Toshiba RAS-10UA-ES3, RAS-10UAH-AS3, RAS-13UA-ES3, RAS-13UKHP-ES3, RAS-13UA-AS3 SERVICE MANUAL

...
Page 1
SERVICE MANUAL
AIR CONDITIONER
RAS-13UKHP-ES3 / RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3
RAS-10UKHP-ES3 / RAS-10UAH-ES3
FILE NO. SVM-04001-(2)
SPLIT WALL TYPE
RAS-10UKHP-AS3 / RAS-10UAH-AS3
RAS-13UKP-ES3 / RAS-13UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3
RAS-10UKP-ES3 / RAS-10UA-ES3
RAS-10UKP-AS3 / RAS-10UA-AS3
RAS-07UKP-ES3 / RAS-07UA-ES3
Page 2
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit
3. WIRING DIAGRAM
3-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3
3-2 RAS-10UKHP-ES3 / RAS-10UAH-ES3
RAS-10UKHP-AS3 / RAS-10UAH-AS3
3-3 RAS-13UKP-ES3 / RAS-13UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3
3-4 RAS-10UKP-ES3 / RAS-10UA-ES3
RAS-10UKP-AS3 / RAS-10UA-AS3 RAS-07UKP-ES3 / RAS-07UA-ES3
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit (RAS-13UKHP-ES3, RAS-13UKHP-AS3,
RAS-10UKHP-ES3, RAS-10UKHP-AS3)
4-2 Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3)
4-3 Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3) 4-4 Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3) 4-5 Indoor Unit (RAS-13UKP-ES3, RAS-13UKP-AS3, RAS-10UKP-ES3,
RAS-10UKP-AS3, RAS-07UKP-ES3)
4-6 Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3)
Outdoor Unit (RAS-07UA-ES3)4-7
FILE NO. SVM-04001
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3
5-2 RAS-10UKHP-ES3 / RAS-10UAH-ES3
RAS-10UKHP-AS3 / RAS-10UAH-AS3
5-3 RAS-13UKP-ES3 / RAS-13UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3
5-4 RAS-10UKP-ES3 / RAS-10UA-ES3
RAS-10UKP-AS3 / RAS-10UA-AS3
5-5
RAS-07UKP-ES3 / RAS-07UA-ES3
6. CONTROL BLOCK DIAGRAM
6-1 RAS-13UKHP-ES3 / RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3 RAS-10UKHP-ES3 / RAS-10UAH-ES3 RAS-10UKHP-AS3 / RAS-10UAH-AS3
6-2 RAS-13UKP-ES3 / RAS-13UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3 RAS-10UKP-ES3 / RAS-10UA-ES3 RAS-10UKP-AS3 / RAS-10UA-AS3
RAS-07UKP-ES3 / RAS-07UA-ES3
1
Page 3
7. OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control
7-6 Defrost Operation 7-7 Current Limit Control 7-8 Auto Restart Function
7-9 Filter Check Lamp 7-10 Self-Cleaning function
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch 8-7 Others
FILE NO. SVM-04001-(1)
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 Troubleshooting Flowcharts 9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board)
10. PARTS REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3) 11-4 Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3) 11-5 Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3) 11-6 Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3) 11-7
Outdoor Unit (RAS-07UA-ES3)
• This air conditioner is charged with
HFC (R410A) that doesn't deplete the Ozone layer.
• This air conditioner requires special
installation for the refrigerant R410A.
2
Page 4
FILE NO. SVM-04001

1. SPECIFICATIONS

MODEL RAS-13UKHP-ES3, AS3 RAS-13UKP-ES3, AS3
RAS-13UAH-ES3, AS3 RAS-13UA-ES3, AS3
ITEM Cooling Heating Cooling
Capacity
Power source V 220 240
Power consumption kW 1.10 1.12 1.14 1.18 1.13 1.17
Power factor % 98 97 97 96 98 97
Running Indoor A 0.15
current Outdoor A 4.95 4.65 5.20 4.95 5.10 4.90
Starting current A 27 28
Moisture removal lit/h 2.0
Noise
Refrigerant
Refrigerant control
Interconnection
pipe
INDOOR UNIT RAS-13UKHP-ES3, AS3 RAS-13UKP-ES3, AS3
Dimensions Width mm 790
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
Air volume Medium fan m3/h 520 550 520
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-13UAH-ES3, AS3 RAS-13UA-ES3, AS3
Dimensions Width mm 780
Net weight kg 39 37
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 2120 2200 2120 2200 2030 2150
Fan motor output W
Compressor
Safety device Fuse, Overload relay
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 10 ~ 24 15 ~ 43
Indoor (H/M/L) dB 41/35/31
Outdoor (220-240V) dB 49 51 49 51 49 50
Name of refrigerant
Rated amount
Gas side size
Connection type Flare connection
Liquid side size mm ∅ 6.35
Connection type Flare connection
Maximum length (One way)
Maximum height difference
Height mm 275
Depth mm 208
High fan m3/h 630 650 630
Low fan m3/h 430 490 430
Height mm 550
Depth mm 270
Model PA150X2T-4FM1
Output W 1100
kW 3.60 3.60 4.20 4.26 3.75 3.75
Phase 1
Hz 50
kg
mm
m
m
220V 240V 220V 240V 220V 240V
R410A
0.95
Capillary tube
12.7
1
15*
6
42
30
3
Page 5
FILE NO. SVM-04001
MODEL RAS-10UKHP-ES3, AS3 RAS-10UKP-ES3, AS3
RAS-10UAH-ES3, AS3 RAS-10UA-ES3, AS3
ITEM Cooling Heating Cooling
Capacity
kW 2.70 2.70 2.90 2.96 2.70 2.70
Phase 1
Power source V 220 240
Hz 50
Power consumption kW 0.82 0.84 0.78 0.82 0.82 0.84
Power factor % 98 97 97 96 98 97
Running Indoor A 0.15
current Outdoor A 3.65 3.45 3.50 3.40 3.80 3.60
Starting current A 18
Moisture removal lit/h 1.2
Noise
Refrigerant
Indoor (H/M/L) dB 39/33/26
Outdoor (220-240V) dB 47 49 47 49 46 47
Name of refrigerant R410A
Rated amount kg 0.70 0.65
Refrigerant control Capillary tube
Gas side size mm ∅ 9.52
Connection type Flare connection
Liquid side size mm ∅ 6.35
Interconnection
pipe
Connection type Flare connection
Maximum length (One way)
Maximum height difference
m 10*
m 5
INDOOR UNIT RAS-10UKHP-ES3, AS3 RAS-10UKP-ES3, AS3
Height mm 275
Dimensions Width mm 790
Depth mm 208
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m
Air volume Medium fan m
Low fan m
3
/h 570 610 610
3
/h 460 520 460
3
/h 340 400 340
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-10UAH-ES3, AS3 RAS-10UA-ES3, AS3
Height mm 550
Dimensions Width mm 780
Depth mm 270
Net weight kg 35 30
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m3/h 2030 2150 2030 2150 1740 1850
Fan motor output W 30 20
Compressor
Model PA108X1T-4FZ1
Output W 750
Safety device Fuse, Overload relay
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43 −10 ~ 24 15 ~ 43
220V 240V 220V 240V 220V 240V
1
4
Page 6
FILE NO. SVM-04001
MODEL
RAS-07UKP-ES3
RAS-07UA-ES3
ITEM
Capacity
220V
kW 2.15 2.18
Phase 1
Cooling
240V
Power source V 220 240
Hz
50
Power consumption kW 0.66 0.68
Power factor % 97 90
Running Indoor A 0.15
current Outdoor A 3.10 3.15
Starting current A 12
Moisture removal lit/h 0.8
Noise
Refrigerant
Indoor (H/M/L) dB 38/32/26
Outdoor (220-240V) dB 44 45
Name of refrigerant R410A
Rated amount kg
0.65
Refrigerant control Capillary tube
Gas side size mm ∅9.52
Connection type Flare connection
Liquid side size mm 6.35
Interconnection
pipe
INDOOR UNIT
Connection type Flare connection
Maximum length (One way)
Maximum height difference
m 10*
m
m
1
5
RAS-07UKP-ES3
Height mm 275
Dimensions Width mm 790
Depth mm 208
Net weight kg 10
Evaporator type Finned tube
Indoor fan type Cross flow fan
High fan m3/h
Air volume Medium fan m3/h
570
460
Low fan m3/h 340
Fan motor output W 20
Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-07UA-ES3
Height mm 530
Dimensions Width mm 660
Depth mm 240
Net weight kg
27
Condenser type Finned tube
Outdoor fan type Propeller fan
Airflow volume m
Fan motor output W
Compressor
Model PA79X1T-4FZ5
Output W 605
3
/h 1420 1520
30
Safety device Fuse, Overload relay
Louver type Automatic louver
Usable outdoor temperature range °C 15 ~ 43
5
Page 7
Note : 1
Capacity is based on the following temperature conditions.
FILE NO. SVM-04001
Condition
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
Charge refrigerant according to the table below.
RAS-13UKHP-ES3 / RAS-13UAH-ES3 RAS-10UKHP-ES3 / RAS-10UAH-ES3
Refrigerant
*1 No need to charge
extra refrigerant
RAS-13UKHP-AS3 / RAS-13UAH-AS3 RAS-10UKHP-AS3 / RAS-10UAH-AS3
RAS-13UKP-ES3 / RAS-13UA-ES3 RAS-10UKP-ES3 / RAS-10UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3 RAS-10UKP-AS3 / RAS-10UA-AS3
(DB) 27°C 20°C
(WB) 19°C 15°C
(DB) 35°C 7°C
(WB) 24°C 6°C
15m or less 10m or less
JIS C9612-1994
Cooling Heating
RAS-07UKP-ES3 / RAS-07UA-ES3
6
Page 8
2-1. Indoor Unit
FILE NO. SVM-04001

2. CONSTRUCTION VIEWS

Front panel
Back body
660
Knock out system
Air inlet
Air filter
790
Heat exchanger
275
Air outlet
120 80
590
Hanger
64
53
48
208
48
Knock out system
660
Drain hose (0.54m)
Hanger
45
Minimum distance to ceiling
275
1
7
0
o
r m
o
re
320
620
235 235
215 215
re
Minimum distance to ceiling
o r m
o 5 6
Hanger
7
Connecting pipe (0.43m) (Flare 6.35)
Connecting pipe (0.33m)
(For 13 series ; Flare 12.7
For 07, 10 series ; Flare 9.52)
For stud bolt (8~10)
Hanger
For stud bolt (6)
Minimum distance to ceiling
1
7
Hanger
150150 160160
9090
Installation plate outline
Center line
26
4519040
0
o
r m
o
re
32
57 18
160
Wireless remote control
Page 9
FILE NO. SVM-04001
2-2. Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3, RAS-10UAH-ES3, RAS-10UAH-AS3,
RAS-13UA-ES3, RAS-13UA-AS3, RAS-10UA-ES3, RAS-10UA-AS3)
A
A Detail Drawing (Back Leg)
600
52
310
36
302
270
6 Hole
R15
R5.5
32.5
310
302
30 Drain outlet
436
530
265
FAN GUARD
115 125
2-∅11x14 Hole (For ∅8-∅10 anchor bolt)
600 90
780 62
102
11x14 Hole
B
B Detail Drawing (Front Leg)
310
302
6 Hole
36
52
310
330
R15
COVER PV
Z
Electrical part cover
Installation dimension
B or more
325
100 or more
Z View
Air outlet
600
Air inlet
A or more
600 or more
120
5
75
4
Service port
13 Series
A 600 mm 400 mm
B 100 mm 45 mm
4x∅11 Long holes (For∅ 8-∅ 10 anchor bolt)
10 Series
Liquid side (Flare ∅6.35)
Gas side (Flare ∅9.52) 10 Series
Gas side (Flare ∅12.7) 13 Series
8
Page 10
Outdoor Unit (RAS-07UA-ES3)
A
A
Detail Drawing (Back Leg)
6 Hole
265
273.5
50
36
660
R 15
R 5.5
530
273.5
420
59.5
25Drain outlet
Fan guard
97
2-
11x14 hole
∅8-∅
(for
10 anchor bolt)
B
FILE NO. SVM-04001
B
Detail Drawing (Front Leg)
265
273.5
6 Hole
11x14 Hole
36 50
R 15
660
Cover PV
Z
242
Installation dimension
100 or more
325
100 or more
Air outlet
500 660
View
Z
600
Air inlet
600 or more
56
(11)
126
48
297
54
97.5
Service port
600 or more
11x14 Long holes (for 8-∅10 anchor bolt)
4x
(12.5)273.5 (pitch)
Liquid side (Flare
Gas side (Flare
6.35)
9.52)
9
Page 11

3. WIRING DIAGRAM

3-1. RAS-13UKHP-ES3 / RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3
73°C
THERMAL FUSE
PNK
PNK
1
2
1
2
CN04
Power Cord
GRN&YEL
POWER SUPPLY
SINGLE PHASE
220-240V~ , 50 Hz
BLK
GRN&YEL
WHI
P04
BRW
BLU
CN27
1
3
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
SG01
DSA
BLK
T02 C.T
VARISTOR
RY03
BLK
R22
BLK
1
(L)2(N)
1
T6.3A 250V
3
4
RY04
WHI
2
F01
RY01
CR01
CR02
BLU
RED
3
3
C15
BLU
R21 VARISTOR
L01
1
2
1
233
YEL
GRY
BRW
BLU
GRN&YEL
4
4
YEL
YEL
YEL
YEL
3
2 1
5
4
3
2 1
5
4
CN07
C01 R01
CR03
C58
150
5 5
BLK
24
1
24
1
CN11
AC FAN MOTOR
INDOOR
OUTDOOR
CHASSIS
CN25
WHI
MAIN P.C. BOARD
MCC-862
R47
R46
D38
R48
3
1
CN10
3
1
WHI
RED
6
35
6
35
FILE NO. SVM-04001
INFRARED RAYS RECEIVE AND INDICATION PARTS
3
1
4 5 6 7 8 9
2
3
1
4 5 6 7 8 9
2
BLU5BLU6BLU7BLU8BLU9BLU10BLU11BLU
3
1 1
DB01
IC03
2
3
CN13
DC 12V DC 5V
4
C02
112
BLK
5
2
BLK
THERMO SENSOR
(TA)
10 11 10 11
BLU2BLU4WHI
6 7 8 9
10 11
POWER SUPPLY CIRCUIT
112
BLK
HEAT
EXCHANGER
SENSOR
(TC)
2
BLK
CN01CN03
COMPRESSOR
PNK
WHI
RED
SOLENOID COIL
CAPACITOR
RED
RED
CAPACITOR
FAN MOTOR
10
WHI
BLK
Page 12
3-2. RAS-10UKHP-ES3 / RAS-10UAH-ES3
RAS-10UKHP-AS3 / RAS-10UAH-AS3
73°C
THERMAL FUSE
PNK
PNK
1
2
1
2
CN04
GRN&YEL
Power Cord
GRN&YEL
POWER SUPPLY
SINGLE PHASE
220-240V~ , 50 Hz
BLK
WHI
P04
BRW BLU
CN27
1
3
INDOOR TERMINAL BLOCK
OUTDOOR TERMINAL BLOCK
SG01
DSA
BLK
T02 C.T
R22
VARISTOR
T6.3A 250V
3
4
RY03
BLK
RY04
BLK
WHI
2
1 4
(L)2(N)
1
F01
RY01
CR01
CR02
BLK
RED
3
3
C15
BLK
R21 VARISTOR
L01
1
2
3
1
2
3
GRY
BRW
YEL
BLU
GRN&YEL
4
Louver motor
YEL
YEL
YEL
YEL
3
2 1
5
4
3
2 1
5
4
CN07
C01 R01
CR03
C58
150
5 5
BLK
24
1
2466
1
CN11
AC FAN MOTOR
INDOOR
OUTDOOR
CHASSIS
CN25
WHI
MAIN P.C. BOARD
MCC-862
R47
R46
D38
R48
3
1
CN10
3
1
WHI
RED
35 35
FILE NO. SVM-04001
INFRARED RAYS RECEIVE AND INDICATION PARTS
3
1
4 5 6 7 8 9
2
3
1
4 5 6 7 8 9
2
BLU5BLU6BLU7BLU8BLU9BLU10BLU11BLU
3
1 1
2
DB01
3
CN13
4
C02
5
DC 12V DC 5V
IC03
112
2
BLK
BLK
THERMO SENSOR
(TA)
10 11 10 11
BLU2BLU4WHI
6 7 8 9
10 11
POWER SUPPLY CIRCUIT
HEAT
EXCHANGER
SENSOR
(TC)
112
BLK
2
BLK
CN01CN03
COMPRESSOR
PNK
WHI
RED
SOLENOID COIL
RED
RED
CAPACITOR
CAPACITOR
FAN MOTOR
11
WHI BLK
Page 13
3-3. RAS-13UKP-ES3 / RAS-13UA-ES3, RAS-13UKP-AS3 / RAS-13UA-AS3
RAS-10UKP-ES3 / RAS-10UA-ES3, RAS-10UKP-AS3 / RAS-10UA-AS3
RAS-07UKP-ES3 / RAS-07UA-ES3, RAS-07UKP-AS3 / RAS-07UA-AS3
Infrared rays receiver and indication parts.
Heat Exchanger Sensor (TC)
Thermo Sensor (TA)
GRN&YEL
Single Phase
BLU (N) BRW (L)
Power Cord
220-240V 50Hz
CN01
121
CN03
121
CN25
CN14
2
2
1 1
BLU
1 1
2
BLU
2
43 432
BLU
BLU
432 43
F01
T6.3 A
250 VAC
8
6
7
5 5
BLU
5
R21 R22
C15
6
BLU
3
6 6587
9 11
8
7
9
BLU
BLU
BLU
8
7
9 9
RY01
2
2
3
L01
10 10
11
BLU
WHI
10
11
10
BLK
11
P04
4
RED
TRANS (T T-10)
WHI
113
CN05 CN06
3
DB50
C50
+
BLU
113
Regulator
circuit
SG01
DSA
IC03
1
C01
4
R47
R46
R48
FILE NO. SVM-04001
GRY
3
MCC-920
DC 12 V
DC 5 V
CR03
D38
C58
CN07 1 2 3 4 5
CN11
1 2 3
CN10
5
3
1
WHI
1
YEL YEL YEL YEL
1
2
2
3
3
4
4
5
5
1 2 3 4 5
Louver motor
YEL
1
GRY
2
BRW
3
WHI
5
BLK
3
RED
1
1 2 3 4 5 6 6
150 C 1 2 3 4 5
Indoor FAN motor
CN31
INDOOR
TERMINAL
BLK
1
BLOCK
OUTDOOR TERMINAL
BLOCK
BLK BLK RED
1(L) 2(N)
FAN MOTOR
WHI
2
RED
WHI
COMPRESSOR
GRN&YEL
CHASSIS
CAPACITOR
RED
PNK
WHI
INDOOR
OUTDOOR
CAPACITOR
CN04
PNK
112
2
PNK
TEMP FUSE
73 C
12
Page 14
FILE NO. SVM-04001

4. SPECIFICATION OF ELECTRICAL PARTS

4-1. Indoor Unit (RAS-13UKHP-ES3, RAS-13UKHP-AS3, RAS-10UKHP-ES3,
RAS-10UKHP-AS3)
No. Parts name Type Specifications
1 Fan motor (for indoor) SKF-220-20-4A-1 mo fuse
2 Thermo sensor (T
3 Switching transformer (T01) SWT-47
4 Microcontroller unit (IC30) TMP87CM40AN
5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270
7 Bridge rectifier (DB01) D3SBA60 4A, 600V
8 Capacitor (C02) KMH400VSSN47M22S 47µF, 400V
9 Fuse (F01) TSCR6.3A T6.3A, 250VAC
10 Varistor (R21, R22) 15G561K 560V
11 Resistor (R01) RF-2TK5R6 5.6, 2W
12 Louver motor MP24Z 12VDC
13 Relay (Comp., RY01) DI12D1 Rating 20A/AC250V, 12VDC
14 Relay (Fan, RY03) G5N-1A Rating 3A/AC250V, 12VDC
15 Relay (Solenoide, RY04) G5N-1A Rating 3A/AC250V, 12VDC
A-sensor) 10k at 25°C
AC Motor with 150°C ther
10k at 25°C
27mH, 600mA
ΩΩ
4-2. Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3)
No. Parts name Type Specifications
Output (Rated) 1100W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PA150X2T-4FM1 Winding resistance (Ω) C-R C-S
(at 20°C) 2.49 3.95
Output (Rated) 42W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) HF-240-42A Winding resistance () Red-Black White-Black
(at 20°C) 176.2 290.5
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5 (for 4-way valve) VHV-01AJ503C1 AC 220 240V, 50Hz
(for Heat pump model)
DS451155BPQC AC 450V, 1.5µF
DS371306CPNB AC 370V, 30µF
13
Page 15
FILE NO. SVM-04001
4-3. Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3)
No. Parts name Type Specifications
Output (Rated) 1100W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PA150X2T-4FM1 Winding resistance (Ω) C-R C-S
(at 20°C) 2.49 3.95
Output (Rated) 30W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) HF-240-30B Winding resistance (Ω) Red-Black White-Black
(at 20°C) 245 388.3
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
DS451155BPQC AC 450V, 1.5µF
DS371306CPNB AC 370V, 30µF
4-4. Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3)
No. Parts name Type Specifications
Output (Rated) 750W , 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PA108X1T-4FZ1 Winding resistance (Ω) C-R C-S
(at 20°C) 3.89 4.51
Output (Rated) 30W, 6poles, 1 phase, 220 240V, 50Hz
2 Fan motor (for outdoor) HF-240-30B Winding resistance (Ω) Red-Black White-Black
(at 20°C) 245 388.3
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve)
DS451155BPQC AC 450V, 1.5µF
DS371256CPNB AC 370V, 25µF
SQ-373
AC 220 240V
14
Page 16
FILE NO. SVM-04001
4-5. Indoor Unit (RAS-13UKP-ES3, RAS-13UKP-AS3, RAS-10UKP-ES3,
RAS-10UKP-AS3, RAS-07UKP-ES3)
No. Parts name Type Specifications
1 Fan motor (for indoor)
2 Thermo sensor (TA-sensor) 10k at 25°C
3 Switching transformer TT-10
4 Microcontroller unit (IC30) TMP87CM40AN
5 Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-06270 27mH, 600mA
7 Bridge rectifier (DB50) KBP06M/51 1.5A, 600V
8 Capacitor (C50) PF1E222MNN1625 2200µF, 25V
9 Fuse (F01) BET6.3A T6.3A, 250VAC
10 Varistor (R21, R22) 15G561K320 560V
Louver motor
11
Relay (Comp., RY01) DI1U
12
SKF-220-20-4A-1
MP24Z
AC Motor with 150°C thermo fuse
10k at 25°C
12VDC
Rating 25A/AC250V, 3~48VDC
4-6. Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3)
No. Parts name Type Specifications
Output (Rated) 750W, 2poles, 1 phase, 220 240V, 50Hz
1 Compressor PA108X1T-4FZ1 Winding resistance (Ω) C-R C-S
(at 20°C) 3.89 4.51
Output (Rated) 20W, 6poles, 1 phase, 220 240V, 50Hz
Winding resistance (Ω) Red-Black White-Black
(at 20°C) 387.3 or 235.2 466.2 or 260.1
2 Fan motor (for outdoor)
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
HF-240-20B or
SKF-240-20B
DS451155BPQC AC 450V, 1.5µF
DS371256CPNB AC 370V, 25µF
15
Page 17
4-7. Outdoor Unit (RAS-07UA-ES3)
FILE NO. SVM-04001
No.
1
2 Fan motor (for outdoor) k White-Black
3
4
Parts name Type
Compressor
Running capacitor
(for fan motor)
Running capacitor
(for compressor)
Specifications
Output (Rated) 605W, 2poles, 1 phase
PA79X1T-4FZ5
HF-240-30B Winding resistance (Ω) Red-Blac
DS451155BPQC
DS371156CPNB
Winding resistance (Ω)
(at 20°C)
Output (Rated) 30W, 6poles, 1 phase
(at 20°C)
AC 450V, 1.5µF
AC 370V, 15µF
, 220 240V, 50Hz
C-R C-S
4.80 8.37
, 220 240V, 50Hz
245 388
– 16
Page 18

5. REFRIGERATION CYCLE DIAGRAM

5-1. RAS-13UKHP-ES3/ RAS-13UAH-ES3
RAS-13UKHP-AS3 / RAS-13UAH-AS3
FILE NO. SVM-04001
Indoor unit
Cooling
0.39m (Connecting pipe) 12.7
O.D.:12.7mm O.D.:6.35mm
Cooling
Heating
Heating
P
Packed valve
(12.7)
Heating
4-way valve
Cooling
Compressor
PA150X2T-4FM1
Accumulator
Evaporator
Cross flow fan
T1
Capillary tube
1.5x1100l
0.49m
(Connecting pipe)
6.35
Packed valve
(6.35)
Capillary tube
1.0x600l
Condenser
Refrigerant
R410A : 0.95 kg.
Cooling Heating
Propeller fan Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standar d
pressure
(MPaG)
P
Surface temp. of heat
exchanger inter changing
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.70 44.0 High 20/15 7/6
Heating Overload*1 3.20 ~ 3.70 52.0 ~ 59.0 Low 27/ 24/18
Low temperature 2.20 35.0 High 20/ 10/10
Standard 0.90 10.0 High 27/19 35/24
Cooling Overload 0.99 14.0 High 32/23 43/26
Low temperature 0.70 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
*1 During heating overload operation, a value for the high temperature limit control operation is included.
17
Page 19
5-2. RAS-10UKHP-ES3 / RAS-10UAH-ES3
RAS-10UKHP-AS3 / RAS-10UAH-AS3
FILE NO. SVM-04001
Indoor unit
Cooling
0.39m (Connecting pipe) 9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Heating
Heating
P
Packed valve
(9.52)
Heating
4-way valve
Cooling
Compressor
PA108X1T-4FZ1
Accumulator
Evaporator
Cross flow fan
T1
Capillary tube
1.2x600
Packed valve
(6.35)
Capillary tube
1.0x1300
l
0.49m (Connecting pipe) 6.35
l
Condenser
Refrigerant
R410A : 0.70 kg.
Cooling Heating
Propeller fan Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standar d
pressure
(MPaG)
P
Surface temp. of heat
exchanger inter changing
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 2.45 40.0 High 20/15 7/6
Heating Overload 3.45 52.0 Low 27/ 24/18
Low temperature 2.10 35.0 High 20/
10/10
Standard 0.90 11.0 High 27/19 35/24
Cooling Overload 1.07 16.0 High 32/23 43/26
Low temperature 0.85 5.0 Low 21/15 21/15
Note :
 Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
18
Page 20
5-3. RAS-13UKP-ES3 / RAS-13UA-ES3
RAS-13UKP-AS3 / RAS-13UA-AS3
FILE NO. SVM-04001
Indoor unit
Cooling
0.39m (Connecting pipe) 12.7
O.D.:12.7mm O.D.:6.35mm
Cooling
Packed valve
Cooling
P
(12.7)
Compressor
PA150X2T-4FM1
Heat exchanger
Cross flow fan
T1
Packed valve
(6.35)
Capillary tube
1.5x500
0.49m (Connecting pipe) 6.35
l
Condenser
Refrigerant
R410A : 0.95 kg.
Cooling
Propeller fan
Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standar d
pressure
(MPaG)
P
Surface temp. of heat
exchanger inter changing
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.90 9.0 High 27/19 35/24
Cooling Overload 1.03 13.0 High 32/23 43/26
Low temperature 0.70 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
19
Page 21
5-4. RAS-10UKP-ES3 / RAS-10UA-ES3
RAS-10UKP-AS3 / RAS-10UA-AS3
FILE NO. SVM-04001
Indoor unit
Cooling
0.39m (Connecting pipe) 9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
Cooling
P
(9.52)
Compressor
PA108X1T-4FZ1
Evaporator
Cross flow fan
T1
0.49m (Connecting pipe) 6.35
Packed valve
(6.35)
Capillary tube
1.5x1100l
Condenser
Refrigerant R410A : 0.65 kg.
Cooling
Propeller fan Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
Indoor Outdoor
Standard 0.95 11.0 High 27/19 35/24
Cooling Overload 1.15 15.0 High 32/23 43/26
Low temperature 0.85 5.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
20
Page 22
5-5. RAS-07UKP-ES3 / RAS-07UA-ES3
FILE NO. SVM-04001
Indoor unit
Cooling
0.39m (Connecting pipe) 9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
Cooling
P
(9.52)
Compressor
PA79X1T-4FZ5
Evaporator
Cross flow fan
T1
0.49m (Connecting pipe) 6.35
Packed valve
(6.35)
Capillary tube
1.2x650l
Condenser
Refrigerant R-22 : 0.65 kg.
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
50Hz
Cooling
Propeller fan Outdoor unit
Standard
pressure P
(MPaG)
Mark( )means check points of Gas Leak.
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Standard 0.97 14.0 High 27/19 35/24
Cooling Overload 1.13 20.0 High 32/23 43/26
Low temperature 0.63 2.0 Low 21/15 21/15
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
21
Page 23
FILE NO. SVM-04001
6. CONTROL BLOCK DIAGRAM
6-1. RAS-13UKHP-ES3 / RAS-13UAH-ES3, RAS-13UKHP-AS3 / RAS-13UAH-AS3,
RAS-10UKHP-ES3 / RAS-10UAH-ES3, RAS-10UKHP-AS3 / RAS-10UAH-AS3
Heat Exchange sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Reciver
Main Unit Control Panel
Functions
 Louver Control
3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Compressor
ON/OFF
Signal
Outdoor Fan
M.C.U.
ON/OFF
Signal
4-Way Valve
ON/OFF
Signal
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
PRE DEF.
Sign Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Relay
RY01
Compressor 4-Way Valve
Remote Control
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Relay
Outdoor Fan Motor
RY03
Infrared Rays
Relay
RY04
Hi power
Filter Reset
22
Page 24
FILE NO. SVM-04001
6-2. RAS-13UKP-ES3 / RAS-13UA-ES3, RAS-13UKP-AS3 / RAS-13UA-AS3
RAS-10UKP-ES3 / RAS-10UA-ES3, RAS-10UKP-AS3 / RAS-10UA-AS3 RAS-07UKP-ES3 / RAS-07UA-ES3
Main Unit Control Panel M.C.U.
Heat Exchange sensor
Thermo. Sensor
Infrared Rays Signal Reciver
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Functions
 Louver Control
3-minutes Delay at Restart
for Compressor
Motor Revolution Control
Processing
(Temperature Processing)
Timer
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
Fan Only
Sign Display
Indoor Fan
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Operation (START/STOP)
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Compressor
ON/OFF
Signal
Relay
RY01
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Temperature Setting
Fan Speed Selection
Louver
ON/OFF
Signal
Louver
Motor
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
23
Page 25

7. OPERATION DESCRIPTION

FILE NO. SVM-04001
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit controller. The outdoor unit controller receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcontroller, and the louver is automatically set at the stored position for the next operation.
(2) Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [FIX] button is pressed, it stops swinging.
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air inlet of the indoor heat exchanger by the indoor temperature sensor
Temperature setting of the indoor heat exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and the room temperature.
Transferring of operation commands to the outdoor unit
Receiving of information of the operation status and judging of the information or indication of error
Table 7-1-1
RAS-13UKHP-ES3 RAS-10UKHP-ES3
Model
HIGH 1,300 630 1,200 570
Cooling MED+ 1,200 570 1,100 520
and MED 1,100 520 1,000 460
Fan only LOW+ 1,020 470 900 400
LOW 950 430 800 340
HIGH 1,350 650 1,250 610
MED+ 1,250 610 1,170 560
Heating MED 1,150 550 1,100 520
LOW+ 1,100 520 1,000 460
LOW 1,050 490 900 400
Model
HIGH 1,300 630 1,250 610
Cooling MED+ 1,200 570 1,120 530
and MED 1,100 520 1,000 460
Fan only LOW+ 1,020 470 900 400
LOW 950 430 800 340
RAS-13UKHP-AS3 RAS-10UKHP-AS3
Motor speed Air flow level Motor speed
(rpm) (m
RAS-13UKP-ES3 RAS-10UKP-ES3 RAS-13UKP-AS3 RAS-10UKP-AS3
3
/h)
(rpm)
Air flow level
24
+
LOW
MED+=
3
(m
/h)
LOW+MED
=
MED+HIGH
Motor speed
(rpm)
1,200
1,100
1,000
+
, MED, MED
2
2
Air flow level
(m
RAS-07UKP-ES3
900
800
3
570
520
460
400
340
+
/h)
Page 26
FILE NO. SVM-04001
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [START / STOP] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation can be effected thereafter simply by pressing [START / STOP] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW HIGH, the motor operates with a constant air flow.
+
, MED, MED+ or
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-2.
ON ON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Fig. 7-2-2
display
OPERATION
+3
+2.5
+2
+1.5
+1
+0.5
(Room temp.) (Preset temp.)
Preset temp.
0
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
(2) The Hi POWER operation cannot be set.
M+
*1
*1
*1
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
(Room temp.) (Preset temp.)
Preset temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
25
Page 27
FILE NO. SVM-04001
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-4.
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Preset temp.)
(Room temp.)
Preset temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-2-4
ON
display
OPERATION
7-2-4. Heating operation *Heat pump model only
([MODE] button on the remote control is set to the heating operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are controlled as shown in Fig. 7-2-6.
Preset temp.
0
-0.5
(Preset temp.)
(Room temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
Fig. 7-2-6
display
OPERATION
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position. The pattern of operation depending on the relation between room temperature and preset temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L.*S.L. S.L.L. L. S.L. L.
*
Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When [FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
0
-0.5
-1
-1.5
-2
(Preset temp.)
-5.0
-5.5
[FAN AUTO]
(Room temp.)
L
*1 *2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The Hi POWER operations cannot be set.
26
Page 28
FILE NO. SVM-04001
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The upper limit of the revolving speed is shown in Fig. 7-2-8 and Table 7-2-1.
RAS-13UKHP-ES3, RAS-13UKHP-AS3
Manual
AUTO
*4
*3
SUL
SUL*1
Stop
(One of 5 steps)
L-H (Up to seting speed)
424134
33
292821
20
*2
A+4
A+4
A-8
A-8
*6 *5
Indoor heat exchanger temperature
RAS-10UKHP-ES3, RAS-10UKHP-AS3
Manual
AUTO
*4
SUL
SUL*1
Stop
*3
(One of 5 steps)
L-H (Up to seting speed)
464534
33
323121
20
*2
A+4
A+4
A-8
A-8
*6 *5
Indoor heat exchanger temperature
Fig. 7-2-8 Cold draft preventing control
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24°C when the preset temperature is 24°C or
more and A is the preset temperature when it is under 24°C.
*3: SUL means Super Ultra Low.
*4: Calculated from difference in motor speed
between SUL and HIGH.
*5 and *6:
Table 7-2-1
Fan *5 *6 speed Starting period Stabilized period
AUTO • Up until 12 minutes
passed after starting the unit
From 12 to 25 minutes passed after starting the unit and room temperature is 3°C lower than preset temperature
Manual Room temperature (L Ð H) < Preset temperature
From 12 to 25 minutes passed after starting the unit and room temperature is between preset temperature and 3°C lower than preset temperature
25 minutes or more passed after starting the unit
Room temperature
Preset temperature
4°C
3.5°C
7-2-5. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-9. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-9.
C
Cooling operation
The louver moves to the position same as Hi POWER operation.
+4
Cooling operation
0
27
Heating operation
RAS-13UKHP-ES3 RAS-13UKHP-AS3
(Room temp.) (Preset temp.)
RAS-10UKHP-ES3 RAS-10UKHP-AS3
Fan only operation
RAS-13UKP-ES3 RAS-13UKP-AS3 RAS-10UKP-ES3 RAS-10UKP-AS3 RAS-07UKP-ES3
Fig. 7-2-9
Page 29
FILE NO. SVM-04001
60
53 52
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger temp.
7-3. Hi POWER Mode
([Hi POWER] button on the remote control is pressed.)
When [Hi POWER] button is pressed while the indoor unit is in Auto, Cooling or Heating operation, Hi POWER mark is indicated on the display of the remote control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the current operation.
(2) Cooling operation
The preset temperature drops 3°C. (The value of the preset temperature on the remote control does not change.)
If the difference between the preset temperature and the room temperature is big, the horizontal louver moves to the Hi POWER position automatically. Then when the difference between them gets smaller, the horizontal louver returns automatically.
FAN speed : [AUTO] If the difference between the preset temperature and room temperature is big, the air conditioner operates at maximum airflow level. If the difference between the preset temperature and the room temperature is small, the air conditioner operates at normal airflow level.
FAN speed : One of 5 levels The air conditioner operates at normal airflow level.
(3) Heating operation *Heat pump model only
The preset temperature increases 2°C, (The value of the preset temperature on the remote control does not change.)
The indoor unit operates in normal heating mode except the preset temperature is higher (+2°C).
(4) The Hi POWER mode can not be set in Dry or Fan
only operation.
7-4. High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1 and 7-5-2.
RAS-13UKHP-ES3 RAS-13UKHP-AS3 RAS-13UKP-ES3 RAS-13UKP-AS3
Heat exchanger temperature
6
2
Fig. 7-5-1
RAS-10UKHP-ES3 RAS-10UKHP-AS3 RAS-10UKP-ES3
RAS-10UKP-AS3 RAS-07UKP-ES3
Heat exchanger temperature
7
5
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Compressor
Less than continues
Outdoor fan
ON
for 5 minutes
OFF
Fig. 7-5-2
28
Page 30
FILE NO. SVM-04001
7-6. Defrost Operation *Heat pump model only
During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen. In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
7-6-1. Condition to start the defrost operation
The defrost operation starts whichever below conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference between the indoor heat exchanger temperature and the room temperature is less than the specified value. (This value is decided by the microprocessor.) (Control example is shown in Fig. 7-6-1. In case of B or C, the defrost operation starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of 90 minutes.
D
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operating time is 10 minutes.
7-6-3. Ending condition at defrost operation
(1) When the compressor current becomes 7.5A or
more during defrost operation, the defrost operation stops and the heating operation restarts. (The current sensor detects the compressor current.)
(2) The defrost operation continues for at most
6 minutes or 10 minutes.
DEFROST LAMP :
During defrost operation, the PRE-DEF. lamp is on and the indoor and outdoor fans are off.
The compressor start protection timer is inter­looked with the PRE-DEF. lamp. So the PRE-DEF. Lamp is off (the fans stop) for about 3 minutes after the START/STOP button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat ex-changer is preheated to about 24°C or higher, the PRE-DEF. Lamp goes off, and the indoor fan starts.
xchanger temp
Indoor heat e
- Room temp
A
B
C
Cumulative compressor operating time
Fig. 7-6-1 (Indoor fan speed : M)
7-6-2. Defrost operation time control
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low, however, the defrost operating time is 10 minutes.)
minutes
40
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
minutes
40
Defrost
Heating
Defrost
Max 6 minutes
1 cycle
Fig. 7-6-2
10 minutes
29
Page 31
7-7. Current Limit Control *Heat pump model
only
The microcontroller detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling operation)
Control is performed as shown below by detecting the compressor operating current with a current sensor (C.T).
RAS-13UKHP-ES3, RAS-13UKHP-AS3 / RAS-10UKHP-ES3, RAS-10UKHP-AS3
FILE NO. SVM-04001
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
Compressor Outdoor fan
More than I4 continues for 3 seconds
More than I3 continues for 5 seconds
Fig. 7-7-1
(2) Current limit control (Heating operation)
Control is performed as shown in Fig. 7-7-2
RAS-13UKHP-ES3, RAS-13UKHP-AS3 / RAS-10UKHP-ES3, RAS-10UKHP-AS3
Input current
13.5A/ 19.2A I4
12.5A/ 17.8A I3
Compressor Outdoor fan
More than I4 continues for 3 seconds
More than I3 continues for 5 seconds
OFF
OFF
ON
OFF
OFF
10A/ 15.6A I2
9A/ 15.0A I1
ON OFF
ON
Fig. 7-7-2
Remark :
This function is available only for heat pump model (Cooling models have no a current sensor (C.T.)
30
Page 32
FILE NO. SVM-04001

7-8. Auto Restart Function

The indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of power supply being accidentally shut down. The operation will resume without warning three minutes after power is restored. This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The green lamp is on.
7-8-1. How to set auto restart function
To set the auto restart function, proceed as follows: The power supply to the unit must be on; the function will not set if the power is off. Push the [TEMPORARY] button located in the center of the front panel continuously for three seconds. The unit receives the signal and beeps three times. The unit then restarts operating automatically in the event of power supply being accidentally shut down.
The unit beeps three times The lamp changes from and continues to operate. green to orange.
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
TEMPORARY button
0
3S
After approx. three seconds,
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The green lamp is on. than three seconds.
The unit stops operating. The green lamp is turned off.
0
3S
TEMPORARY button
While this function is being set, if the unit is in
operation, the orange lamp is on.
This function can not be set if the timer operation
has been selected.
When the unit is turned on by this function, the
louver will not swing even though it was swinging automatically before shutting down.
The unit beeps three times
If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on.
After approx. three seconds,
While the filter check lamp is on, the
TEMPORARY button has the function of filter reset button.
31
Page 33
7-8-2. How to cancel auto restart function
To cancel auto restart function, proceed as follows: Repeat the setting prodedure: the unit receives the signal and beeps three times. The unit will be required to be turned on with the remote control after the main power supply is turned off.
When the unit is on standby (Not operating)
Operation Motions
Push [TEMPORARY] button for more The unit is on standby. than three seconds.
The unit starts to operate. The orange lamp is on.
0
3S
The unit beeps three times The lamp changes from and continues to operate. orange to green.
FILE NO. SVM-04001
After approx. three seconds,
TEMPORARY button
When the unit is in operation
Operation Motions
Push [TEMPORARY] button for more The unit is in operation. The orange lamp is on. than three seconds.
0
3S
TEMPORARY button
While this function is being set, if the unit is in
operation, the orange lamp is on.
7-8-3. Power failure during timer operation
When the unit is in Timer operation, if it is turned off because of power failure, the timer operation is cancelled. Therefore, set the timer operation again.
If the unit is not required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it off.
The unit stops operating. The orange lamp is turned off.
The unit beeps three times
If the unit is required to operate at this time, push [TEMPORARY] button once more or use the remote control to turn it on.
After approx. three seconds,
7-9. Filter Check Lamp
When the elapsed time reaches 1000 hours, the filter check lamp indicates. After cleaning the filters, turn off the filter check lamp.
7-9-1. How to turn off filter check lamp
Press [FILTER] button on the remote control. OR push [TEMPORARY] button on the indoor unit.
Note:
If [TEMPORARY] button is pushed while the filter check lamp is not indicating, the indoor unit will start the Automatic Operation.
32
Page 34
y
y
g
g
play
g
(
(
p
g
)
g
y
g Op
g
g
p
g
g
y
g
(
(
g
g
)
g
y
g
g
g
p
FILE NO. SVM-04001-(1)
7-10. Self-Cleaning function.
Self-Cleaning function is designed to reduce humidity that causes mold to form inside the air conditioning unit. This advanced, efficient s fan activates and dries the moisture in the coil for 20 minutes, then turns off automaticall
stem reduces moisture in the coil. When you turn off your air conditioner, the internal
.
Operation display
FCU fan
FCU louver OPEN CLOSE CLOSE
Timer display
Compressor
CDU fan
rpm is depend on preseting. rpm is SUL speed.
depend on preseting of timer function. depend on preseting of timer function.
depend on preseting per room temperature.
depend on preseting per room temperature.
Cool mode or dry mode Self-Cleaning mode
operation more than 10 mins. operate 20 mins.
ON OFF OFF
ON ON
ON or OFF
ON or OFF
ON or OFF
Turn off by remote controller
or timer-off function.
ON
OFF OFF
OFF OFF
Automatically turn-off.
ON or OFF
The Self-Cleaning function is set as default at ex-factory.
Self-Cleaning operation can stop manually by press START/STOP botton of the remote control one more time.
7-10-1. How to cancel Self-Cleanin
To cancel the Self-Cleanin
Press TEMPORARY button one time or use remote control to
function, proceed as follows:
function
turn on air conditioner. The OPERATION dis oran
e color (When AUTO-RESTART is ON) or green color
When AUTO-RESTART is OFF).
Hold down the TEMPORARY button for more than 20 seconds.
The air conditioner will stop suddenly when the TEMPORARY is
ressed but keep holding it continue. Then will beep 3 times in
the first 3 seconds but it is not related to Self-Cleanin
After holdin
times without an
The Self-Cleanin
about 20 seconds, the air conditioner will beep 5
blinking of display.
eration had been concelled.
OFF
Operation time
will show in
function
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-8-1.
7-10-2. How to set Self-Cleanin
To set the Self-Cleanin
Press TEMPORARY button one time or use remote control to
function, proceed as follows.
turn on air conditioner. The OPERATION displa
e color (When AUTO-RESTART is ON) or green color
oran
function.
will show in
When AUTO-RESTART is OFF).
Hold down the TEMPORARY button for more than 20 seconds.
The air conditioner will stop suddenly when the TEMPORARY is
pressed but keep holdin
it continue. Then will beep 3 times is
the first 3 seconds but it is not related to Self-Cleanin
After holdin
5 times and OPERATION displa
The Self-Cleanin
about 20 seconds, the air conditioner will beep
blinks 5 times.
function had been set.
Remarks
Per settin
of Self-Cleaning function above, AUTO-RESTART
function had been cancelled. To set AUTO-RESTART a
lease follow item 7-8-1.
32-(1)
ain,
function
ain,
Page 35
FILE NO. SVM-04001

8. INSTALLATION PROCEDURE

8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be at least polychloroprene sheathed flexible cord (design H07 RN-F), or cord designation 245 IEC66.
CAUTION
THIS AIR CONDITIONER USES THE NEW HFC REFRGERANT (R410A), WHICH DOES NOT DESTROY THE OZONE LAYER.
R410A refrigerant is apt to be affected by impurity such as water, oxidizing membranes, and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter into the refrigerating cycle of a new-refrigerant air conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting sections on the main unit are different from those for the conventional refrigerant, and different size tools are also required. Accordingly, special tools are required for the new refrigerant (R410A) as shown below. For connecting pipes, use new and clean piping materials with high-pressure withstand capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its pressure withstand may be insufficient, and may contain impurities.
CAUTION
This appliance must be connected to the main power supply by means of a circuit breaker or a switch with a contact separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after installation. The plug must be disconnected from the power supply socket in order to disconnect the appliance completely from the mains.
New Refrigerant Air conditioner Installation
To Disconnect the Appliance from the Main Power Supply
33
Page 36
FILE NO. SVM-04001
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY, ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATORS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
Before doing the electrical work, attach an approved plug to the power supply cord. Also, make sure the equipment is properly earthed.
Appliance shall be installed in accordance with national wiring regulations. If you detect any damage, do not install the unit. Contact your TOSHIBA dealer immediately.
CAUTION
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise and discharged air might disturb neighbors.
To avoid personal injury, be careful when handling parts with sharp edges.
Please read this installation manual carefully before installing the unit. It contains further important instruc-
tions for proper installation.
REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER
Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems, or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.
Remark per EMC Directive 89/336/EEC
To prevent flicker impressions during the start of the compressor (technical process) following installation conditions do apply.
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution has to be of an impedance. Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!
2. No other equipment should be connected to this power line.
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply for products like washing machines, air conditioners or electrical ovens.
4. For power details of the air conditioner, refer to the rating plate of the product.
34
Page 37
8-2. Installation Diagram of Indoor and Outdoor Units
FILE NO. SVM-04001
Before installing the wireless remote control
With the remote control cover
open, load the batteries supplied correctly, observing their polarity.
22
2 Wireless remote control
22
Cover
33
3 Batteries
33
(Attach to the front panel)
5 Zeolite filter
2 Wireless remote
control
13 series
A 600 mm 400 mm
07,10 series
170 mm
or more
Air filter
6 Bioenzyme filter
8 Pan head wood screw
Hook
1 Installation
65 mm or more
Hook
4 Remote control holder
plate
Shield pipe
170 mm
or more
For the rear left and left
piping
Wall
Insert the cushion between the indoor unit and wall, and tilt the indoor unit for better operation.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected the left, rear left, rear right, right, bottom right or bottom left.
B 100 mm 45 mm
100 mm or more
A mm or more
B mm or more
600 mm or more
Vinyl tape Apply after carrying out a drainage test.
Extension drain hose
(Option: RB–821SW)
600 mm or more
Saddle
Right
Rear right
Rear left
Bottom right
Bottom left
Insulate the refrigerant pipes separately with insulation, not together.
6 mm thick heat resisting polyethylene foam
Left
35
Page 38
8-3. Installation
8-3-1. Optional installation parts
FILE NO. SVM-04001
Part
Code
Parts name
Refrigerant piping Liquid side : ∅6.35 mm
A
Gas side : 9.52 mm (07, 10 series) Gas side : ∅12.70 mm (13 series)
Pipe insulating material
B
(polyethylene foam, 6 mm thick) Putty, PVC tapes
C
<Fixing bolt arrangement of outdoor unit>
RAS-10, 13 Series
125 mm115 mm
310 mm
7 mm
32.5 mm
73 mm
30
Air inlet
102 mm
Q'ty
One
each
1
One
each
275 mm
60 mm
RAS-07 Series
500 mm
97 mm
Air inlet
Air outlet
600 mm
90 mm
Drain outlet
Air outlet
Drain outlet
Fig. 8-3-1
Secure the outdoor unit with fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
Use8 mm or10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach 9 drain nipple and 10 cap water proof to the
bottom plate of the outdoor unit before installing it.
36 −
Page 39
8-3-2. Accessory and installation parts
FILE NO. SVM-04001
Part
No.
Part name (Q'ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
This model is not equipped with an extension drain hose.
Name
Owner’s manual
Installation manual
Part
No.
Part name (Q'ty)
4
Remote control holder x 1
5
Zeolite filter x 1
6
Bioenzyme filter x 1
Part
No.
Part name (Q'ty)
7
Mounting screw
8
Pan head wood screw 3.1 x 16 s x 2
9
Drain nipple* x 1
!
Cap water proof* x 2
(For Heat pump model only)
The part marked with asterisk ( outdoor unit.
4 x 25 s x 6
(For Heat pump model only)
*) is packaged with the
Option :
For the extension drain hose, use an optionally available RB-821SW or commercially available one.
37 −
Page 40
FILE NO. SVM-04001
8-3-3. Installation/Servicing tools
<Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)
 In order to increase the pressure
size of opposite side of flare nuts have been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A Applicable to R22 model Changes
Gauge manifold As pressure is high, it is impossible to measure by
Charge hose In order to increase pressure withstand strength,
Electronic balance As pressure is high and gasification speed is fast, for refrigerant charging it is difficult to read the indicated value by means
withstand
strength of the refrigerant piping, flare processing diameter and
means of conventional gauge. In order to prevent any other refrigerant from being charged, each port diameter has been changed.
hose materials and port size have been changed (to 1/2 UNF 20 threads per inch). When purchasing a charge hose, be sure to confirm the port size.
of a charging cylinder, as air bubbles occur.
Torque wrench (nominal dia. 1/2, 5/8) Incidentally, a common wrench is used for nominal
Flare tool By increasing the clamp bar's receiving hole, (clutch type) strength of spring in the tool has been improved.
Gauge for projection Used when flare is made with a conventional flare adjustment tool.
Vacuum pump adapter Connected to conventional vacuum pump. It is
Gas leakage detector Exclusive for HFC refrigerant.
 Incidentally, the "refrigerant cylinder" comes with the refrigerant designation (R410A) and protector coating in the U. S ARI specified rose color (ARI color code: PMS 507).
 Also, the "charge port and packing for refrigerant cylinder" require 1/2 UNF 20 threads per inch corresponding to the port size of the charge hose.
The size of opposing flare nuts has been increased.
diameters 1/4 and 3/8.
necessary to use an adapter to prevent vacuum pump oil from flowing back to the charge hose. The charge hose connecting part has two ports: one for conventional refrigerant (7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump mineral oil mixes with R410A, a sludge may occur and damage the equipment.
38
Page 41
FILE NO. SVM-04001
62
85
82.5
170
8-4. Indoor Unit
8-4-1. Installation place
A place which provides the spaces around the indoor unit as shown in the above diagram.
A place where there is no obstacle near the air inlet and outlet.
A place that allows easy installation of the piping to the outdoor unit.
A place which allows the front panel to be opened.
CAUTION
Direct sunlight to the indoor unit's wireless
receiver should be avoided.
The microprocessor in the indoor unit should not
be too close to RF noise sources. (For details, see the owner's manual.)
<Remote control>
A place where there are no obstacles such as a curtain that may block the signal from the indoor unit.
Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
The location of the remote control should be determined as shown below.
8-4-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
Pipe hole
65 mm
The center of the pipe hole is above the arrow.
100 mm
Fig. 8-4-2
1. After determining the pipe hole position on the mounting plate (A), drill the pipe hole (65 mm) at a slight downward slant to the outdoor side.
NOTE
When drilling a wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
Thread
Hook
Weight
Hook
Pipe hole
7 Mounting screw
1
Installation plate
Indoor unit
(Side view)
7 m
°
75
Reception range
Remote control
(Top view)
Indoor unit
Reception range
* : Axial distance
Fig. 8-4-1
5 m
5 m
45
°
45
°
Remote control
7 m
*
Pipe hole
Hook
Indoor unit
Fig. 8-4-3
39
Page 42
FILE NO. SVM-04001
<When the installation plate is directly mounted on the wall>
1. Securely fit the installation plate onto the wall by screwing it in the upper and lower parts to hook up the indoor unit.
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
Installation plate <Keep horizontal direction>
Anchor bolt
Projection
5 mm dia. hole
15 mm or less
77
7 Mounting
77
screw 4 x 25
ss
s
ss
8-4-3. Electrical work
1. The supply voltage must be the same as the rated voltage of the air conditioner.
2. Prepare the power source for exclusive use with the air conditioner.
CAUTION
This appliance can be connected to the mains in either of the following two ways. (1) Connection to fixed wiring:
A switch or circuit breaker which disconnects all poles and has a contact separation of at least 3 mm must be incorporate in the fixed wiring. An approved circuit breaker or switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord and plug it into wall outlet. An approved power supply cord and plug must be used.
NOTE
Ensure all wiring is used within its electrical rating.
RAS-13UKHP-ES3 RAS-10UKHP-ES3
Model
RAS-13UKHP-AS3 RAS-10UKHP-AS3
RAS-13UKP-ES3 RAS-10UKP-ES3 RAS-13UKP-AS3 RAS-10UKP-AS3
RAS-07UKP-ES3
Clip anchor (local parts)
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
In case of block, brick, concrete or similar type walls, make 5 mm dia. holes in the wall.
Insert clip anchors for appropriate 7 mounting screws.
NOTE
Secure four corners and lower parts of the installation plate with 4 to 6 mounting screws to install it.
Power source 50 Hz, 220 240 V Single phase
Maximum running current
Plug socket &
fuse rating
Power cord 1.3 mm2 or more 1 mm2 or more
12A 7.5A
16A
40
Page 43
FILE NO. SVM-04001
1
2
3
4
1
2
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out without removing the front panel.
1. Remove the air inlet grille. Open the air inlet grille upward and pull it toward you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable slot on the rear panel so that it protrudes about 15 cm from the front.
5. Insert the connecting cable fully into the terminal block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air inlet grille on the indoor unit.
CAUTION
Be sure to refer to the wiring system diagram
labeled inside the front panel.
Check local electrical cords and also any specific
wiring instructions or limitations.
For RAS-13/10/07UK
Terminal cover
Connecting cable
about 15 cm
Screw
10 mm
Stripping length of the connecting cable
Cord clamp
Screw
Screw
Fig. 8-4-7
60 mm
10 mm
50 mm
1
2
Connecting cable
Earth line
Terminal block
Earth line
For RAS-13/10UKH
Terminal
cover
Connecting
cable
about 15 cm
Screw
Stripping length of the connecting cable
Cord clamp
Screw
Fig. 8-4-5
10 mm
10 mm
Screw
80 mm
70 mm
0 mm
1
1
2
3
50 mm
4
Connecting cable
Earth line
Terminal block
Earth line
Fig. 8-4-8
NOTE
Use stranded wire only.
Wire type : H07 RN-F or more
<How to install the air inlet grille on the indoor unit>
When attaching the air inlet grille, the contrary of the removed operation is performed.
Fig. 8-4-9
Fig. 8-4-6
41
Page 44
FILE NO. SVM-04001
8-4-4. Piping and drain hose installation <Piping and drain hose forming>
* Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Changing
Left Bottom right Right
Die-cutting
Front panel slit
drain hose
Piping preparation
1. Die-cutting Front panel slit
For leftward connection, cut out slit on the left side of the front panel. (A knife will produce splinters, so use nippers.)
2. Changing drain hose
For leftward connection, bottom leftward connection and rear leftward connection’s piping, it is necessary to change the drain hose and drain cap.
How to remove the drains cap
Clip drain cap by needle-nose plier, and pull out.
How to fix the drains cap
1) Insert hexagonal wrench (4 mm) in a center head.
4 mm
Fig. 8-4-12
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil (refrigerant machine oil) when inserting the drain cap. Application causes deterioration
Insert a hexagon wrench (4 mm)
and drain leakage of the plug.
Fig. 8-4-13
CAUTION
Firmly insert the drain hose and drain cap; otherwise, water may leak.
<In case of right or left piping>
Fig. 8-4-10
How to install the drain hose
Firmly insert drain hose connecting part until hitting on a heat insulator.
Heat insulator
Drain hose
Fig. 8-4-11
After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Slit
Fig. 8-4-14
<In case of bottom right or bottom left piping>
After scribing slits of the front panel with a knife or a making-off pin, cut them with a pair of nippers or an equivalent tool.
Slit
42
Fig. 8-4-15
Page 45
FILE NO. SVM-04001
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use a spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
170 mm
R 30 mm (Use polisin (polyethylene)
43 mm
core or the like for bending pipe.)
0
8
Liquid side
Gas side
Outward form of indoor unit
Use the handle of screwdriver, etc.
Fig. 8-4-16
8-4-5. Indoor unit fixing
1. Pass the pipe through the hole in the wall, and hook the indoor unit on the installation plate at the upper hooks.
2. Swing the indoor unit to right and left to confirm that it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it at the lower part on the installation plate. Pull the indoor unit toward you to confirm that it is firmly hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig. 8-4-17
For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
NOTE
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall. After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and wrap the facing tape around them.
CAUTION
Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
When bending a pipe, carefully do it, not to crush it.
Connecting cable
PushPush
Fig. 8-4-18
43
Page 46
FILE NO. SVM-04001
8-4-6. Drainage
1. Run the drain hose sloped downwards.
NOTE
Hole should be made at a slight downward slant on the outdoor side.
Do not form the Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
Fig. 8-4-
drain hose into
a wavy shape.
19
Do not put the drain hose end in the drainage ditch.
2. Put water in the drain pan and make sure that the water is drained out of doors.
3. When connecting extension drain hose, insulate the connecting part of extension drain hose with shield pipe.
Shield pipe
Drain hose
Inside the room
Fig. 8-4-
Extension drain hose
20
CAUTION
Arrange the drain pipe for proper drainage from the unit. Improper drainage can result in dew-dropping.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan. Therefore, do not store the power cord and other parts at a height above the drain guide.
8-5. Outdoor Unit
8-5-1. Installation place
A place which provides the spaces around the outdoor unit as shown in the left diagram.
A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level and vibration.
A place where the operation noise and discharged
air do not disturb your neighbors.
A place which is not exposed to a strong wind.
A place free of a leakage of combustible gases.
A place which does not block a passage.
When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
An allowable length of the connecting pipe is up to
10 m (RAS-10UA) or 15 m (RAS-13UA).
An allowable height level is up to 5 m (RAS-10,07UA)
or 6 m (RAS-13UA).
A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking the air discharging.
2. When the outdoor unit is installed in a place exposed always exposed to strong wind like a coast or on a high storey of a building, secure the normal fan operation using a duct or a wind shield.
3. In particularly windy areas, install the unit such as to avoid admission of wind.
4. Installation in the following places may result in trouble. Do not install the unit in such places.
A place full of machine oil.
A saline-place such as the coast.
A place full of sulfide gas.
A place where high-frequency waves are likely
to be generated as from audio equipment, welders, and medical equipment.
Space for pipes
Fig. 8-4-
21
Wall
Drain guide
44
Strong
wind
Fig. 8-5-1
Page 47
FILE NO. SVM-04001
8-5-2. Refrigerant piping connection
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness Warp
Fig. 8-5-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 8-5-3
Rigid (Clutch type)
Outer dia. R410A Conventional
of copper pipe tool used tool used
(Unit : N·m)
Outer dia.
of copper pipe
6.35
16 to 18 (1.6 to 1.8 kgf·m)
Tightening torque
9.52 30 to 42 (3.0 to 4.2 kgf·m)
12.70 50 to 62 (5.0 to 6.2 kgf·m)
Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of R22. (Approx. 1.6 times). It is therefore necessary to firmly tighten the flare pipe connecting sections (which connect the indoor and outdoor units) up to the specified tightening torque. Incorrect connections may cause not only a gas leakage, but also damage to the refrigerant cycle.
Flare at indoor unit side
6.35 0 to 0.5 1.0 to 1.5
9.52 0 to 0.5 1.0 to 1.5
12.70 0 to 0.5 1.0 to 1.5
Imperial (wing nut type, conventional tool)
Outer dia.
of copper pipe
R410A
6.35 1.5 to 2.0
9.52 1.5 to 2.0
12.70 2.0 to 2.5
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
Do not apply excess torque.
Otherwise, the nut may crack depending on the
conditions.
Externally threaded side
Use a wrench to secure.
CAUTION
Flare at outdoor unit side
Fig. 8-5-4
Mark line
Fig. 8-5-5
Flare nutHalf union
Internally threaded side
Use a torque wrench to tighten.
Fig. 8-5-6
KEEP IMPORTANT 4 POINTS FOR PIPING WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
45
Page 48
FILE NO. SVM-04001
8-5-3. Evacuating
After the piping has been connected to the indoor unit, you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the indoor unit using a vacuum pump. Do not use the refrigerant in the outdoor unit. For details, see the manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow prevention function so that inside oil of the pump does not flow backward into pipes of the air conditioner when the pump stops. (If oil inside of the vacuum pump enters into the air conditioner, which use R410A, refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum pump.
3. Open fully the low pressure side handle of the gauge manifold valve.
4. Operate the vacuum pump to start evacuating. Perform evacuating for about 15 minutes if the piping length is 20 meters. (15 minutes for 20 meters) (assuming a pump capacity of 27 liters per minute.) Then confirm that the compound pressure gauge reading is 101 kPa (76 cmHg).
5. Close the low pressure side valve handle of gauge manifold.
6. Open fully the valve stem of the packed valves (both sides of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
<Packed valve handling precautions>
 Open the valve stem all the way out; but do not try to open it beyond the stopper.
 Securely tighten the valve stem cap with torque in the following table:
Gas side 50 to 62 N·m (12.70 mm) (5.0 to 6.2 kgf·m)
Gas side 30 to 42 N·m (9.52 mm) (3.0 to 4.2 kgf·m)
Liquid side 16 to 18 N·m (6.35 mm) (1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m (0.9 to 1.0 kgf·m)
Hexagonal wrench is required.
mm
4
Fig. 8-5-8
Compound pressure gauge
-101kPa (-76cmHg)
Handle Lo
Charge hose
(For R410A only)
Connecting pipe
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
Fig. 8-5-7
Pressure gauge
Manifold valve
Handle Hi (Keep full closed)
Charge hose (For R410A only)
Vacuum pump adapter for counter-flow prevention (For R410A only)
Vacuum
pump
46
Page 49
FILE NO. SVM-04001
Selector Switch
LED Assembly
8-5-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as identified with their respective matched numbers on the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the outdoor unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any water coming in the outdoor unit. Proceed them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable> For RAS-13/10UAH
Terminal block
70 mm
10 mm
Earth line
10 mm
60 mm
Terminal screw
Connecting cable
Screw
Cord clamp
Fig. 8-5-9
8-6. How to Set Remote Control Selector
Switch
When two indoor units ae installed in seperated rooms, there is no need to change the selector switch.
<Remote control selector switch>
When two indoor units are installed in the same room or the adjacent two rooms, they may be controlled simultaneously with a single remote control. To prevent this, set either unit and its remote control to B setting. (Both units are set to A setting before shipment.)
The remote control signal is not recived when the indoor unit setting is different from the remote control one.
1. Set the remote control selector switch with the indoor unit.
1) Turn the circuit breaker of the main power switch off
before setting the selector switch.
2) Remove the Air inlet grille and Front panel. (Refer to
Earth line
page 63, 10-1)
3) Select the terminal of selector switch from [A position] to [B position].
For RAS-13/10/07UA
Terminal block
10 mm
60 mm
Earth line
10 mm
50 mm
Terminal screw
Connecting cable
Screw
Fig. 8-5-10
CAUTION
Wrong wiring connection may cause some electrical parts burn out.
Be sure to comply with local codes on running the wire from indoor unit to outdoor unit (size of wire and wiring method etc.)
Every wire must be connected firmly.
Earth line
Cord clamp
Fig. 8-6-1
NOTE
Wire type: H07 RN-F or 245 IEC66 (2.0 mm2 or more)
47
Page 50
FILE NO. SVM-04001
2. Set the remote control selector switch with the
remote control
[B] is indicated on the liquid crystal display when setting remote control selector switch to B. [A] is not indicated on the display even if the selector switch is set to A.
1) Load the remote control with the batteries.
2) Press the [CHECK] button using something with
sharp point. (The preset temperature on the remote control changes to [00].)
3) Press the [MODE] button while pressing the
[CHECK] button, [B] is indicted at the right of the present temperature display.
To reset the switch to the [A] setting, press the
[MODE] button again while pressing the [CHECK] button.
A
A B
B
8-7. Others
8-7-1. Gas leak test
Valve cover
Valve stem cap connection
Service cap connection
Fig. 8-7-1
Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or soap water.
8-7-2. Test operation
To switch the TEST RUN (COOL) mode, press TEMPORARY button for 10 sec. (The beeper will make a short beep.)
PRESET
START/STOP
ECO
AUTO
Hi-POWER
MEMO
CLOCK CHECKRESET
[MODE] button
FAN MODE
SWING
TIMER
FIX
ON
OFF SET CLR
FILTER
[CHECK] button
Fig. 8-6-2
3. Confirm that the indoor unit can operate with the new setting.
TEMPORARY button
Fig. 8-7-2
8-7-3. Auto restart setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the auto restart>
Press and hold the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the Owner’s Manual.
 − 48
Page 51

9. TROUBLESHOOTING CHART

FILE NO. SVM-04001
9-1. Troubleshooting Procedure
Follow the details of 9-2. Basic Check Items.
If there is no troub le corresponding to 9-2, check whether or not there are faulty parts following 9-4. Self-Diagnosis by Remote Control.
9-2. Basic Check Items
9-2-1. Power supply voltage
The line voltage must be AC 220 240V. If it is not within this range, the air conditioner may not operate normally.
9-2-2. Incorrect cable connection between Indoor
and outdoor units
The indoor unit is connected to the outdoor unit with 5 cables (Heat pump model) or 3 cables (Cooling Only model). Check that the indoor and outdoor units have been properly connected with terminals assigned the same numbers. If the connectors are not properly connected, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5Hz).
9-2-3. Program control
The microcontroller operates as shown in Table 9-2-1 to control the air conditioner. If there are any opera­tional problems, check whether or not the problems correspond to Table 9-2-1. If they correspond to the Table, they are not problems with the air conditioner, but they are indispensable operations to control and maintain the air conditioner properly.
Table 9-2-1
No. Operation of air conditioner Descriptions
1 When the main power supply is turned on,
the OPERATION lamp on the indoor unit blinks.
2 The indoor fan motor speed does not change
in the Dry operation.
The OPERATION lamp blinks to indicate that power is turned on. If the [START/STOP] button is pressed, the lamp stops blinking.
The indoor fan motor speed is automatically controlled in the Dry operation.
3 The compressor is not turned off even though
the room temperature is in the range that the compressor is turned off.
4 The compressor is not turned on and off even
though the thermo control is operated in the Dry operation.
5 The PRE-DEF. lamp is indicated when the
Heating operation starts.
6 The outdoor fan motor stops in the Heating
operation.
7 The compressor is not turned on even though
the room temperature is in the range that the compressor is turned on.
8 The operation mode changes in the
Automatic operation.
9 The Fan only operation continues in the
Automatic operation.
10 The Hi-POWER operation does not work.
The compressor has a function that it is not turned off for 3 minutes after it is turned on even though the room temperature is in the range that the compressor is turned off.
In the Dry operation, the compressor is turned on and off automatically at the regular intervals, independent of the thermo control.
The PRE-DEF. lamp is indicated during the Defrosting operation or if the indoor heat exchanger temperature is low when the Heating operation starts. At this time, the indoor fan motor stops to prevent cold air from blowing in the room.
When the indoor heat exchanger temperature is high, the outdoor fan motor is stopped by the high-temperature limit control operation.
The compressor is not turned on in the restart delay timer (3-minutes timer) operation. It is also not turned on after the power supply is turned on because of this timer operation.
In Automatic operation, the room temperature is detected all time for control fan speed and the operation mode is changed every 15 minutes according to difference between the room temperature and the preset temperature.
When the room temperature is in the range (Preset temperature ± 1°C), the Fan only operation is selected.
This operation does not work when the unit is in the Dry operation or Fan only operation.
49
Page 52
FILE NO. SVM-04001
9-3. Primary Judgement
9-3-1. Role of indoor unit controller
The indoor unit controller receives the operation commands from the remote control and executes them.
Temperature measurement at the air outlet of the indoor heat exchanger by the indoor temperature sensor
Temperature setting of the indoor heat exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the outdoor
unit
Table 9-3-1
Lamps Self-diagnosis
A OPERATION lamp is blinking. (1Hz)
B OPERATION lamp is blinking. (5Hz)
C OPERATION lamp is blinking. (5Hz)
D OPERATION lamp is blinking. (5Hz)
E OPERATION lamp is blinking. (5Hz)
F OPERATION and TIMER lamps are blinking.
(5Hz)
9-3-2. Failure diagnosis
The indoor unit diagnoses the operation condition and indicates the information of the self-diagnosis with the lamps on the display panel of the indoor unit.
Power failure (when the power supply is turning on)
Thermo sensor (TA) short or break
Heat exchanger sensor (TC) short or break
Indoor fan motor lock or failure
Indoor P.C. board failure
Wrong wiring of connecting cable
G OPERATION, TIMER and PRE-DEF.
(or FAN ONLY for cooling only model) lamps are blinking.
Table 9-3-2 Diagnosis by detective operation
Symptom Check Primary judgement
The remote control does not work.
The outdoor fan does not rotate.
Turn off the power supply once, then turn it on. Try to operate the remote control.
The compressor operates.
The compressor does not operate.
Cycle failure
Gas shortage or other refrigerant cycle trouble
Heat exchanger sensor open, break or short
Overload relay or thermostat trouble of compressor
The remote control still does not work.
The remote control works.
The indoor unit (and/or remote control) is/are defective.
OK.
The outdoor unit (Outdoor fan motor) is defective.
An internal part of the compressor or PCB is defective.
50
Page 53
9-4. Self-Diagnosis by Remote Control
(Check Code)
(1) If the lamps are indicated as shown B to G in Table
9-3-1, exchanger the self-diagnosis by the remote control.
(2) When the remote control is set to the service
mode, the indoor controller diagnoses the operation condition and indicate the information of the self-diagnosis on the display of the remote control with the check codes. If a fault is detected, all lamps on the indoor unit will blink at 5Hz and it
will beep for 10 seconds (Pi, Pi, Pi....). The timer
lamp usually blinks (5Hz) during the self-diagnosis.
9-4-1. How to use remote control in service mode
SET CLR
CLOCK CHECKRESET
FILE NO. SVM-04001
(1) Press [CHECK] button with a tip of pencil to set the
remote control to the service mode.
“00” is indicated on the display of the remote control.
The timer lamp on the indoor unit blinks continuously. (5 times per 1 sec.)
AUTOA
START/STOP
FAN MODE
SWING
ON
ECO
TIMER
FIX
OFF SET CLR
FILTER
A B
PRESET
AUTO
Hi-POWER
MEMO
CLOCK CHECKRESET
(2) Press [TIMER 8] button.
If there is no fault with a code, the indoor unit will beep once (Pi) and the display of the remote control will change as follows:
00
01
Check the unit with all 35 check codes (00 to 22).
1d
02
1E
22
as shown in Table 9-4-1.
Press [TIMER 9] button to change the check code backwards.
If there is a fault, the indoor unit will beep for 10 seconds (Pi, Pi, Pi...). Note the check code on the display of the remote control.
2-digits alphanumeric will be indicated on the display.
All lamps on the indoor unit will blink. (5 times per 1 sec.)
(3) Press [CLR] button. After service finish for clear
service code in memory.
“7F” is indicated on the display of the remote control.
Alphanumeric characters are used for the check code.
is 5. is 6. is A. is B. is C. is D.
* This illustration in only for Heat pump model.
For Cooling only model, there is not the ( ) symbol.
(4) Press [START/STOP] button to release the service
mode.
The display of the remote control returns to as it was before service mode was engaged.
51
Page 54
Block level Diagnosis function
Check Check
code
Block
Indoor P.C. board
code
Symptom Conditioner Condition
Thermo. sensor short/break.
Table 9-4-1
Continued operation.
Air
status
FILE NO. SVM-04001
Indicated when detected abnormal
Judgement and action
1.Check thermo sensor.
2.If it is OK, check P.C. board.
Cable connection/ Thermal fuse Refrigerant system
Heat exchanger sensor short/break.
Indoor fan lock, abnormality of indoor fan or thermal fuse break.
Abnormality of other indoor unit P.C. board.
1) Wrong wiring or disconnection of connective cable.
2) Terminal fuse cut off.
Continued operation.
All off
All off
All off
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
1.Check heat exchanger sensor.
2.If it is OK, check P.C. board.
1.Check heat thermal fuse is blow or not? (Terminal block part.)
2.If the thermal fuse is not blow, check indoor fan motor. (Refer to trouble shooting flow charts.)
Replace P.C. borad.
1.Check connective cable correct if wiring is wrong.
2.Check thermal fuse and Terminal blocks.
3.If it is OK, check P.C. board.
Other parts (including compressor)
1) Overload relay or thermostat for compressor
All off
Indicated when detected abnormal
1.If overload relay and
break.
2.If refrigerant cycle is
3. If heat exchanger
Content detected by the check codes "
" o " t " are stored in memory of the microcomputer even if the
power supply is turned off. Therefore, contents of operations in the past are all displayed.
52
themostat for compres­sor are OK, check refrigerant cycle.
OK, check P.C. board.
sensor is OK, check overload relay and themostat for compressor.
Page 55
9-5. Troubleshooting Flowcharts
9-5-1. Power can not be turned on (No operation at all)
<Preliminary checks>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK.?
Heat pump Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-04001
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the fuse
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C02 measured
DC310V ~ 340V?
YES
NO
(F01) blow?
fuse blow?
NO
Does the OPERATION
lamp blink?
Does the power turn on by pushing the [START/
STOP] button of the
remote control?
YES
NO
YES
NO
YES
Refer to the paragraph
"Pre-check", or defective circuit
before power P.C. board block.
YES
NO NO
YES
Parts (R21, R22, SG01,
C15, C01, DB01, C02,
Q01, T01) are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN13
connector the wrong
connecting?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
(No problem)
YES
NO
YES
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the secondary
voltage of SW
transformer (T01)
measured DC12V,
and DC7V?
YES YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
Shut off the power
NO NO
supply once, and
disconnecting the motor
connector CN11*.
Check Resistance
of Pin 1 and 3
of Fan-motor
= 162Ω .
Replace Fan-motor
and P.C. board.
Replace P.C. board
53
Page 56
Cooling Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-04001
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C50 measured
DC12V ~ 15V?
YES
NO
Does the fuse
(F01) blow?
fuse blow?
NO
Does the OPERATION
lamp blink?
Does the power turn on by pushing the [START/
STOP] button of the
remote control?
NO
NO
YES
Refer to the paragraph
"Pre-check", or defective circuit
before power P.C. board block.
YES
YES
YES
NO NO
YES
Parts (R21, R22, SG01,
C15, C01, DB50, C50,
are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the CN14
connector the wrong
connecting?
Does the transmission
indicator of remote
control flash normally
and transmit certainly?
(No problem)
YES
NO
YES
P.C. board is
defective.
Remote control is
defective.
Replace the remote
control.
Replace the
thermal fuse set.
Check connection.
Replace the main
P.C. board.
Re-wiring the cable.
Is the secondary
voltage of
transformer (TT-10)
measured DC12V?
YES YES
* Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
Shut off the power
supply once, and turn
NO NO
it on again after
disconnecting the motor
connector CN10*.
Is the secondary
voltage of
transformer
measured DC12V?
transformer (TT-10)
for power supplyis
defective.
Replace the main
P.C. board.
Motor is defective.
54
Page 57
9-5-2. Power can not be turned on after replacing indoor P.C. board
<Checking Procedure>
Connect the AC
Power supply
FILE NO. SVM-04001
Does the OPERATION
lamp blink?
YES
NO NO
RAS-13UKHP-ES3, RAS-13UKHP-AS3
Is it wired as shown
in Figure below?
YES
Return the wiring of the
power relay is returned to
the normal procedure.
To the paragraph of
"No Power turns on".
RAS-10UKHP-ES3, RAS-10UKHP-AS3
55
Page 58
RAS-13UKP-ES3, RAS-13UKP-AS3, RAS-10UKP-ES3, RAS-10UKP-AS3
9-5-3. Outdoor unit does not operate
FILE NO. SVM-04001
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
Does the OPERATION lamp blink?
YES
Does the power turn on by pushing
the [START/STOP] button of the
remote control?
YES
Is AC 220-240V supplied between
terminal block 1 -
Is cable connection between indoor
and outdoor units correct?
Check items as following procedure
in 9-5-4, 9-5-5, 9-5-6
YES
YES
2
?
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or IC31
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Replace the
P.C. board.
56
Page 59
9-5-4. Only compressor does not operate
Shut off the power supply
from AC outlet once and turn
it on after 5 seconds.
FILE NO. SVM-04001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 1 - 2 ) AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 1 - 2 ) AC 220-240V?
YES
Are all the cords for compressor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01) or IC31
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor and outdoor units are defective.
Re-wire or replace the defective cords.
Replace the
P.C. board.
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal.
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leakage)
57
Page 60
9-5-5. Only outdoor fan does not operate
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-04001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 : Heat pump model, 1 - 2 :
Cooling only model) AC 220-240V?
YES
Are all the cords for outdoor
fan motor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY03) or IC31
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outdoor units are defective.
Correct the wire or
replace the defective cords.
Replace the
P.C. board.
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
Is the capacitor for compressor normal?
YES
Outdoor fan motor is defective.
NO
NO
Outdoor fan motor is defective.
Capacitor for outdoor
fan motor is defective.
58
Page 61
9-5-6. Only 4-Way valve does not operate (During heating operation)
Heat Pump Model
Shut off the power supply
from AC outlet once and
turn it on after 5 seconds.
FILE NO. SVM-04001
Does the OPERATION lamp blink?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the indoor terminal
( 2 - 3 ) 220-240V?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the outdoor terminal
( 2 - 3 ) 220-240V?
YES
Is the wiring of solenoid coil for
4-way valve normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY04) or IC31
or IC30 is failure.
Correct cabling between indoor
and outdoor units.
Cables between indoor
and outddor units are defective.
Solenoid coil is defective.
Replace the P.C.
board.
4-way valve is defective.
59
Page 62
9-5-7. Only the indoor fan does not operate
<Check procedure>
Heat Pump Model
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-04001
Does the fan stop in
no operating status?
YES
Start the operation with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the bearing of
the fan.
Motor control circuit failure
(IC30, IC03, T01) or 12V power
circuit failure (D03, Q33).
Replace the P.C. board.
Replace the P.C. board.
NO
Thermal fuse operated
due to prevent
temperature rising cause
of incompleted connecting.
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
60
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 63
Cooling Model
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-04001
Does the fan stop in
no operating status?
YES
Start the operation with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to hight fan.
Does the fan speed
become higher?
YES
NO
NO
NO
Control P.C. board is defective.
Does AC 120V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow fan rotate normally?
YES
Turn on the power supply.
Operation
stops
NO
NO
Replace the P.C. board.
Does connecting
terminal, connecting
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the bearing of
the fan.
Motor control circuit failure
(IC30, IC03, TT-10) or 12V power
circuit failire (IC31).
Replace the P.C. board.
Thermal fuse operated
temperature rising cause
of incompleted connecting.
NO
due to prevent
Normal
Is the rotation signal (DC+5V-0V)
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating
the cross flow fan by hand in no
operating status?
(1 pulse/one turn)
YES
Replace the control
P.C. board.
61
NO
Replace the fan motor
Replace connecting
the cable (or power cord),
thermal fuse and
terminal block.
Page 64
FILE NO. SVM-04001
9-6. Troubleshooting for Remote Control (Including the Indoor P.C. Board)
There is no been from
Push the START/STOP button.
the indoor unit. The operation lamp of the air conditioner main unit does not light.
Is there direct
sunlight on the
receptor of the air
conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
YES
NO NO
Is operation possible
when setting the
temporary switch of the
air conditioner main unit
to "TEST RUN" or
"TEMPORARY AUTO"?
Does the transmission
indicator blink?
Is operation
possible when the
transmitter is moved nearer to the infrared sinnal receiver of the
air conditioner?
YES
Battery life
NO
Reset the remote control
by use the tip pencil push
in the RESET hole
Push the START/
STOP button
Dose the
transmission
indicator light?
YES
NO
Avoid direct
sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
YES
Can any signal tone
be heard in a trasistor
radio when transmitting
within 5 cm distance
from the radio?
YES
P.C. board is failure.
Replace
P.C. board
Note: After battery replacement, Shortcircuit the metal
terminal at the side of the battery comparment (all-clear terminal) with a pencil.
NO
Replace the
batteries
NO
Normal
Is there any
beep and
operation?
YES
Remote control
is failure.
Replace remote
control.
62
Page 65
FILE NO. SVM-04001
9-6-1 How to check the P.C. board
(1) Operating precautions
1) When removing the front panel or the P.C. board, be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.
3) When connecting or disconnecting the connec­tors on the P.C. board, hold the Whole housing. Do not pull at the lead wire.
(2) Inspection procedres
1) When a P.C. board is judged to be defective, check for disconnection, burning, or discolora­tion of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral circuits, buzzer drive circuit and buzzer.
b. Infrared rays receive and indication parts:
Infrared rays receiver unit and LED.
63
Page 66
(3) Checking procedure
Heat Pump Model
FILE NO. SVM-04001
Table 9-6-1
No.
1
Shut off the power supply and remove the P.C. board assembly from the electronic parts base. Remove the connecting cable from the terminal block.
2
Remove the connector for the motor, and turn the power on. If the OPERATION lamp blinks (0.5 sec. : ON, 0.5 sec. : OFF) when the power turning on, the checking points described as 1-4 of right column are not necessary to perform.
3
Make the operation status by pushing once the START/STOP button, except the status of [FAN ONLY], [ON TIMER].
4
Start the operation with the system which the time of the restart delay timer is shortened.
Procedure
Check Point (Symptom) Causes
1.Is the fuse blown?
Voltage check
1.Between
(AC 220~240V)
2.Between + and of C02
(DC 310 ~ 340V)
3.Between
4.Between 12V and GND
Voltage check
1.Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GND Between pin 11 of IC31 and GND
2.Between No. 1 and 2 of connect­ing cable terminal block.
(AC 220~240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
TP1 and TP2
5V and GND
1.•Application of shock voltage.
Overload by short-circuit of the parts.
1.•AC power cord is defective.
Poor contact of the terminal plate.
Miss wiring of the power relay.
2.Capacitor (C01, C15) is defective.
Line filter (L01) is defective.
Resistor (R01) is defective.
Diode (DB01) is defective.
3.Q01, T01, F03 are defective.
4.Q01, T01, F02, Q29, IC03 are defective.
1.Breaking wire of the relay coil, defective relay driver. (IC31)
2.Poor contact of relay.
Defective indicator, or poor
}
housing assembly. (CN13)
5
Make the operation status by pressing once the START/STOP button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
6
The status of No. 5 is continued, and make the following condition.
1.Heat operation
2.Make the setting temperature higher enough than room temperature.
7
Turn the power on after connecting the motor connector. Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key operation is accepted.)
2.The Motor rotates, but it vibrates too much.
1. The temperature of the indoor heat exchanger is abnomally lower.
2. Poor contact of the heat exchanger sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main P.C. board are defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.Main P.C. board is defective.
1.The temperature of the heat exchanger is abnormally high.
2.The heat exchanger sensor connector has short-circuit. (CN01)
3.The heat exchanger sensor is defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.P.C. board is defective.
1.Poor contact of the motor connector.
2.P.C. board is defective.
64
Page 67
Cooling Model
FILE NO. SVM-04001
Table 9-6-2
No.
1
Shut off the power supply and remove the P.C. board assembly from the electronic parts base. Remove the connecting cable from the terminal block.
2
Remove the connector for the motor, and turn the power on. If the OPERATION lamp blinks (0.5 sec. : ON, 0.5 sec. : OFF) when the power turning on, the checking points described as 1-4 of right column are not necessary to perform.
3
Make the operation status by pushing once the START/STOP button, except the status of [FAN ONLY], [ON TIMER].
4
Start the operation with the system which the time of the restart delay timer is shortened.
Procedure
Check Point (Symptom) Causes
1.Is the fuse blown?
Voltage check
1.Between 3 of RY01 and CN31 (AC 220~240V)
2.Between + and of C50 (DC 12 ~ 16V)
3.Between
4.Between 12V and GND
Voltage check
1.Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GND Between pin 11 of IC31 and GND
2.Between No. 1 and 2 of connecting cable terminal block.
(AC 220~240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
5V and GND
1.Application of shock voltage.
Overload by short-circuit of the
parts.
1.A C power cord is defective.
P oor contact of the terminal plate.
Miss wiring of the power relay.
2.Capacitor (C01, C15) is defective.
Line filter (L01) is defective.
Diode (DB01) is def
3. IC61 are defective.
4.IC51 are detective.
1.Breaking wire of the relay coil, defective relay driver. (IC31)
2.Poor contact of relay.
Defective indicator, or poor
}
housing assembly. (CN14)
ective.
5
Make the operation status by pressing once the START/STOP button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
6
The status of No. 5 is continued, and make the following condition.
1.Heat operation
2.Make the setting temperature higher enough than room temperature.
7
Turn the power on after connecting the motor connector. Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key operation is accepted.)
2.The Motor rotates, but it vibrates too much.
1. The temperature of the indoor heat exchanger is abnormally lower.
2. Poor contact of the heat exchanger sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main P.C. board are defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.Main P.C. board is defective.
1.The temperature of the heat exchanger is abnormally high.
2.The heat exchanger sensor connector has short-circuit. (CN01)
3.The heat exchanger sensor is defective. (Refer to Table 9-6-2 for the judgment of defective resistance values.)
4.P.C. board is defective.
1.Poor contact of the motor connector.
2.P.C. board is defective.
65
Page 68
FILE NO. SVM-04001
17
Table 9-6-3 Approximate resistance value of thermo sensor
Temperature 0°C 10°C 20°C 25°C 30°C
Resistance value 33.8 20.35 12.59 10.00 7.99
9-6-3. How to shorten time of restart delay timer
1 Press [CLR] button while pressing [CHECK] button
with a tip of a pencil.
2 Then press [START/STOP] button to transmit the
signal to the indoor unit.
AUTOA
A B
(kΩ)
PRESET
START/STOP
ECO
AUTO
Hi-POWER
MEMO
CLOCK CHECKRESET
FAN MODE
SWING
TIMER
FIX
ON
OFF SET CLR
FILTER
9-6-4. How to set/cancel the self cleaning function
The self cleaning function is set from a factory. To cancel this function, should keep press the
temporary switch for 20 seconds till can hear the long combination sound and repeat the sane
procedure when need to set.
2
1
17
66
Page 69
FILE NO. SVM-04001

10. PART REPLACEMENT

10-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
2 Electrical part
How to remove the front panel
1) Stop the operation of the air conditioner and turn off its main power supply.
2) Pull the air inlet grille toward you to open it and remove the air inlet grille. Then remove the 4 screws fixing the front panel.
3) First open the horizontal louver, and then remove the front panel from the back body by pulling it toward you.
How to mount the front panel
Push the front panel back in and make sure all hooks are locked.
How to remove the electrical part.
1) Remove the front panel with procedure 1.
2) Remove the screw holding the electrical part cover.
3) Remove the drain guide.
4) Disconnect the 2 connectors (3P) for the fan motor and the connector (5P) for the louver motor from the P.C. board assembly.
5) Pull out the TC sensor from the sensor holder.
6) Remove the screw for the ground connection, remove the 2 screws for the electrical part box and remove the screw from the LED unit. Then remove the LED unit and the electrical part box from the main unit.
How to mount the electrical part.
1) To put back the electrical part box, lock it to the upper hook of the back body.
2) Tighten the screws on the electrical part box.
3) Connect the 3 connectors and arrange the wiring same as original condition and then tighten the screw from the LED unit to the back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Assemble the drain guide (the TC sensor wire should be covered by the drain guide).
7) Tighten the screw on the electrical part cover.
2
6 Screw
2
2
2 4-Screws
3
2 Screws
3 Drain guide
5 TC Sensor
4
3-Connectors
6 Screw
3 Horizontal
louver
1) Remove the front panel and the electrical part following procedure 2.
2) Remove the center shaft of the horizontal louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back body.
67 −
3 Left shaft
2 Center shaft
Page 70
FILE NO. SVM-04001
No. Part name Procedures Remarks
4 Heat exchanger
5 Cross flow fan
1) Remove the front panel, electrical part and the horizontal louver following procedure 3.
2) Remove the pipe holder at the rear side of main unit.
3) Remove the 2 screws on the heat exchanger at the base bearing.
4) Remove the 2 screws on the heat exchanger at the 2 fixed plates (upper and lower) from the back body, and then pull out the upper side of the heat exchanger slowly.
1) Remove the front panel, electrical part, horizontal louver and the heat exchanger following procedure 4.
2) Remove the 2 screws on the band motor (L) and remove the 2 screws on the band motor (R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan then separate the fan and the fan motor.
Notice To assemble cross flow fan and fan motor to the unit, please turn the fan motor unit the center of its terminal meets the lowest point of band motor (R) (point A).
Fix the cross flow fan with the set screw at the position where the gap between the back body and the right surface of the cross flow fan is 6 mm.
2 Pipe holder
3
2-Screws
4
2-Screws
2
2-Screws
(R)
2 2-Screws (L)
6 mm
6 Set screw
Middle of the fan motor terminal
6 Base bearing
1) Remove the front panel, electrical part, horizontal louver, heat exchanger and the cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base bearing.
3) Remove the bearing from the base bearing. If the housing protrudes from the base bearing, put the housing in position and attach the bearing to the base bearing.
68
2
2-Screws
Page 71
FILE NO. SVM-04001
10-2. Outdoor Unit
No. Part name Procedures Remarks
1 Common
procedure
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove packed valve cover and Electric parts cover. (3-Screws 4 x 10L)
3) Remove the cord clamp (2-Screws 4 x 22L) and disconnect the connecting cable.
Remove the upper cabinet (4-Screws 4 x 10L)
4) Pulling out upword.
5) Remove the front cabinet. (3-Screws
4 x 10L) Pull the front right portion toward you, and remove it pulling out upward.
Cord clamp
2-Screws Ø4 x 22L
Electric parts cover
3-Screws Ø4 x10L
Packed valve cover
Upper cabinet
69
Front cabinet
Page 72
FILE NO. SVM-04001
No. Part name Procedures Remarks
2 Capacitor for
compressor
3
Capacitor for fan motor
1) Perform the common procedure
2) Remove the fixing screw and the capacit band.
(1-Screw 4 x 8L for 10k, 13k)
(1-Screw 4 x 10L for 07k)
3) Disconnect the lead wires.
1) Perform the common procedure
2) Remove the fixing screw (1-Screw 4 x 10L)
3) Disconnect the lead wires.
1
.
1
.
Screws 4 x 8L
or
Capacitor for fan motor
Capacitor band
RAS-10K, 13K
Screws 4 x 10L
Capacitor
for compressor
Screws Ø4 x10L
Capacitor for
Compressor
Capacitor band
Capacitor for
fan motor
Screws 4 x10L
RAS-07K
70
Page 73

11. EXPLODED VIEWS AND PARTS LIST

11-1. Indoor Unit (E-Parts Assy)
(For Heat pump model)
FILE NO. SVM-04001
Location Part
No. No.
401 43T60001 Terminal Block, 2P
402
403
43T60002 Terminal Block, 3P
43T69371 TC Sensor
10kΩ 25°C 404 405
43T69005 43T69079
Sensor, Thermostat 10k 25°C
.C.
P
Board ASSY,
Description
WRS-LED MCC-861
Location Part
No. No.
406 43T69364 Fuse, Temperature, 73°C
410 43T62003 Cord Clamp
411 411
71
43T69384
43T69385
Description
P.C. Board (RAS-10UKHP-ES3/AS3)
P.C. Board (RAS-13UKHP-ES3/AS3)
Page 74
11. EXPLODED VIEWS AND PARTS LIST
Indoor Unit (E-Parts Assy)
(For Cooling model)
FILE NO. SVM-04001
Location Part
No. No.
402 43T60002 Terminal Block, 3P
43T69371 TC Sensor
403
10kΩ 25°C
404 405
43T69005 43T69079
Sensor, Thermostat 10k 25°C
.C.
Board ASSY,
P
MCC-861
Description
WRS-LED
Location Part
No. No.
406 43T69364 Fuse, Temperature, 73°C
410 43T62003 Cord Clamp
411 411 411
412
72
43T69365 43T69366
43T69367 43T69361
Description
P.C. Board (RAS-07UKP-ES3)
P.C. Board (RAS-10UKP-ES3/AS3) P.C. Board (RAS-13UKP-ES3/AS3)
Transformer
Page 75
11-2. Indoor Unit
FILE NO. SVM-04001-(1)
Location Part
No. No.
201 43T00391 Front Panel Assy 202 43T09326 Inlet Grille Assy 203 43T03302 Back Body Assy 204 43T80301 Air Filter 205 43T09328 Horizontal Louver 206 43T08392 LED Panel Assy
(For Heat pump model)
206 43T08393 LED Panel Assy
(For Cooling only model)
207 43T70002 Drain Hose 208 43T79301 Cap Drain
209 43T21321 Motor, Louver, MP24Z, DC 12V
210
210 43T44322
210
212 43T47005
212 43T47016
213 43T49009 214 43T11301 214 215 216 217 218
43T44321 Refrigeration Cycle Assy
(For 07 Series) Refrigeration Cycle Assy
(For 10 Series)
43T44325
211 43T47006
43T11302 Pipe Shield (For 13 Series) 43T19302 Holder Sensor 43T49302 Plate of EVA Seal 43T49006 Holder, Plate EVA Seal 43T79302 Guide Drain
Refrigeration Cycle Assy (For 13 Series) Pipe, Delivery 6.35
Pipe, Suction 9.52 (For 07,10 Series) Pipe, Suction 12.7 (For 13 Series)
Spring Pipe Shield (For 07,10 Series)
Description
Location Part
No. No.
219 43T22002
220 221 222 223
224 225 226
226
227 228
228
228
228
229 230 230 231 233 234
73
Description
Bearing
43T39301 Base, Bearing 43T20302 Cross Flow Fan 43T39302 Band Motor-L
43T21338 Motor, Fan, SKF-220-20-4A-1,
AC 220-240V
43T39303 Band Motor-R 43T82301 Plate, Installation 43T69309 Remote Controller, Wireless
WH-H2UE (For Heat pump model)
43T69310 Remote Controller, Wireless
WC-H2UE (For Cooling only model) 43T83003 Holder Remote Controller 43T85410 Owner's Manual
(All model)
43T85411 Owner's Manual
(RAS-10,13UKHP-ES3, RAS-07,10,13UKP-ES3)
43T85412 Owner's Manual
(RAS-10,13UKHP-ES3, RAS-07,10,13UKP-ES3)
43T85413 Owner's Manual
(RAS-10,13UKHP-ES3, RAS-07,10,13UKP-ES3)
43T62302 Terminal Cover 43T60343 43T60342
Cord Power (For Heat pump model) Cord Power (For Cooling model)
43T60317 Cord Motor Louver 43T07303 Holder Pipe 43T01004 Mark
Page 76
11-3. Outdoor Unit (RAS-13UAH-ES3, RAS-13UAH-AS3)
FILE NO. SVM-04001
Location Part
No. No.
01 43T00368 Front cabinet assembly
02 43T03308 Back cabinet assembly 03 43T42310 Base cabinet assembly 04 43T00395 Upper cabinet assembly
05 43T09318 Guard fan
06 43T62311 Electrical part cover
07 43T20307 Fan propeller
08 43T21308 Motor fan (HF-240-42A)
09 43T47001 Nut flange
10 43T43337 Condenser assembly
11 43T46317 Valve packed 6.35 Dia
12 43T46318 Valve packed 12.7 Dia
13 43T47331 Bonnet, 6.35 Dia 14 43T47333 Bonnet, 12.7 Dia
Description
Location Part
No. No.
74
Description
15 43T03303 Fixing plate valve
16 43T47011 1.5ID
17 43T41321
43T47324 Bolt compressor(M6)
18
43T49008 Cushion rubber
19
20
43T52310 Packed valve cover assembly
21
43T55306 Capacitor Plastic film (30µF 370V)
22
43T55314 Capacitor Plastic film (1.5µF 450V)
23
43T60323 Terminal-4P
24
43T46319 4-Way Valve
25
43T46310 Coil V-4Way (AC220-240V 50Hz)
26 43T79305 Drain Nipple
29 43T47308 Capillary Tube 1.0ID
Capillary Tube
Compressor (PA150XT2-4FM1)
Page 77
11-4. Outdoor Unit (RAS-10UAH-ES3, RAS-10UAH-AS3)
FILE NO. SVM-04001
LocationPart
No. No.
0143T00368 Front cabinet assem bly
02 43T03306 Back cabinet assembly
03 43T42311 Base coat assembly
04 43T00396 Upper cabinet assembly
05 43T09318 Guard fan
06 43T62311 Electrical part cover
07 43T20307 Fan propeller
08 43T21323 Motor fan (HF-240-30B)
09 43T47001 Nut flange
10 43T43338 Condenser assembly
11 43T46317 Valve packed 6.35 Dia
12 43T46320 Valve packed 9.52 Dia
13 43T47331 Bonnet, 6.35 Dia
14 43T47332 Bonnet, 9.52 Dia
Description
Location Part
No. No.
75
Description
15 43T63303 Fixing plate valve
16 43T47007 1.2ID
17 43T41327
43T47325 Bolt compressor(M6)
18
43T49001 Cushion rubber
19
20
43T52310 Packed valve cover assembly
21
43T55305 Capacitor Plastic film (25µF 370V)
22
43T55314 Capacitor Plastic film (1.5µF 450V)
23
43T60323 Terminal-4P
24
43T46321 4-Way Valve
25
43T49307 Solinoid Coil
26 43T79305 Drain Nipple
29 43T47308 Capillary Tube 1.0ID
Capillary Tube
Compressor (PA108X1T-4FZ1)
Page 78
11-5. Outdoor Unit (RAS-13UA-ES3, RAS-13UA-AS3)
FILE NO. SVM-04001
Location Part
No. No.
01 43T00368 Front cabinet assembly
02 43T03308 Back cabinet assembly
03 43T42310 Base coat assembly 04 43T09318 Guard Fan 05 43T62311 Electric part cover 06 43T20307 Fan propeller 07 43T21323 08 43T47001 09 43T43336 10 43T46317 11 43T46318 12 43T47331
Motor fan (HF-240-30B)
Nut flange
Condenser assembly
Valve packed 6.35 Dia
Valve packed 12.7 Dia
Bonnet 6.35 Dia
Description
Location Part
No. No.
13 43T47333 Bonnet 12.7 Dia 14 43T63303 Finxing plate valve 15 43T47008 Capillary tube 1.5 Dia 16 43T41321 Compressor (PA150X2T-4FM1) 17 43T47327 Bolt compressor (M6) 18 43T49008 Cushion rubber 19 43T52310 Packed valve cover assembly 20 43T00395 Upper cabinet assembly
21 43T55306 Capacitor, Plastic film (30µF 370V)
22 43T55314 Capacitor, Plastic film (1.5µF 450V)
23 43T60322 Terminal 2P
76
Description
Page 79
11-6. Outdoor Unit (RAS-10UA-ES3, RAS-10UA-AS3)
FILE NO. SVM-04001
Location Part
No. No.
01 43T00368 Front cabinet assembly
02 43T03308 Back cabinet assembly
03 43T42311 Base coat assembly 04 43T09318 Guard Fan 05 43T62311 Electric part cover 06 43T20307 Fan propeller 07 43T21320 08 43T47001 09 43T43339 10 43T46317 11 43T46320 12 43T47331
Motor fan (HF-240-20B)
Nut flange
Condenser assembly
Valve packed 6.35 Dia Valve packed 9.52 Dia
Bonnet 6.35 Dia
Description
Location Part
No. No.
13 43T47332 Bonnet 9.52 Dia 14 43T63303 Finxing plate valve 15 43T47008 Capillary tube 1.5 Dia 16 43T41327 Compressor (PA108X1T-4FZ1) 17 43T47325 Bolt compressor (M6) 18 43T49001 Cushion rubber 19 43T52310 Packed valve cover assembly 20 43T00395 Upper cabinet assembly 21 43T55305 Capacitor, Plastic film (25µF 370V)
22 43T55314 Capacitor, Plastic film (1.5µF 450V)
23 43T60322 Terminal 2P
77
Description
Page 80
11-7. Outdoor Unit (RAS-07UA-ES3)
24
FILE NO. SVM-04001-(1)
20
23
01
25
03
13
02
12
04
22
15
08 , 09
14
06
05
19
07
10, 11
16
17
21
18
Location Part
No. No.
01 43T19313 Guard, Fan
02 43T20306 Fan, Propeller
03 43T00398 Front Cabinet Coating Assembly
04 43T43335 Condenser Assembly
05 43T62304 Electric Parts Cover
06 43T00397 Back Cabiinet Coating Assembly
07 43T47007 Capillary Tube 1.2 DIA
08 43T46320 Valve, Packed 9.52 DIA
09 43T47332 Bonnet, 9.52 DIA
10 43T46317 Valve, Packed 6.35 DIA
11 43T47331 Bonnet, 6.35 DIA 12 43T21323 Motor, Fan (HF-240-30B)
Description
Location Part
No. No.
13 43T47001 Nut, Flange
14 43T19312 Handle
15 43T49001 Cushion, Rubber
18 43T41309 Compressor, PA79X1T-4FZ5
19 43T62305 Packed Valve Cover
20 43T00394 Upper Cabinet Coating Assembly
21 43T63301 Fixing Plate Valve
22 43T42314 Base Coating Assembly
23 43T55310 Capacitor, Plastic Film, 15µF 370V
24 43T55314 Capacitor, Plastic Film, 1.5µF 450V
25 43T60322 Terminal-2P
78
07 : CAPILLARY TUBE
Description
Page 81
FILE NO. SVM-03001(1)
TOSHIBA CARRIER (THAILAND) CO.,LTD.
144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,
AMPHUR MUANG, PATHUMTHANI 12000,THAILAND.
– 72 –