Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and
air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered
equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the
literature and on the tags, stickers, and labels that are attached to the equipment.
January 2019
CCVVHHEE--SSVVNN0044MM--EENN
Introduction
WARNING
CAU
TION
NOTICE
Read this manual thoroughly before operating or
servicing this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper
operation of this machine depend upon the strict
observance of these precautions.
The three types of advisories are defined as follows:
Indicates a potentially hazardous situation
which, if not avoided, could result in death or
serious injury.
Indicates a potentially hazardous situation
which, if not avoided, could result in minor or
moderate injury. It could also be used to alert
against unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are
refrigerants that contain Chlorine, Fluorine and Carbon
(CFCs) and those containing Hydrogen, Chlorine,
Fluorine and Carbon (HCFCs). Not all refrigerants
containing these compounds have the same potential
impact to the environment. Trane advocates the
responsible handling of all refrigerants-including
industry replacements for CFCs and HCFCs such as
saturated or unsaturated HFCs and HCFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices
are important to the environment, our customers, and
the air conditioning industry. All technicians who
handle refrigerants must be certified according to local
rules. For the USA, the Federal Clean Air Act (Section
608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management
of refrigerants. Know the applicable laws and follow
them.
This document and the information in it are the
property of Trane, and may not be used or reproduced
in whole or in part without written permission. Trane
reserves the right to revise this publication at any time,
and to make changes to its content without obligation
to notify any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Revision History
•Update to Figure 1, p. 10
•Update to Figure 2, p. 11
Factory Warranty Information
Compliance with the following is required to preserve
the factory warranty:
AAllll UUnniitt IInnssttaallllaattiioonnss
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY.
Contractor must provide a two-week startup
notification to Trane (or an agent of Trane specifically
authorized to perform startup).
When a new chiller is shipped and received from our
Trane manufacturing location and, for any reason, it
requires disassembly or partial disassembly, and
reassembly— which could include but is not limited to
the evaporator, condenser, control panel, compressor/
motor, economizer, purge, factory-mounted starter or
any other components originally attached to the fully
assembled unit— compliance with the following is
required to preserve the factory warranty:
•Trane, or an agent of Trane specifically authorized
to perform start-up and warranty of Trane®
products, will perform or have direct on-site
technical supervision of the disassembly and
reassembly work.
•The installing contractor must notify Trane—or an
agent of Trane specifically authorized to perform
startup and warranty of Trane® products—two
weeks in advance of the scheduled disassembly
work to coordinate the disassembly and
reassembly work.
•Start-up must be performed by Trane or an agent of
Trane specifically authorized to perform startup and
warranty of Trane® products.
Trane, or an agent of Trane specifically authorized to
perform start-up and warranty of Trane® products, will
provide qualified personnel and standard hand tools to
perform the disassembly and reassembly work at a
location specified by the contractor. The contractor
shall provide the rigging equipment such as chain falls,
gantries, cranes, forklifts, etc. necessary for the
disassembly and reassembly work and the required
qualified personnel to operate the necessary rigging
equipment.
This Installation, Operation, and Maintenance manual
applies to CenTraVac™ chillers with two different
refrigerant and oil systems:
•R-123 and OIL00022
•R-514A and OIL00334/OIL00335
IImmppoorrttaanntt:: Verify proper refrigerant and oil for your
chiller before proceeding!
The information and procedures in this document are
to facilitate unit disassembly for clearance and accessreasons during the installation process.
The understanding is that the chiller has what is
referred to as the “compressor doweling option” or
“separable shell option” (which includes compressor
doweling). Compressor doweling sets up the
compressor for removal. The separable shell option
includes a bolt together design between the evaporator
and condenser and allows the shells to be separated in
the field.
IImmppoorrttaanntt:: These procedures do NOT apply to units
that have been installed and electrical
supply wiring has been completed.
•Protect all internal components from exposure to
elements, which could contaminate or corrode
chiller components
•Chiller reassembly
•Replace all gaskets with new gaskets or O-rings and
sealing compound; the contractor should assist a
qualified Trane Technician with this responsibility
The following table shows dimensional data for Figure
1, p. 10 and Figure 2, p. 11.
8
CVHE-SVN04M-EN
Table 3. Dimensional data for CVHE, CVHF and CVHG CenTraVac chillers
ModelNTONShell Size
Comp
Size
190–27003232079.8
230–32005032094.1
CVHE
300–42005050092.5
360–500080500
300–450
050/080
500
05048092.7
350–570
050/080
480
080480
080870
620–870
080/142
870
142870
080910
CVHF
650–910
080/142
142910
080/142
910
1300
1421300
1070–1300
142/210
1300
2101300
2501300140.7
1470–1720
142/210
2101720
1720
2501720140.7
05056593.3
480–565
080565
050/080
565
080780
670–780
080/142
780
142780
CVHG
920–1067
080/142
142920
142/210
920
920
210920
1100
080/142
1421100
142/210
1100
1100
2101100
Notes:
1. Refer to Table 5, p. 13.
2. All dimensions are in inches (±0.5 inch).
(a)
When indicated, see Note 1 (above).
(b)
Does not extend beyond the main unit control panel.
UATR
USID
UPIR
USTR
UXL
Y1Y2Y1Y2ADY1Y2AD
N/A
N/A
N/A
(a)(a)(a)(a)
(a)(a)(a)(a)
N/A
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(b)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)
N/A
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
(a)(a)(a)(a)
USID
USTR
49.1
57.5
55.9
56.1
80.2
80.2
56.6
UATR
UPIR
UXL
N/A
N/A
N/A
405–608A900–1210A
94.964.2
101.264.6
101.264.6
110.677.0
111.570.63
N/A
101.264.6
111.570.63
110.677.0
125.892.27.0133.399.84.8
140.081.75
139.977.5
119.385.7
132.775.33
130.477.5
140.081.75
139.977.5
147.983.63.5154.990.65.6
N/AN/AN/A
(a)
N/AN/AN/A
N/AN/AN/A
N/AN/AN/A
(a)
N/AN/AN/A
N/AN/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
N/AN/AN/AN/AN/AN/A
DDiimmeennssiioonnss aanndd WWeeiigghhttss
AFDE UAFD
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/AN/AN/AN/A
N/A
147.088.85.8
N/A
144.091.04.6
N/A
126.893.34.8
N/A
146.288.85.8
N/A
144.091.04.6
N/A
147.088.86.3
N/A
146.091.04.6
152.495.93.9
160.099.53.1
155.090.75.6
152.495.93.9
160.099.53.1
See Table 1, p. 6 through for dimensional data
regarding the following figure.
CVHE-SVN04M-EN
9
H
V
G
Y1
Y1
Y3
AB
U
1.6 405–608A UAFD
1.0 900–1210A UAFD
2.5 318A & 530–636A UAFD
Y1
AD
1.00
USID, USTR, OR UACD
4
PURGE
CVHE
320
FRCL
2
UATR, UPIR, UXL OR SMP
COMPRESSOR MAX WIDTH
ECONOMIZER
CONDENSER
COMPRESSOR
MOTOR TERMINAL BOX (NOT SHOWN)
PURGE
OPTIONAL USID O
R USTR
SEE UNIT SUBMITTALS FOR DIMENSIONS
OPTIONAL UATR, UPIR, UXL OR SMP
SEE UNIT SUBMITTALS FOR DIMENSIONS
MAIN UNIT CONTROL PANEL
OPTIONAL UAFD
SEE UNIT SUBMITTALS FOR DIMENSIONS
2
UAFD DISCONNECT SWITCH TO
ENCLOSURE DOOR LATCHES
MAIN UN
IT CONTROL PANEL
5
UAFD
EVAPO
RATOR
SEE NOTE 4
P
N
SMALLEST
MOTOR
J
Z
AA
X
1.3
3.0
A
5.7
A
B
K
OIL FILTER
WHEN CONDENSER IS WIDEST
MAIN CONTROL PANEL
OPTIONAL CPTR
CPTR
LIFTING
LUG
WHEN OIL TANK IS WIDEST
5
MOTOR
SUPPORT
EVAPORATOR
CONDENSER
PURGE
5
CVHF-080 UNIT SHOWN (COOLING ONLY) WITH COMPRESSOR AND ECONOMIZER REMOVED
DDiimmeennssiioonnss aanndd WWeeiigghhttss
Figure 1. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers
NNootteess::
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A
UAFD are welded on and non-removable. See Table 5, p. 13 for applicable dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer AdaptiView
™
display mounting arm in stowed position.
10
CVHE-SVN04M-EN
See Table 1, p. 6 through for dimensional data for the
T
MAX OD
LARGEST
MO
TOR
E
F
C
S
R
MOTOR
REMOVAL SPACE
OPTIONAL
UATR OR UPIR
REDUCED VOLTAGE
ENCLOSURE
DIMENSIONS: 40.0 W X 26.2 D X 27.0 H
WEIGHT: 1200 LBS MAX
MAIN UNIT
CONTROL PANEL
COMPRESSOR
MOTOR
LARGEST MOTOR
OPTIONAL
CPTR
SHORT SHELL
LONG SHELL
.100
CVHF-080 UNIT SHOWN (COOLING ONLY)
2
2
M
W
M
AC
Y2
AD
Y2
Y2
L
1.6 405-608A UAFD
1.0 900-1210A UAFD
2.5 339A & 539-677A UAFD
OPTIONAL USID OR USTR
SEE UNIT SUBMITTALS FOR DIMENSIONS
OIL FILTER
USID, USTR, OR UACD
MAIN UNIT CONTROL PANEL
SUPPORTS FOR OPTIONAL UNIT MOUNTED UATR
OR UPIR REDUCED VOLTAGE ENCLOSURE
(ENCLOSURE NOT SHOWN)
WHEN CONDENSER IS WIDEST
OPTIONAL FRCL CONNECTION
PURGE
WHEN OIL TANK IS WIDEST
CONDENSER
UAFD
MOTOR SUPPORT
OPTIONAL UATR, UPIR, UXL OR SMP
SEE UNIT SUBMITTALS FOR DIMENSIONS
MAIN UNIT CONTROL PANEL
OPTIONAL UAFD
SEE UNIT SUBMITTALS FOR DIMENSIONS
UAFD DISCONNECT SWITCH TO
ENCLOSURE DOOR LATCHES
UATR, UPIR, UXL OR SMP
EVAPORATOR
5
following figure.
Figure 2. Assembly for CVHE, CVHF, and CVHG CenTraVac chillers (CVHF-080 shown)
DDiimmeennssiioonnss aanndd WWeeiigghhttss
NNootteess::
1. All dimensions are in inches (±0.5 inch). See Table 1, p. 6 through Table 5, p. 13 for dimension tables.
2. UAFD brackets and supports shown are bolt-on and removable. Most brackets and supports on 405–608A
UAFD are welded on and non-removable. See Table 5, p. 13 for application dimensions.
3. Applies only to CVHE 190–320 NTON on 032 shells with free-cooling option.
4. Add 1.5 inch for distance to Tracer Adaptiview
™
display mounting arm in stowed position.
CVHE-SVN04M-EN
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.