Toshiba RAS-10YKV-E, RAS-13YKV-E, RAS-10YAV-E, RAS-13YAV-E SERVICE MANUAL

SERVICE MANUAL
AIR-CONDITIONER
FILE NO. A00-T004
SUPPLEMENT
SPLIT TYPE
RAS-10YKV-E RA-88YKV-E
/
/
RAS-13YAV-E
RAS-10YAV-E
R410A
PRINTED IN JAPAN, Aug.,2000 ToMo
CONTENTS
1. SPECIFICATIONS ...........................................................3
2. REFRIGERANT R410A...................................................6
3 . CONSTRUCTION VIEWS..............................................14
4. WIRING DIAGRAM........................................................16
5. SPECIFICATIONS OF ELECTRICAL PARTS...............18
6. REFRIGERANT CYCLE DIAGRAM..............................19
7. CONTROL BLOCK DIAGRAM .....................................21
8. OPERATION DESCRIPTION ........................................23
9. INSTALLATION PROCEDURE .....................................36
10. HOW TO DIAGNOSE THE TROUBLE ...........................40
11. HOW TO REPLACE THE MAIN P ARTS ........................59
12. EXPLODED VIEWS AND PARTS LIST.........................69
– 2 –
1. SPECIFICATIONS
1-1. Specifications
RAS-10YKV-E/RAS-10YAV-E
Unit model Current limited
Cooling capacity (kW) 2,7 Cooling capacity range (kW) 0,8 – 3,4 Heating capacity (kW) 3,6 Heating capacity range (kW) 0,8 – 6,2 Power supply 220 – 230 –240V – 1Ph – 50/60Hz Electric
characteristics
COP (Cooling/Heating) 3,86 / 4,00 Operating noise
Indoor unit
Outdoor unit
Piping connection
Accessory
Indoor Outdoor
Indoor
Outdoor
Indoor
Outdoor (Cooling / Heating) (dBA) 45 / 46 Unit model Dimension
Net weight (kg) 8 Fan motor output (W) 19 Air flow rate (Cooling / Heating) (m³/h) 480 / 520 Unit model Dimension
Net weight (kg) 38 Compressor
Fan motor output (W) 40 Air flow rate (Cooling / Heating) (m³/h) 2120 / 2120 Type Flare connection
Maximum length (Per unit) (m) 15 Maximum chargeless length (m) 15 Maximum height difference (m) 10 Name of refrigerant R410ARefrigerant Weight (kg) 0,8
Indoor unit
Outdoor unit Drain nipple 1
Operation mode Running current (A) 0,15 0,15 Power consumpti on (W) 30 30 Power factor (%) 87 87 Operation mode Running current (A) 3,39 / 3,23 / 3,09 4,40 / 4,20 / 4,02 Power consumption (W) 670 870 Power factor (%) 90 90 Starting current (A) 4,55 / 4,35 / 4,17
High (Cooling / Heating) (dBA) 38 / 39 Medium (Cooling / Heating) (dBA) 34 / 35 Low (Cooling / Heating) (dBA) 30 / 30
Height (mm) 265 Width (mm) 790 Depth (mm) 189
Height (mm) 550 Width (mm) 780 Depth (mm) 270
Motor output (W) 750 Type Twin rotary type with DC-inverter variable speed control Model DA91A1F-44F
Liquid side Ø6,35Indoor unit Gas side Ø9,52 Liquid side Ø6,35Outdoor unit Gas side Ø9,52
Power supply 3 Wires : includes earthWiring connection Interconnection 4 Wires : includes earth Indoor (Cooling / Heating) (°C) 21 – 32 / 0 – 28Usable temperature range Outdoor (Cooling / Heating) (°C) 10 – 43 / –10 – 21 Installation plate 1 Wireless remote control 1 Label 2 Remote controller holder 1 Pan head wood screw 2 (Ø3,1 x 16L) Purifying filter 1 Deodorizing filter 1 Batteries 2 Mounting screw 6 (Ø4 x 25L) Installation manual 1 Owner's manual 1
Cooling Heating
Cooling Heating
• The specifications may be subject to change without notice for purpose of improvement.
RAS-10YKV-E
RAS-10YAV-E
RAS-10YKV-E
RAS-10YAV-E
– 3 –
RAS-13YKV-E/RAS-13YAV-E
Unit model
Current limited — Cooling capacity (kW) 3,7 Cooling capacity range (kW) 0,8 – 4,0 Heating capacity (kW) 4,8 Heating capacity range (kW) 0,8 – 6,6 Power supply 220 – 230 –240V – 1Ph – 50/60Hz Electric
characteristics
COP (Cooling/Heating) 3,08 / 3,20 Operating noise
Indoor unit
Outdoor unit
Piping connection
Accessory
Indoor Outdoor
Indoor
Outdoor
Indoor
Outdoor (Cooling / Heating) (dBA) 48 / 50 Unit model Dimension
Net weight (kg) 8 Fan motor output (W) 19 Air flow rate (Cooling / Heating) (m³/h) 530 / 560 Unit model Dimension
Net weight (kg) 38 Compressor
Fan motor output (W) 40 Air flow rate (Cooling / Heating) (m³/h) 2520 / 2520 Type Flare connection
Maximum length (Per unit) (m) 15 Maximum chargeless length (m) 15 Maximum height difference (m) 10 Name of refrigerant R410ARefrigerant Weight (kg) 0,8
Indoor unit
Outdoor unit Drain nipple 1
Operation mode Running current (A) 0,15 0,15 Power consumption (W) 30 30 Power factor (%) 87 87 Operation mode Running current (A) 5,59 / 5,34 / 5,11 7,03 / 6,71 / 6,43 Power consumption (W) 1170 1470 Power factor (%) 95 95 Starting current (A) 7,18 / 6,86 / 6,58
High (Cooling / Heating) (dBA) 41 / 41 Medium (Cooling / Heating) (dBA) 36 / 36 Low (Cooling / Heating) (dBA) 30 / 30
Height (mm) 265 Width (mm) 790 Depth (mm) 189
Height (mm) 550 Width (mm) 780 Depth (mm) 270
Motor output (W) 750 Type Twin rotary type with DC-inverter variable speed control Model DA91A1F-44F
Liquid side Ø6,35Indoor unit Gas side Ø9,52 Liquid side Ø6,35Outdoor unit Gas side Ø9,52
Power supply 3 Wires : includes earthWiring connection Interconnection 4 Wires : includes earth Indoor (Cooling / Heating) (°C) 21 – 32 / 0 – 28Usable temperature range Outdoor (Cooling / Heating) (°C) 10 – 43 / –10 – 21 Installation plate 1 Wireless remote control 1 Label 2 Remote controller holder 1 Pan head wood screw 2 (Ø3,1 x 16L) Purifying filter 1 Deodorizing filter 1 Batteries 2 Mounting screw 6 (Ø4 x 25L) Installation manual 1 Owner's manual 1
Cooling Heating
Cooling Heating
RAS-13YKV-E
RAS-13YAV-E
RAS-13YKV-E
RAS-13YAV-E
The specifications may be subject to change without notice for purpose of improvement.
4
1-2. Operation Characteristic Curve
<Cooling> <Heating>
7
6
7
6
RAS-10YKV-E RAS-13YKV-E
5
4
3
Current (A)
2
Conditions
5
4
3
Current (A)
2
Indoor : DB 27˚C/WB 19˚C Outdoor : DB 35˚C
1
Air flow : High
1
Pipe length : 5m 230V
0
0 20 40 60 80 100
0
0 20 40 60 80 100
Compressor speed (rps)
1-3. Capacity Variation Ratio According to Temperature
RAS-10YKV-E RAS-13YKV-E
• Conditions Indoor : DB 20˚C Outdoor : DB 7˚C/WB 6˚C Air flow : High Pipe length : 5m 230V
Compressor speed (rps)
<Cooling>
105
Current Limited Start
100
95 90 85
RAS-10YKV-E RAS-13YKV-E
80 75 70
Capacity ratio (%)
65 60
Conditions Indoor : DB27˚C/WB19˚C
55 50
32 34
Indoor air flow : High Pipe length 5m
36 38 40 4233 35 37 39 41 43
Outdoor temp. (˚C)
Capacity ratio : 100% = 2,7 kW (RAS-10YKV-E)
*
100% = 3,7 kW (RAS-13YKV-E)
120 110 100
90 80 70 60 50
Capacity ratio (%)
40 30 20
RAS-10YKV-E RAS-13YKV-E
Conditions Indoor : DB 20˚C
10
0
–10–9–8–7–6–5–4–3–2–1012345678910
Indoor air flow : High Pipe length : 5m
Outdoor temp. (˚C)
– 5 –
2. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1,6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water, dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
2-1. Safety During Installation/Servicing
As R410A’s pressure is about 1,6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusiv e for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
(1) Never use refrigerant other than R410A in an air
conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pres­sure in the refrigeration cycle becomes abnor­mally high, and it may cause personal injury, etc. by a rupture.
(2) Confirm the used refrigerant name, and use
tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
(3) If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully. If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
(4) When installing or removing an air conditioner,
do not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture or personal injury may be caused.
(5) After completion of installation work, check to
make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(6) When an air conditioning system charged with a
large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks , its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal level, an oxygen starvation accident may result.
(7) Be sure to carry out installation or remova l
according to the installation manual. Improper installation may cause refrigeration
trouble, water leakage, electric shock, fire, etc.
(8) Unauthoriz ed modifications to the air conditioner
may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repair’s may result in water leakage, electric shock and fire, etc.
2-2. Refrigerant Piping Installation
2-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refriger ant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants .
(1) Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discol­ored portion (especially on the interior surface). Otherwise, the expansion valve or capillary tube may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 2-2-1. Never use copper pipes thinner than 0,8 mm even when it is available on the market.
– 6 –
Table 2-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
Nominal diameter Outer diameter (mm) R410A R22
1/4 6,35 0,80 0,80 3/8 9,52 0,80 0,80 1/2 12,70 0,80 0,80 5/8 15,88 1,00 1,00
(2) Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all con­taminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 2-2-3 to 2­2-6 below .
Table 2-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 6,35 0,50 3/8 9,52 0,60 1/2 12,70 0,70
Reference outer diameter of
copper pipe jointed (mm)
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm. Thicknesses of socket joints are as shown in Table 2-2-2.
Minimum joint thickness
(mm)
5/8 15,88 0,80
2-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil other than lubricating oils used in the installed air conditioner is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
(1) Flare Processing Procedures and Precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
– 7 –
c) Insertion of Flare Nut d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Table 2-2-3 Dimensions related to flare processing for R410A
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen- sion A by using a gauge for size adjustment.
ØD
A
Fig. 2-2-1 Flare processing dimensions
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
Conventional flare tool
Clutch type Wing nut type
1/4 6,35 0,8 0 to 0,5 1,0 to 1,5 1,5 to 2,0 3/8 9,52 0,8 0 to 0,5 1,0 to 1,5 1,5 to 2,0 1/2 12,70 0,8 0 to 0,5 1,0 to 1,5 2,0 to 2,5 5/8 15,88 1,0 0 to 0,5 1,0 to 1,5 2,0 to 2,5
Table 2-2-4 Dimensions related to flare processing for R22
A (mm)
A (mm)
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Flare tool for R410A
clutch type
Conventional flare tool
Clutch type Wing nut type
1/4 6,35 0,8 0 to 0,5 0,5 to 1,0 1,0 to 1,5 3/8 9,52 0,8 0 to 0,5 0,5 to 1,0 1,0 to 1,5 1/2 12,70 0,8 0 to 0,5 0,5 to 1,0 1,0 to 2,0 5/8 15,88 1,0 0 to 0,5 0,5 to 1,0 1,0 to 2,0
Table 2-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
ABCD
Dimension (mm)
Flare nut
1/4 6,35 0,8 9,1 9,2 6,5 13 17 3/8 9,52 0,8 13,2 13,5 9,7 20 22 1/2 12,70 0,8 16,6 16,0 12,9 23 26 5/8 15,88 1,0 19,7 19,0 16,0 25 29
– 8 –
width
(mm)
Table 2-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
ABCD
Dimension (mm)
1/4 6,35 0,8 9,0 9,2 6,5 13 17 3/8 9,52 0,8 13,0 13,5 9,7 20 22 1/2 12,70 0,8 16,2 16,0 12,9 20 24 5/8 15,88 1,0 19,7 19,0 16,0 23 27 3/4 19,05 1,0 23,3 24,0 19,2 34 36
46˚
~
45˚
B A
43˚
~
45˚
D
C
Flare nut
width
(mm)
Fig. 2-2-2 Relations between flare nut and flare seal surface
(2) Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions
do not have any scar or dust, etc.
b) Correctly align the processed flare surface
with the union axis.
c) Tighten the flare with designated torque by
means of a torque wrench. The tightening torque for R410A is the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
Table 2-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
1/4 6,35 14 to 18 (140 to 180) 16 (160), 18 (180)
Note:
When applying oil to the flare surface, be sure to use oil designated by the manufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
N•m (kgf•cm)
When it is strong, the flare nut may cr ack and may be made non-removable. When choosing the tightening torque, comply with values designated by manufacturers. Table 2-2-7 shows reference values.
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
3/8 9,52 33 to 42 (330 to 420) 42 (420) 1/2 12,70 50 to 62 (500 to 620) 55 (550) 5/8 15,88 63 to 77 (630 to 770) 65 (650)
– 9 –
2-3. Tools
2-3-1. Required T ools
The service port diameter of pack ed valv e of the outdoor unit in the air conditioner using R410A is changed to pre vent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12,7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as gener ation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used f or conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
R410A air conditioner
installation
No. Used tool
Flare tool
Copper pipe gauge for
adjusting projection
margin Torque wrench
(For Ø12,7)
Gauge manifold Charge hose
Vacuum pump adapter
Electronic balance for
refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary .
(Note 2) Charging cylinder for R410A is being currently developed.
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refriger­ant charge, run check, etc.
Vacuum evacuating Refrigerant charge
Refrigerant charge Gas leakage check Refrigerant charge
Existence of Whether new equipment conventional for R410A equipment can
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
be used
(Note 1)
*
(Note 1)
*
X X
X X
X X X
Conventional air
conditioner installation
Whether new equip­ment can be used with conventional refriger­ant
¡
(Note 1)
*
X X
¡ ¡
X
¡
X
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the f o llowing equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (For Ø6,35) (3) Pipe cutter
Also prepare the following equipments for other installation method and run check.
(1) Clamp meter (2) Thermometer
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench
(3) Insulation resistance tester (4) Electroscope
(9) Hole core drill (Ø65) (10) Hexagon wrench
(Opposite side 5mm)
(11) Tape measure (12) Metal saw
– 10 –
2-4. Recharging of Refrigerant
When it is necessary to recharge refriger ant, charge the specified amount of new refrigerant according to the following steps .
Recover the refrigerant, and check no refrigerant remains in the equipment.
Connect the charge hose to packed valve service port at the outdoor units gas side.
When the compound gauge’s pointer has indicated –0,1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Connect the charge hose of the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
Nev er charge refrigerant exceeding the specified amount.
If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
Do not carry out additional charging.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(For refrigerant charging, see the figure below.)
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
(INDOOR unit)
Refrigerant cylinder
(With siphon pipe)
Check valve
Open/Close valve
for charging
Electronic balance for refrigerant charging
Fig. 2-4-1 Configuration of refrigerant charging
(Liquid side)
(Gas side)
– 11 –
(OUTDOOR unit)
Opened
Closed
Service port
Be sure to make setting so that liquid can be charged.
When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ] [ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas , the compo­sition of the charged refrigerant changes and the characteristics of the equipment varies.
2-5. Brazing of Pipes
2-5-1. Materials for Brazing
(1) Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expen­sive though it excels in solderability.
(2) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
(3) Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
Fig. 2-4-2
Electronic
balance
Siphon
Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound water solution, which may cause a gas leak­age. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
When performing brazing again at time of
servicing, use the same type of brazing filler.
2-5-2. Flux
(1) Reason why flux is necessary
By removing the oxide film and any foreign matter on the metal surface, it assists the flo w of brazing filler.
In the brazing process, it prevents the metal surface from being oxidized.
By reducing the brazing fillers surface tension, the brazing filler adheres better to the treated metal.
– 12 –
(2) Characteristics required for flux
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature range, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
(3) Types of flux
Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing temperature is higher than 800°C.
Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased oxide film removing capability due to the addition of compounds such as potassium fluoride, potassium chlo­ride and sodium fluoride to the borax-boric acid compound.
(4) Piping materials for brazing and used braz-
ing filler/flux
2-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
(1) Brazing method to prevent oxidation
Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder. Use a copper pipe to direct the piping
material, and attach a flow-meter to the cylinder.
Apply a seal onto the clearance between the
piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
When the Nitrogen gas is flowing, be sure to
keep the piping end open. Adjust the flow rate of Nitrogen gas so that it
is lower than 0,05 m3/Hr or 0,02 MPa (0,2kgf/ cm2) by means of the reducing valve.
After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
Remove the flux completely after brazing.
Piping
material
Copper - Copper
Copper - Iron
Iron - Iron
Do not enter flux into the refrigeration cycle.
When chlorine contained in the flux remains
within the pipe, the lubricating oil deterio­rates. Therefore, use a flux which does not contain chlorine.
When adding water to the flux, use water
which does not contain chlorine (e.g. distilled water or ion-exchange water).
Remove the flux after brazing.
Used brazing Used
filler flux
Phosphor copper Do not use
Silver Paste flux Silver Vapor flux
– 13 –
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Nitrogen gas
Rubber plug
Fig. 2-5-1 Pre vention of oxidation during brazing
3-1. Indoor Unit
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;;
;;;;;;
;;;;;;
;;;;;;
;;;;;;
;;;;;;
;;;;;;
;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
;;;;;;;;;;;;;;;;;
RAS-10YKV-E, RAS-13YKV-E
3. CONSTRUCTION VIEWS
Air inlet
265
Air outlet
Air filter
790
Heat exchanger
50 94
790
Hanger
232 326 232
47
Back body
Knock out system
Front panel
189
47
50
10
External length reference
Hanger
46
26
265
178,5
37
3,5
321
Connecting pipe (0,39m)
(Flare ø9,52)
65965,5
Hanger
Drain hose (0,54m)
Connecting pipe (0,49m)
(Flare ø6,35)
65,5 450 344 326
Minimum distance
2,5
to ceiling
66 or more
Minimum distance
17 20
to wall
20 20
120 or more 120 or more
37
Hanger
60,5
126269319
10,5
76
Hanger
Installation plate outline
Center line
790
47
50
10
Knock out system
Hanger
For stud bolt (ø8~ø10)
For stud bolt (ø6)
Minimum distance to wall
Wireless remote controller
40,5
55
136
16
– 14 –
3-2. Outdoor Unit
RAS-10YAV-E RAS-13YAV-E
310
A leg part
296
270
600
Ø25 drain hole
115
76
90
50
Ø11 x 17U-shape hole (For Ø8-Ø10 anchor bolt)
Hanger
(ø6 hole pitch)
(Anchor bolt long hole pitch)
B leg part
Ø4,5 embossing (Ø4STS used) (For sunshade roof attaching)
14749,5
21
540
548
8
Fan guard
16
115,5
780 61
8-Ø6 hole (For fixing outdoor unit)
Ø11 x 17 long hole
(For Ø8-Ø10 anchor bolt)
Valve cover
Charging port
Earth terminal
157
322
59
21
54
Z
Connecting pipe port
(Pipe dia.Ø6,35)
Connecting pipe port
(Pipe dia.Ø9,52)
4 x Ø11 x 17U-shape hole (For Ø8-Ø10 anchor bolt)
Intake
100 or
C
310
more
200 or more
Mounting dimensions of anchor bolt
600
50 or
more
D
Outlet
B
Intake
Outside line of product
4 x Ø11 × 17 long hole (For Ø8-Ø10 anchor bolt)
Z
view
A
250 or more
(Minimum distance from wall)
Detailed A leg part
50 36
11
310
296
R5,5
310
296
11
36 50
Detailed B leg part
600
2-Ø6 hole
2-Ø6 hole
600
R15
Outside line of product
Outside line of product
R15
R5,5
– 15 –
4-1. Indoor Unit
RAS-10YKV-E, RAS-13YKV-E
BLK
P04
SG01 DSA
T6,3A 250V
INDOOR
TERMINAL
BLOCK
2
BLK
1 2 3
WHI RED
CN30
4. WIRING DIAGRAM
R109
VARISTOR
F01 FUSE
3
J04
R21
LOUVER
MOTOR
R116
BLU
PNK
YEL
6 5 4 3 2 1 6 5 4 3 2 1
CN07
IC04
L01
C15
R01
C01
MAIN P.C. BOARD
(MCC-772)
ORN
RED
BRW
DB01
C02
FAN MOTOR
DC MOTOR
4 3 2
5
4
3 211
5
CN10
TO1
C06
65
DC35V
DC12V
DC7V
DC0V
IC02
OUTDOOR
UNIT
Check items
OPERATION indicator
Terminal block
Fuse 6,3A
DC 5V
DC 12V
DC 35V
GRN & YEL
INDOOR
UNIT
CN23
CN13
1
2
3
4
BLU
BLU
BLU
BLU
1
2
3
1
1
INFRARED RAYS RECEIVE
AND INDICATION PARTS
4
2
3
4
5
BLU
5 5
6
BLU
6 6
4
7
PNK
7 7
8
BLK
8 8
9
WHI
9 9
Table 4-1-1 Simple check points for diagnosing faults
Diagnosis result
Check to see if the OPERATION indicator goes on and off when the main switch or breaker is turned on, or the power cord is plugged in the wall outlet. (Check the primar y and secondary voltage of transformer.)
Check for power supply voltage between Q – R. (Refer to the name plate.) (Check the primary and secondary voltage of transformer.) Check for fluctuate voltage between R – S. (DC 15 to 60V)
Check to determine if the fuse is open. (Check Var istor : R109, R21)
Check for voltage at the pink lead of the infrared rays receive parts. (Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the (Check the transformer and the rated voltage power supply circuit.)
Check for voltage at the CN10 connector side point. (Check the transformer and the rated voltage power supply circuit.)
lead of louver motor.
QS
CN25
CN03
21 21
BLK
BLK
IC
IC01
THERMO SENSOR
(TA)
CN01
21 21
BLK
BLK
HEAT
EXCHANGER
SENSOR
(TC)
COLOR
IDENTIFICATION
BROWNBRW : REDRED : WHITEWHI : YELLOWYEL : BLUEBLU : BLACKBLK : GRAYGRY : PINKPNK : ORANGEORN : GREEN &
GRN
:
&YEL
YELLOW
For detailed diagnostic procedure, refer to the service data. DSA : Surge Absorber
– 16 –
4-2. Outdoor Unit
RAS-10YAV-E, RAS-13YAV-E
TE TD TO TS
BLK
BLK
21
321
21
321
C13
C14C12
ORN P10
G
E A ~
MODULE
CONVERTER
~
DB01
+
BLK
21 21
P.C. BOARD
MCC-808
P09
POWER RELAY
ELECTRONIC
YEL
BU EU BV
EV BW EW
BX
IGBT MODULE
BY
Q200
BLU
BLK
CN601 CN602 CN603CN600
STARTER
P19 P20
+
BZ
P18 P17
GRN
321 321
P22
1
221
REACTOR
GRY
F03 FUSE 15A
REDP21 WHI BLKP23
PNK
YEL
1234455 123
CN301
CT
1
1
2
2
3
3
COMPRESSOR
P.M.V. : Pulse Modulating Valve
COIL FOR 4WA Y VAL VE
FAN MOTOR
FM
RED
WHI
BLK
321
CN300 CN701 CN703 CN500
F04
FUSE
3,15A
321
RELAY
RELAY
321
BLK
321
P06 P01 P02 P03P08 P07
CM
THERMOSTAT FOR COMPRESSOR
P.M.V.
WHI
YEL
ORN
BLU
RED
GRY
6
3
5
1
4
6
3
5
221
4
SURGE
ABSORBER
VARISTOR
COLOR IDENTIFICATION
BLK : BLACK
BLU : BLUE RED : RED GRY : GRAY
PNK : PINK
21 21
POWER SUPPLY
220/240V~
50/60Hz
~ ~ ~
L N
BLK
WHI
F01 FUSE 25A
WHI : WHITE
BRW : BROWN
ORN : ORANGE
YEL : YELLOW
PUR : PURPLE
ORN
P11 P12
P13
P14
To
INDOOR
UNIT
~ ~ ~~
1 2 3
11 22
REACTOR
PUR
– 17 –
g
5. SPECIFICATIONS OF ELECTRICAL PARTS
5-1. Indoor Unit
RAS-10YKV-E, RAS-13YKV-E
No. Parts name Type Specifications
1 Fan motor (for indoor) TICF-35-19-4 DC35V, 19W 2 Thermo. sensor (TA-sensor) ( – ) 10kΩ at 25°C 3 DC-DC transformer (T01) SWT-34 or SWT-46 DC390V, Secondary DC35V, 12V, 7V 4 Microcomputer TMP87PM40AF or TMP87CM40AF
Heat exchanger temp. sensor
5
(TC-sensor) 6 L ine filter (L01) UF-253Y0R7 25mH, AC0,7A 7 Diode (DB01) RBV-406 or D3SBA60 4A, 600V 8 Capacitor (C02) KMH450VNSN100M25B 100µF, 450V 9 Fuse (F01) TSCR6,3A T6,3A, 250V
10 Power supply IC (IC01) MA2830-FJ 4A, 600V 11 Varistor (R21, R109) 15G561K 560V 12 Resistor (R01) ERF-5TK5R6 5,6Ω, 5W 13 Louver motor MP35EA7 Output (Rated) 2W, 10poles, 1phase DC12V
5-2. Outdoor Unit
RAS-10YAV-E, RAS-13YAV-E
( – ) 10kΩ at 25°C
No. Parts name Model name Rating
SC coil
1
(Noise filter)
2 DC-DC transformer SWT-43 3 Reactor CH38Z-K L=10mH, 16A x 2
4 Outside fan motor ICF-140-40-7 DC140V, 40W 5 Fan control relay AJQ1341
Suction temp. sensor
6
(TS sensor)
Dischar
7
(TD sensor)
Outside air temp. sensor
8
(TO sensor)
Heat exchanger temp.
9
sensor (TE sensor)
10 Terminal block (9P) —— 20A, AC250V
12 Electrolytic capacitor LLQ2G501KHUATF, 400LISN500K35F 500µF, DC400V X 3 pieces 13 Transistor module 6MBI25GS-060-01 or 6MBI25GS-060-01A 25A, 600V 14 Compressor DA91A1F-44F 3-phases 4-poles 750W 15 Compressor thermo. US-622KXTMQO-SS OFF: 125 ± 4°C, ON: 90 ± 5° C 16 Converter module MP7003 Diode: 25A, 600V, IGBT: 40A, 600V
L03 SC-15-S06J 15A, 0,6mH L01 SC-20-01J 20A, 150µH
(Inverter attached) 10kΩ (25°C)
e temp. sensor
For protection of switching power source 3,15A, AC250V For protection of transistor module breakage 15A, AC250V11 Fuse For protection of inverter input overcurrent 25A, AC250V
(Inverter attached) 62kΩ (20°C)
(Inverter attached) 10kΩ (25°C)
(Inverter attached) 10kΩ (25°C)
Primary side DC280V, Secondary side 7,5V x 1, 13V x 1, 26,5V x 3, 16V x 1, 15V x 1
Coil DC12V Contact AC125V, 3A
– 18 –
6. REFRIGERANT CYCLE DIAGRAM
6-1. Refrigerant Cycle Diagram
RAS-10YKV-E/RAS-10YAV-E RAS-13YKV-E/RAS-13YAV-E
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port Deoxidized copper pipe
Outer dia. : 9,52mm Thickness : 0,8mm
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6,35mm Thickness : 0,8mm
Sectional shape of heat insulator
T1
Temp. measurement
Allowable height
difference : 10m
Allowable pipe length
Max. : 15m
4 way valve (CHV-0213)
TS
Temp. measurement
T2
Muffler
Muffler
TD
Compressor DA91A1F-44F
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
Split capillary
Ø1,5 x 200
Ø1,5 x 200
TE
Strainer
Pulse modulating valve at liquid side (SEV15RC2)
Refrigerant amount : 0,8kg
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
NOTE :
• The maximum pipe length of this air conditioner is 15 m. The additional charging of refrigerant is unneces­sary because this air conditioner is designed with charge-less specification.
– 19 –
6-2. Operation Data
<Cooling>
Temperature
condition (°C)
Indoor Outdoor
27/19 35/–
Standard
Model name
10YKV-E 0,8 to 1,0 9 to 11 42 to 44 High High 56
13YKV-E 0,8 to 1,0 8 to 10 46 to 48 High High 85
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
Indoor fan
mode
Outdoor fan
mode
Compressor
revolution
<Heating>
Temperature
condition (°C)
Indoor Outdoor
20/– 7/6
Standard
Model name
10YKV-E 3,5 to 3,7 42 to 44 2 to 4 High High 70
13YKV-E 2,5 to 2,7 50 to 52 0 to 3 High High 97
pressure
P (MPa)
Heat exchanger
pipe temp.
T1 (°C) T2 (°C)
Indoor fan
mode
Outdoor fan
mode
Compressor
revolution
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m
(rps)
(rps)
– 20 –
7-1. Indoor Unit
RAS-10YKV-E, RAS-13YKV-E
Heat Exchanger Sensor
Temperature Sensor
Infrared Rays Signal Receiver
7. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
• Louver Control
• 3-minute Delay at Restart for Compressor
Operation
Display
Timer
Display
Infrared
Initializing Circuit
Rays
Clock Frequency
Oscillator Circuit
Power Supply
Remote
Circuit
Controller
Noise Filter
From Outdoor Unit
REMOTE CONTROLLER
• Motor Revolution Control
• Processing (Temperature Processing)
• Timer
• Serial Signal Communication
Louver ON/OFF Signal
Serial Signal Transmitter/Receiver
Serial Signal Communication
Louver Driver
Infrared
Rays
ECONO.
Sign Display
PRE DEF.
Sign Display
Indoor
Fan Motor
Louver
Motor
Remote Controller Operation (START/STOP) Operation Mode Selection
AUTO, COOL, DRY, HEAT
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
– 21 –
RAS-10YAV-E, RAS-13YAV-E
7-2. Outdoor Unit (Inverter Assembly)
– 22 –
For INDOOR UNIT
Discharge
temp. sensor
Outdoor air
temp. sensor
Suction temp.
sensor
Heat exchanger
temp.sensor
220–230–240 V
~ 50/60 Hz
Inddor unit
send/receive
circuit
MICRO-COMPUTER BLOCK DIAGRAM
MCC808 (P.C.B) OUTDOOR UNIT
M.C.U
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
• Signal communication to indoor unit
High Power
factor Correction
circuit
Clock
frequency
16MHz
Rotor position
detect circuit
Rotor position
detect circuit
Over current
detect circuit
Over current
sensor
Gate drive
circuit
Gate drive
circuit
Noise
Filter
Input current
sensor
Driver circuit
of P.M.V.
P.M.V.
Converter
(AC DC)
Relay circuit
4-way
valve
Over current
sensor
Over current
sensor
Inverter
(DC AC)
Inverter
(DC AC)
Outdoor
Fan motor
Compressor
8. OPERATION DESCRIPTION
8-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses DC motor for the indoor fan motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 13 to 120 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit. The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote control­ler, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation command from the indoor unit side, and controls the outdoor fan and the pulse modulating valve. Besides, detecting revolution position of the com­pressor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
(1) Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
• Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor.
• Temperature setting of the indoor heat ex­changer by using heat exchanger sensor (Prevent-freezing control)
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation command signal (Serial signal) to the outdoor unit
• Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
(2) Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor controller, the outdoor unit performs its role.
• Compressor operation
Operations follow ed
control
• Operation control of outdoor fan motor
• P.M.V. control
• Detection of inverter input current and current release operation
• Over-current detection and prevention opera­tion to transistor module (Compressor stop function)
• Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
• Transferring of operation information (Serial signal) from outdoor unit to indoor unit
• Detection of outdoor temperature and opera­tion revolution control
• Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for f our-way valve and outdoor fan)
to judgment of serial
signal from indoor side.
– 23 –
(3) Contents of operation command signal (Serial
signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
• Operation mode set on the remote control
• Compressor revolution command signal defined by indoor temperature and set temperature (Correction along with variation of room temperature and correction of indoor heat exchanger temperature are added.)
• For these two types of signals ( [Operation mode] and [Compressor revolution] ), the outdoor unit controller monitors the input current to the inverter, and performs the followed oper ation within the r ange that current does not exceed the allowable value.
• Temperature of indoor heat exchanger b y indoor heat exchanger sensor (Minimum revolution control)
(4) Contents of operation command signal (Serial
signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation For transferring of these signals, the indoor
unit controller monitors the contents of signals, and judges existence of trouble occurrence .
Contents of judgment are described below .
• Whether distinction of the current operation status meets to the operation command signal
• Whether protective circuit operates When no signal is received from the
outdoor unit controller, it is assumed as a trouble.
8-1-1. Capacity Control
The cooling and heating capacity is varied by changing compressor motor speed. The inverter changes compressor motor speed by changing AC 220–230–240V power to DC once, and controls capacity by changing supply power status to the compressor with transistor module (includes 6 transistors). The outline of the control is as follows: The rev olution position and revolution speed of the motor are detected by detecting winding electromo­tive force of the compressor motor under operation, and the revolution speed is changed so that the motor drives based upon revolution speed of the operation command by changing timing (current transfer timing) to e xchange inverter output voltage and supply power winding.
Detection of the revolution position for controlling is performed 12 times per 1 rev olution of compressor. The range of supply power frequency to the com­pressor differs according to the operation status (COOL, HEAT, DRY).
Table 8-1-1 Compressor rev olution range
Operation
mode
COOL
HEAT
Model name
10YKV-E 13 to 74 13YKV-E 13 to 94 10YKV-E 16 to 110 13YKV-E 16 to 114
Compressor
revolution (rps)
8-1-2. Current Release Control
The outdoor main circuit control section (Inverter assembly) detects the input current to the outdoor unit. If the current value with compressor motor speed instructed from indoor side exceeds the specified value, the outdoor main circuit control section controls compressor motor speed by reduc­ing motor speed so that value becomes closest to the command within the limited value.
8-1-3. Power Factor Improvement Control
Power factor improvement control is performed mainly aiming to reduce the current on much power consumption of cooling/heating operation. Control­ling starts from the time when input power has reached at a certain point. To be concrete, IGBT of the power factor improvement circuit is used, and the power factor is impro ved by keeping IGBT on for an arbitrary period to widen electro-angle of the input current.
– 24 –
8-1-4. Prevent-Freezing Control
8-1-6. Louver Control
The indoor heat exchanger sensor detects refriger­ant vapor temperature in COOL/DRY operation. If the temperature is below the specified v alue, compressor motor speed is reduced so that opera­tion is performed in temperature below the specified value to prevent-freezing of indoor heat exchanger.
8-1-5. P. M. V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is varied for the optimum temperature . Controlling each unit separately by two P.M.V. corresponds to difference of pipe length, fan speed, and unit tem­perature.
After the power has been turned on, when a serial operation signal is received from indoor at the first time, or when PMV alarm is detected and the equipment is reactivated, move the valve once until it hits on the stopper for positioning of the valve. In this case, ticktack sound may be heard.
(1) Vertical air flow louvers
Positions of vertical air flow louvers are auto­matically controlled according to the operation status (AUTO, COOL, DRY, HEAT). Besides, positions of vertical air flow louvers can be arbitrarily set by pressing the [SET] button. The louver position which has been set by the [SET] button is stored in microcomputer, and the louver is automatically set at the stored position in the next operation.
(2) Swing
If the [AUTO] button is pressed during running operation, vertical air flow louvers start swinging. When the [AUTO] button is pressed again, swinging stops.
8-1-7. Indoor Fan Control (DC Fan Motor)
The indoor fan is operated by motor speed non-step variable DC drive system motor. For flow rate, motor speed is controlled manually in three steps (LOW, MED, HIGH), and with the unit of 10 rpm from upper limit to lower limit in AUTO mode as described in Table 8-1-2. It is not selected by relay, so selecting sound does not generate.
Table 8-1-2
Operation
mode
DRY 820 320 820 320
Fan mode
H 1120 480 1210 530 M 980 400 1020 420COOL
L 850 330 850 330
H 1200 520 1270 560 M 1070 450 1100 470HEAT
L 930 380 930 380
Motor speed
RAS-10YKV-E RAS-13YKV-E
(rpm)
Air flow rate
(m³/h)
Motor speed
(rpm)
Air flow rate
25
(m³/h)
Loading...
+ 57 hidden pages