Toshiba MMY-MAP0802FT8, MMY-MAP1202FT8, MMY-MAP1002FT8 INSTALLATION MANUAL

FILE NO : A06-009
Quick reference
R410A
Refrigerant Piping
01
Allowable length of refrigerant pipe and height difference
Follower unit B
Height difference between outdoor units H3 £ 5 m
Height difference between outdoor and indoor units H1 £ 50 m
•Allowable length/height difference of the refrigerant pipe
Total extension of pipe (Liquid pipe/real length)
Farthest piping length L (*1)
Max. equivalent length of main piping Equivalent length of farthest piping from 1 st branching Li (*1)
Pipe
Max. real length of indoor unit connecting piping
length
Max. real length between FS unit and indoor unit (*2) Max. equivalent length of outdoor unit connecting pipe LO (*1) Max. real length of outdoor unit connecting pipe Max. equivalent length between FS unit and indoor unit Lj Max. real length between FS unit and indoor unit which FS unit
control wiring is connected Lh (*2) Height between
indoor unit and outdoor unit H1
Height between
Height
indoor unit H2
difference
Height between outdoor units H3 Height difference between indoor units in group control by one
FS unit H4
*1 : The farthest indoor unit from 1st branch to be named C, and fa rthest indoor unit from 1st branch to be named (q). *2 : Attached connection cable can be used up to 5 m in pipe length between indoor unit and FS unit.
When the pipe length between indoor and FS unit exceeds 5 m, be sure to use the connection cable kit (RBC-CBK15FE).
• Restriction to the system
Max. No. of combined outdoor units Max. capacity of combined outdoor units Max. No. of connected indoor units
Max. capacity of connected indoor units
Min. capacity of connected indoor units
*3 : MMY-MAP1202FT8 up to 120%.
Header unit A
Outdoor unit
T-Shape branching main piping
L1
Branching piping L2 Connecting piping of
1st
indoor unit branching section
L3
Indoor unit
Equivalent length corresponded to farthest piping L £ 150 m
Equivalent length corresponded to farthest piping after 1st branching Li £ 50 m
L4
d
FS unit
l
Indoor unit
Indoor unit which FS unit control wiring is connected.
H2 < 15 m 135% (*3) H2 > 15 m 105%
Outdoor capacity : 70%
Lb Lc
La
LA
Main connecting piping between outdoor units Length corresponded to farthest piping between outdoor units LO £ 25 m
bca
hi jkg
L6 L7
L5
f
e
n
m
Real length Equivalent length
Upper outdoor unit Lower outdoor unit Upper outdoor unit Lower outdoor unit
3 units
84.0 kW 48 units
Branching header
L9
FS unit
<Cooling only> <Cooling only>
L8
FS unit
o
Lh
When connecting the plural indoor units to single FS unit.
Allowable value
Note 1) Combination of outdoor unit : Header unit (1 unit) + Follow unit
Note 2) Install the outdoor units in order of capacity.
Note 3) Refer to outdoor unit combination table in page 5. Note 4) Piping to indoor units shall be per pendicular to piping to the
•Cautions concerned with installation/construction
1) The leading outdoor unit connected with the indoor inter-unit pipe is made “A (Header unit)”.
2) Set the units in order of the outdoor capacity. (A (Header unit) > B > C > D)
3) For the combination of the outdoor units, refer to “Combination of outdoor unit” list.
Note:
In case of connecting method <Ex.2>, a large amount of refrigerant and refrigerant oil may return to the head unit. Therefore, set the T-shape joint so that oil does not enter directly.
Lj
p
q
<Group control>
LA + La + Lb + Lc + L1 + L2 + L3 + L4 + L5 + L6 + L7 + L8 + L9
300 m
+ a + b + c + d + e + f + g + h + i + j + k + l + m + n + o+ p + q 125 m 150 m
85 m 50 m 30 m 15 m 25 m 10 m 30 m
15 m 50 m
30 m 35 m 15 m
5 m
0.5 m
(0 to 2 units). Header unit is outdoor unit nearest to the con­nected indoor units.
Header
<Ex.1>
unit A
OK
Header
<Ex.2>
unit A
NO GOOD
Height difference between indoor units H2 £ 35 (Upper outdoor unit)
Height difference between indoor units in group control by one FS unit H4 £ 0.5 m
Pipe section
LA + Lc + L1 + L3 + L4 + L5 + L6 + L7 + L8 + q
a + g, b + h, c + i, d + l, e + m, f + m, f + n, j, k
L1
L3 + L4 + L5 + L6 + L7 + L8 + q
g, h, i, l, m, n, L7 + o
LA + Lc (LA + Lb)
La, Lb, Lc
L7 + L8 + p, L7 + L8 + q
L7 + o
—— —— —— —— ——
——
(Header unit > Follow unit 1 > Follow unit 2)
head outdoor unit as <Ex. 1>. Do not connect piping to indoor units in the same direction of head outdoor unit as <Ex. 2>.
Follower
unit B
Follower
unit B
Follower
unit C
Follower
unit C
02
Addition of refrigerant
After vacuuming work, exchange the vacuum pump with the refrigerant bomb and then start the additional charging work of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipe at the local site. For refrigerant to be charged in pipe at the local site, calculate the amount and charge it additionally. Note) If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
addition of refrigerant.
Outdoor unit Model Charging amount (kg)
Additional refrigerant charge amount at local site
Example : Additional charge amount R (kg) = {(L1 × 0.025kg/m) + (L2 × 0.055kg/m) + (L3 × 0.105kg/m)} × 1.3
Table-1 Table-2
Liquid
pipe dia.
Charging of refrigerant
•Keeping valve of the outdoor unit closed, be sure to charge the liquid refrigerant into service port at liquid side.
• If the specified amount of refrigerant cannot be charged, open fully valves of outdoor unit at liquid and discharge/ suction gas sides, balance side operate the air conditioner in COOL mode under condition that valve at suction gas side is a little returned to close side, and then charge refrigerant into service port at suction gas side. In this time, choke the refrigerant slightly by operating valve of the bomb to charge liquid refrigerant. The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
•When refrigerant leaks and refrigerant shortage occurs in the system, recover the refrigerant in the system and re­charge refrigerant newly up to the correct level.
<Entry of refrigerant charge amount>
•Fill the additional refrigerant record column of the wiring diagram indication plate with the additional refrigerant
• The total refrigerant amount means the total value of the refrigerant amount at shipment and the additional refriger-
Additional refrigerant
amount/1m liquid pipe (kg/m)
(mm)
6.4
9.5
12.7
15.9
19.1
22.2
amount at installation work, total refrigerant amount and the name of the service man who charged refrigerant at installation time.
0.025
0.055
0.105
0.160
0.250
0.350
ant amount at installation time. The refrigerant amount at the shipment is one described on the “Unit nameplate”.
MMY-MAP0802FT8 MMY-MAP1002FT8 MMY-MAP1202FT8
Real length
×
( )
of liquid pipe
Additional refrigerant charge amount per 1m liquid pipe (Table 1)
L1 : Real total length of liquid pipe Ø6.4 (m) L2 : Real total length of liquid pipe Ø9.5 (m) L3 : Real total length of liquid pipe Ø12.7 (m) System : 10HP
Combined
(HP)
8 10 12 16 18 20 24 26 28 30
Combined outdoor unit
8 10 12 8 8 10 8 10 10 8 8 8 10 8 8 10 10 8 10 10 10
(HP)
11.5
Compensation by
1.3
system HP (Table 2)
C (Corrected refrigerant amount)
–1.5
–4.5 –3.0 –1.5
(kg)
2.0
2.5
3.0
0.0
2.0
0.0
REQUIREMENT
Refrigerant Piping Diagram (Outdoor)
03
Inverter unit (8, 10, 12HP)
Model: MMY-MAP0802FT8, MAP1002FT8, MAP1202FT8
Propeller fan
Fan motor
FM
(Right side)
Main heat exchanger
(Left side)
Main heat exchanger
Sub heat exchanger (Right side)
Sub heat exchanger (Left side)
Solenoid valve (SV11)
Check valve
Solenoid valve
Oil
separator
Strainer
Check valve Check valve
tube
Sensor
(TK3)
Strainer
Check
valve
Sensor
(TK1)
(SV3A)
Check valve
Strainer
Solenoid valve (SV3C)
Strainer
Check
valve
Capillary tube
Sensor
(TK2)
Oil tank
Solenoid valve
(SV3B)
Check valve
Compressor 2
Capillary
Sensor (TK4)
Solenoid valve
(SV2)
(Inverter)
4-Way valve
Capillary
tube
Capillary tube
Solenoid valve
(SV42)
High-pressure
switch
Sensor
(TD2)
Sensor
(TO)
Pulse motor valve
Solenoid valve
(PMV1) (PMV2)
Check valve
Strainer
Sensor
(TL)
Liquid
tank
Check
joint
Strainer Strainer
Service valve
Service valve at
of balance pipe
discharge gas side
Service valve
Service valve at
at liquid side
suction gas side
Sensor (TE1)
Strainer
(SV12)
Strainer
(PMV3)
Check valve
Solenoid valve (SV5)
Capillary
High-pressure
tube
Solenoid valve
(SV6)
Solenoid valve
Solenoid valve
sensor Check joint
Capillary tube
Strainer
(SV3D)
Capillary tube
(SV41)
High-pressure switch
Sensor
(TD1)
Compressor 1
(Inverter)
Capillary tube
Solenoid valve
(SV3E)
Capillary tube Capillary tube
Strainer
Sensor
(TS1)
Sensor
(TS2)
Low-pressure
Accumulator
sensor
Check
joint
Explanation of functional parts
Functional part name
Solenoid valve
4-way valve
Pulse motor valve
Oil separator
Temp. sensor
(Connector CN324: Red)
SV3A
Closed : Allows oil to collect/remain in the oil tank. Open : Allows oil to exit the oil tank.
(Connector CN313: Blue)
SV3B
Open : Allows oil to return to the outdoor unit via the balance pipe. (Connector CN314: Black)
SV3C
Open : Pressurizes the oil tank. (Connector CN323: White)
SV3D
Open : Supplies oil to the compressor from the oil separator. (Connector CN323: White)
SV3E
Open : Tu rns on during operation and balances oil between compressors. (Hot gas bypass) (Connector CN312: White)
1) Low pressure release function
ASV2
2) High pressure release function
3) Gas balance function during stop time (Gas balance control for compressor start-up) (Connector CN311: Blue)
SV41
1) For gas balance start
SV42
2) High pressure release function
3) Low pressure release function (Connector CN310: White)
SV5
1) Increase of No. of heating indoor units, Gas balance function in defrost time
2) Low-pressure balance function of discharge gas pipe during all cooling operation (Connector CN309: White)
SV6
1) Liquid bypass function for discharge temp. release (Cooling bypass circuit) (Connector CN322: White)
SV11
1) For shutdown discharge gas (During all cooling operation and defrost operation) (Connector CN319: White)
SV12
1) Flow-rate control function of refrigerant to sub heat exchanger during simultaneous operation
2) Flow-rate control function of refrigerant to sub heat exchanger during defrost operation (Connector CN317: Blue)
1) Cooling/Heating selection
2) Reverse defrost
3) Main-/Sub-heat exchanger selection (Connector CN300, 301: White)
1) Super heat control function during all heating operation and mainly heating, partly cooling operation
PMV1, 2
2) Under-cool adjustment function during all cooling operation
3) Divided flow control function during mainly cooling, partly heating operation (Connector CN302: Red)
1) For flow-rate control of sub heat exchanger during simultaneous operation
PMV3
TD1, TD2
TS1
TS2
TE
TK1, TK2, TK3, TK4
TL
TO
(Control function of heating divided flow)
2) A function preventive high pressure up during all cooling or all heating operation
1) Prevention for early drop of oil level (Decrease of flow-out of discharge oil to cycle)
2) Reser ve function of surplus oil (TD1: Connector CN502: White, TD2: Connector CN503: Pink)
1) Protection of compressor discharge temp.
2) Releasing of discharge temp. (Connector CN504: White)
1) Controls super heat of PMV1 and 2 during all heating operation and simultaneous operation (Connector CN522: Black)
1) Controls indoor oil recovery during all cooling operation and mainly cooling, partly heating operation
2) Detects overheat of cycle. (Connector CN505: Green)
1) Controls defrost during all heating operation and simultaneous operation.
2) Controls outdoor fan during all heating operation and simultaneous operation. TK1: Connector CN514: Black, TK2: Connector CN515: Green,
æ ö è ø
TK3: Connector CN516: Red, TK4: Connector CN523: Yellow
1) Judges oil level of compressor.
(Connector CN521: White)
1) Detects under-cool during all cooling operation and simultaneous operation.
(Connector CN507: Ye llow)
1) Detects external ambient temperature.
04
Functional outline
Continued
05
Functional part name
High pressure sensor
Pressure sensor
Low pressure sensor
Heater
Balance pipe
Compressor case heater
Accumulator case heater
<Operation mode>
Operation mode
1. All Indoor Unit(s) Operating for Cooling
2. All Indoor Unit(s) Operating fo r Heating
3. Simu ltaneous operation
3-1. Mainly cooling, par tly heating operation
3-2. Mainly heating, par tly cooling operation
4. Defrost
(Connector CN501: Red)
1) Detects high pressure and uses it to control capacity of compressor.
2) Detects high pressure during all cooling operation and uses it to control fan when cooling with low outside air.
3) Detects under-cool of the indoor unit of which heating thermo.-ON during all heating operation and simultaneous operation.
4) Controls outdoor fan rpm during mainly cooling, par t heating operation.
(Connector CN500: White)
1) Detects low pressure and uses it to control capacity of compressor during all cooling operation and simultaneous operation
2) Detects low pressure and uses it to controls super heat during all heating operation and simultaneous operation
(Compressor 1 Connector CN316: White, Compressor 2 Connector CN315: Blue)
1) Prevents liquid accumulation in the compressor
(Connector CN321: Red)
1) Prevents liquid accumulation to accumulator
1) Oil balancing pipe between outdoor unit (This unit does not use this Balance pipe.)
Only cooling operation without heating operation Outdoor heat exchanger (Main heat exchanger) is used as condenser.
Only heating operation without cooling operation Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
MIU for simultaneous operation
Cooling/heating simultaneous operation with subjective cooling operation Outdoor heat exchanger (Sub heat exchanger) is used as condenser.
Cooling/heating simultaneous operation with subjective heating operation Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
Using reversing operation of 4-way valve, ice of the outdoor heat exchanger is dissolved with single cooling cycle.
Functional outline
Outline
Configuration of outdoor unit heat exchanger Flow Selector Unit (FS Unit)
* RBM-Y1801FE has two “SVS” valves.
Check
valve
Strainer
SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipe Suction gas pipe
To indoor
gas side
To indoor liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
Check
valve
Strainer
SVS SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipe Suction gas pipe
To indoor
gas side
To indoor liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
* RBM-Y2802FE has three “SVS” valves and two “SVD”.
Check
valve
Strainer
SVS SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipe Suction gas pipe
To indoor
gas side
To indoor liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
SVS
RBM-Y1122FE
Propeller fan
Fan motor
Main heat exchanger
RBM-Y1802FE
Wind
Sub heat exchanger
Front side
(Right)
Sub heat
exchanger
Rear side
(Left)
Wind
RBM-Y2802FE
06
Functional part name
Solenoid valve
(Discharge gas block valve)
SVD
1) High pressure gas circuit during heating operation (Suction gas block valve)
SVS
1) Low pressure gas circuit during cooling operation (Pressure valve)
SVDD
1) For pressurizing when No. of heating indoor units increases. (Reducing valve)
SVSS
1) For recovery of refrigerant of the stopped indoor unit of which cooling thermo-OFF
2) For reducing pressure when No. of heating indoor units decreases.
Functional outline
System Refrigerant Cycle Drawing
07
Refrigerant piping systematic diagram in system
<Selection of operation mode>
For the selection of each operation mode, see the table below: “Stop Once” means the system does not operate for 3 minutes after operation before update has stopped.
After update
All cooling operation Mainly cooling, partly Mainly heating, partlyAll heating operation
(OFF) (ON) (ON) (ON)
All cooling operation
(OFF)
Mainly cooling, partly
heating cooperation (ON)
Before update
Mainly heating, partly
cooling operation (ON)
All heating operation
(ON)
Note) Phrases in parentheses in the table indicate status of 4-way valve.
Operation continues Operation continues Operation continues
(ON ® OFF) (As ON) (As ON)
Stop Once Operation continues Operation continues
(ON ® OFF) (As ON) (As ON)
Stop Once Operation continues Operation continues
(ON ® OFF) (As ON) (As ON)
<ON-OFF list of Flow Selector Unit (FS Unit) valve>
Indoor operation mode
1. Stop (Remote controller OFF) <All system stop>
2. Cooling ther mo-OFF
3. Cooling ther mo-ON
4. Heating ther mo-OFF
5. Heating ther mo-ON
6. “E04” error is being detected
SVD SVDD SVS SVSS
(High pressure(Pressure valve (Low pressure (Reducing valve
circuit valve) <For delay>) circuit valve) <For delay>)
OFF OFF OFF ON
<OFF> <OFF> <OFF> <OFF>
OFF OFF OFF ON
OFF OFF ON ON
ON OFF OFF OFF
OFF ON OFF OFF
heating cooperation cooling operation
Operation continues Operation continues Stop once
(OFF ® ON) (OFF ® ON) (OFF ® ON)
Outline of control valve output of FS unit (Basic operation)
Check Code List
08
Main
remote
controller
display
Communication error between indoor and remote controller
E01
(Detected at remote controller side)
E02
Sending error of remote controller
Communication error between indoor and remote controller
E03
(Detected at indoor side)
Communication circuit error between indoor and outdoor
E04
(Detected at indoor side)
E06
Decrease of No. of indoor units
Communication circuit error of indoor and outdoor
E07
(Detected at outdoor side)
E08
Duplicated indoor addresses
E09
Duplicated master remote controllers
E10
Communication error in indoor P. C. B ass’y
E12
Automatic address start error
E15
No indoor automatic address
E16
No. of connected indoor units / Capacity over
E18
Communication error between indoor header and follower units
E19
Outdoor header units quantity error
E20
Other line connected during automatic address
E23
Sending error in communication between outdoor units
E25
Duplicated follower outdoor addresses
E26
Decrease of No. of connected outdoor units
E28
Follower outdoor error
E31
IPDU communication error
F01
Indoor TCJ sensor error
F02
Indoor TC2 sensor error
F03
Indoor TC1 sensor error
F04
TD1 sensor error
F05
TD2 sensor error
F06
TE1 sensor error
F07
TL sensor error
F08
TO sensor error
F10
Indoor TA sensor error
F12
TS1, TS2 sensor error
F13
TH sensor error
F15
Outdoor temp sensor misconnecting (TE, TL)
F16
Outdoor pressure sensor misconnecting (Pd, Ps)
F23
Ps sensor error
F24
Pd sensor error
F29
Indoor other error
F31
Outdoor EEPROM error
H01
Compressor break down
Magnet switch error
H02
Overcurrent relay operation Compressor error (lock)
H03
Current detect circuit system error
Check code name
Main
remote
controller
display
H04
Comp 1 case thermo operation
H06
Low pressure protective operation
H07
Oil level down detective protection
H08
Oil level detective temp sensor error
H14
Comp 2 case thermo operation
Oil level detective circuit error
H16
Magnet switch error Overcurrent relay operation
L03
Duplicated indoor header units
L04
Duplicated outdoor line addresses
Duplicated indoor units with priority
L05
(Displayed on indoor unit with priority)
Duplicated indoor units with priority
L06
(Displayed in unit other than indoor unit with priority)
L07
Group line in individual indoor unit
L08
Indoor group/Address unset
L09
Indoor capacity unset
L10
Outdoor capacity unset
L17
Inconsistency error of outdoor units
L18
FS unit error
L20
Duplicated central control addresses
L28
Over No. of connected outdoor units
L29
No. of IPDU error
L30
Auxiliary interlock in indoor unit
L31
IC error
P01
Indoor fan motor error
P03
Discharge temp TD1 error
P04
High-pressure SW detection error
P05
Phase-missing detection / Phase order error
P07
Heat sink overheat error
P10
Indoor overflow error
P12
Indoor fan motor error
P13
Outdoor liquid back detection error
P15
Gas leak detection
P17
Discharge temp TD2 error
P19
4-way valve inverse error
P20
High-pressure protective operation
P22
Outdoor fan IPDU error
P26
G-TR short protection error
P29
Comp position detective circuit system error
P31
Other indoor unit error (Group follower unit error)
Error in indoor group
AI-NET communication system error
Duplicated network adaptors
Check code name

Address Setup

09
Pre-check for address setup
<Check on outdoor unit>
1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P. C. board of the outdoor unit are set up
to “1”.
2. If other error code is displayed on 7-segment [B], remove the cause of trouble referring to “9. Troubleshooting”.
3. Check that [L08] is displayed on 7-segment display [B] on the interface P. C. board of the outdoor unit.
(L08: Indoor address unset up) (If the address setup operation has already finished in service time, etc, the above check code is not displayed, and
only [U1] is displayed on 7-segment display [A].)
Interface P. C. board
7-segment display [A] 7-segment display [B]
SW01 SW02 SW03
<Check on indoor unit>
1. Display check on remote controller (In case of wired remote controller)
Check that a frame as shown in the following left figure is displayed on LC display section of the remote controller.
GOOD
TEMP.
FILTER
TEST
RESET
(Power and operation stop)
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally turned on. Therefore check the following items.
• Check power supply of indoor unit.
• Check wiring between indoor unit and remote controller.
• Check whether there is cutoff of cable around the indoor control P. C. board or not, and check connection failure of
connectors.
• Check failure of transformer for the indoor microcomputer.
FAN
TIMER SET
SWING/FIXTIME
UNITSET CL
Normal status
ON / OFF
MODE
VENT
NO
GOOD
FILTER RESET
(Power is not normally turned on.)
TEMP.
TIMER SET
SWING/FIXTIME
TEST
Abnormal status
ON / OFF
FAN
MODE
VENT
UNITSET CL

Automatic Address Setup

Without central control : To the address setup procedure 1 With central control: To the address setup procedure 2
(Example)
Address setup procedure
Cable systematic diagram
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
In case of central control in a single refrigerant line
Outdoor
Indoor
Remote
controller
To procedure 1
Central
remote controller
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central
remote controller
Indoor
Remote
controller
In case of central control over refrigerant lines
Outdoor
Indoor
Remote
controller
To procedure 2
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central
remote controller
Indoor
Remote
controller
10
Address setup procedure 1
1. Tu rn on power of indoor/outdoor units.
(In order of indoor
2. After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is displayed in
7-segment display section on the interface P. C. board of the outdoor unit.
3. Push SW15 to start the setup of the automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
4. When the count Auto 1 ® Auto 2 ® Auto 3 is displayed in 7-segment
display section, and it changes from U. 1. - - - (U. 1. flash) to
U. 1. - - - (U. 1. light) , the setup finished.
5. When performing an automatic address setup on a single refrigerant
line with central control, connect relay connected between [U1, U2] and [U3, U4] terminals in the header unit.
®®
® Outdoor)
®®
REQUIREMENT
•When a group control is performed over the multiple refrigerant lines, be sure to turn on the power supplies of all the indoor units connected in a group at the time of address setup.
• If turning on the power for each refrigerant line to set up address, a header indoor unit is set for each line. Therefore, an alarm code “L03” (Duplicated header indoor units) is output in operation after address setup. In this case, change the group address from the wired remote controller for only one header unit is set up.
Header unit interface P. C. board
ON
1
2 3 4
1ON2 3 4
1ON2 3 4
1ON2 3 4
SW11
SW12
SW13
11 2 3 4
SW09SW08
SW14
1 2 3 4
SW10
ON ONON ON
1ON2 3 4
1
2 3 4
SW06
SW07
(Example)
Cabling systematic
diagram
Header unit interface P. C. board
SW04
SW05 SW15
D600 D601 D602 D603 D604
SW01
SW02 SW03
111
3
2, 4
5
U1 U2
U3 U4
For internal wiring between indoor and outdoor
Group control over
multiple refrigerant lines
Outdoor
Indoor
Indoor
Remote
Remote
controller
controller
For wiring of central control system
Outdoor
Indoor
Remote
controller
For internal wiring between outdoor units
controller
U5 U6
Indoor
Remote
Continued
U1 U2
For internal wiring between indoor and outdoor
U3 U4
For wiring of central control system
U5 U6
2
For internal wiring between outdoor units
11
Address setup procedure 2
1. Using SW13 and 14 on the interface P. C. board of the outdoor unit in each system, set up the address for each sys­tem. (At shipment from factory: Set to Address 1)
Note) Be careful not to duplicate addresses with the other refrigerant line.
Line address switch on outdoor interface P.C. board
Line
address
1 2 3 4 5 6 7 8
9 10 11 12 13 14
SW13 SW14
12341234
ЧЧЧЧЧ Ч ×××
¡
×× ××
¡
× ××
¡
¡
××× × × × × ×× × × × ×××× × ×× ×× × × × ××× × ×
¡
¡ ¡
¡ ¡
¡
¡ ¡
¡ ¡
¡
¡¡¡
¡ ¡ ¡ ¡
¡
¡ ¡
Line
address
15 16 17 18 19 20 21 22 23 24 25 26 27 28
(¡ : Switch ON, × : Switch OFF)
SW13 SW14
12341234
××
¡ ¡ ¡
×
¡¡¡¡
××××
¡
×××
¡¡
× ××
¡¡
¡
×× ×
¡ ¡
× ×
¡ ¡¡
× ×
¡
¡¡
×××
¡
××
¡¡
× ×
¡
¡ ¡
¡¡
: Is not used for setup of system address. (Do not change setup.)
2. Check that the relay connectors between [U1, U2] and [U3, U4]
terminals are not connected in all the outdoor units to which the central control is connected. (At shipment from factory: Connector not connected)
3. Tu rn on power of indoor/outdoor. (In order of indoor
4. After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the outdoor unit.
5. Push SW15 to start the setup of automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
6. When the count Auto 1 ® Auto 2 ® Auto 3 is displayed in
7-segment display section, and it changes from U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup finished.
7. Procedure 4. to 6. are repeated in other refrigerant lines.
8. How to set up the terminal resistance
When all the address setups have finished in the same refrigerant circuit system, put the terminal resistance in the same central control line into one.
• Remain only SW30-2 of the header outdoor unit with address 1 as
ON. (With end terminal resistance)
• Set up SW30-2 of the other header outdoor units to OFF.
(Without terminal resistance)
9. Connect the relay connector between [U1, U2] and [U3, U4] of the
header unit for each refrigerant line.
10. Then set up the central control address.
(For the central control address setup, refer to the Installation manual of the central control devices.)
®®
® outdoor)
®®
Header unit interface P. C. board
1ON2
SW30
1ON2 3 4
1ON2 3 4
1ON2 3 4
SW11
SW12
SW13
ON ONON ON
1ON2 3 4
1
2 3 4
11 2 3 4
SW06
SW07
SW09SW08
¡
××
¡¡ ¡¡
×
SW30
1ON2 3 4
SW14
1 2 3 4
SW10
¡
×
¡ ¡ ¡ ¡
Loading...
+ 28 hidden pages