Trane 4TTX5018A1000A, 4TTX5024A1000A, 4TTX5049E1000A, 4TTX5048A1000A, 4TTX5060A1000A Installer's Manual

...
18-AC74D1-4
Installer’s Guide
Condensing Units
4TTX5018A–060A, 049E
ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service informa­tion pack upon completion of work.
These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the installation. Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser’s purposes, the matter should be referred to your installing dealer or local distributor.
Table of Contents
Section 1. Safety .....................................................................................2
Section 2. Unit Location Considerations..............................................3
Section 3. Unit Preparation .................................................................... 5
Section 4. Setting the Unit ..................................................................... 5
Section 5. Refrigerant Line Considerations ......................................... 6
Section 6. Refrigerant Line Routing .....................................................7
Section 7. Refrigerant Line Brazing ...................................................... 8
Section 8. Refrigerant Line Leak Check ............................................. 10
Section 9. Evacuation ...........................................................................11
Section 10. Service Valves ................................................................... 11
Section 11. Electrical - Low Voltage .................................................... 13
Section 12. Electrical - High Voltage ................................................... 16
Section 13. Start Up .............................................................................. 17
Section 14. System Charge Adjustment ............................................. 18
Section 15. Checkout Procedures and Troubleshooting ................... 22
Section 1. Safety
WARNING
!
WARNING
!
WARNING
!
WARNING
!
CAUTION
!
CAUTION
!
WARNING
!
This information is intended for use by individuals possessing adequate backgrounds of electrical and mechanical experience. Any attempt to repair a central air conditioning product may result in personal injury and/or property damage. The manufacture or seller cannot be responsible for the interpretation of this information, nor can it assume any liability in connec­tion with its use.
These units use R-410A refrigerant which operates at 50 to 70% higher pressures than R-22. Use only R-410A approved service equipment. Refrigerant cyl­inders are painted a “Rose” color to indicate the type of refrigerant and may contain a “dip” tube to allow for charging of liquid refrigerant into the system. All R-410A systems use a POE oil that readily absorbs moisture from the atmosphere. To limit this “hygro­scopic” action, the system should remain sealed whenever possible. If a system has been open to the atmosphere for more than 4 hours, the compressor oil must be replaced. Never break a vacuum with air and always change the driers when opening the system for component replacement. For specific handling concerns with R-410A and POE oil reference Retrofit Bulletins SS-APG006-EN and APP-APG011-EN.
LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and trouble­shooting of this product, it may be necessary to work with live electrical components. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
Scroll compressor dome temperatures may be hot. Do not touch the top of compressor; it may cause minor to severe burning.
UNIT CONTAINS R-410A REFRIGERANT! R-410A operating pressures exceed the limit of R-22. Proper service equipment is required. Failure to use proper service tools may result in equipment damage or personal injury.
SERVICE
USE ONLY R-410A REFRIGERANT AND AP-
PROVED POE COMPRESSOR OIL.
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
2 18-AC74D1-4
Section 2. Unit Location Considerations
D
H
W
60’
Max Vertical Change
Standard Line Set
60’ Max
Line Length
60’
Max Vertical Change
2.1 Unit Dimensions and Weight
Table 2.1
Unit Dimensions and Weight
Models H x D x W (in)
4TTX5018A1000A
4TTX5024A1000A
4TTX5030A1000A
4TTX5036A1000A
4TTX5042A1000A
4TTX5048A1000A
4TTX5049E1000A
4TTX5060A1000A
* Weight values are estimated.
41 x 34 x 37 227
41 x 34 x 37 230
41 x 34 x 37 232
50 x 34 x 37 254
50 x 34 x 37 257
54 x 34 x 37 302
54 x 34 x 37 287
54 x 34 x 37 304
When mounting the outdoor unit on a roof, be sure the roof will support the unit’s weight.
Properly selected isolation is recommended to alleviate sound or vibration transmission to the building structure.
Please refer to application bulletin SSC­APG006-EN for detailed mounting information.
Weight* (lb)
2.2 Refrigerant Piping Limits
1. The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty (60) feet.
2. The maximum vertical change should not exceed sixty (60) feet.
3. Service valve connection diameters are shown in Table 5.1.
Note: For line lengths greater than sixty (60) feet, Refer to Refrigerant Piping Application Guide, SS-APG006-EN or Refrigerant Piping Software Program, 32-3312-03 (or latest revi­sion).
18-AC74D1-4 3
Min. 12” to Shrubbery
Avoid Install Near Bedrooms
Min 5’ Unrestricted
Access Panel
Min 3’ Unrestricted
2.3 Suggested Locations for Best Reliability
Min. 12” to Shrubbery
Min. 12” to Wall
Ensure the top discharge area is unrestricted for at least five (5) feet above the unit.
Three (3) feet clearance must be provided in front of the control box (access panels) and any other side requiring service.
Do not locate close to bedrooms as operational sounds may be objectionable.
Position the outdoor unit a minimum of 12” from any wall or surrounding shrubbery to ensure adequate airflow.
Outdoor unit location must be far enough away from any structure to prevent excess roof runoff water from pouring directly on the unit.
2.4 Coastal Considerations
If installed within one mile of salt water, including seacoasts and inland waterways, models without factory supplied Seacoast Salt Shields require the addition of BAYSEAC001 (Seacoast Kit) at installation time. Please refer to Application Guide SS-APB006-EN: Trane - Sea Coast Applications and Seascoast Corrosion Protection Bulletin UN-SVB11A-EN.
4 18-AC74D1-4
Section 3. Unit Preparation
3.1 Prepare The Unit For Installation
STEP 1 - Check for damage and report prompt-
ly to the carrier any damage found to the unit.
STEP 2 - To remove the unit from the pallet, remove tabs by cutting with a sharp tool.
Section 4. Setting the Unit
4.1 Pad Installation
When installing the unit on a support pad, such as a concrete slab, consider the following:
• The pad should be at least 1” larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.
For other applications refer to Application Guide SSC-APG006-EN.
18-AC74D1-4 5
Section 5. Refrigerant Line Considerations
Line Length
5.1 Refrigerant Line and Service Valve Connection Sizes
Table 5.1
Line Sizes Service Valve Connection Sizes
Model
4TTX5018A1000A 1/2 3/8 1/2 3/8
4TTX5024A1000A 5/8 3/8 5/8 3/8
4TTX5030A1000A 3/4 3/8 3/4 3/8
4TTX5036A1000A 3/4 3/8 3/4 3/8
4TTX5042A1000A 3/4 3/8 3/4 3/8
4TTX5048A1000A 7/8 3/8 7/8 3/8
4TTX5049E1000A 7/8 3/8 7/8 3/8
4TTX5060A1000A 7/8 3/8 7/8 3/8
Vapor
Line
5.2 Factory Charge
Trane outdoor condensing units are factory charged with the system charge required for the outdoor condensing unit, fifteen (15) feet of tested connecting line, and the smallest indoor evaporative coil match. If connecting line
length exceeds fifteen (15) feet and/or a larger indoor evaporative coil is installed, then final refrigerant charge adjustment is necessary.
Liquid
Line
Vapor Line
Connection
Liquid Line
Connection
5.3 Required Refrigerant Line Length
Determine required line length and lift. You will need this later in STEP 2 of Section 14.
Total Line Length = __________ Ft.
Total Vertical Change (lift) = __________ Ft.
5.4 Refrigerant Line Insulation
Important: The Vapor Line must always be insulated. DO NOT allow the Liquid Line and Vapor Line to come in direct (metal to metal) contact.
Liquid Line
Vapor Line
Insulation
6 18-AC74D1-4
5.5 Reuse Existing Refrigerant Lines
CAUTION
!
If using existing refrigerant lines make certain that all joints are brazed, not soldered.
For retrofit applications, where the existing indoor evaporator coil and/or refrigerant lines will be used, the following precautions should be taken:
• Ensure that the indoor evaporator coil and
refrigerant lines are the correct size.
• Ensure that the refrigerant lines are free of
leaks, acid, and oil.
Important: For more information see publi­cation numbers SS-APG006-EN and APP­APG011-EN.
Section 6. Refrigerant Line Routing
6.1 Precautions
Important: Take precautions to prevent noise within the building structure due to vibration transmission from the refrigerant lines.
For Example:
• When the refrigerant lines have to be fastened to floor joists or other framing in a structure, use isolation type
hangers.
• Isolation hangers should also be used when refrigerant lines are run in stud spaces or enclosed ceilings.
• Where the refrigerant lines run through a wall or sill, they should be insulated and isolated.
• Isolate the lines from all ductwork.
Minimize the number of 90º turns.
8 Feet Maximum
Side View
8 Feet Maximum
Secure Vapor line from joists using isolators every 8 ft. Secure Liquid Line directly to Vapor line using tape, wire, or other appro­priate method every 8 ft.
Comply with National, State, and Local Codes when isolating line sets from joists, rafters, walls, or other structural elements.
Joist/Rafter
Isolator
Line Set
18-AC74D1-4 7
Isolation From Joist/Rafter
8 Feet Maximum
Wall
Isolator
Wall
Side View
8 Feet Maximum
Line Set
Secure Vapor Line using isolators every 8 ft. Secure Liquid Line directly to Vapor Line using tape, wire, or other appropriate method every 8 ft.
Isolation In Wall Spaces
Sealant
Ductwork
Insulation
Vapor Line
Isolator
Line Set
Isolation Through Wall
Section 7. Refrigerant Line Brazing
7.1 Braze The Refrigerant Lines
STEP 1 - Remove caps or plugs. Use a debur-
ing tool to debur the pipe ends. Clean both internal and external surfaces of the tubing using an emery cloth.
DO NOT hang line sets from ductwork
8 18-AC74D1-4
STEP 2 - Remove the pressure tap cap and valve cores from both service valves.
STEP 3 - Purge the refrigerant lines and indoor coil with dry nitrogen.
STEP 4 - Wrap a wet rag around the valve body to avoid heat damage and continue the dry nitrogen purge.
Braze the refrigerant lines to the service valves.
Continue the dry nitrogen purge. Do not re­move the wet rag until all brazing is completed.
Important: Remove the wet rag before stopping the dry nitrogen purge.
NOTE: Precautions should be taken to avoid heat damage to basepan during brazing. It is recommended to keep the flame directly off of the basepane.
18-AC74D1-4 9
STEP 5 - Replace the pressure tap valve cores
150 PSI
after the service valves have cooled.
Section 8. Refrigerant Line Leak Check
8.1 Check For Leaks
STEP 1 - Pressurize the refrigerant lines and
evaporator coil to 150 PSIG using dry nitrogen.
STEP 2 - Check for leaks by using a soapy solu­tion or bubbles at each brazed location.
Remove nitrogren pressure and repair any leaks before continuing.
10 18-AC74D1-4
Section 9. Evacuation
1 MIN.
0350
Microns
ON
OFF
CAP
1/4 TURN ONLY COUNTERCLOCKWISE FOR FULL OPEN POSITION
VALVE STEM
GAS LINE CONNECTION
UNIT SIDE OF VALVE
PRESSURE TAP PORT
9.1 Evacuate the Refrigerant Lines and Indoor Coil
Important: Do not open the service valves until the refrigerant lines and indoor coil leak check and evacuation are complete.
STEP 1 - Evacuate until the micron gauge reads no higher than 350 microns, then close off the valve to the vacuum pump.
STEP 2 - Observe the micron gauge. Evacuation is complete if the micron gauge does not rise above 500 microns in one (1) minute.
Once evacuation is complete blank off the vacuum pump and micron gauge, and close the valves on the manifold gauge set.
Section 10. Service Valves
10.1 Open the Gas Service Valve
Important: Leak check and evacuation must be completed before opening the service valves.
NOTE: Do not vent refrigerant gases into the atmosphere
STEP 1 - Remove valve stem cap.
STEP 2 - Using an adjustable wrench, turn valve
stem 1/4 turn counterclockwise to the fully open position.
STEP 3 - Replace the valve stem cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
18-AC74D1-4 11
10.1 Open the Liquid Service Valve
WARNING
!
Extreme caution should be exercised when opening the Liquid Line Service Valve. Turn counterclockwise until the valve stem just touches the rolled edge. No torque is required. Failure to follow this warning will result in abrupt release of system charge and may result in personal injury and /or property damage.
Important: Leak check and evacuation must be completed before opening the service valves.
STEP 1 - Remove service valve cap.
STEP 2 - Fully insert 3/16” hex wrench into the
stem and back out counterclockwise until valve stem just touches the rolled edge (approximately five (5) turns.)
STEP 3 - Replace the valve cap to prevent leaks. Tighten finger tight plus an additional 1/6 turn.
Cap
Unit Side
of Service
Valve
Service Port
3/16” Hex Wrench
Rolled Edge to
Captivate Stem
Hex Headed
Valve System
Section 11. Electrical - Low Voltage
11.1 Low Voltage Maximum Wire Length
Table 11.1 defines the maximum total length of low voltage wiring from the outdoor unit, to the indoor unit, and to the thermostat.
Table 11.1
24 VOLTS
WIRE SIZE MAX. WIRE LENGTH
18 AWG 150 Ft.
16 AWG 225 Ft.
14 AWG 300 Ft.
12 18-AC74D1-4
11.2 Low Voltage Hook-up Diagrams
Red Yellow
Green White Black
Blue
W1 W2
B
G
Y1
Yellow
Yellow
Blue
Blue
R
Comfort Control
Air Handler
Air Conditioner
W1 W2 W3
G
Y
B
BK
Y
LO
R
Neatly bundle all low voltage wires behind the service valve cover as shown.
Comfort Control
Va riable Speed Furnace
Air Conditioner
Neatly bundle all low voltage wires behind the service valve cover as shown.
Red Yellow
Green White
Blue
W1
B
G
Y1
R
W1 W2
G
B
BK Y
R
Yellow
Yellow
Blue
Blue
Black
W2
Y
LO
Air Handler Hook-up Diagram
Notes:
1. If electric heat does not have 3rd contactor (CH), connect a jumper wire from W3 to W2. If electric heat does not have 2nd contactor (BH), connect a jumper wire from W2 to W1.
2. Ylo and BK may not be present on unit.
Variable Speed Furnace Hook-up Diagram
18-AC74D1-4 13
Notes:
1. If single stage heating thermostat is used, jumper W1-W2 on furnace terminal strip.
Red Yellow
Green White Black
Blue
Red
Brown
Blue
W1
B
W2
G
Y1
R
Comfort Control
Comm. Variable Speed
Furnace or Air Handler
B
D R
Communicating Comfort Control
(*CONT900)
Comm. Variable Speed
Furnace or Air Handler
Air Conditioner
Air Conditioner
W1 W2 W3
G
Y2
B O
BK D Y1
R
Neatly bundle all low voltage wires behind the service valve cover as shown.
W1 W2 W3
G
Y2
B O
BK
D
Y1
R
Neatly bundle all low voltage wires behind the service valve cover as shown.
Yellow
Yellow
Blue
Blue
Yellow
Yellow
Blue
Blue
Communicating Indoor Unit with 24 V Control Hook-up Diagram
Notes:
1. See User Interface setup menu for 24 VAC control mode and cooling CFM options.
2. W3 terminal may not be present on unit.
3. If single stage heating thermostat is used, jumper W1-W2 on furnace termi­nal strip.
Communicating Indoor Unit in Comm. Mode Hook-up Diagram
14 18-AC74D1-4
Notes:
1. See User Interface setup menu for cooling CFM options.
2. W3 terminal may not be present on unit.
Red
Yellow
Green
White
Blue
Yellow
Green
White
Blue
B
B - Blue
Blue
W
G Y
Y - Yellow
Yellow
R
Red
O
Orange
Comfort Control
Air Handler
Field wiring
O ** R ** B
YI (In)
W1
YO (Out)
G
W2
W3
Neatly bundle all low voltage wires behind the service valve cover as shown.
Air Conditioner
Comfort Control
Air Handler
Air Conditioner
Neatly bundle all low voltage wires behind the service valve cover as shown.
Field wiring
Yellow
Blue
Red
Yellow
Green
White
Blue
B
B - Blue
W G Y1
Y2
Y1 - Yellow
R
O
O R B
YI
W1
YO Y2 DH/BK
G
W2
W3
(In)
(Out)
1
1
1 2 3 4 5
1 2 3 4 5
HP
2(Compressor)
2(Stages)
AC (S ystem)
}
OUTDOOR
Capacity(Tons)
OUTDOOR
}
Torque
CFM/Ton
CoolOffDelay
}
INDOOR
CFM
+12V
R13
R14
R4
1
U1
RNET 1
S1
on
on
S2
RNET 2
R
6
C22
C19
C15C
12
C10
D9
L1
*AM7 Air Handler Hook-up Diagram
Control Board
Must configure to
“ON” for AC Units.
GAM5 Air Handler Hook-up Diagram
18-AC74D1-4 15
Must configure to “OFF” for
single-stage compressors.
* For multiple stages of 1. electric heat, jumper W1, W2, and W3 together if comfort control has only one stage of heat.
** R to 2. O jumper must be in place as shown for cooling only, non-heat pump systems for proper operation.
Yi and Yo connections 3. must be made as shown for freeze protection and internally mounted con­densate overflow circuits to work properly.
Internally mounted con-4. densate switch is optional and must be ordered separately.
If 3rd party condensate 5. overflow switches are installed, they should be wired in series between YO and Y to the outdoor unit.
Section 12. Electrical - High Voltage
WARNING
!
12.1 High Voltage Power Supply
LIVE ELECTRICAL COMPONENTS! During installation, testing, servicing, and troubleshooting of this product, it may be nec­essary to work with live electrical components. Failure to follow all electrical safety precau­tions when exposed to live electrical compo­nents could result in death or serious injury.
The high voltage power supply must agree with the equipment nameplate.
Power wiring must comply with national, state, and local codes.
Follow instructions on unit wiring diagram located on the inside of the control box cover and in the Service Facts document included with the unit.
12.2 High Voltage Disconnect Switch
Install a separate disconnect switch at the outdoor unit.
For high voltage connections, flexible electri­cal conduit is recommended whenever vibra­tion transmission may create a noise problem within the structure.
12.3 High Voltage Ground
Ground the outdoor unit per national, state, and local code requirements.
16 18-AC74D1-4
Section 13. Start Up
OFF
DON
E
CANCEL
ON
OFF
60 MIN.
ON
DON
E
CANCEL
13.1 System Start Up
STEP 1 - Ensure Sections 7 through 12 have
been completed.
STEP 2 - Set System Thermostat to OFF.
STEP 3 - Turn on disconnect(s) to apply power
to the indoor and outdoor units.
STEP 4 - Wait one (1) hour before starting the unit if compressor crankcase heater acces­sory is used and the Outdoor Ambient is below 70ºF.
STEP 5 - Set system thermostat to ON.
18-AC74D1-4 17
Section 14. System Charge Adjustment
LIFT
14.1 Temperature Measurements
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recom­mended method of charging above 55º F ambi­ent outdoor temperature.
For best results the indoor temperature should be kept between 70º F to 80º F.
Note: It is important to return in the spring or summer to accurately charge the system in the cooling mode when outdoor ambient tempera­ture is above 55º F.
120º F
55º F
Outdoor Temp
80º F
70º F
Indoor Temp
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
18 18-AC74D1-4
60
Add 4º
50
Add 3º
40
Add 1º Add 2º
30
Add 1º 25 20 15 10
0
10 20 25 30 40 60
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
Use Design Subcooling
TOTAL REFRIGERANT LINE LENGTH (FT)
STEP 2 -
20 MIN.
60 Add 3º 50 Add 2º 40 Add 1º 30 25 20 15 10
0
10 20 25 30 40 60
Use Design Subcooling
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
TOTAL REFRIGERANT LINE LENGTH (FT)
60
Add 5º 50
Add 4º 40
Add 2º Add 3º
30
Add 2º 25 20 15 10
0
10 20 25 30 40 60
Use Design Subcooling
Add 1º
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
TOTAL REFRIGERANT LINE LENGTH (FT)
60 Add 5º 50 Add 4º 40 30 25 20 15 10
0
10 20 25 30 40 60
Add 1º
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
TOTAL REFRIGERANT LINE LENGTH (FT)
Add 3º
Add 2º
Use Design Subcooling
60 Add 6º 50 Add 5º 40 Add 3º Add 4º 30 Add 3º 25 Add 2º 20 15 10
0
10 20 25 30 40 60
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
TOTAL REFRIGERANT LINE LENGTH (FT)
Add 2º
Add 1º
Use Design Subcooling
60 Add 2º 50 Add 1º 40 30 25 20 15 10
0
10 20 25 30 40 60
REFRIGERANT LINE LIFT (FT)
TOTAL REFRIGERANT LINE LENGTH (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
Use Design Subcooling
60 Add 4º 50 Add 2º 40 30 25 20 15 10
0
10 20 25 30 40 60
TOTAL REFRIGERANT LINE LENGTH (FT)
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
Add 1º
Use Design Subcooling
60
Add 6º 50
Add 5º 40
Add 3º Add 4º 30 25 20 15 10
Use Design Subcooling Add 1º
0
10 20 25 30 40 60
REFRIGERANT LINE LIFT (FT)
SUBCOOL CHARGING CHART CORRECTIONS TABLE
TOTAL REFRIGERANT LINE LENGTH (FT)
Add 2º
Add 3º
Add 1º
Add 2º
Determine the final subcooling value using total Line Length and Lift measured in STEP 1 and the charts below.
018 Units
030 Units
042 Units
024 Units
036 Units
048 Units
049 Units 060 Units
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
STEP 3 - Stabilize the system by operating for a minimum of 20 minutes.
At startup, or whenever charge is removed or added, the system must be operated for a mini­mum of 20 minutes to stabilize before accurate measurements can be made.
18-AC74D1-4 19
Final Subcooling Value = __________º F
STEP 4 - Measure the liquid line temperature
8910 11 12 13 14
179 182 185 188 191 195 198
195 198 201 204 208 211 215
211 215 218 222 225 229 232
229 232 236 240 243 247 251
247 251 255 259 263 267 271
267 271 275 279 283 287 291
287 291 296 300 304 309 313
309 313 318 322 327 331 336
331 336 341 346 351 355 360
355 360 365 370 376 381 386
381 386 391 396 402 407 413
407 413 418 424 429 435 441
435 441 446 452 458 464 470
464 470 476 482 488 495 501
495 501 507 514 520 527 533
R-410A REFRIGERANT CHARGING CHART
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
LIQUID
TEMP
(
°
F)
FINAL SUBCOOLING (
°
F)
LIQUID GAGE PRESSURE (PSI)
From Dwg. D154557P01 Rev. 3
107 °F
and pressure at the outdoor unit’s service valve.
Measured Liquid Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Final Subcooling Value = __________ º F
STEP 5 - Use the final subcooling value, refriger­ant temperature and pressure from STEP 4, to determine the proper liquid gage pressure using Table 14.2.
Example: Assume a 12º F Final Subcooling
value and liquid temp of 90º F.
1. Locate 12º F Final Subcooling in Table 14.2.
2. Locate the Liquid Temperarature (90º F) in the left column.
3. The Liquid Gage Pressure should be ap­proximately 327 PSI. (This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row.
Table 14.2
20 18-AC74D1-4
STEP 6 - Adjust refrigerant level to attain
20 MIN.
PRESSURE CURVES FOR 4TTX5049E1000A
4TXCD010CC3
Cooling @ 1400 CFM
LIQUID PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
125
130
135
140
145
150
155
160
165
170
170
220
270
320
370
420
470
520
40 50 60 70 80 90 100 110 120
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 67, 63 AND 59 DEG F.
INDOOR ENTERING WET BULB CURVES TOP TO BOTTOM 71, 67, 63 AND 59 DEG F.
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure is lower than the chart value.
Connect gages to refrigerant bottle 1. and unit as illustrated.
Purge all hoses.2.
Open bottle.3.
Stop adding refrigerant when liquid 4. line temperature and Liquid Gage Pressure matches the charging chart Final Subcooling value.
Recover refrigerant if the Liquid Gage Pres­sure is higher than the chart value.
STEP 7 - Stabilize the system.
Wait 20 minutes for the system condi-1. tion to stabilize between adjustments.
Note: When the Liquid Line Temperature and Gage Pressure approximately match the chart, the system is properly charged.
Remove gages.2.
Replace service port caps to prevent 3. leaks. Tighten finger tight plus an ad­ditional 1/6 turn.
STEP 8 - Verify typical performance.
Refer to System Pressure Curves in the Service Facts to verify typical performance.
18-AC74D1-4 21
(Example only - see Service Facts)
STEP 9 - Record System Information for refer­ence.
Record system pressures and temperatures after charging is complete.
Outdoor model number = _________________
Measured Outdoor Ambient = __________ º F
Measured Indoor Ambient = __________ º F
Measured Suction Line Temp = __________ º F
Liquid Gage Pressure = __________ PSI
Suction Gage Pressure = __________ PSI
Measured Liquid Line Temp = __________ º F
Section 15. Checkout Procedures and Troubleshooting
15.1 Operational And Checkout Procedures
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units must be operated and charge adjustments made.
Important: Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if nec­essary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and properly secured.
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
1. Leak check refrigerant lines. ........................................ [ ]
2. Properly insulate suction lines and fittings. ................... [ ]
3. Properly secure and isolate all refrigerant lines. ........... [ ]
4. Seal passages through masonry. If mortar is used, prevent mortar from coming
into direct contact with copper tubing. .......................... [ ]
5. Verify that all electrical connections are tight. ............... [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation. .................................................. [ ]
7. Be sure that indoor coil drain line drains freely. Pour water
into drain pan. ............................................................... [ ]
8. Be sure that supply registers and return grilles are open
and unobstructed. ......................................................... [ ]
9. Be sure that a return air filter is installed. ..................... [ ]
10. Be sure that the correct airflow setting is used.
(Indoor blower motor) ................................................... [ ]
11. Operate complete system in each mode to
ensure safe operation. .................................................. [ ]
22 18-AC74D1-4
SYSTEM FAULTS
REFRIGERA NT CIRCUIT
Head Pressure Too High
Head Pressure Too Low
Suction Pressure To o High
Suction Pressure To o Low
Liquid Refrig. Floodback (TXV/EEV)
Liquid Refrig. Floodback (Cap. Tube)
I.D. Coil Frosting
Compresso r Runs Inadequat e or No Cooling/H tg
ELECTRICA L
Compresso r & O.D. Fan Won’t Start
Compresso r Will Not Start But O.D. Fan Runs
O.D. Fa n Won’t Start
Compresso r Hums But Won’t Start
Compresso r Cycles on IOL
I.D. Blower Won’t Start
DEFROST
Unit Won’t Initiate Defrost
Defrost Te rminates on Time
Unit Icing Up
WHAT TO CHECK MODE
POWER SUPPLY
HIGH VO LTAGE WIRING
COMP RESSOR IOL
RUN CAPACITOR
START CAPACITOR
START RELAY
CONTACTOR CONTACTS
LOW VOLTAGE WIRING
CONT ROL TRANS FORMER
THER MOSTAT
CONTACTOR CO IL
LOW VOLTAGE FUSE
STUC K COMPRESSOR
INEF FICIEN T COMP.
REF. UNDERCH ARGE
REF. OVERCHARGE
EXCE SSIVE EVAP. LOAD
NONC ONDENS ABLES
RES. O.D. AI RFLOW
O.D. AIR RE CIRCUL ATION
TXV/ EEV STUCK OPEN
SUPE RHEAT
RES. I.D. AIR FLOW
REF. CIR. RESTRICTIONS
SOV LEAK ING
SOV COIL DEFECTIV E
CHEC K VA LVE LEAKI NG
*
DEFRO ST RELAY DEF.
DEFRO ST CONTRO L DEF.
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
C
H
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
S
S
S
S
PPP
P
S
S
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
S
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
S
S
S
S
S
S
S
P
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
S
S
S
S
P
P
P
P
P
P
S
S
S
S
S
S
S
S
S
S
S
P
P
S
S
S
S
S
S
S
S
P
P
P
P
P
P
P
S
S
P P
P
P
C - Cooling H - Heating P - Primary Causes S - Secondary Causes * - 3 Phase Only
15.2 Troubleshooting
18-AC74D1-4 23
6200 Troup Highway Tyler, TX 75707 www.trane.com
24 18-AC74D1-4
The manufacturer has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice.
Representative-only illustrations included in this document.
© 2010 Trane 10/10
Loading...