Toshiba MMY-MAP0801FT8, MMY-MAP1201FT8, MMY-MAP1001FT8 User Manual

INSTALLATION MANUAL
Heat Reco very Type
FILE NO. A04-002
R410A
Indoor Unit
<4-way Air Discharge Cassette Type>
MMU-AP0091H, AP0121H, AP0151H, MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H
<2-way Air Discharge Cassette Type>
MMU-AP0071WH, AP0091WH, AP0121WH, MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH, AP0481WH*
* CHINA market only
<1-way Air Discharge Cassette Type>
MMU-AP0071YH, AP0091YH, AP0121YH, MMU-AP0151SH, AP0181SH, AP0241SH
<Concealed Duct Standard Type>
MMD-AP0071BH, AP0091BH, AP0121BH, MMD-AP0151BH, AP0181BH, AP0241BH, MMD-AP0271BH, AP0301BH, AP0361BH, MMD-AP0481BH, AP0561BH
<Concealed Duct High Static Pressure Type>
MMD-AP0181H, AP0241H, AP0271H, MMD-AP0361H, AP0481H
Outdoor Unit
<Inverter Unit>
MMY-MAP0801FT8 MMY-MAP1001FT8 MMY-MAP1201FT8
FS unit
RBM-Y1121FE RBM-Y1801FE
<Under Ceiling Type>
MMC-AP0151H, AP0181H, AP0241H, MMC-AP0271H, AP0361H, AP0481H
<High Wall Type>
MMK-AP0071H, AP0091H, AP0121H, MMK-AP0151H, AP0181H, AP0241H
<Floor Standing Cabinet Type>
MML-AP0071H, AP0091H, AP0121H, MML-AP0151H, AP0181H, AP0241H
<Floor Standing Concealed Type>
MML-AP0071BH, AP0091BH, AP0121BH, MML-AP0151BH, AP0181BH, AP0241BH
<Floor Standing Type>
MMF-AP0151H, AP0181H, AP0241H MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H
PRINTED IN JAPAN, Aug, 2004 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
Outdoor unit
e.g., charged amount (15kg)
Indoor unit
Important
NOTE : 2
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant piping
Outdoor unit
Very small room
Small room
Mechanical ventilation device - Gas leak detector
Medium room
Large room
NOTE 3 : The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
40
Range below the
35
density limit of 0.3 kg/m³
30
(countermeasures not needed)
25 20 15 10
5
Min. indoor floor area
0
10 20 30
Total amount of refrigerant
Range above the density limit of 0.3 kg/m³ (countermeasures needed)
Indoor unit
kg
NOTE
A direct current motor is adopted for indoor fan motor in the Concealed Duct Standard Type air conditioner. Caused from its characteristics, a current limit works on the direct current motor. When replacing the high­performance filter or when opening the service panel, be sure to stop the fan. If an above action is executed during the fan operation, the protectiv e control works to stop the unit operation, and the check code “P12” may be appear. However it is not a trouble. When the desired operation has finished, be sure to reset the system to clear “P12” error code using the electric leak breaker of the indoor unit. Then push the operation ON/OFF button of the remote controller to return to the usual operation.
CONTENTS
1. SELECTING A LOCATION FOR INSTALLATION ..................................... 4
2. SAFETY NOTES......................................................................................... 8
3. CHECK POINTS......................................................................................... 9
4. KEY POINTS OF AIR CONDITIONER INSTALLATION .......................... 10
5. REFRIGERANT PIPE INSTALLATION .................................................... 11
6. INDOOR UNIT INSTALLATION................................................................ 41
7. FLOW SELECTOR UNIT INSTALLATION ............................................... 77
8. OUTDOOR UNIT INSTALLATION............................................................ 81
9. ELECTRIC WIRING .................................................................................. 87
10. INDOOR UNIT TERMINAL BOARD PLACEMENT AND WIRING ......... 102
11. DRAIN PIPE INSTALLATION................................................................. 107
12. ADJUSTMENT OF AIR DIRECTION...................................................... 115
13. APPLIED CONTROL.............................................................................. 119
14. ADDRESS SETUP.................................................................................. 123
15. TEST OPERATION ................................................................................. 136
16. SUPPORT FUNCTION IN TEST OPERATION ....................................... 143
17. TROUBLESHOOTING............................................................................ 165
18. AIR SPEED CHARACTERISTICS.......................................................... 170
19. FAN CHARACTERISTICS...................................................................... 175
CAUTION New Refrigerant Air Conditioner Installation
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY OZONE LAYER.
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A). For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust
does not enter. Moreover, do not use the existing piping because there are problems with pressure­resistance force and impurity in it.
1. SELECTING A LOCATION FOR INSTALLATION
WARNING
Install the air conditioner certainly at a location to sufficiently withstand the weight.
If the strength is insufficient, the unit may fall down resulting in human injury.
Perform a specified installation work to guard against a great wind such as typhoon or an earth quake.
An incomplete installation can cause accidents by the units failing and dropping.
The following models must be installed at height 2.5m or more from the floor. (Concealed type duct type and cassette type air conditioners)
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous
because you may contact with revolving fan or active electricity.
Installation Location Selection for Outdoor unit
Obtain permission from the customer to install the unit in a location that satisfies the following requirements :
• A location that permits level installation of the unit.
• A location that provides enough space to service the unit safety
• A location where water draining from the unit will not pose a problem
Avoid installing in the following places.
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)
• Place exposed to oil, vapor, oil smoke or corrosive gas.
• Place where organic solvent is used nearby.
• Place close to a machine generating high frequency.
• Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)
• Place where noise of the outdoor unit is easily transmitted. (When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)
• Place with poor ventilation. (Especially in Concealed duct type indoor unit, before air ducting work, check whether value of air volume, static pressure and duct resistance are correct.)
4
Equipments
1. Outdoor units
Corresponding HP
Model name MMY- MAP0801FT8 MAP1001FT8 MAP1201FT8
Cooling capacity (kW) 22.4 28.0 33.5
Heating capacity (kW) 25.0 31.5 35.5
HP
(Capacity code)
8 HP ( 8) MAP0801HT8 1 MAP0801FT8 1
10 H P (10) MAP1001HT8 1 MAP1001FT8 1 12 H P (12) MAP1201HT8
Model name
MMY-
combined units
8 HP 10 HP 12 HP
No. of
1
Inverter 8HP
Inverter unit
MMY-
Used
Q’ty
Inverter 10HP
MMY-
Allocation atandard of model name
MMY– MAP T 8
F
Used
Q’ty
Appearance
Inverter 12HP
MMY-
MAP1201FT8
Used
Q’ty
1
Power supply specifications, 3Ø 380–415 V, 50Hz ....... 8
T : Capacity variable unit
F : Heat recovery
Development series No. Capacity rank HP x 10 New refrigerant R410A M : Single module unit, No mark : Combined Model name Modular Multi
2. FS units (Flow selector units)
Model name Inverter unit Appearance
RBM-Y1121FE Capacity rank f or indoor unit : Type 007 to 030
RBM-Y1801FE Capacity rank f or indoor unit : Type 036 to 056
Accessory part : Connection cable kit (RBC-CBK15FE), up to 15m.
5
3. Indoor units
Type Appearance Model name Capacity rank Capaci t y code
009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 030 type 3.2 9.0 036 type 4 11.2 048 type 5 14.0 056 type 6 16.0 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 030 type 3.2 9.0
1)
048 type 5 14.0 16.0 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 030 type 3.2 9.0 036 type 4 11.2 048 type 5 14.0 056 type 6 16.0 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 036 type 4 11.2 048 type 5 14.0 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 036 type 4 11.2 048 type 5 14.0 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 007 type 0.8 2.2 009 type 1 2.8 012 type 1.25 3.6 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 015 type 1.7 4.5 018 type 2 5.6 024 type 2.5 7.1 027 type 3 8.0 036 type 4 11.2 048 type 5 14.0 056 type 6 16.0
4-way Air Discharge Cassette Type
2-way Air Discharge Cassette Type
1-way Air Discharge Cassette Type
Concealed Duct Standard Type
Concealed Duct High Static Pressure Type
Under Ceiling Type
High Wall Type
Floor Standing Cabinet Type
Floor Standing Concealed Type
Floor Standing Ty pe
MMU-AP0091H MMU-AP0121H MMU-AP0151H MMU-AP0181H MMU-AP0241H MMU-AP0271H MMU-AP0301H MMU-AP0361H MMU-AP0481H MMU-AP0561H MMU-AP0071WH MMU-AP0091WH MMU-AP0121WH MMU-AP0151WH MMU-AP0181WH MMU-AP0241WH MMU-AP0271WH MMU-AP0301WH MMU-AP0481WH* MMU-AP0071YH MMU-AP0091YH MMU-AP0121YH MMU-AP0151SH MMU-AP0181SH MMU-AP0241SH MMD-AP0071BH MMD-AP0091BH MMD-AP0121BH MMD-AP0151BH MMD-AP0181BH MMD-AP0241BH MMD-AP0271BH MMD-AP0301BH MMD-AP0361BH MMD-AP0481BH MMD-AP0561BH MMD-AP0181H MMD-AP0241H MMD-AP0271H MMD-AP0361H MMD-AP0481H MMC-AP0151H MMC-AP0181H MMC-AP0241H MMC-AP0271H MMC-AP0361H MMC-AP0481H MMK-AP0071H MMK-AP0091H MMK-AP0121H MMK-AP0151H MMK-AP0181H MMK-AP0241H MML-AP0071H MML-AP0091H MML-AP0121H MML-AP0151H MML-AP0181H MML-AP0241H MML-AP0071BH MML-AP0091BH MML-AP0121BH MML-AP0151BH MML-AP0181BH MML-AP0241BH MMF-AP0151H MMF-AP0181H MMF-AP0241H MMF-AP0271H MMF-AP0361H MMF-AP0481H MMF-AP0561H
*1) China only
Cooling
capacity (kW)
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
18.0
6.3
8.0
9.0
12.5
16.0
5.0
6.3
8.0
9.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
12.5
16.0
18.0
6
Tools
Required Tools
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) (2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) (3) Tools commonly used for R410A and for conventional refrigerant (R22) The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Conventional air
conditioner installation
Whether new equipment can be used with conventional refrigerant
¡
*(Note 1)
× ×
¡
¡
×
¡
×
No.
  
  
Used tool
Flare tool Copper pipe gauge for
adjusting projection margin
Torque wrench Gauge manifold Charge hose
Vacuum pump adapter Electronic balance for
refrigerant charging Refrigerant cylinder Leakage detector Charging cylinder
Usage
Pipe flaring Flaring by conventional
flare tool
Connection of flare nut
Evacuating, refrigerant charge, run check, etc.
Vacuum evacuating Refrigerant charge Refrigerant charge
Gas leakage check Refrigerant charge
air conditioner installation
Existence of new equipment for R410A
Yes
Yes
Yes
Yes
Yes Yes Yes
Yes
(Note 2)
R410A
Whether conventional equipment can be used
*(Note 1)
*(Note 1)
× ×
×
Yes
× × ×
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter. (2) Torque wrench (3) Pipe cutter
(4) Reamer (5) Pipe bender (6) Level vial (7) Screwdriver (+, –) (8) Spanner or Monkey wrench
(9) Hole core drill (10) Hexagon wrench
(Opposite side 4mm) (11) Tape measure (12) Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
7
2. SAFETY NOTES
Ensure that all Local, National and International regulations are satisfied.
Read this SAFETY NOTES carefully before Installation.
The precautions described below include the important items regarding safety. Observe them without fail.
After the installation work, perform a trial operation to check for any problem. Follow the Owners Manual to explain how to use and maintain the unit to the customer.
Turn off the main power supply switch (or breaker) before the unit maintenance.
Ask the customer to keep the Installation Manual together with the Owners Manual.
WARNING
• Ask an authorized dealer or qualified installation professional to install/maintain the air
conditioner.
Inappropriate installation may result in water leakage, electric shock or fire.
• Turn off the main power supply switch or breaker before attempting any electrical work.
Make sure all power switches are off. Failure to do so may cause electric shock.
• Connect the connecting wire correctly.
If the connecting wire is connected in a wrong way, electric parts may be damaged.
• When moving the air conditioner for the installation into another place, be very careful not to enter
any gaseous matter other than the specified refrigerant into the refrigeration cycle.
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it as a result causes pipe burst and injuries on persons.
• Do not modify this unit by removing any of the safety guards or by by-passing any of the safety
interlock switches.
• Exposure of unit to water or other moisture before installation may cause a short-circuit of
electrical parts.
Do not store it in a wet basement or expose to rain or water.
• After unpacking the unit, examine it carefully if there are possible damage.
• Do not install in a place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
• Perform installation work properly according to the Installation Manual.
Inappropriate installation may result in water leakage, electric shock or fire.
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that
the concentration of refrigerant leakage occur in the room does not exceed the critical level.
• Install the air conditioner securely in a location where the base can sustain the weight adequately.
• Perform the specified installation work to guard against an earthquake.
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
• After the installation work, confirm that refrigerant gas does not leak.
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might generate.
• Electrical work must be performed by a qualified electrician in accordance with the Installation
Manual. Make sure the air conditioner uses an exclusive power supply.
An insufficient power supply capacity or inappropriate installation may cause fire.
• Use the specified wires for wiring connect the terminals securely fix. To prevent external forces
applied to the terminals from affecting the terminals.
• Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock.
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks, and stays around the unit, a fire may occur.
8
3. CHECK POINTS
Check before operation
Turn on the main power switch 12 hours or more before starting the operation.
Check whether earth wire is disconnected or out of place.
Check that air filter is installed to the indoor unit.
Heating capacity
For heating operation, a heat pump type which absorbs the outdoor heat and deliver the heat in the room is adopted. If the outdoor temperature lowers, the heating capacity decreases.
When the outdoor temperature is low, common use with other heating devices is recommended.
Defrost operation in heating operation
If frost is found on the outdoor unit during heating operation, the defrost operation starts automatically (for approx. 2 to 10 minutes) so as to increase the heating effect.
During defrost operation, the fans of both indoor and outdoor units stop.
Protection for 3 minutes
The outdoor unit does not operate for approx. 3 minutes after air conditioner has been immediately restarted after stop, or power switch has been turned on. This is to protect the system.
Main power failure
If a power failure occurs during operation, all operations stop.
When the power is turned on after power failure, the operation lamp of the remote controller flashes to notify.
When restarting the operation, push ON/OFF button again.
Fan rotation of stopped unit
While other indoor units operate, the fan on indoor units on stand-by rotates to protect the machine once per approx. 1 hour for several minutes.
Protective device (High pressure switch)
The high pressure switch operate the air conditioner automatically stops when excessive load is applied to the air conditioner. If the protective device works, the operation lamp keeps lit but the operation stops. When the protective device works, CHECK characters in the remote controller display section flash. The protective device may work in the following cases.
Cooling
When air inlet or outlet of the outdoor unit is closed.
When strong wind blows continuously against air outlet of the outdoor unit.
Heating
When much dust or dirt is excessively adhered to air filter of the indoor unit.
When air outlet of the indoor unit is blocked.
NOTE
If the protective device works, turn off the main power switch, remove the cause, and then restart the operation.
Cooling/ heating operation of Multi system air conditioner
When COOL or HEAT mode is fixed by the manager of the air conditioner, other operation than the set mode is unavailable. If other operation than the set mode has been performed, [ operation part goes on and the operation stops.
Operating temperature of Super HRM
When outdoor temperature goes out of specified range, or mark is indicated on the remote controller display and required operation will stop.
[Notice]
This indication is not failure.
When outdoor temperature goes back to specified range,
Operation stops because concurrent operation can not be kept in the condition of out of specification for Super HRM.
(Outdoor temp. (DB) < 5°C : Cooling, > 21°C : Heating)
Do not use Super HRM for other than personal usage where the ambient temperature may go down below 5°C.
(For example, OA equipment/Electric device/Food/Animals and plants/Art object)
& : When heating operation. : When cooling operation.
or disappear and start normal operation.
Characteristics of heating operation
Air does not blow out immediately after start of the operation. When the indoor heat exchanger has been heated after 3 to 5 minutes passed (differs according to temperature of indoor/outdoor temperature), hot air starts blowing.
During operation, the outdoor unit may stop when outdoor temperature becomes high.
When other indoor unit performs heating operation during fan operation, fan operation may be stopped temporarily to
prevent discharge of hot air.
9
PRE-HEAT] or [ Operation ready] on the
4.
g
KEY POINTS OF AIR CONDITIONER INSTALLATION
In order to prevent problems before they arise, carefully read (1) the Installation Manual provided with the equipment, and (2) the Owners Manual before installing the air conditioner.
4-1. Flow of Air Conditioner Installation Work
[Step] [Key Points]
(Prior to Installation)
Determination of extent of installation work
Drafting of diagrams
(Installation)
Sleeve/insert installation
Indoor unit and flow selector unit installation
Refrigerant pipe installation
(to outdoor outlet)
Drain pipe installation
Duct installation
Insulation work
Clearly determine the extent of the installation work. Draft :
Control wiring system diagram
Refrigerant line system diagram
Power wiring system diagram
Pay careful attention to the downward slope of the drain pipe. Be sure to check the name of the model in order to avoid any
installation mistakes. If the model has an installation pattern, attach the pattern to the ceiling to mark the position of the ceiling openings and to keep dust away.
Make sure that the pipe system is dry, clean, and airtight. When brazing pipes, blow out the system with nitrogen gas.
Do not forget the system indications.
Pipes should have downward slope (of at least 1/100). Make sure the duct is lar
Be careful not to make any errors in the external static pressure calculations.
Be especially careful to close off all gaps where connections are m ade to the indoor unit, and at joints in the branching kit. Do not forget the drain pipes.
e enough to carry the desired volume of air.
Use two-core shielded wires for the control wires, and use separate
(control wires and power wires)
Electrical work
Various s witc h setting s
Outdoor unit base installation
Outdoor unit installation
Outside circulation, refrigerant pipe instal lation
Gas-leak test
Vacuum suction
Addition of refrigerant
Ceiling panel installation
Test operation and adjustment
Owner’s Manual transfer
power supplies for the indoor and outdoor units. For connecting the flow selector unit, be sure to use the attached cable or connection cable kit sold separately.
Set the switches correctly, as indicated in the control wiring system diagram.
Make sure that the base is level. Provide for adequate air flow and service space around the outdoor
unit. Indicate the system names clearly. From outside outlet to outdoor unit. In the final test, the system must be pressurized at 3.73MPa
(38kg/cm²G) for 24 hours with no decrease in pressure. Use a vacuum pump with reverse flaw prevention adaptor with a large
output volume and that can achieve a high level of vacuum. Record the amount of refrigerant that was added to the system on
both the outdoor unit and on the pre-test operation checklist. Make sure that the ceiling panel is attached to the ceiling material
tightly, with no gaps. Operate the indoor units one by one, making sure that all wiring and
pipes are connected correctly, and fill out the checklist. Explain how to operate the system clearly and concisely.
The procedure described above presents only the general sequence of steps; the sequence of steps may have to be altered according to the circumstances of any specific installation job.
10
5. REFRIGERANT PIPE INSTALLATION
5-1. Work Procedure
Indoor unit installation
Sizing
the pipes
Preliminary
installation
Nitrogen gas blow
Flaring
Flushing
Brazing
Leak test
5-2. Three Principles of Refrigerant Pipes
<Observe the three principles of refrigerant pipes>
Causes of Problems Preventing Problems
Moisture (in the form of
Dry
Clean
rainwater or water used during installation, for example) getting inside of the pipes
Moisture from condensation forming or seeping into the pipes
Oxidation inside pipes during brazing
Dirt, dust, or foreign matter getting inside pipes
Careful
handling
of pipes
Nitrogen gas blow
Careful handling of pipes
Flushing
Vacuum
suction
Vacuum
suction
Flushing
Use of suitable materials
(copper pipes, solder, etc.)
Air-
tight
Poor brazing
Poor flaring
Perform basic work
of brazing carefully
Perform basic work
of flaring carefully
<Three principles of refrigerant pipes>
Dry
Make sure there is no moisture
inside of the pipes
Moisture
Make sure there is no dirt
Clean Airtight
Make sure the refrigerant
inside of the pipes
Dirt
Not good Not good Not good
Leak test
does not leak
Leak
11
5-3. Selecting the Refrigerant Line Material
q
q
• Refrigerant pipes
• Material: Phosphoric deoxidized seam-less pipe
• Capacity code of outdoor unit / indoor unit
For each indoor unit, the capacity code is determined for every capacity rank.
For each outdoor unit, the capacity code is determined for every capacity rank. The Max. number of the
connectable indoor units and the total capacity code value of the indoor units are also determined. Against the capacity code of the outdoor unit, the total capacity codes of the connectable indoor units differ
according to the height difference between indoor units.
 
When the height difference between indoor units is 15m or less : Up to 135%* of capacity code of outdoor unit
(* For 12HP system, up to 120%.)
When the height difference between indoor units is 15m or more : Up to 105% of capacity code of outdoor unit
Table 1 Table 2
Indoor unit
capacity rank
007 type 0.8 2.2
009 type 1 2.8
012 type 1.25 3.6
015 type 1.7 4.5
018 type 2 5.6
024 type 2.5 7.1
027 type 3 8
030 type 3.2 9
036 type 4 11.2
048 type 5 14
056 type 6 16
Capacity code
E
uivalent toHPEquivalent to
capacity
Outdoor unit
model name
MMY-MAP0801FT8 8 22.4 13 5.6 15.7 10.8 30.2
MMY-MAP1001FT8 10 28.0 16 7.0 19.6 13.5 37.8
MMY-MAP1201FT8 12 33.5 16 8.4 23.5 14.4 40.3
Capacity code
E
uivalent toHPEquivalent to
capacity
No. of
indoor units
Total capacity code of connectable indoor units
Min Max.
Equivalent
to HP
Equivalent to capacity
Equivalent
to HP
Table 3
No. Piping parts Name Selection of pipe size Remarks
Outdoor unit
1st branching joint
Outdoor unit main pipe
1) Connecting pipe outdoor unit
Model name Suction gas side Discharge gas side Liquid side
MMY-MAP0801FT8 Ø22.2 Ø19.1 Ø12.7 MMY-MAP1001 FT8 Ø22.2 Ø19.1 Ø12.7 MMY-MAP1201 FT8 Ø28.6 Ø19.1 Ø12.7
Same to connecting pipe size of outdoor unit
Equivalent to capacity
Branching section
Branching pipe
2) Pipe size betw een branching sections
Pipe size differs based on total capacity code
Branching section
Total capacity codes of indoor units
at downstream side
Equivalent to
capacity
Below 18.0 Below 6.4 Ø15.9 Ø12.7 Ø9.5
18.0 to below 34.0 6.4 to below 12.2 Ø22.2 Ø19.1 Ø12.7
34.0 to below 45.5 12.2 to below 16.2 Ø28.6 Ø22.2 Ø15.9
If exceeding the main pipe size, decide the size same to main pipe
Equivalent
to HP
Suction
gas side
Discharge
gas side
Liquid side
value of indoor units at downstream side.
If the total value exceeds the capacity code of the outdoor unit, apply capacity code of the outdoor unit. (See tables 1 and 2.)
size.
When two pipes are used for the circuits exclusive to cooling, use pipes at liquid and suction gas sides.
12
No. Piping parts Name Selection of pipe size
g
g
End branching section
Flow selector unit
Branching section or flow selector unit
Indoor unit
Branching section
Connecting pipe of flow selector unit
Connecting pipe of indoor unit
Branchin
header of Y-shape branching joint
3) Pipe size between end branching section and flow selector unit
To tal capac ity codes of indoo r units
at downstream side
Equivale nt to capacity Equivalent to HP
Below 4.5 Below 1.7 Ø12.7 Ø9.5 Ø6.4
4.5 to below 18.0 1.7 to below 6.4 Ø15.9 Ø12.7 Ø9.5
Suction
gas side
Discharge
gas side
Liquid side
4) Connecting pipe size of indoor unit
Capacity rank Gas side Liqu id side
007 to 012 type
When pipe len
Real length: Below 15m Ø9.5
Real length: Over 15m 015 to 018 type Ø12.7 024 to 056 type Ø15.9 Ø9.5
Ø12.7
Ø6.4
th between the end branching section and cooling-only indoor unit exceeds 15m,
decide pipe size at gas side to the bigger one with Ø12.7.
5) Selection of branching joint/header
To tal capac ity codes of indoo r units Model name RBM-
Equivalent to
capacity
Y-shape branching joint
1, 2
Branching header
1, 2, 3
1 For branching pipe of the 1st branching section, select one by the outdoor unit capacity code.
2 When total capacity codes of indoor units exceed capacity code of outdoor unit, select one by
Below 18.0 Below 6.4 BY53FE BY53E
18.0 to below 40.0 6.4 to below 14.2 BY103FE BY103E Below 40.0 Below 14.2 HY1043 FE HY1043E Below 40.0 Below 14.2 HY1083 FE HY1083E
Equivalent to HP
For 3
pipes piping
For 2
pipes piping
capacity code of outdoor unit.
3 1 line after header branching is connectable up to total maximum capacity codes 6.0
(Equivalent to HP).
Branching Flow selector unit
Outdoor unit
1 Main piping
1st branching
section
6) Selection of flow selector unit
Model name Capacity rank of connectable indoor unit
RBM-Y1121FE 007 to 030 type RBM-Y1801FE 036 to 056 type
Confirm also Installation Manual of flow selector unit.
(Liquld,discharge gas,suction gas)
3 piping
Outdoor unit to FS unit
2
3
6 6 6
FS unit
2
4 4 4 4 4
Indoor unit
2 2 2
5 Header branching
3
5 Y-shape branching joint
2
3
FS unit to indoor unit Branching section indoor unit
< Cooling only > < Cooling only >
2 piping
(Liquld, gas pipe)
3 3 3
6 6 6
FS unit
4 4 4 4 4
Indoor unit
< Cooling only > < Cooling only >
13
5-4. Allowable Length/Height Difference of Refrigerant Piping
Height difference between outdoor and indoor units H1
50m
1st branching section
Main piping
Outdoor unit
L1
• System restrictions
For 12HP system, up to 120%
Branching
Branching piping L2
Connecting piping of indoor unit
L3
FS unit
a
ghi j
Indoor unit
Equivalent length corresponded to farthest piping L 125m
Equivalent length corresponded to farthest piping after 1st branching Li 50m
L4 L5 L6
def
lmn
header
L7
bc
FS unit
Max. capacity of combined indoor unit
k
< Cooling only >
o
< Cooling only >
< Cooling only >
p
< Cooling only >
H2 15m H2 > 15m
Height difference between indoor units
35m
H2
135% 105%
• Allowable length and height difference of refrigerant piping
Allowable value Piping section
Total extension of pipe (Liquid pipe, real length) 250 m
Pipe Length
Height difference
1 The farthest indoor unit from the 1st Branch to be named as (p).
*
2 Attached connection cable can be used up to 5 m in pipe length between indoor and FS unit. When the pipe length
*
Farthest piping length L (*1)
Max. equivalent length of main piping 85 m L1 Equivalent length of farthest piping from 1st branching Li (*1) 50 m L3 + L4 + L5 + L6 + p Max. real length of indoor unit connecting piping 30 m a + g, b + h, c + l, d + l, e + m, f + n, j, k, o, p Max. real length between FS unit and indoor unit (
Height between indoor and outdoor units H1
Height between indoor units H2
Real length 100 m Equivalent length 125 m
2) 15 m g, h, i, l, m, n Upper outdoor unit 50 m —— Lower outdoor unit 30 m —— Upper outdoor unit 35 m —— Lower outdoor unit 15 m ——
*
between indoor and FS unit exceeds 5 m, be sure to use the connection cable kit (RBC-CBK15FE). (Sold separately)
FS unit
L1 + L2 + L3 + L4+ L5 + L6 + L7 + a + b + c +
d + e + f + g + h + i + j + k + l + m + n + o + p
L1 + L3 + L4 + L5 + L6 + p
FS unit
Indoor unit Indoor unit
[NOTE] :
Dont connect two or more indoor units to one FS unit. Arrange one indoor unit and one FS unit set to 1 by 1.
14
• Brazed couplings and special branches
Use suitable parts for typical elbow couplings and socket couplings. (Consider the size, material, thickness, etc.)
Special branches
Use deoxidized parts sold separately.
Branching at indoor unit side
Branch header
Branching jo int
4 branching 8 branching
RBM-BY53E RBM-BY103E RBM-BY53FE
RBM-BY103FE
RBM-HY1043E
RBM-HY1043FE
RBM-HY1083E
RBM-HY1083FE
• Solder
Because only copper-to-copper connections are made in the multi type air conditioning system, use the hard solder phosphor copper solder.
15
5-5. Careful Handling
Careful handling is the most important step in preventing moisture, dirt, and dust from getting inside of the pipes. Moisture in pipes has caused major problems in numerous instances in the past. Therefore, it is important to be as careful as possible in order to prevent problems before they occur.
Pipe delivery and storage
When pipes are delivered, care should be taken to prevent it from becoming bent or deformed, and the ends of the pipes should be capped in order to prevent dirt, mud, rain, etc., from getting inside. Build a wooden frame to hold the pipes securely, and store the pipes in the specified location.
Delivery of copper pipes without caps to a work site is not acceptable.
Cap
Frame for careful handling
and to prevent rolling
Careful handling on a pallet
Pipe caps
The ends of all pipes must be sealed. The most reliable method is the pinch method, but the taping method can be selected in some circumstances.
Location
Outdoors
Indoors
Time for installation
One month or more
Less than one month
Does not matter
Careful handling method
Pinch method Pinch or taping method Pinch or taping method
n Pinch method
Pinch the end of the copper pipe closed, and braze any opening closed.
Copper pipe
Solder
Braze here
n Taping method
Cover the end of the copper pipe with vinyl tape.
[Taping method]
Opening
Copper pipe
Vinyl tape
Flatten
Fold over
Tape again
16
CAUTIONS
1) Do not allow dirt or moisture inside of the pipes.
Keep the open ends of all pipes
capped until all pipes have been connected.
Pipe openings should face
horizontally or downwards if at all possible.
GOOD NOT GOOD
Dirt and moisture get inside
Cap
Pipe
2) When passing a pipe through an
opening in a wall, always keep the end of the pipe capped.
3) Do not place pipes directly on the ground. Do not scrape pipes on the ground.
4) When deflashing (removing burrs from) a pipe, point the opening downwards so that no scraps fall inside of the pipe.
5) When installing pipes on a rainy day, always keep the ends of the pipes capped.
Cap or
Wall
plastic bag
Rubber band
Rubber
Cap or
band
plastic bag
Do not allow pipe to touch ground
Ground Ground
Pipe
Burrs
Deflasher
Cap or plastic bag
Rubber band
Rain
Wall
Dirt gets inside of pipe
Scraps get inside of pipe
Rain
Particles of the wall get inside the pipe
Rain gets inside of pipe
17
5-6. Parts of Branching Header/Joint
Branching Header : RBM-HY1043E / HY1083E Branching Joint : RBM-BY53E / BY103E
Check the following parts in the package.
For piping material and size of the refrigerant pipes, refer to the Installation Manual of the Air Conditioner.
NOTE : 1. All dimensions are in millimeters. In the following tables, ( ) indicates diameter of the indicated position, and
others indicate diameter of the connecting pipe.
2. Please connect pipe to the side with a projection of the socket.
( 51 , 52 , 54 , 58 , 59 , 61 , 62 , 70 , 89 : without projection)
Diameter of the connecting pipe
projection
socket
NAME
MODEL
Branching header gas side
Branching header liquid side
Heat insulator (gas side/liquid side)
side
diameter of the connected pipe
Gas
Branching Header
Socket
Outlet sealed pipe at gas side Header sealed pipe at liquid side
Outlet sealed pipe at liquid side
external diameter of socket
side
Liquid
No.
Ø15.9 x (Ø22.2) 1pc
14
Ø19.1 x (Ø22.2) 1pc
18
Ø28.6 x (Ø22.2) 1pc
70
( )
06
Ø12.7 x (Ø15.9) 1pc
09
Ø15.9
Ø15.9
Ø9.5
Ø22.2
No.
Ø 9.5 x (Ø15.9) 4pcs
06
Ø12.7 x (Ø15.9) 4pcs
09
Ø 6.4 x (Ø 9.5) 4pcs01Ø 9.5 x (Ø15.9) 1pc
(Ø15.9) 1pc (Ø15.9) 1pc
(Ø 9.5) 1pc
1pc
1pc
1pc each
Ø15.9
Ø9.5
Ø15.9
No.
Ø15.9 x (Ø22.2) 1pc
14
Ø19.1 x (Ø22.2) 1pc
18
Ø28.6 x (Ø22.2) 1pc
70
06
Ø12.7 x (Ø15.9) 1ps
09
RBM-HY1083ERBM-HY1043E
Ø22.2
No.
Ø 9.5 x (Ø15.9) 8pcs
06
Ø12.7 x (Ø15.9) 8pcs
09
Ø 6.4 x (Ø 9.5) 8pcs01Ø 9.5 x (Ø15.9) 1ps
1pc
1pc
1pc each
(Ø15.9) 3pcs (Ø15.9) 1pc
(Ø 9.5) 3pcs
NAME
Branching joint gas side
Branching joint liquid side
Heat insulator (gas side/liquid side)
Branching Joint
diameter of the connected pipe
Gas side
Socket
external diameter of socket
Liquid side
MODEL
( )
Ø12.7
No.
Ø12.7 x (Ø15.9) 1pc
09
Ø19.1 x (Ø15.9) 1pc
51
RBM-BY53E
Ø12.7
Ø15.9
Ø12.7
Ø9.5 Ø9.5
No.
05 54
1pc
1pc
1pc each
Ø 9.5 x (Ø12.7) 2pcs Ø15.9 x (Ø12.7) 2pcs
Ø 6.4 x (Ø 9.5) 2pcs01Ø 9.5 x (Ø12.7) 1pc05
Ø15.9
No.
Ø19.1 x (Ø22.2) 1pc
18
Ø28.6 x (Ø22.2) 1pc
70
Ø 9.5 x (Ø15.9) 1pc
06
Ø12.7 x (Ø15.9) 1pc
09
RBM-BY103E
Ø19.1
Ø22.2
Ø19.1
Ø12.7
Ø12.7
No.
Ø 9.5 x (Ø19.1) 1pc
07
Ø12.7 x (Ø19.1) 1pc
10
Ø15.9 x (Ø19.1) 2pcs
13
Ø22.2 x (Ø19.1) 2pcs
52
Ø28.6 x (Ø19.1) 1pc
89
Ø 6.4 x (Ø12.7) 1pc
02
Ø 9.5 x (Ø12.7) 2pcs
05
Ø15.9 x (Ø12.7) 1pc
54
1pc
1pc
1pc each
18
Branching Header : RBM-HY1043FE / HY1083FE Branching Joint : RBM-BY53FE / BY103FE
Check the following parts in the package.
For piping material and size of the refrigerant pipes, refer to the Installation Manual of the Air Conditioner.
NOTE : 1. All dimensions are in millimeters. In the following tables, ( ) indicates diameter of the indicated position, and
others indicate diameter of the connecting pipe.
2. Please connect pipe to the side with a projection of the socket.
( 52 , 54 , 70 , 89 : without projection)
Diameter of the connecting pipe
projection
socket
NAME
MODEL
Suction gas side
Discharge gas side
Liquid side
Heat insulator (suction gas side/ discharge gas side/liquid side)
Socket
Suction gas side
Discharge gas side
Branching Header
Liquid side
Outlet sealed pipe at suction gas side Outlet sealed pipe at discharge gas side
Outlet sealed pipe at liquid side Header sealed pipe at liquid side
diameter of the connected pipe
external diameter of socket
No. No. No. No.
14 70
85
( )
18 06
09
Ø22.2
Ø22.2
Ø15.9
Ø15.9 x (Ø22.2) 1pc Ø28.6 x (Ø22.2) 1pc
Ø12.7 x (Ø22.2) 1pc Ø19.1 x (Ø22.2) 1pc
Ø 9.5 x (Ø15.9) 1pc Ø12.7 x (Ø15.9) 1pc
Ø15.9
Ø15.9
Ø9.5
Ø15.9
06
Ø 9.5 x (Ø15.9) 3pcs
09
Ø12.7 x (Ø15.9) 4pcs
06
Ø 9.5 x (Ø15.9) 4pcs
09
Ø12.7 x (Ø15.9) 4pcs
01
Ø 6.4 x (Ø 9.5) 4pcs
(Ø15.9) 1pc (Ø15.9) 3pcs
(Ø 9.5) 1pc (Ø15.9) 1pc
RBM-HY1083FERBM-HY1043FE
Ø22.2
1pc 1pc
Ø22.2
1pc 1pc
Ø15.9
1pc 1pc
1pc each 1pc each
14
Ø15.9 x (Ø22.2) 1pc
70
Ø28.6 x (Ø22.2) 1pc
85
Ø12.7 x (Ø22.2) 1pc
18
Ø19.1 x (Ø22.2) 1pc
06
Ø 9.5 x (Ø15.9) 1pc
09
Ø12.7 x (Ø15.9) 1pc
06 09
06 09
01
Ø15.9
Ø15.9
Ø9.5
Ø15.9
Ø 9.5 x (Ø15.9) 7pcs Ø12.7 x (Ø15.9) 8pcs
Ø 9.5 x (Ø15.9) 8pcs Ø12.7 x (Ø15.9) 8pcs
Ø 6.4 x (Ø 9.5) 8pcs
(Ø15.9) 3pcs (Ø15.9) 7pcs
(Ø 9.5) 3pcs (Ø15.9) 1pc
NAME
MODEL
Suction gas side
Discharge gas side
Liquid side
Heat insulator (suction gas side/ discharge gas side/liquid side)
Socket
Suction gas side
Branching Joint
Discharge gas side
Liquid side
diameter of the connected pipe
( )
external diameter of socket
RBM-BY103FERBM-BY53FE
Ø
Ø
15.9
Ø
15.9
Ø
12.7
No. No. No. No.
05 54
09
Ø12.7 x (Ø15.9) 1pc
05
Ø 9.5 x (Ø12.7) 1pc
05 54
01
12.7
Ø
12.7
Ø
12.7
Ø
12.7
Ø
9.5
Ø
9.5
Ø 9.5 x (Ø12.7) 2pcs Ø15.9 x (Ø12.7) 2pcs
Ø 9.5 x (Ø12.7) 2pcs Ø15.9 x (Ø12.7) 1pc
Sealed pipe
x (Ø19.1) 1pc
Ø 6.4 x (Ø 9.5) 2pcs
1pc 1pc
1pc 1pc
1pc 1pc
1pc each 1pc each
Ø
22.2
Ø
22.2
Ø
15.9
70
Ø28.6 x (Ø22.2) 1pc
18
Ø19.1 x (Ø22.2) 1pc
09
Ø12.7 x (Ø15.9) 1pc
07 10 13 52 89
10 52
02 05 54
Ø
19.1
Ø
19.1
Ø
19.1
Ø
19.1
Ø
12.7
Ø
12.7
Ø 9.5 x (Ø19.1) 1pc Ø12.7 x (Ø19.1) 1pc Ø15.9 x (Ø19.1) 2pcs Ø22.2 x (Ø19.1) 2pcs Ø28.6 x (Ø19.1) 1pc
Ø12.7 x (Ø19.1) 2pcs Ø22.2 x (Ø19.1) 1pc
Sealed pipe
x (Ø19.1) 1pc
Ø 6.4 x (Ø12.7) 1pc Ø 9.5 x (Ø12.7) 2pcs Ø15.9 x (Ø12.7) 1pc
19
5-7. Branching Kit Connection Method
[1] Branch joint
<Suction gas/Discharge gas side>
Socket
Pipe in use on the site
Inlet
To outdoor unit
Socket
Gas side branch joint
Outlet (2)
Outlet (1)
<Liquid side>
Socket
Outlet (1)
Pipe in use on the site
Inlet
To outdoor unit
Socket
Installation direction of branch pipe Install the branching pipes so that it branch either vertically or horizontally.
Outlet (2)
Gas/Liquid side branch joint
Both directions are possible.
Pipe in use on the site
To other branching pipe or indoor unit
Socket
To other branch­ing pipe or indoor unit
Pipe in use on the site
Socket
NOTE :
Install the branch pipes horizontally or vertically so that they branch evenly.
Install the branching joint within ± 15 degrees.
Heat insulating for pipes (Branching Joint)
In order to prevent dripping at the place where the insulation provided with the branching kit meets the insulating material obtained on the site, butt the two types of insulation up against each other, and then wrap the seam between the two types of insulation in at least 10mm of the insulating material (in use on the site).
<Suction gas/Discharge gas/Liquid side>
Heat insulator for piping (in use on the site)
Heat insulator (in use on the site) by 10mm or more thickness.
Butt together
150
Branching joint
Heat insulator in package
Butt together
Heat insulator for piping (in use on the site)
Butt together
In case of vertical installation
<Suction gas/Discharge gas/Liquid side>
A
B
(Horizontal line)
(A view)
(Horizontal line)
(B view)
<In case of horizontal installation>
NOTE :
Install the branch pipes horizontally or vertically so that they are branched evenly.
Install the branching joint within ±15 degrees.
Within ± 15
Within ± 15
degrees
degrees
On the gas-side pipe, use insulation that can withstand heat of 120°C or higher. For the branch pipe, either use a commercially available coupling cover (for T-shape) that is at least 10mm thick, or else insulate the pipe as shown in the figure at below.
After applying insulation as outlined above, tape the insulation in place.
Taping (in use on the site)
Heat insulator
Heat insulator (in use on the site)
(in use on the site)
20
[2] Branch header
<Suction gas/Discharge gas side>
Branching Header
Select and install the socket that matches the diameter of a pipe to be connected to the indoor unit.
<Suction gas/Discharge gas side branch header>
Pipe in use on the site
To outdoor unit
Socket
Socket
Pipe in use on the site
To indoor unit
<Liquid-side branch header>
Socket
Pipe in use on the site
To outdoor unit
Socket
Pipe in use on the site
To indoor unit
If the number of indoor units to be connected is fewer than the maximum number of units that can be connected to the branch header, attach a sealed pipe to the unused connectors.
<Suction gas/Discharge gas side branch header>
Outlet sealed pipe (Provided with branch header)
A
B
<Liquid-side branch header>
Outlet sealed pipe (Provided with branch header)
C
Install the branch header so that it branches horizontally. It cannot be used in a vertical position.
D
(Horizontal line)
(Horizontal line)
(A view)
(B view)
Within ± 15
Within ± 10
degrees
degrees
<Liquid-side>
(Horizontal line)
(C view)
When arranging the branching header at the liquid side, attach a header sealed pipe on the sealing side of the header as shown in the fiqure at below.
Be sure to install the branch pipe downward. Horizontal viewed from D point should be within ± 10 degrees same as view B.
Supporting branching header After applying the insulation, set the hanging metals
as support. (in use on the site).
NOTE :
1. Install the branching header so that it branches
horizontally. It cannot be used in a vertical position.
2. Do not use T-type pipe for the branching section.
Inlet socket
Pipe in use on the site
Branching Header
(D view) Sealing side
Within
degrees
± 15
Header sealed pipe
Within ± 10
degrees
CAUTION
1. On the inlet side of a Y-type branch joint or branch header, allow for at least 300mm of straight pipe.
2. A Y-type branch joint can be installed so that it branches either vertically or horizontally; if branching horizontally, it should be within an angle of ± 15°.
3. A branch header should be installed so that it branches horizontally.
4. Do not use T-type branch joints.
CAUTION
In the multi air conditioning system, because the refrigerant pipes congregate at the rooftop pipeshaft outlet in the vertical pipeshaft, it is necessary to attach labels to each pipe in order to make clear to which system a given pipe belongs so as to prevent pipes from being connected incorrectly.
21
How to connect “Cooling Only” indoor unit
Branch joint
When connecting a Cooling Only indoor unit, attach a sealed pipe to the unused connectors of the branching pipe of discharge gas side.
Suction gas side
* Discharge gas side
Liquid side
Refer to above. There is the method of connecting without using branching joint pipe of discharge gas side.
For details, refer to the Installation Manual of the Air Conditioner.
Connect sealed pipe.
Flow selector unit
Indoor unit Cooling only
Indoor unit Heating and Cooling
Branch header
When connecting a Cooling Only indoor unit, attach a sealed pipe to the unused connectors of the branching pipe of discharge gas side.
Suction gas side
Connect sealed pipe.
Discharge gas side
Liquid side
Flow selector unit
Indoor unit Cooling only
Indoor unit Heating and Cooling
[NOTE]
For cooling only indoor unit in Super-HRM system, item code (DN) setting from the wired remote controller is necessary. (Refer to the section 13-1.”)
22
5-8. External Dimensions of Branch Connectors
y
y
y
y
y
(Outline drawings are shown on the following pages.)
Branching joints and headers
Model name Usage Appearance
RBM-BY53FE
RBM-BY103FE
Y-shape branching joint (*2)
RBM-BY53E
RBM-BY103E
RBM-HY1043FE
4-branching header (*3)
RBM-HY1043E
RBM-HY1083FE
8-branching header (*3)
RBM-HY1083E
1 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
*
2 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.
*
3 Max. 6.0 capacity code in total can be connected.
*
4 This is used for branching to cooling only indoor unit.
*
5 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.
*
Indoor unit capacit Total below 6.4
Indoor unit capacit Total below 14.2
Indoor unit capacit Total below 6.4
Indoor unit capacity code Total below 14.2
Indoor unit capacit Total below 14.2
Indoor unit capacity code Total below 14.2
Indoor unit capacit Total below 14.2
Indoor unit capacity code Total below 14.2
code
code
code
code
code
For 3 piping
For 2 piping (*4)
For 3 piping
For 2 piping (
For 3 piping
For 2 piping (
4)
*
4)
*
5-9. Nitrogen Gas Blow Method (During Brazing)
If nitrogen gas is not passed through the pipes during brazing, a film of oxidized material will form on the inner surfaces of the pipes. The presence of a such a film in the system will adversely affect the operation of the valves and compressor in the refrigerant system, and will prevent the system from operating normally.
In order to prevent this from occurring, nitrogen gas is passed through the pipes while brazing is in progress. This process of replacing the air in the pipes with nitrogen is called the nitrogen gas blow.
This is the basic method that is used for brazing work.
CAUTION
1. Nitrogen gas must be used. (Oxygen, carbon dioxide, and fluorocarbons cannot be used.)
2. Always be sure to use a pressure-reducing valve.
Piping
Valve
Hose
Reducing valve
Nitrogen gas bomb
Piping at site
Brazing position
Copper pipe Ø6.4
Valve
Taping
Reducing valve
Pressure tight hose
Outside
Nitrogen
gas bomb
23
5-10. Brazing Work
1. Brazing work should be performed downwards or
(Recommended brazing)
sideways. Avoid brazing upwards (in order to avoid incomplete brazing). (Recommendation)
2. Always used the specified piping materials for
liquid pipes and gas pipes, and make sure that
Brazing material
they are installed in the proper direction and at the proper angle.
3. The nitrogen gas blow method should be used
when brazing.
(Direction downward) (Direction upward)
Lateral direction
Brazing material
Brazing material
CAUTIONS
1. Pay attention to fire prevention concerns. (Take preventative measures in the area where brazing work is
to be performed, such as keeping a fire extinguisher or water handy.)
2. Be careful not to burn yourself.
3. Make sure that any gaps between pipes and couplings are appropriate. (Do not miss brazing any joints.)
4. Make sure that pipes are adequately supported.
The following table provides basic guidelines for the interval between supports for horizontal copper pipe.
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
G
ØF
Interval between supports for copper pipe
Nominal dia.
Max. interval (m)
Avoid securing copper pipes with metal brackets directly.
20 or less 25 to 40
1.0 1.5
(Unit: mm)
Connected section
Standard outer dia. of
connected copper pipe
6.35
9.52
12.70
15.88
19.05
22.22
28.58
External size Internal size
Standard outer dia. (Allowable difference)
CF
6.35 (±0.03) 6.45 ( )
9.52 (±0.03) 9.62 ( )
12.70 (±0.03) 12.81 ( )
15.88 (±0.03) 16.00 ( )
19.05 (±0.03) 19.19 ( )
22.22 (±0.03) 22.36 ( )
28.58 (±0.04) 28.75 ( )
+0.04 –0.02
+0.04 –0.02
+0.04 –0.02
+0.04 –0.02
+0.03 –0.03
+0.03 –0.03
+0.06 –0.02
Min. depth
of insertion
KG
76 87 98
98 11 10 11 10 13 12
Oval value
0.06 or less
0.08 or less
0.10 or less
0.13 or less
0.15 or less
0.16 or less
0.20 or less
Min. thickness
of coupling
0.50
0.60
0.70
0.80
0.80
0.82
1.00
Gas brazing of refrigerant pipes must be performed by personnel qualified to do so under local ordinances.
Minmum wall thickness for R410A application
Soft (Coil)
¡ ¡ ¡ ¡
NG NG NG
Hard or Half hard
¡ ¡ ¡ ¡ ¡ ¡ ¡
OD (Inch)
1/4 3/8 1/2 5/8 3/4 7/8
1.1/8
OD (mm)
6.35
9.52
12.70
15.88
19.05
22.20
28.58
Minium wall thickness
0.80
0.80
0.80
1.00
1.00
1.00
1.00
24
5-11. Flare Processing
Flare processing procedure
Parts and material : Copper pipe, flare nut. Flare nut shallbe of attached on the indoor unit or R410A exclusive. Tools : Flare tool (“Rigid” type), reamer, pipe cutter
Work procedure
Straighten the coiled copper pipe.
Cut the pipe with the pipe cutter.
Use the reamer to remove burrs from the cut surface of the pipe.
Pipe
Burr
Deburring
Key point
Uncoil the pipe.
1. Position the blade of the cutter so that it will cut the pipe at a perpendicular angle.
2. Rotate the pipe cutter to the left to cut the pipe.
3. Move the pipe cutter slowly.
1 . Keep the opening of the pipe
facing downwards.
2. Be careful not to scratch the inner surface of the pipe.
(Reason)
It is difficult to cut the coiled pipe correctly, which increases the chance of failure.
The cut surface will be at an angle.
The cutter will bite too tightly.
The copper pipe will be
deformed.
Scraps will get inside of the pipe.
A gas leak could result.
Clear out the inside of the pipe by tapping on the end with a screwdriver.
Insert the flare nut.
Make sure that all scraps of metal are out of the tube by lightly tapping on the tube while the opening is pointing down.
Be certain to insert the flare nut before beginning the flare process.
25
Metal scraps in the tube can damage the compressor.
If the scraps adhere to the flared region, a gas leak may result.
The flare nut will not fit inside the copper pipe after the flare process.
Work procedure
Key point
(Reason)
Attach the (Rigid”) flare tool to the copper pipe.
Align the punch. (Align the arrow with the line adjacent to the next hole.)
1. Make sure that the inner surfaces of the flare tool are clean.
2. Determine the dimensions of the copper pipe in accordance with the flare tool.
45˚
A
Flare tool
Copper pipe
Align the arrow on the punch with the prescribed position on the flare tool.
The copper pipe will slip out while the flaring process is in progress.
The flared dimensions vary.
Dimensions to end of copper tube when flared with one tool surface
• Projection margin in flaring : A (Unit : mm)
Rigid (Clutch type)
Outer dia. of copper pipe
6.4
9.5
12.7
15.9
R410A tool used
R410A R22 0 t o 0 .5 (Same as left) 0 t o 0 .5 (Same as left) 0 t o 0 .5 (Same as left) 0 t o 0 .5 (Same as left)
Conventional tool used
R410A R22
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
1.0 to 1.5 0.5 to 1.0
Imperial (Wing nut type)
Outer dia. of copper pipe
6.4
9.5
12.7
15.9
R410A R22
1.5 to 2.0 1.0 to 1.5
1.5 to 2.0 1.0 to 1.5
2.0 to 2.5 1.5 to 2.0
2.0 to 2.5 1.5 to 2.0
Flare the pipe.
Remove the flare tool and check the flared surface.
Slowly and carefully turn the flare tool handle while it clicks, until it turns freely. Turn the handle to the left and raise it to the top.
If the handle is not raised to the top, the flare tool will scratch the extended portion of the pipe (the cone-shaped portion).
If the A dimension is small, the flared contact surface is
smaller and a gas leak becomes more likely.
The pipe will not be flared fully.
The extended portion of the pipe (the cone-shaped portion)
will be scratched.
• Extruding margin of copper pipe with flare machining : A (Unit: mm)
Copper pipe outer dia.
9.5
12.7
15.9
A
13.2
16.6
19.7
+0.0 –0.4
A
Check list :
Is the inner surface of the flared portion equal in width and shiny?
Is the thickness of the flared portion equal?
Is the flared portion of a suitable size?
26
5-12. Flushing
The flushing process uses gas pressure to remove foreign matter from the inside of pipes.
Three major effects
(1) Removes oxidation that formed inside of the pipe during brazing as a result of an inadequate nitrogen gas
blow procedure. (2) Removes foreign matter and moisture that has gotten inside of pipes due to improper handling. (3) Checks the connections in the pipe system between the indoor unit and the outdoor unit.
[Example work procedure]
1. Install a pressure reducing valve on a nitrogen cylinder. (Fluorocarbon gases and carbon dioxide carry a risk
of promoting condensation, while oxygen causes explosion.)
2. Connect the pressure reducing valve to a gauge manifold and then to the gas-side pipe and the liquid-side
pipe on the outdoor unit.
Indoor unit
Ø6.4 copper pipe
N21
Diff. size union
3. On the indoor unit side, plug all gas-side pipes except those for the
indoor units that are to be flushed.
4. Open the source valve on the nitrogen cylinder and increase the
pressure on the secondary side of the pressure reducing valve until it reaches 0.5MPa (5kg/cm2G), and then open the valve on the gauge manifold connected to the gas-side pipe.
5. Flushing
Press down on the end of the indoor-side gas pipe with your palm.
VLV
H
Gauge manifold valve
Source valve
Reducing valve
Nitrogen gas bomb
Plug (Brass)
1st side
Source valve
Flare nut
Copper pipe
2nd side
0.5MPa (5kg/cm²G)
When the pressure becomes so great that you can no longer hold it against the end of the pipe, remove your hand from the pipe. (This is the first flush.) Press down against the end with your hand again.
Flush the pipe a second time. (When flushing, place a piece of gauze, etc., on the end of the pipe, and then check the gauze for debris or moisture. Repeat the flushing process until nothing more comes out of the pipe.)
6. Close the gauge manifold valve, and repeat the above process for
next indoor unit (No. 2 to No. N). Close the gauge manifold valve, open the valve on the gauge manifold that is connected to the liquid­side pipe to allow the nitrogen to flow, and flush that liquid-side pipe.
27
Nitrogen
Hand
gas
Reducing valve
Pressure
0.5MPa (5kg/cm²G)
5-13. Pipe Connections to the Indoor Unit
1. Once you remove the flare nut from the pipe on
the indoor unit (always use a torque wrench), a small amount of gas will escape, but this is simply nitrogen gas with atmospheric pressure that was sealed inside to prevent corrosion, and does not indicate a problem.
2. Flare the pipe according to the procedure
described previously.
3. Centering
Center the pipes be seating the tapered portion of the half union in the flared portion of the pipe.
4. Tightening the flare nut
First hand-tighten the flare nut as much as possible, and then use a torque wrench to tighten the nut completely.
<Indoor unit> <Pipe>
Center
Brazing union (half union)
Tapered portion
Flared portion
Flare nut
Connecting pipe outer dia.
(mm)
Ø6.4 Ø9.5
Ø12.7 Ø15.9
Tightening torque
(N•m)
14 to 18 (1.4 to 1.8 kgfm) 34 to 42 (3.4 to 4.2 kgf•m) 50 to 62 (5.0 to 6.2 kgf•m) 68 to 82 (6.8 to 8.2 kgf•m)
: R410A torque wrench required.
<Two spanners>
Turn flare nut with a wrench
<Indoor unit> <Pipe>
Secure half union in place with a wrench
Tightening the flare nut with a torque wrench
* Avoid initially tightening the nut with a wrench. * When tightening a 6.4mm-diameter pipe, tighten the nut lightly with a wrench, and then tighten the nut about
90° to 120° (1.5 to 2 corners of the nut) with a torque wrench.
28
5-14. Pipe Connection to the Outdoor Unit
WARNING
If the refrigerant gas leaks during installation work, ventilate the room.
If the leaked refrigerant gas comes to contact with a fire, the noxious gas may generate.
After installation work, check that the refrigerant gas does not leak.
If the refrigerant gas leaks in the room and comes to contact with a fire such as fan heater, stove, or kitchen range, the noxious gas may generate.
Connection of refrigerant pipe
1. The refrigerant pipe connecting section is set in the outdoor unit. Remove the front panel and the piping/wiring
panel. (M5: 9 pcs.)
As shown in the right figure, the hooking hooks are attached at right and left sides each on the front panel. Lift up and remove the front panel.
2. Pipes can be drawn out forward and downward from the outdoor unit.
3. When drawing out the pipe forward, draw out the pipe to outside via piping/wiring panel, and keep space of 500mm or more from the main pipe connecting the outdoor unit with the indoor unit, considering service work, etc. (For replacing the compressor, 500mm or more space is required.)
4. When drawing out the pipe downward, remove the knockout of the base plate of the outdoor unit, apply the pipe to outside of the outdoor unit, and perform piping at right/left or rear side. Leading pipe of the balancing should be within 4m.
Hook
Packed valve at suction gas side
(Left piping)
500mm
or more
Drawing out forward
(Left piping)
(Right piping)
Drawing out downward
Front panel
Piping/wiring panel
(Rear piping)
(Right piping)
Packed valve at liquid side
Packed valve at balance side (It is not used in this model.)
Ball valve at discharge gas side
REQUIREMENT
For brazing, be sure to use nitrogen gas to avoid oxidation of pipe inside.
1. In a welding work for the refrigerant pipes, be sure to use the nitrogen gas in order to prevent oxidation inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale generates.
2. Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust is not mixed.
3. Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, a required tightening cannot be obtained. Tighten the flare not with the specified torque.
Outer dia. of copper pipe
12.7 mm
15.9 mm
Tightening torque (N•m)
50 to 62 (5.0 to 6.2 kgf-m) 68 to 82 (6.8 to 8.2 kgf-m)
29
Pipe connecting method of valve (Example)
Using the attached pipes as shown in the following figure, braze elbows, sockets, and pipes which are procured locally.
MMY- Drawing out forward Drawing out downward
Liquid pipe Use the attached pipe for connection.
Discharge gas pipe
Suction gas pipe
Use the attached pipe (L-shape) and connect it with socket.
Cut L-shape pipe and connect it with elbow, attached pipe and socket.
Pipe connection at the local site (Bend rightward slightly.)
Use the attached pipe (Straight pipe) and connect it with socket.
Cut L-shape pipe and connect it with attached pipe and socket.
MAP0801FT8 MAP1001FT8
MAP1201FT8
Suction gas pipe
Discharge gas pipe
Liquid pipe
Attached pipe
Socket
Pipe
Suction gas pipe
L-shape pipe
Attached pipe
Pipe
Attached pipe
Socket
Pipe
Cut
Liquid pipe Use the attached pipe for connection.
Discharge gas pipe Use the attached pipe and connect it with socket.
Suction gas pipe
Cut L-shape pipe and connect it with attached pipe.
Suction gas pipe
Discharge gas pipe
Liquid pipe
Attached pipe
Socket
Pipe
Suction gas pipe
Cut
L-shape pipe
Attached pipe
Pipe
Pipe
Suction gas pipe
Discharge gas pipe
Liquid pipe
Attached pipe
Pipe
Socket
Pipe
Suction gas pipe
Cut
L-shape pipe
Attached pipe
Socket
Pipe
Pipe connection at the local site (Bend rightward slightly.)
Use the attached pipe (Straight pipe) and connect it with socket.
Cut L-shape pipe and connect it with attached pipe and socket.
Suction gas pipe
Discharge gas pipe
Liquid pipe
Attached pipe
Pipe
Socket
Pipe
Suction gas pipe
Cut
L-shape pipe
Attached pipe Socket
Pipe
30
Loading...
+ 148 hidden pages