Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
February 2013VRF-SVX30A-EN
Introduction
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required. Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
CAUTIONs
NOTICE
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs). Not all refrigerants containing these compounds
have the same potential impact to the environment. Trane
advocates the responsible handling of all refrigerantsincluding industry replacements for CFCs such as HCFCs
and HFCs.
Important Responsible Refrigerant Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain refrigerants
and the equipment that is used in these service procedures.
In addition, some states or municipalities may have
additional requirements that must also be adhered to for
responsible management of refrigerants. Know the
applicable laws and follow them.
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Personal Protective Equipment (PPE)
Required!
Failure to wear proper PPE for the job being undertaken
could result in death or serious injury. Technicians, in
order to protect themselves from potential electrical,
mechanical, and chemical hazards, MUST follow
precautions in this manual and on the tags, stickers,
and labels, as well as the instructions below:
•Before installing/servicing this unit, technicians
MUST put on all PPE recommended for the work
being undertaken. ALWAYS refer to appropriate
MSDS sheets and OSHA guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection, and handling recommendations.
•If there is a risk of arc or flash, technicians MUST put
on all PPE in accordance with NFPA 70E or other
country-specific requirements for arc flash
protection, PRIOR to servicing the unit.
Copyright
This document and the information in it are the property of
Trane and may not be used or reproduced in whole or in
part, without the written permission of Trane. Trane
reserves the right to revise this publication at any time and
to make changes to its content without obligation to notify
any person of such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
Digit 4: Configuration Type (also see separate tab)
B = mini 4-way cassetteL = Slim duct type (low pressure)
C = 4-way cassetteA = HSP duct type high pressure)
D = MSP duct type (mid-pressure)X = Ceiling
E = 1-way cassetteW = High-wall
A = First design sequence
B = Second design sequence
VRF-SVX30A-EN5
Preparing for Installation
Preparing for Installation
Accessories
In addition to product literature, the following accessories are supplied with this unit. The type and
quantity may differ, depending on the model.
Installation plate
Location Considerations
When deciding on a location for the indoor unit, the following factors must be considered:
•The air inlet and outlet must be unobstructed.
•The wall or ceiling must support the weight of the unit.
•The wall or ceiling must not be subject to vibration.
•Pre-plan for easy and short routing of the refrigerant tubing and wiring to the outdoor unit.
•The air must circulate freely in the area to be cooled/heated.
•Sufficient clearance must be maintained around the unit.
•Condensate must be managed correctly and safety away from the unit.
•The unit should be installed in a way that prevents unauthorized access.
•The unit must not be installed in an area that is damp or could come into contact with water
(such as a laundry room).
•The unit must not be exposed to direct sunshine or to other direct heat sources.
•The filter must be able to be removed and cleaned easily.
•The unit should be placed as far as possible from fluorescent lights so the remote control is not
subject to interference.
•Care should be taken to prevent harmonics generated by loose or unsupported material in close
proximity to a running unit.
•The unit must not be installed in an area that is exposed to salt, machine oil, sulfide gas, or
corrosive environmental conditions.
6 VRF-SVX30A-EN
Service Clearances
11.81 in. (300 mm)
4.9 in. (125 mm)
4.9 in. (125 mm)
Preparing for Installation
VRF-SVX30A-EN7
Installation
5.51
(140)
2.56 (65)
1.34 (34)
1.34 (34)
2.68
(68)
Pipe hole:
Pipe hole:
4.72
(120)
1.06 (27)
1.06 (27)
2.68
(68)
2.56 (65)
Pipe hole:
4TVW0007B100NB
4TVW0009B100NB
4TVW0012B100NB
4TVW0018B100NB
4TVW0020B100NB
4TVW0024B100NB
Installation
Review “Installation Considerations” before proceeding with installation.
Follow the procedures in these sections in the order given.
Notes:
Mounting the Unit
The wiring, piping, and drain hose can be connected to run from the indoor unit in one of the
following directions:
•Right (A)
•Left (B)
•Underside (C)
•Rear (right or left)
• Install the Y-joint before installing the indoor unit.
• Install an electronic expansion valve (EEV) on this unit. Refer to the EEV Kit installation
guide (VRF-SVN43) for information.
1. Determine the position of the piping and drain hose and drill a 2.56 in. (65 mm) hole that slants
slightly upward.
2. Attach the installation plate to a wall or a window frame, considering the weight of the unit.
Refer to the following dimensional diagrams.
• If you are mounting the installation plate to a concrete wall, use anchor bolts making sure
they do not project more than 0.8 in. (20 mm).
• For an existing structure, attach the installation plate to wall studs or take other necessary
precautions for supporting the unit.
• For mounting on a window frame, install wood mounting supports for the unit. Attach the
installation plate to the wooden uprights using tapping screws.
3. Install the unit on the plate.
8 VRF-SVX30A-EN
Purging the Unit
Liquid refrigerant port
Gas refrigerant port
The unit is shipped from the factory with a holding charge of nitrogen. All of this gas must be
purged from the unit.
To purge the unit, remove the caps from the ends of both gas and liquid refrigerant pipes. Make
sure all gas has escaped before connecting the piping.
Note: To prevent dirt or foreign objects from getting into the pipes during installation, do not
Installation
remove the caps completely until you are ready to connect the piping.
VRF-SVX30A-EN9
Installation
Correct: 90º
Oblique
Rough
Burr
Length of pipe extending above flare bar
Pipe
Flaring
bar
Installing Refrigerant Piping
Connect field-supplied piping using flared connections (not supplied) or by brazing. The large unit
port is for gas refrigerant; the small one is for liquid refrigerant.
Cut or extend field-supplied piping as needed. Use the following procedures.
System Failure!
If brazing is used for pipe connections, a nitrogen purge is required to prevent the formation of
copper oxides inside the piping. Failure to follow this procedure could damage the system.
•Before connecting the pipes, make sure they are free of dirt and debris.
•Use insulated, unwelded, degreased, and deoxidized copper pipe (Cu-DHP type according to
ISO 1337 or UNI EN 12735-1) suitable for an operating pressure of at least 609.15 psi (4200 kPa)
and a burst pressure of at least 3002.28 psi (20,700 kPa). Copper pipe for hydro-sanitary
applications is unsuitable.
•For sizing and limits (height difference, line length, maximum bends, refrigerant charge, and
so on) see the outdoor unit installation manual.
•All refrigerant connections must be accessible for servicing and maintenance.
Pipe Cutting
Required tools:
•Pipe cutter
•Reamer
•Pipe holder
1. Using a pipe cutter, cut the pipe so that the cut edge is at 90° to the side of the pipe.
2. Use a reamer to remove all burrs at the cut edge.
See examples of correctly and incorrectly cut pipes.
NOTICE
Flared Pipe Connections
Clutch type and wing nut type flare tools are available for flared pipe connections.
1. Slide the flare nut over the pipe to be flared.
2. Slide the end of the pipe into the hole on the flaring bar that fits the pipe, leaving a length of
pipe, determined by tool type (see table), extending above the flaring bar. Clamp it down.
10 VRF-SVX30A-EN
Installation
Yoke
Flaring bar
Copper pipe
Flare nut
Inclined
Damaged
surface
Uneven
thickness
Correct
Cracked
R.016–.031
45°±2°
90°±2°
R-410A clutch type
Clutch typeWing nut type
Conventional flare tool
0–0.020 in.0.04–0.06 in.0.06–0.08 in.
3. Attach the yoke to the flaring bar, centering the conical part over the end of the pipe that is
extending above the flaring bar.
4. Tighten the yoke securely to flare the end of the pipe.
5. Remove the pipe. The end of the pipe that you flared should look like the end of a trumpet. See
examples of correctly and incorrectly flared pipes.
6. Align the pipes and tighten the flare nuts manually and then with a spanner torque wrench,
applying the torque according to pipe dimensions:
Do not work in confined spaces where refrigerant or other hazardous, toxic or flammable gas
may be leaking. Refrigerant or other gases could displace available oxygen to breathe, causing
possible asphyxiation or other serious health risks. Some gases may be flammable and or
explosive. If a leak in such spaces is detected, evacuate the area immediately and contact the
proper rescue or response authority. Failure to take appropriate precautions or to react properly
to such potential hazards could result in death or serious injury.
Explosion Hazard!
Never use an open flame to detect gas leaks. It could result in an explosion. Use a leak test
solution for leak testing. Failure to follow recommended safe leak test procedures could result
in death or serious injury or equipment or property-only-damage.
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene,
oxygen or compressed air or mixtures containing them for pressure testing. Do not use
mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure
testing as they may become flammable and could result in an explosion. Refrigerant, when
used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to
follow these recommendations could result in death or serious injury or equipment or
property-only damage.
Do not exceed unit nameplate design pressures when leak testing system. Failure to follow
these instructions could result in an explosion causing death or serious injury.
WARNI NG
WARNI NG
Notes:
• All required piping pressure tests must be completed in accordance with national and/or
local codes.
• When leak-testing refrigerant systems, observe all safety precautions.
• Leak test only one circuit at a time to minimize system exposure to potentially harmful
moisture in the air.
• Use R-410A refrigerant gas as a tracer for leak detection and use oil-pumped dry nitrogen
to develop required test pressures.
1. Close liquid line angle valve.
2. Connect R-410A refrigerant cylinder to high side charging port (at condenser or field supplied
discharge line access port). Add refrigerant to reach pressure of 12 to 15 psig.
3. Disconnect refrigerant cylinder. Connect dry nitrogen cylinder to high side charging port and
increase pressure to 150 psig. Do not exceed high side (discharge) unit nameplate design
pressure. Do not subject low side (suction) components to high side pressure.
4. Check all piping joints, valves, etc. for leaks. Recommend using electronic detector capable of
measuring 0.1 oz/year leak rate.
5. If a leak is located, use proper procedures to remove the refrigerant/nitrogen mixture, break
connections and make repairs. Retest for leaks.
6. Make sure all service valves are open.
12 VRF-SVX30A-EN
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.