Trane CAUJ-C20, CAUJ-C40, CAUJ-C80, CAUJ-C25, CAUJ-C50 Installation and Maintenance Manual

...
Installation, Operation, and Maintenance
Remote Split System Units and Remote Chillers
Models
RAUJ-C20 RAUJ-C40 RAUJ-C80 RAUJ-C25 RAUJ-C50 RAUJ-D10 RAUJ-C30 RAUJ-C60 RAUJ-D12
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
October 2012 SS-SVX11H-EN

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provide to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
Read this manual thoroughly before operating or servici ng this unit.
ATT EN TI ON : Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that
must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING
R-410A Refrigerant under Higher Pressure than R-22!
The units described in this manual use R-410A refrigerant which operates at higher pressures than R-22 refrigerant. Use ONLY R-410A rated service equipment or components with these units. For specific handling concerns with R-410A, please contact your local Trane representative. Failure to use R-410A rated service equipment or components could result in equipment exploding under R-410A high pressures which could result in death, serious injury, or equipment damage.
WARNI NG
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
WARNI NG
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
© 2012 Trane All rights reserved SS-SVX11H-EN

Introduction

Overview of Manual
Note: One copy of this document ships inside the control
panel of each unit and is customer property. It must be retained by the unit's maintenance personnel.
This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized. It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Revision Summary
SS-SVX11H-EN
Update valve selection part numbers and wiring diagram drawing numbers.
Introduction
Trademarks
Trane, Frostat and the Trane logo are trademarks of Trane in the United States and other countries. All trademarks referenced in this document are the trademarks of their respective owners.
SS-SVX11H-EN 3
Table of Contents
Model Number Descriptions . . . . . . . . . . . . . . 6
General Information . . . . . . . . . . . . . . . . . . . . . 7
Unit Inspection . . . . . . . . . . . . . . . . . . . . . . 7
Unit Dimensions & Weights . . . . . . . . . . . . . 10
Unit Clearances . . . . . . . . . . . . . . . . . . . . . . 10
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . . . 32
Neoprene Isolators (20 - 60 Ton units) . . 32
Spring Isolators (20 - 120 Ton units) . . . . 32
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Foundation . . . . . . . . . . . . . . . . . . . . . . . . 34
Unit Isolation . . . . . . . . . . . . . . . . . . . . . . 34
Leveling the Unit . . . . . . . . . . . . . . . . . . . 34
General Unit Requirements . . . . . . . . . . . 34
Refrigerant Piping Requirements . . . . . . 34
EVP Chilled Water Piping Requirements 34
Main Electrical Power Requirements . . . 35
Field Installed Control Wiring
Requirements . . . . . . . . . . . . . . . . . . . . . . 35
Low Voltage Wiring (AC & DC) . . . . . . . . 36
Refrigerant Line Components . . . . . . . . . 36
Refrigerant Piping . . . . . . . . . . . . . . . . . . 38
Typical Field-Installed Evaporator Piping:
Dual-Circuit Examples . . . . . . . . . . . . . . . 40
Typical Field-Installed EVP Chiller
Evaporator Piping . . . . . . . . . . . . . . . . . . . 41
Hot Gas Bypass for Commercial
Comfort-Cooling Applications . . . . . . . . . 41
Optional Pressure Gauges . . . . . . . . . . . . 42
Final Refrigerant Pipe Connections . . . . 43
Brazing Procedures . . . . . . . . . . . . . . . . . 43
Leak Testing Procedure . . . . . . . . . . . . . . 44
Remote EVP Chiller . . . . . . . . . . . . . . . . . 44
Field Installed Power Wiring . . . . . . . . . . 48
Disconnect Switch External Handle (20-120 Ton Factory Mounted Option) . . 48
Main Unit Power Wiring . . . . . . . . . . . . . 49
Power Wire Sizing and Protection Device 49
Field Installed Control Wiring . . . . . . . . . 52
Controls Using 115 VAC . . . . . . . . . . . . . 52
Controls using 24 VAC . . . . . . . . . . . . . . . .53
Controls using DC Analog Input/Outputs .54
Economizer Actuator Circuit . . . . . . . . . . .54
No System Control . . . . . . . . . . . . . . . . . . .55
Variable Air Volume Control (Honeywell
W7100A) . . . . . . . . . . . . . . . . . . . . . . . . . . .60
Discharge Air Sensor (Honeywell 6RT3 or Honeywell 8RT3) Discharge Air Sensor . .62
Suction Line Thermostat . . . . . . . . . . . . . .62
Night Setback . . . . . . . . . . . . . . . . . . . . . . .63
EVP Chiller Control . . . . . . . . . . . . . . . . . . .63
Outside Air Thermostat
(5S57 Field Provided) . . . . . . . . . . . . . . . . .66
Constant Volume Control (Honeywell W973) — 20 - 60TUnits Only .66
System Pre-Start Procedures . . . . . . . . . . . . .70
EVP Chiller Applications . . . . . . . . . . . . . .70
System Evacuation Procedures . . . . . . . .70
Discharge Air Controller Checkout
(Honeywell W7100A) . . . . . . . . . . . . . . . . .72
Discharge Air Sensor Checkout
(Honeywell Sensor) . . . . . . . . . . . . . . . . . .73
Economizer Actuator Checkout . . . . . . . . .73
EVP Chiller Control Checkout
(Honeywell W7100G) . . . . . . . . . . . . . . . . .74
Chilled Water Sensor Checkout
(Honeywell Sensor) . . . . . . . . . . . . . . . . . .75
Master Energy Control Checkout . . . . . . . .75
Zone Thermostat Checkout
(Honeywell T7067) . . . . . . . . . . . . . . . . . . .76
Discharge Air Sensor Checkout
(Honeywell 6RT1) . . . . . . . . . . . . . . . . . . . .77
Voltage Imbalance . . . . . . . . . . . . . . . . . . .77
Electrical Phasing . . . . . . . . . . . . . . . . . . .78
Operating Principals . . . . . . . . . . . . . . . . . . . . .79
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
Low Ambient Damper Adjustment
(Factory or Field Installed) . . . . . . . . . . . . .83
EVP Chiller Applications . . . . . . . . . . . . . .83
“Air Over” Evaporator Application . . . . . .83
System Airflow Measurement . . . . . . . . .84
Preliminary Expansion Valve Adjustment 84
4 SS-SVX11H-EN
Adding Preliminary Charge . . . . . . . . . . . 86
Compressor Start-Up (All Systems) . . . . 86
Pressure Curves . . . . . . . . . . . . . . . . . . . . 92
Final System Setup . . . . . . . . . . . . . . . . . 95
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Compressor Operational Sounds . . . . . . 97
Scroll Compressor Failure Diagnosis
and Replacement . . . . . . . . . . . . . . . . . . . 97
Fuse Replacement Data . . . . . . . . . . . . . 101
Fall Restraint - Condenser Section Roof 101
Monthly Maintenance . . . . . . . . . . . . . . 102
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . 102
Warranty and Liability Clause . . . . . . . . . . . 104
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . 105
SS-SVX11H-EN 5

Model Number Descriptions

20 to 60-Ton Units
1
DIGIT 1 — UNIT TYPE
R = Condensing Unit
DIGIT 2 — CONDENSER
A = Air Cooled
DIGIT 3 — AIRFLOW
U = Upflow
DIGIT 4 — DEVELOPMENT SEQUENCE
J= Third
DIGITS 5,6,7 — NOMINAL CAPACITY
C20 = 20 Tons C25 = 25 Tons C30 = 30 Tons C40 = 40 Tons C50 = 50 Tons C60 = 60 Tons
DIGIT 8 — VOLTAGE AND START CHARACTERISTICS
E = 200/60/3 XL D = 415/50/3 XL F = 230/60/3 XL 4 = 460/60/3 XL 5 = 575/60/3 XL 9 = 380/50/3 XL
DIGIT 9 — SYSTEM CONTROL
B = No System Control C = Constant Volume Control E = Supply Air VAV Control P = EVP Control
DIGIT 10 — DESIGN SEQUENCE
X = Factory Assigned
DIGIT 11 — AMBIENT CONTROL
0 = Standard 1 = 0°F (Low Ambient Dampers)
DIGIT 12 — AGENCY APPROVAL
0 = None 3 = cULus (not available for 50 Hz)
DIGIT 13
A = Non Fused Unit Disconnect Switch
DIGIT 14
B = Hot Gas Bypass Valve
DIGIT 15
D = Suction Service Valves
DIGIT 16
F = Pressure Gauges and Piping
DIGIT 17
G = Return Air Sensor
DIGIT 18
J = Corrosion Protected Condenser Coil
DIGIT 19
C = Remote Chiller Evaporator & Install
Kit
T = Flow Switch (EVP Control Only)
DIGIT 20
1 = Spring Isolators 2 = Neoprene Isolators
80 to 120-Ton Units
1
DIGIT 1 — UNIT TYPE
R = Remote Condensing Unit
DIGIT 2 — CONDENSER
A = Air-Cooled
DIGIT 3 — AIRFLOW
U = Upflow
DIGIT 4 — DEVELOPMENT SEQUENCE
J = Third
DIGITS 5,6,7 — NOMINAL CAPACITY
C80 = 80 Tons D10 = 100 Tons D12 = 120 Tons
DIGIT 8 — VOLTAGE AND START CHARACTERISTICS
E = 200/60/3 XL F = 230/60/3 XL 4 = 460/60/3 XL 5 = 575/60/3 XL * = 380/50/3 XL * = 415/50/3 XL2
2
DIGIT 9 — SYSTEM CONTROL
B = No System Control E = Supply Air VAV Control P = EVP Control
DIGIT 10 — DESIGN SEQUENCE
X = Factory Assigned
DIGIT 11 — AMBIENT CONTROL
0 = Standard 1 = 0°F (Low Ambient Dampers)
DIGIT 12 — AGENCY APPROVAL
0 = None 3 = cULus (not available for 50 Hz)
DIGIT 13 — NUMBER OF CIRCUITS
2 = Dual (All 80-120 Ton)
DIGIT 14
B = Hot Gas Bypass Valve
DIGIT 15
D = Suction Service Valves
DIGIT 16
F = Pressure Gauges and Piping
DIGIT 17
H = Corrosion Protected Condenser Coil
DIGIT 18
1 = Spring Isolators
DIGIT 19
C = Remote Chiller Evap & Install Kit 3 = Flow Switch ( EVP Control only)
1
The service digit for each model number contains 21 digits; all 21 digits must be referenced.
2
Contact the local Trane Sales Office for ordering information regarding 80-120 50Hz models.
6 SS-SVX11H-EN

General Information

Unit Inspection

As soon as the unit arrives at the job site
Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
Verify that the power supply complies with the unit nameplate specifications.
Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.
Check for material shortages. Refer to the Component Layout and Ship with Location illustration.
Important: If the job site inspection of the unit reveals
damage or material shortages, file a claim
with the carrier immediately. Specify the type and extent of the damage on the ‘bill of lading” before signing.
Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
WARN ING
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.
If concealed damage is discovered, notify the carrier's terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the appropriate Trane office before installing or repairing a damaged unit.
When ordering replacement parts or requesting service, be sure to refer to the specific model number, serial number, and DL number (if applicable) stamped on the unit nameplate.
Compressor Nameplate
The nameplate for the “Scroll” compressors is located on the compressor lower housing.
EVP Chiller - Applications Only
If ordered with remote EVP chiller kit, piping components ship in condenser section. The heat exchanger ships separately. The 20-30 chiller nameplate is located on same side as water connections near center left. The 40-120 Ton chiller nameplate is located on same side as water connections near bottom. To view, raise insulation flap over nameplate. Replace and retape insulation flap after viewing.
Phase Monitor (1U3)
The unit is equipped with a phase monitor in the control box. The phase monitor will protect against phase loss, imbalance and reversal of the line voltage. If a fault occurs, the red LED will energize. While the fault condition is present the phase monitor interrupts the 115V control circuit. If no faults are observed, a green LED will be energized.
Manual Motor Protectors (380V through 575V Only):
circuit protection for compressors. These devices are capable of providing both overload and short-circuit protection.
Before operating, the manual motor protector must be switched with the rotary on/off switch to the “ON” position and the overload setpoint dial must be set to the appropriate rating of the motor.
Important: In order to avoid nuisance trips, the
Figure 1. Compressor protection module
Manual motor protectors will be used as branch
overload setpoint dial must be adjusted to the following calculated value:
Overload Setting = (Compressor RLA) x 1.12
Unit Nameplate
One Mylar unit nameplate is located on the outside upper right corner of the control panel door. It includes the unit model number, serial number, electrical characteristics, weight, refrigerant charge, as well as other pertinent unit data. A small metal nameplate with the Model Number, Serial Number, and Unit Weight is located just above the Mylar nameplate, and a third nameplate is located on the inside of the control panel door.
SS-SVX11H-EN 7
General Information
On 80-120 Ton units, the CSHN*** compressors come equipped with a compressor protection device capable of detecting phase reversal, phase loss, and phase unbalance. The compressor protection device uses a Green and Red LED to indicate the compressor status. A solid Green LED denotes a fault free condition; a blinking Red LED indicates an identifiable fault condition. Once a problem has been detected, the power will have to be cycled to clear the reset circuit.
Note: If the compressor has tripped, the resistance will be
4500 ohms or greater; when reset, they will be less than 2750 ohms.
Blink Code: The blink code consists of different on / off time of the Red LED which is repeated continuously until either the fault is cleared or until power is cycled.
Table 1. Blink codes
Fault LED on LED off LED on LED off
(a)
PTC
overheat or PTC
reset delay active
Phase loss long long long long
Incorrect phase sequence
(a) PTC = Positive Temperature Coefficient
short long short long
short short short long
Discharge Line Thermostat
The first compressor on each circuit is equipped with a Discharge Line Thermostat. If the temperature of the line exceeds 230F the thermostat interrupts the 115V control circuit for the compressors and all the compressors on the circuit will de-energize. Once the temperature drops below 180F the thermostat will close and allow the compressor to be energized.
Unit Description
All air cooled condensing units are designed for outdoor installations with vertical air discharge. These units may be installed on a flat roof or placed on a concrete slab at ground level.
Before shipment, each unit is leak-tested, evacuated, a nitrogen holding charge is added, and the controls are tested for proper operation.
The condenser coils an all Aluminum Microchannel design. Corrosion protected condenser coils are a standard option. Louvered condenser grilles for coil protection are standard. Direct-drive, vertical discharge condenser fans are provided with built-in current and overload protection.
For “Ship with” items, see Figure 2, p. 9 and Figure 3, p. 9.
If low ambient operation is required, low ambient dampers are available as a field or factory installed option.
Units may be ordered with one of the following options:
No System Controls (Field provided controls required)
Constant Volume Controls
Supply Air Temperature Control (VAV applications)
EVP Chiller Controls
Basic unit components include:
Manifolded Scroll Compressors
Condenser coils
Condenser fans (number based on unit size)
Discharge service valve (one per circuit)
Liquid line service valve (one per circuit)
Table 2. General data - 20 - 120 Ton remote chillers
Model Number
Shipping weight, lbs 44 84 113 90 135 157 208 292 320
Operating weight, lbs 56 104 142 131 206 244 330 473 520
No. of refrigerant circuits 1 1 1 2 2 2 2 2 2
Water volume, Gal 1.4 2.2 3.3 4.6 7.9 9.7 13.6 20.1 22.2
Chiller refrig charge @ AHRI condition, lbs 0.9 1.5 2.2 3.1 5.3 6.4 9.0 13.3 14.7
Minimum water flow rate, GPM 24 30 36 48 60 72 96 120 144
Maximum water flow rate, GPM 69 89 100 136 176 201 275 346 407
Chiller Water Supply/Return Pipe Size, in 2.0 2.0 2.0 3.0 3.0 3.0 4.0 4.0 4.0
Notes:
1. All heat exchangers are brazed plate.
2. All heat exchangers are single circuit on the water side.
3. Shipping and operating weights are approximate.
4. Refrigerant charge is approximate and for chiller only.
5. Applications with leaving water temperature below 42°F require freeze protection down to 15°F.
6. Maximum chiller operating ambient is 115°F.
8 SS-SVX11H-EN
RAUJ-
C20
RAUJ-
C25
RAUJ-
C30
RAUJ-
C40
RAUJ-
C50
RAUJ-
C60
RAUJ-
C80
RAUJ-
D10
RAUJ-
D12
General Information
Condenser Coil
Access Panels
Lifting Bracket (2/side)
Condenser Air Intake Grills
Control Panel
Compressors
Condenser Fans
“Shipwith” Area
Figure 2. Component layout and ‘ship-with’ locations 20 - 60T units
Condenser Coil
Control Panel
Access Panels
Compressors
(a) 60T unit shown
Condenser Fans
Figure 3. Component layout and ‘ship-with’ locations 80 - 120T units
(a)
“Shipwith” Area
(a)
Lifting Bracket (2/side)
Condenser Air Intake Grills
(a) 120T unit shown
SS-SVX11H-EN 9

Unit Dimensions & Weights

Unit Clearances

Figure 4, p. 10 illustrates the minimum operating and
service clearances for either a single, multiple, or pit application. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.
NOTICE:
Equipment Damage!
Providing less than the recommended clearances could result in condenser coil starvation or recirculation of hot condenser air.
Locate the unit as close to the applicable system support equipment as possible to minimize refrigerant piping lengths.
Figure 4. Typical installation clearances for single, multiple or pit applications (20-60 Ton units only)
Allow adequate clearance for water and refrigerant piping connections, space to perform service procedures, i.e. read gauges, thermometers, and operate water system valves.
EVP Chiller Considerations
Allow adequate clearance for water and refrigerant piping connections, space to perform service procedures, (i.e. read gauges, thermometers, and operate water system valves.
Note: The braze plate chiller is intended for indoor
application. If a sub-freezing location is required, contact Trane for installation precautions required to prevent damage.
10 SS-SVX11H-EN

Dimensions

4" CONDUIT MAIN POWER
1 3/4" KO LOW VOLTAGE (30V MAX.)
37 11/16"
3 3/8"
CONTROL PANEL
35 13/16"
31 1/4"
29 1/4"
4 1/2"
2 5/8"
5 5/16"
5 3/8"
3 3/8"
1/2" X 4 KO (115V)
1/2" X 2 KO (115V)
4 3/8"
6 1/8"
88 5/16"
74 1/4"
60"
11 1/2"
18"
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
4" LINE VOLTAGE ACCESS
78"
5 3/16"
1 13/16"
LOW AMBIENT DAMPER (SEE NOTE 2)
FAN GRILLE
FAN GRILLE
CONTROL PANEL (SEE DETAIL A)
26 13/16"
CONTROL BOX BOTTOM (SEE DETAIL A)
13"
6 1/4"
57 5/8"
1 1/4"
8"
72 1/2"
3/4" X 4 MTG HOLES
DOOR 43 1/4" W/ 180 DEG SWING
2 1
4 3
FRONT (SEE NOTE 3 FOR ALL MIN. CLEARANCE)
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT OF UNIT CLEARANCE 72" . BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42".
DETAIL A
CONTROL BOX BOTTOM
Figure 5. 20-Ton air-cooled condensing unit
Unit Dimensions & Weights
SS-SVX11H-EN 11
VOLTAGE ACCESS
CONTROL PANEL
5/8" O.D.
LIQUID LINE
8 1/16"
13"
42"
SCALE1,00
0
34 1/2"
5 7/16"
5 3/4"
LIQUID LINE
SUCTION LINE
COIL
1 5/8" O.D. SUCTION LINE
CONTROL PANEL SIDE
CONTROL
PANEL SI DE
20 TON UNIT
PLAN VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAW ING
CONTROL PANEL SIDE VIEW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
NOTES:
1. VERIFY WEIGHT , CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
Unit Dimensions & Weights
Figure 6. 20-Ton air-cooled condensing unit (connections)
12 SS-SVX11H-EN
Unit Dimensions & Weights
1/2" X 4 KO (115V)
1 3/4" KO LOW VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
CONTROL PANEL
4 1/2"
3 3/8"
5 3/8"
2 5/8"
37 11/16"
35 13/16"
5 5/16"
3 3/8"
31 1/4"
29 1/4"
4" CONDUIT MAIN POWER
1.6
CONTROL BOX BOTTOM (SEE DETAIL A)
FAN GRILLE
LOW AMBIENT DAMPER (SEE NOTE 2)
FAN GRILLE
4" LINE
VOLTAGE ACCESS
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
88 1/2"
60 1/8"
74 1/4"
18"
11 1/2"
88 5/16"
78"
4 3/8"
6 1/8"
5 3/16"
1 13/16"
13"
6 1/4"
CONTROL PANEL (SEE DETAIL A)
27 1/4"
57 5/8"
1 1/4"
8"
72 1/2"
DOOR 43 1/4" W/ 180 DEG SWING
2 1
3
4
3/4" X 4 MTG HOLES
FRONT (SEE NOTE 3 FOR
ALL MIN.
CLEARANCE)
CONTROL BOX BOTTOM
DETAIL A
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT OF 20 AND 30 UNIT CLEARANCE 72" . BACK OF UNIT CLEARANCE 72”. LEFT AND RIGHT SIDE OF 20 AND 30 UNIT CLEARANCE 42”.
Figure 7. 25- and 30-Ton air-cooled condensing unit
SS-SVX11H-EN 13
Unit Dimensions & Weights
HOT GAS BYPASS (OPTIONAL)
LIQUID LINE
7/8" O.D. HOT GAS BYPASS (OPTIONAL)
7/8" O.D. LIQUID LINE
SERVICE VALVE (OPTIONAL)
COIL
COMPRESSOR S
16 9/16"
5 11/16"
7 9/16"
34 1/2"
23 1/2"
A
B
A
CONTROL PANEL
VOLTAGE ACCESS
SCALE1.000
CONTROL PANEL SIDE
AA
C
FRONT
AA
A
C
AA
C
FRONT
AA
A
C
AA
C
FRONT
A A
A
C
AA
C
FRONT
A A
A
C
SUCTION LINE
18 9/16"
SUCTION LINE
LIQUID LINE
COIL
25 - 30 TON UNIT
DIMENSIONAL CONNECTION DRAWING
PLAN VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAW ING
CONTROL PANEL SIDE VIEW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
BACK VIEW OF UNIT
CONNECTION DRAW ING
SUCTION LINE Horizontal 25T: 2 1/8” O.D. 30T: 2 1/8” O.D. Vertical 25T: 1 5/8” O.D. 30T: 2 1/8” O.D.
Figure 8. 25- and 30-Ton air-cooled condensing unit (connections)
14 SS-SVX11H-EN
Figure 9. 40-Ton air-cooled condensing unit
Unit Dimensions & Weights
6
4
2
CONTROL PANEL (SEE DETAIL A)
DOOR 43 1/4" W/ 180 DEG SWING
85 5/8"
FAN GRILLE
5
3
1
FAN GRILLE
36 1/8"
36 1/8"
1 1/4"
3/4" X 6 MTG HOLES
88 9/16"
8"
FRONT (SEE NOTE 3 FOR ALL MIN. CLEARANCE)
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42".
1/2" X 4 KO (115V)
1/2" X 2 KO (115V)
2 5/8"
1 3/4" KO LOW VOLTAGE (30V MAX.)
5 5/16"
5 3/8"
3 3/8"
3 3/8"
29 1/4"
31 1/4"
35 13/16"
37 11/16"
CONTROL PANEL
DETAIL A
BOTTOM OF CONTROL BOX
LOW AMBIENT DAMPER (SEE NOTE 2)
4 1/2"
4" CONDUIT MAIN POWER
BOTTOM OF CONTROL BOX (SEE DETAIL A)
88 5/16"
79 1/4"
32 3/16"
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
6 1/4"
4" LINE VOLTAGE ACCESS
22 1/2"
16"
6 1/8"
4 3/8"
13"
1 15/16"
5 3/16"
88 5/16"
SS-SVX11H-EN 15
Unit Dimensions & Weights
1 5/8" O.D. SUCTION LINE
COMPRESSORS
COMPRESSOR
COIL
7/8" O.D. HOT GAS BYPASS (OPTIONAL)
7/8" O.D. HOT GAS
BYPASS (OPTIONAL)
5/8" O.D. LIQUID LINE
12"
7 11/16"
13 3/4"
4 3/4"
10 1/4"
711/16"
12"
71/4"
16 1/4"
SERVICE VALVE
(OPTIONAL)
2 7/8"
AA
C
AA
C
SCALE1,000
5 7/16"
18 1/2"
513/16"
LIQUID LINE
HOT GAS BYPASS (OPTIONAL)
SUCTION LINE
VOLTAGE ACCESS
CONTROL PANEL
CONTROL PANEL SIDE
CONTROL PANEL SIDE
40 TON UNIT
DIMENSIONAL CONNECTION DRAW ING
PLAN VIEW OF UNIT
CONNECTION DRAWING
CONNECTION DRAW ING
CONTROL PANEL SIDE VI EW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
BACK VIEW OF UNIT
CONNECTION DRAW ING
NOTES:
1. VERIFY WEIG HT, CONNECTION, AND ALL DIMENSION W ITH INSTALLER DOCUMENTS BEFORE INSTALLATION
Figure 10. 40-Ton air-cooled condensing unit (connections)
16 SS-SVX11H-EN
Figure 11. 50-Ton air-cooled condensing unit
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"
5 5/16"
2 5/8"
5 3/8"
1 3/4" KO LOW VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT
MAIN POWER
CONTROL PANEL
88 5/16"
113 13/16"
103 1/2"
16"
22 1/2"
79 1/4"
1 15/16"
FAN GRILLE
LOW AMBIENT DAMPER (SEE NOTE 2)
FAN GRILLE
1 1/4" x 4 1/2" SLOT FOR 115
VOLT CONTROL
4" LINE VOLTAGE ACCESS
BOTTOM OF CONTROL BOX (SEE DETAIL A)
13"
6 1/4"
32 1/4"
CONTROL PANEL (SEE DETAIL A)
DOOR 43 1/4" W/ 180 DEG SWING
8 1/8"
48 7/8"
48 7/8"
85 5/8"
3/4" X 6 MTG HOLES
12
34
56
FRONT (SEE NOTE 3 FOR ALL MIN. CLEARANCE)
DETAIL A
BOTTOM OF CONTROL BOX
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42".
Unit Dimensions & Weights
SS-SVX11H-EN 17
Unit Dimensions & Weights
COMPRESSORS
COIL
COMPRESSOR
COIL
15/8" O.D. SUCTION LINE for vertical 2 1/8” O.D. SUCTION LINE for horizontal
SUCTION LINE
LIQUID LINE
7/8" O.D. HOT GAS BYPASS (OPTIONAL)
HOT GAS BYPASS (OPTIONAL)
7/8" O.D, HOT GAS BYPASS (OPTIONAL)
12"
10 13/16"
41 3/4"
32 3/4"
7 11/16"
7/8" O.D. LIQUID LINE
SERVICE VALVE (OPTIONAL)
12"
7 11/16"
10 13/16"
29 3/4"
38 3/4"
CONTROL
PANEL
VOLTAGE ACCESS
CONTROL PANEL SIDE
CONTROL
PANEL SID E
AAAAA
A
5 7/16"
5 13/16
18 1/2"
DIMENSIONAL CONNECTION DRAWING
50 TON UNIT
PLAN VIEW OF UNIT
CONNECTION DRAWI NG
CONNECTION DRAWI NG
CONTROL PANEL SIDE VIEW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
BACK VIEW OF UNIT
CONNECTION DRAWING
NOTES:
1. VERIFY WEIGHT, CONNECTION , AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
Figure 12. 50-Ton air-cooled condensing unit (connections)
18 SS-SVX11H-EN
Unit Dimensions & Weights
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"
5 5/16"
2 5/8"
5 3/8"
1 3/4" KO LOW VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT MAIN POWER
CONTROL PANEL
FAN GRILLE
4" LINE VOLTAGE ACCESS
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
FAN GRILLE
CONTROL PANEL (SEE DETAIL A)
1 15/16"
103 1/2"
5 3/16"
113 13/16"
22 1/2"
16"
79 1/4"
114"
88 5/16"
13"
LOW AMBIENT DAMPER (SEE NOTE 2)
32 3/16"
BOTTOM OF CONTROL BOX (SEE DETAIL A)
6 1/4"
3/4" X 6 MTG HOLES
DOOR 43 1/4" W/ 180 DEG SWING
8 1/8"
48 7/8"
48 7/8"
85 5/8"
2 1
3
4
6
5
FRONT (SEE NOTE 3 FOR
ALL MIN. CLEARANCE)
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
BOTTOM OF CONTROL BOX
DETAIL A
3. FRONT AND BACK OF UNIT CLEARANCE 72" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 42".
Figure 13. 60-Ton air-cooled condensing unit
SS-SVX11H-EN 19
Unit Dimensions & Weights
COMPRESSORS
COIL
COMPRESSOR
COIL
2 1/8" O.D. SUCTION LINE
SUCTION LINE
LIQUID LINE
7/8" O.D. HOT GAS BYPASS (O PTIONAL )
HOT GAS BYPASS (OPTIONAL)
7/8" O.D, HOT GAS BYPASS (OPTIONAL)
12"
10 13/16"
41 3/4"
32 3/4"
711/16"
7/8" O.D. LIQUID LINE
SERVICE VALVE (OPTIONAL)
12"
7 11/16"
10 13/16"
29 3/4"
38 3/4"
CONTROL PANEL
VOLTAGE ACCESS
CONTROL PANE L SIDE
CONTROL
PANEL SIDE
AAAAA
A
5 7/16"
5 13/16"
18 1/2"
60 TON UNIT
DIMENSIONAL CONNECTION DRAW ING
NOTES:
1. VERIFY WEIGHT , CONNECTION, AND ALL DIMENSIO N WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
PLAN VIEW OF UNIT
CONNECTION DRAWI NG
CONNECTION DRAWI NG
CONTROL PANEL SIDE VIEW OF UNIT
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
BACK VIEW OF UNIT
CONNECTION DRAWING
Figure 14. 60-Ton air-cooled condensing unit (connections)
20 SS-SVX11H-EN
Figure 15. 80-Ton air-cooled condensing unit
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"
5 5/16"
2 5/8"
5 3/8"
1 3/4" KO LOW
VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT MAIN POWER
CONTROL PANEL
1.6
1 13/16"
176 7/16"
83 1/8"
30 1/4"
30 1/8"
83 1/4"
88 5/16"
176 11/16"
FAN GRILLE
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
4" LINE VOLTAGE ACCESS
FAN GRILLE
79 1/4"
7"
9"
14"
LOW AMBIENT
DAMPER (SEE NOTE 2)
6 1/4"
1
16 5/16"
BOTTOM OF CONTROL BOX (SEE DETAIL A)
CONTROL PANEL (SEE DETAIL A)
2 1/4" x 1 1/4" 24 VOLTAGE CONTROL WIRING
3/4" X 8 MTG HOLES
DOOR 43 1/4" W/ 180 DEG SWING
1 1/4"
8"
72 1/8"
16"
72 1/8"
85 5/8"
12
4 3
6
5
8
7
FRONT (SEE NOTE 3 FOR ALL MIN. CLEARANCE)
DIMENSIONAL DETAIL
DETAIL A
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT AND BACK OF UNIT CLEARANCE 96" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 48".
Unit Dimensions & Weights
SS-SVX11H-EN 21
Unit Dimensions & Weights
1 1/8" O.D. LIQUID LINE
2 1/8" O.D .SUCTION LINE
COIL
21/8"O.D.SUCTIONLINE
1 3/8" O.D. HOT GAS BYPASS (OPTIONAL)
COMPRESSOR (6)
13/8"HOTGAS BYPASS (OPTIONAL)
COMPRESSOR (6)
HOT GAS BYPASS (OPTIONAL)
14 13/16"
25 1/8"
46 3/16"
SERVICE VALUE (OPTIONAL SEE DETAIL A)
42 9/16"
25 1/8"
14 1/16"
19 1/16"
73 3/8"
45 9/16"
CONTROL PANEL SIDE
18 5/16"
SUCTION LINE
LIQUID LINE
DETAIL A
VOLTAGE ACCESS
CONTROL PANEL
CONTROL PANEL SIDE
5 9/16"
93/8"
LIQUID LINE
COIL
COMPRESSOR (6)
SERVICE VALUE (OPTIONAL SEE DETAIL A)
DETAIL A
DETAIL DRAWING
NOTES: 1
. VERIFY WEIGHT, CONN ECTION, AND ALL DIMENSION W ITH
INSTALLER DOCUMENTS BEFORE INSTALLATION
PLAN VIEW OF UNIT
CONNECTION DRAW ING
CONNECTION DRAW ING
CONTROL PANEL SIDE VIEW OF UNIT
LEFT VIEW OF UNIT
CONNECTION DRAW ING
ISOMETRIC DRAWING
ORIENTATION VIEW OF UNIT
Figure 16. 80-Ton air-cooled condensing unit (connections)
22 SS-SVX11H-EN
Figure 17. 100- and 120-Ton air-cooled condensing unit
29 1/4"
31 1/4"
35 13/16"
37 11/16"
3 3/8"
3 3/8"
5 5/16"
2 5/8"
5 3/8"
1 3/4" KO LOW VOLTAGE (30V MAX.)
1/2" X 2 KO (115V)
1/2" X 4 KO (115V)
4 1/2"
4" CONDUIT MAIN POWER
CONTROL PANEL
1 15/16"
108 11/16"
20 1/16"
5 3/16"
108 5/8"
5 1/8"
20 1/16"
79 1/4"
7"
14"
9"
88 5/16"
FAN GRILLE
CONTROL PANEL (SEE DETAIL A)
4" LINE VOLTAGE ACCESS
1 1/4" x 4 1/2" SLOT FOR 115 VOLT CONTROL
FAN GRILLE
LOW AMBIENT
DAMPER (SEE NOTE 2)
BOTTOM OF CONTROL BOX (SEE DETAIL A)
16 3/16"
2 1/4" x 1 1/4" 24 VOLTAGE CONTROL WIRING
6 1/4"
13"
3/4" X 8 MTG HOLES
DOOR 43 1/4" W/
180 DEG SWING
8"
1 1/4"
97 5/8"
16"
97 5/8"
85 13/16"
FRONT (SEE NOTE 3 FOR
ALL MIN.
CLEARANCE)
DIMENSIONAL DETAIL
DETAIL A
NOTES:
1. SEE CONNECTION DRAWING FOR CONNECTION LOCATION AND SIZES.
2. LOW AMBIENT DAMPER ONLY COMES WITH SELECTED UNIT .
3. FRONT AND BACK OF UNIT CLEARANCE 96" . LEFT AND RIGHT SIDE OF UNIT CLEARANCE 48".
227 1/4”
Unit Dimensions & Weights
SS-SVX11H-EN 23
Unit Dimensions & Weights
1 3/8"HOT GAS
BYPASS (OPTIONAL)
1 1/8" O.D. LIQUID LINE
COMPRESSOR (6)
SUCTION LINE
COIL
COMPRESSOR (6)
LIQUID LINE
SUCTION LINE
HOT GAS BYPASS (OPTIONAL)
1 3/8"HOT GAS BYPASS (OPTIONAL)
25 1/8"
39 5/8"
67 7/16"45 7/8"
18 1/16"
13 1/16"
/8" O.D.
2 5/8" O.D. SUCTION LINE
46 1/4"
74"
25 1/8"
SCALE1,000
18 5/16"
59/16"
93/8"
VOLTAGE ACCESS
CONTROL PANEL
CONTROL PANEL SIDE
CONTROL
PANEL SIDE
SERVICE VALUE (OPTIONAL SEE DETAIL A)
SERVICE VALUE (OPTIONAL SEE DETAIL A)
DETAIL A
DETAIL DRAWING
NOTES:
1. VERIFY WEIGHT, CONNECTION, AND ALL DIMENSION WITH INSTALLER DOCUMENTS BEFORE INSTALLATION
PLAN VIEW OF UNIT
CONNECTION DRAW ING
CONNECTION DRAW ING
CONTROL PANEL SIDE VIEW OF UNIT
LEFT VIEW OF UNIT
CONNECTION DRAWING
ISOMETRIC DRAWI NG
ORIENTATION VIEW OF UNIT
2 5/8” O.D. for horizontal 2 1/8” O.D. for vertical
SUCTION LINE
2 5/8” O.D. for horizontal 2 1/8” O.D. for vertical
Figure 18. 100- and 120-Ton air-cooled condensing unit (connections)
24 SS-SVX11H-EN
Figure 19. 20-Ton evaporator chiller
Notes:Notes:
THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLYTHIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4)HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4)
INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT
TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINESTUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINES
INSTALL INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY INSTALL INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY
REQUIRE TRIMMING REQUIRE TRIMMING
USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATIONUSE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
WATER CONNECTIONS ARE GROOVED (VICTAULIC)WATER CONNECTIONS ARE GROOVED (VICTAULIC)
REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.
SEE IOM BRAZE PROCEDURES.SEE IOM BRAZE PROCEDURES.
REQUIRES FIELD
PROVIDED
1/2”X14NPTE
STAINLESS STEEL
OR PVC PLUG
Unit Dimensions & Weights
SS-SVX11H-EN 25
Unit Dimensions & Weights
Notes:
THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4)
INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT TUBING, OR
MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINES
Install INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY REQUIRE
TRIMMING
USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
WATER CONNECTIONS ARE GROOVED (VICTAULIC)
REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.
SEE IOM BRAZE PROCEDURE.
REQUIRES FIELD
PROVIDED
1/2”X14NPTE
STAINLESS STEEL
OR PVC PLUG
Figure 20. 25 and 30-Ton evaporator chiller
26 SS-SVX11H-EN
Figure 21. 40-Ton evaporator chiller
Notes:Notes:
THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLYTHIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4)HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4)
INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT
TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINESTUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINES
Install INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY Install INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY
REQUIRE TRIMMING REQUIRE TRIMMING
USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATIONUSE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
WATER CONNECTIONS ARE GROOVED (VICTAULIC)WATER CONNECTIONS ARE GROOVED (VICTAULIC)
REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.
SEE IOM BRAZE PROCEDURE.SEE IOM BRAZE PROCEDURE.
REQUIRES FIELD
PROVIDED
1/2”X14NPTE
STAINLESS STEEL
OR PVC PLUG
Unit Dimensions & Weights
SS-SVX11H-EN 27
Unit Dimensions & Weights
Notes:Notes:
THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLYTHIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4). HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS (ITEM 4).
ATTACH MOUNTING LEGS BEFORE PIPING AND INSULATINGATTACH MOUNTING LEGS BEFORE PIPING AND INSULATING
INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & REFRIGERANT
TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINESTUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT LINES
INSTALL FACE INSULATION FIRST (ITEMS 6 & 7), THEN WRAPPER INSULATION (ITEM 5), ITEM 5 MAY INSTALL FACE INSULATION FIRST (ITEMS 6 & 7), THEN WRAPPER INSULATION (ITEM 5), ITEM 5 MAY
REQUIRE TRIMMING REQUIRE TRIMMING
USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATIONUSE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
WATER CONNECTIONS ARE GROOVED (VICTAULIC)WATER CONNECTIONS ARE GROOVED (VICTAULIC)
REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.
SEE IOM BRAZE PROCEDURES.SEE IOM BRAZE PROCEDURES.
REQUIRES FIELD
PROVIDED
1/2”X14NPTE
STAINLESS STEEL
OR PVC PLUG
Figure 22. 50 and 60-Ton evaporator chiller
28 SS-SVX11H-EN
Figure 23. 80 and 120-Ton evaporator chiller
Notes:Notes:
THIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLYTHIS HEAT EXCHANGER IS INTENDED FOR INDOOR INSTALLATION ONLY
HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS HEAT EXCHANGER MOUNTING LEGS ARE INSTALLED AT JOB SITE WITH SUPPLIED FASTENERS
(ITEM 4)(ITEM 4)
INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS & INSULATION (ITEMS 5, 6, & 7) SHOULD BE INSTALLED AFTER INSTALLING LEGS &
REFRIGERANT TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING REFRIGERANT TUBING, OR MUST BE ADEQUATELY SHIELDED AGAINST HEAT WHEN BRAZING
REFRIGERANT LINESREFRIGERANT LINES
Install INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY Install INSULATION SIDE PIECES FIRST (ITEMS 6 & 7), THEN WRAPPER (ITEM 5), ITEM 5 MAY
REQUIRE TRIMMING REQUIRE TRIMMING
USE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATIONUSE VINYL TAPE (FIELD SUPPLIED) TO SEAL INSULATION AFTER INSTALLATION
WATER CONNECTIONS ARE GROOVED (VICTAULIC)WATER CONNECTIONS ARE GROOVED (VICTAULIC)
REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.REFRIGERANT CONNECTIONS ARE STAINLESS STEEL AND REQUIRE SPECIAL BRAZE MATERIALS.
SEE IOM BRAZE PROCEDURES.SEE IOM BRAZE PROCEDURES.
REQUIRES FIELD
PROVIDED
1/2”X14NPTE
STAINLESS STEEL
OR PVC PLUG
Unit Dimensions & Weights
SS-SVX11H-EN 29
Unit Dimensions & Weights
80-120 Ton
1
2
3
4
5
6
7
8
Y
X
20-30 Ton
40-60 Ton
1
1
2
2
3
3
4
4
5
6
Y
Y
X
X
Table 3. Typical unit weights and point loading data 20 - 120 Ton units
Weight CG Locations Weight on isolator mounting location (lbs.)
Tons Model Shipping Operating X Y Loc. 1 Loc. 2 Loc 3. Loc 4. Loc. 5 Loc. 6 Loc. 7 Loc. 8
20 RAUJC20 1548 1573 40.8 33.0 475.5 383.3 403.2 311.0 --- --- --- ---
25 RAUJC25 1598 1623 40.6 32.8 491.2 399.3 412.2 320.3 --- --- --- ---
30 RAUJC30 1598 1623 40.6 32.8 491.2 399.3 412.2 320.3 --- --- --- ---
40 RAUJC40 2482 2532 43.4 46.0 452.3 415.7 440.3 403.7 428.3 391.8 --- ---
50 RAUJC50 2826 2868 52.3 45.9 365.5 331.0 427.8 393.3 700.1 650.3 --- ---
60 RAUJC60 2803 2853 52.1 45.9 367.2 332.8 426.0 391.6 692.5 642.9 --- ---
80 RAUJC80 4870 4940 86.0 55.8 798.3 462.1 786.7 450.5 785.1 448.9 772.4 436.1
100 RAUJC100 5539 5622 110.9 55.0 871.1 609.5 881.0 616.2 882.6 432.1 892.5 436.8
120 RAUJC120 5995 6121 111.5 54.2 988.2 614.7 948.3 587.4 941.8 583.0 901.8 555.8
Figure 24. Air-cooled condensing units
Control
Panel
Control
Panel
Control
Panel
Table 4. Isolator mounting locations
Mounting Location
Unit Size 12345678
20/25/30
40
50/60
80
100/120
X8”86' 8 1/86' 8 1/8----
Y4' 10 3/41 1/44' 10 3/41 1/4”----
X 8” 8” 3' 8 1/8” 3' 8 1/8” 6' 8 1/4” 6' 8 1/4” - -
Y 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” - -
X 8” 8” 4' 8 7/8” 4' 8 7/8” 8' 9 3/4” 8' 9 3/4” - -
Y 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” - -
X 8” 8” 6' 8 1/8” 6' 8 1/8” 9' 1/8” 9' 1/8” 14' 1/4” 14' 1/4"
Y 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4"
X 8” 8” 8' 9 5/8” 8' 9 5/8” 10' 1 5/8” 10' 1 5/8” 18' 3 1/4 18' 3 1/4”
Y 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4” 7' 3 1/8” 1 1/4"
Table 5. General data - 20 - 120 Ton remote chillers
Model Number
Shipping weight, lbs 44 84 113 90 135 157 208 292 320
Operating weight, lbs 56 104 142 131 206 244 330 473 520
No. of refrigerant circuits 1 1 1 2 2 2 2 2 2
Water volume, Gal 1.4 2.2 3.3 4.6 7.9 9.7 13.6 20.1 22.2
Chiller refrig charge @ ARI condition, lbs 0.9 1.5 2.2 3.1 5.3 6.4 9.0 13.3 14.7
Minimum water flow rate, GPM 24 30 36 48 60 72 96 120 144
Maximum water flow rate, GPM 69 89 100 136 176 201 275 346 407
Chiller Water Supply/Return Pipe Size, in 2.0 2.0 2.0 3.0 3.0 3.0 4.0 4.0 4.0
Notes:
1. All heat exchangers are brazed plate.
2. All heat exchangers are single circuit on the water side.
3. Shipping and operating weights are approximate.
4. Refrigerant charge is approximate and for chiller only.
5. Applications with leaving water temperature below 42°F require freeze protection down to 15°F.
6. Maximum chiller operating ambient is 115°F.
C20
RAUJ-
RAUJ-
C25
RAUJ-
C30
RAUJ-
C40
RAUJ-
C50
RAUJ-
C60
RAUJ-
C80
RAUJ-
D10
RAUJ-
D12
30 SS-SVX11H-EN
Loading...
+ 76 hidden pages