoff valves
• Pipe unions
• Vibration eliminators (rubber boots)
• Shutoff (isolation) valve
• Thermometers
• Clean out tees
• Balancing valve
• Pressure relief valve
To prevent condenser damage, do not exceed 10 bar water pressure for standard units.
To prevent heat exchangers damage, install a strainer in condenser water inlet piping.
Water Pressure Gauges and Thermometers
Install field-supplied thermometers and pressure gauges (with manifolds, whenever practical). Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite­end water connections.
RLC-SVX023A
13
Installation - Mechanical
Water Pressure Relief Valves
Install a pressure relief valve in both evaporator and condenser water systems. Failure to do so could result in Heat Exchanger damage.
When shutoff valves are installed on the water circuits, the water temperature can increase and create a high pressure in the water systems. Refer to applicable regulation for relief valve installation guidelines.
Flow Sensing Devices
Use field-provided flow switches or differential pressure switches with pump interlocks to sense system water flow.
To provide chiller protection, install and wire flow switches in series with the water pump interlocks, for both chilled water and condenser water circuits (refer to the “Installation Electrical” section). Specific connections and schematic wiring diagrams are shipped with the unit.
Flow switches must stop or prevent compressor operation if either system water flow drops off drastically. Follow the manufacturer’s recommendations for selection and installation procedures. General guidelines for flow switch installation are outlined below.
• Mount the switch upright, with a minimum of 5 pipe
diameters of straight, horizontal run on each side.
• Do not install close to elbows, orifices or valves.
Note: The arrow on the switch must point in the direction of the water flow. To prevent switch fluttering, remove all air from the water system.
Note: The Tracer UC800 provides a 6-second time delay on the flow switch input before shutting down the unit on a loss-of-flow diagnostic. Contact a qualified service organization if nuisance machine shutdowns persist. Adjust the switch to open when water flow falls below nominal. Refer to the General Data table for minimum flow recommendations. Flow switch contacts are closed on proof of water flow.
Refrigerant Pressure Relief Valve Venting
To prevent injury due to inhalation of refrigerant gas, do not discharge refrigerant anywhere. If multiple chillers are installed, each unit must have separate venting for its relief valves. Consult local regulations for any special relief line requirements.
All relief valve venting is the responsibility of the installing contractor. All RTSF units use condenser pressure relief valves that must be collected. Relief valve connection sizes and locations are shown in the unit submittals. Refer to national regulations for relief valve vent line sizing information.
Do not exceed vent piping code specifications. Failure to heed specifications could result in capacity reduction, unit damage and/or relief valve damage.
Note: Once opened, relief valves tend to leak.
14
RLC-SVX023A
0.1
1
10
100
1000
1.0 10.0 100.0
Pressure Drop (kPa)
WaterFlow (L/s)
RTSF condensers Pressure drop on waterside
A
B
C
D
1
10
100
1000
1.0 10.0 100.0
Pressure Drop (kPa)
WaterFlow (L/s)
RTSF evaporators Pressure drop on waterside
A
B
C
D
Installation - Mechanical
RTSF condensers Pressure drop on waterside
RTSF evaporators Pressure drop on waterside
RLC-SVX023A
15
Loading...
+ 33 hidden pages