Toshiba RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-B13GKVP-E, RAS-4M27GAV-E, RAS-M16GKCVP-E Service Manual

...
R410A
FILE NO. A05-011
PRINTED IN JAPAN, Dec.,2005 ToMo
SERVICE MANUAL
SPLIT TYPE
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
RAS-4M27GAV-E
RAS-4M27GA CV-E
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
RAS-3M26GAV-E
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
– 2 –
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 3
2. SPECIFICATIONS ..................................................................................... 5
3. REFRIGERANT R410A ........................................................................... 24
4. CONSTRUCTION VIEWS ........................................................................ 32
5. WIRING DIAGRAM.................................................................................. 34
6. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 36
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 37
8. CONTROL BLOCK DIAGRAM................................................................ 45
9. OPERATION DESCRIPTION................................................................... 48
10. INSTALLATION PROCEDURE................................................................ 72
11. HO W TO DIAGNOSE THE TROUBLE...................................................... 87
12. HOW TO REPLACE THE MAIN PARTS................................................. 107
13. EXPLODED VIEWS AND PARTS LIST................................................. 123
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
3
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm² (H07RN-F or 245IEC66) polychloroprene sheathed flexible cord.
Read this SAFETY PRECAUTIONS” carefully bef ore servicing.
The precautions described below include the important items regarding safety. Observe them without fail.
After the servicing work, perform a trial operation to check for any problem.
Turn off the main power supply s witch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore , during installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact separation of at least 3 mm.
The installation fuse (25A D type ) must be used for the power supply line of this air conditioner.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO IN­STALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated. Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR­RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
4
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE
TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE­FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PER­SONNEL INJURIES.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source such as a cooking range, noxious gas may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires f or telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
Exposure of unit to water or other moisture bef ore installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed f or a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner. For details, contact the dealer.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
5
2. SPECIFICATIONS
The indoor and outdoor units that can be used in combination are shown in the tables below.
Table of models that can be connected
Table of models that can be used in combination
NOTES
A 1-room connection is not an option for the indoor units (you cannot connect only one indoor unit). Be sure to connect indoor units in two rooms or more.
The contents noted in this service manual limit the indoor units to the RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E, RAS-M10GKCVP-E, RAS-M13GKCVP-E and RAS-M16GKCVP-E.
For other indoor units that can also be used in combination, see the service manual of each indoor unit.
Indoor unit
RAS-M10GDV-E RAS-M10GDCV-E RAS-M13GDV-E RAS-M13GDCV-E RAS-M16GDV-E RAS-M16GDCV-E RAS-M10GKV-E RAS-M10GKCV-E RAS-M13GKV-E RAS-M13GKCV-E RAS-M16GKV-E RAS-M16GKCV-E
File No.
A05-010
TBA
Type
Heat pump
Cooling-only
Outdoor unit
RAS-3M26GAV-E RAS-4M27GAV-E
RAS-4M27GACV-E
Indoor unit
RAS-B10GKVP–E RAS-B13GKVP–E RAS-B16GKVP–E RAS-M10GKV–E RAS-M13GKV–E RAS-M16GKV–E RAS-M10GDV–E RAS-M13GDV–E RAS-M16GDV–E RAS-M10GKCVP–E RAS-M13GKCVP–E RAS-M16GKCVP–E RAS-M10GKCV–E RAS-M13GKCV–E RAS-M16GKCV–E RAS-M10GDCV–E RAS-M13GDCV–E RAS-M16GDCV–E
Type
Heat pump
Cooling-only
Outdoor unit
RAS-3M26GAV-E RAS-4M27GAV-E RAS-3M26GACV-E
Combinations of indoor unit models that can be connected
Refer to page 17 to 22 Refer to page 8 to 13 Refer to page 14 to 16
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
– 6 –
Indoor
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E
Unit model
Outdoor
RAS-4M27GAV-E RAS-3M26GAV-E
Cooling capacity (kW) 8.0 7.5 Cooling capacity range (kW) 1.4 – 9.2 1.4 – 8.9 Heating capacity (kW) 9.0 9.0 Heating capacity range (kW) 0.8 – 11.0 0.8 – 10.8 Power supply 220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz
Unit model
RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E
Running current (A) 0.15 0.15 0.15 Power consumption (W) 30 30 30
Indoor
Power factor (%) 91/87/83 91/87/83 91/87/83 Unit model
RAS-4M27GAV-E RAS-3M26GAV-E
Operation mode
Cooling Heating Cooling Heating
Running current (A)
11.60/11.09/10.63 10.44/9.98/9.57 10.44/9.98/9.57 11.83/11.31/10.84
Power consumption (W) 2500 2250 2250 2550 Power factor(%)98989898
Electric characteristics
Outdoor
Starting current (A) 11.60/11.09/10.63 11.83/11.31/ 10.84
COP (Cool ing/Heati ng) 3.20/4.00 3.33/3.53
Unit model
RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E
High (dBA) 42/43 43/44 45/45 Medium (dBA) 33/34 34/35 36/36
Indoor (Coolin
g
/Heating)
Low (dBA) 27/27 27/27 29/29 Unit model
RAS-4M27GAV-E RAS-3M26GAV-E
Operating noise
Outdoor (Coolin
g
/Heating)
Full indoor units operatin
g
(dBA) 48/48 48/48
Unit model
RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E
Height (mm) 250 250 250 Width (mm) 790 790 790Dimension
Depth (mm) 215 215 215 Net weight (kg)9 9 9 Fan motor output (W) 30 30 30
Indoor unit
Air flow rate (Cooling/Heating) (m³/h) 550/610 560/640 640/660 Unit model
RAS-4M27GAV-E RAS-3M26GAV-E
Height (mm) 795 795
Width (mm) 900 900Dimension
Depth (mm) 320 320 Net weight (kg)65 64
Motor output (W) 2000
Type Twin rotary type with DC-invert er variable speed control
Compressor
Model DA220A2F-20L Fan motor output (W) 60 Air flow rate (m³/h) High : 3000, Medium : 2800
Outdoor unit
Type Flare connection
Unit model
RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E
Indoor unit
Liquid side/Gas side Ø6.35/ Ø9.52 Ø6.35/ Ø9.52 Ø6.35/ Ø12.7
Unit model
RAS-4M27GAV-E RAS-3M26GAV-E
A unit liquid side/Gas side Ø6.35/ Ø12.7 Ø6.35/ Ø12.7
B unit liquid side/Gas side Ø6.35/ Ø9.52 Ø6.35/ Ø9.52
C unit liquid side/Gas side Ø6.35/ Ø9.52 Ø6.35/ Ø9.52
Outdoor unit
D unit liquid side/Gas side Ø6.35/ Ø9.52 Maximum length (per unit) (m) 25 25 Maximum length (total) (m) 70 50 Maximum chargeless length (m) 70 50 Maximum height difference (m) 15 15 Name of refrigerant R410A
Piping connection
Weight (k
g
)2.4
Power supply 3 Wires : includes earth
Wiring connection
Interconnection 4 Wires : includes earth Indoor (Cooling/Heating)(°C) 21 to 32/0 to 28
Usable temperature range
Outdoor (Coolin
g
/Heating)(°C) 10 to 43/–5 to 24
Unit model
RAS-B10GKVP-E RAS-B13GKVP-E RAS-B16GKVP-E
Installation plate 1 1 1 Wireless remote controller 1 1 1 Batteries 2 2 2 Remote controller holder 1 1 1 Zeolit e-plus filter 1 1 1 Plasma pure filter 1 1 1 Remote controller holder mounting screw 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L) Owners manual 1 1 1 Mounting screw 6 (Ø4 × 25L) 6 (Ø4 × 25L) 6 (Ø4 × 25L)
Indoor unit
Installation manual 1 1 1 Unit model
RAS-4M27GAV-E RAS-3M26GAV-E
Installation manual 1 1
Accessory
Outdoor unit
Specifications 1 1
For perfor mance when each indoor unit is combined with other unit, refer to the separate table.
The specifications may be subject to change without notice for purpose of improvement.
2-1. Specifications
<Heat Pump Models>
RAS-B10GKVP-E, RAS-B13GKVP-E, RAS-B16GKVP-E / RAS-4M27GAV-E, RAS-3M26GAV-E
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
7
For perfor mance when each indoor unit is combined with other unit, refer to the separate table.
The specifications may be subject to change without notice for purpose of improvement.
<Cooling Only Models>
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E / RAS-4M27GACV-E
Indoor
RAS-M10GKCVP-E, RAS-M13GKCVP-E, RAS-M16GKCVP-E
Unit model
Outdoor
RAS-4M27GACV- E
Cooling capacity (kW) 8.0 Cooling capacity range (kW) 1.4 – 9.2 Heating capacity (kW) — Heating capacity range (kW) — Power supply 220–240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz
Unit model
RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E
Running current (A) 0.15 0.15 0.15 Power consumption (W) 30 30 30
Indoor
Power factor (%) 91/87/83 91/87/83 91/87/83 Unit model
RAS-4M27GACV- E
Running current (A) 11.60/11.09/10.63 Power consumption (W) 2500 Power factor (%) 98
Electric characteristics
Outdoor
Starting current (A) 11.60/11.09/10.63
COP 3.20
Unit model
RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E
High (dBA) 42 43 45 Medium (dBA) 33 34 36
Indoor
Low (dBA) 27 27 29 Unit model
RAS-4M27GACV- E
Operating noise
Outdoor
Full indoor units operating (dB•A) 48
Unit model
RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E
Height (mm) 250 250 250 Width (mm) 790 790 790Dimension
Depth (mm) 215 215 215 Net weight (kg) 9 9 9 Fan motor output (W) 30 30 30
Indoor unit
Air flow rate (m³/h) 550 560 640 Unit model
RAS-4M27GACV- E
Height (mm) 795
Width (mm) 900Dimension
Depth (mm) 320 Net weight (kg) 63
Motor output (W) 2000
Type Twin rotary type with DC-invert er variable speed controlCompressor
Model DA220A2F-20L Fan motor output (W) 60 Air flow rate (m³/h) High : 3000, Medium : 2800
Outdoor unit
Type Flare connection
Unit model
RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E
Indoor unit
Liquid side/Gas side Ø6.35/ Ø9.52 Ø6.35/ Ø9.52 Ø6.35/ Ø12.7
Unit model
RAS-4M27GACV- E
A unit liquid side/Gas side Ø6.35/ Ø12.7
B unit liquid side/Gas side Ø6.35/ Ø9.52
C unit liquid side/Gas side Ø6.35/ Ø9.52
Outdoor unit
D unit liquid side/Gas side Ø6.35/ Ø9.52 Maximum length (per unit) (m) 25 Maximum length (total) (m) 70 Maximum chargeless length (m) 70 Maximum height difference (m) 15 Name of refrigerant R410A
Piping connection
Weight (kg) 2.2
Power supply 3 Wires : includes earth
Wiring connection
Interconnection 4 Wires : includes earth
Indoor (°C ) 21 to 32
Usable temperature range
Outdoor (°C) 10 to 43
Unit model
RAS-M10GKCVP-E RAS-M13GKCVP-E RAS-M16GKCVP-E
Installation plate 1 1 1
Wireless remote controller 1 1 1
Batteries 2 2 2
Remote controller holder 1 1 1
Zeolit e-plus filter 1 1 1
Plasma pure filter 1 1 1
Remote controller holder mounting screw 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L) 2 (Ø3.1 × 16L)
Owners manual 1 1 1
Mounting screw 6 (Ø4 × 25L) 6 (Ø4 × 25L) 6 (Ø4 × 25L)
Indoor unit
Installation manual 1 1 1
Unit model
RAS-4M27GACV- E
Installation manual 1
Accessory
Outdoor unit
Specifications 1
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
8
2-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit
Outdoor Unit : RAS-4M27GAV-E
<Cooling/220V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capacity (kW)Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
220 1 unit 10 –––2.70 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.87
(3.68 to 4.64 )
48
13 –––3.70 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.74
(3.68 to 7.20 )
48
16 –––4.50 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.81
(3.68 to 9.28 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
7.10
(3.64 to 9.46 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.40
(3.75 to 10.30)
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.76
(3.92 to 11.92)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.83
(3.98 to 12.76)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
11.13
(4.80 to 12.62)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
11.18
(4.85 to 12.71)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
11.18
(4.85 to 12.94)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
11.18
(4.85 to 12.94)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
11.27
(4.90 to 13.03)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
11.27
(4.90 to 13.03)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
11.32
(4.90 to 13.13)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
11.32
(4.90 to 13.13)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
11.32
(4.90 to 13.36)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
11.36
(4.95 to 13.45)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
11.36
(4.70 to 12.99)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
11.36
(4.75 to 13.08)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.60
(4.75 to 13.27)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.60
(4.75 to 13.27)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.60
(4.80 to 13.36)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.60
(4.80 to 13.36)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
9
Outdoor Unit : RAS-4M27GAV-E
<Cooling/230V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
230 1 unit 10 –––2.7 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.71
(3.52 to 4.44 )
48
13 –––3.7 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.49
(3.52 to 6.88 )
48
16 –––4.5 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.47
(3.52 to 8.87 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.79
(3.48 to 9.05 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.03
(3.59 to 9.85 )
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.29
(3.75 to 11.40)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.31
(3.80 to 12.20)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
10.65
(4.59 to 12.07)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
10.69
(4.64 to 12.16)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.69
(4.64 to 12.38)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.69
(4.64 to 12.38)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.78
(4.69 to 12.47)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.78
(4.69 to 12.47)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.83
(4.69 to 12.56)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.83
(4.69 to 12.56)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
10.83
(4.69 to 12.78)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
10.87
(4.73 to 12.87)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
10.87
(4.49 to 12.42)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
10.87
(4.54 to 12.51)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.09
(4.54 to 12.69)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.09
(4.54 to 12.69)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.09
(4.59 to 12.78)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.09
(4.59 to 12.78)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
10
Outdoor Unit : RAS-4M27GAV-E
<Cooling/240V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
240 1 unit 10 –––2.7 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.55
(3.38 to 4.26 )
48
13 –––3.7 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.26
(3.38 to 6.60 )
48
16 –––4.5 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.16
(3.38 to 8.50 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.51
(3.33 to 8.67 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
7.70
(3.44 to 9.44 )
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
9.86
(3.59 to 10.93)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
10.84
(3.65 to 11.69)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
10.20
(4.40 to 11.56)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
10.25
(4.44 to 11.65)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.25
(4.44 to 11.86)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.25
(4.44 to 11.86)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.33
(4.49 to 11.95)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.33
(4.49 to 11.95)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.37
(4.49 to 12.03)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.37
(4.49 to 12.03)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
10.37
(4.49 to 12.24)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
10.42
(4.54 to 12.33)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
10.42
(4.31 to 11.90)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
10.42
(4.35 to 11.99)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
10.63
(4.35 to 12.16)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
10.63
(4.35 to 12.16)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
10.63
(4.40 to 12.24)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
10.63
(4.40 to 12.24)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
11
Outdoor Unit : RAS-4M27GAV-E
<Heating/220V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Unit capacity (kW)Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Heating
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
220 1 unit 10 –––4.0 –––
4.0
(0.8 to 5.2)
1450
(300 to 1980)
6.73
(1.87 to 9.18 )
48
13 –––5.0 –––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
9.51
(1.93 to 12.76)
48
16 –––5.5 –––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
11.13
(1.93 to 13.91)
48
2 units 10 10 ––3.60 3.60 ––
7.2
(1.5 to 10.0)
2100
(320 to 3200)
9.74
(1.94 to 14.84)
48
13 10 ––4.22 3.38 ––
7.6
(1.5 to 10.1)
2320
(320 to 3210)
10.76
(1.94 to 14.89)
48
16 10 ––4.57 3.33 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
11.50
(1.94 to 14.98)
48
13 13 ––3.95 3.95 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
11.50
(1.94 to 14.98)
48
16 13 ––4.35 3.95 ––
8.3
(1.5 to 10.2)
2700
(320 to 3240)
12.52
(1.94 to 15.03)
48
16 16 ––4.30 4.30 ––
8.6
(1.5 to 10.2)
2860
(320 to 3250)
13.27
(1.94 to 15.07)
48
3 units 10 10 10 2.87 2.87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
10.67
(2.16 to 12.76)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.90
(2.16 to 12.80)
48
16 10 10 3.54 2.58 2.58
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.90
(2.16 to 12.80)
48
13 13 10 3.11 3.11 2.49
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.90
(2.16 to 12.80)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2400
(380 to 2780)
11.13
(2.16 to 12.89)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2400
(380 to 2780)
11.13
(2.16 to 12.89)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2450
(380 to 2790)
11.36
(2.16 to 12.94)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2450
(380 to 2790)
11.36
(2.16 to 12.94)
48
16 16 13 3.06 3.06 2.78
8.9
(2.0 to 10.7)
2450
(380 to 2790)
11.36
(2.16 to 12.94)
48
16 16 16 3.00 3.00 3.00
9.0
(2.0 to 10.8)
2500
(380 to 2800)
11.60
(2.16 to 12.99)
48
4 units 10 10 10 10 2.23 2.23 2.23 2.23
8.9
(2.2 to 10.8)
2100
(450 to 2810)
9.74
(2.56 to 13.03)
48
13 10 10 10 2.62 2.09 2.09 2.09
8.9
(2.2 to 10.9)
2100
(460 to 2830)
9.74
(2.61 to 13.13)
48
16 10 10 10 2.83 2.06 2.06 2.06
9.0
(2.2 to 10.9)
2250
(460 to 2830)
10.44
(2.61 to 13.13)
48
13 13 10 10 2.50 2.50 2.00 2.00
9.0
(2.2 to 10.9)
2250
(470 to 2830)
10.44
(2.67 to 13.13)
48
16 13 10 10 2.68 2.43 1.95 1.95
9.0
(2.2 to 11.0)
2250
(480 to 2850)
10.44
(2.73 to 13.22)
48
13 13 13 10 2.37 2.37 2.37 1.89
9.0
(2.2 to 11.0)
2250
(480 to 2850)
10.44
(2.73 to 13.22)
48
16 13 13 10 2.54 2.31 2.31 1.85
9.0
(2.2 to 11.0)
2250
(490 to 2850)
10.44
(2.78 to 13.22)
48
13 13 13 13 2.25 2.25 2.25 2.25
9.0
(2.2 to 11.0)
2250
(490 to 2850)
10.44
(2.78 to 13.22)
48
16 16 10 10 2.61 2.61 1.89 1.89
9.0
(2.2 to 11.0)
2250
(500 to 2850)
10.44
(2.84 to 13.22)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
12
Outdoor Unit : RAS-4M27GAV-E
<Heating/230V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Heating
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
230 1 unit 10 –––4.0 –––
4.0
(0.8 to 5.2)
1450
(300 to 1980)
6.43
(1.79 to 8.78 )
48
13 –––5.0 –––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
9.09
(1.85 to 12.20)
48
16 –––5.5 –––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
10.65
(1.85 to 13.31)
48
2 units 10 10 ––3.60 3.60 ––
7.2
(1.5 to 10.0)
2100
(320 to 3200)
9.32
(1.86 to 14.20)
48
13 10 ––4.22 3.38 ––
7.6
(1.5 to 10.1)
2320
(320 to 3210)
10.29
(1.86 to 14.24)
48
16 10 ––4.57 3.33 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
11.00
(1.86 to 14.33)
48
13 13 ––3.95 3.95 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
11.00
(1.86 to 14.33)
48
16 13 ––4.35 3.95 ––
8.3
(1.5 to 10.2)
2700
(320 to 3240)
11.98
(1.86 to 14.37)
48
16 16 ––4.30 4.30 ––
8.6
(1.5 to 10.2)
2860
(320 to 3250)
12.69
(1.86 to 14.42)
48
3 units 10 10 10 2.87 2.87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
10.20
(2.07 to 12.20)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.43
(2.07 to 12.24)
48
16 10 10 3.54 2.58 2.58
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.43
(2.07 to 12.24)
48
13 13 10 3.11 3.11 2.49
8.7
(2.0 to 10.5)
2350
(380 to 2760)
10.43
(2.07 to 12.24)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2400
(380 to 2780)
10.65
(2.07 to 12.33)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2400
(380 to 2780)
10.65
(2.07 to 12.33)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.87
(2.07 to 12.38)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.87
(2.07 to 12.38)
48
16 16 13 3.06 3.06 2.78
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.87
(2.07 to 12.38)
48
16 16 16 3.00 3.00 3.00
9.0
(2.0 to 10.8)
2500
(380 to 2800)
11.09
(2.07 to 12.42)
48
4 units 10 10 10 10 2.23 2.23 2.23 2.23
8.9
(2.2 to 10.8)
2100
(450 to 2810)
9.32
(2.45 to 12.47)
48
13 10 10 10 2.62 2.09 2.09 2.09
8.9
(2.2 to 10.9)
2100
(460 to 2830)
9.32
(2.50 to 12.56)
48
16 10 10 10 2.83 2.06 2.06 2.06
9.0
(2.2 to 10.9)
2250
(460 to 2830)
9.98
(2.50 to 12.56)
48
13 13 10 10 2.50 2.50 2.00 2.00
9.0
(2.2 to 10.9)
2250
(470 to 2830)
9.98
(2.55 to 12.56)
48
16 13 10 10 2.68 2.43 1.95 1.95
9.0
(2.2 to 11.0)
2250
(480 to 2850)
9.98
(2.61 to 12.64)
48
13 13 13 10 2.37 2.37 2.37 1.89
9.0
(2.2 to 11.0)
2250
(480 to 2850)
9.98
(2.61 to 12.64)
48
16 13 13 10 2.54 2.31 2.31 1.85
9.0
(2.2 to 11.0)
2250
(490 to 2850)
9.98
(2.66 to 12.64)
48
13 13 13 13 2.25 2.25 2.25 2.25
9.0
(2.2 to 11.0)
2250
(490 to 2850)
9.98
(2.66 to 12.64)
48
16 16 10 10 2.61 2.61 1.89 1.89
9.0
(2.2 to 11.0)
2250
(500 to 2850)
9.98
(2.72 to 12.64)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
13
Outdoor Unit : RAS-4M27GAV-E
<Heating/240V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Heating
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
240 1 unit 10 –––4.0 –––
4.0
(0.8 to 5.2)
1450
(300 to 1980)
6.16
(1.71 to 8.42 )
48
13 –––5.0 –––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
8.72
(1.77 to 11.69)
48
16 –––5.5 –––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
10.20
(1.77 to 12.76)
48
2 units 10 10 ––3.60 3.60 ––
7.2
(1.5 to 10.0)
2100
(320 to 3200)
8.93
(1.78 to 13.61)
48
13 10 ––4.22 3.38 ––
7.6
(1.5 to 10.1)
2320
(320 to 3210)
9.86
(1.78 to 13.65)
48
16 10 ––4.57 3.33 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
10.54
(1.78 to 13.73)
48
13 13 ––3.95 3.95 ––
7.9
(1.5 to 10.1)
2480
(320 to 3230)
10.54
(1.78 to 13.73)
48
16 13 ––4.35 3.95 ––
8.3
(1.5 to 10.2)
2700
(320 to 3240)
11.48
(1.78 to 13.78)
48
16 16 ––4.30 4.30 ––
8.6
(1.5 to 10.2)
2860
(320 to 3250)
12.16
(1.78 to 13.82)
48
3 units 10 10 10 2.87 2.87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
9.78
(1.98 to 11.69)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2350
(380 to 2760)
9.99
(1.98 to 11.73)
48
16 10 10 3.54 2.58 2.58
8.7
(2.0 to 10.5)
2350
(380 to 2760)
9.99
(1.98 to 11.73)
48
13 13 10 3.11 3.11 2.49
8.7
(2.0 to 10.5)
2350
(380 to 2760)
9.99
(1.98 to 11.73)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2400
(380 to 2780)
10.20
(1.98 to 11.82)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2400
(380 to 2780)
10.20
(1.98 to 11.82)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.42
(1.98 to 11.86)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.42
(1.98 to 11.86)
48
16 16 13 3.06 3.06 2.78
8.9
(2.0 to 10.7)
2450
(380 to 2790)
10.42
(1.98 to 11.86)
48
16 16 16 3.00 3.00 3.00
9.0
(2.0 to 10.8)
2500
(380 to 2800)
10.63
(1.98 to 11.90)
48
4 units 10 10 10 10 2.23 2.23 2.23 2.23
8.9
(2.2 to 10.8)
2100
(450 to 2810)
8.93
(2.34 to 11.95)
48
13 10 10 10 2.62 2.09 2.09 2.09
8.9
(2.2 to 10.9)
2100
(460 to 2830)
8.93
(2.40 to 12.03)
48
16 10 10 10 2.83 2.06 2.06 2.06
9.0
(2.2 to 10.9)
2250
(460 to 2830)
9.57
(2.40 to 12.03)
48
13 13 10 10 2.50 2.50 2.00 2.00
9.0
(2.2 to 10.9)
2250
(470 to 2830)
9.57
(2.45 to 12.03)
48
16 13 10 10 2.68 2.43 1.95 1.95
9.0
(2.2 to 11.0)
2250
(480 to 2850)
9.57
(2.50 to 12.12)
48
13 13 13 10 2.37 2.37 2.37 1.89
9.0
(2.2 to 11.0)
2250
(480 to 2850)
9.57
(2.50 to 12.12)
48
16 13 13 10 2.54 2.31 2.31 1.85
9.0
(2.2 to 11.0)
2250
(490 to 2850)
9.57
(2.55 to 12.12)
48
13 13 13 13 2.25 2.25 2.25 2.25
9.0
(2.2 to 11.0)
2250
(490 to 2850)
9.57
(2.55 to 12.12)
48
16 16 10 10 2.61 2.61 1.89 1.89
9.0
(2.2 to 11.0)
2250
(500 to 2850)
9.57
(2.60 to 12.12)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
14
Outdoor Unit : RAS-4M27GACV-E
<Cooling/220V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capacity (kW)Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
220 1 unit 10 –––2.7 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.87
(3.68 to 4.64 )
48
13 –––3.7 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.74
(3.68 to 7.20 )
48
16 –––4.5 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.81
(3.68 to 9.28 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
7.10
(3.64 to 9.46 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.40
(3.75 to 10.30)
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.76
(3.92 to 11.92)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.83
(3.98 to 12.76)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
11.13
(4.80 to 12.62)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
11.18
(4.85 to 12.71)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
11.18
(4.85 to 12.94)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
11.18
(4.85 to 12.94)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
11.27
(4.90 to 13.03)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
11.27
(4.90 to 13.03)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
11.32
(4.90 to 13.13)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
11.32
(4.90 to 13.13)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
11.32
(4.90 to 13.36)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
11.36
(4.95 to 13.45)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
11.36
(4.70 to 12.99)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
11.36
(4.75 to 13.08)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.60
(4.75 to 13.27)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.60
(4.75 to 13.27)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.60
(4.80 to 13.36)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.60
(4.80 to 13.36)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.60
(4.80 to 13.45)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
15
Outdoor Unit : RAS-4M27GACV-E
<Cooling/230V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
230 1 unit 10 –––2.7 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.71
(3.52 to 4.44 )
48
13 –––3.7 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.49
(3.52 to 6.88 )
48
16 –––4.5 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.47
(3.52 to 8.87 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.79
(3.48 to 9.05 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.03
(3.59 to 9.85 )
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.29
(3.75 to 11.40)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.31
(3.80 to 12.20)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
10.65
(4.59 to 12.07)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
10.69
(4.64 to 12.16)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.69
(4.64 to 12.38)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.69
(4.64 to 12.38)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.78
(4.69 to 12.47)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.78
(4.69 to 12.47)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.83
(4.69 to 12.56)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.83
(4.69 to 12.56)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
10.83
(4.69 to 12.78)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
10.87
(4.73 to 12.87)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
10.87
(4.49 to 12.42)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
10.87
(4.54 to 12.51)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.09
(4.54 to 12.69)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
11.09
(4.54 to 12.69)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.09
(4.59 to 12.78)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
11.09
(4.59 to 12.78)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
11.09
(4.59 to 12.87)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
16
Outdoor Unit : RAS-4M27GACV-E
<Cooling/240V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Unit capa ci t y (kW )Power
su
pply
(V)
O
p
eratin
g
status
ABCD A B C D
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
240 1 unit 10 –––2.7 –––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.55
(3.38 to 4.26 )
48
13 –––3.7 –––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.26
(3.38 to 6.60 )
48
16 –––4.5 –––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.16
(3.38 to 8.50 )
48
2 units 10 10 ––2.70 2.70 ––
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.51
(3.33 to 8.67 )
48
13 10 ––3.41 2.49 ––
5.9
(2.7 to 6.6)
1810
(660 to 2220)
7.70
(3.44 to 9.44 )
48
16 10 ––3.94 2.36 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
13 13 ––3.15 3.15 ––
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
16 13 ––3.73 3.07 ––
6.8
(3.0 to 7.2)
2320
(690 to 2570)
9.86
(3.59 to 10.93)
48
16 16 ––3.60 3.60 ––
7.2
(3.2 to 7.5)
2550
(700 to 2750)
10.84
(3.65 to 11.69)
48
3 units 10 10 10 2.53 2.53 2.53
7.6
(3.8 to 8.2)
2400
(950 to 2720)
10.20
(4.40 to 11.56)
48
13 10 10 3.13 2.28 2.28
7.7
(3.9 to 8.3)
2410
(960 to 2740)
10.25
(4.44 to 11.65)
48
16 10 10 3.50 2.10 2.10
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.25
(4.44 to 11.86)
48
13 13 10 2.82 2.82 2.06
7.7
(4.0 to 8.5)
2410
(960 to 2790)
10.25
(4.44 to 11.86)
48
16 13 10 3.22 2.65 1.93
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.33
(4.49 to 11.95)
48
13 13 13 2.60 2.60 2.60
7.8
(4.1 to 8.6)
2430
(970 to 2810)
10.33
(4.49 to 11.95)
48
16 16 10 3.04 3.04 1.82
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.37
(4.49 to 12.03)
48
16 13 13 2.99 2.46 2.46
7.9
(4.1 to 8.7)
2440
(970 to 2830)
10.37
(4.49 to 12.03)
48
16 16 13 2.80 2.80 2.30
7.9
(4.2 to 8.9)
2440
(970 to 2880)
10.37
(4.49 to 12.24)
48
16 16 16 2.67 2.67 2.67
8.0
(4.3 to 9.0)
2450
(980 to 2900)
10.42
(4.54 to 12.33)
48
4 units 10 10 10 10 1.98 1.98 1.98 1.98
7.9
(4.0 to 8.7)
2450
(930 to 2800)
10.42
(4.31 to 11.90)
48
13 10 10 10 2.48 1.81 1.81 1.81
7.9
(4.1 to 8.8)
2450
(940 to 2820)
10.42
(4.35 to 11.99)
48
16 10 10 10 2.86 1.71 1.71 1.71
8.0
(4.1 to 9.0)
2500
(940 to 2860)
10.63
(4.35 to 12.16)
48
13 13 10 10 2.31 2.31 1.69 1.69
8.0
(4.1 to 9.0)
2500
(940 to 2860)
10.63
(4.35 to 12.16)
48
16 13 10 10 2.65 2.18 1.59 1.59
8.0
(4.2 to 9.1)
2500
(950 to 2880)
10.63
(4.40 to 12.24)
48
13 13 13 10 2.14 2.14 2.14 1.57
8.0
(4.2 to 9.1)
2500
(950 to 2880)
10.63
(4.40 to 12.24)
48
16 13 13 10 2.47 2.03 2.03 1.48
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
13 13 13 13 2.00 2.00 2.00 2.00
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
16 16 10 10 2.50 2.50 1.50 1.50
8.0
(4.2 to 9.2)
2500
(950 to 2900)
10.63
(4.40 to 12.33)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
17
Outdoor Unit : RAS-3M26GAV-E
<Cooling/220V>
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
220 1 unit 10 ––2.7 ––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.87
(3.68 to 4.64 )
48
13 ––3.7 ––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.74
(3.68 to 7.20 )
48
16 ––4.5 ––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.81
(3.68 to 9.28 )
48
2 units 10 10 2.70 2.70
5.4
(2.5 to 6.3)
1530
(640 to 2040)
7.10
(3.64 to 9.46 )
48
13 10 3.41 2.49
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.40
(3.75 to 10.30)
48
16 10 3.94 2.36
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
13 13 3.15 3.15
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.46
(3.81 to 11.13)
48
16 13 3.73 3.07
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.76
(3.92 to 11.92)
48
16 16 3.60 3.60
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.83
(3.98 to 12.76)
48
3 units 10 10 10 2.47 2. 47 2.47
7.4
(3.8 to 8.2)
2230
(950 to 2720)
10.34
(4.80 to 12.62)
48
13 10 10 3.01 2.20 2.20
7.4
(3.9 to 8.3)
2230
(950 to 2750)
10.34
(4.80 to 12.76)
48
16 10 10 3.36 2.02 2.02
7.4
(4.0 to 8.5)
2230
(950 to 2820)
10.34
(4.80 to 13.08)
48
13 13 10 2.71 2.71 1.98
7.4
(4.0 to 8.5)
2230
(950 to 2820)
10.34
(4.80 to 13.08)
48
16 13 10 3.10 2.55 1.86
7.5
(4.0 to 8.6)
2250
(980 to 2850)
10.44
(4.95 to 13.22)
48
13 13 13 2.50 2.50 2.50
7.5
(4.0 to 8.6)
2250
(980 to 2850)
10.44
(4.95 to 13.22)
48
16 16 10 2.88 2.88 1.73
7.5
(4.1 to 8.8)
2250
(980 to 2920)
10.44
(4.95 to 13.54)
48
16 13 13 2.84 2.33 2.33
7.5
(4.1 to 8.8)
2250
(980 to 2920)
10.44
(4.95 to 13.54)
48
16 16 13 2.66 2.66 2.19
7.5
(4.2 to 8.9)
2250
(980 to 2950)
10.44
(4.95 to 13.68)
48
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
18
Outdoor Unit : RAS-3M26GAV-E
<Cooling/230V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
230 1 unit 10 ––2.7 ––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.71
(3.52 to 4.44 )
48
13 ––3.7 ––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.49
(3.52 to 6.88 )
48
16 ––4.5 ––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.47
(3.52 to 8.87 )
48
2 units 10 10 2.70 2.70
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.79
(3.48 to 9.05 )
48
13 10 3.41 2.49
5.9
(2.7 to 6.6)
1810
(660 to 2220)
8.03
(3.59 to 9.85 )
48
16 10 3.94 2.36
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
13 13 3.15 3.15
6.3
(2.9 to 6.9)
2040
(670 to 2400)
9.05
(3.64 to 10.65)
48
16 13 3.73 3.07
6.8
(3.0 to 7.2)
2320
(690 to 2570)
10.29
(3.75 to 11.40)
48
16 16 3.60 3.60
7.2
(3.2 to 7.5)
2550
(700 to 2750)
11.31
(3.80 to 12.20)
48
3 units 10 10 10 2.47 2. 47 2.47
7.4
(3.8 to 8.2)
2230
(950 to 2720)
9.89
(4.59 to 12.07)
48
13 10 10 3.01 2.20 2.20
7.4
(3.9 to 8.3)
2230
(950 to 2750)
9.89
(4.59 to 12.20)
48
16 10 10 3.36 2.02 2.02
7.4
(4.0 to 8.5)
2230
(950 to 2820)
9.89
(4.59 to 12.51)
48
13 13 10 2.71 2.71 1.98
7.4
(4.0 to 8.5)
2230
(950 to 2820)
9.89
(4.59 to 12.51)
48
16 13 10 3.10 2.55 1.86
7.5
(4.0 to 8.6)
2250
(980 to 2850)
9.98
(4.73 to 12.64)
48
13 13 13 2.50 2.50 2.50
7.5
(4.0 to 8.6)
2250
(980 to 2850)
9.98
(4.73 to 12.64)
48
16 16 10 2.88 2.88 1.73
7.5
(4.1 to 8.8)
2250
(980 to 2920)
9.98
(4.73 to 12.95)
48
16 13 13 2.84 2.33 2.33
7.5
(4.1 to 8.8)
2250
(980 to 2920)
9.98
(4.73 to 12.95)
48
16 16 13 2.66 2.66 2.19
7.5
(4.2 to 8.9)
2250
(980 to 2950)
9.98
(4.73 to 13.09)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
19
Outdoor Unit : RAS-3M26GAV-E
<Cooling/240V>
The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Cooling
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
240 1 unit 10 ––2.7 ––
2.7
(1.4 to 3.2)
750
(640 to 950)
3.55
(338 to 4.26)
48
13 ––3.7 ––
3.7
(1.4 to 4.4)
1200
(640 to 1520)
5.26
(3.38 to 6.60 )
48
16 ––4.5 ––
4.5
(1.4 to 5.0)
1650
(640 to 2000)
7.16
(3.38 to 8.50 )
48
2 units 10 10 2.70 2.70
5.4
(2.5 to 6.3)
1530
(640 to 2040)
6.51
(3.33 to 8.67 )
48
13 10 3.41 2.49
5.9
(2.7 to 6.6)
1810
(660 to 2220)
7.70
(3.44 to 9.44 )
48
16 10 3.94 2.36
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
13 13 3.15 3.15
6.3
(2.9 to 6.9)
2040
(670 to 2400)
8.67
(3.49 to 10.20)
48
16 13 3.73 3.07
6.8
(3.0 to 7.2)
2320
(690 to 2570)
9.86
(3.59 to 10.93)
48
16 16 3.60 3.60
7.2
(3.2 to 7.5)
2550
(700 to 2750)
10.84
(3.65 to 11.69)
48
3 units 10 10 10 2.47 2. 47 2.47
7.4
(3.8 to 8.2)
2230
(950 to 2720)
9.48
(4.40 to 11.56)
48
13 10 10 3.01 2.20 2.20
7.4
(3.9 to 8.3)
2230
(950 to 2750)
9.48
(4.40 to 11.69)
48
16 10 10 3.36 2.02 2.02
7.4
(4.0 to 8.5)
2230
(950 to 2820)
9.48
(4.40 to 11.99)
48
13 13 10 2.71 2.71 1.98
7.4
(4.0 to 8.5)
2230
(950 to 2820)
9.48
(4.40 to 11.99)
48
16 13 10 3.10 2.55 1.86
7.5
(4.0 to 8.6)
2250
(980 to 2850)
9.57
(4.54 to 12.12)
48
13 13 13 2.50 2.50 2.50
7.5
(4.0 to 8.6)
2250
(980 to 2850)
9.57
(4.54 to 12.12)
48
16 16 10 2.88 2.88 1.73
7.5
(4.1 to 8.8)
2250
(980 to 2920)
9.57
(4.54 to 12.41)
48
16 13 13 2.84 2.33 2.33
7.5
(4.1 to 8.8)
2250
(980 to 2920)
9.57
(4.54 to 12.41)
48
16 16 13 2.66 2.66 2.19
7.5
(4.2 to 8.9)
2250
(980 to 2950)
9.57
(4.54 to 12.54)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
20
Outdoor Unit : RAS-3M26GAV-E
<Heating/220V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Heating
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
220 1 unit 10 ––4.0 ––
4.0
(0.8 to 5.2)
1500
(300 to 1980)
6.96
(1.87 to 9.18 )
48
13 ––5.0 ––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
9.51
(1.93 to 12.76)
48
16 ––5.5 ––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
11.13
(1.93 to 13.91)
48
2 units 10 10 3.60 3.60
7.2
(1.5 to 10.0)
2050
(320 to 3200)
9.51
(1.94 to 14.84)
48
13 10 4.22 3.38
7.6
(1.5 to 10.1)
2240
(320 to 3210)
10.39
(1.94 to 14.89)
48
16 10 4.57 3.33
7.9
(1.5 to 10.1)
2380
(320 to 3230)
11.04
(1.94 to 14.98)
48
13 13 3.95 3.95
7.9
(1.5 to 10.1)
2380
(320 to 3230)
11.04
(1.94 to 14.98)
48
16 13 4.35 3.95
8.3
(1.5 to 10.2)
2560
(320 to 3240)
11.87
(1.94 to 15.03)
48
16 16 4.30 4.30
8.6
(1.5 to 10.2)
2700
(320 to 3250)
12.52
(1.94 to 15.07)
48
3 units 10 10 10 2.87 2. 87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
10.67
(2.16 to 12.76)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2360
(380 to 2760)
10.95
(2.16 to 12.80)
48
16 10 10 3.59 2.61 2.61
8.8
(2.0 to 10.6)
2430
(380 to 2780)
11.27
(2.16 to 12.89)
48
13 13 10 3.14 3.14 2.51
8.8
(2.0 to 10.6)
2430
(380 to 2780)
11.27
(2.16 to 12.89)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2430
(380 to 2780)
11.27
(2.16 to 12.89)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2430
(380 to 2780)
11.27
(2.16 to 12.89)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2490
(380 to 2790)
11.55
(2.16 to 12.94)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2490
(380 to 2790)
11.55
(2.16 to 12.94)
48
16 16 13 3.09 3.09 2.81
9.0
(2.0 to 10.8)
2550
(380 to 2800)
11.83
(2.16 to 12.99)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
21
Outdoor Unit : RAS-3M26GAV-E
<Heating/230V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Heating
capacity
(kW)
Power
consum
p
tion
(W)
Operating
current
(A)
Outdoor
noise
(dB)
230 1 unit 10 ––4.0 ––
4.0
(0.8 to 5.2)
1500
(300 to 1980)
6.65
(1.79 to 8.78 )
48
13 ––5.0 ––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
9.09
(1.85 to 12.20)
48
16 ––5.5 ––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
10.65
(1.85 to 13.31)
48
2 units 10 10 3.60 3.60
7.2
(1.5 to 10.0)
2050
(320 to 3200)
9.09
(1.86 to 14.20)
48
13 10 4.22 3.38
7.6
(1.5 to 10.1)
2240
(320 to 3210)
9.94
(1.86 to 14.24)
48
16 10 4.57 3.33
7.9
(1.5 to 10.1)
2380
(320 to 3230)
10.56
(1.86 to 14.33)
48
13 13 3.95 3.95
7.9
(1.5 to 10.1)
2380
(320 to 3230)
10.56
(1.86 to 14.33)
48
16 13 4.35 3.95
8.3
(1.5 to 10.2)
2560
(320 to 3240)
11.36
(1.86 to 14.37)
48
16 16 4.30 4.30
8.6
(1.5 to 10.2)
2700
(320 to 3250)
11.98
(1.86 to 14.42)
48
3 units 10 10 10 2.87 2. 87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
10.20
(2.07 to 12.20)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2360
(380 to 2760)
10.47
(2.07 to 12.24)
48
16 10 10 3.59 2.61 2.61
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.78
(2.07 to 12.33)
48
13 13 10 3.14 3.14 2.51
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.78
(2.07 to 12.33)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.78
(2.07 to 12.33)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.78
(2.07 to 12.33)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2490
(380 to 2790)
11.05
(2.07 to 12.38)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2490
(380 to 2790)
11.05
(2.07 to 12.38)
48
16 16 13 3.09 3.09 2.81
9.0
(2.0 to 10.8)
2550
(380 to 2800)
11.31
(2.07 to 12.42)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
22
Outdoor Unit : RAS-3M26GAV-E
<Heating/240V>
The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/ WB=7/6°C.
Indoor unit Uni t capa ci t y (kW )
Power
suppl
y
(V)
O
p
eratin
g
status
ABCABC
Heating
capacity
(kW)
Power
consumption
(W)
Operating
current
(A)
Outdoor
noise
(dB)
240 1 unit 10 ––4.0 ––
4.0
(0.8 to 5.2)
1500
(300 to 1980)
6.38
(1.71 to 8.42 )
48
13 ––5.0 ––
5.0
(0.8 to 6.5)
2050
(310 to 2750)
8.72
(1.77 to 11.69)
48
16 ––5.5 ––
5.5
(0.8 to 6.9)
2400
(310 to 3000)
10.20
(1.77 to 12.76)
48
2 units 10 10 3.60 3.60
7.2
(1.5 to 10.0)
2050
(320 to 3200)
8.72
(1.78 to 13.61)
48
13 10 4.22 3.38
7.6
(1.5 to 10.1)
2240
(320 to 3210)
9.52
(1.78 to 13.65)
48
16 10 4.57 3.33
7.9
(1.5 to 10.1)
2380
(320 to 3230)
10.12
(1.78 to 13.73)
48
13 13 3.95 3.95
7.9
(1.5 to 10.1)
2380
(320 to 3230)
10.12
(1.78 to 13.73)
48
16 13 4.35 3.95
8.3
(1.5 to 10.2)
2560
(320 to 3240)
10.88
(1.78 to 13.78)
48
16 16 4.30 4.30
8.6
(1.5 to 10.2)
2700
(320 to 3250)
11.48
(1.78 to 13.82)
48
3 units 10 10 10 2.87 2. 87 2.87
8.6
(2.0 to 10.4)
2300
(380 to 2750)
9.78
(1.98 to 11.69)
48
13 10 10 3.35 2.68 2.68
8.7
(2.0 to 10.5)
2360
(380 to 2760)
10.03
(1.98 to 11.73)
48
16 10 10 3.59 2.61 2.61
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.33
(1.98 to 11.82)
48
13 13 10 3.14 3.14 2.51
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.33
(1.98 to 11.82)
48
16 13 10 3.34 3.03 2.43
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.33
(1.98 to 11.82)
48
13 13 13 2.93 2.93 2.93
8.8
(2.0 to 10.6)
2430
(380 to 2780)
10.33
(1.98 to 11.82)
48
16 16 10 3.26 3.26 2.37
8.9
(2.0 to 10.7)
2490
(380 to 2790)
10.59
(1.98 to 11.86)
48
16 13 13 3.16 2.87 2.87
8.9
(2.0 to 10.7)
2490
(380 to 2790)
10.59
(1.98 to 11.86)
48
16 16 13 3.09 3.09 2.81
9.0
(2.0 to 10.8)
2550
(380 to 2800)
10.84
(1.98 to 11.90)
48
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
23
16 14 12 10
8 6 4 2 0
0
10 20 30 40 50 60 70 80
Inverter output frequency (rps)
Current (A)
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Air flow : High Pipe length: 5m x 4 4 units operating
240V
230V
220V
14 12 10
8 6 4 2 0
0
10 10020 30 40 50 60 70 80 90
Inverter output frequency (rps)
Current (A)
• Conditions Indoor : DB20˚C Outdoor : DB7˚C / WB6˚C Air flow : High Pipe length: 5m x 4 4 units operating
240V
230V
220V
110
105
100
95
90
85
80
0
10 20 30 40 50 60 70 80
Total pipe length (m)
Coolimg capacity ratio (%)
• Conditions Indoor : DB27˚C/WB19˚C Outdoor : DB35˚C Indoor air flow: High 4 units operating
Standard pipe length 20m
110
105
100
95
90
85
80
0
10 20 30 40 50 60 70 80
Total pipe length (m)
Heating capacity ratio (%)
• Conditions Indoor : DB20˚C Outdoor : DB7˚C/WB6˚C Indoor air flow: High 4 units operating
Standard pipe length 20m
50
60
70
80
90
100
110
32
33 34 35 36 37 38 39 40 41 42 43 44
Outdoor temp. (˚C)
Cooling capacity ratio (%)
• Conditions Indoor : DB27˚C/WB19˚C Indoor air flow : High Pipe length : 5m x 4 4 units operating
Current limited start
50
60
70
80
90
100
110
-
10
-9-8-7-6-5-4-3-2-1012345678910 Outdoor temp. (˚C)
Heating capacity ratio (%)
• Conditions Indoor : DB20˚C Air flow : High Pipe length : 5m x 4 4 units operating
2-2-1. Operation Characteristic Curve
<Cooling> <Heating>
2-2-2. Capacity Variation Ratio According to Outdoor Temperature
<Cooling> <Heating>
2-2-3. Capacity Variation Ratio According to Pipe Length
<Cooling> <Heating>
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
24
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water , dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrig­eration cycle. Otherwise, pressure in the refrig­eration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal le vel, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become bloc ked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is availab le on the mark et.
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
25
Table 3-2-1 Thicknesses of annealed copper pipes
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
Thickness (mm)
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or soc ket joints are used. Prior to use, be sure to remov e all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter e xceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
26
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen- sion A by using a gauge for size adjustment.
Fig. 3-2-1 Flare pr ocessing dimensions
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4 3/8 1/2 5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R410A
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Table 3-2-4 Dimensions related to flare processing for R22
Nominal
diameter
1/4 3/8 1/2 5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Flare nut width
(mm)
17 22 26 29
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
27
43˚ to 45˚
45˚ to 46˚
B A
C
D
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal diameter
1/4 3/8 1/2 5/8 3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
Flare nut width
(mm)
17 22 24 27 36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removab l e. When choosing the tighten-
ing torque, comply with values designated by man ufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated b y the man ufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
28
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conv entional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
1
2
3
4 5 6
7 8
9
10
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
R410A
air-water heat pump installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
× ×
× × ×
× ×
Conventional air-water heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
× ×
¡
¡
×
¡
×
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also f or R22 are necessary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11 . Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
29
Connect the charge hose to packed valve service port at the outdoor units gas side.
Recover the refrigerant, and check no refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(Water heat exchanger unit)
(Outdoor unit)
Opened
Opened
Refrigerant cylinder
(with siphon)
Check valve
Open/close valve for charging
Electronic balance for refrigerant charging
Opened
Closed
Service port
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
Fig. 3-4-1 Configuration of refrigerant charging
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807
30
Gauge manifold
[ Cylinder with siphon ] [ Cylinder without siphon ]
OUTDOOR unit
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Refrigerant
cylinder
Electronic
balance
Siphon
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
1. Reason why flux is necessary
By removing the o xide film and an y foreign matter on the metal surface, it assists the flow of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing fillers surface tension, the brazing filler adheres better to the treated metal.
Fig. 3-4-2
Heronhill - for all your Toshiba requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 01823 665807