11. HOW TO DIAGNOSE THE TROUBLE...................................................... 59
12. HOW TO REPLACE THE MAIN PARTS................................................... 79
13. EXPLODED VIEWS AND PARTS LIST ................................................... 89
7
– 1 –
FILE NO. SVM-07008
1. SAFETY PRECAUTIONS
For general public use
Power supply cord of outdoor unit shall be more than 1.5 mm2 (H07RN-F or 60245IEC66) polychloroprene
sheathed flexible cord.
• Read this “SAFETY PRECAUTIONS” carefully before servicing.
• The precautions described below include the important items regarding safety. Observe them without fail.
• After the servicing work, perform a trial operation to check for any problem.
• Turn off the main power supply switch (or breaker) before the unit maintenance.
CAUTION
New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT
DESTROY OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membrane, and oils because
the working pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. Accompanied with the
adoption of the new refrigerant, the refrigeration machine oil has also been changed. Therefore, during
installation work, be sure that water , dust, former refrigerant, or refrigeration machine oil does not enter into
the new type refrigerant R410A air conditioner circuit.
To prevent mixing of refrigerant or refrigerating machine oil, the sizes of connecting sections of charging
port on main unit and installation tools are different from those used for the conventional refrigerant units.
Accordingly, special tools are required for the new refrigerant (R410A) units. For connecting pipes, use new
and clean piping materials with high pressure fittings made for R410A only, so that water and/or dust does
not enter. Moreover, do not use the existing piping because there are some problems with pressure fittings
and possible impurities in existing piping.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAIN POWER SUPPLY
This appliance must be connected to the main power supply by a circuit breaker or a switch with a contact
separation of at least 3 mm.
DANGER
• ASK AN AUTHORIZED DEALER OR QUALIFIED INSTALLATION PROFESSIONAL TO INSTALL/MAINTAIN THE AIR CONDITIONER.
INAPPROPRIATE SERVICING MAY RESULT IN WATER LEAKAGE, ELECTRIC SHOCK OR FIRE.
• TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK. MAKE SURE
ALL POWER SWITCHES ARE OFF. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
DANGER: HIGH VOLTAGE
The high voltage circuit is incorporated.
Be careful to do the check service, as the electric shock may be caused in case of touching parts
on the P.C. board by hand.
• CORRECTLY CONNECT THE CONNECTING CABLE. IF THE CONNECTING CABLE IS INCORRECTLY CONNECTED, ELECTRIC PARTS MAY BE DAMAGED.
• CHECK THAT THE EARTH WIRE IS NOT BROKEN OR DISCONNECTED BEFORE SERVICE AND
INSTALLATION. FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
– 2 –
FILE NO. SVM-07008
• DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS. FAILURE
TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
• TO PREVENT THE INDOOR UNIT FROM OVERHEATING AND CAUSING A FIRE HAZARD, PLACE
THE UNIT WELL AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT
REGISTORS, FURNACE, STOVES, ETC.
• WHEN MOVING THE AIR-CONDITIONER FOR INSTALLATION IN ANOTHER PLACE, BE VER Y CAREFUL NOT TO ALLOW THE SPECIFIED REFRIGERANT (R410A) TO BECOME MIXED WITH ANY
OTHER GASEOUS BODY INTO THE REFRIGERATION CIRCUIT. IF AIR OR ANY OTHER GAS IS
MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CIRCUIT WILL
BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PERSONNEL INJURIES.
• IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE
WORK AND THE INSTALLATION WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE
REFRIGERANT GAS IS HEATED, SUCH AS BY FIRE, GENERATION OF POISONOUS GAS MAY
RESULT.
WARNING
• Never modify this unit by removing any of the safety guards or bypass any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit. Personal injury and property
damage can result if the unit falls.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas
may generate.
• The electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive circuit.
An insufficient circuit capacity or inappropriate installation may cause fire.
• When wiring, use the specified cab les and connect the terminals securely to prevent external
forces applied to the cable from affecting the terminals.
• Be sure to provide grounding.
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
CAUTION
• Exposure of unit to water or other moisture before installation may result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of the unit or where noise or discharged air might disturb neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
For Reference:
If a heating operation would be continuously perf ormed for a long time under the condition that the outdoor
temperature is 0°C or lower, drainage of defrosted water may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an antifreeze heater locally for a safe installation of the air conditioner.
For details, contact the dealer.
Net weight (kg) 8
Fan motor output(W)20
Air flow rate(Cooling / Heating)
Outdoor unitUnit modelRAS-10SAV-E, RAS-10SAV-A
Dimension Height (mm) 530
Width(mm)660
Depth(mm)240
Net weight (kg) 29
CompressorMotor output(W)750
TypeSingle rotary type with DC-inverter variabl e speed control
ModelDA89X1C-23FZ
Fan motor output(W)20
Air flow rate(Cooling / Heating)
PipingTypeFlare connection
connectionIndoor unitLiquid side(mm)
Gas side(mm)
Outdoor unitLiquid side(mm)
Gas side(mm)
Maximum length(m)10
Maximun charge-less length (m) 10
Maximum height difference (m) 8
Refrigerant Name of refrigerant R410A
Weight(kg)0.63
WiringPower supply3 Wires: Includes earth (Outdoor)
connectionInterconnection4 Wires: Includes earth
Usable temperature rangeIndoor(Cooling / Heating)
Outdoor(Cool ing / Heating)
Accessory Indoor unit Installation plate 1
Wireless remote controller1
batteries2
Remote controller holder 1
Super Oxi Deo filter1
Super Sterilizer filter1
M
ounting screw 6 (∅4 x 25L)
Pan head wood screw 2 (∅ 3.1 x 16L)
Plasma air puri fier-
Installation manual 1
Owner's manual1
Outdoor unitDrain nipple1
Water proof rubber cap-
* The specification may be subject to change without notice for purpose of improvement.
– 4 –
3
/ min)
(m
3
/ min)
(m
o
C)
(
o
C)
(
8.7/9.6
27/27
∅6.35
∅9.52
∅6.35
∅9.52
21 - 32/Up to 27
15 - 43/-10 - 24
2-2. Operation Characteristic Curve
<Cooling><Heating>
FILE NO. SVM-07008
6
5
4
3
Current (A)
2
Conditions
1
Indoor : DB 27
Outdoor : DB 35
Air Flow : High
Pip Length : 5m
Voltage : 230V
0
0 102030405060708090100110120
o
C/WB 19oC
o
C
6
5
4
3
Current (A)
2
1
0
0 102030405060708090100110120
Compressor Speed (rp s)
2-3. Capacity Variation Ratio According to Temperature
Conditions
Indoor : DB 20
Outdoor : DB 7
Air Flow : High
Pip Length : 5m
Voltage : 230V
Compressor Speed (rp s)
o
C
o
C/WB 6oC
<Cooling><Heating>
105
100
95
90
85
80
75
70
Cooling Capacity ratio (%)
65
60
55
Capacity ratio: 100%
2.5kW (RAS-10SKV-E)
2.5kW (RAS-10SKV-A)
Conditions
Indoor : DB 27
Indoor Air Flow : High
Pip Length : 5m
Voltage : 230V
o
C/WB 19oC
50
323334353637383940414243
Outside Temperature ( oC)
120
100
80
60
Heating Capacity ratio (%)
40
20
0
-10-50510
Conditions
Indoor : DB 20
Indoor Air Flow : High
Pip Length : 5m
Voltage : 230V
o
C
Outside Temperature ( ºC)
– 5 –
3. REFRIGERANT R410A
FILE NO. SVM-07008
This air conditioner adopts the new refrigerant HFC
(R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A
is 1.6 times higher than conventional refrigerant
(R22). The refrigerating oil is also changed in
accordance with change of refrigerant, so be careful
that water , dust, and existing refrigerant or refrigerating oil are not entered in the refrigerant cycle of the
air conditioner using the new refrigerant during
installation work or servicing time.
The next section describes the precautions for air
conditioner using the new refrigerant. Conforming to
contents of the next section together with the
general cautions included in this manual, perform
the correct and safe work.
3-1. Safety During Installation/Servicing
As R410A’s pressure is about 1.6 times higher than
that of R22, improper installation/servicing may
cause a serious trouble. By using tools and materials exclusive for R410A, it is necessary to carry out
installation/servicing safely while taking the following
precautions into consideration.
1. Never use refrigerant other than R410A in an air
conditioner which is designed to operate with
R410A.
If other refrigerant than R410A is mixed, pressure
in the refrigeration cycle becomes abnormally
high, and it may cause personal injury, etc. b y a
rupture.
2. Confirm the used refrigerant name, and use tools
and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the
visible place of the outdoor unit of the air conditioner using R410A as refrigerant. To prevent
mischarging, the diameter of the service port
differs from that of R22.
3. If a refrigeration gas leakage occurs during
installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire,
a poisonous gas may occur.
4. When installing or removing an air conditioner, do
not allow air or moisture to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so
that a rupture or personal injury may be caused.
5. After completion of installation work, check to
make sure that there is no refrigeration gas
leakage.
If the refrigerant gas leaks into the room, coming
into contact with fire in the fan-driven heater,
space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a
large volume of refrigerant is installed in a small
room, it is necessary to exercise care so that,
even when refrigerant leaks, its concentration
does not exceed the marginal le vel.
If the refrigerant gas leakage occurs and its
concentration exceeds the marginal le vel, an
oxygen starvation accident may result.
7. Be sure to carry out installation or removal
according to the installation manual.
Improper installation may cause refrigeration
trouble, water leakage , electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner
may be dangerous. If a breakdown occurs
please call a qualified air conditioner technician
or electrician.
Improper repair’s may result in water leakage,
electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes
and joints are mainly used. Copper pipes and joints
suitable for the refrigerant m ust be chosen and
installed. Furthermore, it is necessary to use clean
copper pipes and joints whose interior surfaces are
less affected by contaminants .
1. Copper Pipes
It is necessary to use seamless copper pipes
which are made of either copper or copper alloy
and it is desirable that the amount of residual oil
is less than 40 mg/10 m. Do not use copper
pipes having a collapsed, deformed or discolored
portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube
may become blocked with contaminants.
As an air conditioner using R410A incurs pressure higher than when using R22, it is necessary
to choose adequate materials.
Thicknesses of copper pipes used with R410A
are as shown in Table 3-2-1. Ne ver use copper
pipes thinner than 0.8 mm even when it is
available on the market.
– 6 –
Table 3-2-1 Thicknesses of annealed copper pipes
Thickness (mm)
FILE NO. SVM-07008
Nominal diameter
1/4
3/8
1/2
5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
R410AR22
0.800.80
0.800.80
0.800.80
1.001.00
2. Joints
For copper pipes, flare joints or socket joints are used. Prior to use, be sure to remove all contaminants.
a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter exceeds
20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose
diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4
3/8
1/2
5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not
enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used,
and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils
whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any
other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage ma y occur.
Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
– 7 –
d) Flare Processing
Make certain that a clamp bar and copper
pipe have been cleaned.
By means of the clamp bar, perform the flare
processing correctly.
Use either a flare tool for R410A or conventional flare tool.
Flare processing dimensions differ according
to the type of flare tool. When using a conventional flare tool, be sure to secure “dimen-
sion A” by using a gauge for size adjustment.
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
Outer
diameter
(mm)
Thickness
(mm)
Fig. 3-2-1 Flare pr ocessing dimensions
Flare tool for R410A
clutch type
FILE NO. SVM-07008
ØD
A
A (mm)
Conventional flare tool
Clutch type Wing nut type
1/4
3/8
1/2
5/8
Nominal
diameter
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
Table 3-2-4 Dimensions related to flare processing for R22
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
0.8
0.8
0.8
1.0
Thickness
(mm)
0.8
0.8
0.8
1.0
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
Flare tool for R22
clutch type
0 to 0.5
0 to 0.5
0 to 0.5
0 to 0.5
1.0 to 1.51.5 to 2.0
1.0 to 1.51.5 to 2.0
1.0 to 1.52.0 to 2.5
1.0 to 1.52.0 to 2.5
A (mm)
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.01.0 to 1.5
0.5 to 1.01.0 to 1.5
0.5 to 1.01.5 to 2.0
0.5 to 1.01.5 to 2.0
Nominal
diameter
1/4
3/8
1/2
5/8
Table 3-2-5 Flare and flare nut dimensions for R410A
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.19.26.513
13.213.59.720
16.616.012.923
19.719.016.025
– 8 –
Flare nut width
(mm)
17
22
26
29
Table 3-2-6 Flare and flare nut dimensions for R22
FILE NO. SVM-07008
Nominal
diameter
1/4
3/8
1/2
5/8
3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
45˚ to 46˚
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
BA
Dimension (mm)
ABCD
9.09.26.513
13.013.59.720
16.216.012.920
19.719.016.023
23.324.019.234
D
C
43˚ to 45˚
Flare nut width
(mm)
17
22
24
27
36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc.
b) Correctly align the processed flare surface with the union axis.
c) Tighten the flare with designated torque b y means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur.
When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by man ufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated by the manufacturer.
If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
Outer diameter
(mm)
Tightening torque
N•m (kgf•cm)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
1/4
3/8
1/2
5/8
6.35
9.52
12.70
15.88
14 to 18 (140 to 180)
33 to 42 (330 to 420)
50 to 62 (500 to 620)
63 to 77 (630 to 770)
– 9 –
16 (160), 18 (180)
42 (420)
55 (550)
65 (650)
FILE NO. SVM-07008
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed valve of the outdoor unit in the air-water heat pump using R410A is
changed to prev ent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing
dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are
lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge ,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used f or conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
air-water heat pump installation
No.
1
2
3
4
5
6
7
8
9
10
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
(Note 2) Charging cylinder for R410A is being currently developed.
Whether new equipment
can be used with
conventional refrigerant
¡
*(Note 1)
×
×
¡
¡
×
¡
×
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.
1. Vacuum pump
Use vacuum pump by attaching
vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench
(Opposite side 4mm)
11 . Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
– 10 –
FILE NO. SVM-07008
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the
following steps .
Recover the refrigerant, and check no refrigerant
remains in the equipment.
Connect the charge hose to packed valve service
port at the outdoor unit’s gas side.
Connect the charge hose to the vacuum pump
adapter.
Open fully both packed valves at liquid and gas
sides.
When the compound gauge’s pointer has indicated
–0.1 Mpa (–76 cmHg), place the handle Low in the
fully closed position, and turn off the vacuum pump’s
power switch.
Keep the status as it is for 1 to 2 minutes, and ensure
that the compound gauge’s pointer does not return.
Set the refrigerant cylinder to the electronic balance,
connect the connecting hose to the cylinder and the
connecting port of the electronic balance, and charge
liquid refrigerant.
Place the handle of the gauge manifold Low in the
fully opened position, and turn on the vacuum pump’s
power switch. Then, evacuating the refrigerant in the
cycle.
(For refrigerant charging, see the figure below.)
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode .
3. Do not carry out additional charging.
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high
pressure, and may cause a rupture or personal injury.
(Water heat
exchanger unit)
Opened
(Outdoor unit)
Refrigerant cylinder
(with siphon)
Check valve
Opened
Open/close
valve for charging
Electronic balance for refrigerant charging
Fig. 3-4-1 Configuration of refrigerant charging
Opened
Closed
Service port
– 11 –
FILE NO. SVM-07008
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the
cylinder upside down if cylinder is not equipped with siphon.
[ Cylinder with siphon ][ Cylinder without siphon ]
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Gauge manifold
OUTDOOR unit
cylinder
Refrigerant
Electronic
balance
R410A refrigerant is HFC mixed refrigerant.
Therefore, if it is charged with gas, the composition of the charged refrigerant changes and the
characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed
of silver and copper. It is used to join iron, copper
or copper alloy, and is relatively expensive though
it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used
to join copper or copper alloy.
Electronic
balance
Siphon
Fig. 3-4-2
1. Phosphor bronze brazing filler tends to react
with sulfur and produce a fragile compound
water solution, which may cause a gas
leakage. Therefore, use any other type of
brazing filler at a hot spring resort, etc., and
coat the surface with a paint.
2. When performing brazing again at time of
servicing, use the same type of brazing filler.
3-5-2. Flux
3. Low temperature brazing filler
Low temperature brazing filler is generally called
solder, and is an alloy of tin and lead. Since it is
weak in adhesive strength, do not use it for
refrigerant pipes.
1. Reason why flux is necessary
• By removing the oxide film and any foreign
matter on the metal surface, it assists the flow
of brazing filler .
• In the brazing process, it prevents the metal
surface from being oxidized.
• By reducing the brazing filler’s surface tension,
the brazing filler adheres better to the treated
metal.
– 12 –
FILE NO. SVM-07008
2. Characteristics required for flux
• Activated temperature of flux coincides with the
brazing temperature.
• Due to a wide effectiv e temper ature range, flux
is hard to carbonize.
• It is easy to remove slag after brazing.
• The corrosive action to the treated metal and
brazing filler is minimum.
• It excels in coating performance and is harmless to the human body.
As the flux works in a complicated manner as
described above, it is necessary to select an
adequate type of flux according to the type and
shape of treated metal, type of brazing filler and
brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric
acid.
It is effective in case where the brazing temperature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing
are this type.
It features an increased o xide film removing
capability due to the addition of compounds
such as potassium fluoride, potassium chloride
and sodium fluoride to the borax-boric acid
compound.
4. Piping materials for brazing and used
brazing filler/flux
3-5-3. Brazing
As brazing work requires sophisticated techniques,
experiences based upon a theoretical knowledge, it
must be performed by a person qualified.
In order to prev ent the oxide film from occurring in
the pipe interior during brazing, it is effective to
proceed with brazing while letting dry Nitrogen gas
(N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to
the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping material, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the
piping material and inserted copper pipe for
Nitrogen in order to prevent backflow of the
Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to
keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it
is lower than 0.05 m3/Hr or 0.02 MPa
(0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the
Nitrogen gas flowing until the pipe cools down
to a certain extent (temperature at which
pipes are touchable with hands).
7) Remove the flux completely after brazing.
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver
Silver
Used flux
Do not use
Paste flux
Vapor flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains
within the pipe, the lubricating oil deteriorates.
Therefore, use a flux which does not contain
chlorine.
3. When adding water to the flux, use w ater
which does not contain chlorine (e.g. distilled
water or ion-exchange water).
4. Remove the flux after brazing.
M
Flow meter
Stop valve
Nitrogen gas
cylinder
From Nitrogen cylinder
Pipe
Nitrogen
gas
Rubber plug
Fig. 3-5-1 Prevention of oxidation during brazing
– 13–
4-1. Indoor Unit
FILE NO. SVM-07008
4. CONSTRUCTION VIEWS
Front panel
60
8
Knock out system
Air inlet
250
50
55 60
105135
Air filter
740
Air outlet
500
Heat exchanger
60 55
Knock out system
50
195
58
52
8
Drain hose (0.5m)
45
250
Hanger
13590
235
215
Hanger
145
290
605
– 14 –
235
215
Hanger
Hanger
145
13590
Installation plate outline
Center line
Connecting pipe (0.37m)
6.35)(Flare
Connecting pipe (0.37m
(Flare 9.52)
For stud bold ( 6)
26
4016545
38
)
8~
10)For stud bold (
56
Wireless remote control
19
157
4-2. Outdoor Unit
FILE NO. SVM-07008
C
L
C
L
− 15 −
5-1. Indoor Unit
FILE NO. SVM-07008
5. WIRING DIAGRAM
– 16 –
FILE NO. SVM-07008
5-2. Outdoor Unit
– 17 –
FILE NO. SVM-07008
6. SPECIFICATION OF ELECTRICAL PARTS
6-1. Indoor Unit
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFS-220-20-4AR AC Motor with 145°C thermo fuse
2 Thermo. sensor (TA-sensor) 10 kΩ at 25°C
3 Micro power module (T101) µRM1260V
4 Microcontroller unit (IC81)
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) SS11V-R06270 27 m H, AC 0.6A
7 Diode (D01,D02,D03 and D04) S5688J
8 Capacitor (C03)
9 Fuse (F01) FJL250V3.15A 3.15A, 250 V
10 Regulator IC (IC12) S7805PIC 5VDC, 0.5A
11 Varistor (R21) TNR10V471K-T8 470V
12 Louver motor DC 12V
µPD780076GK-703-9ET-A
10 kΩ at 25°C
EKMH401VSN470MP20S 47µF, 400V
24BYJ48
– 18 –
FILE NO. SVM-07008
6-2. Outdoor Unit (RAS-10SAV-E, RAS-10SAV-A)
No.Parts nameModel nameRating
1 SC coil L01 GET-0451 0.6mH, 15A
(Noise filter) L03
3 Reactor CH-51-Z-T L=19mH, 10A
4 Outside fan motor
5
Fan control relay
Outside air temp.
6
sensor (TO sensor)
Heat exchanger temp.
7
sensor (TE sensor)
Dischenge temp.
8
sensor (TD sensor)
GET-0452
SWT-72
SKF-240-20B-1
G5NB-1ACoil DC12V Contact AC250V-1.5A
(Inverter attached) 10kΩ (25°C)
(Inverter attached) 10kΩ (25°C)
(Inverter attached) 62kΩ (20°C)
20W
2.0 mH, 10A
Primary side DC280V, Secondary2 DC-DC transformer
side 7.0 V x 1, 12 V x 1, 17V x 2
9
Terminal block (6P)
Fuse
10
11
Electrolytic capacitor LLQ2G501KHUBTF 500µF, DC 400 V x 3 pieces
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)
NOTE :
• The maximum pipe length of this air conditioner is 10 m. The addition charging of refrigevant is
unnecessary because this air condition is design with charge-less specitication.
– 20 –
7-2. Operation Data
<Cooling>
FILE NO. SVM-07008
TempeatureHeat exchanger
condition(°C)
IndoorOutdoorP (MPa)T1 (°C)T2 (°C)(rps)
27/19 35/- 10SKV-E
Model nameStandardIndoorOutdoorCompressor
RAS-pressurefan modefan moderevolution
10SKV-A
0.9 to 1.1 9 to 11 47 to 49 High High 54
pipe temp.
<Heating>
TempeatureHeat exchanger
condition(°C)pipe temp.
IndoorOutdoorP (MPa)T1 (°C)T2 (°C)(rps)
20/- 7/6 10SKV-E
Model nameStandardIndoorOutdoorCompressor
RAS-pressurefan modefan moderevolution
10SKV-A
2.4 to 2
.6 43 to 45 0 to 3 High High 68
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
– 21 –
8-1. Indoor Unit
Heat Exchanger Sensor
8. CONTROL BLOCK DIAGRAM
Indoor Unit Control Panel
M.C.U
Functions
• Louver Control
FILE NO. SVM-07008
Operation
Display
Temperature Sensor
Infrared Rays Signal Receiver
Initiallizing Circuit
Infrared
Rays
36.7KHz
Clock Frequency
Oscillator Circuit
Power Supply
Remote
Control
Noise Filter
From Outdoor Unit
Circuit
•
3-minute Delay at Restart for Compressor
•
Motor Revolution Control
•
Processing
(Temperature Processing)
•
Timer
•
Serial Signal Communication
Louver ON/OFF Signal
Louver Driver
Serial Signal Transmitter/Receiver
Serial Signal Communication
Timer
Display
Indoor
Fan Motor
Louver Motor
REMOTE CONTROL
Infrared Rays
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
One Touch
– 22 –
8-2. Outdoor Unit (Inverter Assembly)
For INDOOR UNIT
1
230V 50Hz
signal
Noise
filter
Input
current
sensor
Converter
(AC DC)
P.C.B (MCC 5009)
Over
current
sensor
Gate drive
circuit
Rotor position
detect circuit
Relay
Fan
motor
4way
Valve
Relay
High power factor
correction circuit
1. PWM synthesis function
2. Input current release control
3. IGBT over-current detect control
4. Outdoor fan control
5. High power factor correction control
6.Signal communication to indoor unit M. C. U
M. C. U
Inverter
(DC AC)
Compressor
MICRO-COMPUTER BLOCK DIAGRAM
FILE NO. SVM-07008
– 23 –
Discharge
temp. sensor
Outdoor air
temp. sensor
temp. sensor
Heat Exchanger
9. OPERATION DESCRIPTION
FILE NO. SVM-07008
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air
conditioner, which uses AC motor both the indoor
fan motor and the outdoor fan motor. And the capacityproportional control compressor which can change the
motor speed in the range from 22 to 83 rps is
mounted. The AC motor drive circuit is mounted to the
indoor unit. The compressor and the inverter is mounted
to the outdoor unit.
The entire air conditioner is mainly controlled by the
indoor unit controller.
The indoor unit controller drives the indoor fan motor
based upon command sent from the remote controller,
and transfers the operation command to the outdoor
unit controller.
The outdoor unit controller receives operation command from the indoor unit side, and controls the
outdoor fan motor. Besides detecting revolution position
of the compressor motor, the outdoor unit controller
controls speed of the compressor motor by controlling
output voltage of the inverter and switching timing of
the supply power (current transfer timing) so that motors
drive according to the operation command.
And then, the outdoor unit controller transfers reversely
the operating status information of the outdoor unit to
control the indoor unit controller.
As the compressor adopts four-pole brushless
DC motor , the frequency of the supply power
from in verter to compressor is two-times cycles
of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation
commands from the remote controller and assumes
the following functions.
•Judgment of suction air temperature of the indoor
heat exchanger by using the indoor temp. sensor.
(TA sensor)
•Judgment of the indoor heat exchanger tempera-
ture by using heat exchanger sensor (TC sensor)
(Prevent-freezing control, etc.)
• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial
signal) to the outdoor unit
•Reception of information of operation status
(Serial signal including outside temp. data) to the
outdoor unit and judgment/display of error
2. Role of outdoor unit controller
Receiving the operation command signal (Serial
signal) from the indoor unit controller, the outdoor
unit performs its role.
• Compressor operation control
• 4-way valve control
Operations followed to judgment
of serial signal from indoor side
•Detection of inverter input current and current
release operation
•Over-current detection and prevention operation
to IGBT module (Compressor stop function)
•Compressor and outdoor fan stop function when
serial signal is off (when the serial signal does not
reach the board assembly of outdoor control by
trouble of the signal system)
•Transferring of operation information (Serial
signal) from outdoor unit controller to indoor unit
controller
•Detection of outdoor temperature and operation
revolution control
•Defrost control in heating operation (Temp.
measurement by outdoor heat exchanger and
control for 4-way valve and outdoor fan)
3. Contents of operation command signal
(Serial signal) from indoor unit controller to
outdoor unit controller
The following three types of signals are sent from
the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined
by indoor temperature and set temperature
(Correction along with variation of room temperature and correction of indoor heat exchanger
temperature are added.)
• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger temperature), the outdoor unit controller monitors the
input current to the inverter, and performs the
followed operation within the range that current
does not exceed the allowable value.
4. Contents of operation command signal
(Serial signal) from outdoor unit controller
to indoor unit controller
The following signals are sent from the outdoor unit
controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation
For transferring of these signals, the indoor unit
controller monitors the contents of signals, and
judges existence of trouble occurrence.
Contents of judgment are described below.
•Whether distinction of the current operation
status meets to the operation command signal
•Whether protective circuit operates
When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
9-3. Auto Restart Function ................................................................................................41
9-3-1. How to Set the A uto Restart Function .............................. ........................................ 41
9-3-2. How to Cancel the Au to Restar t Function ................................................................ 42
9-3-3. Power Failure During Timer Operation ................................................................... 43
9-4. Remote Controller and Its Fuctions .................................................................... 44
9-4-1. Parts Name of Remote Contr oller ............................................................................. 44
9-4-2. Operation of remote control ...................................................................................... 44
9-4-3. Name and Functions of Indications on Remote Contr oller ....................................... 45
– 25−
9-2. Operation Description
FILE NO. SVM-07008
Item
1. Basic
operation
Operation flow and applicable data, etc.
1. Operation control
Receiving the user’s operation condition setup, the operation statuses of indoor/outdoor units are
controlled.
1) The operation conditions are selected by the remote controller as shown in the below.
2) A signal is sent by ON button of the remote controller.
3) The signal is received by a sensor of the indoor unit and processed by the indoor controllers as
shown in the below.
4) The indoor controller controls the indoor fan motor and louver motor.
5) The indoor controller sends the operation command to the outdoor controller, and sends/receives
the control status with a serial signal.
6) The outdoor controller controls the operation as shown in the left, and also controls the compressor, outdoor fan motor and 4-way valve.
Selection of
operation conditions
ON/OFF
Remote controller
Control contents of remote controller
• ON/OFF (Air conditioner)
• Operation select (COOL/HEAT/AUTO/DRY)
• Temperature setup
• Air direction
• Swing
• Air volume select (AUTO/LOW/LOW+/MED/MED+/HIGH)
• ECO
• ON timer setup
• OFF timer setup
• Hi POWER
• COMFORT SLEEP
• QUIET
• PRESET
• ONE-TOUCH
Description
Signal receiving
Indoor unit control
Operation command
Serial signal send/receive
Serial signal send/receive
Outdoor unit control
Indoor unit
Indoor unit control
• Command signal generating function of
indoor unit operation
• Calculation function (temperature calculation)
• Activation compensation function of indoor fan
• Cold draft preventive function
• Timer function
• Indoor heat exchanger release control
Outdoor unit
Outdoor unit control
• Frequency control of inverter output
• Waveform composite function
• Calculation function
(Temperature calculation)
• AD conversion function
• Quick heating function
• Delay function of compressor reactivation
• Current release function
• GTr over-current preventive function
• Defrost operation function
• Indoor fan motor
• Louver motor
~
Inverter
• Compressor
• Outdoor fan motor
• 4-way valve
– 26 –
FILE NO. SVM-07008
Ite m
1. Basic
operation
Operation flow and applicable data, etc.
2. Cooling/Heating operation
The operations are performed in the following parts by controls according to cooling/heating conditions.
1) Receiving the operation ON signal of the remote controller, the cooling or heating operation signal
starts being transferred form the indoor controller to the outdoor unit.
2) At the indoor unit side, the indoor fan is operated according to the contents of “2. Indoor fanmotor control” and the louver according to the contents of “9. Louver control”, respectively.
3) The outdoor unit controls the outdoor fan motor, compressor and 4-way valve according to the
operation signal sent from the indoor unit.
Operation ON
Indoor unit control
Sending of operation command signal
Outdoor unit control
Setup of remote controller
Indoor fan motor control / Louver control / Operation Hz
Control (Requierment)
Compressor revolution control / Outdoor fan motor control /
Operation Hz control (Include limit control)
4-way valve control In cooling operation:
In heating operation:
[ ]
Description
OFF
ON
3. AUTO operation
Selection of operation mode
As shown in the following figure, the operation starts by
selecting automatically the status of room temperature
(Ta) when starting AUTO operation.
*1. When reselecting the operation mode, the fan
speed is controlled by the previous operation mode.
Ta
Cooling operation
Ts + 1
Monitoring (Fan)
Ts – 1
Heating operation
4. DRY operation
DRY operation is performed according to the difference
between room temperature and the setup temperature as
shown below.
In DRY operation, fan speed is controlled in order to
prevent lower ing of the room temperature and to avoid air
flow from blowing directly to persons.
[˚C]
Ta
L– (W5)
1) Detects the room temperature (Ta) when
the operation started.
2) Selects an operation mode from Ta in
the left figure.
3) Fan operation continues until an
operation mode is selected.
4) When AUTO operation has started
within 2 hours after heating operation
stopped and if the room temperature is
20°C or more, the fan operation is
performed with ”Super Ultra LOW” mode
for 3 minutes.
Then, select an operation mode.
5) If the status of compressor-OFF
continues for 15 minutes the room
temperature after selecting an operation
mode (COOL/HEAT), reselect an
operation mode.
1) Detects the room temperature (Ta) when
the DRY operation started.
2) Starts operation under conditions in the
left figure according to the temperature
difference between the room temperature and the setup temperature (Tsc).
Setup temperature (Tsc)
= Set temperature on remote controller
(Ts) + (0.0 to 1.0)
3) When the room temperature is lower
1°C or less than the setup temperature,
turn off the compressor.
+
+
Tsc
1.0
0.5
(W5+W3) / 2
SUL (W3)
Fan speed
− 27 −
(
)
FILE NO. SVM-07008
Item
2. Indoor fan
motor control
COOL ON
Fan speed setup
AUTO
Ta
[˚C]
+2.5
a
+2.0
b
+1.5
c
+1.0
Operation flow and applicable data, etc.
<In cooling operation>
(This operation controls the fan speed at indoor unit side.)
The indoor fan (cross flow fan) is operated by the phase-
control induction motor. The fan rotates in 5 stages in
MANUAL mode, and in 5 stages in AUTO mode, respectively. (Table 1)
MANUAL
(Fig. 1)
Indication
L
L+
M
M+
H
Fan speed
W6
(L + M) / 2
W9
(M + H) / 2
WC
(Fig. 2)
Air volume AUTO
M+(WB)
*3
*4
*5
*3 : Fan speed = (M + –L) x 3/4 + L
*4 : Fan speed = (M + –L) x 2/4 + L
*5 : Fan speed = (M + –L) x 1/4 + L
Description
* Symbols
UH: Ultra High
H: High
M+: Medium+
M: Medium
L+: Low+
L: Low
L-: Low–
UL: Ultra Low
SUL: Super Ultra Low
* The fan speed broadly varies due
to position of the louver, etc.
The described value indicates one
under condition of inclining
downward blowing.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is
performed with the constant
speed shown in Fig. 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 2 and Table 1
according to the setup temperature, room temperature, and heat
exchanger temperature.
1) When setting the fan speed to L,
L+, M, M+ or H on the remote
controller, the operation is performed with the constant speed
shown in Fig. 3 and Table 1.
2) When setting the fan speed to
AUTO on the remote controller,
revolution of the fan motor is
controlled to the fan speed level
shown in Fig. 5 according to the set
temperature and room temperature.
3) Min air flow rate is controlled by
temperature of the indoor heat
exchanger (Tc) as shown in Fig. 4.
4) Cold draft prevention, the fan
speed is controlled by temperature
of the indoor heat exchanger (Tc)
as shown in Fig. 6.
5) In order to prevent cold draft when
compressor stop during heating
operation. Then louver will move to
upper position and fan speed will
reduce or off.
*Fan speed=
TC
Fan spee
AUT
L+ (W9)
*1
*2
*3
M+ (WD)
H (WE
Basic fan contr
A
TS
–0.
d
–1.0
e
–1.5
f
–2.0
g
–2.5
–5.0
(Fig. 4)
*1: Fan speed = (M + -L+) x 1 4 + L+
*2: Fan speed = (M + -L+) x 2 4 + L+
*3: Fan speed = (M + -L+) x 3 4 + L+
(Calculated with linear approximation from M+ and L+)
(Fig. 5)
No limi
W8) + W
Cold draft preventive control
T
4646
454533
333321
323220
*A+4*A+4*A+4
*A-4*A-4*A-4
* No limitation while fan speed MANUAL mode is in stabilit
* A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
34
Fan speed MAN
Fan speed AUTO in stabilit
Fan speed AUTO in startin
H (WE
Line-approximate
H and S
SUL (W2
L with Tc
Stop
AL in startin
(Fig. 6)
[In starting and in stability]
FAN AUTO
F AN Man ual
In starting
• Until 12 minutes passed after operation start
• When 12 to 25 minutes passed after operationstart and room temp. is 3°C or lo w er than set temp.
• Room temp. < Set temp. –4°C
• When 12 to 25 minutes passed after operation startand room temp. is higher than (set temp. –3°C)
• When 25 minutes or more passed after operation start
• Room temp. ≥ Set temp. –3.5°C
In stability
– 29 –
e
FILE NO. SVM-07008
Item
3. Capacity
control
Remote controllerIndoor unit
Operation flow and applicable data, etc.
The cooling or heating capacity depending on the load is
adjusted.
According to difference between the setup value of temperature and the room temperature, the capacity is adjusted by
the compressor revolution.
Set temp. (Ts)
Ts –Ta
Correction of Hz signal
Detection of electromotive force
of compressor motor winding
Detection of motor speed and rotor position
Correction value of Hz signal ≤ Operating Hz
Inverter output change
Commutation timing change
Room temp. (Ta)
Description
1) The difference between set
temperature on remote controller
(Ts) and room temperature (Ta)
is calculated.
2) According to the temperature
difference, the correction value of
Hz signal which determines the
compressor speed is set up.
3) The rotating position and speed
of the motor are detected by the
electromotive force occurred on
the motor winding with operation
of the compressor.
4) According to the difference
resulted from comparison of the
correction value of Hz signal with
the present operation Hz, the
inverter output and the commutation timing are varied.
5) Change the compressor motor
speed by outputting power to the
compressor.
* The contents of control
operation are same in cooling
operation and heating
operation
Change of compressor speed
4. Current release
control
This function prevents troubles on the electronic parts of the
compressor driving inverter.
This function also controls drive circuit of the compressor
speed so that electric power of the compressor drive circuit
does not exceed the specified value.
1) The input current of the outdoor
unit is detected in the inverter
section of the outdoor unit.
2) According to the detected
outdoor temperature, the
specified value of the current is
selected.
3) Whether the current value
exceeds the specified value or
not is judged.
4) If the current value exceeds the
specified value, this function
reduces the compressor speed
and controls speed up to the
closest one commanded from the
indoor unit within the range
which does not exceed the
specified value.
10.80A
– 30 –
FILE NO. SVM-07008
Item
5. Release protective
control by temperature of indoor heat
exchanger
7˚C
6˚C
5˚C
Indoor heat exchanger temperature
Operation flow and applicable data, etc.
<In cooling/dry operation>
(Prevent-freezing control for indoor heat exchanger)
In cooling/dry operation, the sensor of indoor heat
exchanger detects evaporation temperature and
controls the compressor speed so that temperature of
the heat exchanger does not exceed the specified
value.
Usual cooling capacity control
R
When the value is
in Q zone, the
Q
compressor speed
is kept.
P
Reduction of compressor speed
Description
1) When temperature of the indoor
heat exchanger drops below 5°C,
the compressor speed is
reduced. (P zone)
2) When temperature of the indoor
heat exchanger rises in the
range from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
3) When temperature of the indoor
heat exchanger rises to 7°C or
higher, the capacity control
operation returns to the usual
control in cooling operation.
(R zone)
55˚C
52˚C
48˚C
Indoor heat exchanger temperature
<In heating operation>
(Prevent-overpressure control for refrigerating cycle)
In heating operation, the sensor of indoor heat ex-
changer detects condensation temperature and controls
the compressor speed so that temperature of the heat
exchanger does not exceed the specified value.
Reduction of compressor speed
P
When the value is
Q
in Q zone, the
compressor speed
is kept.
R
Usual heating capacity control
1) When temperature of the indoor
heat exchanger rises in the
range from 50°C to 55°C, the
compressor speed is kept.
(Q zone)
When temperature of the indoor
heat exchanger drops in the
range from 46°C to under 55°C,
the compressor speed is kept.
(Q zone)
2) When temperature of the indoor
heat exchanger rises to 55°C or
higher, the compressor speed is
reduced. (P zone)
3) When temperature of the indoor
heat exchanger does not rise to
50°C, or when it drops below to
46°C, the capacity control
operation returns to the usual
control in heating operation.
(R zone)
– 31 –
FILE NO. SVM-07008
Item
6. Defrost control
(Only in heating
operation)
Start of heating operation
0’10’ 15’27’40”34’
–5˚C
–7˚C
–20˚C
Outdoor heat exchanger temperature
A zone
B zone
C zone
Operation flow and applicable data, etc.
(This function removes frost adhered to the outdoor
heat exchanger.)
The temperature sensor of the outdoor heat exchanger (Te sensor) judges the frosting status of the
outdoor heat exchanger and the defrost operation is
performed with 4-way valve reverse defrost system.
Operation time
(Minute)
C zone
A zone
B zone
*
* The minimum value of Te sensor 10 to 15 minutes
after start of operation is stored in memory as Te0.
Table 1
When T e0 - TE ≥ 2.5 continued for 2 minutes in A zone,
defrost operation starts.
When the operation continued for 2 minutes in B zone,
defrost operation starts.
When T e0 - TE ≥ 3 continued for 2 minutes in C zone,
defrost operation starts.
Description
The necessity of defrost operation is
detected by the outdoor heat exchanger
temperature. The conditions to detect the
necessity of defrost operation differ in A,
B, or C zone each. (Table 1)
<Defrost operation>
• Defrost operation in A to C zones
1) Stop operation of the compressor for
20 seconds.
2) Invert (OFF) 4-way valve 10 seconds
after stop of the compressor.
3) The outdoor fan stops at the same time
when the compressor stops.
4) When temperature of the indoor heat
exchanger becomes 38°C or lower,
stop the indoor fan.
<Finish of defrost operation>
• Returning conditions from defrost
operation to heating operation
1) Temperature of outdoor heat exchanger
rises to +8°C or higher.
2) T emperature of outdoor heat exchanger
is kept at +5°C or higher for 80 seconds.
3) Defrost operation continues for
15 minutes.
<Returning from defrost operation>
1) Stop operation of the compressor for
approx. 50 seconds.
2) Invert (ON) 4-way valve approx. 40
seconds after stop of the compressor.
3) The outdoor fan starts rotating at the
same time when the compressor starts.
– 32 –
FILE NO. SVM-07008
Item
7. Louver control
1) Louver
position
Operation flow and applicable data, etc.
This function controls the air direction of the indoor unit.
• The position is automatically controlled according to the operation
mode (COOL/HEAT).
• The set louver position is stored in memory by the microcomputer,
and the louver returns to the stored position when the next operation
is performed. (Cooling/Heating memory position)
The angle of the louver is indicated as the louver closes fully is 0°.
• Swing operation is performed in width 35° with the stop position as
the center.
• If the stop position exceeds either upper or lower limit position,
swing operation is performed in width 35° from the limit which the
stop position exceeded.
* 12 (DRY max - COOL min) /6 x 5 + COOL min
* 11 (DRY max - COOL min) /6 x 4 + COOL min
* 10 (DRY max - COOL min) /6 x 3 + COOL min
* 9 (DRY max - COOL min) /6 x 2 + COOL min
* 8 (DRY max - COOL min) /6 x 1 + COOL min
Hz 10SKVR-E, 10SKV-A
Cool min
Dry max
<Heating operation>
30 minutes
A
B
C
22
32
→ Time Compressor
A
B
C
speed
0Hz
A zone
aHz
B zone
a to cHz
C zone
cHz
<Heating operation>
1) Setting the compressor speed to
Max. aHz, the temperature zone
in which the operation can be
performed with Max. cHz is
gradually widened after 30
minutes passed when starting
ECO operation.
2) The indoor fan speed is depend
on presetting and can change
every speed after setting ECO
operation.
Hz
10SKV-E
10SKV-A
a 22
c 52
– 34 –
FILE NO. SVM-07008
Item
9. Temporary
operation
Operation flow and applicable data, etc.
Pressing [RESET] button starts the temporary operation of [AUTO] operation. When keeping [RESET]
button pressed for 10 seconds or more, the temporary
[COOL] operation is performed.
1) When pressing [RESET] button, the
temporary [AUTO] operation starts.
2) When keeping [RESET] button pressed
for 3 seconds or more, Pi, Pi, Pi sound is
heard and [AUTO RESTART] control is
changed.
Filter lamp ON
NO
Did you press [RESET] button
for 3 seconds or more?
YES
Did you press [RESET] button
for 10 seconds or more?
NO
Switch to [AUTO RESTART] control.
YES
NO
YES
Press RESET button.
Temporary [AUTO] operation
Temporary [COOL] Operation
3) When keeping [RESET] button pressed
for 10 seconds or more, “Pi” sound is
heard and the temporary [COOL]
operation starts.
4) If the filter lamp goes on, press [RESET]
button to go off the filter lamp, and then
press [RESET] button again.
5) To stop the temporar y operation, press
the button again.
10. Discharge temperature control 1. Purpose
Td value
117°C
112°C
108°C
105°C
98°C
Control operation
Judges as an error and stops the compressor.
Reduce the compressor speed.
Reduce slowly compressor speed.
Keeps the compressor speed.
If the operation is performed with lower speed than one
commanded by the serial signal, speed is slowly raised
up to the commanded speed.
Operates with speed commanded by the serial signal.
This function detects error on the
refrigerating cycle or error on the compressor, and performs protective control.
2. Operation
• Control of the compressor speed
The speed control is performed as
described in the left table based upon
the discharge temperature.
Description
– 35 –
FILE NO. SVM-07008
Item
Operation flow and applicable data, etc.
11. Self-Cleaning
function
Unit now performing cooling or dry operation
Press “STOP” button
Only timer indicator lights, and Self Cleaning operation starts
Time set now elapses
Operation stops
Description
1. Purpose
The Self-Cleaning operation is to minimize the
growth of mold, bacteria etc. by running
the fan and drying so as to keep the
inside of the air conditioner clean.
Self-Cleaning operation
When the cooling or dry operation shuts
down, the unit automatically starts the Self-Cleaning operation which is then performed
for the specified period based on duration
of the operation which was performed
prior to the shutdown, after which the
Self-Cleaning operation stops.
(The Self-Cleaning operation is not
performed after a heating operation.)
2. Operation
1) When the stop signal from the remote
controller or timer-off function is received,
only the timer indicator light.
2) The period of the Self-Cleaning operation
is determined by the duration of the
operation performed prior to the
reception of the stop code.
3) After the Self-Cleaning operation has
been performed for the specified period,
the unit stops operating.
• During Self-Cleaning operations: The louver opens
slightly. The indoor fan operates continuously at
a speed of 500 rpm.
Self-Cleaning operation times
Self-Cleaning operation time
No Self-Cleaning operation
performed (0 minutes)
30 mins.
Cooling: Auto (cooling) Dry
Heating: Auto (heating)
Auto (fan only)
Shutdown
Operation time
Up to 10 minutes
10 minutes
or longer
No Self-Cleaning operation performed
• To stop an ongoing Self-Cleaning operation at any time
Press the start/stop button on the remote controller twice during the Self-Cleaning
operation. (After pressing the button for the first time, press it for the
second time without delay (within 10 minutes).)
– 36 –
FILE NO. SVM-07008
Item
11. Self-Cleaning
• Self-Cleaning diagram
Operation flow and applicable data, etc.
Description
function
Operation displayONOFFOFF
FCU fan
FCU louver OPEN OPEN (12.7º)CLOSE
Timer display
Compressor
CDU fanON or OFF
12. Self-Cleaning
function release
rpm is depend on presetting. (500RPM)
depend on presetting of timer function.depend on presetting of timer function.
depend on presetting per room temperature.
depend on presetting per room temperature.
Cool mode or dry mode
operation more than 10 mins.
How to cencel Self-Cleaning function
To cancel the Self-Cleaning function, proceed as
ON ON
ON or OFF
ON or OFF
Turn off by remote controller or
timer-off function.
ON
OFFOFF
OFFOFF
Self-Cleaning mode
operate 30 mins.
Automatically turn-off.
ON or OFF
follows:
OFF
Operation time
• Press [RESET] button one time or use remote
control to turn on air conditioner. Display will show
in green color.
• Hold down the [RESET] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [RESET] is pressed but keep holding it
continue. The will beep 3 times in the first
3 seconds but it is not related to Self-Cleaning
function)
• After holding about 20 seconds, the air conditioner
will beep 5 times without any blinking of display.
• The Self-Cleaning Operation had been cancelled.
Remark
Presetting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 9-3-1
How to set Self-Cleaning function
To set the Self-Cleaning function, proceed as follows.
• Press [RESET] button one time or use remote
control to turn on air conditioner. Display will show
in green color.
• Hold down the [RESET] button for more than
20 seconds. (The air conditioner will stop suddenly
when the [RESET] is pressed but keep holding it
continue. Then will beep 3 times is the first 3
seconds but it is not related to Self-Cleaning
function)
• After holding about 20 seconds, the air conditioner
will beep 5 times and OPERATION display blinks
5 times.
• The Self-Cleaning function had been set.
Remark
Presetting of Self-Cleaning function above, AUTORESTART function had been cancelled. To set
AUTO-RESTART again, please follow item 9-3-1
RESET button
− 38 −
FILE NO. SVM-07008
Item
13. Romote-A or B
selection
Operation flow and applicable data, etc.
Setting the remote controller
To separate using of remote control for each indoor
unit in case of 2 air conditioner are installed nearly.
Remote Control B Setup.
1) Press RESET button on the indoor unit to turn
the air conditioner ON.
2) Point the remote control at the indoor unit.
3) Push and hold CHK • button on the Remote
Control by thetip of the pencil. "00" will be shown
shown on the display.
4) Press MODE • during pushing CHK • . "B" will
show on the display and "00" will disappear and
the air conditioner will turn OFF. The Remote
Control B is memorized.
Note : 1. Repeat above step to reset Remote Control
to be A.
2. Remote Control A has mot "A" display.
3. Default setting of Remote Control from
factory is A.
Description
1. Purpose
This operation is to operate only one
indoor unit using one remote controller.
2. Description
When operating one indoor unit in a
situation where two indoor units have
been installed in the same room or
nearby rooms, this operation prevents the
remote controller signal from being
received simultaneously by both units,
thus preventing both units from operating.
3. Operation
The indoor unit on which the remote
controller selection has been set to B
receives the signal of the remote controller also set to B.
(At the factory the remote controller
selection is set to A on all the indoor
units. There is no A setting display.)
− 38 −
FILE NO. SVM-07008
Item
14. QUIET mode
Operation flow and applicable data, etc.
When the [QUIET] button is pressed, the fan of the
indoor unit will be restricted the revolving speed at
speed L
−
until the [QUIET] button is pressed once
again (cancel Quiet mode).
15. COMFORT
SLEEP mode
Cooling mode
• The preset temperature will increase as
show on ECO operation (Item No. 9)
• Press the [COMFORT SLEEP] button to
choose the operating hours. Repeat
pressing to select the hours.
(1hr, 3hr, 5hr or 9hr)
• If the [COMFORT SLEEP] button is pressedagain means cancel comfort sleep mode.
Heating mode
• The preset temperature will drop down as
show on ECO operation (Item No. 9)
• Press the [COMFORT SLEEP] button to
choose the operating hours. Repeat
pressing to setect thehours.
(1hr, 3hr, 5hr or 9 hr)
• If the [COMFORT SLEEP] button is pressedagain means cancel comfort sleep mode.
Description
Quiet mode is the system which, control the
revolving speed of indoor fan to work
constantly at lower than speed L. In addition,
noise level of indoor unit is less than usual.
Remarks :
1. Quiet mode is unable to work in dry mode.
2. Quiet mode is appropriate to work with less
cooling load and less heating load condition.
Because of the fan speed L- may cause not
enough the cooling capacity or heating
capacity.
The principles of comfort sleep mode are:
• Quietness for more comfortable. When
room temperature reach setting temperature
• Save energy by changing room temperature
automatically.
• The air condition can shut down by itself
automatically.
Remarks:
1.
Comfort sleep mode will not operate in dry
mode and fan only mode.
16. One-Touch
Comfort
One touch comfort is the fully automated operation
that is set according to the preferable condition in
a region.
Fan
Operation
AUTO
0 1225
AUTO/L L
*
Time after operation
starts (min)
*AUTO/L: Fan operates depends on the setting
temperature and room temperature.
During the One Touch Comfort mode if the indoor
unit receives any signal with other operation mode,
the unit will cancel the comfort mode and operates
according to the signal received.
Operation condition for model to Europe
market
When an indoor unit receives "One Touch
Comfort Signal" from the remote controller,
the indoor unit operates as following.
1) Air conditioner starts to operation when
the signal is received, even if the air
conditioner was OFF.
2) Operation mode is set according to room
temperature, the same as AUTO mode.
) Target temperature is 24ºC.
3
4) Louver position is set as stored position
of the operating mode.
5) Fan is controlled as followings.
− 39 −
FILE NO. SVM-07008
Item
17. Hi-POWER
Mode
Operation flow and applicable data, etc.
([Hi-POWER] button on the remote controller
is pressed)
When [Hi-POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi-
POWER mark is indicated on the display of the remote
controller and the unit operates as follows.
1. Automatic operation
• The indoor unit operates in according to the
current operation.
2. Cooling operation
• The preset temperature drops 1ºC
(The value of the preset temperature on the
remote controller does not change.)
The indoor unit's fan speed level increase 1 tap
3. Heating operation
• The preset temperature increases 2ºC
(The value of the preset temperature on the
remote controller does not change.)
The indoor unit's fan speed level increase 1 tap
4. The Hi-POWER mode can not be set in Dry
operation
Description
− 40 −
.
FILE NO. SVM-07008
9-3. Auto Restart Function
This indoor unit is equipped with an automatic restarting function which allows the unit to restart operating with
the set operating conditions in the ev ent of a power supply being accidentally shut down.
The operation will resume without warning three minutes after power is restored.
This function is not set to work when shipped from the factory. Therefore it is necessary to set it to work.
9-3-1. How to Set the Auto Restart Function
To set the auto restart function, proceed as follows:
The power supply to the unit must be on ; the function will not set if the power is off.
Press the [RESET] button located in the center of the front panel continuously f or three seconds.
The unit receives the signal and beeps three times.
The unit then restarts operating automatically in the event of power supply being accidentally shut down.
• When the unit is standby (Not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
RESET button
• When the unit is in operation
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.The green indicator is on.
↓After approx. three seconds,
The unit beeps three timesThe green indicator flashes
and continues to operate.for 5 seconds.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
Motions
The unit is in operation.The green indicator is on.
↓
The unit stops operating.The green indicator is turned off.
↓After approx. three seconds,
The unit beeps three times.The green indicator flashes
for 5 seconds.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET button
• While the filter check indicator is on, the RESET button has the function of filter reset betton.
– 41 –
FILE NO. SVM-07008
9-3-2. How to Cancel the Auto Restart Function
To cancel auto restart function, proceed as follows :
Repeat the setting procedure : the unit receives the signal and beeps three times.
The unit will be required to be turned on with the remote controller after the main power supply is turned off.
• When the system is on stand-by (not operating)
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
RESET button
• When the system is operating
Operation
Press [RESET] button for more than
three seconds. (Less than 10 seconds)
Motions
The unit is on standby.
↓
The unit starts to operate.The green indicator is on.
↓After approx. three seconds,
The unit beeps three times and continues to operate.
If the unit is not required to operate at this time, press [RESET]
button once more or use the remote controller to turn it off.
Motions
The unit is in operation.The green indicator is on.
↓
The unit stops operating.The green indicator is turned off.
↓After approx. three seconds,
The unit beeps three times.
If the unit is required to operate at this time, press [RESET] button
once more or use the remote controller to turn it on.
RESET button
9-3-3. Power Failure During Timer Operation
When the unit is turned off because of power failure
during timer operation, the timer operation is cancelled. In that case, set the timer operation again.
NOTE :
The Everyday Timer is reset while a command signal
can be received from the remote controller even if it
stopped due to a power failure .
– 42 –
9-4. Remote control
9-4-1. Remote control and its functions
11
1
Infrared signal emitter
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON)
Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Setup button (SET)
11
12
20
Clear button (CLR)
13
Memory and Preset button (PRESET)
14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
20
Clock Reset button (CLOCK)
21
Check button (CHK)
FILE NO. SVM-07008
9-4-2. Operation of remote control
1. ONE-TOUCH
Press the "ONE-TOUCH" button for fully automated operation that is customised to the typical consumer
preferences in your region of the world. The coutomised settings control temperature air flow strength, air flow
direction and other settings to provide you alternate contact with "ONE-TOUCH" OF THE BUTTON. If you
prefer other settings you can select from the many other operation functions of your Toshiba unit
Press ONE-TOUCH : Start the operaton.
2. AUTOMATIC OPERATION
To automatically select cooling, heating, or fan only operation.
1. Press MODE : Select A.
2. Press MODE : Select A.
3. COOLING / HEATING / FAN ONLY OPERATION
To automatically select cooling, heating, or fan only operation.
1. Press MODE : Select Cool , Heat , or Fan only .
2. Press MODE : Set the desired temperature.
Cooling: Min. 17°C, Heating : Max, 30°C, Fan Only: No temperature indication
3. Press FAN : Select AUTO, LOW , LOW+ , MED , MED+ , or
HIGH .
− 43 −
4. DRY OPERATION (COOLING ONLY)
For dehumidification, a moderate cooling performance is controlled automatically.
1. Press MODE : Select Dry .
2. Press MODE : Set the desired temperature.
5. Hi-POWER OPERATION
To automatically control room temperature and airflow for faster cooling or heating
operation (except in DRY and FAN ONLY mode)
Press HI-POWER : Start and stop the operation.
6. ECO OPERATION
To automatically control room to save energy (except in DRY and FAN ONLY mode)
Press ECO : Start and stop the operation.
Note: Cooling operation; the set temperature will increase automatically 1 degree/
hour for 2 hours (maximum 2 degrees increase). For heating operation the
set temperature will decrease.
7. TEMPORARY OPERATION
In case of the misplaced or discharged remote control
FILE NO. SVM-07008
• Pressing the RESET button, the unit can start or stop
without using the remote control.
• Operation mode is set on AUTOMATIC
operation, preset temperature is 24°C
and fan operation is automatic speed.
8. TIMER OPERATION
Setting the ON TimerSetting the OFF Timer
1
Press ON : Set the desired ON timer.
Press
2
3
3
Press
SET
: Set the timer.Press
CLR
: Cancel the timer.Press
Press
OFF
: Set the desired OFF timer.
SET
: Set the timer.
CLR
Everyday timer allows the user to set both the ON & OFF timers and will be activated on a daily basis.
Setting Everyday Timer
1
Press
2
Press
ON
: Set the ON timer.
OFF
: Set the OFF timer.
3
Press
Press
4
mark flashing.
SET
.
SET
button during the ( or )
• During the every day timer is activation, both arrows are indicated.
( or )
Note:
• Keep the remote control in accessible transmission to the indoor unit;
otherwise, the time lag of up to 15 minutes will occur.
• The setting will be saved for the next same operation.
– 44 –
9. PRESET OPERATION
Set your preferred operation for future use. The setting will be memorized by the
unit for future operation (except air flow direction).
1. Select your preferred operation.
2. Press and hold PRESET for 3 seconds to memorize the setting. The mark
displays.
3. Press PRESET : Operate the preset operation.
10. AUTO RESTART OPERATION
To automatically restart the conditioner after the power failure (Power of the unit
must be on.)
Setting
1. Press and hold the RESET button on the indoor unit for 3 seconds to set the
operation. (3 beep sound and OPERATION lamp blink 5 time/sec for 5 secpmds)
• Do not operate ON timer and OFF timer.
2. Press and hold the RESET button on the indoor unit for 3 seconds to cancel the
operation. (3 beep sound but OPERATION lamp does not blink)
11. QUIET OPERATION
To operate at super low fan speed for quiet operation (except in DRY mode)
FILE NO. SVM-07008
P
Press QUIET : Start and stop the operation.
Note: Under certain conditions, QUIET operation may not provide adequate
cooling or heating due to low sound features.
12. COMFORT SLEEP OPERATION
To save energy while sleeping, automatically control air flow and automatically turn OFF.
Press COMFORT SLEEP : Select 1, 3, 5 or 9 hrs for OFF timer operation.
Note: The cooling operation, the set temperature will increase automatically
1 degree/hour for 2 hours (maximum 2 degrees increase). For heating operation,
the set temperature will decrease.
13. SLEEP TIMER OPERATION
To start the sleep timer (OFF timer) operation
Press SLEEP : Select 1, 3, 5 or 9 hrs for OFF timer operation.
− 45 −
FILE NO. SVM-07008
9-4-3. Name and Functions of Indications on Remote Controller
[Display]
All indications, except for the clock time indicator, are displayed by pressing the button.
1. Transmission mark
This transmission mark
remote controller transmits signals to the indoor
unit.
2. Mode indicator
Indicates the current operation mode.
(AUTO : Automatic control, A : Auto changeover
control,
3. Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed.
AUTO or five fan speed levels
(
LOW , LOW+ , MED , MED+ ,
HIGH ) can be shown.
Indicates AUTO when the operating mode is
either AUTO or
: Cool, : Dry, : Heat)
: Dry.
indicates when the
9
12
1
2
13
10
5. TIMER and clock time indicator
The time setting for timer operation or the clock
time is indicated.
The current time is always indicated except
during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is
pressed during operation.
The
button for more than 3 seconds while the mark is
flashing.
Press another button to turn off the mark.
8. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is
set, “B” appears in the remote controller display .
(When the remote controller setting is “A”, there is
no indication at this position.)
10. Comfort sleep
Indicates when comfort sleep is activaled.
Press comfort sleep bu
mark is shown when holding down the
tton to selectter
11
11. Quiet
Indicates when quiet is activated.
Press quiet button to start and press it again to stop
operation.
12. One-Touch
Indicates when one touch comfort is activated.
Press one-touch button to start the operation.
13. Swing
Indicates when louver is swing.
Press swing button to start the swing operation
and press it again to stop the swing operation.
8
6
3
7
4
5
– 46 –
10. INSTALLATION PROCEDURE
10-1-1. Installation Diagram of Indoor and Outdoor Units
FILE NO. SVM-07008
3 Batteries
(
A
t
t
a
c
h
t
o
5 Super Oxi
Deo filter
170 m
m or m
A
t
h
e
f
r
o
n
t
p
a
n
e
6 Super Sterilizer
filter
8 Pan head
wood screw
Hook
ore
Hook
65 mm or more
1 Installation plate
170
mm or more
Wal l
Insert the cushion between
the indoor unit and wall, and
tilt the indoor unit for better
operation.
For the rear left and left piping
ir
f
ilt
e
r
Do not allow the drain hose to
get slack.
Shield pipe
l.)
Cut the piping
hole sloped
slightly .
Make sure to run the drain
hose sloped downward.
4 Remote control holder
The auxiliary piping can be
connected to the left, rear left,
rear right, right, bottom right
or bottom left.
2 Wireless remote
1
0
0
mm o
r
mor
e
m
0
0
4
Before installing the wireless remote controller
• Loading Batteries
1. Remove the battery cover.
2. Insert 2 new batteries (AAA type)
following the (+) and (
-
) positions.
Vinyl tape
Apply after carrying
out a draina g e test.
r more
o
mm
5
4
600 mm or more
Extension drain hose
e
r
o
m
r
o
m
A
C
L
(Not available, provided
by installer)
6
0
0
m
m
o
Saddle
r
m
o
re
3 Batteries
Right
Rear right
Bottom
right
Rear
left
Left
Bottom left
Insulate the refrigerant pipes
separately with insulation, not
together.
6 mm thic k heat resisting
pol yeth ylene f oam
2 Wireless remote controller
− 47 −
10-1-2. Optional installation parts
FILE NO. SVM-07008
Part
Code
Parts name
Refrigerant piping
Liquid side : ∅6.35 mm
A
Gas side : 9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
Putty, PVC tapes
C
∅
<Fixing bolt arrangement of outdoor unit>
500 mm
Air inlet
97 mm
53 mm
280 mm
Air outlet
Drain outlet
Q'ty
One
each
1
One
each
Fig. 9-1-2
•
Secure the outdoor unit with the fixing bolts and nuts if the unit is likely to be exposed to a strong wind.
•
Use 8 mm or 10 mm anchor bolts and nuts.
If it is necessary to drain the defrost water, attach drain nipple 9 to the bottom plate of the outdoor
∅
•
∅
outdoor unit before installing it.
– 48−
10-1-3. Accessory and installation parts
Part
No.
Part name (Q’ty)
Part
No.
Part name (Q’ty)
Part
No.
FILE NO. SVM-07008
Part name (Q’ty)
1
Installation plate x 1
2
Wireless remote control x 1
3
Battery x 2
Others
Name
Owner’s manual
Installation manual
4
Remote control holder x 1
5
Super Oxi Deo filter x 1
6
Super Sterilizer filter x 1
7
Mounting screw ∅4 x 25 s x 6
8
Flat head wood screw
∅3.1 x 16 s x 2
9
Drain nipple* x 1
The part marked with asterisk (*) is packaged with the
outdoor unit.
– 49 –
FILE NO. SVM-07008
10-1-4. Installation/Servicing Tools
<Changes in the product and components>
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged
accidentally, the service port diameter of the outdoor unit control valve (3 way valve) has been changed.
(1/2 UNF 20 threads per inch)
• In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and
size of opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)
New tools for R410A
New tools for R410A
Gauge manifold
Charge hose
Electronic balance
for refrigerant charging
Torque wrench
(nominal diam. 1/2, 5/8)
Flare tool
(clutch type)
Gauge for projection
adjustment
V acuum pump adapter
Applicable to R22 modelChanges
As pressure is high, it is impossible to measure by
means of conventional gauge. In order to prevent any
other refrigerant from being charged, each port
diameter has been changed.
In order to increase pressure resisting strength, hose
materials and port size have been changed (to 1/2
UNF 20 threads per inch).
When purchasing a charge hose, be sure to confirm
the port size.
As pressure is hight and gasification speed is fast, it
is difficult to read the indicated value by means of
charging cylinder, as air bubbles occur.
The size of opposite sides of flare nuts have been
increased. Incidentally, a common wrench is used for
nominal diameters 1/4 and 3/8.
By increasing the clamp bar’s receiving hole, strength
of spring in the tool has been improved.
—
Used when flare is made by using conventional flare
tool.
Connected to conventional vacuum pump. It is
necessary to use an adapter to prevent vacuum
pump oil from flowing back to the charge hose.
The charge hose connecting part has two ports-one
for conventional refrigerant (7/16 UNF 20 threads per
inch) and one for R410A. If the vacuum pump oil
(mineral) mixes with R410A a sludge may occur and
damage the equipment.
Gas leakage detector
• Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in
the U. S’s ARI specified rose color (ARI color code: PMS 507).
• Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch
corresponding to the charge hose’s port size.
Exclusive for HFC refrigerant.
– 50 –
FILE NO. SVM-07008-1
10-2. Indoor Unit
10-2-1. Installation place
• A place which provides the spaces around the
indoor unit as shown in the above diagram.
• A place where there is no obstacle near the air inlet
and outlet.
• A place that allows easy installation of the piping to
the outdoor unit.
• A place which allows the front panel to be opened.
• The indoor unit shall be installed as top of the
indoor unit comes to at least 2 m height.
Also it must be avoided to put anything on the top of
the indoor unit.
CAUTION
• Direct sunlight to the indoor unit’s wireless
receiver should be avoided.
• The microprocessor in the indoor unit should not
be too close to RF noise sources.
(For details, see the owner’s manual.)
<Remote controller>
• A place where there are no obstacles such as a
curtain that may block the signal from the indoor
unit.
• Do not install the remote control in a place exposed
to direct sunlight or close to a heating source, such
as a stove.
• Keep the remote control at least 1 m apart from the
nearest TV set or stereo equipment. (This is
necessary to prevent image disturbances or noise
interference.)
• The location of the remote control should be
determined as shown below.
Remote
control
(Top view)
Indoor unit
Reception
range
45°
5
4
°
Remote
control
Indoor unit
(Side view)
°
75
Reception
range
10-2-2. Cutting a hole and mounting installation
plate
<Cutting a hole>
When installing the refrigerant pipes from the rear.
90 mm
66 mm
Pipe hole
42 mm
65 mm
Fig. 10-2-2
1. After determining the pipe hole position on the
mounting plate (A), drill the pipe hole (∅65 mm) at
a slight downward slant to the outdoor side.
NOTE:
• When drilling a wall that contains a metal lath, wire
lath or metal plate, be sure to use a pipe hole brim
ring sold separately.
<Mounting the installation plate>
Anchor bolt holes
62
82.5
1
Installation
plate
170
85
Pipe hole
Indoor unit
Hook
Hook
Thread
Weight
Hook
Pipe hole
7 Mounting screw
Fig. 10-2-3
2 m or more from floor
Fig. 10-2-1
– 51 –
FILE NO. SVM-07008
<When the installation plate is directly mounted on
the wall>
1. Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook up
the indoor unit.
2. To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
illustrated in the above figure.
3. Install the installation plate horizontally in the wall.
CAUTION
When installing the installation plate with a
mounting screw , do not use the anchor bolt hole.
Otherwise the unit may fall down and result in
personal injury and property damage.
Installation plate
<Keep horizontal direction>
Anchor
bolt
Projection
15 mm or less
10-2-3. Electrical work
1. The supply voltage must be the same as the rated
voltage of the air conditioner.
2. Prepare the power source for exclusive use with the
air conditioner.
CAUTION
• This appliance can be connected to the mains in
either of the following two ways.
(1) Connection to fixed wiring:
A switch or circuit breaker which disconnects
all poles and has a contact separation of at
least 3 mm must be incorporate in the fixed
wiring. An approved circuit breaker or
switches must used.
(2) Connection with power supply plug:
Attach power supply plug with power cord
and plug it into wall outlet. An approved
power supply cord and plug must be used.
NOTE
• Ensure all wiring is used within its electrical rating.
Fig. 10-2-4
5 mm dia. hole
77
7 Mounting
77
screw
ss
∅4 x 25
s
ss
Clip anchor
(local parts)
Fig. 10-2-5
CAUTION
Failure to firmly install the unit may result in
personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type
walls, make 5 mm dia. holes in the wall.
• Insert clip anchors for appropriate mounting screws
7.
NOTE:
• Secure four corners and lower parts of the
installation plate with 4 to 6 mounting screws to
install it.
Model
Power source 50Hz, 220
Maximum
running current
Plug socket &
fuse rating
Power cord1 mm2or more
10 Class
-
240 V Single phase
7.5A
16A
– 52 –
FILE NO. SVM-07008
10-2-4. Wiring connection
<How to connect the connecting cable>
Wiring of the connecting cable can be carried out
without removing of the front panel.
1. Remove the air inlet grille.
Open the air inlet grille upward and pull it toward
you.
2. Remove the terminal cover and cord clamp.
3. Insert the connecting cable (according to the local
cords) into the pipe hole on the wall.
4. Take out the connecting cable through the cable
slot on the rear panel so that it protrudes about
15 cm from the front.
5. Insert the connecting cable fully into the terminal
block and secure it tightly with screws.
6. Tightening torque : 1.2 N·m (0.12 kgf·m)
7. Secure the connecting cable with the cord clamp.
8. Fix the terminal cover, rear plate bushing and air
inlet grille on the indoor unit.
CAUTION
• Be sure to refer to the wiring system diagram
labeled inside the front panel.
• Check local electrical cords and also any specific
wiring instructions or limitations.
Terminal cover
Screw
Cord clamp
1
2
3
Terminal block
1
2
3
Earth line
10-2-5. Piping and drain hose installation
<Piping and Drain Hose Forming>
*Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
Rear right
Rear left
Bottom left
Left
Bottom right
Right
Die-cutting
Front panel slit
Changing
drain hose
Piping preparation
Fig. 10-2-8
1. Die-cutting Front panel slit
Cut out the slit on the left or right side of the front panel
for the left or right connection and the slit on the
bottom left or right side of the front panel for the
bottom left or right connection with a pair of nippers.
2. Changing drain hose
For left connection, bottom-leftward connection and
rear-leftward connection’s piping, it is necessary to
change the drain hose and drain cap.
<How to remove the Drains Cap>
Clip drain cap by needle-nose pliers, and pull out.
Screw
Screw
Connecting cable
about 15 cm
Stripping length of the connecting cable
Connecting cable
110 mm
10 mm
10 mm
50 mm
Earth line
<How to install the Drain Hose>
Firmly insert drain hose connecting part until hitting on
a heat insulator.
NOTE :
• Use stranded wire only.
• Wire type : H07RN-F or more
<How to install the air inlet grille on the indoor unit>
• When attaching the air inlet grille, the contrary of the removed
.
operation is performed.
– 53 –
Fig. 10-2-9
Heat insulator
Drain hose
Fig. 10-2-10
FILE NO. SVM-07008
<How to fix the Drains Cap>
1) Insert hexagonal wrench (∅4 mm) in a center head.
∅4 mm
Fig. 10-2-11
2) Firmly insert drains cap.
No gap
Do not apply lubricating oil
(refrigerant machine oil) when
inserting the drain cap. Application
causes deterioration and drain
Insert a hexagon
wrench (∅4 mm)
leakage of the plug.
Fig. 10-2-12
CAUTION
Firmly insert the drain hose and drain cap;
otherwise, water may leak.
<In case of right or left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm
above the wall surface. If the connecting pipe is laid
exceeding 43 mm above the wall surface, the indoor
unit may unstably be set on the wall. When bending the
connecting pipe, make sure to use a spring bender so
as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm
(∅6.35) 40 mm (∅9.52).
To connect the pipe after installation of the unit (figure)
(To the forefront of flare)
270 mm
170 mm
R 30 mm or less (∅6.35) R 40 mm or less (∅9.52)
(Use polisin (polyethylene core) or the like for
43 mm
bending pipe.)
0
8
Gas side
Liquid side
Outward form of indoor unit
Use the handle of screwdriver, etc.
10-2-15
Fig.
NOTE:
If the pipe is bent incorrectly, the indoor unit may
unstably be set on the wall.
After passing the connecting pipe through the pipe
hole, connect the connecting pipe to the auxiliary pipes
and wrap the facing tape around them.
Slit
Fig. 10-2-13
<In case of bottom right or bottom left piping>
• After scribing slits of the front panel with a knife or a
making-off pin, cut them with a pair of nippers or an
equivalent tool.
Slit
Fig. 10-2-14
– 54 –
CAUTION
• Bind the auxiliary pipes (two) and connecting
cable with facing tape tightly. In case of leftward
piping and rear-leftward piping, bind the auxiliary
pipes (two) only with facing tape.
Indoor unit
Auxiliary pipes
Installation plate
10-2-16
Fig.
• Carefully arrange pipes so that any pipe does not
stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and
connecting pipes to each other and cut off the
insulating tape wound on the connecting pipe to
avoid double-taping at the joint, moreover, seal
the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make
sure to insulate both the connecting pipes. (Use
polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush it.
Connecting cable
FILE NO. SVM-07008
10-3. Outdoor Unit
10-3-1. Installation place
• A place which provides the spaces around the
outdoor unit as shown in the left diagram.
• A place which can bear the weight of the outdoor
unit and does not allow an increase in noise level
and vibration.
• A place where the operation noise and discharged
air do not disturb users neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an
elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up
15 m.
• An allowable height level is up to 10 m.
• A place where the drain water does not raise any
problem.
CAUTION
1. Install the outdoor unit without anything blocking
the air discharging.
2. When the outdoor unit is installed in a place
exposed always exposed to strong wind like a
coast or on a high storey of a building, secure
the normal fan operation using a duct or a wind
shield.
3. In particularly windy areas, install the unit such
as to avoid admission of wind.
4. Installation in the following places may result in
trouble.
Do not install the unit in such places.
• A place full of machine oil.
• A saline-place such as the coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely
to be generated as from audio equipment,
welders, and medical equipment.
10-3-2. Refrigerant piping connection
<Flaring>
1. Cut the pipe with a pipe cutter.
90°
Obliquity
Roughness
Fig. 10-3-2
2. Insert a flare nut into the pipe, and flare the pipe.
Projection margin in flaring : A (Unit : mm)
A
Die
Pipe
Fig. 10-3-3
Rigid (Clutch type)
Outer dia. R410A Conventional
of copper pipe tool used tool used
6.350 to 0.51.0 to 1.5
9.52 0 to 0.5 1.0 to 1.5
ial (wing nut type)
Imper
Outer dia.
of copper pipe
R410A
6.351.5 to 2.0
9.521.5 to 2.0
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
Warp
Strong
wind
Fig. 10-3-1
– 55 –
Flare nutHalf union
Externally
threaded side
Use a wrench to secure.
Use a torque wrench to tighten.
Internally
threaded side
Fig. 10-3-4
CAUTION
•
Do not apply excess torque.
•
Otherwise, the nut may crack depending on the
conditions.
FILE NO. SVM-07008-1
(Unit : Nám)
Outer dia.
of copper pipe
Tightening torque
∅6.35 mm16 to 18 (1.6 to 1.8 kgf·m)
∅
9.52 mm30 to 42 (3.0 to 4.2 kgf·m)
Tightening torque of flare pipe connections
The operating pressure of R410A is higher than that of
R22. (Approx. 1.6 times).
It is therefore necessary to firmly tighten the flare pipe
connecting sections (which connect the indoor and
outdoor units) up to the specified tightening torque.
Incorrect connections may cause not only a gas
leakage, but also damage to the refrigerant cycle.
Flare at
indoor unit side
Flare at
outdoor unit side
Fig. 10-3-5
<Shaping pipes>
1. How to shape the pipes
Shape the pipes along the incused line on the
outdoor unit.
2. How to fit position of the pipes
Put the edges of the pipes to the place with a
distance of 85 mm from the incused line.
m
m
5
8
Incused line
10-3-3. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit. For details, see the
manual of the vacuum pump.
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops. (If oil inside of the vacuum pump
enters into the air conditioner, which use R410A,
refrigeration cycle trouble may result.)
1. Connect the charge hose from the manifold valve to
the service port of the gas side packed valve.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the
piping length is 20 meters. (15 minutes for
20 meters) (assuming a pump capacity of 27 liters
per minute. Then confirm that the compound
pressure gauge reading is − 101 kPa (76 cmHg).
5. Close the low pressure side valve handle of gauge
manifold.
6. Open fully the valve stem of the packed valves
(both side of Gas and Liquid).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
Compound pressure gauge
–101 kPa (76 cmHg)
Handle Lo
Charge hose (For R410A only)
Connecting pipe
Pressure gauge
Manifold valve
Handle Hi (Keep full closed)
Charge hose (For R410A only)
Vacuum pump adapter for
counter-flow prevention
(For R410A only)
Fig. 10-3-6
Vacuum
pump
Packed valve at gas side
Service port (Valve core (Setting pin))
Packed valve at liquid side
Fig.10-3-7
CAUTION
• KEEP IMPORTANT 4 POINTS FOR PIPING
WORK
(1) Take away dust and moisture (Inside of the
connecting pipes.)
(2) Tight connection (between pipes and unit)
(3) Evacuate the air in the connecting pipes using
VACUUM PUMP.
(4) Check gas leak (connected points)
– 56 –
FILE NO. SVM-07008
<Packed valve handling precautions>
Open the valve stem all the way out; but do not try
to open it beyond the stopper.
Securely tighten the valve stem cap with torque in
the following table:
Gas side30 to 42 N·m
(∅9.52 mm)(3.0 to 4.2 kgf·m)
Liquid side16 to 18 N·m
(∅6.35 mm)(1.6 to 1.8 kgf·m)
Service port
9 to 10 N·m
(0.9 to 1.0 kgf·m)
Hexagonal wrench
is required.
4 mm
Fig. 10-3-8
10-3-4. Wiring connection
1. Remove the valve cover from the outdoor unit.
2. Connect the connecting cable to the terminal as
identified with their respective matched numbers on
the terminal block of indoor and outdoor unit.
3. When connecting the connecting cable to the
outdoor unit terminal, make a loop as shown in the
installation diagram of indoor and outdoor unit, to
prevent water coming in the outdoor unit.
4. Insulate the unused cords (conductors) from any
water coming in the outdoor unit. Proceed them so
that they do not touch any electrical or metal parts.
<Stripping length of connection cable>
Terminal block
Power cord
Connecting cable
3
2
1
10
10
4540
Connecting cable
6050
Earth line
L
10
Power cord
N
10
Earth line
Fig. 10-3-8
Model
RAS-10SKV
Power source 50 Hz, 220 - 240 V Single phase
Maximum
running current
Installation fuse
rating
Power cord
H07RN-F or 245 IEC66 (1.5 mm
or more)
8A
25A
CAUTION
• Wrong wiring connection may cause some
electrical parts burn out.
• Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).
• Every wire must be connected firmly.
• This installation fuse (25A
be used for the power supply line of this air
conditioner.
If incorrect or incomplete wiring is carried out, it
will cause an ignition or smoke.
Prepare the power supply for exclusive use with
the air conditioner.
This product can be connected to the mains.
Connection to fixed wiring: A switch which
disconnects all poles and has a contact
separation of at least 3 mm must be incorporated
in the fixed wiring.
) must
2
NOTE: Connecting cable
• Wire type: More than H07RN-F or 245 IEC66
(1.0 mm2 or more)
– 57 –
FILE NO. SVM-07008
10-3-5. Gas leak test
Check places for
indoor unit (Flare
nut connection)
Valve cover
Electric parts
cover
Check places
for outdoor unit
Fig. 10-3-10
• Check the flare nut connections for the gas leak
with a gas leak detector or soap water.
10-3-6. Indoor unit fixing
10-3-7. Test operation
To switch the TEST RUN (COOL) mode, press
RESET button for 10 sec.
(The beeper will make a short beep.)
Fig. 10-3-13
-3-8. Auto restart setting
10
This product is designed so that, after a power failure,
it can restart automatically in the same operating mode
as before the power failure.
1. Pass the pipe through the hole in the wall, and hook
the indoor unit on the installation plate at the upper
hooks.
2. Swing the indoor unit to right and left to confirm that
it is firmly hooked up on the installation plate.
3. While pressing the indoor unit onto the wall, hook it
at the lower part on the installation plate. Pull the
indoor unit toward you to confirm that it is firmly
hooked up on the installation plate.
1
2
Hook
Hook here
1 Installation
plate
Press
(unhook)
Fig.10-3-11
• For detaching the indoor unit from the installation
plate, pull the indoor unit toward you while pushing
its bottom up at the specified parts.
Information
The product was shipped with Auto Restart function
in the off position. Turn it on as required.
<How to set the auto restart>
• Press and hold the RESET button for about
3 seconds. After 3 seconds, the electronic beeper
makes three short beeps to tell you the Auto
Restart has been selected.
• To cancel the Auto Restart, follow the steps
described in the section Auto Restart Function of
the Owner’s Manual.
PushPush
Fig. 10-3-12
– 58 –
11. HOW TO DIAGNOSE THE TROUBLE
FILE NO. SVM-07008
The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose troubles
according to the diagnosis procedure as described
below. (Refer to the check points in servicing written
on the wiring diagrams attached to the indoor/outdoor
units.)
Table 11-1
No. Troubleshooting Procedure
1 First Confirmation
2 Primary Judgment
3 Judgment by Flashing LED
of Indoor Unit
4 Self-Diagnosis by Remote Control
5 Judgment of Trouble by
Every Symptom
6 How to Check Simply the Main Parts
Discharging position
(Discharging period
10 seconds or more)
NOTE:
A large-capacity electrolytic capacitor is used in the
outdoor unit control (inverter). Therefore, if the power
supply is turned off, charge (charging voltage DC280V)
remains and discharging takes a lot of time. After
turning off the power source, if touching the charging
section before discharging, an electrical shock may be
caused. Discharge the electrolytic capacitor completely
by using soldering iron, etc.
<Discharging method>
(1) Remove the inverter cover (plating) by opening four
mounting claws.
(2) As shown below, connect the discharge resistance
(approx. 100Ω40W) or plug of the soldering iron to
voltage between + – terminals of the C14
(“CAUTION HIGH VOLTAGE 380 V” is indicated.)
electrolytic capacitor (760µF/400 V) on P.C. board,
and then perform discharging.
Plug of
soldering
iron
Inverter cover
P . C. boar d
(Soldered surface)
10-1. First Confirmation
10-1-1. Confirmation of power supply
Confirm that the power breaker operates (ON)
normally.
Fig. 11-1
10-1-2. Confirmation of power voltage
Confirm that power voltage is AC 220-240 V ± 10%. If
power voltage is not in this range, the unit may not
operate normally.
– 59 –
FILE NO. SVM-07008
11-1-3. Operation which is not a trouble (Program operation)
For controlling the air conditioner, the program operations are built in the microcomputer as described in the
following table. If a claim is made for running operation, check whether or not it meets to the contents in the
following table. When it does, we inform you that it is not trouble of equipment, but it is indispensable for controlling and maintaining of air conditioner.
Table 11-1-1
No.Operation of air conditionerDescription
1When power breaker is turned “ON”,
the operation lamp (Green) of the
indoor unit flashes.
The OPERATION lamp of the indoor unit flashes when power source
is turned on. If [ ] button is operated once, flashing stops.
(Flashes also in power failure)
2Compressor may not operate even if
the room temperature is within range of
compressor-ON.
3In Dry and ECO. mode, FAN (air flow)
display does not change even though
FAN (air flow select) button is operated.
4Increasing of compressor motor speed
stops approx. 30 seconds after
operation started, and then compressor
motor speed increases again approx.
30 seconds after.
5The set value of the remote control
should be below the room temperature.
6In AUTO mode, the operation mode is
changed.
7In HEAT mode, the compressor motor
speed does not increase up to the
maximum speed or decreases before
the temperature arrives at the set
temperature.
11-2. Primary Judgment
The compressor does not operate while compressor restart delay
timer (3-minutes timer) operates. The same phenomenon is found
after power source has been turned on because 3-minutes timer
operates.
The air flow indication is fixed to [AUTO].
For smooth operation of the compressor, the compressor motor speed
is restricted to Max. 41 rps for 2 minutes, and Max.91 rps for 2 minutes
to 3 minutes, respectively after the operation has started.
If the set value is above the room temperature, Cooling operation is
not performed. And check whether battery of the remote control is
consumed or not.
After selecting Cool or Heat mode, select an operation mode again if
the compressor keeps stop status for 15 minutes.
The compressor motor speed may decrease by high-temp. release
control (Release protective operation by temp.-up of the indoor heat
exchanger) or current release control.
To diagnose the troubles, use the following methods.
(1) Judgment by flashing LED of indoor unit
(2) Self-diagnosis by service check remote control
(3) Judgment of trouble by every symptom
Firstly, use the method (1) for diagnosis. Then, use the method (2) and (3) to diagnose the details of troubles.
– 60 –
FILE NO. SVM-07008
11-3. Judgment by Flashing LED of Indoor Unit
While the indoor unit monitors the operation status of the air conditioner, if the protective circuit operates, the
contents of self-diagnosis are displayed with block on the indoor unit indication section.
(1) The contents of items B and C and a part of item E are displayed when air conditioner operates.
(2) When item B and C, and item B and a part of item E occur concurrently, priority is given to the block of item B.
(3) The check codes can be confirmed on the remote control for servicing.
– 61 –
FILE NO. SVM-07008-1
11-4. Self-Diagnosis by Remote Controller (Check Code)
1. If the lamps are indicated as shown B to E in Table 11-3-1, execute the self-diagnosis b y the remote controller.
2. When the remote controller is set to the service mode, the indoor controller diagnoses the operation condition and indicates the information of the self-diagnosis on the display of the remote controller with the check
codes. If a fault is detected, all lamps on the indoor unit will flash at 5Hz and it will beep for 10 seconds
(Beep, Beep, Beep ... ). The timer lamp usually flashes (5Hz) during self-diagnosis.
11-4-1. How to Use Remote Controller in Service Mode
1
Press [CHECK] button with a tip of pencil to set the
remote controller to the service mode.
•“” is indicated on the display of the remote
controller.
PR E S E T
ON E- TOU CH
QU IE T
S WIN G
TI ME R
SL E E P
C HK
TOSHIBA
FA N
TE MP
TEMP
MOD E
C OMF OR T
PU R E
FI X Hi -PO WE R E C O
ON
FI LT E R
S LE E P
OF F
C LO CK
2
Press [ON ] or [OFF ] button
If there is no fault with a code, the indoor unit will beep
once (Beep) and the display of the remote controller will
change as follows :
• • •
• The TIMER indicator of the indoor unit flashes continuously.
(5 times per 1 sec.)
• Check the unit with all 52 check codes ( to )
as shown in Table-11-4-1.
• Press [ON ] or [OFF ] button to change the check
code backward.
CL R
SE T
If there is a fault, the indoor unit will beep for 10
seconds (Beep, Beep, Beep...).
Note the check code on the display of the remote
controller.
• 2-digits alphanumeric will be indicated on the display.
• All indicators on the indoor unit will flash.
(5 times per 1 sec.)
Alphanumeric characters are
used for the check codes.
is 5. is 6.
is A. is B.
is C. is D.
Press [START/STOP] button to release the service mode.
3
• The display of the remote controller returns to as it
was before service mode was engaged.
Time shortening method.
4
1. Press SET button while pushing CHECK button.
2. Press [START/STOP] button.
Fig. 11-4-1
– 62 –
FILE NO. SVM-07008
11-4-2. Caution at servicing
(1) After servicing, push the [ ] button to return to the normal mode.
(2) After servicing by the check code, turn off breaker of the power supply, and turn on breaker of the power
supply again so that memory in the microcomputer returns the initial status. However, the check codes are
not deleted even if the power supply is turned off because they are stored in the fixed memory.
Table 11-4-1
Block distinctionOperation of diagnosis function
Check
codecodestatus
Block
Indoor
P.C .
board
etc.
Not
displayed
Check
Cause of operation
Short-circuit or disconnection of the room
temperature sensor
(TA sensor).
Being out of place,
disconnection, short-circuit,
or migration of heat
exchanger sensor
(TC sensor)
Lock of indoor fan or trouble
on the indoor fan circuit
Trouble on other indoor
P.C. boards
Air conditioner
Operation
continues.
Operation
continues.
All off
Operation
continues.
Remarks
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Displayed when
error is detected.
Judgment and action
1. Check the room temp. sensor.
2. When the room temp. sensor is
normal, check P.C. board.
1. Check heat exchanger sensor.
2. When heat exchanger sensor is
normal, check P.C. board.
1. Check P.C. board.
2. When P.C. board is normal, check
the motor.
Replace P.C. board.
Connecting cable
and serial
signal
Return serial signal is not
sent to indoor side from
operation started.
(1) Defective wiring of
connecting cable
(2) Operation of
compressor thermo.
Gas shortage
Gas leak
Operation command signal
is not sent to outdoor side.
Operation
continues.
Operation
continues.
Flashes when
trouble is
detected on
return serial
signal, and
normal status
when signal is
reset.
Flashes when
trouble is
detected on
operation
command signal,
and normal status
when signal is
reset.
1. When the outdoor unit never
operate:
(1) Check connecting cable, and
correct if defective wiring.
(2) Check 25A fuse of inverter
P.C. board
(3) Check 3.15A of inverter
P.C. board.
2. To display [Other] block during
operation, check compressor
thermo. operation and supply gas
(check gas leak also).
3. Unit operates normally during
check.
If Return serial signal does not
stop between 2 and 3 of the
indoor terminal block, replace
inverter P.C. board.
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.
If return serial signal does not stop
between indoor terminal block 2
and 3, replace inverter P.C. board.
If signal stops between indoor
terminal block 2 and 3, replace
indoor P.C. board.
When 20 seconds passed after
startup, position-detect circuit error
occurred. : Replace compressor.
1. Repeat Start and Stop with
interval of approx. 10 to 40
minutes. (Code is not displayed
during operation.)
Supply gas. (Check also gas leak.)
2. Unit operates normally during
check.
If return serial signal does not
stop between indoor terminal
block, 2 and 3 replace inverter
P.C. board.
If signal stops between indoor
terminal block, 2 and 3 replace
indoor P.C. board.
1. Trouble on compressor
2. Trouble on wiring of compressor
(Missed phase)
1. Check discharge temp . sensor (TD).
2. Degassing
3. Trouble on P.M.V.
1. Check power voltage. (220-240 V
+10%)
2. Overload operation of
refrigeration cycle
Check installation condition
(Short-circuit of outdoor diffuser.)
1. Check 4-way valve operation.
– 64 –
11-5. Judgement of Trouble by Every Symptom
11-5-1. Indoor unit (Including remote controller)
(1) Power is not turned on (Does not operate entirely)
FILE NO. SVM-07008
supply once, and 5
second later, turn it
NO
Is fuse (F01)
of indoor control
board blown?
NO
Turn off power
on again.
Is OPERATION
lamp blinking?
YES
Is it possible to
turn on power
supply by
pressing
[ ] button
on remote
control?
YES
YES
(D01 ~ D04,
and IC12 are
NO
Parts
C03, T101
defective.
Does
transmission
mark on
remote control
flash normally,
and is its signal
transmitted
properly?
YES
NO
Does
fan motor
connector
between 1
3
and
short-circuit?
Remote control is
defective.
Refer to (5)
"Troubleshooting for
Remote Control.
YES
"
Operation
Check item
Conceivable principle
cause
Measure
Item by symptoms
Unit operates
normally.
Is voltage
(DC 12V or 5V)
NO
indicated on
rear of indoor
control board
normal?
Is the
voltage
across C03
mesured
DC 310V~340V?
YES
Are DC 5V,
DC 12V
supplied
to main
P.C. board?
YESYES
NO
NO
Refer to
<Primary check>
or this problem
is one step short
of power P.C.
board block.
Turn off breaker
once and turn it
on again after
removing motor.
YES
Are DC 5V,
or DC 12V
supplied
to main
P.C. board?
NO
NO
Microcomputer
is defective.
Regulator IC
(IC12) or T101
are defective
Replace main
P.C. board.
Replace motor
• Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
damage of the motor.
.
– 65 –
(2) Power is not turned on though Indoor P.C. board is replaced
<Confirmation procedure>
Turn on power supply.
FILE NO. SVM-07008
Does operation lamp flash?
YESYES
NONO
Is wired correctly to white and black
lead wires of terminal board?
Correct wiring.
To item of
“Power is not turned on”.
– 66 –
(3) Only the indoor fan does not operate.
<Check procedure>
Shut off the
power supply once.
Turn the power supply.
FILE NO. SVM-07008
Does the fan stop in
no operating status?
YES
Start the operation
with low fan setting
in cool operation.
Does the fan rotate?
YES
Change the setting of
cooling to high fan.
Does the fan speed
become higher?
NO
NO
NO
Control P.C. board is defective.
Does AC 120 V
or higher voltage apply
to between red and black
lead of fan motor?
YES
Shut off the power supply.
Does the cross flow
fan rotate normally?
YES
Turn on the power supply.
Operation
stops
Replace the P.C. board.
Does connecting
terminal, connecting
NONO
NO
cable or power supply
cord completely?
Does not found the short
wire about connecting
cable and power cord?
YES
Repair the
bearing of
the fan.
Motor control circuit failure
(IC31, D301) or 12 V
switching module failure (T101).
YES
Normal
−
Is the rotation signal (DC+5 V
output between 2 (gray lead wire)
and 3 (brown lead wire) of the motor
connector (CN11) when rotating the
cross flow fan by hand in no operating
status? (1 pulse/one turn)
YES
Replace the control
P.C. board.
0 V)
– 67 –
NO
Replace the P.C. board.
Replace the fan motor.
Replace connecting the
cable (or power cord)
and terminal
block.
FILE NO. SVM-07008
(4) Indoor fan motor starts rotating by turning on power supply alone.
<Cause>
The IC is built in the indoor fan motor. Therefore the P.C. board is also mounted to the inside of the motor.
If the P.C. board is soldered imperfectly or the IC is defective, the fan motor may automatically rotate by turning
on power supply.
<Confirmation procedure>
(1) Rem
(2) Remove cover of the fan motor lead wires.
(3) Check DC voltage with CN31 connector while the fan rotating.
NOTE :
• Do not disconnect the connector while the fan rotates.
• Use a thin tester rod.
Indoor fan starts rotating when power supply breaker is turned “ON”.
ove the front panel.
P.C. board
CN10
(Check output voltage (DC) of the fan motor on P.C. board.)
Measure the voltage of the motor connector
CN31 pin
Above DC 0.4V
P.C. board is defective.
2
(GND : Black) and pin 5 (V line : Yellow)
under condition that the indoor fan rotates.
Below DC 0.4V
Motor is defective.
Yellow
Black
DC
6 (Blue)
5 (Yellow)
4 (Blue)
3 (Yellow)
2 —
1 (Red)
– 68 –
(5) Troubleshooting for remote control
FILE NO. SVM-07008
Is receiver on
indoor unit exposed
to direct sunlight?
YES
NO
Is there any
thyristor fluorescent
light nearly?
YES
YES
NONO
Press [ ]
button.
Is transmission
mark indicated?
Does indoor unit
operate when
moving remote control
near receiver or
indoor unit?
YES
Batteries are
exhausted.
The unit does not beep at all.
OPERATION lamp on
indoor unit is not indicated.
NO
Press RESET button
on remote control
with tip of pencil.
Press [ ]
button.
Avoid direct
sunlight.
Keep indoor unit
away from
thyristor
fluorescent light.
Does indoor unit
NO
start to operate by
automatic restart
function?
YES
Does radio sound
is affected by
remote control when
a signal is transmitted
at distance of 5 cm
from radio?
P.C. board is
defective.
Replace
P.C. board.
YES
Is transmission mark
indicated?
NO
NO
Replace
batteries.
Note :After replacing batteries,
press the RESET button
with a tip of a pencil.
Does indoor unit
beep and operate?
operation
YES
YES
Normal
NO
Remote control
is defective.
Replace
remote control.
– 69 –
FILE NO. SVM-07008
11-5-2. Wiring Failure (Interconnecting and serial signal wire)
(1) Outdoor unit does not operate.
1) Is the voltage between indoor terminal block 2 and 3 varied?
Confirm that transmission from indoor to outdoor is correctly performed based on the following diagram.
NOTE:
• Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
• Be sure to prepare a diode for judgment.
Terminal block on indoor side
Red
White
Normal time: Voltage swings between DC15 V and 60 V.
Abnormal time : Voltage does not vary.
(2) Outdoor unit stops in a little while after operation started.
<Check procedure> Select phenomena described below.
3
2
1
Terminal block
S5277G
S5277G or equivalent (G or J type)
(Diode with rated voltage of 400 V
or more is acceptable.)
Tester
1) The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are
required to restart the unit.
Gas circulation amount is down.
Measure gas pressure.
Thermo operation of compressor
Gas shortage
Gas leak
Pipe clogging
2) If the unit stops once, it dose not operate until the power will be turned on again.
To item of compressor does not operate.
3) The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed.
(Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)
Gas leak
P.M.V. is defective.
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and coming-off TC sensor
– 70 –
Refer to the chart in 10-6.
11-6. Check Code 1C (Miswiring in indoor/outdoor units) and 1E
<Check procedure>
1C1E
Gas leakage,
disconnection of TS/TC
sensors (Check code 02, 1C)
Valve drive check
Discharge temp. error,
gas leakage
(Check code 03, 1E)
FILE NO. SVM-07008
Is coil of the pulse modulation valve
(P.M.V.) correctly set?
YES
Is connector of coil connected to inverter?
YES
Is positioning sound of valve (sound hitting to stopper) heard from valve
when the air conditioner starts the operation after turning off power of the
air conditioner once?
NOTE :
After all the operations stopped by the remote control, the power keeps
being supplied to outdoor unit for approx. 3 minutes. If operating the air
conditioner by remote control again just after all the operations stopped by the
remote control, positioning of the valve is not performed when outdoor unit
is activated because supplying power to the outdoor unit is not interrupted.
After positioning of the valve, activate the compressor and the outdoor fan.
It takes approx. 7 seconds for positioning of the valve, and sound ticktack
(hitting sound to stopper) is heard for approx. 0.5 seconds at least of that
period. As the sound is low, check sound by using screwdriver, etc.
YES
Are temp. sensors of indoor/outdoor units correctly set to the holder?
NOTE :
The temperature sensors which are used to control electronic control valve
include indoor heat exchanger sensor (TC), outdoor heat exchanger temp.
sensor (TE), and outdoor suction temp. sensor (TS).
YES
NO
NO
NO
NO
Set it correctly.
Set it correctly.
Replace coil valve.
Set it correctly.
Gas amount check and valve clogging check
Remove TC sensor connector from the P.C. board in indoor unit.(Remove connector from the P.C. board.)
Operate the air conditioner in COOL mode by TEMP button ( Pi sound is heard if keeping pushed for 10 seconds.).
The operation enters temporary operation mode which fixes opening degree of P.M.V. and No. of revolution of
compressor. Check condensation at outlet of P.M.V., and then check operating pressure from the service port.
If there is condensation at outlet (1/4 inch=∅6.35mm valve side),
Check the operating pressure from service port, and add gas if pressure is low.
Existence of condensation at outlet of P.M.V.
the valve is clogged.
YES
– 71 –
Replace valve.
Add gas.
FILE NO. SVM-07008
11-7. How to Diagnose Trouble in Outdoor Unit
11-7-1. Summarized inner diagnosis of inverter assembly
Table 11-7-1
Diagnosis/Process flowchartItemContentsSummary
Remove
connector of
compressor.
Check 25 A fuse
(Part No.F01).
OK
Check
terminal voltage
of electrolytic
capacitor.
OK
NG
NG
Replace fuse.
Check
electrolytic
capacitor,
diode block
(DB01), etc.
Check
electrolytic
capacitor,
diode
(DB01), etc.
Preparation
Check
Check
Turn “OFF” the power
breaker, and remove 3P
connector which connects
inverter and compressor.
• Check whether 25 A fuse
on the control board
assembly is blown or not.
(F01)
If fuse was blown,
be sure to check the
electrolytic capacitor
and diode block. (DB01)
• Connect discharge
resistance (approx.
100Ω40W) or soldering
iron (plug) between +, –
terminals of the electrolytic
capacitor (500µF)
of C14 (with printed
CAUTION HIGH VOLTAGE) on P.C. board.
Discharging position
(Discharging period
10 seconds or more)
Plug of
soldering
iron
Does outdoor
fan rotate?
YES
NG
Replace
outdoor
fan motor.
NO
Does LED on control
board flash or go on?
NO
Remove connector
CN300 of outdoor
fan motor, and using
a tester, check
resistance value
between every phase
at motor side
OK
YES
ABC
Operation
Measurement
Check
Stop
Check
Measurement
Turn on power breaker, and
operate the air conditioner in
COOL mode by short-circuit
of the timer.
Measure terminal voltage of
electrolytic capacity.
500µF: 400WV x 3
After operation, turn off the
power breaker after 2
minutes 20 seconds passed,
and discharge the electrolytic
capacity by soldering iron.
Check voltage between
motor phases.
• Is not winding
between 1-2, 2-3, or
1-3 opened or
short-circuited?
• Is not frame grounded with
1, 2 or 3?
OK if 500µF →
DC280 to 380 V
Remove CN300 by pushing
the part an arrow because
CN01 is a connector with
lock.
→ Resistance between
phases should be approx.
55 to 77Ω.
→ Should be 10MΩ or
more.
– 72 –
FILE NO. SVM-07008
Diagnosis/Process flowchartItemContentsSummary
NG
Replace
outdoor
fan
motor.
Check
compressor
winding
resistance.
OK
Replace
control board.
winding of
compressor.
OK
Check
fan motor
position
detect
signal.
OK
Replace control
board assembly.
NG
CBA
Check
Replace
pressor.
Replace
compressor.
com-
NG
Check
Operation
Check winding resistance
between phases of
compressor, and resistance
between outdoor frames by
using a tester.
• Is not grounded.
• Is not short-circuited
between windings.
• Winding is not opened.
Remove connector CN300 of
the outdoor fan motor, turn on
the power breaker, and
perform the operation. (Stops
though activation is
prompted.)
Check operation within 2
minutes 20 seconds after
activation stopped.
<Output check of fan motor
position detect signal>
While connecting connector
5P (CN301) for position
detection, using a tester,
measure voltage between
1-5. Between 5-4 : 5 V
→ OK if 10MΩ or more →
OK if 0.51Ω → 0.57Ω
}
(Check by a digital tester.)
a) One or two of three
voltages should be 5 V,
and others should be 0V.
(When all are 0V or 5 V,
it is not accepted.)
b) When rotating the fan
slowly with hands, the
voltage between pins
should move from 0V to 5 V.
(Check it with an analog
tester.)
11-8. How to Check Simply the Main Parts
11-8-1. How to check the P.C. board (Indoor unit)
(1) Operating precautions
1) When removing the front panel or the P.C.
board, be sure to shut off the power supply
breaker.
2) When removing the P.C. board, hold the edge
of the P.C. board and do not apply force to the
parts.
3) When connecting or disconnecting the connectors on the P.C. board, hold the whole housing.
Do not pull at the lead wire.
(2) Inspection procedures
1) When a P.C. board is judged to be defective,
check for disconnection, burning, or discoloration of the copper foil pattern or this P.C. board.
2) The P.C. board consists of the following 2 parts
a. Main P.C. board part:
DC power supply circuit (5 V, 12 V, 15 V),
Indoor fan motor control circuit, CPU and
peripheral circuits, buzzer, and Driving circuit
of louver.
b. Indication unit of infrared ray receiving
Infrared ray receiving circuit, LED:
To check defect of the P.C. board, follow the
procedure described below.
– 73 –
(3) Checking procedure.
FILE NO. SVM-07008
Table 11-6-1
No.
1
Shut off the power supply and
remove the P.C. board assembly
from the electronic parts base.
Remove the connecting cable from
the terminal block.
2
Remove the connector for the motor,
and turn the power on.
If the OPERATION lamp blinks
(0.5 sec. : ON, 0.5 sec. : OFF) when
the power turning on, the checking
points described as 1-4 of right
column are not necessary to
perform.
3
Start the operation with the system
which the time of the restart delay
timer is shortened.
4
Make the operation status by
pressing once the [
1.The time of the restart delay timer
is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower
enough than room temperature.
5.Continuous operation.
Procedure
] button.
Check Point (Symptom)
1.Is the fuse blown?
Voltage check
1.Between F01 and CN01(pin 1)
(AC 220 ~ 240 V)
2.Between + and −of C03
DC310~DC340V
3.Between
4.Between 12V and GND
1.All indicators light for 3 sec..
2. Indicators do not indicate normally
after approximate 3 sec..
1.Compressor does not operate.
2.OPERATION lamp blinks.
5V and GND
Causes
1. Application of shock voltage.
Overload by short-circuit of the
parts.
1. AC power cord is defective.
Poor contact of the terminal plate.
2. Capacitor (C121) is defective.
Line filter (L01) is defective.
Capacitor (C03) is defective.
Diode (D01,D02,D03, or D04)
is defective.
3. T101 is defective.
Defective indicator, or poor
}
housing assembly. (CN21)
1. The temperature of the indoor
heat exchanger is abnormally
lower.
2. Poor contact of the heat
exchanger sensor. (The connector
is disconnected.) (CN62)
3.Heat exchanger sensor, main
P.C. board are defective. (Refer to
4.Main P.C. board is defective.
5
The status of No. 4 is continued, and
make the following condition.
1.Heat operation
2.Make the setting temperature
higher enough than room
temperature.
6
Turn the power on after connecting
the motor connector. Start the
operation with the following
condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
1.Compressor does not operate.
2.OPERATION lamp blinks.
1.Motor does not rotate. (The key
operation is accepted.)
2.The Motor rotates, but it vibrates
too much.
1.The temperature of the heat
exchanger is abnormally high.
2.The heat exchanger sensor
connector has short-circuit. (CN62)
of the connector
(CN300 : Motor winding)
is 17 to 25Ω, it is normal.
YES
Fan motor is normal.
(Outdoor P.C. board error)
NO
CN300
NO
Fan motor error
NOTE :
However, GND circuit error inside of the motor may be accepted in some cases when the above check is
performed.
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.
– 78 –
FILE NO. SVM-07008
12. PART REPLACEMENT
12-1. Indoor Unit
No. Part name Procedures Remarks
1 Front panel
2 Electrical part
How to remove the front panel
1) Stop the operation of the air conditioner and
turn off its main power supply.
2) Pull the air inlet grille toward you to open it
and remove the air inlet grille.
Then remove the 2 screws fixing the front
panel.
3) First open the horizontal louver, and then
remove the front panel from the back body
by pulling it toward you.
How to mount the front panel
Push the front panel back in and make sure
all hooks are locked.
How to remove the electrical part.
1) Remove the front panel with procedure 1 .
2) Remove the screw holding the electrical part
cover.
3) Disconnect the 3 connectors 2-(3P) for the fan
motor and the connector (5P) for the louver
motor from the P.C. board assembly.
4) Pull out the TC sensor from the sensor
holder.
5) Remove the screw for the ground connection,
remove the screw for the electrical part box.
Then remove the LED and the electrical part
box from the main unit.
2
2
2 2-Screws
3
2 Screws
4 TC Sensor
2
3 Horizontal
louver
How to mount the electrical part.
1) To put back the electrical part box, lock it to
the upper hook of the back body.
2)
Tighten the screws on the electrical part box.
3) Connect the 3 connectors and arrange the
wiring same as original condition and then
tighten the screw from the LED unit to the
back body.
4) Attach the TC sensor to the holder.
5) Tighten the screw for the ground connection.
6) Tighten the screw on the electrical part cover.
1) Remove the front panel and the electrical
part following procedure 2.
2) Remove the center shaft of the horizontal
louver from the back body.
3) Remove the left shaft from the back body.
4) Remove the horizontal louver from the back
body.
3 Left shaft
3-Connectors
5
2 Center shaft
3
Screws
− 79 −
FILE NO. SVM-07008
No. Part name Procedures Remarks
4 Heat exchanger
5 Cross flow fan
1) Remove the front panel, electrical part and
the horizontal louver following procedure 3.
2) Remove the pipe holder at the rear side of
main unit.
3) Remove the 2 screws on the heat exchanger
at the base bearing.
4) Remove the screw on the heat exchanger
at the fixed plate from the back body and then
pull out the right hand side until the socket of
heat exchanger released from the hook of the
band motor (L), and then pull out the upper
side of heat exchanger slowly.
1) Remove the front panel, electrical part,
horizontal louver and the heat exchanger
following procedure 4.
2) Remove the 2 screws on the band motor (L)
and remove the 2 screws on the band motor
(R) and then remove the cross flow fan.
3) Loosen the set screw of the cross flow fan
then separate the fan and the fan motor.
Notice
To assemble cross flow fan and fan motor to the
unit, please turn the fan motor unit the center of
its terminal meets the top position of band motor
(R).
Fix the cross flow fan with the set screw at the
position where the gap between the back body
and the right surface of the cross flow fan is
4.7 mm.
2 Pipe holder
3
2-Screws
2-Screws (R)
2
2-Screws (L)
2
4.7 mm
6 Set screw
Middle of the fan motor terminal
4 Screws
6 Base bearing
1) Remove the front panel, electrical part,
horizontal louver, heat exchanger and the
cross flow fan following procedure 5.
2) Remove the 2 screws fixing the base bearing.
3) Remove the bearing from the base bearing. If
the housing protrudes from the base bearing,
put the housing in position and attach the
bearing to the base bearing.
− 80 −
2
2-Screws
FILE NO. SVM-07008
12-2. Microcomputer
No.Part nameProceduresRemarks
1Common
procedure
<P.C. board layout>
1) Turn the power supply off to stop the operation
of air conditioner.
2) Remove the front panel.
• Remove the 4 fixing screws.
3) Remove the electrical part base.
Replace the thermal fuse, terminal
block, microcomputer ass’y and the
P.C. board ass’y
Component side
– 81 –
<P.C. board layout>
FILE NO. SVM-07008
Solder side
– 82 –
FILE NO. SVM-07008
12-3-1. Outdoor Unit
No.Part nameProceduresRemarks
1Common
procedure
1. Detachment
1) Stop operation of the air conditioner, and
turn off the main switch and breaker of the
air conditioner.
2) Remove the valve cover. (ST1T∅4 x 10s
1 pc)
• After removing screw, remove the valve
cover pulling it downward.
3) Remove the wiring cover (ST1T∅4 x 10s2
pcs.), and then remove the power cord,
connecting cable, and cord clamp
(ST2T∅4 x 16s3 pcs.).
4) Remove the upper cabinet.
(ST1T∅4 x 10s5 pcs.)
• After removing screws, remove the
upper cabinet pulling it upward.
2. Attachment
1) Attach the upper cabinet.
(ST1T∅4 x 10s5 pcs.)
• Hook the rear side of the upper cabinet
to the claw of the rear cabinet, and then
place it on the front cabinet.
2) After connecting the power cord and
connecting cable, attach the cord clamp
and wiring cover.
• Insert the upper part into the upper
cabinet, and insert the claw which has
been hooked to the lower part into the
square hole, and then fix it with screw.
(ST1T∅4 x 10s 1 pc.)
3)
Attach the valve cover. (ST1T∅4 x 10s 1 pc.)
• Insert the upper part to the upper
cabinet, set the hook claw of the valve
cover to square holes (at three
positions) of the main unit, and attach it
pushing upward.
Upper cabinet
Wiring cover
Valve cover
Upper cabinet
2Front cabinet
1. Detachment
1) Perform work of item 1 of 1.
2) Remove upper screw (ST1T∅4 x 10s4 pcs.)
of the front cabinet, and lower screws
(ST1T∅4 x 10s8 pcs.) of the front cabinet.
• Both side of front cabinet envelop the
unit, so remove it by pulling sideward.
2. Attachment
1) Assemble front cabinet to the unit.
2) Attach the removed screws to the original
positions.
– 83 –
FILE NO. SVM-07008
No.Part nameProceduresRemarks
3Inverter
assembly
1) Perform work of item 1 of 1.
2) Remove screw (ST1T∅4 x 10s 1 pc.) of
the upper part of the front cabinet.
• If removing the inverter cover in this
condition, the P.C. board can be checked.
• If there is no space in the upper part of
the upper cabinet, perform work of 2.
Be careful when checking the
inverter because high-voltage
circuit is incorporated in it.
3) Perform discharging by connecting the
e,d polarities by discharging resistance
(approx. 100Ω40W) or plug of soldering
iron to e,d terminals of the C13 (printed
“CAUTION HIGH VOLTAGE” is attached.)
electrolytic capacitor (760µF/400 WV) on
the P.C. board.
Be careful to discharge the capacitor
because the electrolytic capacitor
cannot naturally discharge and
voltage remains depending on the
malfunction state in some cases.
Discharging time
(Discharging period
10 seconds or more)
Inverter cover
PC board
(Soldered surface)
Plug of
soldering iron
NOTE :
This capacitor has mass capacity.
Therefore, it is dangerous that a
large spark generates if shortcircuiting between the e,d polarities
with screwdriver, etc. for discharging.
4) Perform the work of 2.
5) Remove the screw (ST1T∅4 x 10s 1 pc.)
fixing the main body and the inverter box.
6) Remove the lead wire from the holder on
the terminal block.
7) Disconnect the connectors of various lead
wires.
Requirement :
As each connector has a lock
mechanism, avoid removing the
connector by holding the lead wire,
but by holding the connector.
Terminal
Partition
block
The connector is one with lock,
so remove it while pushing the
part indicated by an arrow.
– 84 –
Be sure to remove the connector
by holding the connector, not by
pulling the lead wire.
FILE NO. SVM-07008
No.Part nameProceduresRemarks
4Control board
assembly
1) Disconnect lead wires and connectors
connected from the control board
assembly to other parts.
(See Note 1)
CN701 : 4 way valve (3P: Yellow)*
CN601 : TD sensor (2P: White)
CN602 : TO sensor (2P: White)
CN500 : Case thermo (2P: White)
∗ Note 1) As the connector has a
stopper, release the housing
lock when removing.
∗∗Note 2) Hold the housing (resin part)
with stopper and pull out to
remove.
2) Remove the control board assembly from
the inver ter box.
Note 2) Remove the claw of the
board support fixed to the
inverter board, and remove
upwards holding the heat
sink.
3) Remove the three screws fixing the heat
sink and control board assemble.
4) Attach the new contro board assembly.
Note 4) When attaching the new
control board assembly.
insert the P.C. board into
the guide rail groove
correctly.
CN602
CN601
CN300 CN701
CN500
As CN300 and CN701 are
connectors with lock, remove
while pushing the part indicated
by an arrow
– 85 –
FILE NO. SVM-07008
No.Part nameProceduresRemarks
Fan motor
ƒ
Compressor
„
1) Perform work of item 1 of 1 and 1 of 2.
2) Remove the flange nut fixing the fan motor
and the propeller fan.
• Flange nut is loosened by turning
clockwise.
(To tighten the flange nut, turn counterclockwise.)
3) Remove the propeller fan.
4) Disconnect the connector for the fan motor
from the inverter .
5) Remove the fixing screws (4 pcs.) holding
the fan motor by hand so that it does not
fall.
6) Cut the motor lead at the point which is
100 mm apart from the connector toward
the fan.
7) Use the connector used for the inverter,
and pinch the lead wires using the closed
end splice.
1)
Perform work of item 1 of 1
ƒ
.
and
, 1 of
2
2) Extract refrigerant gas.
3) Remove the partition board.
(ST1T∅4 x 10s 3 pcs.)
4) Remove the sound-insulation material.
5) Remove the terminal cover of the
compressor, and disconnect the lead wire
of the compressor thermo and the
compressor from the terminal.
6) Remove the pipe connected to the
compressor with a burner.
• Make sure the flame does not touch the
4 way valve.
7) Remove the fixing screw of the base plate
and heat exchanger.
(ST1T∅4 x 10s2 pcs.)
8) Pull upward the refrigeration cycle.
9) Remove the nut fixing the compressor to
the base plate.
Propeller fan
Flange nut
Fan motor
Compressor
100
Closed end
splice
…
Reactor
1) Perform work of item 1 of 1, 1 of 2,
and 3.
2) Remove the screw fixing the reactor.
(ST1T∅ 4 x 10 2 PCS.)
s
– 86 –
Reactor
FILE NO. SVM-07008
No.Part nameProceduresRemarks
†
Fan guard
1. Detachment
1) Perform work of item 1 of 1 and 1 of 2.
Requirement:
Perform the work on a corrugated
cardboard, cloth, etc. to prevent
scratches to the product.
2) Remove the front cabinet, and place it
down so that the fan guard side faces
downwards.
3) Remove the hooking claws by pushing a
minus screwdriver according to the arrow
mark in the right figure, and remove the
fan guard.
2. Attachment
1) Insert the claws of the fan guard in the
hole of the front cabinet. Push the hooking
claws (8 positions) by your hand and fix
the claws.
Requirement:
This completes all the attaching
work. Check that all the hooking
claws are fixed to the specified
positions.
Minus screwdriver
Hooking claw
– 87 –
FILE NO. SVM-07008
No.Part nameProceduresRemarks
!Replacement of
temperature
sensor for
servicing only
Common service
parts of sensor
TO , TS, TE, TD
1)
Cut the sensor 100 mm longer than old
one.
2) Cut the protective tube after pulling out it
(200 mm).
3) Move the protective tube toward the
thermal sensor side and tear the tip of
lead wire in two, then strip the covering
part.
4) Pass the stripped part through the ther-
mal constringent tube.
5) Cut the old sensor 100 mm length on the
connector side, and recycle that connector.
6) Tear the lead wire in two on the connector
side and strip and covering part.
7) Twist the leads on the connector and
sensor sides, and solder them.
8) Move the thermal constringent tubes
toward the soldered parts and heat them
with the dryer and constring them.
9) Wind the attached color tape round the
both terminals of the protective tube when
colored protective tube is used.
10) Fix the sensor again.
NOTES:
1) Store the joint part of the sensor and the
connector in the electric parts box.
2) Never joint them near the thermal sensor
part. Otherwise, it would cause insulation
inferiority because of dew drops.
3) When replacing the sensor using the
colored protective tube, wind the color
tape matching the color of that tube.
Thermal
sensor part
200
Winding the color tape
Cutting here
Connector
Thermal
constringent tube
Cutting here
100
15
70
Soldered part
Dryer
100
Cutting here
15
70
These are parts
for servicing
sensors.
Please check
that the accessories shown in the
right table are
packed.
Part nameQ’tyRemarks
1Sensor1Length: 3 m
2Sensor Spring (A)1For spare
3Sensor Spring (B)1For spare
4Thermal constringent tube3Including one spare
5Color tape19 colors
6Terminal3
– 88 –
13. EXPLODED VIEWS AND PARTS LIST
13-1. Indoor Unit (E-Parts Assy)
405
FILE NO. SVM 07008
411
401
403
410
404
LocationPartLocationPart
DescriptionDescription
No.No.No.No.
40143T60365 TERMINAL BLOCK; 3P40543T69612 PC BOARD ASSY ;WRS-LED
40343T69319 TEMPERATURE SENSOR41043T62003CORD CLAMP
40443T69320 TEMPERATURE SENSOR41143T69628ASM-PCB-SERV
− 89 −
13-2. Indoor Unit
FILE NO. SVM-07008
LocationPartLocationPart
DescriptionDescription
No.No.No.No.
20143T00478 FRONT PANEL ASSY21343T19333FIX-PIPE-SENSOR
20243T09402 GRILLE OF AIR INLET (ORIGINAL)21743T22312ASM-BEAR-MOLD
20243T09404 GRILLE OF AIR INLET21843T39323BEARING BASE
(OPTIONAL;GRAY)21943T20323 ASSY CROSS FLOW FAN
20343T03357 BACK BODY ASSY22043T39324MOTOR BAND (LEFT)
20443T80317 AIR-FILTER22143T39321MOTOR BAND(RIGHT)
20543T09392HORIZONTAL LOUVER22243T21393FAN MOTOR
20643T70313 DRAIN-HOSE22443T82309 INSTALLATION PLATE
20743T79301 CAP-DRAIN22543T69615WIRELESS-REMOCO
20843T21363 MOTOR; STEPPING22643T83003HOLDER; REMOTE CONTROLLER
20943T44387 REFRIGERATION CYCLE ASSY22743T62326TERMINAL COVER
21043T47353 PIPE; SUCTION (RAS-13)22843T60317CORD MOTOR LOUVER
21143T47355 PIPE; SUCTION (U1U2_GD)22943T 07311PIPE HOLDER
21243T11319 PIPE SHIELD
− 90 −
13-3. Outdoor Unit
FILE NO. SVM-07008
LocationPartLocationPart
DescriptionDescription
No.No.
143T19335 FAN GUARD1543T49327CUSHION,RUBBER
243T20324 PROPELLER FAN1743T50316BIMETAL THERMO
343T00482 FRONT CABINET1843T41358COMPRESSOR(Made in China)
443T43403 CONDENSOR ASSEMBLY1943T19337 PACKED VALVE COVER
543T62323 TERMINAL COVER2043T00481 UPPER CABINET
643T19336 FIN GUARD2143T00448 FIXING PLAT E VALVE
743T47308 CAPILLARY TUBE; 1.0 DIA2243T42331BASE PLATE ASSEMBLY
843T46331 VALVE;PACKED 9.52 DIA2343T79305 DRAIN NIPPLE
943T47332 BONNET, 9.52 DIA2443T46313 REACTOR
1043T46332VALVE;PACKED 6.35 DIA2543T46333 4 WAY VALVE
1143T47331BONNET, 6.35 DIA2643T46334 COIL-4WAY ASSEMBLY
1243T21396FAN-MOTOR (MADE IN CHINA)2743T04303PARTITION
1343T47001NUT FLANGE2843T39325MOTOR BASE
14 43T19312 HANDLE 29 43T39326 MOTOR BASE CONNECTION PLATE