Toshiba RAS-B10N3KV2-E1, RAS-B13N3KV2-E1, RAS-B16N3KV2-E1, RAS-10N3AV2-E1, RAS-13N3AV2-E1 Service Manual

...
R410A
SERVICE MANUAL
SPLIT TYPE
Indoor Unit Outdoor Unit
<High Wall, Heat Pump Type> <Heat Pump Type>
January
, 201
5
RAS-
B10N3KV2-E1
RAS-
B13N3KV2-E1
RAS-
B16N3KV2-E1
RAS-
10N3AV2-E1 RAS-13N3AV2-E1 RAS-16N3AV2-E
1
CONTENTS
1. SAFETY PRECAUTIONS .......................................................................... 2
2. SPECIFICATIONS ..................................................................................... 5
3. REFRIGERANT R410A ............................................................................. 7
4. CONSTRUCTION VIEWS ........................................................................ 17
5. WIRING DIAGRAM .................................................................................. 19
6. SPECIFICATIONS OF ELECTRICAL PARTS ......................................... 21
7. REFRIGERANT CYCLE DIAGRAM ........................................................ 22
8. CONTROL BLOCK DIAGRAM ................................................................ 25
9. OPERATION DESCRIPTION................................................................... 28
10. INSTALLATION PROCEDURE ................................................................ 53
11. HOW TO DIAGNOSE THE TROUBLE...................................................... 67
12. HOW TO REPLACE THE MAIN PARTS................................................... 99
13. EXPLODED VIEWS AND PARTS LIST ................................................. 117
For general public use
Power supply cord and connecting cable of appliance for outdoor use shall be at least polychloroprene sheathed flexible cord (design H07RN-F) or cord designation 60245 IEC66. (Shall be installed in accordance with national wiring regulations.)
CAUTION
New refrigerant air conditioner installation
THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A), WHICH DOES NOT DESTROY
OZONE LAYER.
R410A refrigerant is apt to be affected by impurities such as water, oxidizing membranes, and oils because the pressure of R410A refrigerant is approx. 1.6 times of refrigerant R22. As well as the adoption of this new refrigerant, refrigerating machine oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating machine oil does not enter the refrigeration cycle of a new-refrigerant air conditioner. To avoid mixing refrigerant and refrigerating machine oil, the sizes of charging port connecting port connecting sections on the main unit are different from those for the conventional refrigerant, and different size tools are also required. For connecting pipes, use new and clean piping materials with highpressure withstand capabilities, designed for R410A only, and ensure that water or dust does not enter. Moreover, do not use any existing piping as its pressure withstand may be insufficient and may contain impurities.
DANGER
FOR USE BY QUALIFIED PERSONS ONLY.
MEANS FOR DISCONNECTION FROM THE SUPPLY HAVING A CONTACT SEPERATION OF AT LEAST 3 mm
IN ALL POLES MUST BE INCORPORATED IN THE FIXED WIRING.
TURN OFF MAIN POWER SUPPLY BEFORE ATTEMPTING ANY ELECTRICAL WORK, MAKE SURE ALL POWER
SWITCHES ARE OFF FAILURE TO DO SO MAY CAUSE ELECTRIC SHOCK.
CONNECT THE CONNECTING CABLE CORRECTLY. IF THE CONNECTING CABLE IS CONNECTED WRONGLY,
ELECTRIC PARTS MAY BE DAMAGED.
CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION.
DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS.
FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION.
TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD, PLACE THE UNIT WELL
AWAY (MORE THAN 2 M) FROM HEAT SOURCES SUCH AS RADIATORS, HEATERS, FURNACE, STOVES, ETC.
WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN, BE VERY
CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT (R410A) WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE. IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT, THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS.
IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE INSTALLATION WORK,
IMMEDIATELY LET FRESH AIR INTO THE ROOM. IF THE REFRIGERANT GAS IS HEATED BY FIRE OR SOMETHING ELSE, IT CAUSES GENERATION OF POISONOUS GAS.
WHEN INSTALLING OR RE-INSTALLING THE AIR CONDITIONER, DO NOT INJECT AIR OR OTHER SUBSTANCES
BESIDES THE DESIGNATED REFRIGERANT "R410A" INTO THE REFRIGERATION CYCLE. IF AIR OR OTHER SUBSTANCES ARE MIXED, AN ABNORMAL PRESSURE CAN OCCUR IN THE REFRIGERATING CYCLEL, AND THIS CAN CAUSE AN INJURY DUE TO A PIPE RUPTURE.
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. Be sure to read this installation manual carefully before installing. Recommend to the owner to perform maintenance periodically when using over long periods of time. Be sure to follow the precautions provided here to avoid safety risks. The symbols and their meanings are shown below.
DANGER : It indicates that incorrect use of this unit can result in a high possibility of severe injury (*1) or death. WARNING : It indicates that incorrect use of this unit may cause severe injury of death. CAUTION : It indicates that incorrect use of this unit may cause personal injury (*2) or property damage (*3).
*1 : A severe injury refers to blindness, injury, burns (hot or cold), electrical shock, bone fracture, or
poisoning that leaves aftereffects and requires hospitalization or extended out-patient treatment.
*2 : Personal injury means a slight accident, burn, or electrical shock which does not require admission
or repeated hospital treatment.
*3 : Preperty damage means greater damage which affects assets or resources.
FILE NO. SVM-15006
1. SAFETY PRECAUTIONS
2
WARNING
Installation work must be requested from the supplying retail dealership or professional vendors. Self-installation may
cause water leakage, electrical shock, or fire as a result of improper installation.
Specified tools and pipe parts for model R410A are required, and installation work must be done in accordance with
the manual. HFC type refrigerant R410A has 1.6 times more pressure than that of conventional refrigerant (R22). Use the specified pipe parts, and ensure correct installation, otherwise damage and/or injury may be caused. At the same time, water leakage, electrical shock, and fire may occur.
Be sure to install the unit in a place which can sufficiently bear its weight. If the load bearing of the unit is not enough,
or installation of the unit is improper, the unit may fall and result in injury.
Electrical work must be performed by a qualified elecrical engineer in accordance with the code governing such
installation work, inernal wiring regulations, and the manual. A dedicated circuit and the rated voltage must be used. Insufficient power supply or improper installation may cause electrical shock or fire.
Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection, stranded wire, and single-wire
connections are not allowed. Improper connection or fixing may cause a fire.
Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be firmly placed.
Improper cover installation may cause increased heat, fire, or electrical shock at the terminal area.
Be sure to use only approved accessories or the specified parts. Failure to do so may cause the unit to fall, water
leakage, fire or electrical shock.
After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the
pipe into the room and is heated by fire or something else from a fan heater, stove or gas range, it causes generation of poisonous gas.
Make sure the equipment is properly earthed. Do not connect the earth wire to a gas pipe, water pipe, lightning
conductor, or telephone earth wire. Improper earth work may be the cause of electrical shock.
Do not install the unit where flammable gas may leak. It there is any gas leakage or accumulation around the unit,
it can cause a fire.
Do not select a location for installation where there may be excessive water or humidity, such as a bathroom.
Deterioration of insulation may cause elestrical shock or fire.
Installation work must be performed following the instructions in this installation manual. Improper installation may
cause water leakage, electrical shock or fire. Check the following items before operating the unit.
- Be sure that the pipe connection is well placed and there are no leaks.
- Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in compressor damage. At the same time, if there is a leak in the connection part, it may cause air suction and overpressure, resulting burst or injury.
In pump down operations, ensure to perform the following procedures.
- Do not inject air into the refrigeration cycle.
- Be sure to close both service valves and stop the compressor before removing the refrigerant pipe. It removing the refrigerant pipe while the compressor is operating with the service valves opened, it may cause to air absorbed and abnormal high pressure inside the refrigeration cycle and resulting burst or injury.
Do not modify the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may
cause contact failure, insulation failure, or excess current, resulting in fire or electrical shock.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally
high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
Be sure to comply with local regulations/codes when running the wire from the outdoor unit to the indoor unit,
(Size of wire and wiring method etc.).
Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of
the air conditioner, it may spontaneously combust and start a fire.
If you detect any damage, do not install the unit. Contact your supplying dealer immediately.
Never modify this unit by removing any of the safety guards.
Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if
the unit falls.
3
FILE NO. SVM-15006
CAUTION
Please read this installation manual carefbefore installing the unit. It contains further important instructions for proper
installation.
Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet
basement or expose to rain or water.
After unpacking the unit, examine it carefully for possible damage.
Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise
level of the unit or where noise and discharged air might disturb neighbors.
This appliance must be connected to the main power supply by means of a circuit breaker depending on the place
where the unit is installed. Failure to do so may cause electrical shock.
Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit.
Ensure that drained water is discharged. Improper drainage can result in water leakage, causing water damage to furniture.
Tighten the flare nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise, the
nut may crack after a long period of usage and it may cause the leakage of refrigerant.
Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal injury
when handling parts with sharp edges.
Do not touch the air intake section or the aluminum fins of the outdoor unit. It may cause injury.
Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and contact
internal electrical parts, causing a failure or fire.
Request the user to keep the place around the unit tidy and clean.
Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit to the
customer in accordance with the manual. Ask the customer to keep the operation manual along with the installation manual.
4
FILE NO. SVM-15006
FILE NO. SVM-15006
2. SPECIFICATIONS
Unit model Indoor
RAS-B10N3KV2-E1 R
AS-B13N3KV2-E1
Outdoor
RAS-10N3AV2-E1 RAS-13N3
AV2-E1
Cooling capacity (kW) 2.5 3.5 Cooling capacity range (kW) 1.1-3.1
1.1-4.
05
Heating capacity (kW) 3.2 4.2 Heating capacity range (kW) 0.9-4.8
1.0-5.3
Power supply Electric Indoor Operation mode Cooling Heating Cooling Heating characteristic Running current (A) 0.21-0.19 0.24-0.22 0.21-0.19 0.24-0.22
Power consumption (W) 35 40 35 40 Power factor (%)7 766 76 76
Outdoor Operation mode Cooling Heating Cooling Heating
Running current (A)
2
.94-2.71
3.
52-3.23
5.03-
4.61
2.31-4.78
Power consumption (W) 563 710
1015
1040
Power factor (%)
87 92 92 91
Starting current (A
)
3.
76
5.17 COP (Cooling / Heating) Operating Indoor High (Cooling / Heating) (dB-A) 38/39 39/40 noise Medium (Cooling / Heating) (dB-A) 33/34 33/34
Low (Cooling / Heating) (dB-A) 26/28 26/28
Outdoor (Cooling / Heating) (dB-A) 46/47 48/50
Indoor unit Unit model
RAS-B10N3KV2-E
1
RAS-B13N3KV2-E
1
Dimension Height (mm) 275 275
Width (mm) 790 790 Depth (mm)
217 217
Net weig
ht
(kg)
10
10 Fan motor output (W) 20 20 Air flow rate (Cooling / Heating)
(m
3
/
/
min)
8.6/9.5 9.5/10.4
Outdoor unit Unit model
RAS-10N3AV2-E1 RAS-13N3AV
2-E1
Dimension Height (mm) 550 550
Width (mm) 780 780
Depth (mm) 290 290 Net weigh (kg) 33 33 Compressor Motor output (W) 750 750
Type
Twin rotary type with DC-inverter variable speed control to
single rotary type with DC-inverter variable speed control
Model
ASM89D16UFZ
Fan motor output (W) Air flow rate (Cooling / Heating)
(m3 min)
30/30 37.5/37.5 Piping Type Flare connection Flare connection connection Indoor unit Liquid side (mm)
6.35 6.35
Gas side (mm) 9.52 9.52
Outdoor unit Liquid side (mm) ∅ 6.35 ∅ 6.35
Gas side (mm) 9.52 9.52
Maximum length (m) 20 20 Maximum charge-less length (m) 15 15 Maximum height difference (m) 10 10
Refrigerant Name of refrigerant R410A R410A
Weight (kg) 0.80 0.80 Wiring Power supply connection Interconnection Usable temperature range Indoor (Cooling / Heating)
(
o
C)
21-32/0-28 21-32/0-28
Outdoor (Cooling / Heating)
(oC)
-10-46/-15-24 -10-46/-15-24
Accessory Indoor unit Installation plate 1 1
Wireless remote controller 1 1 batteries 2 2 Remote controller holder 1 1 TOSHIBA IAQ filer (long type) 1 1 Mounting screw
6 ( ∅ 4 x 25L) 6 ( ∅ 4 x 25L)
Pan head wood screw
2 ( 3.1 x 16L) 2 ( 3.1 x 16L)
Plasma air purifier - ­Installation manual 1 1 Owner's manual 1 1
Outdoor unit Drain nipple 1 1
Water proof rubber cap 2 2
* The specification may be subject to change without notice for purpose of improvement.
43
1Ph
/50Hz/220
-240V , 1Ph/60Hz/220-230V
4.18/4.27
3
.33/3.89
3 Wires: Includes earth (Outdoor)
4 Wires: Includes earth
5
2-1. Specification
FILE NO. SVM-15006
6
Unit model Indoor
RAS-B16N3KV2-E1
Outdoor RAS-16N3AV2-E
Cooling capacity (kW) 4.5 Cooling capacity range (kW) 0.8-5.0 Heating capacity (kW) 5.5 Heating capacity range (kW) 0.9-6.9 Power supply Electric Indoor Operation mode Cooling Heating characteristic Running current (A)
0.21-0.19 0.24-0.22 Power consumption (W) 30 35 Power factor (%)
65 66
Outdoor Operation mode Cooling Heating
Running current (A) 6.33-5.80 6.86-6.28 Power consumption (W)
1365 1485 Power factor (%) 98 98 Starting current (A) 7.10
COP (Cooling / Heating) Operating Indoor High (Cooling / Heating) (dB-A) 45/45 noise Medium (Cooling / Heating) (dB-A) 40/40
Low (Cooling / Heating) (dB-A) 30/31
Outdoor (Cooling / Heating) (dB-A)
49/50
Indoor unit Unit model
RAS-B16N3KV2-E1
Dimension Height (mm)
275 Width (mm) 790 Depth (mm) 225
Net weight (kg) 10 Fan motor output (W) 30 Air flow rate (Cooling / Heating)
(m
3
/
/
min)
11.5/12.3
Outdoor unit Unit model RAS-16N3AV2-E
Dimension Height (mm) 550
Width (mm) 780 Depth (mm) 290
Net weicht (kg) 38 Compressor Motor output (W) 1100
Type Twin rotary type with DC-inverter variable speed control Model DA131S1B-31FZ
Fan motor output (W) Air flow rate (Cooling / Heating)
(m3 min)
36/32 Piping Type Flare connection connection Indoor unit Liquid side (mm)
6.35
Gas side (mm)
12.7
Outdoor unit Liquid side (mm)
6.35
Gas side (mm)
12.7
Maximum length (m) 20 Maximum charge-less length (m) 15 Maximum height difference (m) 10
Refrigerant Name of refrigerant R410A
Weight (kg) 1.10 Wiring Power supply connection Interconnection Usable temperature range Indoor (Cooling / Heating)
(
o
C)
21-32/0-28
Outdoor (Cooling / Heating)
(oC)
-10-46/-15-24
Accessory Indoor unit Installation plate 1
Wireless remote controller 1 batteries 2 Remote controller holder 1 TOSHIBA IAQ Filter (long type) 1 Mounting screw
6 (4 x 25L)
Pan head wood screw
2 (3.1 x 16L)
Plasma air purifier ­Installation manual 1 Owner's manual 1
Outdoor unit Drain nipple 1
Water proof rubber cap 2
* The specification may be subject to change without notice for purpose of improvement.
3 Wires: Includes earth (Outdoor)
4 Wires: Includes earth
3.23/3.62
1Ph/50Hz/220-240V, 1Ph/60Hz/220V
43
2-2. Specification
7
<Heating>
0
1
2
3
4
5
6
7
8
9
0 01 20 03 0540 60 07 08 90100110120
Current (A)
Compressor Speed (rps)
0
1
2
3
4
5
6
7
8
9
0 01 02 03 40 05 06 07 08 90100110120
Current (A)
Compressor Speed (rps)
Conditions Indoor : DB 27oC/WB 19oC Outdoor : DB 35
o
C Air Flow : High Pipe Length : 5m Voltage : 230V
Conditions Indoor : DB 20oC Outdoor : DB 7
o
C/WB 6oC Air Flow : High Pipe Length : 5m Voltage : 230V
<Cooling>
<Cooling>
2-3. Operation Characteristic Curve
RAS-B16N3KV2-E1
RAS-B10N3KV2-E1,
RAS-B13N3KV2-E1
0
1
2
3
4
5
6
7
0 02 40 06 80100
Current (A)
Compressor Speed (rps)
Conditions Indoor : DB 27oC/WB 19oC Outdoor : DB 35
o
C/WB 24oC Indoor Air Flow : High Pipe Length : 5m Voltage : 230V
RAS-B13N3KV2-E1
RAS-B10N3KV2-E1
<Heating>
0
2
4
6
8
0 51 5430 06 57 90105120
Current (A)
Compressor Speed (RPS)
RAS-B13N3KV2-E1
Conditions Indoor : DB 20oC/WB 15oC Outdoor : DB 7
o
C/WB 6oC Indoor Air Flow : High Pipe Length : 5m Voltage : 230V
RAS-B10N3KV2-E1
2-4.Capacity Variation Ration According to Temperature
50
55
60
65
70
75
80
85
90
95
100
105
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Capacity ratio (%)
Outdoor temp. (oC)
0
20
40
60
80
100
120
-15 -10 -5 0 5 10
Capacity ratio (%)
Outdoor temp. (oC)
Conditions Indoor : DB 27oC/WB 19oC Outdoor : DB 35
o
C Air Flow : High Pipe Length : 5m Voltage : 230V
Conditions Indoor : DB 20oC Outdoor : DB 7
o
C/WB 6oC Air Flow : High Pipe Length : 5m Voltage : 230V
Capacity ratio 100% is 4.5 kW
Capacity ratio 100% is 5.5 kW
8
<Cooling>
<Heating>
<Heating>
<Cooling>
RAS-B16N3KV2-E1
RAS-B10N3KV2-E1, RAS-B13N3KV2-E1
0.0
20.0
40.0
60.0
80.0
100.0
120.0
-25 -20 -15 -10 -5 0 5 10
Heating Capacity ratio (%)
Outside Temperature ( ºC)
RAS-B10N3KV2-E1 RAS-B13N3KV2-E1
50.0
55.0
60.0
65.0
70.0
75.0
80.0
85.0
90.0
95.0
100.0
105.0
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46
Cooling Capacity ratio (%)
Outside Temperature ( oC)
Conditions Indoor : DB 27oC/WB 19oC Outdoor : DB 35
o
C/WB 24oC Indoor Air Flow : High Pipe Length : 5m Voltage : 230V
Capacity ratio : 100 %=
2.50kW(RAS-B10N3KV2-E1)
3.50kW(RAS-B13N3KV2-E1)
RAS-B10N3KV2-E1
RAS-B13N3KV2-E1
Conditions Indoor : DB 20oC/WB 15oC Outdoor : DB 7
o
C/WB 6oC Indoor Air Flow : High Pipe Length : 5m Voltage : 230V
9
3. REFRIGERANT R410A
This air conditioner adopts the new refrigerant HFC (R410A) which does not damage the ozone layer.
The working pressure of the new refrigerant R410A is 1.6 times higher than conventional refrigerant (R22). The refrigerating oil is also changed in accordance with change of refrigerant, so be careful that water , dust, and existing refrigerant or refrigerat­ing oil are not entered in the refrigerant cycle of the air conditioner using the new refrigerant during installation work or servicing time.
The next section describes the precautions for air conditioner using the new refrigerant. Conforming to contents of the next section together with the general cautions included in this manual, perform the correct and safe work.
3-1. Safety During Installation/Servicing
As R410As pressure is about 1.6 times higher than that of R22, improper installation/servicing may cause a serious trouble. By using tools and materi­als exclusive for R410A, it is necessary to carry out installation/servicing safely while taking the following precautions into consideration.
1. Never use refrigerant other than R410A in an air conditioner which is designed to operate with R410A.
If other refrigerant than R410A is mixed, pressure in the refrigeration cycle becomes abnormally high, and it may cause personal injury, etc. by a rupture.
2. Confirm the used refrigerant name, and use tools and materials exclusive for the refrigerant R410A.
The refrigerant name R410A is indicated on the visible place of the outdoor unit of the air condi­tioner using R410A as refrigerant. To prevent mischarging, the diameter of the service port differs from that of R22.
3. If a refrigeration gas leakage occurs during installation/servicing, be sure to ventilate fully.
If the refrigerant gas comes into contact with fire, a poisonous gas may occur.
4. When installing or removing an air conditioner, do not allow air or moisture to remain in the refrig­eration cycle. Otherwise, pressure in the refrig­eration cycle may become abnormally high so that a rupture or personal injury may be caused.
5. After completion of installation work, check to make sure that there is no refrigeration gas leakage.
If the refrigerant gas leaks into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
6. When an air conditioning system charged with a large volume of refrigerant is installed in a small room, it is necessary to exercise care so that, even when refrigerant leaks, its concentration does not exceed the marginal level.
If the refrigerant gas leakage occurs and its concentration exceeds the marginal le vel, an oxygen starvation accident may result.
7. Be sure to carry out installation or removal according to the installation manual.
Improper installation may cause refrigeration trouble, water leakage, electric shock, fire, etc.
8. Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner technician or electrician.
Improper repairs may result in water leakage, electric shock and fire, etc.
3-2. Refrigerant Piping Installation
3-2-1. Piping Materials and Joints Used
For the refrigerant piping installation, copper pipes and joints are mainly used. Copper pipes and joints suitable for the refrigerant must be chosen and installed. Furthermore, it is necessary to use clean copper pipes and joints whose interior surfaces are less affected by contaminants.
1. Copper Pipes
It is necessary to use seamless copper pipes which are made of either copper or copper alloy and it is desirable that the amount of residual oil is less than 40 mg/10 m. Do not use copper pipes having a collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become bloc ked with contaminants.
As an air conditioner using R410A incurs pres­sure higher than when using R22, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in Table 3-2-1. Never use copper pipes thinner than 0.8 mm even when it is availab le on the mark et.
10
Table 3-2-1 Thicknesses of annealed copper pipes
Nominal diameter
1/4 3/8 1/2 5/8
Outer diameter (mm)
6.35
9.52
12.70
15.88
Thickness (mm)
R410A R22
0.80 0.80
0.80 0.80
0.80 0.80
1.00 1.00
2. Joints
For copper pipes, flare joints or soc ket joints are used. Prior to use, be sure to remove all contaminants. a) Flare Joints
Flare joints used to connect the copper pipes cannot be used for pipings whose outer diameter e xceeds 20 mm. In such a case, socket joints can be used.
Sizes of flare pipe ends, flare joint ends and flare nuts are as shown in Tables 3-2-3 to 3-2-6 below.
b) Socket Joints
Socket joints are such that they are brazed for connections, and used mainly for thick pipings whose diameter is larger than 20 mm.
Thicknesses of sock et joints are as shown in Table 3-2-2.
Table 3-2-2 Minimum thicknesses of socket joints
Nominal diameter
1/4 3/8 1/2 5/8
Reference outer diameter of
copper pipe jointed (mm)
6.35
9.52
12.70
15.88
Minimum joint thickness
(mm)
0.50
0.60
0.70
0.80
3-2-2. Processing of Piping Materials
When performing the refrigerant piping installation, care should be taken to ensure that water or dust does not enter the pipe interior, that no other oil than lubricating oils used in the installed air-water heat pump is used, and that refrigerant does not leak. When using lubricating oils in the piping processing, use such lubricating oils whose water content has been removed. When stored, be sure to seal the container with an airtight cap or any other cover.
1. Flare processing procedures and precautions
a) Cutting the Pipe
By means of a pipe cutter, slowly cut the pipe so that it is not deformed.
b) Removing Burrs and Chips
If the flared section has chips or burrs, refrigerant leakage may occur. Carefully remove all burrs and clean the cut surface before installation.
c) Insertion of Flare Nut
11
A
ØD
d) Flare Processing
Make certain that a clamp bar and copper pipe have been cleaned.
By means of the clamp bar, perform the flare processing correctly.
Use either a flare tool for R410A or conven­tional flare tool.
Flare processing dimensions differ according to the type of flare tool. When using a con­ventional flare tool, be sure to secure “dimen- sion A by using a gauge for size adjustment.
Fig. 3-2-1 Flare pr ocessing dimensions
Table 3-2-3 Dimensions related to flare processing for R410A
Nominal
diameter
1/4 3/8 1/2 5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R410A
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Conventional flare tool
Clutch type Wing nut type
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 1.5 to 2.0
1.0 to 1.5 2.0 to 2.5
1.0 to 1.5 2.0 to 2.5
Table 3-2-4 Dimensions related to flare processing for R22
Nominal
diameter
1/4 3/8 1/2 5/8
Outer
diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
A (mm)
Flare tool for R22
clutch type
0 to 0.5 0 to 0.5 0 to 0.5 0 to 0.5
Conventional flare tool
Clutch type Wing nut type
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.0 to 1.5
0.5 to 1.0 1.5 to 2.0
0.5 to 1.0 1.5 to 2.0
Table 3-2-5 Flare and flare nut dimensions for R410A
Nominal
diameter
1/4 3/8 1/2 5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Thickness
(mm)
0.8
0.8
0.8
1.0
Dimension (mm)
ABCD
9.1 9.2 6.5 13
13.2 13.5 9.7 20
16.6 16.0 12.9 23
19.7 19.0 16.0 25
Flare nut width
(mm)
17 22 26 29
12
43˚ to 45˚
45˚ to 46˚
B A
C
D
Table 3-2-6 Flare and flare nut dimensions for R22
Nominal
diameter
1/4 3/8 1/2 5/8 3/4
Outer diameter
(mm)
6.35
9.52
12.70
15.88
19.05
Thickness
(mm)
0.8
0.8
0.8
1.0
1.0
Dimension (mm)
ABCD
9.0 9.2 6.5 13
13.0 13.5 9.7 20
16.2 16.0 12.9 20
19.7 19.0 16.0 23
23.3 24.0 19.2 34
Flare nut width
(mm)
17 22 24 27 36
Fig. 3-2-2 Relations between flare nut and flare seal surface
2. Flare Connecting Procedures and Precautions
a) Make sure that the flare and union portions do not have any scar or dust, etc. b) Correctly align the processed flare surface with the union axis. c) Tighten the flare with designated torque by means of a torque wrench. The tightening torque for R410A is
the same as that for conventional R22. Incidentally, when the torque is weak, the gas leakage may occur. When it is strong, the flare nut may crack and may be made non-removable. When choosing the tighten-
ing torque, comply with values designated by man ufacturers. Table 3-2-7 shows reference values.
NOTE :
When applying oil to the flare surface, be sure to use oil designated b y the man ufacturer. If any other oil is used, the lubricating oils may deteriorate and cause the compressor to burn out.
Table 3-2-7 Tightening torque of flare for R410A [Reference values]
Nominal
diameter
1/4 3/8 1/2 5/8
Outer diameter
(mm)
6.35
9.52
12.70
15.88
Tightening torque
N•m (kgf•cm)
14 to 18 (140 to 180) 33 to 42 (330 to 420) 50 to 62 (500 to 620) 63 to 77 (630 to 770)
Tightening torque of torque
wrenches available on the market
N•m (kgf•cm)
16 (160), 18 (180)
42 (420) 55 (550) 65 (650)
13
3-3. Tools
3-3-1. Required T ools
The service port diameter of packed v alve of the outdoor unit in the air-water heat pump using R410A is changed to prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
1. Tools exclusiv e for R410A (Those which cannot be used for conventional refrigerant (R22))
2. Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3. Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
1
2
3
4 5 6
7 8
9
10
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench (For Ø12.7)
Gauge manifold Charge hose Vacuum pump adapter
Electronic balance for refrigerant charging
Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring Flaring by
conventional flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
R410A
air-water heat pump installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
Whether conven­tional equipment can be used
*(Note 1)
*(Note 1)
× ×
× × ×
× ×
Conventional air-water heat pump installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
× ×
¡
¡
×
¡
×
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
1. Vacuum pump Use vacuum pump by attaching vacuum pump adapter.
2. Torque wrench (For Ø6.35, Ø9.52)
3. Pipe cutter
4. Reamer
5. Pipe bender
6. Level vial
7. Screwdriver (+, –)
8. Spanner or Monkey wrench
9. Hole core drill (Ø65)
10. Hexagon wrench (Opposite side 4mm)
11 . Tape measure
12. Metal saw
Also prepare the following equipments for other installation method and run check.
1. Clamp meter
2. Thermometer
3. Insulation resistance tester
4. Electroscope
14
Connect the charge hose to packed valve service port at the outdoor units gas side.
Recover the refrigerant, and check no refrigerant remains in the equipment.
(For refrigerant charging, see the figure below.)
Connect the charge hose to the vacuum pump adapter.
Open fully both packed valves at liquid and gas sides.
Place the handle of the gauge manifold Low in the fully opened position, and turn on the vacuum pumps power switch. Then, evacuating the refrigerant in the cycle.
When the compound gauge’s pointer has indicated –0.1 Mpa (–76 cmHg), place the handle Low in the fully closed position, and turn off the vacuum pump’s power switch.
Keep the status as it is for 1 to 2 minutes, and ensure that the compound gauges pointer does not return.
Set the refrigerant cylinder to the electronic balance, connect the connecting hose to the cylinder and the connecting port of the electronic balance, and charge liquid refrigerant.
(Indoor unit)
(Outdoor unit)
Opened
Opened
Refrigerant cylinder
(with siphon)
Check valve
Open/close valve for charging
Electronic balance for refrigerant charging
Opened
Closed
Service port
3-4. Recharging of Refrigerant
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the following steps.
1. Never charge refrigerant exceeding the specified amount.
2. If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.
3. Do not carry out additional charging. When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high pressure, and may cause a rupture or personal injury.
Fig. 3-4-1 Configuration of refrigerant charging
15
Gauge manifold
[ Cylinder with siphon ] [ Cylinder without siphon ]
OUTDOOR unit
Gauge manifold
OUTDOOR unit
Refrigerant
cylinder
Electronic
balance
Electronic
balance
Siphon
1. Be sure to make setting so that liquid can be charged.
2. When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant. Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the cylinder upside down if cylinder is not equipped with siphon.
R410A refrigerant is HFC mixed refrigerant. Therefore, if it is charged with gas, the composi­tion of the charged refrigerant changes and the characteristics of the equipment varies.
3-5. Brazing of Pipes
3-5-1. Materials for Brazing
1. Silver brazing filler
Silver brazing filler is an alloy mainly composed of silver and copper. It is used to join iron, copper or copper alloy, and is relatively expensive though it excels in solderability.
2. Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
3. Low temperature brazing filler
Low temperature brazing filler is generally called solder, and is an alloy of tin and lead. Since it is weak in adhesive strength, do not use it for refrigerant pipes.
1. Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution, which may cause a gas leakage. Therefore, use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2. When performing brazing again at time of servicing, use the same type of brazing filler.
3-5-2. Flux
1. Reason why flux is necessary
By removing the oxide film and any f oreign matter on the metal surface, it assists the flow of brazing filler.
In the brazing process, it prev ents the metal surface from being oxidized.
By reducing the brazing fillers surface tension, the brazing filler adheres better to the treated metal.
Fig. 3-4-2
Refrigerant
cylinder
16
Nitrogen gas
cylinder
Pipe
Flow meter
M
Stop valve
From Nitrogen cylinder
Nitrogen gas
Rubber plug
2. Characteristics required for flux
Activated temperature of flux coincides with the brazing temperature.
Due to a wide effective temperature r ange, flux is hard to carbonize.
It is easy to remove slag after brazing.
The corrosive action to the treated metal and
brazing filler is minimum.
It excels in coating performance and is harm­less to the human body.
As the flux works in a complicated manner as described above, it is necessary to select an adequate type of flux according to the type and shape of treated metal, type of brazing filler and brazing method, etc.
3. Types of flux
• Noncorrosive flux
Generally, it is a compound of borax and boric acid. It is effective in case where the brazing tem­perature is higher than 800°C.
• Activated flux
Most of fluxes generally used for silver brazing are this type. It features an increased o xide film removing capability due to the addition of compounds such as potassium fluoride, potassium chloride and sodium fluoride to the borax-boric acid compound.
4. Piping materials for brazing and used brazing filler/flux
1. Do not enter flux into the refrigeration cycle.
2. When chlorine contained in the flux remains within the pipe, the lubricating oil deteriorates. Therefore, use a flux which does not contain chlorine.
3. When adding water to the flux, use water which does not contain chlorine (e.g. distilled water or ion-exchange water).
4. Remove the flux after brazing.
3-5-3. Brazing
As brazing work requires sophisticated techniques, experiences based upon a theoretical knowledge, it must be performed by a person qualified.
In order to prevent the oxide film from occurring in the pipe interior during brazing, it is effective to proceed with brazing while letting dry Nitrogen gas (N2) flow.
Never use gas other than Nitrogen gas.
1. Brazing method to prevent oxidation
1) Attach a reducing valve and a flow-meter to the Nitrogen gas cylinder.
2) Use a copper pipe to direct the piping mate­rial, and attach a flow-meter to the cylinder.
3) Apply a seal onto the clearance between the piping material and inserted copper pipe for Nitrogen in order to prevent backflow of the Nitrogen gas.
4) When the Nitrogen gas is flowing, be sure to keep the piping end open.
5) Adjust the flow rate of Nitrogen gas so that it is lower than 0.05 m3/Hr or 0.02 MPa (0.2kgf/cm2) by means of the reducing valve.
6) After performing the steps above, keep the Nitrogen gas flowing until the pipe cools down to a certain extent (temperature at which pipes are touchable with hands).
7) Remove the flux completely after brazing.
Fig. 3-5-1 Prevention of oxidation during brazing
Piping material
Copper - Copper
Copper - Iron
Iron - Iron
Used brazing filler
Phosphor copper
Silver Silver
Used flux
Do not use
Paste flux Vapor flux
FILE NO. SVM-15006
4. CONSTRUCTION VIEWS
4-1. Indoor Unit
17
190
160.5 160.5 150
215
235
235
215
275
84.5
84.5
40
45
84.5 150 84.5
40
Installation plate outline
Hanger
Hanger
Center line
Hanger
621
Drain hose (0.40m)
Connecting pipe (0.40m)
(Flare 6.35mm)
480
Installation plate hanger
Installation plate hanger
116
170 or more
170 or more
65 or more
Minimum distance
to wall
Minimum
distance
to wall
Minimum
distance
to ceiling
Connecting pipe (0.35m) (for 10 series : Flare 9.52mm) (for 13 series : Flare 12.7mm)
194
Air filter
Air filter
Heat exchanger
790
48
63
7
Front panel
217
63
7
48
Wireless remote controller
63
Remote controller holder
17.5
149
57
172
18
18
4-2. Outdoor Unit
320
306
30
Z View
600
A detail Drawing (Back leg)
320
306
Ø
25 Drain outlet
11 x 14
Hole
(For 8 -
10 anchor bolt)
B Detail Drawing (Front leg)
FAN-GUARD
COVER-PV
Liquid side (Flare 6.35)
Ø
Flare Ø 9.52:10,13k)
Gas side (
Service port
2 - ∅11 x 14 Long holes (For ∅8 - ∅10 anchor bolt)
Installation dimension
Air outlel
100 or more
100 or more
600 or more
600 or more
Air intlel
Ø
Ø
Ø
Ø
6 hole
86
Ø
6 hole
Ø
11x14 hole
R
15
28
A
320
R5.5
36
108 125
50
137
92
5
4
600
320
9060090
275
290
550
Ø
436
Z
R
15
50
36
-
2
320
342
69
2 - R5-5 x 17L Ushape
(For 8 - 10 anchor bolt)
FILE NO. SVM-15006
(Flare Ø 12.7:16k)
19 –
FILE NO. SVM-15006
5. WIRING DIAGRAM
CN62
CN63
6
DB01
ORN
3
21 NL
F01 FUSE 25A
P03
C07
ABSORBER
SURGE
5 4 3 2 1
CM
COMPRESSOR
3
3
BLK
WHI
RED
1 2
1 2
P09
P10 P11
6
2
2
TD
TEMP. SENSOR)
(DISCHARGE PIPE
TEMP. SENSOR)
(OUTDOOR
TO
1
3
1
1
3 2
1
TEMP. SENSOR)
(SUCTION PIPE
TS
3
1
2 1
3
PMV
5 4 3 2 1
IPM module
VARISTOR
COIL FOR 4WAY VALVE
F02
FUSE
3.15A
(From Main Line)
C08
RAS-B10N3KV2-E1 / RAS-10N3AV2-E1 RAS-B13N3KV2-E1 / RAS-13N3AV2-E1
20
FILE NO. SVM-15006
RAS-B16N3KV2-E1 / RAS-16N3AV2-E
P22
Compressor
CM
P. C. Board
MCC-5009
RED WHI
BLK
P04 P05 P06
P25
YEL
P24
R221
Q200 ~ 205 IGBT
Q300 ~ 305 MOS-FET
CN300
CN700
CN603
CN602
CN601
CN600
Suction pipe
Temp. Sensor
(TS)
Fan Motor
Pulse Motor Valve
FM
1 2 3
1 2
P11
P08
P32
PUR
P33 P30 BLK
CN701 P07
ORN
BLK
WHI
P03
P10
P02
P31
Q404
CT
3
BLK WHI RED
3 2 1
3 2 1
6 5 4
6 5
4 3 3 2 2 1 1
3 2 1
3
2
1
P23
YEL
P34
P35 L03
L01
Varistor
Varistor
Surge
Absorber
F01 Fuse 250V ~, T25A
Power Relay
Relay
DB01
DB02
C12 C14
C13
YEL
P21
BRW
P20
R220
R219
PMV
Discharge pipe
Temp. Sensor
(TD)
3 2 1
3
2
1
Condenser pipe
Temp. Sensor
(TE)
212
1
Outdoor
Temp. Sensor
(TO)
212
1
R321
R320
R319
P19
P18
Reactor
Reactor
Coil for
4-way Valve
ORN
+ + +
121
2
112
2
11223
3
F03 Fuse 250V ~, T3.15A
1 2 3 L N
N
Power Supply (From Main Line)
6-1. Indoor Unit
6-2. Outdoor Unit
No.
Parts name Type Specifications
RPG-240-25A
AC 240V, 20W
2 Room temp. sensor (TA-sensor) ( - ) 10k at 25°C 3 Heat exchanger temp. sensor (TC-sensor) ( - ) 10k at 25°C 4 Louver motor
24BYJ48-HTP
Output (Rated) 1W, 16 poles, DC12V
No. Parts name Type Specifications
L = 19mH, 10A
2 Outdoor fan motor ICF-140-43-4R DC140V, 43W 3 Suction temp. sensor (TS sensor) (Inverter attached) 10k (25°C) 4 Discharge temp. sensor (TD sensor) (Inverter attached) 62k (20°C) 5 Outside air temp. sensor (TO sensor) (Inverter attached) 10k (25°C) 6 Heat exchanger temp. sensor (TE sensor) (Inverter attached) 10k (25°C)
Reactor
1
1
Fan motor
(RAS-B10N3KV2-E1, RAS-B13N3KV2-E1)
20A, AC250V
ASM89D16UEZ
CAM-MD12TCTH-5
SQA2522G-000352
3-phases 4-poles 750W
DC12V AC220-240V
Coil for 4-way valve
Coil for PMV
Compressor
Terminal block (5P)7
8
9
10
CH-69
6. SPECIFICATIONS OF ELECTRICAL PARTS
FILE NO. SVM-15006
21
JX0-5B
(RAS-B16N3KV2-E1)
DC 340V, 30W
MF-340-30-3
CH-57
L = 10mH, 16A
10, 13k
16k
DA131S1B-31FZ
3-phases 4-poles 1100W
10, 13k
16k
STF-H01AJ1872A1
AC220-240V
10, 13k
16k
FILE NO. SVM-15006
22
7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
RAS-B10N3KV2-E1 / RAS-10N3AV2-E1
RAS-B13N3KV2-E1 / RAS-13N3AV2-E1
NOTE :
The maximum pipe length of this air conditioner is 20 m. When the pipe length exceeds 15m, the additional
Deoxidized copper pipe Outer dia. : 9.52mm Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
TC
TA
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P
Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side
TD
4-way valve
Compressor ASM89D16UFZ
TS
T2
Outdoor heat
exchanger
Temp. measurement
Propeller fan
Refrigerant amount : 0.80kg
OUTDOOR UNIT
Muffler
Muffler
TE
Min. : 2m Chargeless : 15m
Strainer
Max. : 20m
Charge : 20g/m (16 to 20m)
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
RAS-B16N3KV2-E1 / RAS-16N3AV2-E
23
NOTE :
Deoxidized copper pipe
Outer dia. : 12.7mm(16)
Thickness : 0.8mm
NOTE :
Gas leak check position Refrigerant flow (Cooling) Refrigerant flow (Heating)
T1
TO
Temp. measurement
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe Outer dia. : 6.35mm Thickness : 0.8mm
Sectional shape of heat insulator
Allowable height
difference : 10m
Allowable pipe length
P Pressure measurement Gauge attaching port
Vacuum pump connecting port
Strainer
Pulse Modulating valve at liquid side
Ø1.2 x 80 Ø1.2 x 80
TD
4-way valve
Compressor DA131S1B-31FZ
TS
T2
Outdoor heat
exchanger
Split capillary
Temp. measurement
Refrigerant amount : 1.10kg
Propeller fan
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
The maximum pipe length of this air conditioner is 15 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 100g)
Max. : 20m
Min. : 2m Chargeless : 15m
Charge : 20g/m (16 to 20m)
TCJ
24 –
FILE NO. SVM-15006
7-2. Operation Data
<Cooling>
<Heating>
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent. (Thermistor themometer)
2. Connecting piping condition : 5 m
Model name Standard Indoor Outdoor Compressor
RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
27/19 35/-
B10N3KV2-E1
0.9 to 1.1 12 to 14 37 to 39 High High 49
0.8 to 1.0 11 to 13 46 to 48 High High 75
condition(°C)
Tempeature Heat exchanger
pipe temp.
Model name Standard Indoor Outdoor Compressor RAS- pressure fan mode fan mode revolution
Indoor Outdoor P (MPa) T1 (°C) T2 (°C) (rps)
20/- 7/6 2.5 to 2.7 39 to 41 0 to 3 High High 60
2.6 to 2.8 41 to 43 0 to 2 High High 80
condition(°C)
Tempeature Heat exchanger
pipe temp.
B13N3KV2-E1
B10N3KV2-E1 B13N3KV2-E1
B16N3KV2-E1
0.8 to 1.0 11 to 13 40 to 42 High High 71
2.7 to 2.9 43 to 45 0 to 2 High High 72
B16N3KV2-E1
25
8. CONTROL BLOCK DIAGRAM
8-1. Indoor Unit
FILE NO. SVM-15006
M.C.U.
Indoor Unit Control Unit
Power Supply
(From Outdoor Unit)
Serial Signal Communication
(Operation Command and Information)
Serial Signal Transmitter/Receiver
Converter
(D.C circuit)
Noise Filter
Indoor
Fan Motor
Louver
Motor
Louver Motor Drive Control
Indoor Fan
Motor Control
Initializing Circuit
Clock Frequency
Oscillator Circuit
Power Supply
Circuit
Infrared Rays, 36.7kHz
Remote Controller
Thermo. Setting
Fan Speed Selection
ON TIMER Setting
OFF TIMER Setting
Louver AUTO Swing
Louver Direction Setting
QUIET
Operation Mode Selection
AUTO, COOL, DRY, HEAT
REMOTE CONTROLLER
ECO
Hi-POWER
Heat Exchanger Sensor (Tc)
Room Temperature Sensor (Ta)
Infrared Rays Signal Receiver
and Indication
Functions
Cold draft preventing Function
3-minute Delay at Restart for Compressor
Fan Motor Starting Control
Processing (Temperature Processing)
Timer
Serial Signal Communication
Clean Function
Operation [ ]
COMFORT SLEEP
26
8-2. Outdoor Unit (Inverter Assembly)
220–240V ~50Hz
MICRO-COMPUTER BLOCK DIAGRAM
Driver circuit
of P.M.V.
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
Indoor unit
send/receive
circuit
Relay
circuit
Noise
Filter
Converter
(AC DC)
Clock
frequency
10MHz
High Power
factor Correction
circuit
Input current
sensor
PWM synthesis function
Input current release control
IPM over-current detect control
Outdoor fan control
High power factor correction control
Inverter output frequency control
A/D converter function
P.M.V. control
Discharge temp. control
4-way valve control
Signal communication to indoor unit
P.M.V. : Pulse Motor Valve
M.C.U. : Micro Control Unit
M.C.U
For INDOOR UNIT
4-way
valve
P.M.V.
Inverter
(DC AC)
Gate drive
circuit
Gate drive
circuit
Inverter
(DC AC)
Outdoor
Fan motor
Compressor
WP-030 (P.C.B)
OUTDOOR UNIT
Current
detect
Current
detect
FILE N. SVM-15006
220
230V ~60Hz
RAS-B10N3KV2-E1 / RAS-10N3AV2-E1
RAS-B13N3KV2-E1 / RAS-13N3AV2-E1
27
220–240V~ 50Hz
MICRO-COMPUTER BLOCK DIAGRAM
Driver circuit
of P.M.V.
Heat exchanger
temp.sensor
Suction temp.
sensor
Outdoor air
temp. sensor
Discharge
temp. sensor
Indoor unit
send/receive
circuit
Relay
circuit
Noise
Filter
Converter
(AC DC)
Clock
frequency
4MHz
High Power
factor Correction
circuit
Input current
sensor
• PWM synthesis function
• Input current release control
• IGBT over-current detect control
• Outdoor fan control
• High power factor correction control
• Inverter output frequency control
• A/D converter function
• P.M.V. control
• Discharge temp. control
• 4-way valve control
• Signal communication to indoor unit
P.M.V. : Pulse Motor Valve
M.C.U. : Micro Control Unit
M.C.U
For INDOOR UNIT
4-way
valve
P.M.V.
Inverter
(DC AC)
Gate drive
circuit
Gate drive
circuit
Inverter
(DC AC)
Outdoor
Fan motor
Compressor
MCC5009 (P.C.B) OUTDOOR UNIT
Current
detect
Current
detect
FILE NO. SVM-15006
RAS-B16N3KV2-E1 / RAS-16N3AV2-E
FILE NO. SVM-15006
28
  
9. OPERATION DESCRIPTION
9-1. Outline of Air Conditioner Control
This air conditioner is a capacity-variable type air conditioner, which uses AC or DC motor for the indoor for motor and the outdoor fan motor. And the capacity­proportional control compressor which can change the motor speed in the range from 11 to 96 rps is mounted. The DC motor drive circuit is mounted to the indoor unit. The compressor and the inverter to control fan motor are mounted to the outdoor unit.
The entire air conditioner is mainly controlled by the indoor unit controller.
The indoor unit controller drives the indoor fan motor based upon command sent from the remote controller, and transfers the operation command to the outdoor unit controller.
The outdoor unit controller receives operation com­mand from the indoor unit side, and controls the outdoor fan and the pulse Modulating valve. (P.M.V) Besides, detecting revolution position of the compres­sor motor, the outdoor unit controller controls speed of the compressor motor by controlling output voltage of the inverter and switching timing of the supply power (current transfer timing) so that motors drive according to the operation command. And then, the outdoor unit controller transfers reversely the operating status information of the outdoor unit to control the indoor unit controller.
As the compressor adopts four-pole brushless DC motor, the frequency of the supply power from inverter to compressor is two-times cycles of the actual number of revolution.
1. Role of indoor unit controller
The indoor unit controller judges the operation commands from the remote controller and assumes the following functions.
Judgment of suction air temperature of the indoor heat exchanger by using the indoor temp. sensor. (TA sensor)
Judgment of the indoor heat exchanger tempera­ture by using heat exchanger sensor (TC sensor) (Prevent-freezing control, etc.)
Louver motor control
Indoor fan motor operation control
LED (Light Emitting Diode) display control
Transferring of operation command signal (Serial
signal) to the outdoor unit
Reception of information of operation status (Serial signal including outside temp. data) to the outdoor unit and judgment/display of error
Air purifier operation control
2. Role of outdoor unit controller
Receiving the operation command signal (Serial signal) from the indoor unit controller, the outdoor unit performs its role.
Compressor operation control
Operation control of outdoor fan motor
P.M.V. control
4-way valve control
Operations followed to judgment of serial signal from indoor side.
Detection of inverter input current and current release operation
Over-current detection and prevention operation to IGBT module (Compressor stop function)
Compressor and outdoor fan stop function when serial signal is off (when the serial signal does not reach the board assembly of outdoor control by trouble of the signal system)
Transferring of operation information (Serial signal) from outdoor unit controller to indoor unit controller
Detection of outdoor temperature and operation revolution control
Defrost control in heating operation (Temp. measurement by outdoor heat exchanger and control for 4-way valve and outdoor fan)
3. Contents of operation command signal (Serial signal) from indoor unit controller to outdoor unit controller
The following three types of signals are sent from the indoor unit controller.
Operation mode set on the remote controller
Compressor revolution command signal defined
by indoor temperature and set temperature (Correction along with variation of room tempera­ture and correction of indoor heat exchanger temperature are added.)
Temperature of indoor heat exchanger
For these signals ([Operation mode] and [Com-
pressor revolution] indoor heat exchanger tem­perature), the outdoor unit controller monitors the input current to the inverter, and performs the followed operation within the range that current does not exceed the allowable value.
4. Contents of operation command signal (Serial signal) from outdoor unit controller to indoor unit controller
The following signals are sent from the outdoor unit controller.
The current operation mode
The current compressor revolution
Outdoor temperature
Existence of protective circuit operation
For transferring of these signals, the indoor unit controller monitors the contents of signals, and judges existence of trouble occurrence.
Contents of judgment are described below.
Whether distinction of the current operation status meets to the operation command signal
Whether protective circuit operates When no signal is received from the outdoor
unit controller, it is assumed as a trouble.
29
9-2. Operation Description
1.
Basic operation ........................................................................................................... 30
1.
Operation control ................................................................................................... 30
2.
Cooling/Heating operation ..................................................................................... 31
3. AUTO operation
4.
DRY operation........................................................................................................ 31
2.
Indoor fan motor control ............................................................................................. 32
3.
Outdoor fan motor control........................................................................................... 34
4.
Capacity control .......................................................................................................... 35
5.
Current release control ............................................................................................... 35
6.
Release protective control by temperature of indoor heat exchanger........................ 36
7.
Defrost control (Only in heating operation) ................................................................ 37
8.
Louver control ............................................................................................................. 39
1)
Louver position....................................................................................................... 39
2)
Air direction adjustment ......................................................................................... 39
3)
Swing
..................................................................................................................... 39
9.
ECO operation ............................................................................................................ 40
10.
Temporary operation ................................................................................................... 41
11.
12.
Discharge temperature control ...................................................................................... 41
13.
Pulse
Modulating valve (P.M.V.) control ......................................................................... 42
Self-Cleaning function ................................................................................................... 43
14.
15.
Remote-A or B selection ...................................
............................................................ 44
9-3. Auto Restart Function ..
9-3-1. How to Set the A uto Restart Function ...........................................................
............ 47
9-3-2. How to C
ancel the Au to Restar t Function ................................................................. 48
9-3-3. Power Failure During Timer Operation ............
........................................................ 48
19.
FIL
TER Indicator ...............................................................................................46
9-4. Remote Control
16.
QUIET
mode ................................................................................................................ 45
COMFORT SLEEP mode ............................................................................................ 4
5
17.
18.
One-To
uch Comfort ..................................................................................................... 45
Hi-POWER Mode ........................................
................................................................ 46
FILE NO. SVM-15006
..................................................................................................... 31
9-4-3. Display of Remote Control ........................................................................................ 52
9-4-1. Function of Push Putton ....
........................................................................................ 49
9-4-2. Operation of remote control .........................
............................................................. 49
Loading...
+ 93 hidden pages