Product Specifications

Model No.
POWER CONNS. — V/PH/HZ
(a)
(b)
4TTR6018J1000A 4TTR6024J1000A 4TTR6030J1000A
208/230/1/60 208/230/1/60 208/230/1/60
MIN. BRCH. CIR. AMPACITY 12 14 17
BR. CIR. PROT. RTG. — MAX. (AMPS)
COMPRESSOR
CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL
20 25 25
RL AMPS — LR AMPS 9 — 47.5 10.9 — 62.9 12.8 — 67.8
Outdoor Fan FL AMPS 0.64 0.64 0.64
Fan HP
Fan Dia (inches)
1/8 1/8 1/8
23.02 — 1 23.02 23.02
Coil SPINE FIN™ SPINE FIN™ SPINE FIN™
Refrigerant R-410A 4 LBS., 15 OZ 5LBS., 3 OZ 6 LBS., 7 OZ
LINE SIZE — IN. O.D. GAS
LINE SIZE — IN. O.D. LIQ.
Charge Spec. Subcooling
Dimensions H x W X D Crated (IN.)
Weight — Shipping (lbs.)
Weight — Net (lbs.)
(c)
3/4 3/4 3/4
3/8 3/8 3/8
8°F 8°F 8°F
34 x 30.1 x 33 34 x 30.1 x 33 42 x 30.1 x 33
189 190 220
161 162 184
Optional Accessories:
Anti-short Cycle Timer
Evaporator Defrost Control
TAYASCT501A TAYASCT501A TAYASCT501A
AY28X079 AY28X079 AY28X079
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101
Extreme Condition Mount Kit BAYECMT023 BAYECMT023 BAYECMT023
Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT302 BAYCCHT302 BAYCCHT302
Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001
Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103
Refrigerant Lineset
(d)
TAYREFLN7* TAYREFLN7* TAYREFLN7*
Service Valve Panel Cover TAYSVPANL0032AA TAYSVPANL0032AA TAYSVPANL0044AA
(a)
Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b)
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c)
Standard line lengths — 60’, Standard lift — 60’ Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32–3312–0* (* denotes latest revision)..
(d)
* = 15, 20, 25, 30, 40 and 50 foot lineset available.
2
22-1916-1D-EN
PPrroodduucctt SSppeecciiffiiccaattiioonnss
Model No.
POWER CONNS. — V/PH/HZ
(a)
(b)
4TTR6036J1000A 4TTR6042J1000A 4TTR6048J1000A
208/230/1/60 208/230/1/60 208/230/1/60
MIN. BRCH. CIR. AMPACITY 18 21 24
BR. CIR. PROT. RTG. — MAX. (AMPS)
COMPRESSOR
CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL
30 35 40
RL AMPS — LR AMPS 13.6 — 79 16.7— 109 18.5 — 124
Outdoor Fan FL AMPS 0.77 0.64 0.93
Fan HP
Fan Dia (inches)
1/8 1/8 1/5
24 27.5 27.5
Coil SPINE FIN™ SPINE FIN™ SPINE FIN™
Refrigerant R-410A 7 LBS., 11 OZ 8 LBS., 10 OZ 8 LBS., 10 OZ
LINE SIZE — IN. O.D. GAS
LINE SIZE — IN. O.D. LIQ.
Charge Spec. Subcooling
Dimensions H x W X D Crated (IN.)
Weight — Shipping (lbs.)
Weight — Net (lbs.)
(c)
7/8 7/8 7/8
3/8 3/8 3/8
8°F 8°F 8°F
42 x 35.1 x 38.7 50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7
246 302 306
212 252 256
Optional Accessories:
Anti-short Cycle Timer
Evaporator Defrost Control
TAYASCT501A TAYASCT501A TAYASCT501A
AY28X079 AY28X079 AY28X079
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101
Extreme Condition Mount Kit BAYECMT004 BAYECMT004 BAYECMT004
Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT302 BAYCCHT302 BAYCCHT302
Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001
Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103
Refrigerant Lineset
(d)
TAYREFLN3* TAYREFLN3* TAYREFLN3*
Service Valve Panel Cover TAYSVPANL0044AA TAYSVPANL0046AA TAYSVPANL0046AA
(a)
Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b)
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c)
Standard line lengths — 60’, Standard lift — 60’ Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32–3312–0* (* denotes latest revision)..
(d)
* = 15, 20, 25, 30, 40 and 50 foot lineset available.
22-1916-1D-EN
3
PPrroodduucctt SSppeecciiffiiccaattiioonnss
Model No.
POWER CONNS. — V/PH/HZ
(a)
(b)
4TTR6049J1000A 4TTR6060J1000A 4TTR6061C1000A
208/230/1/60 208/230/1/60 208/230/1/60
MIN. BRCH. CIR. AMPACITY 26 32 32
BR. CIR. PROT. RTG. — MAX. (AMPS)
COMPRESSOR
CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL CLIMATUFF®- SCROLL
40 50 50
RL AMPS — LR AMPS 18.5 — 124 23.7 — 152.5 23.7 — 152.5
Outdoor Fan FL AMPS 2.80 1.05 1.05
Fan HP
Fan Dia (inches)
1/3 1/5 1/5
27.5 27.5 27.6
Coil SPINE FIN™ SPINE FIN™ SPINE FIN™
Refrigerant R-410A 10 LBS., 3 OZ 9 LBS., 13 OZ 10 LBS., 15 OZ
LINE SIZE — IN. O.D. GAS
LINE SIZE — IN. O.D. LIQ.
Charge Spec. Subcooling
Dimensions H x W X D Crated (IN.)
Weight — Shipping (lbs.)
Weight — Net (lbs.)
(c)
7/8 1–1/8 1–1/8
3/8 3/8 3/8
10°F 10°F 10°F
50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7 50.4 x 35.1 x 38.7
322 327 327
272 277 277
Optional Accessories:
Anti-short Cycle Timer
Evaporator Defrost Control
TAYASCT501A TAYASCT501A TAYASCT501A
AY28X079 AY28X079 AY28X079
Rubber Isolator Kit BAYISLT101 BAYISLT101 BAYISLT101
Extreme Condition Mount Kit BAYECMT004 BAYECMT004 BAYECMT004
Start Kit BAYKSKT263 BAYKSKT263 BAYKSKT263
Crankcase Heater Kit BAYCCHT302 BAYCCHT302 BAYCCHT302
Seacoast Kit BAYSEAC001 BAYSEAC001 BAYSEAC001
Low Ambient Kit BAYLOAM103 BAYLOAM103 BAYLOAM103
Refrigerant Lineset
(d)
TAYREFLN3* TAYREFLN3* TAYREFLN3*
Service Valve Panel Cover TAYSVPANL0046AA TAYSVPANL0046AA TAYSVPANL0046AA
(a)
Certified in accordance with the Unitary Air-conditioner equipment certification program which is based on AHRI standard 210/240.
(b)
Calculated in accordance with N.E.C. Only use HACR circuit breakers or fuses.
(c)
Standard line lengths — 60’, Standard lift — 60’ Suction and Liquid line. For Greater lengths and lifts refer to refrigerant piping software Pub#32–3312–0* (* denotes latest revision)..
(d)
* = 15, 20, 25, 30, 40 and 50 foot lineset available.