Toshiba RAS-4M36SAH-E, RAS-3M31SAH-E-1, RAS-10SKH-E-1 SERVICE MANUAL

SERVICE MANUAL
AIR-CONDITIONER
MULTI SPLIT WALL TYPE
FILE NO. A00-9805
SUPPLEMENT
RAS-10SKH-E-1 RAS-10SKH-E-1
x
2, RAS-13SKH-E
RAS-10SKH-E-1
x 2 x 3 x 4
x 2 / RAS-M18SAH-E
x 4 / RAS-4M36SAH-E
/
RAS-3M31SAH-E-1
PRINTED IN JAPAN, Apr.,1998 ToMo

CONTENTS

1. DESCRIPTION .................................................................................................................3
2. SPECIFICATIONS............................................................................................................ 4
3. CONSTRUCTION VIEWS .............................................................................................. 11
3-1. Indoor Unit ................................................................................................................................ 11
3-2. Outdoor Unit ............................................................................................................................. 12
4. REFRIGERANT CYCLE DIAGRAMS ............................................................................ 14
5. WIRING DIAGRAM ........................................................................................................ 17
6. SPECIFICATIONS OF ELECTRICAL PARTS ............................................................... 19
6-1. Indoor Unit ................................................................................................................................ 19
6-2. Outdoor Unit ............................................................................................................................. 20
7. MICROCOMPUTER BLOCK DIAGRAMS ..................................................................... 21
8. OPERATION DESCRIPTIONS....................................................................................... 23
8-1. FAN ONLY Operation ............................................................................................................... 2 3
8-2. COOL Operation....................................................................................................................... 23
8-3. DRY Operation.......................................................................................................................... 24
8-4. HEAT Operation........................................................................................................................ 25
8-5. AUTO Operation ....................................................................................................................... 26
8-6. ECONO. Mode ........................................................................................................................... 27
8-7. Current Limit Control............................................................................................................... 27
8-8. High-Temperature Limit Control............................................................................................. 28
8-9. Low-Temperature Limit Control (Cooling Operation) .......................................................... 28
8-10. Cool Airflow Prevention Control (Heating Operation) ......................................................... 29
8-11. Defrost Operation..................................................................................................................... 29
8-12. Auto Restart Function ............................................................................................................. 3 1
8-13. Operation Control of Following Outdoor Unit....................................................................... 33
9. TROUBLESHOOTING CHART...................................................................................... 34
9-1. What to be Prechecked First................................................................................................... 34
9-2. Primary Judgement of Trouble Sources ................................................................................ 36
9-3. Troubleshooting Flowcharts ................................................................................................... 40
9-4. How to Check the Remote Control (Including the Indoor P.C. Board) ............................... 47
10. PART REPLACEMENT.................................................................................................. 52
10-1. Indoor Unit ................................................................................................................................ 5 2
10-2. Microcomputer ......................................................................................................................... 54
10-3. Outdoor Unit ............................................................................................................................. 5 5
11. CAUTIONS ON REPLACEMENT OF P.C. BOARD ASSEMBLY ................................... 64
12. EXPLODED VIEWS AND PARTS LIST ......................................................................... 65
12-1. Indoor Unit (1) ........................................................................................................................... 65
Indoor Unit (2)........................................................................................................................... 66
Indoor Unit (3)........................................................................................................................... 67
12-2. Outdoor Unit ............................................................................................................................. 6 8
– 2 –

1. DESCRIPTION

RAS-M18SAH-E
RAS-M18SAH-E can be used alone with two indoor units RAS-10SKH-E-1.
RAS-3M31SAH-E-1
in a combination of two outdoor units
RAS-13SAH-E (upper unit, one compressor) RAS-M18SAH-E (lower unit, two compressors)
The upper unit can be used with one indoor unit RAS-13SKH-E and the lower unit with two indoor units RAS-10SKH-E-1.
RAS-4M36SAH-E
The lower unit RAS-M18SAH-E can be used as a double decker under the combination name RAS-4M36SAH-E with four indoor units RAS-10SKH-E-1.
– 3 –

2. SPECIFICATIONS

RAS-10SKH-E-1 x 2 / RAS-M18SAH-E
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current Starting current A
Moisture removal lit/h Noise
Refrigerant Refrigerant control
Interconnection pipe
Condensate drain pipe Outer diameter mm
INDOOR UNIT
Dimensions Width mm
Net weight kg Evaporator type Indoor fan type
Air volume Medium fan m3/h
Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Width mm
Net weight kg Condenser type Outdoor fan type Airflow volume (220/230/240V) m3/h Fan motor output W Compressor Model
Safety device Auto louver Usable outdoor temperature range °C
Indoor (H/M/L) dB Outdoor (220/230/240V) dB Name of refrigerant Rated volume kg
Gas side size mm Connection type Liquid side size mm Connection type Maximum length (One way) m *2 Maximum height difference
Indoor unit Outdoor unit
Height mm
Depth mm
High fan m3/h
Low fan m3/h
Height mm
Depth mm
Output W
A
Indoor/Outdoor
m
Model
RAS-10SKH-E-1 x 2 / RAS-M18SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
5,0 5,0 5,0 5,6 5,6 5,6
Single
220/230/240
50
2,04/2,10/2,18 1,78/1,86/1,96
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,22/9,54 0,22/9,7 0,22/9,96 0,22/8,38 0,22/8,66 0,22/9,16
19
1,2 41/36/31 52/53/54
R-22
1,4 (0,7+0,7)
Capillary tube
9,52
Flare connection
6,35
Flare connection
15
5
16
RAS-10SKH-E-1
265 790 174
8
Finned tube
Cross flow fan
600 500 400
19
Polypropylene net filter (Washable)
RAS-M18SAH-E
538 830 300
55
Finned tube
Propeller
1830/1920/2010
28
PH120T1-4C x 2
750W x 2
Fuse, Overload relay
Yes
21 ~ 43 – 5 ~ 21
Specifications are subject to change without notice.
– 4 –
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current
A
Indoor/Outdoor
Model
RAS-10SKH-E-1 / RAS-M18SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
2,50 2,50 2,50 2,80 2,80 2,80
Single
220/230/240
50
1,02/1,05/1,09 0,89/0,93/0,98
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,11/4,77 0,11/4,85 0,11/4,98 0,11/4,19 0,11/4,33 0,11/4,58
– 5 –
RAS-10SKH-E-1 x 2, RAS-13SKH-E / RAS-3M31SAH-E-1
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current Starting current A
Moisture removal lit/h Noise
Refrigerant Refrigerant control
Interconnection pipe
Condensate drain pipe Outer diameter mm
INDOOR UNIT
Dimensions Width mm
Net weight kg Evaporator type Indoor fan type
Air volume Medium fan m3/h
Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Width mm
Net weight kg Condenser type Outdoor fan type Airflow volume (220/230/240V) m3/h Fan motor output W Compressor Model
Safety device Auto louver Usable outdoor temperature range °C
Indoor (H/M/L) dB Outdoor (220/230/240V) dB Name of refrigerant Rated volume kg
Gas side size mm Connection type Liquid side size mm Connection type Maximum length (One way) m *2 Maximum height difference
Indoor unit Outdoor unit
Height mm
Depth mm
High fan m3/h
Low fan m3/h
Height mm
Depth mm
Output W
A
Indoor/Outdoor
m
Model
RAS-10SKH-E-1 x 2, RAS-13SKH-E / RAS-3M31SAH-E-1
Cooling Heating
220V 230V 240V 220V 230V 240V
8,45 8,50 8,50 9,60 9,65 9,70
Single
220/230/240
50
3,30/3,38/3,48 2,97/3,09/3,23
96/93/90 94/93/89
220V 230V 240V 220V 230V 240V
0,37/15,24 0,37/15,36 0,37/15,71 0,37/13,92 0,37/14,14 0,37/14,70
19+19+25
1,2+1,2+2,0
RAS-10SKH-E-1 : 41/36/31 RAS-13SKH-E : 44/39/36
52/53/54
R-22
2,28 (0,7+0,7+0,88)
Capillary tube
RAS-10SKH-E-1 : 9,52 RAS-13SKH-E : 12,7
Flare connection
6,35
Flare connection
15
RAS-10SKH-E-1 : 5 RAS-13SKH-E : 6
16
RAS-10SKH-E-1 RAS-13SKH-E
265 790 174
8
Finned tube
Cross flow fan 600 650 500 560 400 510
19
Polypropylene net filter (Washable)
RAS-3M31SAH-E-1
1125
830 300 106
Finned tube
Propeller
1830/1920/2010
28
PH120T1-4C x 2 + PH170T2-4L2
750W x 2 + 1100W x 1
Fuse, Overload relay
Yes
21 ~ 43 – 5 ~ 21
Specifications are subject to change without notice.
– 6 –
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current
Item
Capacity *1 kW
Power source V
Power consumption kW Power factor %
Running current
Item
Capacity *1 kW
Power source V
Power consumption kW Power factor %
Running current
Item
Capacity *1 kW
Power source V
Power consumption kW Power factor %
Running current
A
Indoor/Outdoor
Phase
Hz
A
Indoor/Outdoor
Phase
Hz
A
Indoor/Outdoor
Phase
Hz
A
Indoor/Outdoor
Model
Model
Model
Model
RAS-10SKH-E-1, RAS-13SKH-E / RAS-3M31SAH-E-1
Cooling Heating
220V 230V 240V 220V 230V 240V
5,95 6,00 6,00 6,80 6,85 6,90
Single
220/230/240
50
2,28/2,33/2,39 2,08/2,16/2,25
97/94/91 95/93/90
220V 230V 240V 220V 230V 240V
0,26/10,47 0,26/10,51 0,26/10,73 0,26/9,73 0,26/9,81 0,26/10,12
RAS-10SKH-E-1 x 2 / RAS-3M31SAH-E-1
Cooling Heating
220V 230V 240V 220V 230V 240V
5,0 5,0 5,0 5,6 5,6 5,6
Single
220/230/240
50
2,04/2,10/2,18 1,78/1,86/1,96
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,22/9,54 0,22/9,70 0,22/9,96 0,22/8,38 0,22/8,66 0,22/9,16
RAS-13SKH-E / RAS-3M31SAH-E-1
Cooling Heating
220V 230V 240V 220V 230V 240V
3,45 3,50 3,50 4,00 4,05 4,10
Single
220/230/240
50
1,26/1,28/1,30 1,19/1,23/1,27
98/96/92 95/95/93
220V 230V 240V 220V 230V 240V
0,15/5,70 0,15/5,66 0,15/5,75 0,15/5,54 0,15/5,48 0,15/5,54
RAS-10SKH-E-1 / RAS-3M31SAH-E-1
Cooling Heating
220V 230V 240V 220V 230V 240V
2,50 2,50 2,50 2,80 2,80 2,80
Single
220/230/240
50
1,02/1,05/1,09 0,89/0,93/0,98
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,11/4,77 0,11/4,85 0,11/4,98 0,11/4,19 0,11/4,33 0,11/4,58
– 7 –
RAS-10SKH-E-1 x 4 / RAS-4M36SAH-E
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current Starting current A
Moisture removal lit/h Noise
Refrigerant Refrigerant control
Interconnection pipe
Condensate drain pipe Outer diameter mm
INDOOR UNIT
Dimensions Width mm
Net weight kg Evaporator type Indoor fan type
Air volume Medium fan m3/h
Fan motor output W Air filter
OUTDOOR UNIT
Dimensions Width mm
Net weight kg Condenser type Outdoor fan type Airflow volume (220/230/240V) m3/h Fan motor output W Compressor Model
Safety device Auto louver Usable outdoor temperature range °C
Indoor (H/M/L) dB Outdoor (220/230/240V) dB Name of refrigerant Rated volume kg
Gas side size mm Connection type Liquid side size mm Connection type Maximum length (One way) m *2 Maximum height difference
Indoor unit Outdoor unit
Height mm
Depth mm
High fan m3/h
Low fan m3/h
Height mm
Depth mm
Output W
A
Indoor/Outdoor
m
Model
RAS-10SKH-E-1 x 4 / RAS-4M36SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
10,0 10,0 10,0 11,2 11,2 11,2
Single
220/230/240
50
4,08/4,20/4,36 3,56/3,72/3,92
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,44/19,08 0,44/19,4 0,44/19,92 0,44/16,76 0,44/17,32 0,44/18,32
19+19+19+19
1,2+1,2+1,2+1,2
41/36/31
54/55/56 55/56/57
R-22
2,8 (0,7+0,7+0,7+0,7)
Capillary tube
9,52
Flare connection
6,35
Flare connection
15
5
16
RAS-10SKH-E-1
265 790 174
8
Finned tube
Cross flow fan
600 500 400
19
Polypropylene net filter (Washable)
RAS-4M36SAH-E
1125
830 300 119
Finned tube
Propeller
1830/1920/2010
28
PH120T1-4C
750W x 4
Fuse, Overload relay
Yes
21 ~ 43 – 5 ~ 21
Specifications are subject to change without notice.
– 8 –
Item
Capacity *1 kW
Phase
Power source V
Hz Power consumption kW Power factor %
Running current
Item
Capacity *1 kW
Power source V
Power consumption kW Power factor %
Running current
Item
Capacity *1 kW
Power source V
Power consumption kW Power factor %
Running current
A
Indoor/Outdoor
Phase
Hz
A
Indoor/Outdoor
Phase
Hz
A
Indoor/Outdoorr
Model
Model
Model
RAS-10SKH-E-1 x 3 / RAS-4M36SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
7,50 7,50 7,50 8,40 8,40 8,40
Single
220/230/240
50
3,06/3,15/3,27 2,67/2,79/2,94
97/94/91 95/93/90
220V 230V 240V 220V 230V 240V
0,33/14,31 0,33/14,55 0,33/14,94 0,33/12,57 0,33/12,99 0,33/13,74
RAS-10SKH-E-1 x 2 / RAS-M36SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
5,0 5,0 5,0 5,6 5,6 5,6
Single
220/230/240
50
2,04/2,10/2,18 1,78/1,86/1,96
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,22/9,54 0,22/9,70 0,22/9,96 0,22/8,38 0,22/8,66 0,22/9,16
RAS-10SKH-E-1 / RAS-4M36SAH-E
Cooling Heating
220V 230V 240V 220V 230V 240V
2,50 2,50 2,50 2,80 2,80 2,80
Single
220/230/240
50
1,02/1,05/1,09 0,89/0,93/0,98
95/92/89 94/91/87
220V 230V 240V 220V 230V 240V
0,11/4,77 0,11/4,85 0,11/4,98 0,11/4,19 0,11/4,33 0,11/4,58
– 9 –
Note : *1
• Capacity is based on the following temperature conditions.
JIS C9612-1994Condition
T emperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Notes : *2
(DB)
(WB)
(DB)
(WB)
Cooling
27°C 19°C 35°C 24°C
Heating
20°C
— 7°C 6°C
RAS-13SKH-E / RAS-3M31SAH-E-1
• No additional refrigerant required.
• This air conditioner accepts a connection piping length of up to 15m and a head of up to 6m.
• There is no need to add the refrigerant as long as the total length of the connection piping is up to 15m.
RAS-10SKH-E-1 / RAS-M18SAH-E, RAS-10SKH-E-1 / RAS-3M31SAH-E-1, RAS-10SKH-E-1 / RAS-4M36SAH-E
• This air conditioner accepts a connection piping length of up to 15m and a head of up to 5m.
• There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
• There is need to add the refrigerant 20g/m as long as the each length of the connection piping is up to 11m to 15m.
– 10 –
3-1. Indoor Unit
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
RAS-10SKH-E-1 RAS-13SKH-E
Air inlet

3. CONSTRUCTION VIEWS

Air filter
790
Heat exchanger
174
265
Air outlet
232 326 232
Drain hose (0,54m)
Hanger
Connecting pipe (0,39m)
13SKH-E 10SKH-E-1: (Flare ø9,52)
: (Flare ø12,7)
790
Hanger
321
Connecting pipe (0,49m) (Flare ø6,35)
Front panel
Back body
47
47
Knock out system
50
10
Knock out system
50
10
65965,5 450
Hanger
326
66 or more
Minimum distance
46
2,5
Minimum distance
17 20
265
to wall
120 or more 120 or more
3,5
40,5
Center line
to ceiling
HangerHanger
Installation plate outline
790
– 11 –
12626931976
65,5
Hanger For stud bolt
(ø8~ø10) For stud bolt
(ø6)
Minimum distance to wall
20 2037
40,5
60,5
Wireless remote control
Remote control holder
55
136
16
112,8
559,6
3-2. Outdoor Unit
RAS-M18SAH-E
Liquid side
Electric
parts cover
6,35)
φ
(Flare
9,52)
φ
Gas side
(Flare
600 or more
10
φ
8-
11x14
φ
φ
for
4x
anchor bolt
10 anchor bolt)
φ
8-
φ
11x14 hole
6 hole
φ
φ
8-
(for
6-
(for fixing outdoor unit)
Service
port
FOR UNIT B
54545491
FOR UNIT A
Air inlet
600
Installation dimension
Air inlet
325
100 or more
600 or more
Air outlet
100 or more
φ25 Drain outlet
120
A
R10
600
50
36
Detail Drawing
A
52
23
325
325
6 hole
φ
301
11x14 hole
φ
Fan guard
Handle
420
φ
830 60 344
90 600 90 50
538
300
– 12 –
RAS-3M31SAH-E-1 RAS-4M36SAH-E
600 or more
4-φ11x14
for φ8-φ10
anchor bolt
Liquid side
Electrical
parts cover
(Flare φ6,35)
Size
φ12,7
φ9,52
Gas side (Flare)
Model name
RAS-3M31SAH-E-1
RAS-4M36SAH-E
Liquid side
Electrical
parts cover
(Flare φ6,35)
Gas side
(Flare φ9,52)
Air inlet
600
Air inlet
Mounting dimension of anchor bolt
325
100 or more
φ25 Drain outlet
120
600 or more
300
Air outlet
100 or more
4-φ11x14 hole
(for φ8 φ10 anchor bolt)
8-φ6 hole
(for fixing outdoor unit)
186
Service
port
54677,5
Handle
60
Service
port
54545491
325 (pitch)(8,5) (8,5)
600 90 55
835 60 342
A
52,5
325
R12
600
Detail Drawing
36
50
A
23
φ 6 hole
311
325
φ11x14 hole
1125
Drain outlet
90
29
– 13 –

4. REFRIGERANT CYCLE DIAGRAMS

RAS-10SKH-E-1 x 2 / RAS-M18SAH-E
P
Packed valve Packed valve
(3/8) (1/4)
T1
Indoor Unit
Indoor heat exchanger A
Indoor heat exchanger B
Heating
Cooling
Accumulator
50Hz
Standard High temperature*1 Low temperature Standard High temperature Low temperature
4-way valve
PH120T1-4C
PH120T1-4C
Outdoor heat exchanger
Outdoor Unit
Standard pressure
P
(kg/cm²G)
10SKH-E-1
15,0
19 ~ 23
12,5 6,0 6,5 4,0
Check valve
CompressorCompressor
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
10SKH-E-1
40,0
52,0 ~ 59,0
35,0 12,0 15,0 2,0
Capillary for cooling & heating ø1,7x800
Dryer
Capillary for heating ø1,7x300
Fan speed
(indoor)
High
Low High High High
Low
Cooling
Heating
Ambient temp.
conditions DB/WB
(°C)
Indoor
20/– 27/–
20/– 27/19 32/23 21/15
Outdoor
7/6
21/15
–10/–10
35/24 43/26 21/15
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 • During heating overload, the high temperature limit control operation is included.
*
– 14 –
RAS-10SKH-E-1 x 2, RAS-13SKH-E / RAS-3M31SAH-E-1 (Upper and Lower Unit)
0,49m (Connecting pipe) ø12,7
O.D.: 12,7mm
Cooling
Heating
RAS-13SKH-E
Indoor Unit
Cooling
Heating
Heat exchanger
Cross flow fan
P
Packed valve
(ø12,7)
Gas container connection (Reinstall etc.) Heating
4-way valve
Cooling
Comp­ressor
PH170T2-4L2
Accumulator
Capillary tube
ø1,7x400
Heat exchanger
T1
Packed valve
(ø6,35)
Capillary tube
ø0,6x1500
Capillary tube
ø1,2x400
0,39m (Connecting pipe) ø6,35
O.D.: 6,35mm
P
4-way valve
Comp-
ressor
PH120T1-4C
Accumulator
RAS-10SKHE-1 x 2
Indoor Unit
Indoor heat
exchanger A
Indoor heat
exchanger B
Packed
valve
(3/8) (1/4)
Packed
valve
Check valve
Comp-
ressor
PH120T1-4C
T1
Capillary for heating ø1,7x300
Capillary for cooling & heating ø1,7x800
Dryer
Cooling Heating
Propeller fan
Outdoor Unit
Mark ( ) means check points of Gas Leak
50Hz
Standard
Heating
High temperature*1 Low temperature Standard
Cooling
High temperature Low temperature
Refrigerant R-22 0,88kg
Standard pressure
P
(kg/cm²G)
13SKH-E
10SKH-E-1
15,0
19 ~ 23
12,5
5,0 6,0
6,0 6,5
4,0
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
13SKH-E 10SKH-E-1
43,0 40,0
52,0 ~ 59,0
35,0 10,0 12,0 14,0 15,0
2,0
Outdoor heat
exchanger
Outdoor Unit
Fan speed
(indoor)
High
Low High High High
Low
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 • During heating overload, the high temperature limit control operation is included.
*
Cooling Heating
Ambient temp.
conditions DB/WB
(°C)
Indoor
20/– 27/–
20/– 27/19 32/23 21/15
Outdoor
7/6
21/15
–10/–10
35/24 43/26 21/15
– 15 –
RAS-10SKH-E-1 x 4 / RAS-4M36SAH-E (Upper and Lower Unit)
P
4-way valve
Comp-
ressor
PH120T1-4C
Accumulator
Indoor Unit
Indoor heat
exchanger A
Indoor heat
exchanger B
Packed
valve
(3/8) (1/4)
Packed
Comp­ressor
PH120T1-4C
valve
Check valve
T1
Capillary for heating ø1,7x300
Capillary for cooling & heating ø1,7x800
Dryer
P
4-way valve
Comp-
ressor
PH120T1-4C
Accumulator
Indoor Unit
Indoor heat
exchanger A
Indoor heat
exchanger B
Packed
valve
(3/8) (1/4)
Packed
Comp-
ressor
PH120T1-4C
valve
Check valve
T1
Capillary for heating ø1,7x300
Capillary for cooling & heating ø1,7x800
Dryer
Heating
Cooling
Outdoor heat
exchanger
Outdoor Unit
50Hz
Standard High temperature*1 Low temperature Standard High temperature Low temperature
Cooling Heating
Standard pressure
P
(kg/cm²G)
10SKH-E-1
15,0
19 ~ 23
12,5 6,0 6,5 4,0
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
10SKH-E-1
40,0
52,0 ~ 59,0
35,0 12,0 15,0 2,0
Outdoor heat
exchanger
Outdoor Unit
Fan speed
(indoor)
High
Low High High High
Low
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 • During heating overload, the high temperature limit control operation is included.
*
Cooling
Heating
Ambient temp.
conditions DB/WB
(°C)
Indoor
20/– 27/–
20/– 27/19 32/23 21/15
Outdoor
7/6
21/15
–10/–10
35/24 43/26 21/15
– 16 –

5. WIRING DIAGRAM

INDOOR UNIT
RAS-13SKH-E / RAS-3M31SAH-E-1 (Upper Unit)
SG01
BLK
GRN&YEL
L N
POWER
TERMINAL
1 2 3 4
BLK WHI RED BLU GRN&YEL
BLOCK
INDOOR UNIT
INDOOR
TERMINAL
BLOCK
RAS-10SKH-E-1x2/RAS-M18SAH-E RAS-10SKH-E-1x2/RAS-3M31SAH-E-1 (Lower Unit) RAS-10SKH-E-1x2/RAS-4M36SAH-E
(Upper and Lower Unit)
SG01
BLK
TERMINAL
INDOOR
TERMINAL
BLOCK
GRN&YEL
L N
POWER
BLOCK
BLK
1
2
WHI
RED
3
BLU
4
P04
GRN & YEL
11 2 3
4 4
CN27
DSA
BRW
BLU
RY02
T02 C.T.
WHI
THERMAL FUSE
77°C × 2
R109
VARISTOR
F01 FUSE
343
4
BLK
RY03
RY04
T3,15A
250V
RY01
CR01
CR02
GRY 1 1
R21
LOUVER
MOTOR
GRY
3
CN04
3
R116
IC04
C15
1
BLU
1 1
INFRARED RAYS RECEIVE
AND INDICATION PARTS
2 3
BLU
2 2
L01
CN07
BLU
3 3
BRW
CN27
4
567 8 9
BLU
BLU
4
567 8 9
4
567 8 9
BLU
BLU
BLU
DSA
P04
RY02
11 2 3
4 4
ORN
PNK
YEL
346
5
346
5
R01
C01
PNK
BLK
WHI
THERMAL FUSE
VARISTOR
343
4 T02 C.T.
WHI
RY03
RED
BRW
2
1
2
1
DB01
C02
CN13
CN25
77°C × 2
R109
F01 FUSE
T3,15A
250V
RY01
BLK
RY04
CR01
CR02
DC
MOTOR
BLK
BLU
YEL
RED
WHI
4
3
5
2
1
4
3
5
2
1
MAIN P.C. BOARD
MCC-713
T01
C06
IC
IC01
2
1
CN03
2
1
BLK
BLK
THERMO SENSOR (TA)
LOUVER
MOTOR
GRY
GRY 3
1
CN04
1
3
R116
C15
R21
INFRARED RAYS RECEIVE
AND INDICATION PARTS
FAN MOTOR
CN10
DC35V
DC12V
DC7V
DC0V
IC02
2
1
CN01
2
1
BLK
BLK
HEAT EXCHANGER SENSOR (TC)
IC04
1
BLU
1 1
2 3
BLU
2 2
L01
CN07
BLU
3 3
4
BLU
4 4
PNK
BLU
5 5
R01
C01
567 8 9
BLU
BLU
PNK
567 8 9 567 8 9
ORN
YEL
RED
BRW
346
2
1
346
2
1
DB01
C02
IC01
CN13
BLK
WHI
CN25
DSA : Surge absorbor C.T : Current trans
FAN MOTOR
DC
MOTOR
BLK
BLU
YEL
RED
WHI
4
3
5
2
1
4
3
5
2
1
CN10
MAIN P.C. BOARD
MCC-713
T01
C06
IC
2
1
CN03 CN01
2
1
BLK
BLK
THERMO SENSOR (TA)
GRN&YEL
L N
POWER
TERMINAL
BLOCK
BLK
WHI
1
2
RED
BLU
3
4
DC 35V
DC 12V
DC 7V
DC 0V
IC02
2
1
2
1
BLK
BLK
HEAT EXCHANGER SENSOR (TC)
BLK
P04
GRN & YEL
4 4
CN27
BRW
BLU
11 2 3
SG01
DSA
RY02
T02
C.T.
WHI
THERMAL FUSE
77°C × 2
R109
VARISTOR
F01 FUSE
T3,15A
250V
343
4
BLK
RY03
RY04
CR01
CR02
RY01
GRY
GRY 3
1 1
3
R21
COLOR IDENTIFICATION
:
BROWN
BRW
:
RED
RED
:
WHITE
WHI
:
YELLOW
YEL
:
BLUE
BLU
:
BLACK
BLK
:
GRAY
GRY
:
PINK
PNK
:
ORANGE
ORN
:
GRN&YEL
LOUVER
MOTOR
CN04
R116
IC04
C15
1
BLU
1 1
INFRARED RAYS RECEIVE
AND INDICATION PARTS
GREEN & YELLOW
ORN
PNK
YEL
BLU
346
5
346
5
CN07
R01
C01
L01
4
2 3
567 8 9
BLU
BLU
BLU
BLU
BLU
PNK
BLK
WHI
4
2
567 8 9
3
4
2
567 8 9
3
DB01
CN13
CN25
RED
2 2
BRW
1 1
MOTOR
BLU
WHI
4
5
4
5
C02
IC
IC01
1 1
BLK
DSA : Surge absorbor C.T : Current trans
DC
FAN MOTOR
BLK
YEL
RED
3
2
1
3
2
1
CN10
MAIN P.C. BOARD
MCC-713
T01
C06
2 2
BLK
CN03
THERMO SENSOR (TA)
DC35V
DC12V
DC7V
DC0V
IC02
2
1
CN01
2
1
BLK
BLK
HEAT EXCHANGER SENSOR (TC)
OVERLOAD RELAY
THERMOSTAT FOR
COMPRESSOR
COMPRESSOR
BLK
1
RED
2
WHI
3
BLK
4
TERMINALS
BLK
1
RED
2
WHI
3
BLK
4
TERMINALS
BLK
L
RED
N
YEL & GRN
TRANSFORMER
RED
WHI
BLU
YEL
ORN
FAN MOTOR
OUTDOOR UNIT
1
2
3
TERMINALS
BLK
BLK
BLK
RED
CAPACITOR
PNK
WHI
4 3
RY01
CN09
1
1
3
3
CN04
4 3
RY02
CN10
1
1
CN05
3
3
F01
Fuse
5
5
3
3
SG01 300V
1
1
CN01
1
1
CN02
3
3
CN
131
03
2 2
3
CN08 CN07 CN06
5 5
BLK RED
BLK
RED WHI
CAPACITOR
4
BRW
BRW
SOLENOID
CAPACITOR
COIL
RED
RED
FAN MOTOR
MAIN P.C. BOARD (MCC-738)
R01
R02
C01 C02
RY06
RY04
CR04 CR02 CR01
1
1 3 1 3
3
1
3
BLK BLK
1 2
UNIT B
COIL FOR
RED
4 WAY VALVE
GRN & YEL
CHASSIS
WHI
BLK
UNIT A
COIL FOR
4 WAY VALVE
RY03
OVERLOAD
RELAY
BLK
OVERLOAD
RELAY
BLK
CN11
1 2 3 4
5 6 7 8
CN12
1 2 313
CN13
1 2 313
CAPACITOR WHI
PNK
COMPRESSOR
CAPACITOR WHI
PNK
COMPRESSOR
HEAT
BLK
EXCHANGER SENSOR
BLK
(TE)
HEAT
BLK
EXCHANGER SENSOR
BLK
(TE)
RED
RED
– 17 – – 18 –
6-1. Indoor Unit
RAS-10SKH-E-1 RAS-13SKH-E

6. SPECIFICATIONS OF ELECTRICAL PARTS

No.
1
Fan motor (for indoor)
Thermo. sensor
2
(TA-sensor)
3
DC-DC transformer (T01)
4
Microcomputer Power relay (RY01),
5
Common relay (RY02) Heat exchanger sensor
6
(TC-sensor) Line filter (L01)
7
Diode (DB01)
8
Capacitor (C02)
9
10
Fuse (F01) Relay (for outdoor fan motor,
11
solenoid coil) (RY03, RY04)
Parts name
Type
ICF-35-19-3
or
TICF-35-19-3
(microprocessor)
SWT-34
TMP87CK40F
DI1U
(microprocessor)
RF-103YOR6
RBV-406
CEAUF2W101M20
MT3
AJQ1341
Specifications
DC 35V, 19W
10k at 25°C
DC390V, Secondary DC35V, 12V, 7V
Coil : DC12V 75mA, Rated AC250V 20A
10k at 25°C
10mH, AC 0,6A 4A, 600V 100µF, 450V T3,15A, 250V
Coil DC12V, 33mA, Rated 1A 250V AC
Power supply IC (IC01)
12
Varistor (R21, R109)
13
Resistor (R01)
14
Current trans (T02)
15
Louver motor
16
MA2830-FJ
15G561K
ERF-5TK5R6
CT422920S-01
MP35EA7
4A, 600V 560V 5,6 Ω, 5W
Output (Rated) 2W, 10 poles, 1 phase DC 12V
– 19 –
– 19 –
6-2. Outdoor Unit
RAS-3M31SAH-E-1 (Upper Unit)
No. Parts name Type
1 Compressor PH170T2-4L2
2 Fan motor (for outdoor) AF-230-28P
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve) 6 Overload relay J-MRA99257-9200 7 Thermostat for Compressor CS-7
SK-50FMP
SK-40CMP35U1
LB60012
RAS-M18SAH-E RAS-3M31SAH-E-1 (Lower Unit) RAS-4M36SAH-E (Upper and Lower Unit)
Specifications
Output (Rated) 1100W, 2 pole, 1 phase, 220/230/240V, 50Hz
Winding resistance (Ω) (at 20°C)
Output (Rated) 28W, 6 pole, 1 phase, 220/230/240V, 50Hz
Winding resistance (Ω) (at 20°C)
500V AC, 1,5µF
400V AC, 35µF
AC : 200/240V
UT 8,0A (80°C), OPEN 145±5°C, CLOSE 75±11°C 130°C OFF, 70°C ON
Red-Black White-Black
2,22 3,04
Red-Black White-Black
198 160
No. Parts name Type
1 Compressor PH120T1-4C
2 Fan motor (for outdoor) AF-230-28P
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve) 6 Overload relay J-MRA99269-9200 7 Transformer FT-70 8 Outdoor P.C. board MCC-738
Heat exchanger sensor
9
(TE-sensor)
SK-45FMP
SK-40CMP30U1
LB60012
(microprocessor)
Specifications
Output (Rated) 750W, 2 pole, 1 phase, 220/230/240V, 50Hz
Winding resistance (Ω) (at 20°C)
Output (Rated) 28W, 6 pole, 1 phase, 220/230/240V, 50Hz
Winding resistance (Ω) (at 20°C)
450V AC, 2µF
400V AC, 30µF
AC : 200/240V
U/T 6,8A (90°C), OPEN 135±5°C, CLOSE 69±11°C AC : 220/240V
10k at 25°C
Red-Black White-Black
4,53 8,73
Red-Black White-Black
198 160
– 20 –
7. MICROCOMPUTER BLOCK DIAGRAMS
RAS-13SKH-E / RAS-3M31SAH-E-1 (Upper Unit)
Operation
C. P. U
Functions
Timer
Display
• Louver Control
Display
ECONO.
Sign Display
• 3-minutes Delay at Restart for Compressor
PRE-DEF.
Sign Display
• Motor Revolution Control
Indoor
Fan Motor
• Processing
(Temperature Processing)
• Timer
Signal
Louver
ON/OFF
Signal
ON/OFF
4-Way Valve
Signal
ON/OFF
Outdoor Fan
Signal
ON/OFF
Compressor
Motor
Louver
Relay
Relay
RY01 RY03 RY04
Relay Driver, Louver Driver
Relay
4-Way ValveOutdoor Fan MotorCompressor
RY02
Relay
Main Unit Control Panel
Current Sensor
Thermo. Sensor
Heat Exchanger Sensor
Initializing Circuit
(Compressor Current)
Infrared Rays Signal Receiver
Oscillator Circuit
Clock Frequency
Rays
Infrared
Remote Control
Circuit
Power
Supply
Thermo. Setting
Fan Speed Selection
Operation Mode Selection
Operation (START/STOP)
AUTO, COOL, DRY, HEAT, FAN ONLY
– 21 –
Noise Filter
ON TIMER Setting
OFF TIMER Setting
ECONO.
Louver AUTO Swing
Louver Direction Setting
AC220/230/240V ~
50Hz
RAS-10SKH-E-1 RAS-10SKH-E-1 RAS-10SKH-E-1
/
RAS-M18SAH-E
/
RAS-3M31SAH-E-1 (Lower Unit)
/
RAS-4M36SAH-E (Upper and Lower Unit)
50Hz
C. P. U
ON/OFF Signal
Compressor (A)
Compressor (B)
4-Way
Valve (A)
RY03
Relay
Relay
Driver
ON/OFF Signal
ON/OFF Signal
4-Way Valve (A)
4-Way
Valve (B)
RY04
Relay
ON/OFF Signal
4-Way Valve (B)
Outdoor
Fan Motor
RY06
Relay
Outdoor Fan
ON/OFF Signal
Circuit
Initializing
Oscillator Circuit
Clock Frequency
• Compressor (A), (B) Control
• 4-Way Valve (A), (B) Control
• Outdoor Fan Control
• Defrost Control
Circuit
Power Supply
AC 220/230/240V
Transformer
Relay
ON/OFF Signal
Compressor (A)
Heat Exchanger Sensor (A)
Heat Exchanger Sensor (B)
RY01
ON/OFF Signal
4-Way Valve (A)
Compressor (A)
Indoor
Unit (A)
Outdoor Fan
ON/OFF Signal
– 22 –
RY02
Relay
ON/OFF Signal
Compressor (B)
ON/OFF Signal
4-Way Valve (B)
Compressor (B)
Indoor
Unit (B)
Outdoor Fan
ON/OFF Signal
Note:
If unit (A) and (B) operation modes are different (as Cool, Heater Auto), operating priority is
given for “Heat” mode unit, and “Cool” mode unit will be stopped due to overload relay actuate.
8. OPERATION DESCRIPTIONS
8-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY) (1) During this mode, the relay R Y01 is alw a ys turned
off so that only the indoor fan is operated. RY02 is always turnd on.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig. 8-1-1.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 8-1-1.
28 27
Room temp.
26 25 24
Fig. 8-1-1 Auto setting of air volume
Table 8-1-1 Manual setting of FAN SPEED
Indication of
FAN SPEED
HIGH
MED LOW(+)
LOW
LOW
HIGH Air volume (m3/h)
13SKH-E 10SKH-E-1
8-2. COOL Operation
(MODE of the remote control : COOL) (1) Compressor, 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 8-2-1.
+1
(Room temp. – Set temp.)
Set
0
temp.
ON
ON ON
OFF
(RY01)
Compressor
Fig. 8-2-1
(2) Relays RY01 and RY02 are turned on to energize
the outdoor unit, and a cool operation is carried out.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig. 8-2-2.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 8-1-1.
ON
OFF
OFF
(RY02)
(RY04)
4-way valve
Common relay
Outdoor fan
(RY03)
OPERATION
display
LOW MED
HIGH
510 400 560 500 650 600
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
AUTO
+4 +3 +2 +1
(Room temp. – Set temp.)
Set
0
temp.
RY01
OFF
HIGH
LOW(+)
(continuous)
Fig. 8-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
– 23 –
MED
LOW LOW
FAN
Manual
According to the set
position