Toshiba RAV-SM1102AT-E, RAV-SP802AT-E, RAV-SP562AT-E, RAV-SM562AT-E, RAV-SP1102AT-E SERVICE MANUAL

...
FILE NO. A05-018
Revised: Jul/25/2005
SERVICE MANUAL/INTEGRATION
SPLIT TYPE
INDOOR UNIT
<DIGITAL INVERTER> RAV-SM562UT-E RAV-SM562BT-E RAV-SM562CT-E RAV-SM802UT-E RAV-SM802BT-E RAV-SM802CT-E RAV-SM1102UT-E RAV-SM1102BT-E RAV-SM1102CT-E RAV-SM1402UT-E RAV-SM1402BT-E RAV-SM1402CT-E
<SUPER DIGITAL INVERTER> RAV-SP1102UT-E
• Service Manual for RAV-SM✻✻✻KRT and RAV-SM✻✻✻XT contact the Sales company or Dealer.
OUTDOOR UNIT
<DIGITAL INVERTER> RAV-SM562AT-E RAV-SM802AT-E RAV-SM1102AT-E RAV-SM1402AT-E
<SUPER DIGITAL INVERTER> RAV-SP562AT-E RAV-SP802AT-E RAV -SP1102AT-E RAV-SP1402AT-E
R410A
PRINTED IN JAPAN, Jan.,2006 ToMo
ADOPTION OF NEW REFRIGERANT
This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the con ventional refrigerant R22 in order to prevent destruction of the oz one layer.
WARNING
Cleaning of the air filter and other parts of the air filter involves dangerous work in high places, so be sure to ha ve a service person do it. Do not attempt it yourself. The cleaning diagram for the air filter is there for the service person, and not for the customer.
NOTE
A direct current motor is adopted for indoor f an motor in the Concealed Duct Standard Type air conditioner. Caused from its characteristics, a current limit works on the direct current motor. When replacing the high­performance filter or when opening the service board, be sure to stop the fan. If an above action is ex ecuted during the fan operation, the protective control works to stop the unit operation, and the check code “P12” may be issued. However it is not a trouble. When the desired operation has finished, be sure to reset the system to clear “P12” error code using the leak breaker of the indoor unit. Then push the operation stop button of the remote controller to return to the usual operation.
CONTENTS
SAFETY CAUTION ............................................................................................ 4
1. SPECIFICATIONS ...................................................................................... 9
1-1. Indoor Unit........................................................................................................... 9
1-2. Outdoor Unit...................................................................................................... 17
1-3. Operation Characteristic Curve....................................................................... 19
2. AIR DUCTING WORK .............................................................................. 22
2-1. Static Pressure Characteristics of Each Model ............................................. 22
3. CONSTR UCTION VIEWS (EXTERNAL VIEWS) ...................................... 24
3-1. Indoor Unit......................................................................................................... 24
3-2. Outdoor Unit...................................................................................................... 28
4. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM.............................. 31
4-1. Indoor Unit/Outdoor Unit ................................................................................. 31
5. WIRING DIAGRAM................................................................................... 39
5-1. Indoor Unit......................................................................................................... 39
5-2. Outdoor Unit (Wiring Diagram)........................................................................ 42
6. SPECIFICATIONS OF ELECTRICAL PARTS.......................................... 46
6-1. Indoor Unit......................................................................................................... 46
6-2. Outdoor Unit...................................................................................................... 48
6-3. Accessory Separate Soldparts........................................................................ 50
– 2 –
7. REFRIGERANT R410A............................................................................ 51
7-1. Safety During Installation/Servicing ............................................................... 51
7-2. Refrigerant Piping Installation....................................................................... 51
7-3. Tools .................................................................................................................. 55
7-4. Recharging of Refrigerant ............................................................................... 55
7-5. Brazing of Pipes................................................................................................ 56
8. CONTROL BLOCK DIAGRAM................................................................. 58
8-1. Indoor Control Circuit....................................................................................... 58
8-2. Control Specifications...................................................................................... 59
8-3. Indoor Print Circuit Board................................................................................ 68
9. CIRCUIT CONFIGURATION AND CONTROL SPECIFICATIONS .......... 69
9-1. Indoor Control Circuit....................................................................................... 69
9-2. Outdoor Controls.............................................................................................. 70
10. TROUBLESHOOTING.............................................................................. 79
10-1. Summary of Troubleshooting........................................................................... 79
10-2. Check Code List................................................................................................ 81
10-3. Error Mode Detected by LED on Outdoor P.C. Board .................................... 84
10-4. Troubleshooting Procedure for Each Check Code ........................................ 85
11. REPLACEMENT OF SERVICE INDOOR P.C. BOARD.......................... 101
12. SETUP AT LOCAL SITE AND OTHERS................................................ 105
12-1. Indoor Unit....................................................................................................... 105
12-2. Setup at Local Site / Others ........................................................................... 112
12-3. How to set up central control address Number ........................................... 114
13. ADDRESS SETUP ................................................................................. 115
13-1. Address Setup ................................................................................................ 115
13-2. Address Setup & Group Control.................................................................... 116
13-3. Address Setup ................................................................................................ 117
14. DETACHMENTS ..................................................................................... 119
14-1. Indoor Unit...................................................................................................... 119
14-2. Outdoor Unit.................................................................................................... 135
15. EXPLODED VIEWS AND PARTS LIST.................................................. 160
15-1. Indoor Unit....................................................................................................... 160
15-2. Outdoor Unit.................................................................................................... 174
15-3. Replacement of Main Parts (Sold Separately).............................................. 182
16. CORD HEATER INSTALLATION WORK ............................................... 184
– 3 –
SAFETY CAUTION
The important contents concerned to the saf ety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions (Refer to the Parts disassembly diag r am (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric shock is caused by high voltage resulted in a death or injur y.
During operation, a high voltage with 400V or higher of circuit () at secondary circuit of the high­voltage transformer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an electric insulator.
: For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between high­voltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury. After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
– 4 –
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused. : For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts. Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead cables with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not br ing inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refriger­ating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrig erant or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recover­ing device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the removed cables as before. Perform the work so that the cabinet or panel does not catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or fire is caused at user’s side.
– 5 –
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to check the resistance is 2M metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
ΩΩ
or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable. If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc. () Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating operation, a burn may be caused.
∗∗
) during repair work.
∗∗
– 6 –
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is per­formed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil. For the tools e xclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prev ent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are specified for R410A.
3) In the installation time, use clean pipe materials and work with great attention so that water and others do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refriger­ant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropri­ate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size , flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less . Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa­tion of the air conditioner. However clear impurities when using them.
– 7 –
4. Tools
q
q
g
1. Required T ools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary , etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive f or R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air conditioner installation
No. Used tool Usage
Flare tool Pipe flaring Yes *(Note 1) Yes
Copper pipe gauge for adjusting projection
margin Torque wrench Connection of flare nut Yes No No
Gauge manifold
Charge hose
V acuum pump adapter Vacuum evacuating Yes No Yes
Electronic balance for
refrigerant charging Refrigerant cylinder Refrigerant charge Y es No No
Leakage detector Gas leakage check Yes No Yes
Charging cylinder Refriger ant charge (Note 2) No No
Flaring by conventional flare tool
Evacuatin charge, run check, etc.
Refrigerant charge Yes Y es Yes
, refrigerant
Existence of
uipment
new e for R410A
Yes *(Note 1) *(Note 1)
Yes No No
R410A
Whether conventional equipment can be used
Conventional air
conditioner installation
Whether new e can be used with conventional refrigerant
uipment
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also f or R22 are necessary as the general tools.
1) Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2) Torque wrench
3) Pipe cutter
4) Reamer
7) Screwdriver (+, –)
8) Spanner or Monkey wrench
9) Hole core drill
10) Hexagon wrench (Opposite side 4mm)
11) Tape measure
12) Metal saw
5) Pipe bender
6) Level vial
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) IInsulation resistance tester
4) Electroscope
– 8 –

1. SPECIFICATIONS

1-1. Indoor Unit
1-1-1. 4-Way Air Discharge Cassette Type
<Digital Inverter>
Model
Cooling capacit y (kW) 5.3 7.1 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Main unit Zinc hot dipping steel plate Ceiling panel
(Sold separately)
Outer dimension
Ceiling panel (Sold separately)
Main unit (kg)21222226
Total weight
Ceiling panel (Sold separately) (k g) 4.5 4.5 4.5 4.5
Heat exchanger Finned tube
Fan Turbo fan Turbo fan Turbo fan Turbo fan Standard air flow H/M/L (m³/min) 17.5/13.9/12.1 20.0/15.7/13.6 24.0/19.0/16.0 33.0/25.0/20.0Fan unit
Motor (W) 60 60 60 90 Air filter TCB-LF1601UE, UFM1601UE, UFH16 01UE Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC 642TLE2, AX21U(W)-E2
Sound pressure level H/M/L (dB•A) 32/29/27 34/31/28 39/36/33 42/38/34 Sound power level H/M/L (dBA) 47/44/42 49/46/43 54/51/48 57/53/49
Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E
Running current (A) 8.42 – 7.72 11.32 – 10.37 16.30 – 16.00 19.20 – 17.60 Power consumption (kW) 1.76 2.34 3.52 4.09 Power factor (%) 95 94 98 97 EER (W/W) 3.01 3.03 2.84 3.01 Energy efficiency class * B B C B Energy rating ** 3.5 3.5 3.0 3.5 Running current (A) 6.89 – 6.32 11.22 – 10.28 16.10 – 14.80 18.70 – 17.20 Power consumption (kW) 1.44 2.32 3.48 4.00 Power factor (%) 95 94 98 97 COP (W/W) 3.89 3.45 3.22 3.50 Energy efficiency class * A B C B Energy rating ** 5.0 3.5 3.5 4.0
Model RBC-U21PG (W)-E2Appearance Panel color Moon-white (Muncel 2.5GY 9.0/0.5) Height (mm) 256 256 256 320 Width (mm) 840 840 840 840Main unit Depth (mm) 840 840 840 840 Height (mm) 35 35 35 35 Width (mm) 950 950 950 950 Depth (mm) 950 950 950 950
Gas side (mm) 12.7 15.9 15.9 15.9 Liquid side (mm) 6.4 9.5 9.5 9.5Connecting pipe Drain port (mm) VP25
– 9 –
* : IEC standard, ** : AS standard
<Super Digital Inverter>
Model
Cooling capacit y (kW) 5.3 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Indoor unit RAV- SM562UT-E SM802UT-E SM1102UT-E SM1402UT-E Outdoor unit RAV- SP562AT-E SP80 2AT-E SP1102AT-E SP1402AT-E
Running current (A) 7.17 – 6.57 8.95 – 8.21 11.24 – 10.31 16.51 – 15.14 Power consumption (kW) 1.53 1.93 2.40 3.56 Power factor (%) 97 98 97 98 EER (W/W) 3.46 3.68 4.17 3.51 Energy efficiency class * A A A A Energy rating ** ———— Running current (A) 5.62 – 5.15 9.42 – 8.63 12.28 – 11.25 16.60 – 15.22 Power consumption (kW) 1.20 2.03 2.62 3.58 Power factor (%) 97 98 97 98 COP (W/W) 4.67 3.94 4.27 3.91 Energy efficiency class * A A A A Energy rating ** ————
Main unit Zinc hot dipping steel plate
Ceiling panel
(Sold separately)
Outer dimension
Ceiling panel
(Sold separately)
Main unit (kg)21222626 Total weight
Ceiling panel (Sold separately) (k g) 4.5 4.5 4.5 4.5 Heat exchanger Finned tube
Fan Turbo fan Turbo fan Turbo fan Turbo fan
Standard air flow H/M/L (m³/min) 17.5/13.9/12.1 20.0/15.7/13.6 28.0/22.0/18.0 33.0/25.0/20.0Fan unit
Motor (W) 60 60 90 90 Air filter TCB-LF1601UE, UFM1601UE, UFH16 01UE Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC 642TLE2, AX21U (W)-E2
Model RBC-U21PG (W)-E2Appearance Panel color Moon-white (Muncel 2.5GY 9.0/0.5) Height (mm) 256 256 320 320 Width (mm) 840 840 840 840Main unit Depth (mm) 840 840 840 840 Height (mm) 35 35 35 35 Width (mm) 950 950 950 950 Depth (mm) 950 950 950 950
Gas side (mm) 12.7 15.9 15.9 15.9
Connecting pipe
Sound pressure level H/M/L (dB•A) 32/29/27 34/31/28 39/36/33 42/38/34 Sound power level H/M/L (dBA) 47/44/42 49/46/43 54/51/48 57/53/49
Liquid side (mm) 6.4 9.5 9.5 9.5 Drain port (mm) VP25
* : IEC standard, ** : AS standard
– 10 –
1-1-2. Concealed Duct Type
<Digital Inverter>
Model
Cooling capacit y (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Main unit Zinc hot dipping steel plate Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit
Air filter TCB-
Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC642TLE2, AX21E2
Sound pressure level H/M/L (dB•A) 40/37/33 40/37/34 42/39/36 44/41/38 Sound power level H/M/L (dBA) 55/52/48 55/52/49 57/54/51 59/56/53
Ceiling panel
(Sold separately)
Ceiling panel
(Sold separately)
Main unit (kg)30395454
Ceiling panel (Sold separately) (k g) ————
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Standard air flow H/M/L (m³/min) 13.0/11.9/9.8 19.0/16.2/13.3 27.0/23.0/18.9 33.0/28.0/23.1
Motor (W) 120 120 120 120
Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E
Running current (A) 8.99 – 8.24 12.23 – 11.21 16.50 – 15.10 20.70 – 19.00 Power consumption (kW) 1.78 2.53 3.56 4.42 Power factor (%) 90 94 98 97 EER (W/W) 2.81 2.81 2.81 2.83 Energy efficiency class * C C C C Energy rating ** 3.0 3.0 3.5 3.0 Running current (A) 8.18 – 7.50 11.65 – 10.68 14.56 – 13.35 18.88 – 17.31 Power consumption (kW) 1.71 2.41 3.14 4.03 Power factor (%) 95 94 98 97 COP (W/W) 3.27 3.32 3.57 3.47 Energy efficiency class * C C B B Energy rating ** 3.0 3.5 5.0 4.0
Model Panel color Height (mm) 320 320 320 320 Width (mm) 700 1000 1350 1350Main unit Depth (mm) 800 800 800 800 Height (mm) ———— Width (mm) ———— Depth (mm) ————
UFM21BE UFM61BE
Gas side (mm) 12.7 15.9 15.9 15.9 Liquid side (mm) 6.4 9.5 9.5 9.5Connecting pipe Drain port (mm) VP25
UFM11BFCE
UFM31BE
UFH51BFCE
UFM71BE
UFM21BFCE
UFM 41BE
UFH61BFCE
UFH 81BE
– 11 –
* : IEC standard, ** : AS standard
<Super Digital Inverter>
Model
Cooling capacit y (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Main unit Zinc hot dipping steel plate Appearance
Outer dimension
Total weight
Heat exchanger Finned tube
Fan unit
Air filter TCB-
Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC642TLE2, AX21E2
Sound pressure level H/M/L (dB•A) 40/37/33 40/37/34 42/39/36 44/41/38 Sound power level H/M/L (dBA) 55/52/48 55/52/49 57/54/51 59/56/53
Ceiling panel
(Sold separately)
Ceiling panel
(Sold separately)
Main unit (kg)30395454
Ceiling panel (Sold separately) (k g) ————
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Standard air flow H/M/L (m³/min) 13.0/11.9/9.8 19.0/16.2/13.3 27.0/23.0/18.9 33.0/28.0/23.1
Motor (W) 120 120 120 120
Indoor unit RAV- SM562BT-E SM802BT-E SM1102BT-E SM1402BT-E Outdoor unit RAV- SP562AT-E SP80 2AT-E SP1102AT-E SP1402AT-E
Running current (A) 6.51 – 5.97 9.74 – 8.93 11.72 – 10.74 18.09 – 16.58 Power consumption (kW) 1.39 2.10 2.50 3.90 Power factor (%) 97 98 97 98 EER (W/W) 3.60 3.38 4.00 3.21 Energy efficiency class * A A A A Energy rating ** ———— Running current (A) 7.26 – 6.66 9.74 – 8.93 11.72 – 10.74 16.70 – 15.31 Power consumption (kW) 1.55 2.10 2.50 3.60 Power factor (%) 97 98 97 98 COP (W/W) 3.61 3.81 4.48 3.89 Energy efficiency class * A A A A Energy rating ** ————
Model Panel color Height (mm) 320 320 320 320 Width (mm) 700 1000 1350 1350Main unit Depth (mm) 800 800 800 800 Height (mm) ———— Width (mm) ———— Depth (mm) ————
UFM21BE UFM61BE
Gas side (mm) 12.7 15.9 15.9 15.9 Liquid side (mm) 6.4 9.5 9.5 9.5Connecting pipe Drain port (mm) VP25
UFM11BFCE
UFM31BE
UFH51BFCE
UFM71BE
UFM21BFCE
UFM 41BE
UFH61BFCE
UFH 81BE
– 12 –
* : IEC standard, ** : AS standard
1-1-3. Under Ceiling Type
<Digital Inverter>
Model
Cooling capacit y (kW) 5.0 7.0 10.0 12.3 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Outdoor unit RAV- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E
Running current (A) 8.71 – 7.98 12.23 – 11.21 16.20 – 14.90 21.18 – 19.40 Power consumption (kW) 1.82 2.53 3.51 4.52 Power factor (%) 95 94 98 97 EER (W/W) 2.75 2.77 2.85 2.72 Energy efficiency class * D D C D Energy rating ** 2.5 2.5 3.0 2.5 Running current (A) 7.85 – 7.19 11.94 – 10.95 14.84 – 13.61 19.40 – 17.78 Power consumption (kW) 1.64 2.47 3.20 4.14 Power factor (%) 95 94 98 97 COP (W/W) 3.41 3.24 3.50 3.38 Energy efficiency class * B C B C Energy rating ** 4.0 4.0 5.0 3.5
Main unit Shine white
Ceiling panel
(Sold separately)
Outer dimension
Ceiling panel
(Sold separately)
Main unit (kg)21253333 Total weight
Ceiling panel (Sold separately) (k g) ———— Heat exchanger Finned tube
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Standard air flow H/M/L (m³/min) 13.0/11.2/10.0 18.5/16.7/14.6 27.5/24.0/21.2 30.0/26.0/23.1Fan unit
Motor (W) 30 40 80 80 Air filter Attached main unit Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC642TLE2, AX21E2
Model Appearance Panel color Height (mm) 210 210 210 210 Width (mm) 910 1180 1595 1595Main unit Depth (mm) 680 680 680 680 Height (mm) ———— Width (mm) ———— Depth (mm) ————
Gas side (mm) 12.7 15.9 15.9 15.9
Connecting pipe
Sound pressure level H/M/L (dB•A) 36/33/30 38/36/33 41/38/35 43/40/37 Sound power level H/M/L (dBA) 51/48/45 53/51/48 56/53/50 58/55/52
Liquid side (mm) 6.4 9.5 9.5 9.5 Drain port (mm) VP25
* : IEC standard, ** : AS standard
– 13 –
<Super Digital Inverter>
Model
Cooling capacit y (kW) 5.0 7.1 10.0 12.5 Heating capacity (kW) 5.6 8.0 11.2 14.0 Power supply 1 phase 230V (220 – 240V) 50Hz
Cooling
Electrical characteristics
Heating
Indoor unit RAV- SM562CT-E SM802CT-E SM1102CT-E SM1402CT-E Outdoor unit RAV- SP562AT-E SP80 2AT-E SP1102AT-E SP1402AT-E
Running current (A) 6.61 – 6.06 9.47 – 8.93 11.24 – 10.31 18.09 – 16.58 Power consumption (kW) 1.41 2.10 2.40 3.90 Power factor (%) 97 98 97 98 EER (W/W) 3.55 3.38 4.17 3.21 Energy efficiency class * A A A A Energy rating ** ———— Running current (A) 7.03 – 6.44 10.20 – 9.35 11.72 – 10.74 17.39 – 15.94 Power consumption (kW) 1.50 2.20 2.50 3.75 Power factor (%) 97 98 97 98 COP (W/W) 3.73 3.64 4.48 3.73 Energy efficiency class * A A A A Energy rating ** ————
Main unit Shine white
Ceiling panel
(Sold separately)
Outer dimension
Ceiling panel
(Sold separately)
Main unit (kg)21253333 Total weight
Ceiling panel (Sold separately) (k g) ———— Heat exchanger Finned tube
Fan Centrifugal Centrifugal Centrifugal Centrifugal
Standard air flow H/M/L (m³/min) 13.0/11.2/10.0 18.5/16.7/14.6 27.5/24.0/21.2 30.0/26.0/23.1Fan unit
Motor (W) 30 40 80 80 Air filter Attached main unit Controller (Sold separately) RBC-AMT31E2, AS21E2, TCB-SC642TLE2, AX21E2
Model Appearance Panel color Height (mm) 210 210 210 210 Width (mm) 910 1180 1595 1595Main unit Depth (mm) 680 680 680 680 Height (mm) ———— Width (mm) ———— Depth (mm) ————
Gas side (mm) 12.7 15.9 15.9 15.9
Connecting pipe
Sound pressure level H/M/L (dB•A) 36/33/30 38/36/33 41/38/35 43/40/37 Sound power level H/M/L (dBA) 51/48/45 53/51/48 56/53/50 58/55/52
Liquid side (mm) 6.4 9.5 9.5 9.5 Drain port (mm) VP25
* : IEC standard, ** : AS standard
– 14 –
1-1-4. Twin T ype
<Digital Inverter>
Type 4-Way Air Cassette Concealed Duct Under Ceiling
Model
Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 1 1.2 14.0
Power supply 1 phase 230V (220 – 240V) 50Hz
Electrical characteristics
Fan unit
Sound pressure level H /M/L (dB•A) 32/29/27 34/31/28 40/37/33 40/37/34 36/33/30 38/36/33 Sound power level H/M/L (dB•A) 47/44/42 49/46/43 55/52/48 55/52/49 51/48/45 53/51/48
Power supply 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
Inter connecting pipes
Fan unit
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 53/54 53/54 53/54 53/54 53/54 53/54 Sound power level Cooling/Heating (dB•A) 70/71 70/71 70/71 70/71 70/71 70/71
Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E SM1102AT-E SM1402AT-E
Indoor unit
Running current (A) 16.33–14.97 19.17–17.57 16.51–15.14 20.71–18.99 16.28–14.92 21.18–19.42 Power consumption (kW) 3.52 4.09 3.56 4.42 3.51 4.52
Cooling
Heating
Fan Turbo fan Turbo fan Centrifugal Centrifugal Centrifugal Centrifugal Standard air flow H/M/L (m³/min) Motor (W) 60 60 120 120 30 40
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5 Min. length (m) 5 .0 5.0 5.0 5.0 5.0 5.0 Max. total length (m) 50 50 50 50 50 50 Over 30m 40g/m (31m to 50m)
Height difference
Fan Propeller fan Standard air flow high (m³/min)757575757575 Motor (W) 100 100 100 100 100 100
Gas side
Liquid side
Power factor(%)989798979897 EER (W/W) 2.84 3.06 2.81 2.83 2.85 2.72 Energy efficiency class * C B C C C D Running current (A) 14.56–13.35 18.74–17.18 14.56–13.35 18.88–17.31 14.84–13.61 19.40–17.78 Power consumption (kW) 3.14 4.00 3.14 4.03 3.20 4.14 Power factor(%)989798979897 COP (W/W) 3.57 3.50 3.57 3.47 3.50 3.38 Energy efficiency class * B B B B B C
17 . 5/13 .9 /12.1 20. 0/15 .7 /13.6
Outdoor unit
Outdoor lower (m) 30 30 30 30 30 30 Outdoor high(m)303030303030
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9 Sub (mm) 12.7 15.9 12.7 15.9 12.7 15.9 Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5 Sub (mm) 6.4 9.5 6.4 9.5 6.4 9.5
13.0/1 1.9/9 .8
19 . 0/16 .2 /13.3 13 . 0/11.2/10.0 18. 5/16 .7/14 .6
– 15 –
* : IEC standard
<Super Digital Inverter>
Type 4-Way Air Cassette Concealed Duct Under Ceiling
Model
Cooling capacity (kW) 10.0 12.5 10.0 12.5 10.0 12.3 Heating capacity (kW) 11.2 14.0 11.2 14.0 1 1.2 14.0
Power supply 1 phase 230V (220 – 240V) 50Hz
Electrical characteristics
Fan unit
Sound pressure level H /M/L (dB•A) 32/29/27 34/31/28 40/37/33 40/37/34 36/33/30 38/36/33 Sound power level H/M/L (dB•A) 47/44/42 49/46/43 55/52/48 55/52/49 51/48/45 53/51/48
Power supply 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
Inter connecting pipes
Fan unit
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 49/51 53/54 49/51 53/54 49/51 53/54 Sound power level Cooling/Heating (dB•A) 66/68 70/71 66/68 70/71 66/68 70/71
Indoor unit 1 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Indoor unit 2 RAV- SM562UT-E SM802UT-E SM562BT-E SM802BT-E SM562CT-E SM802CT-E Outdoor unit RAV- SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E SP1102AT-E SP1402AT-E
Indoor unit
Running current (A) 11.24–10.31 16.51–15 .14 1 1. 72–10.74 18.09–16.58 11.24–10.31 18.09–16.58 Power consumption (kW) 2.40 3.56 2.50 3.90 2.40 3.90
Cooling
Heating
Fan Turbo fan Turbo fan Centrifugal Centrifugal Centrifugal Centrifugal Standard air flow H/M/L (m³/min) Motor (W) 60 60 120 120 30 40
Standard length (m) 7.5 7.5 7.5 7.5 7.5 7.5 Min. length (m) 5 .0 5.0 5.0 5.0 5.0 5.0 Max. total length (m) 50 50 50 50 50 50 Over 30m 40g/m (31m to 50m)
Height difference
Fan Propeller fan Standard air flow high (m³/min) 125 125 125 125 125 125 Motor (W) 63 + 63 63 + 63 63 + 63 63 + 63 63 + 63 63 + 63
Gas side
Liquid side
Power factor(%)979897989798 EER (W/W) 4.17 3.51 4.00 3.21 4.17 3.21 Energy efficiency class * A A A A A A Running current (A) 11.95–10.95 16.60–15 .22 1 1. 95–10.95 16.70–15.31 11.95–10.95 17.39–15.94 Power consumption (kW) 2.55 3.58 2.55 3.60 2.55 3.75 Power factor(%)979897989798 COP (W/W) 4.39 3.91 4.39 3.89 4.39 3.79 Energy efficiency class * A A A A A A
17.5/13.9/12.1 20.0/15.7/13.6
Outdoor unit
Outdoor lower (m) 30 30 30 30 30 30 Outdoor high(m)303030303030
Main (mm) 15.9 15.9 15.9 15.9 15.9 15.9 Sub (mm) 12.7 15.9 12.7 15.9 12.7 15.9 Main (mm) 9.5 9.5 9.5 9.5 9.5 9.5 Sub (mm) 6.4 9.5 6.4 9.5 6.4 9.5
13.0/1 1.9/9 .8
19.0/16.2/13.3 13.0/11.2/10.0 18.5/16.7/1 4.6
– 16 –
* : IEC standard
1-2. Outdoor Unit
g
<Digital Inverter>
Model name Power supply 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
Ty pe Hermetic comp re sso r Motor (kW) 1.1 1.6 2.5 3.0Compressor
Pole 4 4 4 4 Refrigerant char ged (kg) 1.0 1.7 2. 8 2.8 Refrigerant control Pulse motor valve
Standard length (m) 7.5 7.5 7.5 7.5
Min. length (m) 5.0 5.0 5.0 5.0
Inter connecti n pipe
Outer dimension
Max. total length (m) 30 30 50 50
Additional refrigerant charge under
long piping connector
Height
difference
Height (mm) 550 550 795 795
Width (mm) 780 780 900 900
Depth (mm) 290 290 320 320
Outdoor lower (m) 30 30 30 30 Outdoor higher (m ) 30 30 30 30
RA V- SM562AT-E SM802AT-E SM1102AT-E SM1402AT-E
20g/m
(21m to 30m)
40g/m
(21m to 30m)
40g/m
(31m to 50m)
40g/m
(31m to 50m)
Appearance Silky shade (Muncel 1Y8.5/0.5) Total weight (kg) 38 42 77 77 Heat exchanger Finned tube
Fan Propeller fan Standard air flow (m³/h) 40 45 75 75Fan unit Motor (W) 43 43 100 100
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 46/48 48/50 53/54 53/54 Sound power level Cool ing/Heating (dB•A) 63/65 65/67 70/71 70/71 Outside air temperature, Cooling (°C) 43 to –15 Outside air temperature, Heating (°C) 15 to –15
Gas side (mm) 12.7 15.9 15.9 15.9 Liquid side (mm) 6.4 9.5 9.5 9.5
– 17 –
<Super Digital Inverter>
g
Model name Power supply 1 phase 230V (220 – 240V) 50Hz (Power exclusive to outdoor is required.)
Ty pe Hermetic comp re sso r
Motor (kW) 2.0 2.0 3.75 3.75Compressor
Pole 4 4 4 4 Refrigerant char ged (kg) 1.5 2.1 2.95 2.95 Refrigerant control Pulse motor valve
Standard length (m) 7.5 7.5 7.5 7.5
Min. length (m) 5.0 5.0 5.0 5.0
Inter connecti n pipe
Outer dimension
Max. total length (m) 50 50 70 70
Additional refrigerant charge under
long piping connector
Height
difference
Height (mm) 795 795 1340 1340
Width (mm) 900 900 900 900
Depth (mm) 320 320 320 320
Outdoor lower (m) 30 30 30 30 Outdoor higher (m ) 30 30 30 30
RA V- SP562AT-E SP802AT-E SP1102AT-E SP1402AT-E
20g/m
(21m to 50m)
40g/m
(31m to 50m)
40g/m
(31m to 70m)
40g/m
(31m to 70m)
Appearance Silky shade (Muncel 1Y8.5/0.5) Total weight (kg) 55 62 95 95 Heat exchanger Finned tube
Fan Propeller fan Standard air flow (m³/h) 57 57 125 125Fan unit Motor (W) 63 63 63 + 63 63 + 63
Connecting pipe
Sound pressure level Cooling/Heating (dB•A) 46/47 47/49 49/51 53/54 Sound power level Cool ing/Heating (dB•A) 63/64 64/66 66/68 70/71 Outside air temperature, Cooling (°C) 43 to –15 Outside air temperature, Heating (°C) 15 to –15
Gas side (mm) 12.7 15.9 15.9 15.9 Liquid side (mm) 6.4 9.5 9.5 9.5
– 18 –
1-3. Operation Characteristic Curve
• Operation characteristic curve <Digital Inverter>
RAV-SM562AT-E, RAV-SM802AT-E
<Cooling> <Heating>
14
12
10
8
6
Current (A)
4
2
0
0 20 40 60708090100
RAV-SM802AT-E
RAV-SM802AT-E
RAV-SM562AT-E
RAV-SM562AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
16
14
RAV-SM802AT-E
12
10
8
RAV-SM802AT-E
Current (A)
6
4
2
0
0 20406080100120
RAV-SM562AT-E
RAV-SM562AT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
RAV-SM1102AT-E, RAV-SM1402AT-E
<Cooling> <Heating>
22 22
20
RAV-SM1102AT-E
RAV-SM1102AT-E
18
16
14
12
10
Current (A)
8
6
4
2
0
0204060
RAV-SM1402AT-E
RAV-SM1402AT-E
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
20
18
RAV-SM1402AT-ERAV-SM1402AT-E
16
14
12
10
Current (A)
8
6
4
2
0
0 204060
Compressor speed (rps)
RAV-SM1102AT-ERAV-SM1102AT-E
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
80 100 120
Compressor speed (rps)
19
• Operation characteristic curve <Super Digital Inverter>
RAV-SP562AT-E, RAV-SP802AT-E
<Cooling> <Heating>
14
12
RAV-SP802AT-E
RAV-SP802AT-E
10
8
6
Current (A)
4
2
0
0 20406050 70 80 100
RAV-SP562AT-ERAV-SP562AT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps) Compressor speed (rps)
16
14
RAV-SP802AT-E
12
10
RAV-SP562AT-E
RAV-SP562AT-E
8
RAV-SP802AT-E
Current (A)
6
4
2
0
0 204060 908070 100
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
RAV-SP1102AT-E, RAV-SP1402AT-E
<Cooling> <Heating>
22
20
18
16
14
12
10
RAV-SP1402AT-E
RAV-SP1402AT-E
Current (A)
8
RAV-SP1102AT-E
6
4
2
0
020406080
RAV-SP1102AT-E
Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length : 7.5m 230V
22
20
18
16
14
12
10
Current (A)
8
6
4
2
0
020406080
RAV-SP1402AT-E
RAV-SP1402AT-E
RAV-SP1102AT-E
RAV-SP1102AT-E
Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Air flow : High Pipe length : 7.5m 230V
Compressor speed (rps)
Compressor speed (rps)
20
• Capacity variation ratio according to temperature
RAV-SM562AT-E, RAV-SM802AT-E, RAV-SM1102AT-E, RAV-SM1402AT-E RAV-SP562AT-E, RAV-SP802AT-E, RAV-SP1102AT-E, RAV-SP1402AT-E
<Cooling> <Heating>
105
100
95
90
85
80
75
70
Capacity ratio (%)
65
60
55
50
32 33 34 35 36 37 38 39
Outsoor temp. (˚C)
Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 7.5m
40
41 42 43
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20 10
0
-14-12-10-8-6-4-20246810
Conditions Indoor : DB20˚C Indoor air flow : High Pipe length : 7.5m
Outsoor temp. (˚C)
21
2. AIR DUCTING WORK
2-1. Static Pressure Characteristics of Each Model
RAV-SM562BT-E, RAV-SM802BT-E, RAV-SM1102BT-E, RAV-SM1402BT-E
Fig. 1 RAV-SM562BT-E (Round duct)
140
120
100
Usable lim
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
0 500 700 780 900
Standard air volume 780m³/h
High static pressure 2H tap
it
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume m³/h
140
120
100
80
60
Static pressure (Pa)
40
Air volume limit (Max.)
20
Fig. 3 RAV-SM802BT-E (Round duct)
Standard air volume 1140m³/h
High static pressure 2H tap
Usable limit
Air volume limit (Min.)
0 800
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1000
Air volume m³/h
Air volume limit (Max.)
12001140 1300
Fig. 2 RAV-SM562BT-E (Square duct)
140
120
108 100
80
60
Usable limit
Static pressure (Pa)
40
Air volume limit (Min.)
20
0 500 700 780 900
Standard air volume 780m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume m³/h
140
120
100
80
60
Static pressure (Pa)
40
Air volume limit (Max.)
20
Fig. 4 RAV-SM802BT-E (Square duct)
Standard air volume 1140m³/h
High static pressure 2H tap
Usable limit
Air volume limit (Min.)
0 800
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1000
Air volume m³/h
Air volume limit (Max.)
12001140 1300
22
0
Fig. 5 RAV-SM1102BT-E (Round duct)
Fig. 7 RAV-SM1402BT-E (Round duct)
140
120
Standard air volume 1620m³/h
140
120
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 2H tap
100
100
Usable limit
High static pressure 1H tap
80
60
Standard H tap
Static pressure (Pa)
40
Air volume limit (Min.)
20
0
1200
Low static pressure H tap
Standard L tap
1620
Air volume limit (Max.)
2000
80
60
Static pressure (Pa)
40
20
0 1200 1800
Air volume m³/h
Usable limit
Air volume limit (Min.)
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
1980
Air volume m³/h
Air volume limit (Max.)
2200 2400
Fig. 6 RAV-SM1102BT-E (Square duct)
140
120
Usable limit
100
80
60
Static pressure (Pa)
40
Air volume limit (Min.)
20
Low static pressure H tap
Standard air volume 1620m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Standard L tap
Air volume limit (Max.)
Fig. 8 RAV-SM1402BT-E (Square duct)
140
120
100
80
60
Usable limit
Static pressure (Pa)
40
Air volume limit (Min.)
20
Standard air volume 1980m³/h
High static pressure 2H tap
High static pressure 1H tap
Standard H tap
Low static pressure H tap
Standard L tap
Air volume limit (Max.)
0
1200
1620
Air volume m³/h
2000
– 23 –
0 1200 1800
Air volume hm³/h
1980
2200 240

3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)

3-1. Indoor Unit
3-1-1. 4-Way Air Discharge Cassette Type
RAV-SM562UT-E, RAV-SM802UT-E
Surface under ceiling
200
113
173
Refrigerant pipe connecting port A
130
200
Check port (¨450)
Check port (¨450)
Cable draw-in port
45
Refrigerant pipe connecting port B
Electric parts box
860 to 910 Recommended external size
30
105
270 25070
950 Panel external dimension
790 Hanging bolt pitch
346.5
860 to 910 Recommended external size
Surface under ceiling
Hanging bolt M10 or W3/8 Procured locally
130
210
360
Indoor unit
Standing 640 or less
Standing 850 or less
Drain up standing size
256
Surface under ceiling
88
SM562 SM802
840 Unit external dimension
A
Ø6.4 Ø9.5
150
105
Ø12.7 Ø15.9
Knockout
97
35
Z view
for humidifier
Ceiling panel (Sold separately)
Surface under ceiling
80
Ø162
B
415.0
105105
240
254.5
840 Hanging bolt
480
227
12097
Surface under ceiling
381.6 227
480
723 Hanging bolt pitch
950 Panel external dimension
35
˚
64
57
57.5
25
188
Surface under ceiling
120
24
RAV-SM1102UT-E, RAV-SM1402UT-E, RAV-SP1102UT-E
860 to 910 Recommended external size
200
Check port (¨450)
200
Check port (¨450)
Take-in port of pipes
45
30
SM1102UT SM1402UT SP1102UT
860 to 910 Recommended external size
Ceiling bottom surface
A
B
Ø12.7
Ø15.9
Ø12.7
Ø15.9
Ø9.5 319183Ø15.9
Standing 850 or less
Standing 640 or less
C
120 183
D
256 319
113
173
Refrigerant pipe connecting port
Ceiling bottom surface
A
Refrigerant pipe connecting port B
130
Ø162
105
80
Electric parts box
434.5
240
105 105
840 Unit external dimension
105
105
270
250
70
860 to 910 Ceiling opening dimension
950 Panel external dimension
790 Hanging bolt pitch
Knockout square hole for divide duct For Ø150
345.5
130
210
Drain pipe connecting port
Hanging bolt M10 or Ø3/8 (To be procured locally)
381.6 227
480
723 Hanging bolt pitch
950 Panel external dimension
860 to 910 Ceiling opening dimension
35˚
360
Indoor unit
Drain up standing size
D
88
Surface under ceiling
Ceiling panel (sold separately)
Ø162
105
Ceiling bottom surface
Knockout square hole for divide duct for Ø150 (2 positions)
C97
254.5
840 Unit external dimension
480
227
25
57.5
188
57
25
C
64
Z view
Surface under ceiling
97
35
Ceiling bottom surface
3-1-2. Concealed Duct Type
RAV-SM562BT-E, RAV-SM802BT-E, RAV-SM1102BT-E, RAV-SM1402BT-E
129
110
Knock-out hole Ø125 (Air take-in port)
6-Ø4 T apping screw undersized hole Ø160
• Dimension
Discharge port flange N-Ø200
60 to 260 9
Suction port canvas (Separate sold)
Refrigerant pipe connecting port (Gas side ØF)
Hanging bolt pitch B
Main unit dimension A
J = M x K H
C
Ceiling open size D
Panel external dimension E
Hanging bolt 4-M10 screw (Arranged locally)
44 49
Refrigerant pipe connecting port (Liquid side ØG)
Drain pipe connecting port for vinyl chloride pipe (Inner dia. 32, VP. 25)
75
Main unit dimension 800
Hanging bolt pitch 700
50
131
50
Ø26 Power supply, remote controller cable take-out port
638
498
393
41
196
243
Panel C.L
410
Ceiling open size
470
Panel external dimension 500
5941
174
Suction port flange (Separate sold)
Suction port panel (Separate sold)
320
ABCDEFGHJKMNO
RAV-SM562BT
RAV-SM802BT
RAV-SM1102BT RAV-SM1402BT
700 766 690 750 780 12.7 6.4 252 280 280 1 2 410 1000 1066 990 1050 1080 15.9 9.5 252 580 290 2 3 410
1350 1416 1340 1400 1430 15.9 9.5 252 930 310 3 4 410
NOTE 1 :
For maintenance of the equipment, be sure to install a check port A at the position as shown below.
NOTE 2 :
Using the drain up kit sold separately, drain-up by 300 (mm) from drain pipe draw-out port of the main unit is necessary. The drain-up over 300mm or more is impossible.
Plane view of main unit
(Pipe side)
Discharge side
Check port A
300
100
450
– 26 –
3-1-3. Under Ceiling Type
RAV-SM562CT-E, RAV-SM802CT-E, RAV-SM1102CT-E, RAV-SM1402CT-E
128
84
170320
(Hanging position)
Hanging bolt
50
Within
Upper pipe draw-out port (Knockout hole)
Power supply cable take-in port (Knockout)
Remote controller cable take- in port (Knockout hole)
53
Left drain size
B (Hanging position)
Refrigerant pipe (Gas side ØD)
Ceiling surface
Unit
Refrigerant pipe (Liquid side ØC)
A
216
110
70
75 97
76
50
130
680
Drain pipe connecting port
146
145
Pipe hole on wall (Ø100 hole)
210
167
105
347
262
135 84
Outside air take-in port (Duct sold separately)(Knockout hole Ø92)
Pipe draw-out port (Knockout hole)
Drain port VP20 (Inner dia. Ø26, hose attached)
114
41
200 (Liquid pipe)
216 (Gas pipe)
Remote controller cable take- in port
Power supply cable take-in port (Knockout hole)
Remote controller cable take- in port
90
32
(Knockout hole)
92
Drain left pipe draw-out port (Knockout hole)
32
171
Wireless sensor mounting section
250 or more250 or more
Model name A B C D 562CT 802CT 1102CT, 1402CT
910 1180 1595
855 1125 1540
Ø6.4 Ø12.7
Ø9.5 Ø15.9
500 or more
– 27 –
3-2. Outdoor Unit
RAV-SM562AT-E, RAV-SM802AT-E
Drain hole (2-Ø20 × 88 long hole)
69.5 147
320
306
Ø6 hole pitch
For anchor bolt)
(Long hole pitch
21
550
290
A legs
6
48335
30
B legs
44952
Drain hole (Ø25)
60
600
108 125
30
20
2-Ø11 × L14 long hole (For Ø8-Ø10 anchor bolts)
483 257
108
90
2-Ø11-14 U-shape hole
54
(For Ø8-Ø10 anchor bolts)
Connecting pipe port Gas flare side RAV-SM562AT -E: Ø12.7
( )
RAV-SM802AT -E: Ø15.9 Connecting pipe port
Liquid flare side RAV-SM562AT-E: Ø6.4
( )
RAV-SM802AT-E: Ø9.5
8-Ø6 hole (For fixing outdoor unit)
25 22
157 79
21
145
31 143
8
Space required for service
2-Ø11 × 14 U-shape holes (For Ø8–Ø10 anchor bolt)
32
Discharge guard
150 or more
320
500 or more
600
54 38
R15
3
320
Ø11 × 14 U-shape hole
Details of A legs Details of B legs
2-Ø6 hole
Product external line
150
or more
500
780
600
Suction port
Discharge port
Discharge guide mounting hole (4-Ø4.5 embossing)
Discharge port
Ø11 × 14 U-shape holes
320
3
137
93
71
300 or more
(Minimum distance up to wall)
2-Ø11 × 14 long hole (For Ø8–Ø10 anchor bolt)
2-Ø6 hole
Product external line
R15
38 54
600
Charge port
342
54
Earth
terminal
28
RAV-SM1102AT-E, RAV-SM1402AT-E / RAV-SP562AT-E, RAV-SP802AT-E
Knockout (For draining)
21
Suction port
365 17.517.5
40 70
(Long hole pitch
for anchor bolt)
21
565 101
Drain hole (Ø20 × 88 Burring hole)
29 90 191 20
Knockout (For draining)
6026
314
43
Suction port
Discharge port
300150 900
Drain hole (Ø25 Burring hole)
Part B
40
39
Part A
95
43
Handles (Both sides)
Refrigerant pipe connecting port Flare at liquid side Ø6.4: RAV-SP562AT-E
( )
Ø9.5: RAV-SP802AT-E Refrigerant pipe connecting port
Flare at gas side Ø12.7: RAV-SP562AT-E
( )
Ø15.9: RAV-SP802AT-E
47
Installation bolt hole (Ø12 × 17 U-shape holes)
17.5 4040
Details of B part
Details of A part
17.5
Installation bolt hole (Ø12 × 17 U-shape holes)
2
Discharge guide mounting hole (4-Ø4 Embossing)
1
60 90
58
27
161
32028
400
264
300
795
25
85
2
Z
2
46
165
60 80
30 45
1
307
2760
96
2-Ø12 × 17 U-shape holes (For Ø8–Ø10 Anchor bolt)
264
6760
154
1
Knockout for lower piping
Space required for service
150 or more
365
500 or more
Z views
Suction port
150
or more
Discharge port
600
86 7
7 58
150 or more
Discharge port
(Minimum distance up to wall)
2-Ø12 × 17 long hole (For Ø8–Ø10 Anchor bolt)
29
RAV-SP1102AT-E, RAV-SP1402AT-E
Knockout (Drain)
365 17.517.5
350 625
Discharge guide mounting port (8-Ø3 embossing)
70 21
Suction port
21 40
9029
Knockout (Drain)
26
150
56567 60 565
164 300
314
Drain hole (Ø20 x 88)
191 20
Suction port
Drain hole (Ø25)
43
60
Discharge port
600 900
B legs
A legs
40
43
40
108
Refrigerant pipe connecting port (Ø9.5 flare at liquid side)
Refrigerant pipe connecting port (Ø15.9 flare at gas side)
54
28
706
715
67
154
60 27
z
95
307 400
60
60 90
27
Mountig bolt hole (Ø12 x 17 long hole)
161
320
58
1340
89
25
Mountig bolt hole (Ø12 x 17 U-shape hole)
12
20
46
8060
165
32 45
40
Details of A legs Details of B legs
2-Ø12 x 17 U-shape holes (For Ø8–Ø10 anchor bolt)
150 or more
365
30
40
86 7
Z view
58 7
Space required for service
600
Suction port
150
or more
Discharge port
500 or more
Discharge port
2-Ø12 x 17 long hole (For Ø8–Ø10 anchor bolt)
150 or more
(Minimum distance up to wall)
Loading...
+ 164 hidden pages