1) When the FAN is set to A UTO, the indoor fan
motor operates as shown in Fig 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
28
27
Room temp.
26
25
24
Fig. 7-1-1 A uto setting of air volume
T a ble 7-1-1 Manual setting of FAN SPEED
Indication ofHIGH Air volume
F AN SPEED(m3/h)
LOW550
MED650
HIGH750
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter
simply by pushing the START/STOP button.
HIGH
MED
LOW(+)
LOW
LOW
7-2. COOL Operation
(MODE of the remote control : COOL)
(1) Compressor, 4-way v alve, outdoor fan and
operation display are controlled as shown in Fig.
7-2-1.
+1
Set temp.)
(Room temp. –
Set
0
temp.
Fig. 7-2-1
ON
OFF
Compressor
(2) A cool operation is carried out when the indoor
microcomputer sends the operation signal to the
outdoor microcomputer.
1) When the FAN is set to A UTO, the indoor fan
motor operates as shown in Fig 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
AUTO
+1,5
+1,0
+0,5
+0
(Room temp. – Set temp.)
Set
–0,5
temp.
RY01 OFF
HIGH
MED (+)
MED
LOW (+)
LOW
Fig. 7-2-2
ON
OFFOFFONON
4-way valve
FAN
Manual
According
to the set
position
Outdoor fan
Common relay
display
OPERATION
– 12 –
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter
simply by pushing the START/STOP button.
7-2-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
And the louver position is stored in the microcomputer, the louv ers will be set to the position
automatically at the next operation.
(2) When the AUT O b utton is pushed, the louv er
vertically swings within range of 25deg.
Page 13
7-3. HEAT Operation
(MODE of the remote control : HEAT)
(1) Compressor, 4-wa y valv e , outdoor fan and
operation display are controlled as shown in Fig.
7-3-1.
0
OFF
ON
ONON
7-3-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
(2) When the AUT O b utton is pushed, the louv er
vertically swings within range of 25deg.
And the louver position is stored in the micro-
computer, and at the ne xt operation, the louvers
will be set to the stored position automatically at
the next operation.
OFF
7-3-2. Cool Airflow Control
–1
(Room temp. – Set temp.)
ON
Compressor
Common relay
ON
4-way valve
Outdoor fan
Fig. 7-3-1
(2) A heat operation is carried out when the indoor
microcomputer sends the operation signal to the
outdoor microcomputer. The indoor f an motor
operates as shown in Fig. 7-3-2, when the FAN
is set to AUTO.
The motor operates with a constant air volume
as listed in Table 7-1-1, when the FAN is set to
LOW, MED, or HIGH.
Set
temp.
RY01 OFF
10,5
0
–0,5
–1,0
–1,5
AUTO
LOW
LOW (+)
MED
MED (+)
HIGH
FAN
Manual
According
to the set
position
display
OPERATION
(1) If the indoor heat-exchanger temperature
detected by the indoor heat-exchanger sensor is
16°C or below , the indoor fan stops and if the
temperature rises to 26°C or above, the f an is
restarted.
Details are in 7-8.
(Room temp. – Set temp.)
Fig. 7-3-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the
same operation can be effected thereafter
simply by pushing the START/STOP button.
– 13 –
Page 14
7-4. A UTO Operation
(MODE of the remote control : AUTO)
(1) One of the 3 modes, Cooling, Fan only and
Heating is selected according to room temperature at which operation is to start, as shown in
Fig. 7-4-1. The Fan mode will continue until
room temperature reaches a level at which
another mode is selected.
7-4-1. Temporary Auto
When the TEMPORARY button is pushed, the set
temperature is fixed at 24°C and controlled in
accordance with the chart shown in Fig. 7-4-1.
Cooling mode
+3
Heating mode
–3
(The same cooling mode as the room temperature control is set at set temp. –3˚C)
(The same heating mode as the room temperature control is set at set temp. +3˚C)
(Room temp. – Set temp.)
7-5. ECONO. Mode
When the ECONO. button is pushed, during COOL,
HEAT and AUTO operation, the OPERATION display
is turned off and the ECONO. display is lit and the
indoor unit operates quietly and mildly with controlling airflow .
7-5-1. Cooling
(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as
shown in Fig. 7-5-1.
(2) Fan speed → LOW
(˚C)
Set temp.
is changed
+2
Set temp.
is changed
+1
Fig. 7-4-1
7-5-2. Heating
(1) In the ECONO. mode, the set temp. by the
remote control is changed automatically as
shown in Fig. 7-5-2.
(2) Fan speed → LOW
ECONO. button
is pushed
1H2HTIME0H
Set temp.
-1
Set temp.
is changed
-2
Set temp.
is changed
(˚C)
Fig. 7-5-2
Set temp.
1H2HTIME0H
ECONO. button
is pushed
Fig. 7-5-1
– 14 –
Page 15
According to the
set position
Indoor fan speed
30
26
20
16
Heat exchanger
temperature
(˚C)
OFF
L (Low)
7-6. High-T emperature Limit Control
(Heating Operation)
7-8. Cool Airflow Prevention Control
(Heating Operation)
The microprocessor detects the indoor heat exchanger temperature so as to prevent e xceeding the
condensate pressure.
Control is performed as shown in Fig. 7-6-1.
Heat exchanger
temperature
(˚C)
60
*
1
54
52
*
1 ····· Only outdoor fan is turned off.
Compressor,
Outdoor fan
OFF
ON
Fig. 7-6-1
7-7. Low-Temperature Limit Control
(Cooling Operation)
The microprocessor detects the indoor heat exchanger temperature so as to prevent freezing up
the indoor heat exchanger .
Control is performed as shown in Fig. 7-7-1.
Heat exchanger
temperature
(˚C)
12
2
Compressor
Less than 2˚C continues
Outdoor fan
ON
for 6 minutes
OFF
(1) During the heating operation, the indoor fan
speed is controlled automatically in accordance
with the indoor heat exchanger temperature to
prevent b lo wing the cool air.
Control is performed as shown in Fig. 7-8-1.
Fig. 7-8-1
(2) As soon as the defrost operation starts, the
indoor fan stops.
7-9. Defrost Operation
During heat operation, if the temperature (Evaporating temperature) detected by the outdoor heat
exchange sensor (TE :Defrost) low ers b y the set
degree less than the temperature detected at start
time, the operation enters the defrost operation. In
this time, the 4-wa y v alve relay and the outdoor fan
are turned off. The indoor fan is turned off by the
cool air blow-out pre v enting control of the indoor
microcomputer at the indoor side, and "PRE.-DEF."
on the remote control goes on.
The defrost operation is automatically reset to the
normal operation when the temperature detected by
the above-mentioned TE sensor rises up to the set
value, or when Max. 12 minutes of the operation
time has passed.
Fig. 7-7-1
– 15 –
Page 16
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for outdoor use shall be more than polychloroprene
sheathed flexible cord (design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
This appliance must be connected to the mains by means of a circuit breaker or a switch with a
contact separation of at least 3 mm.
If this is not possible, a power supply plug with earth must be used. This plug must be easily
accessible after installation. The plug must be disconnected from the power supply socket in order
to disconnect the appliance completely from the mains.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make sure certainly that the installation of this air conditioner will be reported to the local
power supplier before installation.
If you have any obscure problems (or if the power supplier does not accept the installation) of this
appliance, service agency will take adequate countermeasures.
To Disconnect the Appliance from the Mains Supply.
8-2. Installation Diagram of Indoor and Outdoor Units
Anchor bolt arrangement of
outdoor unit
340 mm
• Secure the outdoor unit with the
anchor bolts if the unit is likely to
be exposed to a strong wind.
• Use Ø8 or Ø10 anchor bolts.
• If it is necessary to drain the
defrost water from the outdoor
unit, base pan attach the
drain nipple to the outdoor unit
before installing it.
The drain outlet is located as
shown above.
64 mm
600 mm
120 mm
Air outlet
Air intlet
Drain outlet
9
Air filters
(for both sides)
Mounting
screw
80mm or more
Clip anchor
(local part)
6
44mm or more
4
Pan head
wood screws
Installation
1
plate
130mm
or more
During piping installation
Wall
Insert the remote control holder cushion
between the indoor unit and wall, and lift
the indoor unit to make work easier.
Do not allow the drain hose
to get slack.
Cut the piping hole
sloped slightly
Make sure to run the drain hose sloped
downward.
The auxiliary piping can be
connected to the left, rear or down.
– 16 –
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE
SURE ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC
SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS
CONNECTED BY WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INST ALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE T O FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE
THE UNIT WELL AWAY (MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS,
HEA T REGISTORS, FURNACE, STO V ES , ETC .
WARNING
• Never modify this unit by removing any of the safety guards or by by-passing any of the safety
interlock switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
And make sure the equipment to be earthed.
• Appliance shall be installed in accordance with national wiring regulations.
CAUTION
• Exposure of unit to water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
If you detect any damage, do not install the unit. Contact y our T oshiba dealer immediately.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can
amplify the noise level of the unit or where noise and discharged air might disturb user’s neighbors.
• To av oid personal injury, be careful when handling parts with sharp edges.
• Please read the installation manual carefully before installing the unit. It contains further
important instructions for proper installation.
Deodorizing
7
filter
8
Before installing the wireless remote control
Wireless remote control
• With the remote control
cover opened, load the
supplied batteries correctly,
observing their polarity.
2
5
Batteries
Cover
100mm
or more
8-2-1. Optional Installation Parts
Part codeParts nameQ’ty
Refrigerant piping
ALiquid: Ø6,35Each one
Gas side : Ø12,7
Pipe insulating material
B
(Polyethylene foam, 6mm thick)
CPutty, PVC tapesEach one
Purifying
filter
600mm or more
1
Remote control
3
holder
2
Wireless remote
control
Vinyl tape
Apply after carrying
out a drainage test.
Saddle
100mm or more
Extention drain hose
(Option : RB-821SW)
600mm or more
Electric
parts
cover
600mm
or more
Loop the connective cable
(about 100 mm in diameter and 300 – 350 mm long).
Rear
Down
Rear left
Insulation of refrigerant pipes insulates
the pipes separately, not together.
6 mm thick heat resisting
polyethylene foam
Left
Drainage
Ø25
Drain
9
nipple
Bottom
plate
• Install the provided drain nipple in the
hole of the bottom plate of the outdoor
unit. (See figure at left.)
• Perform proper drainage processing
using a separately sold or market
available drain hose.
(16 mm inner diameter.)
• Do not use an ordinary hose available
at the market, since it tend to get flat,
resulting in a clog of drain water.
Separately sold or
market available
drain hose.
Page 17
– 17 –
Concrete wallConcrete wall
Installation
plate
Hole in anchor
Bolt
Hole in anchorInstallation plate
Nut with threaded
hole 8 mm dia.
Less than 15 mm
(6)Screws
(6)
(7)
(7)
(1) (2) (1) (2)(1) (2)Screw caps and screws
(5)
(3) (4)
(3) (4)
Front panel
Rear plate
Rear plate
bushing
Electrical component
box cover
Screws
Cord clamp
Wiring cover
Screw
8-3. Indoor Unit
8-3-1. Installation Place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place which allows an easy installation of the
piping to the outdoor unit.
• A place which allows the front panel to be opened.
CAUTION
• Direct sunlight to the indoor unit wireless
receiver should be avoided.
• The microprocessor in the indoor unit should
not be too close to r-f noise sources.
(For details, see the owner's manual.)
Remote control
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment.
(This is necessary to prevent image disturbances or
noise interference.)
• The location of the remote control should be
determined as shown below.
(Side view)
Indoor unit
75˚
Reception
range
8-3-2. Installation Parts
Part with an asterisk (*) is packaged with outdoor unit.
Part
Name of parts (Q'ty)
No.
1
Installation plate x 1
2
Wireless remote control x 1
3
Remote control holder x 1
4
Pan head wood screw
Ø3,1 x 16
5
Batteries x 2
x 2
7m
Remote
control
Fig. 8-3-1
(Top view)
Indoor unit
*
Part
Reception
range
: Axial distance
No.
6
7
8
9
Others
5m
5m
45˚
45˚
7m
*
Remote
control
Name of parts (Q'ty)
Mounting screw Ø4x 25
Deodorizing filter x 1
Purifying filter x 1
Drain nipple
x 1
*
Name
Owner’s manual
Installation manual
x 8
8-3-3. Cutting a Hole and Mounting
Installation Plate
Cutting a hole
Hooking
section
Center of pipe hole is located
on the line indicated by the
arrow and 100 mm apart from
the pipe hole center line.
100mm
Fig. 8-3-2
Refrigerant pipe hole
Ø65mm
47mm
Indoor unit outline
When installing the refrigerant pipes from the rear.
Determine the pipe hole position using the installation
plate, and drill the pipe hole Ø65 mm slightly downward.
NOTE
When using the drill to pierce the wall that contains a
metal lath, wire lath or metal plate, be sure to use a
pipe hole brim ring sold separately.
Mounting the installation plate
For installation of the indoor unit, use the paper
pattern on the back.
1 Installation plate
80mm
or more
40mm
100mm
Refrigerant pipe hole
Ø65mm
When the installation plate is directly
mounted on the wall
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation
plate on a concrete wall with
anchor bolts, utilize the
anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate
horizontally in the wall.
450mm
Anchor
Thread
Fig. 8-3-3
44mm
or more
bolt hole
100mm
Weight
Indoor unit
outline
40mm
21mm
4mm
130mm
or more
47mm
Refrigerant
pipe hole
Ø65mm
Installation plate
(Keep horizontal direction)
Fig. 8-3-4
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
1. Adjust the lateral position of the installation plate
without changing the height, so that each screw hole
in the plate comes in the center of a pillar or stud.
2. Make pilot holes with a bit to prevent the studs
from cracking, and then drive the screws into the
holes and tighten.
CAUTION
When installing the installation plate with
mounting screw, do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
• In the case of a reinforced concrete wall
(1) In the selected area on the reinforced concrete wall,
bore holes at intervals of 450 mm, and drive
clip anchors or hole in anchors into them.
(2) Attach the installation plate to the wall by
screwing bolts or nuts into the anchors.
However, in the case where hole in
anchors are used, the depth of the
holes should be adjusted so that the nutheads extend no more than 15 mm.Fig. 8-3-5
• There may be a wire conduit embedded in the wall.
Confirm on the blue prints or ask the builder.
• Install the installation plate using 4 to 8 pieces of
mounting screw securing four corners with screws.
• Make sure of the proper installation of the
installation plate before mounting the indoor unit.
Anchor
bolt
Projection
15mm
or less
Fig. 8-3-6
• In the case of the pipe on the back
Using the pattern, position the pipe hole, and bore the
hole slightly downward.
8-3-4. Electrical Work
Important items of indoor unit wiring
1. For electrical works the wiring and cables must be
performed in compliance with national wiring
standard or regulation. If incorrect and incomplete
wiring is carried out, it will cause an electrical fire
or electrical shock.
2. Do not use the inter-connecting cable.
Never execute the connection of electrical wiring
with other method than the approved one.
(exp. use the terminal block etc.)
3. Prepare the interior power supply cord capacity
sufficient for starting and usage current of air
conditioner.
4. Connect the connecting cable to the terminal as
identified with their respective matched numbers
on the terminal block of outdoor unit.
5. Fix the cable securely with the cord clamps to the
specified position.
6. Do not damage or scratch the conductive core &
inner insulator of power supply and inter
connecting cables when peeling them.
7. Do not deform or smash the surface of the cables.
Do not press or fix the cord and cables firmly with
staples, etc.
How to connect the cable
1. Remove the side panel. (2 screws)
2. Remove the electric parts cover and cord clamp.
3. Insert the connecting cable fully into the terminal
block and secure it by screw tightly.
Tightening torque : 1,2 N•m (0,12 kgf•m)
4. Secure the connecting cable with
the cord clamp.
5. Fix the electric
parts cover and
side panel.
How to open the screw cap
• Place your finger on the
lower part and push up to
open the screw cap.
Fig. 8-3-7
CAUTION
• Be sure to refer the wiring system diagram
labeled inside the side panel.
• Check local electrical codes and also any
specific wiring instruction or limitation.
How to remove the front panel
Fig. 8-3-8
(1) Open the screw caps and remove three front
panel fixing screws.
(2) Put the screw caps back as they were.
(3) Press the part saying “PUSH” on the air inlet grille
to open the air inlet grille.
Remove three black front panel fixing screws.
(4) Close the air inlet grille.
(5) Manually open the vertical air flow louver directly
below.
(6) Open the front panel lower portion until it comes in
contact with the vertical air flow louver. Lift up the
front panel upper portion in a forward diagonal
direction to unhook the clicks inside the front
panel upper portion.
(7) After unhooking the nails inside the main unit
upper portion, rotate the front panel upper portion
towards you to remove the front panel from the
unit body.
Fig. 8-3-9
Stripping length of connecting cable
220 mm
10 mm
3
2
1
50 mm
60 mm
Fig. 8-3-10
NOTE
• Use standard wire only
• Wire type : More than H05 RN-F (1,3 mm² or more)
• Inser t the connecting cable fully into the terminal
block and secure it by screw tightly.
• Tightening torque : 1,2 N•m (12 kgf•cm)
• Secure the connecting cable with the cord clamp.
• Fix the wiring cover, rear plate bushing and front
panel on the indoor unit.
Page 18
– 18 –
TEMPORARY
REMOTE CONTROL
AUTO
TEST RUN
(COOL)
Cord clamp
Grounding
wire
21
Terminal block
Connecting
cable
Wiring cover
Screws
Screw
Fig. 8-3-11
8-3-5. Piping and Drain Hose Installation
Left-hand connection with piping
• After scribing slits of the rear
panel by a knife or a markingoff pin, cut them by a pair
of nippers or the like.
Slit (rear panel)
Fig. 8-3-12
Bend the connecting pipe so that it is laid within 52
mm above the wall surface. If the connecting pipe is
laid exceeding 52 mm above the wall surface, the
indoor unit may unstably be set on the wall.
When bending the connecting pipe, make sure to use
spring bender so as not to crush the pipe.
Bend the connecting pipe within a radius of 40 mm.
NOTE
If the pipe is bent incorrectly, the indoor unit would be
unstably set on the wall and the air conditioner might
be raised.
1. When the piping runs to the left, remove the left
side body bushing of the rear panel. You may need
the body bushing when you relocate the unit, so
be sure to make customer keep it in a safe place.
2. After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary
pipes and wrap facing tape around them.
Outward form of indoor unit
R 40mm (Use polisin (polyethylene core)
or the like for bending pipe.)
52 mm
80˚
Use the handle of screwdriver,etc.
Fig. 8-3-13
Underside connection with piping
1. Cut out the knock-out piece from the right below of
the rear plate with a knife, etc. Smooth the cut
edges.
Pipe holder Rear plate
Slit part
Pipe holder
Fig. 8-3-14
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the
auxiliary pipes (two) only with facing tape.
Fig. 8-3-15
1
2
Indoor unit
Space for pipes
Connecting
cable
Hook here
1
Hook here
Fig. 8-3-16
Fig. 8-3-17
Installation
plate
Wall
Drain
guide
Auxiliary
pipes
Installation
plate
• Carefully arrange pipes so that any pipe does
not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble,
make sure to insulate both the connecting
pipes. (Use polyethylene foam as insulating
material.)
• When bending a pipe, carefully do it not to
crush it.
8-3-6. Indoor Unit Fixing
1. Pass the pipe through the hole in the wall, and
hook the indoor unit on the installation plate at the
upper hooks.
2. Swing the indoor unit to right and left to confirm
that it is firmly hooked up on the installation plate.
3. While pushing the indoor unit onto the wall by the
lower part, hook it up on the installation plate by
the lower part.
Pull the indoor unit
toward you by the
lower part to confirm
that it is firmly
hooked up on the
installation plate.
This air conditioner has the
structure designed to drain
water collected from dew,
which forms on the back of the
indoor unit, to the drain pan.
Therefore, do not store the
power cord and other parts
at a height above the drain
guide.
8-3-7. Drainage
1. Run the drain hose sloping downwards.
NOTE
• Hole should be made at a slight downward slant to
the outdoor side.
Do not rise the drain hose.
50 mm
or more
2. Put water in the drain pan and make sure that the water
is drained out of doors.
3. When connecting extension drain hose, insulate the
connecting part of extension drain hose with shield
pipe.
Drain hose
Do not form the drain hose
into the waved shape.
Do not put the
drain hose end
into water.
Fig. 8-3-18
Shield pipe
Inside the room
Do not put the drain
hose end in the
drainage ditch.
Extension drain hose
Fig. 8-3-19
CAUTION
Arrange the drain pipe for proper drainage from the
unit. Improper drainage can result in dew-dropping.
How to install the front panel on the indoor unit
Install the front panel through the opposite order of “How
to remove the front panel”.
When the panel is removed and mounted again, take the
following action : After fastening the 6 screws, be sure to
hook the inside clicks
shown in the diagram, right gap is between the front panel
and the rear plate.
• If cooling (dr y) operation is made without pushing the air
outlet, dew can be deposited on the front panel surface.
In addition, a gap between the front panel and the body
will become wider, spoiling the appearance.
8-3-8. Gas Leak Test
• Check the flare nut connections, valve stem cap
connections and service
cap connections for gas
leak with a leak detector
or soap water.
Fig. 8-3-21
, , and of the front panel
PushPushPush
3
Fig. 8-3-20
Flare nut
connections
(Outdoor unit)
1
Electric parts
cover
2
Valve stem cap connection
D
B
C
Flare nut
connections
(indoor unit)
Valve stem
cap connection
A
Service cap
connection
8-3-9. Check and Test Operation
¨ 1. Check the unit is firmly hooked up on the
installation plate.
¨ 2. Check the connecting pipes tightened
securely.
Confirm that there is no gas leakage.
¨ 3. Confirm that all connecting cables are
secured and correct.
¨ 4. Check the pipe insulation.
¨ 5. Check the drainage.
¨ 6. Connection of the grounding wire.
¨ 7. To switch the TEST RUN (COOL) mode,
turn the switch on.
TEMPORARY
REMOTE CONTROL
AUTO
TEST RUN
(COOL)
Fig. 8-3-22
Make sure to return the TEMPORARY switch
to REMOTE CONTROL.
Three-minutes protection feature
A protection feature prevents the air
conditioner from being active for about 3
minuets when it is restarted immediately
after operation.
¨ 8. Operate the unit at cooling operation
mode for fifteen minutes or more.
Measure the temperature of the intake
and discharge air. Ensure the difference
between the intake temperature and the
discharge one is more than 8°C.
NOTE: Three-minutes protection feature
A protection feature prevents the air
conditioner from being activated for
about 3 minutes when it is restarted
immediately after operation.
¨ 9. Check the remote control operation when
it is at fixed position.
When finished the check and test operation,
make sure to return the TEMPORARY switch
to REMOTE CONTROL.
¨ 10. Explain to the customer on the correct
usage of air conditioner with simple
layman’s terms.
Page 19
8-4. Outdoor Unit
8-4-1. Installation Place
• A place which provides the spaces around the outdoor
unit as required above in the diagram.
• A dr y sunny place. If the place is exposed to direct
sunlight use an awning for protection.
•
A place which can bear the weight of the outdoor unit and
does not allow an increase in noise level and vibration.
• A place where the operation noise and discharged air
do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an elevated
position, be sure to secure its feet.
• A place where the drain water does not raise any problem.
• An allowable length of the refrigerant piping is up to 15 m.
• An allowable heat level is up to 6 m.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always to a strong wind like a coast or
on a high story of a building, secure the normal
fan operation using a duct or a wind shield.
3. Specially in windy area, install the unit to
prevent the admission of wind.
– 19 –
4. Installation in the following places may result
trouble. Do not install the unit such places.
• A place full of machine oil.
• A saline-place such as coast.
• A place full of sulfide gas.
• A place where high-frequency
waves are likely to be
generated as from
audio equipment,
welders, and
medical
equipment.
8-4-2. Refrigerant Piping Connection
Flaring
2. Insert a flare nut into the pipe, and flare the pipe.
Outer dia.
(mm)
6,351,30,70,8
12,71, 81,0 to 1,11,0
Tightening Connection
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
• Do not apply excess torque.
Otherwise, the nut may crack depending on the conditions.
Evacuate the air in the connecting pipes and in the
indoor unit using vacuum pump. Do not use the
refrigerant in the outdoor unit.
For details, see the manual of vacuum pump.
Use of vacuum pump
1. Connect the charge hose (A) from the manifold valve
to the charge inlet of the gas side packed valve.
2. Connect the charge hose (B) to the port of vacuum
pump.
3. Open fully the low pressure side handle of the
manifold valve.
4. Operate the vacuum pump.
5. Close the low pressure side handle of manifold valve
after evacuating and stop the vacuum pump.
Continue evacuating more than 15 minutes and check
the pressure gage indicates –0,1 MPa (–76 cm Hg).
6. Open the stems of packed
valves A and B1 all the way.
7. Securely tighten the stem
cap to each of the packed
valve stems.
Indoor unit
C
A
Gas
(Ø12,7)
D
B
1
Liquid
(Ø6,35)
Low pressure
side handle
Outdoor unit
Service port
Packed
valve
Pressure
gage
Fig. 8-4-5
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING W ORK
(1)Take away dust and moisture
(Inside of the connecting pipes.)
(2)Tight connection (between pipes and unit)
(3)Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4)Check gas leak (connected points)
A
Packed V alve Handling Precautions
• Open the valve stem all the way out; so not try to
open it beyond the stopper.
• Securely tighten the valve stem cap torque is as follows;
Gas pipes side (ø12,7 mm) : 49 N•m (5,0 kgf•m)
Liquid pipe side (ø6,35 mm) : 16 N•m (1,6 kgf•m)
Flare nut
Valve body
Valve stem
Hexagon wrench is required.
Stopper
5mm
Valve stem cap
(Unit : N•m)
Internally
threaded side
Manifold valve
Lo Hi
Charge
hose (B)
Charge
hose (A)
Fig. 8-4-6
High
pressure
side
handle
VP
8-4-4. Electrical Work
How to connect the power cord
For the air conditioner that has no power cord,
connect a power cord to it as mentioned below.
• Remove the electric parts cover from the outdoor
unit. (4 screws)
• After removing the electric parts cover, remove
the cord clamp.
• Connect and secure the power supply cord.
Earth line
Cord
clamp
Terminal block
N
L
Screw
2
1
Power
supply
cord
3
Terminal block
Earth line
Screw
Cord
clamp
Connecting
cable
Fig. 8-4-7
Stripping length of power cord
90mm
10mm
N
L
10mm
80mm
Fig. 8-4-8
Earth line
NOTE
• Use standard wire only.
• Wire type : 3,5 mm² or
more AWG-12.
WARNING
To plug the cable in the plug receptacle, take
the following precaution.
THIS APPLIANCE MUST BE EARTHED.
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE
COLORED IN ACCORDANCE WITH THE
FOLLOWING CODE :
L
: Brown
N
: Blue
: Green and Yellow
As the colors of the flexible cord of this
appliance may not correspond with the colored
markings, to identify terminals in your plug, as
follows :
Connect BROWN colored core to plug terminal
marked letter “L”.
Connect BLUE colored core to plug terminal
marked letter “N”.
Connect GREEN and YELLOW colored core to
plug terminal marked Earth symbol “
The installation of the cables has to be done in
such a way that the basic insulated wires for the
infrared sensor can not be touched.
Use the power supply cord/cables with
thickness, type, and protective devices
specified in the installation manual.
Prepare the interior power supply cord and
cables wiring with current capacity sufficient for
starting and usage of air conditioner.
-LIVE
-NEUTRAL
-EARTH
Fig. 8-4-9
L
N
”.
ModelRAS-18YAH-E RAS-18YAH-A
Power source
Maximum running current16,8 A
Plug socket & fuse rating20 A
Wiring3,5 mm² (AWG-12) or more
(RAS-18YKH-E) (RAS-18YKH-A)
50 Hz ~, 220 – 240V
50 Hz ~, 240V
CAUTION
If incorrect/incomplete wiring is carried out, it
will cause an electrical fire or smoke.
Prepare the power source for exclusive use with
the air conditioner.
This product can be connected to the mains.
Connection to fixed wiring :
A switch or circuit breaker which disconnects all
poles and has a contect separation of at least 3
mm must be incorporated in the fixed wiring.
An approved short circuit breaker or switches
must be used.
8-4-5. Wiring Connection
1. Remove the electric parts cover from the
outdoor unit. (4 screws)
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers
on the terminal block of indoor and outdoor unit.
(1,3 mm² AWG-16 or more)
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown
installation diagram, to prevent water coming in
the outdoor unit.
4. Insulate the unused cords (conductors) with
strip the sheath of connecting cable to prevent
the shortage or electric leakage.
Process them so that they do not touch any
electrical or metal parts.
Stripping length of connecting cable
60mm
Earth line
10mm
3
2
1
10mm
50mm
Fig. 8-4-10
Connecting
cable
123
Screws
Cord clamp
Terminal
block
Terminal
screw
CAUTION
1. Wrong wiring connection may cause some
electrical parts burn out.
2. Be sure to use the cord clamps and the
electric parts cover to the specified positions
with attached to the product.
Mount the electrical parts cover for cables of
connecting section firmly with the screws.
3. Do not damage or scratch the conductive
core and inner insulator of power supply and
inter connecting cables when peeling them.
4. Be sure to comply with local cords on running
the wire from indoor unit to outdoor unit (size
of wire and wiring method etc.) Wire type :
More than H05 RN-F
5. Use the power supply cord and inter-connecting
cable with specified thickness, specified type,
and protective devices specified.
6. No wire should touch refrigerant piping,
compressor of any moving parts.
Page 20
9. TROUBLESHOOTING CHART
Troubleshooting Procedures :
• Following details of “What to be pre-chec k ed
first”, make sure of the basic items.
• When there is no trouble corresponding to
above, chec k in detail the faulty parts following “How to judge f aulty parts by symptoms”
later.
9-1. What to be Prechecked First
9-1-1. Power Supply Voltage
The line voltage must be A C 220–240V (RAS18YKH-E, RAS-18YAH-E), 240V (RAS-18YKH-A,
RAS-18YAH-A). If the line voltage is not within this
range, this air conditioner may not work normally.
No.
Operation of air-conditioner
9-1-2. Incorrect Cable Connection between
Indoor and Outdoor Units
The indoor unit is connected to the outdoor unit with
4 cables. Make certain that the indoor and outdoor
units have been connected properly, with terminals
assigned the same numbers wired to each other.
If the connectors are not connected as specified, the
outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will flash (5Hz).
9-1-3. Misleading but Good Operations
(Program Controlled Operation)
The microcomputer performs the operations listed in
Table 9-1-1 to control the air conditioner. If a claim
is made on the operation, check whether it corresponds to the contents in the Table 9-1-1.
If it does, it is an indispensable operation for the
control and maintenance of the air conditioner: it is
not a failure of the unit.
T able 9-1-1
Description
1
When the breaker is turned on, the
OPERATION lamp on the setting
indication part flashes.
2
Fan speed remains unchanged in the
dry mode.
3
Room temperature is in the range
under which the compressor is turned
off, but the compressor will not stop.
4
The compressor will not switch on or
off even when the thermo control is
operated in the dry operation.
5
The PRE-DEF. lamp comes on when
the heating operation is started.
6
The outdoor fan stops once in the
while during the heating operation.
7
Compressor does not work though
room temperature is in the range of
turning the compressor on.
8
During automatic operation, the
operation mode changes.
The OPERATION lamp flashes, indicating that power is
turned on. If this happens, push the START/STOP b utton
once to cause the lamp to stop flashing. A po wer outage
also causes the lamp to flash.
Fan speed is automatically controlled in the dry mode.
The compressor will not stop while the compressor on hold
timer (3-minutes timer) is actuated.
In the dry mode, the compressor goes on and off at regular
intervals, independent of the thermo control.
The PRE-DEF. lamp comes on during defrost operation and
when the indoor heat exchanger temperature is low when the
heating operation is started. At this time, the indoor fan is
stopped to prevent cold air from drifting into the room.
• When the indoor heat exchanger temperature is high, the
outdoor fan may be stopped b y the high-temper ature limit
control operation.
Compressor does not work while the compressor restart
delay (3-min.) timer is active. The same is true after power is
turned on, as the time is still active.
After selection of the cooling and heating operation, the
operation mode is selected again when the compressor off
mode continues for 15 min. according to the room temperature.
9
During automatic operation mode, the
fan only operation continues.
When the room temperature is within setting temperature ±
1°C the fan only mode is selected.
– 20 –
Page 21
9-2. Primary Judgment of Trouble
Sources
9-2-1. Role of Indoor Unit Control
The indoor unit controller receives the operation
commands from the remote control and assumes
the following functions.
• Measurement of the draft air temperature of the
indoor heat exchanger by using the thermo
sensor (TA).
• Louver motor control
• Control of the indoor fan motor operation
• Control of the LED display
• Sends the operation signal to the outdoor microcomputer.
9-2-2. Display of Abnormalities and
Judgement of the Abnormal Spots
The indoor unit of this machine observes the operation condition of the air conditioner and displays the
contents of the self-diagnosis as block displa ys on
the display panel of the indoor unit.
T able 9-2-1
Block display
A
OPERATION display flashing (1 Hz)
B
OPERATION display flashing (5 Hz)
C
OPERATION display flashing (5 Hz)
D
OPERATION display flashing (5 Hz)
E
OPERATION display flashing (5 Hz)
F
OPERATION and TIMER display flashing (5 Hz)
G
OPERATION, TIMER and PRE-DEF. display
flashing (5 Hz)
H
OPERATION, TIMER and PRE-DEF. display
flashing (5 Hz)
(1) Judgement from defective operation or abnormal operation
T able 9-2-2
Po w er f ailure (when power is ON)
Thermo sensor (TA) short/break
Heat exchanger sensor (TC) short/break
Indoor fan lock, abnormality of indoor fan
Indoor P.C. board failure
Wrong wiring of connecting cable
• Gas shortage, other refrigerant cycle trouble
• Heat exchanger sensor open/break/short
• Overload relay or thermostat for compressor
trouble
Cycle abnormal
Block display
Symptom
No reaction on
remote control
operation
The outdoor fan
does not rotate
Check
Turn off the power once, turn it on
again and try to operate the remote
control again.
The compressor operates.
The compressor does not operate.
– 21 –
Remote control is
not possible.
Remote control is
possible.
Primary judgement
The indoor part (including the
remote control) is defective .
OK.
The outdoor part is defective.
(outdoor fan motor)
The inside part is defective.
Page 22
(2) Self-diagnosis with remote control
With the indoor unit control, self-diagnosis of
protective circuit action can be done by turning
the remote control operation into service mode,
operating the remote control, observing the
remote control indicators and checking whether
TIMER lamp flashes (5 Hz).
Note :
• T o perf orm this self-diagnosis, the remote
control with the service code of 43069666
is required.
<How to select remote control operation mode>
1) Selecting service mode
Push the switch button pro vided on rear
bottom of the wireless remote control with a
tip of pencil for more than 3 seconds.
Make sure the setting temperature is
displayed on the display and other display is
turned off.
2) Selecting ordinary mode
Push the all clear button (ACL) on the rear
bottom of the wireless remote control with a
tip of pencil for more than 3 seconds. Make
sure the operation mode display, wind volume
display, clock display and setting temperature
display are turned on and “ : ” of the clock
display is flashing.
<Cautions when doing service>
1) After completion of servicing, always push
the all clear (ACL) button to return the
operation mode to the normal mode.
2) After completion of servicing by the check
code, turn off the power once and then turn
on the power to reset memorized contents of
the microcomputer to the initial status.
ACL CLOCK
(Rear bottom of remote control)
Fig. 9-2-1
All clear button
Switch for selecting
service mode
ACL
CLOCK
Rear bottom cover
– 22 –
Page 23
<Self-diagnosis by check codes>
1) The self-diagnosis by the check codes is conducted under the block displays of item B-H in
Table 9-2-1.
2) Remote control key operation under the service
mode is conducted by ON/OFF or TEMP. The
remote control display by each key operation is
varied as shown below . Two digit number is
displayed in a he xadecimal n umber .
3) The self-diagnosis by the check codes is conducted with procedures shown below .
a) Enter the service mode and make sure the
off timer display of the remote control shows
.
b) Operate the “ON/OFF” key and mak e sure
the timer lamp on the display section is
flashing (5 Hz).
c) At the same time, also make sure the opera-
tion lamp is also flashing. This shows that
the protection circuit on the indoor P.C. board
is working.
d) Operate the TEMP. key and make sure
the remote control display shows and
flashing of the operation lamp. If the operation lamp is flashing, it shows the protection
circuits for connecting cable is working or
thermal fuse is blown.
e) In the same way, operate the TEMP.
key so that the displa y is increased one by
one to continue checks by the self-diagnosis
as shown in the next table. From up to
check operations of protection circuits
for each block, and to check
operations of the typical protection circuits.
Operating key
ON/OFF
TEMP.(Up)
TEMP.(Down)
“AUTO” LOUVER
“SET” LOUVER
T able 9-2-3
Indication after operation
1 is added to data before operation.
(Example)
1 is subtracted from data before operation.
(Example)
10 is subtracted from data before operation.
(Example)
Data before operation is directly transferred.
(Example)
➞
➞
➞
➞
– 23 –
Page 24
T able 9-2-4
Block level
Check
code
Block
Indoor P.C.
board
Cable
connection
Refrigerant
system
Check
code
Diagnosis function
Symptom
Indoor temp. (TA) sensor is
out of place.
Disconnection or short-circuit
Indoor temp. (TC) sensor is
out of place.
Disconnection or short-circuit
Trouble on indoor fan
Abnormal revolution speed of
fan
Indoor unit or other part is
defective.
EEPROM access error
Outdoor temp. sensor is out of
place.
Disconnection or short-circuit
Outdoor temp. sensor is out of
place.
Disconnection or short-circuit
Discharge temp. error
Detection of discharge temp.
over the set value
High-pressure switch
operation
IOL operation
Serial signal is not sent from
the outdoor unit to the indoor
unit.
• Miswiring of crossover wire
• Serial send circuit of the
outdoor P.C. board is
defective.
• Serial receive circuit of the
indoor P.C. board is
defective.
Trouble on the four-way valve
system
• After cooling operation has
started, the indoor heat
exchanger temp. rises.
• After heating operation has
started, the indoor heat
exchanger temp. lowers.
Trouble on other cycle line
• After cooling/heating
operation has started, the
indoor heat exchanger
temp. (TC) does not vary.
• When the compressor stop
command is sent by freezepreventing control.
Compressor break down.
Air
Conditioner
status
Operation
continues.
Operation
continues.
All off
Operation
continues.
All off
All off
All off
All off
Operation
continues.
Operation
continues.
Operation
continues.
Operation
continues.
Compressor stops.
Indoor fan
LOW
All off
Condition
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Indicated when
detected
abnormal
Judgment and action
1. Check the indoor temp. sensor (TA).
2. Check the indoor P.C. board.
1. Check the indoor temp. sensor (TC).
2. Check the indoor P.C. board.
1. Check the connector circuit for
revolution speed input (CN13).
2. Check the indoor fan.
3. Check the indoor P.C. board.
1. Check the indoor P.C. board.
(EEPROM and peripheral circuits)
1. Check the outdoor temp. sensor (TE).
2. Check the P.C. board.
1. Check the outdoor temp. sensor (TD).
2. Check the P.C. board.
1. Check the refrigerating cycle
(Gas leak).
2. Check the pipe sensor (TD).
1. Check the high-pressure switch.
2. Check the circuits of high-pressure
switch line.
• Disconnection and contact failure of
CN04 connector
• Check the P.C. board.
3. Overload operation of the refrigerating
cycle
1. In case that the outdoor unit does not
operate at all,
• Check crossover wire./Correct
miswiring.
• Check the outdoor P.C. board.
2. In case that the outdoor unit operates
normally,
While the outdoor send Serial LED (Green)
on the indoor P.C. board flashes , If the
receive Serial LED (Orange)
Flashes : Check the indoor P.C. board.
Does not flash : Check the outdoor P.C. board.
1. Check the four-way valve.
2. Check the indoor heat exchanger
sensor (TC).
3. Check the indoor P.C. board.
1. Inner overload relay operation of
compressor case thermostat
(Electromagnetic contact OFF-STOP)
2. Indoor heat exchanger sensor sensing
part out of place
3. Check the indoor heat exchanger
sensor (TC).
4. Check the indoor P.C. board.
1. Check the charged amount of
refrigerant gas.
• Gas shortage →
Gas refilling, gas leak check
2. Check the indoor fan. (Lock)
1. Check compressor.
2. If it is OK, check P.C. board.
Contents detected by the check codes to are stored in memory of the microcomputer even if the power supply is turned off.
Therefore, contents of operations in the past are all displayed.
– 24 –
Page 25
Details of Table 9-2-2
Judgment of Trouble by Every Symptom
[04 Serial signal error]
Does outdoor
unit operate?
YES
Does LED (Orange)
on indoor
P.C. board flash?
YES
NO
Are 1, 2, and 3 crossover
wires normal?
YES
Is connection of
connector normal?
YES
Does LED (Orange) on
outdoor P.C. board flash?
YES
NO
Does LED (Green) on
outdoor P.C. board flash?
YES
NO
NO
NO
NO
Check outdoor P.C. board.
Failure
Check indoor P.C. board.
Failure
Correct crossover wires.
Correct connection
of connector.
Replace
P.C. board.
Replace
P.C. board.
[08 Four-way valve error]
Is operation of
four-way valve normal?
YES
Is characteristic of
TC sensor resistance
value normal?
NO
NO
YES
• Refer to the Characteristic diagram.
10k
Has coil
terminal 220–240V
in heating?
Are circuit
wires normal?
Outdoor P.C. board
check?
at 25˚C
Unsatisfied
YES
YES
Satisfied
NO
NO
– 25 –
Four-way valve check
Failure
Outdoor P.C. board check
Failure
(CN11 220–240V)
Indoor P.C. board check
Failure
Replace
Circuit check/modification
Replace
P.C. board.
Replace
P.C. board.
Replace TC sensor.
Page 26
[09 Other cycle error] (1)
NO
Replace
TC sensor.
YES
Correct
connection
Does compressor
operate?
YES
Does compressor
tune off halfway?
NO
Is characteristic of
TC sensor resistance
value normal?
YES
• Refer to the
Characteristic
diagram.
at 25˚C
10k
Isn't TC sensor
disconnected from
the sensing part?
NO
NO
YESYES
Doesn't
inner over-relay
(in compressor)
operate?
NO
Is circuit wiring
normal?
YES
Outdoor
P.C. board
check?
Normal
NO
Failure
Check charged amount of refrigerant.
Check abnormal overload.
Trouble on compressor
Replace
compressor
Wiring check/modification
Replacement failure
of outdoor P.C. board
Indoor P.C. board check
Failure
Replace
P.C. board.
Replace
P.C. board.
[09 Other cycle error] (2)
NO
Is connection of
connector normal?
Modify
connection
of connector
NO
Replace
condenser.
NO
Replace
fan motor.
Is condenser
normal?
Is indoor fan
motor normal?
YES
YES
YES
NO
Does indoor
fan operate?
Isn't filter clogged?
Is characteristic of
TC sensor resistance
value normal?
Is charged amount
of refrigerant normal?
YES
Is outside air
low load?
YES
YES
NO
NO
Refer to Characteristic diagram.
at 25˚C
YES
Amount (1,45kg) charged in factory.
NO
10k
NO
YES
Freeze-preventing
operation
Freeze-preventing
operation
Clean filter.
Replace
TC sensor.
Addition of
refrigerant
Indoor P.C. board check
Failure
– 26 –
Replace
P.C. board.
Page 27
[0C Indoor TA sensor error]
Is connection of CN04
TA sensor connector normal?
YES
Is characteristic of TA sensor
resistance value normal?
YES
[0d Indoor TC sensor error]
Is connection of CN05
TC sensor connector normal?
YES
Is characteristic of TC sensor
resistance value normal?
YES
NO
NO
• Refer to Characteristic diagram.
10k
at 25˚C
Indoor P.C. board check
Failure
NO
NO
• Refer to Characteristic diagram.
10k
at 25˚C
Modify connection
of connector.
Replace
TA sensors.
Replace
P.C. board.
Modify connection
of connector.
Replace
TC sensors.
[18 Outdoor TE sensor error]
Is connection of TE sensor
connector normal?
YES
Is characteristic of TE sensor
resistance value normal?
YES
Indoor P.C. board check
Failure
NO
NO
• Refer to Characteristic diagram.
10k
at 25˚C
Outdoor P.C. board check
Failure
– 27 –
Replace
P.C. board.
Modify connection
of connector.
Replace
TE sensors.
Replace
P.C. board.
Page 28
[19 Outdoor TD sensor error]
Is connection of TD sensor
connector normal?
YES
Is characteristic of TD sensor
resistance value normal?
YES
[1E Discharge temp. error]
NO
NO
• Refer to Characteristic diagram 4 and 5.
10k
at 25˚C
Outdoor P.C. board check
Failure
Modify connection
of connector.
Replace
TL/TD sensors.
Replace
P.C. board.
Is protective
control such as discharge
thermostat normal?
YES
Is charged amount
of refrigerant normal?
YES
Isn't it abnormal
overload?
NO
Is characteristic of
TD sensor resistance
value normal?
YES
NO
NO
YES
NO
• 10k
at 25˚C
Are wiring/connector
connection normal?
Outdoor P.C. board check
Failure
NO
Modify wiring/connector
connection.
Check and modify charged
amount of refrigerant.
1,45kg
Make better/delete the cause.
Replace TD sensor.
Replace P.C. board.
– 28 –
Page 29
9-3. T r oubleshooting Flo wcharts
9-3-1. Power cannot be Turned on (No Operation at All)
< Preliminary checks >
(1) Is the supply voltage normal?
(2) Is the connection to the AC output OK?
(3) Are the connection of the primary side and the secondary
side of the power transformer inserted into the P.C. board?
(4) Is the FUSE (F01) blown?
Turn the power off for about 5
seconds and then turn it on again.
Does the OPERATION
lamp flash?
NO
YES
Does the transmission indicator of the
remote control flash normally, and is
Does operation start
when you push the ON/OFF button
of the remote control?
NO
the transmission really performed?
YES
Is the lead wire disconnected from
the infrared rays receive parts?
NO
Infrared rays receive parts
or P.C. board failure
YES
NO
YES
(Normal)
Remote
control
failure
Operations
Check items
Probable
main causes
Remedies
Item by
symptoms
Replace
Connect the
wire properly
Replace
Is 50Hz 220–240V AC
supplied to the primary side of
the power source transformer?
Refer to above “Preliminary checks”.
Or there is a defect before the power transformer.
Power
transformer
is failure
Microcomputer
is failure
Replace
transformer
Replace the
P.C. board
Replace the
P.C. board
Fig. 9-3-1 P o wer transf ormer connection diagram
– 29 –
Page 30
9-3-2. Only the Indoor Fan does not Operate
< Preliminary checks >
Does it neither work in COOL or FAN ONLY operation?
< Checking procedure >
Turn OFF the power
(“REMOTE CONTROL” position)
Turn ON the power
(“REMOTE CONTROL” position)
Does the fan stop at the
operation stop condition?
YES
Start operation at HIGH cooling
Does the fan rotate?
YES
Change the setting
to LOW cooling
Does the rotating speed
of the fan lower?
YES
NO
NONO
NO
Stop the
operation
Control P.C. board failure
Does 120V AC or higher
voltage apply to between red and
black lead of the motor?
YES
Turn OFF the power
Is it possible to rotate the
cross flow fan by hand?
YES
Turn ON the power
NO
Replace the
P.C. board
Motor control
circuit failure
(lC01, 05, D04) or
12V power circuit
(Q03, D01) or
thermal fuse failure.
Repair the
cross flow fan
Normal
When rotating the
cross flow fan by hand at
the operation stop condition,
is the rotation signal (+12VDC
detected between (2) (gray lead)
and (3) (brown lead) of the motor
connector (PJ13 or CN13)?
(1 pulse/1 revolution)
YES
Motor circuit (D03, Q06, IC01)
or 12V power circuit
(Q03, D01) failure
– 30 –
0V)
NO
Replace the
fan motor
Replace the
control P.C. board
Page 31
9-3-3. Wiring Failure (Interconnecting and Serial Signal Wire)
(1) Outdoor unit does not operate
1) Is the voltage between and of the indoor terminal block varied?
Confirm that transmission from indoor to outdoor is correctly performed based upon the following dia-
gram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
Terminal block at indoor side
Red
White
Normal time: Voltage swings between DC15 and 60V.
Abnormal time : Voltage does not vary.
3
2
Terminal block
1
S5277G
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400V
or more is acceptable.)
Tester
Fig. 9-3-2
(2) Outdoor unit stops in a little while after operation started
<Check procedure> Select phenomena described below.
(1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to
restart the unit.
Gas circulation amount is down.
Measure gas pressure.
Thermo. operation of compressor
Gas shortage
Gas leak
Pipe clogging
Fig. 9-3-3
(2) If the unit stops once, it does not operate until the power will be turned on again.
To item of Compressor does not operate.
Fig. 9-3-4
(3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.