Toshiba RAS-24NKHD-E5, RAS-24NAH-E, RAS-18NKDX5-T, RAS-18N2AX-T, RAS-24NKDX5-T Service Manual

...
FILE NO. SVM-06010
SERVICE MANUAL
AIR CONDITIONER
SPLIT WALL TYPE
June, 2006
RAS-24NKHD-E5 / RAS-24NAH-E RAS-18NKDX5-T / RAS-18N2AX-T RAS-24NKDX5-T / RAS-24N2AX-T
FILE NO. SVM-06010
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit (24 Class)
2-3 Outdoor Unit (18 Class)
3. WIRING DIAGRAM
3-1 RAS-24NKHD-E5 / RAS-24N2AH-E 3-2 RAS-24NKDX5-T / RAS-24N2AX-T 3-3 RAS-18NKDX5-T / RAS-18N2AX-T
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-24NKHD-E5) 4-2 Outdoor Unit (RAS-24NAH-E) 4-3 Indoor Unit (RAS-18,24NKDX5-T) 4-4 Outdoor Unit (RAS-18N2AX-T)
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-24NKHD-E5 / RAS-24NAH-E 5-2 RAS-24NKDX5-T / RAS-24N2AX-T 5-3 RAS-18NKDX5-T / RAS-18N2AX-T
6. CONTROL BLOCK DIAGRAM
6-1 RAS-24NKHD-E5 6-2 RAS-18, 24NKDX5-T
1
4-4 Outdoor Unit (RAS-24N2AX-T)
7-10 QUIET Mode
7. OPERA
7-11 COMFORT SLEEP mode
TION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Defrosting Operation 7-7 Auto Restart Function 7-8 Filter Check Lamp 7-9 Self-Cleaning function
2
FILE NO. SVM-06010
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch
8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 How to Diagnose Faulty Part 9-6 Troubleshooting for Indoor Unit 9-7 Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire) 9-8 Troubleshooting for P.C. Board 9-9 Troubleshooting for Remote Control
10. PARTS REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E - Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit (RAS-24N2AH-E) 11-4 Outdoor Unit (RAS-24N2AX-T) 11-5 Outdoor Unit (RAS-18N2AX-T)
FILE NO. SVM-06010
RAS-24NKHD-E5
RAS-18NKDX5-T
ITEM Cooling Heating Cooling Cooling
RAS-24NKDX5-T
RAS-24NAH-E
Capacity kW
220 V 240 V 220 V 240 V
220 V 220 V
RAS-18N2AX-T
RAS-24N2AX-T
6.30 6.30 6.60 6.70 5.10 6.40
Phase 1
Power source V 220 240
Hz 50
Power consumption W
2430 2510 2310 2410
1560
2250
Power factor % 96 91 94 88
95
95
Running current A
0.3/7.2
0.3/10.50
Indoor/Outdoor
11.2 11.2 10.9 11.10
Starting current A
42
Moisture removal lit/h
2.5
Noise
Indoor (H/M/L) dB Outdoor (220 240 V) dB 56-57 57-58 56
Refrigerant
Name of refrigerant R22 Rated amount kg 2.00
Refrigerant control Capillary tube
Gas side size
mm
15.88
Connection type Flare connection Liquid side size
mm
6.35 Interconnection Connection type Flare connection pipe Maximum length
m
15*
1
(One way)
25*
2
Maximum height
INDOOR UNIT RAS-24NKHD-E5 RAS-18NKDX5-T RAS-24NKDX5-T
Height mm 298
Dimensions Width mm 998
Depth mm 220 Net weight kg 13 Evaporator type Finned tube Indoor fan type Cross flow fan
High fan m3/h 1050 1050
1050
Air volume Medium fan m3/h 830 900
975
Low fan m3/h 625 667 667 Fan motor output W 30 Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-24NAH-E RAS-18N2AX-T RAS-24N2AX-T
Height mm 715 Dimensions Width mm 780
Depth mm 290 Net weight kg 56
46
Condenser type Finned tube Outdoor fan type Propeller fan
W
42
W Safety device IOL, Td Sensor IOL Louver type Automatic louver Usable outdoor temperature range °C 15 ~ 43 10 ~ 24
1800
MODEL
0.3/
0.3/
0.3/ 0.3/
67
48/46/44/41/39
m
10
2440
220
2
48/45/42/38/33
1.50
20*
2
8
790 543
715 780
290
2400
1700
21 ~ 43
67
2.7
53/50/47/43/40
1.68
25*
2
10
1200
52
1800
PH400X3CS-4KT1
PH290X2C-4FT1
PH400X3CS-4KT1
1. SPECIFICATIONS
3
2550
2440
2550
FILE NO. SVM-06010
Note : 1
Capacity is based on the following temperature conditions.
Note : 2
Charge refrigerant according to the table below.
Temperature
Condition
JIS B8615-1
Cooling Heating
Indoor unit inlet air temperature
(DB) 27°C 20°C
(WB) 19°C 15°C
Outdoor unit inlet air temperature
(DB) 35°C 7°C
(WB) 24°C 6°C
Refrigerant
RAS-24NKHD-E5 / RAS-24NAH-E
RAS-18NKDX5-T / RAS-18N2AX-T
RAS-24NKDX5-T / RAS-24N2AX-T
*1 No need to charge
15 m or less 15 m or less
extra refrigerant
*2 Need to charge
Over 15 m up to 25 m (30 g/m) Over 15 m up to 20 m (20 g/m)
extra refrigerant
4
5
FILE NO. SVM-06010
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
Air outlet
Plasma air purifierHeat exchangerAir filter
Air inlet
998
220
50
75
8
Knock out system
75
56
50
58
19
163
Wireless remote control
Connection pipe (0.49 m) (Flare 6.35)
Drain hose (0.54 m)
90 or more
Minimum distance
to ceiling
100
40
48
450
20
20
48
100
65
998
298
10
763.5
5555
55
41
29
6
5
(For stud bolt 6) (For stud bolt 8 - ∅ 10)
Installation Plate outline
Outline of indoor unit
Connection pipe (0.39 m) (Flare 15.88)
Back body
Front panel
Grille inlet
298
75
7
51
Knock out system
HANDLE
COVER-PV
HANDLE
600
Z View
Service port
321
307
A Detail Drawing (Back leg)
Ø
25 Drain outlet
2Ø11x14 Hole (For
Ø8-Ø
10 anchor bolt)
B
Ø
6
Hole
Ø
11x14 Hole
50 36
R
15
R
5.5
Ø
6 hole
28
321
86
A
124109
6
00 or more
Air out
let
321
600
Air inlet
4x
Ø
11 Long holes(For
Ø8-Ø
10 anchor bolt)
Gas-side (Flare Ø15.88)
Liquid side (Flare Ø6.35)
90 600 90 69
342
321
Z
50
36
R
15
B Detail Drawing (Front leg)
Ø
436
FAN-GUARD
715
290
275
600 or more
84
129
54
Electrical part cover
321
307
100 or more
100 or more
Installation dimension
2.2 Outdoor Unit
FILE NO. SVM-06010
6
FILE NO. SVM-06010
3. WIRING DIAGRAM
3-1. RAS-24NKHD-E5 / RAS-24NAH-E
1
1 2 3
3
1
1 2 3
3
i
L
N
3
1
2
i
FERRITE CORE
GRN&YEL
RED
RED
BLK
BLK
MAGNETIC
CONTACTOR
R
A1
A2
52C
U
S
V
T
W
PNK
WHI
COMPRESSOR TERMINAL
BLK
S
R
C
WHI
BLK BLK
COIL FOR 4 WAY VALVE
RED
RED
RED
CAPACITOR
CAPACITOR
BLK BLK WHI RED
CN01
CN05
GRY
1 3 5 7 9
1 3 5 7 9
GRN&YEL
CHASSIS
TRANSFORMER
BLK BLK
RED RED
1
1
3
3
1
1
3
3
2
CN11
BLU
YEL
1 313
1 1
3
CN02
BLU
BLU
11 33
CN03
F01
250VAC T6. 3A
CR11
CR12
CR13
RY07
RY05
RY06
SG01
CN06
TNR R74
TNR R73
MAIN P.C. BOARD (MCC-890)
COMPRESSOR
FAN MOTOR
POWER SUPPLY 220- 240 V ~ 50 Hz
R
3
1
2
3
1
2
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
INDOOR UNIT
C OLO R IDE NT IF IC ATI ON
BR W : BR O WN R E D : R ED WH I : WH ITE YE L : YE LL OW BL U : B LUE BL K : B LA CK GR Y : G RA Y OR N : O R ANG E GR N : GR E E N PN K : P INK
G R N& YE L : G R E EN & YE LL OW
4
5
S erial Signa l circuit
MAI N P .C . B OA R D (W P -008)
3
2
1
CN 30
FA N MO TO R
DC MO TO R
CN 10
sens or (TA )
The rmo.
(TC )
sens or
Hea t excha nger
B
L
K
B
L
K
B
L
K
B
L
K
CN 03 CN 01
1 2
21
21
21
WP -008
electrode
Air purifier
e
l
e
c
t
r
o
d
e
I
o
n
B
L
K
B
L
K
/
R
E
D
RE D B LK
+5V
+12V (B )
+12V (A)
Powe r s upply
High-voltage
BLK
BR W
R
E
D
B
R
W
B
R
W
CN 34
RE D
BR W
BR W
BR W
Micro S W .
BLU
BR W
4334
2 2
11
2112
CN 34
10
10
9988776655443
3
21
21
10
10
9988776655443
3
2
211
W
HI
BL U
BL U
BL U
BL U
BL U
BL U
BL U
BL U
BL U
CN 13
CN 25
MCC -81 9
and I ndication parts
Infrare d rays rec eive
Louve r motor
BR W
R ED
OR N
YE L
PN K
BL U
6655443
3
2
2 1
1
CN 07
C0 3
DB 01R01
C0 2C0 1
L01
V a ris
tor
6.3 A 25 0V
F0 1
DS A
Va ristor
P0 4BL K
DISCHARGE PIPE SENSOR (TD)
HEAT EXCHANGER SENSOR (TE)
CN08
CN07
BLU
BLU
BLK
BLK
S
OUTDOOR
C
UNIT
7
FILE NO. SVM-06010
3-2. RAS-24NKDX5-T / RAS-24N2AX-T
i
L
N
i
GRN&YEL
RED
RED
RED
RED
BLK
BLK
CHASSIS
GRY
POWER SUPPLY 220 V ~ 50 Hz
SPARK KILLER
MAGNETIC CONTACTOR
BLK BLK
RED
A2 A1
52C
1/L1 2/T1
3/L2 4/T2
5/L3
6/T3
COMPRESSOR
WHI PNK
BLK
C
S
R
CAPACITOR
CAPACITOR
WHI RED
F AN M OT OR
B LK
C OMP R ES S O R TE R MIN AL
R
S
C
INDOOR TERMINAL BLOCK
INDOOR UNIT
3
1
2
566
BLUPN K
YE L
OR N
R ED
BR W
Louve r motor
Infrare d rays rec eive and I ndication parts
MCC -81 9
CN 25
CN 13
BL U
BL U
BL U
BL U
BL U
BL U
BL U
BL U
BL U
W
HI
112
2
334
4 5
5 6677889
9
10 10
1 2 1 2
3
3 445
5 6
6 778
8 9
9
10 10
CN 34
2
1 1 2
1 1
22
4 3 3
4
BR W BL U
Micro S W .
BR W BR W BR W RE D
CN 34
B
R
W
B
R
W
R
E
D
BR W
BL K
High-voltage
Powe r s upply
+12V (A)
+12V (B )
+5V
BL KR ED
B
L
K
/
R
E
D
B
L
K
I
o
n
e
l
e
c
t
r
o
d
e
Air purifier
electrode
WP -008
1 2 1
2
1 2
2
1
CN 01CN 03
B
L
K
B
L
K
B
L
K
B
L
K
Hea t excha nger se nsor (T C)
The rmo.
(T A)
se nsor
CN 10
DC MO TO R
FA N MO TO R
R elay
CN 30
1
2 3
1 1
3 3
MAI N P .C . B OA R D
BL K P 04
Va ristor
DS A
F0 1
6.3 A 25 0V
Va ristor
L01
C0 1 C0 2
R 01 D B01
C0 3
CN 07
1122
33445
BR W : BR O WN R E D : R ED WH I : WH ITE YE L : YE LL OW BL U : B LU E BL K : B LA CK GR Y : G RA Y OR N : O R ANG E GR N : GR E E N P NK : P INK
G R N& YE L : G R E EN & YE L LOW
C OLO R IDE N TIF IC ATI ON
GR N &Y EL
BL K
WH I
R E D
C N31
C N27
1 1
3
3 445
5 6
6
112
2
334
4 5
5 6
6
112
23344
P ower s upply
circuit
3
1
2
OUTDOOR TERMINAL BLOCK
OUTDOOR UNIT
8
FILE NO. SVM-06010
3-3. RAS-18NKDX5-T / RAS-18N2AX-T
i
L
N
3
1
2
i
GRN&YEL
RED
RED
RED
RED
BLK
BLK
CHASSIS
GRY
POWER SUPPLY 220 V ~ 50 Hz
SPARK KILLER
MAGNETIC CONTACTOR
BLK BLK
RED
A1 A2
52C
R U
SV
TW
COMPRESSOR
WHI PNK
BLK
C
S
R
FAN MOTOR
BLK
COMPRESSOR TERMINAL
OUTDOOR TERMINAL BLOCK
OUTDOOR UNIT
R
S
C
CAPACITOR
CAPACITOR
WHI
RED
9
INDOOR TERMINAL
566
BL U
PN K
YE L
OR N
R ED
BR W
Louve r motor
Infrare d rays rec eive and I ndication parts
MCC -81 9
CN 25
CN 13
BLUBLUBLUBLUBLUBLUBLUBLUBL
U
W
HI
112
2
334
4 5
5 6677889
9
10 10
1 2 1 2
3
3 445
5 6
6 778
8 9
9
10 10
CN 34
2
1 1 2
1 1
22
4 3 3
4
BR W BL U
Micro S W .
BR W BR W BR W RE D
CN 34
B
R
W
B
R
W
R
E
D
BR W
BL K
High-voltage
Powe r s upply
+12V (A)
+12V (B )
+5V
BL KR ED
B
L
K
/
R
E
D
B
L
K
I
o
n
e
l
e
c
t
r
o
d
e
Air purifier
electrode
WP -008
1 2 1
2
1 2
2
1
CN 01CN 03
B
L
K
B
L
K
B
L
K
B
L
K
Hea t excha nger se nsor (T C)
The rmo.
(T A)
se nsor
CN 10
DC MO TO R
FA N MO TO R
R elay
CN 30
1 2 3
1 1
3 3
MAI N P .C . B OA R D
BL K P 04
Va ristor
DS A
F0 1
6.3 A 25 0V
Va ris
tor
L01
C0 1 C0 2
R 01 D B01
C0 3
CN 07
1122
33445
BR W : BR O WN R E D : R ED WH I : WH ITE YE L : YE LL OW BL U : B LU E BL K : B LA CK GR Y : G RA Y OR N : O R ANG E GR N : GR E E N P NK : P INK
G R N& YE L : G R E EN & YE L LOW
C OLO R IDE N TIF IC ATI ON
GR N &Y EL
BL K
WH I
R E D
C N31
C N27
1 1
3
3 445
5 6
6
112
2
334
4 5
5 6
6
112
23344
P ower s upply
circuit
BLOCK
INDOOR UNIT
3
1
2
FILE NO. SVM-06010
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
4-2. Outdoor Unit (RAS-24NAH-E)
No. Parts name Type Specifications
Output (Rated) 2200 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
1 Compressor PH400X3CS-4KT1 Winding resistance () C-R C-S
(at 20°C) 1.13 2.10
Output (Rated) 42 W, 4 poles, 1 phase, 220 – 240 V, 50 Hz
2 Fan motor (for outdoor) FG-240-42A-1 Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
3
Running capacitor
451405L AC 450 V, 4.0µF
(for fan motor)
4
Running capacitor
RS44B506K0218S AC 440 V, 50µF
(for compressor)
5
Solenoid coil
VHV (STF) AC 220 – 240 V
(for 4-way valve)
6 Thermo sensor TE / TD 10 k at 25°C / 50 k at 25°C
7 Magnetic contactor A35 220 240 V, 50 Hz
8 Transformer TT-05 220 – 240 V
9 Microcontroller TMP47C840N 10 Varistor (R73, R74, R86) 15G471K 470 V 11 Fuse (F01) MT3 T6.3 A, 250 V
No. Parts name Type Specifications
1 Fan motor (for indoor) ICF-340-30-2 DC 310-340V, 30W 2 Thermo sensor (TA-sensor) ——— 10 k at 25°C 3 Switchins transformer (T01) SWT-77 Output DC 7V, 12Va and 12Vb 4 Microcontroller TMP87CM40ANG 6G60 5 Heat exchanger sensor
——— 10 k at 25°C
(TC-sensor) 6 Line filter (L01) SS11V-R07190 19 mH, AC 0.7 A 7 Diode (DB01) D3SBA60 4 A, 600 V 8 Capacitor (C03) EKMH451VSN121MQ35S 120µF, 450 V 9 Fuse (F01) TSCR T6.3 A, 250 V
10 Switching IC (IC01) MA8920 5 A, 900 V 11 Varistor (R09, R10) 15G561K 560 V 12 Resistor (R01) RF-5TK4R8 1.8 , 5 W 13 Louver motor MP35EA12 Output (Rated) 2 W, 10 poles, 1 phase,
DC 12 V
10
FILE NO. SVM-06010
4-3. Outdoor Unit (RAS-18N2AX-T)
4-4. Indoor Unit (RAS-24N2AX-T)
No. Parts name Type Specifications
Output (Rated) 1500 W, 2 poles, 1 phase, 220 – 240 V, 50 Hz
1 Compressor PH290X2C-4FT1 Winding resistance (Ω) C-R C-S
(at 20°C) 1.71 3.09 Output (Rated) 42 W, 4 poles, 1 phase, 220 – 240 V, 50 Hz
2 Fan motor (for outdoor) FG-240-42A Winding resistance (Ω) Red-Black White-Black
(at 20°C) 128 126
3
Running capacitor
451305L AC 450 V, 3.0µF
(for fan motor)
4
Running capacitor
RA44B356U0215S AC 440 V, 35µF
(for compressor)
5 Magnetic contactor CLK-26J 220 – 240 V, 50 Hz
11
No. Parts name Type Specifications
Output (Rated) 2200 W, 2 poles, 1 phase, 220 − 240 V, 50 Hz
1 Compressor PH400X3CS-4KT1 Winding resistance ( ) C-R C-S
(at 20 °C) Output (Rated) 42 W, 4 poles, 1 phase, 220 240 V, 50 Hz Winding resistance () Red-Black White-Black
2 Fan motor (for outdoor)
(at 20 °C)
128 126
FG-240-42A
AC 440 V, 50µF
1.13
2.10
3
Running capacitor
451305L
AC 450 V, 3.0µF
(for fan motor)
RS44B506U0218S
4
5 Magnetic contactor
A35
220 − 240 V, 50 Hz
Running capacitor
(for compressor)
FILE NO. SVM-06010
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-24NKHD-E5 / RAS-24NAH-E
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*1 : During heating overload, the high temperature limit control operation is included.
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 1.72 43.5 High 20/ 7/6
Heating High temperature 2.21 58.9 Low 27/ 24/18
Low temperature*1 1.35 38.4 High 20/ 10/10 Standard 0.43 11.0 High 27/19 35/24
Cooling High temperature 0.53 15.7 High 32/23 43/26
Low temperature 0.34 1.4 Low 21/15 21/15
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger inter changing
pipe
T
(°C)
Fan speed
(indoor)
50 Hz
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PH400X3CS-4KT1
Accumulator
Cooling Heating
Mark ( ) means check points of Gas Leak
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Heating
Gas container connection (Reinstall etc.)
Packed valve
(
6.35)
Packed valve
(∅15.88)
0.39 m (Connecting pipe)
15.88
0.49 m (Connecting pipe)
6.35
T
P
Refrigerant R22
2.00kg
Capillary tube
1.0x1200 l
Capillary tube
2.0x1400 l
12
FILE NO. SVM-06010
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
5-4. RAS-24NKDX5-T / RAS-24N2AX-T
Evaporator
Indoor unit
Cross flow fan
Cooling
Compressor
Condenser
Propeller fan Outdoor unit
PH400X3CS-4KT1
Cooling
O.D.:15.88 mm O.D.:6.35 mm
Cooling
Gas container connection (Reinstall etc.)
Packed valve
(
6.35)
Packed valve
(∅15.88)
0.39 m (Connecting pipe)
15.88
0.49 m (Connecting pipe)
6.35
T
P
Refrigerant R22 1.68 kg
Mark ( ) means check points of Gas Leak
Capillary tube
2.4x700
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.46 10.4 High 27/19 35/24
Cooling High temperature 0.56 13.8 High 32/23 43/26*
Low temperature
0.3
2 2.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
l
13
FILE NO. SVM-06010
5-8. RAS-18NKDX5-T / RAS-18N2AX-T
Indoor unit
Cross flow fan
Compressor
Condenser
Propeller fan
Outdoor unit
PH290X2C-4FT1
O.D.:15.88 mm O.D.:6.35 mm
Packed valve
(15.88)
Packed valve
(6.35)
T
P
Refrigerant R22 1.50 kg
Evaporator
0.39 m
(Connecting pipe)
15.88
0.49 m (Connecting pipe) 6.35
Mark ( ) means check points of Gas Leak
Capillary tube
2.0x1000 s
Accumulator
Note : Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.52 11.0 High 27/19 35/24
Cooling High temperature 0.62 14.7 High 32/23 43/26
Low temperature 0.38 3.0 Low 21/15 21/15
Fan speed
(indoor)
50 Hz
Standard
pressure
P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe
T
(°C)
14
FILE NO. SVM-06010
6. CONTROL BLOCK DIAGRAM
6-1. RAS-24NKHD-E5
REMOTE CONTROL
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
Infrared Rays
Indoor Unit Control Panel
Heat Exchanger Sensor
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
From Outdoor Unit
220 ~ 240 V AC 50 Hz
M.C.U.
Functions
Louver Control
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
Timer
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Operation
Display
Timer
Display
Filter Sign
Display
PRE DEF.
Sign Display
Indoor
Fan Motor
Hi Power
Sign Display
Louver Motor
Infrared
Rays
Remote
Control
(Temperature Processing)
15
FILE NO. SVM-06010
6-2. RAS-18, 24NKDX5-T
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
Infrared Rays
Heat Exchanger Sensor
Relay RY04
Outdoor Unit
Outdoor unit
ON/OFF Signal
Relay Driver
Indoor Unit Control Panel
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise Filter
From Outdoor Unit 220 ~ 240 V AC 50 Hz
M.C.U.
Functions
Louver Control
3-minute Delay at Restart for Compressor
Motor Revolution Control
Processing
Timer
Louver ON/OFF Signal
Louver Driver
Operation
Display
Timer
Display
Filter Sign
Display
Fan Only
Sign Display
Indoor
Fan Motor
Hi Power
Sign Display
Louver Motor
Infrared
Rays
Remote
Control
(Temperature Processing)
REMOTE CONTROL
16
FILE NO. SVM-06010
7. OPERATION DESCRIPTION
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts swinging. When [FIX] button is pressed, it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
+
and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and the room temperature.
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit controller. The outdoor unit controller receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes them.
Temperature measurement at the air inlet of the indoor heat exchanger by the indoor
temperature sensor
Temperature setting of the indoor heat
exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status and judging of the information or indication of error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and executes them.
Compressor operation control
Operation control of
outdoor fan motor
Turning off the compressor and outdoor fan when the outdoor unit receives the shutdown command
Defrost control in heating operation (Temperature measurement by the outdoor heat exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only
Operations according to the commands
from the indoor unit
LOW
+
=
MED+=
LOW+MED
2
MED+HIGH
2
Table 7-1-1
17
FAN TAP
Cooling UH H M+
L+
L- SUL/SL-
OPERATION
Fan only
H
M
L
L-
Dry
M
L
L- UL SUL
MODE
Heat
UH H
M+
L
RAS-18NKDX5-T
rpm
1400
Air flow volume (m3/h)
975 900
1200
1100
380 220
RAS-24NKHD-E5
rpm
1125
1400
708
Air flow volume (m3/h)
1200
1300
300
1400
975
1050
700
975
1200
900
380
Model
1050
1500
1050
RAS-24NKDX5-T
rpm Air flow volume (m3/h)
SUL/SL-
1500
U
1600
LL+
790
M+ M
L+
L
L-
1700
M
L+
L
800
600
461
700 380
461
800
800 461
900
543
543
900
900
543
1050
666
625
1000
1300
700
500
1050 1300
900
1500
790
666
1000
625
1200
790
600
300
600 300
FILE NO. SVM-06010
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation can be effected thereafter simply by pressing [ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L–.
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-2.
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L–.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
*1 *1 *1
+3 +2.5 +2 +1.5 +1 +0.5
-0.5
0
M+
Preset temp.
°C
(Room temp.) (Preset temp.)
0.5
0
Preset temp.
ON ON
OFF OFF OFF ON
Compressor
4-way valve
Outdoor fan
OPERATION
display lamp
(Room temp.) (Preset temp.)
(Preset temp.: 24°C)
+2
+2.5
+3
°C
+1.5 +1 +0.5 0
M+
*1 *1 *1
(Room temp.) (Preset temp.)
Preset temp.
°C
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
(2) The Hi POWER, ECO and COMFORT SLEEP
18
FILE NO. SVM-06010
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-6.
Fig. 7-2-6
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in Fig. 7-2-4.
Fig. 7-2-4
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset temperatures is shown in Fig. 7-2-5.
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO and Hi Power operations can not be set.
Preset temp.
+3
+2
+1
0
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
L. *S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*Super Low
OFF
ON
OFF
4-way valve
Outdoor fan
OPERATION
Compressor
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
display lamp
(Room temp.) (Preset temp.)
R oom temp.
ON
OFF
ON
OFF
ON
4-way valve
Outdoor fan
Compressor
Preset temp.
OPERATION
display lamp
0
0.5
(Room temp.) (Preset temp.)
ON
[FAN AUTO]
-0.5
-1
-1.5
-2
*1 *2
-5.0
-5.5
0
Preset temp.
M
+
H
L
°C
(Room temp.) (Preset temp.)
°C
°C
19
20
FILE NO. SVM-06010
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-2-8 and Table 7-2-1.
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF. *2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24°C. *3: SUL means Super Ultra Low. *4: Calculated from difference in motor speed
between SUL and HIGH.
Fig. 7-2-8 Cold draft preventing control
*5 and *6:
Table 7-2-1
Fan *5 *6 speed Starting period Stabilized period
AUTO • Up until 12 minutes
passed after starting the unit
From 12 to 25 minutes passed after starting the unit and room temperature is 3°C lower than preset temperature
Manual • Room temperature (L – H) < Preset temperature
–4°C
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit
is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-9.
Fig. 7-2-9
From 12 to 25 minutes passed after starting the unit and room temperature is between preset temperature and 3°C lower than preset temperature
25 minutes or more passed after starting the unit
Room temperature
Preset temperature
–3.5°C
A+4 A+4
A-8 A-8
464534
33
33 21 32 20
*2
*6 *5
Manual (One of 5 steps)
L-H (Up to setting speed)
AUTO
*4
SUL*
3
SUL*1 Stop
(Room temp.) (Preset temp.)
°C
+4
0
-1
The louver moves to the position same as Hi POWER operation.
Cooling operation
Heating operation
Cooling operation
Fan only operation
RAS-24NKHD-E5 RAS-24NKDX5-T
RAS-18NKDX5-T
7-2-6. Plasma Air-Purifier (PAP) operation.
Plasma Air-Purifier is able to operate together with other operations mode of air conditioner by pressing [PAP] button to turn ON/OFF the Plasma Air-Purifier while other mode is on operation. Plasma Air-Purifier is able to operate individual by pressing [PAP] button to turn ON/OFF instead of pressing [
] button.
For pressing the [
] button is able to turn both air conditioner and Plasma Air-Purifier ON/OFF at the same time. (depends on presetting before turning off.)
When [PAP] button is pressed, mark is indicated on the display of the remote control and the Plasma Air-Purifier operates as follows.
21
FILE NO. SVM-06010
(1) Operation flow chat.
Descriptions
In case of the first operation, after circuit breaker turns OFF/ON or after reset by case No. 4-1, 4-2, 8 and 9. The Air-Purifier will operates after 1 hour.
For daily used, without turning OFF circuit breaker, Air-Purifier operates immediately. By using short timer function of remote control*, Air-Purifier operates immediately. In case of some error occurs within 1 minute, the above items need to be checked. Case no 3, reset by [RESET] button on the indoor unit. Then Air-Purifier will operate again after 1 hour. Case no 3, reset by [FILTER] button on the remote control. Then Air-Purifier will operate again after 1 hour. Case no 3, reset by turning OFF the unit and turning ON again. Then Air-Purifier operates immediately. In case of some error occurs after 1 minute. Air-Purifier will turn OFF but in contrast, PAP LED will keep turning
ON continuously. Case no 5, the Air-Purifier will operate again after 10 minute. After complete 500 hours operation, FILTER LED will turn ON and Air-Purifier will turn OFF. In addition, Air-Purifier
should be cleaned. Case no 7, reset by [RESET] button on the indoor unit, and Air-Purifier will operate again after 1 hour. Case no 7, reset by [FILTER] button on the remote control, and Air-Purifier will operate again after 1 hour. Case no 7, can not reset by turning unit OFF and ON.
Case
1&2
3
4-1 4-2 4-3
5
6
7
8 9 !
* Short timer is the function of the remote control that activates the setting for the sudden operation. This
function can be set as shown below.
1. Press [
] button to turn the unit OFF.
2. Use the tip of the pencil to push the [CHECK] button and hold, 00 will show on display, then press [SET] button to make 00” disappear.
3. Press [
] button again to turn the unit ON.
4. When short timer is activated, all setting on the remote operates immediately, Besides, all LED turns ON continuously for 2 seconds.
PAP
START
OPERATION LED ON
PAP LED ON
Indoor fan ON
1 hour later
Less than 1 hour
Air-Purlfier ON
Air-Purlfier OFF
Operation confirm
Error within 1 minute
Error after 1 minute
10 minutes
No error
500 hours
PAP LED ON
Air-Purifier ON
PAP LED ON
Air-Purifier OFF
FILTER LED ON
Air-Purifier OFF
FILTER LED ON
Air-Purifier OFF
Checking
Air-Purifier insertion Inlet-Grlll assembly Micro switch Hi voltage unit
Reset by
1. [RESET] button
2. [FILTER] button
Reset by
1. [RESET] button
2. [FILTER] button
3. Turn unit OFF/ON
1
5
3
7
8 9
!
4-3
4-1 & 4-2
6
2
22
FILE NO. SVM-06010
(2) The indoor fan motor and Plasma Air-Purifier operation.
When Plasma Air-Purifier has been operated with other operation of air conditioner mode (Fan only, AUTO, Cooling, Dry or Heat). The speed revolution of indoor fan is based upon the operated mode of air conditioner. In fact, Plasma Air-Purifier works continuously.
When the Plasma Air-Purifier is activated individually and the fan speed is set to LOW, LOW+, MED, MED+, or HIGH, the speed revolution of the indoor fan will be constant. In fact, Plasma Air-Purifier works continuously.
Moreover, when the Plasma Air-Purifier is activated individually and the fan speed is set to AUTO, the speed revolution of the indoor fan and the operation of Plasma Air-Purifier is shown as the fig. 7-2-10
Fig. 7-2-10
ON
ON 5 min
OFF 10 min
15 min 30 min 45 min 60 min
Operation time
OFF 10 min
ON 5 min
Plasma Air-Purifier
Revolution
speed of the
indoor fan.
OFF
M
SL
L
23
FILE NO. SVM-06010
7-4.High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5.Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1.
Fig. 7-5-1
7-6.Defrost Operation *Heat pump model only
When the indoor unit is in heating operation, if the refrigerant evaporation temperature detected by the outdoor heat exchanger sensor is under the specified temperature, the outdoor unit starts the defrosting operation. At this time, the 4-way valve relay and the outdoor fan motor are turned off. The indoor fan motor is also turned off by the cold draft preventing control of the indoor microcomputer. Then, [PRE. DEF.] lamp on the indoor unit comes on. The defrosting operation stops and the 4-way valve relay, outdoor fan motor and the indoor fan motor are turned on automatically when the refrigerant evaporation increases to the specified temperature, or when the defrosting time is over 12 minutes.
62
55 54
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger temp. (°C)
6
(°C)
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Heat exchanger temperature
7-3.Hi PO
(2) Cooling operation
The setting temperature drops 3°C. (The value of the setting temperature on the remote control does not change.)
If the room temperature is higher than the setting temperature by 3.5°C or more, the horizontal louver moves to the Hi POWER position automatically. Then when the room temperature is 1°C less than the setting temperature the horizontal louver returns automatically.
FAN speed : [AUTO] If the room temperature is higher than the setting temperature by 3.5°C or more, the air conditioner operates at maximum airflow level. If the room temperature is higher than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
FAN speed : One of 5 levels If the room temperature is higher than the setting temperature by 3.5°C or more, the air conditioner operates at higher consecutive airflow level. If the room temperature is higher than the setting temperature by less than 3.5°C, the air conditioner operates at normal airflow level.
WER Mode
(3)
([Hi PO
Heating operation
WER] b
The preset temper
utton on the remote
ature increases 2
contr
°C,
ol is pressed.)
(The v
When [Hi PO
alue of the preset temper
WER] b
ature on the
utton is pressed while the indoor
remote control does not change
unit is in A.)uto
The indoor unit oper
, Cooling or Heating oper
ates in nor
ation, Hi
mal heating
PO
mode e
WER mar
xcept the preset temper
k is indicated on the displa
ature is higher
y of the remote
(+2
control and the unit oper
°C).
ates as f
(4)
ollo
The Hi POwsWER mode can not be set in Dr.y or F
(1)anA
only operation.
utomatic operation
·
The indoor unit oper·ates in according to the current operation.
·
7-6-1. Defrost starting condition
A-Zone : If -10°C > Teo ≥ − 18°C, defrost will
start when. Teo - Te 2.5°C at teat 20 sec or
~ 30 min after operation.
B-Zone : If Te ≤ −18°C, defrost start instantaneously
(Suddenly) 00 ~ 25 min ofter operation
C-Zone : If -2ºC Teo ≥ −10°C defrost will start when
7-6-2. Defrost finish condition.
1) If Te 3°C at least 60 sec -->4 way value on.
2) If Te 8°C --> 4 way value on.
Timing
Fig. 7-6-2
Operation time (4 Loops = Tt)
Td1
Td2
FILE NO. SVM-05016
24
-
-
Teo - Te ≤ −3°C at least 20 sec or ~ 60 min after operation.
Td3 Td4
Finish time recordStart time record
Defrost time rate : (Td/Tt) x 100 Heating time rate : (Tt - Td) x Tt
25
FILE NO. SVM-06010
7-7.Auto Restart Function
The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
When the unit is on standby (Not operating)
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The green lamp is on.
After approx. three seconds,
The unit beeps three times The lamp changes from and continues to operate. green to orange.
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
7-7-1. How to set auto restart function
To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.
While the filter check lamp is on, the [TEMPORARY] button has the function of filter reset button.
→ →
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds.
The unit stops operating. The green lamp is turned off.
After approx. three seconds,
The unit beeps three times. If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
→ →
While this function is being set, if the unit is in operation, the orange lamp is on.
This function can not be set if the timer operation has been selected.
When the unit is turned on by this function, the louver will not swing even though it was swinging automatically before shutting down.
0
3S
0
3S
TEMPORARY button
TEMPORARY button
26
FILE NO. SVM-06010
7-7-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
When the unit is on standby (Not operating)
When the unit is in operation
While this function is being set, if the unit is in operation, the orange lamp is on.
7-7-3. Power failure during timer operation
When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is cancelled. Therefore, set the timer operation again.
7-8. Filter Check Lamp
When the elapsed time reaches 1000 hours, the filter check lamp indicates. After cleaning the filters, turn off the filter check lamp.
7-8-1. How to turn off filter check lamp
Press [FILTER] button on the remote control. OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic Operation.
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The orange lamp is on.
After approx. three seconds,
The unit beeps three times The lamp changes from and continues to operate. orange to green.
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
→ →
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds.
The unit stops operating. The orange lamp is turned off.
After approx. three seconds,
The unit beeps three times. If the unit is required to operate at this time, push [TEMPORARY]
button once more or use the remote control to turn it on.
→ →
0
3S
0
3S
TEMPORARY button
TEMPORARY button
7-9. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient s
y
stem reduces moisture in the coil. When you turn off your air conditioner, the internal
fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
y
.
Operation time
The Self-Cleaning function is set as default at ex-factory.
Self-Cleaning operation can stop manually by press [ ] botton of the remote control two more time.
7-9-1. How to cancel Self-Cleanin
g
function
To cancel the Self-Cleanin
g
function, proceed as follows:
Press TEMPORARY button one time or use remote control to
turn on air conditioner. The OPERATION dis
play
will show in
oran
g
e color (When AUTO-RESTART is ON) or green color
(
When AUTO-RESTART is OFF).
Hold down the TEMPORARY button for more than 20 seconds.
(
The air conditioner will stop suddenly when the TEMPORARY is
p
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleanin
g
function
)
After holding about 20 seconds, the air conditioner will beep 5
times without an
y
blinking of display.
The Self-Cleanin
g Op
eration had been concelled.
Remarks
Per settin
g
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
g
ain,
p
lease follow item 7-7-1.
7-9-2. How to set Self-Cleanin
g
function.
To set the Self-Cleanin
g
function, proceed as follows.
Press TEMPORARY button one time or use remote control to
turn on air conditioner. The OPERATION displa
y
will show in
oran
g
e color (When AUTO-RESTART is ON) or green color
(
When AUTO-RESTART is OFF).
Hold down the TEMPORARY button for more than 20 seconds.
(
The air conditioner will stop suddenly when the TEMPORARY is
pressed but keep holdin
g
it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleanin
g
function
)
After holding about 20 seconds, the air conditioner will beep 5 times and OPERATION displa
y
blinks 5 times.
The Self-Cleanin
g
function had been set.
Remarks
Per settin
g
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
g
ain,
p
lease follow item 7-7-1.
Automatically turn-off.
Turn off by remote controller
or timer-off function.
Cool mode or dry mode Self-Cleaning mode
operation more than 10 mins. operate 20 mins.
CDU fan
ON or OFF
OFF OFF
depend on preseting per room temperature.
Compressor
ON or OFF
OFF OFF
depend on preseting per room temperature.
Timer display
ON or OFF
ON
ON or OFF
depend on preseting of timer function. depend on preseting of timer function.
FCU louver OPEN CLOSE CLOSE
ON OFF OFF
FCU fan
ON ON
OFF
rpm is depend on preseting. rpm is SUL speed.
Operation display
27
FILE NO. SVM-06010
TEMPORARY button
When the [QUIET] button is pressed, the fan of the indoor unit will be restricted the revolving speed at
-
until the [QUIET] button is pressed once
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less cooling load and less heating load condition.
7-11. COMFORT SLEEP mode
The principles of comfort sleep mode are:
Quietness for more comfortable.
Save energy by changing room temperature
The air condition can shut down by itself
Remarks:
1. Comfort sleep mode will not operate in dry mode
FILE NO. SVM-06010
- 28 -
7-10. QUIET Mode
Quiet mode is the system which, control the revolving speed of indoor fan to work constantly at lower than speed L. In addition, noise level of indoor unit is less than usual.
speed L
again (cancel Quiet mode).
Because of the fan speed L- may cause not
enough the cooling capacity or heating capacity.
automatically.
and fan only mode.
2. Comfort sleep mode is appropriate to work with less
cooling load and less heating load condition. Because of the fan speed L- may cause not enough the cooling capacity or heating capacity.
7-11-1. Cooling mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
-
OFF SL
The preset temperature will increase 1°C after the
Comfort sleep mode has operated for 1 hour and
automatically.
the temperature will increase another 1°C after the comfort sleep mode has operated for 2 hour. (The value of the preset temperature on the remote control does not change.)
Press the [COMFORT SLEEP] button to choose the
operating hours. Repeat pressing to select the hours. (1hr, 3hr, 5hr or 9hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
7-11-2. Heating mode
The fan speed of indoor unit operates automatically,
it relates with the compressor's operation.
Compressor’s Operation Fan Speed
ON L
-
OFF SL
The preset temperature will drop down 1°C after the
comfort sleep mode has operated for 1 hour and the temperature will decrease another 1°C after the comfort sleep mode has operated for 2 hour. (The value of the preset temperature on the remote control. dose not change.)
operating hours. Repeat pressing to select the hours.
Press the [COMFORT SLEEP] button to choose the
(1hr, 3hr, 5hr or 9 hr)
If the [COMFORT SLEEP] button is pressed again
means cancel comfort sleep mode.
FILE NO. SVM-06010
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord. Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
8. INSTALLATION PROCEDURE
8-1.Safety Cautions
For general public use
Power supply cord of Outdoor unit shall be more than 4 mm2 (H07RN-F or 245 IEC66 : polychloroprene sheathed flexible cord) or 3.5 mm2 (AWG-12).
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance completely from the mains.
To Disconnect the Appliance from the Main Power Supply.
29
FILE NO. SVM-06010
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC (For Europe model only)
To prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance. Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
30
FILE NO. SVM-06010
8-2. Installation Diagram of Indoor and Outdoor Units
(A
tta
c
h
to
th
e
fr
o
n
t p
a
n
e
l.) (A
tta
c
h
to
th
e
a
ir
filte
r
.)
Do not allow the drain hose to
The auxiliary piping can be connected to the left, rear left, rear, right or bottom.
Insulate the refrigerant pipes separately with insulation, not together.
6 mm thick heat resisting polyethylene foam
Rear left
Left
Bottom
Right
Rear
Wall
For the rear left and left piping
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
get slack.
Make sure to run the drain hose sloped downward.
Cut the piping hole sloped slightly .
100 mm or more
170 mm or mo
r
e
170 mm or more
1 Installation
plate
Hook
Hook
Before installing the wireless remote control
• With the remote control cover open, load the batteries supplied correctly, observing their polarity.
3 Batteries
2 Wireless remote control
Cover
2 Wireless remote control
1
0
0
m
m
o
r
m
o
r
e
6
0
0
m
m
o
r
m
o
r
e
60
0
m
m o
r m
ore
1
0
0
m
m
o
r
m
o
r
e
600 mm or more
Saddle
Vinyl tape Apply after carr ying out a draina ge test.
Extension drain hose (Not available, provided by installer)
6 Plasma air purifier
5 Sasa-Zeolite plus filter
Shield
pipe
31
FILE NO. SVM-06010
8-3.Installation
8-3-1. Optional installation parts
<Fixing bolt arrangement of outdoor unit>
Part
Code
Parts name
Refrigerant piping Liquid side : 6.35 mm Gas side : 15.88 mm
Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
Use 
8 mm or ∅ 10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple 9 to the bottom plate of the outdoor unit
before installing it.
Fig. 8-3-1.
Air inlet
Air outlet
Drain outlet
600 mm
90 mm
124 mm109 mm
28 mm
86 mm
116 mm
321 mm
25
Æ
B
C
1
One
each
Pipe insulating mater (polyethylene foam, 6 mm thick)
Putty, PVC tapes
One
A
each
Q'ty
32 −
33
FILE NO. SVM-06010
8-3-2. Accessory and installation parts
Part
No.
1
2
3
Part name (Q'ty)
Installation plate x 1
Wireless remote control x 1
Battery x 2
Part name (Q'ty)
Remote control holder x 1
Sasa-Zeolite plus filter x 2
Plasma air purifier x 1
Part
No.
4
5
6
Part
No.
7
8
9
Others
Name
Owner’s manual
Installation manual
Part name (Q'ty)
Mounting screw 4 x 25 x 8
l
Pan head wood screw
3.1 x 16 x 2
l
Drain nipple * x 1 (For Heat pump model only)
The part marked with asterisk (*) is packaged with the
outdoor unit.
FILE NO. SVM-06010
8-4.Indoor Unit
8-4-1. Installation place
A place which provides the spaces around the indoor unit (See Fig 8-2).
A place where there is no obstacle near the air inlet and outlet.
A place that allows easy installation of the piping to the outdoor unit.
A place which allows the front panel to be opened.
CAUTION
Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
The microprocessor in the indoor unit should not
be too close to RF noise sources. (For details, see the owner’s manual.)
<Remote control>
A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be determined as shown below.
Fig. 8-4-1
5 m
5
m
45
°
45
°
7
5
°
* 7 m
7 m
(Top view)
Indoor unit
* : Axial distance
Reception range
Reception range
Remote control
Indoor unit
Remote control
(Side view)
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Fig. 8-4-2
1. After determining the pipe hole position on the mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
Fig. 8-4-3
Pipe hole
100 mm
6
5
m
m
The center of the pipe hole is above the arrow.
170
120
55
65
7 Mounting screw
Pipe hole
Pipe hole
Indoor unit
Thread
Weight
Hook
Hook
1
Installation plate
Hook
34
FILE NO. SVM-06010
<When the installation plate is directly mounted on the wall>
1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw , do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Projection 15 mm or less
Clip anchor (local parts)
5 mm dia. hole
Anchor bolt
Fig. 8-4-4
7 Mounting
screw 4 x 25
ss
ss
s
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
Insert clip anchors for appropriate mounting screws 7 .
NOTE
Secure four corners and lower parts of the installation plate with 6 to 8 mounting screws to install it.
Installation plate <Keep horizontal direction>
8-4-3. Electrical work
1. The supply voltage must be the same as the rated voltage of the air conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
NOTE
Wire type : More than 1.5 mm
2
(H07RN-F or
245 IEC66) or 1.3 mm2 (AWG-16)
CAUTION
This appliance can be connected to the mains in the following way. Connection to fixed wiring: A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or switches must used.
NOTE
Perform wiring works so as to allow a generous wiring capacity.
35
FILE NO. SVM-06010
8-4-4. Wiring connection
Fig. 8-4-5
<How to connect the connecting cable> Wiring of the connecting cable can be carried out
without removing of the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to local cords) into pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m).
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
Earth line
Connecting cable
Cord clamp
Terminal block
Screw
Terminal cover
Screw
CAUTION
Be sure to refer to the wiring system diagram labeled inside the front panel.
Check local electrical cords and also any specific wiring instructions or limitations.
Fig. 8-4-6
<Stripping length of connecting cable>
Fig. 8-4-7
NOTE
Use stranded wire only.
Wire type : More than 1.5 mm2 (H07RN-F or 245 IEC66) or 1.3 mm2 (AWG-16)
Fig. 8-4-8
NOTE
Connect the earth line to the metallic part (i mark) located at the side of 3P terminal.
<How to install the air inlet grille on the indoor unit>
When attaching the air inlet grille, the contrary of
the removed operation is performed.
Fig. 8-4-9
a
b
o
u
t 1
5
c
m
Connecting cable
Earth line
50
40
10
10
Air Inlet grille
Front panel
2
1
36
FILE NO. SVM-06010
8-4-5. Piping and Drain Hose Installation <In case of rightward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
Fig. 8-4-10
<In case of downward piping>
After scribing slits of the body-right by a knife or a making-off pin, cut them by a pair of nippers or the like.
Fig. 8-4-11
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
Slit (Body-right)
Slit (Body-right)
To connect the pipe after installation of the unit (figure)
Fig. 8-4-12
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine trouble , make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it not to crush it.
(To the forefront of flare)
Liquid side
Outward form of indoor unit
R 30 mm (Use polisin (polyethylene) core or the like for bending pipe.)
Use the handle of screwdriver, etc.
400 mm
300 mm
43 mm
80
Gas side
Installation plate
Auxiliary pipes
Indoor unit
Connecting cable
Drain hose
37
FILE NO. SVM-06010
8-4-7. Drainage
1. Run the drain hose sloped downwards.
NOTE
Hole should be made at a slight downward slant on the outdoor side.
Fig. 8-4-15
2. Put water in the drain pan and make sure that the water is drained out of doors.
3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
Fig. 8-4-16
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
Fig. 8-4-17
Inside the room
Drain hose
Shield pipe
Extension drain hose
Wall
Drain guide
Space for pipes
Do not put the drain hose end in the drainage ditch.
Do not form the drain hose into a wavy shape.
Do not put the drain hose end into water.
Do not rise the drain hose.
50 mm or more
8-4-6. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
Fig. 8-4-13
For detaching the indoor unit from the installation plate, pull the indoor unit toward you while
pressing
its bottom up at the specified parts.
1
2
PressPress
Press
(unhook)
Fig. 8-4-14
Hook
Hook here
1 Installation
plate
38
FILE NO. SVM-06010
A place where the operation noise and discharged air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up 15 m. (Refer to the table of TO CHARGE REFRIGERANT for detail.)
An allowable height level is up to 8 m. (18 Class) or 10 m. (24 Class)
A place where the drain water does not raise any problem.
CAUTION
1. Install the outdoor unit without anything blocking the air discharging.
2. When the outdoor unit is installed in a place exposed always to a strong wind like a coast or on a high story of a building, secure the normal fan operation using a duct or a wind shield.
3. Specially in windy area, install the unit to prevent the admission of wind.
4. Installation in the following places may result in trouble. Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from audio equipment, welders, and medical equipment.
Fig. 8-5-1
Strong
wind
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
Fig. 8-5-3
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
Do not apply excess torque.
Otherwise, the nut may crack depending on the
conditions.
90°
Roughness
Warp
Obliquity
A
Die
Pipe
Outer dia.
A
of copper pipe
Rigid Imperial
6.35 1.0 to 1.5 1.5 to 2.0
15.88 1.0 to 1.5 2.0 to 2.5
A place which provides the spaces around the outdoor unit as shown in the installation diagram
A place which can bear the w
eight of the outdoor unit and does not allow an increase in noise level and vibration.
of indoor and outdoor unit.
8-5. Outdoor Unit
8-5-1. Installation place
39
FILE NO. SVM-06010
8-5-3. Evacuating
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops.
1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2. Connect the charge hose to the port of vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start for evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is –101 kPa (–76 cmHg).
5. Close the low pressure side valve handle of gauge manifold.
6. Open fully the valve stem of the packed valves (both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Fig. 8-5-6
Use a wrench to secure.
(Unit : N·m)
Use a torque wrench to tighten.
Flare nutHalf union
Externally threaded side
Internally threaded side
Flare at indoor unit side
Flare at outdoor unit side
Outer dia.
Tightening torque
of copper pipe
6.35 mm 16 to 18 (1.6 to 1.8 kgf·m)
15.88 mm 65 to 80 (6.5 to 8.0 kgf·m)
Tightening torque of flare pipe connections
Fig. 8-5-4
Fig. 8-5-5
CAUTION
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
Pressure gauge
Manifold valve
Handle Lo
Connecting pipe
Compound pressure gauge
Vacuum
pump
Handle Hi (Keep full closed)
Charge hose
Charge hose
Vacuum pump adapter for counter-flow prevention
Service port (Valve core (Setting pin))
Packed valve at liquid side
Packed valve at gas side
-101kPa (-76cmHg)
40
FILE NO. SVM-06010
<Packed valve handling precautions>
Open the valve stem all the way out; but do not try to open it beyond the stopper.
Securely tighten the valve stem cap with torque in the following table:
Hexagonel wrench : A (Unit : mm)
Fig. 8-5-7
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as identified with their respective matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.
Gas side Tightening torque A
Gas side 65 to 80 N·m 4 mm (15.88 mm) (6.5 to 8.0 kgf·m)
Liquid side 16 to 18 N·m Same as (6.35 mm) (1.6 to 1.8 kgf·m) Gas side
Service port
9 to 10 N·m (0.9 to 1.0 kgf·m)
A
Hexagonal wrench is required.
<Stripping length of connecting cable>
Fig. 8-5-8
CAUTION
Wrong wiring connection may cause some electrical parts burn out.
Be sure to comply with local codes on running the wire from indoor unit to outdoor unit (size of wire and wiring method etc).
Every wire must be connected firmly.
NOTE: Connecting cable
Wire type: More than 1.5 mm2 (H07RN-F or 245 IEC66) or 1.3 mm2 (AWG-16)
Power supply cord
Terminal block
Connecting cable
Screw
Cord clamp
Cord clamp
Earth line
Connecting cable
Power supply cord
Earth line
Terminal screw
LN 1 32
70
60
L
N
10
70
10
10
80
10
123
TO CHARGE REFRIGERANT
Refrigerant
No need to charge
15 m or less 15 m or less
extra refrigerant
Need to charge Over 15 m up to Over 15 m up to extra refrigerant 25 m (30 g/m) 20 m (20 g/m)
24 class 18 class
Model
50 Hz, 220 - 240 V Single phase
Power source
50 Hz, 220 V Single phase
(For RAS-24NKDX5-T / RAS-24N2AX-T and
RAS-18NKDX5-T / RAS-18N2AX-T model)
Maximum
18A 16A
running current Plug socket &
20A 20A
fuse rating Power cord 4 mm2 (H07RN-F or 245 IEC66) or 3.5 mm2 (AWG-12)
24 class 18 class
41
42
FILE NO. SVM-06010
8-6.How to Set Remote Control Selector
Switch
When two indoor units as installed in seperated rooms, there is no need to change the selector switch.
<Remote control selector switch>
When two indoor units are installed in the same room or the adjacent two rooms, they may be controlled simultaneously with a single remote control. To prevent this, set either unit and its remote control to B setting. (Both units are set to A setting before shipment.)
The remote control signal is not recived when the indoor unit setting is different from the remote control one.
1. Set the remote control selector switch with the indoor unit.
1) Turn the circuit breaker of the main power switch off before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
2. Set the remote control selector switch with the remote control
[B] is indicated on the liquid crystal display when setting remote control from A to B. [A] is not indicated on the display even if the selector is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with sharp point. (The preset temperature on the remote control changes to [00].)
3) Press the [MODE] button while pressing the [CHECK] button, [B] is indicted at the right of the present temperature display.
To reset the switch to the [A] setting, press the [MODE] button again while pressing the [CHECK] button.
Fig. 8-6-2
3. Confirm that the indoor unit can operate with the new setting.
[MODE] button
[CHECK] button
PAP
AUTO
PRESET
MODE
CLOCK
CHECK
FILTER
RESET
HiPOWER
ECO
MEMO
CLR
SET
SWING
FIX
FAN
SLEEP
ON
OFF
TEMP
1.3.5.9H
A B
CAUTION
Do not use any other sharp tools (such as cutters, pliers, or the like), Such tools may cause breakage or damage.
with only the nippers.
3) Open the Electrical part cover (Refer to chapter 10-1, procedure 2 ), then cut the jumper (J01)
Chapter 10-1, procedure 1 )
See Fig. 8-6-1
Fig. 8-6-1
FILE NO. SVM-06010
8-7.Others
8-7-1. Gas leak test
Fig. 8-7-1
Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press TEMPORARY b utton for 10 sec. (The beeper will make a short beep.)
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>
Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
Service port cap connection
Valve stem cap connection
Flare nut connections (Outdoor unit)
Flare nut connections (Indoor unit)
Valve stem cap connection
A
B
43
TEMPORARY button
44
FILE NO. SVM-06010
9-2-2. Incorrect cable connection between Indoor
and outdoor units
The indoor unit is connected to the outdoor unit with 4 cables. Check that the indoor and outdoor units have been properly connected with terminals assigned the same numbers. If the connectors are not properly connected, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5 Hz).
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1 to control the air conditioner. If there are any opera­tional problems, check whether or not the problems correspond to Table 9-2-1. If they correspond to the Table, they are not problems with the air conditioner, but they are indispensable operations to control and maintain the air conditioner properly.
9. TROUBLESHOOTING CHART
9-1. Troub leshooting Pr ocedure :
Follow the details of 9-2. Basic Check Items. If there is no trouble corresponding to 9-2, check whether or not there are faulty parts following
9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 – 240 V. If it is not within this range, the air conditioner may not operate normally.
Table 9-2-1
1 When the main power supply is turned
on, the OPERATION lamp on the indoor unit blinks.
2 The indoor fan motor speed does not
change in the Dry operation.
3 The compressor is not turned off even
though the room temperature is in the range that the compressor is turned off.
4 The compressor is not turned on and
off even though the thermo control is operated in the Dry operation.
5 The compressor is not turned on even
though the room temperature is in the range that the compressor is turned on.
6 The operation mode changes in the
Automatic operation.
7 The Fan only operation continues in the
Automatic operation.
8 The ECO operation or Hi-POWER
operation does not work.
9 When [Hi POWER] button is pressed,
the display on the remote control does not change at all.
No. Operation of air conditioner Descriptions
The OPERATION lamp blinks to indicate that power is turned on. If the [ ] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry operation.
The compressor has a function that it is not turned off for 3 minutes after it is turned on even though the room temperature is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically at the regular intervals, independent of the thermo control.
The compressor is not turned on in the restart delay timer (3-minutes timer) operation. It is also not turned on after the power supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time for control fan speed and the operation mode is changed every 15 minutes according to difference between the room temperature and the preset temperature.
When the room temperature is in the range (Preset temperature ± 1°C), the Fan only operation is selected.
These operations do not work when the unit is in the Dry operation or Fan only operation.
The display on the remote control does not change when [Hi POWER] button is pressed. However the microcontroller gives commands to change the preset temperature and air flow level.
45
FILE NO. SVM-06010
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air outlet of the indoor heat exchanger by the indoor temperature sensor
Temperature setting of the indoor heat exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the outdoor
unit
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and indicates the information of the self-diagnosis with the lamps on the display panel of the indoor unit.
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1 Hz) B OPERATION lamp is blinking. (5 Hz) C OPERATION lamp is blinking. (5 Hz) D OPERATION lamp is blinking. (5 Hz) E OPERATION lamp is blinking. (5 Hz)
F OPERATION and TIMER lamps are blinking.
(5 Hz)
G OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
The remote control does not work.
The outdoor fan does not rotate.
Turn off the power supply once, then turn it on. Try to operate the remote control.
The compressor operates.
The compressor does not operate.
The remote control still does not work.
The remote control works.
The indoor unit (and/or remote control) is/are defective .
OK.
The outdoor unit (Outdoor fan motor) is defective .
An internal part of the compressor or P.C. board is defective.
Symptom Check Primary judgement
Power failure (when the power supply is turning on) Thermo sensor (TA) short or break Heat exchanger sensor (TC) short or break Indoor fan motor lock or failure Indoor P.C. board failure Wrong wiring of connecting cable
Cycle failure
Gas shortage or other refrigerant cycle trouble
Heat exchanger sensor open, break or short
Overload relay or thermostat trouble of compressor
FILE NO. SVM-06010
46
9-4.Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
(1) Press [CHECK] button with a tip of pencil to set the
remote control to the service mode.
“00” is indicated on the display of the remote control.
The timer lamp on the indoor unit blinks continuously. (5 times per 1 sec.)
(2) Press [ON 8] or [OFF 9] button.
If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows:
Check the unit with all 52 check codes (00 to 33). as shown in Table 9-4-1.
Press [ON 8] or [OFF 9] button to change the check code backwards.
If there is a fault, the indoor unit will beep f or 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control.
2-digits alphanumeric will be indicated on the display.
All lamps on the indoor unit will blink. (5 times per 1 sec.)
(4) Press [
] button to release the service mode.
The display of the remote control returns to as it was before service mode was engaged.
(3) Press [CLR] button. After service finish for clear
service code in memory.
“7F” is indicated on the display of the remote control.
Alphanumeric characters are used for the check code. is 5. is 6.
is A. is B. is C. is D.
00 01 1d 1E02 33
(5) Time shotening method.
1. Press [SET] button while pressing [CHECK] button.
2. Press [
] button.
PAP
AUTO
PRESET
MODE
CLOCK
CHECK
FILTER
RESET
HiPOWER
ECO
MEMO
CLR
SET
SWING
FIX
FAN
SLEEP
ON
OFF
TEMP
1.3.5.9H
CLOCK
CHECK
RESET
CLR
ON
O
F
47
FILE NO. SVM-06010
The indoor thermo sensor (TA) is defective. Disconnection or short-circuit
The indoor heat exchanger sensor (TC) is defective. Disconnection or short-circuit
The indoor fan motor or its circuit is defective.
The part other than the above parts on the indoor P.C. board is defective. EEPROM access error
IOL operation
The serial signals can not be transmitted and received between indoor and outdoor units.
The crossover wire is connected wrongly. The serial signal transmitting circuit on the outdoor P.C. board is defective. The serial signal receiving circuit on the indoor P.C. board is defective.
The operation command signals are not transmitted from the indoor unit to the outdoor unit.
The outdoor thermo sensor (TE) is defective. Disconnection or short-circuit
The outdoor heat exchanger (TD) sensor is defective. Disconnection or short-circuit
The reply serial signal has been transmitted when starting the unit, but stops being transmitted shortly after.
1. Compressor thermo operation Gas shortage
Gas leak
2. Instantaneous power failure
The discharge temperature is over 120°C.
The IOL operation is defective.
Table 9-4-1
Block level Diagnosis function
Judgement and action
Check
Block
Check
Symptom
Unit
Condition
code code status
Operation continues.
Operation continues.
All off
Operation continues.
All off
Operation continues.
Operation continues.
All off
All off
Operation continues.
All off
All off
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is defected. And it returns to the normal condition when recovering from errors.
The lamp on the indoor unit blinks when error is defected.
The lamp on the indoor unit blinks when error is detected.
1. Check the indoor thermo sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor heat exchanger sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit of the indoor fan motor (CN10).
2. Check the indoor fan motor.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board. (EEPROM and peripheral circuits)
Overload operation of refrigerating cycle
1. In the case of the outdoor unit not operating at all;
Check the crossover cable and connect it properly. Check the outdoor P.C. board.
2. In the case of the outdoor unit operating normally;
Check whether or not both of serial LED (Green) and serial LED (Orange) is blinking. If the serial LED (Green) is not blinking, check the outdoor P.C. board. If the serial LED (Orange) is not blinking, check the indoor P.C. board.
If the operation command signals continue to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board.
1. Check the outdoor thermo sensor (TE).
2. Check the outdoor P.C. board.
1. Check the outdoor heat exchanger sensor (TD).
2. Check the outdoor P.C. board.
1. Repeatedly turn the indoor unit on and off with the interval of approx. 10 to 40 minutes. (The check code is not indicated during operation.) And supply gas. (Check gas leak.)
2. The indoor unit operates normally during the check. If the reply serial signal continues to be transmitted between 2 and 3 of the indoor terminal block, replace the outdoor P.C. board. If the signal stops between them, replace the indoor P.C. board.
1. Check the heat exchanger sensor (TD).
2. Gas purging
When turning on the unit, the normal phase (RST) is detected but T-R waveform has not been detected for 120 seconds or more.
Indoor P.C. board
Cable connection
Outdoor P.C. board
Other parts (including compressor)
48
FILE NO. SVM-06010
9-5. How To Diagnose Faulty Parts
[08 Four-way valve error] (Heat pump model)
[04 Serial signal error] (Heat pump model)
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
Does outdoor
unit operate?
Are 1, 2 and 3 crossover
wires connected properly?
Is connector
connected properly?
Does LED (Orange) on
outdoor P.C. board blink?
Does LED (Green) on
outdoor P.C. board blink?
Outdoor P.C. board
is defective.
Replace
P.C. board.
Connect crossover
wires properly.
Connect connector
properly.
Indoor P.C. board
is defective.
Replace
P.C. board.
Operation
Check item
Conceivable principle cause
Measure
Item by symptoms
Does four-way valve
operate properly?
Does coil terminal have 220 240 V
in heating operation?
Are circuit
wires normal?
Is outdoor P.C. board
normal?
Four-way valve
is defective.
Outdoor P.C. board
is defective.
(CN11 220 240 V)
Indoor P.C. board
is defective.
Replace
Four-way valve
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
Is TC sensor
resistance value
(10 k at 25°C) normal?
49
FILE NO. SVM-06010
NO
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
Does compressor operate?
Is compressor
turned off shortly?
Does inner
overload relay
(in compressor)
operate?
Check charged amount of refrigerant.
Check defective overload.
Check compressor.
Replace
compressor.
Replace TC
sensor.
Connect TC
sensor properly.
Is TC sensor
disconnected from
the sensing element?
Is circuit wiring
normal?
Is outdoor P.C.
board normal?
Wiring check/modification
Replace
P.C. board.
Replace
P.C. board.
Outdoor P.C. board
is defective.
Indoor P.C. board
is defective.
Is TC sensor
resistance value
(10 k at 25°C) normal?
Failure
[09 Other cycle error] (1) (Heat pump model)
[09 Other cycle error] (2)
Clean filters.
Replace
TC sensor.
Charge
refrigerant.
Replacd
P.C. board.
Anti-freezing operation
Anti-freezing operation
Does indoor fan operate?
Are filters clogged?
Is charged amount
of refrigerant normal?
Is outside air
low load?
Indoor P.C. board
is defective.
Is connector
connected properly?
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
Is condenser normal?
Is indoor fan
motor normal?
Connect
connector
properly.
Replace
condenser.
Replace
fan motor.
Is TC sensor
resistance value
(10 k at 25°C) normal?
50
FILE NO. SVM-06010
[0C Indoor TA sensor error]
[0d Indoor TC sensor error]
[18 outdoor TE sensor error] (Heat pump model)
NO
NO
YES
YES
Is CN03 (TA sensor connector)
connected properly?
Is TA sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Connect CN03 properly.
Replace T A sensor.
Replace P.C. board.
NO
NO
YES
YES
Is CN01 (TC sensor connector)
connected properly?
Is TC sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Connect CN01 properly.
Replace TC sensor.
Replace P.C. board.
NO
NO
YES
YES
Is TE sensor connector
connected properly?
Is TE sensor resistance value
(10 k at 25°C) normal?
Indoor P.C. board is defective.
Connect connector
properly.
Replace TE sensor.
Replace P.C. board.
51
FILE NO. SVM-06010
[19 outdoor TD sensor error] (Heat pump model)
[1E Discharge temp. error] (Heat pump model)
NO NO
NO
YES
NO
YES
YES
NO
YES
Is protective
controller such as discharge
thermostat normal?
Is charged amount
of refrigerant normal?
Is overload relay normal?
Is TD sensor resistance value
(50 k at 25°C) normal?
Are wires connected
to connector properly?
Outdoor P.C. board is defective.
Connect wires to
connector properly.
Check and modify charged
amount of refrigerant.
Unit operates normally.
Replace TD sensor.
Replace P.C. board.
NO
NO
YES
YES
Is TD sensor
connected properly?
Is TD sensor resistance value
(50 k at 25°C) normal?
Outdoor P.C. board is defective.
Connect connector
properly.
Replace TD sensor.
Replace P.C. board.
52
FILE NO. SVM-06010
9-6. Troubleshooting for Indoor unit
9-6-1. Power can not be turned on. (The unit does not operate at all.)
<Primar check>
(1) Is the supply voltage normal? (2)Is the connection to the AC output OK? (3) Is the fuse (F01) blown?
Turn off power supply once, and 5 second later, turn it
on again.
Is OPERATION
lamp blinking?
NO
YES
NO
NO
YES
YES
Is it possible to
turn on power
supply by
pressing
[ ]
button on remote
control?
Does
transmission
mark on
remote
control flash
normally, and
is its signal
transmitted
properly?
Remote control is
defective.
Refer to 9-9
Remote Control."
Parts (R10,
C01, DB01,
or C02, C03
IC01)
are defective.
Is fuse (F01)
of indoor
control board
blown?
Is voltage (DC
12V or 5V)
indicated on rear of indoor control board
normal?
Microconlroler
defective.
Replace main P.C.
board.
Is DC 310 -
340V across
C03?
Are DC 12V,
across C27?
Turn off breaker
once and turn it
on again after
removing motor.
Are DC 12V,
across C27?
T01 or IC01 is
def
ec
tive.
Replace motor.
YES
YES
NO
NO
NO
NO
YES
YES
YES
NO
NO
YES
Does the fan
motor
connector
between 1
and
3
short-
circuit?
Unit operates
normally.
Operation
Measure
Item by symptoms
Check item
Conceivable principle
cause
"Troubleshooting for
53
FILE NO. SVM-06010
9-6-2. Only indoor fan motor does not operate.
<Primary check>
(1) Is it possible to detect the power supply voltage (200 – 240 V) between 1 and 2 on the terminal block? (2) Does the indoor fan motor operate in cooling operation?
(In heating operation, the indoor fan motor does not operate for approximately 5 minutes after it is turned on, to prevent a cold air from blowing in.)
[ ]
54
FILE NO. SVM-06010
9-6-3. Compressor does not operate. <Primary check>
(1) Is the preset temperature higher than the room temperature in cooling operation? (2) Is the crossover cable connected properly?
<Inspection procedure>
Turn on power supply.
Does OPERATION
lamp blink?
Does miniature relay RY04
switch on and off due to
temperature changes?
Is resistance value of thermo
sensor (TA) and heat ex-
changer sensor (TC) normal?
Thermo sensor or
heat exchanger
sensor is defective.
Replace thermo sensor
or heat exchanger
sensor.
Refer to 9-6-1 “Power
can not be turned on”.
Is it possible to detect AC
220 – 240V between 2
and 3 on terminal block?
Are all of compressor cords normal?
Is compressor motor winding
normal?
(Check winding resistor.)
Is capacitor for compressor normal?
Is overload relay normal?
Does compressor start?
Does compressor stop after a while?
Is gas quantity normal?
(Check gas pressure.)
Compressor is defective.
NO
YES
YES
YES
Replace P.C. board.
Gas shortage (Gas leak)
Compressor is defective.
Microcomputer is defective.
Miniature relay RY04 is
defective.
Overload relay is
defective.
Capacitor is defective.
Compressor is defective.
Replace P.C. board.
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
YES
YES
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
NO
NO
NO
YES
NO
55
<Inspection procedure>
Is it possible to start
unit by remote control?
YES
Turn on power supply.
Does OPERATION
lamp blink?
YES
NO
Refer to item Power
can not be turned on .
NO
Refer to 9-9 Troubleshooting
for Remote Control .
YES
YES
YES
NO
Connect crossover
cable properly.
NO
Are all of compressor cords normal?
Rewire or replace
defective cords.
NO
Replace compressor.
Replace P.C. Board
Is resistance of compressor motor
windining normal?
NO
Compressor is defective.
YES
Replace compressor.
Is capacitor for compressor normal?
NO
Capacitor is defective.
Is it possible to detect AC 200V
between 2 and 3 on terminal block?
Is crossover cable normal?
YES
Is overload relay normal?
Does compressor start?
Does compressor stop after a while?
Is gas quantity normal?
(Check gas pressure.)
Compressor is defective.
Replace Compressor
YES
YES
YES
YES
YES
NO
NO
NO
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leak)
Replace overload relay.
Replace compressor.
Supply gas.
FILE NO. SVM-06010
- Cooling model -
56
<Inspection procedure)
- Heating model -
Replace transformer
FILE NO. SVM-06010
AC 70-100V
outdoor
P.C. board.
(CN06) of transformer?
57
YES
YES
YES
YES
YES
Rewire or replace
defective cords.
Replace compressor.
Replace capacitor.
Replace overload relay.
Replace compressor.
Supply gas.
NO
NO
YES
YES
YES
YES
Are all of compressor cords normal?
Is compressor motor winding normal?
(Check winding resistor.)
Is gas quantity normal?
(Check gas pressure.)
Is capacitor for compressor normal?
Is overload relay normal?
Does compressor start?
Does compressor stop after a while?
Replace compressor.
Compressor is defective.
Compressor is defective.
NO
Capacitor is defective.
NO
Overload relay is defective.
NO
Compressor is defective.
NO
Gas shortage (Gas leak)
FILE NO. SVM-06010
58
FILE NO. SVM-06010
9-7. Troubleshooting for Wiring (Interconnect cable and Serial Signal Wire)
9-7-1. Outdoor unit does not operate. <Inspection procedure>
(1) Is the voltage between and of the indoor terminal block varied? (2) Are signals from the indoor unit to the outdoor unit transmitted correctly based upon the following diagram?
NOTE:
 Measure the voltage for 2 minutes and 30 seconds after starting the unit. 
Normal condition : Voltage varied between AC70 ~ 100V Abnormal condition : Voltage does not vary.
9-7-2. Outdoor unit stops a while after starting the unit.
<Confirmation procedure> Select one of 3 cases below and follow the procedure.
(1) The outdoor unit stops between 10 and 20 minutes passed after starting and it takes 10 minutes or more to
restart the unit.
2
1
3
Terminal block on indoor side
Terminal block
Tester
Red
White
(2) The outdoor unit stops once, it would not operate until the power is turned on again.
(3) The outdoor unit stops between 10 minutes to 1 hour after starting and a check code is indicated on the
remote control. (Check code 03-1E : Refer to Table 9-4-1.)
Measure gas pressure.
Gas shortage
Pipe clogging
Compressor is turned off and on automatically by thermo sensor
(Heat pump Model) or thermostat (Cooling only Model).
Gas has a low circulation.
Gas leak
Refer to 9-6-4 "Compressor does not operate"
1
2
Fig. 9-7-1
Normal condition : After start operated about 2 minutes and 30 seconds. Voltage between 2 and 3 of the
Abnormal condition : Don't found voltage AC 220 ~ 240V from terminal block (0V)
2
1
3
Terminal block on indoor side
Terminal block
Tester
Red
White
Heatpump model
Cooling model
of the indoor's Terminal block should be equal AC 220 ~ 240V
FILE NO. SVM-06010
59
9-8. Troubleshooting for Air Purifier and Minus Ion
9-8-1. How to Check Whether the Air Purifier is Good or Not
Push the switch
ON
Releaes the switch
OFF
ON
Tester
Ionizer
Output
High-voltage tester
Collector output
Micro-switch malfunction
Micro-switch is stuck
Is DC12V applied
between
1
(+) and 2 (−)
of CN33 of the main
P.C. board (WP-008)?
Are the dust
collector/ionizer/ionized
wire units dirty?
Is an abnormal sound
(cracking noise) heard
from the electrode?
Is output of the ionizer approx. 3.9kV to 4.7kV? Is output of the collector approx. 2.9kV to 3.7kV?
Refer to items, cleaning and check for the dust collector/ionizer/ionized wire units.
When the ionized wire is disconnected or when dirt is not cleaned even cleaned, replace each unit.
Referring to the right figure, check the high-output voltage of the air filter unit.
(NOTE)
Use an exclusive high voltage tester; otherwise the tester may be broken.
Dry the dust collector and ionizer.
Is DC-5V to DC-10V
applied between
4 (Brown/Negative voltage)
and 2 (Brown/GND)
of CN33 of the main
P.C. board?
Are the dust collector
and ionizer dried?
(Electrode check)
Does the plasma lamp
go off within 2 seconds after
it was ON, and does the
filter lamp (Orange) go on?
Does the plasma lamp (Blue) or
the filter lamp (Orange) go on?
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote control.
In this time, check that the remote control is in status which is shortened by time on the reactivation preventive timer and all display lamps go on for approx. 3 seconds when a signal is received.
If time on the reactivation preventive timer is not shortened, the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
While the air purifier operates, check that the fan speed [AUTO] is not displayed. (Because the power ON/OFF is controlled on the program)
3) Be sure not to touch the dust collector, ionizer, or ionized wire unit with the human body.
Does the OPERATION lamp blink?
Replace the high-voltage unit.
Replace the main P.C. board (WP-008).
Replace micro-switch.
Turn off the power breaker and remove CN34 (Micro switch connector). Short-circuit between 1 and 2 pin of CN34 at PC side, and turn on the power breaker after 10 seconds.
[ ]
GND
No trouble
• Conduction check of micro-switch
YES
YES
NO
YES
NO
NO
YES
NO
Turn off the power breaker once, and turn on again after 10 seconds.
Operation check Primary check
Is there conduction of
micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
Is there conduction of micro-switch connector under ON status of the micro-switch
(Front panel closed)?
Does the indoor fan rotate?
Is DC12V applied
between
1
(Red/DC12V) and
(Brown/GND) of CN1 of the
high-voltage unit?
Replace the main P.C. board (WP-008)
YES
YES
YES
YES
YES
NO
NO
NO
YES
YES
YES
NO
NO
NO
YES
NO
• How to check output of the air purifier <Caution on High Voltage!!>
Be sure not to come to contact to the silver part or not to touch the ionized cables.
( )
( )
To item Power supply is not turned on
To item Only indoor fan does not operate
FILE NO. SVM-06010
60
9-8-2. How to Check Whether the Minus Ion Generator is Good or Not
How to check output of minusion
<Caution on High Voltage!!>
No trouble
Does the plasma lamp (Blue) or
the filter lamp (Orange) go on?
Replace the main P.C. board (WP-008).
1) Check operation while short-circuiting CN34 of the main P.C. board.
2) Perform air purifying operation by the remote control.
In this time, check that the remote control is in status which is shortened by time on the reactivation preventive timer and all display lamps go on for approx. 3 seconds when a signal is received.
If time on the reactivation preventive timer is not shortened, the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.
While the air purifier operates, check that the fan speed [AUTO] is not displayed. (Because the power ON/OFF is controlled on the program)
3) Be sure not to touch the electrode with the human body.
( )
Turn off the power breaker and remove CN34 (Micro switch connector). Short-circuit between 1 and 2 pin of CN34 at PC side, and turn on the power breaker after 10 seconds.
Does the electrode
output approx. 6kV?
Referring to the right figure, check the high-voltage output of the air ionizer. In this time, peel the thermal insulator, and attach it to the original position after check operation. NOTE : Use an exclusive high voltage tester; otherwise the tester may be broken.
Does the plasma lamp
go off within 2 seconds after
it was ON, and does the
filter lamp (Orange) go on?
Does the indoor fan rotate?
Micro-switch is stuck
Micro-switch malfunction
Is there conduction of micro-switch connector under ON status of the micro-switch
(Front panel closed)?
Is there conduction of micro-switch connector under
OFF status of the micro-switch
(Front panel opened)?
Is DC12V applied between 1 (Red/DC12V) and 2 (Brown/GND) of CN1 of the
high-voltage unit in the air purifier?
Does the OPERATION lamp blink?
Turn off the power breaker once, and turn on again after 10 seconds.
Conduction check of micro-switch
Replace micro-switch.
Operation check Primary check
YES
YES
NO
YES
NO
NO
YES
NO
YES
YES
YES
NO
NO
NO
NO
NO
YES
Replace the power P.C. board
(WP-008) or the housing assembly.
Integrated
power supply assembly
Push the switch
ON
Releaes the switch
OFF
ON
Tester
GND
Electrode
High-voltage unit
High-voltage tester
To item Power supply is not turned on
To item Only indoor fan does not operate
To item How to check whether
the air purifier is good or not
9-9. Troubleshooting for P.C. board
9-9-1. How to check indoor P.C. board
<Cautions for handling P.C. board>
(1) When removing the front panel and the P.C. board,
be sure to turn off the power supply.
(2) When removing the P.C. board, hold the edge of
the P.C. board and do not apply force to the parts.
(3) When connecting or disconnecting the connectors
on the P.C. board, hold the housing. Do not pull at lead wires.
61
FILE NO. SVM-06010
1 Turn off the power supply and
remove the P.C. board assembly from electric parts base. Remove the connecting cables from the terminal block.
2 Remove the connector of the motor
and turn on the power supply. If OPERATION lamp blinks (once per second), it is not neccessary to check steps (1 to 3) in the right next column.
3 Press [ ] button once
to start the unit. (Do not set the mode to Fan Only or On-Timer operation).
4 Shorten the line of the restart delay
timer and start unit.
<Inspection procedure>
(1) If the P.C. board is defective , check for disconnec-
tion, burn or discoloration of the copper foil pattern of the P.C. board.
(2) The P.C. board consists of the following 2 parts:
a. Main P.C. board parts.
Power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, buzzer drive circuit and buzzer.
b. Infrared rays parts:
Infrared rays receiving circuit
Check the defects of the P.C. board with Table 9-8-1.
Table 9-9-1 Inspection procedure
No. Procedure Check points Causes
Impluse voltage was applied or the indoor fan motor short-circuited.
1. The terminal block or the crossover cable is connected wrongly.
2. The capacitor (C01 and C02 ) line filter (L01), resistor (R09), or the diode (DB01) is defective.
3. C27, T01 and IC01 are defective.
4. IC10, C30, C11 or T01 are
defective.
<Heat pump model> IC03 or IC04 are defectice.
<Cooling only model>
1. The wire of the relay coil (RY03) comes down or the relay drive (Q08) is defective.
2. CN27 or RY03 is connected wrongly.
The lamps are defective or the housing assembly (CN13) is defective.
Check whether or not the fuse (F01) is blown.
Check power supply voltage;
1. Between CN30 and CN31 (220 240 V AC) : Except
2. Between + and
of C03
(DC310 340 V)
3. Between 12 V and GND
4. Between 5 V and GND
Check power supply voltage; <Heat pump model>
1. Between CN31 and CN23
<Cooling only model>
1. Between collector of Q08 and GND (for relay coil (DC12 V))
2. Between 2 and 3 of terminal block for connecting cable
Check whether or not all lamps (OPERATION, Auto restart, TIMER PAP, FILTER and Hi-power) are indicated for 3 seconds and they return to normal 3 seconds later.
(AC70 ~ 100V)
62
FILE NO. SVM-06010
Table 9-9-2 Approximate resistance value of thermo sensor
9-9-2. How to Shorten Time of Restart Delay Timer
5 Press [ ] button once
to start the unit.
Shorten the time of the restart delay timer.
Set the operation mode to COOL.
Set the fan speed level to AUTO.
Set the preset temperature must
lower than the room temperature. (The unit (compressor) operates continuously in the above condition.)
6 If the above condition (No. 5) still
continues, start the unit in the following condition.
Set the operation mode to HEAT.
Set the preset temperature must
higher than room temperature.
7 Connect the motor connector to the
main P.C. borad and turn on the power supply. Start the unit in the following condition.
Set the operation mode to FAN.
Set the fan speed level to HIGH.
(The unit (compressor) operates continuously in the above codition.)
No. Procedure Check points Causes
1. The temperature of the indoor heat exchanger is extremely low.
2. The connection of the heat exchanger sensor is loose. (The connector is disconnected.) (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to Table 9-8-2.)
4. The main P.C. board is defective.
1. The temperature of the indoor heat exchanger is extremely high.
2. The connector of the heat exchanger sensor short-circuited. (CN01)
3. The heat exchanger sensor and the P.C. board are defective. (Refer to T ab le 9-8-2.)
4. The main P.C. board is defective.
1. The indoor fan motor is defective. (Protected operation of P.C. board)
2. The connection of the motor connector is loose.
3. The P.C. board is defective.
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. Check whether or not the compressor operates.
2. Check whether or not the OPERATION lamp blinks.
1. Check it is impossible to detect the voltage (DC 12 V) between and6
3 of the motor terminals.
2. The motor does not operate. (But it is possible to receive the signal from the remote control.)
3. The motor rotates but vibrates strongly.
Temperature 0°C10°C20°C25°C30°C
Resistance value 33.8 20.35 12.59 10.0 7.99
(kΩ)
The self cleaning function is set from a factory. To cancel this function, should keep press the RESET switch on Indoor unit for 20 secounds till can hear the long combination sound and repeat the
same procedure when need to set.
PAP
AUTO
PRESET
MODE
CLOCK
CHECK
FILTER
RESET
HiPOWER
ECO
MEMO
CLR
SET
SWING
FIX
FAN
SLEEP
ON
OFF
TEMP
1.3.5.9H
2
17
17
1
] button to transmit the signal to the
indoor unit.
1 Press [SET] button while pressing [CHECK] button
with a tip of a pencil.
2 Then press [
9-9-3. How to set/cancel self cleaning function
63
FILE NO. SVM-06010
Press [ ]
button.
Is transmission
mark indicated?
Press RESET button
on remote control
with tip of pencil.
Is receiver on
indoor unit exposed
to direct sunlight?
Is there any
thyristor fluorescent
light nearby?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
Press [ ]
button.
Batteries are
exhausted.
Is transmission mark
indicated?
Does indoor unit
beep and operate?
Remote control
is defective.
Does indoor unit
start to operate by
automatic restart
function?
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Keep indoor unit
away from
thyristor
fluorescent light.
Avoid direct
sunlight.
Replace
P.C. board.
Replace
batteries.
Normal
operation
Replace
remote control.
The unit does not beep at all. OPERATION lamp on indoor unit is not indicated.
Note : After replacing batteries,
press the RESET button with a tip of a pencil.
NO
YES
YES
NO
NO NO
YES
YES
NO
YES
NO
YES
YES
YES
NO
NO
9-10. Troubleshooting for Remote Control
64
FILE NO. SVM-06010
10. PART REPLACEMENT
10-1. Indoor Unit
How to remove the front panel
1) Stop the operation of the air conditioner and turn off its main power supply.
2) Pull the inlet grille toward you to open it and remove the inlet grille.
3) Take off the right side of air filter.
4) Pull out the plasma air purifier and remove 4 screws fixing the front panel before open the horizontal louver and then remove the front panel from back
How to mount the front panel
1) Mount the front panel with the inverse procedure of
"How to remove the front panel".
2) Push 3 places (right, left and center) of the air outlet.
3) Check the gap between the front panel and the back body. If you operate the air conditioner in cooling or dry operation without pushing the 3 places, the surface of the front panel may be covered with frost and have dewdrops.
Open the horizontal grille right below by hand.
5)
body by pulling it toward you.
Pull the lower side of the front panel toward you
6) until it touches the horizontal grille to remove it.
1) Remove the front panel with the procedure 1.
2) Remove the screw fixing the electrical part box.
3) Remove the drain guide.
4) Remove the connector (5P) for the fan motor and the connector (6P) for the louver motor from the microcomputer assembly.
5) Remove the screw for the earth, and pull the electrical part base toward you to remove it from the main unit.
6) Pull out the TC sensor from the sensor holder.
1 Front panel
2 Electrical part
assembly
No. Part name Procedures Remarks
When assembling the electrical parts assembly, make the connecting cable U-shaped and put it in the drain pan.
(3) Drain guide
(6) TC sensor
(3) Drain guide
(2) screws
(5) screws
5P 6P
(4)
(3)
4-screws
(2)
(2)
(2)
65
FILE NO. SVM-06010
(1) Center shafts
(2) Left shafts
Pipe holder
(3) 2 screws
(4) 2 screws
(2) Screw
Bearing base
(2) Set screw
(3) Screws
Bearing base
Bearing
Motor fixture
(4) BODY (R)
(3) 2 screws
(4)
1) Remove center 2 shafts of the horizontal grille from the back body.
2) Remove left shaft of the horizontal grille from the back body.
3) Remove the horizontal grille from the back body.
1) Remove the front panel, electrical parts assembly and the horizontal grille with procedure 2 and 3.
2) Remove the screw on the rear side of the main unit to remove the pipe holder.
3) Remove 2 screws fixing the heat exchanger and the bearing base.
4) Remove 2 screws fixing the heat exchanger fixtures (upper and lower) and the back body then pull out the upper side of the heat exchanger slowly.
1) Remove the front panel, electrical parts assembly, horizontal grille and the heat exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws fixing the bearing base and the back body.
4) Pull the cross flow fan toward you.
1) Remove the front panel, electrical parts assembly, horizontal grille, heat exchanger and the cross flow fan with procedure 5.
2) Remove the bearing from the bearing base. If the housing protrudes from the base bearing, put the housing in position and assemble the bearing to the bearing base.
1) Remove the front panel, electrical parts assembly, horizontal grille, and the heat exchanger with procedure 4.
2) Loosen the set screw of the cross flow fan.
3) Remove 2 screws of the motor fixture.
4) Remove the lower side of the body (R) and move it right to remove it.
5) Remove the motor from the motor fixture.
3 Horizontal grille
4 Heat exchanger
5 Cross flow fan
6 Bearing base
7 Fan motor
No. Part name Procedures Remarks
When assembling the cross flow fan, fix it with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 8 mm.
FILE NO. SVM-06010
10-2. Outdoor Unit
1) Stop the operation of the air conditioner and turn off its main power supply or remove the power supply cord.
3) Remove 2 cord clamps (4 screws 4 x 16L) and disconnect the power supply cord and connecting cable after removing 6 screwson on the terminal block and 1 ground screw on the electrical parts base.
1 Common
procedure
No. Part name Procedures Remarks
Front cabinet
Side cabinet
2) Remove the packed valve cover and the electrical parts cover (2 screws4 x 10L)
4) Remove the top cabinet. (7 screws 4 x 10L) (Pulling out upward)
5) Remove the top cabinet. (2 screws 4 x 10L) (Pull the front right portion toward you, and remove it pulling out upward)
Top cabinet
Front
cabinet
2 screws
4 x 10L
4 screws 4 x 16L
2 Cord clamps
7 screws 4 x 10L
Packed valve cover
66
FILE NO. SVM-06010
1) Perform the common procedure 1
2) Remove the capacitor band. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screw ∅4 x 10L)
3) Disconnect the lead wires from the capacitor terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws 4 x 16L)
3) Disconnect the lead wires from the terminal.
1) Perform the common procedure 1
2) Remove the fixing screw. (1 screws 4 x 10L)
3) Disconnect the lead wires from the terminal.
2 Running
capacitor for compressor
3 Running
capacitor for fan motor
4 Magnetic
contactor
5 Spark killer
(Cooling only model)
Spark killer
Running capacitor for compressor
Running capacitor for fan motor
Magnetic contactor
Cooling only model
Procedures
Remarks
Part name
No.
Heat pump model
1) Perform the common procedure 1
2) Remove the fixing screw. (2 screws ∅4 x 10L)
3) Disconnect the housing from the P.C. Board.
1) Perform the common procedure 1
2) Disconnect the lead wires from the P.C. Board.
3) Remove P.C.Board after unhooking 4 clams.
6 Transformer
(Heat pump model)
7 Transformer
(Heat pump model)
Running capacitor for compressor
Running capacitor for fan motor
Magnetic
P.C. Board
Transformer
67
FILE NO. SVM-06010
11. EXPLODED VIEWS AND PARTS LIST
11-1. Indoor Unit (E-Parts Assy)
68
Location Part Location Part
No. No. No. No.
402 43T60365 TERMINAL BLOCK; 3P 411 43T69537 PC BOARD (FOR RAS-18NKDX5-T) 403 43T50004 SENSOR; HEAT EXCHANGER 411 43T69538 PC BOARD (FOR RAS-24NKDX5-T) 404 43T50314 SENSOR;THERMOSTAT 411 43T69539 PC BOARD (FOR RAS-24NKHD-E5) 405 43T69482 PC BOARD ASSY;WRS-LED 412 43T51307 MICRO SWITCH 407 43T62003 CORD CLAMP 413 43T63310 SENSOR HOLDER
Description Description
411
407
412
413
FILE NO. SVM-06010
11-2. Indoor Unit
69
232
214
215
220
219
218
227
208
228
229
222
221
213
235
233
204
202
203
201
212
223
210
207
216
230
209
226
224
211
231
238
237
236
234
217
Electric Part Assembly
Location Part Location Part
No. No. No. No.
201 43T00412 FRONT PANEL ASSY 223 43T79007 GUIDE DRAIN 202 43T09353 GRILLE ASSY 224 43T39016 FIX FOR MOTOR 203 43T80306 AIR FILTER (L) 226 43T21371 MOTOR FAN 204 43T80313 AIR FILTER (R) 227 43T20314 FAN; CROSS FLOW 207 43T03010 BODY; RIGHT 228 43T22309 ASM-M-BEARING 208 43T03011 BODY; LEFT 229 43T39015 BASE; BEARING 209 43T03012 HIDE; CLAW 230 43T03340 BACK BODY ASSY 210 43T09345 LOUVER-H (FOR RAS-18,24NKDX5-T) 211 43T70301 HOSE ASSY;DRAIN 230 43T03343 BACK BODY ASSY 212 43T21367 STEPPING MOTOR (FOR RAS-24NKHD-E5) 213 43T44310 REFRIGERATION CYCLE ASSY 231 43T07022 HOLDER; PIPE
(FOR RAS-24NKHD-E5) 232 43T82007 PLATE; INSTALLATION
213 43T44372 REFRIGERATION CYCLE ASSY 234 43T69402 WIRELESS REMOCON
(FOR RAS-18,24NKDX5-T) (FOR RAS-24NKHD-E5) 214 43T47311 PIPE; DELIVERY 234 43T69403 WIRELESS REMOCON 215 43T47016 PIPE; SUCTION (FOR RAS-18,24NKDX5-T) 216 43T49010 PIPE; SHIELD 235 43T83003 HOLDER; REMOTE CONTROLLER 217 43T19003 FIX-P-SENSOR 236 43T62029 COVER; TERMINAL 218 43T49009 SPRING 237 43T69496 ELECTRICAL SUPPLY ASSY 219 43T49036 PLATE; EVA-SEAL (FOR RAS-18,24NKDX5-T) 220 43T49039 HOLDER; PLATE EVA-SEAL 237 43T69497 ELECTRICAL SUPPLY ASSY 221 43T49038 PLATE; EVA-SEAL (FOR RAS-24NKHD-E5) 222 43T49037 HOLDER; PLATE EVA-SEAL 238 43T69499 ELECTRICAL PURIFIER ASSY
Description Description
FILE NO. SVM-06010
11-3. Outdoor Unit (RAS-24NAH-E)
70
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 23 43T39318 MOTOR BASE 2 43T41370 COMPRESSOR(Made in China) 24 43T19330 PACKED VALVE COVER 3 43T 49011 SPRING BASE(UPPER) 25 43T00455 UPPER CABINET 4 43T 49012 SPRING BASE (LOWER) 26 43T96304 BUSHING 5 43T 49019 SPRING; BUFFER 27 43T62325 ELECTRIC PART COVER 6 43T 97307 COMPRESSOR BOLT (M6) 28 43T61306 ELECTRIC PARTS BASE 7 43T 43372 CONDENSER ASSEMBLY 29 43T52305 MAGNETIC CONTACTOR 8 43T 00448 FIXING PLATE VALVE 30 43T55340 MF CAPACITOR
9 43T 46308 VALVE;PACKED 6.35 DIA 31 43T55333 MF-CAPACITOR 10 43T46338 VALVE,PACKED 15.88 DIA 32 43T60352 TERMINAL BLOCK; 6P 11 43T47331 BONNET, 6.35 DIA 35 43T19331 FIN GUARD 12 43T47334 BONNET; 15.88 DIA. 36 43T00456 UPPER FRONT CABINET; A 13 43T47013 CAPILLARY TUBE; 2.0 DIA 37 43T00457 UPPER FRONT CABINET; B 14 43T00449 FRONT CABINET 38 43T71301 HANDLE 15 43T00453 LEFT CABINET 39 43T46337 4 WAY VALVE 16 43T00454 RIGHT CABINET 40 43T46339 COIL;V-4WAY;AC220-240V 50Hz 17 43T21378 FAN MOTO R;AC220-240V 50Hz 41 43T69059 SENSOR; TE 18 43T20319 PROPELLER FAN 42 43T69060 SENSOR; TD 19 43T47001 NUT FLANGE 43 43T79305 DRAIN NIPPLE 20 43T19329 FAN GUARD 44 43T58301 TRANSFORMER; TT-05 21 43T04302 PARTITION 45 43T69336 PC Board 22 43T39317 MOTOR BASE CONNECTION PLATE 46 43T60325 FILTER;CLAMP
Description Description
72 –
FILE NO. SVM-06010
11-5. Outdoor Unit (RAS-24N2AX-T)
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 20 43T19329 FAN GUARD 2 43T41370 COMPRESSOR(Made in China) 21 43T04302 PARTITION 3 43T49011 SPRING BASE(UPPER) 22 43T39317 MOTOR BASE 4 43T49012 SPRING BASE (LOWER)
CONNECTION PLATE
5 43T49019 SPRING; BUFFER 23 43T39318 MOTOR BASE 6 43T97307 COMPRESSOR BOLT (M6) 24 43T19330 PACKED VALVE COVER 7 43T43370 CONDENSER ASSEMBLY 25 43T00455 UPPER CABINET 8 43T00448 FIXING PLATE VALVE 26 43T96304 BUSHING
9 43T46308 VALVE;PACKED 6.35 DIA 27 43T62325 ELECTRIC PART COVER 10 43T46338 VALVE,PACKED 15.88 DIA 28 43T61306 ELECTRIC PARTS BASE 11 43T47331 BONNET, 6.35 DIA 29 43T52305 MAGNETIC CONTACTOR 12 43T47334 BONNET; 15.88 DIA. 30 43T55340 MF CAPACITOR 13 43T47013 CAPILLARY TUBE; 2.0 DIA 31 43T55341 CAPACITOR;PLASTIC-FILM 14 43T00449 FRONT CABINET 32 43T60352 TERMINAL BLOCK; 6P 15 43T00453 LEFT CABINET 33 43T33002 SPARK-KILLER 16 43T00454 RIGHT CABINET 35 43T19331 FIN GUARD 17 43T21377 FAN MOTOR;AC220-240V 50Hz 36 43T00456 UPPER FRONT CABINET; A 18 43T20319 PROPELLER FAN 37 43T00457 UPPER FRONT CABINET; B 19 43T47001 NUT FLANGE 38 43T71301 HANDLE
Description Description
FILE NO. SVM-06010
11-3. Outdoor Unit (RAS-18N2AX-T)
71
Location Part Location Part
No. No. No. No.
1 43T42324 BASE PLATE ASSEMBLY 20 43T19329 FAN GUARD 2 43T41369 COMPRESSOR(Made in China) 21 43T04302 PARTITION 3 43T49011 SPRING BASE(UPPER) 22 43T39317 MOTOR BASE CONNECTION PLATE 4 43T49012 SPRING BASE (LOWER) 23 43T39318 MOTOR BASE 5 43T49019 SPRING; BUFFER 24 43T19330 PACKED VALVE COVER 6 43T97307 COMPRESSOR BOLT (M6) 25 43T00455 UPPER CABINET 7 43T43370 CONDENSER ASSEMBLY 26 43T96304 BUSHING 8 43T00448 FIXING PLATE VALVE 27 43T62325 ELECTRIC PART COVER
9 43T46308 VALVE;PACKED 6.35 DIA 28 43T61306 ELECTRIC PARTS BASE 10 43T46338 VALVE,PACKED 15.88 DIA 29 43T52302 MAGNETIC CONTACTOR; 11 43T47331 BONNET, 6.35 DIA AC220-240V 50Hz 12 43T47334 BONNET; 15.88 DIA. 30 43T55337 MF CAPACITOR 13 43T47013 CAPILLARY TUBE; 2.0 DIA 31 43T55341 CAPACITOR;PLASTIC-FILM 14 43T00449 FRONT CABINET 32 43T60352 TERMINAL BLOCK; 6P 15 43T00453 LEFT CABINET 33 43T33002 SPARK-KILLER 16 43T00454 RIGHT CABINET 35 43T19331 FIN GUARD 17 43T21377 FAN MOTOR;AC220-240V 50Hz 36 43T00456 UPPER FRONT CABINET; A 18 43T20319 PROPELLER FAN 37 43T00457 UPPER FRONT CABINET; B 19 43T47001 NUT FLANGE 38 43T71301 HANDLE
Description Description
87
FILE NO. SVM-03010(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000, THAILAND.
Loading...