Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
January 2011CAUJ-SVX01D-EN
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at
appropriate intervals throughout this manual. Warnings are provide to alert installing contractors
to potential hazards that could result in death or personal injury. Cautions are designed to alert
personnel to hazardous situations that could result in personal injury, while notices indicate a
situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance
of these precautions.
Read this manual thoroughly before operating or servicing this unit.
ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this
literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
accidents.
Important
Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally
occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the
identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine
and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all
refrigerants containing these compounds have the same potential impact to the environment.
Trane advocates the responsible handling of all refrigerants-including industry replacements for
CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry. All technicians who handle refrigerants must be
certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these
service procedures. In addition, some states or municipalities may have additional requirements
that must also be adhered to for responsible management of refrigerants. Know the applicable
laws and follow them.
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
The units described in this manual use R-410A refrigerant which operates at higher pressures
than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with these
units. For specific handling concerns with R-410A, please contact your local Trane
representative.
Failure to use R-410A rated service equipment or components could result in equipment
exploding under R-410A high pressures which could result in death, serious injury, or
equipment damage.
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical
hazards.
•Before installing/servicing this unit, technicians MUST put on all Personal Protective
Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
•When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS
sheets and OSHA guidelines for information on allowable personal exposure levels, proper
respiratory protection and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment
(PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash
protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
Trademarks
Trane and the Trane logo are trademarks of Trane in the United States and other countries. All
trademarks referenced in this document are the trademarks of their respective owners.
CAUJ-SVX01D-EN3
Table of Contents
Model Number Descriptions .............................................6
General Information ....................................................7
Unit Inspection .................................................... 7
Dimensions and Weights ...............................................10
Unit Clearances ...................................................10
Unit Dimensions & Weight Information .............................. 10
number contains 14 digits; all 14
digits must be referenced.
80 to 120 Ton
Digit 1 — Unit Type
C = Condenser
Digit 2 — Condenser
A =Air-Cooled
Digit 3 — Airflow
U = Upflow
Digit 4 — Development
Sequence
J= Fourth
Digits 5,6,7 — Nominal Capacity
C80= 80 Tons
D10=100 Tons
D12=120 Tons
Digit 8 — Power Supply
F= 230/60/3
4= 460/60/3
5= 575/60/3
E =200/60/3
Digit 9 — Condenser Circuit
2= Dual Circuit
Digit 10 — Design Sequence
A =First
Digit 11 — Ambient Control
0= Standard
1=0F
Digit 12 — A gency Approval
0= None
2= CSA
3= cULus
Digits 13, 14 — Miscellaneous
J= Corrosion Protected Cond Coil
1= Spring Isolators
Note: The service digit for each model
number contains 14 digits; all 14
digits must be referenced.
6CAUJ-SVX01D-EN
General Information
Unit Inspection
As soon as the unit arrives at the job site
•Verify nameplate data matches data on sales order and bill of lading (including electrical data).
•Verify that the power supply complies with the unit nameplate specifications.
•Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
•Check for material shortages. Refer to the Com
illustration.
Important: If the job site inspection of the unit re
file a claim with the carrier immediately. Specify the type and extent of the
damage on the bill of lading before signing.
•Visually inspect the intern
delivery and before it is stored. Do not walk on the sheet metal base pans.
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the
supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this
recommendation could result in death or serious injury.
Bridging between unit main supports may consist of multiple 2 by 12 boards or sheet metal grating.
•If concealed damage is discovered, notify the carrier's terminal of damage immediately by
one and by mail. Concealed damage must be reported within 15 days.
ph
•Request an immediate joint inspect
remove damaged material from the receiving location. Take photos of the damage, if possible.
The owner must provide reasonable evidence that the damage did not occur after delivery.
•Notify the appropriate Trane office before installing or repairing a damaged unit.
ponent Layout and Ship with Location
veals damage or material shortages,
al components for shipping damage as soon as possible after
WARNI NG
ion of the damage by the carrier and the consignee. Do not
Unit Nameplate
One Mylar unit nameplate is located on the outside upper right corner of the control panel door.
It includes the unit model number, serial number, electrical characteristics, weight, refrigerant
charge, as well as other pertinent unit data. A small metal nameplate with the Model Number, Serial
Number, and Unit Weight is located just above the Mylar nameplate, and a third nameplate is
located on the inside of the control panel door.
When ordering replacement parts or requesting service, be sure to refer to the specific model
number, serial number, and DL number (if applicable) stamped on the unit nameplate.
Unit Description
All air cooled condensing units are designed for outdoor installations with vertical air discharge.
These units may be installed on a flat roof or placed on a concrete slab at ground level.
Before shipment, each unit is leak-tested, evacuated, a Nitrogen holding charge is added, and the
controls are tested for proper operation.
The condenser coils are an all aluminum Microchannel design. Louvered condenser grilles for coil
protection are standard. Direct-drive, vertical discharge condenser fans are provided with built-in
current and overload protection.
For “Ship with” items, see Figure 1, p. 8 for 20-60T units, or Figure 2, p. 8 for 80-120 T units.
If low ambient operation is required, low ambient dampers are available as a field or factory
installed option.
CAUJ-SVX01D-EN7
General Information
The unit control panel contains all required fan cycling controls, compressor interlocks, and a 115
volt control power transformer. Field wiring, electrical schematics and panel connection diagrams
are located inside the control panel access door.
Figure 1. Unit component layout and ‘shipwith’ locations 20 - 60 ton units
Figure 2. Unit component layout and ‘shipwith’ locations 80 - 120 ton units
8 CAUJ-SVX01D-EN
General Information
Table 1. General data
20 Ton25 Ton30 Ton40 Ton50 Ton60 Ton80 Ton100 Ton120 Ton
Model NumberCAUJC-20 CAUJC-25 CAUJ-C30 CAUJ-C40 CAUJ-C50 CAUJ-C60 CAUJ-C80 CAUJ-D10 CAUJ-D12
Minimum Outdoor Air Temperature for Mechanical Cooling
Standard Ambient
Operating Range (F)
Low Ambient Option (F)000000000
(a) Gross Heat Rejection is at a 30 F ITD (Initial Temperature Difference) between condensing temperature and ambient air entering condenser (includes
the effect of subcooling).
(b) At conditions of 95° ambient, condenser is 95 percent full
(c) Condensing units are shipping with nitrogen holding charge only.
(d) Operating charge is for condensing unit only, and does not include charge for low side or interconnecting lines.
Figure 3, p. 11 and Figure 4, p. 11 illustrate the minimum operating and service clearances for either
a single, multiple, or pit application. These clearances are the minimum distances necessary to
assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
Equipment Damage!
Providing less than the recommended clearances may result in condenser coil starvation or
recirculation of hot condenser air.
Locate the unit as close to the applicable system support equipment as possible, to minimize
refrigerant piping lengths.
Unit Dimensions & Weight Information
Overall unit dimensional data for each unit are illustrated in Figure 5, p. 12 to Figure 18, p. 25.
A Center-of-Gravity illustration and the dimensional data are shown in Figure 20, p. 28, Figure 21,
p. 28, and Table 3, p. 26.
Table 2, p. 26 lists the typical unit operating and point loading weights.
Foundation
If the unit is installed at ground level, elevate it above the snow line. Provide concrete footings at
each support location or a slab foundation for support. See Table 2, p. 26 for the unit operating and
point loading weights when constructing the footing foundation.
Anchor the unit to the footings or slab using hold down bolts or isolators. Isolators should be
installed to minimize the transmission of vibrations into the building. See “Unit Isolation,” p. 28 for
isolator installation instructions.
For rooftop applications, ensure the roof is strong enough to support the unit. See Table 2, p. 26
for the unit operating weights.
NOTICE:
WARNI NG
Risk of Roof Collapsing!
Confirm with a structural engineer that the roof structure is strong enough to support the
combined weight of the roofcurb and the unit. Refer to the 'Weights' Table 2, p. 26 section for
typical unit and curb weights. Failure to ensure proper structural roof support could cause the
roof to collapse, which could result in death or serious injury and property damage.
Anchor the unit to the roof with hold-down bolts or isolators. Follow the instructions in section
“Unit Isolation,” p. 28 for proper isolator placement and installation.
Check with a roofing contractor for proper waterproofing procedures.
10 CAUJ-SVX01D-EN
Dimensions and Weights
Figure 3. Typical installation clearances for single, multiple, or pit applications: 20-60 ton units
Figure 4. Typical installation clearances for single, multiple, or pit applications: 80-120 ton units
CAUJ-SVX01D-EN11
Dimensions and Weights
Figure 5. 20-ton air-cooled condenser
FAN GRILLE
43
72 1/2"
21
8"
3/4" X 4 MTG HOLES
1/2" X 4 KO (115V)
1/2" X 2 KO (115V)
1 3/4" KO LOW
VOLTAGE (30V MAX.)
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
A Rigging illustration and Center-of-Gravity dimensional data table is shown in Figure 20, p. 28,
Figure 21, p. 28, and Table 2, p. 26.SeeTable 2, p. 26 for typical unit operating weights table before
proceeding.
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid
dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could
result in unit dropping and possibly crushing operator/technician which could result in death
or serious injury and possible equipment or property-only damage.
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being
lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be
capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be
of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could
cause equipment or property damage. Failure to follow instructions above or properly lift unit
could result in unit dropping and possibly crushing operator/technician which could result in
death or serious injury.
WARNING
WARNING
Note: Use spreader bars as shown in diagram. Refer to installation manual or nameplate for unit
weight. Refer to installation instructions located inside control panel for further rigging
information.
1. Rig the condensing unit as shown in Figure 20, p. 28 and Figure 21, p. 28. Attach adequate
strength lifting slings to all four lifting brackets in the unit base rail. Do not use cables, chains,
or slings except as shown.
2. Install spreader bars, as shown in Figure 20, p. 28 and Figure 21, p. 28, to protect the unit and
to facilitate a uniform lift. The minimum distance between the lifting hook and the top of the
unit should be 7 feet.
3. Test-lift the unit to ensure it is properly rigged and balanced, make any necessary rigging
adjustments.
4. Lift the unit and position it into place.
CAUJ-SVX01D-EN27
Installation
Figure 20. Rigging and center-of-gravity data: 20-60 ton units
Y
Figure 21. Rigging and center-of-gravity data: 80-120 ton units
Y
Unit Isolation
To minimize unit sound and vibration transmission, us one of the following installation methods:
1. Install the unit directly on an isolated (detached) concrete pad or on isolated concrete footings
located at each unit load point.
2. Install the optional spring isolators at each mounting location. See “Spring Isolators (available
for 20-120 ton units),” p. 30.
Note: 20-60 ton units may install the optional neoprene isolators at each mounting location
instead of the spring isolator. If this is the case, see “Neoprene Isolators (available for 20-
60 ton units only),” p. 29.
28CAUJ-SVX01D-EN
Neoprene Isolators (available for 20-60 ton units only)
Install the neoprene isolators at each unit mounting (load) point, using the following procedure:
1. Elevate the unit (one side at a time) to allow access to the base rail mounting holes.
Note: Use solid type blocks, i.e. 4" X 4" wood blocks or similar material to prevent collapsing. Keep
hands and other body limbs clear of elevated base rail while installing isolators to prevent
personal injury.
2. Align the mounting holes in the base rail of the unit with the holes in the top of the appropriate
isolator. Refer to
3. Install a 1/2" NC bolt (field supplied) through the base rail of the unit into the threaded bolt hole
of the isolator. Position the isolator to allow access to the mounting holes in the base of the
isolator, then tighten securely.
4. Lowerthe unit and isolator onto the mounting surface. The maximum isolator deflection should
be approximately 1/4 inch.
5. Secure the isolator to the mounting surface using the base holes in the isolator.
6. Level the unit carefully. See “Leveling the Unit,” p. 31.
7. After the unit is level, tighten isolator base mounting bolts to secure them to the mounting
surface.
Table 4. Typical neoprene isolator selection & location (20-60 ton units only)
Table 4, p. 29 for the appropriate isolator for each load point.
Install the spring isolators at each unit mounting (load) point using the following procedure:
1. Elevate the unit (one side at a time) to allow access to the base rail mounting holes.
Note: Use solid type blocks, i.e. 4" X 4" wood blocks or similar material to prevent collapsing. Keep
hands and other body limbs clear of elevated base rail while installing isolators to prevent
personal injury.
2. Align the mounting holes in the base rail of the unit with the positioning pin in the top of the
appropriate isolator. See
3. Position the isolator to allow access to the mounting holes in the base of the isolator.
4. Lower the unit onto the isolator. The positioning pin on the isolator must engage into the hole
of the base rail. The clearance between the upper and lower isolator housings should be
approximately 1/4 to 1/2 inch. Refer to
indicates that shims are required to level the unit. See “Leveling the Unit,” p. 31.
5. Make minor clearance adjustments by turning the isolator leveling bolt (Figure 23, p. 30)
clockwise to increase the clearance and counterclockwise to decrease the clearance. If proper
isolator clearance cannot be obtained by turning the leveling bolt, level the isolators
themselves. A 1/4 inch variance in elevation is acceptable.
6. Secure the isolator to the mounting surface using the base holes in the isolator.
7. After the unit is level, tighten the isolator base mounting
Figure 23. Spring isolator 20-120 ton data
Table 5, p. 30 for the appropriate isolator for each load point.
Figure 23, p. 30. A clearance greater than 1/2 inch
Table 5. Typical spring isolator selection and location
Before tightening the mounting bolts, level the unit carefully. Use the unit base rail as a reference.
Level the unit to within 1/4 inch over its entire length. Use shims if adjustable isolators (neoprene)
are not used.
If adjustable isolators (spring) are used, ensure that the proper isolator housing clearance is
maintained while leveling the unit. Isolators are identified by color and/or an isolator part number.
Shims under the isolators may be required if the unit can not be leveled using the isolator leveling
bolt.
General Unit Requirements
The checklist listed below lists steps required to successfully install a commercial air cooled
condenser. This checklist is intended to assist installing personnel with installation process. It does
not replace detailed instruction called out in the applicable sections of this manual.
•Verify that the power supply complies with unit nameplate specifications.
•Check the unit for shipping damage and material shortage; file a freight claim and notify Trane
office.
•Verify installation location of the unit will has required clearance for proper operation.
•Install appropriate isolators, if required.
Installation
Piping
•Install properly sized liquid line(s) between the liquid line connections on the unit and the
evaporator. (i.e., DX evaporator or an EVP Chiller Barrel). Refer to the
section for recommended liquid line components and guidelines.
•Install properly sized discharge (hot gas) line(s) between the discharge line connections on the
unit and the compressor unit. Refer to the
discharge line components and guidelines.
•Install shutoff valves in the liquid line(s) to isolate the filter drier(s) for service.
•Install proper filter driers in each liquid line.
•Leak test the system. Refer to the “Leak Testing Procedure,” p. 37 for recommended procedures.
Main Electrical Power Requirements
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
•Verify the power supply meets the required power requirements of the system.
•Install power wiring in accordance with all applicable codes.
•Install and connect properly sized power supply wiring, with over current protection, to the
main power terminal block (1TB1) in the unit control panel.
•Install proper grounding wires to an earth ground.
“Refrigerant Piping,” p. 32
“Refrigerant Piping,” p. 32 section for recommended
WARNING
CAUJ-SVX01D-EN31
Installation
Field Installed Control Wiring
•Verify the Control transformer (1T1) is wired for the proper operating voltage.
•Install the interlock circuitry wiring between the unit and the appropriate compressor unit to
permit condenser fan operation when the compressor starter auxiliary contacts closes. Refer
to the Field Connection Diagram that shipped with the unit for interlocking information.
•Verify the appropriate jumpers have been installed on the unit to allow proper condenser fan
operation (If applicable). Refer to the control wiring diagram that shipped with the unit for
jumper details.
Refrigerant Piping
Refrigerant piping must be properly sized and applied. These two factors have a very significant
effect on both system performance and reliability.
Note: Use Type “L” refrigerant grade copper tubing only.
Refrigerant Piping should be sized and laid out according to the job plans and specifications. This
should be done when the system components are selected. The primary objective when sizing
refrigerant piping for this unit is to make refrigerant line sizes as small as possible while avoiding
excessive refrigerant pressure drops.
Sizing refrigerant lines as small as possible minimizes the required refrigerant charge and
maximizes compressor life.
Trane recommends that the Refrigerant Line Sizing program in the “Trane C.D.S. Application
Toolbox" be used to size the refrigerant lines. This program supersedes the line sizing tables in both
the Trane Reciprocating Refrigeration publication and the Trane Air Conditioning Manual. If you do
not have access to this program, contact your local Trane Commercial Sales office for assistance.
Liquid Lines
Basic sizing parameters with the system operating at full load for liquid lines are:
•Maximum Liquid velocity: 600 fpm
•Maximum allowable pressure drop: 7 psig (1o F)
As the pressure drop in the liquid line increases, the potential for liquid flashing, due to reduced
refrigerant pressure corresponding to a reduced liquid temperature (subcooling), increases. Under
these conditions, liquid lines exposed to high surrounding ambient temperatures must be
insulated.
Note: Adding refrigerant to a system with improperly sized refrigerant lines will only decrease
system performance and reliability and accentuate poor operating condition.
Isolate all refrigerant lines from the building. This prevents transferring line vibration to the
structure. Do not secure the lines rigidly to the building at any point since this will defeat the
isolation system of the unit.
Refer to the appropriate unit illustration in Figure 5, p. 12 through Figure 18, p. 25 for refrigerant
line size connections and locations. Connect the liquid line piping to the stubs provided at the liquid
line shutoff valves.
Note: The installer must cut an appropriately-sized opening in the unit sheet metal for the
refrigerant piping entrance into the unit.
32CAUJ-SVX01D-EN
Liquid Line Components
Filter driers and valves (expansion valves, charging valves, etc.) should be provided in the liquid
lines just before the evaporator. Minimize the use of valves, reducers and tube bends as much as
possible to avoid excessive pressure drop before the expansion valve.
Liquid Line Filter Drier
Install the filter driers (provided by the installer) in the liquid lines as close as possible to the
expansion valves. Locate them upstream of the moisture indicator and solenoid valves (Solenoid
valves may not be applicable).
Liquid Line Moisture Indicators
To aid in troubleshooting, charging and servicing the system, install moisture indicators in the
liquid lines near the evaporator, down stream of the liquid line drier between the solenoid valve
(if applicable) and the expansion valve.
Liquid Line Solenoid Valves
Liquid line solenoid valves are not recommended on units when they are connected to DX coils.
Liquid line solenoid valves are recommended for refrigerant migration control when they are
connected to an EVP chiller and should be connected as described in the “Electrical Wiring”
section.
Installation
Thermostatic Expansion Valve (TXV)
Trane recommends a balance-ported externally equalized valve to maintain satisfactory superheat
control down to lower valve loading conditions and to compensate for pressure drops between
expansion valve and superheat control point (evaporator refrigerant outlet). For fin and tube
evaporator applications, a 30% bleed port TXV is required for 20-60T units, and a 15% bleed port
is required for 80-120T units.
For proper refrigerant distribution into coil, an expansion valve is required for each coil distributor.
NOTICE:
Equipment Damage!
Do not use any solenoid valve as a pumpdown device. Equipment damage will occur.
CAUJ-SVX01D-EN33
Installation
Table 6. Valve selections
Capacity
Bleed SelectionMinimumMaximum
0
15%80-120 MCHE
30%20-60T MCHE
Applicable Units
Any BPHE or any Fin and
Tube OK Coils
BBIZE-1-1/2-GA22
BBIZE-2-GA23
BBIZE-3-GA2.54
BBIZE-4-GA3.55.5
BBIZE-5-GA4.56.5
BBIZE-6-GA5.57.5
BBIZE-8-GA6.510.5
BBIZE-12-1/2-GA8.513.5
BBIZE-15-GA1116.5
OZE-20-GA1322
OZE-25-GA1726
OZE-35-GA20.539
OZE-50-GA30.559
OZE-60-GA45.570
BBIZE-1-1/2-GA (BP/15)22.5
BBIZE-2-GA (BP/15)2.53
BBIZE-3-GA (BP/15)34.5
BBIZE-4-GA (BP/15)46
BBIZE-5-GA (BP/15)57.5
BBIZE-6-GA (BP/15)69
BBIZE-8-GA (BP/15)712
BBIZE-12-1/2-GA (BP/15)9.515.5
BBIZE-15-GA (BP/15)12.519
OZE-20-GA (BP/15)1525
OZE-25-GA (BP/15)19.530
OZE-35-GA (BP/15)23.545
OZE-50-GA (BP/15)3568
OZE-60-GA (BP/15)52.570
BBIZE-1-1/2-GA (BP/30)23
BBIZE-2-GA (BP/30)2.53.5
BBIZE-3-GA (BP/30)3.55
BBIZE-4-GA (BP/30)4.57
BBIZE-5-GA (BP/30)68.5
BBIZE-6-GA (BP/30)710
BBIZE-8-GA (BP/30)813.5
BBIZE-12-1/2-GA (BP/30)1117.5
BBIZE-15-GA (BP/30)1421.5
OZE-20-GA (BP/30)1728.5
OZE-25-GA (BP/30)2230
34CAUJ-SVX01D-EN
Discharge (Hot Gas) Lines
Discharge lines should be pitched downward 1/2 inch for each 10 feet of horizontal run in the
direction of hot gas flow and away from the compressor. Insulate any portion of the discharge
piping that is exposed to outdoor ambient temperature.
Discharge line sizing is based on minimum velocity required for good oil movement in system.
Basic discharge line parameters are:
•Maximum allowable pressure drop: 6 psig
•Maximum velocity: 3500 fpm
Minimum velocities at Minimum Load:
•Horizontal Lines: 500 fpm
•Vertical Lines: Refer to the Table 7, p. 35
A double riser system may be necessary to meet the discharge line velocity requirements.
either a single or double discharge riser is used, the line should drop well below the
When
discharge outlet of the compressor before starting the vertical rise to prevent the possibility of
refrigerant draining back to the compressor during the “Off” cycle.\
Table 7. Minimum vertical line velocities
Line Dia. Minimum Velocity (fpm) Line Dia. Minimum Velocity (fpm)
7/8"4702-1/8"750
1-1/8"5402-5/8"825
1-3/8"6003-1/8"915
1-5/8"6503-5/8"975
Installation
Discharge (Hot Gas) Line Components
Field supplied hot gas mufflers, pipe anchors, single or double risers, oil traps, etc. as applicable,
should be provide to prevent excessive line vibration and assure proper oil return to the
compressor for proper system operation.
A field supplied discharge “shutoff” valve in each hot gas line near the condenser is recommended
to facilitate refrigerant storage in the condenser during service procedures.
A “constant drain” oil trap is illustrated below and can be used as an alternative to a double riser
application. The constant drain oil trap assures adequate oil return to the suction line even at part
load conditions. Refer to “Reciprocating Direct Expansion Piping Systems” (AM-REF 1/82) for
suggested piping arrangement details.
Figure 24. Hot gas line components
1/4" Solenoid
Valve
Oil Return
Line
Hot Gas
5 feet of 1/8"
Copper Tubing
Filter
Oil Trap
Drip Leg
CAUJ-SVX01D-EN35
Installation
Final Refrigerant Pipe Connections
To access the refrigerant pipe connections, remove the louvered side grills. Refer to Figure 5, p. 12
through Figure 18, p. 25.
These condensing units are shipped with a Nitrogen holding charge. Install pressure gauges to the
appropriate access valve(s) and take a reading. If no pressure is present, refer to the “Leak Testing
Procedure” section. If pressure is present, relieve the pressure before attempting to unsweat the
“seal” caps. If refrigerant connections are not capped, but are “spun-end” tubes, use a tubing
cutter to remove the end from the pipe.
Equipment Damage!
To prevent damage to the system, do not drill a hole in the seal caps or saw the ends off pipe
stubs. This could introduce copper chips into the system piping.
Brazing Procedures
Proper brazing techniques are essential when installing refrigerant piping. The following factors
should be kept in mind when forming sweat connections.
Hazard of Explosion!
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene,
oxygen or compressed air or mixtures containing them for pressure testing. Do not use
mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure
testing as they may become flammable and could result in an explosion. Refrigerant, when
used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to
follow these recommendations could result in death or serious injury or equipment or
property-only damage.
NOTICE:
WARNING
1. Whencopperis heated in the presence of air, Copper oxide forms. To prevent copper oxide from
forming inside the tubing during brazing, sweep an inert gas, such as dry nitrogen, through the
tubing. Nitrogen displaces air in the tubing and prevents oxidation of the interior surfaces. A
nitrogen flow of one to three cubic feet per minute is sufficient to displace the air. Use a pressure
regulating valve or flow meter to control the flow.
2. Ensure that the tubing surfaces to be brazed are clean, and that the ends of the tubes have been
carefully reamed to remove any burrs.
3. Make sure the inner and outer tubes of the joint are symmetrical and have a close clearance,
providing an easy slip fit. If the joint is too loose, the tensile strength of the connection will be
significantly reduced. The overlap distance should be equal to the diameter of the inner tube.
4. Wrapthe body of each refrigerant line component with a wet cloth to keep it cool during brazing.
Move any tube entrance grommets away for the brazing area.
Note: Use 40 to 45% silver brazing alloy (BAg-7 or BAg-28) on dissimilar metals. Use BCup-6
brazing alloy on copper to copper joints.
5. If flux is used, apply it sparingly to the joint. Excessive flux can enter the system which will
contaminate the refrigerant system.
6. Apply heat evenly over the length and circumference of the joint to draw the brazing material
into the joint by capillary action. Remove the brazing rod and flame from the joint as soon as
a complete fillet is formed to avoid possible restriction in the line.
7. Visually inspect the connection after brazing to locate any pin holes or crevices in the joint. The
use of a mirror may be required, depending on the joint location.
36CAUJ-SVX01D-EN
Leak Testing Procedure
Hazard of Explosion!
Never use an open flame to detect gas leaks. It could result in an explosion. Use a leak test
solution for leak testing. Failure to follow recommended safe leak test procedures could result
in death or serious injury or equipment or property-only-damage.
Hazard of Explosion!
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene,
oxygen or compressed air or mixtures containing them for pressure testing. Do not use
mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure
testing as they may become flammable and could result in an explosion. Refrigerant, when
used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to
follow these recommendations could result in death or serious injury or equipment or
property-only damage.
Installation
WARNING
WARNING
When Leak-testing a refrigerant system, observe all safety precautions.
Trane condensing units are shipped with a Nitrogen holding charge. If there is no pressure, the unit
must be leak tested to determine the location of leak as follows:
Note: These service procedures require working with refrigerant, Do NOT release refrigerant to
the atmosphere! The service technician must comply with all federal, state, and local laws.
Refer to general service bulletin MSCU-SB-1 (latest edition).
Use refrigerant gas as a tracer for leak detection and use oil-pumped dry nitrogen to develop the
required test pressure. Test the high and low side of the system at pressures dictated by local codes.
1. Close the field supplied liquid line service valve(s) installed near the evaporator and the
compressor discharge service valve to isolate the system's high side from the low side.
Pressure test the liquid line, discharge line, and condenser coils at pressures dictated by local
codes. Do not exceed 10# above the pressure control settings.
2. Connect a refrigerant cylinder to the charging port of the liquid line service valve. Use the
refrigerant to raise the high side pressure to 12 to 15 psig.
3. Disconnect the refrigerant cylinder. Connect a dry nitrogen cylinder to the charging port and
increase the high side pressure. Do not exceed the condenser maximum working pressure
listed on the unit nameplate.
4. Use a halide torch, halogen leak detector or soap bubbles to check for leaks. Check all piping
joints, valves, etc...
5. Ifa leak is located, use proper procedures to remove the refrigerant/nitrogen mixture, break the
connection and remake as a new joint. Retest for leaks after making repairs.
6. Repeatthe test procedure for the low side of the system, charging through the suction pressure
gauge port or through an access provided on the suction line by the installer. Increase the
system pressure to 100 psig.
7. Ifa leak is located, use proper procedures to remove the refrigerant/nitrogen mixture, break the
connection and remake as a new joint. Retest for leaks after making repairs.
8. Open the liquid line service valve and the compressor discharge service valve.
CAUJ-SVX01D-EN37
Installation
Field Installed Power Wiring
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
An overall dimensional layouts for the field installed wiring entrance into the unit are illustrated in
Figure 5, p. 12 through Figure 18, p. 25. To insure that the unit’s supply power wiring is properly
sized and installed, follow the guidelines outlined below.
Note: All field installed wiring must conform to NEC guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit’s nameplate ratings. The available
supply power must be within 10% of the rated voltage stamped on the nameplate. Use only copper
conductors to connect the 3-phase power supply to the unit.
Main Unit Power Wiring
WARNING
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper
conductors could result in equipment damage.
Table 8, p. 39 and Table 9, p. 39 list the field connection wire ranges for the main power terminal
block 1TB1. Table 10, p. 42 lists the condensing unit electrical data. The electrical service must be
protected from over current and short circuit conditions in accordance with NEC requirements.
Protection devices must be sized according to the electrical data on the nameplate. Refer to the
“Electrical Service Sizing Equations”, for determining;
• Electrical service wire size based on “Minimum Circuit Ampacity" (MCA).
• “Maximum Over Current Protection” (MOP) device.
• “Recommended Dual Element fuse size” (RDE).
1. A field supplied disconnect switch must be installed at or near the unit in accordance with the
National Electrical Code (NEC latest addition). Refer to the “Electrical Service Sizing Equations”
(DSS calculation), for determining the correct size.
2. Completethe unit's power wiring connections onto the main terminal block 1TB1 inside the unit
control panel. Refer to the customer connection diagram that shipped with the unit for specific
termination points.
3. Provide proper supply power (with over current protection) to the Compressor unit and Air
Handling unit (“No Control”, “VAV”, and “Constant Volume”) applications. For chilled water
systems, provide a properly sized power supply to the circulating pump motor (EVP control
applications). Be certain that these components are properly grounded.
4. Provide proper grounding for the unit in accordance with local and national codes.
38CAUJ-SVX01D-EN
Table 8. Customer connection wire range: 20-60 ton units
Customer wire selection and fuse replacement
Power Wire Selection to Main Terminal Block (1TB1)
Unit VoltageTerminal Block SizeConnector Wire Range
All175A(1) #14-2/0
Control Wire Selection to Control Terminal Block (1TB2) “See Note 6"
Wire GaugeOHMS per 1000 Feet
188
165
143
122
Table 9. Customer connection wire range (80-120 ton units)
Customer wire selection and fuse replacement
Power Wire Selection to Main Terminal Block (1TB1)
Unit VoltageTerminal Block SizeConnector Wire Range
All175 AMP(1) #12-2/0
Control Wire Selection to Control Terminal Block (1TB4) “See Note 6"
Wire GaugeOHMS per 1000 FeetMax Wire Length
188500 FT
1651000 FT
1432000 FT
1223000 FT
Installation
CAUJ-SVX01D-EN39
Installation
Power Wire Sizing and Protection Device Equations
To correctly size the main power wiring for the unit, use the appropriate calculation(s) listed below.
Read the load definitions that follow and use Calculation #1 for determining the MCA (Minimum
Circuit Ampacity), MOP (Maximum Over current Protection), and RDE (Recommended Dual
Element fuse size) for each unit. Use Calculation #2 to determine the DSS (Disconnect Switch Size)
for each unit.
Load Definitions:
•LOAD 1 = CURRENT OF THE LARGEST MOTOR (COMPRESSOR OR FAN MOTOR)
•LOAD 2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS
•LOAD 4 = CONTROL POWER TRANSFORMER = AND ANY OTHER LOAD RATED AT 1 AMP OR
MORE
Calculation #1 (MCA, MOP, and RDE)
• MCA=(1.25xLOAD1)+LOAD2+LOAD4
•MOP = (2.25 x LOAD 1) + LOAD2+LOAD4
Select a fuse rating equal to the MOP value. If the MOP value does not equal a standard fuse size
as listed in NEC 240 - 6, select the next lower standard fuse rating.
Note: If selected MOP is less than the MCA, then select the lowest standard maximum fuse size
which is equal to or larger than the MCA, provided the selected fuse size does not exceed
800 amps.
• RDE=(1.5xLOAD1)+LOAD2+LOAD4
Select a fuse rating equal to the RDE value. If the RDE value does not equal a standard fuse size as
listed in NEC 240 - 6 select the next higher standard fuse rating.
Note: Note: If the selected RDE is greater than the selected MOP value, then select the RDE value
to equal the MOP value.
Calculation #2
Disconnect Switch Sizing (DSS)
• DSS=1.15X(LOAD1+LOAD2+LOAD4)
40CAUJ-SVX01D-EN
Field Installed Control Wiring
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded
field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC and your
local/state electrical codes. Failure to follow code could result in death or serious injury.
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before installing any connecting wiring, refer to Figure 5, p. 12 through Figure 18, p. 25 for the
electrical access locations provided on the unit. Install appropriately sized control wiring for the 115
volt electrical components as required by the application.
Since the unit-mounted 115V control power transformer (1T1) is provided on all units, it is not
necessary to run a separate 115 volt control power source to the unit.
Note: 200/230 Volt units are shipped with transformer 1T1 wired for 200 volt operation. If the unit
is to be operated on a 230 volt power supply, rewire the transformer as shown on the unit
schematic.
When the 115 volt control circuit is properly connected to the field provided interlock contacts 5K1
for circuit #1 and 5K2 for circuit #2 (if applicable), proper condenser fan cycling and ambient control
for the remaining fans is achieved with corresponding compressor operation.
Note: All field wiring must conform to NEC guidelines as well as state and local codes.
Installation
WARNING
WARNING
CAUJ-SVX01D-EN41
Installation
Electrical Data
Table 10. Electrical data
Unit CharacteristicsCondenser Fan Motor
Nominal
TonsModel No.
20
25
30
40
50
60
80
100
120
Notes:
1. Electric information is for each individual motor.
2. Maximum fuse size is permitted by NEC 440-22 is 300 percent of one motor RLA plus the RLA of the remaining motors.
3. Minimum circuit ampacity equals 125 percent of the RLA of one motor plus the RLA of the remaining motors.
4. All Kw values taken at conditions of 45°F saturated suction temperature at the compressor and 95°F ambient.
5. Local codes may take precedence.
CAUJ-C20G
CAUJ-C204
CAUJ-C205
CAUJ-C25G
CAUJ-C254
CAUJ-C255
CAUJ-C30G
CAUJ-C304
CAUJ-C305
CAUJ-C40G
CAUJ-C404
CAUJ-C405
CAUJ-C50G
CAUJ-C504
CAUJ-C505
CAUJ-C60G
CAUJ-C604
CAUJ-C605
CAUJ-C80E
CAUJ-C80F
CAUJ-C804
CAUJ-C805
CAUJ-D10E
CAUJ-D10F
CAUJ-D104
CAUJ-D105
CAUJ-D12E
CAUJ-D12F
CAUJ-D124
CAUJ-D125
Electrical
Characteristics
200-230/60/3
460/60/3
575/60/3
200-230/60/3
460/60/3
575/60/3
200-230/60/3
460/60/3
575/60/3
200-230/60/3
460/60/3
575/60/3
200-230/60/3
460/60/3
575/60/3
200-230/60/3
460/60/3
575/60/3
200/60/3
230/60/3
460/60/3
575/60/3
200/60/3
230/60/3
460/60/3
575/60/3
200/60/3
230/60/3
460/60/3
575/60/3
Voltage
Range
180-220/208-254
416-508
520-635
180-220/208-254
416-508
520-635
180-220/208-254
416-508
520-635
180-220/208-254
416-508
520-635
180-220/208-254
416-508
520-635
180-220/208-254
416-508
520-635
180-220
208-254
416-508
520-635
180-220
208-254
416-508
520-635
180-220
208-254
416-508
520-635
Allowable
Circuit
Ampacity
(3),(5)
9.2
4.1
3.2
13.3
5.9
4.6
13.3
5.9
4.6
17.4
7.7
6.0
25.6
11.3
8.8
25.6
11.3
8.8
34
34
15
12
50
50
22
17
50
50
22
17
Minimum
Maximum
Fuse
Size
(2),(5)
15
15
15
20
15
15
20
15
15
20
15
15
30
15
15
30
15
15
40
40
20
15
60
60
25
20
60
60
25
20
No./HP
(1)
2/1.0
2/1.0
2/1.0
3/1.0
3/1.0
3/1.0
3/1.0
3/1.0
3/1.0
4/1.0
4/1.0
4/1.0
6/1.0
6/1.0
6/1.0
6/1.0
6/1.0
6/1.0
8/1.0
8/1.0
8/1.0
8/1.0
12/1.0
12/1.0
12/1.0
12/1.0
12/1.0
12/1.01
12/1.0
12/1.0
FLA
(Ea.)
(1)
4.1
1.8
1.4
4.1
1.8
1.4
4.1
1.8
1.4
4.1
1.8
1.4
4.1
1.8
1.4
4.1
1.8
1.4
4.1
4.1
1.8
1.4
4.1
4.1
1.8
1.4
4.1
4.1
1.8
1.4
LRA
(Ea.)
(1)
20.7
9.0
7.2
20.7
9.0
7.2
20.7
9.0
7.2
20.7
9.0
7.2
20.7
9.0
7.2
20.7
9.0
7.2
20.7
20.7
9.0
7.2
20.7
20.7
9.0
7.2
20.7
20.7
9.0
7.2
KW
(Ea.)
(1),(4)
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
0.9
42CAUJ-SVX01D-EN
Operating Principals
Standard air cooled condensers function as the outdoor condensing units for appropriately sized
split refrigeration systems. These units, operating in conjunction with a matched indoor
compressor/evaporator configuration, provide refrigerant condensing for these systems down to
a normal ambient temperature of 40º F. Operation to 0º F ambient is possible with the addition of
externally mounted low ambient dampers.
All condenser fans are direct drive, 26 inch propeller type. They are driven by 1 HP thermally
protected motors.
When wired properly, the unit will start and operate satisfactorily as long as the operating
temperature is above the minimum operating temperature listed in Table 13, p. 52.
The condensing unit operation starts and stops automatically when the cooling demand is initiated
and terminated by the cooling circuit interlock relays. (See illustrations in diagram numbers 23079123, 2307-9124, 2307-9125, and 2307-9126)
The control components are mounted in the various areas of the unit as illustrated in diagrams
2307-9123, 2307-9124, 2307-9125, and 2307-9126).
20-60 Ton Specs
Condenser fan cycling is accomplished through interlocking the fan operation with compressor
operation (5K1 & 5K2), liquid line pressure switches (4S11 & 4S12). When the low ambient option
is applied, ambient temperature thermostats (1S36 & 1S37) are used to provide additional fan
cycling control. Table 11, p. 43 lists the condenser fan sequencing data and Figure 27, p. 49
illustrates the condenser fan locations with their respective fan and relay designators.
Table 11. Condenser fan sequencing data: 20-60 ton units
Controlling Device (3) Fan "ON" Fan "OFF" Fan Identification
1. Bold fan identifies fans used on 25, 30, 50 & 60 Ton units only.
2. 1S36 and 1S37 normally-closed contacts open on ambient temperature drop to 65°F. Contacts reclose on ambient
temperature rise to 65ºF and 67.5°F.
67.5º F65º F2B3 (1)
1S37 (2)
67.5º F65º F2B6
4S11
444 psig255 psig2B1 (1)
4S12
444 psig255 psig2B6
CAUJ-SVX01D-EN43
Operating Principals
80-120 Ton Specs
Condenser fan cycling is accomplished through interlocking the fan operation with compressor
operation (6K1 & 6K2), and ambient temperature thermostats (1S42 & 1S43) are used to provide
additional fan cycling control. Table 12, p. 44 lists the condenser fan sequencing data and
Figure 28, p. 50 illustrates the condenser fan locations with their respective fan and relay
designators.
Table 12. Condenser fan sequencing data: 80-120 ton units
Notes:
1. Bold fan identifies fans used on CAUJ-D10 & D12 units only.
2. 1S42 and 1S43 normally-closed contacts open on ambient temperature drop to "OFF" setpoints. Contacts reclose on
Use the checklist provided below in conjunction with the “General Unit Requirement” checklist” to
ensure that the unit is properly installed and ready for operation. Be sure to complete all of the
procedures described in this section before starting the unit for the first time.
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
•Turn the field supplied disconnect switch, located upstream of the unit, to the “Off” position.
•Turn the “System” selection switch (at the Remote Panel) to the “Off” position and the “Fan”
selection switch (if applicable) to the “Auto” or “Off” position.
•Check all electrical connections for tightness and “point of termination” accuracy.
•Verify that the condenser airflow will be unobstructed.
•Check the condenser fan blades. Ensure they rotate freely within the fan orifices and are
securely fastened to the fan motor shaft.
Compressor Damage!
Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the
liquid lines may result in compressor damage.
WARNING
NOTICE:
•Verify that all compressor service valves, discharge service valves, and liquid line service valves
is back seated on each circuit.
•Inspect the interior of the unit for tools and debris.
System Evacuation Procedures
Each refrigeration circuit for split system applications must be evacuated before the unit can be
started. Use a rotary type vacuum pump capable of pulling a vacuum of 100 microns or less. Verify
that the unit disconnect switch and the system control circuit switches are “OFF”.
The oil in the vacuum pump should be changed each time the pump is used with a high quality
vacuum pump oil. Before using any oil, check the oil container for discoloration which usually
indicates moisture in the oil and/or water droplets. Moisture in the oil adds to what the pump has
to remove from the system, making the pump inefficient.
When connecting the vacuum pump to a refrigeration system, it is important to manifold the
vacuum pump to both the high and low side of the system (liquid line access valve and suction line
access valve). Follow the pump manufacturer’s directions for the proper methods of using the
vacuum pump.
Motor Damage!
Do not, under any circumstances, use a megohm meter or apply power to the windings of a
compressor while it is under a vacuum. Electrical shorting between motor windings and/or
housing can occur while in a vacuum, causing motor burnout.
NOTICE:
CAUJ-SVX01D-EN45
System Pre-Start Procedures
The lines used to connect the pump to the system should be copper and of the largest diameter
that can practically be used. Using larger line sizes with minimum flow resistance can significantly
reduce evacuation time. Rubber or synthetic hoses are not recommended for system evacuation
because they have moisture absorbing characteristics which result in excessive rates of
evaporation, causing pressure rise during the standing vacuum test. This makes it impossible to
determine if the system has a leak, excessive residual moisture, or a continual or high rate of
pressure increase due to the hoses.
An electronic micron vacuum gauge should be installed in the common line ahead of the vacuum
pump shutoff valve, as shown in Figure 25, p. 47. Close Valves B and C, and open Valve A. Start the
vacuum pump, after several minutes, the gauge reading will indicate the maximum vacuum the
pump is capable of pulling. Rotary pumps should produce vacuums of 100 microns or less.
Open Valves B and C. Evacuate the system to a pressure of 300 microns or less. As the vacuum is
being pulled on the system, there could be a time when it would appear that no further vacuum
is being obtained, yet, the pressure is high. It is recommended that during the evacuation process,
the vacuum be “Broken”, to facilitate the evacuation process.
To break the vacuum: Shutoff valves A, B, & C and connect a refrigerant cylinder to the charging
port on the manifold. Purge the air from the hose. Raise the standing vacuum pressure in the
system to “zero” (0 psig) gauge pressure. Repeat this process two or three times during evacuation.
Note: It is unlawful to release refrigerant into the atmosphere. When service procedures require
working with refrigerants, the service technician must comply with all Federal, State, and
local laws. Refer to the General Service Bulletin MSCU-SB-1 (latest edition).
Standing Vacuum Test
Once 300 microns or less is obtained, close Valve A and leave valves B and C open. This will allow
the vacuum gauge to read the actual system pressure. Let the system equalize for approximately
15 minutes. This is referred to as a “standing vacuum test” where, time versus pressure rise. The
maximum allowable rise over a 15 minute period is 200 microns. If the pressure rise is greater than
200 microns but levels off to a constant value, excessive moisture is present. If the pressure steadily
continues to rise, a leak is indicated. Figure 26, p. 47 illustrates three possible results of the
“standing vacuum test”. If a leak is encounter, repair the system and repeat the evacuation process
until the recommended vacuum is obtained. Once the system has been evacuated, break the
vacuum with refrigerant, and complete the remaining “Pre-Start Procedures” before starting the
unit.
46CAUJ-SVX01D-EN
Figure 25. Typical vacuum pump hookup
S
System Pre-Start Procedures
Figure 26. Evacuation time vs. pressure rise
1600
1400
1200
1000
800
PRESSURE IN MICRON
600
400
200
-100102030405060708090
Initial evacuati on pressure
TIME IN MINUT ES
Continuously increas ing pressure
indicat es the pres ence of leaks,
moisture or both.
Stat e of equilibrium indic ates t he
Stat e of equilibrium indic ates t he
true amount of moisture left i n
the system. It indicates that no
leaks are present and the
system is properly evacuated.
true amount of moisture left i n
the system. It indicates that no
leaks are present, but further
evacuation is requi red.
CAUJ-SVX01D-EN47
System Pre-Start Procedures
Voltage Imbalance
Excessive three phase voltage imbalance between phases will cause motors to overheat and
eventually fail. The maximum allowable voltage imbalance is 2%. Measure and record the voltage
between phases 1, 2, and 3 and calculate the amount of imbalance as follows:
% Voltage Imbalance = 100 X [(AV - VD)/(AV)] where;
AV (Average Voltage) = (Volt 1 + Volt 2 + Volt 3)/3
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average voltage.
Example: If the voltage readings of the supply power measured 221, 230, and 227, the average volts
would be:
(221 + 230 + 227)/3 = 226 Avg.
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
100 X [(226 - 221)/226)] = 2.2%
The 2.2% imbalance in this example exceeds the maximum allowable imbalance of 2.0%. This
much imbalance between phases can equal as much as a 20% current imbalance with a resulting
increase in motor winding temperatures that will decrease motor life. If the voltage imbalance is
over 2%, notify the proper agencies to correct the voltage problem before operating this
equipment.
Electrical Phasing
Proper electrical phasing can be quickly determined and corrected before starting the unit by using
an instrument such as an Associated Research Model 45 Phase Sequence Indicator and following
the steps below:
•Turn the field supplied disconnect switch that provides power to terminal block 1TB1 to the
“Off” position.
WARNING
High Voltage is Present at Terminal Block 1TB1 or Unit Disconnect
Switch 1S1!
To prevent injury or death form electrocution, it is the responsibility of the technician to
recognize this hazard and use extreme care when performing service procedures with the
electrical power energized.
•Connect the phase sequence indicator leads to the terminal block or to the “Line” side of the
optional factory mounted disconnect switch as follows;
Black (phase A) to L1
Red (phase B) to L2
Yellow (phase C) to L3
•Close the main power disconnect switch or circuit protector switch that provides the supply
power to the condensing unit.
•Observe the ABC and CBA phase indicator lights on the face of the sequencer. The ABC
indicator light will glow if the phase is ABC. If the CBA indicator light glows, open the disconnect
switch or circuit protection switch and reverse any two power wires.
•Restore the main electrical power and recheck the phasing.
•If the phasing is correct, open the main power disconnect switch or circuit protection switch and
remove the phase sequence indicator.
48CAUJ-SVX01D-EN
Start-Up
Low Ambient Damper Operation
Low Ambient Dampers are available as a factory installed option or can be field-installed. Dampers
are used to extend the operation of these units from the standard operational temperatures to a
minimum of 0º F without hot gas bypass or 10º F with hot gas bypass. (These values apply when
wind speed across the condenser coil is less than 5 m.p.h.). If typical wind speeds are higher than
5 m.p.h., a wind screen around the unit may be required. By restricting the airflow across the
condenser coils, saturated condensing temperatures can be maintained as the ambient
temperatures change.
The low ambient damper actuator controls damper modulation for each refrigerant circuit in
response to saturated condensing temperature.
Low Ambient Thermostat Operation: 20-60 ton units
In addition to the low ambient dampers on 25, 30, 50 & 60 Ton units, a low ambient thermostat is
installed to further restrict the airflow across the condenser by cycling the 2B3 condenser fan on
25 & 30 Ton units plus 2B6 on 50 & 60 Ton units. The thermostat opens when the ambient
temperature approaches 65º F and closes at approximately 67.5º F.
Figure 27. Condenser fan locations: 20-60 ton units
CAUJ 20 Ton
CAUJ 40 Ton
CAUJ 25 & 30 Ton
CAUJ 50 & 60 Ton
Low Ambient Thermostat Operation: 80-120 ton units
In addition to the low ambient dampers a two stage low ambient thermostat is installed to further
restrict the airflow across the condenser by cycling the 4B1 + 4B6, 5B1 + 5B6 on 100 & 120 Ton units.
The final stage thermostats opens when the ambient temperature approaches 65º F and closes at
CAUJ-SVX01D-EN49
Start-Up
approximately 73º F. The second stage opens when the ambient temperature approaches 45º F and
closes at approximately 53º F.
Figure 28. Condenser fan locations: 80-120 ton units
CAUJ 80 Ton
CAUJ 100 & 120 Ton
Verifying Proper Condenser Fan Rotation
Rotating Components!
The following procedures involve working with rotating components. Disconnect all electric
power, including remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized. Failure to disconnect
power before servicing could result in rotating components cutting and slashing technician
which could result in death or serious injury.
1. “Open” the field supplied disconnect switch or circuit protector switch that provides power to
the compressor unit and lock it in the “Off” position.
2. Open the disconnect switch or circuit protector switch that provides power to the condensing
unit.
3. To Install temporary jumpers:
a. For 20-60 ton units: install temporary jumpers across terminals 1TB2-1 to 1TB2-3, 1TB2-1 to
1TB2-8, and the applicable cycling controls, i.e., pressure switches and ambient
thermostats, to start the condenser fans, as illustrated in Figure 27, p. 49.
b. For 80-120 ton units: Install temporary jumpers across terminals 1TB4-7 to 1TB4-9, 1TB4-7
to 1TB4-11, and the applicable cycling controls, i.e., pressure switches and ambient
thermostats, to start the condenser fans, as illustrated in Figure 28, p. 50.
4. “Close”the disconnect switch or circuit protector switch that provides power to the condensing
unit. Turn the control circuit switch 1S5 to the “On” position. The fans will start when the power
is applied.
5. Check the condenser fans for proper rotation. The direction of rotation is clockwise when
viewed from the top of the unit.
4B4
4B1
WARNING
4B6
4B3
5B6
5B3
All Fans are Rotating Backwards
1. Turn the field supplied disconnect switch or circuit protector switch that provides power to the
condensing unit to the “Off” position. Lock the disconnect switch in the open position while
working at the unit.
2. Interchange any two of the field connected main power wires at the unit terminal block 1TB1
in the unit control panel.
3. Remove all temporary jumpers previously installed in step 3 of “Verifying Proper Condenser
Fan Rotation”.
50CAUJ-SVX01D-EN
Note: Interchanging “Load” side power wires at the fan contactors will only affect the individual
fan rotation. Ensure that the voltage phase sequence at the main terminal block 1TB1 is ABC
as outlined in the “Electrical Phasing” section.
Some Fans are Rotating Backwards;
1. “Open” the field supplied disconnect switch upstream of the unit. Lock the disconnect switch
in the “Open” position while working at the unit.
2. Interchange any two of the fan motor leads at the fan contactor for each fan that is rotating
backwards.
3. Remove all temporary jumpers previously installed in step 3 of “Verifying Proper Condenser
Fan Rotation”.
Low Ambient Damper Adjustment (Factory or Field Installed)
When a unit is ordered with the low ambient option (i.e., Digit 11 is a “1” in the model number),
a damper is factory installed over the lead condenser fan for each refrigeration circuit. See
Figure 27, p. 49 and Figure 28, p. 50 for damper locations.
For field installation, mount the dampers over the condenser fans at the locations shown in
Figure 27, p. 49 and Figure 28, p. 50 and connect the actuator, controller, and sensor for each circuit.
(Refer to the Installation Instructions provided with each low ambient damper kit.)
The controller has a factory default setpoint of 80 ºF. This setpoint can be adjusted by installing a
field supplied resistor on 2TB34 in the low ambient control panel located in the back of the main
control panel. (See the low ambient wiring diagram, that shipped with the unit or with the field kit,
for resistance values and installation location.)
Inspect the damper blades for proper alignment and operation. Dampers should be in the closed
position during the “Off” cycle.
Start-Up
NOTICE:
Actuator Damage!
To prevent damage, do not depress actuator clutch while actuator is energized.
If adjustment is required:
WARNING
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
1. Remove the sensor leads from the input terminals 6 and 7 for circuit #1 and/or 11 and 12 for
circuit #2. (Controller output signal will go to 0.0 VDC and the damper will drive to the closed
position.)
2. Loosen the actuator clamp.
3. Firmly hold the damper blades in the closed position.
4. Retighten the acuator clamp.
CAUJ-SVX01D-EN51
Start-Up
To check damper operation, jumper between the sensor input terminals 6 and 7 and/or 11 and 12
(if applicable). Controller output signal will go to 10 VDC and the damper will drive to the full open
position.
Charging the System
1. Verify that all discharge service valves and liquid line service valves for each circuit is back
seated.
2. Attacha set of service gauges onto the liquid line and discharge line gauge ports for each circuit.
3. Chargeliquid refrigerant into the liquid line of each refrigerant circuit with the required amount
of R-410A. Refrigerant should be charged into the system by weight.
Use an accurate scale or a charging cylinder to monitor the amount of refrigerant entering the
system. Refer to Table 14, p. 52 for the recommended refrigerant capacities for the condensing
unit. The weight of refrigerant required for the liquid line and liquid line driers are listed in
Table 15, p. 53.
If the pressure within the system equalizes with the pressure in the charging cylinder before
charging is completed, complete the process by vapor charging into the suction (low) side of
the system after the system has been started.
Table 13, p. 52 gives the minimum starting temperatures for both “Standard” & “Low”
Ambient units.
Do not attempt to charge the system with the low ambient dampers and/or hot gas bypass
operating (if applicable). Disable the low ambient dampers in the “Open” position (refer to the
“Low Ambient Damper Adjustment” section) and de-energize the hot gas bypass solenoid
valves before proceeding.
4. On units with dual circuits, start only one circuit at a time. To disable the second circuit
compressors, refer to the compressor sequencing information that shipped with the
compressor unit.
5. With the compressors operating, slowly open the “Low Side” valve on the manifold gauge set.
The remainder of the refrigerant will be drawn into the system.
6. Once the charging for the operating circuit has been completed, check and record the:
Record this data on an “operator’s maintenance log” like the one shown in Table 16, p. 53. If the
operating pressures indicate a refrigerant shortage, measure the system superheat and system
subcooling. Repeat steps 1 through 6 for the second refrigeration circuit, if applicable.
circuit);
Table 13. Minimum starting ambient temperatures
Standard UnitsLow Ambient Units
Unit SizeWith HGBPNo HGBPWith HGBPNo HGBP
20-60 Ton Units4030100
80-120 Ton Units80-120 Ton Units40100
Note: Minimum starting ambients in degrees F, based on unit at minimum step of unloading and 5 mph wind across condenser.
Table 14. Recommended refrigerant capacities
Unit SizeOperating Charge per Circuit
C201219
C251219
52CAUJ-SVX01D-EN
1
Condenser Storage Capacity
2
Table 14. Recommended refrigerant capacities
Unit SizeOperating Charge per Circuit
C301219
C401124
C501225
C601332
C802947
D103050
D123363
Notes:
1. CAUJ-C20 - C30 are single-circuit units; CAUJ-40 - C60 are dual-circuit units; CAUJ 80-120 are dualcircuit units
2.
Pounds R-410A per circuit @ 95°F ambient, 95% full
1
Condenser Storage Capacity
2
Table 15. Liquid line & drier refrigerant requirements
Liquid Line O.D.Liquid Line ChargeSporlan Part NoDrier Refrigerant Charge
5/8"1.827C-305-S1 lb. - 1 oz.
3/4"2.728
7/8"3.790
1-1/8"6.461C-419-S1 lb. - 8 oz.
Note: Refrigerant charge given in ounces per foot.
C-307-S
C-417-S
C-307-S
C-417-S
1 lb. - 1 oz.
1 lb. - 8 oz.
1 lb. - 1 oz.
1 lb. - 8 oz.
Start-Up
Table 16. Sample maintenance log
Current
Ambient
Date
Temp.
Note: Check and record the data requested above each month during the cooling season with the unit running
(F)
Compr.
Oil level
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
Refrigerant Circuit #1Refrigerant Circuit #2
Suct.
Press.
(Psig)
Disch.
Press.
(Psig)
Liquid
Press.
(Psig)
Super-
heat (F)
Subcool
(f)
Compr.
Oil level
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
- ok
- Low
Suct.
Press.
(Psig)
Disch.
Press.
(Psig)
Liquid
Press.
(Psig)
Super-
heat (F)
Subcool
(f)
CAUJ-SVX01D-EN53
Service and Maintenance
Fuse Replacement Data
Table 17. Fuse replacement selection: 20-60 ton units
Control Circuit Fuse (1F1)AllAllBussmann SRD-3.23.2 AMP
Transformer Fuse
(1F12 & 1F13)
All
Fall Restraint - Condenser Section Roof
200/230 Volt
460/575 Volt
380/415 Volt
200 Volt
230 Volt
460 Volt
RK5
FNQ-R
FNQ-R
FNQ-R
25 AMP
15 AMP
3.5 AMP
3.2 AMP
1.6 AMP
WARNING
Falling Off Equipment!
This unit is built with fall restraint slots located on unit top that MUST be used during
servicing. These slots are to be used with fall restraint equipment that will not allow an
individual to reach the unit edge. However such equipment will NOT prevent falling to the
ground, for they are NOT designed to withstand the force of a falling individual. Failure to use
fall restraint slots and equipment could result in individual falling off the unit which could
result in death or serious injury.
This unit is built with fall restraint slots located on unit top that must be used during servicing.
Figure 29. Fall restraint slot unit location and detail
54CAUJ-SVX01D-EN
Monthly Maintenance
Air Handling Equipment
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
Before completing the following checks, turn the system control circuit switch 1S2 and 5S1 to the
“Off” position. Open the main power disconnect switch for the Condensing Unit and Air Handling
Unit and “lock it” in the “Off” position before removing any access panels.
•Inspect the return air filters. Clean or replace them if necessary.
•Check the evaporator drain pan and condensate piping to ensure that there are no blockages.
•Inspect the evaporator coils for dirt. If the coils appear dirty, clean them according to the
instructions described in the “Coil Cleaning” section.
•Inspect the economizer damper hinges and pins (if applicable) to ensure that all moving parts
are securely mounted. Clean the blades as necessary.
•Verify that all damper linkages move freely; lubricate with white grease, if necessary.
•Check Supply Fan motor bearings; repair or replace the motor as necessary.
•Check the fan shaft bearings for wear. Replace the bearings as necessary.
•Lubricate the supply fan bearings. Refer to the equipment manufacturer for their recommended
greases.
Note: Over lubrication can be just as harmful as not enough grease. Use a hand grease
Note: After greasing the bearings, check the setscrews to ensure that the shaft is held securely to
•Check the supply fan belt(s). If the belts are frayed or worn, replace them.
•Verify that all wire terminal connections are tight.
•Generally inspect the unit for unusual conditions (e.g., loose access panels, leaking piping
connections, etc.)
•Make sure that all retaining screws are reinstalled in the unit access panels once these checks
are complete.
Service and Maintenance
WARNING
gun to lubricate these bearings; add grease until a light bead appears all around the seal.
Do not over lubricate!
the bearings and Fan wheels. Make sure that all bearing supports are tight.
Condensing Unit
WARNING
Rotating Components!
The following procedure involves working with rotating components. Disconnect all electric
power, including remote disconnects before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently energized. Failure to disconnect
power before servicing could result in rotating components cutting and slashing technician
which could result in death or serious injury.
•Manually rotate the condenser fans to ensure free movement and check motor bearings for
wear. Verify that all of the fan mounting hardware is tight.
•Verify that all wire terminal connections are tight.
CAUJ-SVX01D-EN55
Service and Maintenance
•Inspect the condenser coils for dirt and foreign debris. If the coils appear dirty, clean them
according to the instructions described in the “Coil Cleaning” section.
•Inspect the compressor and condenser fan motor contactors. If the contacts appear severely
burned or pitted, replace the contactor. Do not clean the contacts.
•Check the compressor oil level. (Compressors “Off”)
System operation
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary
to work with live electrical components. Have a qualified licensed electrician or other
individual who has been properly trained in handling live electrical components perform these
tasks. Failure to follow all electrical safety precautions when exposed to live electrical
components could result in death or serious injury.
•Close the main power disconnect switch for the condensing unit and all system support
equipment. Turn all system control circuit switches to the “On” position.
•With the unit running, check and record the:
– ambient temperature;
– compressor oil level (each circuit);
– compressor suction and discharge pressures (each circuit);
– superheat and Subcooling (each circuit);
•Record this data on an “operator’s maintenance log” similar to the one illustrated in the “Final
Setup” section of this manual. If the operating pressures indicate a refrigerant shortage,
measure the system Superheat and system Subcooling. For guidelines, refer to the “System
Start-Up” section.
Note: Do Not release refrigerant to the atmosphere! If adding or removing refrigerant is required,
WARNING
the service technician must comply with all federal, state and local laws. Refer to general
service bulletin MSCU-SB-1 (latest edition).
Coil Cleaning
.
NOTICE:
Coil Cleaners!
Coil cleaners can damage roofs, surrounding buildings, vehicles, etc. Cleaning substances
should be checked to ensure that they will not cause damage to surroundings. Coils and roof (if
applicable) should be rinsed thoroughly. Do not spray coil cleaners in windy conditions.
Regular coil maintenance, including annual cleaning enhances the unit’s operating efficiency by
minimizing:
• compressor head pressure and amperage draw;
• water carryover;
• fan brake horsepower; and,
• static pressure losses.
At least once each year—or more often if the unit is located in a “dirty” environment—clean the
microchannel condenser using the instructions outlined below. Be sure to follow these instructions
as closely as possible to avoid damaging the coils.
56CAUJ-SVX01D-EN
Service and Maintenance
To clean refrigerant coils, use a soft brush and a sprayer.
Note: DO NOT use detergents with microchannel condenser coils. Pressurized water or air ONLY.
1. Remove enough panels from the unit to gain safe access to coils..
WARNI NG
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the
supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this
recommendation could result in death or serious injury.
Important: Bridging between the main supports required before attempting to enter into the
unit. Bridging may consist of multiple 2 by 12 boards or sheet metal grating.
2. Straighten any bent coil fins with a fin comb.
3. For accessible areas, remove loose dirt and debris
microchannel condenser coil applications, seek pressure coil wand extension through the local
Trane Parts Center.
Note: DO
4. Pour the cleaning solution
5. Spray the leaving-airflow side of the coil first; the
6. Rinse both sides of the coil
7. Inspect both sides of the coil; if it still appears to be dirty, repeat Steps 6 and 7.
8. Reinstall all of the components and
NOT use any detergents with microchannel coils. Pressurized water or air ONLY.
into the sprayer. If a high-pressure sprayer is used:
a. The minimum nozzle spray angle is 15 degrees.
Do not allow sprayer pressure to exceed 600 psi.
b.
c. Spray the solution perpendicular (at 90 degrees) to the coil face.
evaporator and reheat coils, allow the cleaning solution to stand on the coil for five minutes.
with cool, clean water.
panels removed in Step 1; then restore power to the unit.
from both sides of the coil. For dual row
n spray the opposite side of the coil. For
Microchannel Condenser Coil Repair and Replacement
If microchannel condenser coil repair or replacement is required, seek HVAC Knowledge Center
information or Service Guide document RT-SVB83*-EN for further details.
CAUJ-SVX01D-EN57
Warranty and Liability Clause
COMMERCIAL EQUIPMENT RATED 20 TONS AND LARGER AND RELATED
ACCESSORIES
PRODUCTS COVERED - This warranty* is extended by American Standard Inc. and applies only to
commercial equipment rated 20 Tons and larger and related accessories.
The Company warrants for a period of 12 months from initial start-up or 18 months from date of
shipment, whichever is less, that the Company products covered by this order (1) are free from
defects in material and workmanship and (2) have the capacities and ratings set forth in the
Company’s catalogs and bulletins, provided that no warranty is made against corrosion, erosion
or deterioration. The Company’s obligations and liabilities under this warranty are limited to
furnishing f.o.b. factory or warehouse at Company designated shipping point, freight allowed to
Buyer’s city (or port of export for shipment outside the conterminous United States) replacement
equipment (or at the option of the Company parts therefore) for all Company products not
conforming to this warranty and which have been returned to the manufacturer. The Company shall
not be obligated to pay for the cost of lost refrigerant. No liability whatever shall attach to the
Company until said products have been paid for and then said liability shall be limited to the
purchase price of the equipment shown to be defective.
The Company makes certain further warranty protection available on an optional extra-cost basis.
Any further warranty must be in writing, signed by an officer of the Company.
The warranty and liability set forth herein are in lieu of all other warranties and liabilities, whether
in contract or in negligence, express or implied, in law or in fact, including implied warranties of
merchantability and fitness for particular use. In no event shall the Company be liable for any
incidental or consequential damages.
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES
AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS OR IMPLIED, IN LAW
OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR
PARTICULAR USE, IN NO EVENT SHALL WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES.
Manager - Product Service
Trane Inc.
Clarksville, Tn 37040-1008
PW-215-2688
*Optional Extended Warranties are available for compressors and heat exchangers of Combination
Gas-Electric Air Conditioning Units.
58CAUJ-SVX01D-EN
Wiring Diagrams
Note: For easier access, published unit wiring diagrams (individual, separate diagrams for unitary
product lines) will become available via e-Library instead of through wiring manuals after
2007.
Drawing
NumberDescription
2307-9123Power Schematic Diagram - Air-Cooled Condensing Unit - Line Voltage 200-230-460-575V/60HZ/3PH - CA 20-60 Ton
2307-9124Unit & Field Connection Wiring Diagram - Air-Cooled Condensing Unit - Line Voltage 200, 230, 460, 575V/60HZ/3PH - CA
2307-9125Power Schematic Diagram - Split System Condensing Unit - Duplex Condenser Units - CA 80-120 ton
2307-9126Unit & Field Connection Wiring Diagram - Air-Cooled Condenser Unit - Duplex Condenser Unit - CA 80-120 ton
20-60 Ton
CAUJ-SVX01D-EN59
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the
leader in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad
portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.Trane.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.