Toshiba RAS-3M18SACV-E, RAS-3M18SAV-E SERVICE MANUAL

SERVICE MANUAL
AIR-CONDITIONER
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E
FILE NO. A06-013
SPLIT TYPE
RAS-3M18SAV-E
RAS-3M18SA C V-E
R410A
PRINTED IN JAPAN, May, 2007 ToMo
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 3
2. SPECIFICATIONS...................................................................................... 5
3. REFRIGERANT R410A ........................................................................... 12
4. CONSTRUCTION VIEWS ........................................................................ 20
5. WIRING DIAGRAM .................................................................................. 22
6. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 24
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 25
8. CONTROL BLOCK DIAGRAM ................................................................ 29
9. OPERATION DESCRIPTION................................................................... 32
10. INSTALLATION PROCEDURE ................................................................ 57
11. HOW TO DIAGNOSE THE TROUBLE ...................................................... 73
12. HOW TO REPLACE THE MAIN P ARTS................................................... 93
13. EXPLODED VIEWS AND PARTS LIST ................................................. 112
– 2 –
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm² (H07RN-F or 60245IEC66) polychloroprene sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigeration machine oil does not enter into the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
Disconnection from the supply mains: The means for disconnection must be incorporated in the fixed wiring in accordance with the wiring rules.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/ MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated. Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCOR­RECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 3 –
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VERY CARE­FUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PERSONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source such as a cooking range, noxious gas may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installa­tion Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cables and connect the terminals securely to prevent external forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short. Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously performed for a long time under the condition that the outdoor temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner. For details, contact the dealer.
– 4 –

2. SPECIFICATIONS

The indoor and outdoor units that can be used in combination are shown in the tables below.
Table of models that can be connected
Type
Heat pump
Cooling-only
Outdoor unit
RAS-B10SKVP–E RAS-B13SKVP–E RAS-B16SKVP–E RAS-M10SKV–E RAS-M13SKV–E RAS-M16SKV–E
RAS-3M18SAV-E
RAS-M10GDV–E RAS-M13GDV–E RAS-M16GDV–E RAS-M10SMUV–E RAS-M13SMUV–E RAS-M16SMUV–E RAS-M10SKCVP–E RAS-M13SKCVP–E RAS-M16SKCVP–E RAS-M10SKCV–E RAS-M13SKCV–E RAS-M16SKCV–E
RAS-3M18SACV-E
RAS-M10GDCV–E RAS-M13GDCV–E RAS-M16GDCV–E RAS-M10SMUCV–E RAS-M13SMUCV–E RAS-M16SMUCV–E
Table of models that can be used in combination
Type
Heat pump Cooling-only
Outdoor unit
RAS-3M18SAV-E RAS-3M18SACV-E
Combinations of indoor unit models that can be connected
Refer to page 8, 9 Refer to page 10
Indoor unit
NOTES
1-room connection is not an option for the indoor units (you cannot connect only one indoor unit). Be sure to connect indoor units in two rooms or more.
The contents noted in this service manual limit the indoor units to the RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E, RAS-M10SKCVP-E, RAS-M13SKCVP-E and RAS-M16SKCVP-E.
For other indoor units that can also be used in combination, see the service manual of each indoor unit.
Indoor unit
RAS-M10GDV-E RAS-M10GDCV-E RAS-M13GDV-E RAS-M13GDCV-E RAS-M16GDV-E RAS-M16GDCV-E RAS-M10SKV-E RAS-M10SKCV-E RAS-M13SKV-E RAS-M13SKCV-E RAS-M16SKV-E RAS-M16SKCV-E RAS-M10SMUV-E RAS-M10SMUCV-E RAS-M13SMUV-E RAS-M13SMUCV-E
File No.
A05-010
TBA
A06-015
RAS-M16SMUV-E RAS-M16SMUCV-E
– 5 –
2-1. Specifications
<Heat Pump Models>
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E / RAS-3M18SAV-E
Unit model Cooling capacity (kW)
Cooling capacity range (kW) Heating capacity (kW) Heating capacity range (kW) Power supply
Electric characteristics
COP (Cooling/Heating)
Operating (Cooling/Heating) Medium (dB•A) noise Low (dB•A)
Indoor unit Depth (mm)
Outdoor unit
Piping Maximum length (per unit) (m) connection Minimum length (per unit) (m)
Wiring connection
Usable temperature range
Accessory
Indoor Outdoor
Unit model
Indoor
Outdoor Power consumption (W)
Indoor High (dB•A)
Outdoor Cooling
Unit model
Dimension Width (mm)
Net weight (kg) Fan motor output (W) Air flow rate (Cooling/Heating) (m³/h)
Dimension Width (mm)
Net weight (kg)
Compressor Type
Fan motor output (W) Air flow rate (m³/h) Type
Indoor unit Liquid side
Outdoor unit B unit liquid side/Gas side
Maximum length (total) (m) Maximum chargeless length (m) Additional refrigerant Maximum height difference (m) Name of refrigerant Weight (kg)
Indoor unit
Outdoor unit
Running current (A) Pow er consumption (W) Power factor (%) Operation mode Running current (A)
Power factor (%) Starting current (A)
Unit model
Heating
Height (mm)
Height (mm)
Depth (mm)
Motor output (W)
Model
Unit model
Gas side A unit liquid side/Gas side
C unit liquid side/Gas side
Power supply Interconnection Indoor (Cooling/Heating) (°C) Outdoor (Cooling/Heating) (°C) Installation plate Wireless remote controller Label Remote controller holder Pan head wood screw Purifying filter Deodorizing filter Batteries Mounting screw Installation manual Installation manual Specifications Drain nipple Water-proof rubber cap
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E
220 – 240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz
RAS-B10SKVP-E RAS-B13SKVP-E RAS-B16SKVP-E
0.15 0.15 0.15 30 30 30
91 / 87 / 83 91 / 87 / 83 91 / 87 / 83
Cooling Heating
6.34 / 6.07 / 5.82 7.58 / 7.25 / 6.94 1340 1600
96 96
3.88 4.25
RAS-B10SKVP-E RAS-B13SKVP-E RAS-B16SKVP-E
42 / 43 43 / 44 45 / 45 33 / 36 34 / 37 36 / 39 27 / 27 27 / 27 29 / 29
RAS-B10SKVP-E RAS-B13SKVP-E RAS-B16SKVP-E
250 250 250 790 790 790 208 208 208
999
30 30 30
550 / 620 570 / 640 620 / 660
Twin rotary type with DC-inverter variable speed control
RAS-B10SKVP-E RAS-B13SKVP-E RAS-B16SKVP-E
Ø6.35 Ø6.35 Ø6.35 Ø9.52 Ø9.52 Ø12.7
No additional refrigerant
3 Wires : includes earth 4 Wires : includes earth
5 to 43 / –15 to 24
• For performance when each indoor unit is combined with other unit, refer to the separate table.
• The specifications may be subject to change without notice for purpose of improvement.
RAS-3M18SAV-E
5.2
2.2 – 6.5
6.8
2.2 – 7.7
47 49
695 780 270
47
1100
DA130A1F-25F
43
2100
Flare connection
Ø6.35/ Ø9.52 Ø6.35/ Ø9.52 Ø6.35/ Ø9.52
20
2 50 50
10
R410A
1.50
21 to 32 / 0 to 28
1
1
2
1
2 (Ø3.1 × 16L)
1
1
2
6 (Ø4 × 25L)
1
1
1
1
2
– 6 –
<Cooling Only Models>
RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E / RAS-3M18SACV-E
Unit model Cooling capacity (kW)
Cooling capacity range (kW) Heating capacity (kW) Heating capacity range (kW) Power supply
Electric characteristics
COP (Cooling/Heating)
Operating (Cooling/Heating) Medium (dB•A) noise Low (dB•A)
Indoor unit Depth (mm)
Outdoor unit
Piping Maximum length (per unit) (m) connection Minimum length (per unit) (m)
Wiring connection
Usable temperature range
Accessory
Indoor Outdoor
Unit model
Indoor
Outdoor Power consumption (W)
Indoor High (dB•A)
Outdoor Cooling
Unit model
Dimension Width (mm)
Net weight (kg) Fan motor output (W) Air flow rate (Cooling/Heating) (m³/h)
Dimension Width (mm)
Net weight (kg)
Compressor Type
Fan motor output (W) Air flow rate (m³/h) Typ
Indoor unit Liquid side
Outdoor unit B unit liquid side/Gas side
Maximum length (total) (m) Maximum chargeless length (m) Additional refrigerant Maximum height difference (m) Name of refrigerant Weight (kg)
Indoor unit
Outdoor unit
Running current (A) Pow er consumption (W) Power factor (%) Operation mode Running current (A)
Power factor (%) Starting current (A)
Unit model
Heating
Height (mm)
Height (mm)
Depth (mm)
Motor output (W)
Model
Unit model
Gas side A unit liquid side/Gas side
C unit liquid side/Gas side
Power supply Interconnection Indoor (Cooling/Heating) (°C) Outdoor (Cooling/Heating) (°C) Installation plate Wireless remote controller Label Remote controller holder Pan head wood screw Purifying filter Deodorizing filter Batteries Mounting screw Installation manual Installation manual Specifications
RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E
RAS-3M18SACV-E
5.2
2.2 – 6.5 — —
220 – 240 V, 1 Ph, 50Hz / 220 V, 1 Ph, 60Hz
RAS-M10SKCVP-E RAS-M13SKCVP-E RAS-M16SKCVP-E
0.15 0.15 0.15 30 30 30
91 / 87 / 83 91 / 87 / 83 91 / 87 / 83
Cooling Heating
9.34 / 6.07 / 5.82 — 1340
96
3.88
RAS-M10SKCVP-E RAS-M13SKCVP-E RAS-M16SKCVP-E
42 / — 43 / — 45 / — 33 / — 34 / — 36 / — 27 / — 27 / — 29 / —
47 —
RAS-M10SKCVP-E RAS-M13SKCVP-E RAS-M16SKCVP-E
250 250 250 790 790 790 208 208 208
999
30 30 30
550 / — 570 / — 620 / —
695 780 270
47
1100
Twin rotary type with DC-inverter variable speed control
DA130A1F-25F
43
2100
Flare connection
RAS-M10SKCVP-E RAS-M13SKCVP-E RAS-M16SKCVP-E
Ø6.35 Ø6.35 Ø6.35 Ø9.52 Ø9.52 Ø12.7
Ø6.35/ Ø9.52 Ø6.35/ Ø9.52 Ø6.35/ Ø9.52
20
2 50 50
No additional refrigerant
10
R410A
1.50 3 Wires : includes earth 4 Wires : includes earth
21 to 32 / —
5 to 43 / —
1 1 2 1
2 (Ø3.1 × 16L)
1 1 2
6 (Ø4 × 25L)
1 1 1
• For performance when each indoor unit is combined with other unit, refer to the separate table.
• The specifications may be subject to change without notice for purpose of improvement.
– 7 –
2-2. Specifications of Performance When Each Indoor Unit is Combined with Other Unit
Outdoor Unit : RAS-3M18SAV-E
<Cooling>
Power
supply
(V)
220
230
240
Operating
status
1 unit
2 units
3 units
1 unit
2 units
3 units
1 unit
2 units
3 units
Indoor unit
ABC
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
Unit capacity (kW) ABC
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
Cooling
capacity
(kW)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
Power
consumption
(W)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
Operating
current
(A)
3.54
(1.94 to 4.20)
5.12
(1.94 to 7.12)
7.83
(1.94 to 8.34)
6.32
(2.15 to 8.43)
6.32
(2.15 to 8.43)
6.56
(2.15 to 8.53)
6.56
(2.15 to 8.53)
6.34
(2.51 to 9.14)
6.34
(2.51 to 9.74)
6.34
(2.51 to 9.74)
6.34
(2.51 to 9.74)
3.39
(1.86 to 4.02)
4.90
(1.86 to 6.81)
7.49
(1.86 to 7.98)
6.04
(2.06 to 8.07)
6.04
(2.06 to 8.07)
6.27
(2.06 to 8.16)
6.27
(2.06 to 8.16)
6.07
(2.40 to 8.74)
6.07
(2.40 to 9.32)
6.07
(2.40 to 9.32)
6.07
(2.40 to 9.32)
3.25
(1.78 to 3.85)
4.69
(1.78 to 6.53)
7.17
(1.78 to 7.65)
5.79
(1.97 to 7.73)
5.79
(1.97 to 7.73)
6.01
(1.97 to 7.82)
6.01
(1.97 to 7.82)
5.82
(2.30 to 8.38)
5.82
(2.30 to 8.93)
5.82
(2.30 to 8.93)
5.82
(2.30 to 8.93)
EER
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
Outdoor
noise
(dB)
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
– 8 –
Outdoor Unit : RAS-3M18SAV-E
<Heating>
Power
supply
(V)
220
230
240
Operating
status
1 unit
2 units
3 units
1 unit
2 units
3 units
1 unit
2 units
3 units
Indoor unit
ABC
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
Unit capacity (kW) ABC
3.4 ––
4.3 ––
5.2 ––
3.10 3.10
3.46 2.74
3.87 2.53
3.20 3.20
2.23 2.23 2.23
2.63 2.08 2.08
2.95 1.93 1.93
2.44 2.44 1.93
3.4 ––
4.3 ––
5.2 ––
3.10 3.10
3.46 2.74
3.87 2.53
3.20 3.20
2.23 2.23 2.23
2.63 2.08 2.08
2.95 1.93 1.93
2.44 2.44 1.93
3.4 ––
4.3 ––
5.2 ––
3.10 3.10
3.46 2.74
3.87 2.53
3.20 3.20
2.23 2.23 2.23
2.63 2.08 2.08
2.95 1.93 1.93
2.44 2.44 1.93
Heating
capacity
(kW)
3.4
(0.8 to 4.5)
4.3
(0.8 to 4.8)
5.2
(0.8 to 6.0)
6.2
(1.8 to 7.3)
6.2
(1.8 to 7.3)
6.4
(1.8 to 7.5)
6.4
(1.8 to 7.5)
6.7
(2.2 to 7.5)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
3.4
(0.8 to 4.5)
4.3
(0.8 to 4.8)
5.2
(0.8 to 6.0)
6.2
(1.8 to 7.3)
6.2
(1.8 to 7.3)
6.4
(1.8 to 7.5)
6.4
(1.8 to 7.5)
6.7
(2.2 to 7.5)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
3.4
(0.8 to 4.5)
4.3
(0.8 to 4.8)
5.2
(0.8 to 6.0)
6.2
(1.8 to 7.3)
6.2
(1.8 to 7.3)
6.4
(1.8 to 7.5)
6.4
(1.8 to 7.5)
6.7
(2.2 to 7.5)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
6.8
(2.2 to 7.7)
Power
consumption
(W)
1050
(300 to 1500)
1470
(300 to 1600)
1850
(300 to 2050)
1720
(360 to 2140)
1720
(360 to 2140)
1840
(360 to 2200)
1840
(360 to 2200)
1580
(420 to 1950)
1600
(420 to 2030)
1600
(420 to 2030)
1600
(420 to 2030)
1050
(300 to 1500)
1470
(300 to 1600)
1850
(300 to 2050)
1720
(360 to 2140)
1720
(360 to 2140)
1840
(360 to 2200)
1840
(360 to 2200)
1580
(420 to 1950)
1600
(420 to 2030)
1600
(420 to 2030)
1600
(420 to 2030)
1050
(300 to 1500)
1470
(300 to 1600)
1850
(300 to 2050)
1720
(360 to 2140)
1720
(360 to 2140)
1840
(360 to 2200)
1840
(360 to 2200)
1580
(420 to 1950)
1600
(420 to 2030)
1600
(420 to 2030)
1600
(420 to 2030)
Operating
current
(A)
5.08
(1.82 to 7.10)
6.96
(1.82 to 7.58)
8.67
(1.82 to 9.51)
8.14
(2.15 to 9.93)
8.14
(2.15 to 9.93)
8.71
(2.15 to 10.20)
8.71
(2.15 to 10.20)
7.48
(2.51 to 9.14)
7.58
(2.51 to 9.42)
7.58
(2.51 to 9.42)
7.58
(2.51 to 9.42)
4.86
(1.74 to 6.79)
6.66
(1.74 to 7.25)
8.29
(1.74 to 9.09)
7.79
(2.06 to 9.49)
7.79
(2.06 to 9.49)
8.33
(2.06 to 9.76)
8.33
(2.06 to 9.76)
7.16
(2.40 to 8.74)
7.25
(2.40 to 9.01)
7.25
(2.40 to 9.01)
7.25
(2.40 to 9.01)
4.65
(1.67 to 6.51)
6.38
(1.67 to 6.94)
7.95
(1.67 to 8.72)
7.47
(1.97 to 9.10)
7.47
(1.97 to 9.10)
7.99
(1.97 to 9.35)
7.99
(1.97 to 9.35)
6.86
(2.30 to 8.38)
6.94
(2.30 to 8.63)
6.94
(2.30 to 8.63)
6.94
(2.30 to 8.63)
COP
3.24
2.93
2.81
3.60
3.60
3.48
3.48
4.24
4.25
4.25
4.25
3.24
2.93
2.81
3.60
3.60
3.48
3.48
4.24
4.25
4.25
4.25
3.24
2.93
2.81
3.60
3.60
3.48
3.48
4.24
4.25
4.25
4.25
Outdoor
noise
(dB)
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
49
• The above specification values are those under the conditions that the indoor DB/WB=20/–°C and the outdoor DB/WB=7/6°C.
– 9 –
Outdoor Unit : RAS-3M18SACV-E
<Cooling>
Power
supply
(V)
220
230
240
Operating
status
1 unit
2 units
3 units
1 unit
2 units
3 units
1 unit
2 units
3 units
Indoor unit
ABC
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
10 ––
13 ––
16 ––
10 10
13 10
16 10
13 13
10 10 10
13 10 10
16 10 10
13 13 10
Unit capacity (kW) ABC
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
2.5 ––
3.5 ––
4.5 ––
2.40 2.40
2.80 2.00
3.21 1.79
2.50 2.50
1.70 1.70 1.70
2.14 1.53 1.53
2.46 1.37 1.37
1.92 1.92 1.37
Cooling
capacity
(kW)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
2.5
(1.4 to 3.2)
3.5
(1.4 to 4.2)
4.5
(1.4 to 5.0)
4.8
(1.8 to 5.9)
4.8
(1.8 to 5.9)
5.0
(1.8 to 6.2)
5.0
(1.8 to 6.2)
5.1
(2.2 to 6.3)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
5.2
(2.2 to 6.5)
Power
consumption
(W)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
600
(320 to 850)
1070
(320 to 1520)
1670
(320 to 1780)
1320
(360 to 1800)
1320
(360 to 1800)
1370
(360 to 1820)
1370
(360 to 1820)
1340
(420 to 1970)
1340
(420 to 2100)
1340
(420 to 2100)
1340
(420 to 2100)
Operating
current
(A)
3.54
(1.94 to 4.20)
5.12
(1.94 to 7.12)
7.83
(1.94 to 8.34)
6.32
(2.15 to 8.43)
6.32
(2.15 to 8.43)
6.56
(2.15 to 8.53)
6.56
(2.15 to 8.53)
6.34
(2.51 to 9.14)
6.34
(2.51 to 9.74)
6.34
(2.51 to 9.74)
6.34
(2.51 to 9.74)
3.39
(1.86 to 4.02)
4.90
(1.86 to 6.81)
7.49
(1.86 to 7.98)
6.04
(2.06 to 8.07)
6.04
(2.06 to 8.07)
6.27
(2.06 to 8.16)
6.27
(2.06 to 8.16)
6.07
(2.40 to 8.74)
6.07
(2.40 to 9.32)
6.07
(2.40 to 9.32)
6.07
(2.40 to 9.32)
3.25
(1.78 to 3.85)
4.69
(1.78 to 6.53)
7.17
(1.78 to 7.65)
5.79
(1.97 to 7.73)
5.79
(1.97 to 7.73)
6.01
(1.97 to 7.82)
6.01
(1.97 to 7.82)
5.82
(2.30 to 8.38)
5.82
(2.30 to 8.93)
5.82
(2.30 to 8.93)
5.82
(2.30 to 8.93)
EER
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
4.17
3.27
2.69
3.64
3.64
3.65
3.65
3.81
3.88
3.88
3.88
Outdoor
noise
(dB)
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
47
• The above specification values are those under the conditions that the indoor DB/WB=27/19°C and the outdoor DB/WB=35/–°C.
– 10 –
2-2-1. Operation Characteristic Curve
<Cooling> <Heating>
RAS3M18SAV-E, RAS-3M18SACV-E RAS-3M18SAV-E
11
• Conditions
10
Indoor : DB27˚C/WB19˚C
9
Outdoor: DB35˚C/WB24˚C Indoor air flow: High
8
Pipe length : 5m × 3 3 units operating
7 6 5 4
Current (A)
3 2 1 0
0 10 20 30 40 50 60 70 90 0 10 20 30 40 50 60 70 80 90 100 120110
220V
230V
240V
80
Compressor speed (rps)
11
• Conditions
10
Indoor : DB20˚C/WB15˚C
9
Outdoor: DB7˚C/WB6˚C Indoor air flow: High
8
Pipe length : 5m × 3 3 units operating
7 6 5 4
Current (A)
3 2 1 0
2-2-2. Capacity Variation Ratio According to Outdoor Temperature
<Cooling> <Heating>
RAS3M18SAV-E, RAS-3M18SACV-E RAS-3M18SAV-E
105 100
95 90 85 80 75 70 65
Capacity ratio (%)
60 55 50
32 33 34 35 36 37 38 39 43 –15 –10 –5 0 5 7 10
Current limited start
• Conditions Indoor : DB27˚C/WB19˚C Indoor air flow: High Pipe length : 5m × 3 3 units operating
40 41 42
Outdoor temp. (˚C)
110 100
90 80 70 60
Capacity ratio (%)
50 40
• Conditions Indoor : DB20˚C/WB15˚C Indoor air flow: High Pipe length : 5m × 3 3 units operating
220V
230V
240V
Compressor speed (rps)
Outdoor temp. (˚C)
2-2-3. Capacity Variation Ratio According to Pipe Length
<Cooling> <Heating>
RAS3M18SAV-E, RAS-3M18SACV-E RAS-3M18SAV-E
110
105
100
95
90
85
Coolimg capacity ratio (%)
80
• Conditions Indoor : DB27˚C/WB19˚C Outdoor: DB35˚C/WB24˚C Indoor air flow: High 3 units operating
Standard pipe length 15m
Maximum pipe length 50m
Total pipe length (m)
6050403020100
110
105
100
95
90
85
Heating capacity ratio (%)
80
Standard pipe length 15m
Maximum pipe length 50m
– 11 –
• Conditions Indoor : DB20˚C/WB15˚C Outdoor: DB7˚C/WB6˚C Indoor air flow: High 3 units operating
Total pipe length (m)
6050403020100
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refriger­ating oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the follow­ing precautions into consideration.
1. Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service por t differs from that of R22.
3. If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
4. When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is available on the market.
– 12 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of socket joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 13 –
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a conventional flare tool, be sure to secure “dimension A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Fig. 3-2-1 Flare processing dimensions
Flare tool for R410A
clutch type
ØD
A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1/4 3/8 1/2 5/8
Nominal
diameter
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
0.8
0.8
0.8
1.0
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Flare tool for R22
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Nominal
diameter
1/4 3/8 1/2 5/8
Table 3-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
– 14 –
Flare nut width
(mm)
17 22 26 29
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4 3/8 1/2 5/8 3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
45˚ to 46˚
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
B A
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
D
C
43˚ to 45˚
Flare nut width
(mm)
17 22 24 27 36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A
is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten­ing torque, comply with values designated by manufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4 3/8 1/2 5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
– 15 –
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air-water heat pump installation
No.
1
2
3
4 5 6
7 8
9
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
(Note 2) Charging cylinder for R410A is being currently developed.
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
Usage
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
R410A
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
× ×
× × ×
× ×
Conventional air-water
heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
× ×
¡
¡
×
¡
×
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are neces­sary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11. Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 16 –
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(Water heat exchanger unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened Open/close valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 17 –
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Reason why flux is necessary
• By removing the oxide film and any foreign matter on the metal surface, it assists the flow of brazing filler.
• In the brazing process, it prevents the metal surface from being oxidized.
• By reducing the brazing filler’s surface tension, the brazing filler adheres better to the treated metal.
– 18 –
2. Characteristics required for flux
• Activated temperature of flux coincides with the brazing temperature.
• Due to a wide effective temperature range, flux is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and brazing filler is minimum.
• It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver Silver
Used flux
Do not use
Paste flux
Vapor flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
3. When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
4. Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Nitrogen gas
Rubber plug
Fig. 3-5-1 Prevention of oxidation during braz-
– 19 –

4. CONSTRUCTION VIEWS

42
Hanging section
Stud bolt hole for Ø6
Outline of installation plate
Lower part hanging section
Center line of installation plateCenter line of main unit
Lower part hanging section
Stud bolt hole for Ø8 to Ø10
Product outline
( )
Minimum distance to wall
674
304
790
30491 91
2591
42
3
167.5
250
3
450 28810 10 10 10
790
Plasma pure filter
Air filter
Front panel
Knockout system Knockout system
55 65
208
790
607
250
7 51.5
Indoor heat exchanger
54.5 60 60 54.5
53
53
Installation plate hanging section
290
Installation plate hanging section Drain hose
(Outside length: 0.54m)
Connecting pipe (Outside length: 0.4m) Flare Ø9.52 (B16SKVP-E, M16SKCVP-E: Ø12.7)
Connecting pipe (Outside length: 0.45m) Flare Ø6.35
47 or more
74 or more140 or more
( )
Minimum distance to ceiling
( )
Remote controller holder
Wireless remote controller
64
125.5
163
5
58 19
Part of Remote controller
WH-H04JE
(Heat pump model)
WC-H04JE
(Cooling only model)
Minimum distance to wall
74.5
4-1. Indoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E
– 20 –
4-2. Outdoor Unit
RAS-3M18SAV-E, RAS-3M18SACV-E
– 21 –

5. WIRING DIAGRAM

5-1. Indoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E (Heat pump models) RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E (Cooling only models)
To outdoor unit
Air Purifier
Electrode
BRW
4
4
High-voltage
3
3
Power Supply
2
2
1 1
Indoor T erminal Block
BLK
BLK
WHI
1
113
CN01CN02 CN51
RED
321
Heat Exchanger
GRN & YEL
CN41
(RED) 121
2
Heat Exchanger Sensor (TCJ)
BLK
BLK
CN63 (YEL)
121
BRW BRW RED
4433221
CN42 (WHI)
2
BRW
Micro SW
BLU
Heat Exchanger Sensor (TC)
BLK
Thermo Sensor (TA)
BLK
Wireless Unit Assembly
BLK
BLK
WHI
1
1
BLU
2
2
BLU
3
3
BLU
4 4
BLU
5 5
BLU
6 6
BLU
7 7
BLU
8 8
MCC-5052
BLU
9 9
BLU
10 10
CN10 (WHI)
121
121
1 2 3 4 4 5 5 6 6 7 7 8 8 9 9
10 10
CN21 (WHI)
2
2
1 2 3
CN62 (BLU)
CN61
(WHI)
Main P. C. Board
MCC-5045
F01 Fuse AC 250V T3.15A
Varistor
R01
Line Filter
RED
1
1
2
2
BLK
3
3
WHI
4 4
CN31 (WHI)
CN32 (WHI)
+
DC5V
DC12V
Circuit
Power Supply
~
+
~
5 5 6 6
1 2 3 4 5 5
1 2 3 4
YEL
BLU
WHI
1
YEL
2
YEL
3
YEL
4
YEL
CN22 (WHI)
1 2 3 4 4 5 5
Fan Motor
DC Motor
1 2 3
Louver Motor
– 22 –
5-2. Outdoor Unit
RAS-3M18SAV-E, RAS-3M18SACV-E
NOTE
IGBT : Insulated Gate Bipolar Transistor PMV : Pulse Motor Valve TD : Discharge Temp. sensor TGa to TGc : Temp. sensor at A to C unit gas side TO : Outdoor Temp. sensor TE : Evaporator Temp. sensor TS : SuctionTemp. sensor 1 Heat Pump model only
Thermostat for compressor
ORN ORN
4-way valve coil
Fan motor
FM
PMV
C
PMV
B
PMV
A
1
GRY PNK
YEL BLK
WHI
RED
WHI GRY ORN RED
YEL
BLK
WHI GRY ORN RED
YEL
BLK
WHI GRY ORN RED
YEL
BLK
212
313
P501
1
P500
1
3
CN705
1
5
5
4
4
3
3
CN301
2
2
1
1
3
3
2
2
CN300
1
1
6
6
5
5
4
4
CN703
3
3
RED
2
2
1
1
6
6
5
5
4
4
CN702
3
3
WHI
2
2
1
1
6
6
5
5
4
4
CN701
3
3
YEL
2
2
1
1
RED
SUB P.C. Board
(MCC-818)
Photo coupler
P03 P04
ORN
Fan
circuit
F300 Fuse, T3.15A 250V
~
F500 Fuse, T6.3A 250V
P07 P05
WHI PNK
Color Identification
BLK : BLACK WHI : WHITE BLU : BLUE BRW : BROWN RED : RED ORN : ORANGE GRY : GRAY YEL : YELLOW PNK : PINK PUR : PURPLE GRN : GREEN
RED
2121212
CN802
313
CN607
CN606
CN605
CN604
1
CN603
CN602
CN601
CN302
CN800
CN303
CN501
GRN
1
313
BRW
1
313
YEL
1
212
BLU
1
212
BLK
1
313
1
212
1
313
1
5 5 5 5 4 4 4 4 3 3 3 3 212
1
212
1
313
1
~
1
BLU YEL
BLK WHI BLU RED PNK
PUR
ORN
WHI RED
TGc
TGb
TGa
TE
TS
TD
TO
Compressor
CN22 CN21
P.C. Board
(MCC-1438)
Power supply circuit
(For P.C. Board)
313
CN04
1
CN06
212
1
212
CN05
1
5 5 313
CN13
1
F01 Fuse T25A 250V
CN01 CN02
BLK
CM
BLK
WHI
RED
3 2 1 3 2 1
F04 Fuse T3.15A 250V
~
Power relay
RY02
RB05
~
CN20
T02 CT
Varistor
WHI
Reactor
T03 CT
T04 CT
C13 C12 C11 C10
Surge
absorber
F02 Fuse T25A 250V
P20 P19
P18 P17
~
P23 P24
P13 P12
P22 P21
P09 P08
CN03
BLK
+
BU EU BV EV BW EW BX BY BZ
YEL
BLU
G C E
+ ~ ~
+ ~ ~
RED
212
BRW
212
Q404
DB02
DB01
1
1
Q200
IGBT
(PFC)
Diode (PFC)
Diode
IGBT
module
block
block
Reactor
Reactor
To
Indoor unit A
1 2 3 L N 2 311 2 3
To
Indoor unit B
Terminal block
– 23 –
Power supply
~
220 240V
220 220V ~60Hz
50Hz
Capacitor
Indoor unit C
To

6. SPECIFICATIONS OF ELECTRICAL PARTS

6-1. Indoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E
No.
1
Fan motor (for indoor)
2
Room temp. sensor (TA-sensor)
3
Heat exchanger temp. sensor (TC-sensor)
4
Heat exchanger temp. sensor (TCJ-sensor)
5
Louver motor
Parts name
6-2. Outdoor Unit
RAS-3M18SAV-E, RAS-3M18SACV-E
1
1
1
No.
SC coil (Noise filter) (L01), (L03)
1
SC coil (Noise filter) (L02)
2
DC-DC transformer
3
Outside fan motor
4
Relay (4-way valve)
5
Relay (Power relay)
Discharge temp. sensor
6
(TD-sensor)
Outside air temp. sensor
7
(TO-sensor)
Temp. sensor at A room
8
gas side (TGA-sensor)
Temp. sensor at B room
9
gas side (TGB-sensor)
Temp. sensor at C room
10
gas side (TGC-sensor)
Evaporator temp. sensor
11
(TE-sensor)
Suction temp. sensor
12
(TS-sensor)
13
Terminal block (9P)
14
Fuse
15
Electrolytic capacitor
16
Transistor module
17
Compressor
18
Compressor thermo.
19
Diode block (Rectifire)
20
Reactor (Main)
21
Reactor (Sub)
Parts name
For protection of switching power source (F04) For protection of power factor converter circuit
breakage For protection of inverter input overcurrent For protection of switching power source (F300) For protection of power source
Type
MF-280-30-5R
( – ) ( – ) ( – )
MP24Z3N
Model name
SC-15-06J-B
SC-20-03J
SWT-75
ICF-140-43-2R
G5NB-1A
G4A-1A-PE-CA
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
(Inverter attached)
LLQ2G501KHUATF
6MBI25GS-060-51A
DA130A1F-25F
US622KXTMQO
D25XB60 CH-47-Z-T CH-43-Z-T
Specifications
DC280–340V, 30W 10k at 25°C 10k at 25°C 10k at 25°C Output (Rated) 1W, 16 poles, DC12V
Rating
AC 250V, 15A, 0.6mH AC 250V, 20A, 0.3mH Primary side DC 240 – 390V
Secondary side : 7V × 1, 13V × 1
16V × 3 DC 140V, 43W Coil : DC 12V
Contact : 2A, AC250V Coil : DC 12V
Contact : 20A, AC250V 64k (20°C)
10k (25°C)
10k (25°C)
10k (25°C)
10k (25°C)
10k (25°C)
10k (25°C) AC 250V, 20A
AC 250V, 3.15A AC 250V, 25A AC 250V, 25A
AC 250V, 3.15A AC 250V, 6.3A DC 400V, 500µF 600V, 25A 3 phases, 4 poles, 1100W OFF : 125 ± 4°C, ON : 90 ± 5°C AC 600V, 25A L = 8mH, 16A L = 10mH, 1A
NOTE) ∗1 : Heat pump model only.
– 24 –

7. REFRIGERANT CYCLE DIAGRAM

7-1. Indoor Unit, Outdoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E / RAS-3M18SAV-E
T1
Temp. measurement
To
C room
B room
To
C room
To
B room
INDOOR UNIT A
Indoor heat
exchanger
Cross flow fan
To
Connecting pipe Thickness : 0.8 mm
9.52 : RAS-B10SKVP-E RAS-B13SKVP-E
12.7 : RAS-B16SKVP-E
Pressure
P
measurement Gauge attaching port
Vacuum pump connecting port
Accumulating tank
54 370
Connecting pipe Thickness : 0.8 mm
6.35
Sectional shape of heat insulator
( 9.52) ( 9.52) ( 9.52) ( 6.35) ( 6.35) ( 6.35)
Strainer
TGaTGbTGc
Pulse motor valve at liquid side (UKV-18D64)
TD
Compressor DA130A1F-25F
Per 1 unit Max. : 20m Min. : 2m
Total Max. : 50m
Allowable height
difference : 10m
Allowable pipe length
Temp. measurement
Outdoor heat
exchanger
T
2
Propeller fan
OUTDOOR UNIT
TE
TO
Refrigerant amount : 1.5kg (R410A)
NOTE : Gas leak check position Refrigerant flow (Cooling)
Refrigerant flow (Heating)
NOTE :
• The maximum pipe length of this air conditioner is 50 m. The additional chaging of refrigerant is unneces-
sary because this air cinditioner is designed with charge-less specification.
• Never connect one indoor unit only. Two or more indoor units should be connected.
– 25 –
RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E / RAS-3M18SACV-E
T1
Temp. measurement
To
C room
To
B room
To
C room
To
B room
INDOOR UNIT A
Indoor heat
exchanger
Cross flow fan
Connecting pipe Thickness : 0.8 mm
9.52 : RAS-M10SKCVP-E RAS-M13SKCVP-E
12.7 : RAS-M16SKCVP-E
Pressure
P
measurement Gauge attaching port
Vacuum pump connecting port
Accumulating tank
54 370
Connecting pipe Thickness : 0.8 mm
6.35
Sectional shape of heat insulator
( 9.52) ( 9.52) ( 9.52) ( 6.35) ( 6.35) ( 6.35)
Strainer
TGaTGbTGc
Pulse motor valve at liquid side (UKV-18D64)
TD
Compressor DA130A1F-25F
Per 1 unit Max. : 20m Min. : 2m
Total Max. : 50m
Allowable height
difference : 10m
Allowable pipe length
Outdoor heat
exchanger
Temp. measurement
T
2
Propeller fan
OUTDOOR UNIT
TO
Refrigerant amount : 1.5kg (R410A)
NOTE :
Gas leak check position Refrigerant flow
NOTE :
• The maximum pipe length of this air conditioner is 50 m. The additional chaging of refrigerant is unneces-
sary because this air cinditioner is designed with charge-less specification.
• Never connect one indoor unit only. Two or more indoor units should be connected.
– 26 –
7-2. Operation Data
Outdoor Unit : RAS-3M18SAV-E
<Cooling>
Temperature
condition
Indoor Outdoor
27 /19°C 35 / –°C
No. of
operating
units
1 unit
2 units
3 units
Operating
combination (Unit)
ABC
10 –– 13 –– 16 –– 10 10 – 13 10 – 16 10 – 13 13 – 10 10 10 13 10 10 16 10 10 13 13 10
Standard pressure
P (MPa)
0.8 to 1.0
0.7 to 0.9
0.6 to 0.8
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
11 to 13 42 to 44
8 to 10 46 to 48
6 to 8 49 to 51 13 to 14 48 to 50 13 to 14 48 to 50 13 to 14 48 to 50 13 to 14 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50
Indoor
fan
(Manual)
High High High High High High High High High High High
Outdoor
fan
MED MED MED MED MED MED MED MED MED MED MED
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor themometer)
2. Connecting piping condition : 5 meters × 3 units (5m/each indoor unit)
Compressor
revolution
(rps)
32 52 75 63 63 65 65 62 62 62 62
Outdoor Unit : RAS-3M18SAV-E
<Heating>
Temperature
condition
Indoor Outdoor
20 / –°C7 / 6°C
No. of
operating
units
1 unit
2 units
3 units
Operating
combination (Unit)
ABC
10 –– 13 –– 16 –– 10 10 – 13 10 – 16 10 – 13 13 – 10 10 10 13 10 10 16 10 10 13 13 10
Standard pressure
P (MPa)
2.6 to 2.8
3.1 to 3.3
3.5 to 3.7
2.7 to 2.9
2.7 to 2.9
2.8 to 3.0
2.8 to 3.0
2.2 to 2.4
2.2 to 2.4
2.2 to 2.4
2.2 to 2.4
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
42 to 44 2 to 4 48 to 50 1 to 3
51 to 53 1 to 3
36 to 38 –1 to 1 36 to 38 –1 to 1 36 to 38 –1 to 1 36 to 38 –1 to 1 32 to 34 –1 to 1 32 to 34 –1 to 1 32 to 34 –1 to 1 32 to 34 –1 to 1
Indoor
fan
(Manual)
High High High High High High High High High High High
Outdoor
fan
MED MED MED MED MED MED MED MED MED MED MED
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor themometer)
2. Connecting piping condition : 5 meters × 3 units (5m/each indoor unit)
Compressor
revolution
(rps)
57 70 81 95 95 98 98 92 93 93 93
– 27 –
Outdoor Unit : RAS-3M18SACV-E
<Cooling>
Temperature
condition
Indoor Outdoor
27 /19°C 35 / –°C
No. of
operating
units
1 unit
2 units
3 units
Operating
combination (Unit)
ABC
10 –– 13 –– 16 –– 10 10 – 13 10 – 16 10 – 13 13 – 10 10 10 13 10 10 16 10 10 13 13 10
Standard pressure
P (MPa)
0.8 to 1.0
0.7 to 0.9
0.6 to 0.8
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
0.8 to 1.0
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
11 to 13 42 to 44
8 to 10 46 to 48
6 to 8 49 to 51 13 to 14 48 to 50 13 to 14 48 to 50 13 to 14 48 to 50 13 to 14 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50 16 to 18 48 to 50
Indoor
fan
(Manual)
High High High High High High High High High High High
Outdoor
fan
MED MED MED MED MED MED MED MED MED MED MED
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor themometer)
2. Connecting piping condition : 5 meters × 3 units (5m/each indoor unit)
Compressor
revolution
(rps)
32 52 75 63 63 65 65 62 62 62 62
– 28 –

8. CONTROL BLOCK DIAGRAM

8-1. Indoor Unit
RAS-B10SKVP-E, RAS-B13SKVP-E, RAS-B16SKVP-E
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
M.C.U.
Functions
• Cold draft preventing Function
• 3-minute Delay at Restart for Compressor
• Fan Motor Starting Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
• Clean Function
Serial Signal Transmitter/Receiver
Indoor Unit Control Unit
Louver
Motor
Louver Motor
Drive Control
Indoor Fan
Motor Control
Indoor
Fan Motor
Air purifier
unit
Micro Switch
From Outdoor Unit
~
220-240V
220V
50Hz
~
60Hz
REMOTE CONTROLLER
Serial Signal Communication
(Operation Command and Information)
Remote Controller
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
Hi-POWER
Infrared Rays, 36.7kHz
SLEEP MODE
– 29 –
Air Purifier
RAS-M10SKCVP-E, RAS-M13SKCVP-E, RAS-M16SKCVP-E
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Converter
(D.C circuit)
Noise Filter
M.C.U.
Functions
• 3-minute Delay at Restart for Compressor
• Fan Motor Starting Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
• Clean Function
Serial Signal Transmitter/Receiver
Indoor Unit Control Unit
Louver
Motor
Louver Motor Drive Control
Indoor Fan
Motor Control
Indoor
Fan Motor
Air purifier
unit
Micro Switch
From Outdoor Unit
220-240V
220V
~
50Hz
~
60Hz
REMOTE CONTROLLER
Serial Signal Communication
(Operation Command and Information)
Remote Controller
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
Hi-POWER
Infrared Rays, 36.7kHz
SLEEP MODE
– 30 –
Air Purifier
Loading...
+ 87 hidden pages