Trane 4TWB3018D, 4TWB3024D, 4TWB3030C, 4TWB3042B, 4TWB3048B Installer's Manual

...
18-BC85D1-2
Installer’s Guide
Heat Pumps
4TWB3018–060
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa­tion pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Table of Contents
Section 1. Safety ..................................................................................... 2
Section 2. Unit Location Considerations..............................................3
Section 3. Unit Preparation .................................................................... 5
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 6
Section 6. Refrigerant Line Routing .....................................................7
Section 7. Refrigerant Line Brazing ...................................................... 8
Section 8. Refrigerant Line Leak Check .............................................10
Section 9. Evacuation ...........................................................................11
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up ..............................................................................17
Section 14. System Charge Adjustment ............................................. 18
Section 15. Checkout Procedures and Troubleshooting ................... 23
Section 1. Safety
WARNING
!
WARNING
!
WARNING
!
WARNING
!
CAUTION
!
CAUTION
!
WARNING
!
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connec­tion with its use.
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the sys­tem. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit Bulletins SS-APG006-EN and APP-APG011-EN or APPAPG012-EN.
LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and trouble­shooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
UNIT CONTAINS R-410A REFRIGERANT! R-410A operating pressures exceed the limit of R-22. Proper service equipment is required. Failure to use proper service tools may result in equipment damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-
PROVED POE COMPRESSOR OIL.
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
2 18-BC85D1-2
Section 2. Unit Location Considerations
D
H
W
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models H x D x W (in)
4TWB3018D 4TWB3024D 4TWB3030C 4TWB3036C 4TWB3042B 4TWB3048B 4TWB3060B
* Weight values are estimated.
29 x 30 x 33 160 29 x 30 x 33 160 33 x 30 x 33 193 33 x 34 x 37 198 33 x 34 x 37 219 37 x 34 x 37 234 41 x 34 x 37 248
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.
Weight* (lb)
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty (60) feet.
2. The maximum vertical change should not exceed sixty (60) feet.
3. Service valve connection diameters are shown in Table 5.1.
Note: For line lengths greater than sixty (60) feet, Refer to Refrigerant Piping Application Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32-3312-03 (or latest revi­sion).
Standard Line Set
60’ Max
Line Length
60’
Max
Vertical
Change
18-BC85D1-2 3
60’
Max
Vertical
Change
2.3 Suggested Locations for Best Reliability
Avoid Install
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
Near Bedrooms
Min 5’ Unrestricted
It is not recommended to install in a location where noise may distract the building occu­pants. Some examples of these types of loca­tions are sleeping quarters and by windows of a living area. Please discuss location with the building owner prior to installation.
Avoid locations such as near windows where condensation and freezing defrost vapor can annoy a customer.
Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water or icicles from falling directly on the unit.
Min. 12” to Shrubbery
Min. 12” to Shrubbery
Min 3’ Unrestricted
Access Panel
Min. 12” to Wall
2.4 Cold Climate Considerations
NOTE: It is recommended that these precau­tions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
• Units should be elevated 3-12 inches above
the pad or roof top, depending on local weather. This additional height will allow drainage of snow and ice melted during defrost cycle prior to its refreezing. Ensure that drain holes in unit base pan are not obstructed preventing draining of defrost water.
• If possible, avoid locations that are likely to
accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit.
4 18-BC85D1-2
Min. 12”
Snow
Barrier
Snow Legs
3-12” Elevation
Pad
2.5 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory sup­plied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report prompt-
ly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet, remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
18-BC85D1-2 5
Section 5. Refrigerant Line Considerations
Line Length
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Line Sizes Service Valve Connection Sizes
Model
4TWB3018D 5/8 3/8 5/8 3/8 4TWB3024D 5/8 3/8 5/8 3/8 4TWB3030C 3/4 3/8 3/4 3/8 4TWB3036C 3/4 3/8 3/4 3/8 4TWB3042B 3/4 3/8 3/4 3/8 4TWB3048B 7/8 3/8 7/8 3/8 4TWB3060B 7/8 3/8 7/8 3/8
Vapor
Line
5.2 Factory Charge
Outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line
length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant charge adjustment is necessary.
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact.
Liquid Line
Vapor Line
Insulation
6 18-BC85D1-2
5.5 Reuse Existing Refrigerant Lines
CAUTION
!
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Important: For more information see publica­tion numbers SS-APG006-EN.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
Minimize the number of 90º turns.
8 Feet Maximum
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure Liquid Line directly to Vapor line using tape, wire, or other appro­priate method every 8 ft.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
Joist/Rafter
Isolator
Line Set
18-BC85D1-2 7
Isolation From Joist/Rafter
8 Feet Maximum
Wall
Isolator
Wall
Side View
8 Feet Maximum
Line Set
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly to Vapor Line using tape, wire, or other appropriate method every 8 ft.
Isolation In Wall Spaces
Sealant
Ductwork
Insulation
Vapor Line
Isolator
Line Set
Isolation Through Wall
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a debur-
ing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
DO NOT hang line sets from ductwork
8 18-BC85D1-2
STEP 2 - Remove the pressure tap cap and valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
Continue the dry nitrogen purge. Do not re­move the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan.
18-BC85D1-2 9
STEP 5 - Replace the pressure tap valve cores
150 PSIG
after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and
evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 - Check for leaks by using a soapy solu­tion or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks before continuing.
10 18-BC85D1-2
Section 9. Evacuation
1/4 TURN ONLY
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
0350
Microns
ON
OFF
1 MIN.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere.
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve
stem 1/4 turn counterclockwise to the fully open position.
STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
CAP
UNIT SIDE OF VALVE
PRESSURE TAP PORT
COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
GAS LINE CONNECTION
18-BC85D1-2 11
10.1 Open the Liquid Service Valve
WARNING
!
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the
stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Cap
Unit Side
of Service
Valve
Service Port
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 Ft. 16 AWG 225 Ft. 14 AWG 300 Ft.
12 18-BC85D1-2
11.2 Low Voltage Hook-up Diagrams
Orange
Heat Pump
Heat Pump
Communicating Indoor Unit with 24 V Control Hook-up Diagram
Comm. Variable Speed
Furnace or Air Handler
Comfort Control
R
Y1
G W1 X2
B
O
Red Yellow
Green White
Blue Orange
R BK
D Y1 Y2 G W1 W2 W3
B
O
Neatly bundle all low voltage wires as shown.
Red
Yellow
Black
Yellow
Blue
Red
Orange
Black
Notes:
1. See User Interface 24 V Mode setup menu for control mode and cooling CFM options.
2. W3 terminal may not
Orange
Blue
(X2)
be present on unit.
3. (Air Handlers only) If electric heat does not have 3rd contac­tor (CH), connect a jumper wire from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a jumper wire from W2 to W1.
4. W1 - X2 is a field installed jumper.
Variable Speed Furnace Hook-up Diagram
Comfort Control
R
Y1
G W1 X2
B
O
Red Yellow
Green White
Blue Orange
Variable Speed Furnace
R
LO
Y Y BK
G W1 W2 B O
Neatly bundle all low voltage wires as shown.
Red
Yellow
Yellow
Red
Black
Black
(X2)
Blue
Blue
Orange
Notes:
1. Comfort control must be dual fuel capable or use accessory TAYPLUS103A.
2. Ylo and BK may not be present on unit.
3. W1 - X2 is a field installed jumper.
18-BC85D1-2 13
1
1
12345
12345
HP
2(Compressor)
2(Stages)
AC (System)
}
OUTDOOR
Capacity (Tons)
OUTDOOR
}
Torque
CFM/Ton
Cool OffDelay
}
INDOOR
CFM
+12V
R13
R14
R4
1
U1
RNET1
S1
on
on
S2
RNET2
R
6
C22
C19
C15C
12
C10
D9
L1
Heat Pump
TAM7 Air Handler Hook-up Diagram
Air Handler
Neatly bundle all low voltage wires as shown.
Black
(X2)
Comfort Control
X2
W G Y1
O R B
White Green Yellow Orange Red Blue
Field wiring
TAM4 Air Handler Hook-up Diagram
W3 Brown
W1 White *
W2 Pink
W3 W2 W1 G
(In)
YI O R B
(Out)
YO
DH/BK
W1 - White
O - Orange R - Red B - Blue Y1 - Yellow
Orange
Red
Must configure to
“OFF” for HP Units.
Must configure to “OFF” for
single-stage compressors.
Blue
Yellow
Control Board
Green
Red
Blue
Yellow YI
Orange
Comfort Control
White
W
Green
G
Yellow
Y
Orange
O
Red
R
Blue
14 18-BC85D1-2
B
Purple YO
Air Handler
Heat Pump
Yellow
Black
(X2)
Orange
Blue
Red
Y - Yellow
O - Orange B - Blue R - Red W1 - White
• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
• YI and YO connections must be made as shown for proper operation, freeze protection, and internally mounted condensate overflow circuits to work properly
• Internally mounted condensate switch is optional and must be ordered separately
• If a 3rd party condensate overflow switch is installed, it should be wired between Y of the thermostat and YI of the EEV control.
• Some models have a terminal strip. Refer to air handler Installer’s Guide.
GAM5 Air Handler Hook-up Diagram
Heat Pump
W2 Pink
W3 Brown
W1 White
Comfort Control
White
W
Green
G
Yellow
Y
Orange
O
Red
R
Blue
B
Field wiring
GAM2 Air Handler Hook-up Diagram
Green
White Green Yellow Orange
Red
Blue
Red
Blue
Yellow
Orange
Black
(X2)
Air Handler
R - Red
B - Blue
Y - Yellow
• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
• Some models have a terminal strip. Refer to air handler Installer’s Guide.
Red
Yellow
Blue
Comfort Control
White Green Yellow
Orange
Red
Blue
Field wiring
Heat Pump
W2 Pink
W3 Brown
W1 White
Green
W
G Y O R
B
White Green Yellow Orange
Red
Blue
Red
Blue
Air Handler
R - Red
Orange
Black
(X2)
Red
Yellow
Blue
B - Blue
Y - Yellow
• * For multiple stages of electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat
18-BC85D1-2 15
GAF2 Air Handler Hook-up Diagram
Heat Pump
W1 White
Green
Comfort Control
White Green
Yellow
Orange Red Blue
W G
Y O R
B
White Green Yellow Orange
Red
Blue
Field wiring
GAF2-36M Air Handler Hook-up Diagram
Red
Blue
Air Handler
R - Red
B - Blue
Y - Yellow
Orange
Black
(X2)
Red
Yellow
Blue
White
Green
Red
Blue
Yellow YI
Comfort Control
White
W
Green
G
Yellow
Y
Orange
O
Red
R
Blue
B
Field wiring
16 18-BC85D1-2
Orange
Purple YO
Heat Pump
Air Handler
• YI and YO connections must be made as shown
• Internally mounted condensate switch is optional and must be ordered separately
• If a 3rd party condensate overflow switch is installed, it should be wired between Y of the thermostat and YI of the EEV control.
Yellow
Orange
Blue
Red
Black
(X2)
11.3 Defrost Control
Defrost controls have a selectable termination temperature. As shipped, defrost will terminate at 47°F. For a higher termination temperature, cut Jumper J2 to achieve 70°F when at or below 30°F ambient. See Service Facts shipped in the outdoor unit for more information.
Pin Identification (See Illustration at right)
1. TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two (2) seconds to initiate a forced defrost. Remove the short after defrost initiates.)
Defrost Control Checkout
Normal operation requires:
• LED on board flashing 1 time/second.
• 24V AC between R & B.
• 24V AC between Y & B with unit operating.
• Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.
If a defrost control problem is suspected, refer to the service information in control box.
Defrost Termination Temperatures
Outdoor
Temperature
As
Shipped
Cut
Jumper 2
All < 6°F
>22°F 47°F
10°F–22°F ODT + 25°F
6°F–10°F 35°F
>30°F 47°F
6°F–30°F 70°F
Termination
Temperature
12 min. or 35°F
every 3 hrs.
Defrost Board Detail
JUMPER 2
TEST PINS
FRC_DFT
TST
J1 J2 J3
TEST_COMMON
U1
18-BC85D1-2 17
Section 12. Electrical - High Voltage
WARNING
!
12.1 High Voltage Power Supply
LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be nec­essary to work with live electrical components. Failure to follow all electrical safety precau­tions when exposed to live electrical compo­nents could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electri­cal conduit is recommended whenever vibra­tion transmission may create a noise problem within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.
18 18-BC85D1-2
Section 13. Start Up
OFF
DON
E
CANCEL
ON
OFF
E
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have
been completed.
STEP 2 - Set System Thermostat to OFF.
STEP 3 - Turn on disconnect(s) to apply power
to the indoor and outdoor units.
STEP 4 - Wait one (1) hour before starting the unit if compressor crankcase heater acces­sory is used and the Outdoor Ambient is below 70ºF.
STEP 5 - Set system thermostat to ON.
60 MIN.
ON
DON
CANCEL
18-BC85D1-2 19
Section 14. System Charge Adjustment
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recom­mended method of charging above 55º F ambi­ent outdoor temperature. See Section 14.2.
For outdoor temperatures below 55º F, see Sec­tion 14.3.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera­ture is above 55º F.
See Section 14.2 for
Outdoor
Temperatures
Above 55º F
See Section 14.3 for
Outdoor
Temperatures
Below 55º F
120º F
55º F
Outdoor Temp 1
55º F
Outdoor Temp 2
For best results the indoor temperature should be kept between 70º F to 80º F.
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
80º F
70º F
Indoor Temp
LIFT
20 18-BC85D1-2
STEP 2 -
Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
1 1/2 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Use Design Subcool Value
Add 1° of Subcooling
Add 3°
Add 2°
2 1/2 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Use Design Subcool Value
Add 2° of Subcooling
Add 1° of Subcooling
Add 4°
Add 3°
3 1/2 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 1° of Subcooling
Use Design Subcool Value
Add 3° of Subcooling
Add 2° of Subcooling
Add 6°
Add 5°
2 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Use Design Subcool Value
Add 1° of Subcooling
Add 4°
Add 2°
3 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Use Design Subcool Value
Add 3° of Subcooling
Add 1° of Subcooling
Add 5°
Add 4°
Add 2°
4 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 1° of Subcooling
Use Design Subcool Value
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 6°
5 Ton Heat Pump
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
60
50
40
30
25
20
15
10
Design
0
REFRIGERANT LINE LIFT (FEET)
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FEET)
Add 2° of Subcooling
Add 1° of Subcooling
Add 5° of Subcooling
Add 4° of Subcooling
Add 3° of Subcooling
Add 6°
STEP 3 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a mini­mum of 20 minutes to stabilize before accurate measurements can be made.
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
20 MIN.
18-BC85D1-2 21
3
STEP 4 - Measure the liquid line temperature and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refriger­ant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using Table 14.2.
Example: Assume a 12º F Final Subcooling
value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in the left column.
3. The Liquid Gage Pressure should be ap­proximately 327 PSIG. (This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row.
Table 14.2
R-410A REFRIGERANT CHARGING CHART
LIQUID
TEMP
F)
(
°
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
FINAL SUBCOOLING (
8910 11 12 13 14
LIQUID GAGE PRESSURE (PSI)
179 182 185 188 191 195 198
195 198 201 204 208 211 215
211 215 218 222 225 229 232
229 232 236 240 243 247 251
247 251 255 259 263 267 271
267 271 275 279 283 287 291
287 291 296 300 304 309 313
309 313 318 322 327 331 336
331 336 341 346 351 355 360
355 360 365 370 376 381 386
381 386 391 396 402 407 413
407 413 418 424 429 435 441
435 441 446 452 458 464 470
464 470 476 482 488 495 501
495 501 507 514 520 527 533
From Dwg. D154557P01 Rev.
107 °F
F)
°
22 18-BC85D1-2
Cooling
42
Heating
PRESSURE TABLES FOR 4TWB30**
*AM4A0****** Air Handler
STEP 6 - Adjust refrigerant level to attain proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
1. Connect gages to refrigerant bottle and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid line temperature and Liquid Gage Pressure matches the charging chart Final Subcooling value.
Recover refrigerant if the Liquid Gage Pres­sure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condi­tion to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent leaks. Tighten finger tight plus an ad­ditional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Tables in the Service Facts to verify typical performance.
20 MIN.
(Example only - see Service Facts)
Outdoor Size & AH
OD ** 18 24 30 36 AH****** A18S11 A24S21 A30S21 A36S31 B42S31 C48S41 C60S51
Discharge Pressure (PSIG)
115 510 490 515 515 540 110 480 460 485 485 510 105 450 435 455 455 480 100 425 405 425 425 450
95 390 375 395 395 420
90 1
365 350
85 340 325 335 335 365 80 315 305 320 320 345 75 290 285 300 300 320 70 275 265 280 280 300 65 255 245 260 260 280
Outdoor Temperature (Degree F)
60 235 225 225 225 260
Outdoor Size & AH
OD ** 18 24 30 36 AH****** A18S11 A24S21 A30S21 A36S31 B42S31 C48S41 C60S51
Outdoor
Indoor Wet
Temp.
Bulb
(Degree F)
(Degree F)
110
100
90 1
80
70
60
OUTDOOR TEMPERATURE (Degree F)
Suction Pressure (PSIG)
71 154 153 154 155 154 67 146 146 147 148 146 63 138 139 139 140 137 59 131 132 133 134 130
71 149 148 150 151 150 67 141 141 143 144 142 63 134 134 136 137 134 59 127 128 129 131 126
71 145 144 147 148 146
67 2
137 137
63 130 131 133 134 131 59 123 124 127 127 123
71 141 141 144 146 144 67 134 134 137 139 136 63 127 128 131 132 128 59 120 122 124 125 121
71 138 138 141 143 141 67 131 131 134 136 133 63 124 125 128 129 126 59 117 119 122 123 118
71 135 135 139 141 138 67 128 128 132 134 131 63 121 122 125 127 123 59 114 116 119 121 116
42 3
48 60
370 4
370 390
3
48 60
139 4
141 138
65
55
45
35
25
15
Outdoor Temperature (Degree F)
5
-5
(Degree F)
Outdoor Temperature
Outdoor Size & AH
OD ** 18 24 30 36 42 48 60 AH****** A18S11 A24S21 A30S21 A36S31 B42S31 C48S41 C60S51
Indoor Entering (Deg.F)
Discharge Pressure (PSIG)
80 480 485 435 445 445 70 440 445 395 405 405 60 400 405 355 365 365
80 455 460 410 420 415 70 415 420 370 385 380 60 375 380 335 345 345
80 430 435 390 395 395 70 390 390 350 360 355
60 350 355 315 325 320
80 415 420 375 380 380 70 370 375 335 345 340 60 335 335 295 305 305
80 390 390 355 365 355 70 350 350 315 325 320 60 310 310 280 285 285
80 370 370 335 345 335 70 330 330 295 305 300 60 290 290 265 270 265
80 350 350 320 325 320 70 310 310 275 285 280 60 270 270 245 255 245
80 335 335 300 315 305 70 290 290 265 275 265 60 255 255 225 235 230
Outdoor Size & AH
OD ** 18 24 30 36 42 48 60 AH****** A18S11 A24S21 A30S21 A36S31 B42S31 C48S41 C60S51
Suction Pressure (PSIG)
65 142 150 138 142 134 55 120 127 116 120 114 45 100 105 96 98 94
35 83 89 82 83 81 25 69 74 67 68 66 15 56 60 53 55 53 5 44 49 42 44 42
-5 35 40 32 35 33
18-BC85D1-2 23
STEP 9 - Record System Information for refer­ence.
Record system pressures and temperatures after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
Suction Gage Pressure = __________ PSIG
Measured Liquid Line Temp = __________ º F
14.3 Subcooling Charging Below 55º F Outdoor Temp. (In Heating Only)
The Subcooling Charging method in cooling is not recommended below 55º F outdoor tem-
perature.
The only recommended method of charging at outdoor temperatures below 55º F is weighing
in the charge in heating mode.
STEP 1 - Determine additional charge.
From the nameplate label (shown in Section
12.1), record namplate charge below.
Note: The nameplate charge value represents the amount of refrigerant shipped in the outdoor unit and is compatible with 15 feet of AHRI rated
Tonnage
refrigerant lines and the smallest AHRI rated coil.
1.5 – 2 Ton 5/8" 3/8" 3 oz 8 oz 14 oz 20 oz 25 oz
Table 14.3
TUBING INFORMATION
LINE TYPE
Suction
Line
Liquid
20 ft 30 ft 40 ft 50 ft 60 ft
Line
REFRIGERANT TO ADD AT
SPECIFIED ADDITIONAL
LENGTH
Using Table 14.3, find the charge associated with the additional length of tubing above 15 ft. and record it below.
Namplate charge = ____________ Oz.
Charge adder = ______________ Oz. (from Table 14.2)
24 18-BC85D1-2
2.5 – 3.5 Ton 3/4" 3/8" 3 oz 9 oz 15 oz 21 oz 27 oz
4 – 5 Ton 7/8" 3/8" 3 oz 9 oz 16 oz 22 oz 28 oz
STEP 2 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a mini­mum of 20 minutes to stabilize before accurate measurements can be made.
STEP 3 - Check the liquid line temperature and liquid gage pressure to obtain a minimum of 10º subcooling in heating mode.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSIG
STEP 4 - Add charge if a minimum of 10º sub­cooling is not obtained with the namplate charge plus additional charge previously added.
20 MIN.
STEP 5 - Return to site for adjustment.
Important: Return in the spring or summer to
accurately charge the system in the cooling mode with outdoor ambient above 55º F.
18-BC85D1-2 25
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if nec­essary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Leak check refrigerant lines. ........................................ [ ]
2. Properly insulate suction lines and fittings. ................... [ ]
3. Properly secure and isolate all refrigerant lines. ........... [ ]
4. Seal passages through masonry. If mortar is used, prevent mortar from coming
into direct contact with copper tubing. .......................... [ ]
5. Verify that all electrical connections are tight. ............... [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation. .................................................. [ ]
7. Be sure that indoor coil drain line drains freely. Pour water
into drain pan. ............................................................... [ ]
8. Be sure that supply registers and return grilles are open
and unobstructed. ......................................................... [ ]
9. Be sure that a return air filter is installed. ..................... [ ]
10. Be sure that the correct airflow setting is used.
(Indoor blower motor) ................................................... [ ]
11. Operate complete system in each mode to
ensure safe operation. .................................................. [ ]
26 18-BC85D1-2
PP
15.2 Troubleshooting
WHAT TO CHEC K MOD E
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Head Pressure To o High
Head Pressure To o Low
Suction Pressure To o High
Suction Pressure To o Low
Liquid Refrig. Floodback (TXV/EEV)
Liquid Refrig. Floodback (Cap. Tube)
I.D. Coil Frosting
Compressor Runs Inadequate or No Cooling/Htg
ELECTRICAL
Compressor & O.D. Fan Won’t Start
Compressor Will Not Start But O.D. Fan Runs
O.D. Fan Won’t Start
Compressor Hums But Won’t Start
Compressor Cycles on IOL
I.D. Blower Won’t Start
DEFROST
Unit Won’t Initiate Defrost
Defrost Te rminates on Time
Unit Icing Up
HIG H VOLTAGE WIRING
COM PRE SSOR IOL
POWE R SUPPLY
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
P
P
P
P
START CA PAC ITOR
RUN C APACITOR
P
P
P
S
P
S
P
P
P
S
P
S
P
P
CON TROL TRA NSFO RME R
CON TAC TOR CONTACTS
LOW VOLTAGE WIR ING
START RE LAY
S
S
P
S
S
P
P
P
S
S
P
S
S
P
S
S
P
S
S
P
REF. UNDER CHA RGE
INE FFI CIEN T COMP.
P
P
P
P
P
P
P
S
S
EXC ESS IVE E VAP. LOAD
REF. OVERCH ARGE
S
S
S
S
S
S
S
S
STU CK COMPR ESSOR
LOW VOLTAGE FUSE
CON TAC TOR COIL
THE RMO STAT
S
P
S
PPP
S
P
S
S
S
S
S
S
S
S
S
S
P
S
S
P
S
NON CON DENS ABL ES
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
O.D. AIR R ECIRCUL AT ION
TXV /EE V STU CK OP EN
RES. O.D. A IRFLOW
P
S
P
S
P
S
S
S
S
S
P
S
S
S
S
S
S
S
C - Cooling H - Heating P - Primary Causes S - Secondary Causes * - 3 Phase Only
REF. CIR. RES TRI CTIONS
RES. I.D. AIRFLOW
SUP ERH EAT
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
CHE CK VALVE LEA KING
*
SOV COIL D EFEC TIV E
SOV LEAKI NG
S
P
S
S
S
P
S
S
P
P
S
P
S
P
S
DEF ROST CONTROL DEF.
DEF ROST RELAY DEF.
S
S
S
P
P
S
S
S
S
S
S
S
P
P
P
P
P
P
P
S
S
P
P
18-BC85D1-2 27
28 18-BC85D1-2
The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Representative-only illustrations included in this document.
© 2013 Trane 04/13
Loading...