7-2-1. Louver Control ......................................................................................................................................13
7-4-1. T emporary Auto.....................................................................................................................................14
8-3-2. Installation Parts ...................................................................................................................................21
8-4.Indoor Unit ................................................................................................................................ 22
8-4-1. Cutting a Hole and Mounting Installation Plate .................................................................................22
8-4-2. Electrical Work ......................................................................................................................................23
8-4-4. Piping and Drain Hose Installation......................................................................................................26
8-4-5. Indoor Unit Installation .........................................................................................................................27
8-6-1. Gas Leak Test .................................................................................................................. ...................... 31
8-6-2. Test Operation .......................................................................................................................................31
8-6-3. Auto Restart Setting .............................................................................................................................31
9-1.What to be Prechecked First .................................................................................................. 32
9-1-1. Power Supply Voltage........................................................................................................................... 32
9-1-2. Incorrect Cable Connection between Indoor and Outdoor Units.....................................................32
9-1-3. Misleading but Good Operations.........................................................................................................33
9-2.Primary Judgement of Trouble Sources ............................................................................... 3 4
9-2-1. Role of Indoor Unit Controller..............................................................................................................34
9-2-2. Display of Abnormalities and Judgement of the Abnormal Spots...................................................34
9-3-1. Power can not be Turned on ................................................................................................................ 38
9-3-2. Power can not be Turned on after Replacing Indoor PC Board .......................................................39
9-3-3. Outdoor Unit does not Operate ...........................................................................................................39
9-3-4. Only Compressor does not Operate ...................................................................................................40
9-3-5. Only Outdoor Fan does not Operate ...................................................................................................41
9-3-6. Only the Indoor Fan does not Operate................................................................................................42
9-4.How to Check the Remote Control (Including the Indoor PC Board) ................................ 43
9-4-1. How to Check the PC Board.................................................................................................................44
9-4-2. PC Board Layout ...................................................................................................................................46
9-4-3. How to Reduce the Operation Time of the Anti-Restar t Timer .........................................................47
10. PART REPLACEMENT ................................................................................................. 48
10-1. Indoor Unit ............................................................................................................... ................. 48
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
Ambient temp.
conditions DB/WB
(°C)
Indoor
27/19
32/23
21/15
Outdoor
35/24
43/26
21/15
– 10 –
6. MICRO-COMPUTER BLOCK DIAGRAM
Operation
C. P. U
Timer
Display
Functions
Display
• Louver Control
ECONO.
Sign Display
• 3-minute Delay at Restart for Compressor
Indoor
FAN-ONLY
Sign Display
• Motor Revolution Control
• Processing
Fan Motor
(Temperature Processing)
• Timer
Motor
Louver
Louver
ON/OFF Signal
Relay Driver, Louver Driver
ON/OFF Signal
Compressor, Outdoor Fan
Relay
Outdoor Fan Motor
RY01
Compressor
RY02
Relay
Main Unit Control Panel
Thermo Sensor
Heat Exchanger Sensor
Initializing Circuit
Infrared
Infrared Rays Signal Receiver
Oscillator Circuit
Clock Frequency
Rays
Remote Control
Operation (START/STOP)
Circuit
Power Supply
Thermo Setting
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Noise Filter
ON TIMER Setting
Fan Speed Selection
– 11 –
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
ECONO.
AC 220/230/240V~
50Hz
7. OPERATION DESCRIPTIONS
(Room temp. – Set temp.)
+1
0
Set
temp.
ON
OFF
OPERATION
display
ONON
Compressor
Outdoor fan
(RY01)
Common relay
(RY02)
7-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY)
(1) During this mode, the relay R Y01 is alwa ys turned
off so that only the indoor fan is operated. RY02
is always turnd on. FAN-ONLY display is lit.
1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
28
27
Room temp.
26
25
24
Fig. 7-1-1 Auto setting of air volume
Table 7-1-1 Manual setting of FAN SPEED
Indication of
FAN SPEED
HIGH
MED
LOW(+)
LOW
LOW
HIGH Air volume
(m3/h)
7-2. COOL Operation
(MODE of the remote control : COOL)
(1) Compressor, outdoor fan and operation display
are controlled as shown in Fig. 7-2-1.
Fig. 7-2-1
(2) Relays RY01 and R Y02 are turned on to energize
the outdoor unit, and a cool operation is carried
out.
1) When the FAN is set to AUTO, the indoor fan
motor operates as shown in Fig 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH,
the indoor fan motor operates with a constant
in volume as listed in Table 7-1-1.
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing the START/STOP button.
LOW
MED
HIGH
430
510
650
– 12 –
FAN
Manual
According
to the set
position
+4
+3
+2
+1
(Room temp. – Set temp.)
Set
0
temp.
RY01
OFF
AUTO
HIGH
MED
LOW(+)
LOW
LOW
(continuous)
Fig. 7-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing the START/STOP button.
7-2-1. Louver Control
(Room temp. – Set temp.)
Set
temp.
ON
+3
+2
+1
0
OFF
OPERATION
display
Compressor
Outdoor fan
(RY01)
Common relay
(RY02)
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
ON
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the
desired position.
And the louver position is stored in the microcomputer, the louvers will be set to the position automatically at the next operation.
(2) When the AUTO b utton is pushed, the louv er v er-
tically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY)
(1) Compressor, outdoor fan and operation display
are controlled as shown in Fig. 7-3-1.
Fig. 7-3-1
•The microprocessor turns the compressor on
and off at regular intervals (4 to 6 minutes on
and/or off). During the compressor off, the
indoor fan will operate in the super low position.
•The indoor fan will operate in the AUTO
position.
(2) The pattern of operation depending on the relation
between room temperature and set temperature
is shown below:
Room temp.
Set temp.+1
Set temp.
Compressor
Outdoor fan
ONONONON
OFFOFFOFF
– 13 –
Indoor fan
L.*S.L.S.L.L.L.S.L.L.
*
Super Low
Fig. 7-3-2
7-4. AUTO Operation
(MODE of the remote control : AUTO)
(1) One of the 2 modes, Cooling or Dry is selected
according to room temperature at which operation
is to start, as shown in Fig. 7-4-1. The Fan mode
will continue until room temperature reaches a
level at which another mode is selected.
7-4-1. T emporary Au to
When the TEMPORARY button is pushed, the set
temperature is fixed at 24°C and controlled in accordance with the chart shown in Fig. 7-4-1.
Cooling mode
+4
Cooling mode
+1
Dry mode
(Room temp. – Set temp.)
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
The Louver moved downward.
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
(The same dry operation as the room temperature control is set at set temp. –1˚C)
Fig. 7-4-1
– 14 –
7-5. ECONO. Mode
Compressor
Less than 5˚C continues
for 5 minutes
OFF
ON
Outdoor fan
7
Heat exchanger
temperature
5
(˚C)
When the ECONO. button is pushed, during COOL
and AUTO operation, the OPERATION display is
turned off and the ECONO. display is lit and the indoor
unit operates quietly and mildly with controlling airflow .
7-5-1. Cooling
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig.
7-5-1.
(2) Fan speed → LOW
(˚C)
Set temp.
is changed
+2
Set temp.
is changed
+1
7-6. Low-Temperature Limit Control
(Cooling Operation)
The microprocessor detects the indoor heat exchanger
temperature so as to prevent freezing up the indoor
heat exchanger.
Control is performed as shown in Fig. 7-6-1.
Fig. 7-6-1
Set temp.
ECONO. button
is pushed
Fig. 7-5-1
1H2HTIME0H
– 15 –
7-7. Auto Restart Function
This unit is equipped with an Automatic restarting
facility which allows the unit to restart and resume the
set operating conditions in the event of a power supply
shutdown without the use of the hand control.
The operation will resume without warning three
minutes after the power is restored.
The Auto Restart function is set not to work on
shipment from the factory, and so it is necessary to
set it to function as required.
• When the system is stand-by (not running)
7-7-1. How to Set the Auto Restart
To set the Auto Restart function, proceed as follows:
Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of
the indoor unit (please refer to section on PARTS
NAME). The power supply to the unit must be on the function will not be set if the power is off.
To enable the Auto Restart function, press the
TEMPORARY button contin uously f or three seconds.
The unit will acknowledge the setting and beep three
times. The system will now restart automatically.
The above A uto Restart settings can be carried out:
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
0
TEMPORARY
• When the system is operating
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
0
TEMPORARY
MOTION
Stand-by
↓
The system starts to operate.The green light will be lit.
↓about three seconds after
3S
The unit beeps three times.The orange light will be lit.
↓
The system is operating.The orange light is lighting.
If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
MOTION
OperatingThe green light is lit.
↓
The system stops to operate.The green light is turned off.
↓about three seconds after
3S
The unit beeps three times.
↓
The system stops.
If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the orange light is lit.
• The Auto Restart function will not accept an
instruction if timer operation with the remote control
is selected.
(Please refer to the section on setting the timer or
setting the louver.)
• During louver s wing (A UTO) operation, after restart
by the Auto Restart function the louver swing stops.
– 16 –
7-7-2. How to Cancel the Auto Restart
To cancel the Auto Restart function, proceed as
follows:
Repeat the setting procedure: the unit will
acknowledge the instruction and bleep three times.
• When the system is stand-by (not running)
The system will now be required to manually restart
with the remote control after the main supply is turned
off.
Cancellation is carried out:
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
0
TEMPORARY
• When the system is operating
OPERATION
Press the TEMPORARY button
continuously more than three
seconds.
0
TEMPORARY
MOTION
Stand-by
↓
The system starts to operate.The orange light will be lit.
↓about three seconds after
3S
The unit beeps three times.The green light will be lit.
↓
The system is operating.
If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
MOTION
OperatingThe orange light is lit.
↓
The system stops to operate.The orange light is turned off.
↓about three seconds after
3S
The unit beeps three times.
↓
The system stops.
If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is lighting.
7-7-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting of
Auto Restart operation, it is cancelled with power
failure. (The OPERATION lamp on the main unit
goes on and off to inform of power failure.) In that
case, try to reserve ON-TIMER operation once
again.
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation
is cancelled with power failure. (The OPERATION
lamp on the main unit goes on and off to inform of
power failure.) In that case, try to reserve OFFTIMER operation. When Auto Restart operation
is set, OFF-TIMER reservation is also cancelled
with power failure.
– 17 –
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.