Trane CenTraVac CDHG, CenTraVac CDHF, CenTraVac CVHF, CenTraVac CVHE, CenTraVac CVHG Assembly/disassembly Manual

Water-Cooled CenTraVacChillers
50 Hz Models: CDHG, CVHE, CVHG 60 Hz Models: CDHF, CVHE, CVHF
X39640718110
SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
January 2019
CCVVHHEE--SSVVNN0044MM--EENN
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified according to local rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell.. IImmpprrooppeerrllyy iinnssttaalllleedd aanndd ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss.. TToo aavvooiidd tthheessee hhaazzaarrddss,, yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn NNEECC aanndd yyoouurr llooccaall// ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess..
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy.. TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,, ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh ccllootthhiinngg)).. AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee MMaatteerriiaall SSaaffeettyy DDaattaa SShheeeettss ((MMSSDDSS))//SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE..
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee aapppprroopprriiaattee MMSSDDSS//SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss..
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt.. NNEEVVEERR PPEERRFFOORRMM AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG.. EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE..
©2019 Ingersoll Rand
CVHE-SVN04M-EN
IInnttrroodduuccttiioonn
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy..
•• AAllll IInnggeerrssoollll RRaanndd ppeerrssoonnnneell mmuusstt ffoollllooww IInnggeerrssoollll RRaanndd EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy ((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,, lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc.. AAllll ppoolliicciieess ccaann bbee ffoouunndd oonn tthhee BBOOSS ssiittee.. WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess..
•• NNoonn--IInnggeerrssoollll RRaanndd ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss..
Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
Update to Figure 1, p. 10
Update to Figure 2, p. 11
Factory Warranty Information
Compliance with the following is required to preserve the factory warranty:
AAllll UUnniitt IInnssttaallllaattiioonnss
Startup MUST be performed by Trane, or an authorized agent of Trane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification to Trane (or an agent of Trane specifically authorized to perform startup).
AAddddiittiioonnaall RReeqquuiirreemmeennttss ffoorr UUnniittss RReeqquuiirriinngg DDiissaasssseemmbbllyy aanndd RReeaasssseemmbbllyy
When a new chiller is shipped and received from our Trane manufacturing location and, for any reason, it requires disassembly or partial disassembly, and reassembly— which could include but is not limited to the evaporator, condenser, control panel, compressor/ motor, economizer, purge, factory-mounted starter or any other components originally attached to the fully assembled unit— compliance with the following is required to preserve the factory warranty:
Trane, or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products, will perform or have direct on-site technical supervision of the disassembly and reassembly work.
The installing contractor must notify Trane—or an agent of Trane specifically authorized to perform startup and warranty of Trane® products—two weeks in advance of the scheduled disassembly work to coordinate the disassembly and reassembly work.
Start-up must be performed by Trane or an agent of Trane specifically authorized to perform startup and warranty of Trane® products.
Trane, or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products, will provide qualified personnel and standard hand tools to perform the disassembly and reassembly work at a location specified by the contractor. The contractor shall provide the rigging equipment such as chain falls, gantries, cranes, forklifts, etc. necessary for the disassembly and reassembly work and the required qualified personnel to operate the necessary rigging equipment.
CVHE-SVN04M-EN
3

General Information

WWAARRNNIINNGG
RReeffrriiggeerraanntt MMaayy BBee UUnnddeerr PPoossiittiivvee PPrreessssuurree!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn aann eexxpplloossiioonn wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr eeqquuiippmmeenntt ddaammaaggee.. SSyysstteemm ccoonnttaaiinnss rreeffrriiggeerraanntt aanndd mmaayy bbee uunnddeerr ppoossiittiivvee pprreessssuurree;; ssyysstteemm mmaayy aallssoo ccoonnttaaiinn ooiill.. RReeccoovveerr rreeffrriiggeerraanntt ttoo rreelliieevvee pprreessssuurree bbeeffoorree ooppeenniinngg tthhee ssyysstteemm.. SSeeee uunniitt nnaammeeppllaattee ffoorr rreeffrriiggeerraanntt ttyyppee.. DDoo nnoott uussee nnoonn--aapppprroovveedd rreeffrriiggeerraannttss,, rreeffrriiggeerraanntt ssuubbssttiittuutteess,, oorr nnoonn-­aapppprroovveedd rreeffrriiggeerraanntt aaddddiittiivveess..
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
MMiixxiinngg rreeffrriiggeerraannttss oorr ooiillss ccoouulldd rreessuulltt iinn eeqquuiippmmeenntt ddaammaaggee iinncclluuddiinngg bbeeaarriinngg ddaammaaggee,, iinnttrroodduuccttiioonn ooff aacciiddss iinnttoo tthhee cchhiilllleerr,, oorr ccoonnttiinnuuoouuss ppuurrggee ppuummpp--oouutt iinn hhiigghh--hheeaadd//hhiigghh aammbbiieenntt aapppplliiccaattiioonnss.. CCeennTTrraaVVaacc cchhiilllleerrss aarree mmaannuuffaaccttuurreedd wwiitthh ddiiffffeerreenntt rreeffrriiggeerraanntt//ooiill ssyysstteemmss:: 11)) cchhiilllleerrss uussiinngg RR--112233 rreeffrriiggeerraanntt aanndd OOIILL0000002222 ccoommpprreessssoorr ooiill,, aanndd 22)) cchhiilllleerrss uussiinngg RR--551144AA rreeffrriiggeerraanntt aanndd OOIILL0000333344//OOIILL0000333355 ccoommpprreessssoorr ooiill.. VVeerriiffyy pprrooppeerr rreeffrriiggeerraanntt aanndd ooiill ffoorr yyoouurr cchhiilllleerr aanndd ddoo NNOOTT mmiixx rreeffrriiggeerraannttss oorr ooiillss!!
This Installation, Operation, and Maintenance manual applies to CenTraVacchillers with two different refrigerant and oil systems:
R-123 and OIL00022
R-514A and OIL00334/OIL00335
IImmppoorrttaanntt:: Verify proper refrigerant and oil for your
chiller before proceeding!
The information and procedures in this document are to facilitate unit disassembly for clearance and access reasons during the installation process.
The understanding is that the chiller has what is referred to as the “compressor doweling option” or “separable shell option” (which includes compressor doweling). Compressor doweling sets up the compressor for removal. The separable shell option includes a bolt together design between the evaporator and condenser and allows the shells to be separated in the field.
IImmppoorrttaanntt:: These procedures do NOT apply to units
that have been installed and electrical supply wiring has been completed.

Contractor Responsibilities

WWAARRNNIINNGG
HHeeaavvyy OObbjjeeccttss!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ccoommppoonneenntt ddrrooppppiinngg wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy,, aanndd eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy ddaammaaggee.. LLooaaddss ccaann sshhiifftt aanndd bbeeccoommee ooffff--cceenntteerr dduurriinngg sshhiippppiinngg.. EEnnssuurree tthhaatt ccoommppoonneennttss aarree cceenntteerreedd bbeeffoorree lliiffttiinngg aanndd aallwwaayyss tteesstt lliifftt eeaacchh ccoommppoonneenntt ttoo vveerriiffyy cceenntteerr ooff ggrraavviittyy uussiinngg lliiffttiinngg eeqquuiippmmeenntt rraatteedd ffoorr tthhee ttaasskk.. OOnnllyy eexxppeerriieenncceedd rriiggggeerrss sshhoouulldd ppeerrffoorrmm uunniitt ddiissaasssseemmbbllyy//rreeaasssseemmbbllyy..
Handle/lift and rig equipment
Protect all internal components from exposure to elements, which could contaminate or corrode chiller components
Chiller reassembly
Replace all gaskets with new gaskets or O-rings and sealing compound; the contractor should assist a qualified Trane Technician with this responsibility
NNOOTTIICCEE
CCoommpprreessssoorr DDaammaaggee!!
PPOOEE ooiill iiss hhyyggrroossccooppiicc –– iitt aabbssoorrbbss wwaatteerr ddiirreeccttllyy ffrroomm tthhee aaiirr.. TThhiiss wwaatteerr iiss nneeaarrllyy iimmppoossssiibbllee ttoo rreemmoovvee ffrroomm tthhee ccoommpprreessssoorr ooiill aanndd ccaann rreessuulltt iinn ccoommpprreessssoorr ffaaiilluurreess.. TToo pprreevveenntt PPOOEE ooiill ffrroomm aabbssoorrbbiinngg wwaatteerr,, tthhee ssyysstteemm sshhoouulldd nnoott rreemmaaiinn ooppeenn ffoorr lloonnggeerr tthhaann nneecceessssaarryy.. WWhheenn ooppeenn,, ddrryy nniittrrooggeenn sshhoouulldd ffllooww tthhrroouugghh tthhee ppiippiinngg.. OOnnllyy nneeww ooiill ccoonnttaaiinneerrss sshhoouulldd bbee uusseedd ffoorr sseerrvviiccee aanndd mmaaiinntteennaannccee.. AAllwwaayyss uussee tthhee ssmmaalllleesstt ccoonnttaaiinneerr ssiizzee rreeqquuiirreedd ffoorr tthhee jjoobb rreeqquuiirreemmeennttss.. AAllwwaayyss lleeaavvee tthhee ooiill ccoonnttaaiinneerr ttiigghhttllyy sseeaalleedd uunnttiill ttiimmee ooff uussee.. DDoo nnoott rreeuussee ooiill tthhaatt hhaass bbeeeenn ooppeenneedd..
Change the compressor oil; the contractor should assist a qualified Trane Technician with this responsibility
Evacuate the chiller under 1000 microns; the contractor should assist a qualified Trane Technician with this responsibility
Recharge the chiller with dry nitrogen to 5 psig; the contractor should assist a qualified Trane Technician with this responsibility
Replace and/or repair insulation
Reconnect electrical connections
Spot paint the chiller if necessary
4
CVHE-SVN04M-EN
GGeenneerraall IInnffoorrmmaattiioonn

Metric Conversions

English Metric
ft·lb x 1.3558 Newton·meter
lb x 0.4536 kg
in x 25.4000 mm

Device Descriptions

Device Description
CPTF
FRCL Optional free cooling
HGBP Optional hot gas bypass
INDP Optional industrial control package
SMP Optional supplemental motor protection
UAFD Unit-mounted Adaptive Frequencydrive
UATR
UPIR
UXL
USID Unit-mounted low-voltage solid state starter
USTR Unit-mounted low-voltage wye-delta starter
Optional control power transformer (INDP units only)
(INDP units only)
Unit-mounted medium-voltage auto transformer Unit-mounted medium-voltage primary reactor Unit-mounted medium-voltage across-the­line starter
CVHE-SVN04M-EN
5

Dimensions and Weights

Dimensions

Single Compressor Chillers: Models CVHE, CVHF, and CVHG

The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
Table 1. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers
Model NTON Shell Size
190–270 032 320 66.7 53.1
230–320 050 320 75.4 53.6
CVHE
CVHF
300–420 050 500 73.7 52.7
360–500 080 500 93.5 77.1 101.3 42.0 87.8 51.7 58.6 93.8 45.5 62.2 63.5 44.3
300–450
350–570
620–870
650–910
1070–1300
1470–1720
050/080
050 480 75.4 52.7
050/080
080 480 93.5 75.7 101.3 42.0 78.3 51.3 59.1 93.8 45.5 62.2 63.5 44.3
080 870 93.5 75.0 101.3 42.0 81.2 59.7 73.2 93.8 45.5 63.9 63.5 44.3
080/142
142 870 98.1 80.4 121.9
080 910
080/142
142 910 98.1 83.0 111.0
080/142
142 1300 120.9 80.4 121.9
142/210
210 1300 106.5 94.5 116.0
250 1300 120.9 98.6 121.9
142/210
210 1720 106.5 92.8 116.0
250 1720 120.9 96.9 121.9
Comp
Size
500 84.1 66.0 90.4 42.0 87.8 51.7 58.6 82.7 46.0 54.9 49.32 41.3
480 84.1 64.6 90.4 42.0 78.3 51.3 59.1 82.7 46.0 54.9 49.32 41.3
870 101.3 79.4 107.5
910 101.3 79.4 107.5
1300 102.2 80.5 107.5
1300 106.0 88.2 109.7
1720 106.0 86.5 109.7
A B C D E F G H J K L M
93.5
N/A N/A
N/A N/A
N/A N/A
N/A N/A
(b)
76.5 101.3 42.0 81.2 54.6 66.7 93.8 45.5 63.9 63.5 44.3
84.9 49.2 49.7 70.8 45.5 53.1 37.9 34.5
73.4 49.2 52.4 77.1 45.5 52.5 43.9 38.7
87.8 51.7 54.4 77.1 45.5 52.5 42.3 38.7
78.3 51.3 54.4 77.1 45.5 52.5 43.9 38.7
(a)
81.3 59.7 73.2 102.0 45.5 67.9 63.59 46.0
(a)
81.2 59.7 73.2 110.9 46.9 65.4 62.5 50.5
(a)
81.3 54.6 66.7 102.0 45.5 64.6 63.59 46.0
(a)
81.2 54.6 66.7 105.5 46.9 69.8 62.5 46.0
(a)
80.5 59.1 72.4 102.0 45.5 65.7 63.59 46.0
(a)
80.2 54.6 72.6 110.9 46.9 64.2 76.5 50.5
(a)
80.5 59.1 72.4 105.4 46.9 73.1 62.5 52.4
(a)
80.2 59.7 72.6 116.4 50.5 84.5 68.2 50.5
(a)
80.2 59.7 72.6 116.4 54.5 84.5 76.7 56.6
(a)
93.8 63.1 75.6 105.4 46.9 73.1 62.5 52.4
(a)
91.2 63.1 75.6 110.9 50.5 78.2 68.2 50.5
(a)
91.2 63.1 75.6 116.4 54.5 84.4 76.7 56.6
6
CVHE-SVN04M-EN
Table 1. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers (continued)
Model NTON Shell Size
050 565 75.4 52.6
480–565
080 565 93.5 74.6 101.3 42.0 94.3 53.0 62.8 93.8 45.5 62.2 63.5 44.3
050/080
080 780 93.5 76.5 101.3 42.0 94.0 54.3 66.6 93.8 45.5 63.9 63.5 44.3
670–780
080/142
142 780 98.1 83.0 111.0
CVHG
920–1067
080/142
142 920 98.1 84.0 111.0
142/210
210 920 106.5 96.0 116.0
080/142
1100
142 1100 98.8 80.4 107.4
142/210
210 1100 106.5 94.5 116.0
Note: All dimensions are in inches (±0.5 inch).
(a)
Does not extend beyond the condenser tube unit.
(b)
Add 1 in. to overall width for compressor.
(c)
Add 0.4 in. to overall width for compressor.
Comp
Size
A B C D E F G H J K L M
N/A N/A
565
63.4 90.2 42.0 94.5 52.9 62.8 82.7 46.0 57.6 49.32 40.0
(c)
82.6
780 101.3 79.4 107.5
920 102.2 82.0 107.5
920 106.0 89.7 109.7
1100 102.2 80.5 107.5
1100 106.0 88.2 109.7
93.8 53.0 57.5 77.1 45.5 52.5 43.9 38.7
(a)
91.9 54.3 66.6 102.0 45.5 66.8 63.59 46.0
(a)
94.0 54.3 66.6 105.5 46.9 69.8 62.5 46.0
(a)
90.9 54.6 68.7 102.0 45.5 64.3 63.59 46.0
(a)
93.2 54.3 68.0 105.5 46.9 69.8 62.5 46.0
(a)
93.3 54.6 68.7 105.4 46.9 76.2 62.5 52.4
(a)
93.2 54.3 68.0 110.9 50.5 81.5 68.2 50.5
(a)
93.2 59.1 72.4 102.0 45.5 65.7 63.59 46.0
(a)
93.2 59.7 71.8 101.9 46.9 62.0 62.3 46.0
(a)
93.2 59.1 72.4 105.4 46.9 76.2 62.5 52.4
(a)
93.2 59.7 72.6 110.9 50.5 78.2 68.2 50.5
DDiimmeennssiioonnss aanndd WWeeiigghhttss
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
CVHE-SVN04M-EN
7
DDiimmeennssiioonnss aanndd WWeeiigghhttss
Table 2. Dimensional data for CVHE, CVHF, and CVHG CenTraVac chillers
Exp
Model NTON Shell Size
190–270 032 320 60.1 71.4 81.9 29.7 17.0 26.5 68.6 93.9 47.0 47.0
230–320 050 320 64.6 71.4 81.9 29.7 17.0 23.4 80.5 98.4 63.4 54.9
CVHE
CVHF
CVHG
300–420 050 500 62.8 71.4 81.9 29.8 17.3 26.5 80.5 98.7 63.4 54.9
360–500 080 500 79.0 71.4 81.9 29.8 17.3 26.5 97.1 114.9 80.8 80.8 66.3
300–450
350–570
620–870
650–910
1070–1300
1470–1720
480–565
670–780
920–1067
1100
Note: All dimensions are in inches (±0.5 inch).
050/080
050 480 64.3 71.4 81.9 29.0 16.3 26.5 80.5 100.0 60.7 54.9
050/080
080 480 79.0 71.4 81.9 29.0 16.3 26.5 97.1 114.9 75.0 75.0 66.3
080 870 75.7 71.4 81.9 30.5 17.8 29.0 97.1 117.1 82.4 82.4 63.9
080/142
142 870 93.8 72.8 83.3 30.5 17.8 29.0 117.4 121.5 82.4 82.4 72.7
080 910 75.7 71.4 81.9 30.5 17.8 29.0 97.1 114.9 82.4 82.4 63.9
080/142
142 910 82.1 72.8 83.3 30.5 17.8 29.0 115.4 121.3 84.4 84.4 72.7
080/142
142 1300 93.8 72.8 83.3
142/210
210 1300 93.8 76.4 86.9
250 1300 97.9 80.4 90.9
142/210
210 1720 92.6 76.4 86.9
250 1720 96.8 80.4 90.9
050 565 66.4 71.4 81.9 32.4 19.9 26.5 80.5 103.0 63.4 54.9
080 565 68.4 71.8 82.3 32.4 19.9 29.0 91.4 104.7
050/080
080 780 75.7 71.4 81.9 33.5 21.1 32.8 98.1 114.7 82.4 82.4
080/142
142 780 82.1 72.8 83.3 27.8 17.8 32.8 115.4 121.2 84.4 84.4
080/142
142 920 82.1 72.8 83.3 28.0 18.0 36.8 115.4 121.2 84.4 84.4
142/210
210 920 93.8 76.4 86.9 33.7 21.3 36.8 124.7 132.8 92.9 92.9
080/142
142 1100 80.1 72.8 83.3 28.0 18.0 36.8 117.4 121.5 78.1 78.1 72.7
142/210
210 1100 93.8 76.4 86.9 33.7 21.3 36.8 124.7 135.2 87.2 87.2 82.4
Comp
Size
500 68.1 71.8 82.3 29.0 16.3 26.5 90.1 103.8
480 68.1 71.8 82.3 29.0 16.3 26.5 90.1 103.7
870 79.0 71.3 81.8
910 79.0 71.3 81.8
1300 80.5 71.3 81.8
1300 87.7 72.8 83.3
1720 86.5 72.8 83.3
565 79.2 71.4 81.9 33.6 21.2 29.0 98.1 115.8 81.7 81.7
780 79.0 71.3 81.8
920 80.5 71.3 81.8
920 87.7 72.8 83.3
1100 80.5 71.3 81.8
1100 87.7 72.8 83.3
Std
N
P W
R S T U V
N/A
18.5 29.0 120.9 121.6
N/A
18.5 29.0 120.9 117.8
N/A
18.6 36.8 121.8 121.6
N/A
21.1 36.8 117.4 121.5 78.1 78.1 72.7
N/A
21.1 36.8 126.9 129.0
N/A
21.1 36.8 124.7 135.2 87.2 87.2 82.4
N/A
18.6 36.8 137.2 139.4
N/A
25.8 36.8 126.9 130.9
N/A
25.8 33.3 124.7 137.2 92.9 92.9 76.4
N/A
23.3 33.3 137.2 141.4
N/A
18.5 32.8 120.9 117.6
N/A
18.6 36.8 121.8 119.4
N/A
21.3 36.8 126.9 126.7
N/A
18.6 36.8 121.8 121.6
N/A
21.3 36.8 126.9 129.0
Short
Long
N/A N/A N/A
N/A N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
X
N/A
N/A
N/A
N/A
72.7
72.7
72.7
72.7
82.7
72.7
82.7
N/A
N/A
N/A
72.7
N/A
72.7
N/A
72.7
N/A
72.7
72.7
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
8
CVHE-SVN04M-EN
Table 3. Dimensional data for CVHE, CVHF and CVHG CenTraVac chillers
Model NTON Shell Size
Comp
Size
190–270 032 320 79.8
230–320 050 320 94.1
CVHE
300–420 050 500 92.5
360–500 080 500
300–450
050/080
500
050 480 92.7
350–570
050/080
480
080 480
080 870
620–870
080/142
870
142 870
080 910
CVHF
650–910
080/142
142 910
080/142
910
1300
142 1300
1070–1300
142/210
1300
210 1300
250 1300 140.7
1470–1720
142/210
210 1720
1720
250 1720 140.7
050 565 93.3
480–565
080 565
050/080
565
080 780
670–780
080/142
780
142 780
CVHG
920–1067
080/142
142 920
142/210
920
920
210 920
1100
080/142
142 1100
142/210
1100
1100
210 1100
Notes:
1. Refer to Table 5, p. 13.
2. All dimensions are in inches (±0.5 inch).
(a)
When indicated, see Note 1 (above).
(b)
Does not extend beyond the main unit control panel.
UATR
USID
UPIR
USTR
UXL
Y1 Y2 Y1 Y2 AD Y1 Y2 AD
N/A
N/A
N/A
(a) (a) (a) (a)
(a) (a) (a) (a)
N/A
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(b)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a)
N/A
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
(a) (a) (a) (a)
USID USTR
49.1
57.5
55.9
56.1
80.2
80.2
56.6
UATR UPIR
UXL
N/A
N/A
N/A
405–608A 900–1210A
94.9 64.2
101.2 64.6
101.2 64.6
110.6 77.0
111.5 70.63
N/A
101.2 64.6
111.5 70.63
110.6 77.0
125.8 92.2 7.0 133.3 99.8 4.8
140.0 81.75
139.9 77.5
119.3 85.7
132.7 75.33
130.4 77.5
140.0 81.75
139.9 77.5
147.9 83.6 3.5 154.9 90.6 5.6
N/A N/A N/A
(a)
N/A N/A N/A
N/A N/A N/A
N/A N/A N/A
(a)
N/A N/A N/A
N/A N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
DDiimmeennssiioonnss aanndd WWeeiigghhttss
AFDE UAFD
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A N/A N/A N/A
N/A
147.0 88.8 5.8
N/A
144.0 91.0 4.6
N/A
126.8 93.3 4.8
N/A
146.2 88.8 5.8
N/A
144.0 91.0 4.6
N/A
147.0 88.8 6.3
N/A
146.0 91.0 4.6
152.4 95.9 3.9
160.0 99.5 3.1
155.0 90.7 5.6
152.4 95.9 3.9
160.0 99.5 3.1
See Table 1, p. 6 through for dimensional data regarding the following figure.
CVHE-SVN04M-EN
9
H
V
G
Y1
Y1 Y3
AB
U
1.6 405–608A UAFD
1.0 900–1210A UAFD
2.5 318A & 530–636A UAFD
Y1
AD
1.00
USID, USTR, OR UACD
4
PURGE
CVHE
320
FRCL
2
UATR, UPIR, UXL OR SMP
COMPRESSOR MAX WIDTH
ECONOMIZER
CONDENSER
COMPRESSOR
MOTOR TERMINAL BOX (NOT SHOWN)
PURGE
OPTIONAL USID O
R USTR
SEE UNIT SUBMITTALS FOR DIMENSIONS
OPTIONAL UATR, UPIR, UXL OR SMP SEE UNIT SUBMITTALS FOR DIMENSIONS
MAIN UNIT CONTROL PANEL
OPTIONAL UAFD SEE UNIT SUBMITTALS FOR DIMENSIONS
2
UAFD DISCONNECT SWITCH TO ENCLOSURE DOOR LATCHES
MAIN UN
IT CONTROL PANEL
5
UAFD
EVAPO
RATOR
SEE NOTE 4
P
N
SMALLEST
MOTOR
J
Z
AA
X
1.3
3.0
A
5.7
A
B
K
OIL FILTER
WHEN CONDENSER IS WIDEST
MAIN CONTROL PANEL
OPTIONAL CPTR
CPTR LIFTING LUG
WHEN OIL TANK IS WIDEST
5
MOTOR SUPPORT
EVAPORATOR
CONDENSER
PURGE
5
CVHF-080 UNIT SHOWN (COOLING ONLY) WITH COMPRESSOR AND ECONOMIZER REMOVED
DDiimmeennssiioonnss aanndd WWeeiigghhttss
Figure 1. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers
NNootteess::
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A UAFD are welded on and non-removable. See Table 5, p. 13 for applicable dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer AdaptiView
display mounting arm in stowed position.
10
CVHE-SVN04M-EN
See Table 1, p. 6 through for dimensional data for the
T
MAX OD
LARGEST
MO
TOR
E
F
C
S
R
MOTOR
REMOVAL SPACE
OPTIONAL
UATR OR UPIR
REDUCED VOLTAGE
ENCLOSURE
DIMENSIONS: 40.0 W X 26.2 D X 27.0 H WEIGHT: 1200 LBS MAX
MAIN UNIT
CONTROL PANEL
COMPRESSOR
MOTOR
LARGEST MOTOR
OPTIONAL
CPTR
SHORT SHELL
LONG SHELL
.100
CVHF-080 UNIT SHOWN (COOLING ONLY)
2
2
M
W
M
AC
Y2
AD
Y2
Y2
L
1.6 405-608A UAFD
1.0 900-1210A UAFD
2.5 339A & 539-677A UAFD
OPTIONAL USID OR USTR SEE UNIT SUBMITTALS FOR DIMENSIONS
OIL FILTER
USID, USTR, OR UACD
MAIN UNIT CONTROL PANEL
SUPPORTS FOR OPTIONAL UNIT MOUNTED UATR OR UPIR REDUCED VOLTAGE ENCLOSURE (ENCLOSURE NOT SHOWN)
WHEN CONDENSER IS WIDEST
OPTIONAL FRCL CONNECTION
PURGE
WHEN OIL TANK IS WIDEST
CONDENSER
UAFD
MOTOR SUPPORT
OPTIONAL UATR, UPIR, UXL OR SMP SEE UNIT SUBMITTALS FOR DIMENSIONS
MAIN UNIT CONTROL PANEL
OPTIONAL UAFD SEE UNIT SUBMITTALS FOR DIMENSIONS
UAFD DISCONNECT SWITCH TO ENCLOSURE DOOR LATCHES
UATR, UPIR, UXL OR SMP
EVAPORATOR
5
following figure.
Figure 2. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers (CVHF-080 shown)
DDiimmeennssiioonnss aanndd WWeeiigghhttss
NNootteess::
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A UAFD are welded on and non-removable. See Table 5, p. 13 for application dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer Adaptiview
display mounting arm in stowed position.
CVHE-SVN04M-EN
11