Toshiba RAV-SM1401CT-E User Manual

FILE NO. A03-016
SERVICE MANUAL
UNDER CEILING TYPE (INDOOR UNIT)
RAV-SM561CT-E
RAV-SM801CT-E RAV-SM1101CT-E RAV-SM1401CT-E
R410A
PRINTED IN JAPAN, Feb.,2004 ToMo
1. SPECIFICATIONS................................................................................................ 3
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ................................................. 7
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM .........................................8
4. WIRING DIAGRAM .............................................................................................. 9
5. SPECIFICATIONS OF ELECTRICAL PAR T S ................................................... 10
6. REFRIGERANT R410A ..................................................................................... 11
7. INDOOR UNIT CONTROL ................................................................................. 19
8. TROUBLESHOOTING ....................................................................................... 28
9. REPLACEMENT OF SERVICE INDOOR P.C. BOARD ..................................... 50
10. SETUP AT LOCAL SITE AND OTHERS ........................................................... 54
11. ADDRESS SETUP ............................................................................................. 64
12. DETACHMENTS................................................................................................. 68
13. EXPLODED VIEWS AND PARTS LIST ............................................................. 73
NOTE :
This Service Manual describes explanation for the Under Ceiling type indoor unit. For the combined outdoor unit, refer to the following Service Manual.
Outdoor unit Model name SVM to be referred RAV-SMXXXAT-E A03-007 RAV-SPXXXAT-E A03-014
1. SPECIFICATIONS
1-1. Under Ceiling Type (Indoor Unit)
Model name
Standard capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Electrical characteristics
Appearance Main unit
Outer dimension
Total weight Main unit (kg)
Running current (A)
Power consumption (kW)
Power factor (%)
Height (mm)
Main unit Width (mm)
Depth (mm)
RAV-SM561CT-E RAV-SM801CT-E
Cooling Heating Average Cooling Heating Average
5.0 5.6 7.0 8.0
(1.5 – 5.6) (1.5 – 6.3) (2.2 – 8.0) (2.2 – 9.0)
2.75 [D] 3.41 [B] 3.08 2.77 [D] 3.24 [C] 3.01
1 phase 230V (220 – 240V) 50Hz
8.71–7.98 7.85–7.19 12.23–11.21 11.94–10.95
1.82 1.64 2.53 2.47
95 95 94 94
Shine white
210 210
680 680
910 1180
20 25
Heat exchanger
Soundproof/Heat-insulating material
Fan
Fan unit Standard air flow High (Mid./Low) (m³/h)
Motor (W)
Air filter
Controller (Sold separately)
Gas side (mm)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Liquid side (mm)
Drain port (Nominal dia.)
Inflammable polyethylene foam
840 1140
60 60
Ø12.7 (1/2”) Ø15.9 (5/8”)
Ø6.4 (1/4”) Ø9.5 (3/8”)
36 33 30 38 36 33
Finned tubu
Multi-blade fan
Attached main unit
RBC-AMT21E
25 (Polyvinyl chloride tube)
Note 1 : The cooling and heating capacities and electrical characteristics are measured under the conditions specified by JIS B
8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
3
Model name
RAV-SM1101CT-E RAV-SM1401CT-E
Cooling Heating Average Cooling Heating Averag e
Standard capacity (Note 1) (kW)
Energy consumption effect ratio (Cooling)
Power supply
Electrical characteristics
Appearance Main unit
Outer dimension
Total weight Main unit (kg)
Heat exchanger
Soundproof/Heat-insulating material
Running current (A)
Power consumption (kW)
Power factor (%)
Height (mm)
Main unit Width (mm)
Depth (mm)
10.0 11.2 12.3 14.0
(2.2 – 11.2) (2.2 – 12.5) (3.0 – 13.2) (3.0 – 16.0)
2.85 [C] 3.50 [B] 3.18 2.72 [D] 3.38 [C] 3.05
1 phase 230V (220 – 240V) 50Hz
16.2–14.9 14.84–13.61 21.18–19.40 19.40–17.78
3.51 3.20 4.52 4.14
98 98 97 97
Shine white
210
680
1595
42
Finned tubu
Inflammable polyethylene foam
Fan
Fan unit Standard air flow High (Mid./Low) (m³/h)
Motor (W)
Air filter
Controller (Sold separately)
Gas side (mm)
Connecting pipe
Sound level High (Mid./Low) (Note 2) (dB•A)
Liquid side (mm)
Drain port (Nominal dia.)
1620 1980
120 120
41 38 35 43 40 37
Multi-blade fan
Attached main unit
RBC-AMT21E
Ø15.9 (5/8”)
Ø9.5 (3/8”)
25 (Polyvinyl chloride tube)
Note 1 : The cooling and heating capacities and electrical characteristics are measured under the conditions specified by JIS B
8616 based on the reference piping 7.5m.
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note : Rated conditions Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
4
1-2. Operation Characteristic Curve
RAV-SM561CT-E
RAV-SM561CT-E
RAV-SM561CT-E / SM801CT-E <Cooling> <Heating>
14
12
RAV-SM801CT-E
RAV-SM801CT-E
10
8
6
Current (A)
4
2
0
15
020
RAV-SM561CT-E
RAV-SM561CT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 220V
40 60 70 80 100
Compressor speed (rps)
16
14
12
10
8
Current (A)
6
4
2
0
15
020
RAV-SM801CT-E
RAV-SM801CT-E
RAV-SM561CT-E
RAV-SM561CT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 220V
40 60 80 90 100
Compressor speed (rps)
RAV-SM1101CT-E <Cooling> <Heating>
20
18
16
RAV-SM1101CT-E
14
12
10
Current (A)
8
6
4
2
0
0 204060
RAV-SM1101CT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
16
14
12
10
Current (A)
8
6
4
2
0
0204060
RAV-SM1101CT-E
RAV-SM1101CT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
Compressor speed (rps)
Compressor speed (rps)
5
RAV-SM1401CT-E <Cooling> <Heating>
22 20
18
RAV-SM1401CT-E RAV-SM1401CT-E
16
RAV-SM1401CT-E RAV-SM1401CT-E
14 12 10
Current (A)
8 6
Conditions
4 2 0
020406080
Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
22 20
18 16 14 12 10
Current (A)
8 6
Conditions
4 2 0
020406080
Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
1-3. Capacity Variation Ratio According to Temperature
<Cooling> <Heating>
105 100
95 90 85 80 75 70
Capacity ratio (%)
65 60 55
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
50
32 33 34 35 36 37 38 39 40 41 42 43
Outsoor temp. (˚C)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14 -12 -10 -8 -6 -4 -2 0 2 4 6 8 10
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (˚C)
6
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
2-1. Under Ceiling Type (Indoor Unit)
RAV-SM561CT-E / SM801CT-E / SM1101CT-E / SM1401CT-E
128 84
170320
(Hanging position)
Hanging bolt
50
Within
Upper pipe draw-out port (Knockout hole)
Power supply cable take-in port (Knockout)
Remote controller cable take- in port (Knockout hole)
53
Left drain size
B (Hanging position)
Refrigerant pipe (Gas side ØD)
Ceiling surface
Unit
Refrigerant pipe (Liquid side ØC)
A
216
110
70
75 97
76
50
130
680
Drain pipe connecting port
146
145
Pipe hole on wall (Ø100 hole)
210
167
105
347
262
135 84
Outside air take-in port (Duct sold separately)(Knockout hole Ø92)
Pipe draw-out port (Knockout hole)
Drain port VP20 (Inner dia. Ø26, hose attached)
114
41
200 (Liquid pipe)
216 (Gas pipe)
Remote controller cable take- in port
Power supply cable take-in port (Knockout hole)
Remote controller cable take- in port
90
32
(Knockout hole)
92
Drain left pipe draw-out port (Knockout hole)
32
171
Wireless sensor mounting section
250 or more250 or more
Model name A B C D 561CT 801CT 1101CT to 1401CT
910 1180 1595
855 1125 1540
Ø6.4 Ø12.7
Ø9.5 Ø15.9
500 or more
7
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM
3-1. Under Ceiling Type
RAV-SM561CT-E / SM801CT-E / SM1101CT-E / SM1401CT-E
RAV-SM 561CT-E 801CT-E
1101CT-E 1401CT-E
Outer diameter of refrigerant pipeModel
Gas side ØA Liquid side ØB
12.7 mm 6.4 mm
15.9 mm 9.5 mm
TC sensor
Indoor unit
TCJ
sensor
Air heat exchanger
Refrigerant pipe at gas side Outer dia. ØA
Pd PsPacked valve
Packed valve Outer dia. ØA
Refrigerant pipe at liquid side Outer dia. ØB
Outer dia. ØB
Outdoor unit
NOTE :
The refrigerating cycle differs according to the combined outdoor units. For the cycle diagram, cycle pressure , etc., refer to the following Service Manual.
RAV -SMXXXXAT-E : A03-007 RAV -SPXXXXAT-E : A03-014
Cooling Heating
8

4. WIRING DIAGRAM

4-1. Under Ceiling Type (Indoor Unit)
RAV-SM561CT-E / SM801CT-E / SM1101CT-E / SM1401CT-E
LM
FM
TA
1 2 1 2
CN104
(YEL)
CN34
FS
(RED)
3 3
2 2
1 1
CN33 (WHI)
5
5
5
5
4
4
3
3
2
2
1
1
4
4
3
3
2
2
1
1
1 2 1 2
CN102
(RED)
TCJ
1 2 1 2
CN101
(BLK)
TC
1 2 3
CN80
(GRN)
(EXCT)
1 2
CN73
(RED)
MCC-1402
Control P.C. Board for
Indoor Unit
DC20V DC15V DC12V DC7V
Power supply
1 2
CN70 (WHI)
5 4
CN620
3
(BLU)
2 1
6 5
CN60
4
(WHI)
3 2 1
CN32
2
(WHI)
1
(FAN DRIVE)
circuit
6 5 4
CN61 (YEL)
3 2 1
5 4
CN50
3
(WHI)
2 1
3
CN309
2
(YEL)
1
3
3
2 2
1 1
CN41 (BLU)
BLK BLK
BLK
WHI
Wireless Remote
BLK
B A
WHI
CN001
2 2
(WHI)
1 1
Adapter for
Controller
CN1
2 2
(WHI)
1 1
Wired Remote
Controller
CN333
(WHI)
5 5
4 4
3 3
2 2
1 1
CN334
(WHI)
1 1
2 2 3 3
4 4 5 5
CN68 (BLU)
Motor
drive
circuit
RY 302
1 233 1 2 3 1 2
RY 303
CN304
(GRY)
Fuse F302 T3.15A 250V~
CN67 (BLK)
Capacitor
+
~~
Fuse F301 250V~ T6.3A
1 233 1 2
WHI BLK
RED
445
P301
5
BLK
1 2
CN66 (WHI)
FM
TA
TC
TCJ
LM DP
FS
RY302
DP
NOTE
: Fan motor : Indoor temp. sensor : Temp. sensor : Temp. sensor : Louver motor : Drain pump motor : Float switch : Drain control relay
RED
WHI
321
Indoor unit earth screw
321
Outdoor unit earth screw
Serial
NL
signal
Single phase 220V, 50Hz
9
Closed-end connector
1 233 1 2
Reactor
Color
Identification
BLACK
:
BLK
BLUE
:
BLU
RED
:
RED
GRAY
:
GRY
PINK
:
PNK
GREEN
:
GRN
WHITE
:
WHI
BROWN
:
BRW
ORANGE
:
ORN
YELLOW
:
YEL
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Under Ceiling Type (Indoor Unit)
RAV-SM561CT-E / SM801CT-E / SM1101CT-E / SM1401CT-E
No.
1
Fan motor (SM501CT-E)
2
Fan motor (SM801CT-E)
3
Fan motor (SM1101CT-E/SM1401CT-E)
4
Thermo. sensor (TA-sensor)
5
Heat exchanger sensor (TCJ-sensor)
6
Heat exchanger sensor (TC-sensor)
7
Louver motor
8
Reactor
Parts name
5-2. Accessory Separate Soldparts
TCB-DP22CE (Drain up kit)
No.
1
Float switch
2
Drain pump motor
Parts name
Type
SWF-280-60-1 SWF-280-60-2
SWF-280-120-2
258 mm
Ø6 mm, 1200 mm Ø6 mm, 1200 mm
MP24GA1
CH-43-2Z-K
Type
FS-0218-106
ADP-1406 or ADP-1415
Specifications
Output (Rated) 60 W, 220–240 V Output (Rated) 120 W, 220–240 V Output (Rated) 120 W, 220–240 V 10 k at 25°C 10 k at 25°C 10 k at 25°C DC 15 V 10 mH, 1 A
Specifications
10
6. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
6-1. Safety During Installation/Servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusiv e for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusiv e for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks , its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or removal
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and fire, etc.
6-2. Refrigerant Piping Installation
6-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 6-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
11
Table 6-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4 3/8 1/2 5/8
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 6-2-3 to 6­2-6 below .
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly f or thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 6-2-2.
Table 6-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all b urrs and clean the cut surface before installation.
12
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Table 6-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen- sion A by using a gauge for size adjustment.
ØD
A
Fig. 6-2-1 Flare processing dimensions
Nominal
diameter
1/4 3/8 1/2 5/8
Nominal
diameter
1/4 3/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for
R410A clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Table 6-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
Thickness
(mm)
0.8
0.8
Flare tool for
R22 clutch type
0 to 0.5 0 to 0.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5 1/2 5/8
Nominal
diameter
1/4 3/8 1/2 5/8
12.70
15.88
Table 6-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70 15,88
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5 0 to 0.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
13
Flare nut
width (mm)
17 22 26 29
Table 6-2-6 Flare and flare nut dimensions for R22
Nominal Outer diameter Thickness
diameter (mm) (mm)
1/4 6.35 0.8 3/8 9.52 0.8 1/2 12.70 0.8 5/8 15.88 1.0 3/4 19.05 1.0
45˚to 46˚
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.4 19.0 16.0 23
23.3 24.0 19.2 34
D
C
43˚to 45˚
Flare nut width
(mm)
17 22 24 27 36
Fig. 6-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 6-2-7 Tightening torque of flare for R410A [Reference values]
Nominal Outer diameter Tightening torque
diameter (mm) N•m (kgf•cm)
1/4 6.35 14 to 18 (140 to 180)
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 6-2-7 shows reference v alues.
NOTE:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180) 3/8 9.52 33 to 42 (330 to 420) 1/2 12.70 50 to 62 (500 to 620) 5/8 15.88 63 to 77 (630 to 770)
14
42 (420) 55 (550) 65 (650)
6-3. Tools
6-3-1. Required T ools
The service port diameter of packed v alve of the outdoor unit in the air conditioner using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No. Used tool
Flare tool
Copper pipe gauge for adjusting projection
margin Torque wrench
Gauge manifold
Charge hose
Vacuum pump adapter
Electronic balance for
refrigerant charging Refrigerant cylinder
Leakage detector
Charging cylinder
Usage
Pipe flaring Flaring by conventional
flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
air conditioner installation
Existence of Whether conven­new equipment tional equipment for R410A can be used
Yes
Yes
Yes
Yes
Yes Yes
Yes Yes
(Note 2)
R410A
(Note 1)
*
(Note 1)
*
X X
X X X
X X
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
¡
(Note 1)
*
X X
¡
¡
X
¡
X
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge , etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench
(9) Hole core drill (Ø65) (10) Hexagon wrench
(Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
15
6-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps .
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
Nev er charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge
liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 6-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
16
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas , the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
6-5. Brazing of Pipes
6-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expen­sive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Fig. 6-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
6-5-2. Flux
(1) Reason why flux is necessary
By removing the oxide film and any f oreign matter on the metal surface, it assists the flo w of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing filler's surface tension, the brazing filler adheres better to the treated metal.
17
(2) Characteristics required for flux
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature r ange, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the br azing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
6-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder. Use a copper pipe to direct the piping mate-
rial, and attach a flow-meter to the cylinder. Apply a seal onto the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open. Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m³/Hr or 0.02 MPa (0.2kgf/ cm²) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
Copper - Copper
Copper - Iron
 
Piping
material
Iron - Iron
Do not enter flux into the refrigeration cycle. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Used brazing
filler
Phosphor copper
Silver
Silver
Used
flux
Do not use
Paste flux
Vapor flux
Fig. 6-5-1 Prevention of oxidation during brazing
18
7-1. Indoor Control Cir cuit
7. INDOOR UNIT CONTROL
Max. 8 units are connectable.*1 *1 Max. 7 units when network adapters
are attached *2 Network adapters are attached to only
one unit. *3 Weekly timer is not connectable to the
sub remote controller.
Central control
remote controller
(Sold separatrly)
Indoor unit
#1
Network adapter (Sold separatrly)
X
Y
Network adapter P.C. board (MCC-1401)
AI NET
communication
circuit
DC5V
Power circuit
Transformer
Remote controller communication circuit
CPU
H8/3687
Switch setup
Louver
motor
Drain pump
Indoor
fan
motor
Indoor control P.C. board (MCC-1402)
DC280V
Main (Sub) master remote controller
Display
LCD
CPU
Remote
controller
communication
circuit
Humidifier
relay output
Heater relay
output
control
circuit
Function setup
Key switch
DC5V
Power circuit
Sold separatrly Sold separatrly
Driver
Outside output
Run
Warning
Ready
Thermo. ON
Cool
Heat
Fan
Power circuit
Display
LED
DC20V DC12V
DC5V
CPU TMP88CH 47FG (TMP88PH 47FG)
Fan motor
AB
Remote
controller
communication
circuit
CPU
H8/3039
AC
synchronous
signal input
circuit
CN2 CN1
3
*
Serial send/
receive
circuit
Weekly timer
Display
LCD
DC5V
Power circuit
EEPROM
TA sensor TC sensor TCJ sensor
Float input
Secondary
LCD
driver
CPU
battery
#2
AB
Same as
the left
*
123
Function setup
Key switch
#3
AB
Same as
the left
2
123
2
*
123 123
Outdoor unit
19
communication
Power
circuit
DC5V
Buzzer
Receive circuit
Wireless remote controller kit
Sensor P.C. board (MCC-1504)
Remote
controller
circuit
CPU
Temporary
operation SW
Display LED
Function
setup SW
Outdoor
unit
Outdoor
unit
7-2. Control Specifications
No.
1
When power supply is reset
2
Operation mode selection
Item
Outline of specifications
1) Distinction of outdoor units When the power supply is reset, the outdoors are
distinguished, and control is exchanged according to the distinguished result.
2) Setting of speed of the indoor fan/setting weather to adjust air direction or unit.
3) Based on EEPROM data, speed of the indoor fan or setting whether to adjust air direction or not is se­lected.
1) Based on the operation mode selecting command from the remote controller, the operation mode is selected.
Remote controller
command
STOP
FAN
COOL
DRY HEAT AUTO
Ta (˚C)
+1.5
Tsc
or Tsh
-1.5
COOL
Outline of control
Air conditioner stops. Fan operation Cooling operation Dry operation Heating operation
COOL/HEAT operation mode is automatically selected by Ta and Ts for operation.
(COOL ON)
(COOL OFF)
HEAT
Remarks
Air speed/ Air direction adjustment
Ta : Room temperature Ts : Setup temperature Tsc : Setup temperature in
cooling operation
Tsh: Setup temperature
+ Room temperature control temperature compensation
1) Judge the selection of COOL/HEAT mode as shown in the figure above.
When 10 minutes passed after thermostat had been turned off, the heating operation (Thermo OFF) is exchanged to cooling operation if Tsh exceeds +1.5 or more.
(COOL OFF) and (COOL ON) in the figure indicate an example.
When 10 minutes passed after thermostat had been turned off, the cooling operation (Thermo OFF) is exchanged to heating operation if Tsc exceeds –1.5 or less.
2) For the automatic capacity control after judgment of COOL/HEAT, refer to item 4.
3) For the temperature correction of room temperature control in automatic heating operation, refer to item 3.
20
No.
3
Item
Room temperature control
Outline of specifications
1) Adjustment range Remote controller setup tem­perature (°C)
Wired type Wireless type
COOL/DRY
18 to 29 18 to 30
Heating operation
18 to 29 16 to 30
Remarks
Auto operation
18 to 29 17 to 27
4
Automatic capacity control
5
Air speed selection
2) Using the item code 06, the setup temperature in heating operation can be compensated.
Setup data Setup temp. compensation
0246
+0°C+2°C+4°C+6°C
Setting at shipment
Setup data 2
1) Based on the difference between Ta and Ts, the operation frequency is instructed to the outdoor unit.
1) Operation with (HH), (H), (L), or [AUTO] mode is performed by the command from the remote controller .
2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between T a and Ts.
Ta (˚C) +3.0
+2.5 +2.0
<COOL>
+1.5 +1.0
+0.5
Tsc
-0.5
Shift of suction tempera­ture in heating operation
HH > H > L > LL
HH (HH)
H (HH) H (HH)
L(H) L(H)
L(H) L(L)
A
B C D
E
F G
F1 F2 F3 F4 F5 F6 F7 F8 F9 FA FB FC FD
Standard
COOL HEAT
HH
HH
H+ H+
H
H
L+
L+ L
L
LL LL
Controlling operation in case when thermo of remote controller works is same as a case when thermo of the body works.
If the air speed has been changed once, it is not changed for 3 minutes. However when the air volume is exchanged, the air speed changes.
When cooling operation has started, the air speed selects a downward slope, that is, the high position.
If the temperature is just on the difference boundary, the air speed does not change.
Mode in the parentheses indicates one in automatic cooling operation.
Type 1
COOL HEAT
HH HH
H+
H+
H
H
L+
L+ L
L
LL LL
Type 2
COOL HEAT
HH HH
H+ H+
H
H
L+
L+ L
L
LL LL
Type 3
COOL HEAT
HH HH
H+,H H+,H
L+ L+
LL
LL LL
Type 7
COOL HEAT
HH
HH H+,H
H+,H
L+
L+ L
L
LL LL
SM561
1120 1080 1000 970 930 910 860 820 800 780 760 740 550
SM801
1140 1080 1040 990 950 940 900 880 860 830 800 780 550
SM1101
1220 1180 1120 1060 1020
980
940 910 880 850 820 790 580
SM1401
1300 1220 1180 1140 1100 1060 1020 970 940 930 880 850 580
21
No.
5
Item
Air speed selection (Continued)
Outline of specifications
<HEAT>
Ta (˚C)
L(L)
(-0.5)
(0)
(+0.5)
–1.0
Tsh
+1.0
L(H) H(H)
H
E
D
(HH)
(+1.0) (+1.5)
(+2.0)
+2.0 +3.0
+4.0
HH
(HH)
C
B A
Value in the parentheses indicates one when thermo­stat of the remote controller works.
Value without parentheses indicates one when thermo­stat of the body works.
If the air speed has been changed once, it is not changed for 1 minute . However when the air speed is exchanged, the air speed changes.
When heating operation has started, the air speed selects a upward slope, that is, the high position.
If the temperature is just on the difference boundary, the air speed does not change.
Mode in the parentheses indicates one in automatic heating operation.
In Tc ≥ 60°C, the air speed increases by 1 step.
3) In heating operation, the mode changes to [UL] if
thermostat is turned off.
4) If T a 25°C when heating operation has started and
when defrost operation has been cleared, it oper­ates with HIGH (H) mode or (HH) for 1 minute from when Tc has entered in E zone of cool air discharge preventive control (Item 6).
5) In automatic cooling/heating operation, the revolu-
tion frequency of [HH] is set larger than that in the standard cooling/heating operation. However the revolution frequency is restricted in the automatic heating operation as shown in the following figure.
Remarks
[PRE-HEAT] display
Tc
(˚C)
47
42
F5 F4
F5
6 Cool air
discharge preventive control
1) In heating operation, the indoor fan is controlled based
on the detected temperature of Tc sensor or Tcj sensor. As shown below, the upper limit of the revolution frequency is determined.
Tc
(˚C)
Tcj
32 30 28 26
20 16
HH
H
UL
OFF
L
E zone D zone
C zone B zone
A zone
22
In D or E zone, the priority is given to setup of air volume exchange .
In A and B zones, [PRE-HEAT] is displayed.
No.
7
Freeze preven­tive control (Low tempera­ture release)
Item
Outline of specifications
1) The cooling operation (including Dry operation) is
performed as follows based on the detected tempera­ture of Tc sensor or Tcj sensor.
When [J] zone is detected for 6 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [J] zone.
In [K] zone, time counting is interrupted and the opera­tion is held.
When [I] zone is detected, the timer is cleared and the operation returns to the normal operation.
If the commanded frequency becomes S0 because the operation continues in [J] zone, the return temperature A is raised from 5°C to 12°C until [I] zone is detected and the indoor fan operates with [M] mode.
(˚C)
5
I
A
K
Remarks
Tcj : Indoor heat ex-
changer sensor temperature
[M] mode : Air speed selection
8
High-temp release control
2
J
In heating operation, the freeze-prev entive control works if 4-way valve is not exchanged and the condition is satisfied. (However the temperature for J zone dashing control is changed from 2°C to –5°C.)
1) The heating operation is performed as follows based on
the detected temperature of Tc sensor or Tcj sensor.
When [M] zone is detected, the commanded fre­quency is decreased from the real operation fre­quency. After then the commanded frequency changes every 30 seconds while operation is per­formed in [M] zone.
In [N] zone, the commanded frequency is held.
When [L] zone is detected, the commanded fre-
quency is returned to the original value by approx. 6Hz every 60 seconds.
Setup at shipment
Control temp (°C)
AB
56 (54) 52 (52)
Tcj
(˚C)Tc
A
B
L
M N
NOTE :
When the operation has started or when Tc or Tcj became lower than 30°C after start of the operation, temperature is controlled between values in parentheses of A and B.
Same when thermostat is turned off.
9 Drain pump
control When, the
drain up kit (sold sepa­rately) is mounted.
1) In cooling operation (including Dry operation), the drain pump is usually operated.
2) If the float switch operates while drain pump operates, the compressor stops, the drain pump continues the operation, and a check code is output.
3) If the float switch operates while drain pump stops, the compressor stops and the drain pump operates. If the float switch keeps operating for approx. 4 minutes, a check code is output. Check code [P10]
23
No.
10
11
Item
DAfter-heat elimination
Frequency fixed operation (Test run)
Outline of specifications
Remarks
When heating operation stops, the indoor fan operates with LOW mode for approx. 30 seconds.
<In case of wired remote controller>
1. When pushing [CHECK] button for 4 seconds or more, [TEST] is displayed on the display screen and the mode enters in Test run mode.
2. Push [ON/OFF] button.
3. Using [MODE] button, change the mode from [COOL] to [HEAT].
Do not use other mode than [COOL]/[HEAT] mode.
During test run operation, the temperature cannot be adjusted.
An error is detected as usual.
A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation. (Display in the display part is same as the procedure in item 1).)
5. Push [CHECK] button to clear the test run mode. ([TEST] display in the display part disappears and the status returns to the normal stop status.)
<In case of wireless remote controller>
1. Turn off the power of the set. Remove the adjuster with sensors from the ceiling panel.
2. Turn Bit [1: TEST] of sensor P.C. board switch [S003] from OFF to ON. Turn on the power of the set.
3. Push [ON/OFF] button of the wireless remote controller and set the operation mode to [COOL] or [HEAT] using [MODE] button. (During test run operation, all the display lamps of wireless remote controller sensors flash.)
Do not use other mode than [COOL]/[HEAT] mode.
An error is detected as usual.
A frequency fixed operation is performed.
4. After the test run, push [ON/OFF] button to stop the operation.
5. Turn off the power of the set. Turn Bit [1: TEST] of sensor P.C. board switch [S003] from ON to OFF. Mount the adjuster with sensors to the ceiling panel.
12
Central control mode selection
1) Setting at the central controller side enables to select the contents which can be operated on the remote controller at indoor unit side.
2) RBC-AMT21
[Last push priority] :
The operation contents can be selected from both remote controller and central controller of the indoor unit side, and the operation is performed with the contents selected at the last.
[Center] :
Start/Stop operation only can be handled on the remote control­ler at indoor unit side.
[Operation Prohibited] :
It cannot be operated on the remote controller at indoor unit side. (Stop status is held.)
24
(No display)
[CENTER] goes on.
[CENTER] goes on.
In a case of wireless type, the display lamp does not change. However, contents which can be operated are same.
The status set in [CEN­TER]/[Operation Prohib­ited] mode is notified with the receiving sound “Pi, Pi, Pi, Pi, Pi (5 times).
Loading...
+ 53 hidden pages