Toshiba RAV-SM404SDT-E, RAV-SM1604UT-E User Manual

FILE NO. A07-003
Revised: Mar., 2008
Revised 2: Jun., 2008
SERVICE MANUAL
AIR-CONDITIONER
SPLIT TYPE
<DIGITAL INVERTER>
RAV-SM564UT-E RAV-SM404SDT-E RAV-SM804UT-E RAV-SM454SDT-E RAV-SM1104UT-E RAV-SM564SDT-E RAV-SM1404UT-E RAV-SM1604UT-E
OUTDOOR UNIT
<SUPER DIGITAL INVERTER>
RAV-SP404AT-E RAV-SP454AT-E RAV-SP404ATZ-E RAV-SP454ATZ-E RAV-SP404ATZG-E RAV-SP454ATZG-E
RAV-SP1104AT-E RAV-SP1404AT-E RAV-SP1104ATZ-E RAV-SP1404ATZ-E RAV-SP1104ATZG-E RAV-SP1404ATZG-E
R410A
PRINTED IN JAPAN, Jun., 2008 ToMo
Adoption of New Refrigerant
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to have a service person do it. Do not attempt it yourself.
The cleaning diagram for the air filter is there for the ser vice person, and not for the customer.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. SPECIFICATIONS ...................................................................................... 9
1-1. Indoor Unit........................................................................................................... 9
1-2. Outdoor Unit...................................................................................................... 25
1-3. Operation Characteristic Curve....................................................................... 27
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)....................................... 29
2-1. Indoor Unit......................................................................................................... 29
2-2. Outdoor Unit...................................................................................................... 33
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM .............................. 36
3-1. Indoor Unit......................................................................................................... 36
3-2. Outdoor Unit...................................................................................................... 37
4. FAN CHARACTERISTICS ........................................................................ 39
4-1. Slim Duct (Filter Attached)............................................................................... 39
5. WIRING DIAGRAM ................................................................................... 40
5-1. Indoor Unit......................................................................................................... 40
5-2. Outdoor Unit...................................................................................................... 42
6. SPECIFICATIONS OF ELECTRICAL PARTS .......................................... 44
6-1. Indoor Unit......................................................................................................... 44
6-2. Outdoor Unit (Parts Ratings) ........................................................................... 45
6-3. Accessory Separate Sold Parts....................................................................... 45
– 2 –
7. REFRIGERANT R410A ............................................................................ 46
7-1. Safety During Installation / Servicing ............................................................. 46
7-2. Refrigerant Piping Installation....................................................................... 46
7-3. Tools .................................................................................................................. 50
7-4. Recharging of Refrigerant................................................................................ 50
7-5. Brazing of Pipes................................................................................................ 51
7-6. Instructions for Re-use Piping of R22 or R407C ............................................ 53
8. INDOOR CONTROL CIRCUIT.................................................................. 58
8-1. Indoor Controller Block Diagram..................................................................... 58
8-2. Control Specifications...................................................................................... 61
8-3. Optional Connector Specifications of Indoor P.C. Board.............................. 74
8-4. Indoor Print Circuit Board................................................................................ 75
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS ........... 76
9-1. Outdoor Controls.............................................................................................. 76
9-2. Outline of Main Controls .................................................................................. 78
10. TROUBLESHOOTING .............................................................................. 87
10-1. Summary of Troubleshooting........................................................................... 87
10-2. Troubleshooting................................................................................................ 89
11. REPLACEMENT OF SERVICE P.C. BOARD.......................................... 141
11-1. Indoort Unit ..................................................................................................... 141
11-2. Outdoor Unit.................................................................................................... 146
12. SETUP AT LOCAL SITE AND OTHERS ................................................ 147
12-1. Indoor Unit....................................................................................................... 147
12-2. Setup at Local Site / Others ........................................................................... 158
12-3. Ho w to Set up Central Control Address Number ......................................... 160
12-4. Outdoor Unit.................................................................................................... 166
13. ADDRESS SETUP.................................................................................. 173
13-1. Address Setup Procedure.............................................................................. 173
13-2. Address Setup & Group Control.................................................................... 174
13-3. Remote Controller Wiring............................................................................... 177
13-4. Address Setup (Manual setting from remote controller)............................. 178
13-5. Confirmation of Indoor Unit No. Position ..................................................... 179
14. DETACHMENTS ..................................................................................... 181
14-1. Indoor Unit...................................................................................................... 181
14-2. Outdoor Unit.................................................................................................... 196
15. EXPLODED VIEWS AND PARTS LIST .................................................. 211
15-1. Indoor Unit....................................................................................................... 211
15-2. Outdoor Unit.................................................................................................... 219
3
SAFETY CAUTION
The important contents concerned to the saf ety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or proper ty damage (∗) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injur y.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high-voltage transformer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high-voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
– 4 –
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused.
: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not br ing inflammables close to the refr igerant cycle, otherwise fire of the welder may catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service por t is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrig erant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires.
If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.
– 5 –
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
Revised 2: Jun., 2008
WARNING
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 2MΩ or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
Check after repair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on the gloves () and a long sleeved shirt: otherwise an injury may be caused with the parts, etc.
() Heavy gloves such as wor k gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
– 6 –
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the for mer refr igerant or the former refrigerating oil is not mixed into the
refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of
the former refrigerant in order to prevent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes. Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the
refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe
without seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes.
(Impurities cause clogging of expansion valves and capillar y tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation of the air conditioner. However clear impurities when using them.
– 7 –
Revised 2: Jun., 2008
4. Tools
1. Required T ools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,
etc. Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Flare tool
Q
Copper pipe gauge for
R
adjusting projection margin Torque wrench
S
Gauge manifold
T
Charge hose
U
V acuum pump adapter
V
Electronic balance for
W
refrigerant charging Refrigerant cylinder
X
Leakage detector
Y
Used tool
Usage
Pipe flaring Flaring by conventional
flare tool Tightening of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating
Refrigerant charge
Refrigerant charge Gas leakage check
air conditioner installation
R410A
Existence of Whether conven-
new equipment tional equipment
for R410A can be used
Yes *(Note)
Yes *(Note)
Yes No
Yes No
Yes No
Yes Yes
Yes No Yes No
Conventional air
conditioner installation
Whether conventional
equipment can be used
Yes
*(Note)
No
No
Yes
Yes
No
Yes
(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1) Vacuum pump. Use vacuum pump by attaching vacuum pump adapter. 7) Screwdriver (+, –)
2) Torque wrench 8) Spanner or Monkey wrench
3) Pipe cutter 9) Hole core drill
4) Reamer 10) Hexagon wrench (Opposite side 4mm)
5) Pipe bender 11) Tape measure
6) Level vial 12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter 3) Insulation resistance tester (Megger)
2) Thermometer 4) Electroscope
– 8 –
1. SPECIFICATIONS
1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min.)
Air filter Controller (Sold separately) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Connecting pipe Liquid side (mm)
Indoor unit RA V-SM Outdoor unit RA V-SP
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
564UT-E 804UT-E 1104UT-E 1404UT-E
562A T(Z)(ZG)-E 802AT(Z)(ZG)-E 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E
5.3 7.1 10.0 12.5
5.6 8.0 11.2 14.0 1 phase 230V (220 – 240V) 50Hz
7.17 – 6.57 8.95 – 8.21 10.36 – 9.49 14.66 – 13.44
1.53 1.93 2.21 3.16 97 98 97 98
3.46 3.68 4.52 3.96
AAAA
————
5.62 – 5.15 9.42 – 8.63 10.96 – 10.05 14.89 – 13.65
1.20 2.03 2.34 3.21 97 98 97 98
4.67 3.94 4.79 4.36
AAAA
————
15.33 15.33 20.50 20.50 Zinc hot dipping steel plate
RBC-U31PG (W, WS)-E, RBC-U31PGS (W, WS)-E
W: Moon-white (2.5GY 9.0/0.5), WS: Stripe-white (2.5GY 9.0/0.5, (Gray: 8B 3/0.3))
256 256 319 319 840 840 840 840 840 840 840 840
30 30 30 30 950 950 950 950 950 950 950 950
20 20 24 24
4.2 4.2 4.2 4.2 Finned tube
Turbo fan
17.5/14.5/13.0 20.5/16.0/13.5 33.5/24.0/19.5 35.0/24.0/20.5 14 20 68 72
Standard filter attached (Long life filter)
RBC-AMT32E, AMS41E, AS21E2, AX31U (W)-E 32 / 29 / 28 35 / 31 / 28 43 / 38 / 33 44 / 38 / 34 47 / 44 / 43 50 / 46 / 43 58 / 53 / 48 59 / 53 / 49
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
– 9 –
: IEC standard, ∗∗ : AS standard
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min.)
Air filter Controller (Sold separately) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Connecting pipe Liquid side (mm)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color
Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM564UT-E SM804UT-E SM1104UT-E SM1404UT -E SM1604UT-E
SM563AT-E SM803AT-E SM1103AT-E SM1403AT -E SM1603AT-E
5.3 6.7 10.0 12.0 14.0
5.6 8.0 11.2 14.0 16.0 1 phase 230V (220 – 240V) 50Hz
7.89 – 7.24 9.97 – 9.12 14.61 – 13.40 17.62 – 16.14 21.48 – 19.69
1.65 2.09 3.11 3.74 4.49 95 95 97 96 95
3.21 3.21 3.22 3.21 3.12
AAAAB
—————
6.89 – 6.32 10.83 – 9.90 13.38 – 12.38 17.88 – 15.87 21.20 – 19.43
1.44 2.21 2.93 3.80 4.43 95 93 99 98 95
3.89 3.62 3.82 3.68 3.61
AAAAA
—————
15.33 15.33 20.50 20.50 32.0 Zinc hot dipping steel plate
RBC-U31PG (W , WS)-E, RBC-U31PGS (W, WS)-E
W: Moon-white (2.5GY 9.0/0.5),
WS: Stripe-white (2.5GY 9.0/0.5, (Gray: 8B 3/0.3)) 256 256 319 319 319 840 840 840 840 840 840 840 840 840 840
30 30 30 30 30 950 950 950 950 950 950 950 950 950 950
20 20 24 24 24
4.2 4.2 4.2 4.2 4.2 Finned tube
Turbo fan
17.5/14.5/13.0 20.5/16.0/13.5 33.5/24.0/19.5 35.0/24.0/20.5 35.5/25.0/21.0 14 20 68 72 72
Standard filter attached (Long life filter)
RBC-AMT32E, AMS41E, AS21E2, AX31U (W)-E 32 / 29 / 28 35 / 31 / 28 43 / 38 / 33 44 / 38 / 34 45 / 40 / 36 47 / 44 / 43 50 / 46 / 43 58 / 53 / 48 59 / 53 / 49 60 / 55 / 51
12.7 15.9 15.9 15.9 15.9
6.4 9.5 9.5 9.5 9.5 VP25
– 10 –
: IEC standard, ∗∗ : AS standard
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RA V- SM564UT-E SM804UT-E
Model Indoor unit 2 RAV- SM564UT-E SM804UT-E
Outdoor unit RA V- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E
Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 10.36 – 9.49 14.66 – 13.44 Po w er consumption (kW) 2.21 3.16
Cooling Power factor (%) 97 98
EER 4.52 3.96
Electrical characteristics
Heating Power factor (%) 97 98
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 17.5 / 14.5 / 13.0 20.5 / 16.0 / 13.5
Motor (W) 14 20 Sound pressure level H/M/L (dB•A) 32 / 29 / 28 35 / 31 / 28 Sound power level H/M/L (dB•A) 47 / 44 / 43 50 / 46 / 43
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Refrigerant pipe Refrigerant charging amount
Max. total length (m) 50 50
(Charge-less up to 30m)
Energy efficiency class AA Running current (A) 10.96 – 10.05 14.89 – 13.65 Po w er consumption (kW) 2.34 3.21
COP 4.79 4.36 Energy efficiency class AA
Outdoor unit
40g/m (31m to 50m)
Height
difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 101 103
Motor (W) 100 + 100 100 + 100
Gas side Connecting
pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 49 / 50 51 / 52 Sound power level Cooling/Heating (dB•A) 66 / 67 68 / 69
Outdoor lower (m) 30 30 Outdoor higher (m) 30 30
Main (mm) 15.9 15.9 Sub (mm) 12.7 15.9 Main (mm) 9.5 9.5 Sub (mm) 6.4 9.5
: IEC standard
– 11 –
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RA V- SM564UT-E SM804UT-E SM804UT -E Model Indoor unit 2 RAV- SM564UT-E SM804UT -E SM804UT-E
Outdoor unit RA V- SM1103AT-E SM1403AT-E SM1603A T-E
Cooling capacity (kW) 10.0 12.5 14.0 Heating capacity (kW) 11.2 14.0 16.0
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 14.59 – 13.38 19.17 – 17.57 21.48 – 19.69 Po w er consumption (kW) 3.11 4.09 4.49
Cooling Power factor (%) 98 97 95
EER 3.22 3.06 3.12
Electrical characteristics
Heating Power factor (%) 99 97 95
Fan Turbo fan Fan unit Standard air flow H/M/L (m³/min.) 17.5 / 14.5 / 13.0 20.5 / 16.0 / 13.5 20.5 / 16.0 / 13.5
Motor (W) 14 20 20 Sound pressure level H/M/L (dB•A) 32 / 29 / 28 35 / 31 / 28 35 / 31 / 28 Sound power level H/M/L (dB•A) 47 / 44 / 43 50 / 46 / 43 50 / 46 / 43
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5 7.5
Min. length (m) 5 5 5
Refrigerant pipe
Max. total length (m) 50 50 50
Refrigerant charging amount
(Charge-less up to 30m)
Energy efficiency class A (B) (B) Running current (A) 13.36 – 12.36 18.74 – 17.18 21.20 – 19.43 Po w er consumption (kW) 2.93 4.00 4.43
COP 3.82 3.50 3.61 Energy efficiency class A (B) (A)
Outdoor unit
40g/m (31m to 50m)
Height
difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 75 75 103
Motor (W) 63 100 100 + 100
Gas side Connecting
pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 53 / 54 54 / 54 51 / 53 Sound power level Cooling/Heating (dB•A) 70 / 71 71 / 71 68 / 70
Outdoor lower (m) 30 30 30 Outdoor higher (m) 30 30 30
Main (mm) 15.9 15.9 15.9 Sub (mm) 12.7 15.9 15.9 Main (mm) 9.5 9.5 9.5 Sub (mm) 6.4 9.5 9.5
: IEC standard
– 12 –
1-1-2. Concealed Duct Type
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit
Air filter (Sold separately) TCB-
Controller (Sold separately) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Connecting pipe Liquid side (mm)
Indoor unit RA V-SM Outdoor unit RA V-SP
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan Standard air flow H/M/L (m³/min.) Motor (W)
External static pressure
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Standard (at shipment)
Set up for tap e xchange
Gas side (mm)
Drain port (mm)
(Pa)
(Pa)
562BT-E 802BT-E 1102BT-E 1402BT-E
562A T(Z)(ZG)-E 802AT(Z)(ZG)-E 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E
5.0 7.1 10.0 12.5
5.6 8.0 11.2 14.0 1 phase 230V (220 – 240V) 50Hz
6.51 – 5.97 9.74 – 8.93 13.78 – 12.63 17.76 – 16.28
1.39 2.10 2.94 3.83 97 98 97 98
3.60 3.38 3.40 3.26
AAAA
————
7.26 – 6.66 9.74 – 8.93 12.98 – 11.90 15.82 – 14.50
1.55 2.41 2.77 3.41 97 94 97 98
3.61 3.32 4.04 4.11
AAAA
————
15.86 16.30 21.73 22.13 Zinc hot dipping steel plate
— 320 320 320 320 700 1000 1350 1350 800 800 800 800
———— ———— ———— 30 39 54 54 ————
Finned tube
Centrifugal
13.0/11.9/9.8 19.0/16.2/13.3 27.0/23.0/18.9 33.0/28.0/23.1 120 120 120 120
40
20/40/70/100 20/40/65/90
UFM11BFCE UFM21BFCE UFM21BE UFM31BE UFM41BE UFM61BE UFM51BFCE UFM61BFCE
UFM71BE UFM81BE
RBC-AMT31E, AMS41E, AS21E2, AX21U(W)-E2 40 / 37 / 33 40 / 37 / 34 42 / 39 / 36 44 / 41 / 38 55 / 52 / 48 55 / 52 / 49 57 / 54 / 51 59 / 56 / 53
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
– 13 –
: IEC standard, ∗∗ : AS standard
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RA V- SM562BT-E SM802BT-E
Model Indoor unit 2 RAV- SM562BT-E SM802BT-E
Outdoor unit RA V- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E
Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 13.78 – 12.63 17.76 – 16.28 Po w er consumption (kW) 2.94 3.83
Cooling Power factor (%) 97 98
EER 3.4 3.26
Electrical characteristics
Heating Power factor (%) 97 98
Fan Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0 / 11.9 / 9.8 19.0 / 16.2 / 13.3
Motor (W) 120 120 Sound pressure level H/M/L (dB•A) 40 / 37 / 33 40 / 37 / 34 Sound power level H/M/L (dB•A) 55 / 52 / 48 55 / 52 / 49
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Refrigerant pipe
Max. total length (m) 50 50
Refrigerant charging amount
(Charge-less up to 30m)
Energy efficiency class AA Running current (A) 12.98 – 11.90 15.82 – 14.50 Po w er consumption (kW) 2.77 3.41
COP 4.04 4.11 Energy efficiency class AA
Outdoor unit
40g/m (31m to 50m)
Height
difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 101 103
Motor (W) 100 + 100 100 + 100
Gas side Connecting
pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 49 / 50 51 / 52 Sound power level Cooling/Heating (dB•A) 66 / 67 68 / 69
Outdoor lower (m) 30 30 Outdoor higher (m) 30 30
Main (mm) 15.9 15.9 Sub (mm) 12.7 15.9 Main (mm) 9.5 9.5 Sub (mm) 6.4 9.5
: IEC standard
– 14 –
1-1-3. Under Ceiling Type
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min.)
Air filter Controller (Sold separately) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Connecting pipe Liquid side (mm)
Indoor unit RA V-SM Outdoor unit RA V-SP
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
562CT-E 802CT-E 1102CT-E 1402CT-E
562A T(Z)(ZG)-E 802AT(Z)(ZG)-E 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E
5.0 7.1 10.0 12.5
5.6 8.0 11.2 14.0 1 phase 230V (220 – 240V) 50Hz
6.61 – 6.06 9.47 – 8.93 12.51 – 11.47 17.30 – 15.86
1.41 2.1 2.67 3.73 97 98 97 98
3.55 3.38 3.75 3.35
AAAA
————
7.03 – 6.44 10.20 – 9.35 12.28 – 11.25 16.93 – 15.52
1.50 2.20 2.62 3.65 97 98 97 98
3.73 3.64 4.27 3.84
AAAA
————
15.48 15.90 21.35 21.35 Shine white
— 210 210 210 210 910 1180 1595 1595 680 680 680 680
———— ———— ———— 21 25 33 33 ————
Finned tube
Centrifugal
13.0/11.2/10.0 18.5/16.7/14.6 27.5/24.0/21.2 30.0/26.0/23.1 60 60 120 120
Attached main unit
RBC-AMT31E, AMS41E, AS21E2, TCB-SC642TLE2, AX21UCE2 36 / 33 / 30 38 / 36 / 33 41 / 38 / 36 43 / 40 / 37 51 / 48 / 45 53 / 51 / 48 56 / 53 / 50 58 / 55 / 52
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5 VP25
– 15 –
: IEC standard, ∗∗ : AS standard
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RA V- SM562CT-E SM802CT-E
Model Indoor unit 2 RAV- SM562CT-E SM802CT-E
Outdoor unit RA V- SP1104AT(Z)(ZG)-E SP1404A(Z)(ZG)-E
Cooling capacity (kW) 10.0 12.5 Heating capacity (kW) 11.2 14.0
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 12.51 – 11.47 17.30 – 15.86 Po w er consumption (kW) 2.67 3.73
Cooling Power factor (%) 97 98
EER 3.75 3.35
Electrical characteristics
Heating Power factor (%) 97 98
Fan Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0 / 11.2 / 10.0 18.5 / 16.7 / 14.6
Motor (W) 60 60 Sound pressure level H/M/L (dB•A) 36 / 33 / 30 38 / 36 / 33 Sound power level H/M/L (dB•A) 51 / 48 / 45 53 / 51 / 48
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5
Min. length (m) 3 3 Refrigerant
pipe
Max. total length (m) 50 50
Refrigerant charging amount 40g/m
(Charge-less up to 30m) (31m to 50m)
Energy efficiency class AA Running current (A) 12.28 – 11.25 16.93 – 15.52 Po w er consumption (kW) 2.62 3.65
COP 4.27 3.84 Energy efficiency class AA
Outdoor unit
Height
difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 101 103
Motor (W) 100 + 100 100 + 100
Gas side Connecting
pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 49 / 50 51 / 52 Sound power level Cooling/Heating (dB•A) 66 / 67 68 / 69
Outdoor lower (m) 30 30 Outdoor higher (m) 30 30
Main (mm) 15.9 15.9 Sub (mm) 12.7 15.9 Main (mm) 9.5 9.5 Sub (mm) 6.4 9.5
: IEC standard
– 16 –
1-1-4. High Wall T ype
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min.)
Air filter
Controller (Sold separately)
Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Connecting pipe Liquid side (mm)
Indoor unit RA V­Outdoor unit RA V-
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Gas side (mm)
Drain port (mm)
SM562KRT-E SM802KRT-E
SP562AT(Z)(ZG)-E SP802AT(Z)(ZG)-E
5.0 6.9
5.6 8.0 1 phase 230V (220 – 240V) 50Hz
8.33 – 7.63 13.15 – 12.05
1.39 2.4 95 94
3.60 2.88
AC
——
8.14 – 7.46 12.91 – 11.84
1.55 2.4 95 94
3.61 3.33
AC
——
15.34 15.47 Pure white
— 298 298 998 998 221 221
—— —— —— 12 12 ——
Finned tube
Cross flow fan Cross flow fan
14.0 / 12.5 / 10.7 18.5 / 14.6 / 12.2 30 30
Attached main unit
RBC-AMT31E, AMS41E, AS21E2, TCB-SC642TLE2, AX21UCE2
(FCU comes with WH-H2UE) 39 / 36 / 33 45 / 41 / 36 54 / 51 / 48 60 / 56 / 51
12.7 15.9
6.4 9.5 VP16
– 17 –
: IEC standard, ∗∗ : AS standard
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RAV- SM562KRT-E SM802KRT-E
Model Indoor unit 2 RAV- SM562KRT-E SM802KRT-E
Outdoor unit RA V- SP1104AT(Z)(ZG)-E SP1404AT(Z)(ZG)-E
Cooling capacity (kW) 10.0 12.3 Heating capacity (kW) 11.2 14.0
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 12.98 – 11.90 18.00 – 16.50 Po w er consumption (kW) 2.77 3.88
Cooling Power factor (%) 97 98
EER 3.61 3.17
Electrical characteristics
Heating Power factor (%) 97 98
Fan Cross flow fan
Fan unit Standard air flow H/M/L (m³/min.) 14.0 / 12.5 / 10.7 18.5 / 14.6 / 12.2
Motor (W) 30 30 Sound pressure level H/M/L (dB•A) 39 / 36 / 33 45 / 41 / 36 Sound power level H/M/L (dB•A) 54 / 51 / 48 60 / 56 / 51
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5 7.5
Min. length (m) 3 3
Refrigerant pipe
Max. total length (m) 50 50
Refrigerant charging amount 40g/m
(Charge-less up to 30m) (31m to 50m)
Energy efficiency class AB Running current (A) 13.12 – 12.03 17.76 – 16.28 Po w er consumption (kW) 2.80 3.83
COP 4.00 3.66 Energy efficiency class AA
Outdoor unit
Height
difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 101 103
Motor (W) 100 + 100 100 + 100
Gas side Connecting
pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 49 / 50 51 / 52 Sound power level Cooling/Heating (dB•A) 66 / 67 68 / 69
Outdoor lower (m) 30 30 Outdoor higher (m) 30 30
Main (mm) 15.9 15.9 Sub (mm) 12.7 15.9 Main (mm) 9.5 9.5 Sub (mm) 6.4 9.5
: IEC standard
– 18 –
1-1-5. Compact 4-Way Cassette (600 × 600) Type
<Single type>
Model
Cooling capacity (kW) Heating capacity (kW) Power supply
Electrical characteristics Running current (A)
Indoor unit Outdoor unit
Cooling
Heating
Running current (A) Power consumption (kW) Power factor (%) EER Energy efficiency class Energy rating
Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating
RAV-SM562MUT-E
RAV-SP562AT(Z)(ZG)-E
5.0
5.6
1 phase 230V (220 – 240V) 50Hz
6.6 – 7.15
1.53 97
3.27
A
4.5
6.62 – 7.21
1.54 97
3.64
A
4.5 Maximum current (A) Main unit
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Standard air flow H/M/L (m³/min.)
Air filter
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan
Motor (W)
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
15.53
Zinc hot dipping steel plate
RBC-UM11PG(W)-E
Moon-white (Muncel 2.5GY 9.0 / 0.5)
268 575 575
27 700 700
17
3
Finned tube
Turbo fan
13.3 / 11.2 / 9.1 60 —
Controller (Sold separately) Sound pressure level H/M/L (dB•A) Sound power level H/M/L (dB•A)
Gas side (mm)
Connecting pipe Liquid side (mm)
Drain port (mm)
– 19 –
As per enclosure
43 / 39 / 34 58 / 54 / 49
12.7
6.4
VP25
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RA V- SM562MUT-E
Model Indoor unit 2 RAV - SM562MUT-E
Outdoor unit RA V- SP1104A T(Z)(ZG)-E
Cooling capacity (kW) 10.0 Heating capacity (kW) 11.2
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 12.51 – 11.47 Po w er consumption (kW) 2.67
Cooling Power factor (%) 97
EER 3.75
Electrical characteristics
Heating Power factor (%) 97
Fan Turbo fan
Fan unit Standard air flow H/M/L (m³/min.) 13.3 / 11.2 / 9.1
Motor (W) 60 Sound pressure level H/M/L (dB•A) 43 / 39 / 34 Sound power lev el H/M/L (dB•A) 58 / 54 / 49
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Standard length (m) 7.5
Min. length (m) 3
Refrigerant pipe
Max. total length (m) 50
Refrigerant charging amount (Charge-less up to 30m) 40g/m (31m to 50m)
Energy efficiency class A Running current (A) 12.51 – 11.47 Po w er consumption (kW) 2.67
COP 4.19 Energy efficiency class A
Outdoor unit
Height difference
Fan Propeller fan Fan unit Standard air flow volume (m³/min.) 101
Motor (W) 100 + 100
Gas side Connecting pipe
Liquid side
Sound pressure level Cooling/Heating (dB•A) 49 / 50 Sound power lev el Cooling/Heating (dB•A) 66 / 67
Outdoor lower (m) 30 Outdoor higher (m) 30
Main (mm) 15.9 Sub (mm) 12.7 Main (mm) 9.5 Sub (mm) 6.4
– 20 –
: IEC standard
1-1-6. Slim Duct Type
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Motor (W)
Air filter Controller (Sold separately)
Sound pressure level
Sound power lev el
Connecting pipe Liquid side (mm)
Indoor unit RAV -SM Outdoor unit RAV-SP
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan Standard air flow H/M/L (m³/min.)
External static pressure
Under air inlet H/M/L (dB•A) Back air inlet H/M/L (dB•A) Under air inlet H/M/L (dB•A) Back air inlet H/M/L (dB•A)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Standard (at shipment) (Pa) Set up for tap exchange (Pa)
Gas side (mm)
Drain port (mm)
404SDT-E 454SDT-E 564SDT-E
404AT(Z)(ZG)-E 454AT(Z)(ZG)-E 562AT(Z)(ZG)-E
3.6 4.0 5.0
4.0 4.5 5.6 1 phase 230V (220 – 240V) 50Hz
5.20 – 4.77 5.87 – 5.38 7.26 – 6.66
1.03 1.20 1.55 90 93 97
3.50 3.33 3.23
AAA
5.0 4.5 4.0
4.94 – 4.53 5.62 – 5.15 6.75 – 6.19
1.00 1.15 1.44 92 93 97
4.00 3.91 3.89
AAA
5.5 5.0 5.0
15.00 15.00 15.00 Zinc hot dipping steel plate
— 210 210 210 845 845 845 645 645 645
——— ——— ——— 22 22 22 ———
Finned tube
Centrifugal
11.5 / 10.0 / 8.7 11.5 / 10.0 / 8.7 13.0 / 11.3 / 9.7 60 60 60
10
10 / 20 / 35 / 50
Standard filter attached (Long life filter)
RBC-AMT32E, AMS41E, AS21E2 39 / 36 / 33 39 / 36 / 33 45 / 40 / 36 30 / 28 / 26 30 / 28 / 26 33 / 31 / 28 54 / 51 / 48 54 / 51 / 48 60 / 55 / 51 45 / 43 / 41 45 / 43 / 41 48 / 46 / 43
12.7 12.7 12.7
6.4 6.4 6.4 VP25
– 21 –
: IEC standard, ∗∗ : AS standard
<Single type>
Revised 2: Jun., 2008
Model
Cooling capacity (kW) Heating capacity (kW) Pow er supply
Electrical characteristics
Appearance
Outer dimension
Total weight
Heat exchanger
Fan unit Motor (W)
Air filter Controller (Sold separately)
Sound pressure level
Sound power lev el
Connecting pipe Liquid side (mm)
Indoor unit RAV -SM Outdoor unit RAV-SM
Running current (A) Power consumption (kW)
Cooling
Heating
Maximum current (A) Main unit
Ceiling panel (Sold separately)
Main unit Width (mm)
Ceiling panel (Sold separately)
Main unit (kg) Ceiling panel (Sold separately) (kg)
Fan Standard air flow H/M/L (m³/min.)
External static pressure
Under air inlet H/M/L (dB•A) Back air inlet H/M/L (dB•A) Under air inlet H/M/L (dB•A) Back air inlet H/M/L (dB•A)
Power factor (%) EER Energy efficiency class Energy rating ∗∗ Running current (A) Power consumption (kW) Power factor (%) COP Energy efficiency class Energy rating ∗∗
Model Panel color Height (mm)
Depth (mm) Height (mm) Width (mm) Depth (mm)
Standard (at shipment) (Pa) Set up for tap exchange (Pa)
Gas side (mm)
Drain port (mm)
564SDT-E
563AT -E
5.0
5.6
1 phase 230V (220 – 240V) 50Hz
7.94 – 7.28
1.66 95
3.01
B
3.5
7.61 – 6.97
1.59 95
3.52
B
4.0
15.00
Zinc hot dipping steel plate
— —
210 845 645
— — — 22 —
Finned tube
Centrifugal
13.0 / 11.3 / 9.7 60 10
10 / 20 / 35 / 50
Standard filter attached (Long life filter)
RBC-AMT32E, AMS41E, AS21E2
45 / 40 / 36 33 / 31 / 28 60 / 55 / 51 48 / 46 / 43
12.7
6.4
VP25
– 22 –
: IEC standard, ∗∗ : AS standard
Revised 2: Jun., 2008
<Twin type>
Indoor unit 1 RAV-SM 564SDT-E 564SDT -E
Model Indoor unit 2 RAV-SM 564SDT-E 564SDT-E
Outdoor unit RA V-SP 1104AT(Z)(ZG)-E 1102AT(Z)(ZG)-E
Cooling capacity (kW) 10.0 10.0 Heating capacity (kW) 11.2 11.2
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 12.98 –11.90 11.72 – 10.74 Pow er consumption (kW) 2.77 2.50
Cooling Power factor (%) 97 97
EER 3.61 4.00
Electrical characteristics
Heating P ower factor (%) 97 97
Fan Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0 / 11.3 / 9.7 13.0 / 11.3 / 9.7
Motor (W) 60 60
Sound pressure level
Sound power lev el
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Refrigerant pipe
Fan unit Standard air flow volume (m³/min.) 101 125
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 49 / 50 49 / 51 Sound power lev el Cooling/Heating (dB•A) 66 / 67 66 / 68
Under air inlet H/M/L (dB•A) 45 / 40 / 36 45 / 40 / 36 Back air inlet H/M/L (dB•A) 33 / 31 / 28 33 / 31 / 28 Under air inlet H/M/L (dB•A) 60 / 55 / 51 60 / 55 / 51 Back air inlet H/M/L (dB•A) 48 / 46 / 43 48 / 46 / 43
Standard length (m) 7.5 7.5 Min. length (m) 3 5 Max. total length (m) 50 50 Refrigerant charging amount (Charge-less up to 30m)
Height difference
Fan Propeller fan
Motor (W) 100 + 100 63 + 63
Gas side
Liquid side
Energy efficiency class AA Running current (A) 12.51 – 11.47 11.95 – 10.95 Pow er consumption (kW) 2.67 2.55
COP 4.19 4.39 Energy efficiency class AA
Outdoor unit
40g/m (31m to 50m) Outdoor lower (m) 30 30 Outdoor higher (m) 30 30
Main (mm) 15.9 15.9 Sub (mm) 12.7 12.7 Main (mm) 9.5 9.5 Sub (mm) 6.4 6.4
– 23 –
: IEC standard
<Twin type>
Indoor unit 1 RAV-SM 564SDT-E
Model Indoor unit 2 RAV-SM 564SDT-E
Outdoor unit RAV-SM 1103A T-E
Cooling capacity (kW) 10.0 Heating capacity (kW) 11.2
Indoor unit
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Running current (A) 16.47 – 15.09 Pow er consumption (kW) 3.55
Cooling Power factor (%) 98
EER 2.82
Electrical characteristics
Heating P ower factor (%) 98
Fan Centrifugal
Fan unit Standard air flow H/M/L (m³/min.) 13.0 / 11.3 / 9.7
Motor (W) 60
Sound pressure level
Sound power lev el
Po w er supply 1 phase 230V (220 – 240V) 50Hz
Outer dimension
Fan unit Standard air flow volume (m³/min.) 75
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 53 / 54 Sound power lev el Cooling/Heating (dB•A) 70 / 71
Under air inlet H/M/L (dB•A) 45 / 40 / 36 Back air inlet H/M/L (dB•A) 33 / 31 / 28 Under air inlet H/M/L (dB•A) 60 / 55 / 51 Back air inlet H/M/L (dB•A) 48 / 46 / 43
Standard length (m) 7.5 Min. length (m) 5 Max. total length (m) 50
Over 30m
Height difference
Fan Propeller fan
Motor (W) 100
Gas side
Liquid side
Energy efficiency class C Running current (A) 14.56 – 13.35 Pow er consumption (kW) 3.14
COP 3.57 Energy efficiency class B
Outdoor unit
40g/m
(31m to 50m) Outdoor lower (m) 30 Outdoor higher (m) 30
Main (mm) 15.9 Sub (mm) 12.7 Main (mm) 9.5 Sub (mm) 6.4
– 24 –
: IEC standard
1-2. Outdoor Unit
<Super Digital Inverter>
Revised 2: Jun., 2008
Model name Outdoor unit RAV-SP
Power supply
Type
Compressor Motor (kW)
Pole
Refrigerant charged (kg)
Refrigerant control
Standard length (m)
Max. total length (m)
Inter Additional refrigerant charge connecting pipe under long piping connector
Height difference
Height (mm)
Outdoor lower (m)
Outdoor higher (m)
562A T(Z)(ZG)-E 802AT(Z)(ZG)-E 1104AT(Z)(ZG)-E 1404AT(Z)(ZG)-E
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
2 2 3.75 3.75
4444
1.5 2.1 3.1 3.1
Pulse motor valve
7.5 7.5 7.5 7.5
50 50 75 75
20g/m 40g/m 40g/m 40g/m
(21m to 50m) (31m to 50m) (31m to 75m) (31m to 75m)
30 30 30 30
30 30 30 30
795 795 1340 1340
Outer dimension Width (mm)
Depth (mm)
Appearance
Total weight (kg)
Heat exchanger
Fan
Fan unit Standard air flow (m³/min.)
Motor (W)
Gas side (mm)
Connecting pipe
Liquid side (mm)
Sound pressure level Cooling/Heating (dB•A)
Sound power level Cooling/Heating (dB•A)
Outside air temperature, Cooling (°C)
Outside air temperature, Heating (°C)
900 900 900 900
320 320 320 320
Silky shade (Muncel 1Y8.5/0.5)
55 62 93 93
Finned tube
Propeller fan
57 57 101 103
63 63 100 + 100 100 + 100
12.7 15.9 15.9 15.9
6.4 9.5 9.5 9.5
46 / 47 47 / 49 49 / 50 51 / 52
63 / 64 64 / 66 66 / 67 68 / 69
43 to –15°C
15 to –15°C 15 to –20°C
– 25 –
Model name Outdoor unit RAV-SP
404AT(Z)(ZG)-E 454AT(Z)(ZG)-E
Power supply
Type
Compressor Motor (kW)
Pole
Refrigerant charged (kg)
Refrigerant control
Standard length (m)
Max. total length (m)
Inter Additional refrigerant charge connecting pipe under long piping connector
Height difference
Height (mm)
Outer dimension Width (mm)
Outdoor lower (m)
Outdoor higher (m)
1 phase 230V (220 – 240V) 50Hz
(Power exclusive to outdoor is required.)
Hermetic compressor
1.1 1.1
44
1.0 1.0
Pulse motor valve
7.5 7.5
30 30
20g/m (21m to 30m)
30 30
30 30
550 550
780 780
Depth (mm)
Appearance
Total weight (kg)
Heat exchanger
Fan
Fan unit Standard air flow (m³/min.)
Motor (W)
Gas side (mm)
Connecting pipe
Liquid side (mm)
Sound pressure level Cooling/Heating (dB•A)
Sound power level Cooling/Heating (dB•A)
Outside air temperature, Cooling (°C)
Outside air temperature, Heating (°C)
290 290
Silky shade (Muncel 1Y8.5/0.5)
40 40
Finned tube
Propeller fan
40 40
43 43
12.7 12.7
6.4 6.4
45 / 47 45 / 47
62 / 64 62 / 64
43 to –15°C
15 to –15°C
– 26 –
1-3. Operation Characteristic Curve
• Operation characteristic curve <Super Digital Inverter>
RAV-SP1104A T-E, RAV -SP1104ATZ-E, RAV-SP1104ATZG-E RAV-SP1404A T-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
<Cooling> <Heating>
22
20
18
16
14
12
10
SP140
SP140
Current (A)
8
SP110
SP110
6
4
2
0
020406080
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
22
20
SP110
18
16
14
12
10
SP110
SP140
SP140
Current (A)
8
6
4
2
0
020406080
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
RAV-SP404A T-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E
<Cooling> <Heating>
14
12
SP45
10
8
6
Current (A)
4
2
0
0 20 405060708090100
SP45
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
SP40
SP40
16
14
12
10
8
Current (A)
6
4
2
0
0 2040608090100120
SP40
SP40
SP45
SP45
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
Compressor speed (rps)
– 27 –
• Capacity variation ratio according to temperature
RAV-SP404A T-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E RAV-SP1104A T-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E RAV-SP1404A T-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
<Cooling> <Heating>
105
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
32 33 34 35 36 37 38 39
Outdoor temp. (˚C)
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
40
41 42 43
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14-16-18-20 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outdoor temp. (˚C)
– 28 –
2-1. Indoor Unit
RAV-SM564UT-E
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
860 to 910 Ceiling open dimension
15 or more
1000 or more
15 or more
The space that is necessary
for equipping and service
860 to 910 Ceiling open dimension
1000 or more
An obstacle
1000 or more
Take-in port of wiring
44
112
172
Refrigerant pipe connecting port Ø6.4 (Liquid side)
Refrigerant pipe connecting port Ø12.7 (Gas side)
Bottom face of ceiling
129 77
105 74
Ø162
80
240
Electric parts box
408
135105207.5 105 287.5
840 Unit external dimension
77
105 74
397.5
157
106.5
263
72 241.5
950 Panel external dimension
780 Hanging bolt pitch
30
105 337.5
For branch duct knockout square hole Ø150
323
300
Bottom face of ceiling
129
189
Drain pipe connecting port (Meterial : PP)
Hanging bolt M10 or Ø3/8(procured by locally)
74
416.5
690 ± 20 Hanging bolt pitch
45˚
950 Panel external dimension
Drain upstanding size
256
105 77
105
384 351
Bottom face of ceilingIndoor unit
132
129
16.5
Standing
661 or less
Standing
850 or less
For branch duct knockout square hole Ø150
Ceiling panel (sold separately)
105
Ø162
For branch duct knockout square hole Ø150 (2 positions)
For branch duct knockout square hole Ø150
Bottom face of ceiling
269
840 Unit external dimension
362.5 105 372.5
7477
105
5
129
– 29 –
57
28.5
187
64
155
Indoor unit
Z
32
61
Bottom face of ceiling
Bottom face
29
of ceiling
Knockout for simple 0A for Ø100
Bottom face of ceiling
Z view
12
Unit : mm
RAV-SM804UT-E
Take-in port of wiring Bottom face of ceiling
44
112
172
Refrigerant pipe connecting port Ø9.5 (Liquid side)
Refrigerant pipe connecting port Ø15.9 (Gas side)
Bottom face of ceiling
129 77
105 74
Ø162
860 to 910 Ceiling open dimension
157
106.5
72 241.5
Electric parts box
30
77
74 105
397.5
950 Panel external dimension
780 Hanging bolt pitch
105 337.5
263
For branch duct knockout square hole Ø150
323
1000 or more
15 or more
1000 or more
15 or more
1000 or more
The space that is necessary
for equipping and service
860 to 910 Ceiling open dimension
129
189
Drain pipe connecting port (Meterial : PP)
Hanging bolt M10 or Ø3/8 (procured by locally)
300
Bottom face of ceilingIndoor unit
Drain upstanding size
256
132
An obstacle
Standing
661 or less
Standing
850 or less
80
240
105
Ø162
For branch duct knockout square hole Ø150 (2 positions)
For branch duct knockout square hole Ø150
Bottom face of ceiling
408
135105207.5 105 287.5
840 Unit external dimension
269
840 Unit external dimension
362.5 105 372.5
7477
105
5
129
74
416.5
105
690 ± 20 Hanging bolt pitch
Z
45˚
32
61
950 Panel external dimension
57
28.5
187
Indoor unit
384 351
64
155
Bottom face of ceiling
129
For branch duct
105 77
29
Knockout for simple 0A for Ø100
knockout square hole Ø150
16.5
Ceiling panel (sold separately)
Bottom face of ceiling
Z view
– 30 –
Bottom face of ceiling
12
Unit : mm
Loading...
+ 196 hidden pages