7-1 Remote control
7-2 Outline of Air Conditioner Control
7-3 Description of Operation Mode
7-4 High-Temperature Limit Control
7-5Low-Temperature Limit Control
7-6Defrost Operation
7-7Current Limit Control
7-8 One-Touch Comfort
7-9 Hi POWER Mode
7-10 QUIET Mode
7-11 ECO Operation
7-12 COMFORT SLEEP mode
7-13 FILTER Check lamp
7-14 Auto Restart Function
7-15 Self-Cleaning function
- 1 -
8.INSTALLATION PROCEDURE
8-1Safety Cautions
8-2Installation Diagram of Indoor and Outdoor Units
8-3Installation
8-4Indoor Unit
8-5Outdoor Unit
8-6How to Set Remote Control Selector Switch
8-7Others
9.TROUBLESHOOTING CHART
9-1Troubleshooting Procedure
9-2Basic Check Items
9-3Primary Judgement
9-4Self-Diagnosis by Remote Control (Check Code)
9-5Troubleshooting Flowcharts
9-6Troubleshooting for Remote Control
FILE NO. SVM-09029
10. PART REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy)
11-2 Indoor Unit
11-3 Outdoor Unit (RAS-10S2AH-ES)
11-4 Outdoor Unit (RAS-10SA-ES)
- 2 -
1. SPECIFICATIONS
FILE NO. SVM-09029
MODEL
ITEMCoolingHeatingCooling
Capacity
Power sourceV220 − 240
Power consumption kW 0.83 0.85 0.79 0.82 0.83 0.85
Power factor%989797969897
RunningIndoorA0.15
current Outdoor A 3.71 3.503.55 3.40 3.71 3.50
Starting currentA18
Moisture removallit/h1.2
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
Indoor (H/M+/M/L+/L)
Outdoor (220-240V) dB474947494647
Name of refrigerantR410A
Rated amount kg 0.78
Gas side size mm ∅ 9.52
Connection typeFlare connection
Liquid side size mm ∅ 6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
kW 2.73 2.73 2.92 2.96 2.73 2.73
Phase 1∅
Hz 50
dB
m10*
m 5
RAS-10SKHP-ES / RAS-10S2AH-ES
220V240V220V240V220V240V
39/37/35/33/31
1
RAS-10SKP-ES / RAS-10SA-ES
0.72
INDOOR UNIT
Height mm 250
Dimensions Width mm 740
Depth mm 195
Net weight kg 8
Evaporator type Finned tube
Indoor fan typeCross flow fan
High fan m3/h 540 560 540
Air volume Medium fan m3/h 460 500 460
Low fan m3/h 390 400 390
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT RAS-10S2AH-ES RAS-10SA-ES
Heightmm550
DimensionsWidthmm780
Depth mm 290
Net weight kg 3130
Condenser typeFinned tube
Outdoor fan typePropeller fan
Airflow volume m3/h203021502030215017401850
Fan motor outputW3020
Compressor
Safety deviceFuse, Overload relay
Louver typeAutomatic louver
Usable outdoor temperature range °C 15 ~ 43 −10 ~ 24 15 ~ 43
ModelPA108X1C-4FZDN
Output W750
RAS-10SKP-ESRAS-10SKHP-ES
− 3 −
Note : 1
·
Capacity is based on the following temperature conditions.
FILE NO. SVM-09029
Temperature
Indoor unit inlet air temperature
Outdoor unit inlet air temperature
Note : 2
*1 No need to change extra refigerant.
Condition
Cooling Heating
(DB) 27°C20°C
(WB)19°C15°C
(DB) 35°C7°C
(WB)24°C6°C
JIS C9612
- 4 -
2-1. Indoor Unit
FILE NO. SVM-09029
2. CONSTRUCTION VIEWS
Front panel
60
8
Knock out system
252
50
Air inlet
Air filter
739
Air outlet
Heat exchanger
195
58
52
8
Knock out system
50
6055
5560
133.41499104.39
56
Wireless remote controller
157
19
125
Drain hose (0.5m)
290
Hanger
606
235
215
235
215
Hanger
45.9
250
90135
Hanger
145
145
Hanger
Installation plate outline
Center line
Remote controller holder
Connecting pipe (0.37m)
(Flare ∅
6.35)
Connecting pipe (0.37m)
(Flare ∅
9.52)
For stud bold (
∅
For stud bold (∅
26.6
45.9164.1
40
38
90135
63
8~
10)
∅
26
6)
– 5 –
2.2. Outdoor Unit
600
50
36
320
306
A detail Drawing (Back leg)
R5.5
R
Ø
15
6 hole
28
86
320
Ø
25 Drain outlet
FAN-GUARD
436
Ø
FILE NO. SVM-09029
A
108 125
306
320
Ø
2
-
Ø
11 x 14
(For 8 -
Ø
Hole
10 anchor bolt)
Ø
6 hole
11x14 hole
Ø
B Detail Drawing (Front leg)
36
50
R
15
COVER-PV
Z
290
550
45 or more
275
320
342
Electrical part cover
Liquid side
(Flare 6.35)
Ø
Gas side
(Flare 9.52)
Ø
5
4
S
ervice port
-Ø 10 anchor bolt)
Ø
Z View
600
Air intlel
9060090
69
129
84
2
-R5- 5x17L UShape (For 8
320
100 or more
Air outlel
400 or more
Installation dimension
− 6 −
600 or more
2- 11x14 Long holes(For 8 - 10 anchor bolt)
Ø
Ø
Ø
3. WIRING DIAGRAM
3-1. RAS-10SKHP-ES / RAS-10S2AH-ES
FILE NO. SVM-09029
BRW
L
BLU
N
GRN & YEL
SINGLE PHASE
220-240V 50/60Hz
BLK
WHI
BLK
P04
CN31
T02
C.T.
1 1
3 3
CN27
CN03
1
1
BLK
2
2
BLK
SENSOR (TA)
SG01
DSA
BLK
THERMO
PINK
1
1
R22
VARISTOR
3
4
RY03
73 C x2
THERMAL FUSE
PINK
2
CN04
2
T6.3A 250VAC
RY01
CN01
2
1
HEAT EXCHANGER
2
1
BLK
BLK
SENSOR (TC)
RY04
CR02
CR01
LOUVER
MOTOR
YEL
5
5
R
1
STO
C01
R2
VARI
MAIN P.C. BOARD
WP-015
INFRARED RAYS RECEIVE
AND INDICATION PARTS
CN25
BLU
WHI
YEL
YEL
YEL
34
2
1
34
2
1
CN07
DC5V
Voltage
Regulator
C02
L01
145 C
1 1
2 2
3 3
4 4
5 5
AC FAN MOTOR
BLU
IC35
CN10
66
321
321
BLU
321
321
C15
BLK
GRY
YEL
BRW
RED
WHI
548
548
BLU
BLU
548
548
R319
5
5
6
7
6
7
WHI
BLU
BLU
6
7
CN14
6
7
Micro
Power
Module
DC12V
+
C63
DB01
3
3
CN11
213
1
213
1
INDOOR
TERMINAL
BLOCK
OUTDOOR
TERMINAL
BLOCK
OVER LOAD RELAY
COMPRESSOR
BLK
BLK
PNK
WHI
BLK
1
(L)2(N)
1
RED
WHI
2
BLU
SOLENOID COIL
RED
RED
CAPACITOR
RED
3
3
BLU
CAPACITOR
FAN
MOTOR
BLU
4
4
WHI BLK
− 7−
INDOOR
OUTDOOR
CHASSIS
3-2. RAS-10SKP-ES / RAS-10SA-ES
FILE NO. SVM-09029
POWERSUPPLY
(Frommainline)
1∅220‑240V
50Hz
Heatexchanger
Sensor(TC)
Thermosensor(TA)
CN25
1
2
3
4
5
6
7
8
andindicationparts.
Infraredraysreceiver
WP‑017
GRN&YEL
Heatexchanger
BLU
1
BLU
2
BLU
3
BLU
4
BLU
5
BLU
6
BLU
7
WHI
8
CN01
1
22
CN03
1
2
CN12
1
2
3
4
5
6
7
8
BRW
L
BLU
N
GRN&YEL
1
6.3A
1
2
1
2
3
4
5
6
7
8
250VAC
R62
WHI
BLK
CN31
4
RY01
F01
R63
21
C25
3
BLK
P04
3
SG01
DSA
C26
L01
4
DB01
R64
C27
Switchingpowersupply
DC5V
Voltageregulator
12V
3
4
MCU
IC03
WP‑018
1
2
CN04
11
22
DC12V
PNK
PNK
CN07
WHI
1
1
YEL
22
YEL
3
3
YEL
44
YEL
55
CN11
YEL
1
1
GRY
2
2
BRW
3
3
C07
CN10
WHI
5
5
BLK
33
RED
1
1
o
Tempfuse73Cx2
1
22
3
44
55
1
3
Louvermotor
1
1
2
2
3
3
ACmotor
4
4
565
6
Fanmotor
INDOOR
TERMINAL
BLOCK
1
BLK
OUTDOOR
TERMINAL
BLOCK
1(L)
BLK
BLK
FAN MOTOR
OVERLOAD RELAY
RED
2
WHI
2(N)
COMPRESSOR
RED
WHI
GRN&YEL
CHASSIS
RED
CAPACITOR
INDOOR
OUTDOOR
CAPACITOR
RED
WHI
− 8 −
FILE NO. SVM-09029
4. SPECIFICATION OF ELECTRICAL PARTS
4-1. Indoor Unit (RAS-10SKHP-ES)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFN-220-20-4D AC Motor with 145°C thermo fuse
2Thermo sensor (TA-sensor)10k at 25 C
3 Micro power module (M01) RM1260V
4 Microcontroller unit (IC30) TMP87CM40AFG-6P69
5Heat exchanger sensor
2Fan motor (for outdoor)Winding resistance (Ω)Red-BlackWhite-Black
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
Solenoid coil
5
(for 4-way valve)
6
Overload relay
WLF-240-30A
(at 20°C)
DS451155NPQBAC 450V~, 1.5µ
RS44B256U0213S
−
LPAP960B
AC 440V~, 25
AC 220 − 240V
U/T: 6.1A(80°C), Open: 135±5°C, Close: 78±11°C
µF
237
F
380
- 9 -
FILE NO. SVM-09029
4-3. Indoor Unit (RAS-10SKP-ES)
No.Parts nameTypeSpecifications
1 Fan motor (for indoor) AFN-220-20-4D AC Motor with 145°C thermo fuse
2Thermo sensor (TA-sensor)10k at 25 C
3 Switching transformer
4 Microcontroller unit (IC30) TMP87CM40ANG-6P68
5Heat exchanger sensor
(TC-sensor)
6 Line filter (L01) LC*SS11V-R06270 27mH, 600mA
2 Fan motor (for outdoor) Winding resistance (Ω)Red-Black White-Black
Running capacitor
3
(for fan motor)
Running capacitor
4
(for compressor)
5
Overload relay
SKF-240-20B
(at 20°C)
DS451155NPQB
B32332I5256J063
LPAP960B
AC 450V~,1.5 µF
AC 450V~,25
U/T: 6.1A(80°C), Open: 135±5°C, Close: 78±11°C
235.2 260.1
µF
− 10−
5. REFRIGERATION CYCLE DIAGRAM
5-1. RAS-10SKHP-ES / RAS-10S2AH-ES
FILE NO. SVM-09029
Indoor unit
Cooling
0.39m
(Connecting pipe)
∅9.52
O.D.:9.52mmO.D.:6.35mm
Cooling
Heating
Heating
P
Packed valve
(∅9.52)
Heating
4-way valve
Cooling
Compressor
PA108X1C-4FZDN
Accumulator
Heat exchanger
Cross flow fan
T1
Capillary tube
∅1.5x1000
Packed valve
(∅6.35)
Capillary tube
∅1.5x1200
l
0.49m
(Connecting pipe)
∅6.35
l
Heat exchanger
Refrigerant
R410A : 0.78 kg.
Cooling
Heating
Propeller fan
Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standar d
pressure
(MPaG)
P
Surface temp. of heat
exchanger inter changing
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 2.9543.5 High 20/15 7/6
Heating Overload 3.70 57.0 Low 27/− 24/18
Low temperature 2.40 32.0 High 20/−
−10/−10
Standard 0.93 10.5 High 27/19 35/24
Cooling Overload 1.08 15.0 High 32/23 43/26
Low temperature 0.692.0 Low 21/15 21/15
Note :
•
Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
− 11 −
5-2. RAS-10SKP-ES / RAS-10SA-ES
FILE NO. SVM-09029
Indoor unit
Cooling
0.39m
(Connecting pipe)
∅9.52
O.D.:9.52mmO.D.:6.35mm
Cooling
Packed valve
Cooling
P
(∅9.52)
Compressor
PA108X1C-4FZDN
Heat exchanger
Cross flow fan
T1
0.49m
(Connecting pipe)
∅6.35
Packed valve
(∅6.35)
Capillary tube
∅1.5x1100l
Heat exchanger
Refrigerant
R410A : 0.72 kg.
Cooling
Propeller fan
Outdoor unit
Mark( )means check points of Gas Leak.
Ambient temp.
50Hz
Standard
pressure
(MPaG)
P
Surface temp. of heat
exchanger interchanging
pipe
T1
(°C)
Fan speed
(indoor)
conditions DB/WB
(°C)
IndoorOutdoor
Standard 0.95 10.5 High 27/19 35/24
Cooling Overload 1.12 16.0 High 32/23 43/26
Low temperature 0.712.0 Low 21/15 21/15
Note :
•Measure the heat exchanger temperature at the center of U-bend. (By means of TC sensor)
− 12 −
6. CONTROL BLOCK DIAGRAM
6-1. RAS-10SKHP-ES / RAS-10S2AH-ES
FILE NO. SVM-09029
Heat Exchange sensor
Thermo. Sensor
Current Sensor
(Compressor Current)
Infrared Rays Signal Reciver
Main Unit Control Panel
Functions
• Louver Control
•3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise FilterRelay Driver, Louver Driver
•Motor Revolution Control
•Processing
(Temperature Processing)
•Timer
Compressor
ON/OFF
Signal
Outdoor Fan
M.C.U.
ON/OFF
Signal
4-Way Valve
ON/OFF
Signal
Operation
Display
Timer
Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Relay
RY01
Compressor4-Way Valve
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, HEAT, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Relay
Outdoor Fan Motor
RY03
Infrared Rays
Relay
RY04
Hi power
Filter Reset
−13−
6-2. RAS-10SKP-ES / RAS-10SA-ES
Main Unit Control PanelM.C.U.
Heat Exchange sensor
Functions
FILE NO. SVM-09029
Operation
Display
Thermo. Sensor
Infrared Rays Signal Reciver
• Louver Control
•3-minutes Delay at Restart
for Compressor
Initiallizing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Noise FilterRelay Driver, Louver Driver
•Motor Revolution Control
•Processing
(Temperature Processing)
•Timer
Compressor
ON/OFF
Signal
Relay
RY01
Timer
Display
Indoor Fan
Motor
Louver
ON/OFF
Signal
Louver
Motor
220-240 V~, 50Hz
REMOTE CONTROL
Compressor, Outdoor Fan Motor
Infrared Rays
Remote Control
Operation ( )
Operation Mode Selection
AUTO, COOL, DRY, FAN ONLY
Temperature Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver Auto Swing
Louver Direction Setting
ECO
Hi power
Filter Reset
- 14 -
7. OPERATION DESCRIPTION
FILE NO. SVM-09029
7-1. Remote control
7-1-1. Function of Push Putton
11 Infrared signal emitter
1
11
2
Start/Stop button
3
Mode select button (MODE)
4
Temperature button (TEMP)
5
Fan speed button (FAN)
6
Swing louver button (SWING)
7
Set louver button (FIX)
8
On timer button (ON)
Off timer button (OFF)
9
18
10
Sleep timer button (SLEEP)
19
Timer setup button (SET)
11
12
20
Timer clear button (CLR)
13
Memory and Preset button (PRESET)
14
One Touch button (ONE-TOUCH)
15
High power button (Hi-POWER)
16
Economy button (ECO)
17
Quiet button (QUIET)
18
Comfort sleep button (COMFORT SLEEP)
19
Filter reset button (FILTER)
Clock Reset button (CLOCK)
20
21
Check button (CHK)
13
14
17
10
21
19
1
TOSHIBA
PRESET
ONE-TOUCH
2
QUIET
SWING
FIX Hi-POWER ECO
6
7
8
TIMER
SLEEP
CHK
ON
FILTER
TEMP
OFF
COMFORT
CLOCK
FAN
MODE
SLEEP
5
4
3
18
15
16
CLR
12
9
SET
11
20
− 15 −
FILE NO. SVM-09029
7-1-2. Display of Remote Control
All indications, except for the clock time indicator, are displayed by pressing the button.
1.Transmission mark
This transmission mark
remote controller transmits signals to the indoor
unit.
indicates when the
2. Mode indicator
Indicates the current operation mode.
(AUTO : Automatic control, A : Auto changeover
control,
: Cool, : Dry, : Heat, : Fan only)
3. Temperature indicator
Indicates the temperature setting.
(17°C to 30°C)
4. FAN speed indicator
Indicates the selected fan speed.
AUTO or five fan speed levels
(
LOW , LOW+ , MED , MED+ ,
HIGH ) can be shown.
Indicates AUTO when the operating mode is
either AUTO or
: Dry.
5. TIMER and clock time indicator
The time setting for timer operation or the clock
time is indicated.
The current time is always indicated except
during TIMER operation.
6. Hi-POWER indicator
Indicates when the Hi-POWER operation starts.
Press the Hi-POWER button to start and press it
again to stop the operation.
7. (PRESET) indicator
Flashes for 3 seconds when the PRESET button is
pressed during operation.
The
button for more than 3 seconds while the mark is
flashing.
Press another button to turn off the mark.
mark is shown when holding down the
8. ECO indicator
Indicates when the ECO is in activated.
Press the ECO button to start and press it again
to stop operation.
9. A, B change indicator remote controller
When the remote controller switching function is
set, “B” appears in the remote controller display.
(When the remote controller setting is “A”, there is
no indication at this position.)
11
10
10.Comfort sleep
Indicates when comfort sleep is activaled.
Press comfort sleep bu
9
15
1
2
13
11.Quiet
Indicates when quiet is activated.
Press quiet button to start and press it again to stop
operation.
tton to selectter
12.One-Touch
Indicates when one touch comfort is activated.
Press one-touch button to start the operation.
13.Swing
Indicates when louver is swing.
Press swing button to start the swing operation
and press it again to stop the swing operation.
8
6
3
7
4
5
− 16 −
FILE NO. SVM-09029
7-2. Outline of Air Conditioner Control
This is a fixed capacity type air conditioner, which uses
a AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which operate the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is mainly controlled by the indoor
unit controller. The controller operates the indoor fan
motor based upon commands transmitted by the
remote control and transfers the operation commands
to the outdoor unit controller.
The outdoor unit receives operation commands from
the indoor unit, and operates the outdoor fan motor
and the compressor.
(1) Role of indoor unit controller
The indoor unit controller receives the operation
commands from the remote control and executes
them.
• Temperature measurement at the air inlet of the
indoor heat exchanger by the indoor
temperature sensor
• Temperature measurement of the indoor heat
exchanger by the heat exchanger sensor
• Louver motor control
• Indoor fan motor operation control
• LED display control
• Transferring of operation commands to the
outdoor unit
• Receiving of information of the operation status
and judging of the information or indication of
error
(2) Role of outdoor unit controller
The outdoor unit controller receives the operation
commands from the indoor controller and
executes them.
• Compressor operation
control
• Operation control of
outdoor fan motor
Operations according
to the commands
from the indoor unit
• Turning off the compressor and outdoor fan
when the outdoor unit receives the shutdown
command
• Defrost control in heating operation
(Temperature measurement by the indoor heat
exchanger and control for the four-way valve
and the outdoor fan motor) *Heat pump Model
only
7-2-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcomputer, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed, it stops
swinging.
7-2-2. Indoor Fan Control
The operation controls the fan speed at indoor unit
side. The indoor fan (cross flow fan) is operated by
the phase control induction motor. The fan rotates in 5
stages in MANUAL model, and in 5 stages in AUTO
mode, respectively. (Table 7-2-1)
1) When setting the fan speed to L, L+, M, M+ or H
on the remote controller, the operation is performed
with the constant speed shown in Fig. 7-2-1 and
Fig 7-2-2
Fig (7-2-1) CoolingFig (7-2-2) Heating
Indication
L
L+
M
M+
H
Fan speed
Low
(L + M) / 2
Med
(M + H) / 2
High
Indication
L
L+
M
M+
H
Fan speed
(L + M) / 2
(M + H) / 2
Low
Med
High
Table 7-2-1 Indoor fan and air flow rate
OPERATION
MODE
RAS-10SKHP-ES
Model
RAS-10SKP-ES
CoolUHHM+ML+LL-ULSUL
HeatUHHM+M+L+LL-ULSUL
DryUHHM+ML+LL-ULSUL
fan speed (rpm)1350 1350 1350 1300 1250 1180 1140 1000 980980900800750700550
Air flow (m3/h)560560560540510500460400390390350300270250180
fan speed (rpm)1350 1350 1350 1300 1250 1180 1140 1000 980980900800750700550
Air flow (m3/h)560560560540510500460400390390350300270250180
2) When setting the fan speed to AUTO on the remote
controller, revolution of the fan motor is controlled
to the fan speed level shown in Table 1 according to
the setup temperature, room temperature, and heat
exchanger temperature.
FAN TAP
− 17 −
FILE NO. SVM-09029
7-3. Description of Operation Mode
(1) When turning on the breaker, the operation lamp
blinks. This means that the power is on (or the
power supply is cut off.)
(2) When pressing [ ] button on the
remote control, receiving beep sounds from the
indoor unit, and the next operation is performed
together with opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcomputer so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-3-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-3. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
7-3-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-3-4.
° C
ONON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-3-4
display lamp
OPERATION
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
(Preset temp.: 24 °C)
M+
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
(Linear approximation
from M+ and L)
NOTE2 : The Hi Power, ECO and COMFORT SLEEP
operation can not be set
Fig. 7-3-3 Setting of air flow [FAN:AUTO]
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-5. When
*1
*2
*3
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Room temp.) − (Preset temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*2
*3
NOTE1 : *1 : Fan speed = (M + − L) x 3/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 1/4 + L
(Linear approximation
from M+ and L)
Fig. 7-3-5 Setting of air flow [FAN:AUTO]
− 18 −
FILE NO. SVM-09029
7-3-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display lamp are controlled as shown in
Fig. 7-3-6.
° C
ON:6min.
OFF:4min.
ON
ON:5min.
OFF:5min.
OFF
4-way valve
Outdoor fan
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
OFF
ON:5min.
OFF:5min.
OFF
0
Compressor
Fig. 7-3-6
7-3-4. Heating operation
RAS-10SKHP-ES
(1) The compressor, 4-way valve, outdoor fan and
Preset
temp.
display lamp
OPERATION
([MODE] button on the remote control is set
to the heating operation.)
operation display lamp are controlled as shown in
Fig. 7-3-8.
° C
0
0.5
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
ON
OFF
ON
4-way valve
Outdoor fan
OPERATION
display lamp
(2) The microprocessor turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-3-7.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L. *S.L.S.L.L.L.S.L.L.
*Super Low
Fig. 7-3-7
(3) [FAN] button on the remote control is set to AUTO
only.
Fig. 7-3-8
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-3-9. When
[FAN] button is set to LOW, LOW+, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-5.0
-5.5
[FAN AUTO]
(Room temp.) − (Preset temp.)
L
*1
*2
+
M
H
*1 : Fan speed = (M + − L) x 1/4 + L
*2 : Fan speed = (M + − L) x 2/4 + L
*3 : Fan speed = (M + − L) x 3/4 + L
(Calculated with inear approximation from M+ and L+)
(4) The ECO and Hi Power operations can not be set.
Fig. 7-3-9
− 19 −
y.
c
e
U
.
c
U
g
y
FILE NO. SVM-09029
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-3-10 and Table 7-3-2.
T
46
34
45 33
33 21
32 20
*A+4 *A+4
*A-4 *A-4
Fan speed MAN
Fan speed AUTO in stabilit
* No limitation while fan speed MANUAL mode is in stabilit
* A: When Tsc 24, A is 24, and when Tsc < 24, A is Ts
Tsc: Set valu
H
Line-approximate
H and S
SUL
L with Tc
Stop
AL in startin
Fig. 7-3-10 Cold draft preventing control
Table 7-3-2
Fan*5*6
speedStarting periodStabilized period
AUTO• Up until 12 minutes
passed after starting
the unit
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3°C
lower than preset
temperature
Manual• Room temperature
(L – H)< Preset temperature
• From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3°C
lower than preset
temperature
• 25 minutes or more
passed after starting
the unit
• Room temperature
Preset temperature
–4°C
–3.5°C
7-3-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-3-11. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the RESET button on the indoor unit
is pushed, the preset temperature is fixed at 24°C
and the indoor unit is controlled as shown in
Fig. 7-3-11.
RAS-10SKHP-ES
°C
Cooling operation
0
Fan only operation
-1
Heating operation
(Room temp.) − (Preset temp.)
RAS-10SKP-ES
°C
Cooling operation
0
Heating operation
(Room temp.) − (Preset temp.)
Fig. 7-3-11
− 20 −
FILE NO. SVM-09029
7-4. High-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger
temp.
(°C)
60
53
52
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1 and 7-5-2.
7-6. Defrost Operation
*Heat pump model only*Heat pump model only
During the heating operation, the outdoor heat
exchanger temperature goes down and sometimes it is
frozen.
In this case, the air conditioner stops the heating
operation and starts the defrost operation to melt ice.
7-6-1. Condition to start the defrost operation
The defrost operation starts whichever below
conditions are satisfied.
(1) When the cumulative compressor operating time is
longer than 40 or 90 minutes and difference
between the indoor heat exchanger temperature
and the room temperature is less than the
specified value. (This value is decided by the
microprocessor.) (Control example is shown in
Fig. 7-6-1. In case of B or C, the defrost operation
starts.)
(2) When the current limit control or the high
temperature limit control is performed for total of
90 minutes.
RAS-10SKHP-ES
RAS-10SKP-ES
Heat exchanger
temperature
(°C)
5
2
Compressor Outdoor fan
Fig. 7-5-1
ON
Less than 2°C continues
for 5 minutes
OFF
D
xchanger temp
A
Indoor heat e
- Room temp
Fig. 7-6-1 (Indoor fan speed : M)
7-6-2. Defrost operation time control
<In case of B>
(1) The heating operation is performed for at least
40 minutes.
(2) The maximum defrost operating time is 6 minutes.
The defrost operating time for the 4th cycle is
10 minutes. (When the outdoor temperature is
very low, however, the defrost operating time is
10 minutes.)
B
C
Cumulative
compressor
operating time
− 21 −