Toshiba MMY-MAP1201HT8, MMY-MAP1001HT8, MMY-MAP0801HT8, MMY-MAP0601HT8 INSTALLATION MANUAL

SUPER MODULAR MULTI
R410A
Quick reference
FILE NO : A04-004
Pipe length
Height difference
Total extended pipe length(Liquid pipe/real length) Farhest equivalent piping length L (*1) Max. equivalent length of main pipe (*3) Farthest equivalent piping length from 1st baranch Li (*1) Farthest equivalent piping length between outdoor units LO (*1) Max. equivalent length of outdoor unit connecting pipe Max. real length of outdoor unit connecting pipe
Outdoor at upper side
Outdoor at lower side Height difference between indoor units H2 Height difference betwenn outdoor units H3
Allowable value
300m 175m
85m 65m 25m 10m 30m 50m
40m (*2)
30m
5m
Height difference between indoor unit and outdoor unit H1
*1 : Farthest outdoor unit: (d), farthest indoor unit: (j) from 1st branch *2 : If the height difference (H2) between indoor units exceeds 3m, set below 30m. *3 : If Max. capacity of the combined outdoor units exceeds 46HP, Max. equivalent length is up to 70m.
Calculation of refrigerant
¥ Keeping valve of the outdoor unit colsed, be sure to charge
the liquid refrigerant into service port at liquid side.
¥ if the specified amount of refrigerant cannot be charged,
open fully valves of outdoor unit at liquid and gas sides,operate the air conditioner in COOL mode under condition that valve at gas side is a little returned to close side (MAP0801*, MAP1001*, MAP1201* only), and then charge refrigerant into service port at gas side. In this time, choke the refrigerant slightly by operating valve of the bomb to charge liquid refrigerant. The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
¥ When refrigerant leaks and refrigerant shortage occurs in
the system, recover the refrigerant in the system and recharge refrigerant newly up to the correct level.
<Entry of refrigerant charge amount>
¥ Fill the additional refrigerant record column of the wiring diagram indication plate with the additional refrigerant amount
at installation work, total refrigerant amount and the name of the service ma who charged refrigerant at installation time.
¥ The total refrigerant amount means the total value of the refrigerant amount at shipment and the additional refrigerant
amount at installation time. the refrigerant amount at the shipment is one described on the ÒUnit nameplateÓ.
After cacuuming work, exchange the vacuum pump with the refrigerant bomb and then start the additional charging work of refrigerant.
Calculation of additional refrigerant carge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipe at the local site. For refrigeranto to be charged in pipe at the local site, calculate the amount and charge it additionally. NOTE) If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without addition of
refrigerant.
Combined HP
(HP)
Combined outdoor units
(HP)
C (Corrective amout
ofrefrigernt) (kg)
Table 1
Table 2
5 6
8 10 12 14 16 18 20
22
24
26 28 30
32
34
36
38 40 42 44 46 48
5 6
8 10 12
8
8 10 10 12
8 12
8 10 10 10 12
8 12 10 12 10 10 10 12 12 12 12
6 8
8 10 10
8 12
8
8 10 10 10
8 12
8 12 10 10 10 10 12 12 12
6
8 8
8 10 10
8 10
8 12
8 10 10 10 10 12 12
8
8
8
8 10 10 10 10 12
0.0
0.0
1.5
2.5
3.5
0.0
0.0
0.0
3.0
5.0
0.0
7.0 Ð4.0 Ð4.0 Ð2.0
0.0
1.0 Ð6.0
3.0 Ð6.0
4.0 Ð6.0 Ð6.0 Ð5.0 Ð4.0 Ð2.0
0.0
2.0
Liquid pipe dia.
(mm)
Additional
refrigerant
amount/1m
quid pipe
(kg/m)
6.4
0.025
9.5
0.055
12.7
0.105
15.9
0.160
19.1
0.250
22.2
0.350
Heat pump model
Outdoor unit Model
(MMY-)
Charging amout (kg)
MAP0501HT* MAP0601HT* MAP0801HT* MAP1001HT* MAP1201HT*
8.5 12.5
Cooling only model
Outdoor unit Model
(MMY-)
Charging amout (kg)
MAP0501T8 MAP0601T8 MAP0801T8 MAP1001T8 MAP1201T8
8.0 11.0
REQUEREMENT
01
Refrigerant Piping
Allowable length of refrigerant pipe and height difference Addition of refrigerant
Max. No. of outdoor units Max. capacity of outdoor units Max. No. of indoor units
¥ Coutions concerned with
installation/construction
1) The leading outdoor unit connected with the indoor inter-unit pipe is madeÒA(Header unit)Ó.
2) Set the units in order of the outdoor capacity.(A (Header unit) ³ B ³ C ³ D)
3) For the combination of the outdoor units, refer to ÒCombination of outdoor unitÓ list.
02
D
(d)
(c)
(b)
(a)
La Lc
Ld
Lb
LA LB
Y-joint
aedcb
L7
L4
L6
L5
Outdoor unit
outdoor unit connecting pipe
Main connecting piping between outdoor units Length corresponded to farthest piping between outdoor units LO ² 25 m
T-shape branching joint
Main piping
1st branching section
L3
Indoor unit
Indoor unit
Height difference between indoor units H2 ² 30 m
Equivalent length corresponded to farthest piping L ² 175 m
Equivalent length corresponded to farthest piping after 1st branching Li ² 65 m
Connecting piping of indoor unit
Branching pipe L2
Branching
header
Header unit
Follower unit 1
Follower unit 2
Height difference between outdoor units H3²5m
Height difference between outdoor units H1 ² 50 m
¥ Restriction to the system
¥ Allowable length/height difference of the refrigerant pipe
Max. capacity of indoor units (Depond on by height dif. between indoor units)
H2 < 15m
15m < H2 < 30m
135% of capa. of outdoor unit 105% of capa. of outdoor unit
4 units
48HP
48 units
fjihg
Refrigerant Piping Diagram <Outdoor>
Inverter Unit 5, 8HP Model: MMY-MAP0501HT, MAP0601HT
03
04
Capillary tube
Capillary
tube
Capillary tube
Propeller fan
Fan motor
Sensor
(TO)
Sensor (TS1)
Sensor
(TL)
Sensor (TE1)
(Right side)
(Left side)
Solenoid valve
(SV2)
Solenoid valve (SV5)
Solenoid valve (SV41)
Solenoid valve (SV3A)
Solenoid valve (SV3E)
Solenoid valve (SV3B)
Solenoid valve (SV3D)
Solenoid valve (SV3C)
4-Way valve
Check joint
Low-pressure sensor
Accumulator
Check joint
Check joint
High-pressure sensor
High-pressure switch
Oil
separator
Check valve
Check
valve
Check
valve
Check
valve
Check valve
Compressor 1
(Inverter)
Strainer
Strainer
Sensor (TK1)
Sensor (TK4)
Sensor (TK3)
Capillary tube
Capillary tube
Capillary tube
Strainer
Strainer
Strainer
(PMV1)
Strainer
StrainerStrainer
Capillary tube
Capillary tube
Solenoid valve
(SV42)
High-pressure
switch
Check
valve
Check valve
Compressor 2
(Inverter)
Strainer
Sensor (TK2)
Sensor (TD2)
Sensor (TD1)
Liquid
tank
Oil tank
Balance pipe servise valve
Liquid side servise valve
Gas side servise valve
Pulse motor valve (PMV)
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
M
Inverter Unit 8, 10, 12HP Model: MMY-MAP0801HT, MAP1001HT, MAP1201HT
Capillary tube
Capillary
tube
Capillary tube
Propeller fan
Fan motor
Sensor
(TO)
Sensor (TS1)
Sensor
(TL)
Sensor (TE1)
(Right side)
(Left side)
Solenoid valve
(SV2)
Solenoid valve (SV5)
Solenoid valve (SV41)
Solenoid valve (SV3A)
Solenoid valve (SV3E)
Solenoid valve (SV3B)
Solenoid valve (SV3D)
Solenoid valve (SV3C)
4-Way valve
Check joint
Low-pressure sensor
Accumulator
Check joint
Check joint
High-pressure sensor
High-pressure switch
Oil
separator
Check valve
Check
valve
Check
valve
Check
valve
Check valve
Compressor 1
(Inverter)
Strainer
Strainer
Sensor (TK1)
Sensor (TK4)
Sensor (TK3)
Capillary tube
Capillary tube
Capillary tube
Strainer
Strainer
Strainer
Strainer
StrainerStrainer
Capillary tube
Capillary tube
Solenoid valve
(SV42)
High-pressure
switch
Check
valve
Check valve
Compressor 2
(Inverter)
Strainer
Sensor (TK2)
Sensor (TD2)
Sensor (TD1)
Liquid
tank
Oil tank
Balance pipe servise valve
Liquid side servise valve
Gas side servise valve
Pulse motor valve (PMV)
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
M
(PMV1) (PMV2)
Continued
Check Code List
05
06
Explanation of Functional Parts
Functional outline
Solenoid
valve
Functional part name
4-way valve
Pulse motor valve
Oil separator
Temp. sensor
Pressure
sensor
Heater
Balance pipe
(Connector CN324: Red)
1)Collects oil in the oil tank during OFF time.
2)Supplies oil reserved in the oil tank during ON time. (Connector CN313: Blue)
1)Returns oil supplied in the balance pipe to the compressor.
1.SV3A
2.SV3B
3.SV3C
4.SV3D
6.SV2
5.SV3E
7.SV4 (n)
8.SV5
PMV1, 2
2.TS1
3.TE1
4.TK1, TK2, TK3, TK4
5.TL
6.TO
2. Low
pressure sensor
Compressor case heater
1.TD1 TD2
1.High pressure sensor
Accumulator case heater
(Connector CN314: Black)
1)Pressurizes oil reserved in the oil tank during ON time. (Connector CN323: White)
1)Reserves oil in the oil separator during OFF time, and supplies oil during ON time. (Connector CN323: White)
1)Turns on during operation and balances oil between compressors. (Hot gas bypass) (Connector CN312: White)
1)Low pressure release function
2)High pressure release function
3)Gas balance function during stop time (Start compensation valve of compressor) (Connector CN311: Blue)
1)For gas balance start
2)High pressure release function
3)Low pressure release function (Connector CN310: White) (for Heating model only)
1)Preventive function for high-pressure rising in heating operation (Connector CN317: Blue)
1)Cooling/heating exchange
2)Reverse defrost (Connector CN300, 301: White)
1) Super heat control function in heating operation
2) Liquid line shut-down function while follower unit stops
3) Sub-cool adjustment function in cooling operation
1)Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle)
2)Reserve function of surplus oil (TD1: Connector, CN502: White, TD2: Connector, CN503: Pink)
1)Protection of compressor discharge temp. Used for release
(Connector CN504: White)
1)Controls super heat in heating operation (Connector CN505: Green)
1)Controls defrost in heating operation
2)Controls outdoor fan in heating operation TK1 Connector CN514: Black, TK2 Connector CN515: Green,
TK3 Connector CN516: Red, TK4 Connector CN523: Yellow
1)Judges oil level of the compressor
(Connector CN521: White)
1)Detects under cool in cooling operation
(Connector CN507: Yellow)
1)Detects outside temperature
(Connector CN501: Red)
1)Detects high pressure and controls compressor capacity
2)Detects high pressure in cooling operation, and controls the fan in low
ambient cooling operation
(Connector CN500: White)
1)
Detects low pressure in cooling operation and controls compressor capacity
2)Detects low pressure in heating operation, and controls the super heat
(Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue)
1)Prevents liquid accumulation to compressor
(Connector CN321: Red)
1) Prevents liquid accumulation to accumulator
1) Oil balancing in each outdoor unit
()
Communication error between indoor and remote controller (Detected at remote controller side) Sending error of remote controller Communication error between indoor and remote controller (Detected at indoor side) Communication circuit error between indoor and outdoor (Detected at indoor side) Decrease of No. of indoor units Communication circuit error of indoor and outdoor (Detected at outdoor side) Duplicated indoor addresses Duplicated master remote controllers Communication error in indoor P.C. B ass'y Automatic address start error No indoor automatic address No. of connected indoor units / Capacity over Communication error between indoor header and follower units Outdoor header units quantity error Other line connected during automatic address Sending error in communication between outdoor units Duplicated follower outdoor addresses Decrease of No. of connected outdoor units Follower outdoor error IPDU communication error Indoor TCJ sensor error Indoor TC2 sensor error Indoor TC1 sensor error TD1 sensor error TD2 sensor error TE1 sensor error TL sensor error TO sensor error Indoor TA sensor error TS1 sensor error TH sensor error Outdoor temp sensor misconnecting (TE, TL) Outdoor pressure sensor misconnecting (Pd, Ps) Ps sensor error Pd sensor error Indoor other error Outdoor EEPROM error Compressor break down Magnet switch error Overcurrent relay operation Compressor error (lock)
Current detect circuit system error Comp 1 case thermo operation Low pressure protective operation Oil level down detective protection Oil level detective temp sensor error Comp 2 case thermo operation Oil level detective circuit error Magnet switch error Overcurrent relay operation Duplicated indoor header units Duplicated outdoor line addresses Duplicated indoor units with priority (Displayed on indoor unit with priority) Duplicated indoor units with priority (Displayed in unit other than indoor unit with priority) Group line in individual indoor unit Indoor group/Address unset Indoor capacity unset Outdoor capacity unset Duplicated central control addresses Over No. of connected outdoor units No. of IPDU error Auxiliary interlock in indoor unit IC errorIndoor TCJ sensor error Indoor fan motor error Discharge temp TD1 error High-pressure SW detection error Phase-missing detection / Phase order error Heat sink overheat error Indoor overflow error Indoor fan motor error Outdoor liquid back detection error Gas leak detection Discharge temp TD2 error 4-way valve inverse error High-pressure protective operation Outdoor fan IPDU error G-TR short protection error Comp position detective circuit system error Other indoor unit error (Group follower unit error) Error in indoor group AI-NET communication system error Duplicated network adaptors
E01
E02 E03
E04
E06 E07
E08 E09 E10 E12 E15 E16 E18
E19 E20 E23
E25 E26 E28 E31 F01 F02 F03 F04 F05 F06 F07 F08 F10 F12 F13 F15 F16 F23 F24 F29 F31 H01 H02
H03 H04 H06 H07 H08 H14 H16
L03 L04 L05
L06
L07 L08 L09 L10 L20 L28 L29 L30
L31 P01 P03 P04 P05 P07 P10 P12 P13 P15 P17 P19 P20 P22 P26 P29 P31
Ð Ð Ð
Check code name
Check code name
Main
remote
controller
display
Main
remote
controller
display
SW04 SW05 SW15
D600 D601 D602 D603 D604
1
SW011SW021SW03
Header unit interface P.C. board
U1 U2 U3 U4 U5 U6
Header unit interface P.C. board
1 2 3 4
ON
SW11
1 2 3 4
ON
SW12
1 2 3 4
ON
SW06
1 2 3 4
ON
SW07
1 2 3 4
ON
SW09
1 2 3 4
ON
SW10
1
ON
SW08
1 2 3 4
ON
SW13
1 2 3 4
ON
SW14
UNIT
SET
CL
UNIT
SET
CL
For internal wiring between indoor and outdoor
For wiring of central control system
For internal wiring between outdoor units
Address Setup
07
08
Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the header unit are set up to Ò1Ó.
If other error code is displayed on 7-segment [B], remove the cause of trouble referring to Ò9. TroubleshootingÓ.
Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the header unit.(L08: Indoor
address unset up) (If the address setup operation has already finished in service time, etc, the above check code is not displayed, and only [U1] is displayed on 7-segment display [A].)
<Check on outdoor unit>
Display check on remote controller (In case of wired remote controller) Check that a frame as shown in the following left figure is displayed on LC display section of the remote controller.
<Check on indoor unit>
1
1
3
2
1
3
4
2
1
5
5
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally turned on. Therefore check the following items. ¥ Check power supply of indoor unit. ¥ Check cabling between indoor unit and remote controller. ¥ Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection failure
of connectors. ¥ Check failure of transformer for the indoor microcomputer. ¥ Check indoor control P.C. board failure.
Abnormal status
(Power is not normally turned on.)
Normal status
(Power and operation stop)
Pre-check for Address Setup Automatic Address Setup
Turn on power of indoor/outdoor units. (In order of indoor Outdoor)
After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is displayed in 7-segment display section on the interface P.C. board of the header unit.
Push SW15 and start setup the automatic address. (Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 Auto 2 Auto 3 is displayed in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1.---(U.1.light) , the
setup finished.
When perform a central control, connect a relay connector between [U1, U2] and [U3, U4] terminals in the header unit.
Address setup procedure 1
Address setup procedure 2
Using SW13 and 14 on the interface P.C. board of the header unit in each system, set up the refrigerant line address for each system. (At shipment from factory: Set to Address 1)
Note) Do not to duplicate with other refrigerant line.
Max. system address is up to 28
3
4
2
Ñ NOTE Ñ
Never connect a relay connector until address setup for all the refrigerant lines finishes; otherwise address cannot be correctly set up.
After address setup
SW13, 14 (Line address)
SW30-2
Terminal-end resistance of indoor/outdoor communi cation line/central control communication line
Relay connector
Indoor side (Automatic setup)
Line address Indoor unit address Group address
1 1 0
1 2 0
2 1 1
2 2 2
3 1 0
Connect short
after
address setup
Connect short
after
address setup
Connect short
after
address setup
Setup at shipment
from factory
U3 U4
U1 U2 U5 U6
U1 U2
A B
Header unit
Header unit Header unit
Individual Group
Remote
controller
U3 U4
21
SW30
ON OFF
U1 U2 U5 U6
U1 U2
A B
Follower unit
Remote
controller
Relay
connector
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U3 U4
U1 U2 U5 U6
U1 U2
A B
Follower unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Relay
connector
Relay
connector
Open
ON
1
2
12 3
3
1
Header unit Follower unit Follower unitHeader unit Header unit
ON
Open Open
OFF after
address setup
OFF after
address setup
(Setup is
unnecessary.)
(Setup is
unnecessary.)
(Setup is
unnecessary.)
(Setup is
unnecessary.)
Outdoor interface
P.C. board
21
SW30
ON OFF
21
SW30 SW30
ON OFF
21
SW30
ON OFF
21
ON OFF
Point
Relay connector
U1 U2
For internal wiring between indoor and outdoor
U3 U4
For wiring of central control system
U5 U6
For internal wiring between outdoor units
SW04 SW05 SW15
D600 D601 D602 D603 D604
1
SW011SW021SW03
1 2 3 4
ON
SW11
1 2 3 4
ON
SW12
1 2 3 4
ON
SW06
1 2 3 4
ON
SW07
1 2 3 4
ON
SW09
1 2 3 4
ON
SW10
1
ON
SW08
1 2 3 4
ON
SW13
1 2 3 4
ON
SW14
12
ON
SW30
Header unit interface P.C. board
Continued
09
10
Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all the header units to which the central control is connected. (At shipment from factory: No connection of connector)
Turn on power of indoor/outdoor. (In order of indoor outdoor)
After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the header
unit. Push SW15 and start setup the automatic address. (Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 Auto 2 Auto 3 is displayed in 7- segment display section, and it changes from
U.1.---(U.1.flash) to U. 1.---(U.1.light) , the setup
finished. Procedure 4. to 6. are repeated in other refrigerant lines. How to set up resistance of the end terminal When all the
address setups have finished in the same refrigerant circuit system, put the resistance of the end terminals in the same central control line into one. ¥ Remain only SW03-2 of the header outdoor unit with the least
circuit system address number as it is ON. (With end terminal resistance)
¥ Set up SW03-2 of the other header outdoor units to OFF.
(Without end terminal resistance)
Connect the relay connector between [U1U2] and [U3U4] of the header unit for each refrigerant line.
Then set up the central control address. (For the central control address setup, refer to the Installation manual of the central control devices.)
1 2 3 4 5 6 7 8
9 10 11 12 13 14
SW13
4 X X X X X X X X X X X X X X
12 3
SW14
1 X O X O X O X O X O X O X O
2 X
X O O X X O O X X O O X X
3 X X X
X O O O O X X X X O O
4 X X X X X X X
X O O O O O O
15 16 17 18 19 20 21 22 23 24 25 26 27 28
SW13
4 X
X O O O O O O O O O O O O
SW14 1 X
O X O X O X O X O X O X O
2 O O X X O O X X O O X X O O
3 O O X X X X O O O O X X X X
4 O O X X X X X X X X O O O O
System address switch on outdoor interface P.C. board
(O : Switch ON, X : Switch OFF)
: Is not used for setup of system address. (Do not change setup.)
5
3
4
7 8
9
10
8
6
2
2
5 4 6
Loading...
+ 12 hidden pages