4-1 Indoor Unit (RAS-10GKHP-ES2, RAS-10GKHP-AS2)
4-2 Outdoor Unit (RAS-10GAH-ES2, RAS-10GAH-AS2)
4-3 Indoor Unit (RAS-10GKP-ES2, RAS-10GKP-AS2)
4-4 Outdoor Unit (RAS-10GA-ES2, RAS-10GA-AS2)
Outline of Air Conditioner Control
7-2 Description of Operation Circuit
7-3 Hi POWER Mode
7-4 High-Temperature Limit Control
7-5 Low-Temperature Limit Control
7-6 Defrost Operation
7-7 Current Limit Control
7-8 Auto Restart Function
7-9 Self-Cleaning function
7-10 QUIET Mode
7-11 COMFORT SLEEP mode
− 1 −
8.INSTALLATION PROCEDURE
8-1 Safety Cautions
8-2 Installation Diagram of Indoor and Outdoor Units
8-3 Installation
8-4 Indoor Unit
8-5 Outdoor Unit
8-6 How to Set Remote Control Selector Switch
8-7 Others
9.TROUBLESHOOTING CHART
9-1 Troubleshooting Procedure
9-2 Basic Check Items
9-3 Primary Judgement
9-4 Self-Diagnosis by Remote Control (Check Code)
9-5 Troubleshooting Flowcharts
9-6 Troubleshooting for Remote Control (Including The Indoor P.C. Board)
10. PARTS REPLACEMENT
10-1 Indoor Unit
10-2 Outdoor Unit
FILE NO. SVM-06039
11. EXPLODED VIEWS AND PARTS LIST
11-1 Indoor Unit (E-Parts Assy) (For RAS-10GKHP-ES2, RAS-10GKP-ES2)
11-2 Indoor Unit (E-Parts Assy) (For RAS-10GKHP-AS2, RAS-10GKP-AS2)
Indoor Unit
11-3
11-4 Outdoor Unit (RAS-10GAH-ES2, RAS-10GNAH-AS2)
11-5 Outdoor Unit (RAS-10GA-ES2, RAS-10GA-AS2)
• This air conditioner is charged with
HFC (R410A) that doesn't deplete the
Ozone layer.
• This air conditioner requires special
installation for the refrigerant R410A.
− 2 −
1. SPECIFICATIONS
FILE NO. SVM-06039
MODEL
ITEMCoolingHeatingCooling
Capacity
Power sourceV220 − 240
Power consumption kW 0.83 0.85 0.79 0.82 0.83 0.85
Power factor%989797969897
RunningIndoorA0.15
current Outdoor A 3.71 3.503.55 3.40 3.71 3.50
Starting currentA18
Moisture removallit/h1.2
Noise
Refrigerant
Refrigerant controlCapillary tube
Interconnection
pipe
INDOOR UNIT
Dimensions Width mm 740
Net weight kg 8
Evaporator type Finned tube
Indoor fan typeCross flow fan
Air volume Medium fan m3/h 460 480 460
Fan motor outputW20
Air filterHoneycomb woven filter with PP frame
OUTDOOR UNIT
DimensionsWidthmm780
Net weight kg 3130
Condenser typeFinned tube
Outdoor fan typePropeller fan
Airflow volume m3/h203021502030215017401850
Fan motor outputW3020
Compressor
Safety deviceFuse, Overload relay
Louver typeAutomatic louver
Usable outdoor temperature range °C 15 ~ 43 −10 ~ 24 15 ~ 43
Indoor (H/M/L) dB 39/35/31
Outdoor (220-240V) dB474947494647
Name of refrigerantR410A
Rated amount kg 0.78
Gas side size mm ∅ 9.52
Connection typeFlare connection
Liquid side size mm ∅ 6.35
Connection typeFlare connection
Maximum length
(One way)
Maximum height
difference
Height mm 250
Depth mm 185
High fan m3/h 540 560 540
Low fan m3/h 380 390 380
Heightmm550
Depth mm 290
ModelPA108X1C-4FZDN
Output W750
kW 2.73 2.73 2.92 2.96 2.73 2.73
Phase 1∅
Hz 50
m10*
m 5
RAS-10GKHP-ES2 / RAS-10GAH-ES2
RAS-10GKHP-AS2 / RAS-10GAH-AS2
220V240V220V240V220V240V
1
RAS-10GKHP-ES2
RAS-10GAH-ES2
RAS-10GAH-AS2RAS-10GA-ES2
RAS-10GKP-ES2 / RAS-10GA-ES2
RAS-10GKP-AS2 / RAS-10GA-AS2
0.72
RAS-10GKP-ES2
RAS-10GKP-AS2RAS-10GKHP-AS2
RAS-10GA-ES2
− 3 −
Note : 1
• Capacity is based on the following temperature conditions.
This is a fixed capacity type air conditioner, which uses
AC motor for an indoor fan. The AC motor drive
circuit is mounted in the indoor unit. And electrical
parts which driving the compressor and the outdoor
fan motor, are mounted in the outdoor unit.
The air conditioner is controlled by the controller
mounted in the indoor unit. The controller operates all
components based on the commands transmitted from
the remote control and the feedback data of the sensor
is as follow:
• The temperature measurement at the air inlet of
the indoor heat exchanger by the indoor
temperature sensor
•The temperature measurement at the indoor
heat exchanger by the indoor heat exchanger
temperature sensor
• Indoor fan motor operation control
• Louver motor control
• LED display control
• Outdoor fan motor operation control
• 4-WAYS-VALVE operation control
(Heat pump model only)
• Compressor operation control
• Receiving the information of the operation
status and judging the information or the
indication of errors
7-1-1. Louver control
(1) Vertical air flow louver
Position of veritcal air flow louver is automatically
controlled according to the operation mode.
Besides, position of vertical air flow louver can be
arbitrarily set by pressing [FIX] button.
The louver position which is set by [FIX] button is
stored in the microcontroller, and the louver is
automatically set at the stored position for the next
operation.
(2) Swing
If [SWING] button is pressed when the indoor unit
is in operation, the vertical air flow louver starts
swinging. When [SWING] button is pressed again,
it stops swinging.
7-1-2. Indoor fan control (AC Fan motor)
(1) The indoor fan is operated by the stepless speed
change AC motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
+
, MED, MED
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
(1) When turning on the breaker, the operation lamp
blinks. This means that the power supply is on.
(2) When pressing [ ] button on the remote control,
receiving beep sounds from the indoor unit, and
the next operation is performed together with
opening the vertical air flow louver.
(3) Once the operation mode is set, it is memorized in
the microcontroller so that the previous operation
can be effected thereafter simply by pressing
[ ] button.
7-2-1. Fan only operation
([MODE] button on the remote control is set
to the fan only operation.)
(1) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-1. When
[FAN] button is set to LOW, LOW
HIGH, the motor operates with a constant air flow.
°C
+3
+2.5
+2
-
+1.5
+1
+0.5
(Room temp.) (Preset temp.)
Preset
temp.
0
(Preset temp.: 22°C)
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
(2) The Hi POWER, ECO and COMFORT SLEEP
operation cannot be set.
Fig. 7-2-1 Setting of air flow [FAN:AUTO]
+
, MED, MED+ or
M+
*1
*1
*1
-
L
7-2-2. Cooling operation
([MODE] button on the remote control is set
to the cooling operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-2.
°C
ONON
OFF OFF OFF ON
4-way valve
Compressor
Outdoor fan
OPERATION
-
(Room temp.) (Preset temp.)
Preset
temp.
0.5
0
Fig. 7-2-2
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-3. When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
°C
(Preset temp.)
−
(Room temp.)
Preset
temp.
+3
+2.5
+2
+1.5
+1
+0.5
0
-0.5
M+
*1
*1
*1
-
L
NOTE :
*1: The values marked with *1 are calculated and
controlled by the difference in motor speed
between M+ and L-.
display
- 16 -
Fig. 7-2-3 Setting of air flow [FAN:AUTO]
FILE NO. SVM-06039
7-2-3. Dry operation
([MODE] button on the remote control is set
to the dry operation.)
(1) The compressor, 4-way valve, outdoor fan and
operation display on the remote control are
controlled as shown in Fig. 7-2-4.
°C
ON:6min.
-
(Room temp.) (Preset temp.)
Preset
temp.
+3
+2
+1
ON:6min.
OFF:4min.
ON:5min.
OFF:5min.
OFF
0
Compressor
OFF
ON:5min.
OFF
4-way valve
OFF:4min.
OFF:5min.
Outdoor fan
Fig. 7-2-4
7-2-4. Heating operation *Heat pump model only
(1) The compressor, 4-way valve, outdoor fan and
ON
display
OPERATION
([MODE] button on the remote control is set
to the heating operation.)
operation display on the remote control are
controlled as shown in Fig. 7-2-6.
°C
Preset
temp.
0
-0.5
-
(Room temp.) (Preset temp.)
ON
OFF
ON
Compressor
4-way valve
Fig. 7-2-6
ON
OFF
ON
Outdoor fan
display
OPERATION
(2) The microcontroller turns the compressor on and
off at the regular intervals (4 to 6 minutes). While
the compressor is turning off, the indoor fan motor
operates in the SUPER LOW position.
The pattern of operation depending on the relation
between room temperature and preset
temperatures is shown in Fig. 7-2-5.
Room temp.
Preset temp.+1
Preset temp.
Compressor
Outdoor fan
Indoor fan
ONONONON
OFFOFFOFF
L *SL SLLL SL L
*
Super Low
Fig. 7-2-5
(3) [FAN] button on the remote control is set to AUTO
only.
(2) When [FAN] button is set to AUTO, the indoor fan
motor operates as shown in Fig. 7-2-7. When
[FAN] button is set to LOW, LOW
+
, MED, MED+ or
HIGH, the motor operates with a constant air flow.
Preset
temp.
°C
0
-0.5
-1
-1.5
-2
-
-5.0
-5.5
[FAN AUTO]
(Room temp.) (Preset temp.)
L
*1
*2
+
M
H
*1, *2 : The values marked with *1 and *2 are
calculated and controlled by the difference in
motor speed between M+ and L.
Fig. 7-2-7 Setting of air flow [FAN:AUTO]
(4) The Hi POWER, ECO, COMFORT SLEEP and
QUIET operations cannot be set.
- 17 -
FILE NO. SVM-06039
(3) The indoor heat exchanger restricts revolving
speed of the fan motor to prevent a cold draft. The
upper limit of the revolving speed is shown in
Fig. 7-2-8 and Table 7-2-1.
10GKH Series
°C
434232
31
323121
20
*2
A+4
A+4
A
−
8
A
−
8
*6*5
Indoor heat exchanger temperature
AUTO
*4
*3
SL
SL*1
Stop
Manual
(One of 5 steps)
L- H (Up to
seting speed)
Fig. 7-2-8 Cold draft preventing control
NOTES :
*1: The fan stops for 2 minutes after thermostat-OFF.
*2: A is 24 °C when the preset temperature is 24°C or
more and A is the preset temperature when it is
under 24 °C.
*3: SL means Super Low.
*4: Calculated from difference in motor speed
between SL and H.
*5 and *6:
Table 7-2-1
Fan*5*6
speedStarting periodStabilized period
·
AUTOUp until 12 minutes
ManualRoom temperature
(L H)< Preset temperature
-
·
passed after starting
the unit
·
From 12 to 25 minutes
passed after starting
the unit and room
temperature is 3 °C
lower than preset
temperature
·
·
-
From 12 to 25 minutes
passed after starting
the unit and room
temperature is
between preset
temperature and 3 °C
lower than preset
temperature
25 minutes or more
·
passed after starting
the unit
Room temperature
·
Preset temperature
4 °C
-
3.5 °C
7-2-5. Automatic operation
([MODE] button on the remote control is set
to the automatic operation.)
(1) One of 3 operations (Cooling, Fan only or Heating)
is selected according to difference between the
preset temperature and the room temperature at
which the automatic operation has started, as
shown in Fig. 7-2-9. The Fan only operation
continues until the room temperature reaches a
level at which another mode is selected.
(2) Temporary Auto
When the [RESET] button on the indoor unit
is pushed, the preset temperature is fixed at 24 °C
and the indoor unit is controlled as shown in
Fig. 7-2-9.
-
-
(Room temp.) (Preset temp.)
-
18
°C
Cooling operation
The louver moves to the position same
as Hi POWER operation.
+4
Cooling operation
0
Fan only operation
1
-
Heating operation
GKH Series GK Series
Fig. 7-2-9
FILE NO. SVM-06039
7-3. Hi POWER Mode
([Hi POWER] button on the remote
control is pressed.)
When [Hi POWER] button is pressed while the indoor
unit is in Auto, Cooling or Heating operation, Hi
POWER mark is indicated on the display of the remote
control and the unit operates as follows.
(1) Automatic operation
The indoor unit operates in according to the
·
current operation.
(2) Cooling operation
• The setting temperature drops 3°C.
(The value of the setting temperature on the
remote control does not change.)
• If the room temperature is higher than the
setting temperature by 3.5°C or more, the
horizontal louver moves to the Hi POWER
position automatically. Then when the room
temperature is 1°C less than the setting
temperature the horizontal louver returns
automatically.
• FAN speed : [AUTO]
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at maximum airflow level.
If the room temperature is higher than the
setting temperature by less than 3.5°C, the air
conditioner operates at normal airflow level.
• FAN speed : One of 5 levels
If the room temperature is higher than the
setting temperature by 3.5°C or more, the air
conditioner operates at higher consecutive
airflow level. If the room temperature is higher
than the setting temperature by less than 3.5°C,
the air conditioner operates at normal airflow
level.
7-4. High-Temperature Limit Control
*Heat pump model only
The microcontroller detects the indoor heat exchanger
temperature to prevent pressure of a refrigerating cycle
from increasing excessively.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-4-1.
Compressor
OFF
ON
ON
Outdoor fan
OFF
OFF
ON
Heat exchanger
temp.
(°C)
60
53
52
Fig. 7-4-1
7-5. Low-Temperature Limit Control
The microcontroller detects the indoor heat exchanger
temperature to prevent the indoor heat exchanger from
freezing.
The compressor and outdoor fan motor are controlled
as shown in Fig. 7-5-1 and 7-5-2.
Heat exchanger
temperature
(°C)
5
2
Compressor Outdoor fan
ON
Less than 2°C continues
for 5 minutes
OFF
(3) Heating operation (GKH Series only)
The preset temperature increases 2°C,
·
(The value of the preset temperature on the
remote control does not change.)
The indoor unit operates in normal heating
·
mode except the preset temperature is higher
(+2°C).
(4) The Hi POWER mode can not be set in Dry or Fan
only operation.
-
19