Toshiba RAS-10SKH-X, RAS-10SKH-E, RAS-10SAH-E SERVICE MANUAL

TO SH IB A
SERVICE M ANUAL
AIR-CONDITIONER
SPLIT W A LL TY PE
FILE N O . A 00-9619
RAS-10SKH-E RAS-10SKHX
RAS-10SAH-E RAS-10SAHX
P R IN T E D IN JAPA N , N ov.,1996 T oM o
CONTENTS
1. SPECIFICATIONS............................................................................................................ 4
2. CONSTRUCTION VIEWS ................................................................................................ 6
2-1. Indoor Unit .................................................................................................................................. 6
2-2. Outdoor Unit ............................................................................................................................... 7
3. WIRING DIAGRAM .......................................................................................................... 8
4. SPECIFICATIONS OF ELECTRICAL PARTS ................................................................. 9
4-1. Indoor Unit .................................................................................................................................. 9
4-2. Outdoor Unit ............................................................................................................................... 9
5. REFRIGERANT CYCLE DIAGRAM .............................................................................. 10
6. MICRO-COMPUTER BLOCK DIAGRAM .......................................................................11
7. OPERATION DESCRIPTIONS....................................................................................... 12
7-1. FAN ONLY Operation ......................................................................................................... ...... 12
7-2. COOL Operation ....................................................................................................................... 12
7-2-1. Louver Control ......................................................................................................................................13
7-3. DRY Operation.......................................................................................................................... 13
7-4. HEAT Operation............................................................................................................. ........... 14
7-4-1. Louver Control ......................................................................................................................................14
7-4-2. Cool Airflow Control .............................................................................................................................14
7-5. AUTO Operation ............................................................................................................. .......... 15
7-5-1. T emporary Auto.....................................................................................................................................15
7-6. ECONO. Mode................................................................................................................ ........... 16
7-6-1. Cooling...................................................................................................................................................16
7-6-2. Heating .................................................................................................................. .................................16
7-7. Current Limit Control............................................................................................................... 16
7-8. High-Temperature Limit Control (Heating Operation) .......................................................... 17
7-9. Low-Temperature Limit Control (Cooling Operation) .......................................................... 17
7-10. Cool Airflow Prevention Control (Heating Operation) ......................................................... 17
7-11. Defrost Operation ......................................................................................................... ............ 18
7-11-1. Condition to Start the Defrost Operation............................................................................................18
7-11-2. Defrost Operation Time Control .......................................................................................................... 18
7-11-3. Ending Condition at Defrost Operation ..............................................................................................18
7-12. Auto Restart Function ..................................................................................................... ........ 19
7-12-1. How to Set the Auto Restart.................................................................................................................19
7-12-2. How to Cancel the Auto Restart ..........................................................................................................20
7-12-3. In Case of Power Failure during the Timer Operation.......................................................................20
8. INSTALLATION PROCEDURE ...................................................................................... 21
8-1. Safety Cautions ............................................................................................................ ............ 21
8-2. Installation Diagram of Indoor and Outdoor Units ............................................................... 23
8-3. Installation ................................................................................................................................ 24
8-3-1. Optional Parts........................................................................................................................................24
8-3-2. Kit Parts .................................................................................................................................................25
– 2 –
8-4. Indoor Unit ................................................................................................................................ 26
8-4-1. Cutting a Hole and Mounting Installation Plate .................................................................................26
8-4-2. Electrical Work ......................................................................................................................................27
8-4-3. Wiring Connection ................................................................................................................................28
8-4-4. Piping and Drain Hose Installation......................................................................................................30
8-4-5. Indoor Unit Installation .........................................................................................................................31
8-4-6. Drainage.................................................................................................................................................31
8-5. Outdoor Unit ............................................................................................................................. 32
8-5-1. Refrigerant Piping Connection ............................................................................................................33
8-5-2. Vacuum Pumping .................................................................................................................................. 33
8-5-3. Wiring Connection ................................................................................................................................34
8-6. Others ........................................................................................................................................ 35
8-6-1. Gas Leak Test .................................................................................................................. ...................... 35
8-6-2. Test Operation .......................................................................................................................................35
8-6-3. Auto Restart Setting .............................................................................................................................35
9. TROUBLESHOOTING CHART...................................................................................... 36
9-1. What to be Prechecked First .................................................................................................. 36
9-1-1. Power Supply Voltage........................................................................................................................... 36
9-1-2. Incorrect Cable Connection between Indoor and Outdoor Units.....................................................36
9-1-3. Misleading but Good Operations.........................................................................................................37
9-2. Primary Judgement of Trouble Sources ...............................................................................38
9-2-1. Role of Indoor Unit Controller..............................................................................................................38
9-2-2. Display of Abnormalities and Judgement of the Abnormal Spots...................................................38
9-3. Troubleshooting Flowcharts ................................................................................................... 42
9-3-1. Power can not be Turned on ................................................................................................................ 42
9-3-2. Power can not be Turned on after Replacing Indoor PC Board .......................................................43
9-3-3. Outdoor Unit does not Operate ...........................................................................................................43
9-3-4. Only Compressor does not Operate ...................................................................................................4 4
9-3-5. Only Outdoor Fan does not Operate ...................................................................................................45
9-3-6. Only 4-Way Valve does not Operate ....................................................................................................46
9-3-7. Only the Indoor Fan does not Operate................................................................................................47
9-4. How to Check the Remote Control (Including the Indoor PC Board) ................................48
9-4-1. How to Check the PC Board.................................................................................................................49
9-4-2. PC Board Layout ...................................................................................................................................5 1
9-4-3. How to Reduce the Operation Time of the Anti-Restart Timer .........................................................52
10. PART REPLACEMENT ................................................................................................. 53
10-1. Indoor Unit ................................................................................................................................ 53
10-2. Microcomputer ......................................................................................................................... 55
10-3. Outdoor Unit ............................................................................................................................. 56
11. CAUTIONS ON REPLACEMENT OF PC BOARD ASSEMBLY.................................... 57
12. EXPLODED VIEWS AND PARTS LIST......................................................................... 58
12-1. Indoor Unit (1)........................................................................................................... ................ 58
Indoor Unit (2)................................................................................................................ ........... 59
Indoor Unit (3)................................................................................................................ ........... 60
12-2. Outdoor Unit .............................................................................................................. ............... 61
– 3 –
1. SPECIFICATIONS
Item
Capacity
Power source
Power consumption Power factor
Running current Starting current
Moisture removal Noise
Refrigerant Refrigerant control
Interconnection pipe
Condensate drain pipe
INDOOR UNIT
Dimensions
Net weight Evaporator type Indoor fan type
Air volume
Fan motor output Air filter
OUTDOOR UNIT
Dimensions
Net weight Condenser type Outdoor fan type Airflow volume Fan motor output
Compressor Safety device
Auto louver Usable outdoor temperature range
Indoor (H/M/L) Outdoor (220/230/240V) Name of refrigerant Rated volume
Gas side size Connection type Liquid side size Connection type Maximum length (of one way) Maximum height difference
Indoor unit Outdoor unit
Outer diameter
Height Width Depth
High fan Medium fan Low fan
Height Width Depth
Model Output
Model
kW
*1
Phase V Hz kW % A Indoor/Outdoor A lit/h dB dB
kg
mm
mm
m *2
↑ ↓
m mm
mm mm mm kg
m3/h m3/h m3/h W
mm mm mm kg
m3/h W
W
°C
RAS-10SKH-E/10SAH-E, RAS-10SKHX/10SAHX
COOLING
220V
2.65
220V
0.11/4.58
230V
2.68
0.98/0.99/1.02 95/92/90
230V
0.11/4.57
Polypropylene net filter (Washable)
21 ~ 43
240V
2.70
220/230/240
240V
0.11/4.61
Capillary tube
Flare connection
Flare connection
RAS-10SKH-E/RAS-10SKHX
Finned tube
Cross flow fan
RAS-10SAH-E/RAS-10SAHX
Finned tube
PH120T1-4C
Fuse, Overload relay
220V
3.00
Single
50
220V
0.11/4.17
19
1.2 41/36/31 47/48/49
R-22
0.74
9.52
6.35
10
5
16
265 790 174
8
600 500 400
19
530 770 200
31
Propeller
1600
18
750
Yes
HEATING
230V
3.05
0.89/0.90/0.91 95/92/88
230V
0.11/4.16
– 5 ~ 21
240V
3.10
240V
0.11/4.22
Specifications are subject to change without notice.
– 4 –
Note : *1
• Capacity is based on the following temperature conditions.
JIS C9612-1994Condition
Temperature
(DB)
Indoor unit inlet air temperature
(WB)
(DB)
Outdoor unit inlet air temperature
(WB)
Notes : *2 CHARGELESS
• No additional refrigerant required.
• This air conditioner accepts a connection piping length of up to 10m and a head of up to 5m.
• There is no need to add the refrigerant as long as the total length of the connection piping is up to 10m.
Cooling
27°C 19°C 35°C 24°C
Heating
20°C 12°C 7°C 6°C
– 5 –
2-1. Indoor Unit
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
,,,,,,,,,,,,,,,,,
RAS-10SKH-E RAS-10SKHX
Air inlet
2. CONSTRUCTION VIEWS
Air filter
790
Heat exchanger
174
265
Air outlet
232 326 232
Drain hose (0.54m)
Hanger
Connecting pipe (0.39m)
(Flare ø9.52)
790
Hanger
321
1800
10SKH-E : Without power cord 10SKHX : With power cord
Connecting pipe (0.49m)
(Flare ø6.35)
Front panel
Back body
47
50
10
47
Knock out system
Knock out system
50
10
65965.5 450
Hanger
326
66 or more
Minimum distance
2.5
46
Minimum distance
17 20
265
to wall
120 or more 120 or more
3.5
40.5
Center line
to ceiling
Installation plate outline
HangerHanger
790
– 6 –
12626931976
65.5 Hanger
For stud bolt (ø8~ø10)
For stud bolt (ø6)
Minimum distance to wall
20 2037
40.5
60.5
Wireless remote control
Remote control holder
55
136
16
112.8
559.6
2-2. Outdoor Unit
RAS-10SAH-E RAS-10SAHX
Detail Drawing
A
600
36 50
216
230
25
ø11x14 Hole
Handle
R10
ø6 Hole
11
A
230
216
30
Fan guard
36
50
600 85
111
ø25 Drain hole
8-ø6 Holes (For fixing the outdoor unit)
4-ø11x14 Long holes (For anchor bolt ø8-ø10)
111
Gas side (flare ø9.52)
Liquid side (flare ø6.35)
200
12
11
525
5
530
ø420
268
89
59
TOSHIBA
770 59
770
268
89
Electric parts cover
Z
54 62
Access for charging
250
230
Inlet port
100 or more
View
Z
600
Inlet port
45 or more
Visible outline of the product
Outlet port
Center
200 or more
Mounting dimension of anchor bolt
port
600 or more
(Minimum distance of the wall)
4-ø11x14 Long holes
(For anchor bolt ø8-ø10)
– 7 –
3. WIRING DIAGRAM
Model Section A
RAS-10SKH-E/SAH-E
220/230/240V ~
50Hz
RAS-10SKHX/SAHX
220/230/240V ~
50Hz
GRN&YEL
Section A
L N
POWER
TERMINAL
BLOCK
BLK
BRW
CN27
L N
P04
BLU
44
11 2 3
L N
SG01
DSA
RY02
T02
C.T.
WHI
THERMAL FUSE
77˚C × 2
R109
VARISTOR
F01 FUSE
T3.15A
250V
3
3
RY01
4
4
BLK
RY03
RY04
CR01
CR02
GRY
1 1
R21
LOUVER
MOTOR
GRY
3 3
CN04
CN07
BLU
6 6
R116
IC04
C01
C15
L01
4
23
BLU
2 2
56789
BLU
BLU
4
56789
3
4
56789
3
BLU
BLU
1
BLU
1 1
INFRARED RAYS RECEIVE
AND INDICATION PARTS
PNK
5 5
R01
PNK
YEL
4 4
BLK
ORN
RED
3
2
3
2
DB01
CN13
WHI
CN25
BRW
1 1
C02
FAN MOTOR
DC
MOTOR
BLK
BLU
YEL
WHI
5 5
RED
4
3
2
1
4
3
2
1
CN10
MAIN P.C. BOARD
MCC-713
T01
C06
IC
IC01
2
1
CN03 CN01
2
1
BLK
BLK
THERMO SENSOR
(TA)
EXCHANGER
DC35V
DC12V
DC7V
DC0V
IC02
2
1
2
1
BLK
BLK
HEAT
SENSOR
(TC)
OVER LOAD
COMPRESSOR
RELAY
BLK
INDOOR
TERMINAL
BLOCK
BLK
RED
CAPACITOR
PNK
WHI
BLK
SOLENOID
COIL
RUNNING
BLK
1
1
BLK
RED
WHI
2
2
RED
RED
BLU
GRN&YEL
3
4
3
4
GRN & YEL
CHASSIS
RUNNING
CAPACITOR
FAN MOTOR
INDOOR
OUTDOOR
WHI
BLK
– 8 –
DSA : Surge absorber C.T : Current trans
COLOR IDENTIFICATION
:
BRW
:
RED
:
WHI
:
YEL
:
BLU
:
BLK
:
GRY
:
PNK
:
ORN
GRN&YEL
:
BROWN RED WHITE YELLOW BLUE BLACK GRAY PINK ORANGE GREEN &
YELLOW
4-1. Indoor Unit
RAS-10SKH-E RAS-10SKHX
4. SPECIFICATIONS OF ELECTRICAL PARTS
No.
1
Fan motor (for indoor)
Thermo sensor
2
(TA-sensor)
3
DC-DC transformer (T01)
4
Microcomputer Power relay (RY01), Com-
5
mon relay (RY02) Heat exchanger sensor
6
(TC-sensor)
7
Line filter (L01)
8
Diode (DB01)
9
Capacitor (C02)
10
Fuse (F01) Relay (for outdoor fan motor,
11
solenoid coil) (RY03, RY04)
12
Power supply IC (IC01)
13
Varistor (R21, 109)
14
Resistor (R01)
15
Current trans (T02)
Parts name
Type
ICF-35-19-3
or
TICF-35-19-3
(microprocessor)
SWT-34
TMP87CK40F
DI1U
(microprocessor)
RF-103YOR6
RBV-406
CEAUF2W101M20
MT3
AJQ1341
MA2830-FJ
15G561K
ERF-5TK5R6
CT422920S-01
Specifications
Output (Rated) 19W, 2pole, 1phase, 220/230/240V, 50Hz
10k at 25°C DC390V, Secondar y DC35V, 12V, 7V
Coil : DC12V 75mA, Rated AC250V 20A
10k at 25°C 10mH, AC 0.6A
4A, 600V 100µF, 450V T3.15A, 250V
Coil DC12V, 33mA, Rated 1A 250V AC 4A, 600V
560V
5.6 , 5W
4-2. Outdoor Unit
RAS-10SAH-E RAS-10SAHX
No.
1
Compressor
2
Fan motor (for outdoor)
Running capacitor
3
(for fan motor) Running capacitor
4
(for compressor) Solenoid coil
5
(for 4-way valve)
6
Overload relay
Parts name
Type
PH120T1-4C
UE6-21SJ5P
SK-50CMP
SK-40CMP25U1
LB60012
J-MRA99269-9200
Specifications
Output (Rated) 750W, 2pole, 1phase, 220/230/240V, 50Hz Winding resistance (Ω)
(at 20°C) Output (Rated) 18W, 6pole, 1phase, 220/230/240V, 50Hz
Winding resistance (Ω) (at 20°C)
500V AC, 1.5µF
400V AC, 25µF
AC : 200/240V U/T 6.8A (90°C), OPEN 135±5°C, CLOSE 69±11°C
Red-Black
4.53
Red-Black
370
White-Black
White-Black
– 9 –
8.73
370
5. REFRIGERANT CYCLE DIAGRAM
g
RAS-10SKH-E / RAS-10SAH-E RAS-10SKHX / RAS-10SAHX
Cooling
Indoor unit
Evaporator
T1
0.39m (Connecting pipe) ø9.52
O.D.:9.52mm O.D.:6.35mm
Cooling
Heating
Heating
Packed valve
Heating
4-way valve
Cooling
Cooling Heatin
P
(ø9.52)
Compressor
PH120T
Accumulator
Propeller fan Outdoor unit
Cross flow fan
Optional piping kits RB-P31BEF1 (3m) RB-P51BEF1 (5m) RB-P71BEF1 (7m)
1
-4C
Condenser
Packed valve
(ø6.35)
Capillary tube
ø1.7x1400
Dryer
Refrigerant R-22 0.74kg
Mark( )means check points of Gas Leak
0.49m (Connecting pipe) ø6.35
Fig. 5-1
Table 5-1
Heating
Cooling
50Hz
Standard High temperature*1 Low temperature Standard High temperature Low temperature
Standard pressure
P
(kg/cm²G)
10SKH-E
10SKHX
15.0
19 ~ 23
12.5
6.0
6.5
4.0
Surface temp. of heat
exchanger interchanging
pipe T1 (°C)
10SKH-E
10SKHX
40.0
52.0 ~ 59.0
35.0
12.0
15.0
2.0
Fan speed
(indoor)
High Low High High High Low
Note :
• Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor.)
1 • During heating overload, the high temperature limit control operation is included.
*
– 10 –
Ambient temp.
conditions DB/WB
(°C)
Indoor
20/– 27/–
20/– 27/19 32/23 21/15
Outdoor
7/6
21/15
–10/–10
35/24 43/26 21/15
6. MICRO-COMPUTER BLOCK DIAGRAM
Operation
C. P. U
Timer
Display
Functions
• Louver Control
Display
ECONO.
Sign Display
• 3-minute Delay at Restart for Compressor
PRE-DEF.
Sign Display
• Motor Revolution Control
Indoor
Fan Motor
• Processing
(Temperature Processing)
• Timer
Louver
ON/OFF Signal
4-Way Valve
ON/OFF Signal
Outdoor Fan
ON/OFF Signal
Compressor
ON/OFF Signal
Motor
Louver
RelayRelayRelay
Relay Driver, Louver Driver
RY01 RY03 RY04
4-Way ValveOutdoor Fan Motor
Compressor
RY02
Relay
Main Unit Control Panel
Current Sensor
Thermo Sensor
Heat Exchanger Sensor
Initializing Circuit
Infrared
(Compressor Current)
Infrared Rays Signal Receiver
Oscillator Circuit
Clock Frequency
Rays
Remote Control
Operation (START/STOP)
Circuit
Power Supply
Thermo Setting
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Noise Filter
ON TIMER Setting
Fan Speed Selection
OFF TIMER Setting
– 11 –
ECONO.
Louver AUTO Swing
Louver Direction Setting
AC220/230/240V ~
50Hz
7. OPERATION DESCRIPTIONS
7-1. FAN ONLY Operation
(MODE of the remote control : FAN ONLY) (1) During this mode, the relay R Y01 is always turned
off so that only the indoor fan is operated. RY 02 is always turnd on.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig 7-1-1.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.
28 27 26 25
(Room temp. – Set temp.)
Set
24
temp.
Fig. 7-1-1 Auto setting of air volume
Table 7-1-1 Manual setting of FAN SPEED
Indication of
FAN SPEED
HIGH
MED LOW(+)
LOW
LOW
HIGH Air volume
(m3/n)
7-2. COOL Operation
(MODE of the remote control : COOL) (1) Compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-2-1.
+1
(Room temp. – Set temp.)
Set
0
temp.
ON
ON ON
OFF
(RY01)
Compressor
Fig. 7-2-1
(2) Relays R Y01 and R Y02 are turned on to energize
the outdoor unit, and a cool operation is carried out.
1) When the FAN is set to AUTO, the indoor fan motor operates as shown in Fig 7-2-2.
2) When the FAN is set to LOW, MED, or HIGH, the indoor fan motor operates with a constant in volume as listed in Table 7-1-1.
ON
OFF
OFF
(RY02)
(RY04)
4-way valve
Common relay
Outdoor fan
(RY03)
OPERATION
display
LOW MED
HIGH
400 500 600
(2) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
– 12 –
FAN
Manual
According to the set
position
+4 +3 +2 +1
(Room temp. – Set temp.)
Set
0
temp.
RY01
OFF
AUTO
HIGH
MED
LOW(+)
LOW LOW
(continuous)
Fig. 7-2-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
7-2-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the desired position.
And the louver position is stored in the microcom­puter, the louvers will be set to the position automatically at the next operation.
(2) When the AUT O b utton is pushed, the louv er v er-
tically swings within range of 25deg.
7-3. DRY Operation
(MODE of the remote control : DRY) (1) Compressor 4-way valve, outdoor fan and
operation display are controlled as shown in Fig. 7-3-1.
ON:6min.
+3
ON:6min.
OFF:4min.
OFF:4min.
+2
+1
(Room temp. – Set temp.)
Set
0
temp.
ON
ON:5min.
OFF:5min.
OFF
(RY01)
Compressor
Common relay
OFF
OFF
(RY04)
(RY02)
4-way valve
ON
ON:5min.
OFF:5min.
(RY03)
Outdoor fan
OPERATION
Fig. 7-3-1
The microprocessor turns the compressor on and off at regular intervals (4 to 6 minutes on and/or off). During the compressor off, the indoor fan will operate in the super low position.
• The indoor fan will operate in the AUTO position.
(2) The pattern of operation depending on the relation
between room temperature and set temperature is shown below:
display
– 13 –
Room temp.
Set temp.+1 Set temp.
Compressor Outdoor fan
Indoor fan
ON ON ON ON
OFF OFF OFF
L.*S.L. S.L.L. L. S.L. L.
*
Super Low
Fig. 7-3-2
7-4. HEAT Operation
(MODE of the remote control : HEAT) (1) Relays, 4-way valve, outdoor fan and operation
display are controlled as shown in Fig. 7-4-1.
0
OFF
ON
ON
(RY04)
(RY02)
Common relay
(RY03)
4-way valve
Outdoor fan
OPERATION
–1
(Room temp. – Set temp.)
Fig. 7-4-1
OFF
ON ON
ON
(RY01)
Compressor
display
7-4-1. Louver Control
(1) By pushing the SET button of the remote control
during the operation, the louver can be set to the desired position.
(2) When the AUT O b utton is pushed, the louv er v er-
tically swings within range of 25deg. And the louver position is stored in the microcom-
puter, and at the next operation, the louvers will be set to the stored position automatically at the next operation.
7-4-2. Cool Airflow Control
(1) If the indoor heat-exchanger temperature detected
by the indoor heat-exchanger sensor is 20°C or below , the indoor fan stops and if the temperature rises to 25°C or above, the fan is restarted.
Details are in 7-10.
(2) Relays R Y01 and R Y02 are turned on to energize
the outdoor unit, and a heat operation is carried out. The indoor fan motor operates as shown in Fig. 7-4-2, when the FAN is set to AUTO.
The motor operates with a constant air volume as listed in Table 7-1-1, when the F AN is set to LOW, MED, or HIGH.
RY01 OFF
Set
0
temp.
-1
-2
-3
-4
(Room temp. – Set temp.)
AUTO
LOW LOW(+) MED(-)
MED
FAN
Manual
According to the set position
Fig. 7-4-2
(3) Once the setting is made, the operation mode is
memorized in the microcomputer so that the same operation can be effected thereafter simply by pushing the START/STOP button.
– 14 –
7-5. AUTO Operation
(MODE of the remote control : AUTO) (1) One of the 3 modes, Cooling, Fan only and Heat-
ing is selected according to room temperature at which operation is to start, as shown in Fig. 7-5-1. The Fan mode will continue until room tempera­ture reaches a level at which another mode is se­lected.
7-5-1. Temporary Au to
When the TEMPORARY button is pushed, the set temperature is fixed at 24°C and controlled in accor­dance with the chart shown in Fig. 7-5-1.
Cooling mode
+4
Cooling mode
+1
Fan only mode
–1
Heating mode
(Room temp. – Set temp.)
(The same cooling mode as the room temperature control is set at set temp. –1˚C) The Louver moved downward.
(The same cooling mode as the room temperature control is set at set temp. –1˚C)
(Only the indoor fan operates at Low speed)
(The same heating mode as the room temperature control is set at set temp. +1˚C)
Fig. 7-5-1
– 15 –
7-6. ECONO. Mode
7-7. Current Limit Control
When the ECONO. button is pushed, during COOL, HEAT and AUTO operation, the OPERATION display is turned off and the ECONO. display is lit and the indoor unit operates quietly and mildly with controlling airflow .
7-6-1. Cooling
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig. 7-6-1.
(2) Fan speed LOW
(˚C)
Set temp. is changed
+2
Set temp. is changed
+1
Set temp.
ECONO. button is pushed
1H 2H TIME0H
The microprocessor detects the input current so as to prevent it exceeds a specified value by means of controlling the outdoor fan control as described in (1) and (2).
(1) Current limit control (Cooling)
Control is performed as shown below by detect­ing the compressor operation current with a cur­rent sensor (C.T).
Compressor Outdoor fan
4
Input current
10A I
9A I
More than I
4
3
More than I3 continues for 5 minutes
continues for 3 seconds
OFF
OFF
ON
Fig. 7-7-1
(2) Current limit control (Heating)
Control is performed as shown in Fig. 7-7-2.
Fig. 7-6-1
7-6-2. Heating
(1) In the ECONO. mode, the set temp. by the remote
control is changed automatically as shown in Fig. 7-6-2.
(2) Fan speed LOW
ECONO. button is pushed
1H 2H TIME0H
Set temp.
-1 Set temp.
is changed
-2
Set temp. is changed
(˚C)
Input current
10A I
9A I
8A I
7.5A I
Compressor Outdoor fan
More than I
4
3
2
1
More than I3 continues for 5 minutes
4
continues for 3 seconds
OFF
OFF
ON OFF
ON
Fig. 7-7-2
Fig. 7-6-2
– 16 –
7-8. High-Temperature Limit Control
(Heating Operation)
7-10. Cool Airflow Prevention Control
(Heating Operation)
The microprocessor detects the indoor heat exchanger temperature so as to prevent exceeding the condensate pressure.
Control is performed as shown in Fig. 7-8-1.
Heat exchanger temperature
(˚C)
60
*
1
53
52
*
1 ····· Only outdoor fan is turned off.
Compressor,
Outdoor fan
OFF
ON
Fig. 7-8-1
7-9. Low-Temperature Limit Control
(Cooling Operation)
(1) During the heating operation, the indoor fan speed
is controlled automatically in accordance with the indoor heat exchanger temperature to prevent blowing the cool air.
Control is performed as shown in Fig. 7-10-1.
Heat exchanger temperature
(˚C)
30 25 20
Indoor fan speed
According to the
set position
U.L. (Ultra Low)
Room temp.
<
Set temp.
OFF
Room temp.
>
Set temp.
S.L (Super Low)
Fig. 7-10-1
(2) As soon as the defrost operation starts, the indoor
fan stops.
The microprocessor detects the indoor heat exchanger temperature so as to prevent freezing up the indoor heat exchanger.
Control is performed as shown in Fig. 7-9-1.
Heat exchanger temperature
(˚C)
7 5
Compressor
Less than 5˚C continues
Outdoor fan
ON
for 5 minutes
OFF
Fig. 7-9-1
– 17 –
7-11. Defrost Operation
minutes40minutes40minutes40minutes
40
Max 6 minutes 10 minutes
1 cycle
Heating
Heating
Heating
Heating
Defrost
Defrost
Defrost
Defrost
(
)
During the heating operation, the outdoor heat exchanger temperature goes down and sometimes it is frozen.
In this case, the air conditioner stops the heating operation and starts the defrost operation to melt ice.
7-11-1. Condition to Start the Defrost
Operation
The defrost operation starts whichever below conditions are specified.
(1) When the cumulative compressor operation time
is longer than 40 or 90 minutes and difference between the indoor heat exchanger temperature and the room temperature is less than the specified value. (This value is decided by the microprocessor.) (Control e xample is shown in Fig. 7-11-1. In case of B or C, the defrost operation starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of 90 minutes.
(˚C)
D
19
Fig. 7-11-2
<In case of C>
(1) The heating operation is performed for at least 90
minutes.
(2) The defrost operation time is 10 minutes.
7-11-3. Ending Condition at Defrost
Operation
(1) When the compressor current becomes 7.5A or
more during defrost operation, the defrost opera­tion stops and the heat operation restarts. (The current sensor detects the compressor current.)
(2) The defrost operation continues for at most 6
minutes or 10 minutes.
10
Indoor heat exchanger temp.
–Room temp.
A
40 90
B
Fig. 7-11-1 (Indoor fan speed : M)
7-11-2. Defrost Operation Time Control
<In case of B>
(1) The heating operation is performed for at least 40
minutes.
(2) The maximum defrost operation time is 6 minutes.
The defrost operation time for the 4th cycle is 10 minutes. (When the outdoor temperature is very low, however, the defrost operation time is 10 minutes.)
C
min.
Cumulative compressor operation time
– 18 –
DEFROST LAMP :
• During defrost operation, the PRE-DEF. lamp is on and the indoor and outdoor fans are off.
• The compressor start protection timer is inter­locked with the PRE-DEF. lamp. So the PRE­DEF. lamp is off (the fans stop) f or about 3 min­utes after the START/STOP button is turned on. When the compressor is turned on, the PRE-DEF. lamp comes on. After the heat ex­changer is preheated to about 30°C or higher, the PRE-DEF. lamp goes off, and the indoor f an starts.
7-12. Auto Restart Function
This unit is equipped with an Automatic restarting facility which allows the unit to restart and resume the set operating conditions in the event of a power supply shutdown without the use of the hand control.
The operation will resume without warning three minutes after the power is restored.
The Auto Restart function is set not to work on shipment from the factory, and so it is necessary to set it to function as required.
• When the system is stand-by (not running)
7-12-1. How to Set the Auto Restart
To set the Auto Restart function, proceed as follows: Access the TEMPORARY button located in the lower
right hand corner beneath the hinged front panel of the indoor unit (please refer to section on PARTS NAME). The power supply to the unit must be on ­the function will not be set if the power is off.
To enable the Auto Restart function, press the TEMPORARY button contin uously f or three seconds.
The unit will acknowledge the setting and beep three times. The system will now restart automatically.
The above A uto Restart settings can be carried out:
OPERATION
Press the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
• When the system is operating
OPERATION
Press the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
MOTION
Stand-by
The system starts to operate. The green light will be lit.
about three seconds after
3S
The unit beeps three times. The orange light will be lit.
The system is operating. The orange light is lighting. If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
MOTION
Operating The green light is lit.
The system stops to operate. The green light is turned off.
about three seconds after
3S
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the orange light is lit.
• The Auto Restart function will not accept an instruction if timer operation with the remote control is selected.
(Please refer to the section on setting the timer or setting the louver.)
• During louver swing (A UTO) oper ation, after restart by the Auto Restart function the louver swing stops.
– 19 –
7-12-2. How to Cancel the Auto Restart
To cancel the Auto Restart function, proceed as follows:
Repeat the setting procedure: the unit will acknowledge the instruction and bleep three times.
• When the system is stand-by (not running)
The system will now be required to manually restart with the remote control after the main supply is turned off.
Cancellation is carried out:
OPERATION
Press the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
• When the system is operating
OPERATION
Press the TEMPORARY button continuously more than three seconds.
0
TEMPORARY
MOTION
Stand-by
The system starts to operate. The orange light will be lit.
about three seconds after
3S
The unit beeps three times. The green light will be lit.
The system is operating. If the system is not required to run at this time, press the TEMPORARY
button once more or use the remote control and the unit will stop.
MOTION
Operating The orange light is lit.
The system stops to operate. The orange light is turned off.
about three seconds after
3S
The unit beeps three times.
The system stops. If the system is not required to stop at this time, use the remote control
and to restart.
During subsequent operation, the green light is lighting.
7-12-3. In Case of Power Failure during the
Timer Operation
(1) If ON-TIMER operation is reserved with setting of
Auto Restart operation, it is cancelled with power failure. (The OPERATION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reserve ON-TIMER operation once again.
(2) If OFF-TIMER operation is reserved without
setting of Auto Restart operation, the reservation is cancelled with power failure. (The OPERA TION lamp on the main unit goes on and off to inform of power failure.) In that case, try to reserve OFF­TIMER operation. When Auto Restart operation is set, OFF-TIMER reservation is also cancelled with power failure.
– 20 –
8. INSTALLATION PROCEDURE
8-1. Safety Cautions
For general public use
Power supply cord of parts of appliance for Outdoor use shall be more than polychloroprene sheathed flexible cord (design H05 RN-F), or cord designation 245 IEC 57.
CAUTION
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY. This appliance must be connected to the mains by means of a circuit breaker or a switch with a contact
separation of at least 3 mm. If this is not possible, a power supply plug with earth must be used. This plug must be easily accessible after
installation. The plug must be disconnected from the power supply soc ket in order to disconnect the appliance completely from the mains.
DANGER
` FOR USE BY QUALIFIED PERSONS ONLY. ` TURN OFF MAIN POWER SUPPLY AND BREAKER BEFORE ATTEMPTING ANY ELECTRICAL WORK.
MAKE SURE ALL POWER SWITCHES AND BREAKER TURN OFF. FAILURE TO DO S O MAY CAUSE ELECTRICAL SHOCK.
` CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED BY
WRONG WAY, ELECTRIC PARTS MAY BE DAMAGED. ` CHECK THE EARTH WIRE IS NOT BR OKEN OR DISCONNECTED BEFORE INSTALLATION. ` DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OF GAS VAPORS.
FAILURE TO FOLLOW THIS INSTR UCTION CAN RESULT IN FIRE OR EXPLOSION. ` TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT
WELL AWAY (MORE THAN 2M.) FROM HEAT SOURCES SUCH AS RADIATORS, HEAT RESISTORS,
FURNACE, STOVES, ETC.. ` WHEN MOVING THE AIR-CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R-22) WITH ANY OTHER GASEOUS BODY
INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT,
THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT
RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS. ` IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION
WORK, IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY
FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WARNING
• Never modify this unit by removing any of the safety guards of by by-passing any of the safety interlock
switches.
• Do not install in a place which cannot bear the weight of the unit.
Personal injury and property damage can result if the unit falls.
• Before doing the electrical work, attach an approved plug to the power supply cord.
And make sure the equipment to be earthed.
• Appliance shall be installed in accordance with national wiring requlations.
If you detect any damage, do not install the unit. Contact your Toshiba dealer immediately.
– 21 –
CAUTION
• Exposure of unit or water or other moisture before installation will result in an electrical short.
Do not store in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully for possible damage.
• Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify
the noise level of unit or where noise and discharged air might disturb user’s neighbors.
• To avoid personal injury, be careful when handling parts with sharp edges.
• Please read the installation manual carefully before installing the unit. It contains further important
instructions for proper installation.
UK Plugs and Sockets etc (Safety) Regulations 1994
SI Number 1768
With regard to Schedule 3, Item 7 of the above UK Regulations, this appliance must be permanently connected to the fixed wiring of the main electrical supply by means other than the use of an approv ed 13 Amp plug-top as outlined in the Regulations.
Electrical work must be carried by suitably qualified persons and in accordance with all relevant safety standards and codes of practice.
We recommend that the power supply f or this appliance is derived from a suitab ly protected dedicated circuit.
(for U.K. only)
For to comply with the specification 61000-3-3 the local power authority has to be conducted for permit of operation. The installation condition has to be done as following :
Installation only by authorized installer
This product has to be connected to the mains supply via a separate connection to the main distribution box
(circuit breaker box).
– 22 –
8-2. Installation Diagram of Indoor and Outdoor Units
For installation of the indoor unit, use the paper pattern on the back.
For the rear and left piping
Front cabinet
Front panel
(Attach to the back side.)
11 Filter frame
9 Deodorizing filter
10 Purifying filter
3 Clip anchorClip anchor
120 mm or more
Air filter
(Attach to the back side.)
2 Wireless remote control
Hook
Hook
6 Pan head wood screw
4 Remote control holder
66 mm or more
Hook
8 Mounting screw
1 Installation plate
120 mm
or more
5 Shield pipe
Wall
Insert the remote control holder cushion between the indoor unit and wall, and lift indoor unit to make work easier.
Do not allow the drain hose to get slack.
Cut the piping hole sloped slightly
Make sure to run the drain hose sloped downward.
The auxiliary piping can be connected the left, rear left, rear, right or bottom.
Right
100 mm or more
Before install the wireless remote control
• With the remote control cover open, load the batteries supplied correctly, observing their polarity.
Wireless remote control
2
7
Batteries
Cover
400 mm or more
Electric parts cover
45 mm or more
600 mm or more
600 mm or more
Loop the connective cable (about 100 mm in diameter and 300~350 mm long).
– 23 –
Extension drain hose (Option: RB-821SW)
Rear
Bottom
Rear left
Left
Insulation of refrigerant pipes insulates the pipes separately, not together.
6 mm thick heat resisting polyethylene foam
8-3. Installation
8-3-1. Optional Parts
Part
code
Parts name
Q’ty
<Drainage>
Bottom plate
ø25
12
Drain nipple
Refrigerant piping
A
Liquid side : ø6.35 mm Gas side : ø9.52 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
<Anchor bolt arrangement of outdoor unit>
600mm
Air inlet
111mm
30mm
230mm
Drain nipple
12
Air outlet
Each
one
1
Each
one
Drain hose sold separately or one on the market.
Fig 8-3-2
• Install the provided drain nipple in the hole of the bottom plate of the outdoor unit. (See the above figure.)
• Perform proper drainage processing using a drain hose sold separately or one on the market. (Inner diameter : 16 mm)
• Do not use an ordinary hose on the market, because it tends to get flat and as a result, it prevents water from draining.
Fig 8-3-1 Air outlet
• Secure the outdoor unit with the anchor bolts if the unit is likely to be exposed to a strong wind.
• Use ø8 or ø10 anchor bolts.
• If it is necessary to drain the defrost water from the outdoor unit, attach
drain nipple to the
12
bottom plate of the outdoor unit before installing it. The drain nipple is located as shown above.
– 24 –
8-3-2. Kit Parts
Parts with an asterisk (*) are packaged with the outdoor unit.
Part
No.
1
2
Name of parts
Q’ty
Installation plate x 1
Part
No.
5
6
Name of parts
Q’ty
Shield pipe x 1
Part
No.
9
10
Name of parts
Q’ty
Deodorizing filter x 1
Pan head wood screw
Wireless remote control x 1
3
Clip anchor x 6
4 8
Remote control holder x 1
ø3.1 x 16l x 2
7
Batteries x 2
Mounting screw ø4 x 25l x 6
Purifying filter x 1
11
Filter frame x 2
12
Drain nipple* x 1
Others This model is not equipped with an extension drain hose.
Name
Installation manual
Option : For the extension drain hose, use an optionally available RB-821SW or commercially available one.
Owner’s manual
– 25 –
8-4. Indoor Unit
t Installation place
• A place which provides the spaces around the indoor unit as shown in the diagram in section 8-2.
• A place where there is no obstacle near the air inlet and outlet.
• A place which allows an easy installation of the piping to the outdoor unit.
• A place which allows the front panel to be opened.
8-4-1. Cutting a Hole and Mounting
Installation Plate
<Cutting a hole>
When installing the refrigerant pipes from the rear
CAUTION
• Direct sunlight to the indoor unit wireless receiver should be avoided.
• The microprocessor in the indoor unit should not be too close to r-f noise sources. (For details, see the owner’s manual.)
<Remote control>
• A place where there are no obstacles such as a curtain that may block the signal from the remote control.
• Do not install the remote control in a place exposed to direct sunlight or close to a heating source, such as a stove.
• Keep the remote control at least 1 m apart from the nearest TV set or stereo equipment. (This is necessary to prevent image disturbances or noise interference.)
• The location of the remote control should be determined as shown below.
The center of the piping slot
The center of the pipe hole is the above arrow.
is the above arrow.
Pipe hole
80mm
65mm
40.5
mm
Fig. 8-4-2
(1) After determining the pipe hole position with the
mounting plate (80 mm ), drill the pipe hole (ø65 mm) at a slight downward slant to the outdoor side.
NOTE :
• When drilling the wall that contains a metal lath, wire lath or metal plate, be sure to use a pipe hole brim ring sold separately.
<Mounting the installation plate>
For installation of the indoor unit, use the paper pattern on the back.
Anchor bolt hole
7m
75˚
(Side view) Indoor unit
Reception range
(Top view)
Remote
control
Fig. 8-4-1
Indoor unit
Reception range
*:Axial distance
5m
45˚
45˚
Remote control
5m
*7m
– 26 –
65.5mm Pipe
hole
Indoor unit
Thread
Weight
Fig. 8-4-3
8
Mounting screw
Pipe hole
65.5mm
1
Installation plate
<When the installation plate is directly mounted on the wall>
(1) Securely fit the installation plate onto the wall by
screwing it in the upper and lower parts to hook
up the indoor unit. (2) Install the installation plate horizontally in the wall. (3) To mount the installation plate on a concrete wall
with anchor bolts, utilize the anchor bolt holes as
shown in the above figure.
CAUTION
When installing the installation plate with mounting screw , do not use the anchor bolt hole. Otherwise the unit may fall down and result in personal injury and property damage.
8-4-2. Electrical Work
(1) The supply voltage must be the same as the rated
voltage of the air conditioner .
(2) Prepare the power source for exclusive use with
the air conditioner.
Maximum
Model
RAS­10SKH-E/ 10SAH-E
RAS­10SKHX/ 10SAHX
Power source
50Hz
*220/230/240V~
Single-phase
running
current
* No adjustment is necessary .
7.5 A
Plug socket & fuse
rating
15 A
Wiring
1mm2 or
more
Anchor bolt
Projection 15mm or less
CAUTION
Installation plate (Keep horizontal direction)
5mm dia, hole
Clip anchor
3
Mounting screw ø4 x 25
8
Fig. 8-4-4
CAUTION
• Use power specified in above table.
• This appliance can be connected to the mains in either of the following two ways.
(1) Connecting the power cord to the main power
supply provided with a circuit breaker or switch with a contact of 3 mm or more.
In this case, an approved circuit breaker or switch must be used.
(2) Attaching a plug to the power cord and pluging
it in to the wall outlet. In this case, an approved power cord and plug
must be used.
NOTE :
• Perform wiring works so as to allow a generous wiring capacity.
Failure to firmly install the unit may result in personal injury and property damage if the unit falls.
• In case of block, brick, concrete or similar type walls, make 5 mm dia, holes in the wall.
• Insert
clip anchors for appropriate
3
mounting screws.
NOTE :
• Install the installation plate using 4 to 6 pieces of mounting screw securing four corners with screws.
8
– 27 –
8-4-3. Wiring Connection
WARNING
Taking out the power cord
To plug the cable in the plug receptacle, take the following precaution.
THIS APPLIANCE MUST BE EARTHED.
IMPORTANT
THE WIRES IN THIS MAINS LEAD ARE COLORED IN ACCORDANCE WITH THE FOLLOWING CODE:
L
: Brown
N
: Blue : Green and Yellow
-LIVE
-NEUTRAL
-EARTH
L N
Fig. 8-4-5
As the colors of the flexible cord of this appliance may not correspond with the colored markings, to identify terminals in your plug, as follows:
Connect BROWN colored core to plug terminal marked letter "L".
Connect BLUE colored core to plug terminal marked letter "N".
Connect GREEN AND YELLOW colored core to plug terminal marked Earth Symbol " ".
<How to remove the front cabinet>
4
4
Slitted portion
• Cut off the slitted portion in the side f ace of the rear panel to take out the power cord. After this, remove burrs, sharp edges, etc., to smooth the cut face.
<How to connect the power cord> For the air conditioner that has no power cord,
connect a power cord to it as mentioned below.
• After removing the front cabinet, remove the terminal cover and the cord clamp.
• Connect and secure the power supply cord and secure the cord clamp and the terminal cover.
• Cut the rear panel following the cutting mark and put the power supply cord through the notch.
• Be sure to smooth out the notch with a file, etc.
Terminal block
Power supply cord
L
N
Cord clamp
Terminal cover
Screw
2
1
3
Vertical air flow louver.
1
2
Fig. 8-4-6
How to open the screw cap
• Place your finger on the lower part and push up to open the screw cap.
(1) Open the screw caps and remove the two screws
securing the front cabinet. (2) Close the screw caps as behind. (3) Open the vertical airflow louver horizontally by
hand. (4) Slightly open the lower part of the front cabinet
then pull the upper part of the front cabinet toward
you to remove it from the rear plate.
– 28 –
Earth line
Fig. 8-4-7
<Stripping length of power cord>
30mm
10mm
L
N
10mm
40mm
NOTE :
• Use standard wire only.
• Wire type: More than H05-RNF
Fig. 8-4-8
Screw
Screw
Earth line
<How to connect the connecting cable> Wiring of the connecting cable can be carried out
without removing of the front panel.
(1) Remove the front panel.
Fully open the front panel. Disengage the support
arm located in the upper center while pushing its
handle leftwards, and then remove the front panel
toward you. (2) Remove the terminal cover and cord clamp. (3) Insert the connecting cable (according to local
codes) into pipe hole on the wall. (4) Take out the connecting cable through the cable
slot on the rear panel so that it is exploded by
about 15 cm long in the front side. (5) Insert the connecting cable fully into the terminal
block and secure it by screw tightly. (6) Tightening torque:1.2 N•m (0.12 kgf•m) (7) Secure the connecting cable with the cord clamp. (8) Fix the terminal cover and front panel on the indoor
unit.
CAUTION
• Be sure to refer the wiring system diagram labeled inside the front panel.
• Check local electrical codes and also any specific wiring instructions or limitation.
Terminal block
Connecting cable
about 15cm
Terminal cover
Screw
Cord clamp
Earth line
<Stripping length of connecting cable>
50mm
10mm
4 3 2 1
10mm
40mm
Earth line
For a five conductor cable
NOTE :
• Use stranded wire only.
• Wire type:More than H05 RN-F
Fig. 8-4-10
<How to install the front cabinet on the indoor unit>
Install the front cabinet through the opposite order of "How to remove the front cabinet".
When the panel is removed and mounted again, take the following actions:
After fastening the two screws, one each at the left and right of the air outlet, be sure to push the upper center1right end2, left end3and the lower center4of the air outlet, and confirm that no gap is left between the front cabinet and the rear plate.
• If cooling (dry) operation is made without pushing the air outlet, dew can be deposited on the front cabinet surface. In addition a gap between the front cabinet and the rear plate will become wider, spoiling the appearance.
Push Push
3
1
Push
2
Screw
Screw
Fig. 8-4-9
Connecting cable
4
Push
Fig. 8-4-11
– 29 –
8-4-4. Piping and Drain Hose Installation
)
Indoor unit
Connecting
cable Installation plate
Auxiliary pipes
To connect pipe after installation of unit (figure)
<In case of rightward piping>
• After scribing slits of the front panel and the rear panel by a knife or a marking-off pin, cut them by a pair of nippers or the like.
Slit (front panel)
Slit (rear panel
Fig. 8-4-12
<In case of downward piping>
• After scribing the slit of the front panel and slit in the lower part of the rear panel by a knife or a marking-off pin, cut them by a pair of nippers or the like.
(To the forefront of flare)
196mm
Side of liquid flow
96mm
Side of gas flow
Outward form of indoor unit
R 30mm (Use polisin or the like for bending pipe.)
43mm
80˚
Use the handle of screwdriver,etc.
Fig. 8-4-14
NOTE :
If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the connecting pipe to auxiliary pipes and wrap the facing tape around them.
Slit (front panel)
Slit (rear panel)
Fig. 8-4-13
<Left-hand connection with piping>
Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. When bending the connecting pipe, make sure to use spring bender so as not to crush the pipe.
Bend the connection pipe within a radius of 30 mm.
CAUTION
• Bind the auxiliary pipes (two) and connecting cable with f acing tape tightly . In case of leftward piping and rear-leftward piping, bind the auxiliary pipes (two) only with facing tape.
• Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.
• Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound on the connecting pipe to avoid double-taping at the joint, moreover, seal the joint with the vinyl tape, etc.
• Since dewing results in a machine trouble, make sure to insulate both the connecting pipes. (Use polyethylene foam as insulating material.)
• When bending a pipe, carefully do it not to crush it.
– 30 –
8-4-5. Indoor Unit Installation
(1) Pass the pipe through the hole in the wall, and
hook the indoor unit on the installation plate at the upper hooks.
(2) Swing the indoor unit to right and left to confirm
that it is firmly hooked up on the installation plate.
(3) While pressing the indoor unit onto the wall by the
lower part, hook it up on the installation plate by the lower part. Pull the indoor unit toward you by the lower part to confirm that it is firmly hooked up on the installation plate.
(1)
(2)
Hook
• For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up by the specified parts.
Hook here
Installation
1
plate
Fig. 8-4-15
Push
8-4-6. Drainage
(1) Run the drain hose sloping downwards.
NOTE :
• Hole should be made at a slight downwrd slant to the outdoor side.
Do not rise the drain hose.
50 mm or more
Do not put the drain hose end into water.
Fig. 8-4-17
(2) Put water in the drain pan and make sure that the
water is drained outdoors.
(3) When connecting extension drain hose, insulate
the connecting part of extension drain hose with
shield pipe.
5
5
Shield pipe
Do not form the drain hose into the wared shape.
Do not put the drain hose end in the drainage ditch.
Push Push
Fig. 8-4-16
Drain hose
Inside the room
Extension drain hose
Fig. 8-4-18
CAUTION
Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in damage to property.
This air conditioner has the structure designed to drain water collected from dew, which forms on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other parts at a height above the drain guide.
Wall
Drain guide
– 31 –
Space for pipes
Fig. 8-4-19
8-5. Outdoor Unit
t Installation place
• A place which provides the spaces around the outdoor unit as shown in the diagram in page 23.
• A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration.
• A place where the operation noise and discharged air do not disturb your neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an elevated position, be sure to secure its feet.
• An allowable length of the connecting pipe is up to 10 m.
• An allowable head level is up to 5 m.
• A place where the drain water does not raise any problem.
CAUTION
Installation in the following places may result in trouble. Do not install the unit in such places.
• A place full of machine oil.
• A saline place such as coast.
• A place full of sulfide gas.
• A place where high-frequency waves are likely to be generated as from radio equipment, welders, and medical equipment.
CAUTION
(1) Install the outdoor unit without anything
blodking the air discharging.
(2) When the outdoor unit is installed in a place
exposed always to a strong wind like a coast or on a high story of a building, secure the normal fan operation using a duct or a wind shield.
(3) Specially in windy area, install the unit to
prevent the admission of wind.
Strong wind
Fig. 8-5-1
– 32 –
8-5-1. Refrigerant Piping Connection
(
)
<Flaring>
(1) Cut the pipe with a pipe cutter.
8-5-2. Vacuum Pumping
AIR PURGE Evacuate the air in the connecting pipes and in the indoor unit using vacuum pump.
90˚
Obliquity Roughness Warp
Fig. 8-5-2
(2) Insert a flare nut into the pipe, and flare the pipe.
A (mm)
Imperial
1.3 mm
1.6 mm
Rigid
0.7 mm
1.0 mm
Die Pipe
A
Outer diam.
6.35 mm
9.52 mm
Fig. 8-5-3
<Tightening connection>
Align the centers of the connecting pipes and tighten the flare nut as far as possible with y our fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.
Do not use the refrigerant in the outdoor unit. For details, see the manual of vacuum pump.
<Use of vacuum pump>
(1) Connect the charge hose (A) from the manifold
valve to the charge inlet of the gas side packed valve.
(2) Connect the charge hose (B) to the port of vacuum
pump.
(3) Open fully the low pressure side handle of the
manifold valve. (4) Operate the vacuum pump. (5) Close the low pressure side handle of manifold
valve after vacuumizing and stop the vacuum
pump.
Continue vacuumizing more than 15 minutes and check the pressure gauge indicates –76 cmHg.
CAUTION
• Do not apply excess torque. Otherwise, the nut may crack depending on the installation conditions.
(Unit : N·m)
Outer diam.
6.35 mm
9.52 mm
Half union or packed valve
Externally threaded side
Use a wrench to secure.
Tightening torque
15.7 (1.6 kgf·m)
29.4 (3.0 kgf·m)
Fig. 8-5-4
Use a torque wrench to tighten.
Additional
tightening torque
19.6 (2.0 kgf·m)
34.3 (3.5 kgf·m)
Flare nut
Internally threaded side
(6) Open the stems of packed valves A and B all the
way.
(7) Securely tighten the stem cap to each of the
packed valve stems.
Indoor unit
Pressure gage
Low pressure side handle
Charge hose (A)
Outdoor unit
Gas (ø9.52)
C
A
Manifold valve
Service port
High pressure side handle
Lo Hi
Charge hose (B)
VP
D
B
Liquid
ø6.35
Fig. 8-5-5
Packed valve
– 33 –
CAUTION
• KEEP IMPORTANT 4 POINTS FOR INSTAL­LATION (PIPING WORK)
(1) Take away dust and moisture (Inside of the
connecting pipes.) (2) Tight connection (between pipes and unit) (3) Evacuate the air in the connecting pipes using
VACUUM PUMP. (4) Check gas leak (connected points)
<Packed Valve Handling Precautions>
• Open the valve stem all the way out; so not try to open it beyond the stopper .
• Securely tighten the valve stem cap with the wrench or like.
• V alve stem cap tightening torque is as follows; Gas pipes side (ø9.52) : 29.4 N•m (3.0 kgf•m) Liquid pipe side (ø6.35) : 16.2 N•m (1.7 kgf•m)
<A5 mm hexagon wrench is required.>
Flare nut
8-5-3. Wiring Connection
(1) Remove the electric parts cover from the outdoor
unit. (1 screw)
(2) Connect the connecting cable to the terminals as
identified with their respective matched numbers on the terminal block of indoor and outdoor units.
(Strip the sheath of connecting cable with following stripping length to and insert into the terminal block.)
(3) When connecting the connecting cable to outdoor
unit terminal, make a loop as shown in the installation diagram of indoor and outdoor unit, to prevent water coming in the outdoor unit.
(4) Insulate the unused cords (conductors) with water
coming in the outdoor unit. Process them so that they do not touch any electrical or metal parts.
<Stripping length of connecting cable>
Terminal block
70mm
10mm
4 3 2 1
Earth line
10mm
60mm
Terminal screw
Connecting cable
1234
Screw
Cord clamp
Valve body
Valve stem
Stopper
Valve stem cap
Fig. 8-5-6
5mm
Fig. 8-5-7
CAUTION
• Wrong wiring connections may cause some electrical parts to burn out.
• Be sure to comply with local code on running the wire from the indoor unit to outdoor unit.
(size of wire and wiring method etc.)
• Every wire must be connected firmly.
NOTE :
• Wipe type : More than H05 RN-F
– 34 –
8-6. Others
8-6-1. Gas Leak Test
Flare nut connections (Indoor unit)
Flare nut connections (indoor unit)
8-6-3. Auto Restart Setting
This product is designed so that, after a power failure, it can restart automatically in the same operating mode as before the power failure.
C
D
Electric parts cover
Flare nut connections (Outdoor unit)
B
Valve stem cap connection
Valve stem cap connection
A
Service cap connection
Fig. 8-6-1
• Check the flare nut connections, valve stem cap connections and service cap connections for gas leak with a leak detector or soap water.
Information
The product was shipped with Auto Restart function in the off position. Turn it on as required.
<How to set the Auto Restart>
• Press and hold down the TEMPORARY button for about 3 seconds. After 3 seconds, the electronic beeper makes three short beeps to tell you the Auto Restart has been selected.
• To cancel the Auto Restart, follow the steps described in the section Auto Restart Function of the User's Manual.
8-6-2. Test Operation
To switch the TEST RUN (COOL) mode, press TEMPORARY button f or 10 sec. (The beeper will make a short beep.)
TEMPORARY
Fig. 8-6-2
– 35 –
9. TROUBLESHOOTING CHART
TROUBLESHOOTING PROCEDURES :
• Following details of “What to be pre-checked first”, make sure of the basic items.
• When there is no trouble corresponding to above, check in detail the faulty parts following “How to judge faulty parts by symptoms” later.
9-1. What to be Prechecked First
9-1-1. Power Supply Voltage
The line voltage must be A C 220/230/240V. If the line voltage is not within this range, this air conditioner may not work normally.
9-1-2. Incorrect Cable Connection between
Indoor and Outdoor Units
The indoor unit is connected to the outdoor unit with 5 cables. Make certain that the indoor and outdoor units have been connected properly , with terminals assigned the same numbers wired to each other. If the connec­tors are not connected as specified, the outdoor unit will not operate normally, or OPERATION lamp and TIMER lamp will flash (5Hz).
– 36 –
9-1-3. Misleading but Good Operations
(Program Controlled Operation)
The microcomputer performs the operations listed in Table 9-1-1 to control the air conditioner . If a claim is made on the operation, check whether it corresponds
Table 9-1-1
to the contents in the Table 9-1-1. If it does, it is an indispensable operation for the control and mainte­nance of the air conditioner: it is not a failure of the unit.
No.
1
2
3
4
5
6
Operation of air-conditioner
When the power plug or the power cord of the indoor unit is inserted, the OPERATION lamp on the setting indication part flashes.
Fan speed remains unchanged in the dry mode.
Room temperature is in the range under which the compressor is turned off, but the compressor will not stop.
The compressor will not switch on or off even when the thermo control is operated in the dry operation.
The PRE-DEF. lamp comes on when the heating operation is started.
The outdoor fan stops once in the while during the heating operation.
Description
The OPERATION lamp flashes, indicating that power is turned on. If this happens , push the START/ST OP button once to cause the lamp to stop flashing. A power outage also causes the lamp to flash.
Fan speed is automatically controlled in the dry mode.
The compressor will not stop while the compressor on hold timer (3-minutes timer) is actuated.
In the dry mode, the compressor goes on and off at regular intervals, independent of the thermo control.
The PRE-DEF. lamp comes on during defrost operation and when the indoor heat exchanger temperature is low when the heating operation is started. At this time, the indoor fan is stopped to prevent cold air from drifting into the room.
• When the indoor heat exchanger temperature is high, the outdoor fan may be stopped by the high-temperature limit control operation.
• When the compressor current is large, the outdoor fan may be stopped by the current limit control operation.
7
Compressor does not work though room temperature is in the range of turning the compressor on.
8
During automatic operation, the operation mode changes.
9
During automatic operation mode, the fan only operation continues.
10
When the power is turned on, the operation starts automatically .
Compressor does not work while the compressor restart delay (3-min.) timer is active. The same is true after power is turned on, as the time is still active.
After selection of the cooling and heating operation, the operation mode is selected again when the compressor off mode continues for 15 min. according to the room temperature.
When the room temperature is within setting temperature ± 1°C the fan only mode is selected.
When the auto restart controlling is selected, the operation is performed automatically in the previous operation mode after the power supply has been turned on.
– 37 –
9-2. Primary Judgement of Trouble
Sources
9-2-1. Role of Indoor Unit Controller
The indoor unit controller receives the operation com­mands from the remote control and assumes the fol­lowing functions.
• Measurement of the draft air temperature of the indoor heat exchanger by using the thermo sen­so r (TA).
• Louver motor control
• Control of the indoor fan motor operation
• Control of the LED display
• Control of the outdoor unit compressor, 4WAY­V A LVE and the outdoor fan motor.
Table 9-2-1
9-2-2. Display of Abnormalities and
Judgement of the Abnormal Spots
The indoor unit of this machine observes the opera­tion condition of the air conditioner and displays the contents of the self-diagnosis as block displays on the display panel of the indoor unit.
Block display
OPERATION display flashing (1 Hz)
A
OPERATION display flashing (5 Hz)
B
OPERATION display flashing (5 Hz)
C
OPERATION display flashing (5 Hz)
D
OPERATION display flashing (5 Hz)
E
OPERATION and TIMER display flashing
F
(5 Hz) OPERATION, TIMER and PRE-DEF. display
G
flashing (5 Hz)
OPERATION, TIMER and PRE-DEF. display
H
flashing (5 Hz)
(1) Judgement from defective operation or abnormal operation
Table 9-2-2
Power failure (when power is ON) Thermo sensor (TA) short/break Heat exchanger sensor (TC) short/break Indoor fan lock, abnormality of indoor fan Indoor PC board failure Wrong wiring of connecting cable
Thermal fuse is blown
• Gas shortage, other refrigerant cycle trouble
• Heat exchanger sensor open/break/short
• Overload relay trouble Compressor trouble
Block display
Symptom
No reaction on remote control operation
The outdoor fan does not rotate
Check
Turn off the power once, turn it on again and try to operate the remote control again.
The compressor operates.
The compressor does not operate.
– 38 –
Remote control is not possible.
Remote control is possible.
Primary judgement
The indoor part (including the remote control) is defective.
OK.
The outdoor part is defective. (outdoor fan motor)
The inside part is defective.

(2) Self-diagnosis with remote control

(
)
With the indoor unit control, self-diagnosis of pro­tective circuit action can be done by turning the remote control operation into service mode, oper­ating the remote control, observing the remote control indicators and checking whether TIMER lamp flashes (5 Hz).
2) Selecting ordinary mode
Push the all clear button (ACL) on the rear bot­tom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the operation mode display, wind volume dis­play, clock display and setting temperature dis­play are turned on and “ : ” of the clock display is flashing.
Note :
• To perform this self-diagnosis, the remote control with the service code of 43069666 is required.
<How to select remote control operation mode>
1) Selecting service mode
Push the switch button provided on rear bot­tom of the wireless remote control with a tip of pencil for more than 3 seconds. Make sure the setting temperature is displayed on
“ ”
the display and other display is turned off.
<Cautions when doing service>
1) After completion of servicing, always push the all clear (ACL) button to return the operation mode to the normal mode.
2) After completion of servicing by the check code, turn off the power once and then turn on the power to reset memorized contents of the microcomputer to the initial status.
All clear button
Switch for selecting service mode
ACL CLOCK
Rear bottom of remote control
Fig. 9-2-1
– 39 –
ACL
CLOCK
Rear bottom cover
<Self-diagnosis by check codes>
1) The self-diagnosis by the check codes is con­ducted under the block displays of item B-H in Table 9-2-1.
2) Remote control key operation under the ser­vice mode is conducted by ON/OFF or TEMP. The remote control display by each key op­eration is varied as shown below. Two digit number is displayed in a hexadecimal num­ber.
3) The self-diagnosis by the check codes is con­ducted with procedures shown below .
a) Enter the service mode and make sure the
off timer display of the remote control shows .
“ ”
b) Operate the “ON/OFF” key and make sure
the timer lamp on the display section is flashing (5 Hz).
Table 9-2-3
c) At the same time, also make sure the op-
eration lamp is also flashing. This shows that the protection circuit on the indoor PC board is working.
d) Operate the TEMP. key and mak e sure
the remote control display shows and flashing of the operation lamp. If the op­eration lamp is flashing, it shows the pro­tection circuits for connecting cable is work­ing or thermal fuse is blown.
e) In the same way, operate the TEMP.
key so that the display is increased one by one to continue checks by the self-di­agnosis as shown in the next table. From
“ ”
up to check operations of
protection circuits for each block, and
“ ”
to check operations of the
typical protection circuits.
“ ”
“ ”
“ ”
Operating key
ON/OFF
TEMP. (Up)
TEMP. (Down)
“AUTO ” LOUVER
“SET” LOUVER
Indication after operation
1 is added to data before operation. (Example)
1 is subtracted from data before operation. (Example)
10 is subtracted from data before operation. (Example)
Data before operation is directly transferred. (Example)
– 40 –
Table 9-2-4
Block level
Check
code
Block
Indoor PC board
Check
code
Diagnosis function
Symptom
Thermo sensor short/break.
Heat exchanger sensor short/break.
Indoor fan lock, abnormality of indoor fan.
Air
Conditioner
status
Continued operation
Continued operation
All off
Condition
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
Judgment and action
1. Check thermo sensor.
2. If it is OK, check PC board.
1. Check heat exchanger sensor.
2. If it is OK, check PC board.
1. Disconnect the power plug from AC outlet, and pull out the connector (CN10) for the motor, then connect the plug of AC power cord again and turn the power on.
2. Check the voltage between pin 1 and 2 of the connector (CN10).
3. If the output voltage is 35V, PC board is OK, check motor.
Cable connection/ Thermal fuse Refrigerant system
Abnormality of other indoor unit PC board.
1) Wrong wiring or disconnection of connective cable.
2) Thermal fuse cut off.
1) Gas shortage. (gas leak)
2) Other refrigerant cycle trouble.
3) Heat exchanger sensor off/break/ short.
4) Overload relay or thermostat for compressor break.
All off
All off
All off
Indicated when detected abnormal
Indicated when detected abnormal
Indicated when detected abnormal
Replace PC board.
1. Check connective cable correct if wiring is wrong.
2. Check thermal fuse and Terminal blocks.
3. If it is OK, check PC board.
1. Check gas quantity. (check gas leakage)
2. If it is OK, check heat exchanger sensor.
3. If heat exchenger sensor is OK. check overload relay and thermostat for compressor.
4. If overload relay and themostat for compressor are OK, check refrigerant cycle.
5. If refrigerant cycle is OK, check PC board.
Compressor break down.
Contents detected by the check codes “ ” to “ ” are stored in memory of the microcomputer even if the power supply is turned off. Therefore, contents of operations in the past are all displayed.
All off
Indicated when detected abnormal
1. Check compressor.
2. If it is OK, check PC board.
– 41 –
9-3. Troubleshooting Flowcharts
9-3-1. Power can not be Turned on (No Operation at All)
<Preliminary checks>
(1) Is the supply voltage normal? (2) Is the connection to the AC output OK.?
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
NO
Does the OPERATION
lamp flash?
YES
Operation
Check Items
Main cause
Countermeasure
Symptom
Does the fuse
Does the thermal
(Under PF. Terminal)
Is the indication voltage
NO
(DC12V or 5V) of main
PC board correct?
Is the voltage
across C02 measured
DC310V~340V?
YES
Does the power turn
on by pushing the
[START/STOP] button
of the remote control?
YES
(F01) blow?
NO
fuse blow?
NO
YES
Refer to the paragraph
NO
"Pre-check", or defective circuit before power PC board block.
YES
YES
(No problem)
Parts (R21, R109, SG01,
C15, C01, DB01, C02,
IC01, T01) are defective.
Wrong wiring of
AC cord or connecting
cable is defective.
Does the transmission
indicator of remote
control flash normally and
transmit certainly?
YES
PC board
is defective.
NONO
Remote control
is defective.
Replace the remote control.
Replace the thermal fuse set. Check connection.
Replace the main PC board.
Is the secondary
voltage of SW trans-
former (T01) measured
DC35V, DC12V,
and DC7V ?
YES
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
*
Shut off the power supply once, and turn
NO
it on again after dis­connecting the motor connector CN10
Is the secondary
voltage of SW
transformer measured
.
*
DC35V, DC12V,
and DC7V?
YES
NO
SW transformer
(T01) or IC (IC01)
for power supply
is defective.
Replace the main PC board.
Motor is defective.
damage of the motor.
– 42 –
9-3-2. Power can not be Turned on after Replacing Indoor PC Board
<Checking Procedure>
Connect the AC plug.
Does the OPERATION
lamp flash?
YES
Black
1 2 3 4
Indoor terminal block
NO
White
Blue
N L
Power terminal block
9-3-3. Outdoor Unit does not Operate
Is it wired as shown
in Figure below?
YES
Brown
C02
RY01
PC board
NO
RY02
Return the wiring of the power relay is returned to the normal procedure.
To the paragraph of “No Power turns on”.
Double winding
T02
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp flash?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is AC220/230/240V
supplied between terminal block
1 - 2 , 3 - 2
Is cable connection
between indoor and outdoor
units correct?
Check items as following procedure in 9-3-4, 9-3-5, 9-3-6.
1, 4 - 2 ?
*
YES
YES
1 Only Heating mode
*
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01, RY02, RY03, RY04) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Replace the PC board.
– 43 –
9-3-4. Only Compressor does not Operate
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp flash?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the terminal
( 1 - 2 ) 220/230/240 VAC?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 1 - 2 ) 220/230/240 VAC?
YES
Are all the cords for compressor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY01, RY02) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Re-wire or replace the defective cords.
Replace the PC board.
Is the compressor motor winding normal?
(Check the winding resistor.)
YES
Is the capacitor for compressor normal?
YES
Is the overload relay normal?
YES
Does the compressor start?
YES
Compressor starts but
it stops after a while?
YES
Is the gas quantity normal?
(Check the pressure)
YES
Compressor is defective
NO
NO
NO
NO
NO
Compressor is defective.
Capacitor is defective.
Overload relay is defective.
Compressor is defective.
Gas shortage (Gas leakage)
– 44 –
9-3-5. Only Outdoor Fan does not Operate
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp flash?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the terminal
( 2 - 4 ) 220/230/240 VAC?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 4 ) 220/230/240 VAC?
YES
Are all the cords for outdoor
fan motor normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY02, RY03) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Correct the wire or replace the defective cords.
Replace the PC board.
Is the outdoor fan motor winding normal?
(Check the winding resistance)
YES
Is the capacitor for compressor normal?
YES
Outdoor fan motor is defective.
NO
NO
Outdoor fan motor is defective.
Capacitor for outdoor fan motor is defective.
– 45 –
9-3-6. Only 4-Way Valve does not Operate (During Heating Operation)
Shut off the power supply from AC outlet once and turn it on after 5 seconds.
Does the OPERATION lamp flash?
YES
Does the power turn on by
pushing the [START/STOP] button
of the remote control?
YES
Is the voltage across the terminal
( 2 - 3 ) 220/230/240 VAC?
YES
Is cable connection between indoor
and outdoor units correct?
YES
Is the voltage across the terminal
( 2 - 3 ) 220/230/240 VAC?
YES
Is the wiring of solenoid coil
for 4-way valve normal?
YES
NO
NO
NO
NO
NO
NO
See "Power can not be turned on".
See "Power can not be turned on".
Relays (RY02, RY04) or IC31 or IC30 is failure.
Correct cabling between indoor and outdoor units.
Cables between indoor and outdoor units are defective.
Solenoid coil is defective.
Replace the PC board.
4-way valve is defective.
– 46 –
9-3-7. Only the Indoor Fan does not Operate
< Preliminary checks >
Does it neither work in COOL or FAN ONLY operation?
< Check procedure >
Shut off the power supply once.
Turn the power supply.
Does the fan
stop in no operating
status?
YES
Start the operation with low fan setting in cool operation.
Does the fan rotate?
YES
Change the setting of cooling to high fan.
Does the fan speed
become higher?
YES
NO
NO
Control PC board is defective.
Is the voltage
NO
measured DC35V
between
and
Shut off the power supply.
Turn on the power supply.
Operation stops
(DC+5V-0V) output between
(blue lead wire) and
lead wire) of the motor connector
(CN10) when rotating the cross
flow fan by hand in no operating
status ? (2 pulses/one turn)
1 (red lead wire, +)
2 (black lead wire, –)
of the motor connector
(CN10) ?
YES
Does the cross
flow fan rotate
normally?
YES
Is the rotation signal
YES
NO
2 (black
NO
Repair the bearing of the drain fan.
4
Replace the PC board.
Shut off the power supply, and turn it on after disconnecting the motor connector (CN10) the PC board.
Is the voltage of
DC35V measured
between 1 (red lead wire, +)
and 2 (black lead wire, –) of
the motor connector
(CN10) ?
NO
YES
*
from
NO
Replace the PC board.
Normal
Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
*
Replace the control PC board.
Replace the fan motor.
damage of the motor.
– 47 –
9-4. How to Check the Remote Control (Including the Indoor PC Board)
There is no beep from the indoor unit.
Push the START/STOP button.
The operation lamp of the air conditioner main unit does not light.
Is there direct sunlight on the receptor of the air conditioner?
YES
NO
Is there any
thyristor
fluorescent light
near by?
YES
NO
Does the transmission
YES
NO
Is operation
possible when setting
the temporary switch of the
air conditioner main unit to
"TEST RUN" or
"TEMPORARY AUTO"?
NO
possible when the
transmitter is moved
nearer to the infrared
signal receiver of the
indicator flash?
Is operation
air conditioner?
YES
Battery life
NO
Short-circuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil. (wait about 10 seconds)
Push the START/ STOP button
Does the
transmission
indicator light?
YES
NO
Avoid direct sunlight.
Keep the air
conditioner away
from thyristor
fluorescent light.
YES
Can any signal tone
be heard in a transistor
radio when transmitting
within 5cm distance
from the radio?
YES
PC Board is failure.
Replace
PC board.
After battery replacement,
Note:
shortcircuit the metal terminal at the side of the battery compartment (all-clear terminal) with a pencil.
– 48 –
NO
Replace the batteries
NO
Normal
Is there any
beep and
operation?
YES
Remote control
is failure.
Replace remote control.
9-4-1. How to Check the PC Board
(1) Operating precautions
1) When removing the front panel or the PC board, be sure to shut off the power supply.
2) When removing the PC board, hold the edge of the PC board and do not apply force to the parts.
3) When connecting or disconnecting the connec­tors on the PC board, hold the whole housing. Do not pull at the lead wire.
(2) Inspection procedures
1) When a PC board is judged to be defective, check for disconnection, burning, or discolora­tion of the copper foil pattern or this PC board.
2) The PC board consists of the following 2 parts
a. Main PC board part:
Power relay, indoor fan motor drive circuit and control circuit, C.P.U. and peripheral cir­cuits, buzzer drive circuit and buzzer.
b. Infrared rays receive and indication
parts:
Infrared rays receive unit and LED.
– 49 –
(3) Checking procedure
Table 9-4-1
No.
1
Shut off the power supply and remove the PC board assembly from the electronic parts base.
Remove the connecting cable from the terminal block.
2
Remove the connector for the motor, and turn the power on.
If the OPERATION lamp flashes (0.5 sec. :ON, 0.5 sec. :OFF) when the power turning on, the checking points described as 1-5 of right column are not necessary to perform.
3
Make the operation status by pushing once the START/STOP button, except the status of [FAN ONLY], [ON TIMER].
4
Start the operation with the system which the time of the restart delay timer is shortened.
5
Make the operation status by pressing once the START/STOP button.
1.The time of the restart delay timer is shortened.
2.Cool operation
3.Air volume [AUTO]
4. Make the setting temperature lower enough than room temperature.
5.Continuous operation.
6
The status of No. 5 is continued, and make the following condition.
1.Heat operation
2.Make the setting temperature higher enough than room temperature.
7
Turn the power on after connecting the motor connector. Start the operation with the following condition.
1.Operation [Cooling]
2.Airflow [High fan]
3.Continuous operation
Procedure
Check Point (Symptom)
1.Is the fuse blown?
Voltage check
1.Between TP1 and TP2 (220/230/240V AC)
2.Between TP2 and pin 1 of CN04 (220/230/240V AC)
3.Between TP2 and pin 3 of CN04 (220/230/240V AC)
4.Between + and - of C02 (310 ~ 340V DC)
5.Between 35V and GND
6.Between 12V and GND
7.Between 5 V and GND
Voltage check
1. Voltage of relay coil. (DC 12V) Between pin 10 of IC31 and GND Between pin 11 of IC31 and GND
2. Between No. 1 and 2 of connecting cable terminal block.
(220/230/240V AC)
1.All indicators light for 3 sec..
2. Indicators do not indicate normally after approximate 3 sec..
1.Compressor does not operate.
2. OPERATION lamp flashes.
1.Compressor does not operate.
2. OPERATION lamp flashes.
1.The voltage of DC 35V is not measured between the red and black of the motor terminals.
2. Motor does not rotate. (The key operation is accepted.)
3. The motor rotates, but it vibrates too much.
Causes
1.* Application of shock voltage. * Overcurrent by short-circuit of the
parts.
1.* AC power cord is defective. * Poor contact of the terminal plate. * Miss wiring of the power relay.
2.Fuse is defective.
3.Operation of the thermal fuse.
4.* Capacitor (C01, C15) is defective. * Line filter (L01) is defective. * Resistor (R01) is defective. * Diode (DB01) is defective.
5.IC01, IC02, T01 are defective.
6.IC01, IC02, T01, F03 are defective.
7.IC01, IC02, T01, F02, Q29, IC03 are defective.
1.Breaking wire of the relay coil, defective relay driver. (IC31)
2.Poor contact of relay.
Defective indicator, or poor
housing assembly. (CN13)
1.The temperature of the indoor heat exchanger is abnomally lower.
2.Poor contact of the heat exchanger sensor. (The connector is disconnected.) (CN01)
3.Heat exchanger sensor, main PC board are defective. (Refer to Table 9-4-2 for the judgment of defective resistance values.)
4.Main PC board is defective.
1.The temperature of the heat exchanger is abnormally high.
2.The heat exchanger sensor connector has short-circuit. (CN01)
3.The heat exchanger sensor is defective. (Refer to Table 9-4-2 for the judgment of defective resistance values.)
4.PC board is defective.
1.Indoor fan motor is defective. (Protecting operation on the PC board.)
2. Poor contact of the motor connector.
3.PC board is defective.
– 50 –
9-4-2. PC Board Layout
Top View
Bottom View
– 51 –
Table 9-4-2 Approximate value of the sensor (thermistor) resistance (TA, TC)
Timer short diode
Wireless remote control
(= kΩ)
Temperature
Sensor
Themo Sensor
0°C
35.8
9-4-3. How to Reduce the Operation Time of
the Anti-Restart Timer
• Attach the diode (1S1555 or equivalent) to the rivet inside the unit through holes on the rear of the wireless remote control unit.
• Push the START/STOP button to start operation with the diode attached.
10°C
20.7
20°C
12.6
25°C
10.0
30°C
7.92
Fig. 9-4-1
– 52 –
10. PART REPLACEMENT
10-1. Indoor Unit (RAS-10SKH-E, RAS-10SKHX)
No.
Part name
Front panel
RemarksProcedure
1) After stopping the operation of the air conditioner, be sure to turn off the circuit breaker or disconnect the power plug from the AC wall socket.
2) Open the screw caps and remove the two screws fixing the front panel.
3) Close the screw caps as they were.
4) Open the horizontal louver right below by your finger.
5) Open the lower side of front panel until it touches the horizontal louver, and remove it from the indoor unit by turning it.
<To assemble the front panel>
1) Fix the two screws to secure the front panel.
2) Close the screw caps as they were.
3) Press four places where are the center, right end, left end and lower portions of the air outlet.
4) Check the gap between the front panel and the main unit.
If cooling or drying operation is performed without pressing the center of the air outlet, the surface of the front panel may be covered with frost and have a waterdrop.
Electrical part
assembly
Drain-pan
assembly
1) Perform the process above.
2) Remove the screw securing the shield metal plate.
3) Remove the electrical part cover by pressing the nail located on upper portion of the electr ical par t cover.
4) Remove the drain guide.
5) Remove the screw securing to the end plate of the heat exchanger.
6) Remove the connector (5p) for the fan motor and the connector (6p) for the louver motor from the microcomputer assembly.
7) After unhooking the electrical part base by pressing the fixing nail located on its lower portion, draw the electrical part base out toward you to remove it from the main unit.
8) Pull the TC sensor out from the holder of the heat exchanger.
9) Dress the connecting cable securely as shown in the right illustration.
(Improper dressing will cause water leakage.)
1) Perform the process above.
2) Remove the drain-pan by pressing the four hooks downwards.
(Keep it with the drain hose.)
– 53 –
Part name
Procedure
RemarksNo.
Horizontal grille
Note:
The horizontal grille can not be removed without removing the louver motor.
Heat exchanger
Cross flow fan
1) Perform the process .
2) Remove the screw fixing the louver motor, and remove the louver motor.
3) Remove the shaft of the horizontal grille from the drain-pan.
1) Perform the process .
2) Remove the pipe holder from the rear side of main unit by removing the screw.
3) Unhook the hooks fixing the left side of the heat exchanger and remove the screw fixing it, then remove the right side of the end plate from the rib fixing the main unit by sliding the heat exchanger slightly to the right side.
1) Perform the process .
2) Loosen the set screw of the cross flow fan.
3) Remove the screw fixing the shaft bearing base.
4) Lift slightly up the left side of the heat exchanger, and pull the shaft bearing base out left downwards.
Shaft bearing
Fan motor
When assembling it, fix it with the set screw on the position where the gap between the rear plate surface and the left end surface of the cross flow fan is 6 ~ 7mm.
1) Perform the process above.
2) Remove the shaft bearing from the shaft bearing base. <Caution for assembling>
• If a part of the shaft bearing is protruded from the housing, assemble it after pushing its portion into the correct position in the housing.
1) Perform the process above.
2) Perform the process
3) Remove the left and right motor bands.
4) Remove the fan motor after pulling the cross flow fan out sliding it left and right.
-2) above.
– 54 –
10-2. Microcomputer (RAS-10SKH-E, RAS-10SKHX)
No.
Part name
Common procedure
Thermal fuse replacement
Procedure
1) Turn the power supply off to stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove the front panel.
• Remove the two fixing screws. (φ4 x 14 )
3) Remove the electrical part base.
1) Perform the process above.
2) Remove terminal cover (Up), (Down).
3) Disconnect the terminal blocks connected with the connecting cable, and the power cord from base E­parts by removing the screws.
4) Remove the thermal fuse (77°C) from base E-parts.
Remarks
Replace the thermal fuse, terminal block, power cord, microcomputer ass’y and the power supply PC board ass’y.
– 55 –
10-3. Outdoor Unit (RAS-10SAH-E, RAS-10SAHX)
No.
Common
procedure
Capacitor for
compressor
Capacitor for fan
motor
Part name
Procedure
1) Stop the operation of air-conditioner, and disconnect the power cord from the AC supply.
2) Remove E-parts cover. (1- ST1T ø4 x 10 )
3) Remove the cord clamp (2- ST2T ø4 x 12 ) and remove the connecting cable.
4) Remove the front cabinet. (7- ST1T ø4 x 10 with nylon washer)
• Pull the front lower portion toward you, and remove it pulling out upward.
1) Remove the fixing screw securing the capacitor band. (1- ST2T ø4 x 8 )
2) Remove the cable connected to the terminal.
1) Remove the fixing screw. (1- ST2T ø4 x 8 )
2) Remove the cable connected to the terminal.
Remarks
Refer to [Electrical parts list and location] in page 61.
Same as above.
Overload relay
1) Perform the process above.
2) Remove terminal cover of compressor.
3) Remove OL holder and pull OL relay up.
4) Remove Fustons of leads.
– 56 –
11. CAUTIONS ON REPLACEMENT OF PC BOARD ASSEMBLY
RY01
C02
RY02
Brown
N L
Power terminal block
T02
PC board
Blue
White
Black
Double winding
1 2 3 4
Indoor terminal block
1. Set the switch (SW03) provided on the PC board as follows.
ON
123456
OFF
2. Check the black lead wire is double wound around the current trans. (CT. T02)
1 2 3
OFF 4 5 6
ON
– 57 –
12-1. Indoor Unit (1)
12. EXPLODED VIEWS AND PARTS LIST
420
415
403
407
414
419
410
411
416
417
Location Part
No. No.
403 43T60002 Base, T erminal
3P, AC 300V, 20A
407 43T69004 Sensor, Heat Exchanger
10k, 25°C
410 43T69005 Sensor, Thermostat
10k, 25°C 41 1 43T60004 Fuse, Temperature 77°C 414 43T69007 PC Board, WRS-LED
MCC-635
Description
403
– 58 –
Location Part
No. No.
415 43T69008 PC Board A’ssy MCC-713 416 43T61001 Base, E-Parts
ABS, Black, UL94-5V
417 43T62006 Base, Shield
SGCC-Z08-LUB
419 43T60001 Base, T erminal
2P, AC 300V, 20A
420 43T60005 Housing 4P
Description
Indoor Unit (2)
Location Part
No. No.
401 43T69003 Relay, Power
DI1U, 20A, A C 250V 402 43T58002 Transfor mer, Switching
SWT-34 404 43T60003 Fuse 3.15A, AC 250V 405 43T32001 Resistor 5.6, 5W 406 43T33001 Capacitor, Electrolytic
100MFD, 450V, AUF
Description
– 59 –
Location Part
No. No.
408 43T55004 Varistor 560V 409 43T34001 Filter, Line 0.6A 412 43T30001 IC, Switching MA 2830P-FJ 413 43T31001 Diode, Rectifier
RBV -406, 600V
418 43T58001 Transformer, Current
CT422920S-01
Description
Indoor Unit (3)
201
202
206
203
207
210
214
211
243
216
217
215
221
208
222
234
212
209
228
229
213
239
230
219
220
218
223
224
235
231
225
241
240
233
232
226
227
236
237
205
204
Location Part
No. No.
201 43T00002 Front Panel Assembly 202 43T00003 Suction Grille 203 43T80001 Air Filter (L) 204 43T80002 Air Filter (R) 205 43T80003 Frame Filter 206 43T07004 Screw Cap (L) 207 43T07003 Screw Cap (R) 208 43T08001 LED Panel (10SKH-E) 208 43T08006 LED Panel (10SKHX) 209 43T19004 Accepted Signal Filter 210 43T09003 Horizontal Louver Assembly
for Service 21 1 43T09004 Louver Assembly 212 43T70001 Drain Hose Assembly 213 43T21003 Motor Stepping 214 43T07001 Bushing 215 43T44002 Refrigerantion Cycle
Assembly 216 43T47006 Pipe, Delivery 217 43T47005 Pipe, Suction 218 43T49007 Pipe, Shield 219 43T19003 Holder, Sensor 220 43T49003 Spring 221 43T49005 Plate of EVA-SEAL
Description
242
Location Part
No. No.
222 43T49006 Holder for Plate of EVA-SEAL 223 43T49004 Rubber of Sound Insulation 224 43T79002 Drain Guide 225 43T39002 Motor Band (Left) 226 43T39001 Motor Band (Right) 227 43T21005 Fan Motor 228 43T20007 Fan, Cross Flow 229 43T22002 Bearing 230 43T39003 Base, Bearing 231 43T03001 Rear Plate 232 43T07002 Pipe Holder 233 43T82001 Installation Plate 234 43T85001 Owner’s Manual (10SKH-E) 234 43T85003 Owner’s Manual (10SKHX) 235 43T11001 Pipe Shield 236 43T69002 Remote Control 237 43T63002 Holder, Remote Control 238 43T62001 Cover, E-Part s 239 43T62002 Terminal Cover (Up) 240 43T62005 T e rminal Cover (Down) 241 43T62003 Cord Clamp 242 43T62004 Shield Cover 243 43T60007 Cord Power
238
Description
– 60 –
12-2. Outdoor Unit
19
23
24
16
25
17
6
4
5
12 15
8, 9
3
14
2
13
10, 11
20
21 22
18
7 : CAPILLARY TUBE
1
Location Part
No. No.
1 43T19001 Guard Fan 2 43T20001 Fan, Propeller 3 43005037 Front Cabinet 4 43T43001 Condenser 5 43062194 Cover, E-Parts 6 43005038 Back Cabinet 7 43T47004 Capillary-Tube 1.7 DIA 8 43T46001 Packed Valve, 9.52 9 43T47002 Bonnet, 9.52 DIA 10 43T46002 Packed Valve, 6.35 11 43T47003 Bonnet, 6.35 DIA 12 43T46003 4-Wa y-Valve, VH7100D 13 43T21001 Fan-Motor UE6-21SJ5P
Description
Location Part
No. No.
14 43T47001 Flange, Nut 15 43046255 Solenoid Coil 16 43T19005 Handle 17 43T49001 Rubber-Cushion 18 43T79001 Nipple, Drain 19 43T19002 Stopper , Guard 20 43T63001 Holder , OL-Relay 21 43054403 Relay, Over-Load
J-MRA 99269-9200 22 43T41400 Compressor, PH120T1-4C 23 43055483 MF Capacitor 25µF 400V 24 43T55001 MF Capacitor 1.5µF, 500V 25 43060049 Terminal Block, 5P
Description
– 61 –
Loading...