ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with
the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the
purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Note: The manufacturer recommends installing only approved matched indoor and outdoor systems. All of the manufacture’s split
systems are A.H.R.I. rated only with TXV/EEV indoor systems. Some of the benefits of installing approved matched indoor and
outdoor split systems are maximum efficiency, optimum performance and the best overall system reliability.
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 12
Section 12. Electrical - High Voltage ................................................... 15
Section 13. Start Up .............................................................................. 16
Section 14. System Charge Adjustment ............................................. 17
Section 15. Checkout Procedures and Troubleshooting ................... 23
Section 1. Safety
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
WARNING
!
▲
CAUTION
!
▲
CAUTION
!
▲
WARNING
!
This information is intended for use by individuals
possessing adequate backgrounds of electrical and
mechanical experience. Any attempt to repair a central
air conditioning product may result in personal injury
and/or property damage. The manufacture or seller
cannot be responsible for the interpretation of this
information, nor can it assume any liability in connection with its use.
These units use R-410A refrigerant which operates
at 50 to 70% higher pressures than R-22. Use only
R-410A approved service equipment. Refrigerant cylinders are painted a “Rose” color to indicate the type
of refrigerant and may contain a “dip” tube to allow
for charging of liquid refrigerant into the system. All
R-410A systems use a POE oil that readily absorbs
moisture from the atmosphere. To limit this “hygroscopic” action, the system should remain sealed
whenever possible. If a system has been open to the
atmosphere for more than 4 hours, the compressor oil
must be replaced. Never break a vacuum with air and
always change the driers when opening the system
for component replacement. For specific handling
concerns with R-410A and POE oil reference Retrofit
Bulletins SS-APG006-EN and APP-APG011-EN.
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and troubleshooting of this product, it may be necessary to work
with live electrical components. Failure to follow all
electrical safety precautions when exposed to live
electrical components could result in death or serious
injury.
The appliance is not to be used by persons (including
children) with reduced physical, sensory or mental
capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction.
Children should be supervised to ensure that they do
not play with the appliance.
If using existing refrigerant lines make certain that all
joints are brazed, not soldered.
UNIT CONTAINS R-410A REFRIGERANT!
R-410A operating pressures exceed the limit of R-22.
Proper service equipment is required. Failure to use
proper service tools may result in equipment damage
or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-
PROVED POE COMPRESSOR OIL.
Extreme caution should be exercised when opening
the Liquid Line Service Valve. Turn counterclockwise
until the valve stem just touches the rolled edge. No
torque is required. Failure to follow this warning will
result in abrupt release of system charge and may
result in personal injury and /or property damage.
Scroll compressor dome temperatures may be hot. Do
not touch the top of compressor; it may cause minor to
severe burning.
2 18-AC100D1-3-EN
Section 2. Unit Location Considerations
D
H
W
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
ModelsH x D x W (in)
4TTX6018J
4TTX6024J
4TTX6030J
4TTX6036J
4TTX6042J
4TTX6048J
4TTX6049H
4TTX6060J
4TTX6061J54 x 34 x 37301
* Weight values are estimated.
37 x 30 x 33172
37 x 30 x 33173
44 x 30 x 33195
46 x 34 x 37221
54 x 34 x 37277
54 x 34 x 37281
54 x 34 x 37281
54 x 34 x 37286
When mounting the outdoor unit on a roof, be
sure the roof will support the unit’s weight.
Properly selected isolation is recommended to
alleviate sound or vibration transmission to the
building structure.
Weight* (lb)
Please refer to application bulletin for detailed
mounting information.
2.2 Refrigerant Piping Limits
1. The maximum TOTAL length of refrigerant
lines from outdoor to indoor unit should
NOT exceed 150 feet (including lift).
2. The maximum vertical change should not
exceed 50 feet.
3. Service valve connection diameters are
shown in Table 5.1.
Note: For other line lengths, Refer to Refrigerant Piping Application Guide, SS-APG006-EN
or Refrigerant Piping Software Program, 323312-03 (or latest revision).
Standard
Line Set
150’ Max
TOTAL Line Length
50’
Max
Vertical
Change
18-AC100D1-3-EN 3
50’
Max
Vertical
Change
Min. 12” to
Shrubber
Avoid Install
2.3 Suggested Locations for Best Reliability
Min. 12” to
Shrubber
Ensure the top discharge area is unrestricted for
at least five (5) feet above the unit.
Three (3) feet clearance must be provided in
front of the control box (access panels) and any
other side requiring service.
Do not locate close to bedrooms as operational
sounds may be objectionable.
Position the outdoor unit a minimum of 12” from
any wall or surrounding shrubbery to ensure
adequate airflow.
Outdoor unit location must be far enough away
from any structure to prevent excess roof runoff
water from pouring directly on the unit.
Near Bedrooms
y
y
Min 5’ Unrestricted
Min 3’
Unrestricted
Access Panel
Min. 12”
to Wall
2.4 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time.
4 18-AC100D1-3-EN
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report prompt-
ly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet,
remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such
as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
18-AC100D1-3-EN 5
Section 5. Refrigerant Line Considerations
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Line SizesService Valve Connection Sizes
Model
4TTX6018J3/43/83/43/8
4TTX6024J3/43/83/43/8
4TTX6030J3/43/83/43/8
4TTX6036J7/83/83/43/8
4TTX6042J7/83/87/83/8
4TTX6048J7/83/87/83/8
4TTX6049J7/83/87/83/8
4TTX6060J1-1/83/87/83/8
4TTX6061J1-1/83/87/83/8
Vapor
Line
5.2 Factory Charge
Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing
unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line
length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant
charge adjustment is necessary.
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will
need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be
insulated. DO NOT allow the Liquid Line and
Vapor Line to come in direct (metal to metal)
contact.
Liquid Line
Line Length
Vapor Line
Insulation
6 18-AC100D1-3-EN
5.5 Reuse Existing Refrigerant Lines
▲
CAUTION
!
If using existing refrigerant lines make certain that
all joints are brazed, not soldered.
For retrofit applications, where the existing
indoor evaporator coil and/or refrigerant lines
will be used, the following precautions should
be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise
within the building structure due to vibration
transmission from the refrigerant lines.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
• Minimize the number of 90º turns.
8 Feet Maximum
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure
Liquid Line directly to Vapor line using tape, wire, or other appropriate method every 8 ft.
Comply with National, State, and Local Codes when
isolating line sets from joists, rafters, walls, or other
structural elements.
Joist/Rafter
Isolator
Line Set
Isolation From Joist/Rafter
18-AC100D1-3-EN 7
8 Feet Maximum
Wall
Isolator
Wall
Side View
8 Feet Maximum
Line Set
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line
directly to Vapor Line using tape, wire, or other appropriate
method every 8 ft.
Isolation In Wall Spaces
Sealant
Ductwork
Insulation
Vapor Line
Isolator
Line Set
Isolation Through Wall
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a debur-
ing tool to debur the pipe ends. Clean both
internal and external surfaces of the tubing
using an emery cloth.
DO NOT hang line sets from ductwork
8 18-AC100D1-3-EN
STEP 2 - Remove the pressure tap cap and
3-4” from valve
valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor
coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body
to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
For units shipped with a field-installed external
drier, check liquid line filter drier’s directional flow
arrow to confirm correct direction of refrigeration
flow (away from outdoor unit and toward evaporator coil) as illustrated. Braze the filter drier to
the Liquid Line.
Continue the dry nitrogen purge. Do not remove
the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping
the dry nitrogen purge.
Note: Install drier in Liquid Line.
NOTE: Precautions should be taken to avoid
heat damage to basepan during brazing. It is
recommended to keep the flame directly off of
the basepan.
18-AC100D1-3-EN 9
STEP 5 - Replace the pressure tap valve cores
150 PSIG
after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and
evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 - Check for leaks by using a soapy solution or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks
before continuing.
10 18-AC100D1-3-EN
Section 9. Evacuation
1/4 TURN ONLY
E
GAS LINE CONNECTION
UNIT SID
OF VALVE
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until
the refrigerant lines and indoor coil leak check
and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads
no higher than 350 microns, then close off the
valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation
is complete if the micron gauge does not rise
above 500 microns in one (1) minute.
Once evacuation is complete blank off the
vacuum pump and micron gauge, and close the
valves on the manifold gauge set.
0350
Microns
ON
OFF
1 MIN.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be
completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the
atmosphere
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve
stem 1/4 turn counterclockwise to the fully open
position.
STEP 3 - Replace the valve stem cap to prevent
leaks. Tighten finger tight plus an additional 1/6
turn.
CAP
E
PRESSURE TAP PORT
COUNTERCLOCKWIS
FOR FULL OPEN
POSITION
VALVE STEM
18-AC100D1-3-EN 11
10.1 Open the Liquid Service Valve
▲
WARNING
!
Extreme caution should be exercised when
opening the Liquid Line Service Valve. Turn
counterclockwise until the valve stem just
touches the rolled edge. No torque is required.
Failure to follow this warning will result in abrupt
release of system charge and may result in
personal injury and /or property damage.
Important: Leak check and evacuation must be
completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the
stem and back out counterclockwise until valve
stem just touches the rolled edge (approximately
five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks.
Tighten finger tight plus an additional 1/6 turn.
Cap
Unit Side
of Service
Valve
Service Port
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of
low voltage wiring from the outdoor unit, to the
indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZEMAX. WIRE LENGTH
18 AWG150 Ft.
16 AWG225 Ft.
14 AWG300 Ft.
12 18-AC100D1-3-EN
11.2 Low Voltage Hook-up Diagrams
With TEM 3, 4, 6With TAM 4, 7
• Units with pigtails require wirenuts for connections. Cap all unused wires.
•
•
* TEM6 Onl
** TEM6 only - When using a BK enabled comfort control, cut BK jumper and bypass Y1 and Y2 at the air handle
control to BK of the air handle
•
•
ThermostatAir Handler
24 VAC HOT
FAN
R
G
R
G
Outdoor
Unit
ThermostatAir Handler
24 VAC HOT
FAN
**
24 VAC
Common
SOV
COOL/HEAT
1st STAGE
B/C
Y
B
Blue
O
Y1
B
Y
24 VAC
Common
SOV
COOL/HEAT
1st STAGE
Y2*
HEATING
2nd STAGE
EMERGENCY
HEAT
W1
W2
BK
WH/BLK
W1
White
W2
Pink
BK
WH/BLK
HEATING
2nd STAGE
EMERGENCY
HEAT
R
G
B/C
Y
l
W1
W2
BK
WH/BLK
R
G
B
Blue
O
Y
l
Y
O
W1
White
W2
Pink
BK
WH/BLK
Outdoor
Unit
B
Y
O
In AC systems for multiple stages of electric heat, jumper W1 and W2 together if comfort control has only one stage of heat.
TEM3/4 - Bypass air handler and connect Y from comfort control directly to OD unit
TAM4 only - Wire as shown, no BK is available
TAM7 only - When using a BK enabled comfort control, cut BK jumper on the AFC and connect BK from comfort control to BK of the air handler
18-AC100D1-3-EN 13
y
r
r. Connect BK from comfort
With FurnaceWith Variable Speed Furnace
• Units with pigtails require wirenuts for connections. Cap all unused wires.
•
* If equipped with second stage heat
** When using a BK enabled comfort control, cut BK jumper and bypass Y and YLo at the furnace. Connect BK from comfort control
BK of the furnace
ThermostatFurnaceFurnace
**
Outdoor
Unit
Thermostat
Outdoor
Unit
24 VAC HOT
FAN
24 VAC
Common
R
G
B/C
R
G
B
B
24 VAC HOT
FAN
24 VAC
Common
R
G
B/C
R
G
B
O
COOL
HEATING
W1
W2
In AC systems for multiple stages of heat, jumper W1 and W2 together if comfort control has only one stage of heat.
YY1
W1
W2
Y
COOL
Y1
**
Y
LO
HEATING
W1
W2
BK
W1
W2
BK
**
B
YY
to
14 18-AC100D1-3-EN
Section 12. Electrical - High Voltage
▲
WARNING
!
12.1 High Voltage Power Supply
LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and
troubleshooting of this product, it may be necessary to work with live electrical components.
Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
The high voltage power supply must agree with
the equipment nameplate.
Power wiring must comply with national, state,
and local codes.
Follow instructions on unit wiring diagram located
on the inside of the control box cover and in the
Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the
outdoor unit.
For high voltage connections, flexible electrical conduit is recommended whenever vibration transmission may create a noise problem
within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and
local code requirements.
18-AC100D1-3-EN 15
Section 13. Start Up
OFF
DON
E
CANCEL
ON
OFF
E
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have
been completed.
STEP 2 - Set System Thermostat to OFF.
STEP 3 - Turn on disconnect(s) to apply power
to the indoor and outdoor units.
STEP 4 - Wait one (1) hour before starting the
unit if compressor crankcase heater accessory is used and the Outdoor Ambient is below
70ºF.
STEP 5 - Set system thermostat to ON.
60 MIN.
ON
DON
CANCEL
16 18-AC100D1-3-EN
Section 14. System Charge Adjustment
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recommended method of charging above 55º F ambient outdoor temperature.
For best results the indoor temperature should
be kept between 70º F to 80º F.
Note: It is important to return in the spring or
summer to accurately charge the system in the
cooling mode when outdoor ambient temperature is above 55º F.
120º F
55º F
Outdoor Temp
80º F
70º F
Indoor Temp
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
LIFT
18-AC100D1-3-EN 17
STEP 2 -
50
4°
40
30
1°
25
Use Design Subcooling
1°
15
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
Add 1°
Add 1°
Add 1°
Add 2°
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
50
1°
40
30
25
Use Design Subcooling
15
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
Add 1°
Add 1°
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Add 2°
REFRIGERANT LINE LIFT (FT)
50
1°
40
30
25
Use Design Subcooling
15
1°
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
Add 1°
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Add 2°
Add 1°
50
4°
40
30
25
Use Design Subcooling
15
1°
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
Add 1°
Add 2°
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Add 1°
50
40
30
25
Use Design Subcooling
15
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
Add 1°
Add 1°
Add 1°
Add 2°
Add 4°
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
50
1°
40
1°
30
25
Use Design Subcooling
15
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Add 4°
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Add 2°
Add 1°
Add 1°
50
40
30
1°
25
Use Design Subcooling
1°
15
1°
10
0
20 30 40 50 60 70 80 90 100110 120 130 140 150
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Add 1°
Add 1°
Add 2°
50
1°
40
1°
30
25
Use Design Subcooling
15
10
0
1°
20 30 40 50 60 70 80 90 100 110 120 130 140 150
Add 4°
Add 2°
Add 1°
Add 1°
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FT) - [ includes lift ]
Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
018 Units
030 Units
042 Units
024 Units
036 Units
048 Units
049 Units
060, 061 Units
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
18 18-AC100D1-3-EN
From Dwg. D154557P01 Rev. 3
STEP 3 - Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a minimum of 20 minutes to stabilize before accurate
measurements can be made.
STEP 4 - Measure the liquid line temperature
and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
20 MIN.
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refrigerant temperature and pressure from STEP 4, to
determine the proper liquid gage pressure using
Table 14.2.
Example: Assume a 12º F Final Subcooling
value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in
the left column.
3. The Liquid Gage Pressure should be approximately 327 PSI. (This is the shown as
the intersection of the Final Subcooling column
and the Liquid Temperature row.
Add refrigerant if the Liquid Gage Pressure
is lower than the chart value.
1. Connect gages to refrigerant bottle
and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pressure is higher than the chart value.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condition to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent
leaks. Tighten finger tight plus an additional 1/6 turn.
20 MIN.
20 18-AC100D1-3-EN
STEP 8 - Verify typical performance.
PRESSURE CURVES FOR 4TTX5049E1
Refer to System Pressure Curves in the Service
Facts to verify typical performance.
STEP 9 - Record System Information for reference.
Record system pressures and temperatures
after charging is complete.
(Example only - see Service Facts)
4TXCD010CC3
520
INDOOR ENTERING
WET BULB CURVES
470
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
420
370
320
270
220
LIQUID PRESSURE (PSIG)
170
40 50 60 7080 90 100 110 120
170
INDOOR ENTERING
165
WET BULB CURVES
TOP TO BOTTOM
160
71, 67, 63 AND 59 DEG F.
155
150
145
(5)
140
135
130
N PRESSURE (PSIG)
125
Cooling @ 1400 CFM
(4)
OUTDOOR TEMPERATURE (Degree F)
(3)
(1)
(2)
(2)
(3)
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Liquid Line Temp = __________ º F
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Suction Gage Pressure = __________ PSI
18-AC100D1-3-EN 21
14.3 Weigh-In Method for Charging
Weigh-In Method can be used for the initial
installation, or anytime a system charge is being
replaced. Weigh-In Method can also be used
when power is not available to the equipment
site or operating conditions (indoor/outdoor
temperatures) are not in range to verify with the
subcooling charging method.
Calculating Charge Using the Weigh-In Method
STEP 1 - Measure in feet the distance between the
outdoor unit and the indoor unit and record on Line 1.
Include the entire length of the line from the service
valve to the IDU.
STEP 2 - Enter the charge multiplier (0.6 lb/ft). Each
linear foot of interconnecting tubing requires the addition of 0.6 lb of refrigerant.
STEP 3 - Multiply the total length of refrigerant tubing
(Line 1) times the value on Step 2. Record the result
on Line 3 of the Worksheet.
STEP 4 - This is the amount of refrigerant to weigh-in
prior to opening the service valves.
1. Line length (ft) ______________
2. Charge multiplier x ____ 0.6 ______
3. Step 1 x Step 2 = _____________
4. Refrigerant = _____________
22 18-AC100D1-3-EN
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units
must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly
secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list: