Allowable length of refrigerant pipe and height difference
Follower unit C
Follower unit B
Height difference
between
outdoor units
H3 £ 5 m
Height difference
between outdoor
and indoor units
H1 £ 50 m
•Allowable length/height difference of the refrigerant pipe
Total extension of pipe (Liquid pipe/real length)
Farthest piping length L (*1)
Max. equivalent length of main piping
Equivalent length of farthest piping from 1 st branching Li (*1)
Pipe
Max. real length of indoor unit connecting piping
length
Max. real length between FS unit and indoor unit (*2)
Max. equivalent length of outdoor unit connecting pipe LO (*1)
Max. real length of outdoor unit connecting pipe
Max. equivalent length between FS unit and indoor unit Lj
Max. real length between FS unit and indoor unit which FS unit
control wiring is connected Lh (*2)
Height between
indoor unit and outdoor unit H1
Height between
Height
indoor unit H2
difference
Height between outdoor units H3
Height difference between indoor units in group control by one
FS unit H4
*1 : The farthest indoor unit from 1st branch to be named C, and fa rthest indoor unit from 1st branch to be named (q).
*2 : Attached connection cable can be used up to 5 m in pipe length between indoor unit and FS unit.
When the pipe length between indoor and FS unit exceeds 5 m, be sure to use the connection cable kit (RBC-CBK15FE).
• Restriction to the system
Max. No. of combined outdoor units
Max. capacity of combined outdoor units
Max. No. of connected indoor units
Max. capacity of connected indoor units
Min. capacity of connected indoor units
*3 : MMY-MAP1202FT8 up to 120%.
Header unit A
Outdoor unit
T-Shape branching
main piping
L1
Branching piping L2
Connecting piping of
1st
indoor unit
branching
section
L3
Indoor unit
Equivalent length corresponded to farthest piping L £ 150 m
Equivalent length corresponded to farthest piping after 1st branching Li £ 50 m
L4
d
FS unit
l
Indoor unit
Indoor unit which FS unit control wiring is connected.
H2 < 15 m 135% (*3)
H2 > 15 m 105%
Outdoor capacity : 70%
LbLc
La
LA
Main connecting piping between outdoor units
Length corresponded to farthest piping
between outdoor units LO £ 25 m
bca
hi jkg
L6 L7
L5
f
e
n
m
Real length
Equivalent length
Upper outdoor unit
Lower outdoor unit
Upper outdoor unit
Lower outdoor unit
3 units
84.0 kW
48 units
Branching header
L9
FS unit
<Cooling only> <Cooling only>
L8
FS unit
o
Lh
When connecting the plural indoor units to single FS unit.
Allowable value
Note 1) Combination of outdoor unit : Header unit (1 unit) + Follow unit
Note 2) Install the outdoor units in order of capacity.
Note 3) Refer to outdoor unit combination table in page 5.
Note 4) Piping to indoor units shall be per pendicular to piping to the
•Cautions concerned with installation/construction
1) The leading outdoor unit connected with the indoor
inter-unit pipe is made “A (Header unit)”.
2) Set the units in order of the outdoor capacity.
(A (Header unit) > B > C > D)
3) For the combination of the outdoor units, refer to
“Combination of outdoor unit” list.
Note:
In case of connecting method <Ex.2>, a large amount of
refrigerant and refrigerant oil may return to the head unit.
Therefore, set the T-shape joint so that oil does not enter directly.
+ a + b + c + d + e + f + g + h + i + j + k + l + m + n + o+ p + q
125 m
150 m
85 m
50 m
30 m
15 m
25 m
10 m
30 m
15 m
50 m
30 m
35 m
15 m
5 m
0.5 m
(0 to 2 units). Header unit is outdoor unit nearest to the connected indoor units.
Header
<Ex.1>
unit A
OK
Header
<Ex.2>
unit A
NO GOOD
Height difference between
indoor units H2 £ 35
(Upper outdoor unit)
Height difference between
indoor units in group control
by one FS unit H4 £ 0.5 m
Pipe section
LA + Lc + L1 + L3 + L4 + L5 + L6 + L7 + L8 + q
a + g, b + h, c + i, d + l, e + m, f + m, f + n, j, k
L1
L3 + L4 + L5 + L6 + L7 + L8 + q
g, h, i, l, m, n, L7 + o
LA + Lc (LA + Lb)
La, Lb, Lc
L7 + L8 + p, L7 + L8 + q
L7 + o
——
——
——
——
——
——
(Header unit > Follow unit 1 > Follow unit 2)
head outdoor unit as <Ex. 1>. Do not connect piping to indoor
units in the same direction of head outdoor unit as <Ex. 2>.
Follower
unit B
Follower
unit B
Follower
unit C
Follower
unit C
02
Addition of refrigerant
After vacuuming work, exchange the vacuum pump with the refrigerant bomb and then start the additional charging work
of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipe at the local site.
For refrigerant to be charged in pipe at the local site, calculate the amount and charge it additionally.
Note) If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without
addition of refrigerant.
Outdoor unit Model
Charging amount (kg)
Additional refrigerant
charge amount at local site
•Keeping valve of the outdoor unit closed, be sure to charge the liquid refrigerant into service port at liquid side.
• If the specified amount of refrigerant cannot be charged, open fully valves of outdoor unit at liquid and discharge/
suction gas sides, balance side operate the air conditioner in COOL mode under condition that valve at suction gas
side is a little returned to close side, and then charge refrigerant into service port at suction gas side. In this time,
choke the refrigerant slightly by operating valve of the bomb to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
•When refrigerant leaks and refrigerant shortage occurs in the system, recover the refrigerant in the system and recharge refrigerant newly up to the correct level.
<Entry of refrigerant charge amount>
•Fill the additional refrigerant record column of the wiring diagram indication plate with the additional refrigerant
• The total refrigerant amount means the total value of the refrigerant amount at shipment and the additional refriger-
Additional refrigerant
amount/1m liquid pipe (kg/m)
(mm)
6.4
9.5
12.7
15.9
19.1
22.2
amount at installation work, total refrigerant amount and the name of the service man who charged refrigerant at
installation time.
0.025
0.055
0.105
0.160
0.250
0.350
ant amount at installation time. The refrigerant amount at the shipment is one described on the “Unit nameplate”.
MMY-MAP0802FT8MMY-MAP1002FT8MMY-MAP1202FT8
Real length
=××
( )
of liquid pipe
Additional refrigerant charge
amount per 1m liquid pipe (Table 1)
L1 : Real total length of liquid pipe Ø6.4 (m)
L2 : Real total length of liquid pipe Ø9.5 (m)
L3 : Real total length of liquid pipe Ø12.7 (m)
System : 10HP
Combined
(HP)
8
10
12
16
18
20
24
26
28
30
Combined outdoor unit
8
10
12
8 8
10 8
1010
8 8 8
10 8 8
1010 8
101010
(HP)
11.5
Compensation by
1.3
system HP (Table 2)
C (Corrected refrigerant amount)
–1.5
–4.5
–3.0
–1.5
(kg)
2.0
2.5
3.0
0.0
2.0
0.0
REQUIREMENT
Refrigerant Piping Diagram (Outdoor)
03
Inverter unit (8, 10, 12HP)
Model: MMY-MAP0802FT8, MAP1002FT8, MAP1202FT8
Propeller fan
Fan motor
FM
(Right side)
Main heat exchanger
(Left side)
Main heat exchanger
Sub heat exchanger (Right side)
Sub heat exchanger (Left side)
Solenoid valve (SV11)
Check valve
Solenoid valve
Oil
separator
Strainer
Check valveCheck valve
tube
Sensor
(TK3)
Strainer
Check
valve
Sensor
(TK1)
(SV3A)
Check valve
Strainer
Solenoid valve
(SV3C)
Strainer
Check
valve
Capillary tube
Sensor
(TK2)
Oil tank
Solenoid valve
(SV3B)
Check valve
Compressor 2
Capillary
Sensor (TK4)
Solenoid valve
(SV2)
(Inverter)
4-Way valve
Capillary
tube
Capillary tube
Solenoid valve
(SV42)
High-pressure
switch
Sensor
(TD2)
Sensor
(TO)
Pulse motor valve
Solenoid valve
(PMV1) (PMV2)
Check valve
Strainer
Sensor
(TL)
Liquid
tank
Check
joint
StrainerStrainer
Service valve
Service valve at
of balance pipe
discharge gas side
Service valve
Service valve at
at liquid side
suction gas side
Sensor
(TE1)
Strainer
(SV12)
Strainer
(PMV3)
Check valve
Solenoid valve
(SV5)
Capillary
High-pressure
tube
Solenoid valve
(SV6)
Solenoid valve
Solenoid valve
sensor
Check joint
Capillary tube
Strainer
(SV3D)
Capillary tube
(SV41)
High-pressure
switch
Sensor
(TD1)
Compressor 1
(Inverter)
Capillary tube
Solenoid valve
(SV3E)
Capillary tubeCapillary tube
Strainer
Sensor
(TS1)
Sensor
(TS2)
Low-pressure
Accumulator
sensor
Check
joint
Explanation of functional parts
Functional part name
Solenoid valve
4-way valve
Pulse motor valve
Oil separator
Temp. sensor
(Connector CN324: Red)
SV3A
Closed : Allows oil to collect/remain in the oil tank.
Open : Allows oil to exit the oil tank.
(Connector CN313: Blue)
SV3B
Open : Allows oil to return to the outdoor unit via the balance pipe.
(Connector CN314: Black)
SV3C
Open : Pressurizes the oil tank.
(Connector CN323: White)
SV3D
Open : Supplies oil to the compressor from the oil separator.
(Connector CN323: White)
SV3E
Open : Tu rns on during operation and balances oil between compressors.
(Hot gas bypass) (Connector CN312: White)
1) Low pressure release function
ASV2
2) High pressure release function
3) Gas balance function during stop time
(Gas balance control for compressor start-up) (Connector CN311: Blue)
SV41
1) For gas balance start
SV42
2) High pressure release function
3) Low pressure release function
(Connector CN310: White)
SV5
1) Increase of No. of heating indoor units, Gas balance function in defrost time
2) Low-pressure balance function of discharge gas pipe during all cooling operation
(Connector CN309: White)
SV6
1) Liquid bypass function for discharge temp. release (Cooling bypass circuit)
(Connector CN322: White)
SV11
1) For shutdown discharge gas (During all cooling operation and defrost operation)
(Connector CN319: White)
SV12
1) Flow-rate control function of refrigerant to sub heat exchanger during simultaneous operation
2) Flow-rate control function of refrigerant to sub heat exchanger during defrost operation
(Connector CN317: Blue)
1) Oil balancing pipe between outdoor unit (This unit does not use this Balance pipe.)
Only cooling operation without heating operation
Outdoor heat exchanger (Main heat exchanger) is used as condenser.
Only heating operation without cooling operation
Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
MIU for simultaneous operation
Cooling/heating simultaneous operation with subjective cooling operation
Outdoor heat exchanger (Sub heat exchanger) is used as condenser.
Cooling/heating simultaneous operation with subjective heating operation
Outdoor heat exchanger (Main heat exchanger) is used as evaporator.
Using reversing operation of 4-way valve, ice of the outdoor heat
exchanger is dissolved with single cooling cycle.
Functional outline
Outline
Configuration of outdoor unit heat exchangerFlow Selector Unit (FS Unit)
* RBM-Y1801FE has two “SVS” valves.
Check
valve
Strainer
SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipeSuction gas pipe
To indoor
gas side
To indoor
liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
Check
valve
Strainer
SVS SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipe Suction gas pipe
To indoor
gas side
To indoor
liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
* RBM-Y2802FE has three “SVS” valves and two “SVD”.
Check
valve
Strainer
SVS SVS
SVSS
SVDD
SVD
Liquid pipe
Strainer
Discharge gas pipe Suction gas pipe
To indoor
gas side
To indoor
liquid side
Strainer
Capillary
tube
Capillary
tube
Capillary
tube
SVS
RBM-Y1122FE
Propeller fan
Fan motor
Main heat exchanger
RBM-Y1802FE
Wind
Sub heat
exchanger
Front side
(Right)
Sub heat
exchanger
Rear side
(Left)
Wind
RBM-Y2802FE
06
Functional part name
Solenoid valve
(Discharge gas block valve)
SVD
1) High pressure gas circuit during heating operation
(Suction gas block valve)
SVS
1) Low pressure gas circuit during cooling operation
(Pressure valve)
SVDD
1) For pressurizing when No. of heating indoor units increases.
(Reducing valve)
SVSS
1) For recovery of refrigerant of the stopped indoor unit of which cooling thermo-OFF
2) For reducing pressure when No. of heating indoor units decreases.
Functional outline
System Refrigerant Cycle Drawing
07
Refrigerant piping systematic diagram in system
<Selection of operation mode>
For the selection of each operation mode, see the table below:
“Stop Once” means the system does not operate for 3 minutes after operation before update has stopped.
(Displayed in unit other than indoor unit with priority)
L07
Group line in individual indoor unit
L08
Indoor group/Address unset
L09
Indoor capacity unset
L10
Outdoor capacity unset
L17
Inconsistency error of outdoor units
L18
FS unit error
L20
Duplicated central control addresses
L28
Over No. of connected outdoor units
L29
No. of IPDU error
L30
Auxiliary interlock in indoor unit
L31
IC error
P01
Indoor fan motor error
P03
Discharge temp TD1 error
P04
High-pressure SW detection error
P05
Phase-missing detection / Phase order error
P07
Heat sink overheat error
P10
Indoor overflow error
P12
Indoor fan motor error
P13
Outdoor liquid back detection error
P15
Gas leak detection
P17
Discharge temp TD2 error
P19
4-way valve inverse error
P20
High-pressure protective operation
P22
Outdoor fan IPDU error
P26
G-TR short protection error
P29
Comp position detective circuit system error
P31
Other indoor unit error (Group follower unit error)
—
Error in indoor group
—
AI-NET communication system error
—
Duplicated network adaptors
Check code name
Address Setup
09
Pre-check for address setup
<Check on outdoor unit>
1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P. C. board of the outdoor unit are set up
to “1”.
2. If other error code is displayed on 7-segment [B], remove the cause of trouble referring to “9.Troubleshooting”.
3. Check that [L08] is displayed on 7-segment display [B] on the interface P. C. board of the outdoor unit.
(L08: Indoor address unset up)
(If the address setup operation has already finished in service time, etc, the above check code is not displayed, and
only [U1] is displayed on 7-segment display [A].)
Interface P. C. board
7-segment display [A]7-segment display [B]
SW01 SW02 SW03
<Check on indoor unit>
1. Display check on remote controller (In case of wired remote controller)
Check that a frame as shown in the following left figure is displayed on LC display section of the remote controller.
GOOD
TEMP.
FILTER
TEST
RESET
(Power and operation stop)
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally turned
on. Therefore check the following items.
• Check power supply of indoor unit.
• Check wiring between indoor unit and remote controller.
• Check whether there is cutoff of cable around the indoor control P. C. board or not, and check connection failure of
connectors.
• Check failure of transformer for the indoor microcomputer.
FAN
TIMER SET
SWING/FIXTIME
UNITSET CL
Normal status
ON / OFF
MODE
VENT
NO
GOOD
FILTER
RESET
(Power is not normally turned on.)
TEMP.
TIMER SET
SWING/FIXTIME
TEST
Abnormal status
ON / OFF
FAN
MODE
VENT
UNITSET CL
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control: To the address setup procedure 2
(Example)
Address setup procedure
Cable systematic diagram
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
In case of central control in a single refrigerant line
Outdoor
Indoor
Remote
controller
To procedure 1
Central
remote controller
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central
remote controller
Indoor
Remote
controller
In case of central control over refrigerant lines
Outdoor
Indoor
Remote
controller
To procedure 2
Indoor
Remote
controller
Outdoor
Indoor
Remote
controller
Central
remote controller
Indoor
Remote
controller
10
Address setup procedure 1
1. Tu rn on power of indoor/outdoor units.
(In order of indoor
2. After approx. 1 minute, check that U. 1. L08 (U. 1. flash) is displayed in
7-segment display section on the interface P. C. board of the outdoor unit.
3. Push SW15 to start the setup of the automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
4. When the count Auto 1 ® Auto 2 ® Auto 3 is displayed in 7-segment
display section, and it changes from U. 1. - - - (U. 1. flash) to
U. 1. - - - (U. 1. light) , the setup finished.
5. When performing an automatic address setup on a single refrigerant
line with central control, connect relay connected between [U1, U2]
and [U3, U4] terminals in the header unit.
®®
® Outdoor)
®®
REQUIREMENT
•When a group control is performed over the multiple
refrigerant lines, be sure to turn on the power supplies
of all the indoor units connected in a group at the time
of address setup.
• If turning on the power for each refrigerant line to set
up address, a header indoor unit is set for each line.
Therefore, an alarm code “L03” (Duplicated header
indoor units) is output in operation after address setup.
In this case, change the group address from the wired
remote controller for only one header unit is set up.
Header unit interface P. C. board
ON
1
2 3 4
1ON2 3 4
1ON2 3 4
1ON2 3 4
SW11
SW12
SW13
112 3 4
SW09SW08
SW14
1 2 3 4
SW10
ONONONON
1ON2 3 4
1
2 3 4
SW06
SW07
(Example)
Cabling systematic
diagram
Header unit interface P. C. board
SW04
SW05 SW15
D600 D601 D602 D603 D604
SW01
SW02 SW03
111
3
2, 4
5
U1 U2
U3 U4
For internal
wiring between
indoor and
outdoor
Group control over
multiple refrigerant lines
Outdoor
Indoor
Indoor
Remote
Remote
controller
controller
For wiring of
central control
system
Outdoor
Indoor
Remote
controller
For internal
wiring between
outdoor units
controller
U5 U6
Indoor
Remote
Continued
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
2
For internal
wiring between
outdoor units
11
Address setup procedure 2
1. Using SW13 and 14 on the interface P. C. board of the outdoor unit in each system, set up the address for each system. (At shipment from factory: Set to Address 1)
Note) Be careful not to duplicate addresses with the other refrigerant line.
Line address switch on outdoor interface P.C. board
Line
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SW13SW14
12341234
ЧЧЧЧЧ
Ч×××
¡
××××
¡
×××
¡
¡
××××
×××
×××
××
××××
×××
×××
××
×××
××
¡
¡¡
¡ ¡
¡
¡ ¡
¡¡
¡
¡¡¡
¡ ¡
¡ ¡
¡
¡
¡
Line
address
15
16
17
18
19
20
21
22
23
24
25
26
27
28
(¡ : Switch ON, × : Switch OFF)
SW13SW14
12341234
××
¡ ¡ ¡
×
¡¡¡¡
××××
¡
×××
¡¡
×××
¡¡
¡
×××
¡¡
××
¡¡¡
××
¡
¡¡
×××
¡
××
¡¡
××
¡
¡
¡
¡¡
: Is not used for setup of system address. (Do not change setup.)
2. Check that the relay connectors between [U1, U2] and [U3, U4]
terminals are not connected in all the outdoor units to which the
central control is connected.
(At shipment from factory: Connector not connected)
3. Tu rn on power of indoor/outdoor. (In order of indoor
4. After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the outdoor unit.
5. Push SW15 to start the setup of automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
6. When the count Auto 1 ® Auto 2 ® Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup finished.
7. Procedure 4. to 6. are repeated in other refrigerant lines.
8. How to set up the terminal resistance
When all the address setups have finished in the same refrigerant
circuit system, put the terminal resistance in the same central
control line into one.
• Remain only SW30-2 of the header outdoor unit with address 1 as
ON. (With end terminal resistance)
• Set up SW30-2 of the other header outdoor units to OFF.
(Without terminal resistance)
9. Connect the relay connector between [U1, U2] and [U3, U4] of the
header unit for each refrigerant line.
10. Then set up the central control address.
(For the central control address setup, refer to the Installation
manual of the central control devices.)
®®
® outdoor)
®®
Header unit interface P. C. board
1ON2
SW30
1ON2 3 4
1ON2 3 4
1ON2 3 4
SW11
SW12
SW13
ONONONON
1ON2 3 4
1
2 3 4
112 3 4
SW06
SW07
SW09SW08
¡
××
¡¡
¡¡
×
SW30
1ON2 3 4
SW14
1 2 3 4
SW10
¡
×
¡
¡
¡
¡
Loading...
+ 28 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.