Toshiba RAV-SM1403AT-E1 User Manual

Page 1
FILE NO. A11-016
SERVICE MANUAL
(SPLIT TYPE)
OUTDOOR UNIT
< DIGITAL INVERTER>
RAV-SM1103AT-E1 RAV-SM1403AT-E1
R410A
PRINTED IN JAPAN, Jan., 2012 ToMo
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Page 30
Page 31
Page 32
Page 33
Page 34
Page 35
Page 36
Page 37
8. TROUBLESHOOTING
8-1. Summary of Troubleshooting
<Wired remote controller type>
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check
a) The following operations are normal.
1. Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Is not the outdoor unit in standby status though the remote controller reached the setup temperature?
• Does not timer operate during fan operation?
• Is not an overflow error detected on the indoor unit?
• Is not outside high-temperature operation controlled in heating operation?
2. Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3. Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4. ON/OFF operation cannot be performed from remote controller.
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up? (When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.)
• Is not being carried out a test run by operation of the outdoor controller?
b) Did you return the cabling to the initial positions?
c) Are connecting cables of indoor unit and remote controller correct?
2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble Confirmation of check code display Check defective position and parts.
NOTE
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked.
If there is any noise source, change the cables of the remote controller to shield cables.
– 37 –
Page 38
<Wireless remote controller type>
1. Before troubleshooting
1) Required tools/instruments
• + and – screwdrivers, spanners, radio cutting pliers, nippers, etc.
• Tester, thermometer, pressure gauge, etc.
2) Confirmation points before check a) The following operations are normal.
1. Compressor does not operate.
• Is not 3-minutes delay (3 minutes after compressor OFF)?
• Is not the outdoor unit in standby status though the remote controller reached the setup temperature?
• Does not timer operate during fan operation?
• Is not an overflow error detected on the indoor unit?
• Is not outside high-temperature operation controlled in heating operation?
2. Indoor fan does not rotate.
• Does not cool air discharge preventive control work in heating operation?
3) Outdoor fan does not rotate or air volume changes.
• Does not high-temperature release operation control work in heating operation?
• Does not outside low-temperature operation control work in cooling operation?
• Is not defrost operation performed?
4) ON/OFF operation cannot be performed from remote controller.
• Is not forced operation performed?
• Is not the control operation performed from outside/remote side?
• Is not automatic address being set up?
• Is not being carried out a test run by operation of the outdoor controller?
a) Did you return the cabling to the initial positions?
b) Are connecting cables between indoor unit and receiving unit correct?
2. Troubleshooting procedure
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation cannot be performed for maximum approx. 5 minutes after power-ON.)
When a trouble occurred, check the parts along with the following procedure.
Confirmation of lamp display
Trouble
1) Outline of judgment
The primary judgment to check where a trouble occurred in indoor unit or outdoor unit is performed with the following method.
→→
(EX : When 4-way air discharge cassette type wireless remote controller is connected)
Method to judge the erroneous position by flashing indication on the display part of indoor unit (sensors of the receiving unit)
The indoor unit monitors operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
Check defective position and parts.
– 38 –
Page 39
8-2. Troubleshooting
8-2-1. Outline of judgment
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method.
Method to judge the erroneous position by flashing indication on the display part of the indoor unit (sensors of the receiving part)
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.
: Go off, : Go on, : Flash (0.5 sec.)
Lamp indication
Operation
No indication at all
Operation
Flash
Operation
Operation
Timer Ready
Timer Ready
Timer Ready
Flash
Timer Ready
Alternate flash
Check code
E01
E02
E03
E08
E09
E10
E18
E04
P01
P10
P12
Cause of tr oub le occurrence
Power supply OFF or miswiring between receiving unit and indoor unit
Receiving error
Sending error
Communication stop
Duplicated indoor unit No.
Duplicated header units of remote controller
Communication error between CPUs on indoor unit P.C. board
Wire connection error between indoor units, Indoor power OFF (Communication stop between indoor master and follower or between main and sub indoor twin)
Miswiring between indoor unit and outdoor unit or connection erorr (Communication stop between indoor and outdoor units)
Outdoor unit case thermostat work on
Overflow was detected. Indoor DC fan error
Receiving unit
⎬ ⎭
⎫ ⎬
Miswiring or wire connection error
between receiving unit and indoor unit
Setup error
................
Protective device of indoor unit worked.
Comp. overheating Outdoor wiring error
P03
P04
P05
P07
Operation
1: These are representative examples and the check code differs according to the outdoor unit to be combined.
Timer Ready
Alternate flash
P15
P19
P20
P22
P26
P29
P31
Outdoor unit discharge temp. error Case thermostat work on, Power error, High pressure protection
Negative phase detection error
Heat sink overheat error Outdoor unit error
Gas leak detection error
4-way valve system error (Indoor or outdoor unit judged.)
Outdoor unit high pressure protection
Outdoor unit: Outdoor unit fan error
Outdoor unit: Inverter Idc operation
Outdoor unit: Position detection error
Stopped because of error of other indoor unit in a group (Check codes of E03/L03/L07/L08)
⎫ ⎬ ⎭
⎫ ⎬ ⎭
Protective device of
outdoor unit worked.
Protective device of outdoor unit worked.
– 39 –
*1
*1
Page 40
Lamp indication
Operation
Alternate flash
Timer Ready
Check code
F01
F02
P10
Cause of trouble occurrence
Heat exchanger sensor (TCJ) error
Heat exchanger sensor (TC) error Indoor unit sensor error
Heat exchanger sensor (TA) error
⎫ ⎪ ⎬ ⎪ ⎭
Operation
Timer Ready
Alternate flash
Operation
Timer Ready
Simultaneous flash
Operation
Timer Ready
Simultaneous flash
Operation
Timer Ready
Flash
Operation
Timer Ready
Simultaneous flash
F04
F06
F07
F08
F12
F13
F15
F29
F31
H01
H02
H03
L03
L07
L08
L09
Discharge temp. sensor (TD) error
Temp. sensor (TE) error
Temp. sensor (TL) error
Temp. sensor (TO) error Sensor error of outdoor unit ∗1
Temp. sensor (TS) error
Temp. sensor (TH) error
Temp. Sensor miswiring (TE, TS)
⎫ ⎪ ⎪ ⎪ ⎪ ⎪ ⎬ ⎪ ⎪ ⎪ ⎪ ⎪ ⎭
Indoor EEPROM error
Outdoor EEPROM error
Compressor break down Outdoor compressor system error ∗1
Compressor lock
⎫ ⎬ ⎭
Current detection circuit error } Power supply, outdoor P.C. board error
Duplicated header indoor units
There is indoor unit of group connection in individual indoor unit.
Unsetting of group address
Missed setting (Unset indoor capacity)
⎫ ⎪ ⎬
AUTO address
* If group construction and
address are not normal power supply turned on, automatically goes to address setup mode.
Operation
Simultaneous flash
Timer Ready
L10
L20
L30
Unset model type (Service board)
Duplicated indoor central addresses
Outside interlock error
1: These are representative examples and the check code differs according to the outdoor unit to be combined.
8-2-2. Others (Other than Check Code)
Lamp indication
Operation
Simultaneous flash
Operation
Timer Ready
Timer Ready
Alternate flash
Check code
Cause of trouble occurrence
During test run
Disagreement of cool/heat (Automatic cool/heat setting to automatic cool/heat prohibited model, or setting of heating to cooling-only model)
– 40 –
Page 41
SET
T
T
CLSAS
X
E
ON / OFF
UNIT
LOUVER
8-2-3. Monitor Function of Remote Controller Switch
T
U
R
T

Calling of sensor temperature display

<Contents>
Each data of the remote controller, indoor unit and outdoor unit can be understood by calling the service monitor mode from the remote controller.
<Procedure>
1 Push
TES
+ CL buttons simultaneously for 4 seconds to
call the service monitor mode.
The service monitor goes on, the master indoor unit No. is displayed at first and then the temperature of CODE No. displayed.
Ø
2 Push temperature set
the CODE No. of data to be monitored.
The CODE No. list is shown below.
CODE No.
01
02 03
04
07
Indoor unit data
F2
F3
F8
Room temperature (Remote controller)
Indoor suction temperature (TA) Indoor heat exchanger (Coil)
temperature (TCJ) Indoor heat exchanger (Coil)
temperature (TC) Indoor fan revolution frequency Indoor fan calculated operation time Filter sign time Indoor discharge temperature*1 (4-way only)
Data name
TEMP.
buttons and then change
Unit
°C
°C °C
°C
rpm
×100h
×1h
°C
• The CODE No. with marks in the above table are displayed only
on the indoor units of 4 series models and after. (4 series indoor units mean RAV-SM1404UT-E for example.).
• The indoor discharge temperature of CODE No. [F8] is the esti­mated value from TC or TCJ sensor.
Use this value to check discharge temperature at test run.
(A discharge temperature sensor is not provided to this model.)
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.
0000
00
is
0000
CODE No.
60
Outdoor heat exchanger (Coil) temperature (TE)
61
Outside temperature (TO)
62
Compressor discharge temperature (TD)
63
Compressor suction temperature (TS)
65
Heat sink temperature (TH)
6A
Operation current (× 1/10)
6D
70
Outdoor unit data
72 73
Outdoor heat exchanger (Coil) temperature (TL) Compressor operation frequency Outdoor fan revolution frequency (Lower) Outdoor fan revolution frequency (Upper)
F1
Compressor calculated operation time
<RBC-AMT32E>
TIMER SE
TESTRESE
WING/FI
MOD
241 3
<Operation procedure>
1 2 3 4
Returned to usual display
Data name
Unit
°C °C °C °C °C
A
°C
rps rpm rpm
×100h
Ø
3 Push
Each data of the indoor unit and its outdoor units can be monitored.
NIT LOUVE
button to select the indoor unit to be monitored.
Ø
4
Pushing
TES
button returns the status to the usual display.
– 41 –
Page 42
– 42 –
8-2-4. Check Code List (Outdoor)
Central
control
indication
19
18
1d 18 A2 43 18 IC
1F
1d 17
88
1E
21
AF 1C AE 22 1A 14 16
97
97
04
96
99
CF
97,99
96 99 99 46 66
08
Remote controller indication
F04
F06
F08 F07 F12 F13 F15 F31
H01
H02 H03
L10
P03
P04
P05 P07 P15 P20 P22 P26 P29
E01
E02
E03
E04
E08
E09
E10
E18
L03 L07 L08 L09 L30
P19
Sensor lamp part
Block indication
Operation
Timer Ready Flash
  
    
 
   
     

    
  
 


   
 
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
ALT
ALT
ALT ALT ALT ALT ALT SIM
SIM
ALT
ALT
ALT ALT ALT ALT ALT ALT ALT
SIM SIM SIM SIM SIM
ALT
ALT (Alternate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
Representative defective position
Outdoor unit Discharge temp. sensor (TD) error
Outdoor unit Temp. sensor (TE, TS, TL) error
Outdoor unit Outside temp. sensor (TO) error Outdoor unit Temp. sensor (TL) error Outdoor unit Temp. sensor (TS) error Outdoor unit Temp. sensor (TH) error Outdoor unit Misconnection of temp. sensor (TE, TS) Outdoor unit EEPROM error
Outdoor unit Compressor break down
Outdoor unit Compressor lock Outdoor unit Current detection circuit error
Outdoor unit Setting error of service P.C. board type
Outdoor unit Discharge temp. error Outdoor unit
High pressure system error, Power supply voltage error Power supply error Outdoor unit Heat sink overheat Gas leak detection Outdoor unit High pressure system error Outdoor unit Outdoor fan error Outdoor unit Inverter Idc operation Outdoor unit Position detection error No remote controller master unit
Remote controller communication error
Remote controller send error
Regular communication error between indoor and remote controller
Indoor/Outdoor serial error, Case thermostat operation of the outdoor unit occurred
Duplicated indoor addresses
Duplicated main remote controllers
Communication error between CPU Regular communication error between master and
follower indoor units Duplicated indoor master units There is group cable in individual indoor unit. Unset indoor group address Unset indoor capacity Outside error input to indoor unit (Interlock)
4-way valve inverse error
  
Detection
Outdoor
Outdoor
Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor
Outdoor
Outdoor Outdoor
Outdoor
Outdoor
Outdoor
Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Outdoor Remote
controller
Remote
controller
Indoor
Indoor
Indoor
Remote
controller
Indoor
Indoor
Indoor Indoor Indoor Indoor Indoor Indoor
Outdoor
: Go on,  : Flash,  : Go off
Explanation of error contents
Open/Short of discharge temp. sensor was detected. Open/Short of heat exchanger temp. sensor was detected.
Miswiring between TE sensor and TS sensor Open/Short of outside temp. sensor was detected. Open/Short of heat exchanger temp. sensor was detected. Open/Short of suction temp. sensor was detected. Open/Short of heat sink temp. sensor (Board installed) was detected. Misconnection of outdoor heat exchanger temp. sensor and suction temp. sensor was detected. Outdoor P.C. board part (EEPROM) error was detected. When reached min-Hz by current release control, short-circuited current (Idc) after
DC excitation was detected. Compressor lock was detected. Current detection circuit error
When outdoor service P.C. board was used, model type select jumper setting was inappropriate.
Error was detected by discharge temp. release control. When case thermostat worked, error was detected by high release control from indoor/
outdoor heat exchanger temp. sensor. Power supply voltage error Power supply voltage error Abnormal overheat was detected by outdoor heat sink temp. sensor. Abnormal overheat of discharge temp. or suction temp. was detected. Error was detected by high release control from indoor/outdoor heat exchanger temp. sensor. Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit. Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked. Position detection error of compressor motor was detected. Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
No communication from remote controller and network adapter
Serial communication error between indoor and outdoor, Case thermostat operation occurred
Same address as yours was detected. In 2-remote controller control, both were set as master.
(Indoor master unit stops warning and follower unit continues operation.) MCU communication error between main motor and micro computer Regular communication was impossible between master and follower indoor units.
Communication between twin master (Main unit) and follower (sub unit) was impossible. There are multiple master units in a group. When even one group connection indoor unit exists in individual indoor unit Indoor address group was unset. Capacity of indoor unit was unset. Abnormal stop by CN80 outside error input
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up of TE, TS.
Automatic Operation
reset
continuation
×× ××

×× ×× ×× ×× ××
×× ××
×× ××
×× ×× ××
×× ×× ×× ×× ×× ××
——
——
× ×
×
××
×
×× ×× ×× ×× ××
×
Page 43
– 43 –
f
m
e
er
01
02
0
9
01
0
31
0
t
on
ash
T
o
T
M
n
e
r
door u
door f
or
o
r
r
p
r
or
s
on
r
r
r
door
door
r
r
rNetw
r
w
/
r
s
e
r
door
ed.
a
y
)
o
ed.
a
03/L07/L03/L08
g
p
y
o
y
)
l
y
y
er
n
e
n
eset
on
l
ol
on
1
entra
ntr
indicati
1
Remot
ntrll
F F F1 F2 P P1
P
L2
Block indicati
ReadyFl
By unit with warning N
nate): Alternate flashing when there are two flashing LED SIM (Simultaneous): Si
Representative defective positio
Indoor unit Heat Indoor unit Heat exchanger sensor (TC) erro
In
nit In Indoor unit Ovrflow detecti Indoor unit Indoor fn erro
ther indoor unit erro
Error in indoor grou
LAN system commnication erro
I
LAN system commnication err
There are multiple communication adapter
n err
Detecti
Indoo Indoo Indoo In In Indoo Indoo Indoo
k adapte
Net
Netwadapter
Netwadapte
Explanation of errr content
Open/Sho
In Float
Sub remote controller error in a grou
Duplicated indoor address of central control system communicatio
There are multiple communication adapters on remote controller communication lin
t of heat
ACn error w detect
itchw
ommunication error of central control system signa
on the remote controll
(Fn thermal rel
detect
w
with unit N
E
woed.
warnin
: Go on, : Flash, : Go o
tomaticOperatio
r
ed.
ntinuati
Page 44
Error mode detected by indoor unit
n
c
03
04
08
03
07
08
09
30
0
9
31
01
02
0
9
0
8
o
t
d
r
m
door u
door u
.
n
n
d
s
i
r
.
s
y
o
n
,
r
o
o
t
s
f
r
)
f
r
)
f
r
)
o
r
r
CU
n
U
een
d
sub u
s
f
er
p
)
p
)
p
p
p
p
p
p
)
p
)
)
p
)
p
)
p
)
p
)
p
)
p
)
o
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
en
ed
s
)
e
g
.
s
.
)
n
.
e
o
)
)
ces
d.
p
p
.
.
r
door f
.
.
.
.
.
.
.
].
d.
).
d.
)
d.
p
d.
ser
)
door
board.
d.
g.
g.
.
p
n
r
.
ge
.
).
.
en
ed
,
s
.
Operation of diagnostic functio
he
Cause of operati
ir condition
tatus o
onditi
udgment and measure
No communication from remo
E
controller (including wireless) an
ommunication adapte
The serial signal is not output fro
t
nit to in
Defective serial sending circuit o
Defective serial receiving circuit o
indoor P.C. boar
E
Case thermostat operatio * Abnormal overheat of compresso
Duplicated indoor unit addres
E
Duplicated indoor master un
L
There is group wire in individual indoo
L
nit
Unset indoor group addre
L
L
Unset indoor capacit
Abnormal input of outside interl
L
Float switch operatio
P1
Float circuit, Disconnection
Coming-off, Float switch contact erro
Sto
utomatic reset
nit
Sto
utomatic reset
Sto
Sto
Sto
Sto
Sto
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Displ wh
rror is detect
Remote controller LCD display OFF (Disconnection Central remote controller [97] check cod
Inter-unit wire check, correction of miswirin Check outdoor P.C. board. Correct wiring of P.C. board
2. When outdoor unit normally operate Check P.C. board (Indoor receiving / Outdoor sending)
1. Check case thermostat and connector
2. Check gas leak, rechar
3. Check full open of service valve
4. Check PMV (Pulse Motor Valve
5. Check broken pipe
1. Check whether remote controller connection (Group/Individual was changed or not after power supply turned o (Finish of group construction/Address check) * If group construction and address are not normal when th power has been turned on, the mode automatically shifts t address setup mode. (Resetting of address
Set indoor capacity (CODE NoDN) = 11
heck outside devi heck indoor
1. Trouble of drain pum
2. Clogging of drain pum . Check float switch
4. Check indoor P.C. board
boar
Indoor DC fn err
-
ayvae system err
P1
P
E1
E1
After heating operation has started indoor heat exchangers temp. i
own
Own unit stops while waing is outpu to other indoor unit
Coming-off, disconnection or short o
F
indoor heat exchanger temp. senso (TCJ
Coming-off, disconnection or short o
F
indoor heat exchanger temp. senso
TC
Coming-off, disconnection or short o
F1
indoor heat exchanger temp. senso
TA
Indoor EEPRM err
F2
M access erro
ommunication error between indoo
M
ommunication error between fa
driving MCU and main MC
Regular commnication error betw indoor aster and fwer units an
tween main and
osition detection erro
Sto
Sto
utomatic reset
Sto
lloer unit
utomatic reset
Sto
utomatic reset
Sto
utomatic reset
Sto
utomatic reset
Sto
utomatic reset
Sto
utomatic reset
Sto
nit
utomatic reset
Display wh
rror is detect
Displ wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Display wh
rror is detect
Displ wh
rror is detect
er-current protectiv circuit of in
. Indoor fan locked
4. Check indoor P.C. board
1. Check 4-way valve
2. Check 2-way valve and check valve
3. Check indoor heat exchanger (TC/TCJ)
4. Check indoor P.C. board
udgefollower unit while header unit is [E03], [L03], [L07] or [L08
heck indoor
heck indoor heat exchanger tem sensor (TCJ heck indoor
heck indoor heat exchanger tem sensor (TC hec indoor
heck indoor heat exchanger tem heck indoor
heck indoor EEPRM. (including socket in heck in
hec indoor
1. Check remote controller wirin
2. Check indoor power supply wirin . Check indoor P.C. board
boar
boar
boar
boar
boar
n driving unit operated
tion
– 44 –
Page 45
Error mode detected by outdoor unit
The indoor unit check code has been ramified from 4 series and after.
The ramified check code is displayed only when combined with 4-series indoor unit.
(Ex. Combination of RAV-SM1404UT-E with RAV-SM1403AT-E1)
When the indoor unit is 3 series and before, the conventional check code is displayed.
(Ex. Combination of RAV-SM1402CT-E and RAV-SM1403AT-E1)
Operation of diagnostic function
Check code
Indoor unit
before after
3 series 4 series
F04 F04
F06
F07
F06
F12
F15
F08 F08
F13
F31
L10
Cause of operation
Disconnection, short of discharge temp. sensor (TD)
Disconnection, short of outdoor temp. sensor (TE)
Disconnection, short of outdoor temp. sensor (TL)
Disconnection, short of suction temp. sensor (TS)
Miss-mounting of outdoor temp. sensor (TE, TS)
Disconnection, short of outside temp. sensor (TO)
Disconnection, short of heat sink temp. sensor (TH)
Outdoor P.C. EEPROM error
Unset jumper of service P.C. board
Status of
air conditioner
Stop
Stop
Stop
Stop
Stop
Continue
Stop
Stop
Stop
Condition
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
1. Check discharge temp. sensor (TD).
2. Check outdoor P.C. board
1. Check temp. sensor (TE).
2. Check outdoor P.C. board .
1. Check temp. sensor (TL).
2. Check outdoor P.C. board .
1. Check suction temp. sensor (TS).
2. Check outdoor P.C. board.
1. Check temp. sensor (TE, TS).
2. Check outdoor P.C. board.
1. Check outside temp. sensor (TO).
2. Check outdoor P.C. board.
1. Check outdoor P.C. board (IC200 is incorporated in TH sensor.)
1. Check outdoor P.C. board.
1. Outdoor service P.C. board. Check model type setting jumper wire.
L29
H01 H01
H02 H02
P07
P15
P19
Heat sink overheat error Heat sink temp. sensor detected
over specified temperature.
Detection of gas leak Discharge temp. sensor (TD),
Suction temp. sensor (TS) detected temperature over specified temp.
4-way valve inverse error After heating operation has started,
indoor heat exchanger temp. lowers under the specified temp.
After heating operation has started,
outdoor heat exchanger / suction temp. rises over the specified temp.
Compressor break down Although operation has started,
operation frequency decreases and operation stops.
Compressor lock * Over-current detection after
compressor start-up
Stop
Stop
Stop
Stop
Stop
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
1. Check screw tightening between P.C. Board and heat sink and check radiator grease.
2. Check heat sink blast path.
1. Check gas leak, recharge
2. Check full open of service valve.
3. Check PMV (Pulse Motor Valve).
4. Check broken pipe.
5. Check discharge temp. sensor (TD), suction temp. sensor (TS).
1. Check operation of 4-way valve.
2. Check outdoor heat exchanger (TE), suction temp. sensor (TS).
3. Check indoor heat exchanger sensor (TC).
4. Check 4-way valve coil.
5. Check PMV (Pulse Motor Valve).
1. Check power supply voltage. (AC198 to 264V)
2. Overload operation of refrigerating cycle
1. Trouble of compressor (Lock, etc.): Replace compres­sor.
2. Wiring error of compressor (Open phase)
– 45 –
Page 46
Check code
Indoor unit
before after
3 series 4 series
H03
P03 P03
P04
P22 P22
P26 P26
P29 P29
H03
P04
P05
P20
Operation of diagnostic function
Cause of operation
Current detection circuit error
Discharge temp. error Discharge temp. (TD) over
specified value was detected.
High pressure SW system error
Power supply voltage error
High pressure protective operation
• During cooling operation, outdoor temp. sensor (TL) detected temperature over specified temp.
• During heating operation, indoor temp. sensor (TC, TCJ) detected temperature over specified temp.
Outdoor fan system error
Short-circuit error of compressor driving element
Position detection circuit error
Status of
air conditioner
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
1. Check outdoor P.C. board. (AC current detection circuit)
1. Check refrigerating cycle (Gas leak)
2. Trouble of electronic expansion valve
3. Check discharge temp. sensor (TD).
1. Check service valves are fully opened. (Gas side, Liquid side)
2. Check of outdoor fan operation.
3. Check motor error of outdoor fan.
4. Check clogging of outdoor PMV.
5. Check clogging of heat exchanger in indoor/outdoor units.
6. Short-circuit status of suction/discharge air in outdoor unit.
7. Check outdoor P.C. board error.
8. Check fan system error (Cause of air volume drop) at indoor side.
9. Check PMV opening status in indoor unit.
1. Check power supply voltage. AC198 to 264V
1. Check outdoor heat exchanger sensor (TL).
2. Check indoor heat exchanger sensor (TC, TCJ).
3. Check full open of service valve.
4. Check indoor/outdoor fan.
5. Check PMV (Pulse Motor Valve).
6. Check clogging and short circuit of indoor/outdoor heat exchanger.
7. Overcharge of refrigerant. Recharge
1. Check lock of fan motor.
2. Check power supply voltage. AC198 to 264V
3. Check outdoor P.C. board.
1. When performing operation while taking-off compressor wire, P26 error occurs. Check control P.C. board.
2. When performing operation while taking-off compressor wire, an error does not occur. (Compressor rare short)
1. Check control P.C. board.
– 46 –
Page 47
Error mode detected by remote controller or central controller (TCC-LINK)
Operation of diagnostic function
Check code
Not displayed at all (Operation on remote controller is impossible.)
Cause of operation
No communication with master indoor unit
• Remote controller wiring is not correct.
• Power of indoor unit is not turned on.
• Automatic address cannot be completed.
Status of
air conditioner
Stop
Condition
Power supply error of remote controller, Indoor EEPROM error
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Chec k indoor P.C. board.
5. Check indoor EEPROM. (including socket insertion)
Automatic address repeating phenom-
enon generates.
Judgment and measures
E01
2
E02
E09
L20
Central controller
L20
3
Central controller
(Send)
C05
(Receive)
C06
Central controller
P30
No communication with master indoor unit
• Disconnection of inter-unit wire between remote controller and master indoor unit (Detected by remote controller side)
Signal send error to indoor unit (Detected by remote controller side)
There are multiple main remote controllers. (Detected by remote controller side)
Duplicated indoor central addresses on communication of central control system (Detected by indoor/central controller side)
Communication circuit error of central control system (Detected by central controller side)
Indoor Gr sub unit error (Detected by central controller side)
Stop
(Automatic reset)
If center exists,
operation continues.
Stop
(Automatic reset)
If center exists,
operation continues.
Stop
(Sub unit
continues operation.)
Stop
(Automatic reset)
Continues
(By remote controller)
Continuation/Stop
(According
to each case)
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Receiving error from remote controller
1. Check remote controller inter-unit wiring.
2. Check remote controller.
3. Check indoor power wiring.
4. Chec k indoor P.C. board.
Sending error of remote controller
1. Check sending circuit inside of remote controller.
Replace remote controller.
1. In 2-remote controllers (including wireless), there are multiple main units.
Check that there are 1 main remote controller and other sub remote controllers.
1. Check setting of central control system network address. (Network adapter SW01)
2. Check networ k adapter P.C. board.
1. Check communication wire / miswiring
2. Check communication (U3, U4 terminals)
3. Check networ k adapter P.C. board.
4. Check central controller (such as central control remote controller, etc.)
5. Check terminal resistance. (TCC-LINK)
Check the check code of the corresponding unit from remote controller.
2 The check code cannot be displayed by the wired remote controller.
(Usual operation of air conditioner becomes unavailable.) For the wireless models, an error is notified with indication lamp.
3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4),
and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according to the contents.
– 47 –
Page 48
Contents Error Display
When fixations of the errors were overlapped, the latest error is displayed.
When D800 to D804 are slowly flashing or D805 is flashing, push and hold SW800 and SW801 simulta-
neously for 5 seconds or more. The error display changes to the error which is generated.
Check code LED display
No.
TD sensor error
1
2
TE sensor error
TL sensor error
3
4
TO sensor error
5
TS sensor error
6
TH sensor error
Heat exchanger sensor (TE, TS)
7
misconnection
8
EEPROM error
Compressor breakdown
9
Compressor lock
10
Model unset
11
Discharge temp. error
12
13
High-pressure SW error
Current detection circuit error
14
Power supply error
15
Heat sink overheat error
16
Gas leak detection
17
4-way valve reversal error
18
High-pressure protective
19
operation
Fan system error
20
Driving element short circuit
21
Position detection circuit error
22
Others (No fixation)
23
Item
Wired remote controller
series
F04
F06
F06
F08
F06
L29
F06
L29
H01
H02
L29
P03
P04
H03
P04
L29
L29
L29
P04
P22
P26
P29
Indoor unit
after 4
series
F04
F06
F07
F08
F12
F13
F15
F31
H01
H02
L10
P03
P04
H03
P05
P07
P15
P19
P20
P22
P26
P29
Indoor unit
before 3
D800
(Yellow)
D801
(Yellow)
D802
(Yellow)
D803
(Yellow)
D804
(Yellow)
D805
(Green)
: ON
: OFF
: Rapid flash (5 times /sec.)
* The LEDs and switches are located at the top right of the P.C. board of the outdoor unit as shown in the figure on the right.
Service switches s cover SW800, SW801
– 48 –
Electric parts cover
Inspection window through which to check the LED displays
D800 D801 D802 D803 D804 D805
(yellow) (yellow) (yellow) (yellow) (yellow) (green)
Page 49
8-2-5. Diagnostic Procedure for Each Check Code (Outdoor Unit)
1) This section describes the diagnostic method for each check code displayed on the wired remote controller.
2) In some cases, a check code indicates multiple symptoms.
In this case, confirm LED display on the outdoor P.C. board to narrow the contents to be confirmed.
3) The check code on the wired remote controller is displayed only when the same error occurred continu­ously by multiple times while LED of the outdoor P.C. board displays even an error which occurred once.
Therefore the display on the wired remote controller may differ from that of LED.
LED display on outdoor P.C. board
Operation method of the service SW
[Display of error which is generating]
• When even one of D800 to D804 rapid flashing, it indicates that an error occurred. When D800 to D801 indicate slow flashing or when D805 flashes, push and hold SW800 and SW801 for 5 seconds or more simultaneously. The error display ex­changes to display of the error under occurrence at present.
Display of the latest error
• The latest error is displayed by the following action. As the memory is kept, it is confirmed even after the power supply was turned off once. (Except outside air temp. sensor (TO) error)
1) Check D800 to D804 are turned off (or rapid flashing) and D805 is turned on. When D800 to D804 are slowly flashing or D805 flashes, push and hold SW800 and SW801 for 5 seconds or more simultaneously. D800 to D804 will be turned off (or rapid flashing) and D805 flashes.
2) Push and hold SW800 for 5 seconds or more. D804 changes to slow flashing.
3) Push SW800 several times and change LED display (D800 to D804) to [Display of latest error (Including the present error)].
4) Push SW801. The latest error is displayed.
5) When finishing the work, be sure to execute item 1) to return LED to the initial status (Display of error under occurrence).
(No error) (Error occurred)
D800 (Yellow)
D801 (Yellow)
D802 (Yellow)
D803 (Yellow)
D804(Yellow)
D805 (Green)
: ON, { : OFF,  :Rapid flashing (5 times /second)
z
D800 (Yellow)
D801 (Yellow)
D802 (Yellow)
D803 (Yellow)
D804(Yellow)
D805 (Green)
: ON, { : OFF,  :Rapid flashing (5 times / second)
z
z zz zz zz zz
{{
(Example of discharge temp. sensor error)
Display of latest error
(Including the present error)
{
z z z z
– 49 –
Page 50
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[Indoor/Outdoor communication error]
Is setting of group address
of remote controller correct?
YES
Are inner wiring and indoor/outdoor
control wires (1, 2, 3) normal?
YES
Are wiring of terminal blocks (1, 2, 3) normal?
YES
[Case thermostat operation]
NO
NO
NO
Check CODE No. [14].
Correct wiring indoor/outdoor
control wires
Correct wiring of connectors
and terminal blocks.
Check outdoor P.C. board .
Defect Replace
[E04]
Are CN500 connection
and case thermostat normal?
YES
Is cooling/heating operation available
when short-circuiting case thermostat?
YES
Is there no gas leak?
Is it not refrigerant shortage?
YES
Is valve fully opened?
YES
Is PMV normal?
YES
NO
NO
NO
NO
NO
Correct connector.
Case thermostat error Replace
Check outdoor P.C. board .
Defect Replace
Repair defectives position.
Recharge refrigerant.
Open valve fully.
Correct defective position.
Replace defective part.
Check crushed or broken pipe. Defect Correct and Replace
– 50 –
Page 51
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[F04]
[F06]
z z z z
{
z
z z z
{
[Discharge temp. sensor (TD) error]
Is CN601 connection normal?
Is resistance value of TD sensor normal?
YES
• There is a possibility that it is one of the following errors. Confirm LED on outdoor P.C. board to judge which error it is. Heat exchanger temp. sensor (TE) error, Heat exchanger temp. sensor (TL) error,
Suction temp. sensor (TS) error, Miswiring of heat exchanger sensor (TE, TS, TL)
Heat exchanger temp. sensor (TE) error]
Is CN603 connection normal?
Is resistance value of TE sensor normal?
YES
NO
Check outdoor P.C. board .
NO
Check outdoor P.C. board.
Correct connector.
Sensor error Replace
Defect → Replace
Correct connector.
Sensor error Replace
Defect → Replace
[F07]
 
z z z
{
z
z z
{
  
z z
{
 
z z z
{
[Heat exchanger temp. sensor (TL) error] Refer to [F07] column.
[Suction temp. sensor (TS) error] Refer to [F12] column.
[Miswiring of heat exchanger sensor (TE, TS)] Refer to [F15] column.
[Heat exchanger temp. sensor (TL) error]
Is CN605 connection normal?
Is resistance value of TL sensor normal?
YES
NO
Correct connector.
Sensor error Replace
– 51 –
Check outdoor P.C. board.
Defect → Replace
Page 52
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[F08]
[F12]
[F13]
z z
z z
{
z
z z
{
z
 
z z
{
[Outside air temp. sensor (TO) error]
Is CN602 connection normal?
Is resistance value of TO sensor normal?
YES
[Suction temp. sensor (TS) error]
Is CN604 connection normal?
Is resistance value of TS sensor normal?
YES
[Heat sink temp. sensor (TH) error]
Check outdoor P.C. board.
Defect → Replace
NO
Check outdoor P.C. board.
NO
Check outdoor P.C. board.
Correct connector.
Sensor error Replace
Defect Replace
Correct connector.
Sensor error Replace
Defect Replace
[F15]
  
z z
{
[Miswiring of heat exchanger sensor (TE, TS)]
Is mounting status of
TE and TS sensors normal?
YES
Is CN604 connection normal?
Is resistance value of TS sensor normal?
YES
Is CN603 connection normal?
Is resistance value of TE sensor normal?
YES
NO
NO
NO
Correct sensor mounting.
Correct connector.
Sensor error Replace
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
– 52 –
Page 53
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[F31]
z
[EEPROM error]
z
Check outdoor P.C. board.
Defect → Replace
z
{
[H01] [Compressor break down]
 
z
z
{
Is power supply voltage normal?
AC198 to 264V
YES
Is wire connection normal?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
YES
Is it not abnormal overload?
NO
NO
NO
YES
Correct power supply line.
Check wire connection
and correct it.
Correct and clear the cause.
[H02] [Compressor lock]
z z
 
z
{
Is power supply voltage normal?
AC198 to 264V
YES
Is wire connection normal?
Compressor lead
(P.C. board side, Compressor side),
Reactor lead, Power supply lead
YES
Is compressor normal?
NO
Is there no refrigerant stagnation?
YES
Does PMV normally operate?
YES
NO
NO
YES
NO
NO
Check outdoor P.C. board.
Defect Replace
Correct power supply line.
Check wire connection
and correct it.
Check outdoor P.C. board.
Defect Replace
Compressor lock → Replace
Check TE, TS sensors and PMV.
Defect Replace
– 53 –
Check outdoor P.C. board.
Defect Replace
Page 54
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[H03]
[Current detection circuit error]
z
 
z
Check outdoor P.C. board.
Defect → Replace
{
[L10] [Unset model type] : Only when service P.C. board is used
z z z z
{
z z z z
{
Cut jumper line according
to the explanation sheet packaged
with the service P.C. board.
[Discharge temp. error][P03]
Is there no gas leak?
Is refrigerant charge amount adequate?
YES
Is PMV normal?
NO
NO
Repair defective position.
Recharge refrigerant.
Repair defective position.
Replace defective part.
YES
Is it not abnormal overload?
NO
Is CN601 connection normal?
Is resistance value of TD sensor normal?
YES
YES
NO
Correct and clear the cause.
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
– 54 –
Page 55
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
<DCheck and troubleshooting
[P04]
There is a possibility that it is one of the following errors.
Confirm LED on outdoor P.C. board to judge which error it is. (1) high-pressure SW system error, (2) power supply error (Vdc), (3) high-pressure protective operation.
 
z z
{
[High pressure SW system error]
Power supply error (Vdc), High pressure protective operation.
Doesn’t high pressure switch
high pressure switch normal?
Is service valve fully opened?
Reset the power supply and
then do a test operation according
operate?
YES
Are parts of
YES
YES
to the season.
B Cooling operation.
Does cooling outdoor fan
normally operate?
YES YES
NO
Is circuit wiring normal?
NO
NO
B ← Cooling operation C ← Heating operation
NO
Parts check
Defective Replace
Open service valve fully.
Is there no fan breakage
or coming-off?
NO
Check outdoor PC board
Defective Replace
Wiring check,
Correct.
NO
YES
Is there any element
which blocks heat exchanger
of the outdoor unit?
Clogging of heat exchanger
Short circuit
NO
Heating operation
C
Does the heating indoor fan
normally operate?
YES
Is there any element which
blocks indoor heat exchanger?
Filter clogging
Clogging of heat exchanger
Short circuit
NO
Repair defective position.
Connection of connectors,
outdoor P.C. board,
Fan motor, Wiring.
YES
NO NO
YES
blocking element
Are connections of
connectors,capacitors
and fan motor normal?
Elimination of
YES
Elimination of
blocking element
Overcharge of refrigerant/
Clogging/Pipe breakage/
Abnormal overload
defective position.
Repair
Clogging by refrigerant
overcharge/Pipe breakage/
Abnormal overload
Check indoor P.C. board
Defective Replace
– 55 –
Are characteristics
of TC and TCJ sensor
resistance value normal?
YES
TC or TCJ sensor.
NO
Replace
Page 56
Check
code
LED display
Outdoor
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[P04]
[Power supply error (Vdc)] Refer to [P05] column.
z
z
{
[High pressure protective operation] Refer to [P20] column.
z z
 
{
[P05]
[Power supply error (Voltage error)]
z
z
{
[P07] [Heat sink overheat error]
z
 
z
{
Is there no down or up
of power supply voltage?
(AC198 to 264V)
NO
Is there no loosening of
screws of motor drive element of
outdoor P.C. board IC200?
Did not forget to apply radiation grease
to rear side of IC200?
NO
Is not the ventilation flue
of the heat sink blocked?
Is not the fan blocked?
(Short-circuit, etc.)
YES
YES
Confirm electric construction, etc.
Check outdoor P.C. board.
Defect → Replace
YES
NO
Apply radiation grease
to objective part.
Retightening of screws.
Remove blocking matter.
Correct short-circuit.
Check outdoor P.C. board.
Defect → Replace
[P15] [Gas leak detection]
  
z
{
Is refrigerant charge amount adequate?
Is there no gas leak?
YES
Is PMV normal?
YES
Is valve fully opened?
YES
Is there no crushed pipe?
NO
Check temp. sensor.
TD sensor CN601, TS sensor CN604
OK
– 56 –
NO
NO
NO
YES
Error
Repair defective position.
Recharge refrigerant.
Correct defective position.
Replace defective part.
Open valve fully.
Correct and replace piping.
Correct connector.
Sensor error Replace
Check outdoor P.C. board.
Defect Replace
Page 57
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[P19]
z z z
 
{
[4-way valve reversal error]
Is operation of 4-way valve
(Check pipe temp. and etc. in
cooling/heating operation.)
Are temperature sensor normal?
normal?
YES
TE sensor: CN603 TS sensor: CN604
YES
Is refrigerant flow by
PMV normal?
YES
NO
Is power supply to 4-way
valve coil normal?
NO
Replace TE sensor. Replace TS sensor.
NO
Check and
replace of PMV
NO
Replace coil
of 4-way valve.
YES
Is power supply to
4-way valve coil in heating?
YES
Check outdoor
P.C. board.
OK
Check outdoor P.C. board.
Defect → Replace
NO
Error
Are TC sensor and TCJ
sensor normal?
YES
NO
Replace TC sensor
Replace TCJ sensor
Check indoor P.C. board.
Defect Replace
Check 4-way valve.
Defective Replace
– 57 –
Page 58
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[P20]
z z
 
{
[High pressure protective operation]
Is valve fully opened?
YES
Reset the power supply
and then perform test run
matching to the season.
Heating season Heating operation
NO
Is there no problem
on outdoor TL sensor?
(Measurement of resistance value)
YES
Is there no crack or
loosening of outdoor fan?
YES
Does not the outdoor fan
perform abnormal operation?
YES
Open valve fully.
Cooling season Cooling operation
NO
Replace sensor.
NO
Check outdoor fan.
Defect Replace, retightening
NO
Check the same items as
[P22] error.
which interfere heat exchange
• Clogging of heat exchanger
• Short circuit
Check overcharge of refrigerant, clogging of cycle, broken pipe, abnormal overload, etc. Defect → Correct defective position.
Does indoor fan
normally operate?
YES
Is there no element which
interfere heat exchange of indoor unit?
• Clogging of filter
• Clogging of heat exchanger
• Short circuit
NO
Is there no element
of outdoor unit?
NO
Are indoor fan motor
and connector normal?
YES
Are resistance values of indoor TC and TCJ
sensors normal?
YES
YES
YES
Eliminate interfering element.
NO
Repair defective position.
NO
Check indoor P.C. board.
Defect Replace
Eliminate interfering element.
Replace
sensor.
NO
– 58 –
Check overcharge of refrigerant, clogging of cycle, broken pipe, abnormal overload, etc. Defect → Correct defective position.
Page 59
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[P22]
z
z
 
{
[Fan system error]
Is there no problem on power supply voltage?
Does the fan rotate without trouble when rotating
shaft of fan motor with hands during power-OFF?
Is there no problem on coil resistance of fan motor?
Between red and white lead wire : 12 to 20Ω Between white and black lead wire : 12 to 20Ω Between black and red lead wire : 12 to 20Ω
Single operation check for outdoor fan
(AC 198 to 264V)
YES
NO
Replace fan motor.
NO
Check wiring construction.
Ask repair of power supply.
YES
Check outdoor P.C. board.
Defect Replace
A single operation of the outdoor fan can be confirmed by handling the
service switch SW800, SW801. Use this method to check whether there is trouble or not on the fan.
[Method]
(1) Check D800 to D804 are turned off (or rapid flashing) and D805 is
turned on. When D800 to D801 flash slowly or D805 flashes, push and hold SW800 and SW801 for 5 seconds or more simultaneously. In the result, D800 to D804 are turned off (or rapid flashing) and D805 changes from flashing to lighting.
(2) Push and hold SW800 for 5 seconds or more. D804 changes to
slow flashing.
(3) Push SW800 and stop it at LED display of the following “Outdoor fan
single operation”.
Outdoor fan single operation
: OFF
: ON,
D800 D801 D802 D803
Rapid flashing
:
D804
(4) Push SW801 and then stop it at the position where D805 flashes
rapidly.
(5) Push and hold SW801 for 5 seconds or more. In the result, D804
changes to slow flashing, D805 changes to lighting and the fan rotates.
(6) The fan stops when pushing long SW800 and SW801 for 5 seconds
or more simultaneously or when 2 minutes passed.
* If an unknown point generated on the way of the operation, push and
hold SW800 and SW801 for 5 seconds or more simultaneously. You can return to the item (1).
– 59 –
Page 60
Check
code
Outdoor
LED display
(Item without special mention Indicates part of outdoor unit.)
Check and troubleshooting
[P26]
[P29]
 
z
 
{
z z
  
{
[Short-circuit of compressor drive element]
Is there no problem on connection
of compressor lead or reactor?
(Check referring to Wiring diagram.)
YES
The same error does not occur in
operation without compressor lead.
YES
[Position detection circuit error]
Check outdoor P.C. board.
Defect → Replace
NO
NO
Check compressor. (Rear short, etc.)
Correct wiring.
Replace outdoor P.C. board.
Defect Replace
No code
z
  
{
[Other error] Compressor disorder due to sudden change of load, etc.
Although the display of outdoor LED outputs, the unit automatically restarts
and error is not determined.
A code may not appear when an open phase shortage, coming-out of wires or
power relay trouble occurred.
– 60 –
Page 61
Temperature sensor Temperature – Resistance value characteristic table
TA, TC, TCJ, TE, TS, TO sensors
Representative value
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
(Minimum value) (Standard value) (Maximum value)
32.33 33.80 35.30
19.63 20.35 21.09
12.23 12.59 12.95
9.75 10.00 10.25
7.764 7.990 8.218
5.013 5.192 5.375
3.312 3.451 3.594
2.236 2.343 2.454
1.540 1.623 1.709
1.082 1.146 1.213
0.7740 0.8237 0.8761
0.5634 0.6023 0.6434
Resistance value (k
TA, TC, TCJ, TE, TS, TO sensors
40
ΩΩ
Ω)
ΩΩ
TD, TL sensors
Representative value
Temperature
(°C)
0
10
20
25
30
40
50
60
70
80
90
100
(Minimum value) (Standard value) (Maximum value)
150.5 161.3 172.7
92.76 99.05 105.6
58.61 62.36 66.26
47.01 49.93 52.97
37.93 40.22 42.59
25.12 26.55 28.03
17.00 17.92 18.86
11.74 12.34 12.95
8.269 8.668 9.074
5.925 6.195 6.470
4.321 4.507 4.696
3.205 3.336 3.468
Resistance value (k
ΩΩ
Ω)
ΩΩ
30
20
Resistance (kΩ)
10
Output voltage (V)
0
0
10 20 30 40 50 60 70 80 90 100
Temperature (˚C)
TD, TL sensors
200
150
100
20
15
10
5
0
Resistance (kΩ) (50˚C or higher)
Resistance (kΩ) (50˚C or lower)
50
0
10 20 30 40 50 60 70 80 90 100
0
Temperature (˚C)
As TH sensor (Outdoor unit heat sink temp. sensor) is incorporated in the outdoor control P.C. board, the
resistance value cannot be measured.
– 61 –
Page 62
k
k
Table Inspection of outdoor unit main parts
No.
1
Compressor
Parts name
(Model : DA422A3F-12M)
2
Outdoor fan motor (Model : WDF-340-A100-1)
3
4-way valve coil (Cooling/heating switching) (Model : STF-H)
Checking procedure
Measure the resistance value of each winding by using the tester.
Red
Position
Resistance value
Red – White
White Blac
White – Black
0.476 Ω
Black – Red
Under 20°C
Measure the resistance value of each winding by using the tester.
Red
Position
Resistance value
Red – White
White Blac
White – Black
17.3 ± 1.7 Ω
Black – Red
Under 20°C
Measure the resistance value of each winding by using the tester.
Resistance value
Connector : White
1215.3 ± 121.5 Ω
Under 20°C
– 62 –
Page 63
9. SETUP AT LOCAL SITE AND OTHERS
T
T
T
X
E
T
LOUVER
T
T
9-1. Calling of Error History
<Contents>
The error contents in the past can be called.
<Procedure>
SET
1 Push
4 seconds or more to call the service check mode.
Service Check goes on, the CODE No. then the content of the latest alarm is displayed. The number and error contents of the indoor unit in which an error oc­curred are displayed.
TES
+
buttons simultaneously for
0101
01
is displayed, and
0101
2 In order to monitor another error history, push the set
temperature history No. (CODE No.).
TES
0101
01
0101
CODE No.
NOTE : 4 error histories are stored in memory.
3 Pushing
/ buttons to change the error
(Latest) CODE No.
0404
04
0404
(Old)
button returns the display to usual display.
TIMER SE
E
TESTRESE
231
WING/FI
N / OFF
MOD
NI
REQUIREMENT
Do not push CL button, otherwise all the error histories of the
<Operation procedure>
1 2 3
indoor unit are deleted.
Returned to usual display
9-2. Group Control Operation
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller. The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to setting on the remote controller.
<System example>
OUT
IN
1-1
Remote controller
OUT
IN
Master 2-1
OUT
IN
3-1
OUT
IN
4-1
OUT
IN
7-1 Max. 8 units
1. Display range on remote controller The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the master unit is reflected on the remote controller.
2. Address setup Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address. If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the
unit No. is not duplicated with one of another unit.
– 63 –
Page 64

Indoor unit power-ON sequence

Power ON
<Automatic address judgment>
Gr construction check
System start
<Initial communication>
<By feed unit>
Not normal NO
Normal Gr normal
1) There is no duplicated indoor unit address.
2) There is no invalid indoor unit address.
3) Individual unit and master/follower units are not intermingled.
4) Only a unit for individual.
5) A master indoor unit and 1 or more follower indoor units for Gr.
• The unit without power feed waits entirely Waiting status is released by system start
• Reboot when power is fed on the way
3 minutes elapse
YES
Automatic address starts.
(Approx. 1 minute up to finish)
Outdoor model distinction (10 seconds) (Indoor unit) Twin Master/follower distinction (Indoor unit) Gr construction, louver information (Remote controller)
Remote controller operation is available.
(Approx. 50 seconds after power-ON)
<Cautions at test run>
• Power supply/Indoor/Outdoor serial and Gr wiring: OK
• Powers of all indoor units are turned on within 3 minutes.
• Reception time for remote controller operation (After power supply was turned on)
1) When address is OK : Approx. 50 seconds
2) In AUTO address : Approx. 4 to 5 minutes
<Usual regular communication>
Regular communication between indoor units (Every 30 seconds) (Master/Follower) Regular communication on the identical pipe (every 30 seconds) (Twin Master/Follower)
(When the above status changes, immediately communicates.)
(Repetition)
• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot
receive regular communication from the master unit and regular communication on identical pipe within 120 seconds after power was turned on, it reboots (system reset).
The operation starts from judgment of automatic address (Gr construction check) again.
(If the address of the master unit was determined in the previous time, the power fed to the master unit and reboot works, the master unit may change though the indoor unit line address is not changed.)
– 64 –
Page 65
9-3. Outdoor Unit
Various displays and various operations are enabled by push buttons (service) switches and LED on the outdoor control P.C. board.
Service switch (SW800, SW801) operations
LED display
• 4 patterns are provided for LED display.
: ON, : OFF,
• In the initial status of LED display, D805 is ON as the right
figure.
When the initial status does not appear (in case of flashing of D805), LED display can be returned to the initial status by pushing and holding the service switches SW800 and SW801 for 5 seconds or more simultaneously.
9-3-1. Refrigerant recovery control
HFC refrigerant is “Ozone layer destructive coefficient = 0”. However the discharge regulation is established for HFC refrigerant as it is greenhouse gas.
For this Model, a switch is mounted for refrigerant recovery operation (pump down) by the outdoor unit so that this Model can easily react to the environment when it will be reinstalled or scrapped.
: Rapid flashing (5 times/second),
: Slow flashing (Once/second)
LED display: Initial status
D800 D801 D802 D803 D804 D805
LED
(Yellow) OFF or rapid flashing (Yellow) OFF or rapid flashing (Yellow) OFF or rapid flashing (Yellow) OFF or rapid flashing (Yellow) OFF or rapid flashing (Green) ON
[Operating method]
1) Set fan operation to the indoor unit.
2) Check LED display is the initial status. If it is not so, set the initial status.
3) Push and hold SW800 for 5 seconds or more and then check D804 flashes slowly.
4) Push SW800 several times and then stop it at the point where LED display (D800 to D804) is indicated as the following table.
D800 D801 D802 D803 D804
: ON, : OFF,
: Rapid flashing (5 times/second)
5) Push SW801 so that D805 flashes rapidly.
6) Push and hold SW801 for 5 seconds or more. The forced cooling operation star ts if D804 flashes slowly and D805 is turned on. (Max. 10 minutes)
7) After operation for 3 minutes or more, close the valve at liquid side.
8) After recovery of refrigerant, close the valve at gas side.
9) Push and hold SW800 and SW801 for 5 seconds or more simultaneously. The LED returns to the initial status, the cooling operation stops and the indoor fan operation stops.
10)Turn off the power supply.
* If an unknown point generated on the way of the operation, push and hold SW800 and SW801 for 5 seconds
or more simultaneously. You can return to the item 2).
– 65 –
Page 66
9-3-2. Various settings on outdoor unit (Existing piping, power save, cooling-only, etc.)
(1) Service switch setting
Various settings are available by setting service switches.
[Operating method]
1) Check LED display is the initial status. If it is not so, set the initial status.
2) Push and hold SW800 for 5 seconds or more and then check D804 flashes slowly.
3) Push SW800 several times and then stop it at the LED display of function item to be set up.
Function LED display Control contents
Existing pipes setting
Power save setting
Snow-break fan control
Max. frequency change
D800 D801 D802 D803 D804
D800 D801 D802 D803 D804
D800 D801 D802 D803 D804
D800 D801 D802 D803 D804
When the existing piping uses Ø19.1 pipe, this function is validated. In this case, the heating capacity may drop due to outside temp. and indoor temp. in heating time.
This function validates the power save function. This function lowers the compressor frequency. In this case, the Max. capacity drops (Approx. –10%)
This function validates the control to prevent occurrence of motor lock by the accumulated snow entered from clearance of the fan guard or heat exchanger into blast route. Even when the compressor stops, the outdoor fan is operated with W3 when the outside temperature is under 7˚C.
This function is validated if the max. value of compressor frequency is required to lower. It lowers the max. frequency in cooling/heating time. In this case, the max. capacity lowers.
Max. compressor frequency (rps)
Model
Standard status When setting is valid
SM110 SM140
Cool Heat Cool Heat
54.0
54.6 65.4 73.2
48.6 48.6 65.4 65.4
: ON, : OFF,
: Rapid flashing (5 times/second)
4) Push SW801 so that D805 will flash rapidly.
5) Push and hold SW801 for 5 seconds or more. D804 changes to slow flashing, D805 changes to lighting and then various settings are validated.
6) When you want to continue the settings, moreover repeat items from 3) to 5).
7) To invalidate various settings, execute items 1) to 3), push SW801 and then turn off D805.
8) Push and hold SW801 for 5 seconds or more. D804 changes to slow flashing, D805 is turned off and then various settings are invalidated.
* If an unknown point generated on the way of the operation, push and hold SW800 and SW801 for 5 seconds
or more simultaneously. You can return to the item (1).
Confirmation method of various settings
You can confirm that various settings are validated.
1) Check LED displays are in the initial status. If it are not so, return them to the initial status.
2) Push and hold SW800 for 5 seconds or more. D804 changes to slow flashing.
3) Push SW800 several times and then stop it at the point where LED display (D800 to D804) to be checked. If the setting became valid, D804 and D805 flash rapidly. (When the setup was invalid, D804 flashes rapidly and D805 goes off.)
4) Push SW800 and SW801 for 5 seconds or more simultaneously to return LED display to the initial status.
– 66 –
Page 67
In the case to return the setting to one at shipment from factory
When to return the setting to one at shipment from the factory due to reinstallation and so on, the setting can be returned in the following procedure.
1) Check LED display is the initial status. If it is not the initial status, return the setting to the initial status.
2) Push and hold SW800 for 5 seconds or more and then check D804 flashes slowly.
3) Push SW800 several times to make LED display status to “LED display to return the setting at shipment from the factory” in the right table.
4) Push and hold SW801 for 5 seconds or more and then check D804 flashes slowly.
5) Push and hold SW800 and SW801 simultaneously to return the LED display to the initial status.
LED display to return the setting at
shipment from the factory
D800 D801 D802 D803 D804 D805
: ON, : OFF, : Rapid flashing (5 times/second)
(2) Cooling-only setting
By changing setting of the jumper line, the setting can be changed to a cooling-only air conditioner.
Function
Cooling-only
setting
Setting
position
J804 When using the machine as a ooling-only
air conditioner, cut the left jumper line. (There is another method to change the machine to a cooling-only air conditioner; that is to use DN code "0F" of the remote controller.)
Control contents
D800 (Yellow LED) D801 (Yellow LED) D802 (Yellow LED) D803 (Yellow LED) D804 (Yellow LED) D805 (Green LED)
SW800 SW801
J806
J800
J801
J802
J803
J804
– 67 –
Page 68
9-3-3. Service support function (LED display, service switch operating method)
1. LED display switching
1-1. Display switching list
The displayed contents of LED D800 to D805 on the outdoor P.C. board can be switched by handling the service switches SW800 and SW801.
[Operating method]
1) Check LED display is the initial status. If it is not so, set the initial status.
2) Push SW800 several times and then stop it at the point where LED display to be indicated.
LED display Control contents
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
D800 D801 D802 D803 D804 D805
Error display (Error which is occurring at present) The error which is occurring at present is displayed. LED goes off while an error does not occur.
Error display (The latest error: The latest error including this moment) After error status was eliminated, if you want to check the error which occurred before, call this setting and check it. (Even after turning off the power supply once, you can recheck it.) * In the case that an error occurred at present, the same contents as that at present is displayed. * TO sensor error only is not displayed in this setting. (Check setting which is occurring at present.)
Discharge temperature sensor (TD) display Detected value of the discharge temperature (TD) is displayed.
Outdoor heat exchanger temperature sensor (TE) display Detected value of the outdoor heat exchanger temperature sensor (TE) is displayed.
Liquid temperature sensor (TL) display The detected value of the liquid temperature sensor (TL) is displayed.
Suction temperature sensor (TS) display Detected value of the suction temperature sensor (TS) is displayed.
Outside temperature sensor (TO) display Detected value of the outside temperature sensor (TO) is displayed.
Heat sink temperature sensor (TH) display Detected value of the heat sink temperature sensor (TH) is displayed.
Current display The current value which flows to the outdoor unit is displayed.
Compressor operation frequency display The operation frequency of the compressor is displayed.
PMV opening display The opening of PMV (Electronic expansion valve) is displayed.
Indoor suction temperature sensor (TA) display The detected value of the indoor suction temperature sensor (TA) is displayed.
Indoor heat exchanger temperature sensor (TC) display The detected value of the indoor heat exchanger temperature sensor (TC) is displayed.
Indoor heat exchanger temperature (TCJ) display The detected value of the indoor heat exchanger temperature sensor (TCJ) is displayed.
(Refer to A)
(Refer to B)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
(Refer to C)
: ON, : OFF,
: Rapid flashing (5 times/second)
3) Pushing SW901 changes item to one to be displayed.
4) To see other display contents, repeat items 1) to 3).
5) To finish LED display, be sure to execute item 1) to return LED to the initial status (error display of current occurrence) and then finish LED display.
– 68 –
Page 69
1-2. Error display
The error which is occurring at present and the latest error (the latest error data including one which is occur­ring now) can be confirmed by lighting LED D800 to D805 on the outdoor control P.C. board.
A. Error display which occurs at present
LED display
D800 D801 D802 D803 D804 D805
: ON, : OFF,
: Rapid flashing (5 times/second)
Error name
Normal Discharge temp. sensor (TD) error Heat exchanger temp. sensor (TE) error Liquid temp. sensor (TL) error Outside temp. sensor (TO) error Suction temp. sensor (TS) error Heat sink temp. sensor (TH) error Heat exchanger sensor (TE, TS) misconnection EEPROM error Compressor breakdown Compressor lock Model unset Discharge temp. error High-pressure SW error Current detection circuit error Power supply error Heat sink overheat error Gas leak detection 4-way valve reversal error High pressure protective operation Fan system error Driving element short circuit Position detection circuit error Others (No determination)
Wired remote controller
error code
Indoor units
before 3 series
­F04 F06 F06 F08 F06 L29 F06 L29
H01 H02
L29 P03 P04
H03
P04 L29 L29 L29 P04 P22 P26 P29 L31
Indoor units
after 4 series
­F04 F06 F07 F08 F12 F13 F15 F31
H01 H02
L10
P03 P04 H03 P05 P07 P15 P19 P20 P22 P26 P29
L31
B. Error display of the latest (including error which occurs at present) error
LED display
D800 D801 D802 D803 D804 D805
Normal Discharge temp. sensor (TD) error Heat exchanger temp. sensor (TE) error Liquid temp. sensor (TL) error Suction temp. sensor (TS) error Heat sink temp. sensor (TH) error Heat exchanger sensor (TE, TS) misconnection EEPROM error Compressor breakdown Compressor lock Model unset Discharge temp. error High-pressure SW error Current detection circuit error Power supply error Heat sink overheat error Gas leak detection 4-way valve reversal error High pressure protective operation Fan system error Driving element short circuit Position detection circuit error Others (No determination)
Error name
: ON, : OFF,
: Rapid flashing (5 times/second),
– 69 –
: Slow flashing (Once/second)
Page 70
C. Sensor, current, compressor operation frequency, PMV opening display
The values, such as the temperature sensor or the current value, which the controller detects are easily confirmed.
* Temperature sensor: TD, TE, TL, TS, TO, TH, TA, TC, TCJ
LED display
D800 D801 D802 D803 D804 D805
: ON, : OFF,
: Slow flashing (Once/second)
Temp. sensor
(
˚
C)
25 or less
25 ~
– 20 ~ – 15 ~ – 10 ~
– 5 ~
0 ~
5 ~ 10 ~ 15 ~ 20 ~ 25 ~ 30 ~ 35 ~ 40 ~ 45 ~ 50 ~ 55 ~ 60 ~ 65 ~ 70 ~ 75 ~ 80 ~ 85 ~ 90 ~ 95 ~
100 ~ 105 ~ 110 ~ 115 ~
120 or more
Sensor error
Current
(A)
0 ~
1 ~ 2 ~ 3 ~ 4 ~ 5 ~ 6 ~ 7 ~ 8 ~
9 ~ 10 ~ 11 ~ 12 ~ 13 ~ 14 ~ 15 ~ 16 ~ 17 ~ 18 ~ 19 ~ 20 ~ 21 ~ 22 ~ 23 ~ 24 ~ 25 ~ 26 ~ 27 ~
28 ~
29 ~ 30 ~
31 or more
Compressor
frequency (rps)
0 ~
5 ~ 10 ~ 15 ~ 20 ~ 25 ~ 30 ~ 35 ~ 40 ~ 45 ~ 50 ~ 55 ~ 60 ~ 65 ~ 70 ~ 75 ~ 80 ~ 85 ~ 90 ~ 95 ~
100 ~ 105 ~ 110 ~ 115 ~ 120 ~ 125 ~ 130 ~ 135 ~ 140 ~ 145 ~ 150 ~
155 or more
PMV opening
(pls)
0 ~ 19
20 ~ 39 40 ~ 59 60 ~ 79 80 ~ 99
100 ~ 119 120 ~ 139 140 ~ 159 160 ~ 179 180 ~ 199 200 ~ 219 220 ~ 239 240 ~ 259 260 ~ 279 280 ~ 299 300 ~ 319 320 ~ 339
340 ~359 360 ~ 379 380 ~ 399 400 ~ 419
420 ~439 440 ~ 459 460 ~ 479 480 ~ 499
500
– – – – – –
– 70 –
Page 71
2. Special operation for maintenance check (SW800 and SW801 operations)
D800 D801 D802 D803 D804
LED displaySpecial operation
Refrigerant recovery operation
Control contents
The outdoor unit performs cooling operation. As the indoor unit does not operate by this operation only, carry out the fan operation beforehand. (Refer to 9-3-1.)
D800 D801 D802 D803 D804
PMV full open operation
Open PMV (Electronic expansion valve) fully. Execute the following item 6) or the control returns to normal operation after 2 minutes. (Refer Note 1)
D800 D801 D802 D803 D804
PMV full close operation
Close PMV (Electronic expansion valve) completely. Execute the following item 6) or the control returns to normal operation after 2 minutes. (Refer Note 1)
D800 D801 D802 D803 D804
PMV middle opening operation
Open PMV (Electronic expansion valve) to middle position (250 pulses). Execute the following item 6) or the control returns to normal operation after 2 minutes. (Refer Note 1)
D800 D801 D802 D803 D804
Indoor heating trial operation command
Carry out a trial heating operation. The operation returns to the normal control by executing the following item 6). (Refer Note 2)
D800 D801 D802 D803 D804
Indoor cooling trial operation command
Carry out a trial cooling operation. The operation returns to the normal control by executing the following item 6). (Refer Note 2)
D800 D801 D802 D803 D804
Fan motor forced operation
Operate the fan motor forcedly. Execute the following item 6) or the control returns to normal operation after 2 minutes. (Refer Note 1)
D800 D801 D802 D803 D804
4-way valve relay operation
Turn on 4-way valve power relay (CN700) Execute the following item 6) or the control returns to normal operation after 2 minutes. (Refer Note 1)
The following special operations for maintenance check can be performed by handling the service switches SW800 and SW801.
[Operating method]
1) Check LED display is the initial status. If it is not so, set the initial status.
2) Push and hold SW800 for 5 seconds or more and then check D804 flashes slowly.
3) Push SW800 and then stop it at the LED display of the function item to be set.
(Note 1) Although these special operations are available even operating time, basically carry out these
(Note 2) Indoor trial cooling operation request / Indoor trial heating operation request
4) Push SW801 and then stop it at point where D805 becomes rapid flashing.
5) Push and hold SW801 for 5 seconds or more. D804 changes to slow flashing, D805 changes lighting and then the special operation becomes valid.
6) To invalidate various settings, push and hold SW800 and SW801 for 5 seconds or more simultaneously. D800 to D804 go off (or rapid flashing), D805 goes on (Initial status: Display of error which is occurring at present), and then the special operation becomes invalid (normal control).
* If an unknown point generated on the way of the operation, push and hold SW800 and SW801 for 5 seconds
or more simultaneously. You can return to the item 1).
: ON, : OFF,
: Rapid flashing (5 times/second)
operations while the machine stops. If carrying out these operations, the pressure may change suddenly and a danger may grow.
Cooling/heating trial operations are available from the outdoor unit only in combination with the following indoor units.
Trial operation is available: Indoor units after 4 series (RAV-SM
Trial operation is unavailable: Indoor units except the above units or in case that the indoor units except the above units are included at twin connection.
Note) The forced trial operation in this setting cannot be cleared by the indoor remote controller.
Be sure to clear it by operation of the outdoor unit (6 below).
– 71 –
****4*
T-E)
Page 72
9-4. Applicable Control of Outdoor unit
The following controls are enabled by connecting the part “Application control kit” (TCB-PCOS1E2) sold separately.
(1) Power peak cut control
* The capacity of the outdoor unit is saved by the Demand signal from outside and corresponds to the
temporary peak cut.
* The capacity save is switched to 3 stages, 75%, 50% and operation stop.
(2) Night operation (Sound reduction) * Input a timer on the market (Arranged at site). The capacity is lowered regardless of load and the operation
noise is reduced until 45dB. However the normal control is carried out if the outside temperature (TO sensor value) is 40°C or more.
(3) Compressor operation output
* When the compressor drives, turn on the contact output of no voltage.
– 72 –
Page 73
10. ADDRESS SETUP
10-1. Address Setup Procedure
When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while automatic address works. (Approx. 4 to 5 minutes)
Setup of line address of outdoor unit, indoor unit address, and group address
Completion of cabling work
Do you arbitrarily set the
indoor unit address?
YES
Connect one remote controller with one indoor unit (1 : 1) tentatively with communication cable.
Turn on power of outdoor unit.
Set to all indoor units one by one.
(MANUAL)
NO
NO
Is group control performed?
YES
Do you change setting after
automatic setting at the first time?
YES
Turn on power of outdoor unit.
After completion of address setup, change is to arbitral
( )
address/group manually.
NO
(To AUTO address mode)
Setup of automatic address finishes within
( )
4 to 5 minutes.
Is refrigerant line 1 line?
Turn on power of outdoor unit.
YES
END
• When the following addresses are not stored in the neutral memory (IC503) on the indoor P.C. board, a test
run operation cannot be performed. (Unfixed data at shipment from factory)
Line address
Indoor unit address
Group address
Item code
12
13
14
Data at shipment
0099
0099
0099
Setup data range
0001 (No. 1 unit) to 0064 (No. 64 unit)
0001 (No. 1 unit) to 0064 (No. 64 unit) Max. value of indoor units in the identical refrigerant line
0000 : Individual (Indoor units which are not controlled in a group) 0001 : Master unit (1 indoor unit in group control) 0002 : Sub unit (Indoor units other than master unit in group control)
– 73 –
Page 74
10-2. Address Setup & Group Control
<Terminology>
Indoor unit No. : N - n = Outdoor unit line address N (Max. 30) - Indoor unit address n (Max. 64) Group address : 0 = Single (Not group control)
1 = Master unit in group control 2 = Sub unit in group control
Master unit (= 1) : The representative of multiple indoor units in group operation sends/receives signals to/from
the remote controllers and sub indoor units. ( It has no relation with an indoor unit which communicates serially with the outdoor units.)
The operation mode and setup temperature range are displayed on the remote controller LCD. (Except air direction adjustment of louver)
Sub unit (= 2) : Indoor units other than master unit in group operation
Basically, sub units do not send/receive signals to/from the remote controllers. (Except errors and response to demand of service data)
Header unit (Representative unit) (Master Twin)
: This unit communicates with the indoor unit (follower) which serial-communicates with the
outdoor units and sends/receives signal (Command from compressor) to/from the outdoor units as the representative of the cycle control in the indoor units of the identical line ad­dress within the minimum unit which configures one of the refrigerating cycles of Twin.
Follower unit (Subordinate unit) (Sub Twin)
: Indoor units excluding the header unit in Twin
This unit communicates with (Header) indoor unit in the identical line address and performs control synchronized with (Header) indoor unit.
This unit does not perform the signal send/receive operation with the outdoor units. : No judgment for serial signal error.
10-2-1. System Configuration
1. Single
Outdoor
Indoor (Master/Header)
Remote controller
3. Single group operation
2-1
Sub/Header
1-1
Individual
1-1
Sub/Header
4-1
Master/Header
2. Twin
Sub/Header
Master/Header
3-1
1-1
1-2
Sub/Follower
8-1
Sub/Header
– 74 –
Page 75
10-2-2. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit)
1) Single
1-1
Individual
(Master/Sub)
2) Group operation (Twin, Triple operation)
(Multiple outdoor units = Miltiple indoor units only with serial communication)
2-1
Sub/Header
1-1
Sub/Header
1-2
Sub/Follower
3-1
Master/Header
3-2
Sub/Follower
Only turning on source power supply (Automatic completion)
3-3
Sub/Follower
• Header unit: The header unit receives the indoor unit data (thermo status) of the follower (Without identical line address & indoor/outdoor serial) and then finally controls the outdoor compressor matching with its own thermo status.
The header unit sends this command information to the follower unit.
• Follower unit: The follower unit receives the indoor unit data from the header (With identical line address & indoor/outdoor serial) and then performs the thermo operation synchronized with the header unit.
The follower unit sends own thermo ON/OFF demand to the header unit.
(Example)
No. 1-1 header unit sends/receives signal to/from No. 1-2 and No. 1-3 follower units. (It is not influenced by the line 2 or 3 address indoor unit.)
– 75 –
Page 76
10-2-3. Automatic Address Example from Unset Address (No miswiring)
1. Standard (One outdoor unit)
1) Single 2) Twin
(1-1) (1-2)
1-1
Individual
(Master/Header)
1-2
Master/Header
Only turning on source power supply (Automatic completion)
2. Group operation (Multiple outdoor units = Multiple indoor units with serial communication only, without twin)
1-1
Sub/Follower
2-1
Sub/Header
Only turning on source power supply (Automatic completion)
3. Multiple groups operation
Single Twin
2-1
Sub/Header
1-1
Sub/Header
1-1
Sub/Header
3-1
Master/Header
2-3
Master/Follower
8-1
Sub/Header
(Max. : 8 units)
2-1
1-1 1-2
Change is necessary
Manually change addresses of the multiple follower units simultaneously from the remote controller.
– 76 –
Page 77
10-3. Remote Controller Wiring
• Strip off approx. 9 mm the wire to be connected.
• For single system, use non polarity, 2 core wire is
used for wiring of the remote controller. (0.5 mm² to 2.0 mm² wires)
• For the synchronous twin, triple system, use
2-conre shield wire (Vinyl cord for microphone 0.5 to 2.0 mm²) to conform to the EMC standard.
Single system
Remote controller
Remote controller wiring
A B
Indoor side
Indoor/Outdoor connecting wires
Outdoor side
1
223
1
3
L N
Power supply
Wiring diagram
Terminal block for remote controller wiring of indoor unit
A B
Remote controller wire (Procured locally)
For details of wiring/installation of the remote
controller, refer to the Installation Manual enclosed with the remote controller.
Terminal block
A
Remote controller
B
unit
Simultaneous twin system
Remote controller
Remote controller wiring
A B
Indoor side
Indoor/Outdoor connecting wires
Outdoor side
1
223
1
3
L N
Power supply
10-4. Address Setup (Manual setting from remote controller)
In case that addresses of the indoor units will be determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.
Line address → 1
Indoor unit address → 1
Group address → 1
(Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe)
Outdoor
1 23
1 2 3
Indoor
A B
A B
Remote controller
For the above example, perform setting by connecting singly the wired remote controller without remote controller inter-unit cable.
Group address Individual : 0000 Master unit : 0001 Sub unit : 0002
1 2 3
Indoor
A B
1 2 2
Outdoor
1 2 3
1 2 3
Indoor
A B
2 1 2
In case of group control
1 2 3
Indoor
A B
2 2 2
– 77 –
Page 78
1 Push
T
T
R
R
2 (
3 Using timer time / buttons, set the line address. 4 Push 5 (
6 Using timer time / buttons, set 1 to the line address. 7 Push 8 (
9 Using timer time / buttons, set 10 Push 11 Push
SET
+ CL +
for 4 seconds or more.
Line address)
Using the temperature setup
1212
12
to the CODE No.
set
1212
SET
button. (OK when display goes on.)
Indoor unit address)
Using the temperature setup
SET
button. (OK when display goes on.)
Group address)
Using the temperature setup
SET
TES
Setup completes. (The status returns to the usual stop status.)
TES
buttons simultaneously
/ buttons,
/ buttons, set
/ buttons, set
00000000
0000
to Individual,
00000000
button. (OK when display goes on.) button.
1313
13
to the CODE No.
1313
1414
14
to the CODE No.
1414
00010001
0001
00010001
to Master unit, and
00020002
0002
to sub unit.
00020002
10-5. Confirmation of Indoor Unit No. Position
1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1 Push 2 Push
Unit No. (It disappears after several seconds.)
The displayed unit No. indicate line address and indoor unit address.
(When other indoor units are connected to the identical remote controller (Group control unit), other unit numbers are also displayed every pushing
NIT LOUVE
ON / OFF
NIT LOUVE
button.
button if the unit stops.
button.
1-11-1
1-1
is displayed on LCD.
1-11-1
– 78 –
Page 79
2. To know the position of indoor unit body by address
T
R
T
• To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are successively displayed, and fan, louver, and drain pump of the corresponding indoor unit are turned on. (Follow to the procedure during operation)
1 Push
VENT
and
TES
buttons simultaneously for
4 seconds or more.
• Unit No. is displayed.
• Fans and louvers of all the indoor units in the group control operate.
2 Every pushing
NIT LOUVE
button, the unit numbers
in the group control are successively displayed.
• The unit No. displayed at the first time indicates the master unit address.
• Fan and louver of the selected indoor unit only operate.
3 Push
TES
button to finish the procedure.
All the indoor units in the group control stop.
<Maintenance/Check list>
Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner.
It is also recommended to maintain the units once a year regularly when operating the air conditioner for a long time.
Check periodically signs of rust or scratches, etc. on coating of the outdoor units. Repair the defective position or apply the rust resisting paint if necessary.
If an indoor unit operates for approx. 8 hours or more per day, usually it is necessary to clean the indoor/ outdoor units once three months at least.
These cleaning and maintenance should be carried out by a qualified dealer. Although the customer has to pay the charge for the maintenance, the life of the unit can be prolonged.
Failure to clean the indoor/outdoor units regularly will cause shortage of capacity, freezing, water leakage or trouble on the compressor.
Part name
Heat exchanger
Fan motor
Filter
Fan
Suction/ Discharge grille
Drain pan
Face panel, Louver
External appearance
Object
Indoor Outdoor
{{ {{
{
{{
{
{
{
{
Contents of check
• Blocking with dust, damage check
• Audibility for sound
• Visual check for dirt and breakage
• Visual check for swing and balance
• Check adhesion of dust and external appearance.
• Visual check for dirt and scratch
• Check blocking by dust and dirt of drain water.
• Check dirt and scratch.
• Check rust and pealing of insulator
• Check pealing and floating of coating film
Contents of maintenance
• Clean it when blocking is found.
• When abnormal sound is heard
• Clean with water if dirty
• Replace if any breakage
• Replace fan when swinging or balance is remarkably poor.
• If a large dust adheres, clean it with brush or water.
• Repair or replace it if deformation or damage is found.
• Clean drain pan, Inclination check
• Cleaning/Coating with repair painting
• Coating with repair painting
– 79 –
Page 80
Model name J 806 J 800 J 801 J 802 J 803 J 804
11. REPLACEMENT OF THE SERVICE P.C. BOARD MCC-1630
1. Removing the P.C. board
(1) Turn off the power supply of the outdoor unit and allow at least 3 minute for the capacitor to discharge.
Confirm that the light of the LED (D800 to D805) fades away.
(2) Remove all the connectors and fast-on terminals connected to the P.C.board.
(Remove the connectors and fast-on terminals by pulling the connector body. Do not pull the wire).
(3) Remove all the screws which secures the P.C.board.
(These screws are to be reused after procedure.)
(4) Remove the P.C.board from the BOX.
2. Setting the jumper wires
Modelswitching (J800 to J804, J806)
Since this service P.C. board is available for several models, cut the jumper wires according to the
following table. If they are not cut correctly, an error code “L10 or E04”h appears on the remote controller and the operation of the air conditioner is disabled.
Factory setting (default) - - - - - - RAV-SM1103AT-E1 - Cut - - - ­RAV-SM1403AT-E1 - - Cut - - -
J806
J800
3. Installing the P.C. board
(1) Apply thermal grease to the back (heat sink contacting side) of devices IC200 and IC300.
(2) Reuse the insulating sheet. When a small amount of thermal grease is applied to the back of the
insulating sheet, it adheres temporarily to the heat sink, which makes it easy to attach the insulating
sheet. (3) Reuse the sub heat sink. Applying thermal grease to the surface and the back of the sub heat sink.
(4) Insert the P.C. board, align the holes of the insulating sheets, semiconductor devices, and heat sinks,
and then secure them with screws.
Tighten the screw (A) at the end. (5) Connect the lead wires according to the wiring diagram sticked on the backside of the panel .
screw (A)
J801
J802
J803
J804
Apply thermal grease to the back (heat sink contacting side) of IC200 and IC300.
Reuse the insulating sheet. Applying thermal grease to the back of the insulating sheet makes it easy to attach the insulation sheet.
– 80 –
Reuse the sub heat sink. Applying thermal grease to the surface and the back of the sub heat sink.
Page 81
12. HOW TO EXCHANGE COMPRESSOR
12-1. Exchanging Procedure of Compressor (Outline)
START
Has refrigerant recovery work been done?
YES
Turn off the leakage breaker.
Remove the defective compressor.
Mount a service compressor.
Leakage check
Vacuuming
Charge the refrigerant.
END
NO
Open PMV forcedly and then recover refrigerant using a refrigerant recovery unit.
Never recover the refrigerant to the outdoor unit. For the refrigerant recovery work during reinstallation
of repair work, be sure to use the refrigerant recovery unit. Recovery of refrigerant to the outdoor unit is unavailable;
otherwise a serious accident such as explosion or injury may be caused.
12-2. Exchange of Compressor
For exchange of compressors, refer to (11) Compressor in Section 13. Detachments.
– 81 –
Page 82
RAV-SM1103AT-E1, RAV-SM1403AT-E1
13. DETACHMENTS
No.cPart name
Common procedure
Procedure
CAUTION
Never forget to put on the gloves at working time, otherwise an injury will be caused by the parts, etc.
1. Detachment
1) Stop operation of the air conditioner, and also turn off switch of the breaker.
2) Remove the front cabinet. (M4 (Hexagon) x 10, 3 pcs.)
• After taking off screws, remove the front
cabinet by pulling it downward.
3) Remove the cover of the terminal block. (M4 x 8, 2 pcs.)
4) Disconnect the connecting cables and power cord from the terminals and cord clamp.
5) Remove the roof plate. (M4 (Hexagon) x 10, 6 pcs.)
Front cabinet
Screw
Remarks
Screw
2. Attachment
1) Attach the roof plate. (M4 (Hexagon) x 10, 6 pcs.)
2) Connect the connecting cable and power cord at the terminal and fix them with cord clamp.
3) Attach the cover of the terminal block. (M4 x 8, 2 pcs.)
CAUTION
Using bundling band sold at a market, be sure to fix the power cables and indoor/outdoor connecting cables along the inter-unit cable so that they do not come to contact with the compressor, valves and cables at gas side, and the discharge pipe.
4) Attach the front cabinet. (M4 (Hexagon) x 10, 3 pcs.)
Cover of the terminal block
Roof plate
– 82 –
Page 83
No.
d
Part name
Discharge port cabinet
Procedure
1. Detachment
1) Perform work of item 1 of c.
2) Remove screws (M4 x 8, 3 pcs.) of discharge port cabinet for partition plate.
3) Remove screws (M4 (Hexagon) x 10, 2 pcs.) of discharge port cabinet for the bottom plate.
4) Remove screw (M4 x 8, 1 pc.) of dis­charge port cabinet for the end plate of the heat exchanger.
5) Remove the screws (M4 x 8, 2pcs) of discharge port cabinet and motor base.
6) Remove screws (M4 (Hexagon) x 10, 2 pcs.) of discharge port cabinet for the fin guard.
2. Attachment
1) Put the upper left side of the discharge port cabinet on the end plate of the heat exchanger, and then fix it with screw.
(M4 x 8, 1 pc.)
2) Attach the removed screws to the original positions.
Remarks
Fin guard
Bottom plate
e
Side cabinet
1) Perform work of item 1 of c.
2) Remove screws fixing the inverter and the side cabinet. (M4 x 8, 2 pcs.)
3) Remove screws of the side cabinet and the valve support plate. (M4 x 8, 2 pcs.)
4) Remove screw of the side cabinet and the piping panel (Rear). (M4 (Hexagon) x 10, 1 pc.)
5) Remove screw of the side cabinet and the bottom plate. (M4 (Hexagon) x 10, 1 pc.)
6) Remove screw of the side cabinet and the fin guard (Heat exchanger). (M4 (Hexagon) x 10, 2 pcs.)
End plate of the heat exchanger
Valve support plate
Inverter assembly
Discharge port cabinet
Side cabinet
Side cabinet
– 83 –
Valve support plate
Piping panel (Rear)
Page 84
No. Part name Procedure Remarks
f
Inverter assembly
1) Perform works of 1 of c,1 of d ,and e.
2) Remove the front cover. (M4 x 8, 3 pcs.)
3) Remove the inverter fixing plate. (M4 x 8, 3 pcs.)
4) Remove connectors connected to other parts from P.C. board.
CN601: TD sensor (3P, White) CN602: TO sensor (2P, Yellow) CN603: TE sensor (2P, White) CN604: TS sensor (3P, White) CN605: TL sensor (2P, White) CN300: Outdoor fan (3P, White) CN500: Case thermo (2P, Blue) CN700: 4-way valve coil (3P, Yellow) CN701: PMV coil (6P, White) CN501: High-pressure SW (3P, Green)
* Unlock the locks of the housing part and
then remove the connectors.
5) Remove the compressor lead connectors.
6) Remove the relay connector of the reactor lead attached to the partition plate side.
7) Cut bunding band which fixed the various lead wires to the inverter assembly.
8) Pull up upward the hook for the partition plate (Back left) so as to remove it.
Inverter assembly
Front cover
Inverter fixing plate
Inverter assembly
* Caution for attachment of the inverter
assembly
When attaching the inverter assembly to the partition plate surely attach the hook for the partition plate (Back left).
Reactor (Partition plate side)
Relay connector
Complessor lead connector
Wire clamp
There is a hook for the partition board at the rear side.
Case thermo lead
4way valve
PMV
– 84 –
Page 85
No. Part name Procedure Remarks
Outdoor unit
g
control P.C. board
1) Perform works of 1 of c, 2) of f.
2) Remove the guide. (M4 x 8, 1 pc.)
3) Remove connectors and lead wires which are connected to the other parts from the cycle P.C. board.
1. Connectors (On P.C. board)
CN601: TD sensor (3P, White) CN602: TO sensor (2P, Yellow) CN603: TE sensor (2P, White) CN604: TS sensor (3P, White) CN605: TL sensor (2P, White) CN300: Outdoor fan (3P, White) CN500: Case thermo (2P, Blue) CN700: 4-way valve (3P, Yellow) CN701: PMV coil (6P, White) CN501: High-pressure SW (3P, Green)
2. Connectors (Relay connection)
Reactor lead wire (White) Reactor lead wire (Gray) Compressor lead wire (Red, White, Black)
* Unlock the locks of the housing part and
then remove the connectors.
4) Remove the Faston terminal (White (3)) on the indoor/outdoor connection terminal block.
5) Remove the earth wire (Black) which is fixed to the terminal fixed plate with screw (1 pc.).
6) Remove the power supply connection lead wire from the power supply terminal block. (L (Red), N (White)
7) Remove screws (4 pcs.) which fixed the heat sink and IPM and screws (3 pcs.) which fixed the heat sink and rectifier.
8) Remove screws which fixed P.C. board and remove board fixed claws (2 posi­tions) to remove P.C. board.
9) Attach a new P.C. board.
Guide
Indoor/outdoor connection terminal block
To remove the guide, pull it toward arrow direction so that the force is not applied to this switch.
Earth wire
Guide fixing screw
Power supply terminal block
– 85 –
Page 86
No.hPart name
Flange nut
Loosened by turning clockwise
Fan motor
Procedure
Remarks
Fan motor
1) Perform works of items 1 of c, 1 of d,
2) Remove the flange nut fixing the fan motor and the propeller fan.
• Loosen the flange nut by turning clock-
wise. (To tighten the flange nut, turn it counterclockwise.)
3) Remove the propeller fan.
4) Remove the lead wire from the hook fixing the fan motor lead wires on the motor base. (Three positions)
5) Disconnect the connector for fan motor from the inverter.
6) Remove the fixing screws (4 pcs.) while holding by hands so that the fan motor does not fall.
*(Note)
Tighten the flange nut with torque 4.9N•m (50kgf/cm).
Be careful that the reactor does not come to contact with the fan motor lead at the rear side of the inverter assembly.
CAUTION
Using a bundling band on the market, be sure to fix the fan motor lead wire to the motor base so that it does not come to contact with the propeller fan.
Flange nut
Flange nut
Motor base
Loosened by
Loosened by
turning clockwise
turning clockwise
Fan motor
Fan motor
Fix with bundling band
– 86 –
Page 87
No.iPart name
Piping panel (Front)
Case thermo
Remove (Discharge pipe)
Procedure
Remarks
Compressor
1) Evacuate refrigerant gas.
2) Perform works of items 1 of c, 1 of d, e and f.
3) Remove screws which fixes the piping panel (Front) and the bottom plate.
(M4 (Hexagon) x 10, 2 pcs.)
4) Remove screw of the piping panel (Front) and the piping panel (Rear).
(M4 (Hexagon) x 10, 1 pc.)
5) Remove screws fixing the partition plate to the valve support plate.(M4 x 8, 2 pcs.)
6) Remove the valve support plate. (M6 x 4 pcs.)
7) Remove screws of the partition plate and the bottom plate. (M4 x 8, 1 pc.)
8) Remove screws of the partition plate and the heat exchanger (M4 x 8, 2 pcs.)
9) Remove the noise-insulator.
10) Remove the terminal covers of the com-
pressor, and disconnect lead wires of the compressor and the compressor thermo assembly from the terminal.
11) Remove pipes connected to the compres-
sor with a burner.
Screw
Partition plate
Piping panel (Front)
Partition plate
Valve support plate
CAUTION
Pay attention to that flame does not involve 4­way valve or PMV. (If doing so, a malfunction may be caused.)
12) Pull the refrigerating cycle upward.
13) Remove bolt fixing the compressor on the
bottom plate. (3 pcs.)
14) Pull the compressor toward you.
CAUTION
When reconnecting the lead wires to the compressor terminals after replacement of the compressor, be sure to caulk the Faston terminal without loosening.
Valve support plate
Sensor pipe cover
Case thermo
Valve
Valve support plate
Compressor lead wire
Case thermo
Remove (Suction pipe)
– 87 –
Remove (Discharge pipe)
Compressor bolt (3 pcs.)
Page 88
No. Part name Procedure Remarks
Dent part
Pulse Modulating
j
Valve (PMV) coil
1. Detachment
1) Perform works of items 1 of c and e.
Positioning projection
PMV main unit
2) Remove the coil from PMV body while pulling it upward.
2. Attachment
1) Match the positioning extrusion of the coil surely to the concavity of PMV body to fix it.
PMV coil
Dent part
Dent part
k
Reactor
1. Detachment
1) Perform works of items of 1 of c and 3) of
f.
2) Remove the reactor lead wire from the cord clamp which fixes lead wires.
3) Remove screw which fixes the reactor. Partition plate side: M4 x 8, 1 pc. Inverter rear side: M4 x 8, 2 pcs.
4) Pull off the reactor upward to remove the reactor.
CAUTION
As the reactor body becomes high temperature in this Model, the lead wires are fixed with the cord clamp so that the reactor lead does not come to contact with the main body. When replacing the reactor or returning the inverter assembly to the original position after removing it, be sure to fix the lead wires with the cord clamp so that the main body does not come to contact to the lead.
Screw
Cord clamp
Do not pull the lead wire strongly too much.
Cord clamp Screw
Bind the lead wires with bundling band.
– 88 –
Page 89
No.
Part name
Procedure
Remarks
l
Fan guard
1. Detachment
1) Perform works of items 1 of c and d.
2) Remove the discharge port cabinet, and put it down so that the fan guard side directs downward.
Perform work on a corrugated card­board, cloth, etc. to prevent flaw to the product.
3) Remove screws fixing the bell mouth. (M4 x 8, 2 pcs.)
4) Remove the bell mouth.
5) Remove the hooking claws by pushing with minus screwdriver along with the arrow mark as shown in right figure.
2. Attachment
1) Insert claw of the fan guard in hole of discharge port cabinet. Push the hooking claws (5 positions) with hands and fix the claws.
After all the attachment works are completed, check that all the hooking claws are fixed to the specified posi­tions.
Minus screwdriver
Discharge port cabinet
Bell mouth
Remove two screws
Bell mouth
Discharge port cabinet
Fan guard
2) Mount the bell mouth by hooking three claws at upper side of the bell mouth in the slits on the discharge port cabinet.
3) After attachment, fix the bell mouth with screws. (M4 x 8, 2 pcs.)
Hooking claw
Discharge port cabinet
Slit (3 positions)
Bell mouth
– 89 –
Claw (3 positions)
Page 90
14. EXPLODED VIEWS AND PARTS LIST
– 90 –
Page 91
Location
No.
1 43005727 CABINET, AIR, OUTLET
Part No. Description
Model Name RAV-
SM1103AT-E1 SM1403AT-E1
11
2 43100350 CABINET, FRONT, ASSY, ROHS
3 43100349 CABINET, SIDE, ASSY, ROHS
4 4310A009 PLATE, ROOF
5 4301V071 GUARD, FIN
6 43191651 GUARD, FAN
7 43122065 BELL MOUTH
8 43F47669 NUT, FLANGE
9 43120224 FAN, PROPELLER, PE492
10 4312C090 MOTOR, FAN, WDF-340-A100-1
11 4314G308 CONDENSOR ASSY
12 43100347 PANEL, FRONT, PIPING, ROHS
13 43100345 PANEL, BACK, PIPING, ROHS
14 43119390 HANGER
15 43141519 COMPRESSOR, DA422A3F-12M
16 43F50407 THERMOSTAT,BIMETAL
17 43F63317 HOLDER,THERMOSTAT
18 43160625 LEAD ASSY, COMPRESSOR
11
11
11
11
11
11
11
11
11
11
11
11
22
11
11
11
11
19 43100343 BASE ASS'Y, ROHS
20 43197183 BOLT, COMPRESSOR
21 43149324 RUBBER, CUSHION
22 43F46500 VALVE, 4WAY, STF-H0218
23 43146749 COIL, SOLENOID, STF-H01AJ1949A1
24 43146634 VALVE, PULSE, MODULATING
25 43046494 COIL, PMV, ASSY
26 43148170 ACCUMULATOR ASS'Y
27 43146686 VALVE, PACKED, 9.52
28 43146724 VALVE, BALL, SBV-JA5GTC-1, ROHS
29 43F47401 BONNET, 3/8 IN
30 43194029 BONNET, 5/8 IN
31 43151301 SWITCH, PRESSURE
32 43158231 REACTOR
33 43F19904 HOLDER, SENSOR (TS)
34 43F63188 HOLDER, TC SENSOR
35 43063332 HOLDER, SENSOR
11
33
33
11
11
11
11
11
11
11
11
11
11
22
22
11
11
36 4314Q068 STRAINER, ROHS
37 4314Q033 STRAINER, ROHS
38 43F89160 CAP, WATERPROOF
39 43F32441 NIPPLE, DRAIN
11
11
55
11
– 91 –
Page 92
Inverter assembly
Location
No.
701 43150351 SENSOR, TD
702 43150350 SENSOR ASSY
703 43150353 SENSOR
704 43150352 SENSOR
705 43150355 SENSOR
706 43F63338 HOLDER, ASSY (SENSOR)
707 4316V496 PC BOARD ASSY, MCC-1630
708 43160589 FUSE
709 43F63248 SUPPORTER, ASSY
710 43160567 TERMINAL BLOCK, 3P, 30A
711 43160565 TERMINAL BLOCK, 3P, 20A
712 43163059 SPACER, BUSH
713 43163066 SPACER, COLLAR
714 43163060 SPACER, COLLAR
Part No. Description
Model Name RAV-
SM1103AT-E1 SM1403AT-E1
11
11
11
11
11
11
11
11
11
11
11
33
22
11
– 92 –
Page 93
TOSHIBA CTOSHIBA C
TOSHIBA C
TOSHIBA CTOSHIBA C
23-17, TAKANAWA 3 CHOME, MINATOKU, TOKYO, 108-8580, JAPAN
Copyright © 1999 to 2012 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.
ARRIER CORPORAARRIER CORPORA
ARRIER CORPORA
ARRIER CORPORAARRIER CORPORA
TIONTION
TION
TIONTION
Loading...