Toshiba SMMS-e Quick Reference

Quick Reference
EU Model
Cooling type
Heat pump type
Q18-001
R410
Refrigerant Piping
Address Setup
Test Operation
Troubleshooting
in Test Operation
Monitoring Function
NFC (Wave Tool)
Refrigerant Leakage Detection
Service Support Function
Backup Operation
Outdoor Interface P.C board
Leaking/Clogging
Troubleshooting
2
Refrigerant Piping
Additional refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200 MAP220
Charged amount (kg) 11.5
Cooling only model
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160 MAP180 MAP200 MAP220
Charged amount (kg) 5.115.01
Additional refrigerant charge amount at site = [1] + [2] + [3] [1]. Compensation by system HP (Table 1) [2]. Additional refrigerant charge amount Indoor unit (Table 2) [3]. (Real length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 m (Table 3)) × 1.2
For HT8P - E model
Table 1
System
Combination
Charged
refrigerant (kg)
Compensation by
System HP
HP HP kg
Standard model
8 8 11.5 -3.5 10 10 11.5 -3.5 12 12 11.5 -1.5 14 14 11.5 -1.0 16 16 11.5 -0.5 18 18 11.5 1.5 20 20 11.5 1.5 22 22 11.5 1.5 24 12 12 23 -3.0 26 14 12 23 -2.5 28 16 12 23 -2.0 30 16 14 23 -1.5 32 16 16 23 -1.0 34 18 16 23 1.0 36 20 16 23 1.0 38 22 16 23 1.0 40 20 20 23 3.0 42 22 20 23 3.0 44 22 22 23 3.0 46 16 16 14 34.5 -6.5 48 16 16 16 34.5 -6.5 50 18 16 16 34.5 -0.5 52 20 16 16 34.5 -0.5 54 22 16 1
6 34.5 -0.5 56 20 20 16 34.5 2.5 58 22 20 16 34.5 2.5 60 22 22 16 34.5 2.5
High efficiency
model
20 10 10 23 -7.0 22 12 10 23 -7.0 36 12 12 12 34.5 -12.5 38 14 12 12 34.5 -10.5 40 14 14 12 34.5 -8.5 42 14 14 14 34.5 -4.5 44 16 14 14 34.5 -4.5 54 20 20 14 34.5 1.5
<Cooling,Heat pump type>
3
Refrigerant Piping
<Cooling,Heat pump type>
Table 2 (For HT8P-E, T8P-E model)
Additional refrigerant charge amount Indoor unit
Standard Indoor
unit
Fresh Air Intake
I
Hot water
Modulendoor Unit
Air to Air Heat
exchanger with
DX-coil
Additional refrigerant charge amount kg/HP 0.4 0.2 0 0.2
Table 3 (For HT8P, HT7P, T8P, T7P model)
Pipe dia. at liquid side mm Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0 Ø22.2 Additional refrigerant amount/1m kg/m 0.025 0.055 0.105 0.160 0.250 0.350
Charging of refrigerant
Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides
, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually
Additional refrigerant charge amount
MMY-MAP***6T8P-E
Additional refrigerant charge amount at site = [1] + [2] + [3]
[1]. Compensation by system HP (Table 1)
[2]. Additional refrigerant charge amount Indoor unit (Table 2)
[3]. (Real length of liquid pipe × Additional refrigerant charge amount per liquid pipe 1 m (Table 3) ) × 1.2
Table 1
Space saving model High efficiency / High Diversity model
System Combination
Charged
refrigerant
Compensation
by System
HP
System Combination
Charged
refrigerant by System
HP
HP HP kg kg HP HP kg kg
8 8
10.5 -3.5
20 10 10 21 -7.0
-7.0
12 10 21 12 12 12 31.5
32.5
-12.5 14 12 12 -10.5 14 14 12 33.5 -8.5 14 14 14 34.5
34.5
-4.5
-4.5
16 14 14 20 20 14 34.5 1.5
10 10
10.5 -3.5
22
12 12
10.5 -1.5
36
14 14
11.5 -1.0
38
16 16
11.5 -0.5
40
1
8
18
11.5 1.5
42
20 20
11.5 1.5
44
22 22
11.5 1.5
54
24 12 12
21 -3.0
26 14 12
22 -2.5
28 16 12
22 -2.0
30 16 14
23 --1.5
32 16 16
23 1.0
34 18 16
23 1.0
36 20 16
23 1.0
38 22 16
23 1.0
40 20 20
23 3.0
42 22 20
23 3.0
44 22 22
23 3.0
46 16 16 14
34.5 -6
.5
48 16 16 16
34.5 -6.5
50 18 16 16
34.5 -0.5
52 20 16 16
34.5 -0.5
54 22 16 16
34.5 -0.5
56 20 20 16
34.5 2.5
58 22 20 16
34.5 2.5
60 22 22 16
34.5 2.5
Note : 14HP* = MMY-MAP1406T8P , MMY-MAP1406T7P
18HP* =
MMY-MAP1806T8P , MMY-MAP1806T7P
Compensation
When the system is charged with refrigerant at the factory,
the amount of refrigerant need
ed for the pipes at the site
is not included. Therefore, calculat
e the additional amount needed and add the required amount to the system.
(Calculation)
0806
10.5kg 10.5kg 10.5kg 10.5kg 11.5kg 11.5kg 11.5kg 11.5kg 11.5kg 11.5kg
1006
1206 14B6 1406
Cooling only model
Refrigerant amount
charged in factory
18B6 1806 2006 22061606
For T8P,T7P model
4
Refrigerant Piping
Allowable length of refrigerant pipes and allowable height difference between units
System restriction
Lc
Lb
La
LA
L3
L4
L5
L6
f
g
h
i
j
a b c d e
(j)
L7
Height difference between outdoor units H3 5 m
For HT8P - E
utdoor unit
A
Header
unit
B
Follower
unit
C Follower unit
Outdoor unit connecting pipes
Outdoor unit connection piping kit (For linking of outdoor units)
The longest piping between outdoor units: LO 25 m
Main piping L1
Height difference between outdoor and indoor units: H1 70 m
First branching section
Branching header
Y-shaped branching joint
Indoo
r unit connecting
pipe
Indoor unit
The longest piping length: L 235 m
The longest piping length from the
first branch: Li
90 m
Y-shaped branching joint
Indoor unit
Height difference between indoor units: H2 40 m
stinu 3 ot pUnoitanibmoc tinu roodtuO
Note (*1):(D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch. (*2) :If the height difference (H1) between indoor and outdoor unit exceeds 3 m, set 65 m or less. (*3) :If the max. combined outdoor unit capacity is 54HP or more, then max. equivalent length is 70 m or less (real length is 50 m or less). (*4) :If the height difference (H2) between indoor units exceeds 3 m, set 50 m or less.
PH 06 ot pUstinu roodtuo fo yticapac latoT
stinu 46 ot pUnoitcennoc tinu roodnI
Total capacity of indoor units (varies depending on the height difference between indoor units.)
H2 15m 135% of outdoor units’ capacity
15m < H2 105% of outdoor units’ capacity
<Cooling,Heat pump type>
5
Refrigerant Piping
Lc
Lb
La
LA
L3
L4
L5
L6
f
g
h
i
j
a b c d e
(j)
L7
Height difference between outdoor units H3 5 m
Outdoor unit A
Header
unit
B
Follower
unit
C Follower unit
Outdoor unit connecting pipes
Outdoor unit connection piping kit (For linking of outdoor units)
The longest piping between outdoor units: LO 25 m
Main piping L1
Height difference between outdoor and indoor units: H1 70 m
First branching section
Branching header
Y-shaped branching joint
Indoo
r unit connecting
pipe
Indoor unit
The longest piping length: L 235 m
The longest piping length from the
first branch: Li
90 m
Y-shaped branching joint
Indoor unit
Height difference between indoor units: H2 40 m
stinu 3 ot pUnoitanibmoc tinu roodtuO
Note (*1):(D) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch. (*2) :If the height difference (H1) between indoor and outdoor unit exceeds 3 m, set 65 m or less. (*3) :If the max. combined outdoor unit capacity is 54HP or more, then max. equivalent length is 70 m or less (real length is 50 m or less). (*4) :If the height difference (H2) between indoor units exceeds 3 m, set 50 m or less.
PH 06 ot pUstinu roodtuo fo yticapac latoT
stinu 46 ot pUnoitcennoc tinu roodnI
Total capacity of indoor units (varies depending on the height difference between indoor units.)
H2 15m 135% of outdoor units’ capacity
15m < H2 105% of outdoor units’ capacity
<Cooling,Heat pump type>
For T8P - E
Allowable length of refrigerant pipes and allowable height difference between units
System restriction
6
Refrigerant Piping
• Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit.
• Install the outdoor units in order of their capacity codes: A (header unit) B C
• When connecting gas pipes to indoor units, use Y-shaped branching joints to keep pipes level.
• When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit and those to
indoor units at a right angle as shown in figure 1 on “Installation of the outdoor unit”. Do not connect
them as in figure 2 on “Installation of the outdoor unit”.
(*1) : (C) is outdoor unit furthest from the 1st branch and (j) is the indoor unit furthest from the 1st branch. (*2) : If the height difference (H1) between indoor and outdoor unit exceeds 3m, set 65m or less. (*3) : If the max. combined
outdoor unit capacity is 46HP or more, then max. equivalent length is 70m or less (real length is 50m or less). (*4) : If the height difference (H2) between indoor units exceeds 3m, set 50m or less. (*5) : If the height difference (H2) between indoor units exceeds 3m, set 30m or less. (*6) : Total charging refrigerant is 140kg or less. (*7) : Extension up till 90m is possible with conditions below.
Item
Allowable
value
Piping section
Piping length
Total extension of pipe (Liquid pipe, real length)
Below 34HP 300m
LA + LB + La + Lb + Lc+ L1 + L2 + L3 + L4+ L5 +L6 + L7 + a + b + c + d + e + f + g + h + i + j
34HP or more 1000m (*6)
Farthest piping Length L (*1)
Equivalent
length
235m
LA+ L1 + L3 + L4 + L5 + L6 + j
Real length 190m
Equivalent length of farthest piping from 1st branching Li (*1)
90m (*2) L3 + L4 +
L5 + L6 + j
Equivalent length of farthest piping between outdoor units LO
25m LA + Lc(LA + Lb)
Max. equivalent length of main piping
Equivalent
length
120m (*3)
L1
Real length 100m (*3)
Max. equivalent length of outdoor unit connecting piping
10m Lc(La, Lb)
Max. real length of indoor unit connecting piping 30m a, b, c, d, e, f, g, h, i, j Max. equivalent length between branches 50m L2, L3, L4, L5, L6, L7
Difference i
n
height
Height between indoor and outdoor units H1
Upper outdoor
unit
70m
(*4, *7)
Lower outdoor
unit
)5*( m04
m042H stinu roodni neewteb thgieH –m53H stinu roodtuo neewteb thgieH
Liquid piping
▼Figu re 1
Main pipe
Header unitAFollower unitBFollower unit
C
To the indoor unit
Correct
▼ Figu re 2
Main pipe
Header unitAFollower unitBFollower unit
C
To the indoor unit
Incorr ect
NO GOOD
- Outdoor Temperature Cooling : 10°C to 46°C (Dry-bulb temp.) Heating : -5°C to 15.5°C (Wet-bulb temp.)
- Equivalent length of farthest piping from 1st branching Li<50m
- Real length of main piping L1<100m
- Height difference between indoor units H2<3m
- Total capacity of combined indoor units : 90%-105%
- Single CDU, and up to 20HP
- Minimum capacity of connectable indoor unit : 4HP or Larger
<Cooling,Heat pump type>
Cautions for installation
Allowable length and allowable height difference of refrigerant piping
7
Refrigerant Piping
(1)(1)
(8)
(8)
(2)
(6)
(4)
(6)
(5) (5) (5) (5)
(4)
(6)
(6)
(6)
(4)
(4)
(4)
(5)(5)(5)(5)(5)
He ade r unit A
F ollower unit B
F ollower unit C
Outdoor unit
(2) Balance pipes Ø9.5
(1) Outdoor unit c onnec ting pipes
(3) Main piping
(8) Outdoor unit c onnec tion piping kit (For linking of outdoor units)
(4) Branching pipe
F irst branch
Y-s hape branc hing joint
(7) Branching hea der
(6) Y-shaped branching joint
(5) Indoor unit connecting pipe
Indoor unit
Indoor unit
<Cooling,Heat pump type>
Selection of refrigerant piping
8
Refrigerant Piping
<Cooling,Heat pump type>
23
skrameRezis epip fo noitceleSemaNstrap gnipiP.oN
(1)
Outdoor unit
Outdoor unit
connection piping
kit
Outdoor unit
connecting pipe
Connectin g pipe size of o utdoor u nit
Type Gas si de Liquid side
MMY-MAP0806* Ø19.1 Ø12.7 MMY-MAP1006* Ø22.2 Ø12.7 MMY-MAP1206* Ø28.6 Ø12.7 MMY-MAP1406* Ø28.6 Ø15.9 MMY-MAP1606* Ø28.6 Ø15.9 MMY-MAP1806* Ø28.6 Ø15.9 MMY-MAP2006* Ø28.6 Ø15.9 MMY-MAP2206* Ø28.6 Ø19.1
Same as connecting pipe size of the o
(
MMY-MAP14B6* use table
MMY-MAP1206*)
(
MMY-MAP18B6* use table
MMY-MAP1606*)
utdoor unit.
(2)
Between Outdoor
unit connection
piping kits
Main connecting
piping between
outdoor units
Piping si ze for connecting pi ping between outdoor units
Total capacity codes of the total
outdo or uni ts at th e downstream
side
Gas
side
Liqui d
side
Balance
pipe
Equivalent
to HP
Equivalent to capac ity
16 to below 22 45.0 to below 61.5 Ø28.6 Ø15.9
Ø9.5
22 to below 24 61.5 to below 67.0 Ø28.6 Ø19.1 24 to below 26 67.0 to below 73.0 Ø34.9 Ø19.1 26 to below 36 73.0 to below 100.0 Ø34.9 Ø19.1
36 or more 100.0 or more Ø41.3 Ø22.2
Pipe size differs based on the total
capacity code value of o
utdoor unit at the
downstream side.
Refrigerant piping (Continued)
<Cooling, Heat pump type >
No. Piping parts Name Selection of pipe size Remarks
(1)
Outdoor unit
Outdoor unit
connection piping
kit
Outdoor unit
connecting pipe
Connecting pipe size of outdoor unit
Type Gas side Liquid side
MMY-MAP0806* Ø19.1 Ø12.7 MMY-MAP1006* Ø22.2 Ø12.7 MMY-MAP1206* Ø28.6 Ø12.7 MMY-MAP1406* Ø28.6 Ø15.9 MMY-MAP1606* Ø28.6 Ø15.9 MMY-MAP1806* Ø28.6 Ø15.9
Same as connecting pipe size of the outdoor unit.
(2)
Between Outdoor
unit connection
piping kits
Main connecting
piping between
outdoor units
Piping size for connecting piping between outdoor units
Total capacity codes of
the total outdoor units at
the downstream side
Gas sid e Liquid side
Equivalent to HP
Equivalent to
capacity
24 to below 32 68.0 to below 91.0 Ø34.9 Ø19.1
Pipe size differ based on the total capacity code value of outdoor unit at the downstream side.
Pipe size differs
(3)
Outdoor unit
connection piping
kit of header unit
First branching
section
Main piping
Size of main piping
Total capacity codes of
all out door u nits
Gas side
Liqui d
side
Equivalent to HP
Equivalent to
capacit y
8 to below 10 22.4 to below 28.0 Ø19.1 Ø12.7 10 to below 12 28.0 to below 33.5 Ø22.2 Ø12.7 12 to below 14 33.5 to below 38.4 Ø28.6 Ø12.7 14 to below 22 38.4 to below 61.5 Ø28.6 Ø15.9 22 to below 24 61.5 to below 67.0 Ø28.6 Ø19.1 24 to below 26 67.0 to below 73.0 Ø34.9 Ø19.1 26 to below 36 73.0 to below 100.0 Ø34.9 Ø19.1
36 or more 1
00.0 or more Ø41.3 Ø22.2
based on all capacity code value of outdoor unit.
For HT7P-K model only
For HT7P-K model only
9
Refrigerant Piping
skrameRezis epip fo noitceleSemaNstrap gnipiP.oN
(5)
Branching section
Indoor unit
Indoor unit
connecting pipe
Connectin g pipe size of indoor unit
edis saGknar yticapaC
Liqui d
side
007 to 012 type
15m or less real length Ø9.5 Ø6.4 Real length exceeds 15m Ø12.7 Ø6.4
4.6Ø7.21Øepyt 810 ot 510
5.9Ø9.51Øepyt 650 ot 420
7.21Ø2.22Øepyt 690 ot 270
(6)
Branching section
Y-shaped
branching joint
Selection o f branching section (Y-shaped branch ing joint)
Total capacity code of indoor unit s
Model nam e
Equival ent to HP
Equival ent to
capacit y
Y-shape branching joint
Below 6.4 Below 18.0 RBM-BY55E
6.4 to below 14.2 18.0 to below 40.0 RBM-BY105E
14.2 to below 25.2 40.0 to below 70.5 RBM-BY205E
25.2 or more 70.5 or more RBM-BY305E
(7)
Branching section Branching header
Selection o f branching section (Branching header)
Total capacity code of indoor unit s
Model nam e
Equival ent to HP
Equival ent to
capacit y
*2 Branching header
For 4 branches
Below 14.2 Below 40.0 RBM-HY1043E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2043E
For 8 branches
Below 14.2 Below 40.0 RBM-HY1083E
14.2 to below 25.2 40.0 to below 70.5 RBM-HY2083E
*2: Up to a total of 6.0 maximum equivalent to HP capacity codes is connectable to one line
after branching of heade
r. When the total capacity codes of all outdoor units are 12 to below 26 (equivalent to HP) and you use a branching header for the first branching section, use a RBM-HY2043E or RBM-HY2083E regardless of the total capacity codes of outdoor units at downstream side. In addition, you cannot use a branching header for the
first branching section when the total capacity codes of all outdoor units are ov
er
26 (equivalent to HP).
(8)
Branching section
Outdoor unit
connection piping
kit (For linking of
outdoor units)
Outdoor u nit conn ection piping kit (For linking of outdoor units)
Total capacity code of outdo or uni ts
*3
Model nam e
Equival ent to HP
Equival ent to
capacit y
Outdoor unit connection piping kit (For linking of outdoor units)
Below 26.0 Below 73.0 RBM-BT14E
26.0 or more 73.0 or more RBM-BT24E
*3: Downstream side when regarding the main piping as the start point
Pipe size differs
(4)
Branching section
Branching section
Branching pipe
Pipe size between branching sections
Total capacity codes of
indoo r unit s at downstream side
Gas side
Liqui d
side
Equivalent to HP
Equivalent to
capacit y
below 2.4 below 6.6 Ø12.7 Ø9.5
2.4 to below 6.4 6.6 to below 18.0 Ø15.9 Ø9.5
6.4 to below 12.2 18.0 to below 34.0 Ø22.2 Ø12.7
12.2 to below 20.2 34.0 to below 56.5 Ø28.6 Ø15.9
20.2 to below 22.4 56.5 to below 62.5 Ø28.6 Ø19.1
22.4 to below 25.2 62.5 to below 70.5 Ø34.9 Ø19.1
25.2 to below 35.2 70.5 to below 98.5 Ø34
.9 Ø19.1
35.2 or more 98.5 or more Ø41.3 Ø22.2
based on the total capacity code value of indoor units at the downstream side. If the total capacity code value of indoor units exceeds that of the outdoor units, apply the capacity code of the outdoor units.
<Cooling,Heat pump type>
10
Refrigerant Piping Systematic
<Cooling,Heat pump type>
Outdoor Unit (8, 10, 12HP) Model: MMY-MAP0806 , MMY-MAP1006 , MMY-MAP1206
(TD2)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TO)
SV
SV
SV
SV
M
(TL1)
SV
SV
SV
(TK5)
(TS3)
(TL3)
Reducer
(SV3A)
(SV2)
(SV3D)
(SV42)(SV41)
(SV3C)
(PMV4)
(TS1)
(SV3B)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
(PMV1)
4-way valve
High-pressure sensor
Low-pressure sensor
Oil separator
Fusible plug
Liquid Tank
Accumulator
High­pressure
switch
High-
pressure switch
Compressor
1
(Inverter)
Oil Header
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Sub cool
heat exchanger
SV
(SV52)
Reducer
FP
Compressor
2
(Inverter)
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
Reducer
11
Refrigerant Piping Systematic
<Cooling,Heat pump type>
Outdoor Unit (14, 16HP) Model: MMY-MAP1406 , MMY-MAP1606
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure
sensor
Low-pressure sensor
Oil separator
Accumulator
Liquid Tank
Liquid side
Service valve
Gas side
Service valve
Balance pipe
Service valve
Oil Header
High-
pressure switch
High-
pressure switch
Reducer
Fusible
plug
FP
Sub cool
heat exchanger
Compressor
1
(Inverter)
Compressor
2
(Inverter)
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
12
Refrigerant Piping Systematic
<Cooling,Heat pump type>
M
Outdoor Unit (18, 20, 22HP)
odel: MMY-MAP1806 ,
MMY-MAP2006 , MMY-MAP220
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan
Fan motor
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure sensor
Low-pressure
sensor
Oil separator
Liquid Tank
Oil Header
High-
pressure switch
High-
pressure switch
Sub cool
heat exchanger
Fusible
plug
FP
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
Reducer
Compressor
1
(Inverter)
Compressor
2
(Inverter)
Accumulator
13
Refrigerant Piping Systematic
<Explanation of Functional Parts>
E x planation of F unc tional P arts
<C ooling, Heat pump type>
Functi onal part n ame
Functi onal outline
Solenoid val ve
SV3A
(Connector CN321: White)
1) Supplies oil reserved in the oil header during ON time.
SV3B
(Connector CN321: White)
1) Returns oil supplied in the balance pipe to the compressor.
SV3C
(Connector CN321: White)
1) Pressurizes oil reserved in the oil header during ON time.
SV3D
(Connector CN322: White)
1) Reserves oil in the oil separator during OFF time.
2)
Returns oil reserved in the oil separator to the compressor during ON time.
SV2
(Hot gas bypass) (Connector CN311: White)
1) Low pressure release function
2) High pressure release function
3) Gas balance function during stop time
SV41 SV42
(Start assure valve of compressor) (SV41 Connector CN312: Blue, SV42 Connector CN312: Blue.
1) For gas balance start
2) High pressure release function
3) Low pressure rele
ase function
SV52
(Connector CN314: White)
1) Gas injection function during hot gas defrost in heating operation
4-way valve
(Connector CN317:Blue)
1) Cooling/heating exchange
2) Reverse defrost
Oil separator
1) Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle)
2) Reserve function of surplus oil
Pressur e sens or
High pressure sensor
(Connector CN501: Red)
1) Detects high pressure and con
trols compressor capacity
2) Detects high pressure in cooling operation, and controls the fan in low ambient cooling operation
3) Detects subcool in indoor unit in heating operation
Low pressure sensor
(Connector CN500: White)
1) Detects low pressure in cooling operation and controls compressor capacity
2) Detects low pressure in heating operation, and controls the super heat
Heater
Balance pipe
1) Oil bala
ncing in each outdoor unit
Comp ressor case h eater
(Compressor 1 Connector CN331: White, Compressor 2 Connector CN332: Blue.
1) Prevents liquid accumulation to compressor
Accumulator case heater
(Connector CN334: Red)
1) Prevents liquid accumulation to accumulator
(PMV1 Connector CN300: White, PMV3 Connector CN302: Blue)
1) Super heat control function in heating operation
2) Liquid line shut-down function while follower unit stops
3) Subcool adjustment function in cooling operation
4) Exchange function between main and sub exchangers in cooling operation
PMV1, 3
Pulese mo tor valve
(Connector CN303: Red)
1) Subcool adjustment function in cooling operation
2) Liquid b
ypass function for discharge temperature release (cooling bypass function)
PMV4
TD1
TD2
(TD1 Connector CN502: White, TD2 Connector CN503: Pink )
1) Protection of compressor discharge temp.
2) Used for dischage temperature release
TS1
(Connector CN505: White)
1) Controls PMV1 super heat in heating operation
2) Protection of compressor
TS3
(Connector CN903: Purple)
1) Controls PMV4 super heat in heating operation
TG1
TG2
(TG1 Connector CN525: Blue, TG2 Connector CN526: White )
1) Controls PMV
1 super heat in heating operation
Temp. Sens or
TE1
TE2
(TE1 Connector CN520: Green, TE2 Connector CN521: Red )
1) Controls defrost in heating operation
2) Controls outdoor fan in heating operation
TK1,TK2 TK4,TK5
(TK1 Connector CN531: Black, TK2 Connector CN532: Green, TK4 Connector CN534: Yellow, TK5 Connector CN535: Red)
1) Judges oil level of the compressor
TL1,TL2 TL3
(TL1 Connector CN523: White, TL2 Connector CN524: Gray, TL3 Connector CN902: Pink)
1) Detects subcool in cooling operation
TO
(Connector CN507: Yellow)
1) Detects outside temperature
(Connector CN314: White)
1) Preventive function for high-pressure rising in heating operation
2) Gas injection function during hot gas defrost in heating operation
SV51
(High pressure SW 1,2 Connector CN251: BLK)
1) Piping resisting pressure protection
)High pressu re swit ch
(4.15MPa)
High pressu re SW 1 High pressu re SW 2
14
Address Setup
After turning on the main power of the indoor units and outdoor unit in the refrigerant line to conduct a test opera­tion, check the following items in each outdoor and indoor unit. (After turning on the main power, be sure to check in order: indoor unit outdoor unit.)
<Check on the outdoor unit>
(1) Check that all the rotary switches, SW01, SW02, and SW03, on the interface PC board of the header unit are
set to “1.”
(2) If another check code is displayed on the 7-segment display [B], remove the cause of the problem referring to
Section, “TROUBLESHOOTING”.
(3) Check that “L08” is displayed on the 7-segment display [B] on the interface PC board of the header unit.
(L08: Indoor address not set up) (If the address setup operation has already been completed during servicing, etc., the above check code
is not
displayed, and “U1” is displayed on the 7-segment display [A].)
<Check on the indoor unit>
(1) Display check on the remote controller (in the case of a wired remote controller)
Check that a frame, as shown in the following figure at left, is displayed on the LC display section of the remote controller.
If no frame is displayed, as shown in the above figure at right, the remote controller does not
have a normal
supply of power; check the following items.
• Check the power supply of the indoor unit.
• Check the cabling between the indoor unit and the remote controller.
• Check whether there is a cutoff of wire around the indoor control PC board or not, and check for connection failures of the connectors.
• Check for failure of the transformer for the indoor electrical control box.
• Check for failure of
the indoor control PC board.
Interface PC board
SW01 SW02 SW03
SW04
D600 D601 D602 D603 D604
SW15SW05
Push switches
Rotary switches
7-segment display
[A]
7-segment display
[B]
SET
TIME
TIMER SET
TEST
FILTER RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
Normal status (power supplied and operation stopped)
Correct
SET
TIME
TIMER SET
TEST
FILTER RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
When power is not supplied normally
Incorrect
Chack at Main Power-on
15
Address Setup
This product requires address setup before operation. Follow this procedure for address setup.
(1) Address setup is not performed simply by turning on the power supply. (2) For indoor units, address setup can be done either by “manual address setup” or “by automatic address setup”
Automatic address setup: Setup from SW15 on the interface PC board of the header unit Manual address setup: Setup from the
wired remote controller. (For details, refer to “Address Setup Procedure.”) (3) Automatic setup usually takes about 5 minutes per line. In some cases, however, it may take up to 10 minutes. (4) It is unnecessary to operate the air conditioner to achieve address setup.
Procedure
1 Indoor unit power-on Turn on the power of the indoor unit for the refrigerant line for which the address is to be set up. 2 Outdoor unit power-on Turn on the power of all the outdoor units for the refrigerant line for which the address is to be set up .
3
7-segment display check
Check that “L08” is displayed on the 7-segment display [B] on the interface PC board of the header unit in the system where the address is to be set up.
4
Address setup start Confirm the items in “Address Setup Procedure,” and then set up the address according to the
operation procedure. (Be careful to note that the setup operation may differ in group control and central control s
ystems.)
Note: The address c annot be set up if switches are not operated .
stnetnoc kcehc dna noitarepOmetI
5
Display check after setup
• After address setup, “U1” “ ” is displayed on the 7-segment display.
• For follower outdoor units, “U2” to “U3” are displayed on the 7-segment display [A].
• If an error code is displayed on the 7-segment display [B], remove the cause of the problem referring to “TROUBLESHOOTING”.
6
System information check after setup
Using the 7-segment display function, check the system information of the scheduled system. (This check is executed on the interface PC board of the header unit.)
System capacity
[Number of
horsepower]
[Ton]1 2 3
SW01 SW02 SW03
[A] [B]
Rotary switch setup 7-segment display
Number of connected outdoor units
[Number of units]
[ P]1 3 3
Number of connected indoor units
[Number of
connected units]
1 4 3
After the above checks, return rotary switches SW01, SW02, and SW03 to 1/1/1.
Interface PC board
SW01 SW02 SW03
SW04
D600 D601 D602 D603 D604
SW15SW05
Push switches
Rotary switches
7-segment display
[A]
7-segment display
[B]
Address Setup
Address Setup and Check Procedure
Precautions
16
Address Setup
1 erudecorp gnittes sserddA ot og:lortnoc lartnec oN
Central control of 2 or more refrigerant lines: go to Address setting procedure 2
Address setting procedure 1
1 Turn on indoor units first, and then turn on outdoor units. 2 About one minute after turning the power on, confirm that the 7-segment display on the interface P.C.
board of the header outdoor unit indicates U. 1. L08 (U. 1. flash) .
3 Push SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates Auto 1 Auto 2 Auto 3 .
After the indication, U. 1. - - - (U. 1. flash) starts flashing on the display. When the flashing stops and U. 1. - - - (U. 1.
light) remain lit on the display, the setting is complete.
Interface P.C. board on the header outdoor unit
5 When using a central control, connect a relay connector between [U1, U2] and [U3, U4] terminals.
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make one unit the header unit using
wired remote controller.
(Example)
When controlling a single refrigerant line
centrally
When controlling 2 or more refrigerant lines
centrally
Address setting procedure
2 erudecorp oT1 erudecorp oT
System wiring diagram
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central remote
controller
Central
remote
controller
Remote
controller
Remote
controller
Remote
controller
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Central remote
controller
Remote
controller
Remote
controller
Remote
controller
SW04
SW05 SW15
SW01
SW02 SW03
D600 D601 D602 D603
D604
3
2,
4
Cautions for installation
17
Address Setup
Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the header
outdoor unit of each system. (Factory default: Address 1)
NOTE
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or “Digital Inverter” side.
Interface P.C. board on the header outdoor unit
(Example) Controlling 2 or more refr ig erant lines as a group
System wiring diagram
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Remote
controller
(Group control)
SW06 SW07 SW09 SW10
SW11 SW12 SW13 SW14
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
Line address switches on the outdoor interface PC board (O : switch on, × : switch off)
SW13 SW14
1 1 2 3 4 5 6 7 8 9
10 11 12 13 14
× × × × × × × × × × × × × ×
×
O
×
O
×
O
×
O
×
O
×
O
×
O
× ×
O O
× ×
O O
× ×
O O
× ×
× × × ×
O O O O
× × × ×
O O
× × × × × × × ×
O O O O O O
2 3 4 1 2 3 4
SW13 SW14
1 15 16 17 18 19 20 21 22 23 24 25 26 27 28
× ×
O O O O O O O O O O O O
×
O
×
O
×
O
×
O
×
O
×
O
×
O
O O
× ×
O O
× ×
O O
× ×
O O
O O
× × × ×
O O O O
× × × ×
O O
× × × × × × × ×
O O O O
2 3 4 1 2 3 4
Not used for setup of line address (do not change setup.)
Line address
Line address
18
Address Setup
2 Be sure to disconnect the relay connectors between the [U1U2] and [U3U4] terminals on all the header
outdoor units that will be connected to the central control. (Factory default: disconnected)
3 Turn on indoor units first, and then turn on outdoor units. 4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface P.C.
board of the header outdoor unit indicates U. 1. L08 (U. 1. flash) .
5 Push SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates Auto 1 Auto 2 Auto 3 .
After the indication, U. 1. - - - (U. 1. flash) starts flashing on the display. When the flashing stops and U. 1. - - - (U. 1. light) , remains lit on the display, the setting is complete.
7 Repeat steps 4 to 6 for other refrigerant lines.
Be sure to implement a test operation prior to the actual operation in each system.
2
19
Address Setup
10 Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices or “Manual address setup from the remote controller” in the next to the following page and after.
SW15
SW04
1 2
SW13
SW30
SW14
SW01 SW02
SW03
D600 D601 D602 D603 D604
SW05
7-segment
display
Header unit interface P.C. board
SW30 bit 2 switch OFF * Except the smallest line address of
header unit
8
1 2
SW30
SW30 bit switch ON * The smallest line adress of header unit
4, 6
5
8 After completing address setting of all systems, turn off DIP switch 2 of SW30 on the interface P.C.
boards of all the header outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
9 Connect the relay connectors between the [U1, U2] and [U3, U4] terminals of the header outdoor unit of
each refrigerant line.
9
U1 U2 S U3 U4 U5 U6 S
DLEIHSDLEIHS
TO CENTRAL CONTROLLER TO OUTDOOR UNITTO INDOOR UNIT
20
Address Setup
*The items in bold font must be set manually.
Outdoor un it’s inter face
P.C. board
Header unit Follow er unit Header unit Follower unit Head er unit Fac tory default
SW13, 14 (Line (system) address)
1
(No setting
required)
2
(No setting
required)
3 1
Bit switch 2 of SW30 (Terminator of indoor/ outdoor communication line and central control line)
ON
(No setting
required)
Set to OFF
after setting
addresses.
(No setting
requi
red)
Set to OFF
after set ting
addresses.
ON
Relay connector
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
Connect after
setting
addresses.
Open
Line (system) address 1 1 2 2 3
Indoor unit address 1 2 1 2 1
Group address 0 0 1 2 0
A
U1 U2
U3 U4 U3U4 U3 U4 U3 U4 U3 U4
U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2 U5 U6 U1 U2
2U1U2U1U2U1U2U1U2U1U
U5 U6
BABABABAB
Central remote
controller
Relay
connector
Relay
connector
Relay
connector
Header unit
Header unit
Header unit
Follower unit
Follower unit
Remote
controller
Remote
controller
Remote
controller
Remote
controller
Individual
Group
Indoor units (automatic setting)
Switch setting (setting example when controlling 2 or more refrigerant lines centrally) Outdoor units (setting manually)
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
21
Address Setup
With indoor wiring work completed and outdoor wiring work not done—in cases where indoor unit addresses are decided in advance from the wired remote controller, or in cases where addresses are change after address setup.
1 Arrange one indoor unit and one remote controller set to
1 by 1.
2 Turn on the power. 3 Push the
SET
+ CL +
TEST
buttons simultaneously for 4
seconds or more.
LCD begins blinking.
(Refrigerant line address)
4 Using the
TEMP
buttons, set the DN code to
.
5 Using the
TIME
buttons, set up the line address (match it with the line address on the interface PC board of the header unit on the same refrigerant line).
6 Push the
SET
button (OK when the display goes on).
(Indoor address)
7 Using the
TEMP
buttons, set the DN code to
.
8 Using the
TIME
buttons, set up the indoor address. ( ~
)
9 Push the
SET
button (OK when the display goes on).
(Group address)
10 Using the
TEMP
buttons, set the DN code
.
11 Using the
TIME
buttons, set Individual =
,
Header unit = , Follower unit = .
12 Push the
SET
button (OK when the display goes on).
(Central control address)
13 Using the
TEMP
buttons, set DN code to .
14 Using the
TIME
buttons, set up the central control
address. (
)
15 Push
SET
button. (OK when display goes on).
16 Push the
TEST
button.
Setup is finished (“Setting up” blinks; when “Setting up” goes off, operation is possible).
17 Return to the original wiring over remote controllers.
Group address
Individual: 0000 Header unit: 0001 Follower unit: 0002
(Wiring example for 2 refrigerant lines)
Line 1 Line 2
Line 1 Line 2
Outdoor
Indoor 1 Indoor 2Indoor 1
(Remote controller group control)
Indoor 2 Indoor 3
Indoor 1 Indoor 2Indoor 1 Indoor 2 Indoor 3
Line address Indoor address
1 1 1
Header
1 2 2
Follower Follower Follower Follower
1 3 2
2 1 2
2 2 2
Outdoor
OutdoorOutdoor
(Wiring during manual address setup)
Remote controller
Remote controller
Remote controller
Remote controller
Remote controller
Remote controller
Group address
In the above example, where remote controllers are not yet wired, set the address manually after individually connecting the wired remote controller.
After address setup, return to the original wiring over remote controllers.
In cases of remote controller group control
SET
TIME
TIMER SET
TEST
FILTER RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
DN code (CODE No.)
Set data
5, 8, 11, 14
6, 9, 12, 15
16
4
7 10 13
3
Manuai address setup from the remote controller
.
~
22
Address Setup
NOTE
(1) When setting the line address from the remote controller, do not use addresses 29 and 30.
Addresses 29 and 30 cannot be set up on the outdoor unit. If they are incorrectly used, the code “E04” (indoor/outdoor communication circuit error) is output.
(2) When manual address setup has been done from a remote controller, and central control over refrigerant
lines is to be done, setup the header unit of
each line as follows:
• Using SW13 and SW14 on the interface PC board of the header unit of each line, setup the line address for each line.
• Except for the line with the smallest line address number, set SW03-bit 2 to “off” for the interface PC board of the header unit of lines connected to the same central control (put the resistance of the end terminals of the central control line, indoors and outdo
ors, into one).
• Connect the relay connector between U1/U2 and U3/U4 of the header unit for each refrigerant line.
• After that, set up the central control address. (For central control address setup, refer to the installation manual of the central control devices.)
Confirming the indoor unit addresses and the position of an indoor unit using the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
When the unit is individual (the indoor unit is paired with a wired remote controller one-to­one), or it is a group-controlled one.
(Execute it while the units are running.)
1 Push the button if the units stop. 2 Push the
UNIT LOUVER
button (left side of the button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each time you push the
UNIT LOUVER
button (left side of the button).
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
Starts running
23
Address Setup
To find an indoor unit’s position from its address
When checking unit numbers controlled as a group
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1 Push and hold the and
TEST
buttons at the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2 Push the
UNIT LOUVER
button (left side of the button). Each time you push the button, the indoor unit numbers
are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
3 Push the
TEST
button to finish the procedure.
All the indoor units in the group stop.
3
1
2
1
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Stop
24
Address Setup
To check all the indoor unit addresses using an arbitrary wired remote controller. (When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line
of the selected unit are indicated
one after another and the fan and louvers of the indicated indoor units are activated.
5
6
1
3
4
2
ON / OF F
TE MP.
TIM E
S ET C L
FILT ER R ES E T
TE S T
TIME R S ET
CODE No.
UNIT No.
SE T TIN G
DATA
SE T
R. C. N o.
1 Push and hold the TIME / and
TEST
buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(
Address Change) are indicated on the LCD display.
(Select an outdoor unit.)
2 Push
UNIT LOUVER
the (left side of the button) and
SWING/FIX
buttons repeatedly to select a system address.
3 Push the
SET
button to confirm the system address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated.
4 Push the
UNIT LOUVER
button (left side of the button). Each time you push the button, the indoor unit numbers
of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
To select another system address
5 Push the
CL
button to return to step 2.
• After returning to step
2, select another system address and check the indoor unit addresses of the line.
6 Push
TEST
the button to finish the procedure.
25
Address Setup
To change an indoor unit address using a wired remote controller.
The method to change the address of an individual indoor unit (the indoor unit is paired with a
wired remote controller one-to-one), or an indoor unit in a group. (The method is available when the addresses have already been set automatically.)
(Execute it while the units are stopped.)
1 Push and hold the
SET
, CL , and
TEST
buttons at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
2 Push the
UNIT LOUVER
button (left side of the button) repeatedly to select an indoor unit number to change if 2
or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
3 Push the TEMP. / buttons repeatedly to select for CODE No.. 4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section to that
you want.
5 Push the
SET
button.
6 Push the
UNIT LOUVER
button (left side of the button) repeatedly to select another indoor UNIT No. to change.
Repeat steps
4 to 6 to change the indoor unit addresses so as to make each of them unique.
7 Push the
UNIT LOUVER
button (left side of the button) to check the changed addresses.
8 If the addresses have been changed correctly, push the
TEST
button to finish the procedure.
3 5
8
1
4
2, 6, 7
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Finish
Change the indoor unit address using a remote controller
26
Address Setup
To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check/change mode and change the addresses.
If no number appears on UNIT No., no outdoor unit exists on the line. Push
CL
button and select another line
following step
2
.
(Execute it while the units are stopped.)
1
Push and hold th e TIME / and
TEST
buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD display.
2
Push
UNIT LOUVER
(left side of the button) and
SWING/FIX
buttons repeatedly to select a system address.
3
Push the
SET
button.
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated. At first, the current indoor unit address is displayed in SET DATA. (No system address is indicated.)
4
Push the TIME / buttons repeatedly to chang e the value of the indoor unit address in SET DATA. Change the value in SET DATA to that of a new address.
5
Push the
SET
button t o confirm the new address on SET DATA.
6
Push the
UNIT LOUVER
button (l eft side of the button) repeatedly to select another address to chan ge. Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor un it are activated.
Repeat steps
4 to 6 to change the indoor unit addresses so as to make each of them unique.
7
Push the
SET
button.
(All the segments on the LCD display light up.)
8
Push the
TEST
button to finish the procedure.
3 2
1
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Cancels t he line selection
- - --
4 8
5, 7
6
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Push to finish
settin g.
Finish
27
Address Setup
<Clearing Indoor Unit address>
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2
U1U3U2
U4
U5 U6
U1 U2
A B
Central remote controller
Header unit
Follower unit
Follower unit
Remote controller
Remote controller
Remote controller
Remote controller
Indoor units to have their addresses initialized
Header unit
Header unit
Method 1
Clearing each address separately using a wired remote controller. Set the system address, indoor unit address and group address to “ ” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previ­ous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1
Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the line as below.
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the ad-
dresses. About one minute after turning on the power, confirm that the 7-segment display on the header outdoor unit indicates “ U.1. - - -” and operate the interface P.C. board on the header outdoor unit of the refrigerant line as follows.
3 Confirm that the 7-segment display indicates “ A.d. c.L.” and set SW01, SW02 and SW03 to 1, 1, 1 respec-
tively.
4 After a time “ U.1.L08” appears on the 7-segment display if the address clearing has been completed
successfully. If the 7-segment display indicates “ A.d. n.G.” , the outdoor unit may still connected with other refrigerant lines. Check the connection of the relay connectors between [U1, U2] and [U3, U4].
NOTE
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. (Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the header outdo
or unit if the switch is OFF. (Leave it as it is if it has already been set to ON.)
sesserdda elbaraelC40WS30WS20WS10WS
2 1 2
Confirm that the 7-segment display indicates “A.d.buS” and turn SW04 ON for more than five seconds.
System/indoor unit/group address
2 2 2
Confirm that the 7-segment display indicates “A.d.nEt” and turn SW04 ON for more than five seconds.
Central control address
Resetting the address (Resetting to he factory default (address undecided)
28
Address Setup
<Clearing Indoor Unit address>
To set up the indoor address of a unit with an address that is undefined due to the extension of indoor units or replacement of PC board, etc., follow the methods below.
Method 1
Set up an address individually from a wired remote controller. (Line address, Indoor address, Group address, Central address) For the setup method, refer to “Manual address setup from the remote controller.” above.
Method 2
Set up an address from the outdoor unit. * Leave the addresses of the units for which addresses have already been set up as they are. Set up an address
only for the unit where the address is undefined. Addresses are allocated from lower numbers.
Setup procedure
Set up the outdoor header units in the refrigerant line to which indoor units have been added, as follows.
1 Remove the relay connector between U1/U2 and U3/U4. 2 If it is off, turn on SW30-bit 2 on the interface PC board at outdoor header unit side.
* Turn off the power, and then execute the operation.
3 Turn on the indoor/outdoor power for the refrigerant line for which an address is to be set up.
After approximately 1 minute, check that “ U.1. - - -” is displayed on the 7-segment display.
4 Execute the following operation on the interface PC board of the header unit.
...
... is counted and displayed on the 7-segment display.
5 When “
” is displayed on the 7-segment display, the setup operation finished.
Turn off the indoor/outdoor power.
6 Return to the following setup as before.
• Relay connector
• SW30-bit 2
• SW01, SW02, SW03
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2 U5 U6
U1 U2
A B
U3 U4
U1 U2
U1U3U2
U4
U5 U6
U1 U2
A B
Central remote controller
Header unit
Follower unit
Follower unit
Remote controller
Remote controller
Remote controller
Remote controller
Added indoor unit
Header unit
Header unit
40WS30WS20WS10WS
2 14 2 After checking that “In.At” is displayed on the 7-segment display, push SW04 for 5 seconds or more.
In the case of an increase in address-undefined indoor units (extension, etc.)
.
.---
29
Address Setup
When the central control system is connected, check that the following setup has finished after address setup.
NOTE
The figure above does not show all the electric wires. For details, refer to the installation manuals for the outdoor unit, indoor unit, remote controller, or optional devices.
U1 U2
U1 U2 U1 U2 U1 U2 U1 U2
U5 U6
U3 U4
)A( tinu redaeH)A( tinu redaeH
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
A B A B A B A B
(5)(4)
(5)
)2()1( (3)
Other refrigerant line
U1 U2
U3 U4
U3 U4
U1 U2 U5 U6
To other refrigerant line
U3 U4
Line address = 1Line address = 2
Central remote controller
Follower unit (B) Follower unit (C)
Outdoor unit
Indoor unit
Remote controller
Remote controller
Remote controller
kcehCsmeti kcehc niaM
Relay connector
(1) Is the relay connector of the header unit connected after address setup?
(2) Is the relay connector of the follower unit disconnect?
Terminator (3) Is the terminator (SW30-bit 2) of the header unit with the smallest line address
number in the central control turned on? (Setup is unnecessary for follower units.)
(4) Is the terminator (SW30-bit 2) of the heade
r units, except for the line with the
smallest central control line address, turned off? (Setup is unnecessary for follower units.)
Line address (5) Are addresses in the line address (SW13, SW14) not duplicated in each refrigerant line?
<Clearing Indoor Unit address>
Check after Address Setup when Central Control System is connected
30
Address Setup
<Clearing Indoor Unit address>
U1 U2
U1 U2 U1 U2 U1 U2 U1 U2
U5 U6
U3 U4
U1 U2 U5 U6
U3 U4
U1 U2 U5 U6
U3 U4
A B A B A B A B
(1) (2) (4) (3)
(5)
(6)
Outdoor unit
Indoor unit
Remote controller
Remote controller
Remote controller
Header unit (A) Follower unit (B) Follower unit (C)
kcehCsmetikcehcniaM
(1) Are the indoor and outdoor communication lines of the header unit connected to the U1/U2 terminals?
(2) Is the relay connector between the U1/U2 terminal and the U3/U4 terminal disconnect? (Set up at shipment from the factory)
(3) Is the communication line between outdoor units connected to the U5/U6 terminal?
(4) Is the terminator (SW30-bit 2) on the interface PC board of the header unit turned on? (Set up at shipment from the factory)
(5) Is the
terminator
of the shield wire open?
(6) Is the
terminator
of the shield wire earthed at the header unit side?
Prior to the test operation, check the following items to verify there are no problems with the installation work.
Main check items for electric wiring
The communication system differs from that of R22 or R407 refrigerant “Modular Multi System” air conditioners. Check wiring points again carefully.
(1) In the case that a central control system is not connected:
NOTE
The figure above does not show all the electric wires. For details, refer to the installation manuals for the outdoor unit, indoor unit, remote controller, or optional devices.
Chaeck items before Test Operation ( before powering - on)
31
Test Operation
Checklist 1
Using Checklist 1, check that there are no problems with the installation work.
Is the capacity of the Outdoor total capacity circuit breaker (Earth leakage breaker) appropriate?
A Indoor unit A A A
A
Is the gauge of the power cable correct?
mm²
mm² mm²
mm²
Indoor unit
Header unit (A)
Follower unit (B)
Follower unit (C)
Header unit (A) Follower unit (B) Follower unit (C)
Is the control communication l
ine
correct?
Indoor-outdoor connection terminals (U1, U2)
Outdoor-outdoor connection terminals (U5, U6)
Central control system connection terminals (U3, U4)
Is the power of indoor units supplied collectively? Is it grounded to earth? Is the resistance sufficient? (10M or higher) Is the main power voltage sufficient? (within 380-415 V ± 10%) Is the diameter of connecting pipe correct? Is the branch kit corr
ect? Is the water drain of the indoor unit arranged so that it flows without accumulation? Is the heat insulation of pipes sufficient? (connecting pipes, branch kit) Is there no short circuit of discharge air in the indoor/outdoor units? After an airtightness test of the pipes, are vacuuming and adding of refrigerant executed? Are the valves of all the outdoor units fully opened?
Gas side Liquid side Bala
nce side
Header unit (A) Follower unit (B) Follower unit (C)
V
10M or higher
32
Test Operation
Cooling, Heat pump type
Calculate the additional amount of refrigerant from the additional amount of refrigerant (A) by the pipe diameter on the liquid side, the pipe length to be connected, and the corrective amount of refrigerant (B) according to Indoor unit horsepower, and the corrective amount of refrigerant (C) according to sys
tem horsepower.
(A)
First, enter the total length for each liquid pipe
diameter in the following table, and then calculate the additional amount of refrigerant by
pipe length.
<Additional amount of refrigerant by pipe length>
Next, refer to the following table for the corrective amount of refrigerant (B) according to indoor unit horsepower.
<According to indoor unit horsepower>
kg/HP
HP
kg
Lastly, add the additional amount of refrigerant by pipe length (A) and the correcti
ve amount of refrigerant by indoor unit horsepower (B) to the corrective amount of refrigerant by combined horsepower (C). This is the final additional amount of refrigerant. If a minus sign is indicated as the result, do not reduce or add the refrigerant (= 0 kg).
<Addit ional am ount o f refri gerant>
Additional amount
of refrigerant
Actual liquid pipe length x Additional amount
of refrigerant per 1 m of l
iquid pipe
Corrective amount of refrigerant
according to
system horsepower
Corrective amount of refrigerant
according to indoor unit horsepower
=
+ +
0.025 x 1.2 x
0.055 x 1.2 x
0.105 x 1.2 x
0.160 x 1.2 x
0.250 x 1.2 x
0.350 x 1.2 x
Ø6.4 Ø9.5 Ø12.7 Ø15.9 Ø19.0 Ø22.2
= kg
kg kg kg kg kg
kg kg kg kg
=
(B)
Pipe diam eter on t he
liqui d side
Standard amount of
refrig erant
Standard Indoor
uni
Fresh Air intake
Indoor unit
Air to Air Heat Exchanger
with DX-coil
Total
pipe len gth on each
liqui d side
m
Addit ional am ount o f refri gerant p ipe
diameter on each l iquid side
kg
= =
= =
HP kg
HP kg
HP kg
Additional refrigerant charge amount Indoor unit
Additional refrigerant charge amount Capacity of Indoor unit Corrective amount of refrigerant
0.4
0.2 0.2
Additional amount of refrigerant by pipe length (A) kg Corrective amount of refrigerant according to indoor unit horsepower (B) kg Corrective amount of refrigerant according to combined horsepower (C) kg Additional amount of refrigerant kg
(C)
Next, refer to the Table 1-1~1-5 on P. 20 "A dding refrig erant" for th e correc tive amo unt of refrig erant (C) acc ording to system horsep ower.
Checklist 2
Check the additional amount of refrigerant.
<Setup Remote Controller>
33
Test Operation
The cooling/heating test operation check can be performed on both the indoor remote control and the outdoor header unit interface PC board.
(1) Test operation start/stop operation Test operation from the indoor remote control
• Wired remote control: Refer to the items below in “Test operation” of the wired remote control.
• Wireless remote control: Refer to the items below in “Test operation” of the wireless remote control.
Wired remote control Wireless remote control (Except the 4-way
Cassette type and the Ceiling type)
Test run (Forced cooling operation) Requirement:
• Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10 sec-
onds or more, “Pi!” sound is heard and the operation changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly. Check cool air starts blowing. If the operation does not start, check wiring again.
2. To stop a test operation, push TEMPORARY button
once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor units after forced cooling operation.
1, 5
3
2, 4
Operation contentProcedure
1
2
When the Test button is pushed for 4 seconds or more, “TEST” is displayed in the display section, and the unit enters test operating mode.
5
Push the Test button to clear the test operating mode. (“TEST” disappears from the display section, and the status returns to the normal stopped status.)
3
Using the Select Mode button, select the “ COOL” or “ HEAT” operating mode.
• Do not use an operating mode other than “ COOL” or “ HEAT”.
• Temperature adjustment is unavailable during test operation.
• Error is detected as usual.
Push the button.
4
When the test operation has finished, push the button to stop the operation. (The same display as in procedure 1 appears in the display section.)
TEMPORARY- Button
<Setup Remote Controller>
Cooling / heating test operation check
34
Test Operation
<Setup Remote Controller>
Wireless remote controller (4-way Cassette type)
Test run (Forced cooling operation) Requirement:
• Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10 sec­onds or more, “Pi!” sound is heard and the operation changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly. Check cool air
starts blowing. If the operation does
not start, check wiring again.
2. To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
Wireless remote controller (Ceiling type)
Test run (Forced cooling operation) Requirement:
• Finish the forced cooling operation in a short time because it applies excessive strength to the air conditioner.
How to perform forced cooling operation
1. When TEMPORARY button is pushed for 10 sec­onds or more, “Pi!” sound is heard and the operation changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly. Check cool air starts blowing. If the operation does not start, check wiring again.
2. To stop a test operation, push TEMPORARY button once again (Approx. 1 second).
• Check wiring / piping of the indoor and outdoor
units in forced cooling operation.
Test operation from the outdoor unit
• Refer to “Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit” in “Service Support Function.”
NOTE : The test operation returns to normal operating mode after 60 minutes.
TEMPORARY
button
TEMPORARY button
35
Troubleshooting in Test Operation
90
If there are phenomena such as the output of a check code or the remote controller is not accepted when powered on after wiring work or during address setup operation, the following causes are considered.
A Check Code is displayed on the remote controller
* “L05”: Displayed on the indoor unit set up with priority
“L06”: Displayed on the indoor units except the one set up with priority
Check code
displayed on the
indoor remote
controller
Header
unit 7-
segment
display
serusaemretnuoCesuaC
E04
no si rewop tinu roodtuo redaeh eht taht kcehCffo si rewop roodtuo nehW
L08
Address setup error
• Only line addresses of the connected indoor units are undefined.
• The outdoor line address and the line addresses of all the indoor units do not match.
• The indoor addresses are duplicated. (Units except t
hose displaying E04 are duplicated.)
• A header unit is not set up in group control (except groups displaying E04).
Set up the address again.
E08 -XX
Alternate
blinking
Duplication of indoor addresses (address number in the subcode of the check code are duplicated).
Set up the address again.
E07
There is no outdoor terminator or there are two or more terminator resistor. (After address setup, when terminator setup is changed after power on)
Check SW30 bit 2 of the header unit. No connection between multiple refrigerant lines: SW30 bit 2 is on. Connection between multiple refrigerant lines: SW30 bit 2 of the connected header unit is turned on only for one line.
Transmission circuit error at the interface side (PC board failure)
Replace the interface PC board.
E06
After address setup, communication from all
t
he indoor units is interrupted under the condition that a normal operation can be performed.
Check and correct disconnection of the indoor/ outdoor communication line (the communication line between the header unit and the leading indoor unit). Check for the influence of communication noise.
E16
E16 -XX
Alternate
blinking
Exceeded the number or capacity of connected indoor units
Adjust the number or capaci
ty of connected indoor
units.
E23 E23
Communication between outdoor units has stopped. Check the number of connected outdoor units.
Check that outdoor unit power is on.
E25 E25
Duplication of outdoor addresses (only when an outdoor address was manually set up)
Do not use manual setup for outdoor addresses.
E26
E26 -XX
Alternate
blinking
Number of connected outdoor units has decreased.
• When installing an outdoor
backup
• The power of a follower unit is not turned on.
Correction of the cause of error occurrence
• If it occurs when installing a backup, clear the error after setup finishes.
• If the power of a follower unit is not turned on, turn on the power.
L04 L04
Duplication of outdoor line addresses
• Line address setup error (occurred after connection between U1/U2 and U3/U4 connectors)
Modify the line address se
tup of the header unit between lines. (Set up SW13 and SW14 on the interface PC board.)
L05(*) L06 Duplication of indoor units with priority Set up priority only for one indoor unit.
L06(*)
There are two or more indoor units set up with priority.
Among indoor units indicating “L05,” set one u nit with priority.
L08 L08
Address setup error
• Only indoor addresses of all the connected indoor units are undefined.
Set up the addresses again. Modify the setup.
ON
1 2
SW30
<Cooling, Heat pump type>
36
Troubleshooting in Test Operation
<Cooling, Heat pump type>
Operation from the indoor remote controller is not accepted, and a Check Code is displayed on the 7 - seqment display of the interface PC board of header unit.
There is no display of a Check Code on the 7 - segment display on the interface PC boardof the header unit, although there is indoor unit that is not accepting operation from the indoor remote controller.
Indoor remote
controller
status
Header unit
7-segment
display
serusaemretnuoCesuaC
No response
L08
Line addresses and indoor addresses of all the connected indoor units are not set.
Set up addresses.
There is no header unit of group control. Set up a group address.
E19 -00
Alternate
blinking
:redro eht nI( .niaga rewop eht no nruT.no denrut ton si rewop tinu roodnI
indoor outdoor)
Indoor/outdoor communication
line is not correctly connected to the U1/U2 terminal of the header unit. (Fig 1) (Indoor / outdoor cannot communicate before address setup.)
Correct wiring
There is no of outdoor terminal resistance, or there are two or more resistances (before address setup).
Check SW30 bit 2 of the header unit. No connection between multiple refrigerant lines: SW30 bit 2 is on. Connection between multiple refrigerant lines: SW30 bit 2 of the connected header unit is turned on only for one line.
E19 -02
Alternate
blinking
When connecting an indoor/outdoor communication line between outdoor units under the condition of a connected communication line between outdoor units. (Fig 2)
Correct wiring
E20 -01
Alternate
blinking
Address setup is performed with connecting an indoor/ outdoor communication line between outdoor units.
(Fig 3)
Correct wiring
Address setup is performed under the condition of connecting multiple refrigerant lines. (Fig 3)
Correct wiring
ON
1 2
SW30
Indoor remote
controller
status
Header unit
7-segment
display
serusaemretnuoCesuaC
No response None
The communication line is not connected between indoor and outdoor (the unit that does not respond to the indoor remote controller).
Modify the wiring.
Line address and indoor address are not set (the unit that does not respond to the indoor remote controller).
Set up the address.
The power of the header unit
of the group is not turned on in indoor group control (the unit that does not respond to the indoor remote controller).
Turn on the power.
Group address is set to the follower unit for individual control (the unit that does not respond to the indoor remote controller).
Set the group address to “0” in the case of individual control.
No display on the
indoor remote
controller (no line
is output.)
None
Th
e power is not turned on (the unit that is not displayed on
the indoor remote controller).
Turn on the power.
The indoor remote controller is not connected with a wire (the unit that is not displayed on the indoor remote controller).
Modify the wiring.
Miswiring of the indoor remote controller (the unit that is not displayed on the indoor remote controller)
Modify the wiring.
Indoor remote controller co
mmunication circuit trouble (the unit that is not displayed on the indoor remote controller) If 220-240 V is incorrectly applied to the indoor remote controller terminal, the remote controller communication circuit fails.
Remove the Faston connect terminal connected to indoor remote controller terminals A/B, and check the voltage. If voltage is not applied (normally 15 to 18 V), replace the PC board.
37
Troubleshooting in Test Operation
In checking the number of connected outdoor units and connected indoor unit after address setup, a lower number of connected units is displayed.
(There are outdoor/indoor units that do not operate in a test operation.)
serusaemretnuoCesuaCsutatS
The number of
connected
outdoor units is
too few.
Miswiring of communication lines between outdoor units or an unconnected wire ( Fig. 4). (Address setup operation finished without recognizing a miswired follower unit.)
After modification of wiring, set up the addresses again and check the number of connected outdoor units.
The number of
connected indoor
units is too few.
Miswi
ring of communication lines between indoor units or an unconnected wire. (Fig 5) (Address setup operation finished without recognizing a miswired indoor unit.)
After modification of wiring, set up the addresses again and check the number of connected indoor units.
The number of
outdoor units
connected to a
group is too few in
group operation
from an indoor
remote controller.
The indoor remote controller
is not connected with wire.
Miswiring of the indoor remote controller
Using the main indoor remote controller connected to a group, start a test operation, specify the unit that is not operating (the unit not connected to the group), and then check the wiring.
Indoor remote controller communication circuit trouble If 220-240 V is incorrectly applied to the remote controller terminal, the remote contr
oller communication
circuit fails.
Using the main indoor remote controller connected to a group, start a test operation and then specify the unit that is not operating (the unit not connected to the group). Remove the Faston connect terminal connected to remote controller terminals A/B, and check the voltage. If voltage is not applied (normally 15 to18 V), replace the PC board.
<Cooling, Heat pump type>
38
Troubleshooting in Test Operation
96
Miswiring example
F igure
R emote
controller
s tatus
He ad er unit
7-s eg ment
dis play
Mis wiring exa mple
F ig. 1
No
res ponse
E 19-00
F ig. 2
No
res ponse
E 19-02
F ig. 3
No
res ponse
E 20-01
elpmaxegniriwsiMsutatSerugiF
F ig. 4
T he number of conne cted outdoor units is too few.
F ig. 5
T he number of conne cted indoor units is too few.
U3 U 4 U5 U 6
U1 U 2 U 1 U 2 U1 U 2 U1 U 2
He ader unit He ader unit
U1 U 2
He ader unit
U1 U 2 U 1 U2
U5 U6 U1 U2 U 5 U 6
Follower unit
U1 U 2
U1 U 2 U1 U2
U1 U 2 U1 U2
U1 U 2 U1 U 2
U5 U 6
U1 U 2
U1 U 2 U 1 U2
[Line 1]
U1 U 2
He ader unit F ollower unit He ader unit F ollower unit
He ader unit F ollower unit
[Line 2]
U1 U 2
U1 U2 U1 U2
U3 U 4U1 U2
U1 U2 U1 U 2
U3 U 4 U1 U2
U1 U2 U 1 U 2
U5 U6
U5 U 6
U3 U4
U1 U2
or
or
U3 U4
U1 U2
He ader unit F ollower unit Hea der unit F ollower uni t Hea der unit F ollower unit
or
Wiring forgotten
U1 U 2
U1 U 2
A B
U1 U2
U1 U2 U1 U 2
tinurewolloFtinuredaeH
Troubles hooting in Tes t Operation (C ontinued)
39
Monitor Function
When using a remote controller with the model name RBC-AMT32E the following monitor functions can be used.
Calling of display screen <Content>
The sensor temperature or operation status of the remote controller, indoor unit, or the outdoor unit can be known by calling up the service monitor mode from the remote controller.
[Procedure]
1 Push
TEST+CL
buttons simultaneously for 4 seconds or more to call up the service monitor mode.
The service monitor goes on, and temperature of the CODE No. is firstly displayed.
2 Push the temperature setup
TEMP
buttons to select the CODE No. to be monitored.
For displayed codes, refer to the table next page.
3 Push
SET
button to determine the item to be monitored.
Then monitor the sensor temperature or operation status of indoor unit and the outdoor unit in the corresponding refrigerant line.
4 Pushing
TEST
button returns the display to the normal display.
SET
TIME
TIMER SET
TEST
FILTER RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
1
4
2
3
40
Monitor Function
.oNEDOC
Indoor unit data *
2
00 Room temperature (Use to
CIndoor suction air temperature (TA)20
C
)JCT(erutarepmetliocroodnI30
C
)2CT(erutarepmetliocroodnI40
C
)1CT(erutarepmetliocroodnI50
06 Indoor discharge air temperature (TF)
*
1
slp0051=]0510[slp01/1×gninepoVMPrhodnI
Filter sign time
80
System data
stinu84=]8400[tinustinuroodnidetcennocfo.oNA0
0B Total horsepower of connected indoor units ×10 HP [
[2500} = 2500h
0415]=41.5HP
[0003]=3 unitstinustinuroodtuodetcennocfo.oNC0
PH24=]0240[PH01×stinuroodtuoforewopesrohlatoTD0
F9
Suction temperature of air to air heat exchanger (TSA)
*1
×1
[0024] = 24
FF3A
Outside air temperature (TOA)
*1
×1
U1 U2 U3 10 20 30 MPa 11 21 31 MPa 12 22 32 13 23 33 15 25 35 16 26 36 17 27 37 18 28 38 19 29 39 1A 2A 3A 1C 2C 3C 1D 2D 3D 1E 2E 3E 1F 2F 3F
U1 U2 U3 50 60 70 pls 51 61 71 pls 52 62 72 pls 53
63 73 A
54
64 74 A
56 66 76 rps 57 67 77 rps 59 69 79 mode 5A 6A 7A 5B 6B 7B 5D 6D 7D 5E 6E 7E 5F 6F 7F HP
Outdoor unit
individual data 3
*5
90 Heating/cooling recovery controlled
0: Normal 1: Recovery controlled
[0010]=Heating recovery controlled [0001]=Cooling recovery controlled
91 Pressure release
0: Normal 1: Release controll ed
[0010]=Pressure release controlled
92
Data nam e Disp lay for mat
Unit
Remot e contr oller dis play exam ple
Data nam e Disp lay for mat
Unit
Remot e contr oller dis play exam ple
Data nam e Disp lay for mat
Unit
Remot e contr
oll er disp lay examp le
Data nam e Disp lay for mat
Unit
Remot e contr oller dis play exam ple
.oNEDOC
dellortnocesaelererutarepmetegrahcsiD=]1000[esaelererutarepmetegrahcsiD
93
Follower unit release (U2/U3 outdoor units)
[0100]=U2 outdoor unit release controlled [0010]=U3 outdoor unit release controlled [0001]=U4 outdoor unit release controlled
erutarepmetknistaeh2UDPIrosserpmoC 1×erutarepmetknistaeh1UDPInafroodtuO 1×erutarepmetknist
aeh2UDPInafroodtuO
PH61=]6100[rewopesrohtinuroodtuO
[0135] = 13.5A
1 fan model : Compressor 2 and Outdoor fan 1 current (I2) 2 fan model : Compressor 2 and Outdoor fan 2 current (I2)
×10
01×snoitulover1rosserpmoC
[0642] = 64.2rps
01×snoitulover2rosserpmoC
Outdoor unit individual data 2
*4
gninepo1VMP
[0500] = 500plsgninepo3VMP
gninepo4VMP 1 fan model : Compressor 1 curent (I1) 2 fan model : Compressor 1 and Outdoor fan 1 current (I1)
×10
edom85=]8500[ed
omnafroodtuO
erutarepmetknistaeh1UDPIrosserpmoC
[0024] = 24
CODE No.
)1LT(edisdiuqiltaerutarepmeT
)2LT(edisdiuqiltaerutarepmeT
)3LT(edisdiuqiltaerutarepmeT
Outdoor unit individual data 1
*3
001×)dP(erusserpnoitnetedrosneserusserp-hgiH
[0123] = 1.23MPa
001×)sP(erusserpnoitnetedrosneserusserp-woL
)1DT(erutarepmetegrahcsid1rosserpmoC
×1
)OT(erutarepmettneibmaedistuO
)1ST(erutarepmetnoitcuS
)3ST(erutarepmetnoitcuS
[0024] = 24
)2DT(erutarepmetegrahcsid2rosserpmoC
)1ET(erutarepmetliocroodtuO
)2ET(erutarepmetliocroodtuO
)1GT(erutarepmetliocroodtuO Outdoor coil temperature (TG2)
CODE No.
*1 Only a part of indoor unit types is installed with the discharge air temperature sensor.This temperature is not
displayed for other types. *2 When the units are connected to a group, data of the header indoor unit only can be displayed. *3 The first digit of an CODE No. indicates the outdoor unit number. *4 The upper digit of an CODE No. -4 indicates the outdoor unit number.
1 , 5 ... U1 outdoor unit (Header unit)
2*, 6 ... U2 outdoor unit (Follower unit 1)
3 , 7 ... U3 outdoor unit (Follower unit 2) *5 Only the CODE No. 9* of U1 outdoor unit (Header unit) is displayed.
***
* *
41
Monitor Function
7- segment display on outdoor unit ( interface P.C. board )
The interface control P.C. board features a 7-segment LED display designed to check operational status. Display items can be changed by changing the combination of the number settings of rotary switches provided on the P.C. board (SW01, SW02 and SW03).
Checking Procedure to Be Followed in Event of Abnormal Shutdown
If the system is shut down due to trouble in the outdoor unit, perform checks in the following steps:
1 Open the panel of the outdoor unit and inspection window of the electric parts box, and check the 7-
segment display.
The check code is displayed in the right-hand section of the 7-segment display [B]. [U1] [OOO] ([OOO]: Check code)
* To c
heck the check code, set the rotary switches SW01/SW02/SW03 to [1/1/1]. If there is a sub-code, the display alternates between the check code [OOO] (3 seconds) and the subcode [OOO] (1 second).
2 Check the check code and follow the applicable diagnostic procedure. 3 If the 7-segment display shows [ ] [ ], there is a check code in a follower unit.
Push the push-switch SW04 on the header unit a
nd hold for several seconds. As the fan of the outdoor unit in which the trouble has occurred comes on, open the panel of the unit, and check the check code shown on the 7-segment display.
4 Perform checks in accordance with the diagnostic procedure applicable to the check code.
Interface P.C. board
SW01 SW02 SW03
SW04
D600 D601 D602 D603 D604
SW15SW05
7-segment display
[A]
Push switch
7-segment display
[B]
Rotary switches
42
Monitor Function
(1) Display of system Information (Displayed on Header Outdoor Unit Only)
liatedyalpsiD30WS20WS10WS
1
1
3
Unused A B
2
System capacity A […8]~[64]:8 to 64 HP
B [HP]
3
No. of outdoor units A […1]~[…3]:1 to
3
B […P]
4
No. of indoor units connected / No. of units with cooling
thermostat
ON
A […0.]~[64.]:0 to 64 (No. of units connected)
B [C…0]~[C64]:0 to 64 (No. of units with cooling
thermostat
ON)
5
No. of indoor units connected / No. of units with heating
thermostat
ON
A […0.]~[64.]:0 to 64 (No. of
units connected)
B [H…0]~[H64]:0 to 64 (No. of units with heating
thermostat
ON)
6
Amount of compressor command correction
A Value displayed in hexadecimal format
B
7
Release control A Normal: [r. …], During release control: [r.1]
B –
8
Oil equalization control Normal: [oiL-0]
During oil equalization control: [oiL-1]
9
Oil equalization request A Displayed through LED segment lighting pattern
B
10
Refrigerant/oil recove
ry operation A Oil recovery in cooling: [C1], Normal: [C …]
B Refrigerant recovery in heating: [H1], Normal: [H …]
11
Automatic addressing A [Ad]
B During automatic addressing: [… FF], Normal: [… … …]
12
Power peak-cut A [dU]
B Normal: [… … …], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
13
BAsutatslortnoclanoitposyalpsiD)tupnidraob.C.P(lortnoclanoitpO
Operation mode
selection: During priority heating (normal) h.
. . . .
.cgniloocytiroirP
. . . .
.HylnognitaeH
. . . .
.CylnognilooC
. . . .
Priority given to No. of indoor units in operati on n.
. . . .
.UtinuroodnicificepsotnevigytiroirP
. . .
.
External master ON/OFF: Normal
.…. . . .
Start input
.1. . . .
Stop input
.0. . . .
Night operation: Normal
. . …. . .
Start input
. . 1. . .
Snowfall operation: Normal
. . .…. .
Start input
. . .1. .
14
Optional control
(BUS line input)
Same as above
15
Unused
16
A
B –
F G
A
D
U2U1 U3 U4
Dp
B
E C
Display section A Display section B
Outdoor unit No.
If element F shown on sketch at left turned on: Header unit oil equalization request If element C shown on sketch at left turned on: Follower unit oil equalization request
43
Monitor Function
(2) Display of Outdoor Unit Information (Displayed on each Outdoor Unit)
liatedyalpsiD30WS20WS10WS
1
1
1
Outdoor unit No.: [U1] to [U3]A
Check code
B Check code (only latest one displayed)
If there is no check code, [– – –] is displayed. If there is sub-code, check code [
] and sub-code [– ] are displayed
alternately, for 3 s econds and 1 second, respectively.
<SW04> push SW function: Fan operation at outdoor unit with check code. 7-segment display section A: [E.1]
<SW04 + SW05> push SW function: Fan operation at outdoor unit without check code. 7-segment display section A: [E.0] <SW05> push SW function: Fan operation function check mode is cancelled.
2
A
B –
3
O
peration mode A Stop [… …]
Normal cooling: [… C], Normal heating: [… H], Normal defrosting: [… J]
B –
4
Outdoor unit HP capacity A
8HP: [… 8], 10HP: [… 10], 12HP: [… 12], 14HP: [14], 16HP: [16], 18HP: [18], 20HP: [20], 22HP: [22]
B […HP]
5
Compressor operation command * Operation data of each compressor is displayed in turn in 2 second intervals.
Normal: Compressor speed (rps) is displayed in decimal format.
7-segment display (A/B): [C1. ... ... ... ] [ ... , ] [C2. ... ... ... ] [... , ]
<SW04> push SW function: Switches to display of operating current (decimal value). 7-segment display (A/B): [i1. ] [i2. ] Pressing of <SW05> restores normal display.
6
Outdoor fan mode A [FP]
B Mode 0 to 63: [… 0] to [63]
7
Compressor backup A [C.b.]
B
Displays compressor backup setting status Normal: [… … …] Compressor No. 1 backup: [1 … …] Compressor No. 2 backup: [… 1 …]
8
A
B –
9
Control valve output data Displays co
ntrol output status of solenoid valve A B
1.HFFO:2evlavyaw-4/NO:evlavyaw-4 …0.HNO:2evlavyaw-4/FFO:evlavyaw-4
10
001.2
SV2: ON / SV51: OFF / SV52: OFF
010.2SV2: OFF / SV51: ON / SV52: ON 100.2SV2: OFF / SV51: OFF / SV52: ON
11
SV3A: ON / SV3B: OFF / SV3C: OFF / SV3D: OFF 3. 1 0 0 0 SV3A: OFF / SV3B: ON / SV3C: OFF / SV3D: OFF 3. 0 1 0 0 SV3A: OFF / SV3B: OFF / SV3C: ON / SV3D: OFF 3. 0 0 1 0 SV3A: OFF / SV3B: OFF
/ SV3C: OFF / SV3D: ON 3. 0 0 0 1
12
001.4
SV41: ON / SV42: OFF
010.4SV41: OFF / SV42: ON 100.4
SV41: OFF / SV42: OFF
13 PMV1/PMV3 opening Displays opening data in decimal format
. P
tamroflamicedniatadgnineposyalpsiDgninepo4VMP
14
. P
15
Oil level judgment status
].Lo[AlamroN
B
Initial display: [… … …], Oil level judgment result: [#. .$] Displayed letters #, and $ represent judgment results for compressor Nos. 1 and 2, respectively (“0” for normal and “1” or “2” for low level).
<SW04> push SW function: Displays low lev el confirmed judgment result of each compressor. * Pressing of <SW05> restores
normal display.
A [L d.] B
Compressor No. 1 low level being confirmed: [L … …] Compr
essor No. 2 low level being confirmed: [… L …]
SV2, SV51, SV52
PMV4
PMV1/PMV3 ,
44
Monitor Function
SW01 SW02 SW03
Pd pressure data A BPd pressure (MPaG) is displayed in decimal format.
(MPaG: Approx. 10 times magnitude of kg/cm2G) P d. 2 Ps pressure data Ps pressure (MPaG) is displayed in decimal format. P s. 3 PL pressure conversion data Converted PL pressure (MPaG) is displayed in decimal format. P L.
... ... 1d tlobmys retteLatad rosnes 1DT Temperature sensor reading (°C) is displayed
ataD.tamrof lamiced ni
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
*
* **
TD2 sensor data • Letter symbol and data are displayed Letter symbol t d 2 ... ...
Data
TS1 sensor data
alternately, for 1 second and display for 3
... ... 1S tlobmys retteL.ylevitcepser ,sdnoces
• Data is displayed in [ ].
Data
TS3 sensor data
• Data with negative value is displayed as [– ].
Letter symbol t S 3 ... ...
Data
... ... 1E tlobmys retteLatad rosnes 1ET
Data
... ... 2E tlobmys retteLatad
rosnes 2ET
Data
... ... 1L tlobmys retteLatad rosnes 1LT
Data
... ... 2L tlobmys retteLatad rosnes 2LT
Data
... ... 3L tlobmys retteLatad rosnes 3LT
Data
... ... ...o tlobmys retteLatad rosnes OT
Data
SW01 SW02 SW03
... ... ...1 Flobmys retteLatad rosnes 1KT Temperature sensor reading (°C) is displayed
ataD.tamrof lamiced ni
... ... ...2 Flobmys retteLatad rosnes 2KT
Data
... ... ...4 Flobmys retteLatad rosnes 4KT
Data
... ... ...5 Flobmys retteLatad rosnes 5KT
Data
... ... 1G tlobmys retteLatad rosnes 1GT
Data
... ... 2G tlobmys retteLatad rosnes 2GT
Data
Display detail
5
7
9
1 2
Display detail
1
2
10
11
13
14
15
16
1
4
5
6
7
51
4
(3) Display of Outdoor Cycle Data (Display at each Outdoor Unit)
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
.
* **
45
Monitor Function
liatedyalpsiD30WS20WS10WS
3
1
1~3
AError data
[U.
], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B Check code is displayed (latest one only).
If there is no check code: [– – –].
2
Type of compressor installed A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B
3
Outdoor unit HP capacity A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B
8HP: [… 8], 10HP: [… 10], 12HP: [… 12], 14HP: [14], 16HP: [16], 18HP: [18], 20HP: [20], 22HP: [22]
4
Compressor operation command A
[U.
], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B Indicates which compressor is ON.
Any unconnected compressors is represented by “–”. B
1 0 NOsi1.oNrosserpmocnehW
0 1NOsi2.oNrosserpmocnehW
5
Fan operation mode A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B At rest: [F … 0], In mode 63: [F 6 3]
6
Release signal A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B Normal: [r … …], Upon receiving release signal: [r … 1]
7
Oil level judgment A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B Normal: [… … …], Low level: [… … L]
8
Compressor 1 operating current A
[U. ], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B [
. ], . is value of operating current in decimal format.
9
Compressor 2 operating current A
[U.
], : SW03 setting No. + 1 (Outdoor unit No. U2 to U 3)
B [
. ], . is value of operating current in decimal format.
SW03 7-segment display section A
1 U2
2 U3
* This method is used when displaying follower unit information on the 7-segment display of the header unit.
Note: Follower unit is selected by setting SW03.
(4) Display of Outdoor Cycle Data (Display at Header Unit)
46
Monitor Function
* The latest check code written in the EEPROM of each outdoor unit is displayed. (This function is used to check the check code after the resetting of the power supply.) To display the check code, push SW04 and hold for at least 5 seconds after setting SW01 to 03 as shown in the table below.
• 7-Segment Display
Set SW01/SW02/SW03 to [1/1/16] and push SW04 and hold for at least 5 seconds. The latest che
ck code of the header unit (U1) will be displayed. If the setting of SW02 is changed, the latest check code of a follow unit (U2-U3) will be displayed.
Anoitcesyalpsidtnemges-7sserddaroodnI30WS20WS10WS
1 E. 1
*** *** ***
.
Latest
check code
of header unit (U1)
Latest
check code
of follower unit No. 1 (U2)
Latest
check code
of follower unit No. 2 (U3)
1
2
16
E. 2.
3 E. 3.
Section A
Section B
D600 D601 D602 D603 D604
(5) Display of Indoor Unit information (Display on Header Unit only)
(6) Display of Outdoor EEPROM Writing Check Code (Display at each Outdoor Unit)
B
4
Indoor BUS communication signal receiving status
Upon receiving signal: [... ... 1], Other times: [... ... ...]
B5 Indoor check code No check code: [– – –]
B
6
Indoor HP capacity 0. 2, 0. 5, 0. 8, ... 1, 1. 2, 1. 7, ... 2, 2. 5,
...3, 3. 2, ...4, ...5, ...6, ...8, 1 0, 1 6, 2 0
8 Indoor PMV opening data Displayed in decimal format
9
1~4
1~16
Indoor TA / TRA opening data Displayed in decimal format
11~1 Indoor TSA opening data
Displayed in decimal format
10 Displayed in decimal format
1~ Indoor TF / TFA opening data
11~1
Indoor TOA opening data
Displayed in decimal format
B11 Indoor TCJ opening data Displayed in decimal format
B12 Displayed in decimal format
B13
1~ Indoor TC1 opening data
Indoor TC2 opening data
Displayed in decimal format
B
7
Indoor request command (S code, operation mode)
[ #. ... ]
# represents mode:
COOL: [C. ...
], HEAT: [H. ... ]
FAN: [F. ... ], OFF: [S. ... ]
represents S code: [#. ... 0] to [#. ... F]
SW01 SW02 SW03 Display detail
Note: Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
B
B
B
B
B
SW02
1~16
SW03
1
11
2
12
3
13
Indoor address
SW02 setting number
SW02 setting number +16
SW02 setting number +32
7-segment display section A
[01]~[16]
[17]~[32]
[33]~[48]
4
14
SW02 setting number +48
[49]~[64]
47
Service Support Function
Check Function for Connecting of Refrigerant and Control Lines
This function is provided to check misconnection of the refrigerant pipes and the control transmission line (Wiring over lines) between indoor unit and outdoor unit by using the switch on the interface P.C. board of the header unit. However, be sure to check the following items prior to executing this check function.
1 This check function does not work when a group operation by remote controller is performed and it is
used over outdoor units.
2 When using this check system, be sure to check for each 1 line in the unit of outdoor unit. If checking
the multiple lines at the same time, misjudgment may be caused.
(Check procedure)
Power ON
-10
18
32
10 43
(7-segment display)
[A]
[ .]
System horsepower
[B]
[ HP]
(7-segment display)
[A]
[ .]
[B]
[ P]
(7-segment display)
[A]
[ .]
[B]
[C ]
(7-segment display)
[A]
[ .]
[B]
[H ]
(7-segment display)
[A] [ J .C ] [ J .H ]
Cooling Heating
[B] [ ] [ ]
A
Be sure to turn on the power at indoor side before power-ON of outdoor unit.
System capacity check Set the
rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/2/3]. Then the system capacity is displayed on 7-segment display [A]. Check that this display surely matches with the expected system capacity.
Check No. of outdoor units Set the rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/3/3]. Then No. of outdoor units connected to the system
is displayed on 7-segment display [A]. Check that this display surely matches with the expected No. of outdoor units.
Check No. of indoor units/No. of units with cooling thermostat ON Set the rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/4/3]. Then No. of indoor units connected to the system is displayed on 7-segment display [A]. Check that this display surely m
atches with the
expected No. of indoor units.
Check No. of indoor units/No. of units with heating thermostat ON Set the rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/5/3]. Then No. of indoor units connected to the system is displayed on 7-segment display [A]. Check that this display surely matches with the expected No. of indoor units.
Check incorrect wiring Accor
ding to the indoor temperature, select one of the following items for setup of the rotary switches on the interface P.C. board of the header unit. Cooling: SW01/SW02/SW03 to [2/1/1] Heating: SW01/SW02/SW03 to [2/2/1]
No. of
connected
outdoor units
No. of
connected
outdoor
units
No. of units
with cooling
thermostat ON
No. of
connected
outdoor
units
No. of units
with heating
thermostat ON
SW02 to
[2]
(Heating)
SW02 to
[1]
(Cooling)
48
Service Support Function
Note 1: Criteria for the difference between suction and discharge temperatures
(1) Cooling operation
After operating for a minimum of 30 minutes in “COOL” mode, if the T dry bulb temperature difference between suction and discharge air of the indoor unit is 8°C deg or more, it is normal.
(2) Heating operation
After operating for a minimum of 30 minutes in “HEAT” mode, if the T dry bulb temperature difference between suction and discharge air of the indoor unit is 15°C deg or more, it is normal.
* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature set
by the remote controller and the temperature of the room is small, then the T temperature difference is small.
* Consider that T temperature difference may diminish in cases of a system in which the co
nnected indoor unit capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among outdoor units.
Note 2: Criteria for operating power current
The table below shows the maximum current for each outdoor unit. Under standard conditions, operating current is about 80% of the value shown in the table below.
Note 3: Criteria for cycle status
(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner of 100% connection
with standard piping length. Data may vary depending on temperature conditions, installed pipe length, and room shape combinations, or indoor unit connection capacity. For pressure criteria in different temperature conditions, refer to (2).
* This compressor is driven with a 4-pole motor. The value of the compressor frequency (rps) measured with a clamp meter at the compressor lead line is two times the rotation count (rps) of the compressor. * Each compressor may have a different frequency as a measure against resonance. * The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and TC2 sensor temperature when heat
ing, respectively
(2) Criteria for operating pressure
* Criteria after 15 minutes or more has passed since operating started
Indoor temperature (°C)
Outdoor temperature (°C)
Operating mode Cooling Heating
15~25
5~10
2.5~3.3
0.5~0.7
18~32
25~35
2.0~3.7
0.5~0.9
Pressure
High pressure (MPa)
Low pressure (MPa)
Pd
Ps
Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating Cooling Heating
2.9
2.6
3.1
2.6
3.2
2.6
3.1
2.6
3.2
2.6
3.2
2.8
3.1
2.6
3.1
2.6
3.1
2.8
3.2
2.7
3.1
2.8
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.7
0.9
0.6
0.9
0.6
0.9
0.7
80 75 85 80 90 85 85 80 90 80 90 85 75 65 80 70 85 75 95 75 80 70
16
5
16
4
16
3
16
5
16
4
16
3
16
4
16
4
15
3
14
3
15
4
10 35 11 35 11 35 10 35 10 35 10 30 11 30 11 30 11 30 11 30 11 30
40
3
40
2
40
2
40
3
40
3
40
2
40
3
40
3
40
2
40
2
40
3
30 30 30 30 30 25 30 30 35 30 35 25 35 30 35 25 35 25 35 20 35 25
50 50 60 65 70 75 50 55 60 65 70 70 60 65 70 75 80 85
100
85 70 75
50 50 60 65 70 75 50 55 60 65 70 70 60 65 70 75 80 85
100
85 70 7
5
High High High High High High High High High High High High High High High High High High High High High High
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
27/19
20/-
35/-
7/6
35/-
7/6
35/-
7/6
35/-
7/6
35/-
7/
6
35/-
7/6
35/-
7/6
35/-
7/6
35/-
7/6
35/-
7/6
35/-
7/6
Outdoor
unit
MMY-
MAP
Operating
mode
Pressure
(MPa)
Indoor
fan
Indoor
Outdoor
Compressor
1
Compress
or
2
Pipe surface temperature
(°C)
Air temperature
condition
(DB/WB) (°C)
Number of compressor
rotations
(rps)
Discharge
(TD)
Suction
(TS)
Outdoor
heat
exchanger
(TE)
Liquid
temperature
(TL3)
Indoor heat
exchanger
(TC)
0806*
1006*
1206*
1406*
1606*
14A6*
16A6*
1806*
2006*
2206*
10A6*
2206* : Heat Recovery type Not use
Outdoor unit MMY-MAP 0806* 1006*
1206*
14B6*
1406*
1606* 18B6* 1806* 2006* 2206*
Current value (A)
20.5 21.5 26.1 29.4
31.0
35.8 39.9 40.6 44.9 49.3
49
Service Support Function
Operation
(7-segment display)
[A] [ C ] [ H ]
Cooling Heating
[B] [ CC ] [ HH ]
(7-segment display)
[A]
[ ]
C or H
[B]
[ # # P]
(7-segment display)
[A]
[ ]
C or H
[B]
[ # # ]
(7-segment display)
[A]
[U1]
[B]
[ ]
A
Operation start Press the push-switch SW04 on the interface P.C. board of the header unit for 2 seconds or more. The operation starts. Check that 7-segment display [B] shows [ CC] for cooling and [ HH] for heating.
Confirmation of check results (1) Check that No. of misconnected indoor u
nits is displayed on 7-segment display [B] after 15 minutes. (If there is no misconnection, [00P] is displayed.)
Confirmation of check results (2) Push the push-switch SW05 on the interface P.C. board of the header unit for 2 seconds or more. The indoor address in which error is being detected is displayed on 7-segment display [B]. If there are multiple indoor address in which check code is being detected, they are succe
ssively exchanged and displayed. (When SW05 is turned on again, the display returns to display of No. of units.
After check, return the rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/1/1].
No. of misconnected
indoor units
This check operation requires 15 minutes even if there is no misconnection or there is any misconnection.
Address display of misconnected
indoor unit
7-segment display [A] 7-segment display [B]
SW04 SW05
<Rotary switches>
SW02 SW03SW01
50
Service Support Function
Function to Start / Stop ( On / Off ) Indoor Unit from Outdoor Unit
The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the header unit.
NOTE 1) This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start,
stop, operation mode, etc. It does not resend the signals even if the indoor unit does not follow the sent signals.
NOTE 2) The above controls are not used during abnormal stop.
yalpsid tnemges-7esaeleR/puteSeniltuOnoitcnuF.oN
1
Straight
Straight
cooling test operation
Changes the mode of all the connected indoor units collectively to cooling test operation. Note)
Control operation same as usual test operation from remote control is performed.
[Setup] Set SW01/SW02/SW03 to [2/5/1], and push SW04 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[C. ]
[ 00] is dis
played on Section B for 5
seconds.
Section B
[ – C]
2
heating test operation
Changes the mode of all the connected indoor units collectively to heating test operation. Note)
Control operation same as usual test operation from remote control is performed.
[Setup] Set SW01/SW02/SW03 to [2/6/1], and push SW04 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[H. ]
Section B
[ – H]
3 Fan test
operation
Changes operation mode of all the connected indoor units collectively to test operation mode. Note) Control operation same as
usual test operation from remote control is performed.
[Setup] Set SW01/SW02/SW03 to [2/9/1], and push SW04 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[F. ]
Section B
[ – F]
4 Batch start Starts all the connected indoor
units collectively. Note)
The contents follow to the setup of remote controller.
[Setup] Set SW01/SW02/SW03 to [2/7/1], and push SW04 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1].
Section A
[C.H]
Section B
[ 11]
Section A: Displays the corresponding indoor address. Section B: Displays [ 11] for 5 seconds from operation-ON.
5 Individual
start
Starts the specified indoor unit. Notes)
• The contents follow to the setup of remote controller.
• The other indoor units keep the status as they are.
[Setup] Set SW01 to [16], set SW02 and SW03 to address No. (1 to 40) to be started, and push SW04 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Section B
[ ]
Section A: Displays the corresponding indoor address. Section B: Displays [ 00] for 5 seconds from operation-OFF.
Individual stop
Stops the specified indoor unit. Note)
The other indoor units keep the status as they are.
[Setup] Set SW01 to [16], set SW02 and SW03 to address No. (1 to 40) to be stopped, and push SW05 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Section B
[
]
Section A: Displays the corresponding indoor address. Section B: Displays [ FF] for 5 seconds from test operation-ON.
Individual test operation
Operates the specified indoor unit. Note)
The other indoor units keep the status as they are.
[Setup] Set SW01 to [16], set SW02 and SW03 to address No. to be operated, and push SW04 for 10 seconds or more. [Release] Return SW01/SW02/SW03 to [1/1/1].
Section A
[ ]
Secti
on B
[ ]
[ 00] is displayed on Section B for 5 seconds.
Batch stop Stops all the connected indoor
units collectively.
[Setup] Set SW01/SW02/SW03 to [2/7/1], and push SW05 for 2 seconds or more. [Release] Return SW01/SW02/SW03 to [1].
Section A
[C.H]
Section B
[ 00]
SW04 SW05
7-segment display [A] 7-segment display [B]
SW02 SW03SW01
<Rotary switches>
51
Service Support Function
(1) All cooling test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system for the cooling test operation mode, by using switches on the interface P.C. board of the header unit.
<Operation procedure>
NOTE)The test operation returns to the normal operation after 60 minutes.
Power ON
Start
Operation check
[A]
[C. ]
[B]
[ – C]
Stop/End
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
Set SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/5/1]. ([C. ] is displayed on 7-segment display [A].)
[Test run] is displayed on the remote controller of the indoor unit to be operated. Check that [ – C] is displayed on 7-segment display [B] on the interface P.C. board of the header unit.
Push S
W04 on the same board for 2 seconds or more.
Return SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/1/1], or push the push switch SW05 for 2 seconds or more.
SW04 SW05
<Rotary switches>
SW02 SW03SW01
7-segment display [A] 7-segment display [B]
52
Service Support Function
(2) All heating test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system for the heating test operation mode, by using switches on the interface P.C. board of the header unit.
<Operation procedure>
NOTE)The test operation returns to the normal operation after 60 minutes.
[A]
[H. ]
[B]
[
H]
Power ON
Start
Operation check
Stop/End
Push SW04 on the same board for 2 seconds or more.
[Test run] is displayed on the remote controller of the indoor unit to be operated. Check that [ – H] is displayed on 7-segment display [B] on the interface P.C. board of the header unit.
Set SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/6/1]. ([H ] is displayed on 7-segment display [A].)
Be sure to turn on power at the i
ndoor side
before power-ON of outdoor unit.
Return SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/1/1], or push the push switch SW05 for 2 seconds or more.
SW04 SW05
7-segment display [A] 7-segment display [B]
<Rotary switches>
SW02 SW03SW01
53
Service Support Function
(3) Single fan test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same system for the fan test operation mode by using switches on the interface P.C. board of the header unit.
<Operation procedure>
NOTE)The test operation ends after 60 minutes and the operation returns to normal status.
[A]
[F. ]
[B]
[
F]
Power ON
Operation
Operation check
Stop/End
Push the push switch SW4 for 2 seconds or more on the P.C. board.
[Test run] is displayed on the remote controller of the indoor unit to be operated. Check that 7-segment display [B] on the interface P.C. board of the header unit changed to [– C]
Match [SW01/SW02/SW03] on the interface P.C.board of the header unit to [2/5/1]. (7-segment display [A] changes to [F. ].)
Be sure to turn on power of t
he indoor unit
and then turn on power supplies at outdoor unit side.
Return [SW01/SW02/Sw03] on the interface P.C. board of the header unit to [1/1/1]. or push the push switch [SW05] for 2 seconds or more.
SW04 SW05
7-segment display [A] 7-segment display [B]
<Rotary switches>
SW02 SW03SW01
54
Service Support Function
(4) Batch start/stop (ON/OFF) function
This function is provided to start/stop collectively all the indoor units connected to the same system by using switches on the interface P.C. board of the header unit.
<Operation procedure>
Power ON
Start
Stop
End
Operation check
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
If check code is already displayed with SW01/SW02/SW03 being [1/1/1], return the status to normal one according to troubleshooting and then execute a test operation.
The unit which is not given with priority by heating priority control, cooling priority control, and selection of cooling or heating mode is not operated. In th
is case, " operation ready" or " operation
mode controlled" is displayed on the remote controller.
If the discharge temperature does not change though COOL or HEAT has been set up from the remote controller, misconnection is considered.
Push SW04 on the same board for 2 seconds or more.
The indoor unit to be started operates.
Push the push switch SW05 on the interface P .C. board of the header
unit for 2 seconds or more.
After test operation, return the rotary switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [1/1/1].
Set up the operation mode of the remote controller. (If it is not set up, the operation continues with the current mode.) (FAN/COOL/HEAT)
Set SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/7/1]. ([C.H ] is displayed on 7-segment disp
lay [A].)
SW04 SW05
7-segment display [A] 7-segment display [B]
<Rotary switches>
SW02 SW03SW01
55
Service Support Function
55
<Check Code Clearing Function>
(1) Clearing from the main remote controller
Check code clearing in outdoor unit
Check code of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the indoor units operated by the remote controller is connected. (Check code of the indoor unit is not cleared.) For clearing check codes, the service monitor function of the remote controller is used.
<Method>
1 Change the mode to service monitor mode by pushing
CL
+
TEST
buttons simultaneously for 4 seconds or
more.
2 Using
TEMP
buttons, set CODE No. to “ ”.
3 The display in Section A in the following figure is counted with interval of 5 seconds as
” . When the count arrives “ ”,the check code is cleared. * However, counting from “ ” is repeated on the display.
4 When
TEST
button is pushed, the status returns to the normal status.
Check code clearing in indoor
Check code in the indoor unit is cleared by button on the remote controller. (Only check code of the indoor unit connected with operating remote controller is cleared.)
SET
TIME
TIMER SET
TEST
FILTER RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
14
2
3
Section A
.
.
56
Service Support Function
<Check Code Clearing Function>
(2) Clearing check code by using switches on the interface board of the header unit
Using the switches on the interface P.C. board of the header unit, this function is to clear the currently detected check code for each refrigerant circuit system without resetting the power supply. Check codes in both outdoor and indoor units are once cleared, and check code detection is performed again.
(3) Clearing check code by resetting power
This function is provided to clear check code in a system by resetting the power of all the outdoor and the indoor units. As same as the clearing method by the interface P.C. board, check codes of both the outdoor and the indoor units are once cleared, and check code detection is performed again.
<Method>
(1) Be sure to reset power of both the outdoor and the indoor units. (2) Turn on the power of the indoor unit prior to the power of the outdoor unit. (If the power is turned on in reverse order, a check code [
] (No. of header unit check code ) is output.)
NOTE)After power reset, it requires usually 3 minutes to power-on due to the initial communication of the system.
In some cases, it requires max. 10 minutes.
7-segment display
[A] [B]
[ E r ] [ ]
7-segment display
[A] [B]
[ E r ] [ C L ]
Set the rotary switches on the interface P.C. board of the header unit as follows. Set SW01/SW02/SW03 to [2/16/1]
Push the push switch SW04 on the same board for 5 seconds or more.
[ C L] is displayed in 7-segment display [B] on the board (for 5 seconds), and the error is completely cleared.
Interface P.C. board
SW04 SW05
SW02 SW03SW01
7-segment display [A] 7-segment display [B]
<Rotary switches>
57
Service Support Function
<Check Code Clearing Function>
Remote Controller Distinction Function
This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for a refrigerant circuit system by using switches on the interface P.C. board of the header unit.
<Distinction procedure>
Power ON
End
Check the connected remote controller
Operation
7-segment display
[A] [B]
[
A 1
] [ ]
7-segment display
[A] [B]
[
A 1
] [
FF
]
Be sure to turn on the power of the indoor unit prior to the power of the outdoor unit.
Set the display select switches on the interface P.C. board of the header unit as follows: Set SW01/SW02/SW03 to [2/4/1]
Push the push switch SW04 on the same board for 2 seconds or more.
"Checking" display of the connected remote controller flashes.
Push the push switch SW05 on the interface P.C. board of the heade
r
unit for 2 seconds or more.
Other end conditions:
1. 10 minutes has passed
2. SW01, SW02, or SW03 changed to other position.
Interface P.C. board
SW04 SW05
SW02 SW03SW01
7-segment display [A] 7-segment display [B]
<Rotary switches>
58
Service Support Function
Pulse Motor Valve (PMV) Forced Open / Close Function in Indoor Unit
ulse Motor Valve (PMV) Forced Open/Close Function in Indoor Unit
This function is provided to open or close forcedly PMV for 2 minutes in all the indoor units by the switch operation on the interface P.C. board of the header unit. This function is also used to open PMV fully when turning off the power and executing an operation.
<Operation>
[Open fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and push SW04 for 2 seconds or more. (Display appears on 7-segment display for 2 minutes as follows.) [ ] [ ]
[Close fully]
Set the switches SW01/SW02/SW03 on the interface P.C. board of the header unit to [2/3/1], and push SW05 for 2 seconds or more. (Display appears on 7-segment display for one minute as follows.) [ ] [ ]
[Clear]
After 2 minutes (1 minutes for “Close fully”) after setting up, the opening automatically returns to the normal opening.
This function is provided to forcedly open or close fully P.M.V. (PMV1/PMV3, PMV4) used in the outdoor unit for 2 minutes.
[PMV1 Open fully]
On the interface board of the outdoor unit, set the DIP switch [SW12·bit1] to [OFF], [SW12·bit2] to [OFF], and short­circuit CN30.
[PMV1 Close fully]
On the interface board of the outdoor unit, set the DIP switch [SW12·bit1] to [OFF], [SW12·bit2] to [OFF], and short­circuit CN31.
< Heat Recovery type Not use >
< Heat Recovery type Not use >
On the interface P.C. board of the outdoor unit, set the DIP switch [SW12·bit1] to [ON], [SW12·bit2] to [OFF], and shortcircuit CN30.
[PMV3 Close fully]
On the interface P.C. board of the outdoor unit, set the DIP switch [SW12·bit1] to [ON], [SW12·bit2] to [OFF], and shortcircuit CN31.
[PMV4 Open fully]
On the interface board of the outdoor unit, set the DIP switch [SW12·bit1] to [OFF], [SW12·bit2] to [ON], and short­circuit CN30.
[PMV4 Close fully]
On the interface board of the outdoor unit, set the DIP switch [SW12·bit1] to [OFF], [SW12·bit2] to [ON], and short­circuit CN31.
[Clear]
For both open fully and close fully, after 2 minutes, the opening returns to the normal opening. Be sure to remove the cord used for short-circ
uit after confirmation, and set the DIP switch [SW12·bit1] to [OFF]
and [SW12·bit2] to [OFF].
<Check Code Clearing Function>
Pulse Motor Valve (PMV) Forced Open fully / Close fully Function in Outdoor Unit
59
Service Support Function
Solenoid Valve Forced Open / Close Function in Outdoor Unit
This function is provided to forcedly open each solenoid valve mounted in the outdoor unit by the switch operation on the interface P.C. board in the outdoor unit. Use this function to check there is no refrigerant clogging with ON/ OFF operation of the solenoid valve.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/3]. (2) When [H. r] is displayed
in 7-segment display [A], keep pushing the switch SW04 for 2 seconds or more. (3) From when [ 2 ] is displayed in 7-segment display [B], SV2 is turned on. (4) After then, ON and OFF of each solenoid valve are exchanged by changing the setup number of the switch
SW02. (ON/OFF output pattern of each solenoid valve is as shown below.)
NOTE 1) Display in 7-segment display [B] is exchanged just when the number of SW02 has been changed; on the
other hand, the solenoid valve output is exchanged when SW02 has been kept with the same number for 5 seconds or more.
NOTE 2) The mark [O] in the table indicates that the corresponding solenoid valve is forcedly turned on. NOTE 3) The mark [-] in the table indicates that ON/OFF of the solenoid valve is controlled based upon the specifi-
cations of the air conditioner.
NOTE 4) The mark [×] in the table indicates that the corresponding solenoid valve is forcedly turned off with this
operation.
NOTE 5) The case heater output is for both the compressor and accumulator heaters.
[Clear]
Return switches SW01/SW02/SW03 on the interface P.C. board to [1/1/1].
NOTE)As this function is not based on the specified general control, be sure to release this mode after checking.
SV2 SV52 SV41 SV42 SV3A SV3B SV3C SV3D
1 [ 2 ]
- - - - - - ­3 [ 52] - - - - - - ­4 [ 41] - - - - - - ­5 [ 42] - - - - - - ­7 [ 3A] - - - - - - ­8 [ 3b] - - - - - - ­9 [ 3C] - - - - - - -
10 [ 3d] - - - - - - ­11 [ 3-] - - - -
12 15
- - - - - - - -
16 [ALL]
SW02
7-segment
display [B]
Operation pattern of solenoid valve
Case heater output relay
SV2 SV 5 SV41 SV42 SV3A SV3B SV3 C SV3D SV3E SV6 SV52 SV11 SV12 SV14
1 2 3 4 6 7 8
9 10 11 12 13 14 15 16
[2]
[5] [41] [42]
[3A]
[3b]
[3C]
[3d]
[3-]
[6] [52] [11] [12] [14]
[ALL]
○ ○
○ ○
○ ○
○ ○
SW02
7-segment display [B]
Case heater output relay
Operation pattern of solenoid valve
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯
¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯
¯ ¯ ¯ ¯ ¯
¯
¯
¯
¯
¯
¯
¯
¯ ¯
¯ ¯
¯¯ ¯
¯
¯
¯
¯
¯
¯
¯
¯
¯
x
x
x
Cooling, Heat Pump type
Heat Recovery type
<Check Code Clearing Function>
60
Service Support Function
Fan Operation Check in Outdoor Unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)Do not use this function during operation of the compressor. It may damage the compressor.
[Operation]
(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4]. (2) When [F. d] is displayed in 7-segment display [A], keep pushing the switch SW04 for 2 seconds or more. (3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation) (4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed. (Mode output pattern of the fan is as follows.)
[Clear]
This function is cleared by one of the following operations. (1) When SW01 setting number was changed to other number. (2) Push-switch SW05 was push for 2 seconds or more.
SW02 SW03 7-segm ent displ ay [B] Fan mo de
1
4
[ 63 ] 63
2 [ 62 ] 62
3 [ 61 ] 61
4 [ 60 ] 60
5 [ 59 ] 59
6 [ 58 ] 58
7 [ 57 ] 57
8 [ 56 ] 56
9 [ 55 ] 55
10 [ 54 ] 54
11 [ 53 ] 53
12 [ 52 ] 52
13 [ 51 ] 51
14 [ 50 ] 50
15 [ 49 ] 49
16 [ 48 ] 48
1
5
[ 47 ] 47
2 [ 46 ] 46
3 [ 45 ] 45
4 [ 44 ] 44
5 [ 43 ] 43
6 [ 42 ] 42
7 [ 41 ] 41
8 [ 40 ] 40
9 [ 39 ] 39
10 [ 38 ] 38
11 [ 37 ] 37
12 [ 36 ] 36
13 [ 35 ] 35
14 [ 34 ] 34
15 [ 33 ] 33
16 [ 3
2 ] 32
SW02 SW03 7-segm ent displ ay [B] Fan mo de
1
6
[ 31 ] 31
2 [ 30 ] 30
3 [ 29 ] 29
4 [ 28 ] 28
5 [ 27 ] 27
6 [ 26 ] 26
7 [ 25 ] 25
8 [ 24 ] 24
9 [ 23 ] 23
10 [ 22 ] 22
11 [ 21 ] 21
12 [ 20 ] 20
13 [ 19 ] 19
14 [ 18 ] 18
15 [ 17 ] 17
16 [ 16 ] 16
1
7
[ 15 ] 15
2 [ 14 ] 14
3 [ 13 ] 13
4 [ 12 ] 12
5 [ 11 ] 11
6 [ 10 ] 10
7 [ 9 ] 9
8 [ 8 ] 8
9 [ 7 ] 7
10 [ 6 ] 6
11 [ 5 ] 5
12 [ 4 ] 4
13 [ 3 ] 3
14 [ 2 ] 2
15 [ 1 ] 1
16 [
0 ] 0
<Check Code Clearing Function>
61
Service Support Function
Abnormal Outdoor Unit Discrimination Method by Fan Operation Function
This function is provided to forcedly operate the fan of the outdoor unit in which a check code occurred or the fan of the normal outdoor unit by the switch operation on the interface P.C. board in the header unit. To specify which one of the follower units connected to the system had problem, use this function for the system stop due to a follower unit failure (Check code [ ]).
[Operation] <In case to operate the fan in the failed outdoor unit only>
(1) Check that the switches SW01/SW02/SW03 on the interface P.C. board in the header unit are set to [1/1/1].
(2) Press the push-switch SW04 for 2 seconds or more. (3) [E 1] is displayed on 7-segment display [A]. (4) The fan of the outdoor unit in which check code occurred starts operation within approx. 10 seconds after [ ] was displayed.
<In case to operate the fans in all the normal outdoor units>
(1) Check that the switches SW01/SW02/SW03 on the interface P.C. board in the header unit are set to [1/1/1]. (2) Push the push switches SW04 and SW05 at the same time for 2 seconds or more. (3) [ ] is displayed on 7-segment display [A]. (4) The fans of all the normal outdoor units start operation with the Max. fan speed within approx. 10 seconds after
[
] was displayed.
[Release]
Push the push switch SW05 on the interface P.C. board in the header unit for 2 seconds or more. The outdoor fan which was operated stops.
.
* Check that [ ]is displayed on 7-segment display [A], and then finish the work.
[A] [B]
7-segment display
Outdoor unit No.
Check code display
<Check Code Clearing Function>
62
Service Support Function
Manual Adjustment
)OT( erutarepmeT edistuO fo noitcnuF tnemtsujdA launaM .01-7-7
Sensor
This function is provided to fix TO sensor value manually by the switch operation on the interface P.C. board in the
outdoor unit. When the unit stops abnormally due to TO sensor failure, etc, an emergent operation is available by setting up the value manually to position near the current outside temperature.
[Operation]
(1) Set the rotary switches on the interface P.C. board to numbers as follows:
• SW01/SW02/SW03 to [2/1/15]
• 7-segment display: [ t o ]
(2) Keep pressing the push-switch SW04 on the interface P.C. board for 1 second or more. The mode changes to
the TO sensor value fix manual mode.
(3) As shown in the following table, TO sensor value can be fixed by setting the rotary switch SW02 on the interface
P.C. board.
[Clear]
Return SW01/SW02/SW03 on the interface P.C. board in the outdoor unit to [1/1/1].
NOTE) If operated with TO sensor fixed by t
his function, the system control operation of the air conditioner may not be based on the specification of the product. Therefore an emergent operation should be restricted to a day or so.
SW02 7-segment display [B] T O sensor value
1 [ 10 ] 10°C
2 [ 15 ] 15°C
3 [ 20 ] 20°C
4 [ 25 ] 25°C
5 [ 30 ] 30°C
6 [ 35 ] 35°C
7 [ 40 ] 40°C
8 [ 43 ] 43°C
9 [ 45 ] 45°C
10 [ –15 ] -15°C
11 [ –10 ] -10°C
12 [ – 5 ] -5°C
13 [ 0 ] 0°C
14 [ 2 ] 2°C
15 [ 5 ] 5°C
16 [ 7 ] 7°C
When the outside temperature is 45ºC or more, set to 45ºC (SW02="9")
<Check Code Clearing Function>
63
Service Support Function
<Service support function list>
stnetnoc noitcnuF]A[ yalpsid tnemges-730WS20WS10WS
)noitarepo gnilooC( noitcnuf kcehc enil noitacinummoc lortnoc dna tiucric tnaregirfeR]C . J[1
)noitarepo gnitaeH( noitcnuf kcehc enil noitacinummoc lortnoc dna tiucric tnaregirfeR]H . J[2
noitcnuf nepo lluf decrof VMP roodnI] . P[3
noitcnuf gnitanimircsid rellortnoc etomer roodnI]1 . A[4
5 1 noitcnuf noitarepo tset gnilooC] . C[2
3 noitcnuf esolc/nepo decrof evlav dioneloS]r . H[2
1~16 4~7 noitcnuf noitarepo decrof naF]d . F[2
15 noitcnuf tnemtsujda launam rosnes erutarepmet edistuO]o . t[2
noitcnuf noitarepo tset gnitaeH] . H[6
noitcnuf )FFO/NO( pots/trats evitcelloc roodnI]H . C[7
)noitcnuf nwod pmuP( noitcnuf noitarepo yrevocer tnaregirfer roodtuO]d . r[11
Check code clear function
]r . E[61
SW01 SW02 SW03
7-segment display [A/B]
Function contents
1 1 Follower unit check code / Corresponding unit fan operation function] 82E [ ]1 U[1
1 [0 1]~[1 6] Indoor No. 1 to 16 unit
1~16
2
16
[1 7]~[3 2] Indoor No. 17 to 32 unit
3 [3 3]~[4 8] Indoor No. 33 to 48 unit
4 [4 9]~[6 4] Indoor No. 49 to 64 unit
Indoor individual start/stop (ON/OFF) function
<Check Code Clearing Function>
64
Refrigerant Leakage Detection
The refrigerant leakage and be confirmed by using the switches on interface PCB of the outdoor unit. If there is a leak, the location must be found in order to recover the refrigerant. After that, implement appropriate countermeasure and refill the refrigerant to its standard volume.
Refrigerant leaks can be detected by comparing the Actual opening of PMV with the calculated opening of PMV* during the Operation. * Calculated opening of PMV : calculated from the initial value (C.i / H.i ), the pressure sensor value, the compressor’s rotation speed, and the opening of PMV. The initial values are automatically saved when the specified conditions are met. (A leak can be detected only when C.i / H.i = 1)
[Operation] (1) Confirming the refrigerant leakage
(2) Clearing the initial valve
(3) Checking the record of the initial value
[ Clear ]
Note (a) During the operation, the slow leaks can be detected.
(b) Poor refrigerant circulation may be detected as a refrigerant leaks.
(d) The initial value can not be saved until the accumulated operating time has reached at least 20 hours. (e) The initial value can not be saved if the indoor unit’s operating ratio is low.
(f) If the following indoor units are connected, leakage determination is not possible.
(c) Due to the outside temperature, the initial value may not be recorded, or it may be impossible to determine the leakage.
SW01 SW02 SW03 Display detail
2 13 14 Refrigerant leakage detection
AB[ L. d ]
SW01 SW02 SW03 Display detail
2 14 14 Colling initial value
A [ C. i ]
Incomplete : [... ... 0]
Completed : [... ... 1]
B
2 15 14 Heating initial value
A [ H. i ]
Incomplete : [... ... 0]
Completed : [... ... 1]
Clear the data : [... C.L] (Only display for 5 seconds)
Set SW01 to 03 as show in the following table to confrim whether the leaks are being detected. (It also can be confirmed by remote control monitor function. Refer to monitor function of remote controller switch)
If the system is changed (e.g. indoor units are increased / replaced, outdoor units are moved, of refrigerant is refilled / increased) it is necessary to clear the initial value that had been saved. Make sure that the compressor has stopped, and then press and hold SW04 for at least 5 seconds.
Set SW01 to 03 as shown in the following table to confirm the record of the initial value.
Return SW01 / SW02 / SW03 on the interface PCB in the Outdoor Unit to [1 / 1 / 1].
However, if the air-conditioner can not cooling down / can not warming up / make an unusual stop, the slow leaks might not be detectable. The fast leaks always can not be detected.
(e.g. plugged strainers / capillaries, malfunction / clogging of the PMV / 2-way valve / 4-way valve)
Air to air heat exchanger with DX coil unit.
65
Outdoor Interface P.C board
Swithch / Function Setting Exchange
SW06 DIP SW 4 bit
bit 1 Compressor 1 backup OFF: Normal, ON: Backup when compressor 1
was in trouble
Part typ e
Exchang e conten ts
Initial setting
at shipment
OFF
SW07 DIP SW 4 bit
bit 1 Demand control 1
(Standard specifications) Exchange of upper limit regulation
OFF: 0 to 100% ON
: Middle to 100%
OFF
SW09 DIP SW 4 bit
In case of header outdoor unit
bit 2 Demand control 2 (Expansion function)
Exchange of 2 steps to 4 steps of upper limit
OFF: 2 steps (Standard) ON
: 4 steps
OFF
bit 2 Compressor 2 backup OFF: Normal, ON: Backup when compressor 2
was in trouble
OFF
In case of terminal outdoor unit
bit 2 Indoor connection capacity over
Judgment of error
OFF: Check code judgment ON
: None (when backup setting for outdoor unit)
OFF
bit 4 Judgment of error for No. of connected
indoor units
OFF: No check code judgment ON
: Check code judgment
OFF
SW10 DIP SW 4 bit
bit 2 Outdoor fan high static pressure
operation
OFF: Normal ON
: High static pressure operation
OFF
SW12 DIP SW 4 bit
bit 1 Selection of PMV open/close or
manual operation
(According to the following setting contents) OFF
bit 1 bit 2
OFF OFF
OFF ON
PMV1 opens/closes by operation of CN30/CN31 (*1)
PMV3 opens/closes by operation of CN30/CN31 (*1)
PMV4 opens/closes by operation of CN30/CN31 (*1)
bit 2 OFF
SW11 DIP SW 4 bit
bit 4 Operation switching when indoor water
overflow error detected
OFF: Entire system stops ON
: System operation continues
(Room which trouble occurred only stops.)
OFF
SW16 DIP SW 4 bit
bit 1 Option function
Output exchange of external output P.C. boa
(According to the following setting contents) OFF
SW14 DIP SW 4 bit
bit 1 Line address setup OFF
bit 1 bit 2 OFF OFF Compressor operation output
ON OFF
bit 2 OFF
bit 2 OFF
bit 3 OFF bit 4 OFF
SW13 DIP SW 4 bit bit 4 Line address setup
(Used by combining with SW14)
OFF
Display of system operation ratio
CN30 Check connector
Manual full opening operation for PMV opening operation
When released: Normal, When short-circuited: Open fully (2 minutes)
Released
SW30 DIP SW 2 bit
bit 1 Communication termination resistance
between outdoor units
OFF: No termination resistance ON
: With termination resistance
ON
CN31 Check connector
Manual full closing operation for PMV opening operation
When released: Normal, When short-circuited: Closed fully (2 minutes)
Released
bit 2 Communication termination resistance
between indoor and outdoor units
OFF: No termination resistance ON
: With termination resistance
ON
bit 3 For low noise operation OFF: Normal
ON
: INV frequency upper limit restriction
OFF
bit 4 OFF: Normal
ON
: Fan rpm upper limit restriction
OFF
bit 4 Exchange of Outdoor unit No. / Start
order No.
OFF: Outdoor unit No. [U. #] (#: 1 to 3) ON
: Outdoor start order No. [y. #] (#: 1 to 3)
OFF
All bit1 and 2 are ON: Setup of outdoor unit backup
OFF
*1 PMV full open/full close operation by short-circuited CN30/CN31 is for PMV which was selected by setting of SW12.
O
Heat Recovery Not use
N OFF
Outdoor Interface P.C. board Function Setting
66
Outdoor Interface P.C board
O : With jumper, X : Without jumper (Cut)
Setup Function switching setup
Jumper
Part typ e Exchang e conten ts
Initial sett ing
at shipment
J01
O
O
Optional function Operation mode selection operation switching
Indoor unit at not selected side is kept with waiting status.
J16
O
O
Demand control 1 (Standard specification) Corresponds to 2-core wire
Normal (3-core wire <Successive MAKE signal> or 4-core wire <Successive M
AKE or Pulse signal>)
×
2-core wire <Successive MAKE signal>
O
Approx. 75% (Normal)
×
The mode is changed a mode which selected the operation mode of the indoor unit at not selected side.
×
Approx. 60%
J04
O
Upper limit setup of demand capacity command in corresponding indoor during saving operation in indoor
*4 When you replace the board with a service board, be sure to cut the jumper wire matching with the outdoor unit model to be installed. (The jumper wires J09 to J12 which were mounted at shipment from the factory are provided to all the boards regardless of model type.)
Switching of Jumper Wire/Function
Cooling, Heat pump type
67
Leaking/Clogging
Li t of Check Codess Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle or Oil Circuit Part (MMY-MAP0806 , 1006 , 1206 )
Note: “XX” represents sub-code
Clogging
Leakage
Part
Locati on of
probl em
(see next p age)
Unit gen erating
check c ode
Detected failure and check code Symp tom
Outdoor PMV1
A
Corresponding unit Activation of high-pressure protection
Activation of low-pressure protection Discharge temp. trouble (TD1) Discharge temp. trouble (TD2
P20 H06 P03 P17
Rise of pressure Fall of pressure Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe convergent section
B
Corresponding unit High-pressure protection trouble
High-pressure SW system trouble
P20 P04-XX
Abnormal rise of pressure
Check valve in discharge pipe C Corresponding unit High-pressure SW system trouble P04-XX Abnormal rise of pressure
Check valve in oil-equalization circuit Capillary Strainer
D
Corresponding unit Oil level detection circuit trouble
Oil level low de
tection and protection
H16-XX H07
Oil circuit trouble or oil level low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCFevlavB3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOGevlavC3VS
SV
3D valve SV3D valve circuit capillary Strainer
H
Corresponding unit Oil level low detection and protection H07 Oil
level low
Reducer
I
Corresponding unit Oil level detection circuit trouble
Oil level low detection and protection
H16-05 H07
Oil circuit trouble Oil level low Oil level low
wol
levelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCJrotubirtsidnruterliO
Oil circuit trouble40-61HOil level detection circuit troubletinugnidnopserroCKyrallipacssapybC3VS
Part
Unit gen erating
check c ode
Detected failure and check code Symp tom
Outdoor PMV1
A
Corresponding unit Outdoor liquid backflow trouble
Oil level low detection and protection
P13 H07
Refrigerant entrapment
Other connected unit Discharge temp. trouble (TD1)
Discharge temp. trouble (TD2)
P03 P17
Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe
Bnoitcestnegrevnoc
Corresponding unit Oil level low detection and prote
ction Compressor breakdown Compressor error (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corresponding unit Oil level low detection and protection
Compressor breakdown Compressor trouble (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in oil-equalization circuit
D
Corresponding unit Oil level low detection and protection H07 Excessive amount of oil
(Leaking side) Insuffi
cient amount of oil
(Normal side)
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCGevlavC3VS
Locati on of
probl em
(see next p age)
68
Leaking/Clogging
<Cooling, Heat pump type>
(TD2)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TO)
(SV3D)
SV
SV
SV
SV
M
(TL1)
SV
SV
SV
(TK5)
(TS3)
(TL3)
Reducer
(SV3A)
(SV2)
(SV42) (SV41)
(SV3C)
(PMV4)
(TS1)
(SV3B)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
(PMV1)
4-way valve
High-pressure sensor
Low-pressure sensor
Oil separator
Fusible
plug
Liquid Tank
Accumulator
High­pressure switch
High­pressure switch
Check valve
Check valve
Compressor
1
(Inverter)
Oil Header
Liquid side
Service valve
Gas side
Service valve
Balance pipe
Service valve
Sub cool heat exchanger
SV
(SV52)
Reducer
FP
Compressor
2
(Inverter)
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
Reducer
A
H
G
K
I
J
E
F
D
C
B
Refrigerant Cycle Circuit
69
Leaking/Clogging
<MMY-MAP0806 , MAP1006 and MAP1206 >
Check items and procedures to follow when checking oil circuit with compressor(s) disconnected
erudecorPnoitacoLmetikcehC
Leakage of outdoor PMV Leakage of check valve in discharge pipe convergent section
A,C
1) With PMV1 fully closed, apply pressure to the check joint of liquid pipe with nitrogen, and check the pressure at the check joint of discharge pipe. If the pressure at the check joint of discharge pipe increases, there is a leak from PMV1 (A) and check valve of discharge pipe (C). Replace the faulty par ts.
2) If the pressure does not increase, fully open outdoo
r PMV 1 and check the pressure at the check joint of discharge pipe again. If the pressure increases, there is a leak from the check valve of discharge pipe (C). Replace the part.
Leakage of check valve in discharge pipe
E
3) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the discharge pipe section of the disconnected compressor, there is a leak from the check valve of discharge pipe (E). Replace the part.
Leakage of check valve in oil e
qualization circuit
F
4) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the oil equalization pipe section of the disconnected compressor, there is a leak from the oil equalization pipe check valve (F). Replace the part.
Leakage of SV3A valve G
5) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3B valve. If gas escapes from the suction pipe section of the disconnected compressor, ther
e is a leak from the SV3A valve.
Replace the part.
Leakage of SV3B valve H
6) Then manually open the SV3A valve. If gas escapes from the suction pipe section of the disconnected compressor, there is a leak from the SV3B valve. Replace the part.
Clogging of SV3D valve Clogging of oil-return capillary Clogging of oil-return distributor
J
7) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3D valve. If gas does not escape from the suction
pipe section of the disconnected compressor, the SV3D valve, oil-return
capillary or oil-return distributor is clogged. Replace the part.
A
J
G
I
G
H
F
E
C
(TD2)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TO)
(SV3D)
SV
SV
SV
SV
M
(TL1)
SV
SV
SV
(TK5)
(TS3)
(TL3)
Reducer
(SV3A)
(SV2)
(SV42) (SV41)
(SV3C)
(PMV4)
(TS1)
(SV3B)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
(PMV1)
4-way valve
High-pressure sensor
Low-pressure sensor
Oil separator
Fusible
plug
Liquid Tank
Accumulator
High­pressure switch
High­pressure switch
Check
valve
Check
valve
Compressor
1
(Inverter)
Oil Header
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Sub cool heat exchanger
SV
(SV52)
Reducer
FP
Compressor
2
(Inverter)
Reducer
<Cooling, Heat pump type>
70
Leaking/Clogging
<Cooling, Heat pump type>
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle or Oil Circuit Part (MMY-MAP1406 , 1606 )
Note: “XX” represents sub-code
Clogging
Leakage
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode
Symptom
Outdoor PMV1, 3
A
Corresponding unit
Activation of high-pressure protection Activation of low-pressure protection Discharge temp.
trouble
(TD1)
Discharge temp.
trouble
(TD2)
P20 H06 P03 P17
Rise of pressure Fall of pressure Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe convergent section
B
Corresponding unit High-pressure protection
trouble
High-pressure SW system
trouble
P20 P04-XX
Abnormal rise of pressure
Check valve in discharge pipe C Corresponding unit High-pressure SW system
trouble
P04-XX Abnormal rise of pressure
Check valve in oil-equalization circuit Capillary Strainer
D
Corresponding unit Oil level detection circuit
trouble
Oil level low detection and protection
H16-
XX
H07
Oil circuit
trouble
or oil level
low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCFevlavB3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOGevlavC3VS
SV
3D valve SV3D valve circuit capillary Strainer
H
Corresponding unit Oil level low detection and protection H07 Oil level low
Reducer
I
Correspo
nding unit Oil level detection circuit
trouble
Oil level low detection and protection
H16-05 H07
Oil circuit
trouble
Oil level low Oil level low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCKrotubirtsidnruterliO
Oil circuit
trouble
40-61HOil level detection circuit
trouble
tinugnidnopserroCLyrallipacssapybC3VS
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode
Symptom
Outdoor PMV1
A
Corresponding unit Outdoor liquid backflow
trouble
Oil level low detection and protection
P13 H07
Refrigerant entrapment
Other connected unit Discharge temp.
trouble
(TD1)
Discharge temp.
trouble
(TD2)
P03 P17
Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe
Bnoitcestnegrevnoc
Corresponding unit Oil level low detection and protection
Compressor breakd
own
Compressor error (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corresponding unit Oil level low detection and protection
Compressor breakdown Compressor
trouble (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in oil-equalization circuit
D
Corresponding unit Oil level low detection and protection H07 Excessive amount of oil
(Leaking side) Insufficient amount of oil (No
rmal side)
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCGevlavC3VS
Locati on of
probl em
(see next page)
Locati on of
probl em
(see next page)
71
Leaking/Clogging
Outdoor Unit (14, 16HP) Model : MMY-MAP1406
, CMMY-MAP1606
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tan k
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Oil Header
High­pressure switch
High-
pressure switch
Reducer
Fusible
plug
FP
Sub cool
heat
exchange
Compressor
1
(Inverter)
Compressor
2
(Inverter)
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
H
G
K
I
J
E
F
D
C
B
A
<Cooling, Heat pump type>
72
Leaking/Clogging
<Cooling, Heat pump type>
<MMY-MAP1406 and MAP1606 >
Check items and procedures to follow when checking oil circuit with compressor(s) disconnected
erudecorPnoitacoLmetikcehC
Leakage of outdoor PMV Leakage of check valve in discharge pipe convergent section
A,B
C
1)
With PMV1 and 3 fully closed, apply pressure to the check joint of liquid pipe with nitrogen, and check the pressure at the check joint of discharge pipe. If the pressure at the check joint of discharge pipe increases, there is a leak PMV1(A) or 3(B) and check valve of dischage pipe (C). Replace the faulty parts.
2) If the pressure does not increase, fully open
outdoor PMV1 and 3 and check the pressure at the check joint of discharge pipe again. If the pressure increases, there is a leak from the check valve of discharge pipe (C). Replace the part.
Leakage of check valve in discharge pipe
E
3)
With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the discharge pipe section of the disconnected compressor, there is a leak fromthe check valve of discharge pipe (E).Replace the part.
Leakage of check valve in oil equalization circuit
F
4) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the oil equalization pipe section of the disconnected compressor, there is a leak from the oil equalization pipe check valve (F). Replace the part.
Leakage of SV3A valve G
5) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3B valve. If gas escapes from the suction pipe section of the disconnected compr
essor, there is a leak from the SV3A valve.
Replace the part.
Leakage of SV3B valve H
6) Then manually open the SV3A valve. If gas escapes from the suction pipe section of the disconnected compressor, there is a leak from the SV3B valve. Replace the part.
Clogging of SV3D valve Clogging of oil-return capillary Clogging of oil-return distributor
J
7) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3D valve. If gas does not escape from
the suction pipe section of the disconnected compressor, the SV3D valve, oil-return
capillary or oil-return distributor is clogged. Replace the part.
A
J
I
G
H
F
E
C
B
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tank
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Oil Header
High­pressure switch
High-
pressure switch
Reducer
Fusible
plug
FP
Sub cool
heat
exchange
Compressor
1
(Inverter)
Compressor
2
(Inverter)
73
Leaking/Clogging
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle or Oil Circuit Part (MMY-MAP1406 , 1606 )
Note: “XX” represents sub-code
Clogging
Leakage
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode
Symptom
Outdoor PMV1, 3
A
Corresponding unit
Activation of high-pressure protection Activation of low-pressure protection Discharge temp.
trouble
(TD1)
Discharge temp.
trouble
(TD2)
P20 H06 P03 P17
Rise of pressure Fall of pressure Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe convergent section
B
Corresponding unit High-pressure protection
trouble
High-pressure SW system
trouble
P20 P04-XX
Abnormal rise of pressure
Check valve in discharge pipe C Corresponding unit High-pressure SW system
trouble
P04-XX Abnormal rise of pressure
Check valve in oil-equalization circuit Capillary Strainer
D
Corresponding unit Oil level detection circuit
trouble
Oil level low detection and protection
H16-
XX
H07
Oil circuit
trouble
or oil level
low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCFevlavB3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOGevlavC3VS
SV
3D valve SV3D valve circuit capillary Strainer
H
Corresponding unit Oil level low detection and protection H07 Oil level low
Reducer
I
Correspo
nding unit Oil level detection circuit
trouble
Oil level low detection and protection
H16-05 H07
Oil circuit
trouble
Oil level low Oil level low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCKrotubirtsidnruterliO
Oil circuit
trouble
40-61HOil level detection circuit
trouble
tinugnidnopserroCLyrallipacssapybC3VS
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode
Symptom
Outdoor PMV1
A
Corresponding unit Outdoor liquid backflow
trouble
Oil level low detection and protection
P13 H07
Refrigerant entrapment
Other connected unit Discharge temp.
trouble
(TD1)
Discharge temp.
trouble
(TD2)
P03 P17
Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe
Bnoitcestnegrevnoc
Corresponding unit Oil level low detection and protection
Compressor breakd
own
Compressor error (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corresponding unit Oil level low detection and protection
Compressor breakdown Compressor
trouble (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in oil-equalization circuit
D
Corresponding unit Oil level low detection and protection H07 Excessive amount of oil
(Leaking side) Insufficient amount of oil (No
rmal side)
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCGevlavC3VS
Locati on of
probl em
(see next page)
Locati on of
probl em
(see next page)
<Cooling, Heat pump type>
74
Leaking/Clogging
<Cooling, Heat pump type>
Outdoor Unit (14, 16HP) Model : MMY-MAP1406
, CMMY-MAP1606
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tan k
Liquid side
Service valve
Gas side
Service valve
Balance pipe
Service valve
Oil Header
High­pressure switch
High-
pressure switch
Reducer
Fusible
plug
FP
Sub cool
heat
exchange
Compressor
1
(Inverter)
Compressor
2
(Inverter)
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
H
G
K
I
J
E
F
D
C
B
A
75
Leaking/Clogging
<MMY-MAP1406 and MAP1606 >
Check items and procedures to follow when checking oil circuit with compressor(s) disconnected
erudecorPnoitacoLmetikcehC
Leakage of outdoor PMV Leakage of check valve in discharge pipe convergent section
A,B C
1)
With PMV1 and 3 fully closed, apply pressure to the check joint of liquid pipe with nitrogen, and check the pressure at the check joint of discharge pipe. If the pressure at the check joint of discharge pipe increases, there is a leak PMV1(A) or 3(B) and check valve of dischage pipe (C). Replace the faulty parts.
2) If the pressure does not increase, fully open
outdoor PMV1 and 3 and check the pressure at the check joint of discharge pipe again. If the pressure increases, there is a leak from the check valve of discharge pipe (C). Replace the part.
Leakage of check valve in discharge pipe
E
3)
With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the discharge pipe section of the disconnected compressor, there is a leak fromthe check valve of discharge pipe (E).Replace the part.
Leakage of check valve in oil equalization circuit
F
4) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the oil equalization pipe section of the disconnected compressor, there is a leak from the oil equalization pipe check valve (F). Replace the part.
Leakage of SV3A valve G
5) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3B valve. If gas escapes from the suction pipe section of the disconnected compr
essor, there is a leak from the SV3A valve.
Replace the part.
Leakage of SV3B valve H
6) Then manually open the SV3A valve. If gas escapes from the suction pipe section of the disconnected compressor, there is a leak from the SV3B valve. Replace the part.
Clogging of SV3D valve Clogging of oil-return capillary Clogging of oil-return distributor
J
7) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3D valve. If gas does not escape from
the suction pipe section of the disconnected compressor, the SV3D valve, oil-return
capillary or oil-return distributor is clogged. Replace the part.
A
J
I
G
H
F
E
C
B
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tank
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Oil Header
High­pressure switch
High-
pressure switch
Reducer
Fusible
plug
FP
Sub cool
heat
exchange
Compressor
1
(Inverter)
Compressor
2
(Inverter)
<Cooling, Heat pump type>
76
Leaking/Clogging
List of Check Codes Generated upon Occurrence of Leakage/Clogging in Outdoor Cycle or Oil Circuit Part (MMY-MAP1806 , MAP2006
and MAP2206 )
Note: “XX” represents sub-code
Clogging
Leakage
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode Sympto m
Outdoor PMV1, 3
A
Corresponding unit Activation of high-pressure protection
Activation of low-pressure protection Discharge temp. trouble (TD1) Discharge temp. trouble (TD2)
P20 H06 P03 P17
Rise of pressure Fall of pressure Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe convergent section
B
Corres
ponding unit High-pressure protection trouble
High-pressure SW system trouble
P20 P04-XX
Abnormal rise of pressure
Check valve in discharge pipe C Corresponding unit High-pressure SW system trouble P04-XX Abnormal rise of pressure
Check valve in oil-equalization circuit Capillary Strainer
D
Corresponding unit Oil level detection circuit trouble
Oil level low detection and protection
H16-XX H07
Oil circuit trouble or oil level low
w
ollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOEevlavA3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCFevlavB3VS
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinudetcennocrehtOGevlavC3VS
SV
3D valve SV3D valve circuit capillary Strainer
H
Corresponding unit Oil level low detection and protection H07 Oil level low
Reducer
I
Corresponding unit Oil level detection circuit trouble
Oil level
low detection and prote
H16-05 H07
Oil circuit trouble Oil level low Oil level low
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCKrotubirtsidnruterliO
Oil circuit trouble 40-61HOil level detection circuit trouble tinugnidnopserroCLyrallipacssapybC3VS
Part
Unit gen erating
check c ode
Detected f ailure and ch eck c ode Sympto m
Outdoor PMV1
A
Corresponding unit Outdoor liquid backflow trouble
Oil level l
ow detection and prote
P13 H07
Refrigerant entrapment
Other connected unit Discharge temp. trouble (TD1)
Discharge temp. trouble (TD2)
P03 P17
Rise of discharge temp. (compressor 1) Rise of discharge temp. (compressor 2)
Check valve in discharge pipe
Bnoitcestnegrevnoc
Corresponding unit Oil level low detection and protection
Compressor breakdown Compressor error (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in discharge pipe
C
Corr
esponding unit Oil level low detection and protection
Compressor breakdown Compressor
trouble (lockup)
H07 H01-XX H02-XX
Refrigerant entrapment
Check valve in oil-equalization circuit
D
Corresponding unit Oil level low detection and protection H07 Excessive amount of oil
(Leaking side) Insufficient amount of oil (Normal side)
wollevelliO70HnoitcetorpdnanoitcetedwollevelliOtinugnidnopserroCEevlavA3VS
wollevelliO70Hnoitcetorpdnanoitcetedwollev
elliOtinugnidnopserroCGevlavC3VS
Locati on of
probl em
(see next page)
Location of
probl em
(see next page)
<Cooling, Heat pump type>
77
Leaking/Clogging
Outdoor Unit (18, 20, 22HP) Model : MMY-MAP1806 , MMY-MAP2006 , MMY-MAP2206
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan
Fan motor
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure
sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tank
Oil Header
High­pressure switch
High-
pressure
switch
Sub cool heat exchanger
Fusible plug
FP
Liquid side
Service valve
Gas side
Service valve
Balance pipe
Service valve
SV
Solenoid
valve
Capillary
tube
Check
valve
Check
joint
Strainer
Temperature
sensor
Symbol
Distributor
Reducer
Compressor
1
(Inverter)
Compressor
2
(Inverter)
A
H
G
K
I
J
E
F
D
C
B
<Cooling, Heat pump type>
78
Leaking/Clogging
<Cooling, Heat pump type>
<MMY-MAP1806 , MAP2006 and MAP2206 >
Check items and procedures to follow when checking oil circuit with compressor(s) disconnected
erudecorPnoitacoLmetikcehC
Leakage of outdoor PMV Leakage of check valve in discharge pipe convergent section
A,B
1) With PMV1 and 3 fully closed, apply pressure to the check joint of liquid pipe with nitrogen, and check the pressure at the check joint of discharge pipe. If the pressure at the check joint of discharge pipe increases, there is a leak from PMV1(A) or 3(B) and check valve of discharge pipe (C). Replace the faulty parts.
2) If the pressure does not increase, fully
open outdoor PMV1 and 3 and check the pressure at the check joint of discharge pipe again. If the pressure increases, there is a leak from the check valve of discharge pipe (C). Replace the part.
Leakage of check valve in discharge pipe
E
3) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the discharge pipe section of the disconnected compressor, there is a leak from the check valve of discharge pipe (E). Replace the part.
Leakage of ch
eck valve in oil
equalization circuit
F
4) With pressure applied to the check joint of discharge pipe with nitrogen, if gas escapes from the oil equalization pipe section of the disconnected compressor, there is a leak from the oil equalization pipe check valve (F). Replace the part.
Leakage of SV3A valve G
5) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3B valve. If gas escapes from the suction pipe section of the disconnected c
ompressor, there is a leak from the SV3A valve.
Replace the part.
Leakage of SV3B valve H
6) Then manually open the SV3A valve. If gas escapes from the suction pipe section of the disconnected compressor, there is a leak from the SV3B valve. Replace the part.
Clogging of SV3D valve Clogging of oil-return capillary Clogging of oil-return distributor
J
7) With pressure applied to the check joint of discharge pipe with nitrogen, manually open the SV3D valve. If gas does not escape
from the suction pipe section of the disconnected compressor, the SV3D valve, oil-return
capillary or oil-return distributor is clogged. Replace the par t.
J
I
G
H
E
C
F
A
B
(TD2)
(TS1)
(TE1)
(TK2)
(TK1)
(TD1)
(TK4)
(TE2)
(TO)
SV
SV
SV
SV
M
M
(TG2)
(TG1)
(TL3)
SV
SV
SV
(
TK5)
(TS3)
(TL1)
(TL2)
(SV3B)
(SV3A)
(SV2)
(SV3D
)
(SV42)
(SV41)
(SV3C)
(PMV4)
Fan
Fan
Fan motor
Fan motor
Right side
Main heat exchanger
Left side
Main heat exchanger
Right side Sub heat exchanger
Left side Sub heat exchanger
(PMV1)
(PMV3)
4-way valve
High-pressure
sensor
Low-pressure
sensor
Oil separator
Accumulator
Liquid Tank
Oil Header
High­pressure switch
High-
pressure
switch
Sub cool heat exchanger
Fusible plug
FP
Liquid side
Service valve
Gas side
Service valve
Balance pipe Service valve
Reducer
Compressor
1
(Inverter)
Compressor
2
(Inverter)
79
Backup Operation
This product offers backup modes of operation to tide over certain emergency situations. If a failure occurs in one of the compressors, it is possible to operate the system on an emergency basis by operating only the remaining compressor, (compressor backup operation). If one of the outdoor units fails in a combined outdoor unit system, the system can be operated on an emergency basis by keeping only the remaining outdoor unit(s), (outdoor unit backup operation). Perform backup operation setting in accordance with the procedure described below.
Note for Backup Operation
The method of backup operation differs according to the contents of fault as shown in the table below.
ukcabfodohteMtluaffostnetno erudecorp gnitteS noitarepo pC
Go to SVM-15067-4, 9-2
Go to SVM-15067-4, 9-3, 9-4
)2etoNees(pukcabrosserpmoC)1etoNees(sliaftinuemasehtnisrosserpmocehtfoenO
-gniloocropukcabtinuroodtuOliaftinuemasehtnisrosserpmocehtllA season outdoor unit backup (see Notes 1, 3, 4 and 5)
A fault occurs in a compressor motor coil (e.g. a layer short-circ uit)
A fault occurs in a refrigerating cycle
part, fan or related part, or electrical part
A fault occurs in a temperature sensor or pressure sensor
Failure
Failure
Prohibited
Example
Backed-up compressor
Backed-up compressor
Prohibited
Example
Backed-up outdoor unit
Backed-up outdoor unit
Prohibited
Example
Backed-up outdoor unit
Backed-up compressor
Prohibited
Example
Backed-up outdoor unit
MMY-MAP1806 (MMY-MAP2006)
MMY-MAP1606
Prohibited
Example
Backed-up outdoor unit
MMY-MAP1406
MMY-MAP1206
Note 1: If the compressor has failed due to a fault in its motor coil (e.g. a layer short-circuit), do not perform com-
pressor backup operation because of severe oil degradation. It could damage other outdoor units.
Note 2: Keep the number of backed-up outdoor units under compressor backup operation to one in the system
(single refrigerant line). As for MMY-MAP1806 , MMY-MAP2006 and MMY-MAP2206 , the ba
ckup opera-
tion of compressor cannot be done.
Note 3: Keep the number of backed-up outdoor units under outdoor unit backup operation to one in the system
(single refrigerant line).
Note 4: It is prohibited to combine compressor backup operation and outdoor unit backup operation.
Note 5: With a two-outdoor unit system, do not perform outdoor unit backup operation to back up the MMY-
MAP1406 (or MAP1606 ). It
could lead to compressor failure due to the abnormal operation.
Failure Failure
Failure
Failure
Failure
Failure
,
80
Backup Operation
Compressor Backup Operation Setting
<Outline>
If a fault occurs to one of the compressors installed in outdoor unit, follow the procedure described below to back up the faulty compressor by using the remaining, normal compressor.
<Work Procedure>
(1) Turn off the power supply to all the outdoor units connected to the system. (2) Set the DIP switches of SW06, provided on the interface P.C. board of the outdoor unit with the faulty
compressor, as shown in the table below.
SW06
Bit 1 Bit 2 Bit 3 Bit 4
When compressor No.1 (front left) is faulty ON OFF OFF OFF
When compressor No.2 (front right) is faulty OFF ON OFF OFF
Factory default setting OFF OFF OFF OFF
123 4 123 4 123 4 123 4
123 4 123 4 123 4 123 4
SW06 SW07 SW09 SW10
SW11 SW12
123 4 123 4
SW16 SW17
SW13 SW14
81
Backup Operation
(3) Change the connection of wiring between Comp-IPDU and Fan-IPDU, as shown in the below.
Outdoor Unit (8, 10, 12, 14, 16, 18HP)
Model: MMY-MAP0806 , MAP1006 , MAP1206 , MAP1406 , MAP1606 ,
1.When compressor No.1 (front left) is faultyNo change the connection of wiring
2.When compressor No.2 (front right) is faulty
Change the connection of wiring between Como-IPDU and Fan-IPDU as shown in the below.
CN21
CN23
CN21
CN23
CN21
CN23
CN21
CN23
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
Change to CN21 of Comp-IPDU1 from CN21 of Comp-IPDU2Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU2
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
Change to CN21 of Comp-IPDU1 from CN21 of Comp-IPDU2Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU2
Ex. MMY-MAP0806*, MAP1006*, MAP1206* , MAP14B6*
Ex. MMY- MAP1406 , MAP1606 , MAP18B6
82
Backup Operation
Outdoor Unit (18, 20, 22HP)
Model: MMY-MAP 1806 , MAP2006 , MAP2206
1.When compressor No.1 (front left) is faulty
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
2.When compressor No.2 (front right) is faulty
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
CN22
CN23
CN21
CN23
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU1
Change to CN22 of Comp-IPDU2 from CN21 of Comp-IPDU1Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU1
(Tighten two wirings together with screw terminal)
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
Change to CN22 of Comp-IPDU1 from CN21 of Comp-IPDU2Change to CN23 of Comp-IPDU1 from CN23 of Comp-IPDU2
(Tighten two wirings together with screw terminal)
CN22
CN23
CN21
CN23
(4) Turn on the power supply to all the units connected to the system.
This is the end of compressor backup operation setting.
83
Backup Operation
<Outline>
This product allows outdoor unit backup operation setting to be performed either at the header unit or a follower unit. If any of the fault modes specified below occurs to one of the outdoor units in a multi-outdoor unit system, proceed with outdoor unit backup operation.
• A compressor failure (e.g. a layer short-circuit or a compressor failure in which no compressor is available to back up the faulty compressor)
A failure of a pressure sensor (Pd or Ps) or a temperature sensor (
Note: Keep the number of backed-up outdoor units to one in the system (single refrigerant line).
<Work procedure>
(1) Turn off the power supply to all the indoor and outdoor units connected to the system. [Setup of failed follower outdoor unit] (2) Fully close the gas pipe service valve of the failed outdoor unit. (3) Leave the service valves of the liquid and balance pipe fully open (to prevent refrigerant stagnation in the unit).
However, if there is a leakage from an outdoor PMV (unable to close), fully close the liquid pipe service valve.
(4) <In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board>
From this point on, keep the power supply to the failed unit off. <In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle part, or fan system part)> Disconnect the connector [CN03] for outdoor-outdoor communication (BUS2) provided on the interface P.C
.
board.
[Setup of header unit] (5) Turn on Bit 2 of SW09 on the interface P.C. board of the header unit.
(Setting to prevent connected indoor units capacity over error. (E16))
Setup of failed follower outdoor unit
(4)
CN03
BUS2
In case of fault in refrigerating circuit or related part, disconnect BUS2 communication connector [CN03] on interface P.C. board.
123 4 123 4 123 4 123 4
123 4 123 4 123 4 123 4
SW06 SW07 SW09 SW10
SW11 SW12
123 4 123 4
SW16 SW17
SW13 SW14
Interface P.C. board of header unit
(5)
Turn on Bit 2 of SW09.
Outdoor Unit Backup Operation Setting
Follower outdoor unit backup operation setting (failure of follower outdoor unit)
(2)
Fully close gas pipe service valve.
(3)
Leave service valves of liquid and balance pipes fully open. (if there is leakage from outdoor PMV, fully close liquid pipe.)
84
Backup Operation
(6) Turn on the power supply to all the units connected to the system other than the failed follower unit.
Determine what to do with the power supply to the failed follower unit in the following manner. <In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board> Leave the power supply off. <In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle part, or fan system part)> Turn on the power supply to protect the compressor (by turning on the case heater). (When the power supply to the unit is turned on, [E19] (error in the number of outdoor header units) will be displayed on the 7-segment display. However, this will not cause any problems.)
(7) Perform settings needed to gain permission for backup operation from the header unit (error clearance).
1) Set SW01/02/03 on the interface P.C. board to 1/1/1 and confirm that [U1] [E26] (dropping out of an outdoor unit) is displayed on the 7-segment display.
2) Set SW01/02/03 on the interface P.C. board to 2/16/1. Upon co
nfirming that [Er] [… … …] is displayed on
the 7-segment display, press SW04 and hold for 5 seconds or more.
3) [Er] [… CL] (error clearance completed) will be displayed on the 7-segment display.
4) Set SW01/02/03 back to 1/1/1. (The display should change to [U1] [– – –].)
This is the end of follower outdoor unit backup operation setting. Check the operation.
Push switch
7-segment display
Rotary switches
Interface P.C. board of header unit
(7) Set SW01/02/03 to 1/1/1 [U1] [E26] will be displayed.
Set SW01/02/03 to [2/16/1]. [Er] [… … …] will be displayed.
Press SW04 and hold for 5 seconds or more [Er] [… CL] will be displayed.
Set SW01/02/03 back to 1/1/1. [U1] [– – –] will be displayed.
85
Backup Operation
Header outdoor unit backup operation setting
(failure of header outdoor unit)
<Work procedure>
(1) Turn off the power supply to all the units connected to the system at the source. [Setup of failed header outdoor unit] (2) Fully close the gas pipe service valve of the failed outdoor unit. (3) Leave the service valves of the liquid and balance pipes fully open (to prevent refrigerant stagnation in the failed
outdoor unit). However, if there is a leakage from an outdoor PMV (unable to close), fully close the liquid pipe service valve.
(4) <In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board>
From this point on, keep the power supply to the failed unit off. <In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle part, or fan system part)> Disconnect the connector [CN03] for outdoor-outdoor communication (BUS2) provided on the interface P.C. board.
[Selection
of new header unit]
(5) Select a new header unit from the follower units on the basis of the following criteria:
• If only one follower unit is connected, select it as the header unit.
If two follower units are connected, select the follower unit that is nearest to the failed header unit.
[Setup of new header unit] (6) Set SW13 and SW14 on the interface P.C. board same as the setting of failed header unit (refrigerant line
address setting).
(7) Turn on Bit 2 of SW09 on the interface P.C. board. (Setting to prevent connected indoor unit capacity over error.
(E16))
Setup of failed follower outdoor unit
(4)
CN03
BUS2
In case of fault in refrigerating circuit or related part, disconnect BUS2 communication connector [CN03] on interface P.C. board.
(2)
Fully close gas pipe service valve.
(3)
Leave service valves of liquid and balance pipes fully open. (if there is leakage from outdoor PMV, fully close liquid pipe.)
86
Backup Operation
(8) Set Bits 1 and 2 SW30 on the interface P.C. board same as that of the failed header unit (terminator
resistance setting)
[Wiring changes to communication line] (9) Redirect the indoor-outdoor communication line connected to the failed header unit [U1/U2] to the unit selected
as the header unit [U1/U2].
(10) If a cental control device is connected, connect the central control communication line [U3/U4] to the
communication line terminal of the unit selected as the new header unit [U3/U4], and connect up the tie connector between the [U1/U2} and [U3/U4] terminal.
(11) Turn on the power supply to all the units connected to the system other than the failed unit.
Determine what to do with the power supply to the failed unit in the following manner. <In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board> Leave the power supply off. <In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle part, or fan system part)>
Turn on the power supply to protect the compressor (by turning on the case heater). (When the power supply to the unit is turned on, [E19] (error in the number of outdoor header units) will be displayed on the 7-segment display. However, this will not cause any problems.
This is the end of header outdoor unit backup operation setting. Check the operation.
123 4 123 4 123 4 123 4
123 4 123 4
123 4 123 4
SW06 SW07 SW09 SW10
SW11 SW12
1 2 3 4 123 4
SW16 SW17
SW13 SW14
(6)
Outdoor interface P.C. board of unit selected as new header unit
(7)
Turn on Bit 2 of SW09.
Set SW13 and SW14 identically to failed header unit.
(10)
Failed header unit
Outdoor-outdoor communication line (U5/U6)
(9) Redirect the indoor-outdoor communication line from failed header unit to unit selected as header unit [U1/U2].
If central control device is connected, redirect central control communication line from failed header unit to unit selected as new header unit [U3/U4].
Unit selected as new header unit (previously follower unit No. 1)
Central control communication line (U3/U4 terminal)
Indoor-outdoor communication line (U1/U2 terminal)
Follower unit No. 2
(8)
Set Bits 1 and 2 of SW30 identically to failed header unit.
87
Backup Operation
Cooling-Season Outdoor Unit Backup Operation Setting
<Outline>
Limited to summer and other situations where there is no need for heating operation, this function makes it possible to get backup operation up and running quickly without going through the normal setup procedure, regardless of which type of outdoor unit has failed, the header unit or a follower unit. In this backup operation, the system behaves in exactly the same way as described in the “Outdoor Unit Backup Operation Setting” section, except that it cannot perform heating operation. Note 1: When the system is set up for this function, heating operation is not available.
( )
Note 2: If the unit failure has been caused by a fault in the interface P.C. board or electric circuit, this function is
not available. In that case, follow the procedure specified in the “Outdoor Unit Backup Operation Setting” section.
<Work procedure>
(1) Turn off the power supply to all the units connected to the system. [Setup of failed outdoor unit] Regardless of whether the failed outdoor unit is the header unit or a follower unit, there is no difference in the setup procedure. (2) Turn on Bits 1 and 2 of SW06 provided on the interface P.C. board. (3) If there is a leakage from an outdoor PMV (unable to close), fully close the liquid pipe service valve. (4) Turn on the power supply to all the units connected
to the system.
If the fault involves poor insulation of a compressor motor, remove the compressor leads before the power is turned on.
This is the end of cooling-season outdoor unit backup operation setting.
123 4 123 4 123 4 123 4
123 4 123 4 123 4 123 4
SW06 SW07 SW09 SW10
SW11 SW12
123 4 123 4
SW16 SW17
SW13 SW14
Turn on Bits 1 and 2 of SW06.
88
NFC (Comminication)
SMMS WAVE TOOL FOR SMARTPHONE
The NFC TAG DEVICE of the Outdoor unit communicates with SMARTPHONE that simplifies the install, the test operation and the maintenance of the SMMS-e. *NFC (Near Field Communication)
As for the details, refer to the Operation Manual of “SMMS WAVE TOOL FOR SMARTPHONE”
• You can download the Application and the Operating Manual from the below URL or QR code.
Prohibition/Permission of the NFC Setting
• This Application enables the functions of the auto-address setup and the test operation of the outdoor unit with Smartphone within 48 hours from the power input to the outdoor unit.
• You should decide whether to make use of the functions of the auto-address setup and test operation at its own responsibility and also be sure to confirm notices in the Operating
Manual before performing the test operation.
• If you want to disable the functions of the auto-address setup and the test operation, perform the following operations.
Switch setting of some functions prohibition
How to set the NFC operation all time prohibition Follow the below procedure.
QR code
URL http://www.toshiba-carrier.co.jp/global/appli/smms_wave_tool/
NFC TAG DEVICE
SMART PHONE
Push switch 7-segment display
SW01 SW02 SW03 SW04 [ A ] [ B ]
(1) 2 1 14 - [ nF] [ c.00 ]
(Default setting) After the power input, :below 48 hours [NFC operation permit] :more than 48 hours [NFC operation prohibit]
(2) 2 1 14
Press for more than 5 secs
[ nF] [ c.01 ]
NFC operation all time prohibition
(3) 1 1 1 - [ U.1. ] [ - - - ] Return the switch
Step
Rotaly switch
NFC operation
setting
89
NFC (Comminication)
How to set the NFC operation all time permission Follow the below procedure.
Push switch 7-segment display
SW01 SW02 SW03 SW04 [ A ] [ B ]
2 1 14 - [ nF] [ c.00 ]
(Default setting) After the power input, :below 48 hours [NFC operation permit] :more than 48 hours [NFC operation prohibit]
2 1 14 (Press 5 secs) [ nF] [ c.01 ]
NFC operation all time prohibition
(2) 2 1 14
Press for more
than 10 secs
[ nF] [ c.02 ]
NFC operation all time permission
(3) 1 1 1 - [ U.1. ] [ - - - ] Return the switch
(1)
Step
Rotaly switch
NFC operation
setting
Push switch 7-segment display
SW01 SW02 SW03 SW04 [ A ] [ B ]
[ nF] [ c.Er ] Abnormal [ nF] [ c.00 ] Normal
(2) 1 1 1 - [ U.1. ] [ - - - ] Return the switch
Step
Rotaly switch
NFC-I/F board
communication
(1) 2 16 14 -
* Do it again if the 7-segment display is different from the above. * The functions other than the auto-address setup and test operation of this Application can work normally even if
the functions of the auto-address setup and the test operation are disabled.
Confirmation for the generation of the trouble of the NFC
When you can not read out the information of the NFC Tag Device with your Smartphone, perform the following operations after restarting the power supply of the outdoor unit.
If there is no problem, refer to the Operation Manual of “SMMS WAVE TOOL FOR SMARTPHONE”.
Trademark Android is a trademark or registered trademark of Google Inc. QR code is a trademark or registered trademark of DENSO WAVE Inc.
90
Troubleshooting
P.C. board or other indoor error
Troubleshooting Method
The remote controllers (main remote controller and central control remote controller) and the interface P.C. board of an outdoor unit are provided with an LCD display (remote controller) or a 7-segment display (outdoor interface P.C. board) to display operational status. Using this self-diagnosis feature, the
site/ part may be
identified in the event of a
by following the method described below.
The list below summarizes check codes detected by various devices. Analyze the check code according to where it is displayed and work out the nature of the
in consultation with the list.
When investigating a on the basis of a display provided on the indoor remote controller or TCC-LINK central control remote controller - See the “TCC-LINK remote control or main remote controller display” section of the list.
When investigating a on the basis of a display provided on an outdoor unit - See the “Outdoor 7-segment display” section of the list.
When investigating a on the basis of a wireless remote controller-controlled indoor unit - See the “Light sensor indicator light block” section of the list.
List of Check Codes (Indoor Unit)
( detected by indoor unit)
Check code
Display of receiving unit
Typical problem site Description of Check code
Outdoor 7-segment display Indicator light block
Sub-code
Flash
E03
Indoor-remote controller periodic communication error
Communication from remote controller or network adaptor has been lost (so has central control communication).
E04
Indoor-outdoor periodic communication error
Signals are not being received from outdoor unit.
E08 E08
E10
Indoor inter-MCU communication error
Duplicated indoor address Duplicated indoor address Indoor unit detects address identical to its own.
MCU communication between main controller and motor microcontroller is faulty.
E18
F01
F02
F03
F10
F11
Error in periodic communication between indoor header and follower unit
Periodic communication between indoor header and follower units cannot be maintained.
Indoor heat exchanger temperature
sensor (TCJ) error
Heat exchanger temperature sensor (TCJ) has been open/short-circuited.
Indoor heat exchanger temperature sensor (TC2) error
Heat exchanger temperature sensor (TC2) has been open/short-circuited.
Indoor heat exchanger temperature sensor (TC1) error
Heat exchanger temperature sensor (TC1) has been open/short-circuited.
temperature sensor
(TA
) error
temperature sensor (TA) has been
open/short-circuited.
Discharge temperature sensor (TF
) error
Discharge
temperature sensor (TF) has been
open/short-circuited.
Duplicated indoor group header unit
There is more than one header unit in group.
Connection of group control cable to stand-alone indoor unit
There is at least one stand-alone indoor unit to which group control cable is connected.
Indoor group address not set
Address setting has not been performed for one or more indoor units (also detected at outdoor unit end).
Indoor capacity not set
Capacity setting has not been performed for indoor unit.
Duplicated central control address
There is duplication in central control address setting.
L30
Detected indoor unit No.
SIM
SIM
SIM
SIM
SIM
SIM
SIM
SIM
Indoor external error input (interlock)
Unit shutdown has been caused by external error input (CN80).
Indoor AC fan error
Indoor AC fan error is detec
ted (activation of fan
motor thermal relay).
P10
P01
P12
P13
L30
P10
Detected indoor unit No.
ALT
ALT
ALT
Indoor overflow error Float switch has been activated.
Indoor DC fan error
Indoor DC fan error (e.g. overcurrent or lock-up) is detected.
Other indoor unit error
Follower unit cannot be operated due to header unit alarm (E03/L03/L07/L08).
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Lighting, : Flashing, : Goes off ALT.: Flashing is alternately when there are two flashing LED SIM: Simultaneous flashing when there are two flashing LED
Operation
Timer Read
y
TCC-LINK central
control or main
remote controller
display
ALT
ALT
ALT
ALT
ALT
ALT
ALT
Discharge temperature sensor (TF) has been open/short-circuited.
F17
F1
F29
L03
L07
L08 L08
L09
L20
8
91
Troubleshooting
(Check code detected bymain remote controller)
(Check code detected bycentral control device)
Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.
Moreover, check codes detected by the main remote controller/central control device do not necessarily have a direct impact on air conditioner operation.
Check code
Display of receiving unit
Typical problem site Description of problem
Main remote
controller
Outdoor 7-segment display Indicator light block
Sub-code
Flash
E01
No master remote controller, faulty remote controller communication (reception)
Signals cannot be received from indoor unit; master remote controller has not been set (including two remote controller control).
E02
Faulty remote controller communication (transmission)
S
ignals cannot be transmitted to indoor unit.
E09
Duplicated master remote controller
Both remote controllers have been set as master remote controller in two remote controller control (alarm and shutdown for header unit and continued operation for follower unit)
Check code
Display of receiving unit
Typical problem site Description of problem
TCC-LINK central
control
Outdoor 7-segment display Indicator light block
Sub-code
Flash
C05
No indication (when main remote controller also in use)
Faulty central control communication (transmission)
Central control device is unable to transmit signal due to duplication of central control device.
C06
Faulty central control communication (reception)
Central control device is unable to receive signal.
Multiple network adapters are connected to remote controller communication line.
2 1 C
Blanket alarm for general­purpose device control interface
Device connected to general-purpose device control interface for TCC-LINK is faulty.
P30
As per alarm unit (see above)
Group control follower unit
Multiple network adapters
error
Group follower unit is faulty (unit No. and above detail [
] displayed on main remote
controller)
Operation
Timer Read
y
Operation
Timer Read
y
92
Troubleshooting
List of Check Codes (Outdoor Unit)
( detected by SMMS- outdoor interface - typical examples)
Check code
Display of receiving unit
Typical problem site Description of problem
Outdoor 7-segment display
TCC-LINK
central control
or main remote
controller
display
Indicator light block
Sub-code
Flash
E06
Number of indoor units from which signal is received normally
of indoor unit
Indoor unit initially communicating normally fails to return signal (reduction in number of indoor units connected).
E07 (E04)
E06
Indoor-outdoor communication circuit error
Signal cannot be transmitted to indoor units (
indoor units left without communication from
outdoor unit).
E08 Duplicated indoor address
(E08)
Duplicated indoor address
More than one indoor unit
assigned same
address (also detected at indoor unit end).
E12
01: Indoor-outdoor communication 02: Outdoor-outdoor communication
E12
Automatic address starting error
• Indoor automatic address setting is started while automatic address setting for equipment in other refrigerant line is in progress.
• Outdoor automatic address setting is started while automatic address setting for indoor units is in progress.
E15 E15
Indoor unit not found during automatic address setting
Indoor unit fails to communi
cate while automatic
address setting for indoor units is in progress.
E16
00: Overloading 01: Number of units connected
E16
Too many indoor units connected/overloading
E19
00: No header unit 02: Two or more header units
E19
Error in number of outdoor header units
There is no or more than one outdoor header unit in one refrigerant line.
E20
01: Connection of outdoor unit from other refrigerant line 02: Connection of indoor unit from other refrigerant line
E20
Connection to other refrigerant line found during automatic address setting
Indoor unit from other refrigerant line is detected while indoor automatic address
setting is in
progress.
E23 E23
Outdoor-outdoor communication transmission error
Signal cannot be transmitted to other outdoor units.
E25 E25
Duplicated follower outdoor address
There is duplication in outdoor addresses set manually.
E26
Address of outdoor unit from which signal is not received normally
E26
E28
of outdoor unit
Follower outdoor unit initially communicating normally fails to do so (reduction in number of follower outdoor units connected).
O
utdoor header unit detects fault relating to follower outdoor unit (detail displayed on follower outdoor unit).
Outdoor follower unit error
1 3 E
There is no communication between IPDUs (P.C. boards) in inverter box.
Outdoor discharge temperature sensor (TD1) error
Outdoor discharge temperature sensor (TD1) has been open/short-circuit
ed.
F05
F04
F05
F04
E31
F06
F07
F08
ALT
ALT
ALT
ALT
Outdoor discharge temperature sensor (TD2) error
Outdoor discharge temperature sensor (TD2) has been open/short-circuited.
F06
F07
F08
01: TE1 02: TE2
Outdoor heat exchanger
temperature
sensor (TE1, TE2) error
Outdoor heat exchanger
temperature sensors (TE1, TE2) have been open/short­circuited.
Outdoor liquid temperature sensor (TL1
) error
Outdoor liquid temperature sensor (TL
)
has been open/short-circuited.
Outdoor outside air temperature sensor (TO) error
Outdoor outside air temperature sensor (TO) has been open/short-circuited.
Outdoor heat exchanger gas side temperature sensor (TG1, TG2) error
Outdoor heat exchanger gas side temperature sensors (TG1, TG2) have been open/short­circuited.
IPDU: Intelligent Power Drive Unit (Inverter P.C. board)
: Lighting, : Flashing, : Goes off ALT.: Flashing is alternately when there are two flashing LED SIM: Simultaneous flashing when there are two flashing LED
Operation
Timer Ready
Circle (O): Faulty IPDU
01: T 1 02: T
2
03: T
3
F09
01: T
1
02: T
2
IPDU communication error
1 2 1 2 1 2 1 2 01 10 02 11 03 12
08 13
09 18 0A ○ ○ 19 0B ○ ○ 1A ○ ○
1B ○ ○
A3-IPDU A3-IPDU Fan-IPDUFan-IPDU
93
Troubleshooting
Outdoor pressure sensor (Pd, Ps) wiring error
Wiring error in outdoor pressure sensors (Pd, Ps) has been detected.
Low pressure sensor (Ps) error
Output voltage of low pressure sensor (Ps) is zero.
High pressure sensor (Pd) error
Outdoor EEPROM error
Output voltage of high pressure sensor (Pd) is zero or provides abnormal readings when compressors have been turned off.
Outd
oor EEPROM is faulty (alarm and shutdown
for header unit and continued operation for followe
r
unit)
H05
F12
F15
F16
F23
F24
F31
H05
F31
F24
F23
F16
F15
F12
Outdoor discharge temperature sensor (TD1) wiring error
Wiring/installation error or detachment of outdoor discharge temperature sensor (TD1) has been detected.
H06 H06
H07
Activation of low-pressure protection
Low oil level protection
Low pressure (Ps) sensor detects abnormally low operating pressure.
Temperature sensor for oil level detection (TK1,TK2,TK4,TK5) detects abnormally low oil level.
H08
H07
01: TK1 sensor error 02: TK2 sen
sor error 04: TK4 sensor error 05: TK5 sensor error
H08
Error in temperature sensor for oil level detection (TK1
T )
Temperature sensor for oil level detection (TK1
) has been open/short-
circuited.
H15 H15
Outdoor discharge temperature sensor (TD2) wiring error
Wiring/installation error or detachment of outdoor discharge temperature sensor (TD2) has been detected.
H16
01: TK1 oil circuit error 02: TK2 oil circuit error 04: TK4 oil circuit error 05: TK5 oil circuit error
H16
Oil level detection circuit error
No temperature change is detected by temperature sensor for oil level detection (TK1
) despite compressor having
been started.
Dup
licated outdoor
refrigerant line address
Identical refrigerant line address has been assigned to outdoor units belonging to different refrigerant piping systems.
L06
L04 L04
L05
L06
(L08)
L10L10
L08
L17L17
L28L28
Number of priority indoor units (check code L05 or L06 depending on individual unit)
Duplicated priority indoor unit (as displayed on priority indoor unit)
More than one indoor unit have been set up as priority indoor unit.
Duplicated priority indoor unit
(as displayed on indoor unit other than priority indoor unit)
More than one indoor unit
been set up
as priority indoor unit.
Indoor group address not set
Outdoor capacity net set
Address setting
not been performed for one
or more indoor units (also detected at indoor end).
Outdoor unit capacity has not been set (after P.C. board replacement).
Outd
oor model
incompatibility error
Old model outdoor unit (prior to 6 series) has been connected.
Too many outdoor units connected
More than
outdoor units have been
connected.
Check code
Display of receiving unit
Typical problem site Description of problem
Outdoor 7-segment display
TCC-LINK
central control
or main remote
controller
display
Indicator light block
Sub-code
Flash
Operation
Timer Read
y
01: T 1 03: T
SIM
SIM
SIM
SIM
SIM
SIM
SIM
SIM
ALT
ALT
ALT
ALT
ALT
SIM
L23L23
94
Troubleshooting
MG-CTT: Magnet contactor
There are insufficient number of IPDUs (P.C. boards) in inverter box.
Indoor external error input (interlock)
Indoor unit has been shut down for external error input in one refrigerant line (detected by indoor unit).
Outdoor discharge (TD1) temperature error
Outdoor discharge temperature sensor (TD1) has detected abnormally high temperature.
P05
00: Open phase detected
Detected indoor unit No.
Open phase/power failure
Open phase is detected when power is turned on. Inverter DC voltage is too high (overvoltage) or too low (undervoltage).
01: Compressor 1 02: Compre
ssor 2
Inverter DC voltage (Vdc) error MG-CTT error
P07
01: Compressor 1 02: Compressor 2
Indoor unit No. detected
Heat sink overheating error
Temperature sensor built into
(TH) detects
overheating.
Indoor unit has been shutdown in one refrigerant line due to detection of overflow (detected by indoor unit).
Outdoor liquid backflow detection error
State of refrigerant cycle circuit indicates liquid backflow operation.
P15
P13
P10 (P10)
P07
P05
P03 P03
L30
L29
L29 SIM
SIM
ALT
ALT
ALT
ALT
ALT
ALT Gas leak detection
Indoor unit overflow
ALT
ALT
ALT
Error in number of IPDUs
(L30)
P17
P19
P20
01: TS condition 02: TD condition
Outdoor suction temperature sensor (TS1) detects sustained and repeated high temperatures that exceed standard value.
Outdoor disc
harge (TD2)
temperature error
Outdoor discharge temperature sensor (TD2) detects abnormally high temperature.
4-way valve reversing error
Abnormality in
refrigerating cycle is detected
during heating operation.
Activation of high-pressure protection
High pressure (Pd) sensor detects high pressure that exceeds standard value.
Check code
Display of receiving unit
Typical problem site Description of problem
Outdoor 7-segment display
TCC-LINK
central control
or main remote
controller
d
isplay
Indicator light block
Sub-code
Flash
Operation
Timer Ready
Circle (O): Faulty IPDU
1 2 1 2 1 2 1 2 01 10 02 11 03 12 08 13 09 18 0A 19 0B 1A
1B
A3-IPDU A3-IPDU Fan-IPDUFan-IPDU
95
Troubleshooting
( detected by IPDU featuring in SMMS- standard outdoor unit - typical examples)
Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration
Check code
Display of receiving unit
Typical problem site Description of proplem
Outdoor 7-segment display
TCC-LINK
central control
or main remote
controller
display
Indicator light block
Sub-code
Flash
F13
01: Compressor 1 02: Compressor 2
Error in temperature sensor built into indoor
(TH)
Temperature sensor built into indoor
(TH)
has been open/short-circuited.
H01
01: Compressor 1 02: Compressor 2
Inverter current (Idc) detection circuit detects overcurrent.
H02
01: Compressor 1 02: Compressor 2
H02
H01
F13
Compressor error (lockup) Compressor lockup is detected
H03
01: Compressor 1 02: Compressor 2
H03
P04
P07
P22
P26
P29
Current detection circuit error
Compressor breakdown
Abnormal current is detected while inverter compressor is turned off.
P04
01: Compressor 1 02: Compressor 2
Activation of high-pressure SW
High-pressure SW is activated.
P07
01: Compressor 1 02: Compressor 2
Heat sink overheating error
Temperature sensor built into
(TH) detects
overheating
P22
P26
01: Compressor 1 02: Compressor 2
Activation of short-circuit protection
Short-circuit protection for compressor motor driver circuit components is activated (momentary overcurrent).
P29 ALT
ALT
ALT
ALT
ALT
ALT
Outdoor fan IPDU error Outdoor fan IPDU detects error.
01: Compressor 1 02: Compressor 2
Compressor position detection circuit error
Compressor motor position detection error is detected.
Operation
Timer Read
y
Quick Reference
Loading...