í ½±³°®»--±®- ú í ·²ª»®¬»®- Í«°»® Ó±¼«´¿® Ó«´¬· ͧ-¬»³
Notice: Toshiba is committed to
continuously improving its pr
oducts to ensure the highest
quality and reliability standard,
and to meet local regulati
ons and market requirements.
1 Foreword ........................
...........................
...........................
2 Safety caution ....................
.........................
.............................................2-1
3 Introduction .............
.................................................................................3-1
4 System overview ..........
...........................................................................4-1
4-1. OUTLINE OF TOSHIBA SMMS
(Super Modular Multi System).......................................................................4-1
4-2. SUMMARY OF SYSTEM EQUI
PMENTS..................................
.........................4-2
4-3. List of product and combined model name.........................................................4-3
4-4. Indoor unit...........................................................................................................4-5
4-5. Remote controller ...............................................................................................4-7
5 Basic system configuration ..................
...........................
.........................5-1
5-1. Basic systems (examples)..................................................................................5-1
5-2. Fresh Air Intake Indoor Unit Type.......................................................................5-5
6 Equipment selection procedure .............
..................................................6-1
6-1. Selection flow chart.............................................................................................6-1
6-2. Operational temperature range...........................................................................6-2
6-3. Combination conditions for indoor unit and outdoor unit....................................6-3
6-4. Cooling/heating capacity charac
teristics.............................................................6-4
6-5. Example of equipment selection.........................................................................6-9
6-6. Selection procedure for fresh air intake indoor unit..........................................6-14
7 Refrigerant piping design .....................
..................................................7-1
7-1. WARNINGS ON REFRIGERAN
T LEAKAGE............................
.........................7-1
7-2. Free branching system.......................................................................................7-2
7-3. Allowable length/height difference of refrigerant piping......................................7-3
7-4. Selection of refrigerant piping.............................................................................7-4
7-5. Charging requirement with additional refrigerant................................................7-5
8 Refrigerant cycle diagram
........................................................................8-1
8-1. Inverter Driven Unit (5, 6HP) ..............................................................................8-1
8-2. Explanation of Functional Parts..........................................................................8-4
8-3. Indoor Unit..........................................................................................................8-6
8-4. COMBINED REFRIGERATION CYCLE.............................................................8-7
9 Wiring Design .........
.................................................................................9-1
9-1. General...............................................................................................................9-1
9-2. Summary of wiring design ..................................................................................9-1
9-3. Electrical wiring design.......................................................................................9-1
9-4. Outdoor unit power supply..................................................................................9-1
9-5. Indoor unit power supply.....................................................................................9-3
10 Controls ..............................
..............................
.....................................10-1
10-1. Outline of application Control chart...................................................................10-1
10-2. Applications for indoor remote controller..........................................................10-2
10-3. Application control for central remote controller ...............................................10-3
10-4. Application controls by optional P.C. board of outdoor unit .............................10-6
10-5. Application control of optional devices connectable to indoor units................10-12
10-6. Application control for network........................................................................10-15
10-7. Dimensionel drawing ......................................................................................10-20
11 Technical Specifications
........................................................................11-1
11-1. Outdoor unit......................................................................................................11-1
11-1.1 Specifications ........................................................................................................11-
11-1.2 Dimensional drawing.........
..................................................................................11-16
11-1.3 Wiring diagram....................................................................................................11-23
11-1.4 Connectingdiagram ............................................................................................11-26
11-1.5 Center of gravity..................................................................................................11-29
11-1.6 Branch header / branch joint...............................................................................11-30
11-1.7 Part Load performance..
......................................................................................11-33
level data (NC CURVE)............................................................11-70
11-2. Indoor unit...................................................................................................... 11-77
11-2-1. 4-way Air Discharge Cassette Type................................................................... 11-77
ssette (600 x 600) Type....................................................... 11-95
11-2-3. 2-way Air Discharge Cassette Type.....
............................................................ 11-106
11-2-4. 1-way Air Discharge Cassette Type.....
............................................................ 11-121
11-2-5. Concealed Duct Type...........................
............................................................ 11-134
11-2-6. Concealed Duct High Static PressureType...................................................... 11-147
11-2-7. Slim Duct Type..............
................................................................................... 11-161
11-2-8. Ceiling Type ............................................
......................................................... 11-182
11-2-9. High-wall(1serires) Type
.................................................................................. 11-192
11-2-10.High-wall(2serires) Type
.................................................................................. 11-201
11-2-11.High-wall(3serires) Type
.................................................................................. 11-211
11-2-12.Floor Standing Concealed Type...........
............................................................ 11-221
11-2-13.FloorStanding Cabinet Type................
............................................................ 11-230
11-2-14.Floor Standing Type......................................................................................... 11-239
11-2-15.FreshAir Intake Indoor
Unit Type.................................................................... 11-249
Appendix Change plan of model name
The engineering data book details
all relevant data, charts
and drawings to enable you to
from the Toshiba Super Modu
lar Multi System i for the
The information is aimed to as
sist you by providing greater
detail of the system and the
wider applications that the
Þ»º±®» «»ô ®»¿¼ ½¿®»º«´´§ ¬¸®±«¹¸ ¬¸» Í¿º»¬§
½¿«¬·±² »½¬·±² ¬± »²«®» ½±®®»½¬ ±°»®¿¬·±²ò
̸» ·³°±®¬¿²¬ ½±²¬»²¬ ½±²½»®²»¼ ¬± ¬¸» ¿º»¬§ ¿®» ¼»½®·¾»¼ ·² ¬¸» Í¿º»¬§ Ý¿«¬·±²ò
Þ» -«®» ¬± µ»»° ¬¸»³ò Ú±® ײ¼·½¿¬·±²- ¿²¼ ¬¸»·® ³»¿²·²¹-ô -»» ¬¸» º±´´±©·²¹ ¼»-½®·°¬·±²ò
É¿®²·²¹ ײ¼·½¿¬·±²- ±² ¬¸» ß·® ݱ²¼·¬·±²»® ˲·¬
Do not operate unit withgrille removed.
Stop the unit before the servicing.
You might get burnedwhen removing this panel.
Do not touchthe aluminiumfins of the unit.
Doingso may result in injury.
Openthe servicevalvesbeforetheoperation,otherwisetheremightbe the
ܱ ²±¬ ½´·³¾ ±²¬± ¬¸» º¿² ¹«¿®¼ò
Doingso may result in injury.
You might get burned when
Do not touch the aluminum
Doing so may result in injury.
ܱ ²±¬ ½´·³¾ ±²¬± ¬¸» º¿²
Û¨°´¿²¿¬·±² ±º ·²¼·½¿¬·±²-
Indicates possibilities that a death or serious in
jury of personnel is caus
ed by an incorrect handling.
Indicates contents that an injury (*
) only may be caused when aninco
rrect work has been executed.
*1: “Injury” meansa hurt, a burn, or an electric shock which does
not require hospitalization or a long-termgoing to the hospi
*2: “Property damage means an enlarged damage concerned to property, or breakage of materials.
ߺ¬»® ·²¬¿´´¿¬·±² ©±®µ ¸¿ º·²·¸»¼ô ½¸»½µ ¬¸»®» · ²± ¬®±«¾´» ¾§ ¿ ¬»¬ ±°»®¿¬·±²ô ¿²¼ »¨°´¿·² «·²¹ ³»¬¸±¼ ¿²¼
¬¸» ½«¬±³»® ¾¿»¼ ±² ¬¸» Ñ©²»® Ó¿²«¿´ò
д»¿-» ¿-µ ¬¸» ½«-¬±³»®- ¬± µ»»° ¬¸·- ײ-¬¿´´¿¬·
±² Ó¿²«¿´ ¬±¹»¬¸»® ©·¬¸ ¬¸» Ñ©²»® Ó¿²«¿´ò
·±²¿´ ¼»¿´»® ¬± ·²-¬¿´´ ¬¸» ¿·® ½±²¼·¬·±²»®ò
If youwill install by yourself, a fire, an electric shock, or water leak is caused.
Ì¿µ» ³»¿-«®»- -± ¬¸¿¬ ¬¸» ®»º®·¹
»®¿²¬ ¼±»- ²±¬ »¨½»»¼ ¬¸» ´·³·¬ ½±
²½»²¬®¿¬·±² »ª»² ·º ·¬ ´»¿µ- ©¸
»² ·²-¬¿´´·²¹ ¬¸» ¿·® ½±²¼·¬·±
For the measures not to exceed the limit of concentration,contact the dealer. If the refrigerant leaks and it exceeds the limi
concentration, an accident of oxygen shortage is caused.
ײ-¬¿´´ ¬¸» ¿·® ½±²¼·¬·±²»® ¿¬
¿ °´¿½» ©¸·½¸ ·- -¿¬·-º¿½¬±
If strengthis insufficient,the unit may fall down resultingin human injury.
л®º±®³ ¿ -°»½·º·»¼ ·²-¬¿´´¿¬·±²
©±®µ ¿¹¿·²-¬ ¿ -¬®±²¹ ©·²¼
-«½¸ ¿- ¬§°¸±±² ±® »¿®¬¸¯«¿µ»ò
If theair conditioneris imperfectly installed, an accidentby falling or dropping may be caused.
׺ ®»º®·¹»®¿²¬ ¹¿- ´»¿µ- ¼«®·²¹ ·²-¬
¿´´¿¬·±² ©±®µô ª»²¬·´¿¬» ¬¸» ®±±³ò
If theleaked refrigerant gas approaches to fire, noxious gas may generate.
ߺ¬»® ·²-¬¿´´¿¬·±² ©±®µô ½±²º·®³ ¬¸
¿¬ ®»º®·¹»®¿²¬ ¹¿- ¼±»- ²±¬ ´»¿µò
If refrigerant gas leaks in the room, and approaches to fire such
as fan heater, stove or kitchenrange, generationof noxious
Ò»ª»® ®»½±ª»® ®»º®·¹»®¿²¬ ·² ¬¸» ±«¬¼±±® «²·¬ò
Be sureto use a refrigerantrecovery device to recover refrigerant in reinstallation or repair work.
Recovery of refrigerant in the outdoor unit is unavailable;otherwise a serious accident such as crack or human injury is cause
ß °»®-±² ¯«¿´·º·»¼ º±® ¬¸» »´»½¬®·½ ©±®µ -¸±«´¼ ¼»¿´ ©·¬¸ ¬¸»
²º±®³·²¹ ¬± ¬¸» ®»¹«´¿¬·±²- ±º ¬¸» ´±½¿´
»´»½¬®·½ ½±³°¿²§ ¿²¼ ¬¸» ײ-¬
¿´´¿¬·±² Ó¿²«¿´ò Þ» -«®» ¬± «-» ¬¸» »¨½´«-·ª» ½·®½«·¬ò
If thereis capacityshortage of thepower supply circuit or incompleteinstallation, a fire or anelectric shock is caused.
Ú±® ½¿¾´·²¹ô «-» ¬¸» -°»½·º·»¼ ½¿
¾´»- ¿²¼ ½±²²»½¬ ¬¸»³ -»½«
®»´§ -± ¬¸¿¬ »¨¬»®²¿´ º±®½» ±º ½¿¾´» ¼±»- ²±¬ ¬®¿²-³·¬ ¬± ¬¸»
If connectionor fixing is incomplete, a fire, etc. may be caused.
Þ» -«®» ¬± ½±²²»½¬ »¿®¬¸ ©·®»ò
Do notconnect earth wire to gas pipe, water pipe, lightning rod, nor earth wire of telephone.
If grounding is incomplete, an electric shock is caused.
ܱ ²±¬ ·²-¬¿´´ ¬¸» ¿·® ½±²¼·¬·±²»® ¿¬
¿ °´¿½» ©¸»®» ½±³¾«-¬·¾´» ¹¿- ³¿§ ´»¿µò
If gasleaks and is collectedat surrounding the unit, the production of fire may be caused.
Þ» -«®» ¬± ¿¬¬¿½¸ ¿² »¿®¬¸ ´»¿µ¿¹» ¾®»¿µ»®å
Ë-·²¹ ¿ ¬±®¯«» ©®»²½¸ô ¬·¹¸¬»² ¬¸»
If the flare nut is exceedingly tightened,
the flare nut is broken and a refrigerant
leakagemay be caused after a long time ha
У¿½¸·²»½§ Ь·®»½¬·ª» шЬ·®»½¬·ª» оррксмосЫЭч
Please read carefully through these instructions that
containimportant informat
"Machinery" Directive(Directive 2006/42/EC
), and ensure that you understand them.
Ù»²»®·½ Ü»²±³·²¿¬·±²æ ß·® ݱ²¼·¬·±²»®
Ü»º·²·¬·±² ±º Ï«¿´·º·»¼ ײ-¬¿´´»® ±® Ï«¿´·º·»¼ Í»®ª·½» л®-±²
The air conditioner must be in
stalled, maintained, repaired and removed by
person. When any of these jobs is to be done, ask a qualif
ied installer or qualified serv
ice person to do them for
you.A qualified installer or
qualified service person is an agent who has the qualifications and knowledge described
Ü»º·²·¬·±² ±º Ю±¬»½¬·ª» Ù»¿®
Whenthe air conditioner is tobe transported, installed,ma
intained, repaired orremoved,
wear protective gloves and
In addition to such normal protective gear, wear the
protective gear described below when undertaking the special
work detailed in the table below.
ou will be more susceptible
electric shocks and other injuries.
Ï«¿´·º·½¿¬·±² - ¿²¼ µ²±©´»¼¹» ©¸ ·½¸ ¬¸» ¿¹»²¬ ³«-¬ ¸¿ª»
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrie
or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,
or she has been instructed in such operations by an individual
or individuals who have been trained and is thus thoroughly acqu
knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work
involved in installation, relocation and removal has the qual
to this electrical work as stipulated by the local laws and
regulations, and he or she is a
person who has been trained in matt
electrical work on the air conditioners made by Toshiba Carrier
Corporation or, alternatively, he or she has been instructed in
an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and
qualifications pertaining to this refrigerant handling and piping
work as stipulated by the local laws and regulations, and he
who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrie
or, alternatively, he or she has been instructed in such matters
by an individual or individuals who have been trained and is t
acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the
by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals
trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs,
maintains, relocates and removes the air conditioners made by
Corporation. He or she has been
trained to install, repair, ma
intain, relocate and remove the
air conditioners made by Toshiba
Corporation or, alternatively, he or she has been instructed in
such operations by an individual or individuals who have been t
thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who
is allowed to do the electrical work involved
pertaining to this electrical work as st
ipulated by the local laws and regulations, and he or she is a person who has been trai
relating to electrical work on the air conditioners made by Tosh
iba Carrier Corporation or, alternatively, he or she has been i
matters by an individual or individuals who have been trained and
is thus thoroughly acquainted with the knowledge related to t
• The qualified service person who is allowed to do the refrigerant
handling and piping work involved in installation, repair, r
has the qualifications pertaining to this refrigerant handling and
piping work as stipulated by the local laws and regulations,
person who has been trained in matters relating to refrigerant han
dling and piping work on the air conditioners made by Toshiba
Corporation or, alternatively, he or she has been instructed in su
ch matters by an individual or individuals who have been trai
thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights
has been trained in matters relating to working at heights with
made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or indivi
been trained and is thus thoroughly acquainted with the knowledge related to this work.
oves ‘Safety’ working clothing
protection for electricians and from heat In
sulating shoes Clothing to provide protect
Helmets for use in industry
Transportation of heavy objects Shoes with additional protective toe cap
de protection for electricians and from heat
пт ЙЯОТЧТЩН СТ ОЫЪОЧЩЫОЯТМ ФЫЯХЯЩЫ
ݸ»½µ ±º ݱ²½»²¬®¿¬·±² Ô·³·¬
The room in which the air cond
itioner is to be installed
requires a design that in the event of refrigerant gas
leaking out, its concentratio
n will not exceeda set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without th
e toxicity or combustibility
of ammonia,and is not restricted by laws tobe imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively.
Suffocationfrom leakageof R410A is almost
nonexistent. With the recent increase in the number of
highconcentration buildings, however, the installationof
multi airconditionersystems is on the increase because
of the need for effective use of floor space, individual
control, energy conservati
on by curtailing heat and
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared
with conventional individual air conditioners. If a single
unit of the multi conditionersystem is to be
installed in a small room, se
lect a suitable model and
installation procedureso that if the refrigerant
accidentally leaks out, its concentration does not reach
the limit (and in the event of an emergency,measures
can be made before injury can occur).
In a room wherethe concentrationmay exceedthe limit,
create an opening with adjacent rooms, or install
mechanical ventilation combinedwith a gas leak
The concentration is as given below.
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
The standardsfor minimumroom volume are as follows.
(1) No partition (shaded portion)
(2) When there is aneffectiveopening with theadjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
(3) If an indoor unit is installed in each partitioned room
and the refrigerant tubing
smallest room of course becomes the object. But
interlocked with a gas leakage detector in the
smallest room where the de
the volume of the next smallest room becomes the
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the
Total amount of refrigerant (kg)
Min. volume of the indoor
Room A Room B Room C Room D Room E Room F
Mechanical ventilationdev
Total amount of refrigerant
̸» ²»¨¬ó¹»²»®¿¬·±² 󯫿´·¬§ ¬®·±
Ü»¼·½¿¬·±² ¬± ·²²±ª¿¬·±² ¿²¼ ¿¼ª¿²½
½®»¿¬·ª·¬§ ©·¬¸ ©¸·½¸ ©» ¼»´·ª»® ¬±¬¿
ײ¼«-¬®§ ´»¿¼·²¹ »²»®¹§ -¿ª·²¹-
Û²»®¹§ó»ºº·½·»²¬ °»®º±®³¿²½» º±® ¹®»¿¬»® »½±ó½±²-½·±«-²»--
Adoptingthe highly efficient new DC twin-rotary compre
ssors and advanced vector-controlledinverters realizes
a COP of 6.41 (under 50% partial load). Greater operati
ng performance is now possible when operating under
ï-¬ ¾®¿²½¸·²¹ °·°·²¹ ´»²¹¬¸
Ú¿®¬¸»-¬ »¯«·ª¿´»²¬ ´»²¹¬¸
* As of December 2009 (according to independent Toshiba testing)
ײ¼«-¬®§ ´»¿¼·²¹ °·°» ´»²¹
¬¸ º±® ¹®»¿¬»® º´»¨·¾·´·¬§
Ô¿§±«¬ º´»¨·¾·´·¬§ ©·¬¸ º»© ¼»-·¹² ´·³·¬¿¬·±²-
System layouts can use a maximum equivalent distance of up to 235 metres. This makes it much easier to
design for floors with many small rooms, or for tenants who often rearrange their floor layouts.
*Calculatedat3.5 metersper floor
*As of December 2009 (according to independent Toshiba testing)
Ù®»¿¬»® -«°°±®¬ º±® ¸»·¹¸¬ ¼·ºº»
Toshiba SMMS-i leads the industry with support for height
differences of up to 40 metres between indoor units
on a single system. For instance, in an 11-story building,
this is enough height to fully
cover the entire floor as
well as the elevator halls.
ß ïêØÐ -§-¬»³ ·²- ¬¿´´¿¬·±² ²±©
±½½«°·»- ±²´ § îñí ¬¸» º±±¬°®·²¬
The outdoor units improve performance to achieve greate
r space efficiency that def
size to deliver greater freedom in layout design. This
minimizes weight-related re
strictions and allows for
ײº·²·¬§ ª¿®·¿¾´» ½±²¬®±´
Ë´¬®¿ó°®»½·-» ðòï ئ ½±²¬®±´ ±ª»® ½±³°®»--±® ®±¬¿¬·±² -°»»¼
Infinityvariable controladjusts compre
ssorrotation speed in near-seamless
0.1 Hz steps. Responding precisely
to the capacity needs of the moment, this fine control minimizes energy loss when changing frequencies, and
also creates a comfortable environment su
bject to minimal temperature variations.
*As of December 2009 (according to independent Toshiba testing)
̸» -«®°´«- ®»°®»-»²¬»¼ ¾§
øß÷ ·- ¼·³·²·-¸»¼ ¿²¼ ¬¸»
̸» -«®°´«- ®»°®»-»²¬»¼ ¾§ø Þ÷ ·- ¼·³·²·-¸»¼
Ñ°¬·³¿´ ®»º®·¹»®¿²¬ ½±²¬®±´
– When a multiplenumber of indoorunits are connected,an insufficientor excess amountof refrigerant maybe
supplied to indoor units depending on the difference in length of the connection pipe from the outdoor unit.
– This is caused by pressure loss and heat leaks as th
e refrigerant travels through the pipes, resulting in
incorrect amounts of refrigerantbeing supplied to the indoor units.
– Optimal refrigerant flow co
ntrol featuring intelligent cont
rol over the refrigerant se
nsors and opening rate of
individual pulse motor valves realizes stable indo
or temperatures throughout a building with height
differences of up to 40m between indoor units.
Ò»© Üݬ©·²ó®±¬¿®§ ½±³°®»--±®
Ñ°¬·³·¦¿¬·±² ±º ¼·-½¸¿®¹» °±®¬ °±-·¬·±²·²¹
¿²¼ ¾´¿¼» ¬¸·½µ²»--®»¼«½»- ½±³°®»--·±² ´±--
¿²¼ º®·½¬·±² ®»-·-¬¿²½»ò× ²½®»¿-·²¹ ¬¸» -«®º¿½»
¿®»¿ ±º ¬¸» ®±¬±® ³¿¹²»¬- ¿²¼¬¸» ¿¼¼·¬·±² ±º
Û¿½¸ ³±¬±® »³°´±§- ¿ ½±³°¿½¬
¿²¼ °±©»®º«´³¿ ¹²»¬·½ ®±¬±® ø®¿®»
»¿®¬¸ ³¿¹²»¬÷ ¿²¼ º»¿¬«®»-
®»¼«½»¼ »¼¼§ó½«®®»²¬ ´±--ò
̸» ª»½¬±®ó½±²¬®±´´»¼ ·²ª»®¬»® ¯«·½µ´§
½±²ª»®¬- ½«®®»²¬ ·²¬± ¿ -³±±¬¸ -·²»
½«®ª» ¬± ¿ ½¸·»ª» -³±±¬¸»® ±°»®¿¬·±²
±º ¬¸» ½±³°®»±® ÜÝ ³±¬±®ò
̸» º¿-¬ó½ ¿´½«´¿¬·²¹ ª»½¬ ±®ó½±²¬®±´´»¼
·²ª»®¬»® °®±¼«½»- ¿ -³±±¬¸ -·²» ½«®ª» ¬¸¿¬
©·¬¸ í ½±³°®»--±®- ¿²¼ í ·²ª»®¬»®-
Ò»© ÜÝ ¬©·²ó®±¬¿®§ ½±³°®»--±®
Ô»¿¼·²¹ ¬¸» ©±®´¼ ©·¬¸ ̱¸·¾¿
compressorsthatfeature outstanding
capacity under partial load drive the
14 and 16HP outdoor unit models,
while two are used by the other
outdoor unit models. These new
compressors improve both energy
efficiency and comfort levels.
ß´´ó·²ª»®¬»® ½±²¬®±´ ®»¿´·¦»- º·²»®
½±²¬®±´ ±ª»® ±°»®¿¬·±² ¬± ³¿¬½¸
Toshiba SMMS-i leadsthe industryin
controlling all 3 compressors with a
dedicatedinverterboard thattaps the
пт СЛМФЧТЫ СЪ МСНШЧЮЯ НУУН
øÍ«°»® Ó±¼«´¿® Ó«´¬· ͧ-¬»³÷
̸» ݱ³¾·²¿¬·±² ±º ´·²» ¿²¼ ¸»¿¼»® ¾®¿²½¸·²¹ ·- ¸·¹¸´§ º´»¨·¾´»ò
Ú±´´±©·²¹ ¬¸» -¸±®¬»-¬ ¼»-·¹² ®±«¬» °±--·¾´»ô ¬¸»®»¾§ -¿ª·²¹
±² ·²-¬¿´´¿¬·±² ¬·³» ¿²¼ ½±-¬ò Ô·²»ñ¸»¿¼»® ¾®¿²½¸·²¹ ¿º¬»® ¬¸»
¸»¿¼»® ¾®¿²½¸·²¹ ·- ±²´§ ¿ª¿·´¿¾´» ©·¬¸ МСНШЧЮЯ Н«°»® УУНт
Ø»¿¼»® ¾®¿²½¸·²¹ ¿º¬»® ¸»¿¼»® ¾®¿²½¸·²¹
Ô·²» ¾®¿²½¸·²¹ ¿º¬»® ¸»¿¼»® ¾®¿²½¸·²¹
From 1st branching to the furthest
)1*1: If the height different between(H2)indoor
units exceeds 3m, set below 50m.
*2 : If the height different between(H1) indoor
and outdoor units exceeds 3m, set below
от НЛУУЯОЗ СЪ НЗНМЫУ ЫПЛЧРУЫТМН
ݱ³¾·²¿¬·±² ±º ±«¬¼±±® «²·¬-
Þ®¿²½¸·²¹ ¶±·²¬- ¿²¼ ¸»¿¼»®-
*1 “Capacity code” can be obtained by the lists on next page an
d after the next page.(Capacity code is not actual capacity.)
*2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
anching joint for 1st branching, select accord
*4 Max. capacity code of 6.
0 in total can be connected.
*5 If capacity code of outdoor unit is 26 or
more, it is not used for 1st branching.
ëØÐö êØÐö èØÐ ïðØÐ ïîØÐ ïìØÐ ïêØÐ
УУЗу УЯР рлрпШМиуЫ УЯ РркрпШ МиуЫ УЯР рирмШМ иуЫ УЯРпррмШ МиуЫ УЯРпор мШМи уЫ УЯРп мрмШМ иуЫ УЯ РпкрмШ МиуЫ
УУЗу УЯР рлрпМиуЫ УЯР ркрпМиуЫ УЯРрирм МиуЫ УЯРпррм МиуЫ УЯРпормМ иуЫ У ЯРпмрм МиуЫ У ЯРпкрмМи уЫ
Cooling capacity (kW) 14.0 16.0 22.4 28.0 33.5 40.0 45.0
Heating capacity (kW) 16.0 18.0 25.0 31.5 37.5 45.0 50.0
УУЗу ЯРп ипмШМ иуЫ ЯРорп мШМиуЫ ЯРоопм ШМиуЫ ЯРо мпмШМиуЫ ЯР окпмШМиуЫ ЯР оипмШ МиуЫ ЯРнрпмШ МиуЫ ЯР нопмШМ иуЫ
ÓÓÇó ßÐï èïìÌ èóÛ ЯРорпм МиуЫ ßÐî îïìÌ èóÛ ЯРомпм МиуЫ ЯРок пмМиуЫ ЯРоипм МиуЫ ЯРн рпмМиуЫ ЯР нопмМи уЫ
capacity (kW) 50.4 56.0 61.5 68.0 73.0 78.5 85.0 90.0
capacity (kW) 56.5 63.0 69.0 76.5 81.5 88.0 95.0 100.0
3033374043474848ݱ®®»-° ±²¼·² ¹ ØÐ íìØÐ
УУЗу ЯРн мпмШМ иуЫ ЯРнкп мШМиуЫ ЯРнипм ШМиуЫ ЯРм рпмШМиуЫ ЯР мопмШМиуЫ ЯР ммпмШ МиуЫ ЯРмкпмШ МиуЫ ЯР мипмШМ иуЫ
ÓÓÇó ßÐí ìïìÌ èóÛ ЯРнкпм ШМиу Ы ЯРнипмМиуЫ ЯРмрп мМиуЫ ЯР мопмМиуЫ ЯР ммпмМиуЫ ЯРм кпмМиуЫ ЯР мипмМиуЫ
capacity (kW) 96.0 101.0 106.5 112.0 118.0 123.5 130.0 135.0
capacity (kW) 108.0 113.0 119.5 127.0 132.0 138.0 145.0 150.0
УУЗу ЯРп комШМ иуЫ ЯРомо мШМиуЫ ЯРоком ШМиуЫ ЯРо иомШМиуЫ ЯР нромШМиуЫ ЯР ноомШ МиуЫ ЯРнмомШ МиуЫ ЯР нкомШМ иуЫ
ÓÓÇó ßÐï êîìÌ èóÛ ЯРомом МиуЫ ßÐî êîìÌ èóÛ ЯРоиом МиуЫ ЯРнр омМиуЫ ЯРноом МиуЫ ЯРн момМиуЫ ЯР нкомМи уЫ
capacity (kW) 45.0 68.0 73.0 78.5 85.0 90.0 96.0 101.0
capacity (kW) 50.0 76.5 81.5 88.0 95.0 100.0 108.0 113.0
2740434748484848ݱ®®»-° ±²¼·² ¹ ØÐ íèØÐ
УУЗу ЯРн иомШМ иуЫ ЯРмро мШМиуЫ ЯРмоом ШМиуЫ ЯРм момШМиуЫ ЯР мкомШМиуЫ ЯР миомШ МиуЫ
ÓÓÇó ßÐí èîìÌ èóÛ ЯРмром МиуЫ ßÐì îîìÌ èóÛ ЯРммом МиуЫ ßÐìê îìÌ èóÛ ЯРмиом МиуЫ
capacity (kW) 106.5 112.0 118.0 123.5 130.0 135.0
capacity (kW) 119.5 127.0 132.0 138.0 145.0 150.0
Ë-¿¹» øÝ´¿--· º·½¿¬·±² ¿½½±®¼· ²¹ ¬± ·² ¼±±® « ²·¬ ½ ¿°¿½·¬§ ½ ±¼» øö
Y-shape branching joint (*
RBM-BY55E Total below 6.4
RBM-BY105E Total 6.4 or more and below 14.2
RBM-BY205E Total 14.2 or more and below 25.2
RBM-BY305E Total 25.2 or more
RBM-HY1043E Total below 14.2
RBM-HY2043E Total 14.2 or more and below 25.2
RBM-HY1083E Total below 14.2 Max.8 branches
RBM-HY2083E Total 14.2 or more and below 25.2
Branching joint for connection
(1set of 1type of Y-shape joint
pipe and 2types ofT-joint pipes
Piping at gas side (Y-shape) Piping at liquid side (T-shape) Balance pipe (T-shape)
RBM-BT24E Total 26 or more
íò Ô·-¬ ±º °®±¼«½¬ ¿²¼ ½±³¾·²»¼ ³±¼»´ ²¿³»
îò ο²¹ ±º ½±³¾·²»¼ ½¿°¿½·¬§
No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)
Cooling: Indoor air temperature 27ºC DB/19ºC WB, Outdoor air temperature 35ºC DB
Heating: Indoor air temperature 20ºC DB, Outdoor air temperature 7ºC DB/6ºC WB
MAP0 501HT 8-E 1 MAP0 501HT8-E 1
MAP0 804HT 8-E 1 MAP10 04HT 8-E 1
MAP1 004HT 8-E 1 MAP12 04HT 8-E 1
MAP1 004HT 8-E 1 MAP1 604HT 8-E 1
MAP1 204HT 8-E 1 MAP1 604HT 8-E 1
MAP1 404HT 8-E 1 MAP16 04HT 8-E 1
MAP1 004HT 8-E 1 MAP12 04HT 8-E 2
MAP1 004HT 8-E 1 MAP12 04HT 8-E 1 MAP16 04HT 8-E 1
MAP1 204HT 8-E 2 MAP1 604HT 8-E 1
MAP1 204HT 8-E 1 MAP14 04HT 8-E 1 MA P1604HT 8-E 1
MAP1 204HT 8-E 1 MAP1 604HT 8-E 2
MAP1 404HT 8-E 1 MAP16 04HT 8-E 2
MAP0 804HT 8-E 2 MAP10 04HT 8-E 1
MAP0 804HT 8-E 1 MAP10 04HT 8-E 2
MAP0 804HT 8-E 3 MAP10 04HT 8-E 1
MAP0 804HT 8-E 2 MAP10 04HT 8-E 2
MAP0 804HT 8-E 1 MAP10 04HT 8-E 3
MAP1 004HT 8-E 3 MAP12 04HT 8-E 1
MAP1 004HT 8-E 2 MAP12 04HT 8-E 2
MAP1 004HT 8-E 1 MAP12 04HT 8-E 3
Power supply specifications, 3Ø
380-400-415V, 50Hz ....... 8
T: Capacity variable unit
0 : Single model, 1: Standard model, 2 : High efficiency model
M: Single module unit, No mark: Combined Model name
îò ο²¹ ±º ½±³¾·²»¼ ½¿°¿½·¬§
No. of combined units: 1 to 4 units
Capacity of combined units: 16 HP(16type) to 48 HP(48type)
Cooling: Indoor air temperature 27ºC DB/19ºC WB, Outdoor air temperature 35ºC DB
5HP(5)* MAP0501T8-E 1 MAP0501T8-E 1
6HP(6)* MAP0601T8-E 1 MAP0601T8-E 1
8HP(8) MAP0804T8-E 1 MAP0804T8-E 1
18HP(18) AP1814T8-E 2 MAP0804T8-E 1 MAP1004T8-E 1
MAP1004T8-E 1 MAP1204T8-E 1
MAP1004T8-E 1 MAP1604T8-E 1
MAP1204T8-E 1 MAP1604T8-E 1
MAP1404T8-E 1 MAP1604T8-E 1
MAP1004T8-E 1 MAP1204T8-E 2
MAP1004T8-E 1 MAP1204T8-E 1 MAP1604T8-E 1
MAP1204T8-E 2 MAP1604T8-E 1
MAP1204T8-E 1 MAP1404T8-E 1 MAP1604T8-E 1
MAP1204T8-E 1 MAP1604T8-E 2
MAP1404T8-E 1 MAP1604T8-E 2
16HP(16) AP1624T8-E 2 MAP0804T8-E 2
24HP(24) AP2424T8-E 3 MAP0804T8-E 3
26HP(26) AP2624T8-E 3 MAP0804T8-E 2 MAP1004T8-E 1
28HP(28) AP2824T8-E 3 MAP0804T8-E 1 MAP1004T8-E 2
32HP(32) AP3224T8-E 4 MAP0804T8-E 4
34HP(34) AP3424T8-E 4 MAP0804T8-E 3 MAP1004T8-E 1
36HP(36) AP3624T8-E 4 MAP0804T8-E 2 MAP1004T8-E 2
38HP(38) AP3824T8-E 4 MAP0804T8-E 1 MAP1004T8-E 3
MAP1004T8-E 3 MAP1204T8-E 1
MAP1004T8-E 2 MAP1204T8-E 2
MAP1004T8-E 1 MAP1204T8-E 3
Power supply specifications, 3Ø
380-400-415V, 50Hz ....... 8
T: Capacity variable unit
0 : Single model, 1: Standard model, 2 : High efficiency model
M: Single module unit, No mark: Combined Model name
ß°°»¿® ¿²½» ß°°´·½¿¬·±² Ú«²½¬·±²
• Self-diagnosis function
• Control by 2 remote controllers is available.
• Control by 2 remote controllers is available.
(For 4-way Air Discharge Cassette)
(For Under Ceiling, 1-way Air Discharge
(For Compact 4-way Cassette,2-way Air
DischargeCassette, 1-wayAir Discharge
Cassette YH, Concealed Duct Standard, Slim
Duct, Floor StandingCabinet, Floor Standing)
ݱ²²»½¬»¼ ¬± ±«¬¼±±® «²·¬ô
• Individualcontrol up to 16 indoor units.
• Setting of simultaneousON/OFF 3 times for
each day of the week when combined with
• Connected to 2 remote controllersis available.
ݱ²²»½¬»¼ ¬± ±«¬¼±±® «²·¬ô
• Individualcontrol up to 64 indoor units.
• Individualcontrol for max. 64 indoor units
• Up to 16 outdoorheader units are connectable.
• 4 type centralcontrol settingto inhibitindividual
operation by remote controller can be selected.
• Setting for one of 1 to 4 zones is available.
• Can be used with other central control devices
(Up to 10 central control devicesandBMSI/Fin
• Two selectablecontrol modes
• Operatingwith SheduleTimer TCB-EX21TLE.
• Individualcontrol of up to (64 indoor units) x 2
• Individualcontrol of up to (64 indoor units
divided 1 to 64 zone) x 2 TCC-LINKbuses (Up
to 64indoor units for each zone)
• Up to 16 outdoorheader units are connectable
• 4 types of central control settingsof inhibit
individualoperation by remote controller can be
• Setting for (one of 1 to 64zones) x 2ch is
• Setting for (one of 1 to 64groups) x 2ch is
• Usable and BMSI/F other central control
(Up to 10 central control devices in one TCC-
• Two control mode selectively
(contral controller mode)
(Remote controllermode) bySW01 bit6.
• Operatingwith SheduleTimer TCB-EX21TLE.
ß°°»¿® ¿²½» ß°°´·½¿¬·±² Ú«²½¬·±²
• Enabling 8 groupsto be programmed
• A maximum of 64 indoor units can be controlled
• A maximum of 100 hours back-uppower supply
• 7 types of weekly schedule and 3
• Can set ON/OFF by one-minuteinterval
Possible to program scheduletimer (7-day
Possible to program 8functions for each day of
* The following items can be set in program:
Operation time, Operation start/stop, Operation
mode, Temperaturesetting, Restrictionon
ß°°»¿® ¿²½» ß°°´·½¿¬·±² Ú«²½¬·±²
Connected to central remote controller or
Basic system configuration
ïò Þ¿-·½ -§-¬»³- ø»¨¿³°´»-÷
5.6 4.8 4.0 3.2 2.4 1.6 0.8
• Max. indoor unit : 13 units
• Capacity code of indoor unit :
Basic system configuration
• Max. indoor unit : 33 units
• Capacity code of indoor unit :
Basic system configuration
14.0 13.0 12.0 11.0 9.75 8.5 6.5
13.25 12.25 11.25 10.25 9.0 7.75 6.5
13.25 12.25 11.25 10.25 9.0 7.75 6.5
13.25 12.25 11.25 10.25 9.0 7.75 6.5
ìð ØÐ -§-¬»³ øͬ¿²¼¿®¼ ³±¼»´÷
• Max. indoor unit : 48 units
• Capacity code of indoor unit :
Basic system configuration
16.55 15.75 14.5 13.25 12.25 11.25 9.25
16.3 15.5 14.25 13.25 12.25 11.25 9.25
14.3 13.5 12.25 11.25 10.25 9.25 7.25
14.75 13.5 12.25 11.25 10.25 9.25 7.25
• Max. indoor unit : 48 units
• Capacity code of indoor unit :
Basic system configuration
îò Ú®»-¸ ß·® ײ¬¿µ» ײ¼±±® ˲·¬ ̧°»
• The total capacity of the fresh air intake un
its andthe indoor units is restricted to 80
to 100% against the capacity of the outdoorunits.
• Up to two fresh air intake units can be
connected on one line of the multi system.
• The allowable total capacity of fresh air intake units shall be 30% or less against
the total capacity of the indoor units
(including the fresh air intake units).
• The fresh air intake units only cannot connected.
Fresh Air Intake Indoor unit
Equipment selection procedure
Determination of indoor air-conditioningload at eachroom.
Preliminary selection of indoor unitsin the standard capacity no less
than air-conditioning load at each room.
Calculate corrected capacityAof each indoor unitby correcting of
indoor temperature for the standard capacityof each indoorunit.(Refer
Preliminary selection of outdoor unit in the standard capacity no less
than total values of correctedcapacityA in indoor units. At the same time,
checkboth connectable indoor units numberand the outdoor unit
diversity(Connectedratio of indoor units to outdoor units) for the
Calculate corrected capacityB of each indoor unit by following 2 steps.
Step1:Find the correction value of "Connecting pipe lengthand lift" by
both the longest length and the largest height with selectedpiping
Step2:Calculatecapacity B by multiplying the valueof step1 by corrected
Corrected capacity B of indoor
unit>= air-conditioningload (for All
Corrected capacity C of indoor
unit>= air-conditioningload (for All
Find correction values of below items for the standard capacity of
Then determination of total corrected capacityof the selectedoutdoor unit
-Correction of indoortemperature condition(Referto Chart [1])
-Correction of outdoor temperature condition(Refer to Chart [2])
-Correction of connecting pipe length and lift between indoor andoutdoor
units by both the longest length and thelargest height (Refer to Chart [3])
-Correction of outdoor unit diversityin only over 100%(Referto Chart [4])
-Correction of frost conditionon outdoor heat exchanger when in heating
Calculate corrected capacityC of each indoor unit by multiplyingthe
total correctedcapacity of outdoor unit at
by proportional divisionof
each indoor unit standard capacity for total standard capacity of all indoor
end5' Increase of outdoorunit capacity.
At the same time, check both
connectable indoor units number
and the outdoor unit diversity
The correctioncharacteristic
of "connecting pipe length and
increasedoutdoor unit at ?'
outdoorunit at ? is different.
Equipment selection procedure
îò Ñ°»®¿¬·±²¿´ ¬»³°»®¿¬«®» ®¿²¹»
201510-10-5051015202530354045-20-15-10-5051015205 10 15 20 25 30
Outdoor air dry bulb temp. (°C)
Indoorairwet bulb temp.(°C)
Outdoorair wet bulbtemp. (°C)
Indoorair dry bulb temp.(°C)
The unit will operatedown to an outdoor
temperature of -20°C,however
considerable performance decrease will
Therefore please consider installation
location/surroundings and system design
when expected to operatebetween-15°C
Equipment selection procedure
íò ݱ³¾·²¿¬·±² ½±²¼·¬·±²- º±®
·²¼±±® «²·¬ ¿²¼ ±«¬¼±±® «²·¬
1. For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank: Correspondence to Btu/h. Capacity code: Correspondenceto Horsepower.
2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
Ý¿°¿½·¬§ ®¿²µ ¬§°» ððé ððç ðïî ðïë ðïè ðîì ðîé ðíð ðíê ðìè ðëê ðéî ðçê
0.8 1 1.25 1.7 2 2.5 3 3.2 4 5 6 8 10
Ñ«¬¼±±® «²·¬ øݱ± ´·²¹ ±²´§÷ Ý¿°¿½·¬§ ½±¼ » ±º ±«¬¼±±® «²·¬ Ó¿¨ò Ò±ò ±º ·²¼±±® «²·¬-
50 to 135% of outdoor unit capacity
Equipment selection procedure
ïò ݱ®®»½¬·±² ½¸¿®¬- º±® ½±±´·²¹ ½¿°¿½·¬§ ½¿´½«´¿¬·±²
[1] Indoor air wet bulb temperatur
e vs. capacity correction value
[2] Outdoor air dry bulb temperature vs.capacity correction value
[3] Connectingpipe length and lift difference between indoor
and outdoorunits vs.capacity correction value
Capacity correction value
Indoor air wet bulb temp. (°C)
Capacity correction value
Outdoor air dry bulb temp. (°C)
(l'o + l'a, l'o + l'b, l'o + l'c)
(Largest one of ha, hb, and hc)
Standard model High efficiency model
Pipe length Graph Pipe length Graph
Equipment selection procedure
100110120130140 150160170 180190200210
Pipe length(Equivalent length) L’(m)
130 140 150160 170 180190 200 210 220
Pipelength (Equivalent length) L’(m)
130 140 150160 170 180190 200 210 220 230
Pipe length(Equivalent length) L’(m)
100110120130140 150160170 180190200210
Pipelength (Equivalent length) L’(m)