7-2 Outline of Air Conditioner Control
7-3 Description of Operation Mode
7-4 Drescription of Safety and Reliability Prevention Function
7-5 One-Touch Operation
7-6 Hi POWER Operation
7-7 QUIET Operation
7-8 ECO Operation
7-9 COMFORT SLEEP Operation
7-10 FILTER Check lamp
7-11 Auto Restart Function
7-12 Self-Cleaning Operation
FILE NO. SVM-09030
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control (Including the Indoor P.C. Board)
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit
- 1 -
FILE NO. SVM-09030
1. SPECIFICATIONS
MODEL
RAS-13SKHP-ES / RAS-13S2AH-ES
ITEM Cooling Heating
Capacity
Power source V 220 - 240
Power consumption kW 1.151.19 1.14 1.18
Power factor % 98 96 97 95
Running Indoor A 0.15
current Outdoor A 5.205.00 5.20 5.00
Starting current A 29
Moisture removallit/h2.0
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
INDOOR UNIT RAS-13SKHP-ES
Dimensions Width mm 790
Net weight kg 9
Evaporator typeFinned tube
Indoor fan type Cross flow fan
Air-flow volume Medium fan m3/h 520550
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT RAS-13S2AH-ES
DimensionsWidthmm780
Net weight kg 38
Condenser typeFinned tube
Outdoor fan typePropeller fan
Air-flow volume m3/h 2120
Indoor (H/M/L) dB
Outdoor (220 - 240 V) dB 50 51 50 51
Name of refrigerant R410A
Rated amount kg 0.95
Gas side size mm Æ12.7
Connection typeFlare connection
Liquid side size mm Æ6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
Height mm 275
Depth mm 205
High fan m3/h 620650
Low fan m3/h 430450
Heightmm550
Depth mm 290
Model
Output W1100
kW 3.75
Phase 1Æ
Hz50
m
m
220 V 240 V 240 V 220 V
3.82 4.20 4.26
41/38/35/33/31
1
15*
6
2200
42
PA150X2C-4FT
2120 2200
− 2−
Note : 1
·
Capacity is based on the following temperature conditions.
FILE NO. SVM-09030
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1 No need to charge extra refrigerant.
Condition
Cooling Heating
(DB) 27°C20°C
(WB)19°C15°C
(DB) 35°C7°C
(WB)24°C6°C
JIS C9612
- 3 -
2-1. Indoor Unit
FILE NO. SVM-09030
2. CONSTRUCTION VIEWS
790
Front panel
63
7
48
Knock out system
275
Air filter
116
Heat exchanger
Installation plate hanger
Air inlet
62 69
193480
205
Knock out system
49
56
Wireless remote controller
48
63
7
157
19
Installation plate hanger
Connecting pipe (0.35m)
(Flare 12.7mm)
84.5
Minimum
distance
to wall
275
170 or more
40
Hanger
84.515084.5
621
235
215
Hanger
Minimum
distance
to ceiling
235
215
160.5160.5150
Center line
- 4 -
Drain hose (0.50m)
Connecting pipe (0.40m)
6.35mm)(Flare
84.5
65 or more
Minimum
distance
to wall
170 or more
Hanger
Installation plate outline
63
Remote controller holder
45
190
40
125
26
2.2. Outdoor Unit
600
50
36
320
306
A detail Drawing (Back leg)
R5.5
R
Ø
15
6 hole
28
86
320
Ø
FAN-GUARD
436
Ø
A
25 Drain outlet
108 125
2
-
Ø
11 x 14
(For 8 -
Ø
Ø
Hole
10 anchor bolt)
FILE NO. SVM-09030
306
320
Ø
6 hole
11x14 hole
Ø
B Detail Drawing (Front leg)
36
50
R
15
COVER-PV
Z
290
550
275
320
342
Electrical part cover
Liquid side
(Flare 6.35)
Ø
Gas side
(Flare 12.7)
Ø
5
4
S
ervice port
Z View
9060090
69
129
84
100 or more
321
100 or more
Air outlel
600
Air intlel
600 or more
− 5 −
600 or more
4x 11 Long holes(For 8- 10 anchor bolt)
Ø
Ø
Ø
3. WIRING DIAGRAM
FILE NO. SVM-09030
OUTDOOR
OUTDOOR
OUTDOOR
TERMINAL
TERMINAL
BLOCK
BLOCK
COMPRESSOR
COMPRESSOR
BLK
BLK
BLK
BLK
BLK
BLK
BLK
BLK
PNK
PNK
WHI
WHI
(L)2(N)
(L)2(N)
(L)2(N)
(L)2(N)
(L)
(L)
1
1
1
1
1
RED
RED
(N)
(N)
2
2
BLU
BLU
BLU
BLU
BLU
BLU
SOLENOID COIL
SOLENOID COIL
CAPACITOR
CAPACITOR
RED
RED
RED
RED
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
CAPACITOR
3
3
3
3
313
BLU
BLU
BLU
BLU
BLU
BLU
FAN
FAN
MOTOR
MOTOR
4
4
4
4
4
4
WHI
WHI
− 6 −
CHASSIS
CHASSIS
BLK
BLK
INDOOR
OUTDOOR
FILE NO. SVM-09030
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No.Parts nameTypeSpecifications
1 Fan motor (for indoor)
2Thermo sensor (TA-sensor)10k at 25 C
3 Micro Power Module (M01)
4 Microcontroller unit (IC30) TMP87CM40ANG
5Heat exchanger sensor
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
·
·
*1During heating overload operation, a value for the high temperature limit control operation is included.
- 8 -
6. CONTROL BLOCK DIAGRAM
FILE NO. SVM-09030
Heat Exchange sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Reciver
Main Unit Control Panel
Functions
• Louver Control
•3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise FilterRelay Driver, Louver Driver
•Motor Revolution Control
•Processing
(Temperature Processing)
•Timer
Compressor
ON/OFF
Signal
Outdoor Fan
Relay
RY01
M.C.U.
ON/OFF
Signal
Relay
4-Way Valve
ON/OFF
Signal
RY03
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PRE DEF.
Sign Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
Relay
RY04
220-240 V~, 50Hz
REMOTE CONTROL
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Compressor 4-Way Valve
Remote Control
Operation ( )
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
TIMER 1.3.5.9H
COMFORT SLEEP
QUIET
Outdoor Fan Motor
Infrared Rays
− 9 −
7. OPERATION DESCRIPTION
FILE NO. SVM-09030
7-1. Remote control
7-1-1. Function of Push Putton
11 Infrared signal emitter
1
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN)
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON)
Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Timer setup button (SET)
11
12
20
Timer clear button (CLR)
13
Memory and Preset button (PRESET)
14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
Clock Reset button (CLOCK)
20
21
Check button (CHK)
13
14
17
10
21
19
1
TOSHIBA
PRESET
TEMP
ONE-TOUCH
2
QUIET
SWING
FIX Hi-POWER ECO
6
7
8
TIMER
SLEEP
CHK
ON
FILTER
OFF
CLOCK
FAN
MODE
COMFORT
SLEEP
CLR
SET
5
4
3
18
15
16
12
9
11
20
− 10 −
FILE NO. SVM-09030
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1.Transmission mark
This transmission mark
remote controller transmits signals to the indoor
unit.
indicates when the
2. Mode indicator
Indicates the current operation mode.
(A : Auto, : Cool,
: Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed.
AUTO or five fan speed levels
LOW , LOW+ , MED , MED+ ,
(
HIGH ) can be shown.
Indicate Auto will be appear with Dry operation
( : Dry) only.
9
1
12
2
13
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock
time is indicated.
The current time is always indicated except
during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is
pressed during operation.
The
button for more than 3 seconds while the mark is
blinks.
Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is
set, “B” appears in the remote controller display.
(When the remote controller setting is “A”, there is
no indication at this position.)
10.Comfort sleep
Indicates when comfort sleep is activaled.
Press comfort sleep button to selectter
11
6
3
8
7
4
5
11.Quiet
Indicates when quiet is activated.
Press quiet button to start and press it again to stop
operation.
12.One-Touch
Indicates when one touch comfort is activated.
Press one-touch button to start the operation.
13.Swing
Indicates when louver is swing.
Press swing button to start the swing operation
and press it again to stop the swing operation.
- 11 -
FILE NO. SVM-09030
7-2. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit.
The outdoor unit receives operation commands
from the indoor unit, and operates the outdoor
fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
Operations according
to the commands
from the indoor unit
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the Indoor heat
exchanger, control the four-way valve and
outdoor fan motor control)
7-2-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button
is stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed, it stops
swinging.
7-2-2. Indoor Fan Control
The operation controls the fan speed at indoor unit
side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 5
stages in MANUAL mode, and in 5 stages in AUTO
mode, respectively. (Table 7-2-3)
1) When setting the fan speed to L, L+,M, M+ or H
on the remote controller, the operation is performed
with the constant speed shown in Table 7-2-1 and
Table 7-2-2
Table (7-2-1) Cooling
Indication
L
L+
M
M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Table (7-2-2) Heating
Indication
L
L+
M
M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Table 7-2-3 Indoor fan and air flow rate
CoolingUHH
OPERATION
MODE
RAS-13SKHP-ES
Model
Fan only
Dry
Heat UHHMLL-ULSL
rpm
Air flow volume (m3/h)
2) When setting the fan speed to AUTO on the remote
controller, revolution of the fan motor is controlled
to the fan speed level show in Table 7-2-3
according to the setup temperature, room temperature,
and heat exchanger temperature.
FAN TAP
M
HMLL-
MLL-ULSL
1300
1350
650 620 550 520 450 430 430 400
1150 1100
950
900
L
L-
850 UL750 SL650
900
350
- 12 -
310
550
260
500
240
FILE NO. SVM-09030
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-1. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-3-2.
° C
ONON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-3-2
display lamp
OPERATION
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) − (Preset temp.)
Preset
temp.
0
(Preset temp.: 24 °C)
NOTE 1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
(Linear approximation from M+ and L)
Fig. 7-3-1 Setting of air flow [FAN:AUTO]
M+
*1
*2
*3
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
(Linear approximation from M+ and L)
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
-
13
-
FILE NO. SVM-09030
7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-3-4.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-4
7-3-4. Heating operation
(1) The compressor, 4-way valve, outdoor fan and
Preset
temp.
display lamp
OPERATION
([MODE] button on the remote control is set
to the heating operation.)
operation display lamp are controlled as shown in
Fig. 7-3-6.
° C
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
display lamp
Fig. 7-3-6
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L.L.
*Super Low
Fig. 7-3-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The ECO, COMFORT SLEEP, QUIET and
Hi POWER operations can not be set.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-7. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) − (Preset temp.)
L
*1
*2
+
M
H
*1 : Fan speed = (M + − L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 3/4 + L
(Calculated with Linear approximation from M+ and L+)
Fig. 7-3-7
-
14
-
FILE NO. SVM-09030
y.
c
e
c
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-3-8
T
46
34
45 33
33 21
32 20
*A+0 *A+0
*A-8 *A-8
Fan speed MANUAL or AUTO in starting
Fan speed AUTO in stability
* No limitation while fan speed MANUAL mode is in stabilit
* A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
Fan speed AUTO Fan speed MANUAL
Normal AUTO
Line-approximate
H and SL with Tc.
SL
Stop
L-H (Up to
setting speed)
Line-approximate
H and SL with Tc.
SL
Stop
[In starting and in stability]
In starting
FAN • Until 12 minutes
AUTO
passed after operation
start
•When 12 to 25 minutes
passed after operation
start and room temp.
is 3°C or lower than
set temp.
In stability
•When 12 to 25 minutes
passed after opeartion
start and room temp.
is than (set )
between preset
• When 25 minutes or
more passed after
operation start
3°C
7-3-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-9.
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) − (Preset temp.)
FAN • Room temp. < Set
Manual
temp.–4°C
• Room temp. Set
temp. –3.5°C
Fig. 7-3-8 Cold draft preventing control
(4) In order to prevent cold draft when compressor
during heating operation.Then louver will move
to upper position and fan speed will reduce or
OFF.
-
15
Fig. 7-3-9
-
7-4. Drescription of Safety and Reliability Prevention Function
FILE NO. SVM-09030
7-4-1. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Heat exchanger
temperature
(°C)
6
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
Fig. 7-4-1
7-4-2 High-Temperature Limit Control
7-4-3. Defrost Operation
During the heating operation, the outdoor heat
exchanger temperature goes down and sometimes it is
frozen.
In this case, the air conditioner stops the heating
operation and starts the defrost operation to melt ice.
Condition to start the defrost operation
The defrost operation starts whichever below
conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference
between the indoor heat exchanger temperature
and the room temperature is less than the
specified value. (This value is decided by the
microprocessor.) (Control example is shown in
Fig. 7-4-3. In case of B or C, the defrost operation
starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of
90 minutes.
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-2.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger
temp.
(°C)
60
53
52
Fig. 7-4-2
xchanger temp
A
Indoor heat e
- Room temp
Fig. 7-4-3 (Indoor fan speed : M)
D
B
C
Cumulative
compressor
operating time
-
16
-
Defrost operation time control
FILE NO. SVM-09030
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is
10 minutes. (When the outdoor temperature is
very low, however, the defrost operating time is
10 minutes.)
minutes
40
Heating
minutes
40
Defrost
Heating
Max 6 minutes
minutes
Defrost
1 cycle
40
Heating
minutes
40
Defrost
Heating
10 minutes
Defrost
Fig. 7-4-4
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operating time is 10 minutes.
Ending condition at defrost operation
(1) When the compressor current becomes 5.40A or
more during defrost operation, the defrost
operation stops and the heating operation restarts.
(The current sensor detects the compressor
current.)
(2) The defrost operation continues for at most
6 minutes or 10 minutes.
DEFROST LAMP :
·
During defrost operation, the PRE-DEF. lamp is
on and the indoor and outdoor fans are off.
·
The compressor start protection timer is interlooked with the PRE-DEF. lamp. So the PRE-DEF.
Lamp is off (the fans stop) for about 3 minutes
after the [ ] button is turned on. When
the compressor is turned on, the PRE-DEF. lamp
comes on. After the heat ex-changer is preheated
to about 24
goes off, and the indoor fan starts.
°C or higher
, the PRE-DEF. Lamp
-
17
-
7-4-4. Current Limit Control
The microcontroller detects the input current so as to
prevent it exceeds a specified value by means of
controlling the outdoor fan control as described in (1)
and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting
the compressor operating current with a current
sensor (C.T).
Input current
11.0A I4
10.0A I3
FILE NO. SVM-09030
CompressorOutdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
(2) Current limit control (Heating operation)
Control is performed as shown in Fig. 7-4-6
Input current
11.0A I4
10.0A I3
6.45A I2
5.40A I1
ON
Fig. 7-4-5
CompressorOutdoor fan
More than I4 continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ONOFF
ON
Fig. 7-4-6
- 18 -
FILE NO. SVM-09030
7-5. One-Touch Operation
One touch comfort is the fully automated operation that is set according to the preferable condition in a region.
Fan
Operation
AUTO
*AUTO/L
L
0
*AUTO/L : Fan operates depends on the setting temperature and room temperature.
During the One Touch Comfort mode if the indoor unit receives any signal with other operation mode, the unit
will cancel the comfort mode and operates according to the signal received.
Operation description
When an indoor unit receives "One Touch Comfort Signal" from the remote controller, the indoor unit operates
as following.
1) Air conditioner starts to operation when the signal is received, even if the air conditioner was OFF.
2)Operation mode is set according to room temperature, the same as AUTO mode.
3) Target temperature is 24ºC.
4) Louver position is set as stored position.
5)Fan is controlled as diagrom.
12
25
Time after operation
starts (min)
-
19
-
FILE NO. SVM-09030
7-6. Hi POWER Operation
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the display of the remote
control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the
·
current operation.
(2) Cooling operation
• The setting temperature drops 3°C.
(The value of the setting temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1°C less than the setting
temperature the horizontal louver returns
automatically.
• FAN speed : [AUTO]
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
• FAN speed : One of 5 levels
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
The indoor unit's fan speed level increase 1 tap
·
(3) Heating operation
The preset temperature increases 2°C,
·
(The value of the preset temperature on the
remote control does not change.)
The indoor unit operates in normal heating
·
mode except the preset temperature is higher
(+2°C).
The indoor unit's fan speed level increase 1 tap
·
(4) The Hi POWER mode can not be set in Dry or
Fan only operation.
(5) The Hi POWER mode can memorize with timer
function.
7-7. QUIET Operation
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L− until the [QUIET] button is pressed once
again (cancel Quiet mode).
Quiet mode is the system which, control the revolving
speed of indoor fan to work constantly at lower than
speed L. In addition, noise level of indoor unit is less
than usual.
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less cooling
load and less heating load condition. Because of the
fan speed L− may cause not enough the cooling
capacity or heating capacity.
7-8. ECO Operation.
Cooling operation
·
The preset temperature will increase 1ºC after the
ECO mode has operated for 1 hour and the temperature
will increase another 1ºC after the ECO mode has
operated for 2 hour. (the value of the preset temperature
on the remote control does not change.)
·
The indoor fan speed is depend on presetting and can
change every speed after setting ECO operation.
Heating operation
·
The preset temperature will drop down 1ºC after the
ECO mode has operated for 1 hour and the temperature
will drop down another 1ºC after the ECO mode has
operated for 2 hour. (the value of the preset temperature
on the remote control does not change.)
·
The indoor fan speed is depend on presetting and can
change every speed after setting ECO operation.
7-9. COMFORT SLEEP Operation
Cooling operation
·
The preset temperature will increase 1ºC after the comfort
sleep mode has operated for 1 hour and the temperature
will increase another 1ºC after the comfort sleep mode
has operated for 2 hour. (the value of the preset temperrature on the remote control does not change)
·
Press the [COMFORT SLEEP] button to select this
function. The comfort sleep function will be activate
togetther with Auto shut down function. Period of
operation time can be select by re-press the
[COMFORT SLEEP] button. The period of operation
time are follows.
1H3H5H9H
-