Toshiba RAS-10SKH-ES, SRAS-13SKH-ES, RAS-10SAH-E, RAS-13SAH-ES Service Manual

SERVICE MANUAL
AIR-CONDITIONER
SPLIT WALL TYPE
FILE NO. A00-9808
SUPPLEMENT
RAS-10SKH-ES RAS-13SKH-ES
/
RAS-10SAH-ES
/
RAS-13SAH-ES
PRINTED IN JAPAN, May.,1998 ToMo
– 2 –
CONTENTS
1. SPECIFICATIONS.......................................................................................................................... 3
2. CONSTRUCTION VIEWS .............................................................................................................. 5
2-1. Indoor Unit ........................................................................................................................................ 5
2-2. Outdoor Unit ..................................................................................................................................... 6
3. WIRING DIAGRAM ........................................................................................................................8
4. SPECIFICATIONS OF ELECTRICAL PARTS ............................................................................... 9
5. REFRIGERANT CYCLE DIAGRAM............................................................................................. 11
6. MICRO-COMPUTER BLOCK DIAGRAM ....................................................................................13
7. OPERATION DESCRIPTIONS..................................................................................................... 14
7-1. FAN ONLY Operation...................................................................................................................... 14
7-2. COOL Operation............................................................................................................................. 14
7-3. DR Y Operation................................................................................................................................ 15
7-4. HEAT Operation .............................................................................................................................. 16
7-5. AUTO Operation ............................................................................................................................. 17
7-6. ECONO. Mode................................................................................................................................. 18
7-7. Current Limit Control ..................................................................................................................... 18
7-8. High-T emperature Limit Control (Heating Operation) ................................................................. 19
7-9. Low-Temperature Limit Control (Cooling Operation) .................................................................. 19
7-10. Cool Airflow Prevention Contr ol (Heating Operation)................................................................. 19
7-11. Defrost Operation........................................................................................................................... 20
7-12. Auto Restart Function.................................................................................................................... 21
8. INSTALLATION PROCEDURE ....................................................................................................23
8-1. Safety Cautions .............................................................................................................................. 23
8-2. Installation Diagram of Indoor and Outdoor Units ...................................................................... 25
8-3. Installation ...................................................................................................................................... 26
8-4. Indoor Unit ...................................................................................................................................... 28
8-5. Outdoor Unit ................................................................................................................................... 34
8-6. Others.............................................................................................................................................. 37
9. TROUBLESHOOTING CHART....................................................................................................38
9-1. What to be Prechecked First ......................................................................................................... 38
9-2. Primary Judgement of Trouble Sources ....................................................................................... 40
9-3. Troubleshooting Flowcharts.......................................................................................................... 44
9-4. How to Check the Remote Contr ol (Including the Indoor P.C. Board)........................................ 50
10. PART REPLACEMENT................................................................................................................ 55
10-1. Indoor Unit ...................................................................................................................................... 55
10-2. Microcomputer ............................................................................................................................... 57
10-3. Outdoor Unit ................................................................................................................................... 58
11. CAUTIONS ON REPLACEMENT OF P.C. BOARD ASSEMBLY ................................................ 59
12. EXPLODED VIEWS AND PARTS LIST ....................................................................................... 61
12-1. Indoor Unit (1)................................................................................................................................. 61
Indoor Unit (2)................................................................................................................................. 63
Indoor Unit (3)................................................................................................................................. 65
12-2. Outdoor Unit ................................................................................................................................... 66
• This air conditioner is charged with HFC (R-410A) that doesn't deplete the Ozone layer.
• This air conditioner requires special service tools for the refrigerant R-410A.
– 3 –
1. SPECIFICATIONS
Model
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
A Running current
Indoor/Outdoor
Starting current A Moisture removal lit/h
Indoor (H/M/L) dB
Noise
Outdoor (220/230/240V) dB
Refrigerant
Name of refrigerant Rated volume kg
Refrigerant control
Gas side size mm Connection type Liquid side size mm
Interconnection
Connection type
pipe
Maximum length
m *2
(One way) Maximum height difference
Indoor unit
m
Outdoor unit
Condensate drain
Outer diameter mm
pipe
INDOOR UNIT
Height mm
Dimensions Width mm
Depth mm Net weight kg Evaporator type Indoor fan type
High fan m3/h Air volume Medium fan m3/h
Low fan m3/h Fan motor output W Air filter
OUTDOOR UNIT
Height mm Dimensions Width mm
Depth mm Net weight kg Condenser type Outdoor fan type Airflow volume m3/h Fan motor output W
Compressor
Model
Output W Safety device Auto louver Usable outdoor temperature range °C
RAS-10SKH-ES/RAS-10SAH-ES RAS-13SKH-ES/RAS-13SAH-ES
Cooling Heating Cooling Heating
220V 230V 240V 220V 230V 240V 220V 230V 240V 220V 230V 240V
2,65 2,68 2,70 3,00 3,05 3,10 3,45 3,50 3,50 4,0 4,05 4, 1
Single
220/230/240
50
0,98/0,99/1,02 0,89/0,90/0,91 1,26/1,28/1,30 1,19/1,23/1,27
98/95/93 95/93/90 98/97/94 97/96/93 220V 230V 240V 220V 230V 240V 220V 230V 240V 220V 230V 240V 0,11/ 0,11/ 0,11/ 0,11/ 0,11/ 0,11/ 0,15/ 0,15/ 0,15/ 0,15/ 0,15/ 0,15/
4,44 4,42 4,46 4,15 4,10 4,10 5,70 5,59 5,61 5,43 5,42 5,54
19 25
1,2 2,0
41/36/31 44/39/36 47/48/49 49/50/51
R-410A
0,69 0,8
Capillary tube
9,52
Flare connection
6,35
Flare connection
10 15
56
16
RAS-10SKH-ES RAS-13SKH-ES
265 790 174
8
Finned tube
Cross flow fan 600 650 500 560 400 510
19
Polypropylene net filter (Washable)
RAS-10SAH-ES RAS-13SAH-ES
530 538 770 780 200 300
31 42
Finned tube
Propeller
1600 1700
18 28
PA118X1T-4FZ PA160X2T-4FM
750 1100
Fuse, Overload relay
Yes
21 ~ 43 – 5 ~ 21 21 ~ 43 – 5 ~ 21
Specifications are subject to change without notice.
– 4 –
Note : *1
• Capacity is based on the following temperature conditions.
Cooling
27°C 19°C 35°C 24°C
Heating
20°C 12°C 7°C 6°C
JIS C9612-1994Condition
(DB)
(WB)
(DB)
(WB)
T emperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Notes : *2 CHARGELESS
RAS-10SKH-ES
• No additional refrigerant required.
• This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
• There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
RAS-13SKH-ES
• No additional refrigerant required.
• This air conditioner accepts a connection piping length of up to 15m and a head of up to 6m.
• There is no need to add the refrigerant as long as the total length of the connection piping is up to 15m.
– 5 –
2. CONSTRUCTION VIEWS
2-1. Indoor Unit
RAS-10SKH-ES RAS-13SKH-ES
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
Air filter
790
Heat exchanger
Air inlet
265
Air outlet
47
10
50
174
47
10
50
Wireless remote control
55
16
559,6
Remote control holder
112,8
136
Knock out system
790
232 326 232
Hanger
321
Drain hose (0,54m)
Connecting pipe (0,39m)
(Flare ø6,35)
(Flare ø9,52)
Hanger
65965,5
326
450
65,5
For stud bolt (ø8~ø10)
For stud bolt (ø6)
Hanger
Minimum distance to wall
Minimum distance to ceiling
265
Knock out system
Front panel
Back body
20 2037
40,5
60,5
790
12626931976
Center line
Installation plate outline
HangerHanger
40,5
3,5
Hanger
Minimum distance to wall
17 20
46
120 or more 120 or more
66 or more
2,5
Connecting pipe (0,49m)
– 6 –
2-2. Outdoor Unit
RAS-10SAH-ES
600 85
36
111
ø25 Drain hole
50
30
216
230
8-ø6 Holes (For fixing the outdoor unit)
4-ø11x14 Long holes (For anchor bolt ø8-ø10)
Gas side (flare ø9,52)
Liquid side (flare ø6,35)
111
A
600
R10
50
36
25
216
230
ø11x14 Hole
ø6 Hole
Handle
11
525
530
5
268
Fan guard
ø420
TOSHIBA
770 59
89
200
11
12
Electric parts cover
Z
54 62
Service port
250
Z
View
600
45 or more
Inlet port
600 or more
(Minimum distance of the wall)
4-ø11x14 Long holes
(For anchor bolt ø8-ø10)
200 or more
Outlet port
Center port
230
100 or more
Inlet port
Visible outline of the product
A
Detail Drawing
Mounting dimension of anchor bolt
268
770
59
89
– 7 –
RAS-13SAH-ES
538
325
325
52,5
23
301
325
300
Handle
ø25Drain outlet
Electric parts cover
Service port
61
54
325 (pitch)
(8,5)
(8,5)
342
100 or more
100 or more
600 or more
600 or more
Installation dimension
600
Air inlet
Air outlet
8-ø6 hole ( (for fixing outdoor unit)
Liquid side (Flare ø6,35)
Gas side (Flare ø9,52)
120
ø11x14 hole
ø6 hole
R10
600
Detail Drawing
50 36
A
A
6-ø11x14 hole (for ø8-ø10 anchor bolt)
600
100
130
780
90
65,5
27
Fan guard
ø420
Z
View
Z
4xø11x14 Long holes (for ø8-ø10 anchor bolt)
– 8 –
3. WIRING DIAGRAM
1
2
3
4
56789
1
2
3
4
56789
1
23
4
56789
1
2
1
2
1
2
1
2
L N
1
2
3
4
44
3
2
11
1
2
3
4
6
5
IC
FAN MOTOR
BLK
WHI
PNK
WHI
BLK
BLU
RED
SOLENOID
COIL
RED
RUNNING
CAPACITOR
RUNNING
CAPACITOR
BLK
GRN & YEL
CHASSIS
INDOOR
OUTDOOR
BLK
WHI
RED
BLU
GRN&YEL
CN27
GRN&YEL
P04
BLK
BRW
BLU
PNK
YEL
ORN
RED
BRW
GRY
GRY
BLU
CN04
CN07
CN10
BLU
CN03 CN01
CN13
CN25
BLK
BLK
BLK
BLK
IC01
IC02
C06
DC35V
DC12V
DC7V
DC0V
T01
MAIN P.C. BOARD
MCC-713
C02
DB01
R01
C01
L01
C15
IC04
R109
F01 FUSE
T3,15A
250V
R21
RY01
RY02
WHI
BLK
3
4
3
4
T02 C.T.
RY03
RY04
POWER
TERMINAL
BLOCK
INDOOR
TERMINAL
BLOCK
INFRARED RAYS RECEIVE
AND INDICATION PARTS
THERMO SENSOR
(TA)
HEAT
EXCHANGER
SENSOR
(TC)
LOUVER
MOTOR
FAN MOTOR
: : : : : : : : : :
BROWN RED WHITE YELLOW BLUE BLACK GRAY PINK ORANGE GREEN &
YELLOW
BRW
RED
WHI YEL BLU BLK
GRY
PNK
ORN
GRN&YEL
COLOR IDENTIFICATION
THERMAL FUSE
77˚C × 2
VARISTOR
3
1
1
2
3
4
6
5
1
2
3
4
5
1
2
3
4
5
3
1
DC
MOTOR
SG01
DSA
CR01
CR02
BLU
BLU
BLU
BLU
BLU
PNK
BLK
WHI
R116
RAS-10SKH-ES/10SAH-ES
220/230/240V ~
50Hz
RAS-13SKH-ES/13SAH-ES
220/230/240V ~
50Hz
L N
Model Section A
1
2
3
4
COMPRESSOR
DSA : Surge absorber C.T : Current trans
BLU
RED
BLU
YEL
BLK
RED
WHI
– 9 –
4. SPECIFICATIONS OF ELECTRICAL PARTS
4-1. Indoor Unit
RAS-10SKH-ES
No. Parts name Type Specifications
1 Fan motor (for indoor) TICF-35-19-3 Output (Rated) 19W, 2poles, 1phase, 220/230/240V, 50Hz
2
Thermo sensor
(microprocessor) 10k at 25°C
(TA-sensor) 3 DC-DC transformer (T01) SWT-34 DC 390V, Secondary DC 35V, 12V, 7V 4 Microcomputer TMP87CK40F
5
Power relay (RY01),
DI1U Coil : DC 12V 75mA, Rated AC 250V 20A
Common relay (RY02)
6
Heat exchanger sensor
(microprocessor) 10k at 25°C
(TC-sensor) 7 Line filter (L01) RF-103YOR6 10mH, AC 0,6A 8 Diode (DB01) RBV-406 4A, 600V 9 Capacitor (C02) CEAUF2W101M20 100µF, 450V
10 Fuse (F01) MT3 T3,15A, 250V
11
Relay (for outdoor fan motor,
AJQ1341 Coil DC 12V, 33mA, Rated 1A, AC 250V
solenoid coil) (RY03, RY04)
12 Power supply IC (IC01) MA2830-FJ 4A, 600V 13 Varistor (R21, 109) 15G561K 560V 14 Resistor (R01) ERF-5TK5R6 5,6 Ω, 5W 15 Current trans (T02) CT422920S-01 16 Louver motor MP35EA7 Output (Rated) 2W, 10poles, 1phase, DC 12V
4-2. Outdoor Unit
RAS-10SAH-ES
No. Parts name Type Specifications
Output (Rated) 750W, 2poles, 1phase, 220/230/240V, 50Hz
1 Compressor PA118X1T-4FZ
Winding resistance (Ω)
Red-Black White-Black
(at 20°C)
3,17 5,18
Output (Rated) 18W, 6pole, 1phase, 220/230/240V, 50Hz
2 Fan motor (for outdoor) UE6-21SJ5P
Winding resistance (Ω)
Red-Black White-Black
(at 20°C)
370 370
3
Running capacitor
SK-50CMP AC 500V, 1,5µF
(for fan motor)
4
Running capacitor
SK-40CMP25U1 AC 400V, 25µF
(for compressor)
5
Solenoid coil
VAV-01A1501A1 AC 200/240V
(for 4-way valve)
– 10 –
No. Parts name Type Specifications
1 Fan motor (for indoor) TICF-35-19-3 DC 35V, 19W
2
Thermo sensor
(microprocessor) 10k at 25°C
(TA-sensor) 3 DC-DC transformer (T01) SWT-34 DC 390V, Secondary DC 35V, 12V, 7V 4 Microcomputer TMP87CK40F
5
Power relay (RY01),
DI1U Coil : DC 12V 75mA, Rated AC 250V 20A
Common relay (RY02)
6
Heat exchanger sensor
(microprocessor) 10k at 25°C
(TC-sensor) 7 Line filter (L01) RF-103YOR6 10mH, AC 0,6A 8 Diode (DB01) RBV-406 4A, 600V 9 Capacitor (C02) CEAUF2W101M20 100µF, 450V
10 Fuse (F01) MT3 T3,15A, 250V
11
Relay (for outdoor fan motor,
AJQ1341 Coil DC 12V, 33mA, Rated 1A, AC 250V
solenoid coil) (RY03, RY04)
12 Power supply IC (IC01) MA2830-FJ 4A, 600V 13 Varistor (R21, R109) 15G561K 560V 14 Resistor (R01) ERF-5TK5R6 5,6 Ω, 5W 15 Current trans (T02) CT422920S-01 16 Louver motor MP35EA7 Output (Rated) 2W, 10poles, 1phase, DC 12V
No. Parts name Type Specifications
Output (Rated) 1100W, 2poles, 1phase, 220/230/240V, 50Hz
1 Compressor PA160X2T-4FM
Winding resistance (Ω)
Red-Black White-Black
(at 20°C)
2,26 3,53
Output (Rated) 28W, 6poles, 1phase, 220/230/240V, 50Hz
2 Fan motor (for outdoor) AF-230-28P
Winding resistance (Ω)
Red-Black White-Black
(at 20°C)
198 160
3
Running capacitor
SK-50FMP AC 500V, 1,5µF
(for fan motor)
4
Running capacitor
SK-40CMP35U1 AC 400V, 35µF
(for compressor)
5
Solenoid coil
VHV-01A1501A1 AC 200/240V
(for 4-way valve)
4-3. Indoor Unit
RAS-13SKH-ES
4-4. Outdoor Unit
RAS-13SAH-ES
– 11 –
Standard pressure Surface temp. of heat
P exchanger interchanging Fan speed
50Hz (MPaG) pipe T1 (°C) (indoor)
RAS-10SKH-ES RAS-10SKH-ES
Standard 2,5 40,0 High
Heating High temperature*1 3,1 ~ 3,6 51,0 ~ 58 Low
Low temperature 2,2 36,0 High Standard 0,9 10,0 High
Cooling High temperature 1,1 16,0 High
Low temperature 0,6 2,0 Low
5. REFRIGERANT CYCLE DIAGRAM
RAS-10SKH-ES/RAS-10SAH-ES
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*
1 • During heating overload, the high temperature limit control operation is included.
Evaporator
Indoor unit
Cross flow fan
Cooling
Heating
4-way valve
Heating
Cooling
Compressor
Accumulator
Condenser
Propeller fan Outdoor unit
Dryer
Capillary tube
ø0,8x400
PA118X1T-4FZ
Cooling Heating
Mark( )means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve
(ø9,52)
Packed valve
(ø6,35)
0,39m (Connecting pipe) ø9,52
0,49m (Connecting pipe) ø6,35
T1
P
Refrigerant R-410A 0,69kg
Capillary tube
ø1,2x400
Muffler
Muffler
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
20/– 7/6 27/– 21/15
20/– –10/–10 27/19 35/24 32/23 43/26 21/15 21/15
– 12 –
RAS-13SKH-ES/RAS-13SAH-ES
Heat exchanger
Indoor unit
Cross flow fan
Gas container connection (Reinstall etc.)
Heating
4-way valve
Heating
Cooling
Compressor
Condenser
Propeller fan Outdoor unit
Capillary tube
ø1,5x500
Cooling
Cooling
Mark ( ) means check points of Gas Leak
O.D.:9,52mm O.D.:6,35mm
Cooling
Heating
Packed valve
(ø9,52)
Packed valve
(ø6,35)
0,49m (Connecting pipe) ø9,52
0,39m (Connecting pipe) ø6,35
(Note) Maximum pipe length is 15m Maximum pipe head is 6m
T1
P
Capillary tube
ø1,2x1200
Heating
Refrigerant R-410A 0,80kg
PA160X2T-4FM
Muffler
Dryer
Standard pressure Surface temp. of heat
P exchanger interchanging Fan speed
50Hz (MPaG) pipe T1 (°C) (indoor)
RAS-13SKH-ES RAS-13SKH-ES
Standard 2,7 43,0 High
Heating High temperature*1 3,2 ~ 3,6 52,0 ~ 57,0 Low
Low temperature 2,0 30,0 High Standard 0,9 11,0 High
Cooling High temperature 1,0 14,0 High
Low temperature 0,6 2,0 Low
Ambient temp.
conditions DB/WB
(°C)
Indoor Outdoor
20/– 7/6
27/– 21/15
20/– –10/–10 27/19 35/24 32/23 43/26 21/15 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
*
1 • During heating overload, the high temperature limit control operation is included.
– 13 –
6. MICRO-COMPUTER BLOCK DIAGRAM
Infrared Rays Signal Receiver
Current Sensor
Thermo. Sensor
Functions
• Louver Control
• 3-minutes Delay at Restart for Compressor
• Motor Revolution Control
• Processing
(Temperature Processing)
• Timer
ECONO.
Louver Direction Setting
Louver AUTO Swing
OFF TIMER Setting
ON TIMER Setting
Fan Speed Selection
Thermo. Setting
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Operation (START/STOP)
Relay Driver, Louver Driver
Clock Frequency
Oscillator Circuit
Heat Exchanger Sensor
Infrared
Rays
Initializing Circuit
C. P. U
Main Unit Control Panel
AC 220/230/240V ~
50Hz
Remote Control
Operation
Display
Timer
Display
ECONO.
Sign Display
PRE-DEF.
Sign Display
Indoor
Fan Motor
Louver
ON/OFF Signal
4-Way Valve
ON/OFF Signal
Outdoor Fan
ON/OFF Signal
Compressor
ON/OFF Signal
RelayRelayRelay
4-Way ValveOutdoor Fan Motor
Louver
Motor
Compressor
(Compressor Current)
Relay
RY02
RY01 RY03 RY04
Noise Filter
Power Supply
Circuit
– 14 –
7. OPERATION DESCRIPTIONS
7-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY) (1) During this mode, the relay R Y01 is alw a ys turned
off so that only the indoor fan is operated. RY02 is always turnd on.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig. 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.
7-2. COOL Operation
(MODE of the remote control : COOL) (1) Compressor, 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-2-1.
Fig. 7-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
Fig. 7-1-1 Auto setting of air volume
Table 7-1-1 Manual setting of F AN SPEED
Indication of
HIGH Air volume
FAN SPEED
(m3/hr)
RAS-10SKH-ES RAS-13SKH-ES LOW 400 510 MED 500 560
HIGH 600 650
HIGH
MED LOW(+)
LOW
LOW
28 27 26 25 24
(Room temp. – Set temp.)
Set temp.
Fig. 7-2-1
(2) Relays RY01 and RY02 are turned on to energize
the outdoor unit, and a cool operation is carried out.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig. 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.
(Room temp. – Set temp.)
+1
0
Set temp.
ON
OFF
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
ON
OFF
OFF
ON ON
Compressor
(RY01)
Common relay
(RY02)
(Room temp. – Set temp.)
MED
LOW(+)
LOW LOW
(continuous)
+4 +3 +2 +1
0
RY01
OFF
Set temp.
Manual
FAN
According to the set
position
HIGH
AUTO
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
– 15 –
Room temp.
Set temp.+1 Set temp.
Compressor Outdoor fan
Indoor fan
L. *S.L. S.L.L. L. S.L. L.
ON ON ON ON
OFF OFF OFF
*Super Low
(Room temp. – Set temp.)
Set temp.
OFF
ON
+3
+2
+1
0
OFF
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
Compressor
(RY01)
Common relay
(RY02)
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
7-2-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the desired position.
And the louver position is stored in the microcom­puter, the louvers will be set to the position automatically at the next operation.
(2) When the AUTO button is pushed, the louver v er-
tically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY) (1) Compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-3-1.
Fig. 7-3-1
• The microprocessor turns the compressor on and off at regular intervals (4 to 6 minutes on and/or off). During the compressor off, the indoor fan will operate in the super low position.
• The indoor fan will operate in the A UTO position.
(2) The pattern of operation depending on the relation
between room temperature and set temperature is shown below:
Fig. 7-3-2
– 16 –
0
–1
ON
OFF
ON
OFF
ON
ON ON
(Room temp. – Set temp.)
4-way valve
(RY04)
Outdoor fan
(RY03)
OPERATION
display
Compressor
(RY01)
Common relay
(RY02)
(Room temp. – Set temp.)
0
-1
-2
-3
-4
Set temp.
MED
RY01 OFF
MED(-)
LOW(+)
LOW
FAN
Manual
AUTO
According to the set position
7-4. HEAT Operation
(MODE of the remote control : HEAT) (1) Relays compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-4-1.
Fig. 7-4-1
(2) Relays RY01 and RY02 are turned on to energize
the outdoor unit, and a heat operation is carried out. The indoor fan motor operates as shown in Fig. 7-4-2, when the FAN is set to AUTO.
The motor operates with a constant air volume as listed in Table 7-1-1, when the FAN is set to LOW, MED, or HIGH.
Fig. 7-4-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
7-4-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the desired position.
(2) When the A UTO button is pushed, the louver v er-
tically swings within range of 25deg. And the louver position is stored in the microcom-
puter, and at the ne xt oper ation, the louv ers will be set to the stored position automatically at the next operation.
7-4-2. Cool Airflow Control
(1) If the indoor heat-exchanger temperature detected
by the indoor heat-exchanger sensor is 20°C or below, the indoor fan stops and if the temperature rises to 25°C or above, the fan is restarted.
Details are in 7-10.
– 17 –
7-5-1. Temporary Auto
When the TEMPORARY button is pushed, the set temperature is fixed at 24°C and controlled in accor­dance with the chart shown in Fig. 7-5-1.
Fig. 7-5-1
Cooling mode
Cooling mode
Fan only mode
Heating mode
+4
+1
–1
(The same cooling mode as the room temperature control is set at set temp. –1˚C) The Louver moved downward.
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
(Only the indoor fan operates at Low speed)
(The same heating mode as the room temperature control is set at set temp. +1˚C)
(Room temp. – Set temp.)
7-5. AUTO Operation
(MODE of the remote control : AUTO) (1) One of the 3 modes, Cooling, F an only and Heat-
ing is selected according to room temperature at which operation is to start, as shown in Fig. 7-5-1. The Fan mode will continue until room tempera­ture reaches a level at which another mode is se­lected.
– 18 –
7-6. ECONO. Mode
When the ECONO. button is pushed, during COOL, HEAT and AUTO operation, the OPERATION display is turned off and the ECONO. display is lit and the indoor unit operates quietly and mildly with controlling airflow .
7-6-1. Cooling
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig. 7-6-1.
(2) Fan speed LOW
7-7. Current Limit Control
The microprocessor detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling)
Control is performed as shown below b y detecting the compressor operation current with a current sensor (C.T).
Fig. 7-6-2
+2
+1
Set temp.
1H 2H TIME0H
(˚C)
ECONO. button is pushed
Set temp. is changed
Set temp. is changed
Fig. 7-6-1
7-6-2. Heating
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig. 7-6-2.
(2) Fan speed LOW
-1
-2
Set temp.
1H 2H TIME0H
(˚C)
ECONO. button is pushed
Set temp. is changed
Set temp. is changed
10A I
4
Input current
9A I
3
Compressor Outdoor fan
More than I
4
continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ON
Fig. 7-7-1
(2) Current limit control (Heating)
Control is performed as shown in Fig. 7-7-2.
10A I
4
Input current
9A I
3
8A I
2
Compressor Outdoor fan
More than I
4
continues for 3 seconds
OFF
More than I3 continues for 5 minutes
OFF
ON OFF
ON
7.5A I
1
Fig. 7-7-2
– 19 –
7-8. High-Temperature Limit Control
(Heating Operation)
The microprocessor detects the indoor heat exchanger temperature so as to prevent exceeding the condensate pressure.
Control is performed as shown in Fig. 7-8-1.
7-10. Cool Airflow Prevention Control
(Heating Operation)
(1) During the heating operation, the indoor fan speed
is controlled automatically in accordance with the indoor heat exchanger temperature to prevent blowing the cool air.
Control is performed as shown in Fig. 7-10-1 and 7-10-2.
RAS-10SKH-ES
60
53
52
(˚C)
Compressor,
Outdoor fan
OFF
ON
*
1 ····· Only outdoor fan is turned off.
*
1
Heat exchanger temperature
Fig. 7-8-1
7-9. Low-Temperature Limit Control
(Cooling Operation)
The microprocessor detects the indoor heat exchanger temperature so as to prevent freezing up the indoor heat exchanger.
Control is performed as shown in Fig. 7-9-1 and 7-9-
2.
RAS-10SKH-ES
Fig. 7-9-2
Fig. 7-9-1
RAS-13SKH-ES
Compressor
Less than 5˚C continues
for 5 minutes
OFF
ON
Outdoor fan
7
Heat exchanger temperature
5
(˚C)
Compressor
Less than 2˚C continues
for 5 minutes
OFF
ON
Outdoor fan
6
Heat exchanger temperature
2
(˚C)
According to the
set position
Indoor fan speed
30 25 20
Heat exchanger temperature
(˚C)
U.L. (Ultra Low)
Room temp.
Set temp.
S.L (Super Low)
Room temp.
Set temp.
OFF
>
<
Fig. 7-10-1
RAS-13SKH-ES
According to the
set position
Indoor fan speed
35 32 30 20
Heat exchanger temperature
(˚C)
U.L. (Ultra Low)
Room temp.
Set temp.
S.L (Super Low)
Room temp.
Set temp.
OFF
>
<
Fig. 7-10-2
(2) As soon as the defrost operation starts, the indoor
fan stops.
– 20 –
7-11. Defrost Operation
During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen.
In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
7-11-1. Condition to Star t the Defrost
Operation
The defrost operation starts whichever below conditions are specified.
(1) When the cumulative compressor operation time
is longer than 40 or 90 minutes and difference between the indoor heat exchanger temperature and the room temperature is less than the specified value. (This value is decided by the microprocessor.) (Control e xample is shown in Fig. 7-11-1. In case of B or C, the defrost operation starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of 90 minutes.
Fig. 7-11-1 (Indoor fan speed : M)
7-11-2. Defrost Operation Time Control
<In case of B>
(1) The heating operation is performed for at least 40
minutes.
(2) The maximum defrost operation time is 6 minutes.
The defrost operation time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low, however, the defrost operation time is 10 minutes.)
minutes40minutes40minutes40minutes
40
Max 6 minutes 10 minutes
1 cycle
Heating
Heating
Heating
Heating
Defrost
Defrost
Defrost
Defrost
Fig. 7-11-2
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operation time is 10 minutes.
7-11-3. Ending Condition at Defrost
Operation
(1) When the compressor current becomes 7,5A or
more during defrost operation, the defrost opera­tion stops and the heat operation restarts. (The current sensor detects the compressor current.)
(2) The defrost operation continues for at most 6
minutes or 10 minutes.
DEFROST LAMP :
• During defrost operation, the PRE-DEF. lamp is on and the indoor and outdoor fans are off .
• The compressor start protection timer is inter­locked with the PRE-DEF. lamp. So the PRE­DEF. lamp is off (the fans stop) for about 3 min­utes after the START/STOP button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat ex­changer is preheated to about 30°C or higher, the PRE-DEF. lamp goes off, and the indoor f an starts.
Cumulative compressor operation time
40 90
Indoor heat exchanger temp.
–Room temp.
A
B
D
C
(˚C)
19
10
(
min.
)
– 21 –
7-12. Auto Restart Function
This unit is equipped with an Automatic restarting facility which allows the unit to restart and resume the set operating conditions in the ev ent of a pow er supply shutdown without the use of the hand control.
The operation will resume without warning three minutes after the power is restored.
The Auto Restart function is set not to work on shipment from the factory, and so it is necessary to set it to function as required.
7-12-1. How to Set the Auto Restart
To set the Auto Restart function, proceed as follows: Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of the indoor unit (please refer to section on PARTS NAME). The power supply to the unit must be on ­the function will not be set if the power is off.
To enable the Auto Restart function, press the TEMPORARY button continuously for three seconds.
The unit will acknowledge the setting and beep three times. The system will now restart automatically.
The above Auto Restart settings can be carried out:
During subsequent operation, the orange light is lit.
• The Auto Restart function will not accept an instruction if timer operation with the remote control is selected.
(Please refer to the section on setting the timer or setting the louver.)
• When the system is stand-by (not running)
• During louver swing (AUTO) operation, after restart by the A uto Restart function the louver swing stops.
• When the system is operating
Operation
Press the TEMPORARY button continuously more than three seconds.
Motion
Stand-by
The system starts to operate. The green light will be lit.
about three seconds after
The unit beeps three times. The orange light will be lit.
The system is operating. The orange light is lighting. If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
Operation
Press the TEMPORARY button continuously more than three seconds.
Motion
Operating The green light is lit.
The system stops to operate. The green light is turned off.
about three seconds after
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
TEMPORARY
0
3S
TEMPORARY
0
3S
– 22 –
7-12-2. How to Cancel the Auto Restart
To cancel the Auto Restar t function, proceed as follows:
Repeat the setting procedure: the unit will acknowledge the instruction and bleep three times.
The system will now be required to manually restart with the remote control after the main supply is turned off.
Cancellation is carried out:
• When the system is stand-by (not running)
Operation
Press the TEMPORARY button continuously more than three seconds.
Motion
Stand-by
The system starts to operate. The orange light will be lit.
about three seconds after
The unit beeps three times. The green light will be lit.
The system is operating. If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
• When the system is operating
Operation
Press the TEMPORARY button continuously more than three seconds.
Motion
Operating The orange light is lit.
The system stops to operate. The orange light is turned off.
about three seconds after
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is lighting.
7-12-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting of
Auto Restart operation, it is cancelled with power failure. (The OPERATION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reserve ON-TIMER operation once again.
TEMPORARY
0
3S
TEMPORARY
0
3S
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation is cancelled with power failure . (The OPERA TION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reser ve OFF­TIMER operation. When Auto Restart operation is set, OFF-TIMER reservation is also cancelled with power failure .
– 23 –
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Pow er supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed fle xible cord (design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY. This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact
separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply sock et in order to disconnect the appliance completely from the mains.
DANGER
• FOR USE BY QUALIFIED PERSONS ONLY.
• TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO SO MAY
CAUSE ELECTRICAL SHOCK.
• CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY WR ONG WAY, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OF GAS VAPORS. FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL AWAY (MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS, FURNACE, STO VES , ETC .
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R-22) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT , THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNOR­MALLY HIGH AND IT RESUL TINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards or by-passing any of the safety interlock switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord. And make sure the equipment to be earthed.
• Appliance shall be installed in accordance with national wiring requlations. If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.
– 24 –
CAUTION
• Exposure of unit or water or other moisture before installation will result in an electrical short. Do not store in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of unit or where noise and discharged air might disturb user’s neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read the installation manual carefully before installing the unit. It contains fur ther impor tant instructions for proper installation.
UK Plugs and Sockets etc (Safety) Regulations 1994
SI Number 1768
With regard to Schedule 3, Item 7 of the above UK Regulations, this appliance must be permanently connected to the fixed wiring of the main electrical supply by means other than the use of an approved 13 Amp plug-top as outlined in the Regulations.
Electrical work must be carried by suitably qualified persons and in accordance with all relev ant safety standards and codes of practice.
We recommend that the power supply f or this appliance is deriv ed from a suitably protected dedicated circuit.
(for U.K. only)
For to comply with the specification 61000-3-3 the local power authority has to be conducted for permit of operation. The installation condition has to be done as following :
Installation only by authorized installer
This product has to be connected to the mains supply via a separate connection to the main distribution box (circuit breaker box).
– 25 –
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern on the back.
3 Clip anchorClip anchor
Hook
66 mm or more
Hook
1 Installation plate
8 Mounting screw
Hook
120 mm or more
Front cabinet
Front panel
Air filter
(Attach to the back side.)
(Attach to the back side.)
5 Shield pipe 6 Pan head wood screw
4 Remote control holder
2 Wireless remote control
9 Deodorizing filter
10 Purifying filter
11 Filter frame
100 mm or more
400 mm or more
Loop the connective cable (about 100 mm in diameter and 300~350 mm long).
600 mm or more
Electric parts cover
45 mm or more
600 mm or more
2
Wireless remote control
7 Batteries
Cover
6 mm thick heat resisting polyethylene foam
Bottom
Rear
Right
Rear left
Left
Cut the piping hole sloped slightly
Wall
120 mm
or more
For the rear and left piping
Insert the remote control holder cushion between the indoor unit and wall, and lift indoor unit to make work easier.
Do not allow the drain hose to get slack.
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected the left, rear left, rear, right or bottom.
Insulation of refrigerant pipes insulates the pipes separately, not together.
Before install the wireless remote control
• With the remote control cover open, load the batteries supplied correctly, observing their polarity.
Extension drain hose (Option: RB-821SW)
– 26 –
8-3. Installation
8-3-1. Optional Parts
<Drainage>
Part
code
A
B
C
Q’ty
Each
one
1
Each
one
Parts name
Refrigerant piping Liquid side : ø6,35 mm
Gas side : ø9,52 mm Pipe insulating material
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
Fig. 8-3-2
• Install the provided drain nipple in the hole of the bottom plate of the outdoor unit. (See the above figure.)
• Perform proper drainage processing using a drain hose sold separately or one on the market. (Inner diameter : 16 mm)
• Do not use an ordinary hose on the market, because it tends to get flat and as a result, it prev ents water from draining.
Drain hose sold separately or one on the market.
12
Drain nipple
Bottom plate
ø25
Fig. 8-3-1-2 Air outlet
• Secure the outdoor unit with the anchor bolts if the unit is likely to be exposed to a strong wind.
• Use ø8 or ø10 anchor bolts.
• If it is necessar y to drain the defrost water from the outdoor unit, attach
12
drain nipple to the
bottom plate of the outdoor unit before installing it. The drain nipple is located as shown above.
<Anchor bolt arrangement of outdoor unit>
RAS-10SKH-ES
Fig. 8-3-1-1 Air outlet
RAS-13SKH-ES
600mm
Air inlet
120mm
Drain nipple
52,5mm
301mm
Air outlet
12
600mm
Air inlet
111mm
Drain nipple
30mm
230mm
Air outlet
12
– 27 –
8-3-2. Kit Parts
Parts with an asterisk (*) are packaged with the outdoor unit.
Name
Installation manual
Owner’s man ual
Others This model is not equipped with an extension drain hose.
Option : For the extension drain hose, use an optionally available RB-821SW or commercially available one.
Deodorizing filter x 1
Purifying filter x 1
Filter frame x 2
1 5 9
2 6 10
3 7 11
4 8
Part
No.
Name of parts
Q'ty
Part
No.
Name of parts
Q'ty
Part
No.
Name of parts
Q'ty
Installation plate x 1
Wireless remote control x 1
Clip anchor x 6
Remote control holder x 1
Shield pipe x 1
Pan head wood screw ø3,1 x 16 x 2
Batteries x 2
Mounting screw ø4x 25 x 6
12
Drain nipple* x 1
– 28 –
8-4. Indoor Unit
tt
tt
t Installation place
• A place which provides the spaces around the indoor unit as shown in the diagram in section 8-2.
• A place where there is no obstacle near the air inlet and outlet.
• A place which allows an easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
CA UTION
• Direct sunlight to the indoor unit wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to r-f noise sources. (For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a curtain that may block the signal from the remote control.
• Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
• The location of the remote control should be determined as shown below.
8-4-1. Cutting a Hole and Mounting
Installation Plate
<Cutting a hole>
When installing the refrigerant pipes from the rear
Fig. 8-4-1
Fig. 8-4-3
(Top view)
Indoor unit
5m
5m
45˚
45˚
Remote control
Reception range
*:Axial distance
Remote
control
Reception range
7m
(Side view) Indoor unit
*7m
75˚
Fig. 8-4-2
(1) After determining the pipe hole position with the
mounting plate (80 mm ), drill the pipe hole (ø65 mm) at a slight downward slant to the outdoor side.
Note :
• When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
The center of the piping slot
is the above arrow. The center of the pipe hole is the above arrow.
80mm
Pipe hole
65mm
40,5
mm
Indoor unit
Pipe hole
65,5mm
Thread
Weight
1
Installation plate
8
Mounting screw
Pipe hole
65,5mm
Anchor bolt hole
– 29 –
<When the installation plate is directly mounted on the wall>
(1) Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook
up the indoor unit. (2) Install the installation plate horizontally in the wall. (3) To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
shown in the above figure.
CAUTION
When installing the installation plate with mounting screw, do not use the anchor bolt hole. Otherwise the unit may fall do wn and result in personal injury and property damage.
8-4-2. Electrical Work
(1) The supply voltage must be the same as the rated
voltage of the air conditioner.
(2) Prepare the power source for exclusive use with
the air conditioner.
Model
RAS-10SKH-ES/ RAS-13SKH-ES/
RAS-10SAH-ES RAS-13SAH-ES
50Hz
Power source 220/230/240V ~
Single-phase
Maximum
7,5A 12A
running current
Plug socket &
15A 16A
fuse rating
Wiring 1mm2 or more 1,3mm2 or more
Fig. 8-4-4
CAUTION
Failure to firmly install the unit may result in personal injury and proper ty damage if the unit falls.
• In case of block, bric k, concrete or similar type walls, make 5 mm dia, holes in the wall.
• Inser t
3
clip anchors for appropriate
8
mounting screws.
Note :
• Install the installation plate using 4 to 6 pieces of mounting screw securing four corners with screws.
Installation plate (Keep horizontal direction)
Anchor bolt
Projection 15mm or less
5mm dia, hole
3
Clip anchor
8
Mounting screw ø4 x 25
* No adjustment is necessary .
CAUTION
• Use power specified in above table.
• This appliance can be connected to the mains in either of the following two ways.
(1) Connecting the power cord to the main power
supply provided with a circuit breaker or switch with a contact of 3 mm or more.
In this case, an approved circuit breaker or switch must be used.
(2) Attaching a plug to the power cord and pluging
it in to the wall outlet. In this case, an approved pow er cord and plug
must be used.
Note :
• Perform wiring works so as to allow a generous wiring capacity.
– 30 –
Fig. 8-4-6
How to open the screw cap
• Place your finger on the lower part and push up to open the screw cap.
(1) Open the screw caps and remov e the two screws
securing the front cabinet. (2) Close the screw caps as behind. (3) Open the vertical airflow louver horizontally by
hand. (4) Slightly open the lower part of the front cabinet
then pull the upper part of the front cabinet toward
you to remov e it from the rear plate.
Taking out the power cord
• Cut off the slitted portion in the side face of the rear panel to take out the power cord. After this, remove burrs, sharp edges, etc., to smooth the cut face.
<How to connect the power cord> For the air conditioner that has no power cord,
connect a power cord to it as mentioned below.
• After removing the front cabinet, remove the terminal cover and the cord clamp.
• Connect and secure the power supply cord and secure the cord clamp and the terminal cover .
• Cut the rear panel following the cutting mark and put the power supply cord through the notch.
• Be sure to smooth out the notch with a file, etc.
8-4-3. Wiring Connection
WARNING
To plug the cable in the plug receptacle, take the following precaution.
THIS APPLIANCE MUST BE EARTHED.
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE COLORED IN ACCORDANCE WITH THE FOLLOWING CODE:
Fig. 8-4-5
As the colors of the flexible cord of this appliance may not correspond with the colored markings, to identify terminals in your plug, as follows:
Connect BROWN colored core to plug terminal marked letter “ L ”.
Connect BLUE colored core to plug terminal marked letter “ N ”.
Connect GREEN AND YELLOW colored core to plug terminal marked Earth Symbol “ ”.
<How to remove the fr ont cabinet>
Slitted portion
Note :
• Use standard wire only.
• Wire type: More than H05-RNF
Fig. 8-4-8
Fig. 8-4-7
<Stripping length of power cord>
3
2
2
1
1
4
4
Vertical air flow louver.
L N
L N
-LIVE
-NEUTRAL
-EARTH
: Brown : Blue : Green and Yellow
Earth line
40mm
10mm
10mm
30mm
L
N
Cord clamp
Terminal cover
Screw
Power supply cord
Terminal block
Earth line
Screw
Screw
L
N
– 31 –
<How to connect the connecting cable> Wiring of the connecting cable can be carried out
without removing of the front panel.
(1) Remove the front panel.
Fully open the front panel. Disengage the sup­port arm located in the upper center while push­ing its handle leftwards, and then remov e the front
panel toward you. (2) Remove the terminal cover and cord clamp. (3) Insert the connecting cable (according to local
codes) into pipe hole on the wall. (4) Take out the connecting cable through the cable
slot on the rear panel so that it is exploded by
about 15 cm long in the front side . (5) Insert the connecting cable fully into the terminal
block and secure it by screw tightly. (6) Tightening torque: 1,2 N•m (0,12 kgf•m) (7) Secure the connecting cable with the cord clamp. (8) Fix the terminal cover and front panel on the indoor
unit.
CA UTION
• Be sure to refer the wiring system diagram labeled inside the front panel.
• Check local electrical codes and also any specific wiring instructions or limitation.
<Stripping length of connecting cable>
For a five conductor cable
Note :
• Use stranded wire only.
• Wire type: More than H05 RN-F
Fig. 8-4-10
<How to install the front cabinet on the indoor unit>
Install the front cabinet through the opposite order of "How to remove the front cabinet".
When the panel is removed and mounted again, tak e the following actions:
After fastening the two screws, one each at the left and right of the air outlet, be sure to push the upper center1right end2, left end3and the lower center4of the air outlet, and confirm that no gap is left between the front cabinet and the rear plate.
• If cooling (dry) operation is made without pushing the air outlet, dew can be deposited on the front cabinet surface. In addition a gap between the front cabinet and the rear plate will become wider, spoiling the appearance.
3
1
2
4
Push Push
Push
Push
Fig. 8-4-11
Fig. 8-4-9
Connecting cable
about 15cm
Terminal block
Cord clamp
Screw
Screw
Connecting cable
Earth line
Terminal cover
Screw
2
10mm
40mm
50mm
10mm
Earth line
3
4
1
– 32 –
8-4-4. Piping and Drain Hose Installation
<In case of rightward piping>
• After scr ibing slits of the front panel and the rear panel by a knife or a marking-off pin, cut them b y a pair of nippers or the like.
To connect pipe after installation of unit (figure)
Fig. 8-4-13
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30mm.
Slit (rear panel)
Slit (front panel)
Fig. 8-4-14
Note :
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to auxiliary pipes and wrap the facing tape around them.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with facing tape tightly. In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush it.
196mm
96mm
Side of liquid flow
Side of gas flow
Outward form of indoor unit
(To the forefront of flare)
R 30mm (Use polisin or the like for bending pipe.)
43mm
Use the handle of screwdriver,etc.
80˚
Fig. 8-4-12
<In case of downward piping>
• After scribing the slit of the front panel and slit in the lower part of the rear panel by a knife or a marking-off pin, cut them by a pair of nippers or the like.
Slit (rear panel
)
Slit (front panel)
Indoor unit
Connecting
cable Installation plate
Auxiliary pipes
– 33 –
8-4-5. Indoor Unit Installation
(1) Pass the pipe through the hole in the wall, and
hook the indoor unit on the installation plate at the upper hooks.
(2) Swing the indoor unit to r ight and left to confir m
that it is firmly hooked up on the installation plate.
(3) While pressing the indoor unit onto the wall by the
lower part, hook it up on the installation plate by the lower part. Pull the indoor unit toward you by the lower part to confirm that it is firmly hooked up on the installation plate.
8-4-6. Drainage
(1) Run the drain hose sloping downwards .
Note :
• Hole should be made at a slight downwrd slant to the outdoor side.
Fig. 8-4-19
Fig. 8-4-15
• For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up by the specified parts.
Space for pipes
Wall
Drain guide
Fig. 8-4-18
CA UTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in damage to property.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.
Therefore, do not store the pow er cord and other parts at a height above the drain guide.
Fig. 8-4-17
(2) Put water in the drain pan and make sure that the
water is drained outdoors.
(3) When connecting extension drain hose, insulate
the connecting part of extension drain hose with
5
shield pipe.
Fig. 8-4-16
5
Shield pipe
Extension drain hose
Inside the room
Drain hose
50 mm or more
Do not rise the drain hose.
Do not form the drain hose into the wared shape.
Do not put the drain hose end into water.
Do not put the drain hose end in the drainage ditch.
Push
1
Installation plate
Hook here
(1)
(2)
Hook
Push Push
– 34 –
CAUTION
Installation in the following places may result in trouble. Do not install the unit in such places.
• A place full of machine oil.
• A saline place such as coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely to be generated as from radio equipment, welders, and medical equipment.
8-5-1. Required Tools for Installation Work
1) Philips screw driver
2) Hole core drill (65mm)
3) Gaugramanifold
4) Spanner
5) Pipe cutter
6) Knife
7) Reamer
8) Gas leak detector
9) Tape measure
10) Thermometer
11) Mega-tester
12) Electro circuit tester
13) V acuum pump
14) Hexagonal wrench (5mm)
15) Torque wrench 1/4 (17mm) 16N•m (1,6kgf•m)
3/8 (22mm) 42N•m (4,2kgf•m) 1/2 (26mm) 55N•m (5,5kgf•m)
8-5. Outdoor Unit
tt
tt
t Installation place
• A place which provides the spaces around the outdoor unit as shown in the diagram in page 25.
• A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration.
• A place where the operation noise and discharged air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an elev ated position, be sure to secure its feet.
• An allowab le length of the connecting pipe is up to:
RAS-10SKH-ES: 10m RAS-13SKH-ES: 15m
• An allowable head level is up to:
RAS-10SKH-ES: 5m RAS-13SKH-ES: 6m
• A place where the drain water does not raise any problem.
CAUTION
(1) Install the outdoor unit without anything
blodking the air discharging.
(2) When the outdoor unit is installed in a place
exposed always to a strong wind like a coast or on a high story of a building, secure the normal fan operation using a duct or a wind shield.
(3) Specially in windy area, install the unit to
prevent the admission of wind.
Fig. 8-5-1
Strong wind
– 35 –
8-5-2. Refrigerant Piping Connection
<Flaring>
(1) Cut the pipe with a pipe cutter .
8-5-3. Vacuum Pumping
AIR PURGE Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump .
Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump.
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manifold
valve to the charge inlet of the gas side packed valve.
(2) Connect the charge hose (B) to the port of vacuum
pump.
(3) Open fully the low pressure side handle of the
manifold valve. (4) Operate the vacuum pump. (5) Close the low pressure side handle of manifold
valve after vacuumizing and stop the vacuum
pump.
Continue vacuumizing more than 15 minutes and check the pressure gauge indicates –76cmHg ( –1,013 x 105Pa).
(6) Open the stems of packed valves A and B all the
way. (7) Securely tighten the stem cap to each of the
packed valve stems.
Fig. 8-5-5
VP
Outdoor unit
Charge hose (B)
Service port
Packed valve
A
B
C
D
Gas (ø9,52)
Liquid
(
ø6,35
)
Indoor unit
Lo Hi
High pressure side handle
Pressure gage
Manifold valve
Low pressure side handle
Charge hose (A)
90˚
Obliquity Roughness Warp
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.
Die Pipe
A
Outer
A (mm)
diameter
Flare tool for
Conventional flare tool
(mm)
R-410A clutch type
Clutch type
Wing nut type
6,35 0 ~ 0,5 1,0 ~ 1,5 1,5 ~ 2,0 9,52 0 ~ 0,5 1,0 ~ 1,5 1,5 ~ 2,0
Fig. 8-5-3
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with y our fingers . Then tighten the nut with a spanner and torque wrench as shown in the figure.
CAUTION
• Do not apply excess torque. Otherwise, the nut may crack depending on the installation conditions.
(Unit : N·m)
Additional
tightening torque
18 (1,8kgf·m) 42 (4,2kgf·m)
Tightening torque
16 (1,6kgf·m) 42 (4,2kgf·m)
Outer diam.
(mm)
6,35 9,52
Half union or packed valve
Flare nut
Externally threaded side
Internally threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Fig. 8-5-4
– 36 –
CAUTION
• KEEP IMPORTANT 4 POINTS FOR INSTAL­LATION (PIPING WORK)
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
<Packed Valve Handling Precautions>
• Open the valve stem all the way out; so not try to open it beyond the stopper.
• Securely tighten the valve stem cap with the wrench or like.
• Valve stem cap tightening torque is as follows; Gas pipes side (ø9,52) : 42N•m (4,2kgf•m) Liquid pipe side (ø6,35) : 16N•m (1,6kgf•m)
<A5 mm hexagon wrench is required.>
8-5-4. Wiring Connection
(1) Remove the electric parts cover from the outdoor
unit. (1 screw)
(2) Connect the connecting cable to the terminals as
identified with their respective matched numbers on the terminal block of indoor and outdoor units.
(Strip the sheath of connecting cable with following stripping length to and insert into the ter minal block.)
(3) When connecting the connecting cable to outdoor
unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prev ent w ater coming in the outdoor unit.
(4) Insulate the unused cords (conductors) with water
coming in the outdoor unit. Process them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Fig. 8-5-7
CAUTION
• Wrong wiring connections may cause some electrical parts to burn out.
• Be sure to comply with local code on running the wire from the indoor unit to outdoor unit.
(size of wire and wiring method etc.)
• Every wire must be connected firmly.
Note :
• Wipe type : More than H05 RN-F
Fig. 8-5-6
5mm
Flare nut
Stopper
Valve body
Valve stem
Valve stem cap
70mm
4 3 2 1
1234
10mm
10mm
60mm
Connecting cable
Screw
Terminal block
Terminal screw
Cord clamp
Earth line
– 37 –
8-6. Others
8-6-1. Gas Leak Test
Flare nut connections (Indoor unit)
Fig. 8-6-2
8-6-3. Auto Restart Setting
This product is designed so that, after a power failure , it can restart automatically in the same operating mode as before the power failure.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the Auto Restart>
• Press and hold down the TEMPORAR Y button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
• To cancel the Auto Restar t, follow the steps described in the section Auto Restart Function of the Owner's Manual.
Flare nut connections (indoor unit)
Electric parts cover
Flare nut connections (Outdoor unit)
A
B
C
D
Valve stem cap connection
Service port
Valve stem cap connection
TEMPORARY
Fig. 8-6-1
• Check the flare nut connections, valve stem cap connections and service cap connections for gas leak with a leak detector or soap water.
8-6-2. Test Operation
To switch the TEST RUN (COOL) mode, press TEMPORARY b utton for 10 sec. (The beeper will make a short beep.)
– 38 –
9. TROUBLESHOOTING CHART
TROUBLESHOOTING PROCEDURES :
• Following details of “What to be pre-checked first”, make sure of the basic items.
• When there is no trouble corresponding to above, check in detail the faulty parts following “How to judge faulty parts by symptoms” later.
9-1. What to be Prechecked First
9-1-1. Power Supply Voltage
The line voltage must be A C 220/230/240V. If the line voltage is not within this range, this air conditioner may not work normally.
9-1-2. Incorrect Cable Connection between
Indoor and Outdoor Units
The indoor unit is connected to the outdoor unit with 5 cables. Mak e certain that the indoor and outdoor units have been connected properly, with terminals assigned the same numbers wired to each other . If the connec­tors are not connected as specified, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will blink (5Hz).
– 39 –
No.
1
2
3
4
5
6
7
8
9
10
Operation of air-conditioner
When the power plug or the power cord of the indoor unit is inserted, the OPERATION lamp on the setting indication part blinks.
Fan speed remains unchanged in the dry mode.
Room temperature is in the range under which the compressor is turned off, but the compressor will not stop.
The compressor will not switch on or off even when the thermo. control is operated in the dry operation.
The PRE-DEF. lamp comes on when the heating operation is started.
The outdoor fan stops once in the while during the heating operation.
Compressor does not work though room temperature is in the range of turning the compressor on.
During automatic operation, the operation mode changes.
During automatic operation mode, the fan only operation continues.
When the power is turned on, the operation starts automatically.
Description
The OPERATION lamp blinks, indicating that pow er is turned on. If this happens, push the START/STOP button once to cause the lamp to stop blinking. A power outage also causes the lamp to blink.
Fan speed is automatically controlled in the dry mode.
The compressor will not stop while the compressor on hold timer (3-minutes timer) is actuated.
In the dry mode, the compressor goes on and off at regular intervals, independent of the thermo. control.
The PRE-DEF. lamp comes on during defrost operation and when the indoor heat exchanger temperature is low when the heating operation is started. At this time, the indoor fan is stopped to prevent cold air from drifting into the room.
• When the indoor heat exchanger temperature is high, the outdoor fan may be stopped b y the high-temperature limit control operation.
• When the compressor current is large, the outdoor fan ma y be stopped by the current limit control operation.
Compressor does not work while the compressor restart delay (3-min.) timer is active. The same is true after power is turned on, as the time is still active.
After selection of the cooling and heating operation, the operation mode is selected again when the compressor off mode continues for 15min. according to the room temperature.
When the room temperature is within setting temperature ± 1°C the fan only mode is selected.
When the auto restart controlling is selected, the operation is performed automatically in the previous operation mode after the power supply has been turned on.
9-1-3. Misleading but Good Operations
(Program Controlled Operation)
The microcomputer performs the operations listed in Table 9-1-1 to control the air conditioner. If a claim is made on the operation, check whether it corresponds
to the contents in the Table 9-1-1. If it does, it is an indispensable operation for the control and mainte­nance of the air conditioner: it is not a failure of the unit.
Table 9-1-1
– 40 –
Symptom
No reaction on remote control operation
The outdoor fan does not rotate
Check
Turn off the power once, turn it on again and try to operate the remote control again.
The compressor operates.
The compressor does not operate.
Primary judgement
The indoor part (including the remote control) is defective .
OK.
The outdoor part is defective. (outdoor fan motor)
The inside part is defective.
Remote control is not possible.
Remote control is possible.
(1) Judgement from defective operation or abnormal operation
Table 9-2-2
Block display
OPERATION display blinking (1Hz) OPERATION display blinking (5Hz) OPERATION display blinking (5Hz) OPERATION display blinking (5Hz) OPERATION display blinking (5Hz) OPERATION and TIMER display blinking
(5Hz) OPERATION, TIMER and PRE-DEF. display
blinking (5Hz)
OPERATION, TIMER and PRE-DEF. display blinking (5Hz)
Description
Power failure (when power is ON) Thermo. sensor (TA) short/break Heat exchanger sensor (TC) short/break Indoor fan lock, abnormality of indoor fa n Indoor P.C. board failure Wrong wiring of connecting cable
Thermal fuse is blown
• Gas shortage, other refrigerant cycle trouble
• Heat exchanger sensor open/break/short
• Overload relay or thermostat for compressor trouble
Compressor trouble
A
B C D
E
F
G
H
9-2. Primary Judgement of Trouble
Sources
9-2-1. Role of Indoor Unit Controller
The indoor unit controller receives the operation com­mands from the remote control and assumes the fol­lowing functions.
• Measurement of the draft air temperature of the indoor heat exchanger by using the thermo. sen­sor (TA).
• Louver motor control
• Control of the indoor fan motor operation
• Control of the LED display
• Control of the outdoor unit compressor, 4-WAY VALVE and the outdoor fan motor.
9-2-2. Display of Abnormalities and
Judgement of the Abnormal Spots
The indoor unit of this machine observes the opera­tion condition of the air conditioner and displays the contents of the self-diagnosis as block displays on the display panel of the indoor unit.
Table 9-2-1
– 41 –
(2) Self-diagnosis with remote control
With the indoor unit control, self-diagnosis of pro­tective circuit action can be done by turning the remote control operation into service mode, oper­ating the remote control, observing the remote control indicators and checking whether TIMER lamp blinks (5Hz).
Note :
• To perform this self-diagnosis, the remote control with the service code of 43069666 is required.
<How to select remote control operation mode>
1) Selecting service mode
Push the switch button provided on rear bot­tom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the setting temperature is displayed on the display and other display is turned off.
2) Selecting ordinary mode
Push the all clear button (ACL) on the rear bot­tom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the operation mode display, wind volume display, clock display and setting temperature display are turned on and “ : ” of the clock display is blinking.
<Cautions when doing service>
1) After completion of servicing, always push the all clear (ACL) button to return the operation mode to the normal mode.
2) After completion of ser vicing by the check code, turn off the power once and then turn on the power to reset memorized contents of the microcomputer to the initial status.
Fig. 9-2-1
ACL CLOCK
(
Rear bottom of remote control
)
ACL
CLOCK
All clear button
Switch for selecting service mode
Rear bottom cover
“ ”
– 42 –
<Self-diagnosis by check codes>
1) The self-diagnosis by the check codes is con­ducted under the block displays of item B-H in Table 9-2-1.
2) Remote control key operation under the ser­vice mode is conducted by ON/OFF or TEMP. The remote control display by each key op­eration is varied as shown below. Two digit number is displayed in a hexadecimal num­ber.
3) The self-diagnosis by the check codes is con­ducted with procedures shown below.
a) Enter the service mode and make sure the
off timer display of the remote control shows .
b) Operate the “ON/OFF” key and make sure
the timer lamp on the display section is blinking (5Hz).
c) At the same time, also make sure the op-
eration lamp is also blinking. This shows that the protection circuit on the indoor P.C. board is working.
d) Operate the TEMP. key and mak e sure
the remote control display shows and blinking of the operation lamp. If the op­eration lamp is blinking, it shows the pro­tection circuits for connecting cable is w ork­ing or thermal fuse is blown.
e) In the same way, operate the TEMP.
key so that the display is increased one by one to continue checks by the self-di­agnosis as shown in the next table. From
up to check operations of
protection circuits for each block, and
to check operations of the
typical protection circuits.
Table 9-2-3
“ ”
“ ”
“ ”
“ ”
“ ”
Indication after operation
1 is added to data before operation. (Example)
1 is subtracted from data before operation. (Example)
10 is subtracted from data before operation. (Example)
Data before operation is directly transferred. (Example)
Operating key
ON/OFF
TEMP. (Up)
TEMP. (Down)
“AUTO” LOUVER
“SET” LOUVER
“ ”
– 43 –
Block level Diagnosis function
Check Check
Air
Block Symptom
conditioner
Condition
code code
status
Indoor Thermo. sensor Continued Indicated when P.C. board shor t/break. operation detected abnormal
Heat exchanger Continued Indicated when sensor short/break. operation detected abnormal
Indoor fan lock, All off Indicated when abnormality of detected abnormal indoor fan.
Abnormality of other All off Indicated when indoor unit P.C. detected abnormal board.
Cable 1)Wrong wiring or All off Indicated when connection/ disconnection of detected abnormal Thermal connective cable.
fuse 2)Thermal fuse cut Refrigerant off. system
1)Gas shortage. All off Indicated when (gas leak) detected abnormal
2)Other refr igerant cycle trouble.
3)Heat exchanger sensor off/break/ short.
4)Overload relay or thermostat for compressor break.
Compressor break All off Indicated when down. detected abnormal
Judgment and action
1. Check thermo. sensor.
2. If it is OK, check P.C. board.
1. Check heat exchanger sensor.
2. If it is OK, check P.C. board.
1. Disconnect the power plug from AC outlet, and pull out the connector (CN10) for the motor, then connect the plug of AC power cord again and turn the power on.
2. Check the voltage between pin 1 and 2 of the connector (CN10).
3. If the output voltage is 35V, P.C. board is OK, check motor.
Replace P.C. board.
1. Check connective cable correct if wiring is wrong.
2. Check thermal fuse and Terminal blocks.
3. If it is OK, check P.C. board.
1. Check gas quantity. (check gas leakage)
2. If it is OK, check heat ex­changer sensor.
3. If heat exchenger sensor is OK, check overload relay and thermostat for compressor.
4. If overload relay and themostat for compressor are OK, check refrigerant cycle.
5. If refrigerant cycle is OK, check P.C. board.
1. Check compressor.
2. If it is OK, check P.C. board.
Table 9-2-4
Contents detected by the check codes to are stored in memory of the microcomputer even if the power supply is turned off. Therefore, contents of operations in the past are all displayed.
“ ” “ ”
– 44 –
9-3. Troubleshooting Flowcharts
9-3-1. Power can not be Turned on (No Operation at All)
<Preliminary checks>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK.?
*
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
P.C. board
is defective.
Symptom
Operation
Check Items
Main cause
Countermeasure
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION
lamp blink?
Does the transmission
indicator of remote
control blink normally and
transmit certainly?
Remote control
is defective.
Replace the remote control.
(No problem)
Does the fuse
(F01) blow?
Replace the main P.C. board.
Wrong wiring of
AC cord or connecting
cable is defective.
Replace the thermal fuse set. Check connection.
Is the indication voltage
(DC12V or 5V) of main
P.C. board correct?
Is the voltage
across C02 measured
DC310V~340V?
Refer to the paragraph "Pre-check", or defective circuit before power P.C. board block.
Shut off the power supply once, and turn it on again after dis­connecting the motor connector CN10
*
.
Is the secondary
voltage of SW
transformer measured
DC35V, DC12V,
and DC7V?
Motor is defective.
Is the secondary
voltage of SW trans-
former (T01) measured
DC35V, DC12V,
and DC7V ?
YES
SW transformer
(T01) or IC (IC01)
for power supply
is defective.
Parts (R21, R109, SG01,
C15, C01, DB01, C02,
IC01, T01) are defective.
Does the power turn
on by pushing the [START/STOP] button of the remote control?
NO
YES
YES
NONO
YES
YES
NO
NO
NO
YES
YES
NO
YES
YES
NO
Does the thermal
fuse blow?
(Under PF. Terminal)
NO
Replace the main P.C. board.
– 45 –
9-3-2. Power can not be Turned on after Replacing Indoor P.C. Board
<Checking Procedure>
To the paragraph of “No Power turns on”.
Does the OPERATION
lamp blink?
YES
NO
Connect the AC plug.
Return the wiring of the power relay is returned to the normal procedure.
Is it wired as shown in
Figure on page 59 and 60?
YES
NO
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
Is AC220/230/240V
supplied between terminal block
1 - 2 , 3 - 2
*
1, 4 - 2 ?
*
1 Only Heating mode
Is cable connection
between indoor and outdoor
units correct?
Check items as following procedure in 9-3-4, 9-3-5, 9-3-6.
Replace the P.C. board.
See "Power can not be turned on".
Relays (RY01, RY02, RY03, RY04) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
NO
NO
NO
NO
YES
YES
YES
YES
See "Power can not be turned on".
9-3-3. Outdoor Unit does not Operate
– 46 –
9-3-4. Only Compressor does not Operate
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
Is cable connection between indoor
and outdoor units correct?
Replace the P.C. board.
See "Power can not be turned on".
NO
NO
NO
NO
YES
YES
YES
YES
Is the voltage across the terminal
( 1 - 2 ) 220/230/240 VAC?
YES
Are all the cords for compressor normal?
Is the compressor motor winding normal?
(Check the winding resistor.)
Is the capacitor for compressor normal?
Is the overload relay normal?
Does the compressor start?
Compressor starts but
it stops after a while?
Cables between indoor and outdoor units are defective.
Re-wire or replace the defective cords.
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Correct cabling between indoor and outdoor units.
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
See "Power can not be turned on".
YES
Is the gas quantity normal?
(Check the pressure)
Gas shortage (Gas leakage)
NO
Compressor is defective
Is the voltage across the terminal
( 1 - 2 ) 220/230/240 VAC?
Relays (RY01, RY02) or IC31 or IC30 is failure.
– 47 –
9-3-5. Only Outdoor Fan does not Operate
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
Is cable connection between indoor
and outdoor units correct?
Replace the P.C. board.
See "Power can not be turned on".
NO
NO
NO
NO
YES
YES
YES
YES
Is the outdoor fan motor winding normal?
(Check the winding resistance)
Is the capacitor for compressor normal?
Outdoor fan motor is defective.
Cables between indoor and outdoor units are defective.
Outdoor fan motor is defective.
Correct cabling between indoor and outdoor units.
NO
NO
NO
NO
YES
YES
YES
YES
Is the voltage across the terminal
( 2 - 4 ) 220/230/240 VAC?
Are all the cords for outdoor
fan motor normal?
Correct the wire or replace the defective cords.
Capacitor for outdoor fan motor is defective.
See "Power can not be turned on".
Is the voltage across the terminal
( 2 - 4 ) 220/230/240 VAC?
Relays (RY02, RY03) or IC31 or IC30 is failure.
– 48 –
9-3-6. Only 4-Way Valve does not Operate (During Heating Operation)
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp blink?
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
Is cable connection between indoor
and outdoor units correct?
Replace the P.C. board.
See "Power can not be turned on".
NO
NO
NO
NO
YES
YES
YES
YES
4-way valve is defective.
Cables between indoor and outdoor units are defective.
Correct cabling between indoor and outdoor units.
NO
NO
YES
YES
Is the wiring of solenoid coil
for 4-way valve normal?
Is the voltage across the terminal
( 2 - 3 ) 220/230/240 VAC?
See "Power can not be turned on".
Solenoid coil is defective.
Is the voltage across the terminal
( 2 - 3 ) 220/230/240 VAC?
Relays (RY02, RY04) or IC31 or IC30 is failure.
– 49 –
9-3-7. Only the Indoor Fan does not Operate
< Preliminary checks >
Does it neither work in COOL or F AN ONLY operation?
< Check procedure >
*
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of damage of the motor.
YES
NO
Replace the P.C. board.
Shut off the power supply once.
Does the fan
stop in no operating
status?
Control P.C. board is defective.
Replace the P.C. board.
Start the operation with low fan setting in cool operation.
Does the fan rotate?
Change the setting of cooling to high fan.
Does the fan speed
become higher?
Operation stops
Normal
Is the voltage
measured DC35V
between
1 (red lead wire, +)
and
2 (black lead wire, –)
of the motor connector
(CN10) ?
Shut off the power supply.
Does the cross
flow fan rotate
normally?
Repair the bearing of the drain fan.
Turn on the power supply.
Is the rotation signal
(DC+5V-0V) output between
4
(blue lead wire) and
2 (black
lead wire) of the motor connector
(CN10) when rotating the cross
flow fan by hand in no operating
status ? (2 pulses/one turn)
Replace the control P.C. board.
Shut off the power supply, and turn it on after disconnecting the motor connector (CN10)
*
from
the P.C. board.
Is the voltage of
DC35V measured
between 1 (red lead wire, +)
and 2 (black lead wire, –) of
the motor connector
(CN10) ?
Replace the fan motor.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
Turn the power supply.
– 50 –
9-4. How to Check the Remote Control (Including the Indoor P.C. Board)
NO
YES
After battery replacement, shortcircuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil.
Push the START/STOP button.
Does the transmission
indicator blink?
There is no beep from the indoor unit. The operation lamp of the air conditioner main unit does not light.
Is there direct sunlight on the receptor of the air conditioner?
Avoid direct sunlight.
Is there any
thyristor
fluorescent light
near by?
Keep the air
conditioner away
from thyristor
fluorescent light.
Is operation
possible when the
transmitter is moved nearer to the infrared signal receiver of the
air conditioner?
Battery life
Can any signal tone
be heard in a transistor
radio when transmitting
within 5cm distance
from the radio?
Does the
transmission
indicator light?
Is there any
beep and
operation?
Short-circuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil. (wait about 10 seconds)
P.C. board is failure.
Replace
P.C. board.
Replace the batteries
Normal
Remote control
is failure.
Replace remote control.
Note:
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
Is operation
possible when setting
the temporary switch of the
air conditioner main unit to
"TEST RUN" or
"TEMPORARY AUTO"?
Push the START/ STOP button
– 51 –
9-4-1. How to Check the P.C. Board
(1) Operating precautions
1) When removing the front panel or the P.C. board, be sure to shut off the power supply.
2) When removing the P.C. board, hold the edge of the P.C. board and do not apply force to the parts.
3) When connecting or disconnecting the connec­tors on the P.C. board, hold the whole housing. Do not pull at the lead wire.
(2) Inspection procedures
1) When a P.C. board is judged to be defective, check for disconnection, b urning, or discolora­tion of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the f ollowing 2 parts
a. Main P.C. board part:
Power relay, indoor fan motor drive circuit and control circuit, C.P.U . and peripheral cir­cuits, buzzer drive circuit and buzzer.
b. Infrared rays receive and indication
parts:
Infrared rays receive unit and LED.
– 52 –
(3) Checking procedure
Table 9-4-1
No.
1
2
3
4
5
6
7
Procedure
Shut off the power supply and remove the P.C. board assembly from the electronic parts base.
Remove the connecting cable from the terminal block.
Remove the connector for the motor, and turn the power on.
If the OPERATION lamp blinks (0.5 sec. :ON, 0.5 sec. :OFF) when the power turning on, the checking points described as 1-5 of right column are not necessary to perform.
Make the operation status by pushing once the START/STOP button, except the status of [FAN ONLY], [ON TIMER].
Start the operation with the system which the time of the restart delay timer is shortened.
Make the operation status by pressing once the START/STOP button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
The status of No. 5 is continued, and make the following condition.
1.Heat operation
2.Make the setting temperature higher enough than room temperature.
Turn the power on after connecting the motor connector.
Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
Check point (Symptom)
1.Is the fuse blown?
Voltage check
1.Between TP1 and TP2 (AC 220/230/240V)
2.Between TP2 and pin 1 of CN04 (AC 220/230/240V)
3.Between TP2 and pin 3 of CN04 (AC 220/230/240V)
4.Between + and - of C02 (DC 310 ~ 340V)
5.Between 35V and GND
6.Between 12V and GND
7.Between 5 V and GND
Voltage check
1.Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GND Between pin 11 of IC31 and GND
2.Between No. 1 and 2 of connecting cable terminal block.
(AC 220/230/240V)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
1.Compressor does not operate.
2. OPERATION lamp blinks.
1.Compressor does not operate.
2. OPERATION lamp blinks.
1.The voltage of DC 35V is not measured between the red and black of the motor terminals.
2. Motor does not rotate. (The key operation is accepted.)
3. The motor rotates, but it vibrates too much.
Causes
1.* Application of shock voltage. * Overcurrent by short-circuit of the
parts.
1.* AC power cord is defective. * Poor contact of the terminal plate. * Miss wiring of the power relay.
2.Fuse is defective.
3.Operation of the ther mal fuse.
4.* Capacitor (C01, C15) is defective. * Line filter (L01) is defective. * Resistor (R01) is defective. * Diode (DB01) is defective.
5.IC01, IC02, T01 are defective.
6.IC01, IC02, T01, F03 are defective.
7.IC01, IC02, T01, F02, Q29, IC03
are defective.
1.Breaking wire of the relay coil,
defective relay driver. (IC31)
2.Poor contact of relay.
Defective indicator, or poor housing assembly. (CN13)
1.The temperature of the indoor heat
exchanger is abnormally lower.
2.Poor contact of the heat exchanger
sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main P.C.
board are defective.
(Refer to Table 9-4-2 for the judgment
of defective resistance values.)
4.Main P.C. board is defective.
1.The temperature of the heat
exchanger is abnormally high.
2.The heat exchanger sensor
connector has short-circuit. (CN01)
3.The heat exchanger sensor is
defective.
(Refer to Table 9-4-2 for the judgment
of defective resistance values.)
4.P.C. board is defective.
1.Indoor fan motor is defective. (Protecting operation on the P.C.
board.)
2. Poor contact of the motor
connector.
3.P.C. board is defective.
  
– 53 –
9-4-2. P.C. Board Layout
Bottom View
T op View
– 54 –
Table 9-4-2 Approximate value of the sensor (thermistor) resistance (TA, TC)
(= kΩ)
9-4-3. How to Reduce the Operation Time of
the Anti-Restart Timer
• Attach the diode (1S1555 or equivalent) to the rivet inside the unit through holes on the rear of the wireless remote control unit.
• Push the START/STOP button to star t operation with the diode attached.
Fig. 9-4-1
T emperature
Sensor Themo. sensor
0°C
35,8
10°C
20,7
20°C
12,6
25°C
10,0
30°C
7,92
Timer short diode
Wireless remote control
– 55 –
RemarksProcedure
1) After stopping the operation of the air conditioner, be sure to turn off the circuit breaker or disconnect the power plug from the AC wall socket.
2) Open the screw caps and remove the two screws fixing the front panel.
3) Close the screw caps as they were.
4) Open the horizontal louver right below by your finger.
5) Open the lower side of front panel until it touches the horizontal louver, and remove it from the indoor unit by turning it.
<To assemble the front panel>
1) Fix the two screws to secure the front panel.
2) Close the screw caps as they were.
3) Press four places where are the center, right end, left end and lower portions of the air outlet.
4) Check the gap between the front panel and the main unit.
If cooling or drying operation is performed without pressing the center of the air outlet, the surface of the front panel may be covered with frost and have a waterdrop.
1) Perform the process above.
2) Remove the screw securing the shield metal plate.
3) Remove the electrical part cover by pressing the nail located on upper portion of the electrical part cover.
4) Remove the drain guide.
5) Remove the screw securing to the end plate of the heat exchanger.
6) Remove the connector (5p) for the fan motor and the connector (6p) for the louver motor from the microcomputer assembly.
7) After unhooking the electrical part base by pressing the fixing nail located on its lower portion, draw the electrical part base out toward you to remove it from the main unit.
8) Pull the TC sensor out from the holder of the heat exchanger.
9) Dress the connecting cable securely as shown in the right illustration.
(Improper dressing will cause water leakage.)
1) Perform the process above.
2) Remove the drain-pan by pressing the four hooks downwards.
(Keep it with the drain hose.)
Part name
Front panel
Electrical part assembly
Drain-pan assembly
No.
ƒ
10. PART REPLACEMENT
10-1. Indoor Unit
RAS-10SKH-ES, RAS-13SKH-ES
– 56 –
RemarksNo.
ˆ
Procedure
1) Perform the process ‚.
2) Remove the screw fixing the louver motor, and remove the louver motor.
3) Remove the shaft of the horizontal grille from the drain-pan.
1) Perform the process ƒ.
2) Remove the pipe holder from the rear side of main unit by removing the screw.
3) Unhook the hooks fixing the left side of the heat exchanger and remove the screw fixing it, then remove the right side of the end plate from the rib fixing the main unit by sliding the heat exchanger slightly to the right side.
1) Perform the process ƒ.
2) Loosen the set screw of the cross flow fan.
3) Remove the screw fixing the shaft bearing base.
4) Lift slightly up the left side of the heat exchanger, and pull the shaft bearing base out left downwards.
When assembling it, fix it with the set screw on the position where the gap between the rear plate surface and the left end surface of the cross flow fan is 6 ~ 7mm.
1) Perform the process above.
2) Remove the shaft bearing from the shaft bearing base. <Caution for assembling>
• If a part of the shaft bearing is protruded from the housing, assemble it after pushing its portion into the correct position in the housing.
1) Perform the process above.
2) Perform the process -2) above.
3) Remove the left and right motor bands.
4) Remove the fan motor after pulling the cross flow fan out sliding it left and right.
Part name
Horizontal grille
Note:
The horizontal grille can not be removed without removing the louver motor.
Heat exchanger
Cross flow fan
Shaft bearing
Fan motor
– 57 –
10-2. Microcomputer
RAS-10SKH-ES, RAS-13SKH-ES
Procedure
1) Turn the power supply off to stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove the front panel.
• Remove the two fixing screws. (φ4 x 14 )
3) Remove the electrical part base.
1) Perform the process above.
2) Remove terminal cover (Up), (Down).
3) Disconnect the terminal blocks connected with the connecting cable, and the power cord from base E­parts by removing the screws.
4) Remove the thermal fuse (77°C) from base E-parts.
No.
Remarks
Replace the thermal fuse, terminal block, power cord, microcomputer ass’y and the power supply P.C. board ass’y.
Part name
Common procedure
Thermal fuse replacement
– 58 –
1-ST2T φ4
x
10
1-ST2T φ4
x
8
1-ST2T φ4
x
8
10-3. Outdoor Unit
RAS-10SAH-ES
Procedure
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove E-parts cover. (1- ST1T ø4 x 10 )
3) Remove the cord clamp (2- ST2T ø4 x 12 ) and remove the connecting cable.
4) Remove the front cabinet. (7- ST1T ø4 x 10 with nylon washer)
• Pull the front lower portion toward you, and remove it pulling out upward.
1) Remove the fixing screw securing the capacitor band. (1- ST2T ø4 x 8 )
2) Remove the cable connected to the terminal.
1) Remove the fixing screw. (1- ST2T ø4 x 8 )
2) Remove the cable connected to the terminal.
No.
ƒ
Part name
Common procedure
Capacitor for compressor
Capacitor for fan motor
Remarks
Refer to [Electrical parts list and location] in page 66/67.
Same as above.
RAS-13SAH-ES
Procedure
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove E-parts cover. (2- ST1T ø4 x 10 )
3) Remove the cord clamp (2- ST2T ø4 x 12 ) and remove the connecting cable.
4) Remove the front cabinet. (7- ST1T ø4 x 10 with nylon washer)
• Pull the front lower portion toward you, and remove it pulling out upward.
1) Perform the process above.
2) Remove the fixing screw securing the capacitor band. (1- ST2T ø4 x 8 )
3) Remove the cable connected to the terminal.
1) Perform the process above.
2) Remove the fixing screw. (1- ST2T ø4 x 8 )
3) Remove the cable connected to the terminal.
No.
ƒ
Part name
Common procedure
Capacitor for compressor
Capacitor for fan motor
Remarks
– 59 –
11. CAUTIONS ON REPLACEMENT OF P.C. BOARD ASSEMBLY
RAS-10SKH-ES
1. Set the switch (SW03) provided on the P.C. board as follows.
2. Check the black lead wire is double wound around the current trans. (CT. T02)
ON
OFF
123456
1 2 3 4 5 6
OFF
ON
RY01
C02
RY02
Brown
N L
Power terminal block
T02
P.C. board
Blue
White
Black
Double winding
1 2 3 4
Indoor terminal block
– 60 –
RAS-13SKH-ES
1. Set the switch (SW03) provided on the P.C. board as follows.
2. Check the black lead wire is double wound around the current trans. (CT. T02)
ON
OFF
123456
1 2 3 4 5 6
OFF ON OFF
ON
RY01
C02
RY02
Brown
N L
Power terminal block
T02
P.C. board
Blue
White
Black
1 2 3 4
Indoor terminal block
– 61 –
12. EXPLODED VIEWS AND PARTS LIST
12-1. Indoor Unit (1)
RAS-10SKH-ES
403 43T60002 Base, T erminal
3P, AC 300V, 20A
407 43T69004 Sensor, Heat Exchanger
10k, 25°C
410 43T69005 Sensor, Thermostat
10k, 25°C 411 43T60004 Fuse, T emperature 77°C 414 43T69007 P.C. Board, WRS-LED
MCC-635
Location Part
Description
No. No.
415 43T69015 P.C. Board A’ssy MCC-713 416 43T61001 Base, E-Parts
ABS, Black, UL94-5V
417 43T62006 Base, Shield
SGCC-Z08-LUB
419 43T60001 Base, T erminal
2P, AC 300V, 20A
420 43T60005 Housing 4P
Location Part
Description
No. No.
403
407
420
411
415
416
417
403
414
410
419
– 62 –
RAS-13SKH-ES
401 43T60002 Base, T erminal
3P, AC 300V, 20A 402 43T69004 Sensor, Heat Exchanger
10k, 25°C 403 43T69005 Sensor, Thermostat
10k, 25°C 404 43T60004 Fuse, T emperature 77°C 405 43T69007 P.C. Board, WRS-LED
MCC-635
Location Part
Description
No. No.
406 43T69016 P.C. Board A'ssy MCC-713 407 43T61001 Base, E-Parts
ABS, Black, UL94-5V
408 43T62006 Base, Shield
SGCC-Z08-LUB
409 43T60001 Base, T erminal
2P, AC 300V, 20A
410 43T60005 Housing 4P
Location Part
Description
No. No.
401
402
410
404
406
407
408
401
405
403
409
– 63 –
Indoor Unit (2)
RAS-10SKH-ES
401 43T69003 Relay, Pow er
DI1U, 20A, A C 250V 402 43T58002 Transformer, Switching
SWT-34 404 43T60003 Fuse 3,15A, AC 250V 405 43T32001 Resistor 5,6, 5W 406 43T33001 Capacitor, Electrolytic
100MFD, 450V, AUF
Location Part
Description
No. No.
408 43T55004 Varistor 560V 409 43T34001 Filter, Line 0,6A 412 43T30001 IC, Switching MA 2830P-FJ 413 43T31001 Diode, Rectifier
RBV -406, 600V
418 43T58001 Transformer, Current
CT422920S-01
Location Part
Description
No. No.
– 64 –
RAS-13SKH-ES
411 43T69003 Relay, Power
DI1U, 20A, A C 250V 412 43T58002 Transformer, Switching
SWT-34 413 43T60003 Fuse 3,15A, AC 250V 414 43T32001 Resistor 5,6, 5W 415 43T33001 Capacitor, Electrolytic
100MFD , 450V, AUF
Location Part
Description
No. No.
416 43T55004 Varistor 560V 417 43T34001 Filter, Line 0,6A 418 43T30001 IC, Switching MA 2830P-FJ 419 43T31001 Diode, Rectifier
RBV -406, 600V
420 43T58001 Transformer, Current
CT422920S-01
Location Part
Description
No. No.
– 65 –
Indoor Unit (3)
201 43T00002 Front Panel Assemb ly 202 43T00003 Suction Grille 203 43T80001 Air Filter (L) 204 43T80002 Air Filter (R) 205 43T80003 Frame Filter 206 43T07004 Screw Cap (L) 207 43T07003 Screw Cap (R) 208 43T08030 LED Panel (10SKH-ES) 208 43T08044 LED Panel (13SKH-ES) 209 43T19004 Accepted Signal Filter 210 43T09003 Horizontal Louver Assembly
for Service 211 43T09004 Louver Assembly 212 43T70001 Drain Hose Assembly 213 43T21003 Motor Stepping 214 43T07001 Bushing 215 43T44007 Refrigeration Cycle
Assembly (10SKH-ES) 215 43T44009 Refrigeration Cycle
Assembly (13SKH-ES) 216 43T47023 Pipe, Delivery 217 43T47022 Pipe, Suction 218 43T49007 Pipe, Shield (10SKH-ES) 218 43T49010 Pipe, Shield (13SKH-ES) 219 43T19003 Holder, Sensor
Location Part
Description
No. No.
220 43T49003 Spring (10SKH-ES) 220 43T49009 Spring (13SKH-ES) 221 43T49005 Plate of EVA-SEAL 222 43T49006 Holder for Plate of EV A-SEAL 223 43T49004 Rubber of Sound Insulation
(10SKH-ES) 224 43T79002 Drain Guide 225 43T39002 Motor Band (Left) 226 43T39001 Motor Band (Right) 227 43T21010 Fan Motor 228 43T20007 Fan, Cross Flow 229 43T22002 Bearing 230 43T39003 Base, Bearing 231 43T03001 Rear Plate 232 43T07002 Pipe Holder 233 43T82001 Installation Plate 234 43T85026 Owner’s Manual 235 43T11001 Pipe Shield 236 43T69002 Remote Control 237 43T63002 Holder, Remote Control 238 43T62001 Cover, E-Parts 239 43T62002 Terminal Cover (Up) 240 43T62005 Terminal Cover (Down) 241 43T62003 Cord Clamp 242 43T62004 Shield Cover
Location Part
Description
No. No.
201
210
214
211
217
216
215
221
222
229
228
230
231
233
232
226
227
223
225
224
220
218
219
213
212
209
208
234
242
238
239
235
241
240
205
237
236
202
206
207
203
204
– 66 –
12-2. Outdoor Unit
RAS-10SAH-ES
14 43T21001 F an-Motor UE6-21SJ5P 15 43T47001 Flange, Nut 16 43T46013 Solenoid Coil 17 43T19005 Handle 18 43T49001 Rubber-Cushion 19 43T79001 Nipple, Drain 20 43T19002 Stopper, Guard 21 43T41406 Compressor, PA118X1T-4FZ 22 43055483 MF Capacitor 25µF 400V 23 43T55001 MF Capacitor 1,5µF, 500V 24 43060049 Terminal Block, 5P 25 43T46005 Valve, Checked 26 43T45004 Dryer
Location Part
Description
No. No.
Location Part
Description
No. No.
1 43T19001 Guard Fan 2 43T20001 Fan, Propeller 3 43005037 Front Cabinet 4 43T43011 Condenser 5 43062194 Cover, E-Parts 6 43005038 Back Cabinet 7 43T47024 Capillary-Tube 0,8 DIA 8 43T47007 Capillary-Tube 1,2 DIA 9 43T46011 Packed Valve, 9,52 10 43T46010 Packed Valve, 6,35 11 43T47021 Bonnet, 9,52 DIA 12 43T47020 Bonnet, 6,35 DIA 13 43T46012 4-Way-Valve, VHV-0104
1
20
3
22
23
24
15
2
14
4
18
17
6
5
21
7 : CAPILLARY TUBE 8 : CAPILLARY TUBE
9, 11
10, 12
13, 16, 25, 26
19
– 67 –
RAS-13SAH-ES
1 43005144 Cabinet, Front 2 43005143 Cabinet, Side 3 43042446 Base 4 43T19001 Guard Fan 5 43T19005 Handle 6 43T19002 Stopper, Guard 7 43T62007 Cover, E-Parts 8 43020302 Fan, Propeller
MIX-Flow , 410DIA
9 43021984 Motor, Fan
AC 220-240V, 50Hz 10 43T47001 Flange, Nut 11 43T46005 Valve, Check 12 43T63004 Holder , Wire, Lead 13 43T96001 Bushing 14 43T43012 Condenser 15 43T46010 Packed Valve, 6,35 16 43T47018 Bonnet, 6,35 DIA
17 43T46011 Packed Valve, 9,52 18 43T47020 Bonnet, 12,7 DIA 19 43T47007 Capillary Tube 1,2 DIA 20 43T47008 Capillary Tube 1,5 DIA 21 43041764 Compressor, PA160X2T-4FM
AC 220/230/240V, 50Hz 22 43T97001 Nut, Flat-Washer 23 43T49008 Cushion, Rubber 24 43T45004 Dryer 25 43T79004 Nipple, Drain 26 43055496 Capacitor, Plastic-Film
35 MFD , 400V 27 43T55009 Capacitor , Plastic-Film
1,5 MFD, 500V 28 43060049 Terminal Block, 5P 29 43T46012 4-Way Valve, VAV-0104 30 43T46013 Solenoid Coil 36 43T47017 Capillary Tube, 0,6 DIA
Location Part
Description
No. No.
Location Part
Description
No. No.
26
14
5
8
10
1
6
4
9
12
22
25
23
16
3
15
18
17
19
20
24
7
2
13
21
27
29
30
28
11
Loading...