Trane 4TTZ0024A, 4TWZ0024A, 4TTZ0036A, 4TWZ0036A, 4TTZ0048A Installer's Manual

...
Page 1
WARNING
!
WARNING
!
CAUTION
!
UNIT CONTAINS R-410A REFRIGERANT!
R-410A OPERATING PRESSURE EXCEEDS THE LIMIT OF R-22. PROPER SERVICE EQUIPMENT IS REQUIRED. FAILURE TO USE PROPER SERVICE TOOLS MAY RESULT IN EQUIPMENT DAMAGE OR PERSONAL INJURY.
SERVICE
USE ONLY R-410A REFRIGERANT AND
APPROVED POE/AB COMPRESSOR OIL.
1’ Behind
From Service Panel
3’
5’ Above
Unrestricted
18-BC53D2-3
Installer’s Guide
Air Conditioner/Heat Pump
4TTZ0/4TWZ0 with ComfortLink™ II and Charge Assist
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon
completion of work.
These instructions and illustrations do not cover all varia­tions in systems nor provide for every possible contingency to be met in connection with installation. All phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES. Should further information be desired or should
particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your install­ing dealer or local distributor.
A. GENERAL
Single Unit Installation
1
This information is intended for use by individuals pos ses s ing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air condition ing product may result in personal injury and or property damage. The manufacturer or seller cannot be respon sible for the interpretation of this information, nor can it assume any liability in connection with its use.
NOTICE: Trane has always recommended installing Trane approved matched indoor and outdoor systems.
The benefits of installing approved matched systems are maxi­mum efficiency, optimum performance and best overall system reliability.
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a
POE/AB To limit this “hygroscopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE/AB oil, reference Retrofit Bulletin TRN-APG02­EN. Check for transportation damage after unit is uncrated. Re port promptly, to the carrier, any damage found to the unit.
oil that readily absorbs moisture from the atmosphere.
Check for transportation damage after unit is uncrated. Report promptly, to the carrier, any damage found to the unit.
To determine the electrical power requirements of the unit, refer to the nameplate of the unit. The electrical power available must agree with that listed on the nameplate.
B. LOCATION AND PREPARATION OF THE UNIT
(INFORMATION APPLICABLE TO HEAT PUMPS ONLY:)
The Heat Pump has been designed and manufactured to withstand and operate in severe winter conditions. However, there are pre­cautionary steps which should be taken at the time of installation which will help assure the efficient operation of the unit. It is rec-
ommended that these precautions be taken for units being installed in areas where snow accumulation and prolonged below freezing temperatures occur.
1. Units should be elevated three (3) to twelve (12) inches above the pad or roof top, depending on local weather. This additional height will allow better drainage of snow and ice (melted dur­ing defrost cycle) prior to its refreezing. This should prevent a
build-up of ice around the unit which occurs when unit is not elevated. Insure that drain holes in unit base pan are
not obstructed preventing draining of defrost water.
2. If possible, avoid locations that are likely to accumulate snow drifts. If not possible, a snow drift barrier should be installed around the unit to prevent a build-up of snow on the sides of the unit and should be of sufficient distance from the unit to prevent restriction of airflow to and from the unit. Also allow for proper maintenance space. The barrier should be constructed of materials which will blend in with the building design.
3. Avoid locating the unit where condensation and freezing of de­frost vapor may annoy the customer. For instance, installing the unit under a bedroom, kitchen, or picture window may be annoying to the customer since condensate and fog will occur during the defrost cycle.
4. Avoid locating the unit under the eaves or other overhead structures as sizeable icicles may form and the unit may be damaged by these falling icicles.
Page 2
Installer’s Guide
CAUTION
!
WARNING
!
BASEPAN
2
TAB REMOVAL
(INFORMATION APPLICABLE TO ALL UNITS:)
1. When removing unit from the pallet, notice the tabs on the basepan. Remove tabs by cutting with a sharp tool as shown in Figure 2 and slide unit off of pallet.
2. The unit should be set on a level support pad at least as large as the unit base pan, such as a concrete slab. If this is not the application used please refer to Application Guide SSC-APG005-EN.
3. The support pad must NOT be in direct contact with any structure. Unit must be positioned a minimum of 12" from any wall or surrounding shrubbery to insure adequate airflow. Clearance must be provided in front of control box (access panels) and any other side requiring service access to meet National Electrical Code. Also, the unit location must be far enough away from any structure to prevent excess roof run-off water from pouring directly on the unit. Do not locate unit(s) close to bedroom(s).
4. The top discharge area must be unrestricted for at least five (5) feet above the unit. See Figure 1.
5. When the outdoor unit is mounted on a roof, be sure the roof will support the unit’s weight. Properly selected isolation is recommended to prevent transmission to the building struc­ture.
6. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed eighty (80) feet.
7. If outdoor unit is mounted above the air handler, maxi mum lift should not exceed twenty-five (25) feet (suction line). If air handler is mounted above condensing unit, maximum lift should not exceed twenty-five (25) feet (liquid line).
8. Locate and install indoor coil or air handler in accordance with instruction included with that unit.
C. INSTALLING REFRIGERANT LINES
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Condensing units have provisions for braze connections.
Pressure taps are provided on the service valves of outdoor unit for compressor suction and liquid pressures.
The indoor end of the recommended refrigerant line sets may be straight or with a ninety (90) degree bend, depending upon situation requirements. This should be thoroughly checked out before ordering refrigerant line sets.
NOTE: The gas line must always be insulated. Liquid lines that run through attic space must also be insulated.
The units are factory charged with the system charge required when using fifteen (15) feet of rated connecting line. See unit nameplate.
Final refrigerant charge adjustment is necessary. Use Charge Assist™ or the Manual Charging procedure found in the outdoor unit Service Facts. Charge level can always be verified with the Refrigerant Charging Chart found in the Service Facts.
NOTE: Large diameter tubing will be very difficult to rebend once it has been shaped.
3. Determine the best starting point for routing the refrigerant tubing — INSIDE OR OUTSIDE THE STRUCTURE.
4. Provide a pull-thru hole of sufficient size to allow both liquid and gas lines.
5. Be sure the tubing is of sufficient length.
6. Uncoil the tubing — do not kink or dent.
7. Route the tubing making all required bends and properly secure the tubing before making connections.
8. To prevent a noise within the building structure due to vibra­tion transmission from the refrigerant lines, the following precautions should be taken:
a. When the refrigerant lines have to be fastened to floor
joists or other framing in a structure, use isolation type hangers.
b. Isolation hangers should also be used when refrigerant
lines are run in stud spaces or enclosed ceilings.
c. Where the refrigerant lines run through a wall or sill, they
should be insulated and isolated.
d. Isolate the lines from all ductwork.
D. SERVICE VALVE OPERATION
BRASS LIQUID LINE SERVICE VALVE
The Brass Liquid Line Service Valve is factory shipped in the seated position to hold factory charge. The pressure tap service port (when depressed) opens only to the field brazing side of the valve when the valve is in the seated position. The liquid line valve is not a back seating valve (see WARNING below).
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn valve stem counterclockwise only until the stem contacts the rolled edge. (See Figure 3). No torque is required. Failure to follow this warning will result in abrupt re­lease of system charge and may result in personal injury and/or property damage.
BRASS GAS LINE BALL SERVICE VALVE
The Brass Gas Line Service Valve is shipped in the closed position to hold the factory refrigerant charge. The pressure tap service port (when depressed) opens only to the field brazing side when the valve is in the closed position.
The Gas Line Ball Service Valve is full open with a 1/4 turn. See Figure 4.
BRAZING REFRIGERANT LINES
1. Remove lower access cover to access service valves.
2. Before brazing, remove plugs from external copper stub tubes. Clean internal and external surfaces of stub tubes prior to brazing.
3. Cut and fit tubing, minimizing the use of sharp 90° bends.
4. Insulate the entire gas line and its fittings.
5. Do NOT allow uninsulated liquid line to come in direct con­tact with bare gas line.
3
LIQUID LINE SERVICE VALVE
1. Determine the most practical way to run the lines.
2. Consider types of bends to be made and space limitations.
© 2009 Trane 18-BC53D2-3
Page 3
Installer’s Guide
WARNING
!
CAP
1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
GAS LINE CONNECTION
UNIT SIDE OF VALVE
PRESSURE TAP PORT
4
6. Precautions should be taken to avoid heat damage
NOTE: Use care to make sure that no moisture enters pressure tap port, while wet rag is being used.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepan.
7. Use a Dry Nitrogen Purge and Brazing Alloy without flux
8. Braze using accepted good brazing techniques.
LEAK CHECK
IMPORTANT: Replace pressure tap port valve core before attaching hoses for evacuation.
GAS LINE BALL SERVICE VALVE
to the pressure tap valve core during brazing. It is recommended that the pressure tap port valve core be removed and a wet rag wrapped around the valve body.
when brazing the field line to the copper factory connection. Flow dry nitrogen into either valve pressure tap port, thru the tubing and out the other port while brazing.
NOTE: DO NOT VENT REFRIGERANT INTO THE ATMOSPHERE.
NOTE: A 3/16" Allen wrench is required to open liquid line service valve. A 1/4" Open End or Adjustable wrench is required to open gas line valve. A 3/4" Open End wrench is required to take off the valve stem cap.
9. The liquid line shut-off valve can now be opened. Remove shut-off valve cap. Fully insert hex wrench into the stem and backout counterclockwise until valve stem just touches rolled edge (approximately five [5] turns) observing WARNING statement on page 2. See Figure 3.
10. Replace liquid service pressure tap port cap and valve stem cap. These caps MUST BE REPLACED to prevent leaks. Replace valve stem and pressure tap cap finger tight, then tighten an additional 1/6 turn.
11. The gas valve can now be opened. For a ball type gas valve, open the gas valve by removing the shut-off valve cap and turn­ing the valve stem 1/4 turn counterclockwise, using 1/4" Open End or Adjustable wrench. See Figure 4 and refer to Step 8 prior to opening gas valve.
12. The gas valve is now open for refrigerant flow. Replace valve stem cap to prevent leaks. Again, these caps MUST BE RE- PLACED to prevent leaks. Replace valve stem and pressure tap cap finger tight, then tighten an additional 1/6 turn. See Figure 4.
If refrigerant lines are longer than fifteen (15) feet and/or a different size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See unit Service Facts.
E. ELECTRICAL CONNECTIONS
After the brazing operation of refrigerant lines to both the outdoor and indoor unit is completed, the field brazed connections must be checked for leaks. Pressurize through the service valve ports, the in­door unit and field refrigerant lines with dry nitrogen to 350-400 psi. Use soap bubbles or other leak-checking methods to see that all field joints are leak-free! If not, release pressure; then repair!
SYSTEM EVACUATION
NOTE: Since the outdoor unit has a refrigerant charge, the gas and liquid line valves must remain closed.
1. Upon completion of leak check, evacuate the refrigerant lines and indoor coil before opening the gas and liquid line valves.
2. Attach appropriate hoses from manifold gauge to gas and liquid line pressure taps.
NOTE: Unnecessary switching of hoses can be avoided and com plete evacuation of all lines leading to sealed system can be accom­plished with manifold center hose and connecting branch hose to a cylinder of R-410A and vacuum pump.
3. Attach center hose of manifold gauges to vacuum pump.
4. Evacuate until the micron gauge reads no higher than 350 mi­crons.
5. Close off valve to vacuum pump and observe the micron gauge. If gauge pressure rises above 500 microns in one (1) minute, then evacuation is incomplete or system has a leak.
6. If vacuum gauge does not rise above 500 microns in one (1) minute, the evacuation should be complete.
7. With vacuum pump and micron gauge blanked off, open valve on R-410A cylinder and charge refrigerant lines and indoor coil with vapor to tank pressure of R-410A supply.
8. Close valve on R-410A supply cylinder. Close valves on mani­fold gauge set and remove refrigerant charging hoses from liquid and gas pressure tap ports.
Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical com­ponents. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
1. Power wiring and grounding of equipment must comply with national, state and/or local codes.
2. Power supply must agree with equipment nameplate.
3. Install a separate disconnect switch at the outdoor unit.
4. Ground the outdoor unit per code requirements.
5. Provide flexible electrical conduit whenever vibration trans­mission may create a noise problem within the structure.
6. The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the Com­fortLink™ II control and the indoor unit
Table 1 – NEC Class II Control Wiring
ComfortLink™ II Control Wiring
WIRE SIZE MAX. WIRE LENGTH
18 AWG 250 FT
NOTE: The maximum total cable length for the entire Comfort Control communicating system is 500 ft. 18 AWG.
7. Mount the ComfortLink™ II control in accordance with in­struction included with the ComfortLink™ II control. Wire per appropriate hook-up diagram (included in these instructions).
18-BC53D2-3 3
Page 4
Installer’s Guide
FRC_DFT
TEST_COMMON
TST
F. DEFROST CONTROL (HEAT PUMPS ONLY)
The demand defrost control measures heat pump outdoor ambi­ent temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termina­tion of the defrost cycle.
FAULT IDENTIFICATION
A fault condition is indicated by the fault LED on the control board inside the heat pump control box.
In normal operation, the status LED will flash once each second. If the light is flashing more than once per second or not at all, refer to the Service Facts for that unit.
OUTDOOR CONTROL
6
BOARD – PIN IDENTIFICATION
G. COMPRESSOR START UP
After all electrical wiring is complete, SET THE COM­FORTLINK™ II CONTROL SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the ComfortLink™ II con­trol Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up.
PIN IDENTIFICATION (SEE FIGURE 6.)
1. TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)
2. TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)
3. FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two [2] seconds to initiate a forced defrost. Remove the short after defrost initiates.)
DEFROST CONTROL CHECKOUT
Normal operation requires:
a. Status LED on board flashing 1 time/second.
b. 12VDC between D & B.
c. Defrost initiation when FRC_DFT pin is shorted to TEST_
COMMON pin.
If a defrost control problem is suspected, refer to the service infor­mation in control box.
4 18-BC53D2-3
Page 5
Installer’s Guide
7
FIELD WIRING DIAGRAM
COMMUNICATING INDOOR UNIT – COMMUNICATING OUTDOOR UNIT
NOTE: For non-
communicating systems use 24-volt harness accessory BAYACHP024A.
18-BC53D2-3 5
Page 6
Installer’s Guide
8
COMMUNICATING INDOOR UNIT WITH 24V COMFORT CONTROL,
24V 2-STAGE OR 2-STEP COOLING
6 18-BC53D2-3
Page 7
Installer’s Guide
9
COMMUNICATING INDOOR UNIT WITH 24V COMFORT CONTROL,
24V 2-STAGE OR 2-STEP HEAT PUMP
18-BC53D2-3 7
Page 8
Installer’s Guide
e r
OUTDOOR CONTROL BOARD –
CHARGE ASSIST™
CHARGE ASSIST™ PORT
DIRECTION FOR CHARGE ASSIST™
NOTE: Outdoor Temperature (ODT) must be between 55°F and 120°F.
Be sure to set Dip Switches on the Outdoor Control Board for Line Length and Lift before entering Charge Assist™ Mode. (See Sub­cool Charging Table Corrections for Line Length and Rise on the next page or in the Service Facts for the outdoor unit.)
To enter Charge Assist™ Mode, press the MODE button for at least one (1) second. The on-board LEDs will indicate if the system is capable of continuing. For a detailed description of on-board LEDs and their function, see the Service Facts.
The system will take approximately 12-20 minutes to stabilize before the charge can be checked by Charge Assist™. Once the system is stabilized, watch to see which LED turns on next. If the system charge is correct, the “CHARGED” LED will turn on and re­main on for one (1) hour. Once charged, the system will exit Charge Assist™ and control will return to the Comfort Control.
NOTE: Charge Assist™ port is designed for liquid refrigerant charging.
If the system charge is low, the “ADD” LED will turn on and stay on up to one (1) hour or until enough refrigerant is added to reach the required system charge level and turn on the “CHARGED” LED.
When the “ADD” LED is on, the charging solenoid output will be active. This feature works to automatically control refrigerant flow with BAYCAKT001.
If the system charge is high, the “REC” LED will turn on and the unit will exit Charge Assist™. You must recover refrigerant from the system before re-entering Charge Assist™.
For instructions on the Charge Assist™ tool BAYCAKT001, see the Installer's Guide 18-HH15D1-* (the position of the * denotes the latest revision number).
For additional information on manual charging, please see the Service Facts shipped with the outdoor unit.
8 18-BC53D2-3
Page 9
Installer’s Guide
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
Dip Switch 1- ON
Dip Switch 2-ON
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
Dip Switch 3-ON
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
TABLE A TABLE B
These matches ONLY
4TXCB003 Coil Downflow & Horizontal Right Only 4TXCC006 Coil Downflow & Horizontal Right Only
4TEE3_03 Air Handler Downflow & Horizontal Left Only
All other approved, matched systems.
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
TOTAL REFRIGERANT LINE LENGTH (FEET)
TABLE A TABLE B
REFRIGERANT LINE LIFT (FEET)
Dip Switch 2-ON
Dip Switch 3-ON
All other approved, matched systems.
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
Dip Switch 1-ON
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
4TEE3_06 Air Handler 4TXCC008 Coil 4TXCD010 Coil
These matches ONLY
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT
LINE LIFT (FEET)
LOWER
UPPER
MIDDLE
Dip Switch 1- ON
Dip Switch 2-ON
Dip Switch 3-ON
25 20 15
10
0
10 20 25 30 40 60 80
Max Lift
All approved, matched systems.
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
SUBCOOL CHARGING TABLE CORRECTIONS FOR LINE LENGTH AND RISE
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
LOWER Dip Switch 1- ON
MIDDLE Dip Switch 2-ON
Dip Switch 3-ON
UPPER
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
Dip Switch 3-ON
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
Max Lift
25
20
15
10
0
10 20 25 30 40 60 80
4TEE3_10 Downflow & Horizontal Left Only
All other approved, matched systems.
SUBCOOL CHARGING TABLE CORRECTIONS
2-TON HP MODEL ONLY
4-TON HP MODEL ONLY
5-TON HP MODELS ONLY
ALL AC MODELS
18-BC53D2-3 9
AND
3-TON HP MODELS
Page 10
Installer’s Guide
SYSTEM FAULTS
REFRIGE RANT CIRCUIT
Head Pressure Too High
Head Pressure Too Low
Suction Pressure Too High
Suction Pressure Too Low
Liquid Refrig. Floodback (TXV/EEV)
Liquid Refrig. Floodback (Cap. Tube)
I.D. Coil Frosting
Compressor Runs Inadequate or No Cooling/Htg
ELECTRI CAL
Compressor & O.D. Fan Won’t Star t
Compressor Will Not Star t But O.D. Fan Runs
O.D. Fan Won’t Star t
Compressor Hums But Won’t Star t
Compressor Cycles on IOL
I.D. Blower Won’t Start
DEFROST
Unit Won’t Initiate Defrost
Defrost Terminates on Time
Unit Icing Up
WHAT TO CHE CK MODE
POWER SUPPLY
HIGH VOLTAGE WIRING
COMP RESS OR IOL
RUN CAPACITOR
START CAPACITOR
START RELAY
CONTACTOR CONTACTS
LOW VOLTAGE WIRING
CONT ROL TRANSF ORMER
THER MOSTAT
CONTACTOR COIL
LOW VOLTAGE FUSE
STUC K COMPRESSO R
INEF FICI ENT COMP.
REF. UN DERCHARGE
REF. OVERCHARGE
EXCE SSIV E EVAP. LOAD
NONC ONDE NSABLES
RES. O.D. AIRFLOW
O.D. AIR RECIRCULATION
TXV/ EEV STUCK OPE N
SUPE RHEAT
RES. I. D. AIRFLOW
REF. CI R. RESTR ICTIONS
SOV LEAK ING
SOV COIL DEFECTIVE
CHEC K VALVE LE AKING
*
DEFROST REL AY DEF.
DEFROST CON TROL DEF.
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
S
S
S
S
PPP
P
S
S
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
P
P
P
P
P
P
P
S
S
P P
P
P
C - Cooling H - Heating P - Primary Causes S - Secondary Causes * - 3 Phase Only
TROUBLESHOOTING CHART — WHAT TO CHECK
H. OPERATIONAL AND
CHECKOUT PROCEDURES
Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction on page
11. To obtain proper performance, all units must be operated and
charge adjustments made in accordance with procedures found in the Service Facts.
IMPORTANT:
Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring con­nections are tight and wire routing is secure.
I. ELECTRIC HEATERS
Electric heaters, if used, are to be installed in the air handling device according to the instructions accompanying the air handler and the heaters.
J. SEACOAST SHIELD
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at in­stallation time. Please refer to Application Guide SS-APB006-EN: Trane - Sea Coast Applications.
IMPORTANT:
See Limited Warranty information in Use and Care Manual.
10 18-BC53D2-3
Page 11
t
Installer’s Guide
4TTZ0/4TWZ0 OUTLINE DRAWING
NOTE: ALL DIMENSIONS ARE IN MM (INCHES).
MODELS BASE A B C D E F G H J K
4TTZ0024A 4TWZ0024A
4TTZ0036A 4TWZ0036A 4TTZ0048A 4TWZ0048A 4TTZ0060A 4TWZ0060A
4 1369 (53 7/8) 946 (37-1/4) 870 (34-1/4) 5/8 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 1035 (40 3/4)
4 1369 (53 7/8) 946 (37-1/4) 870 (34-1/4) 3/4 3/8 152 (6) 98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 1035 (40 3/4)
From Dwg. D152635 Rev. 15
18-BC53D2-3 11
Page 12
Installer’s Guide
y
MOUNTING HOLE LOCATION
NOTE: ALL DIMENSIONS ARE IN MM (INCHES).
From Dwg. D152637 Rev. 2
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Refrigerant Line, Leak checked ............................................ [ ]
2. Suction Lines and Fittings properly insulated ..................... [ ]
3. Have all Refrigerant Lines been secured and
isolated properly? ................................................................... [ ]
4. Have passages through masonry been sealed? If mortar is used, prevent mortar from coming
into direct contact with copper tubing .................................. [ ]
5. Verify tightness of all electrical connects ............................. [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation ............................................................ [ ]
7. Indoor coil drain line drains freely. Pour water
into drain pan ......................................................................... [ ]
8. Supply registers and return grilles open and
unobstructed........................................................................... [ ]
9. Return air filter installed ...................................................... [ ]
10. ComfortLink™ II control is accurate. Check against a reliable thermometer. Adjust per
instructions with ComfortLink™ II control ......................... [ ]
11. Is correct airflow setting used?
(Indoor blower motor) ............................................................ [ ]
12. Operate complete system in each mode to
insure safe operation. ............................................................ [ ]
Trane www.trane.com
Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.
02/09
Loading...