Toshiba RAS-13UKP-ES, RAS-13UA-ES, RAS-07UA-ES, RAS-10UKP-ES, RAS-10UA-ES Service Manual

...
SERVICE MANUAL
AIR-CONDITIONER
SPLIT WALL TYPE
FILE NO. SVM-02005(2)
10/13 Class
Revised on January, 2005
07 Class
– 1 –
FILE NO. SVM-02005(1)
CONTENTS
1. SPECIFICATIONS
2. CONSTRUCTION VIEWS
2-1 Indoor Unit 2-2 Outdoor Unit (RAS-13UA-ES) 2-3. Outdoor Unit (RAS-10UA-ES) 2-4. Outdoor Unit (RAS-07UA-ES)
3. WIRING DIAGRAM
4. SPECIFICATION OF ELECTRICAL PARTS
4-1 Indoor Unit 4-2 Outdoor Unit (RAS-13UA-ES) 4-3 Outdoor Unit (RAS-10UA-ES, RAS-07UA-ES)
5. REFRIGERATION CYCLE DIAGRAM
5-1 RAS-13UKP-ES / RAS-13UA-ES 5-2 RAS-10UKP-ES / RAS-10UA-ES 5-3 RAS-07UKP-ES / RAS-07UA-ES
6. CONTROL BLOCK DIAGRAM
7. OPERATION DESCRIPTION
7-1 Outline of Air Conditioner Control 7-2 Description of Operation Circuit 7-3 Hi POWER Mode 7-4 High-Temperature Limit Control 7-5 Low-Temperature Limit Control 7-6 Auto Restart Function
7-7 Filter Check Lamp
8. INSTALLATION PROCEDURE
8-1 Safety Cautions 8-2 Installation Diagram of Indoor and Outdoor Units 8-3 Installation 8-4 Indoor Unit 8-5 Outdoor Unit 8-6 How to Set Remote Control Selector Switch 8-7 Others
9. TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure 9-2 Basic Check Items 9-3 Primary Judgement 9-4 Self-Diagnosis by Remote Control (Check Code) 9-5 Troubleshooting Flowcharts 9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board)
– 2 –
FILE NO. SVM-02005(1)
10. PARTS REPLACEMENT
10-1 Indoor Unit 10-2 Outdoor Unit (RAS-13UA-ES) 10-3 Outdoor Unit (RAS-10UA-ES) 10-4 Outdoor Unit (RAS-07UA-ES)
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy) 11-2 Indoor Unit 11-3 Outdoor Unit (RAS-13UA-ES) 11-4 Outdoor Unit (RAS-10UA-ES) 11-5 Outdoor Unit (RAS-07UA-ES)
This air conditioner is charged with HFC (R-410A) that doesn’t deplete the Ozone layer.
This air conditioner requires special installation for the refrigerant R-410A.
– 3 –
FILE NO. SVM-02005(1)
MODEL RAS-13UKP-ES RAS-10UKP-ES RAS-07UKP-ES
RAS-13UA-ES RAS-10UA-ES RAS-07UA-ES
ITEM Cooling
Capacity
220V 240V 220V 240V 220V 240V
kW 3.70 3.75 2.65 2.70 2.15 2.18
Phase 1
Power source V 220 – 240
Hz 50 Power consumption kW 1.25 1.29 0.77 0.83 0.66 0.68 Pow er factor % 98 95 92 92 97 90 Running Indoor A 0.15 current Outdoor A 5.66 5.53 3.65 3.60 2.95 3.00 Starting current A 24 16 12 Moisture removal lit/h 2.0 1.2 0.8
Noise
Indoor (H/M/L) dB 41/35/31 39/33/26 38/32/26 Outdoor (220-240V) dB 46 47 46 47 44 45
Refrigerant
Name of refrigerant R-410A Rated amount kg 0.86 0.65 0.65
Refrigerant control Capillary tube
Gas side size mm 9.52 Connection type Flare connection Liquid side size mm ∅6.35
Interconnection
Connection type Flare connection
pipe
Maximum length
m 15*
1
10*
1
(One way) Maximum height
m6 5
difference
INDOOR UNIT RAS-13UKP-ES RAS-10UKP-ES RAS-07UKP-ES
Height mm 275
Dimensions Width mm 790
Depth mm 208 Net weight kg 10 Evaporator type Finned tube Indoor fan type Cross flow fan
High fan m3/h 630 630 570 Air volume Medium fan m3/h 550 490 460
Low fan m3/h 460 370 340 Fan motor output W 30 Air filter Honeycomb woven filter with PP frame
OUTDOOR UNIT RAS-13UA-ES RAS-10UA-ES RAS-07UA-ES
Height mm 538 530 530 Dimensions Width mm 780 770 660
Depth mm 300 200 240 Net weight kg 39 29 27 Condenser type Finned tube Outdoor fan type Propeller fan Airflow volume m3/h 1700 1900 1500 1700 1420 1520 Fan motor output W 30
Compressor
Model PA150X2T-4FM PA98X1T-4FZ PA79X1T-4FZ5
Output W 1100 750 605 Safety device Fuse, Overload relay Louver type Automatic louver Usable outdoor temperature range °C 21 ~ 43
1. SPECIFICATIONS
– 4 –
FILE NO. SVM-02005(1)
Note : 1
Capacity is based on the following temperature conditions.
Note : 2
Charge refrigerant according to the table below.
Refrigerant RAS-13UKP-ES / RAS-13UA-ES
RAS-10UKP-ES / RAS-10UA-ES RAS-07UKP-ES / RAS-07UA-ES
*1 No need to charge
15m or less 10m or less
refrigerant
Temperature
Condition
JIS C9612-1994
Cooling
Indoor unit inlet air temperature
(DB) 27°C
(WB) 19°C
Outdoor unit inlet air temperature
(DB) 35 °C
(WB) 24 °C
– 5 –
FILE NO. SVM-02005(1)
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
Knock out system
Back body
Front panel
Air outlet
Air inlet
Air filter
Heat exchanger
Knock out system
660
275
790
208
48
48
26
4519040
32
64
590
320
620
235 235
215 215
9090
275
45
150150 160160
120 80
53
660
Hanger
Hanger
Hanger
Hanger
Hanger
Drain hose (0.54m)
Connecting pipe (0.43m) (Flare 6.35)
For stud bolt (8~10)
For stud bolt (6)
Installation plate outline
Center line
Minimum distance to ceiling
170 or more
Minimum distance to ceiling
170 or more
65 or more
Minimum distance to ceiling
Wireless remote control
57 18
160
Flare (9.52)
Connecting pipe (0.33m)
6
FILE NO. SVM-02005(1)
2-2. Outdoor Unit (RAS-13UA-ES)
538
325
325
52.5
23
301
325
300
Handle
25Drain outlet
Electric parts cover
Service port
61
54
325 (pitch)
(8.5)
(8.5)
342
100 or more
100 or more
600 or more
600 or more
Installation dimension
600
Air inlet
Air outlet
8-6 hole (for fixing outdoor unit)
Liquid side (Flare 6.35)
Gas side (Flare 9.52)
120
11x14 hole
6 hole
R10
600
Detail Drawing
50 36
A
A
4-11x14 hole (for 8-10 anchor bolt)
600
100
130
780
90
59
27
Fan guard
420
Z
View
Z
4x11x14 Long holes (for 8-10 anchor bolt)
7
FILE NO. SVM-02005(1)
2-3. Outdoor Unit (RAS-10UA-ES)
600 85
36
111
25 Drain hole
50
30
216
230
8-6 Holes (For fixing the outdoor unit)
4-11x14 Long holes (For anchor bolt 8-10)
Gas side (flare 9.52)
Liquid side (flare 6.35)
111
A
600
R10
50
36
25
216
230
11x14 Hole
6 Hole
Handle
11
525
530
5
268
Fan guard
420
770
59
89
200
11
12
Electric parts cover
Z
54 62
Access for charging
250
Z
View 600
45 or more
Air inlet
600 or more
(Minimum distance of the wall)
4-11x14 Long holes
400 or more
Air outlet
Center port
230
100 or more
Air inlet
Visible outline of the product
A
Detail Drawing
Mounting dimension of anchor bolt
268
770
59
89
(For anchor bolt 8-10)
8
FILE NO. SVM-02005(1)
2-4. Outdoor Unit (RAS-07UA-ES)
Z
Cover PV
54
273.5
59.5
420
500 97.5
(11)
297
(12.5)273.5 (pitch)
660
242
56
A Detail Drawing (Back Leg)
660
50 36
R 15
R 5.5
273.5
265
6 Hole
B Detail Drawing (Front Leg)
50
36
R 15
660
265
273.5
6 Hole
11x14 Hole
A
B
Z View
97
25Drain outlet
2-11x14 hole (for 8-10 anchor bolt)
Fan guard
530
Liquid side
(Flare 6.35) Gas side (Flare 9.52)
Service port
126
48
325
100 or more
100 or more
600 or more
600 or more
Installation dimension
600
Air inlet
Air outlet
4x11x14 Long holes (for 8-10 anchor bolt)
– 9 –
FILE NO. SVM-02005(1)
3. WIRING DIAGRAM
CN13
CN07
BLK
GRN&YEL
POWER TERMINAL BLOCK
POWER SUPPLY SINGLE PHASE 220-240V , 50 Hz
BRW
BLU
BLK
WHI
GRN&YEL
OUTDOOR TERMINAL BLOCK
INDOOR TERMINAL BLOCK
WHI
DSA
VARISTOR
RY01
4
3
F01
C15
L01
IC03
C58
R48
R46
R47
CR03
D38
C01 R01
DB01
POWER SUPPLY CIRCUIT
C02
DC 12V DC 5V
R21 VARISTOR
MAIN P.C. BOARD
MCC-862
T6.3A 250V
P04
SG01
CN04
INDOOR
OUTDOOR
1 2
1 2
CAPACITOR
CAPACITOR
RED
RED
RED
WHI
WHI
BLKCBLK
BLK
GRN & YEL CHASSIS
RED
FAN MOTOR
R
S
YEL
135
GRY
BRW
BLK
WHI
RED
CN01CN03
THERMO
SENSOR
(TA)
HEAT
EXCHANGER
SENSOR
(TC)
CN10CN11
AC FAN MOTOR
BLK
BLK
1
35
1
35
24 24
6 6
1
3
5
1
3
5
1
2
1
2
3 3
112
2
BLK
BLK
112
2
: : : : : : : : :
:
:
BROWN RED WHITE YELLOW BLUE BLACK GRAY PINK ORANGE GREEN & GREENGRN
YELLOW
BRW
RED
WHI YEL BLU BLK
GRY
PNK
ORN
GRN&YEL
COLOR IDENTIFICATION
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
WHI
YEL
CN25
PNK
PNK
YEL
YEL
YEL
WHI
INFRARED RAYS RECEIVE AND INDICATION PARTS
4 5 6 7 8 9
10 11
3
1
2
4 5 6 7 8 9
10 11
3
1
2
4 5 6 7 8 9
10 11
3
1
2
2 1
3
5
4
2 1
3
5
4
1
2
1
2
R22
N
L
Louver motor
GRN&YEL
– 10 –
FILE NO. SVM-02005(1)
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit
No. Parts name Type Specifications
1 Fan motor (for indoor) MMF-240-20-4A-1 AC Motor with 135°C thermo fuse 2 Thermo sensor (TA-sensor) ——— 10k at 25°C 3 Switching transformer (T01) SWT-47 4 Microcontroller unit (IC30) TMP87CM40AN-2C67 5 Heat exchanger sensor
——— 10k at 25°C
(TC-sensor) 6 Line filter (L01) LC*SS11V-06270 27mH, 600mA 7 Bridge rectifier (DB01) D3SBA60 4A, 600V 8 Capacitor (C02) KMH400VSSN47M22S 47µF, 400V 9 Fuse (F01) TSCR6.3A T6.3A, 250VAC
10 Varistor (R21, R22) 15G561K 560V 11 Resistor (R01) RF-2TK5R6 5.6, 2W 12 Louver motor MP24GA 12VDC 13 Relay (Comp., RY01) DI12D1 Rating 20A/AC250V, 12VDC
4-2. Outdoor Unit (RAS-13UA-ES)
No. Parts name Type Specifications
Output (Rated) 1100W , 2poles , 1 phase , 220 – 240V, 50Hz
1 Compressor PA150X2T-4FM Winding resistance (Ω) C-R C-S
(at 20°C) 2.49 3.95 Output (Rated) 30W, 6poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) HF-240-30B Winding resistance (Ω) Red-Black White-Black
(at 20°C) 245 388
3
Running capacitor
SK-50FMP1.5U2 AC 500V, 1.5µF
(for fan motor) 4
Running capacitor
DS371356CPNB AC 370V, 35µF
(for compressor)
– 11 –
FILE NO. SVM-02005(1)
No. Parts name Type Specifications
Output (Rated) 750W , 2poles, 1 phase, 220 – 240V, 50Hz
1 Compressor Winding resistance () C-R C-S
(at 20°C) 3.81 5.09 Output (Rated) 605W , 2poles, 1 phase, 220 – 240V, 50Hz Winding resistance (Ω) C-R C-S (at 20°C) 4.80 8.37 Output (Rated) 30W, 6poles, 1 phase, 220 – 240V, 50Hz
2 Fan motor (for outdoor) HF-240-30B Winding resistance (Ω) Red-Black White-Black
(at 20°C) 245 388
3
Running capacitor
SK-50FMP1.5U2 AC 500V, 1.5µF
(for fan motor)
DS371256CPNB
AC 370V, 25µF
4
Running capacitor (RAS-10UA-ES)
(for compressor) DS371156CPNB
AC 370V, 15µF
(RAS-07UA-ES)
4-3. Outdoor Unit (RAS-10UA-ES, RAS-07UA-ES)
PA98X1T-4FZ
(RAS-10UA-ES)
PA79X1T-4FZ5
(RAS-07UA-ES)
– 12 –
FILE NO. SVM-02005(1)
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Standard 0.95 10.0 High 27/19 35/24
Cooling Overload 1.15 13.0 High 32/23 43/26
Low temperature 0.65 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-13UKP-ES / RAS-13UA-ES
Heat exchanger
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan Outdoor unit
Capillary tube
1.5x900S
PA150X2T-4FM
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m (Connecting pipe) 9.52
0.49m (Connecting pipe) 6.35
T1
P
Refrigerant R-22 : 0.86 kg.
13
FILE NO. SVM-02005(1)
5-2. RAS-10UKP-ES / RAS-10UA-ES
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Standard 0.86 12.0 High 27/19 35/24
Cooling Overload 1.12 18.0 High 32/23 43/26
Low temperature 0.61 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PA98X1T-4FZ
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m (Connecting pipe) 9.52
0.49m (Connecting pipe) 6.35
T1
P
Refrigerant R-22 : 0.65 kg.
Evaporator
Capillary tube
1.5x1200S
14
FILE NO. SVM-02005(1)
5-3. RAS-07UKP-ES / RAS-07UA-ES
Note :
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
Standard 0.97 14.0 High 27/19 35/24
Cooling Overload 1.13 20.0 High 32/23 43/26
Low temperature 0.63 2.0 Low 21/15 21/15
50Hz
Fan speed
(indoor)
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
Standard
pressure P
(MPaG)
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
Indoor unit
Cross flow fan
Cooling
Cooling
Compressor
Condenser
Propeller fan
Outdoor unit
PA79X1T-4FZ5
Cooling
Mark( )means check points of Gas Leak.
O.D.:9.52mm O.D.:6.35mm
Cooling
Packed valve
(9.52)
Packed valve
(6.35)
0.39m (Connecting pipe) 9.52
0.49m (Connecting pipe) 6.35
T1
P
Refrigerant R-22 : 0.65 kg.
Evaporator
Capillary tube
1.2x650S
– 15 –
FILE NO. SVM-02005(1)
6. CONTROL BLOCK DIAGRAM
REMOTE CONTROL
Remote Control
Operation (START/STOP) Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
Infrared Rays
Heat Exchange sensor
Main Unit Control Panel M.C.U.
Functions
Operation
Display
Timer
Display
Filter Sign
Display
Hi Power
Sign Display
Fan Only
Sign Display
Indoor Fan
Motor
Louver
Motor
Louver
ON/OFF
Signal
Compressor
ON/OFF
Signal
Power Supply
Circuit
Noise Filter Relay Driver, Louver Driver
Relay
RY01
220-240 V~, 50Hz
Compressor, Outdoor Fan Motor
Initiallizing Circuit
Clock Frequency Oscillator Circuit
Louver Control
3-minutes Delay at Restart
for Compressor
Processing (Temperature Processing)
Motor Revolution Control
Timer
Thermo. Sensor
Infrared Rays Signal Reciver
– 16 –
FILE NO. SVM-02005(1)
7. OPERATION DESCRIPTION
7-1-1. Louver control
(1)Vertical air flow louver
Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button. The louver position which is set by [FIX] button is stored in the microcontroller, and the louver is automatically set at the stored position for the next operation.
(2)Swing
If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [FIX] button is pressed, it stops swinging.
7-1-2. Indoor fan control (AC fan motor)
(1)The indoor fan is operated by the stepless speed
change AC motor.
(2)For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
+
and HIGH). If AUTO mode is selected, the fan motor speed is automatically controlled by the difference between the preset temperature and the room temperature.
Table 7-1-1
7-1. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses a AC motor for an indoor fan. The AC motor drive circuit is mounted in the indoor unit. And electrical parts which operate the compressor and the outdoor fan motor, are mounted in the outdoor unit. The air conditioner is mainly controlled by the indoor unit controller. The controller operates the indoor fan motor based upon commands transmitted by the remote control and transfers the operation commands to the outdoor unit controller. The outdoor unit controller receives operation commands from the indoor unit, and operates the outdoor fan motor and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes them.
Temperature measurement at the air inlet of the indoor heat exchanger by the indoor temperature sensor
Temperature setting of the indoor heat exchanger by the heat exchanger sensor
Louver motor control
Indoor fan motor operation control
LED display control
Transferring of operation commands to the
outdoor unit
Receiving of information of the operation status and judging of the information or indication of error
LOW
+
=
MED+=
LOW+MED
2
MED+HIGH
2
RAS-13UKP-ES RAS-10UKP-ES RAS-07UKP-ES
Model Motor speed Air flow level Motor speed Air flow level Motor speed Air flow level
(rpm) (m3/h) (rpm) (m3/h) (rpm) (m3/h)
HIGH 1,300 630 1,300 630 1,200 570 Cooling MED+ 1,220 600 1,180 560 1,100 520 and MED 1,150 550 1,050 490 1,000 460 Fan only LOW+ 1,070 500 950 430 900 400
LOW 1,000 460 850 370 800 340
– 17 –
FILE NO. SVM-02005(1)
7-2. Description of Operation Circuit
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the power supply is cut off.)
(2) When pressing [START / STOP] button on the
remote control, receiving beep sounds from the indoor unit, and the next operation is performed together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation can be effected thereafter simply by pressing [START / STOP] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L–.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
(2) The Hi POWER operation cannot be set.
7-2-2. Cooling operation
([MODE] button on the remote control is set to the cooling operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as shown in Fig. 7-2-2.
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When [FAN] button is set to LOW, LOW+, MED, MED+ or HIGH, the motor operates with a constant air flow.
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed between M+ and L–.
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
+2
+2.5
+3
+1.5 +1 +0.5 0
M+
*1 *1 *1 L-
(Room temp.) (Preset temp.)
Preset temp.
0.5
0
Preset temp.
ON ON
OFFOFF ON
Compressor
Outdoor fan
OPERATION
display
(Room temp.) (Preset temp.)
*1 *1 *1
L-
+3 +2.5 +2 +1.5 +1 +0.5
-0.5
0
M+
(Room temp.) (Preset temp.)
Preset temp.
18
FILE NO. SVM-02005(1)
7-2-4. Automatic operation
([MODE] button on the remote control is set to the automatic operation.)
(1) One of 2 operations (Cooling, Fan only) is
selected according to difference between the preset temperature and the room temperature at which the automatic operation has started, as shown in Fig. 7-2-6. The Fan only operation continues until the room temperature reaches a level at which another mode is selected.
(2) Temporary Auto
When the TEMPORARY button on the indoor unit is pushed, the preset temperature is fixed at 24°C and the indoor unit is controlled as shown in Fig. 7-2-6.
Fig. 7-2-6
7-2-3. Dry operation
([MODE] button on the remote control is set to the dry operation.)
(1) The compressor, outdoor fan and operation
display on the remote control are controlled as shown in Fig. 7-2-4.
Fig. 7-2-4
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While the compressor is turning off, the indoor fan motor operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset temperatures is shown in Fig. 7-2-5.
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(4) The Hi POWER operations cannot be set.
Preset temp.
ON
+3
+2
+1
0
OFF
Outdoor fan
OPERATION
display
Compressor
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
(Room temp.)
(Preset temp.)
Room temp.
Preset temp.+1 Preset temp.
Compressor Outdoor fan
Indoor fan
L.*S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*
Super Low
+4
0
(Room temp.) – (Preset temp.)
°C
Cooling operation
The louver moves to the position same as Hi POWER operation.
Cooling operation
Fan only operation
RAS-13UKP-ES RAS-10UKP-ES RAS-07UKP-ES
19
FILE NO. SVM-02005(1)
7-3. Hi POWER Mode
([Hi POWER] button on the remote control is pressed.)
When [Hi POWER] button is pressed while the indoor unit is in Auto, Cooling, Hi POWER mark is indicated on the display of the remote control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the current operation.
(2) Cooling operation
The preset temperature drops 3°C. (The value of the preset temperature on the remote control does not change.)
If the difference between the preset temperature and the room temperature is big, the horizontal louver moves to the Hi POWER position automatically. Then when the difference between them gets smaller, the horizontal louver returns automatically.
FAN speed : [AUTO] If the difference between the preset temperature and room temperature is big, the air conditioner operates at maximum airflow level. If the difference between the preset temperature and the room temperature is small, the air conditioner operates at normal airflow level.
FAN speed : One of 5 levels The air conditioner operates at normal airflow level.
(3) The Hi POWER mode can not be set in Dry or Fan
only operation.
7-4. High-Temperature Limit Control
The microcontroller detects the indoor heat exchanger temperature to prevent pressure of a refrigerating cycle from increasing excessively. The compressor and outdoor fan motor are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
7-5. Low-Temperature Limit Contr ol
The microcontroller detects the indoor heat exchanger temperature to prevent the indoor heat exchanger from freezing. The compressor and outdoor fan motor are controlled as shown in Fig. 7-5-1 and 7-5-2.
RAS-13UKP-ES
Fig. 7-5-1
RAS-10UKP-ES ;RAS-07UKP-ES
Fig. 7-5-2
60
53 52
Compressor
Outdoor fan
OFF
OFF
ON
ON
OFF
ON
Heat exchanger temp.
6
2
Compressor Outdoor fan
ON
Less than continues
for 5 minutes
OFF
Heat exchanger temperature
7
5
Compressor
Heat exchanger temperature
Outdoor fan
ON
Less than continues
for 5 minutes
OFF